ITELCO INDUSTRY VLS-VLH-VLC chiller unit User manual
The VLS-VLH-VLC chiller unit is designed for cooling applications and offers a range of features for efficient and reliable operation. It features a microprocessor-controlled system with advanced features such as proportional and integral control of the return water temperature (RWT) and hysteresis control of the leaving water temperature (LWT). The unit also incorporates closed-loop condensing pressure control, pump-down logic, compressor rotation, oil return function, night mode control, and a variety of alarms and monitoring capabilities.
PDF
Download
Document
Advertisement
Advertisement
Chiller unit VLS-VLH-VLC R 410 A VLS-VLH-VLC CHILLER - 4 COMPRESSORS 1 GENERAL INFORMATION 1.1 INTRODUCTION 2.1 2.1.1 GENERAL INFORMATION The figure shows the terminal with the front door open. It is provided with a LCD 4 lines x 20 columns, keyboard and microprocessor-controlled LED's, so as to allow the programming of the control parameters (setpoint, differential bands, alarm thresholds) and the main operations to be carried out by the user. This document contains the information and the operating instructions for VLS-VLH-VLC 4 compressors & electronic control. This information is for the after-sales service and the production operators, for the end-of-line testing. 1.2 MAIN CHARACTERISTICS – Microprocessor control – User-friendly keyboard – Proportional and integral control of the return water temperature (RWT) – Hysteresis control of the leaving water temperature (LWT) – Access code to enter the Manufacturer's Level – Access code to enter the Assistance Level – Alarm buzzer and LED – Backlighted LCD – Closed-loop condensing pressure control – Pump-Down logic (start-stop) – Rotation of the compressor operation – Oil return function – Night mode (or Low Noise) control – Counting of the pump/compressors' hours of operation – Display of discharge pressure values – History of stored alarms (option) – Programming of different setpoints with 4 ranges of time/setpoint. The following accessories can be also connected: – Real Time Clock Memory Card: alarm history and programming of different setpoints with ranges of time – Serial Communication RS485 Card; to connect the Chiller Control to a BMS network – Remote Display Terminal – Wire Remote Control – Phase monitor kit 2 KEYBOARD & DISPLAY TERMINAL 2.1.2 TERMINAL & KEY BOARD DESCRIPTION The terminal makes it possible to carry out the following operations: – the initial configuration of the machine – the change of all the main operating parameters – the display of the detected alarms and their acoustic signalling by a “buzzer” – the display of all the measured quantities The terminal and the card are connected by a 6-way phone cable. The connection of the terminal to the basic card is not essential for the normal operation of the controller. CONTROL OF VLS-VLH-VLC WITH 4 COMPRESSORS THE CHILLER CONTROL SYSTEM The VLS-VLH machines with 4 scroll compressors are provided with a microprocessor card which is fully programmed by default for the control of a chiller of cold only type with 2 circuits, 2 compressors per circuit, a high-pressure transducer per circuit. The control system consists of: 2 VLS/VLH/VLC 10/06 2.2 Access to the “display mask” of the machine status. DISPLAY Utente Costruttore Manutenzione In/Out Setpoint Versione Fasce orarie Esc key: allows you to move from one mask to another. The display is an LCD 4 lines x 20 columns. The quantities and the information about the operation of the unit are alternated in the form of subsequent screens, named. Alarm key: used to display the alarms, to reset them in manual Press it one to display the mask of the activated alarm, press it again to reset the alarm signal. + + x Home Prg-Esc keys: Pressing these keys at the same time,allows you to turn the unit on/off. + Up-Down keys: allows you to set the control parameters' values and to move from one mask to another (not backlighted). 2.3 Riga0 Riga1 Riga2 Riga3 + KEYBOARD 2.3.1 ARROWS KEY - UP/DOWN/ENTER If the cursor is in the top left-hand corner (Home), press the UP/DOWN keys to access the subsequent masks associated to the selected branch. If a mask includes some value setting fields and you press the ENTER key, the cursor will reach these fields. Once you have reached the quantity setting field, you can modify any value (within the expected limits) by pressing the UP/DOWN keys. After you have selected the desired value, press the ENTER key again to store it. Enter key: used to move the cursor inside the masks and to save the values of the set parameters. Alarm-Enter keys:Press these keys at the same time to enter the "storical alarm“ after 1’ come back at status machine menu’. 3 VLS/VLH/VLC 10/06 2.3.2 ALARMS Code AL00 Alarm unit description Automatic alarm Comp Status on Ventil. Status on Pump Status on Aut/Man Reset Aut Delay Notes 0 AL01 Efficiency alarm CPS Off Off Off Man 30 sec AL02 Flow meter alarm Off Off Off Man Parameter AL03 Sys 1 High pressure “manual reset” Off Sys 1 Run Run Man No AL04 Sys 2 High pressure “manual reset” Off Sys 2 Run Run Man No AL07 Failure of sensor B3 Sys 1 DP1 Run Max Run Auto 10 sec AL08 Failure of sensor B4 Sys 2 DP2 Run Max Run Auto 10 sec AL09 Failure of sensor B5 Tair Run Max Run Auto 10 sec AL10 Failure of sensor B6 T LAN Off Off Run Auto 10 sec AL11 Failure of sensor B7 Tin Off Off Run Auto 10 sec AL.12 Failure of sensor B8 Tout Off Off Run Auto 10 sec AL13 Failure of sensor B1 Tcoil1 Run Run Run Auto 10 sec defrost every 40’ AL14 Failure of sensor B2 Tcoil2 Run Run Run Auto 10 sec defrost every 40’ AL15 Failure of sensor B3 TANDEM 1 Run Max Run Auto 10 sec AL16 Failure of sensor B4 TANDEM 2 Run Max Run Auto 10 sec AL17 Maintenance of compressor 1 Run Run Run Man No AL18 Maintenance of compressor 2 Run Run Run Man No AL19 Maintenance of compressor 3 Run Run Run Man No AL20 Maintenance of compressor 4 Run Run Run Man No AL21 Pump maintenance alarm Off Off Off Man No AL22 Failure of clock card Run Run Run Man No AL23 Thermal switch, compressor 1 Off Comp. 1 Run Run Man No AL23A Thermal switch, compressor 1 Off Comp. 1 Run Run Auto 1 time auto VLS 3 time auto VLH AL24 Thermal switch, compressor 2 Off Comp. 2 Run Run Man No AL24A Thermal