merten ARGUSMEG5522-00 Operating Instructions Manual
merten ARGUSMEG5522-00 is a presence sensor module with IR for indoor ceiling mounting. It can be installed in a flush-mounted box or a surface-mounted housing (available as an accessory). It detects moving heat sources within an adjustable detection range and triggers a staircase lighting function.
The maximum detection radius is approximately 7 m. The detection angle is 360°. As long as movement is detected, the connected load remains switched on. The adjustable follow-up time only begins when no more movement is detected (trigger function).
The sensor module has a light sensor with adjustable brightness threshold. Connected lighting is switched on only below a certain brightness threshold (motion detector function). The presence function allows the sensor module to switch off the lighting even if a person is present when there is sufficient daylight.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
ARGUS Präsenz Sensor-Modul mit IR© Merten 2009V5522-581-0012/11 de en
ARGUS Präsenz Sensor-Modul mit IR
Gebrauchsanleitung
Art.-Nr. MEG5522-00..
Notwendiges Zubehör
– Komplettieren Sie das ARGUS Präsenz Sensor-Modul mit IR mit entsprechenden Einsätzen (siehe Funktionsübersicht).
Zubehör
– Aufputzgehäuse für ARGUS Präsenz
(Art.-Nr. 550619)
– IR-Fernbedienung Distance 2010 (Art.-Nr. 570222)
Für Ihre Sicherheit
¼ GEFAHR
Lebensgefahr durch elektrischen Schlag.
Alle Tätigkeiten am Gerät dürfen nur durch ausgebildete Elektrofachkräfte erfolgen. Beachten Sie die länderspezifischen Vorschriften.
Sensor-Modul kennenlernen
Das ARGUS Präsenz Sensor-Modul mit IR (im Folgenden Sensor-Modul genannt) ist ein Präsenzmelder für die Deckenmontage im Innenbereich. Das Sensor-Modul kann sowohl in einer Unterputzdose, als auch in einem Aufputzgehäuse (als Zubehör erhältlich) montiert werden. Es erfasst sich bewegende Wärmequellen (z. B.
Personen) in einem einstellbaren Erfassungsbereich und startet eine Treppenlichtfunktion.
Der maximale Erfassungsradius beträgt ca. 7 m. Der Erfassungswinkel bertägt 360°. Solange eine Bewegung erfasst wird, bleibt die angeschlossene Last eingeschaltet. Die einstellbare Nachlaufzeit beginnt erst, wenn keine Bewegung mehr erkannt wird (Triggerfunktion).
Das Sensor-Modul verfügt über einen Lichtfühler mit einstellbarer Helligkeitsschwelle, so dass die Beleuchtung nur unterhalb einer bestimmten Helligkeitsschwelle eingeschaltet wird (Bewegungsmelderfunktion). Durch die
Präsenzfunktion kann das Sensor-Modul die Beleuchtung trotz einer anwesenden Person ausschalten, wenn genügend natürliches Licht vorhanden ist.
| Der angegebene Erfassungsradius und die Helligkeitsschwelle beziehen sich auf durchschnittliche Verhältnisse bei der empfohlenen
Montagehöhe von ca. 2,50 m und sind deshalb als Richtwerte anzusehen. Die Reichweite kann bei wechselnden Temperaturverhältnissen stark schwanken.
Beispiel zur Verdeutlichung der Präsenzfunktion: lx
1000
800
600
A
400
200
B C D E F
A
B
C
D
E
F
Helligkeitsschwelle ist auf 500 Lux eingestellt.
Beleuchtung ist ausgeschaltet, Helligkeit im Raum beträgt 200 Lux
Sensor-Modul erkennt Bewegung: Beleuchtung
(400 Lux) wird eingeschaltet. Gesamthelligkeit im
Raum beträgt nun 600 Lux.
Tageslicht und damit die Gesamthelligkeit im Raum nehmen zu.
Gesamthelligkeit überschreitet 900 Lux. Tageslicht alleine liegt nun über der Helligkeitsschwelle von
500 Lux. Die Beleuchtung wird ausgeschaltet (nach
Ablauf der Nachlaufzeit).
Sensor-Modul schaltet trotz Bewegungserkennung die Beleuchtung nicht ein, da das Tageslicht ausreicht.
Die zuschaltbare Lichtregelung (nur in Kombination mit dimmbaren Einsätzen) sorgt für eine nahezu konstant helle Beleuchtung des Raumes. Das Sensor-Modul misst ständig die Helligkeit im Raum und regelt sie um einen einstellbaren Sollwert.
Über eine IR-Fernbedienung können Sie zwischen den
Funktionen „Automatikbetrieb“, „24 h einschalten“ und
„24 h ausschalten“ wechseln.
Funktionsübersicht des Sensor-Moduls auf empfangenden Einsätzen
Komplettieren Sie das Sensor-Modul mit den empfangenden Einsätzen zum Schalten oder Dimmen, um lokale Lichtsteuerung und weitere Funktionen auszuführen.
Schalten
• Elektronik-Schalt-Einsatz
• Relais-Schalt-Einsatz
• Elektronik-Schalt-Einsatz, 2fach
• Relais-Schalt-Einsatz,
2fach
Sensor-Modul: helligkeitsabhängige Treppenlichtfunktion
Sensor-Modul:
Kanal 1: helligkeitsabhängige Treppenlichtfunktion
Kanal 2: helligkeits hängige Treppenlichtfunktion un ab-
Dimmen
• Universal-Dimmer-Einsatz
• Steuerungs-Einsatz
1-10 V
• DALI-Steuerungs-Einsatz
• Universal-Dimmer-Einsatz, 2fach
Sensor-Modul: helligkeitsabhängige Treppenlichtfunktion, Lichtregelung
Sensor-Modul:
Kanal 1: helligkeitsabhängige Treppenlichtfunktion,
Lichtregelung
Kanal 2: helligkeits un abhängige Treppenlichtfunktion, Lichtregelung
Funktionsübersicht des Sensor-Moduls auf sendendem Einsatz
Komplettieren Sie das Sensor-Modul mit dem sendenden Zentralstellen-Einsatz, um Lichtsteuerung
über den PlusLink (PL) globale
auszuführen.
