- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Heat Controller
- A-DVH24SD-1
- Service manual
advertisement
SERVICE MANUAL
DVC/DVH 09/12/18/24
Inverter Single Zone
Ductless Mini-Split
AITONS/MARS 35 Brownridge Road, Unit 6, Halton Hills, ON L7G 0C6 • 1-888-744-2911 • [email protected] • www.aitons.com
DVC/DVH Inverter Mini-Split Heat Controller
TABLE OF CONTENTS
1. Precaution ........................................................................................................................................................................3
1.1 Safety Precaution ......................................................................................................................................................3
1.2 Warning .....................................................................................................................................................................4
2. Part Identification and Functions ...................................................................................................................................5
2.1 Model Numbers of Indoor/Outdoor units ...................................................................................................................5
2.2 Required clearances for Indoor/Outdoor units .......................................................................................................5-6
2.3 Features .................................................................................................................................................................6-7
3. Dimensional Data ............................................................................................................................................................8
3.1 Indoor Unit ................................................................................................................................................................8
3.2 Indoor Unit Mounting Bracket ...................................................................................................................................9
3.3 Outdoor Unit ............................................................................................................................................................10
4. Refrigerant Cycle Diagram ...........................................................................................................................................11
4.1 Cooling Only Models (DVC) ....................................................................................................................................11
4.2 Heat Pump Models (DVH) ......................................................................................................................................12
5. Wiring Diagrams ............................................................................................................................................................13
5.1 Indoor Units ........................................................................................................................................................13-14
5.2 Outdoor Units ..........................................................................................................................................................15
6. Installation Details .........................................................................................................................................................16
6.1 Electrical .................................................................................................................................................................16
6.2 Line Set Connection Sizes ......................................................................................................................................16
6.3 Line Set Lengths and Elevations ............................................................................................................................16
6.4 Field Charging .........................................................................................................................................................16
7. Operating Conditions ....................................................................................................................................................17
8. Electronic Display Functions .......................................................................................................................................18
8.1 Abbreviations ..........................................................................................................................................................18
8.2 Display Functions ....................................................................................................................................................18
8.3 Main Protection .......................................................................................................................................................18
9. Operation Modes and Functions ..................................................................................................................................19
9.1 Fan Only Mode .......................................................................................................................................................19
9.2 Cooling Mode .....................................................................................................................................................19-21
9.3 Heating Mode .....................................................................................................................................................21-23
9.4 Defrost Mode .....................................................................................................................................................23-24
9.5 Evaporator Coil Temp. Protection ...........................................................................................................................24
9.6 Auto-Mode ..........................................................................................................................................................24-25
9.7 Dry Mode ................................................................................................................................................................25
9.8 Forced Operation ....................................................................................................................................................25
9.9 Timer Function ...................................................................................................................................................25-26
9.10 Sleep Mode ...........................................................................................................................................................26
9.11 Auto-Restart Function............................................................................................................................................26
9.12 Automatic Panel Function .....................................................................................................................................26
9.13 47°F (8°C) Heating ................................................................................................................................................26
10. Troubleshooting ..........................................................................................................................................................27
10.1 Indoor Unit Error Codes ........................................................................................................................................27
10.2 Outdoor Unit Errors and Troubleshooting ........................................................................................................28-31
10.3 Diagnosis and Solution ....................................................................................................................................32-48
10.4 Pressure on Service Port ......................................................................................................................................49
WARNING
• Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code
NFPA70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1. Where conflicts exist, the local
and/or national codes shall prevail.
• The information contained in the manual is intended for use by a qualified, licensed service technician familiar with safety
procedures and equipped with the proper tools and test instruments
• Installation or repairs made by unqualified persons will void the warranty and may cause hazards or incorrect operation.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage,
personal injury and/or death.
2
Heat Controller
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service the unit, be sure to read this service manual at first.
1.2 Warning
Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
3
1
DVC/DVH Inverter Mini-Split
Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock..
Do not touch (operation) the product with wet hands..
Do not allow water to run into electrical parts or the unit.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible materials near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
If abnormal noises or smoke comes from product, turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the is equipped with one .)
There is risk of physical injury, electric shock, or product failure..
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product will not be used for a long period of time, turn off the circuit breaker.
There is risk of product damage or failure, or unintended operation.
CAUTION
Always check for refrigerant leakage after installation or repair of product.
Low refrigerant levels may cause operational failure.
Install the drain hose to ensure that water is drained away properly.
Improper installation may cause water leakage and damage to personal property.
DVC/DVH Inverter Mini-Split
Keep the unit level even when installing the product.
This helps to avoid vibration or water leakage.
Do not install the product where it will be directly exposed to seaside wind (salty air).
It may cause corrosion on the product.
Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operational
Do not block the inlet or outlet of air flow.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp.
Always insert the filter securely.
Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through air inlet or outlet while the product is operated.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different brands of batteries.
There is risk of fire or explosion.
If battery acid from the batteries gets onto your skin or clothes, wash it well with clean water and contact your local poison control center. Do not use the remote of the batteries have leaked.
4
2
Heat Controller
Heat Controller
2. Part Identification and Functions
2.1 Model Numbers of Indoor/Outdoor units
Capacity
9KBTU/H
12KBTU/H
18KBTU/H
24KBTU/H
Indoor Units
B-DVH09SD-0 / B-DVC09SD-0
B-DVH12SD-0 / B-DVC12SD-0
B-DVH18SD-1 / B-DVC18SD-1
B-DVH24SD-1 / B-DVC24SD-1
2.2 Required Clearances for Indoor and Outdoor units
DVC/DVH Inverter Mini-Split
Outdoor Units
A-DVH09SD-0 / A-DVC09SD-0
A-DVH12SD-0 / A-DVC12SD-0
A-DVH18SD-1 / A-DVC18SD-1
A-DVH24SD-1 / A-DVC24SD-1
3
5
DVC/DVH Inverter Mini-Split Heat Controller
2.3 Features
Note: For Reference Only. Your model may differ and is subject to change.
Follow Me(O)
1W Standby
6
4
H Valve Protection Cover
Anti-rust Cabinet
Slump Heater
PTC Heating Belt(O)
Compressor Crankcase Heater(O)
Heat Controller
2.3.1 Description of Features and Functions
DVC/DVH Inverter Mini-Split
•
Auto-Restart:
The unit will memorize the set conditions before a power failure and resume operation automatically when the power re-starts.
•
Sleep Mode:
This feature helps keep the room conditions at the most desirable levels when you sleep.
•
Turbo Mode:
Turbo mode allows the unit to quickly heat or cool and room, at a high speed fan setting.
•
Anti-Cold Blow:
In heating mode, this feature prevents cold air from blowing until warm air is ready to be delivered.
•
Silver Ion Filter:
The silver filter sterilizes bacteria in the air stream by decomposing cell wall of bacteria.
•
Low Ambient Operation:
Allows the unit to operate under low outdoor temperatures.
•
Gold Hydrophilic Condensers Fin Coating:
This coating improves the heating efficiency by accelerating the defrosting process. The anticorrosive gold coating on the condenser helps withstand salty air and corrosive elements for sea side applications.
•
Self Clean:
This function wicks away any moisture, essentially cleaning the inside of indoor unit to prevents bacteria for forming. This feature is especially useful at the end of the season and/or when the unit will not be used for an extended period of time.
•
Follow me:
A temperature sensor is built in the remote control, which signals the unit to automatically change the operation mode to supply a comfortable temperature. Using this feature allows the unit to sense the conditions where you are in the room, rather than up high in the room where it traditionally senses the conditions via the indoor unit.
•
Low Room Temperature Protection:
Allows the unit to maintain a set temperature to protect the area it is installed in from freezing when you will be away for an extended period of time in the winter.
•
Louver Swing and Position Memory:
The louvers can swing to make a breeze like affect in the air flow from the indoor unit. When starting the unit after shutting down, the louver will restore the user’s settings for louver position.
•
Refrigerant Leak Detection:
The refrigerant leakage detect function prevents the unit from freezing due to low charge and protects the compressor from being damaged.
•
Self-Diagnosis Function:
The system monitors itself for abnormal operations and turns of the unit automatically to protect it from further damage, then displays an error code to help troubleshoot the problem for a quick solution.
•
Sump Heater:
A PTC heater is installed in the base pan of the outdoor unit to prevent the rain, snow or defrosted water from accumulating and icing up the unit.
