Foster HR 100, HR 120, HR 150-A, HR 200, HR 240, HR 360, HR B120, HR 200FT, HR 360FT, LR 120, LR 150-A, LR 200, LR 240, LR 360, LR B120 Undercounter Cabinet Service Manual
Below you will find brief information for Undercounter Cabinet HR 100, Undercounter Cabinet HR 120, Undercounter Cabinet HR 150-A, Undercounter Cabinet HR 200, Undercounter Cabinet HR 240, Undercounter Cabinet HR 360, Undercounter Cabinet LR 120, Undercounter Cabinet LR 150-A, Undercounter Cabinet LR 200, Undercounter Cabinet LR 240. These Undercounter Cabinets are manufactured as a one piece foamed shell with the condensing unit located on the base of the cabinet. These cabinets conform to ISO Climate Class 4 (32°C with 40% RH) and have their temperature controller by a LAE microprocessor controller with digital temperature display.
Advertisement
Advertisement
Undercounter Cabinets,
Space Savers &
Prep Tables with
BIT25 Controller &
LCD5S Display
ISO 9001 ISO 14001
Issued December 2011
Contents
Manual Information & Health & Safety Notes
Environmental Management Policy
Disposal Requirements
Cabinets Description & 1 st
Serial Numbers
Controller Description, Operation & Diagram
Individual Unit Temperatures & Capacities
Controller Wiring Diagram, dimensions & Technical
Configuration of & Parameters lists
Parts Replacement Instructions for HR/LR 150
Technical Specification
Wiring Diagrams
Troubleshooting & Notes
1
2
2
3
4 to 6
7
8
9 to 15
16 to 20
21 to 22
23
24 to 26
Service Manual Information
The products and all information in this manual are subject to change without prior notice.
We assume by the information given that the person(s) working on these refrigeration units are fully trained and skilled in all aspects of their workings. Also that they will use the appropriate safety equipment and take or meet precautions where required.
The service manual does not cover information on every variation of this unit; neither does it cover the installation or every possible operating or maintenance instruction for the units.
Health & Safety Warnings and Information
Make sure the power supply is turned off before making any electrical repairs.
To minimise shock and fire hazards, please do not plug or unplug the unit with wet hands.
During maintenance and cleaning, please unplug the unit where required.
Care must be taken when handling or working on the unit as sharp edges may cause personal injury, we recommend the wearing of suitable PPE.
E nsure the correct moving and lifting procedures are used when relocating a unit.
Do NOT use abrasive cleaning products, only those that are recommended. Never scour any parts of the refrigerator. Scouring pads or chemicals may cause damage by scratching or dulling polished surface finishes.
Failure to keep the condenser clean may cause premature failure of the motor/compressor which will NOT be covered under warranty policy.
Do NOT touch the cold surfaces in the freezer compartment. Particularly when hands are damp or wet, skin may adhere to these extremely cold surfaces and cause frostbite.
Please ensure the appropriate use of safety aids or Personnel Protective Equipment
(PPE) are used for you own safety.
1
Environmental Management Policy for Service Manuals and Duets.
Product Support and Installation Contractors
Foster Refrigerator recognises that its activities, products and services can have an adverse impact upon the environment.
The organisation is committed to implementing systems and controls to manage, reduce and eliminate its adverse environmental impacts wherever possible, and has formulated an Environmental Policy outlining our core aims. A copy of the Environmental Policy is available to all contractors and suppliers upon request.
The organisation is committed to working with suppliers and contractors where their activities have the potential to impact upon the environment. To achieve the aims stated in the Environmental Policy we require that all suppliers and contractors operate in compliance with the law and are committed to best practice in environmental management.
Product Support and Installation contractors are required to:
1.
Ensure that wherever possible waste is removed from the client’s site, where arrangements are in place all waste should be returned to Foster Refrigerator’s premises. In certain circumstances waste may be disposed of on the client’s site; if permission is given, if the client has arrangements in place for the type of waste.
2. If arranging for the disposal of your waste, handle, store and dispose of it in such a way as to prevent its escape into the environment, harm to human health, and to ensure the compliance with the environmental law.