switch, compressor 2 Off Comp. 2 Run Run Auto 1 time auto VLS 3 time auto VLH AL25 Thermal switch, compressor 3 Off Comp. 3 Run Run Man No AL25A Thermal switch, compressor 3 Off Comp. 3 Run Run Auto 1 time auto VLS 3 time auto VLH AL26 Thermal switch, compressor 4 Off Comp. 4 Run Run Man No AL26A Thermal switch, compressor 4 Off Comp. 4 Run Run Auto 1 time auto VLS 3 time auto VLH AL27 Sys 1 Low pressure Off Sys 1 Run Run Man Parameter AL27A Sys 1 Low pressure Off Sys 1 Run Run Auto 3 time auto AL28 Sys 2 Low pressure Off Sys 2 Run Run Man Parameter AL28A Sys 2 Low pressure Off Sys 2 Run Run Auto 3 time auto AL29 Thermal switch, fans Off Off Run Man No AL29A Thermal switch, fans A Off Off Run Auto 1 time auto AL30 Sys 1 Antifreeze alarm Off Sys 1 Off Run Man No AL30A Sys 1 Antifreeze alarm Off Sys 1 Off Run Auto 1 time auto AL32 Espansion off line Run Run Run Auto No AL33 Eprom failure Off Off Off Man No 4 VLS/VLH/VLC 10/06 Code Alarm driver description CIRC 1 - EEV 1 Status CIRC 2 - EEV 2 Status Notes AL34 Eprom failure driver 1 Off Run Man AL35 Eprom failure driver 2 Run Off Man AL36 Cable motor EVV driver 1 Off On Man AL37 Cable motor EVV driver 2 On Off Man AL38 Timeout MOP driver 1 0% – Auto AL39 Timeout MOP driver 2 – 0% Auto AL40 Timeout LOP driver 1 100% – Auto AL41 Timeout LOP driver 2 – 100% Auto AL42 Low SH driver 1 Run Run Auto AL43 Low SH driver 2 Run Run Auto AL44 Valve open driver 1 Off Run Auto AL45 Valve open driver 2 Run Off Auto AL46 High SH driver 1 Run Run Auto AL47 High SH driver 2 Run Run Auto AL48 Sensor 1 driver 1 Off Run Auto AL49 Sensor 1 driver 2 Run Off Auto AL50 Sensor 2 driver 1 Off Run Auto AL51 Sensor 2 driver 2 Run Off Auto AL52 Sensor 3 driver 1 Off Run Auto AL53 Sensor 3 driver 2 Run Off Auto AL54 GaAhead driver 1 Run Run Auto AL55 GaAhead driver 2 Run Run Auto AL56 Lan driver 1 disconnected Off Run Auto AL57 Lan driver 2 disconnected Run Off Auto AL58 Auto set up driver 1 Off Run Auto AL59 Auto set up driver 2 Run Off Auto 2.3.3 Advanced alarm history file DISPLAY LOG DATA Which memory? This is a special function that can be enabled by using a memory expansion board and from a list of variables that has been loaded together with the software. This function will enable the user to record and display some readouts of pre-established parameters at regular intervals or to download the file on a Pc and to display the history file in the Excel format. To display the advanced history file, press the Alarm and Enter keys at the same time until the mask of the advanced history file appears. EXPANSION MEMORY Here below select the Log file you wish to display since you can have more than one Log file on the same expansion memory. DISPLAY LOG DAT Which Log? Log01. >SYSTEM INFORMATION LOG DATA OTHER INFORMATION – After having selected the Log file you wish, the following mask will require you to select the record you wish to display. The latest record will be displayed by default, but you can select an earlier record by using the arrow keys and by pressing the Enter key to confirm. Select the Log Data item and press Enter to confirm. The following mask will require you to select the type of memory you wish to access, i.e. the internal one or the additional one. The additional memory is selected by default. Then press Enter. 3 06-06-06 UP : DOWN : ENTER : 15:50:16 next record prev. record view data 5 VLS/VLH/VLC 10/06 2.3.4 MAINTENANCE LEVEL Press the “Prg” key to access the Maintenance” masks: Parameter Type Min. Value Max. Value Default T in °C -3 3 0 T out °C -3 3 0 T P Lan °C -3 3 0 T coil 1 °C -3 3 0 T coil 2 °C -3 3 0 DP 1 bar -3 3 0 DP 2 bar -3 3 0 T.tandem Sys 1 °C -3 3 0 T.tandem Sys 2 °C -3 3 0 N (Hours (010x1000) 0 100 10 Pump flag N=NO Y=YES N Compressors flag N=NO Y=YES N EEV Modality flag AUTO MAN AUTO Step flag 0 2625 EEV position flag 0 2625 EEV Modality flag AUTO MAN Step flag 0 2625 EEV position flag 0 2625 S1 bar -3 3 0 S3 °C -3 3 0 S1 bar -3 3 0 S3 °C -3 3 0 AL 000 Setpoint RWT N° 0000 h 00:00 00/00/00 00,0 °C 00,0 °C SYS 1 – comp. 1. 000000 h SYS 1 – comp. 2. 000000 h SYS 2 – comp. 1. 000000 h SYS 2 – comp. 2. 000000 h Pump 000000 h Insert the password 0000 Offset probe Maintenance Alarm threshold Reset hours Disabile compressors Driver 1 Manual manAge Driver 2 Manual manAge AUTO Driver 1 status Nessuna anomalia Driver 2 status Nessuna anomalia Offset probe driver 1 Offset probe driver 2 6 VLS/VLH/VLC 10/06 2.3.5 PRINTING KEY (NO AVAILABLE) 2.3.6 I/O (INPUT/OUTPUT) Acronym Description Tin Entering water temperature Tout Leaving water temperature TPLAN Water temperature plant (Option) Tair External air temperature Tcoil #1 Sensor coil SYS 1 (only HP) Tcoil #2 Sensor coil SYS 2 (only HP) DP minore (see note) DP #1 Sys 1: discharge pressure transducer DP #2 Sys 2: discharge pressure transducer INVERTER FAN % % FAN SPEED TEMPERATURE TANDEM SYS #1 Discharge temp tandem sys1 TEMPERATURE TANDEM SYS #2 Discharge temp tandem sys2 DIGITAL INPUT Input del pCO1 DIGITAL INPUT EXPANSION Input expansion DIGITAL OUPUT ANALOG OUTPUT FAN INVERTER 0-10V to the FSC Threshold alarm high SH Driver 1 Cool EEV Valve position Power required EEV circuit 1 Status Driver 2 Cool EEV Valve position Power required EEV circuit 2 Status Driver 1 SH Evap.temp Suction temp. Circuit 1 SH value Driver 2 SH Evap.temp Suction temp. Circuit 2 SH value Driver 1 Evap.pressure Evap.temp Suction temp. Drive value circuit 1 Driver 2 Evap.pressure Evap.temp Suction temp. Drive value circuit 2 Ver. Driver 1 SOFT WARE VERSION EEV 1 Ver. Driver 2 SOFT WARE VERSION EEV 2 (Note) DP roule IF Tair < 0 °C the fan speed % depend by the minimum value between DP1- DP2 IF Tair > 0 °C the fan speed % depend by the maximum value between DP1- DP2 7 VLS/VLH/VLC 10/06 2.3.7 ANALOG/DIGITAL DESCRIPTION Analog input pCO1 Digital input pCO1 n° Description n° Description B1 Low pressure transducer #1 ID1 Remote On/Off B2 Low pressure transducer #2 ID2 Cool/Heat B3 High pressure transducer #1 ID3 Fan thermal B4 High pressure transducer #2 ID4 Compressor thermal #1 B5 Air temperature ID5 Compressor thermal #2 B6 T pLAN ID6 Compressor thermal #3 B7 Water inlet temperature ID7 Compressor thermal #4 B8 Outlet water temperature ID8 Flow switch ID9 Step 1 ID10 Step 2 Description ID11 Step 3 NO1 Compressor #1 circuit #1 ID12 Step 4 NO2 Compressor #2 circuit #1 ID13H High pressure switch # 1 (230V) NO3 Solenoid liquid valve circuit #1 ID14H High pressure switch # 2 (230V) NO4 Compressor #1 circuit #2 NO5 Compressor #2 circuit #2 NO6 Solenoid liquid valve circuit #2 n° Description NO7 Antifreezing heater Y1 Inverter fan NO8 Reversing valve Y2 NO9 Fan step 1 Y3 NO10 Fan step 2 Y4 NO11 Pump NO12 Alarm circuit # 1 NO13 Alarm circuit # 2 Digital output pCO1 n° Analog output pCO1 Analog input t LAN pCOE Digital input PCOE t LAN B1 Defrost temperature #1 ID1 High temperature tandem. 