PRASTEL EASYBKR is a vandal-resistant keypad access control unit perfect for external applications. It features a weatherproof design with IP65 protection and can store up to 500 users with unique PIN codes. The backlit keypad allows easy operation even in low-light conditions, and the unit also includes an auxiliary input and output for added functionality. With its ability to work in three different modes (Normal, Secure, and Bypass), the PRASTEL EASYBKR provides flexible access control solutions for various scenarios.

advertisement

Prastel EASYBKR Keypads Instruction manual | Manualzz

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

1. INTRODUCTION

The EASYBKA/R is a vandal resistant keypad access control unit suitable for external applications. The unit accepts up to 500 users and provides entry via the use of PIN codes.

Model EASYBKA/R is provided with LED backlight.

2. MAIN TECHNICAL FEATURES

Operating Voltage Range:

Maximum Input Current: without heating: with heating, 12Vcc: with heating, 24Vcc:

Lock Strike Relay:

12-24 VAC/DC

70mA in standby

– 130 mA max

550mA in standby – 610 mA max

350mA in standby

– 465 mA max

Form C, 2A

Auxiliary Relay: Form C, 2A

Inputs :

REX N.O., Dry Contact

Auxiliary Input (In / Monitor) N.C., Dry Contact in Monitor Mode

N.O., Dry Contact in Input Mode

Operating Temperature :

Keypad Heater Enabled: da

–20 °C a 60 °C

Keypad Heater Disabled: da 0 °C a 63 °C

IP protection degree:

Dimensions:

Weight:

IP 65

120mm x 76mm x 22mm

521 g

30

EASYBKA - EASYBKR

3. MOUNTING

ENGLISH ISEASYBK_08_18.pdf.docx

Before starting, select the location to mount the EASYBKA/R controller.

This location should be at shoulder height and on the same side as the door handle.

For fixing, drill two holes, in correspondence of the two points marked as A.

B

A

B

CAUTION! DO NOT DRILL

This is the Tamper Lens

C

B

A

B

Drill in correspondence of sign C for the passage of cables.

1. Wire the controller according to the wiring instructions on the following page.

2. Screw the EASYBKA/R back cover to its mounting location.

3. Return the front cover of the EASYBKA/R to the mounted back plate.

4. Secure the front cover by using the supplied security screw in the Installation Kit. An L-Shaped tool is provided for use when tightening the security screw.

3.1 Wiring the EASYBKA/R

The controller is supplied with a 1 m pigtail, having a 10 conductor cable. To wire the EASYBKA, perform the following steps.

1. Prepare the controller cable to the required length.

2. Splice the controller pigtail wires to the corresponding devices and cover each connection. Refer to the wire color guide provided below and to the wiring diagrams provided on the following pages.

31

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

Terminal block

Color

(EASYBKR)

(EASYBKA)

Description

+

-

REX1/BL

COM

NC

NO

Red

Black

Green

Purple

Brown

Gray

Power supply (12-24V)

Ground

REX/BL

Main relay : COM

N.C.

N.O.

REX2

COM

White

Blue

IN/Monitor

Aux. Relay : COM

NC

NO

Orange

Yellow

N.C.

N.O.

3. Trim and cover all conductors that are not used.

Two typical wiring diagrams are shown on the next pages.

32

EASYBKA - EASYBKR

3.2

ENGLISH ISEASYBK_08_18.pdf.docx

Wiring the Lock Strike Relay and REX

- / Black

+ / Red

REX1/BL / Green

NO(1) / Gray

COM(1) / Violet

(+)

ELECTRIC LOCK

STRIKE

FAIL SAFE or

FAIL SECURE

(-)

(-)

(+)

(-)

COMMON

POWER SUPPLY

12V

– 24V AC/DC

Optional Varistor

33

EASYBKA - EASYBKR

3.3

ENGLISH ISEASYBK_08_18.pdf.docx

Wiring the Auxiliary Input and Output

REX2 / White

NO(2) / Yellow

NC(2) / Orange

COM(2) / Blue

- / Black

+ / Red

COMMON

POWER SUPPLY

12V – 24V AC/DC

(+)

(-)

Optional Varistor

(-)

Auxiliary Relay

N.C.