Globale Lichtsteuerung:
• Zentralstellen-Einsatz Sensor-Modul: helligkeits un abhängige
Treppenlichtfunktion
Sensor-Modul im Zusammenspiel mit
Alarmanlagen
|
|
Bewegungs-/Präsenzmelder sind nicht als Komponente einer Alarmanlage im Sinne des Verbandes der Sachversicherer (VdS) geeignet.
Bewegungs-/Präsenzmelder können Fehlalarme auslösen, wenn der Montageort ungünstig gewählt wurde.
Bewegungs-/Präsenzmelder schalten, sobald sie eine sich bewegende Wärmequelle wahrnehmen. Dabei kann es sich um Menschen handeln, aber auch um Tiere oder Temperaturdifferenzen in Fenstern. Um Fehlalarme zu vermeiden, ist der Montageort so zu wählen, dass unerwünscht auslösende Wärmequellen nicht erfasst werden können (siehe Abschnitt „Montageort auswählen“).
Anschlüsse, Anzeigen und
Bedienelemente
Vorderseite:
A
B
A
B rote LED (im Testmodus) grüne LED (bei 24 h-Treppenlichtschaltung)
Rückseite:
D
C LUX
2min
Test
Time Ch.1
30min
ON DIP
1 2 3 4
Sensitivity
1h
5min
2h
Time Ch.2
OFF
B
E
F
A
A
B
C
D
E
F
Modul-Schnittstelle
DIP-Schalter
1: Präsenzfunktion/Bewegungsmelderfunktion
2: 24 h-Treppenlichtschaltung
3: Vorwarnung für Kanal 1
4: Lichtregelung
Potentiometer für Nachlaufzeit Kanal 1
Potentiometer für Helligkeitsschwelle
Potentiometer für Empfindlichkeit
Potentiometer für Nachlaufzeit Kanal 2
Montageort auswählen
• Sensor-Modul an Stellen montieren, die eine optimale
Überwachung des gewünschten Bereichs ermöglichen.
Sensor-Modul montieren
A B
• Sensor-Modul an der Decke, möglichst in der Mitte des Raumes, montieren.
• Sensor-Modul nicht an Schrägen oder Wänden montieren.
• Sensor-Modul mit einem Abstand von mind. 0,5 m zu
Leuchten montieren.
• Die empfohlene Montagehöhe beträgt 2,50 m. Bei abweichenden Montagehöhen ändert sich der Erfassungsbereich.
• Maximaler Erfassungsbereich des Sensor-Moduls:
360° Erfassungswinkel, ca. 7 m Erfassungsradius.
2,5 m
C C
D
E E
A
B
C
D
E
Unterputzdose
Aufputzgehäuse für ARGUS Präsenz (Zubehör)
Einsatz (siehe Funktionsübersicht)
Schrauben (im Lieferumfang des Aufputzgehäuses)
Sensor-Modul
| Bei Netzspannungszufuhr schaltet das Sensor-
Modul den Kanal 1 für 30 s ein und anschließend wieder aus. Kanal 2 bleibt ausgeschaltet. In den folgenden 2 s reagiert das Sensor-Modul nicht auf Bewegung. Nach Ablauf dieser Initialisierungszeit ist das Sensor-Modul betriebsbereit.
12,0 m
14,0 m
• Innerer/äußerer Erfassungsbereich
– innerer Erfassungsbereich (ca. 6 m Radius):
Bewegungserkennung einer sitzenden Person aufgrund geringerer Bewegung
– äußerer Erfassungsbereich (ca. 7 m Radius):
Bewegungserkennung einer gehenden Person aufgrund stärkerer Bewegung
• Um eine lückenlose Überwachung, z. B. eines langen
Flures, zu gewährleisten, müssen sich die Erfassungsbereiche der Sensor-Module überschneiden.
• Bewegungs-/Präsenzmelder erfassen Objekte, die
Wärme abstrahlen. Wählen Sie den Montageort so, dass unerwünschte Wärmequellen nicht erfasst werden, wie z. B.:
– geschaltete Lampe im Erfassungsbereich
– offene Feuer (z. B. Kaminfeuer)
– sich bewegende Vorhänge, Gardinen, usw., die durch starke Sonneneinstrahlung eine andere Temperatur haben als deren Umgebung.
– Fenster, in denen es durch die Wechselwirkung zwischen Sonneneinstrahlung und Wolken zu einer schnellen Temperaturveränderung kommt.
– größere Wärmequellen (z. B. Autos), die durch
Fenster hindurch erfasst werden.
– lichtdurchflutete Räume, in denen es aufgrund spiegelnder Gegenstände (z. B. Böden) zu schnellen
Temperaturveränderungen kommt.
– durch Sonneneinstrahlung aufgeheizte Fensterscheiben
– Hunde, Katzen, usw.
• Um Fehlschaltungen zu verhindern, sollte der Einsatz in einer winddichten Unterputzdose installiert werden.
Bei Unterputzdosen und Rohrverkabelungssystemen kann ein Luftzug an der Rückseite des Gerätes zum
Auslösen des Sensor-Moduls führen.
• Direkte Sonneneinstrahlung vermeiden. Diese kann im Extremfall den Sensor zerstören.
Sensor-Modul einstellen
Auf der Rückseite des Sensor-Moduls können Sie über
Potentiometer die Empfindlichkeit, Helligkeitsschwelle und Nachlaufzeit des Sensor-Moduls einstellen.