Guidance is available from the Environment Agency on how to comply with the waste management ‘duty of care’.
3. The following waste must be stored of separately from other wastes, as they are hazardous to the environment: refrigerants, polyurethane foam, and oils.
4. When arranging for disposal of waste, ensure a waste transfer note or consignment note is completed as appropriate. Ensure that all waste is correctly described on the waste note and include the appropriate six-digit code from the European Waste Catalogue. Your waste contractor or Foster can provide further information if necessary.
5. Ensure that all waste is removed by a registered waste carrier, a carrier in possession of a waste management licence, or a carrier holding an appropriate exemption. Ensure the person receiving the waste at its ultimate destination is in receipt of a waste management licence or valid exemption.
6. Handle and store refrigerants in such a way as to prevent their emission to atmosphere, and ensure they are disposed of safely and in accordance with environmental law.
7. Make arrangements to ensure all staff who handle refrigerants do so at a level of competence consistent with the City Guilds 2078 Handling Refrigerants qualification or equivalent qualification.
8. Ensure all liquid substances are securely stored to prevent leaks and spills, and are not disposed of into storm drains, foul drain, or surface water to soil.
Disposal Requirements
If not disposed of properly all refrigerators have components that can be harmful to the environment. All old refrigerators must be disposed of by appropriately registered and licensed waste contractors, and in accordance with national laws and regulations.
2
Cabinet Descriptions
All Ranges - The cabinets are manufactured as a one piece foamed shell with the condensing unit located on the base of the cabinet. All the cabinets conform to ISO Climate Class 4 (32
° c with 40% RH) and have their temperature controller by a LAE microprocessor controller with digital temperature display.
Undercounter - The doors are fitted with pivot hinges, integral door handle situated at the front centre and magnetic door gasket. All models are fitted with 4mm roller castors to the rear and M8 adjustable levelling bolts at the front.
On the glass door models the interior light is fitted to the top of the storage area at the front. The on/off switch is incorporated into the light.
Prep Tables
– The doors are the same as the above undercounter but these units also combine a worktop for food prep with a back section that holds pans for food with a hygienic stainless cover.
Space Savers
– Are the same as the undercounter range but as the title describes are made for the kitchen without a lot of space and or tight areas.
HR and LR 120, 200, 240 and 360 models refrigeration systems are integral with an air-cooled condensing unit.
The refrigerant is distributed into the evaporator which is controlled by a capillary. All these units have forced air cooling which is where the air is circulated through the evaporator, via the fan/s then into the storage area. The
HR150-A also have forced air cooling but instead the air is drawn over the evaporator and then in to the storage area.
The HR150-A refrigeration system is also integral with an air-cooled compressor and static condenser where the refrigerant is distributed into the evaporator controlled by a capillary.
The LR150-A model has static freezer shelves with circulation in the storage compartment by natural convection.
This means they also require manual defrosting.
The HR150-A, 200 and LR200 condensate vaporisation is provided by a self-contained condensation vaporiser tray attached to the top of the compressor.
The LR120, 200, 240 and 360 have electric defrost set at 4 times per 24 hours, whereas the HR120, 150-A, 200,
240 and 360 are on a timed off cycle defrost.
Bit25 Controller Introduction by Models
Model 1 st
Serial Number Issued Manufacturer Date from
100 (H - Burger King Only Spec)
120 (H,L & Broadway)
150-A (H&L)
200 & 200FT (H&L)
240 (H&L)
360 & 360FT (H&L)
Unknown
E5306481 & E5306484
E5307001
E530587 & E5305856
E5307002
November 2011
October 2011
October 2011
November 2011
October 2011
3
Controller Operation
The controller consists of two pieces, the controller & separate display. This two piece controller has the controller/PCB unit fitted at the rear of the cabinet with the display fitted into the front of the cabinet, interconnected by a ribbon cable.
