Digi-Sense 20250-58 User Manual
Digi-Sense 20250-58 is a versatile measuring device that combines multiple functions into one compact tool, making it suitable for various electrical and temperature measurement applications. It features True RMS technology, enabling accurate measurements of AC signals, and a wide range of capabilities including AC/DC voltage, AC/DC current, resistance, capacitance, frequency, duty cycle, and temperature measurements. It also offers advanced features like data hold, backlight, and auto power-off, enhancing its user-friendliness and convenience during measurements.
Advertisement
Advertisement
User Manual
Autoranging Clamp Meters
with NIST-Traceable Calibration
Models 20250-57 (1000 A AC),
20250-58 (1000 A AC/DC, True RMS)
THE STANDARD IN PRECISION MEASUREMENT
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 1 8/8/2017 1:06:47 PM
Introduction
The Digi-Sense Autoranging Clamp Meters (1000 A AC
Model 20250-57; 1000 A AC/DC True RMS Model 20250-58) offer all the basic features needed for measurement. The double-molded plastic housing and jaw are designed for use in tight places. A large backlit display provides easy-toread measurements. The instruments are fully tested and calibrated to NIST-traceable standards. Careful use of the meter will provide years of reliable service.
Safety
International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages may be present
Double insulation
2
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 2 8/8/2017 1:06:48 PM
SAFETY NOTES
• Do not exceed the maximum allowable input range of any function.
• Do not apply voltage to meter when resistance function is selected.
• Set the function switch OFF when the meter is not in use.
WARNINGS
• Set rotary function switch to the appropriate position before measuring.
• When measuring volts, do not switch to current/resistance modes.
• When changing ranges using the rotary function switch, always disconnect the test leads from the circuit under test.
• Do not exceed the maximum rated input limits:
Function
A
V
Frequency, Duty cycle, Resistance,
Diode, Continuity,
Capacitance Test
Temperature (°C/°F)
Input Limits
Maximum Input,
Model 20250-57
1000 A AC
600 V AC/DC
250 V AC/DC
—
Maximum Input,
Model 20250-58
1000 A AC/DC
600 V AC/DC
250 V AC/DC
60 V DC, 24 V AC
3
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 3 8/8/2017 1:06:48 PM
CAUTIONS
• Improper use of this meter can cause damage, shock, injury or death. Read and understand this user manual before operating the meter.
• Always remove the test leads before replacing the battery.
• Inspect the condition of the test leads and the meter itself for any damage before operating the meter. Repair or replace any damage before use.
• Use great care when making measurements if the voltages are greater than 25 VAC rms or 35 VDC. These voltages are considered a shock hazard.
• Remove the battery if the meter is to be stored for long periods.
• Always discharge capacitors and remove power from the device under test before performing Diode,
Resistance, or Continuity tests.
• Voltage checks on electrical outlets can be difficult and misleading because of the uncertainty of connection to the recessed electrical contacts. Other means should be used to ensure that the terminals are not "live".
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
4
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 4 8/8/2017 1:06:48 PM
Unpacking
Check individual parts against the list of items below. If anything is missing or damaged, please contact your instrument supplier immediately.
1. Meter
2. Test leads
3. Temperature probe (model 20250-58 only)
4. Carrying case
5. 9 V battery
6. User manual
7. NIST-traceable calibration report with data
Key Features
1. Durable double-molded housing
2. 1 3 ⁄
16
" (30 mm) jaw opening
3. CAT III 600 V safety rating
4. Electronic overload protection
5. Autoranging with auto power-off
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 5
5
8/8/2017 1:06:48 PM
6
Meter Description (Model 20250-57)
1. Current clamp
2. Clamp trigger
3. Data HOLD and Backlight button
4. MODE select button
5. RANGE select button
6. LCD
7. COM input jack
8. Rotary function switch
9. Hz% Hold button
10. Max/Min button
11. V Ω •))) Hz jack
12. Battery compartment (on rear)
1
2
5
6
3
4
7
A
600A
60A
Meter Description (Model 20250-58)
1. Current clamp
2. Clamp trigger
3. Data HOLD and Backlight button
4. MODE select button
5. RANGE select button
6. LCD
7. COM input jack
8. Rotary function switch
9. DC ZERO button
10. Max/Min button
11. V Ω •))) CAP Hz Temp jack
12. Battery compartment (on rear)
6
A
A
600A
60A
A
A
8
9
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 6 8/8/2017 1:06:49 PM
1
2
5
6
3
4
7
A
600A
60A
8
9
Display Layout
1. AC DC
2. –
3. 8.8.8.8
AC (alternating current) and
DC (direct current)
Minus sign
6000 count (0 to 5999) measurement reading with 61-segment analog bar graph
4. AUTO Autorange mode
5. MAX MIN Max and Min readings
6. HOLD
7.