Zusätzliche Einstellmöglichkeiten über DIP-Schalter:
DIP 1 Präsenzfunktion
Pos. ON
(oben) aktiv
Pos. OFF
(unten) inaktiv
DIP 2 24 h-Treppenlichtschaltung über Plus-
Link
24 h „EIN“ 24 h „EIN“ oder 24 h
„AUS“
DIP 3 Vorwarnung für Kanal 1 aktiv
DIP 4 Lichtregelung aktiv inaktiv inaktiv
Empfindlichkeit einstellen
1
10s
2min
30min
Test
2
B
A
Sensitivity
C A B C
1 Testmodus aktivieren und Helligkeitsschwelle auf
„unendlich“ stellen.
Die rote LED leuchtet bei erkannter Bewegung.
2
3
Empfindlichkeit stufenlos einstellen (max. 7 m Erfassungsradius).
Erfassungsbereich abschreiten und prüfen, ob das
Sensor-Modul wie gewünscht schaltet. Empfindlichkeit ggf. anpassen.
Helligkeitsschwelle einstellen
4
4 Gewünschte Helligkeitsschwelle stufenlos einstellen. Das Sensor-Modul schaltet unterhalb der eingestellten Helligkeitsschwelle.
erkennt Bewegung bei Dunkelheit (ca. 10 Lux) erkennt Bewegung bei Tageslicht
(ca. 1000 Lux) erkennt Bewegung helligkeits un abhängig
5 Prüfen, ob das Sensor-Modul bei gewünschter/eingestellter Helligkeit schaltet. Helligkeitsschwelle ggf. anpassen.
| In Kombination mit einem 2fach-Einsatz bezieht sich die Helligkeitsschwelle nur auf Kanal 1. Der
Kanal 2 schaltet immer helligkeits un abhängig.
Treppenlichtfunktion einstellen
Sie können die Art der Treppenlichtfunktion (ohne/mit
Vorwarnung) und die Nachlaufzeit einstellen.
Mit der Nachlaufzeit stellen Sie ein, wie lange der angeschlossene Verbraucher eingeschaltet bleibt (stufenlos von 10 s bis 30 min.). Beim 2fach-Einsatz können Sie die
Nachlaufzeit für beide Kanäle separat einstellen.
Die Vorwarnung zeigt das Ende der Nachlaufzeit an. Die
Verbraucher werden kurz aus- und wieder eingeschaltet
(in Kombination mit Schalt-Einsätzen), bzw. werden langsam heruntergedimmt (in Kombination mit dimmbaren Einsätzen). Nach Ablauf der Vorwarnzeit (30 s, nicht einstellbar) werden die Verbraucher ausgeschaltet.
1 Art der Treppenlichtfunktion wählen und Nachlaufzeit einstellen
Treppenlichtfunktion ohne Vorwarnung
1
2min
ON DIP
10s
30min
Test
1 2 3 4
A t
B t
C
A
B
C
Schalten ohne Vorwarnung
Dimmen ohne Vorwarnung
Nachlaufzeit
Treppenlichtfunktion mit Vorwarnung
1
2min
ON DIP
10s
30min
Test
1 2 3 4
A t
B t
C D
A
B
C
D
Schalten mit Vorwarnung
Dimmen mit Vorwarnung
Nachlaufzeit
Vorwarnzeit (30 s, nicht einstellbar)
| Die Vorwarnung bezieht sich nur auf Kanal 1.
Nachlaufzeit für Kanal 2 einstellen
Bei Verwendung eines 2fach-Einsatzes können Sie die
Nachlaufzeit für Kanal 2 über ein separates Potentiometer einstellen. Die einstellbare Zeitspanne unterscheidet sich von der des Kanals 1.
1
1h
5min
2h
OFF
Präsenzfunktion aktivieren/deaktivieren
Bei der helligkeitsabhängigen Bewegungserkennung
überprüft das Sensor-Modul ständig die Helligkeit im
Raum und vergleicht diese mit der eingestellten Helligkeitsschwelle. Ist ausreichend natürliches Licht vorhanden, schaltet das Sensor-Modul die Beleuchtung trotz einer anwesenden Person aus.
Die Präsenzfunktion des Sensor-Moduls ist werksseitig aktiviert. Mit dem DIP-Schalter 1 können Sie die Funktion deaktivieren („OFF“) und wieder aktivieren („ON“).
ON DIP
1 2 3 4
Bei deaktivierter Präsenzfunktion führt das Sensor-Modul weiterhin die Bewegungsmelderfunktion aus.
24 h-Treppenlichtschaltung einstellen
Mit dem DIP-Schalter 2 können Sie eine Treppenlichtschaltung für 24 Stunden einstellen, die Sie von anderer
Stelle über PlusLink abrufen können.
Dazu haben Sie folgende Möglichkeiten:
• DIP 2 „ON“: Treppenlichtzeit für 24 h über PL nur schalten
ein-
• DIP 2 „OFF“: Treppenlichtzeit für 24 h über PL ein-/ ausschalten
ON DIP
1 2 3 4
Lichtregelung aktivieren/deaktivieren
(Nur in Kombination mit dimmbaren Einsätzen, siehe
Funktionsübersicht)
Die Lichtregelung des Sensor-Moduls ist werksseitig deaktiviert. Mit dem DIP-Schalter 4 können Sie die Funktion aktivieren („ON“) und wieder deaktivieren („OFF“).
ON DIP
1 2 3 4
Lichtregelung
Grundfunktion der Lichtregelung
(Nur in Kombination mit dimmbaren Einsätzen)
Die Lichtregelung sorgt für eine nahezu konstant helle
Beleuchtung des Raumes. Das Sensor-Modul misst ständig die Helligkeit im Raum und regelt sie um einen einstellbaren Sollwert. Bei Bewegungserkennung dimmt der Einsatz die Beleuchtung zunächst zum Sollwert. Ändert sich die Umgebungshelligkeit, dimmt der Einsatz die Beleuchtung entsprechend nach. Ist ausreichend natürliches Licht vorhanden, schaltet das Sensor-Modul die Beleuchtung trotz einer anwesenden Person aus.