1 B2 Defrost temperature #2 ID2 High temperature tandem. 2 B3 Tandem 1 discharge temperature (150 °C) ID3 Second Set – Point selection B4 Tandem 2 discharge temperature (150 °C) ID4 8 VLS/VLH/VLC 10/06 2.3.8 USER LEVEL - SETPOINT Press the PRG key to enter the Setpoint level, which can are listed below, together with the limit values and the User parameters be accessed by the user. The parameters that can be set default values (standard factory set-up). Control mode Min. Value Max. Value Default Sys #1 – OFF ON OFF Sys #2 – OFF ON OFF Unit managment Cooling Heating Cooling Setpoint Return mCS+2 20 Outlet mCS 20 8 Heating Setpoint Return 20 MHS-5 40 Outlet 20 MHS 40 Glycole Setpoint Return –15 20 10 Outlet –15 20 8 Proportional Band Return 1 10 5 Neutral Band Outlet Language selection 1 — ITA Where mCS = min. cold limit for the setpoint (see At this level you can select the language of opera-tion Service level) (English or Italian). French, German and Spanish are Where MHS = max. heat limit for the setpoint (see available with other eproms. Service level) ENG 10 6 GER SPA 2 FRA ITA When the machine is turned on, every single circuit is activated through the SYSTEM # ON/OFF parameters (SET key). 2.3.9 SERVICE LEVEL Press the “Prg” key (correct password 1234) to access the Service Level: Parameters Type Min. Value Max. Value Default Min. time stop compressor Sec 10 600 90 Min.running time compressor Sec 10 180 90 Time betw. On same compr. Sec 10 999 450 Loading time Between comp. Sec 10 999 20 LWT Unloading time compressor Sec 10 999 20 ChillerNet Flag N=NO Y=YES N Water temperature control mode Flag RWT - P RWT P+I LWT RWT P RWT P+I Sec 0 999 600 LWT Stop Comp Cooling °C -20 +20 4,5 Heating °C +20 +60 55 Heat set. comp. Flag N=NO Y=YES N Set point °C -999,9 999,9 5.0 Diff. °C -999,9 999,9 10.0 Max. °C -999,9 999,9 5.0 9 VLS/VLH/VLC 10/06 Parameters Cool set.comp. Type Min. Value Max. Value Default Flag N=NO Y=YES N Set point °C -999,9 999,9 24.0 Diff. °C -999,9 999,9 10.0 °C -999,9 999,9 2.0 Auto restart Max. Flag N=NO Y=YES N Glycole Flag N=NO Y=YES N Enable rotation Flag N=NO Y=YES YES Clock 32 Kbyte Flag N=NO Y=YES N Pump management Remote logic Stand-by Delay stop Flag N=NO Y=YES N hour 1 24 12h Sec 0 60 20 Flowswitch/Interbloc delay time alarm running Sec 0 99 1 Start-up Sec 0 99 10 Sec 0 99 40 Sec 0 10 2 Limit °C -15 10 4 Diff. °C 0 99 2 Setpoint °C -15 10 5 Diff. Low pressure Delay time Fan termal relè alarm Delay time Antifreeze Antifreeze heater °C 0 99 2 Condensation type control (note 2) Flag STEP FSC STD: STEP LAK: FSC Delay start fans Sec -10 10 0 °C -20 0 -10 Setpoint (with odd fans) °C -20 0 -20 Diff. °C 0 99 45 HP1 bar 16 28 34 LP1 bar 10 16 21 DPSET (only if FSC) bar 10 24 28 LS (low speed) only if STEP Setpoint (with peer fans) LS (low speed) only if STEP MINDP (only if FSC) bar 1 25 18 MIN Speed (only if FSC) Vdc 0 10 0 MAX Speed (only if FSC) Vdc 0 10 10 Condensation MDP bar 18 28 37 High bar 18 28 40 Fan step heating with odd fans Low °C 0 99 15 with peer fans Low °C 0 99 20 High °C 0 99 30 10 VLS/VLH/VLC 10/06 Parameters Type Min. Value Max. Value Default Start bar -20 20 5,5 Stop °C -20 20 10 Defrost mangement Start time Min 0 99 40 Max time Min 1 10 5 Off tandem Sec N=NO Y=YES N Enable Flag N=NO Y=YES Y-VLS N-VLH Max time Sec 5 90 10 Pump down Min.cooling setpoint (mCS) °C 5 12 6 Max. heating setpoint (MHS) °C 30 55 45 Efficiency value bar 0.0 3.0 0 Serial Card Flag N=NO Y=YES N On/off remote enabled Flag N=NO Y=YES N Cool/heat remote enabled Flag N=NO Y=YES N Night mode Flag N=NO Y=YES N DPOFFSET bar 0 8 2 Cool mode TMAX °C -20 50 30 DELTA-V Volt 0.0 5.0 5 T MIN °C -20 30 -2 DELTA V Volt 0 5 5 Set point °C - 20 °C 99,9 - 20°C Diff. °C 0 99,9 0,5 Min.T air °C - 20 °C 99,9 00.0 0 1 0,5 0 1 0,4 Heat mode Min.twin air temp. Set point Low pressure alarme managment Eph LOL Press key ENTER for reset history Press the ENTER key to erase the alarm history memory Press the key ENTER for default values Press the ENTER key to go back default value Warning: Carry out this operation whenever the eprom is changed Insert the new service password 1234 Note 2: Set this parameter to FSC only if the speed controller is available, otherwise set it to STEP. 11 VLS/VLH/VLC 10/06 2.3.10 MANUFACTURER LEVEL Press the “Prg” key (correct password 4939) to access the Manufacturer Level: The parameters are available only in Italian. User parameters Type Min. Value Max. Value Default Enter password Manifactured Exact password 0000 0 9999 4939 Unit Flag VLS: Chiller VLH: Heat pump VLC: Condensing unit Chiller Heat pump Condensing unit Number of compressor per circuit LWT sensor Log N° 1 2 2 Driver number N° 1 2 2 Flag N=NO Y=YES Expansion enable Y=YES Enable sensor B1:N B2:N B3:Y B4:Y B5:Y B6:N B7:Y B8:Y Expansion Enable sensor B1:Y B2:Y B3:N B4:N Sensor air NTC-pt 1000-PTC NTC Sensor water in NTC-pt 1000-PTC NTC Sensor water out NTC-pt 1000-PTC NTC Sensor defrost 1-2 NTC-pt 1000-PTC NTC Analog inputs Range 0-5 V High pressure DP Start 0 Bar End 45 Bar Liquid solenoid valve Flag N=NO Y=YES N Cycle rev. valve Flag NA NC NA LP 1 alarm N° 0 99 3 LP 2 alarm N° 0 99 3 Term.comp 1 N° 0 99 1 VLS-VLC 3 VLH Term.comp 2 N° 0 99 1 VLS-VLC 3 VLH Term.comp 3 N° 0 99 1 VLS-VLC 3 VLH Term.comp 4 N° 0 99 1 VLS-VLC 3 VLH Term.fan N° 0 99 1 Antifreezing N° 0 99 0 T air range Transduce type °C 0 diff 0 Hour autoreset numbers Klixon reset tandem discharge time SYS 1 min 0 99 3‘ SYS 2 min 0 99 3‘ threshold °C 0 99 25 diff °C 0 99 1 Gas Type R410c Only Cooling version Max TIN Push the ENTER key to the driver configuration Push the ENTER key to initialize the unit Warning Carry out this operation whenever download new software Set the new manufacturer’s password……. 