COM

N.O.

34

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

4. NORMAL, SECURE & MASTER USERS

The EASYBKA/R accepts up to 500 users and provides entry via the use of PIN codes. Each user is provided with two code memory slots,

Memory Slot 1 (Primary Code) and Memory Slot 2 (Secondary Code).

The way in which the two memory slots are programmed determines a user access level and also determines the way in which the EASYBKA/R grants access in its three Modes of Operation.

There are three user levels

:

Normal User

A Normal User only has a Primary Code and is only granted access when the EASYBKA/R is in Normal or Bypass Mode.

Secure User

A Secure User must have a Primary and Secondary Code programmed, the two codes must not be the same. The Secure User can gain access when the EASYBKA/R is in any of its three Modes of Operation. In

Normal Mode the Secure User must use their Primary Code to gain entry. In Secure Mode the Secure User must present both their Primary and Secondary Codes in order to gain entry.

Master User

A Master User must have both Primary and Secondary Codes programmed with the same PIN code. The Master User can gain access during any Mode of Operation by presenting their PIN code to the controller. (The Master User is convenient but is less secure than a

Secure User).

35

EASYBKA - EASYBKR

5. Modes of Operation

ENGLISH ISEASYBK_08_18.pdf.docx

The EASYBKA/R has 3 Modes of Operation:

1. Normal Mode

Normal Mode is the default mode and the Mode LED is green. In

Normal Mode the door is locked until a Primary Code is presented to the controller. Special codes such as "Open Code" and "Auxiliary Code" are active in Normal mode. (see

par. 9 and 11).

2. Bypass Mode.

In Bypass mode the Mode LED is orange. In Bypass Mode, access to the premises is dependent on whether the controller's Lock Strike Relay is programmed for Fail Safe

Operation or Fail Secure Operation.

 When the Lock Strike Relay is programmed for Fail

Secure Operation, the door is locked until the Door Bell Button is pressed.

 When the Lock Strike Relay is programmed for Fail Safe

Operation, the door is constantly unlocked.

3. Secure Mode

In secure mode the LED is red. Only

Secure and Master Users can access the premises during the

Secured Mode.

A Secure User must enter their Primary and Secondary Codes to gain entry. After entering their Primary Code the Door LED will flash green for 10 seconds, during which the Secondary Code must be entered.

A Master User only needs to present their PIN code once to gain entry.

36

EASYBKA - EASYBKR ENGLISH

5.1

Changing the Modes of Operation

5.1.1

ISEASYBK_08_18.pdf.docx

Changing from Normal Mode to Secure Mode:

The default factory setting for the Normal / Secure Code is 3838 .

1. Insert the code. Mode LED will flash red.

2. Press the "#" key to confirm the

Mode change. Mode LED is red.

GREEN

5.1.2

The default factory setting for the

Normal / Secure Code 3838 .

1. Insert the code. Mode LED will flash green.

2. Press the "#" key to confirm the

Mode change: the LED will turn green. The EASYBKA/R Auxiliary

Input can also be used to switch the Mode of Operation from

Normal to Secure and vice versa.

(see par.13).

5.1.3

Changing from Secure Mode to Normal Mode:

RED

RED

RED

GREEN

GREEN

Changing from Normal Mode to Bypass Mode:

To set the Normal/Bypass code refer to par. 14).

1. Insert the code. Mode LED will flash orange.

2. Press the "#" key to confirm the

Mode change. Mode LED will turn orange.

GREEN

ORANGE

ORANGE

37

EASYBKA - EASYBKR

5.1.4

ENGLISH ISEASYBK_08_18.pdf.docx

Changing from Bypass Mode to Normal Mode:

To set the Normal/Bypass code refer to

par 14.

1. Insert the code. Mode LED will flash green.

2. Press the "#" key to confirm the

Mode change. Mode LED will turn green.