Beispiel zur Verdeutlichung der Lichtregelung: lx
F
A
B
C D E
E
F
G
H
A
B
C
D
Sollwert
Umgebungshelligkeit
Beleuchtung ausgeschaltet
Startphase
Regelungsphase
Regelungsbereich
Vorwarnung
Beleuchtung ausgeschaltet
G H
| Beim 2fach-Einsatz ist das Verhalten der Lichtregelung für beide Kanäle gleich.
Lichtregelung einstellen
Sobald die Lichtregelung mit dem DIP-Schalter 4 aktiviert ist, bekommen die anderen DIP-Schalter eine neue, bzw. zusätzliche Funktion:
DIP 1 Reaktionsgeschwindigkeit
Pos. ON
(oben) langsam
Sollwertänderung gesperrt
Pos. OFF
(unten) schnell
DIP 2
24 h-Treppenlichtschaltung über PL
DIP 3 Startphase einstellen
24 h „EIN“
50 %-Helligkeit der Beleuchtung per IR-Fernbedienung oder Taster-
Modul
24 h „EIN“ oder 24 h
„AUS“
Sollwert
Reaktionsgeschwindigkeit einstellen
Mit dem DIP-Schalter 1 können Sie die Reaktionsgeschwindigkeit einstellen, mit der das Sensor-Modul das
Licht an den Sollwert anpasst.
lx
A
ON DIP
1 2 3 4 t
A langsame Lichtregelung lx
B
ON DIP
1 2 3 4 t
B schnelle Lichtregelung
Sollwert ändern
Der Sollwert ist ein gewünschter Helligkeitswert, der im
Raum nahezu konstant eingehalten werden soll. Dieser
Wert ergibt sich aus der Umgebungshelligkeit und der
Beleuchtung.
Mit dem DIP-Schalter 2 können Sie wählen, ob der Sollwert geändert werden darf. Dies ist möglich mit der IR-
Fernbedienung oder über ein Taster-Modul auf dem
Zentralstellen-Einsatz.
Die Helligkeit der Beleuchtung ändert sich bei der Sollwertänderung entsprechend.
ON DIP
A
1 2 3 4
ON DIP
B
1 2 3 4 lx
C
10
Startphase einstellen
Mit dem DIP-Schalter 3 können sie die Startphase einstellen, mit der das Sensor-Modul das Licht einschaltet.
Start mit 50 %-Helligkeit der Beleuchtung lx
ON DIP
1 2 3 4
A
B
C
D
A
E
F
G
B
C
D
E F G t max. Gesamthelligkeit (Umgebungshelligkeit und
Beleuchtung)
Sollwert
50 %-Helligkeit der Beleuchtung
Umgebungshelligkeit
Beleuchtung ausgeschaltet
Startphase
Regelungsphase
Start mit Sollwert lx
ON DIP A
1 2 3 4 B
C D
A
B
C
D
E
Sollwert
Umgebungshelligkeit
Beleuchtung ausgeschaltet
Startphase
Regelungsphase
E t
Sensor-Modul mit IR-Fernbedienung bedienen
Sie können mit der Taste 10 auf der IR-Fernbedienung
B zwischen drei Funktionen des Sensor-Moduls umschalten. t
A
B
Sollwertänderung gesperrt
Sollwertänderung freigegeben mit IR-Fernbedienung oder über Taster-Modul auf Zentralstellen-Einsatz
C Sollwert ändern
– mit IR-Fernbedienung:
Taste 8: Sollwert erhöhen
Taste 9: Sollwert reduzieren
– mit Taster-Modul:
Taste oben: Sollwert erhöhen
Taste unten: Sollwert reduzieren
A
B
9
8
7
6
4
10 2
1
3
5
24 h 24 h
•
•
• Funktion Auto : Das Sensor-Modul befindet sich im
Automatikbetrieb und schaltet Verbraucher bei erkannter Bewegung ein und nach Ablauf der Nachlaufzeit aus.
24 h „EIN“ : Verbraucher ist für 24 Stunden eingeschaltet (keine Bewegungserkennung). Grüne LED
A leuchtet.
24 h „AUS“ : Verbraucher ist für 24 Stunden ausgeschaltet (keine Bewegungserkennung). Grüne LED
A leuchtet.
Sensor-Modul von anderer Stelle steuern
Verbraucher von anderer Stelle über
PlusLink steuern mit:
• Taster-Modul auf Zentralstellen-Einsatz
• Sensor-Modul auf Zentralstellen-Einsatz
• Nebenstelle Plus, 1fach/2fach
• mechanischem Taster
Beispiel für globale Steuerung mit Taster-Modul auf
Zentralstellen-Einsatz
Treppenlichtfunktion starten
Bei Betätigung des Taster-Moduls auf dem Zentralstellen-Einsatz un
A starten alle lokalen Sensor-Module abhängig.
B in den PL-Linien die eingestellte Treppenlichtfunktion helligkeits
Beispiel für globale Steuerung mit mechanischem
Taster
Bei Betätigung des mechanischen Tasters A alle lokalen Sensor-Module B stellte Treppenlichtfunktion helligkeits un
starten
in der PL-Linie die eingeabhängig.
A
PL
B
A
PL4
PL3
PL2
PL1
B
B
A
B
Taster-Modul auf Zentralstellen-Einsatz (alternativ:
Nebenstelle Plus für eine PL-Linie)
Sensor-Modul in PL-Linie
24 h-Treppenlichtschaltung
• Taste oben links: Treppenlicht für 24 h einschalten
• Taste unten links: Treppenlicht für 24 h ausschalten
(Voraussetzung: DIP2 auf „OFF“)
| Wenn DIP 2 auf „ON“ steht, ist ein Ausschalten
über ein Taster-Modul für 24 h nicht möglich.
• Taste oben/unten rechts: 24 h-Treppenlichtschaltung deaktivieren.