0000 12 VLS/VLH/VLC 10/06 DRIVER CONFIGURATION EXPANSION VALVE Configuration type Type Type EVD Min. Value EVD 400 PLAN Sensor type EVD Type valve 2625 step Max. Value Default EVD 400 TLAN 400 TLAN Sheat NTC – P (RAZ) NTC>S3 P (RAZ) >S1 PT 1000-P NTC-NTC Sheat NTC –P (RAZ) ALCO EX 5 ALCO EX 6 VLS 504 TO 704 ALCO EX 7 Danfoss ETS 25 AST-g ALCO EX8 SPORLAN 0.5-20 TONS SPORLAN 25-30 TONS SPORLAN 50-250 TONS CAREL EV2 **P VLS 804 TO 1204 CAREL EV2 **A Danfoss ETS 50 AST-g DANFOSS ETS 25 AST-g DANFOSS ETS 50 AST-g DANFOSS ETS 100 AST-g Refrigerant R 22 R 744 R 717 R 600 R 290 R 507c R 410 a R 407 c R 404 a R 134 a R 410 a Conf. valve Step min 0 8100 0 Step max 0 8100 0 Step closure 0 8100 0 Extra open Y Y N Extra closing Y Y N Conf. valve Conf. valve Amp mov. mA 0 1000 0 Amp stop mA 0 1000 0 Frequence HZ 32 501 32 Duty cycle % 0 100 0 0 2625 0 % 0 100 0 Min Bar -9,9 99,9 0 Max Bar 0 99,9 15 Low SH sec 0 3600 0 High SH min 0 500 0 LOP sec 0 3600 0 MOP sec 0 3600 0 Sensor sec 0 999 10 Conf. valve Step in stand by EEV EEV position Limit sensor S1 Delay alarms 13 VLS/VLH/VLC 10/06 DRIVER CONFIGURATION EXPANSION VALVE Configuration type Type Min. Value Max. Value Default CH-Proportional °C 2 50 10 ETS 25 25 ETS 50 CH Integral time sec 0 999 30 ETS 25 60 ETS 50 CH SH set °C CH Low SH °C -4 21 2 HP % open EEV % 0 100 60% HP-Proportional °C 0 99,9 20 ETS 25 10 ETS 50 HP integral time sec 0 999 70 ETS 25 90 ETS 50 HP - set SH °C 2 50 5,5 HP low SH °C -4 21 4,5 DF % open EEV % 0 100 60% 0 99,9 20 0 999 60 5 DF-Proportional DF integral time sec DF - set SH °C 2 50 5 DF - low SH °C -4 21 3 SH dead band °C 0 9,9 0,3 Derivation time sec 0 99,9 20 Low SH integral time sec 0 30 1 LOP integral time sec 0 25,5 0 MOP integral time sec 0 25,5 10 LOP integral time sec 0 500 60 Y N Y Proportional dynamic control Blockage control EEV sec 0 999 0 High condensation temperature alarm °C 0 99,9 0 Integration time temperature condensation sec 0 25,5 0 Start Open percentage % 0 100 60% Unit compressor Capacity Scroll Screw Scroll N0/steeps NO/STEEPS Evaporator type Cooling exchanger/pipes Heat pump exchanger/pipes Minimum saturation temperature Cooling °C -50 90 -10 Heating °C -50 90 -25 Defrost °C -50 90 -25 °C -50 90 15 Maximum saturation temperature Cooling Heating °C -50 90 15 Defrost °C -50 90 10 Threshold alarm high SH °C 0 100 30 14 VLS/VLH/VLC 10/06 3 CONDENSING VERSION Procedure after Pico1 change 1. Check if address board is already fitted on pCO board, if not add it (look at “clock” labelled socket on pCO) and set only dip1 to ON. 2. Check if terminal display is addressed with (dip1,2,3,4 = ON). 3. Replace the eprom with a new one. 4. Power on the control pressing in the same time both arrow keys and enter until. 1. Disables the Tin and Tout B7 and B8 water probes 2. Access the manufacturer menu 4939, in the following mask set up the type of unit: Chiller Heatpump CONDENSING Chiller Unit .................... Number compressors per circuit ....................2 Number driver 2 Display address Setting......................: 32 I/O Board address:-- Use ARROWS and to set the address at 00. Display address Setting......................: 00 I/O Board address:-- CONDENSING Unit ....... Number compressors per circuit ....................2 Number driver 2 Power off the machine. Press the keys Alarm and arrow up at the same time and hold them down. Power on the machine. Hold the keys down until the pCO1 addressing mask appears. Set the address to a value from 1 to 8. pLAN address: 1 UP: increase DOWN: decrease ENTER: save & exit 4 Power off the machine. Repeat the procedure intended to address the terminal by assigning 32 as an address. Press Enter. Type the pCO1 address you have just set and press Enter. COPY FROM A PROGRAMMING KEY TO PCO1 Terminal config The programming key will enable the operator to copy an application programme from a pCO1 or to a pCO1, with all the values setup at the time of copying. To copy an application programme from or to a key. – Disconnect the machine – Connect the pCO1 key with the board by means of a jack – Supply the machine and wait for the arrow symbols to stop blinking – Press the MODE key on the key to decide whether the application programme must be copied on the pCO1 board (arrow up on) or on the key (arrow down on) and press the START key – Wait for the process to come to an end, which will be signalled by a 2-second intermittent sound. Press ENTER to continue In the following mask, please confirm address 32 once again and define it as PR. In the other fields set NONE and press ENTER until you are required to save the setup. Select YES and press Enter. Check the addresses and press ENTER: P:01 Trm1 Trm2 Trm3 ADR 32 None None Priv/Shared Pr --- Ok? Yes 15 VLS/VLH/VLC 10/06 5 COMPRESSORS LEAVING LIQUID CONTROL (COOLING MODE) If Leaving Control mode is selected, the leaving mixed water temperature LWT will be controlled between the setpoint and the setpoint + Neutral Band. The SetPoint High Limit is the Setpoint plus the Neutral Band. The SetPoint Low Limit is the Setpoint. If the mixed leaving water temperature LWT is above the SetPoint High Limit, the compressors will be energized one by one separated by the Time between Start and Start different compressors. 6 If the LWT falls below the SetPoint High Limit and greater than the SetPoint Low Limit, temp is in the Neutral Band. No actions is occurring. No load and no unloading. If the LWT falls below the SetPoint one compressor is switched off. Until the LWT is below the Setpoint, compressors are unloaded according to the Unload time parameter value. COMPRESSORS LEAVING LIQUID CONTROL (HEATING MODE) If Leaving Control mode is selected, the leaving mixed water temperature LWT will be controlled between the setpoint and the setpoint - Neutral Band. The SetPoint High Limit is the Setpoint. The SetPoint Low Limit is the Setpoint – Neutral Band. If the mixed leaving water temperature LWT is below the SetPoint Low Limit, the compressors will be energized one by one separated by the Time between Start and Start different compressors. If the LWT is between the SetPoint Low Limit and the SetPoint High Limit, temp is in the Neutral Band. No actions is occurring. No load and no unloading. If the LWT is above the SetPoint High Limit one compressor is switched off. Until the LWT is above the Setpoint High Limit, compressors are unloaded according to the Unload time parameter value. 