ORANGE

GREEN

GREEN

6. Auxiliary Input and Output

The EASYBKA/R auxiliary input and output can be configured in different combinations, for optimum usability in different applications.

(see par.15).

7. Request to Exit (REX) Button

The REX button must be located inside the premises to be secured and is used to open the door without the use of a proximity card or PIN code, it is usually located in a convenient location, e.g. Inside the door or at a receptionist's desk. The function of the REX button depends on whether the Lock Strike Relay is programmed for Fail Safe Operation or Fail

Secure Operation.

1. Fail Secure Operation: From the moment the REX button is pressed, the door will be unlocked until the "Lock Strike Release

Time" has passed. After this time, the door will be locked even if the REX button has not been released.

2. Fail Safe Operation: From the moment the REX button is pressed, the door will be unlocked until the REX button is released, plus the "Lock Strike Release Time". In this case the "Lock Strike

Relay" only begins its count down once the REX button has been released.

38

EASYBKA - EASYBKR ENGLISH

8. Programming the EASYBKA/R

ISEASYBK_08_18.pdf.docx

Programming the EASYBKA/R is done solely via the unit's keypad

driven Programming Menu System (see par.8.1). Some codes and

settings are pre-programmed with Default Factory Settings. The table below shows the names of all the EASYBKA/R Menus, default factory codes and settings.

The keypad accepts as default a 4-digit sequence and in the same manner, the access code for programming functions is of 4 digits (default

1234 ).

The number of digits can be increased to 5, 6 or 8 digits. This modification is made using menu “0”, after having entered the programming mode (see paragraph 23).

ATTENTION: this programming must be done at the time of installation because passing from one length to another cancels all the memory content.

When the code length is modified, the programming access code

(initially 1234 ) is modified as shown in the following table:

39

EASYBKA - EASYBKR

Menu Description du menu

7

8

9

0

3

4

1

2

5

6

Change Open Code

Change Auxiliary Code

Change Program Code

Change Normal / Secure Code

Change Normal / Bypass Code

Change Door Release Time

Define Auxiliary Inputs / Outputs

Enabling the built-in keypad heater

Changing the backlight and LED behavior

Enroll Proximity Cards, PIN Code or both

Delete Proximity Cards Or PIN Code

Code Assignment with Strike/Auxiliary

Return to Factory Default Settings and selection of code length

ENGLISH

Default

4 digits

2580

0852

1234

3838

ISEASYBK_08_18.pdf.docx

After modifying the code length

5 digits 6 digits 8 digits

25802 258025 25802580

08520

12341

38383

085208

123412

383838

08520852

12341234

38383838

-

0004

2004

3000

5100

-

-

-

-

Par.

14

16

15

20

9

17

18

19

10

11

12

13

23

40

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

8.1

Entering Programming Mode

1. Press the "#" key two times.

Mode LED will turn off. Door

LED will turn red.

2. Insert the programming code.

3. If the Programming Code is valid the door LED will turn green and the EASYBKA/R will be in Programming Mode.

NOTE

RED

The EASYBKA/R must be in Normal Mode to enter the

GREEN

Programming Mode.

 The factory default Programming Code is 1234

If a Programming Code is not entered within 5 seconds, the

EASYBKA/R will return to Normal Mode.

8.2

To exit the Programming Mode

1. Press # twice to exit Programming mode at any time. You hear 3 beeps.

2. The Door LED will be off and the Mode LED will turn green, the

EASYBKA/R has returned to Normal Mode.

NOTE

 Wrong entries may reset the controller back to Normal Mode.

While in Programming Mode if no key is pressed for 1 minute the EASYBKA/R will exit programming mode and return to

Normal Mode.

41

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

9. Changing the backlight and LED behavior

1) Enter Programming Mode

2) Press "6" to enter Menu 6, the Mode LED will flash green.

3) Construct and enter a code using the following instructions: the first digit is 5, indicating the backlight and Led option, the second digit is the option number for the backlight mode that you wish to select (see the following table). The third and fourth digits are 0.