A
PL4
PL3
PL2
PL1
B
24 h
B
A
B
Taster-Modul auf Zentralstellen-Einsatz (alternativ:
Nebenstelle Plus für eine PL-Linie)
Sensor-Modul in PL-Linie
B
A
B
Mechanischer Taster
Sensor-Modul in PL-Linie
Beispiel für globale Steuerung mit Paniktaster an
Zentralstellen-Einsatz
Bei Betätigung des Paniktasters B
Sensor-Module C
starten alle lokalen
in den PL-Linien eine feste Nachlaufzeit von 30 Minuten (Panikszene) helligkeits un abhängig.
| Ein vorzeitiges Beenden der Funktion ist möglich mit einem Taster-Modul auf dem Zentralstellen-
Einsatz. Drücken Sie dazu die rechte Taste.
Beim Zentralstellen-Einsatz in Kombination mit einem Sensor-Modul ist die Panikfunktion daher nicht möglich.
A B
PL1
PL4 PL3
C
PL2
30 min
C
A
B
C
Taster-Modul auf Zentralstellen-Einsatz
Mechnischer Taster (Paniktaster)
Sensor-Modul in PL-Linie
Sensor-Modul bedienen: Globale
Treppenlichtfunktion über PlusLink
| Die globale Steuerung über PlusLink ist möglich in Kombination von Zentralstellen-Einsatz und
Sensor-Modul.
Beispiel für globale Steuerung über
Sensor-Modul auf dem Zentralstellen-
Einsatz
Erkennt das Sensor-Modul A
Einsatz eine Bewegung, sendet es einen Triggerbefehl an alle lokalen Sensor-Module
auf dem Zentralstellen-
B in den PL-Linien.
Die lokalen Sensor-Module B prüfen die Umgebungshelligkeit. Nur wenn die eingestellte Helligkeitsschwelle unterschritten ist, startet die Treppenlichtfunktion.
Zusätzlich können Sie die Treppenlichtfunktion der Taster-Module Comfort und Comfort Plus in den PL-Linien starten.
A
PL4
PL3
PL2
PL1
B
C
A
B
C
Sensor-Modul auf Zentralstellen-Einsatz
Sensor-Modul in PL-Linie 1
Taster-Modul Comfort oder Comfort Plus mit eingestellter Treppenlichtfunktion
| Hinweise:
• Taster-Module
Link.
C ohne eingestellte Treppenlichtfunktion ignorieren die Befehle über Plus-
• Das Sensor-Modul sendet auf dem Zentralstellen-Einsatz immer helligkeits un abhängig.
• Die DIP-Schalter des Sensor-Moduls haben auf dem Zentralstellen-Einsatz keine Funktionalität.
Beispiel für zwei Sensor-Module auf Zentralstellen-
Einsätzen in der PL-Linie
A
PL1
B
PL1
A
A
B
Sensor-Modul auf Zentralstellen-Einsatz
Sensor-Module in PL-Linie
Was tun bei Störungen?
Verbraucher wird nicht eingeschaltet.
• Empfindlichkeit zu gering eingestellt.
– Empfindlichkeit erneut einstellen.
• Helligkeitsschwelle zu gering eingestellt.
– Helligkeitsschwelle erneut einstellen.
Verbraucher ist ständig eingeschaltet.
• Nachlaufzeit oder Empfindlichkeit zu hoch eingestellt.
Das Sensor-Modul erkennt ständig neue Bewegungen und startet die Nachlaufzeit erneut.
– Nachlaufzeit oder Empfindlichkeit reduzieren.
Sensor-Modul reagiert nicht. Rote LED blinkt schnell.
• Sensor-Modul und Einsatz sind nicht kompatibel (z. B.
Jalousiesteuerungs-Einsatz)
– Sensor-Modul auf kompatiblen Einsatz (siehe Funktionsübersicht) stecken.
Technische Daten
Erfassungswinkel: 360°
Anzahl der Ebenen: 6
Anzahl der Zonen: 136
Anzahl Bewegungssensoren: 4
Empfohlene Montagehöhe:
Reichweite (einstellbar über „Sensitivity“):
2,50 m
Nachlaufzeit
Kanal 1: max. ca. 7 m Erfassungsradius
Helligkeitsschwelle: ca. 10 Lux bis ca. 1000 Lux (stufenlos einstellbar), helligkeitsunabhängig ca. 10 s bis ca. 30 min. (stufenlos einstellbar), Testmodus (1 s)
Nachlaufzeit
Kanal 2:
Anzeigeelemente: ca. 5 min. bis ca. 2 Std. (stufenlos einstellbar), OFF
1 rote LED
1 grüne LED
DIP-Schalter:
Anschluss:
1: Präsenzfunktion/Bewegungsmelderfunktion
2: 24 h-Treppenlichtschaltung
3: Vorwarnung Kanal 1
4: Lichtregelung
Modul-Schnittstelle mit 8 Kontaktstiften
Merten GmbH
Merten GmbH, Fritz-Kotz-Str. 8, D-51674 Wiehl www.merten.de
Service Center (Warenrücksendung):
Telefon: +49 2261 702-204
Telefax: +49 2261 702-136
E-Mail: [email protected]
Technische Auskünfte / InfoLine:
Telefon: +49 2261 702-235
Telefax: +49 2261 702-680
E-Mail: [email protected]
ARGUS Presence sensor module with IR© Merten 2009V5522-581-0012/11
de en
ARGUS Presence sensor module with
IR
Operating instructions
Art. no. MEG5522-00..
Necessary accessories
– Complete the ARGUS Presence sensor module with
IR with the corresponding inserts (see function overview).
Accessories
– Surface-mounted housing for ARGUS Presence
(Art. no. 550619)
– IR remote control Distance 2010 (Art. no. 570222)
For your safety
¼ DANGER
Risk of death from electric shock.
All work on the device should only be carried out by trained and skilled electricians. Observe the country-specific regulations.
Getting to know the sensor module
The ARGUS Presence sensor module with IR (referred to below as sensor module ) is a presence detector for indoor ceiling mounting. The sensor module can be mounted either in a flush-mounted socket or in surfacemounted housing (available as an accessory). It detects moving heat sources (e.g. people) within an adjustable area of detection and starts a staircase lighting function.