•
Compressor Crankcase Heater:
The oil dissolves easily into the refrigerant, especially in low temperature condition, therefore the crankcase heating belt is used to warm the bottom of the compressor to avoid pumping out too much oil within the refrigerant, which helps to protect the compressor.
7
5
DVC/DVH Inverter Mini-Split Heat Controller
3. Dimensional Data
3.1 Indoor Unit
Note: The drawings below are only for reference. Actual dimensions may be different and are subject to change.
D
H
W
Note: The above drawing is only for reference. The dimensions of your actual unit may be different and are subject to change.
Model W D H
B-DVC09SD-0
B-DVH09SD-0
26.8in
(680mm)
7.0in
(178mm)
B-DVC12SD-0
10.0in
(255mm)
B-DVH12SD-0
30.3in
(770mm)
7.4in
(188mm)
B-DVC18SD-1
B-DVH18SD-1
B-DVC24SD-1
B-DVH24SD-1
35.6in
(905mm)
40.6in
(1030mm)
7.8in
(198mm)
8.6in
(218mm)
10.8in
(275mm)
12.4in
(315mm)
6
8
Heat Controller DVC/DVH Inverter Mini-Split
3.2 Indoor Unit Mounting Bracket
Note: The drawings below are only for reference. Actual dimensions may be different and are subject to change.
L
R
H
Model R
B-DVC/DVH09 3.6in(92mm)
L
6.7in
(170mm)
B-DVC/DVH12 3.7in(95mm)
B-DVC/DVH18 3.1in(80mm) 3.9in(100mm)
H
1.8in
(45mm)
Hole Diameter
Φ2.56in
(65mm)
L
R
H
Model R L
B-DVC/DVH24 6.4in(163mm) 11.5in(293mm) 1.8in(45mm) Φ2.56in(65mm)
9
7
H Hole Diameter
DVC/DVH Inverter Mini-Split Heat Controller
3.3 Outdoor Unit
Note: The drawings below are only for reference. Actual dimensions may be different and are subject to change.
Note: The above drawing is only for reference. The dimensions of your actual unit may be different and are subject to change.
Model W H D W1 A B
A-DVC/DVH09
A-DVC/DVH12
26.0in
(660mm)
10.5in
(265mm)
21.25in
(540mm)
28.8in
(732mm)
18in
(458mm)
10.9in
(276mm)
A-DVC/DVH18
30in
(760mm)
A-DVC/DVH24
33.3in
(845mm)
11.25in
(285mm)
12.5in
(320mm)
23.2in
(590mm)
27.6in
(700mm)
32.5in
(823mm)
35.7in
(908mm)
20.9in
(530mm)
22in
(560mm)
11.5in
(290mm)
13.2in
(335mm)
10
8
Heat Controller
4. Refrigerant Cycle Diagram
4.1 Cooling Only Models (DVC):
INDOOR
LIQUID SIDE
HEAT
EXCHANGE
(EVAPORATOR)
OUTDOOR
DVC/DVH Inverter Mini-Split
CAPILIARY TUBE
HEAT
EXCHANGE
(CONDENSER)
GAS SIDE COMPRESSOR
ATTENTION:
Units can be pumped down for service and recharged.
• A servicer can pump down the refrigerant into the outdoor unit for maintenance or replacement of the indoor unit.
• Also the entire system can be evacuated for maintenance or replacement of the outdoor unit.
11
9
DVC/DVH Inverter Mini-Split
4.2 Heat Pump Models (DVH):
INDOOR
HEAT
EXCHANGE
(EVAPORATOR)
LIQUID SIDE
2-WAY VALVE
OUTDOOR
CHECK VALVE
(Heating Model only)
CAPILIARY TUBE
HEAT
EXCHANGE
(CONDENSER)
Heat Controller
GAS SIDE
3-WAY VALVE
ACCUMULATOR
COMPRESSOR
REVERSING VALVE
(Heating Model only)
COOLING
HEATING
ATTENTION:
Units can be pumped down for service and recharged.
• A servicer can pump down the refrigerant into the outdoor unit for maintenance or replacement of the indoor unit.
• Also the entire system can be evacuated for maintenance or replacement of the outdoor unit.
12
10
Heat Controller
5.0 Wiring Diagrams:
5.1 Indoor Units:
B-DVC09SD-0, B-DVH09SC-0, B-DVH12SD-0, B-DVH12SD-0
DVC/DVH Inverter Mini-Split
B-DVC18SD-1, B-DVH18SD-1
13
11
DVC/DVH Inverter Mini-Split
B-DVC24SD-1, B-DVH24SD-1
Heat Controller
14
12
Heat Controller
5.2 Outdoor Units
A-DVC09SD-0, A-DVH09SD-0, A-DVC12SD-0, A-DVH12SD-0
DVC/DVH Inverter Mini-Split
A-DVC18SD-1, A-DVH18SD-1
15
13
DVC/DVH Inverter Mini-Split
6 Installation Details
6.1 Electrical
All electrical wiring must be done according to local codes. Additionally installations in the
USA, must conform to the current National
Electric Code (NEC) and Installations in
Canada must conform to current Canadian
Electric Code (CEC).
Nameplate data indicates the operating voltage, phase, ampacity, maximum over current protection, and minimum voltage.
The contractor is to provide an individual branch circuit for over current protection for the unit as required by code. Some codes may require a disconnect between the indoor and outdoor unit. Run power supply wiring through a weatherproof disconnect box and conduit to the unit connection. Disconnects are required to be within sight and easy reach of the unit
(usually within 3 feet).
Circuit breakers and disconnect switches should be properly sized based on the required codes and the unit’s nameplate requirements.
Check the unit wiring diagram for the number of conductors required. Ensure that the proper
AWG (gauge) and type of wired is used to comply with code and the unit’s nameplate.
Route neatly and protect from sharp edges and damage. Inadequate wiring and/or improper electrical supply will likely result in failure of the compressor and other electrical components and voids the warranty.
6.2 Line Set Connection Sizes
Connection Size
Models
Gas Liquid
Models
DVC/DVH09SD-0
DVC/DVH12SD-0
DVC/DVH18SD-1
DVC/DVH24SD-1
Max.
Elevation
26ft (8m)
33ft (10m)
6.4 Field Charging:
Max.
Length
66ft
(20m)
82ft
(25m)
Heat Controller
DVC09SD-0 / DVH09SD-0
DVC12SD-0 / DVH12SD-0
DVC18SD-1 / DVH18SD-1
DVC24SD-1 / DVH24SD-1
3/8in
(9.52mm)
1/2in
(12.7mm)
5/8in
(15.9mm)
6.3 Line Set Lengths and Elevations
1/4in
(6.35mm)
1/4in
(6.35mm)
3/8in
(9.52mm)
Heat Controller DVC/DVH Inverter Mini-Split
7. Operating Conditions
Indoor (Room)
Temperature
Cool Mode
≥62°F(17°C)
Heat Mode
≤86°F(30°C)
Dry Mode
>50°F(10°C)
Outdoor (Ambient)
Temperature
5°F - 122°F
(-15°C - 50°C)
5°F - 86°F
(-15°C - 30°C)
32°F - 122°F
(0°C - 50°C)
CAUTION:
1. If the unit is used outside of the above conditions, certain safety protection features may come into operation and cause the unit to operate abnormally.
2. If the room relative humidity is greater than 80%, the surface of the indoor unit may attract condensation. To lessen the chance for condensate dripping, set the vertical air flow louver to its maximum angle (vertically to the floor) and set the fan mode to HIGH.
17
15
DVC/DVH Inverter Mini-Split
8. Electronic Display Functions
8.1 Abbreviations
T1: Indoor room temperature
T2: Coil temperature of evaporator
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Temperature Set Point
8.2 Display functions
8.2.1 Icon Identification on indoor display board.
Defrost
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating mode
Run
Flashes when the unit is in standby.
Illuminates a solid light when the unit is on
.
Timer
This indicator illuminates when
TIMER is set ON/OFF.
Signal
Temperature indicator
Displays the temperature settings when the unit is operational, also displays any error codes for diagnosis and troubleshooting.
Receives the signal from the remote control.