4) System returns to Transmit Mode, you will hear one beep, the Door

LED will turn off and the Mode LED will turn green.

WARNING: In modes 2 and 3, backlight is actually turned off or dimmed 10 seconds after programming.

Backlight and LED mode Option number

LED active, backlight OFF

LED active, backlight ON (default)

LED and backlight OFF, both activated on any key press for ten seconds.

LED active / backlight Dimmed, backlight activated on any key press for ten seconds.

0

1

2

3

10. Changing the Open Code

The Open Code is mainly used as a method to quickly test the Lock

Strike Relay during installation.

The Default Factory Setting for the Open Code is 2580 .

42

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

When the first user is added to the controller, the default Open Code will automatically be deleted, ready for a new Open Code to be re-entered.

1. Enter Programming Mode

2. Press "1" to enter Menu 1. The

Mode LED will turn red.

3. Insert the new “Opening Code”.

4. The EASYBKA/R returns to

Normal Mode: the Door LED will turn off and the Mode LED will turn green.

RED

GREEN

GREEN

GREEN

NOTE

 Open Code does not function in Secure Mode.

 Wrong entries will return the controller to Normal Mode.

 Code 0000 will erase and deactivate the Open Code.

11. Changing the Auxiliary Code

The Auxiliary Code is mainly used as a method to quickly test the

Auxiliary Relay during installation. The Default Factory Setting for the

Auxiliary Code is 0852 .

43

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

When the first user is added to the controller, the default Auxiliary Code will automatically be deleted, ready for a new Auxiliary Code to be re-entered.

1. Enter Programming Mode.

2. Press "2" to enter Menu 2. The

Mode LED will turn orange.

3. Insert the new “Auxiliary Code”.

4. The EASYBKA/R returns to

Normal Mode: you will hear three beeps. The Door LED will turn off and the Mode LED will turn green.

ORANGE

GREEN

GREEN

NOTE

 Auxiliary Code does not

GREEN work in Secure Mode and only works when the Auxiliary Mode is 0, 1, 8 or 9.

 Code 0000 will erase and deactivate the Auxiliary Code.

12. Changing the Programming Code

1. Enter Programming Mode.

2. Press "3" to enter Menu 3: the Mode

LED will turn green.

3. I nsert the new “Programming Code”.

4. The EASYBKA/R returns to Normal

Mode: the Door LED will turn off and the Mode LED will turn green.

GREEN

GREEN GREEN

GREEN

NOTE

 Programming Code cannot be erased, i.e. the code 0000 is not valid and will not erase the Programming Code.

44

EASYBKA - EASYBKR ENGLISH

13. Changing the Normal / Secure Code

ISEASYBK_08_18.pdf.docx

1. Enter Programming Mode

2. Press "4" to enter Menu 4: the Mode

LED will flash red.

3. Insert the new code

4. The EASYBKA/R returns to Normal

Mode: The Door LED will turn off and the Mode LED will turn green.

RED

GREEN

GREEN

GREEN NOTE

 When the Auxiliary Mode is 1, 2, 3, or 4 the Auxiliary Input takes priority over the Normal / Secure Code.

14. Changing the Normal / Bypass Code

1. Enter Programming Mode

2. Press "5" to enter Menu 5: the Mode LED will flash orange.

3. Insert a 4 digit code with 0 as the last digit for the selection of the bypass mode. To cancel the access code to the by-pass mode, insert

0000 .

4. The EASYBKA/R returns to Normal Mode: the Door LED will turn off and the Mode LED will turn green.

45

EASYBKA - EASYBKR ENGLISH

15. Defining Auxiliary Inputs/Outputs

ISEASYBK_08_18.pdf.docx

1. Enter

Mode.

Programming

2. Press "6" to enter Menu

6: the Mode LED will flash green.

3. Construct the 4-digit code using instructions below the

GREEN

GREEN GREEN

The system returns to Normal

Time Settings

Mode: The Door LED will turn off and the Mode LED will turn green.