The maximum detection radius is approx. 7 m. The angle of detection is 360°. As long as a movement is detected, the connected load remains switched on. The adjustable overshoot time only begins when no further movements are detected (trigger function).
The sensor module is equipped with a light sensor with an adjustable brightness threshold so that the lighting is only switched on below a specified brightness threshold
(movement detector function). If there is sufficient natural light, the presence function allows the sensor module to switch off the lighting even when a person is present.
| The specified detection radius and brightness threshold refer to average conditions and a recommended mounting height of approx. 2.50 m and should therefore be taken as guide values.
The range can vary greatly when the temperature fluctuates.
Example to illustrate the presence function: lx
1000
800
600
A
400
200
B C D E F
A
B
C
D
E
F
Brightness threshold is set to 500 lux.
Lighting is switched off, brightness in the room is
200 lux.
Sensor module detects movement: Lighting
(400 lux) is switched on. Overall brightness in the room is now 600 lux.
Daylight and thus the overall brightness in the room increases.
Overall brightness exceeds 900 lux. Daylight on its own is now above the brightness threshold of
500 lux. The lighting is switched off (after the overshoot time has elapsed).
Despite detecting movement, the sensor module does not switch on the lighting since there is still sufficient daylight.
The switchable light control (only in combination with dimmable inserts) keeps the lighting in the room at a constant brightness. The sensor module permanently measures the brightness in the room and keeps it at an adjustable setpoint.
You can switch between the "automatic mode", "24 h on" and "24 h off" modes via an IR remote control.
Function overview of the sensor module on receiving inserts
Complete the sensor module with the receiving inserts for switching or dimming in order to perform control and other functions.
local light
Switching
• Electronic switch insert
• Relay switch insert
• Electronic switch insert,
2-gang
• Relay switch insert,
2-gang
Sensor module: brightness-dependent staircase lighting function
Sensor module:
Channel 1: brightness-dependent staircase lighting function
Channel 2: brightnessin dependent staircase lighting function
Dimming
• Universal dimmer insert
• 1-10 V insert
• DALI insert
• Universal dimmer insert,
2-gang
Sensor module: brightness-dependent staircase lighting function, light control
Sensor module:
Channel 1: brightness-dependent staircase lighting function, light control
Channel 2: brightnessin dependent staircase lighting function, light control
Function overview of the sensor module on sending insert
Complete the sensor module with the sending central unit insert in order to perform global light control via the
PlusLink (PL) .
Global light control:
• Central unit insert Sensor module: brightness in dependent staircase lighting function
Using the sensor module with alarm systems
|
|
Movement/presence detectors are not suitable for use as components of an alarm system.
Movement/presence detectors can trigger false alarms if the installation site has been chosen unfavourably.
Movement/presence detectors switch on as soon as they detect a moving heat source. This can be a person, but also animals or differences in temperature in windows. In order to avoid false alarms, the chosen installation site should be such that undesired heat sources cannot be detected (see section „Selecting the installation site“).
Connections, displays and operating elements
Front:
A
B
A
B red LED (in test mode) green LED (for 24-h staircase lighting circuit)
Rear:
D
C LUX
2min
Test
Time Ch.1
30min
ON DIP
1 2 3 4
Sensitivity
1h
5min
2h
Time Ch.2
OFF
B
E
F
A
A
B
C
D
E
F
Module interface
DIP switches
1: Presence function / movement detector function
2: 24-h staircase lighting circuit
3: Prewarning for channel 1
4: Light control
Potentiometer for overshoot time channel 1
Potentiometer for brightness threshold
Potentiometer for sensitivity
Potentiometer for overshoot time channel 2
Selecting the installation site
• Only mount the sensor module in positions that allow the desired area to be monitored optimally.
Mounting the sensor module
Setting the brightness threshold
4
A B
• Install the sensor module on the ceiling, if at all possible in the centre of the room.
• Do not install the sensor module on inclines or walls.
• Install the sensor module at least 0.5 m away from lights.
• The recommended mounting height is 2.50 m. Any mounting height which deviates from this will affect the area of detection.
• Maximum area of detection of the sensor module:
360° angle of detection, approx. 7 m detection radius.
2,5 m
C C
D
E E
A
B
C
D
E
Flush-mounted socket
Surface-mounted housing for ARGUS Presence
(accessory)
Insert (see function overview)
Screws (included with surface-mounted housing)
Sensor module
| When the mains voltage is supplied, the sensor module switches channel 1 on for 30 s and then back off. Channel 2 remains switched off. During the 2 s that ensue, the sensor module does not react to any movement. After this initialisation period has elapsed, the sensor module is ready for operation.
12,0 m
14,0 m
• Inner/outer area of detection
– inner area of detection (approx. 6 m radius): movement detection of a seated person due to less movement
– outer area of detection (approx. 7 m radius): movement detection of a person walking due to greater movement
• In order to ensure continuous monitoring, e.g. of a long hall, the areas of detection of the individual sensor modules have to intersect.
• Movement/presence detectors detect objects that radiate heat. You should select an installation site that will not result in undesired heat sources being detected, such as:
– switched-on lamps in the area of detection
– open fires (such as in fireplaces)
– moving curtains, etc., that have a different temperature to their environment due to strong sunlight
– windows where the influence of alternating sunlight and clouds could cause rapid changes in temperature
– larger heat sources (e.g. cars), that are detected through windows
– sunlit rooms with reflecting objects (e.g. the floor), which can be the cause of rapid changes in temperature
– windowpanes heated up by sunlight
– dogs, cats, etc.
• To prevent faulty operation, the insert should be installed in a wind-resistant flush-mounted socket. With flush-mounted sockets and pipe cabling systems, a draught of air at the back of the equipment can trigger the sensor module.
• Avoid direct sunlight. This can destroy the sensor in extreme cases.