Receiver
18
16
Heat Controller
8.3 Main Protection
8.3.1 Compressor Three Minute Time Delay
There is a 1 minute delay the 1 st
time the unit is started-up, then a 3 minute delay each time the unit is started up after the 1 st
time.
8.3.2 Compressor Top Temperature
Protection
The unit will stop working when the top of the compressor temperature is reached, and will restart after the compressor top temperature protector restarts.
8.3.3 Compressor Discharge Temperature
Protection
When the compressor discharge temperature is getting high, the frequency of the compressor will be limited as stated below:
When the compressor discharge temperature
T5>239°F(115°C) for 5s, the compressor will stop. However, when the temperature is between 226.4°F (108°C)<T5<239°F (115°C), the compressor frequency will decrease to the lowest level every 3 minutes. Then when the temperature is 194°F (90°C) <T5<221°F
(105°C), the compressor will keep running at the current frequency. When T5<194°F
(90°C), there will be no limit on the compressor frequency.
8.3.4 Out of Control Fan Speed
When Indoor Fan Speed runs at 300RPM or lower, for a designated period of time, the unit will stop running and the appropriate error code will show on the display.
8.3.5 Inverter Module Protection
The Inverter module has protection features regarding current, voltage and temperature. If these any of these are abnormal, the corresponding error code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately, but the indoor fan will not start for
10s. If the unit is in heating mode, the indoor fan will be also controlled by anti-cold wind function to eliminate cold blow.
Heat Controller
8.3.7 Compressor Crankcase Heater
If the outdoor ambient temperature T4<38°F
(3°C) and the unit connects to a new power supply or if the compressor has stopped for over 3 hours, the crankcase heater will turn on.
When T4>41°F (5°C) or the compressor starts running, the crankcase heater will turn off.
8.3.8 Zero Crossing Detection Error
If the unit detects a time interval is not correct for a continuous 240s, the unit will stop and the
LED will display the appropriate error code. The correct zero crossing signal time interval should be between 6-13ms.
8.4.2.9 Condenser temperature protection
131°F (55°C) <T3<140°F (60°C), the compressor frequency will decrease until it
9.0 Operation Modes and Functions
9.1 Fan Only Mode
In Fan only mode, the outdoor fan and compressor stop running. The temperature setting function is disabled and no setting temperature is displayed on the indoor unit.
The Indoor fan can be set to high/med/low/auto in fan only mode. The louver will operate the same as it does in cooling mode. When the fan only mode is placed in Auto Mode, it operates as shown below:
°F (°C)
DVC/DVH Inverter Mini-Split reaches level F1 and will continue to run at this level. When T3<129°F (54°C), the compressor will keep running at the current frequency.
However, if T3<126°F (52°C), the compressor will not limit the frequency and resume to the former frequency based on demand. But, if
T3>140°F (60°C) for 5 seconds, the compressor will stop until T3<126°F (52°C).
8.4.2.10 Evaporator temperature protection
When T2<32°F(0°C), the compressor will stop and will restart when T2
≥
41°F(5°C). At
32°F(0°C) ≤T2≤39°F(4°C), the compressor frequency will be limited and decreased to the lower level. However when the temperature is
39°F(4°C)≤T2≤45°F(7°C)≤, the compressor will keep the current frequency. At T2>45°F(7°C)≤, the compressor frequency will not be limited.
Fmax=F4
Fmax=F7
Fmax=F8
Fmax=F6
°F (°C)
High
Medium
Low
9.2 Cooling Mode
9.2.1 Compressor Operation-Cooling Mode
The maximum operating frequency (Fmax), follows the chart below based on the outdoor ambient temperature T4
19
17
Fmax=F3
DVC/DVH Inverter Mini-Split
However, if the unit is turned on using the remote control, the compressor will run at the
Fmax frequency for 7 minutes according to the outdoor ambient temperature T4. But after 7 minutes, the operation will take into account the difference (ΔT) in indoor room temperature (T1) and the Set Point Temperature (Ts) and the compressor frequency will operate as follows:
ΔT =T1-Ts
X ΔT°
3.5
A
3.0
B
2.5
C
2.0
D
1.5
E
1.0
F
0.5
-0.5
G
-1.0
H
The zones (A,B,C...H) shown on the chart above correspond to the various compressor running frequencies as a result (ΔT) of the difference between T1-Ts. When the temperature differential (ΔT) of T1-Ts remains in the same zone for 3 minutes, the compressor will run as follows:
In zones A thru E the ΔT is between 3.5 and 1
Degree, the compressor will continue to increase the frequency until it reaches its highest level where Fmax=F8.
In zone F, the compressor continues to run at its current frequency when the temperature differential (ΔT) is between 0.5 and 1 degree.
Once the temperature differential (ΔT) falls below 0.5 degrees, the compressor’s frequency will decrease unit it reaches the lowest level where Fmax=F1.
In zone H, where the ΔT is -1 degree or less, the compressor will run at the lowest frequency where Fmax=F1 for 1hour.
However, when the temperature differential (ΔT) is less than -2 degrees, the compressor will stop.
Additionally, the compressor running frequency is always limited by the current. Therefore, the running currents also must be taken into account. I3COOL, I2COOL, and I1COOL refer to different running current values in the table below.
I
I3COOL
Decrease
I2COOL
I1COOL
Off
Resume
Heat Controller
Hold
Indoor units
I1COOL I2COOL I3COOL
(Amps)
(Amps) (Amps)
B-DVC09SD-0
B-DVH09SD-0
B-DVC12SD-0
B-DVH12SD-0
B-DVC18SD-1
13.0
13.0
13.0
13.0
10.0
14.0
14.0
14.0
14.0
11.0
15.0
15.0
15.0
15.0
13.0
B-DVH18SD-1
B-DVC24SD-1
10.5
12.0
11.5
13.0
13.0
14.0
B-DVH24SD-1 12.0 13.0 14.0
If the running current is too high (above
I3COOL) in the “Off” zone of the chart above, the compressor will stop. Between I3COOL and I2COOL, in the “Decrease” zone the compressor will lower the frequency to the lowest level. The “Hold” zone allows the compressor to continue to run at the current frequency. Note: When the unit is in “hold”
zone for 3 minutes, the compressor frequency will rise to the next highest level. This rise in frequency can occur twice at most while in this
zone. The “Resume” zone places no limitation on the frequency.
Heat Controller
9.2.2 Outdoor Fan Operation - Cooling Mode
The outdoor fan operates based on the Outdoor
Ambient Temperature (T4):
T4
°F (°C)
High
Low
When the outdoor ambient temperature T4 is above 78°F(22°C), the outdoor fan runs high speed, however when the temperature is below this, the fan speed decreases to low and continues to run at low speed when the temperature is 68°F(20°C) or below.
9.4.2.3 Indoor Fan Operation-Cooling Mode
In cooling mode, indoor fan runs all the time and the speed can be set to high, medium, low or auto. When the fan is placed in auto mode, while the unit is in cooling mode, the auto fan operation takes into account the difference (ΔT) in indoor room temperature (T1) and the set point temperature (Ts):
ΔT =T1-Ts
ΔT°
4
High
3
Medium
1.5
1
Low
When there is a 3 to 4 degree difference (ΔT) in set and room temperatures, the fan runs high speed. When the difference in temperature
(ΔT) is between 1 and 3 degrees, the fan speed is medium. However, as the room temperature begins to get closer to the set temp, within 1 degree or less temperature differential (ΔT), the fan speed will run on low.
21
19
15
14
12
11
6
5
34
33
28
27
25
24
22
21
66 (19)
65 (18)
DVC/DVH Inverter Mini-Split
9.3 HEATING MODE
9.3.1 Compressor Operation-Heating Mode
The maximum operating frequency (Fmax), follows the chart below based on the outdoor ambient temperature T4:
T4
°F (°C)
Off
Fmax=F2
Fmax=F3
Fmax=F4
Fmax=F5
Fmax=F6
Fmax=F7
Fmax=F8
Fmax=F9
Fmax=F10
DVC/DVH Inverter Mini-Split
However, if the unit is turned on using the remote control, the compressor will run at the
Fmax frequency for 7 minutes according to the outdoor ambient temperature T4. But after 7 minutes, the operation will take into account the difference (ΔT) in indoor room temperature (T1) and the Set Point Temperature (Ts) and the compressor frequency will operate as follows:
ΔT =T1-Ts
ΔT°
H
H
+5.0
+4.5
+3.5
G
+1.5
+1.0
+0.5
+3.0
+2.5
+2.0
A
B
C
E
D
F
Heat Controller
Additionally, the compressor running frequency is always limited by the current. Therefore, the running currents also must be taken into account. I3HEAT, I2HEAT, and I1HEAT refer to various running current values, see chart.