BIT25 Controller PCB (00-556354)
LCD 5S Display (00-555992)
Controller Connection Cable (00-556415)
BIT25 Controller/PCB Cover/Housing (00-556361)
Probe Air T1 (00-556376)
Probe Evap T2 (00-556356)
LCD 5S Display (00-555992)
Indicators and Buttons
Symbol Reason Button Use
Alarm Info / Set Point Button
Thermostat Output Manual Defrost / Decrease Button
Fan Output Increase Button / Manual Activation
Defrost Output
Activation of 2 nd
parameter set
Exit/ Stand-by Button
Display
During normal operation the display shows either the temperature measured or one of the following indicators:
Symbol Reason
Defrost in progress
Controller in stand-by
Condenser clean warning
Door open alarm
Condenser high temperature alarm
Generic Alarm
Information Menu
The information available in the menu is shown below:
Symbol Reason
Condenser High Pressure Alarm
Internal High temperature Alarm
Internal Low Temperature Alarm
Probe T1 Failure
Probe T2 Failure
Symbol Reason
Instant probe 1 temperature
Instant probe 2 temperature *
Instant probe 3 temperature *
Maximum probe 1 temperature recorded
* Displayed only if enabled (see configuration parameters)
** Displayed only if ACC > 0
Symbol
4
Reason
Minimum probe 1 temperature recorded
Compressor working weeks **
Keypad state lock
User Functions
Start Sequence
When the unit is first connected to the mains the display will automatically light up and show either current ambient temperature.
To start or activate when in standby:
Press and hold the button for 5 seconds then release.
Access to the menu and information displayed
or the
Press and immediately release button
With button or select the data to be displayed
Press and hold button to display the value
To exit from the menu, press button or wait for 10 seconds.
Set point: Display and modification
Press button and hold to display the set point.
By keeping button pressed, use button or to set the desired value (adjustment is within the minimum SPL and the maximum SPH limit)
When button is released, the new value is stored.
Standby
When pressing the button for 3 seconds, will allow the controller to be put on a standby or output control to be resumed (with SB = YES only).
When on Standby
Keypad Lock
will be displayed.
The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controller is operating in a public place. In the INFO menu, set parameter = YES to inhibit all functions of the button.
To resume normal operation of keypad, adjust setting so that = NO.
Selection of second parameter group
It is possible to select control parameters between two different pre-programmed groups, in order for the fundamental control parameters to be adapted to changing needs. Changeover from Group I to Group II (and vice versa) may take place Manually by pressing
II°
for 2 seconds (with IISM = MAN), or Automatically when
IISM=D12 and the Auxiliary Input D12 is activated (the activation of D12 selects Group II). If IISM = NON, switchover to Group II is inhibited. The activation of Group II is signalled by the lighting up of relevant LED on the controller display.
Defrost
Automatic Defrost
– excluding LR150 & LR410
Defrost starts automatically as soon as the time set with parameter DFT has elapsed.
Time Defrost With DFM = TIM defrost takes place at regular intervals when the timer reaches the value
DFT. For example, with DFM = TIM and DFT = 06, a defrost will take place every 6 hours.
Optimized Defrost With DFM=FRO the timer is increased only when the condition for frost to form in the evaporator occurs. Once the DFT value is reached, defrost takes place. If the evaporator works at 0°C, defrost frequency depends on the thermal load and climatic conditions. With setpoints much lower than
0°C, defrost frequency mainly depends on the refrigerator operating time.
Defrost time count backup At the power
–up, if DFB = YES, the defrost timer resumes the time count from where it was left off before the power interruption. Visa versa with DFB=NO, the time count re-starts from
0. In stand-by the accumulated time count is frozen.
Defrost type
Once defrost has started, compressor and defrost outputs are controlled according to parameter DTY. If FID =YES, the evaporator fans are active during defrost.
5
Defrost Termination
Time termination
– T2=NO the evaporator temperature is not monitored and defrost will last as long as time DTO.
Temperature termination
– T2=YES In this case, if the sensor T2 measures the temperature DLI before the time
DTO elapses, defrost will be terminated in advance.
Resuming Thermostatic Cycle
When defrost is over, if DRN is greater than 0, all outputs will remain off the DRN minutes, in order for the ice to melt completely and the resulting water to drain. The fans will only re-start when the evaporator temperature is lower than FDD (if T2=YES), or after FTO minutes have elapsed.