Setting the sensor module
On the rear side of the sensor module, the potentiometer can be used to set the sensor module's sensitivity, brightness threshold and overshoot time.
Additional possible settings using DIP switches:
DIP 1 Presence function
Pos. ON
(upper)
Active
Pos. OFF
(lower)
Inactive
DIP 2 24 h staircase lighting circuit via PlusLink
DIP 3 Prewarning for channel
1
24 h "ON" 24 h "ON"
Active or 24 h
"OFF"
Inactive
DIP 4 Light control Active Inactive
Setting the sensitivity
1
10s
2min
30min
Test
2
B
A
Sensitivity
C A B C
1 Activate the test mode and set the brightness threshold to "infinite".
The red LED lights up when movement is detected.
2
3
Infinitely adjust the sensitivity (max. 7 m detection radius).
Walk around the area of detection and check whether the sensor module is switching as desired. Adjust the sensitivity if required.
4 Infinitely set the desired brightness threshold. The sensor module switches below the set brightness threshold.
Detects movement in the dark (approx. 10 lux)
Detects movement during daylight
(approx. 1000 lux)
Detects movement in dependently of brightness
5 Check that the sensor module switches at the desired/set brightness. Adjust the brightness threshold if required.
| In combination with a 2-gang insert, the brightness threshold only applies to channel 1. Channel 2 always switches in brightness.
dependently of
Adjusting the staircase lighting function
You can set the type of staircase lighting function (without/with prewarning) and the overshoot time.
When setting the overshoot time, you specify how long the connected load remains switched on (continuously from 10 s to 30 min.). In the case of a 2-gang insert, the overshoot time for both channels can be adjusted separately.
The prewarning indicates the end of the overshoot time.
The loads are switched off briefly and then back on again
(in combination with switch inserts), or are dimmed down slowly (in combination with dimmable inserts). The loads are switched off after the prewarning time has elapsed
(30 s, not adjustable).
1 Select the type of staircase lighting function and set the overshoot time.
Staircase lighting function without prewarning
1
2min
ON DIP
10s
30min
Test
1 2 3 4
A t
B t
C
A
B
C
Switching without prewarning
Dimming without prewarning
Overshoot time
Staircase lighting function with prewarning
1
2min
ON DIP
10s
30min
Test
1 2 3 4
A t
B t
A
B
C
D
C D
Switching with prewarning
Dimming with prewarning
Overshoot time
Prewarning time (30 s, not adjustable)
| The prewarning only applies to channel 1.
Setting the overshoot time for channel 2
When using a 2-gang insert, the overshoot time for channel 2 can be adjusted using a separate potentiometer.
The adjustable time period differs from that of channel 1.
1
1h
5min 2h
OFF
Activating/deactivating the presence function
In the case of brightness-dependent movement detection, the sensor module constantly monitors the brightness in the room and compares it to the set brightness threshold. If sufficient natural light is available, the sensor module will switch the lighting off even if a person is present.
The sensor module's presence function is activated as a factory default. You can deactivate the function ("OFF") and reactivate it ("ON") using DIP switch 1.
ON DIP
1 2 3 4
When the presence function has been deactivated, the sensor module continues to carry out the movement detector function.
Adjusting the 24-h staircase lighting circuit
DIP switch 2 can be used to set a 24-hour staircase lighting circuit which you can retrieve from another location via PlusLink.
The following options are available for this:
• DIP 2 "ON": only
24 h via PL
switch on the staircase lighting for
• DIP 2 "OFF": switch the staircase lighting on/off for
24 h via PL
ON DIP
1 2 3 4
Activating/deactivating light control
(Only in combination with dimmable inserts, see function overview)
The sensor module's light control is deactivated as a factory default. You can activate the function ("ON") and deactivate it ("OFF") using DIP switch 4.
ON DIP
1 2 3 4
Light control
Basic function of light control
(Only in combination with dimmable inserts)
Light control keeps the lighting in the room at a constant brightness. The sensor module permanently measures the brightness in the room and keeps it at an adjustable setpoint. When movement is detected, the insert initially dims the lighting to the setpoint value. If the ambient brightness changes, the insert dims the lighting accordingly. If sufficient natural light is available, the sensor module will switch the lighting off even if a person is present.
Example to illustrate light control: lx
F
A
B
C D E
E
F
G
H
A
B
C
D
Setpoint
Ambient brightness
Lighting switched off
Start phase
Control phase
Control range
Prewarning
Lighting switched off
G H
| In the case of a 2-gang insert, the behaviour of the light control is the same for both channels.
Adjusting the light control
As soon as the light control is activated via DIP switch 4, the other DIP switches take on a new or additional function:
DIP 1 Response speed
DIP 2
Setpoint change
Pos. ON (upper)
Slow
Disabled
Pos. OFF
(lower)
Fast
Via IR remote control or push-button module
24-h staircase lighting circuit via PL
24 h "ON" 24 h "ON" or
24 h "OFF"
DIP 3 Adjust start phase 50% brightness of the lighting
Setpoint
Adjusting the response speed
The speed with which the sensor module adjusts the light to the setpoint value can be adjusted using DIP switch 1.
lx
A
ON DIP
1 2 3 4 t
A slow light control lx
B
ON DIP
1 2 3 4 t
B fast light control
Changing the setpoint
The setpoint is a desired brightness value that should be observed constantly in the room. This value results from the ambient brightness and the lighting.
You can select whether or not the setpoint value may be altered using DIP switch 2. This is possible via the IR remote control or via a push-button module on the central unit insert.
The brightness of the lighting alters accordingly for setpoint changes.
ON DIP
A
1 2 3 4
ON DIP
B
1 2 3 4 lx
C
10 t
A
B
Setpoint change disabled
Setpoint change enabled via IR remote control or via push-button module on central unit insert
C Change setpoint
– via IR remote control:
Push-button 8: Increase setpoint
Push-button 9: Reduce setpoint
– via push-button module:
Upper push-button: Increase setpoint
Lower push-button: Reduce setpoint
Adjusting the start phase
The start phase with which the sensor module switches on the light can be adjusted using DIP switch 3.