I
I3HEAT
Decrease
I2HEAT
I1HEAT
Indoor Unit
B-DVC09SD-0
I1HEAT
(Amps)
6.5
Off
Resume
I2HEAT
(Amps)
7.5
Hold
I3HEAT
(Amps)
8.5
The zones (A,B,C...H) shown on the chart above correspond to the various compressor running frequencies as a result (ΔT) of the difference between T1-Ts. When the temperature differential (ΔT) of T1-Ts remains in the same zone for 3 minutes, the compressor will run as follows:
When the ΔT is between 0.5 and 2.5 Degrees, in zones A thru E, the compressor frequency will increase until it reaches the highest level
Fmax=F10.
In zone F, where the ΔT is 3 Degrees, the compressor will continue to run at the current frequency.
Once the ΔT is between 3.5 and 5 degrees in zone G, the compressor will decrease the frequency to its lowest level where Fmax=F1.
When ΔT is above 5 Degrees in the H zone, the compressor will continue to run at Fmax=F1 for
1hour.
When ΔT is greater and 6 degrees, the compressor will stop.
B-DVH09SD-0
B-DVC12SD-0
B-DVH12SD-0
B-DVC18SD-1
B-DVH18SD-1
B-DVC24SD-1
14.0
6.0
14.0
9.0
10.5
11.0
15.0
7.0
15.0
10.0
11.5
12.0
16.0
8.0
16.0
11.0
13.0
13.0
B-DVH24SD-1 12.0 13.0 14.0
22
20
If the running current is too high (above I3HEAT) in the “Off” zone of the chart above, the compressor will stop. Between I3HEAT and
I2HEAT, in the Decrease zone, the compressor will lower the frequency to the lowest level.
The “Hold” zone allows the compressor to continue to run at the current frequency. Note:
When the unit is in “hold” zone for 3 minutes, the compressor frequency will rise to the next highest level. This rise in frequency can occur
twice at most while in this zone. The “Resume” zone places no limitation on the frequency.
Heat Controller DVC/DVH Inverter Mini-Split
9.3.2 Outdoor Fan Operation-Heating Mode
The outdoor fan operates based on the Outdoor
Ambient Temperature (T4):
T4
°F (°C)
15
59 (15)
Low
High
When the outdoor ambient temperature T4 is above 63°F(17°C), the outdoor fan runs low speed, however when the temperature is below this, the fan speed increases to high and continues to run at high speed when the temperature is 63°F(17°C) or below.
9.3.3 Indoor Fan Operation-Heating Mode
The indoor fan runs based on the evaporator coil temperature (T2) as follows: forced to run for 127seconds in breeze mode. During this period, the anti-cold-wind is disabled.
• If the unit runs in forced operation mode, the indoor fan will run with rating speed and the anti-cold-wind function is disabled.
9.3.3.1 Auto Fan Operation-Heating Mode
When the fan is placed in auto mode, while the unit is in cooling mode, the auto fan operation takes into account the difference (ΔT) in indoor room temperature (T1) and the set point temperature (Ts):
ΔT =T1-Ts
ΔT°
Low
2.5
2
Medium
1.5
1
High
TEL8
Setting
TEL7
TEL6
TEL5
TEL4
Medium
Low
TEL3
TEL2
TEL1
TEL0
Off
Breeze
Super
Breeze
TEL0 TEL1 TEL2 TEL3 TEL4 TEL5 TEL6 TEL7 TEL8
75°F 83°F 90°F 95°F 97°F 102°F 111°F
(24°C) (28°C) (32°C) (35°C) (36°C) (39°C) (44°C)
Notes:
• If the compressor stops due to the room temperature rising, the indoor fan will be
21
23
The indoor fan will run at low speed when the
ΔT is greater than 2.5Degrees, medium speed when the ΔT is between 2.5 and 1.5 degrees, and high speed between 1.5 and 1 degrees or less.
9.4 Defrost Mode
9.4.1 Defrosting Conditions:
When T4>32°F(0°C), if the following two items are satisfied, the units start defrosting:
1. T3<38°F(3°C) for 40 minutes and T3 remains lower than 21°F(-6°C) for more than 3 minutes.
2. T3<38°F(3°C) for 80 minutes and T3 remains lower than 25°F(-4°C) for more than 3 minutes.
When T4<32°F(0°C), both the first and second conditions are satisfied, then the program will determine if T2 has decreased more than
41°F(5°C) or not. When T2 has decreased more than 41°F(5°C), the unit enter the defrost mode.
DVC/DVH Inverter Mini-Split
However, no matter what value T4 is, if the unit runs with T3<38°F(3°C) for more than 120 minutes and T3 remains lower than 29°F(-2°C) for more than 3 minutes, the unit will enter defrosting mode whether or not T2 drops more than 41°F(5°C) or not.
9.4.2 Ending Defrosting Operation:
If any one of the following items is satisfied, the defrost operation will end and the unit will return to normal heating mode.
• T3 rises to be higher than TCDE1.
• T3 remains higher than TCDE2 for 80 seconds.
• The unit has run in defrosting mode for
10 minutes.
Indoor units TCDE1 TCDE2
B-DVC/DVH 09, 12 54°F(12°C)
B-DVC/DVH 18, 24 59°F(15°C)
9.4.3 Defrosting Process:
DVC/DVH 9K,12K:
47°F(8°C)
Frequency F2 FrequencyF8
Compressor
4-way valve
Outdoor fan
Indoor fan on off on off on off on off
Indoor fan breeze(10s)
10s xx
10s no longer than 10m 30s
Where xx= 60seconds.
DVC/DVH 18K, 24K:
Frequency F2 Frequency F8
Compressor
4-way valve
Outdoor fan
Indoor fan on off on off on off on off
Indoor fan breeze(10s)
10s xx
10s no longer than 10m 30s
Where xx=60seconds for 18K model
Where xx=90seconds for 24K model
9.5 Evaporator Coil Temp. Protection
When T2>140°F(60°C), the compressor will turn off, but will restart when T2<119°F(48°C).
When T2>128°F(53°C), the compressor frequency will decrease to a lower level and runs at this level for 20seconds to protect the unit. When the frequency decreases to
Fmax= F2 and T2>128°F(53°C) for 3 minutes, the compressor will turn off. However, when the coil temperature lowers to T2<119°F(48°C) or
T2 remains at 119°F(48°C) for 6 minutes, the frequency will not be limited by the evaporator coil temperature (T2).
9.6 Auto-Mode
This mode can be selected using the remote control. The set temperature (Ts) can be changed between 63-86°F (17-30°C).
In auto mode, the machine will choose the mode according to ΔT, where ΔT =T1-Ts:
ΔT=T1-Ts Auto Mode Function:
ΔT>1°
-1°<ΔT≤1°
ΔT≤-1°
Cooling
Fan-only
Heating
Heat Controller
Heat Controller
Indoor fan will run in auto fan mode and the louver will operate based on the mode selected automatically (Heat, Cool, Fan-Only).
Notes:
• If the unit switches between heating and cooling modes automatically, the compressor will stop for 15 minutes and re-select the mode according to the ΔT conditions.
• If the setting temperature is modified, the machine will choose running function again based on ΔT.
9.7 Dry mode
9.7.1 Dry Model Fan Speed and Louver
Function
Indoor fan speed is fixed at breeze speed and can’t be changed. The louver angle will operate the same as it does in cooling mode.
9.7.2 Compressor Operation in Dry Mode
ΔT =T1-Ts
ΔT°
2.5
F3
2.0
1.5
1.0
F2
0.5
0.0
F1
F1
In Dry mode, the compressor’s frequency will decrease from F3 to F1, as the temperature difference (ΔT) between indoor room temperature (T1) and the Set point temperature
(Ts) decreases from 2.5 to 0 Degrees.
9.7.3 Low Room Temperature Protection
In dry mode, if room temperature is lower than
50°F(10°C), the compressor will stop and will not resume operation until room temperature exceeds 54°F(12°C).