46

EASYBKA - EASYBKR

ENGLISH ISEASYBK_08_18.pdf.docx

Auxiliary

Mode

0

1

2

3

4

5

6

7

8

9

Auxiliary Input

REX-2

Auxiliary Ouput

Activated On

Valid Code or REX-2

Normal / Secure Valid Code

Normal / Secure Bell Button ( * )

Normal / Secure Tamper Event

Normal / Secure Direct Shunt

Door Monitor

Door Monitor

Door Monitor

LED Ctrl

LED Ctrl – Red

Shunt

Forced Door

Door Ajar

– Green Valid code

Valid code

Aux.

Relay

N.O.

N.O.

Time Settings

(All times and delay are in seconds)

01 to 99 Aux. Relay Release Time

00 Aux. Relay Toggles

01 to 99 Aux. Relay Release Time

00 Aux. Relay Toggles

N.O.

N.C.

01 to 99 Aux. Relay Release Time

00 Aux. Relay Toggles

01 to 99 Aux. Relay Release Time

00 Aux. Relay activated by Tamper

N.O. 00 to 99 Shunt time

N.C. 00 to 99 Maximum Shunt Time

N.C. 00 to 99 Forced Delay

N.C. 00 to 99 Ajar Delay

N.O.

N.O.

01 to 99 Aux relay release time

00 Aux relay toggle

01 to 99 Aux relay release time

00 Aux relay toggle

47

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

16. Setting Fail Safe/Secure Operation and Lock

Strike Release Time

1. Enter Programming Mode

2. Press "6" to enter Menu 6: the Mode LED will flash green.

3. Construct the 4-digit code using the instructions below:

GREEN

GREEN

GREEN

First Digit: 0 for Fail Secure, 1 for Fail Safe

Second Digit: 0 .

Third and Fourth Digit: Lock Strike Time, enter 1 to 99 seconds

For example: 0 0 1 2 means: Fail Secure Operation, with a 12 second Lock Strike release time.

17. Enrolling Primary & Secondary Codes

Primary Codes

 Primary Codes can only be enrolled to an empty User Slot, i.e. a slot where there is no existing Primary Code.

 Primary Codes must be unique, i.e. one user Primary Code may not be the same as another user Primary Code.

 Primary Codes cannot be the same as any system codes, such as the Normal / Secure Code or Open Code.

 Users who hold a Primary Code can gain entry during Normal and Bypass modes

Secondary Codes

48

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

 Secondary Codes can only be enrolled to User Slot that already has a Primary Code enrolled but no Secondary Code.

 Secondary Codes do not have to be unique, i.e. multiple users can all hold the same Secondary Code.

 Secondary Codes cannot be the same as any system codes, such as the Normal / Secure Code or Open Code.

 Users who hold Secondary Codes can gain entry in any Mode of Operation.

Enrolling codes

There are two methods to enroll Primary and Secondary codes, the

Standard Method and the Code Search Method.

A. The Standard Method is mainly used when the User Slot number for the user you wish to program is known. You can program both Primary and Secondary Codes using the Standard method.

B. The Code Search Method is mainly used when enrolling a users Secondary Code and the User Slot Code is unknown. The Code Search method only works if a user's

Primary Code is already enrolled but the Secondary Code is not.

17.1 Enrolling Primary and Secondary Codes using the

Standard Method

1. Enter Programming Mode.

2. Press "7" to enter Menu 7: the

Door LED will turn orange.

3. Enter the 3-digit User Slot number between 001 to 500 that you wish to enroll a Primary or Secondary code to. (For example, the User Slot 003 represents User #3).

GREEN

ORANGE

49

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

 If the selected slot has no

Primary Code, the Mode

LED will flash green, indicating that the controller is ready to accept a Primary Code.

 If the selected slot already has

GREEN ORANGE a Primary Code but no

Secondary Code, the Mode

RED ORANGE

LED will flash red, indicating that the controller is ready to accept a Secondary Code.

