Halton Ecolo Air Unit Operators Manual

EcoloAir Unit is designed to operate with specific pressure drops across filter stages: Pre Filter .2” to .75”, Medium Efficiency Filter .4” to 1.25”, and High Efficiency Filter .75” to 2.0”. When pressure drop exceeds upper limits, audible/visual alarm will sound and activate pilot light. The alarm is a warning only and doesn't shut the system down. The system has a firestat capable of triggering alarm on the control panel. Upon detecting 350°F, it will shut off the exhaust fan and display a FIRE alarm. Once the temperature drops below 320°F, it will clear the alarm and restore operation.

PDF Download
Document
Halton Ecolo Air Unit Operators Manual | Manualzz

Advertisement

Advertisement

Advertisement

Key features

  • Filter stage pressure drop alarm
  • Firestat alarm
  • Filter not in place alarm
  • Fire alarm
  • Odor control liquid
  • Odor nozzle
  • Belt tension adjustment
  • Fan bearing lubrication
  • Motor starter contacts check
  • Fan motor amperage draw check

Frequently asked questions

The EcoloAir filter unit is designed to operate with the following pressure drops across each filter stage: Pre Filter .2” to .75”, Medium Efficiency Filter .4” to 1.25”, and High Efficiency Filter .75” to 2.0”.

When the pressure drop for each filter bank exceeds the upper limits, an audible/visual alarm will sound and activate a pilot light.

The firestat is capable of triggering an alarm on the control panel. Upon the firestat detecting 350°F, it will shut the exhaust fan off and display a FIRE alarm. Once the firestat sees the temperature drop down below 320°F it will clear the alarm on the panel and restore operation of the exhaust fan.

There are two other alarm conditions: 1) “A filter not in place” sensing system. 2) A fire state to sense excessive temperatures in the duct. Should either alarm be triggered, the audible/visual alarm will sound, an indicator light labeled “filters overall” will be illuminated, and the system will shut down.

You should check the condition of the air filters monthly and replace them if necessary.

You should check the odor control liquid level monthly and replace it if necessary.

You should check the odor nozzle condition monthly and check for debris.

You should check the belt tension at the exhaust fan quarterly and tighten as required.

In addition to checking belt tension, you should also check belt alignment, lubricate motor bearings, lubricate fan bearings, check contacts on motor starter in control panel, check amperage draw of fan motor, check to see if the overall filter warning system operates correctly by removing the high efficiency filters and starting the system, and check fusible link on the fire dampers (filter section).

User questions

A A E

What does the "Low Ecolo Level" alarm indicate?
The "Low Ecolo Level" alarm indicates that the Ecolo Scentry Solution in the odor control unit is low.
How do I replace the Ecolo Scentry Solution?
Instructions for replacing the Ecolo Scentry Solution bottle are available.