9.7.4 Additional Protections in this Mode:
Evaporator anti-freezing, condenser high temperature protection and Compressor
DVC/DVH Inverter Mini-Split frequency and Outdoor fan are all limited in the same method that they would be in the cooling mode.
9.8 Forced Operation
Note: See Forced Operation information in the
Installation instructions.
When the unit is off, pressing the AUTO/COOL button on the indoor unit, under the main cover panel, will force the unit into auto mode. If the
AUTO/COOL button is pressed again within 5 seconds of the first time it was pushed, the machine will go into forced cooling mode.
Pressing the AUTO/COOL button again, any time after 5 seconds of the first time it was pushed, will turn off the unit. In forced operation mode, all general protections and remote control are available.
9.8.1 Operation rules:
Forced cooling mode:
The compressor will run at Fmax=F2 frequency and indoor fan runs in breeze mode. After running for 30 minutes this way, the unit will then run in auto mode with 75°F(24°C) set temperature (Ts). Note: See Auto-Mode
section of this manual for more information.
9.9 Timer function
9.9.1 Timer Range
The timer range is 24 hours and is relevant time, which means it is the time that has elapsed from the time the timer is set.
9.9.2 Timer On
The unit will turn on automatically when the
Timer On set time is reached.
9.9.3 Timer Off
The unit will turn off automatically when the timer off set time is reached.
9.9.4 Timer On/Off
The unit will turn on automatically when the
Timer On set time is reached and then the unit will automatically turn off when the timer off set time is reached.
9.9.5 Timer Off/On
The unit will turn off automatically when the timer off set time is reached and then
DVC/DVH Inverter Mini-Split automatically turn on when the Timer On set time is reached.
9.9.6 Mode within Timer Funtion
The timer function will not change the current operation mode.
9.10 Sleep Mode
9.10.1 Sleep Mode Duration
Sleep mode operates for 7 hours when it is activated. After 7 hours, the unit turns off.
9.10.2 Sleep Mode Operation
When sleep mode is activated while the unit is in cooling mode, the set temperature rises 1° every hour for 2 hours. After 2 hours, the set temperature stops rising and indoor fan is fixed at low speed.
When sleep mode is activated while the unit is in heating mode, the set temperature decreases 1°every hour for 2 hours. After 2 hours, the set temperature stops rising and indoor fan is fixed at low speed (Anti-cold wind function will still have the priority).
9.10.3 Timer Function in Sleep Mode
The Timer function is still available during sleep mode. When the timer off is set for less than 7 hours while in sleep mode, the sleep mode will stop once the set time off is reached.
However, if the timer off is set for more than 7 hours, the unit will not stop operating until reaches the set time in sleep mode.
9.11 Auto-Restart Function
In case of a sudden power failure, the unit will memorize the set conditions before the power failure. When the power returns, the unit will resume its previous operation settings (except for the swing function) automatically after 3 minutes.
9.12 Automatic panel function
The panel will automatically move to the closing direction at an angle of 50° when the unit is receiving power, and this action is not affected by any signal from remote control.
9.12.1 Panel Operation when Powering On
24
26
Heat Controller
When the unit is turned on, the panel is opened automatically at an angle of 50° and then the horizontal louver will open.
9.12.2 Panel Operation when Powering Off
When the unit is turned off, the panel is closed automatically at an angle of 50° and then the horizontal louver will close.
9.12.3 Panel Interference
If the panel is being closed when the horizontal louver is still moving, the unit will stop the horizontal louver from moving and allow the panel to move first. After this, the horizontal louver will continue its pervious movement.
9.13 47°F(8°C) Heating
Note: This is an optional feature and may not be present on your actual model.
In heating operation, the set temperature of the unit can be set as low as 47°F(8°C) in order to keep the room temperature above freezing when the house is unoccupied for an extended period of time in severe cold weather.
Heat Controller DVC/DVH Inverter Mini-Split
10. Troubleshooting
10.1 Indoor Unit Error Codes
KEY: ☆ = Flashing Light X = Light is Off O= Solid Light is On
Operation Timer Display Error:
☆ 1 time
☆
2 times
☆
3 times
X
X
X
E0
E1
E2
Indoor unit EEPROM parameter error
Communication Error between indoor and outdoor unit
Zero-crossing signal detection error
☆
4 times X E3
☆
5 times
☆
6 times
☆
7 times
X
X
X
E4
E5
EC
Indoor fan speed is out of control
T1 Indoor room temperature sensor has an open or short circuit
T2 Evaporator coil temperature sensor has an open or short circuit
Refrigerant leakage detection error
☆
2 times
☆
3 times
☆
4 times
O
O
O
F1
F2
F3
T4 Outdoor temperature sensor has an open or short circuit
T3 Condenser coil temperature sensor has an open or short circuit
T5 Compressor discharge temperature sensor has an open or short circuit
☆
5 times O F4
☆
1 times
☆
2 times
☆
3 times
☆
5 times
☆
☆
☆
☆
P0
P1
P2
P4
Outdoor unit EEPROM parameter error
IPM malfunction or IGBT over-strong current protection error
Over voltage or over low voltage protection error
High temperature protection of compressor top
Inverter compressor drive error
27
25
DVC/DVH Inverter Mini-Split
10.2 Outdoor Unit Errors and Trouble shooting
WARNING: Risk of Electrical Shock
Discharge the power in the capacitors on the board (if it contains electrolytic capacitors):
Heat Controller
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Note: All images are for reference only, they may vary from your particular model.
A-DVC09SD-0, A-DVH09SD-0, A-DVC12SD-0, and A-DVH12SD-0
LED1 is Blue. Slow flash = Standby Mode. Fast flash = Error.
26
28
Heat Controller
A-DVC24SD-1, A-DVH24SD-1
DVC/DVH Inverter Mini-Split
LED1 is Blue. Slow flash = Standby Mode. Fast flash = Error.
29
27
DVC/DVH Inverter Mini-Split
DVC18SD-1 and DVH18SD-1
Heat Controller
This board contains four LED lights, shown above. (This image is for reference only).
•
LED1 is Red and signals PCB Power by a solid light when the unit is operating or in standby mode.
•
LED2 is Yellow, which will flash slowly when the unit is in standby mode and remain solid when the unit is in operation. If this light flashes fast, there is an error.
•
LED3 is Red and LED4 is Green. These LEDs are both controlled by the compressor drive chip. See the following chart for more information on how these lights correspond with the
indoor unit error codes.
30
28
Heat Controller DVC/DVH Inverter Mini-Split
DVC18SD-1 and DVH18SD-1 LED3 and LED4 Error Codes:
8
6
7
4
5
2
3
KEY: ☆ = Flashing Light X = Light is Off O= Solid Light is On
No. Error
LED4
(Green)
1 Standby (Normal Operation) O
Operating Normally
IPM malfunction or IGBT over-strong current protection
X
☆
Over voltage or too low voltage protection
Over voltage or too low voltage protection
Inverter compressor drive error
Inverter compressor drive error
Inverter compressor drive error
O
O
X
☆
☆
O
☆
☆
O
LED3
(Red)
X
O
X
☆
Indoor Unit
Display
N/A
N/A
P0
P1
P1
P4
P4
P4
31
29
DVC/DVH Inverter Mini-Split
10.3 Diagnosis and Solution
10.3.1 EEPROM Parameter Error Diagnosis and Solution (E0/F4)
Error Code
E0/F4
Malfunction
Possible Causes
Trouble shooting:
Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code?
Main PCB chip is not receiving feedback from EEPROM chip
(Indoor/Outdoor)
●
●
Installation error
Faulty PCB
No No further action.
Heat Controller
Yes
If the EEPROM chip is welded on main
PCB, replace the main PCB directly.
Otherwise, check whether the
EEPROM chip plugged in main PCB well?
Yes
No Correct the connection.
Replace the main PCB.
EEPROM: Has a read-only memory, whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the representative photos below.
Indoor PCB
32
30
Outdoor PCB
Heat Controller DVC/DVH Inverter Mini-Split
10.3.2 Indoor / Outdoor Unit Communication Error Diagnosis and Solution (E1)
Error Code
E1
Malfunction
Possible Causes
Indoor unit does not receive the feedback from outdoor unit during
110 seconds and this condition happens four times continuously.
●
●
Wiring error
Faulty Indoor/Outdoor PCB
Trouble shooting:
Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes?