16 VLS/VLH/VLC 10/06 7 COMPRESSORS RETURN LIQUID CONTROL (COOLING MODE) If Return Control Mode is selected, the return water temperature RWT is controlled between the Setpoint and the Setpoint + Proportional Band. We call this zone: the Loading Zone. All stages, 2 or 4 compressors, are placed in the proportional band, dividing it in the number of the compressors. If the RWT is above the Sepoint, control starts to load each stages. The higher is the RWT, the more compressors will be loaded, according to the compressor activity logic, timer and rules described. Example: regulation diagram for machines with max. 4 compressors: All the unit compressors will be proportionally positioned in the band called Loading Zone. 8 COMPRESSORS RETURN LIQUID CONTROL (HEATING MODE) The compressors are loaded in the same proportional way used in Return Control in Cooling. The difference is that the loading zone is between Set Point – Proportional Band and Set Point. 17 VLS/VLH/VLC 10/06 9 CONDENSER FAN CONTROL (IN COOLING MODE WITH FAN SPEED CONTROL) Parameter used: Minimum Fan Speed, Max Fan Speed, Discharge Pressure Set (DPSET), Max Discharge Pressure, MINDP, Condensation type Control (STEP or FSC). Control uses one digital output to power on one fans relay and an analogue output 0-10Vdc to drive a Fan Speed Controller (FSC). The fans try to maintain a constant condenser pressure equal to the programmed set point by varying fan speed. As soon as the first compressor starts, the fan relay will turn on, and it will stay on until the all compressors turn off. For the first 10 seconds the fans will begin at an output level proportional to the ambient temperature. The hotter it is out, the faster the fans will start. Below is a chart showing the correlation. Table 1 – Startup Fan Values ning at lower capacity as long as neither pressure exceeds the maximum discharge pressure. Once on, the fan speed is recalculated every second according to the below basic rules: There is one high pressure transducer each system. If only one compressor is running, the fans control to its discharge pressure. If two compressors are running, the fans control the pressure of the 1st system started, or the one which is running at 100% capacity if the other one is run- If DPSET-1 < DP < DPSET+1 then no change in AO If (DPSET+1 < DP < DPSET+2) AND (DP IS NOT DECREASING) then AO = AO + 1% If (DP > DPSET + 2) AND (DP IS NOT DECREASING) then AO = AO + 5% If (DPSET-2 < DP < DPSET-1) AND (DP IS NOT INCREASING) then AO = AO -1% If (DPSET-2 < DP < 10.5) AND (DP IS NOT INCREASING) then AO = AO -2% If (DP < MINDP) then AO = AO - 2% To check if DP is increasing or decreasing, value DDP = ± 0.2 bar/sec is used. 18 VLS/VLH/VLC 10/06 10 CONDENSER FAN CONTROL (COOLING MODE) IN STEP The fan step control is managed by the parameters LP1-HP1-LS-Diff The fans start under sensor air (B4) control OAT During the fans running : If DP>HP1 one step is load independent by OAT value If DP<LP1 unloaded the step DP is the leader between the two transducers LS DIFF HP1 LP1 - Default Default Default Default = = = = Peer fans -10°C Odd fans -20°C Peer/Odd 45°C 21 bar (R410C) 14 bar (R134A) 13 bar (R410C) 7 bar (R134A) 19 VLS/VLH/VLC 10/06 11 CONSENSER FAN CONTROL IN HEATING MODE WITH FSC Two parameters used: Low Air Temp Heating and High Air Temp Heating. If the Tair probe is installed, fan control in heat pump mode is always based on ambient temperature and not pressure. At unit startup, the fans will run for 3 seconds at max speed before the compressor starts. After startup, the fans will run according to the following rule: If Tair < Low Air Temp Heating then AO = Max Fan Speed If Low Air Temp Cooling < Tair < High Air Temp Cooling then AO from Max to Min with linear progression If Tair > High Air Temp Heating then AO = Min Fan Speed If Air Temp Probe (B4) isn’t installed, the Analogue Output is forced to the 10 Vdc value. The Fan relay is energized whenever at least one compressor is running. If High pressure transducer are installed, during the defrost cycle, the fans will turn on at 20 Bar and run at 50%. AO = 5 Vdc. The fans will stay on until the higher discharge pressure drops to 15 Bar, and then they will turn off. 20 VLS/VLH/VLC 10/06 12 CONDENSER FAN CONTROL (HEATING MODE) IN STEP LOW – Default = Odd fans 15°C Peer fans 20°C HIGH – Default = Peer/Odd fans 30°C 21 VLS/VLH/VLC 10/06 13 NIGHT MANAGEMENT (OR LOW NOISE OPTION) The parameter is defined at the Service level: “Night Mode”. If set to SI, the DPSET is modified as follows: DPSET night = DPSET+DPOFFSET from PM hours to AM hours Where: DPOFFSET = parameter in bars at Service Level. It is the correction of the pressure target of the condensation control with speed controller. PM and AM = parameters that can be set with a mask with the CLOCK key, if enabled: PM = night mode start AM = night mode end MAX FAN SPEED IN COOLING IN NIGHT MODE: MaxFanSpeed is no longer a fixed parameter, but is a function of B4, air temperature The analogue output value AO, is always between the Min Fan Speed and the Max Fan Speed. Whenever one of the two high pressure measures by the transducer rea- 14 ches the MDP Value, soon the fan must run at max speed, until that high pressure value falls again to the 90% of the Max High Pressure Value. COMPRESSORS CAPACITY CONTROL Parameters used: Disch Pressure Limit, (HI) Max Disch Pressure. (MDP) If high pressure transducer are installed and if the unit is a 4 compressors unit, the compressors capacity control is active. If, at any time while the system is full loaded (2 comps running), the high pressure value reaches the setted Disch Pressure Limit default value 26 bar, the last system compressor loaded is soon unloaded. Second compressor of the system will be allowed to run only when System High Pressure value falls below the Max Discharge Pressure default value 24 bar. 22 VLS/VLH/VLC 10/06 15 OIL RECOVERY FUNCTION If one of the tandem (System1-2) running at 50% (only one compressor running) more than 40’ the control will force the tandem at 100% for 5 minuts. If the air inlet temperature is < of the minimum tandem temperature In COOLING mode the two circuit run with all the compressors for 30’, after one compressor for circuit will be stop for 3’, passed 3’ the two compressors will be restart In HEATING mode the two circuit run with all the compressors for 30’, after one compressor for circuit will be stop for 3’, passed 3’ the two compressors will be restart If the air inlet temperature is > of the minimum tandem temperature In COOLING/HEATING the two circuit with all the compressors uninterruptedly 16 PUMP CONTROL Parameters used in Pump management mask: Remote logic, Stand-by, Delay Stop. Pump always starts 30 seconds before the first compressor is loaded and stops always a parameter Pump Delay Time value in seconds after the unit is stopped locally or by remote start/stop digital input. 