Caution- if DFM=NON all defrost functions are inhibited; if DFT=0, automatic defrost functions are excluded; during a high pressure alarm or a DI1 (DI2) generic alarm, defrost is suspended; during defrost, high temperature alarm is bypassed.
Manual Defrost
-
‘LR150’ and ‘LR410’’ Freezer Shelves
To initiate a manual defrost press and hold the defrost button for 2 seconds.
All other ‘Under-Counter’ and ‘Space-Saver’ models are fitted with a fully automatic defrost system to ensure that the evaporator remains free from ice in normal use. Melt-water is evaporated using the heat from the refrigeration system.”
6
Controller Wiring Diagram, Dimensions & Technical Data
(Dimensions in mm)
Technical Data
Power Supply
BIT-
25…E
Relay Output
Compressor
230Vac±10%, 50/60Hz, 3W
20(8)A 240Vac
Auxiliary Loads 1
Auxiliary Loads 2
Input
NTC 10K
Ω@25°C
16(4)A 240Vac
7(2)A 240Vac
Measurement Range
--50 / -
9.9…19.9 /110°C
Measurement Accuracy
<0.5°C within the measurement range
7
Operating Conditions
-
10…+50°C; 15%...80%r.H
CE (Reference norms)
EN60730-1; EN60730-2-9
EN55022 (Class B)
EN50082-1
Configuration Parameters
To get access to the parameter configuration menu, press + for 5 seconds
With button or select the parameter to be modified.
Press button and hold briefly to display the value. On releasing the button the controller will then show the next parameter.
By keeping button pressed, use button or to set the desired value. On releasing the button the controller will store the amended value and then show the next parameter.
To exit from the setup, press button or wait for 30 seconds.
Default Controller Parameter Settings
Parameter:
SPL
SPH
SP
Range: Description:
-
50 … SPH
Minimum limit for 'SP' setting.
S
PL … 110 o
Maximum limit for 'SP' setting.
SPL … SPH
Temperature setpoint to be achieved.
C-H
HYS
CRT
CT1
REF - HEA
1 … 10 o
0 … 30 min
0 … 30 min
Refrigeration or Heating control mode.
Off / On thermostat differential.
Compressor rest time.
Thermostat run time with faulty T1 probe.
('CT1' = 0 output with faulty T1 will always be off).
CT2
CSD
DFM
DFT
DFB
DLI
DTO
DTY
DPD
DRN
DDM
0 … 30 min
0 … 30 min
Thermostat off time with faulty T1 probe.
('CT2' = '0' & 'CT1' =>'0' output with faulty T1 will always be on).
Compressor stop delay after door has been opened.
(Only if 'DS' = 'YES').
NON
TIM
Defrost start mode:
Defrost function is disabled (the following parameter will be 'FCM').
Regular time defrost.
FRO Defrost time elapses only in condition of frost accumulation.
0 … 99 hours
Time interval between defrosts.
YES
NO
Defrost timer clock.
Following mains interruption, timer resumes count.
Following mains interruption, timer restarts from zero.
-
50 … 110 o
Defrost end temperature
(Only if 'T2' = 'YES').
1 … 120 min
Maximum defrost duration.
Defrost type:
OFF
ELE
Timed off cycle defrost (compressor and heater off).
Electric heater defrost (compressor off, heater on).
GAS Hot gas defrost (compressor and heater on).
0 … 240 sec
Evaporator pump down. Timed pause at start of defrost.
0 … 30 min
Drain down period.
RT
LT
Defrost display mode:
Real (actual) air temperature.
Last temperature display before start of defrost.
SP
DEF
The current setpoint value.
"DEF"
Default
1
3
2
REF
3
2
6
4
1
TIM
6
YES
15
20
OFF
0
2
DEF
DDY
FID
FDD
FTO
FCM
FDT
FDH
FDS
FT1
FT2
FT3
ATM
ALA
AHA
ALR
AHR
ATI
ATD
ADO
0 … 60 min
-
YES
NO
50 … 110
NON o
0 … 120 min
TMP
TIM
Defrost display delay period.
Time 'DDM' is shown following defrost termination.
Fans in defrost:
Fans run during defrost.
Fans do not run during defrost.