No No further action.
Yes
Measure Vs, is it moving alternately
(Vs is the voltage between L2 and S of outdoor unit. Connect the red pin of multimeter with L2 port, black pin with
S port)
No
Yes
Check all the wiring with outdoor u n i t s . Is the wiring to the outdoor main PCB connected correctly? Is the reactor connected well?
Yes
Measure the resistance of the reactor(The one without capacitor).
If it is zero ,follow the below step. If not, replace a new reactor.
Check all the wiring with indoor units.
Is the wiring to the indoor main PCB connected correctly?
Replace the outdoor main PCB.
Yes
Replace the indoor main PCB.
Replace the indoor main PCB.
Replace the outdoor main PCB.
* Note: See next page for masuring Vs and the resistance of the reactor.
33
31
DVC/DVH Inverter Mini-Split Heat Controller
Remark:
Use a multimeter to test the DC voltage between the L2 and S terminals of the outdoor unit.
The red pin of the multimeter should connect to L2 terminal while the black pin is for the S terminal.
When the unit running normally, the voltage will alternate between -50V to
50V.
If the outdoor unit has a malfunction, the voltage will alternate with positive voltage values.
If the indoor unit has malfunction, the voltage will be a constant value.
Remark:
Use a multimeter to test the resistance of the reactor (which does not connect with the capacitor).
The normal value should be around zero ohms. Otherwise, the reactor has malfunctioned and needs to be replaced.
32
34
Heat Controller DVC/DVH Inverter Mini-Split
10.3.3 Zero Crossing Detection Error Diagnosis and Solution (E2)
Error Code
E2
Malfunction
Possible Causes
When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.
●
●
Connection Error
Faulty PCB
Trouble shooting:
Check if the connections and power supply is normal?
No
Correct the connections. Turn on the unit when the power supply is good.
Yes
Indoor main PCB is defective. Replace indoor main PCB.
35
33
DVC/DVH Inverter Mini-Split
10.3.4 Fan Speed is Out of Control Diagnosis and Solution (E3)
Error Code
E3
Malfunction decision conditions
Possible Causes
Trouble shooting:
Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code?
When indoor fan speed runs at 300RPM or lower for certain period of time, the unit will stop and the LED will display the failure.
●
●
●
●
Wiring error
Faulty Fan Assembly
Faulty Fan Motor
Faulty PCB
No The unit operates normally.
Yes
Shut off the power supply, rotate the fan by hand.
Does it rotate properly?
No
Find out the cause and have it solved. For example, check whether the fan is
Yes
Check the wires of fan motor. Are all the connections good?
Yes
Check whether the fan motor is normal through index 1?
No
No Correct the connections.
Replace the fan motor
If the malfunction is exists, replace
No
Yes
Check whether the main PCB is normal through index 2?
No
Replace the main PCB.
The malfunction is solved?
Yes
Note: See next page for information pertaining to Index 1 and 2.
36
34
Heat Controller
Heat Controller
10.3.4 Index 1: Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
DVC/DVH Inverter Mini-Split
Position
Black -
Red
White -
Black
RPG13B
530Ω±8%
(20℃/68℉)
(Brand:
Weiling)
315Ω±8%
(20℃/68℉)
(Brand:
Weiling)
RPG15A
75Ω±8%
(20℃/68℉)
(Brand:
Weiling)
150Ω±8%
(20℃/68℉)
(Brand:
Weiling)
Resistance Value
RPG20B RPG28H
381Ω±8%
(20℃/68℉)
(Brand:
Weiling)
267Ω±8%
(20℃/68℉)
(Brand:
Weiling)
183.6Ω±8%
(20℃/68℉)
(Brand:
Weiling)
206Ω±8%
(20℃/68℉)
(Brand:
Weiling)
RPG45B
112Ω±8%
(20℃/68℉)
(Brand:
Weiling)
82Ω±8%
(20℃/68℉)
(Brand:
Weiling)
118.5Ω±8%
(20℃/68℉)
(Brand:
Dayang)
78.5Ω±8%
(20℃/68℉)
(Brand:
Dayang)
10.3.4 Index 2: Indoor AC Fan Motor
Power on and set the fan speed to high. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V (208~240V power supply) or 50V (115V power supply), the PCB is defective and needs to be replaced.
37
35
DVC/DVH Inverter Mini-Split
10.3.5 Open or Short Circuit of Temperature Sensor Diagnosis and Solution (E5)
Error Code
Malfunction
Possible Causes
E5
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the this error code.
●
●
Wiring Error
Faulty Sensor
Trouble shooting:
Check the connections between temperature sensor and main PCB.
Are the connections good?
No Correct the connections.
Yes
Heat Controller
Check the resistance value of the sensor via table1(p64)and table
2(p65), is it normal?
No
Replace the sensor and check if the problem happen again?
Yes
Replace indoor or outdoor main PCB.
Disconnect the temperature sensor from PCB, measure the resistance value of each winding by using the multi-meter.
36
38
Temperature Sensors:
T1: Room Temperature Sensor
T2: Indoor Coil Temperature Sensor
T3: Outdoor Coil Temperature Sensor
T4: Outdoor Ambient Temperature Sensor
T5: Compressor Discharge Temperature Sensor
Heat Controller
℃
-1
0
1
-5
-4
-3
-2
-11
-10
-9
-8
-7
-6
-20
-19
-18
-17
-16
-15
-14
-13
-12
12
13
14
8
9
10
11
15
16
17
18
19
4
5
2
3
6
7
℉
30
32
34
23
25
27
28
12
14
16
18
19
21
5
7
1
3
9
10
-4
-2
0
54
55
57
46
48
50
52
59
61
63
64
66
36
37
39
41
43
45
T1, T2, T3,T4 Temperature Sensor Resistance Value Table
K Ohm
115.266
108.146
101.517
46.5725
44
41.5878
39.8239
37.1988
35.2024
33.3269
31.5635
29.9058
28.3459
26.8778
25.4954
24.1932
96.3423
89.5865
84.219
79.311
74.536
70.1698
66.0898
62.2756
58.7079
56.3694
52.2438
49.3161
22.5662
21.8094
20.7184
19.6891
18.7177
17.8005
16.9341
16.1156
15.3418
14.6181
13.918
13.2631
K Ohm
12.6431
12.0561
11.5
6.40021
6.13059
5.87359
5.62961
5.39689
5.17519
4.96392
4.76253
4.5705
4.38736
4.21263
4.04589
3.88673
10.9731
10.4736
10
9.55074
9.12445
8.71983
8.33566
7.97078
7.62411
7.29464
6.98142
6.68355
3.73476
3.58962
3.45097
3.31847
3.19183
3.07075
2.95896
2.84421
2.73823
2.63682
2.53973
2.44677
℃
39
40
41
35
36
37
38
29
30
31
32
33
34
23
24
25
26
27
28
20
21
22
52
53
54
48
49
50
51
55
56
57
58
59
42
43
44
45
46
47
K Ohm
2.35774
2.27249
2.19073
1.38703
1.34105
1.29078
1.25423
1.2133
1.17393
1.13604
1.09958
1.06448
1.03069
0.99815
0.96681
0.93662
2.11241
2.03732
1.96532
1.89627
1.83003
1.76647
1.70547
1.64691
1.59068
1.53668
1.48481
1.43498
0.90753
0.8795
0.85248
0.82643
0.80132
0.77709
0.75373
0.73119
0.70944
0.68844
0.66818
0.64862
℉
95
97
99
100
102
104
106
84
86
88
90
91
93
73
75
77
79
81
82
68
70
72
118
120
122
124
126
127
129
131
133
135
136
138
108
109
111
113
115
117
℃
79
80
81
75
76
77
78
69
70
71
72
73
74
63
64
65
66
67
68
60
61
62
92
93
94
88
89
90
91
95
96
97
98
99
82
83
84
85
86
87
℉
167
169
171
172
174
176
178
156
158
160
162
163
165
140
142
144
145
147
149
151
153
154
190
192
194
196
198
199
201
203
205
207
208
210
180
181
183
185
187
189
37
39
℃
115
116
117
118
119
120
121
109
110
111
112
113
114
100
101
102
103
104
105
106
107
108
128
129
130
131
132
133
134
135
136
137
138
139
122
123
124