8. •)))
Data HOLD mode
Diode test mode
Audible continuity
9. µ,m,V,A,K, Units of measure list (20250-57);
M, Ω ;
°C,°F, µ,m,V, Units of measure list (20250-58)
A,K,M, Ω
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 7
7
8/8/2017 1:06:49 PM
8
Setup and Operation
Note: Read and understand all warning and precaution statements listed in the safety section of this operation manual prior to using this meter. Set the rotary function switch to the OFF position when the meter is not in use.
AC and AC/DC Current Measurements
WARNING: Ensure that the test leads are disconnected from the meter before making current clamp measurements.
1. Set the Function switch to the 1000A or 600A or 60A range.
2. For model 20250-58 only, select AC or DC by pressing the MODE button.
No
.
Yes
.
3. If the range of the measured is unknown, select the higher range first then move to the lower range as necessary.
! n n
.
A
+ DC
AC
! n n
.
A
+
4. Press the trigger to open jaw. Fully enclose one conduc tor to be measured (see diagram above). The LCD will display the reading.
5. In DCA mode, to ensure the reading is correct, press the DC ZERO button to clear the reading on the LCD before measurement. The LCD will display the reading
(model 20250-58 only).
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 8 8/8/2017 1:06:49 PM
AC/DC Voltage Measurements
1. Insert the black test lead into the negative COM terminal and the red test lead into the positive V terminal.
2. Set the rotary function switch to the V position.
3. For model 20250-58, select AC or DC by pressing the
MODE button.
4. Connect the test leads in parallel to the circuit under test.
5. Read the voltage measurement in the display.
Resistance and Continuity Measurements
1. Insert the black test lead into the negative COM terminal and the red test lead into the positive terminal.
2. Set the rotary function switch to the Ω •))) position.
3. Use the multifunction MODE button to select resistance.
4. Touch the test probe tips across the circuit or component under test. It is best to disconnect one side of the device under test so the rest of the circuit will not interfere with the resistance reading.
5. For Resistance tests, read the resistance value in the display.
6. For Continuity tests, if resistance is <100 Ω , a tone will sound.
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 9
9
8/8/2017 1:06:49 PM
Diode and Continuity Measurements
1. Insert the black test lead banana plug into the negative
COM jack and the red test lead banana plug into the positive diode jack.
2. Turn the rotary function switch to the •))) position.
3. Press the MODE button until “ “ appears in the display.
4. Touch the test probes to the diode under test. Forward voltage will indicate 0.4 V to 0.7 V. Reverse voltage will indicate “OL”. Shorted devices will indicate near 0 mV and an open device will indicate “OL” in both polarities.
Red Black Black Red
Forward test Reverse test
Capacitance Measurements
WARNING: To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking any capacitance measurements. Remove the batteries and unplug the line cords.
1. Set the rotary function switch to the Ω •))) CAP position.
2. Insert the black test lead banana plug into the negative
COM jack and the red test lead banana plug into the positive V jack.
3. Touch the test leads to the capacitor to be tested.
4. Read the capacitance value on the display.
10
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 10 8/8/2017 1:06:50 PM
Frequency or % Duty Cycle Measurements
For Model 0250-57:
1. Set the rotary function switch to the Hz% position.
2. Press the Hz% button to indicate “Hz” in the display.
3. Insert the black lead banana plug into the negative COM jack and the red test lead banana plug into the positive
Hz jack.