 If the selected slot already has a Primary and Secondary

Code, you will hear a long beep and the controller will return to Normal Mode.

4. Enter the 4-digit PIN that you want to assign as the Primary or

Secondary Code for this slot number. If the PIN that is entered is valid the Mode LED will stop flashing and then the controller is ready for you to enter the next 3 Digit slot number (refer to step

3) that you want to assign a code to.

5. Press the "#" key to move to the next slot number (refer to step

4). If you do not wish to continue enrolling codes, press the "#" key twice and the controller will return to Normal Mode.

50

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

17.2 Enrolling Secondary Codes using the Code Search

Method

1. Enter Programming Mode

2. Press "7" to enter Menu 7: the

Door LED will turn Orange

3. Enter the 3-digit User Slot number

000 , the Door LED will flash

Orange: the controller is now waiting for the Primary Code of

GREEN

ORANGE the User you want to add a

Secondary Code to.

4. Enter the 4 Digit PIN Code of the

Primary Code: the Mode LED will flash red (If the Primary Code

ORANGE entered is not valid, you will hear a long beep and the EASYBKA/R

RED ORANGE will continue to wait for a valid Primary Code).

5. Enter the 4-digit PIN Code to be used as the Secondary Code., If the Secondary Code is valid the controller will beep three times and return to Normal Mode. (If the Secondary Code is invalid the controller will make a long beep and then the EASYBKA/R will continue to wait for a valid Secondary code to be entered).

18. Deleting Primary & Secondary Codes

There are two methods to delete Primary and Secondary codes, the

Standard Method and the Code Search Method. When deleting a User

Slot, both the Primary Code and the Secondary code are erased.

51

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

18.1 Deleting Primary and Secondary Codes using the

Standard Method

1. Enter Programming Mode.

2. Press "8" to enter Menu 8: the

Mode LED will turn red.

3. Enter the 3-digit User Slot codes you wish to delete: The Mode LED will flash red indicating the controller is waiting for the Programming Code to confirm the deletion. If the User Slot is empty you will hear a long beep

RED

GREEN

ORANGE and the EASYBKA/R will return to

Normal Mode.

RED

ORANGE

4. Enter your Programming Code to confirm the deletion: If the Programming Code is valid, you will hear three beeps and the EASYBKA/R will return to Normal Mode (If the

Programming Code is invalid, you will hear a long beep and the

EASYBKA/R will return to Normal Mode).

18.2

Deleting Primary and Secondary Codes using the Code

Search Method

1. Enter Programming Mode.

2. Press "8" to enter Menu 8: the Mode LED will turn red.

3. Enter the 3-digit User Slot 000: the Door

LED will flash orange.

4. Enter the 4-digit PIN Code of the Primary

Code belonging to the user you want to

GREEN

GREEN ORANGE delete: the Mode LED will flash red (if the

PIN Code is invalid, you will hear a long beep and the Mode LED will not flash). GREEN ORANGE

5. Enter your Programming Code to confirm the deletion: If the Programming Code is valid,

RED ORANGE you will hear three beeps and the

EASYBKA/R will return to Normal Mode (If the Programming Code is invalid, you will hear a long beep and the EASYBKA/R will return to Normal

Mode).

52

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

19. Lock Strike Relay and Auxiliary Relay Code

Assignment using the Standard Method

When a Primary Code is enrolled for any user, that user is assigned rights to activate the Lock Strike Relay when they present a valid code to the controller. The Code Assignment Menu allows you to assign whether the Lock Strike Relay and/or the Auxiliary Relay is activated when a user enters a valid code. There are two methods to Assign

Codes, Standard Method and the Code Search Method.

19.1 Relay Code Assignment using the Standard Method

1. Enter Programming Mode

2. Press "9" to enter Menu 9: the

Mode LED will turn green.

3. Enter the 3-digit User Slot that you want to assign a code to: The

Mode LED will flash green.