17 If the parameter “Pump Remote Logic” is in YES, if the unit is stopped by the remote Start/Stop digital input, the pump continues to run. It only stops if the unit is locally stopped by panel. PUMP-DOWN LOGIC – LIQUID LINE EEV CONTROL Pump Down during start-up of the first compressor of each system and during stop of the last compressor of each system. Parameters used: Pump-Down Max Time, Pump-Down Enable, Liquid Line Solenoid Valve Enable. All the following logic is valid only if Liquid Line Valve are selected as present in Factory Level, and if Pump-Down is enable in Service Level. 23 VLS/VLH/VLC 10/06 18 DEFROST CYCLE (HEAT PUMPS ONLY) Defrosting of a circuit with time/temperature control: Parameters used: Defrost start Evap press; Defrost stop temp, defrost Delay time, defrost Max time, Reversing Off Time. Moreover cycle reversion during normal operation (changing from summer to winter mode or back) always follow compressors switch off. If one of the two Evap press sensor values fall below the Defrost start Evap press, a timer starts. The timer is increased while the EP value is under the Defrost start value. When the timer (t1 + t2 + t3 + …) reaches the defrost start time value, the defrost cycle starts for both system. During defrost cycle, fans are stopped, all compressors run (if one or more are in off, they must be powered), reverse valve is powered. During defrost Tcoil increases. There are two coils temp sensor, one each coil. When one of the coil reaches a setted limit then this tandem is part loaded to 50% but unit is still in defrost. When also second coil temp reaches the limit, then defrost cycle ends. During defrost cycle, if the discharge pressure in one of the two systems, reaches an high dangerous value, fans must run at max speed. So, if discharge pressure transducer are attached, if one of the two high pressure values reaches the Max Discharge Pressure value (see MDP) the fans contactor is energized and the analogue output is forced to 5Vdc. Defrost cycle stops when both the Tcoil values rises up to the Defrost Stop Temp value, anyway if the Defrost Max Time has elapsed. When defrost cycle is ended, the reverse valve is unpowered and fans are powered again, according to fans rule logic. The following table details possible unit faults, their probable cause and suggested remedies, for any other problems not immediately recognisable and/or technical assistance, call an authorised Technical Service Center. 24 VLS/VLH/VLC 10/06 19 VLS-VLH-VLC TROUBLE SHOOTING The following table details possible unit faults, their probable cause and suggested remedies, for any other problems not immediately recognisable and/or technical assistance, call an authorised Technical Service Center. Faulty Probable cause Remedy AL01 Efficiency alarm CPS Gas circuit empty Wrong compressors rotation To charge the circuit To check the electrical connection AL30 Antifreezing MANUAL RESET Low water flow Wrong pump Water filter dirty Dirty exchanger High circuit pressure drop To To To To To check the pump check the pump size clean the filter clean the exchanger check the plant pressure drop AL30a Antifreezing Only with “AUTO RESET” Low water flow Wrong pump Water filter dirty Dirty exchanger High circuit pressure drop To To To To To check the pump check the pump size clean the filter clean the exchanger check the plant pressure drop AL02 Flow meter Water pump stop Water pump blocked Pump thermal contact open Flow switch blocked To check the pump To release the pump To reset the thermal contact and to check the scale To release the flow switch AL27 Sys 1 Low pressure MANUAL RESET Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To To To To To To replace the espansion valve charge the circuit find and repair the leak check the plant thermal load check the electrical connection check Pump Down setting AL27a Sys 1 Low pressure Only with “AUTO RESET” Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open To To To To To replace the espansion valve charge the circuit find and repair the leak check the plant thermal load check the electrical connection AL28 Sys 2 Low pressure MANUAL RESET Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To To To To To To replace the espansion valve charge the circuit find and repair the leak check the plant thermal load check the electrical connection check Pump Down setting AL28a Sys 2 Low pressure Only with “AUTO RESET” Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To To To To To To replace the espansion valve charge the circuit find and repair the leak check the plant thermal load check the electrical connection check Pump Down setting AL02 Sys 1 High pressure MANUAL RESET COOL Fan stop Low ventilation Fan thermal contact open High gas charge Coil dirty Coil obstruct Faulty high pressure transducer To To To To To To To check the fan check the fan speed reset the contact check the gas charge clean the coil check the installation position replace the transducer HEAT Low water flow Wrong pump Dirty filter Dirty exchanger High circuit pressure drop To To To To To check the pump check the pump size clean the filter clean the exchanger check the plant pressure drop 25 VLS/VLH/VLC 10/06 Faulty Probable cause Remedy AL03 Sys 2 High pressure MANUAL RESET COOL Fan stop Low ventilation Fan thermal contact open High gas charge Coil dirty Coil obstruct Faulty high pressure