4. Touch the test probe tips to the circuit under test.
5. Press the Hz% button again to indicate “%” on the display. Read the % of duty cycle on the display.
For Model 20250-58:
1. Set the rotary function switch to the Hz% position.
2. Insert the black lead banana plug into the negative COM jack and the red test lead banana plug into the positive
Hz jack.
3. Press the MODE button to select “Hz” or “%”.
4. Touch the test probe tips to the circuit under test.
5. Read the frequency or % of duty cycle on the display.
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 11
11
8/8/2017 1:06:50 PM
Temperature Measurements (Model 20250-58 only)
WARNING: To avoid electric shock, disconnect both test probes from any source of voltage before making a temperature measurement.
1. Set the function switch to TEMP.
2. Insert the temperature probe into the negative COM and the V jacks, making sure to observe the correct polarity.
3. Select °C or °F units by pressing the MODE button.
4. Touch the temperature probe head to the part whose temperature you wish to measure. Keep the probe touching the part under test until the reading stabilizes
(about 30 seconds).
5. Read the temperature in the display. The digital reading will indicate the proper decimal point and value.
WARNING: To avoid electric shock, be sure the thermocouple has been removed before changing to another measurement function.
MODE Button
To select DC/ACV, OHM/Diode/Continuity/CAP
(°C or °F model 20250-58 only).
Data HOLD and Backlight Button
To “freeze” a reading on the screen, press the data HOLD button. While data HOLD is active, the “HOLD” display icon appears on the LCD. Press the HOLD button again to resume normal operation.
Note: The HOLD feature will activate when the Backlight is turned on.
12
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 12 8/8/2017 1:06:50 PM
The backlight function illuminates the display and is used when the ambient light to too low to permit viewing of the displayed readings. Press the HOLD/backlight button for one second to turn the backlight on and press the button a second time to turn the backlight off.
RANGE Button
When the meter is first turned on, it defaults to Auto
Ranging. This automatically selects the best range for the measurements being made and is generally the optimal mode for most measurements. For measurement situations requiring that a range be manually selected, perform the following:
1. Press the RANGE button. The “Auto Range” display indicator will turn off, and the “Manual Range” display indicator will turn on.
2. Press the RANGE button again to step through the available ranges until you select the range you want.
3. Press and hold the RANGE button for 2 seconds to exit the Manual Ranging mode and return to Auto Ranging.
Note: Manual Ranging does not function in the AC Current,
Diode, and Continuity check functions.
Automatic Power-Off
To conserve battery life, the meter automatically turns off after 30 minutes of nonuse.
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 13
13
8/8/2017 1:06:50 PM
Specifications
Function
AC Current
DC Current
DC Voltage
AC Voltage
Resistance
Model 20250-57
Range &
Resolution
60.00 AAC ±(2.5% + 10 digits)
600.0 AAC
—
6.000 VAC
60.00 VAC
600.0 VAC
750 VAC
600.0 Ω
6.000 K Ω
60.00 K Ω
600.0 K Ω
±(2.0 % + 5 digits)
1000 AAC
— —
—
—
—
—
600.0 mVDC ±(0.8% + 3 digits)
6.000 VDC
60.00 VDC ±(1.5% + 3 digits)
600.0 VDC
— —
1000 VDC ±(2.0% + 3 digits)
—
Accuracy
(% of reading)
±(1.5% + 5 digits)
±(2.0% + 5 digits)
±(2.0% + 5 digits)
±(1.0% + 4 digits)
±(1.5% + 2 digits)
6.000 M Ω ±(2.5% + 3 digits)
Model 20250-58
600.0 VDC
800 VDC
—
600.0 mVAC
(True RMS)
6.000 VAC
(True RMS)
60.00 VAC
(True RMS)
600.0 VAC
(True RMS)
750 VAC
(True RMS)
600.0 Ω
6.000 K Ω
60.00 K Ω
600.0 K Ω
6.000 M Ω
Range &
Resolution
60.00 AAC
(True RMS)
600.0 AAC
(True RMS)
1000 AAC
(True RMS)
60.00 ADC
Accuracy
(% of reading)
±(3.0% + 10 digits)
±(3.0 % + 8 digits)
±(3.0 % + 5 digits)
±(2.8% + 10 digits)
600.0 ADC
1000 ADC
±(2.8 % + 8digits)
±(3.0 % + 5 digits)
600.0 mVDC ±(0.8% + 3 digits)
6.000 VDC
60.00 VDC ±(1.5% + 3 digits)
±(2.0% + 3 digits)
—
±(0.8% + 20 digits)
±(1.8% + 5 digits)
±(2.5% + 5 digits)
±(1.0% + 4 digits)
±(1.5% + 2 digits)
±(2.5% + 3 digits)
Note: No autoranging in 600 mV AC voltage range (model 20250-58).