125
126
127
DVC/DVH Inverter Mini-Split
K Ohm
0.62973
0.61148
0.59386
0.41164
0.4006
0.38991
0.37956
0.36954
0.35982
0.35042
0.3413
0.33246
0.3239
0.31559
0.30754
0.29974
0.57683
0.56038
0.54448
0.52912
0.51426
0.49989
0.486
0.47256
0.45957
0.44699
0.43482
0.42304
0.29216
0.28482
0.2777
0.27078
0.26408
0.25757
0.25125
0.24512
0.23916
0.23338
0.22776
0.22231
℉
239
241
243
244
246
248
250
228
230
232
234
235
237
212
214
216
217
219
221
223
225
226
262
264
266
268
270
271
273
275
277
279
280
282
252
253
255
257
259
261
℉
45
46
48
50
52
54
37
39
41
43
25
27
28
30
18
19
21
23
32
34
36
55
57
59
61
63
64
66
1
3
5
7
-4
-2
0
9
10
12
14
16
℃
7
8
9
10
11
12
5
6
3
4
-4
-3
-2
-1
0
1
2
-8
-7
-6
-5
13
14
15
16
17
18
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
19
DVC/DVH Inverter Mini-Split
T5 Temperature Sensor Resistance Value Table
K Ohm
℃
542.7 20
95.05
90.66
86.49
82.54
78.79
75.24
71.86
155.2
147.6
140.4
133.5
127.1
121
115.2
109.8
104.6
99.69
275.9
261.4
247.8
234.9
222.8
211.4
200.7
190.5
180.9
171.9
163.3
511.9
483
455.9
430.5
406.7
384.3
363.3
343.6
325.1
307.7
291.3
57
58
59
53
54
55
56
47
48
49
50
51
52
43
44
45
46
36
37
38
39
40
41
42
32
33
34
35
25
26
27
28
29
30
31
21
22
23
24
109 25.86
111 24.85
113 23.89
115 22.89
117 22.1
118 21.26
120 20.46
122 19.69
124 18.96
126 18.26
127 17.58
129 16.94
131 16.32
133 15.73
135 15.16
136 14.62
138 14.09
℉
68
70
72
73
75
77
79
81
82
84
86
88
K Ohm
℃
68.66
90
91
93
95
40.57
38.89
37.3
35.78
97
99
34.32
32.94
100 31.62
102 30.36
104 29.15
106 28
108 26.9
65.62
62.73
59.98
57.37
54.89
52.53
50.28
48.14
46.11
44.17
42.33
60
65
66
67
68
69
70
71
61
62
63
64
76
77
78
79
80
81
82
72
73
74
75
97
98
40
99
93
94
95
96
87
88
89
90
91
92
83
84
85
86
38
Heat Controller
℉
K Ohm
212 3.702
253 1.955
255 1.905
257 1.856
259 1.808
261 1.762
262 1.717
264 1.674
266 1.632
214 3.595
216 3.492
217 3.392
219 3.296
221 3.203
223 3.113
225 3.025
226 2.941
228 2.86
230 2.781
232 2.704
234 2.63
235 2.559
237 2.489
239 2.422
241 2.357
243 2.294
244 2.233
246 2.174
248 2.117
250 2.061
252 2.007
℉
K Ohm
℃
140 13.59 100
181 6.228
183 6.033
185 5.844
187 5.663
189 5.488
190 5.32
192 5.157
194 5
196 4.849
198 4.703
199 4.562
201 4.426
203 4.294
205 4.167
207 4.045
208 3.927
210 3.812
142 13.11
144 12.65
145 12.21
147 11.79
149 11.38
151 10.99
153 10.61
154 10.25
156 9.902
158 9.569
160 9.248
162 8.94
163 8.643
165 8.358
167 8.084
169 7.82
171 7.566
172 7.321
174 7.086
176 6.859
178 6.641
180 6.43
127
128
129
130
123
124
125
126
116
117
118
119
112
113
114
115
120
121
122
105
106
107
108
101
102
103
104
109
110
111
Heat Controller DVC/DVH Inverter Mini-Split
10.3.6 Refrigerant Leakage Detection Diagnosis and Solution (EC)
Error Code
Malfunction
Possible Causes
EC
In the first 5 minutes that the compressor starts up, if the temperatures
do not remain a constant function where T2 < (Tcool – 2) for 4 seconds
and occurs 3 times, the display will show error code “EC” and unit will turn off.
T2 is the Indoor Coil Temperature Sensor
Tcool is the temp when the compressor first begins to run.
●
●
●
T2 Sensor faulty
Indoor PCB Faulty
Refrigeration Circuit problems, such as gas leakage or blockages.
Trouble shooting:
Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code?
Yes
Is there cool air blowing out from indoor air outlet?
No
Is there any leakage? Especially the connection parts, such as the gas valve and the liquid valve.
Yes
Check if T2 sensor is well fixed. Correct the installation or replace T2 sensor. Does the problem remain again?
Yes
Replace indoor PCB.
No
Yes
Repair the leakage and recharge the refrigerant.
Is there any block i n g ? (Such as the capillary or the welded points of the pipes.)
Yes
41
39
DVC/DVH Inverter Mini-Split Heat Controller
10.3.7 IPM Malfunction or IGBT Over Current Protection Diagnosis and Solution (P0)
Error Code
Malfunction decision conditions
Possible Causes
P0
When the voltage signal that IPM sends to compressor drive chip is abnormal, the display LED will show “P0” and unit will turn off.
●
Wiring error
●
IPM malfunction
●
●
●
Outdoor Fan Assembly faulty
Compressor Malfunction
Outdoor PCB Faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by error and if the wires and connectors are broken?
Yes
Correct the connection or replace the wires and connectors.
No
IPM continuity check. Check if the
IPM terminal resistance values are uniform. Refer to page 64.
No
Replace the IPM board or replace the main PCB if the IPM board and main
PCB are integrated together.
Yes
Check if the outdoor fan runs properly or the outdoor unit ventilation is good.
Yes
Check if the compressor resistance values are uniform .Refer to page 63.
Yes
Replace the outdoor main PCB if the main PCB and IPM are separate.
No
No please refer to the below remark, check whether the resistance of the fan motor is normal. If not, replace the fan motor.
Replace the compressor.
42
40
Heat Controller DVC/DVH Inverter Mini-Split
10.3.7 Index: IPM continuity check
Turn off the power, let the electrolytic capacitors discharge completely, and dismount the IPM.
Use a digital tester to measure the resistance between P and U,V,W,N; U,V,W and N.
(+)Red
Digital tester
(-)Black
N
U
P
V
W
Normal resistance value
∞
(Several MΩ)
Digital tester
(+)Red (-)Black
U
V
N
W
(+)Red
Normal resistance value
∞
(Several MΩ)
Note:
1) DVC09SD-0, DVH09SD-0, DVC12SD-0, DVH12SD-0 models:
Measure the black pin and red pin of the motor connector, the resistance should be around 50Ω at 20℃(68℉)
2) DVC18SD-1 and DVH24SD-1 models:
Measure the
black pin and red pin of the motor connector, the resistance should be around 84.5Ω at 20℃(68℉)
3) DVC24SD-1 and DVH24SD-1 models:
Measure the black pin and red pin of the motor connector, the resistance should be around 88.5Ω at 20℃(68℉)
P-U
43
41
DVC/DVH Inverter Mini-Split Heat Controller
P-V
P-W
44
42
Heat Controller DVC/DVH Inverter Mini-Split
P-N
45
43
DVC/DVH Inverter Mini-Split Heat Controller
10.3.8 High Temperature Protection of Compressor Top Diagnosis and Solution (P2)
Error Code
P2
Malfunction
Possible Causes
Trouble shooting:
Check if the air flow of the indoor and outdoor units are are obstructed?
If the sampling voltage is not 5V, the LED will display the error.
●
●
●
Power Supply Problems.
Refrigerant Circuit leakage or blockage
PCB Faulty
Yes
Clear up the air inlet and outlet or the heat exchanger of indoor and outdoor units.
No
Turn off the power supply and turn it on 10 minutes later.
Yes
Check if the unit can start normally.
No No Correct the connection.
Yes
Check if the refrigerant charge volume is normal?
Check if all the connections, especially if the OLP (Over Load
Protector) sensor is good.
Yes
Measure the resistance between the two ports of the OLP. Is it zero?
No Replace the OLP.