transducer To To To To To To To check the fan check the fan speed reset the contact check the gas charge clean the coil check the installation position replace the transducer HEAT Low water flow Wrong pump Dirty filter Dirty exchanger High circuit pressure drop To To To To To check the pump check the pump size clean the filter clean the exchanger check the plant pressure drop AL23 Thermal switch compressor 1 MANUAL RESET Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL23a Thermal switch compressor 1 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL24 Thermal switch compressor 2 MANUAL RESET Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL24a Thermal switch compressor 2 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL25 Thermal switch compressor 3 MANUAL RESET Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL25a Thermal switch compressor 3 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL26 Thermal switch compressor 4 MANUAL RESET Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL26a Thermal switch compressor 4 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL29 Thermal switch fans MANUAL RESET Fan stop Fan thermal contact open To check the motor To reset the thermal contact and to check the scale To release the fan To check the electrical connection, to tighten the terminal block screws Fan blocked Wrong electrical cable connection & phase missing 26 VLS/VLH/VLC 10/06 Faulty Probable cause Remedy AL29a Thermal switch fans Only with “AUTO RESET” Fan stop Fan thermal contact open Fan blocked Wrong electrical cable connection & phase missing To check the motor To reset the thermal contact and to check the scale To release the fan To check the electrical connection, to tighten the terminal block screws AL11 Failure sensor B7 Entering water temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL12 Failure sensor B8 Outlet water temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL10 Failure sensor B6 temperature LAN Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL09 Failure sensor B5 Outdoor air temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL13 Failure sensor B1 Coil 1 temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL14 Failure sensor B2 Coil 2 temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To To To To replace the sensor replace cable check the electrical connection check the insulation AL07 Failure sensor B3 Transducer High pressure Circuit 1 High pressure transducer damaged Cut cable Water inside the transducer Connector loose To To To To replace the transducer check the cable check the insulation tighten the connector screws AL08 Failure sensor B4 Transducer High pressure Circuit 2 High pressure transducer damaged Cut cable Water inside the transducer Connector loose To To To To replace the transducer check the cable check the insulation tighten the connector screws AL17 Compressor 1 Maintenance Exceeded hours of operation compressor 1 To do maintenance AL18 Compressor 2 Maintenance Exceeded hours of operation compressor 2 To do maintenance AL19 Compressor 3 Maintenance Exceeded hours of operation compressor 3 To do maintenance AL20 Compressor 4 Maintenance Exceeded hours of operation compressor 4 To do maintenance AL21 Pump Maintenance Exceeded hours of operation pump To do maintenance Espansion faulty To replace the clock To insert the clock card in the support Eprom faulty To replace the program AL32 Espansion off line AL33 Eprom failure 27 VLS/VLH/VLC 10/06 20 LIST OF ITELCO-INDUSTRY APPLICATION SUPERVISOR VARIABLES FOR PCO1 APPLICATION CHILLER: VLS – VLH – VLC Index Meaning Read/Write Type Read Digital 1 Heating operation 2 Cooling operation Read Digital 3 Compressor #1 sys #1 Read Digital 4 Compressor #2 sys #1 Read Digital 5 Solenoide valve sys #1 Read Digital 6 Compressor #1 sys #2 Read Digital 7 Compressor #2 sys #2 Read Digital 8 Solenoide valve sys #2 Read Digital 9 Fan Read Digital 10 Heater Read Digital 11 4 - way valve Read Digital 12 Alarm sys #1 Read Digital 13 Alarm sys #2 Read Digital 14 Pump Read Digital 15 RWT/LWT Control temperature Read/Write Digital 16 Automatic restart Read/Write Digital 17 Glicole enable Read/Write Digital 18 Compressors rotation enable Read/Write Digital 19 Remote enable pump Read/Write Digital 20 Pump down enable Read/Write Digital 21 Daily zone enable Read/Write Digital 22 Sys #1disable Read/Write Digital 23 Sys #2 disable Read/Write Digital 24 Chiller/heatpump enable Read/Write Digital 25 Sensor B1 enable Read/Write Digital 26 Sensor B2 enable Read Digital 27 Sensor B3 enable Read Digital 28 Sensor B4 enable Read Digital 29 Sensor B5 enable Read Digital 30 Sensor B6 enable Read Digital 31 Sensor B7 enable Read/Write Digital 32 Sensor B8 enable Read/Write Digital 33 Unit on Read Digital 34 On/Off by supervisor Read/Write Digital 35 Compressor #1 disable Read/Write Digital 36 Compressor #2 disable Read/Write Digital 37 Compressor #3 disable Read/Write Digital 38 Compressor #4 disable Read/Write Digital 39 Alarm eff Read Digital 40 Antifreezing circuit #1 Read Digital 41 Antifreezing circuit #2 Read Digital 42 Low pressure circuit #1 Read Digital 43 Low pressure circuit #2 Read Digital 28 VLS/VLH/VLC 10/06 Index Meaning Read/Write Type 44 High pressure circuit #1 Read Digital 45 High pressure circuit #2 Read Digital 46 Thermal compressor #1 Read Digital 47 Thermal compressor #2 Read Digital 48 Thermal compressor #3 Read Digital 49 Thermal compressor #4 Read Digital 50 Fan thermal Read Digital 51 Faulty probe B1 Read Digital 52 Faulty probe B2 Read Digital 53 Faulty probe B3 Read Digital 54 Faulty probe B4 Read Digital 55 Faulty probe B5 Read Digital 56 Faulty probe B6 Read Digital 57 Faulty probe B7 Read Digital 58 Faulty probe B8 Read Digital 59 Compressor Maintenance #1 Read Digital 60 Compressor Maintenance #2 Read Digital 61 Compressor Maintenance #3 Read Digital 62 Compressor Maintenance #4 Read Digital 63 Flow switch alarm 64 Remote on/off enable 65 Fan 2 speed 66 Fan inverter enable 67 Night mode enable Read/Write Digital Read Digital Read/Write Digital Read Digital Read/Write Digital 68 Chillernet enable Read/Write Digital 69 Heat/Cool selection Read/Write Digital 29 VLS/VLH/VLC 10/06 Index Meaning Read/Write Type 1 Sys #1 state Read