14
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 14 8/8/2017 1:06:50 PM
Function
AC Current
DC Current
DC Voltage
AC Voltage
Resistance
Model 20250-57
Range &
Resolution
Accuracy
(% of reading)
60.00 AAC ±(2.5% + 10 digits)
600.0 AAC
±(2.0 % + 5 digits)
1000 AAC
— —
—
—
—
—
600.0 mVDC ±(0.8% + 3 digits)
6.000 VDC
60.00 VDC ±(1.5% + 3 digits)
600.0 VDC
— —
1000 VDC ±(2.0% + 3 digits)
— —
6.000 VAC ±(1.5% + 5 digits)
60.00 VAC
600.0 VAC
±(2.0% + 5 digits)
750 VAC ±(2.0% + 5 digits)
600.0 Ω
6.000 K Ω
60.00 K Ω
600.0 K Ω
±(1.0% + 4 digits)
±(1.5% + 2 digits)
6.000 M Ω ±(2.5% + 3 digits)
Model 20250-58
600.0 VDC
800 VDC
—
600.0 mVAC
(True RMS)
6.000 VAC
(True RMS)
60.00 VAC
(True RMS)
600.0 VAC
(True RMS)
750 VAC
(True RMS)
600.0 Ω
6.000 K Ω
60.00 K Ω
600.0 K Ω
6.000 M Ω
Range &
Resolution
60.00 AAC
(True RMS)
600.0 AAC
(True RMS)
1000 AAC
(True RMS)
60.00 ADC
Accuracy
(% of reading)
±(3.0% + 10 digits)
±(3.0 % + 8 digits)
±(3.0 % + 5 digits)
±(2.8% + 10 digits)
600.0 ADC
1000 ADC
±(2.8 % + 8digits)
±(3.0 % + 5 digits)
600.0 mVDC ±(0.8% + 3 digits)
6.000 VDC
60.00 VDC ±(1.5% + 3 digits)
±(2.0% + 3 digits)
—
±(0.8% + 20 digits)
±(1.8% + 5 digits)
±(2.5% + 5 digits)
±(1.0% + 4 digits)
±(1.5% + 2 digits)
±(2.5% + 3 digits)
Function
Capacitance
Frequency
Duty cycle
Temperature, type K (probe accuracy not included)
Model 20250-57 Model 20250-58
400.0 μF
4000 μF
9.999 Hz
99.99 Hz
999.9 Hz
9.999 kHz
99.99 kHz
999.9 kHz
10 MHz
Range &
Resolution
40.00 nF
400.0 nF
4.000 μF
40.00 μF
—
—
—
Accuracy
(% of reading)
±(3.0% reading
+ 50 digits)
±(3.5% reading
+ 10 digits)
—
±(5.0% reading
+ 5 digits)
±(1.2% reading
+ 2 digits)
Sensitivity:
9 to 1000 kHz:
10 Vrms min.
1000 kHz to 10 MHz:
20 Vrms min.
@ 20% to 80% duty cycle
Pulse width: 100 μs to 100 ms;
Frequency: 30 Hz to 15 kHz
—
—
Range &
Resolution
40.00 nF
400.0 nF
4.000 μF
40.00 μF
100.0 μF
Accuracy
(% of reading)
±(5.0% reading
+ 100 digits)
±(3.0% reading
+ 5 digits)
±(3.5% reading
+ 5 digits)
±(5.0% reading
+ 5 digits)
—
—
—
—
9.999 Hz
99.99 Hz
999.9 Hz
9.999 kHz
99.99 kHz
999.9 kHz
10 MHz
±(1.2% reading
+ 2 digits)
Sensitivity:
10 Vrms min.
0.5 to 99.0%
±(1.2% reading
+ 2 digits)
Pulse width: 100 μs to 100 ms;
Frequency: 5.000 Hz to 100.0 kHz
–20 to 1000°C
–4 to 1832°F
±(3.0% reading
+ 5°C)
±(3.0% reading
+ 7°F)
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 15
15
8/8/2017 1:06:50 PM
Specifications (continued)
Clamp size Opening 1 3 ⁄
16
" (30 mm) approximately
Diode test Test current of 0.3 mA typical;
Open circuit voltage 1.5V DC typical
Continuity check
Threshold <30 Ω (20250-57), <100 Ω
(20250-58), Test current <1 mA
Low-battery
indication
“ ” is displayed
“ OL” is displayed Overrange
indication
Measurement
rate
Input
impedance
Display
AC Current
AC Voltage bandwidth
Operating
temperature
Storage
temperature
Operating
humidity
2 per second, nominal
7.8 M Ω (VDC and VAC)
6000 counts LCD
50–60Hz (AAC) (20250-57),
50–60Hz (AAC TRMS) (20250-58)
50–60Hz (VAC) (20250-57),
50–60Hz (VAC TRMS) (20250-58)
14 to 122°F (–10 to 50°C)
–14 to 140°F (–30 to 60°C)
90% (0 to 30°C); 75% (30 to 40°C);
45% (40 to 50°C)
16
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 16 8/8/2017 1:06:50 PM
Operating
altitude
Overvoltage
9842 ft (3000 meters),
Storage 32,808 ft (10,000 meters)
Category III 600 V
Battery One 9 V battery
Auto power-off 30 minutes approximately
Weight 7.1 oz (200 g) model 20250-57;
10.7 oz (303 g) model 20250-58
Dimensions 8 7 ⁄
8
" x 3 3 ⁄
16
" x 1 11 ⁄
16
" (22.6 x 8 x 4.3 cm)
Safety For indoor use and in accordance with
Overvoltage Category II, Pollution
Degree 2. Category II includes local level, appliance, portable equipment, etc., with transient overvoltages less than Overvoltage Cat. III
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 17
17
8/8/2017 1:06:50 PM
Maintenance, Recalibration, and Repair
Cleaning and Storage
• The meter should be cleaned with a damp cloth and mild detergent when necessary. Do not use solvents or abrasives.
• Store the meter in an area with moderate temperature and humidity.
Battery Replacement
1. Remove the one rear Phillips head screw.
2. Open the battery compartment.
3. Replace the old battery with one 9 V battery.
4. Replace the cover and secure the screw.
18
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 18 8/8/2017 1:06:50 PM
It is recommended that Digi-Sense products are
calibrated annually to ensure proper function and accurate measurements; however, your quality system or regulatory body may require more frequent calibrations.
To schedule your recalibration, please contact InnoCal, an
ISO 17025 calibration laboratory accredited by A2LA.
Phone: 1-866-INNOCAL (1-866-466-6225)
Fax: 1-847-327-2993
E-mail: [email protected]
Web: InnoCalSolutions.com
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 19
19
8/8/2017 1:06:50 PM
www.novatech-usa.com
Tel: (866) 433-6682
Tel: (281) 359-8538
Fax: (866) 433-6684
Fax: (281) 359-0084
For Product and Ordering Information, Contact:
Toll-Free: 1-800-323-4340
Phone: 1-847-549-7600
Fax: 1-847-247-2929
ColeParmer.com/Digi-Sense
1065DGMAN_20250-57,-58
Toll-Free: 1-800-358-5525
Phone: 1-847-327-2000
Fax: 1-847-327-2700
Davis.com/Digi-Sense
Manual Part No. 00101-92
1065DGMAN_20250-57,-58 DS Clamp Meter Man.indd 20 8/8/2017 1:06:50 PM