4. Enter the assignment digit for the current User Slot:

GREEN

GREEN ORANGE

"1" assigns the Lock Strike

Relay only

"2" assigns the Auxiliary

GREEN ORANGE

Strike Relay only

"3" assigns the Lock Strike and Auxiliary Relay

5. If the assignment code is valid the Mode LED will stop flashing and the EASYBKA/R is now waiting for another slot number.

Press the "#" key to go to the next slot, press the "#" key twice to return to Normal Mode.

53

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

19.2 Relay Code Assignment using the Code Search Method

1. Enter Programming Mode

2. Press "9" to enter Menu 9: The Mode

LED will turn green.

3. Enter the 3-digit User Slot 000: The

Door LED will flash orange.

4. Enter the 4-digit PIN Code of the

Primary Code belonging to the user you want to assign a code to: The

Mode LED will flash green.

5. Enter the assignment digit for the current User Slot:

"1" assigns the Lock Strike Relay only

GREEN

GREEN

ORANGE

GREEN ORANGE

"2" assigns the Auxiliary Strike

Relay only

GREEN ORANGE

"3" assigns the Lock Strike and Auxiliary Relay

6. If the assignment digit is valid, three beeps are heard and the controller returns to Normal mode. If the assignment digit is invalid, a long beep sounds and the controller waits for another assignment digit to be entered.

20. Enabling or Disabling the built-in keypad heater

The EASYBKA/R contains a built-in keypad heater. When is enabled the keypad heater will activate when the ambient temperature drops to approx. 3

C to 5 C and will remain active until the

GREEN keypad temperate rises to approx. 6 C to

9 C.

When the heater is enabled the

EASYBKA/R is lowest operating

GREEN

GREEN temperature is -20 C, otherwise is 0°C;

When the built-in keypad heater is active it will require additional power.

54

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

The factory default setting for the keypad heater is disabled, to changing it:

1. Enter Programming Mode.

2. Press "6" to enter Menu 6: the Mode LED will flash green.

3. Construct the digit code 3 0 0 and the fourth digit as follows:

“0” to DISABLE the heater

“1” to ENABLE the heater

21. Replacing a lost Programming Code

NOTE: The EASYBKA/R must be in Normal Mode otherwise this will not work. Make sure that the Mode LED is green before proceeding

1. Remove power

2. Press the REX button

3. Apply power to the unit with REX button pressed

4. Release the REX button

5. Within 15 seconds :

 enter programming mode by pressing # twice

 insert the default programming code (see table in paragraph 8)

Press 3 to access the programming code modification function

Enter the new programming code.

6. The EASYBKA/R returns to Normal mode: the ‘Door’ LED switches off and the ‘Mode’ LED turns green.

22. Replacing a lost Normal / Secure Code

NOTE: The EASYBKA/R must be in Secure Mode otherwise this will not work. Make sure that the Mode LED is red before proceeding.

1. Remove power

2. Press the REX Button

3. Apply power to the unit with REX button pressed

4. Release the REX Button

55

EASYBKA - EASYBKR ENGLISH ISEASYBK_08_18.pdf.docx

5. You now have 15 seconds to use the default Normal/Secure Code

3838 in order to return to normal mode, where you may enter programming mode and enter a new Normal/ Secure Code

23. Return to Factory Default Settings and selection of code length

Warning:

You must be very careful before using this command! Doing so will erase the entire memory which includes all User and Special

Codes, and return all codes to their factory default settings.

1. Enter Programming Mode

2. Press "0" to enter Menu 0

3. Press the number corresponding to the desired

GREEN length of the code:

0 = 4 digits

5 = 5 digits

6 = 6 digits

8 = free length, from 4 to 8 digits (in this mode, when a

RED code with less than 8 digits is input, it must be confirmed by pressing the # key).

Both the LED will flash red

RED

4. Insert the programming code: If the Programming Code is valid, all memory will be erased, you will hear three beeps and the controller will return to Normal Mode (If the Programming Code is invalid you will hear a long beep and the controller will return to

Normal Mode without erasing the memory of the controller).

Note : if the programming code is misplaced, follow the procedure

.

described in section 21 before restoring factory settings.