No
Yes
Yes Replace the outdoor control PCB.
Refrigerant system is blocked, such as capillary or welded point of pipes.
or welded joints of pipes.
Fix blockage or replace blocked component.
Recharge the correct refrigerant volume.
46
44
Heat Controller DVC/DVH Inverter Mini-Split
10.3.9 Inverter Compressor Drive Error Diagnosis and Solution (P4)
Error Code
P4
Malfunction decision conditions
Possible Causes
An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, and compressor rotation speed signal detection, etc.
●
Wiring mistake
●
●
●
●
IPM Malfunction
Outdoor Fan Assembly Faulty
Compressor Malfunction
Outdoor PCB Faulty
Trouble shooting:
Check if the wiring between main
PCB and compressor connected by error and if the wires and connectors are broken?
Yes
Correct the connection or replace the wires and connectors.
No
IPM continuity check. Check if the
IPM terminal resistance values are uniform. Refer to page 64.
No
Replace the IPM board or replace the main PCB if the IPM board and main
PCB are integrated together.
Yes
Check if the outdoor fan runs properly or the outdoor unit ventilation is good.
Yes
Check if the compressor resistance values are uniform .Refer to page 63.
Yes
Replace the outdoor main PCB if the main PCB and IPM are separate.
No
No
For MSV1-09HRFN1-MT0W and MSV1-12HRFN1- MT0W models, r efer to the solution of fan speed has been out of control malfunction . Find out the cause and have it solved. For other models, please refer to the below remark, check whether the resistance of the fan motor is normal. If not, replace the fan motor.
Replace the compressor.
47
45
DVC/DVH Inverter Mini-Split
10.3.9 Index: Compressor Resistance
Measure the resistance value of each winding by using the tester.
Position
Blue - Red
Blue - Black
Red - Blue
DA108X1C-23EZ
1.1Ω
(20℃/68℉)
Resistance Value
DA130M1C-31FZ
1.77Ω
(20℃/68℉)
DA150S1C-20FZ
0.95Ω
(20℃/68℉)
Heat Controller
48
46
Heat Controller DVC/DVH Inverter Mini-Split
10.4: Pressure on Service Port
10.4.1 Cooling:
℉
(℃)
PSI
PSI
PSI
℉
(℃) ODT
IDT
BAR 70/59
75
(
23.89)
8.2
BAR 75/63
BAR 80/67
8.6
9.3
ODT
IDT 75
(
23.89)
70/59 119
75/63
80/67
124
135
℉
(℃) ODT
IDT
MPA 70/59
75
(
23.89)
0.82
MPA 75/63
MPA 80/67
0.86
0.93
12.0
85
(
29.44)
7.8
8.3
8.9
95
(
35)
8.1
8.7
9.1
85
(
29.44)
113
120
129
85
(
29.44)
0.78
0.83
0.89
95
(
35)
117
126
132
95
(
35)
0.81
0.87
0.91
105
(
40.56)
8.6
9.1
9.6
115
(
46.11)
10.1
10.7
11.2
105
(
40.56)
125
132
140
115
(
46.11)
147
155
162
105
(
40.56)
0.86
0.91
0.96
115
(
46.11)
1.01
1.07
1.12
10.0
8.0
6.0
4.0
2.0
0.0
75 (23.89) 85 (29.44) 95 (35) 105 (40.56) 115 (46.11)
70/59
75/63
80/67
49
47
DVC/DVH Inverter Mini-Split Heat Controller
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
℉
(℃)
BAR
BAR
BAR
10.4.2
Heating Chart:
IDT
ODT
57/53
(13.89/11.67)
55
65
75
30.3
32.5
33.8
℉
(℃)
PSI
PSI
PSI
IDT
ODT
57/53
(13.89/11.67)
55
65
75
439
471
489
℉
(℃)
IDT
ODT
MPA 55
57/53
(13.89/11.67)
3.03
MPA 65
MPA 75
3.25
3.38
57/53
(13.89/11.67)
47/43
(8.33/6.11)
47/43
(8.33/6.11)
28.5
30.0
31.5
47/43
(8.33/6.11)
413
435
457
47/43
(8.33/6.11)
2.85
3.00
3.15
37/33
(2.78/0.56)
37/33
(2.78/0.56)
25.3
26.6
27.8
37/33
(2.78/0.56)
367
386
403
37/33
(2.78/0.56)
2.53
2.66
2.78
27/23
(-2.78/-5)
27/23
(-2.78/-5)
22.8
25.4
26.3
27/23
(-2.78/-5)
330
368
381
27/23
(-2.78/-5)
2.28
2.54
2.63
17/13
(-8.33/-10.56)
20.8
23.3
24.9
17/13
(-8.33/-10.56)
302
339
362
17/13
(-8.33/-10.56)
2.08
2.33
2.49
17/13
(-8.33/-10.56)
55
65
75
50
48
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
℉
(℃)
BAR
BAR
BAR
10.4.2
Heating Chart:
IDT
ODT
57/53
(13.89/11.67)
55
65
75
30.3
32.5
33.8
℉
(℃)
PSI
PSI
PSI
IDT
ODT
57/53
(13.89/11.67)
55
65
75
439
471
489
℉
(℃)
IDT
ODT
MPA 55
57/53
(13.89/11.67)
3.03
MPA 65
MPA 75
3.25
3.38
57/53
(13.89/11.67)
47/43
(8.33/6.11)
47/43
(8.33/6.11)
28.5
30.0
31.5
47/43
(8.33/6.11)
413
435
457
47/43
(8.33/6.11)
2.85
3.00
3.15
37/33
(2.78/0.56)
37/33
(2.78/0.56)
25.3
26.6
27.8
37/33
(2.78/0.56)
367
386
403
37/33
(2.78/0.56)
2.53
2.66
2.78
27/23
(-2.78/-5)
27/23
(-2.78/-5)
22.8
25.4
26.3
27/23
(-2.78/-5)
330
368
381
27/23
(-2.78/-5)
2.28
2.54
2.63
17/13
(-8.33/-10.56)
20.8
23.3
24.9
17/13
(-8.33/-10.56)
302
339
362
17/13
(-8.33/-10.56)
2.08
2.33
2.49
17/13
(-8.33/-10.56)
55
65
75
Heat Controller DVC/DVH Inverter Mini-Split
This page is left intentionally blank.
51
48
DVC/DVH Inverter Mini-Split Heat Controller
AITONS/MARS 35 Brownridge Road, Unit 6, Halton Hills, ON L7G 0C6 • 1-888-744-2911 • [email protected] • www.aitons.com
4/2014
52
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 1.1 Safety Precaution
- 4 1.2 Warning
- 5 2. Part Identification and Functions
- 5 2.2 Required clearances for Indoor/Outdoor units
- 6 2.3 Features
- 8 3. Dimensional Data
- 9 3.2 Indoor Unit Mounting Bracket
- 10 3.3 Outdoor Unit
- 11 4. Refrigerant Cycle Diagram
- 11 4.1 Cooling Only Models (DVC)
- 12 4.2 Heat Pump Models (DVH)
- 13 5. Wiring Diagrams
- 13 5.1 Indoor Units
- 15 5.2 Outdoor Units
- 16 6. Installation Details
- 16 6.1 Electrical
- 16 6.2 Line Set Connection Sizes
- 16 6.3 Line Set Lengths and Elevations
- 16 6.4 Field Charging
- 17 7. Operating Conditions
- 18 8.1 Abbreviations
- 18 8.2 Display Functions
- 18 8.3 Main Protection
- 19 9. Operation Modes and Functions
- 19 9.1 Fan Only Mode
- 19 9.2 Cooling Mode
- 21 9.3 Heating Mode
- 23 9.4 Defrost Mode
- 24 9.5 Evaporator Coil Temp. Protection
- 24 9.6 Auto-Mode
- 25 9.7 Dry Mode
- 25 9.8 Forced Operation
- 25 9.9 Timer Function
- 26 9.10 Sleep Mode
- 26 9.11 Auto-Restart Function
- 26 9.12 Automatic Panel Function
- 26 9.13 47°F (8°C) Heating
- 27 10. Troubleshooting
- 27 10.1 Indoor Unit Error Codes
- 28 10.2 Outdoor Unit Errors and Troubleshooting
- 32 10.3 Diagnosis and Solution
- 49 10.4 Pressure on Service Port