Integer 2 Sys #2 state Read Integer 3 Machine state Read Integer 4 Minimum time stop Read Integer 5 Minimum time start Read Integer 6 Minimum time stop compressor Read/Write Integer 7 Delay time between the compressors Read/Write Integer 8 (LWT) Stop compressor Read/Write Integer 9 Stand-by time pump Read/Write Integer 10 Pump delay time stop Read/Write Integer 11 Delay time flow switch running Read/Write Integer 12 Delay time flow switch Start/up Read/Write Integer 13 Delay alarm low pressure Read/Write Integer 14 Delay time start defrost Read/Write Integer 15 Max time defrost Read/Write Integer 16 Delay time stop compressor during defrost Read/Write Integer 17 Pump-down maximum time Read/Write Integer 18 Time zone hour #1 Read/Write Integer 19 Time zone hour #2 Read/Write Integer 20 Time zone hour #3 Read/Write Integer 21 Time zone minute #1 Read/Write Integer 22 Time zone minute #2 Read/Write Integer 23 Time zone minute #3 Read/Write Integer 25 Pump hours (segment 1) Read/Write Integer 26 Pump hours (segment 2) Read/Write Integer 27 Compressor #1 (segment 1) Read/Write Integer 28 Compressor #1 (segment 2) Read/Write Integer 29 Compressor #2 (segment 1) Read/Write Integer 30 Compressor #2 (segment 2) Read/Write Integer 31 Compressor #3 (segment 1) Read/Write Integer 32 Compressor #3 (segment 2) Read/Write Integer 33 Compressor #4 (segment 1) Read/Write Integer 34 Compressor #4 (segment 2) Read/Write Integer 35 Fan start delay Read/Write Integer 36 Integration time regulation P+I Read/Write Integer 37 Night mode hour start Read/Write Integer 38 Night mode minute start Read/Write Integer 39 Night mode stop hour Read/Write Integer 40 Night mode stop minute Read/Write Integer 41 DELTA-V cooling (night mode) Read/Write Integer 42 DELTA-V heating (night mode) Read/Write Integer 24 30 VLS/VLH/VLC 10/06 Index Meaning Read/Write Type 1 Water inlet temperature RWT Read Analog 2 Outlet water temperature circuit #1 (LWT) Read Analog 3 Outlet water temperature circuit #2 (LWT) Read Analog 4 Outdoor air temperature (OAT) Read Analog 5 Defrost temperature/Low pressure transducer circuit #1 Read Analog 6 Defrost temperature/Low pressure transducer circuit #2 Read Analog 7 High pressure transducer circuit #1 Read Analog 8 High pressure transducer circuit #2 Read Analog 9 Regulated temperature Read Analog Read Analog Read/Write Analog 10 Inverter speed 11 Soglia freddo stop compressore LWT 12 Soglia caldo stop compressore LWT Read/Write Analog 13 Antifreezing set point Read/Write Analog 14 Antifreezing differential Read/Write Analog 15 Antifreezing electric heater set point Read/Write Analog 16 Antifreezing electric heater differential Read/Write Analog Analog 17 Inverter set point Read/Write Analog 18 Inverter minimum speed Read/Write Analog 19 Inverter maximum speed Read/Write Analog 20 Compressor maximum capacity Read/Write Analog 21 Compressor minimum capacity Read/Write Analog 22 High temperature heat Read/Write Analog 23 Low temperature heat Read/Write Analog 24 Defrost start set point Read/Write Analog 25 Defrost stop set point Read/Write Analog 26 Cooling set point limit Read/Write Analog 27 Coolind set point maximum Read/Write Analog 28 Efficiency value Read/Write Analog 29 Cooling set point RWT time zone #1 Read/Write Analog 30 Cooling set point RWT time zone #2 Read/Write Analog 31 Cooling set point RWT time zone #3 Read/Write Analog 32 Cooling set point RWT time zone #4 Read/Write Analog 33 Heat set point RWT time zone #1 Read/Write Analog 34 Heat set point RWT time zone #2 Read/Write Analog 35 Heat set point RWT time zone #3 Read/Write Analog 36 Heat set point RWT time zone #4 Read/Write Analog 37 Cooling set point LWT time zone #1 Read/Write Analog 38 Cooling set point LWT time zone #2 Read/Write Analog 39 Cooling set point LWT time zone #3 Read/Write Analog 40 Cooling set point LWT time zone #4 Read/Write Analog 41 Heat set point LWT time zone #1 Read/Write Analog 42 Heat set point LWT time zone #2 Read/Write Analog 43 Heat set point LWT time zone #3 Read/Write Analog 44 Heat set point LWT time zone #4 Read/Write Analog 45 Glicole Set point RWT time zone #1 Read/Write Analog 31 VLS/VLH/VLC 10/06 Index Meaning Read/Write Type 46 Glicole Set point RWT time zone #2 Read/Write Analog 47 Glicole Set point RWT time zone #3 Read/Write Analog 48 Glicole Set point RWT time zone #4 Read/Write Analog 49 Glicole Set point LWT time zone #1 Read/Write Analog 50 Glicole Set point LWT time zone #2 Read/Write Analog 51 Glicole Set point LWT time zone #3 Read/Write Analog 52 Glicole Set point LWT time zone #4 Read/Write Analog 53 Cooling set point RWT Read/Write Analog 54 Cooling set point LWT Read/Write Analog 55 Heat set point RWT Read/Write Analog 56 Heat set point LWT Read/Write Analog 57 Glicole Set point RWT Read/Write Analog 58 Glicole Set point LWT Read/Write Analog 59 Band Read/Write Analog 60 Dead band Read/Write Analog 61 Setpoint low speed Read/Write Analog 62 Differential low speed Read/Write Analog 63 MINDP (night mode) Read/Write Analog 64 DPOFFSET (night mode) Read/Write Analog 65 TMAX (night mode) Read/Write Analog 66 TMIN (night mode) Read/Write Analog 67 Set point minimum air temperature tandem Read/Write Analog 68 Differential minimum air temperature tandem Read/Write Analog 32 VLS/VLH/VLC 10/06 ">
Advertisement
Key features
- Microprocessor control
- User-friendly keyboard
- Proportional and integral control of RWT
- Hysteresis control of LWT
- Closed-loop condensing pressure control
- Pump-Down logic
- Compressor rotation
- Oil return function
- Night mode control
Frequently asked questions
The control parameters can be programmed using the LCD display, keyboard, and microprocessor-controlled LEDs on the terminal. This terminal allows you to set the setpoint, differential bands, alarm thresholds, and carry out main operations.
The Pump-Down logic manages the operation of the liquid line expansion valve during the start-up and shut-down of the compressors, ensuring that the system operates efficiently and safely.
The night mode, also known as low noise mode, adjusts the condenser pressure setpoint to reduce noise levels during nighttime hours. This is achieved by modifying the DPSET value by a DPOFFSET value, which can be programmed using the Service Level menu.