Start at 50% brightness of the lighting lx
ON DIP
1 2 3 4
A
B
C
D
A
E
F
G
B
C
D
E F G t max. overall brightness (ambient brightness and lighting) setpoint
50% brightness of the lighting ambient brightness lighting switched off start phase control phase
Start with setpoint lx
ON DIP A
1 2 3 4 B
C D
A
B
C
D
E setpoint ambient brightness lighting switched off start phase control phase
E t
Operating sensor module by IR remote control
You can toggle between three functions of the sensor module by pressing key 10 on the IR remote control B .
Controlling the sensor module from another location
Controlling loads from another location via PlusLink with:
• Push-button module on central unit insert
• Sensor module on central unit insert
• Side controller Plus, 1-gang/2-gang
• Mechanical push-button
Example of global control with push-button module on central unit insert
Starting the staircase lighting function
When the push-button module on the central unit insert
A is actuated, all local sensor modules B in the PL lines start the set staircase lighting function in ently of brightness.
depend-
A
PL4
PL3
PL2
PL1
B
A
B
9
8
7
10
6
2
4
1
3
5
24 h 24 h
•
•
•
Auto function: The sensor module is in automatic mode and switches the loads on when movement is detected and then off again after the overshoot time has elapsed.
24 h "ON" : Load is switched on permanently for 24 h
(no movement detection). Green LED A lights up.
24 h "OFF" : Load is switched off permanently for 24 h
(no movement detection). Green LED A lights up.
B
A
B
Push-button module on central unit insert (alternatively: side controller Plus for one PL line)
Sensor module in PL line
24-h staircase lighting circuit
• Upper left push-button: switch on the staircase lighting for 24 h
• Lower left push-button: switch off the staircase lighting for 24 h (prerequisite: DIP2 "OFF")
| If DIP 2 is switched to "ON", the lighting cannot be switched off for 24 h via the push-button module.
• Upper/lower right push-button: deactivate the 24-h staircase lighting circuit.
A
PL4
PL3
PL2
PL1
B
24 h
B
A
B
Push-button module on central unit insert (alternatively: side controller Plus for one PL line)
Sensor module in PL line
Example of global control with mechanical pushbutton
When the mechanical push-button A cal sensor modules B case lighting function in
is actuated, all lo-
in the PL lines start the set stairdependently of brightness.
A
PL
B
B
A
B
Mechanical push-button
Sensor module in PL line
Example of global control with panic button on the central unit insert
When the panic button B modules C
is actuated, all local sensor
in the PL lines start a fixed overshoot time of
30 minutes (panic scene) in dependently of brightness.
| When a push-button module is used on the central unit insert, the function can be stopped early.
Press the right push-button in order to do this.
When the central unit insert is used in combination with a sensor module, the panic function is not available.
A B
PL1
PL4 PL3
C
PL2
30 min
C
A
B
C
Push-button module on central unit insert
Mechanical push-button (panic button)
Sensor module in PL line
Operating the sensor module: global staircase lighting function via PlusLink
| The global control via PlusLink is possible with the combination of central unit insert and sensor module.
Example of global control via sensor module on the central unit insert
If the sensor module sor modules B
A on the central unit insert detects a movement, it sends a trigger command to all local sen-
in the PL lines.
The local sensor modules B check the ambient brightness. The staircase lighting function only starts if the brightness is below the set brightness threshold.
You can also start the staircase lighting function of the push-button modules Comfort and Comfort Plus in the
PL lines.
A
PL4
PL3
PL2
PL1
B
C
A
B
C
Sensor module on central unit insert
Sensor module in PL line 1
Push-button modules Comfort or Comfort Plus with set staircase lighting function
| Notes:
• Push-button modules case lighting function ignore the commands via
PlusLink.
C without a set stair-
• On the central unit insert, the sensor module always sends in dependently of brightness.
• The sensor module's DIP switches do not function on the central unit insert.
Example of two sensor modules on central unit inserts in the PL line
A
PL1
B
PL1
A
A
B
Sensor module on central unit insert
Sensor modules in PL line
What should I do if there is a problem?
Load is not switching on.
• The sensitivity is set too low.
– Reset the sensitivity.
• The brightness threshold is set too low.
– Reset the brightness threshold.
Load is permanently switched on.
• The overshoot time or the sensitivity is set too high.
The sensor module constantly detects new movements and restarts the overshoot time.
– Reduce the overshoot time or sensitivity.
The sensor module is not reacting. The red LED is flashing quickly.
• The sensor module and insert are not compatible (e.g. blind control insert)
– Place the sensor module onto a compatible insert
(see function overview).
Technical data
Angle of detection: 360°
Number of levels: 6
Number of zones: 136
Number of presence detectors: 4
Recommended mounting height:
Range (can be adjusted under "Sensitivity"):
2.50 m max. approx. 7 m detection radius
Brightness threshold: approx. 10 lux to approx.
1000 lux (infinitely adjustable), brightness independent
Overshoot time channel 1: approx. 10 s to approx. 30 min
(infinitely adjustable), test mode
(1 s)
Overshoot time channel 2:
Display elements:
DIP switches: approx. 5 min. to approx. 2 hrs.
(infinitely adjustable), OFF
1 red LED
1 green LED
1: Presence function / movement detector function
Connection:
2: 24-h staircase lighting circuit
3: Prewarning for channel 1
4: Light control module interface with 8 contact pins
Merten GmbH
Merten GmbH, Fritz-Kotz-Str. 8, D-51674 Wiehl www.merten.com
Service Center:
Phone: +49 2261 702-204
Fax: +49 2261 702-136
E-Mail: [email protected]
Technical support / InfoLine:
Phone: +49 2261 702-235
Fax: +49 2261 702-680
E-Mail: [email protected]