Evaporator fan restart temperature following defrost.
(Only if 'T2' = 'YES').
Maximum evaporator fan stop period following defrost (only when
'T2' = 'YES').
Evaporator fan mode during thermostatic control:
Fan(s) run continuously (subject to door & defrost).
Temperature based control. When compressor is on, fans are on. When compressor is off, fans run as long as temperature difference Te-Ta > 'FDT'. Fans on again with 'FDH'.
Time based control. When compressor is on, fans are on.
When compressor is off, fans in accordance to parameters
FT1', 'FT2' and 'FT3'.
-
12.0 … 0 o
Te-Ta difference for fans to turn off after compressor stopped.
(Only if 'T2' = 'YES' and 'FCM' = 'TMP').
1 … 12.0
o
Temperature differential for evaporator fan restart.
(Only if 'T2' = 'YES' and 'FCM' = 'TMP').
0 … 120 sec
Minimum evaporator fan stop period (following door opening etc.).
0 … 180 sec
Fan stop delay after compressor stop.
0 … 30 min
Timed fan stop following 'FT1'.
(With FT2 = '0' the fans remain on all the time).
0 … 30 min
NON
Timed fan run following 'FT2'.
(With 'FT3' = '0' & 'FT2' > '0' the fans remain off all the time).
Alarm threshold configuration:
All temperature alarms are inhibited (the following parameter will be
'ADO').
The value set in 'ALA' & 'AHA' represent actual alarm setpoints. ABS
REL
The values set in 'ALR' & 'AHR' are alarm differentials which relate to 'SP' and 'SP' + 'HYS' (the following parameter will be 'ALR').
-
-
50 … 120
50 … 120 o o
Low temperature alarm threshold.
High temperature alarm threshold (the following parameter will be
'ATI').
Low temperature alarm differential.
-
12 … 0 o
(With 'ALR' = '0' the low temperature alarm is excluded).
High temperature alarm differential.
0 … 12 o
(With 'AHR' = '0' the low temperature alarm is excluded).
Alarm probe:
T1 Air temperature probe used for alarm detection.
T2
Evaporator temperature probe used for alarm detection (if 'T2' =
'YES').
T3
Third temperature probe used for alarm detection (if 'DI2' = 'T3').
0 … 120 min
Delay before alarm temperature warning.
0 … 30 min
Delay before door open alarm warning (only when 'DI2' = 'DOR').
10
YES
NON
-1
2
REL
-3
8
-5
5
T1
90
8
3
20
15
0
5
3
9
AHM
AHT
ACC
IISM
SB
IISL
IISH
IISP
IIHY
IIFC
IIDF
NON
ALR
STP
-
50 … 110 o
Operation in case of high condenser alarm (if 'DI2' = 'T3' and 'T3' =
'CND' ):
High condenser temperature alarm inhibited.
Condenser warning - 'HC' displayed, alarm sounds.
As 'ALR', with compressor stopped and defrosts suspended.
Condenser alarm temperature (if 'DI2' = 'T3').
0 … 52 weeks
Condenser cleaning period.
(With 'ACC' = '0' condenser cleaning alarm is disabled).
NON
MAN
Switchover method to second parameter set:
Second parameter set is excluded (the following parameter will be
'SB').
Second parameter set is activated / deactivated by button 'M'.
DI2 Second parameter set activated by 'DI2' input ('DI2' = 'IISM').
-
50 … IISH
Minimum limit for 'IISP' setting.
IISL … 110 o
Maximum limit for 'IISP' setting.
IISP … IISH
Temperature setpoint to be achieved in 'Mode 2'.
1 … 10 o
Off / On thermostat differential in 'Mode 2'.
Evaporator fan mode during 'Mode 2' thermostatic control:
NON
TMP
Fan(s) run continuously.
Temperature based control. When compressor is on, fans are on.
When compressor is off, fans run as long as temperature difference
Te-Ta > 'FDT'. Fans on again with 'FDH'.
Time based control. When compressor is on, fans are on.
When compressor is off, fans in accordance to parameters TIM
FT1', 'FT2' and 'FT3'.
0 … 99 hours
Time interval between defrosts in 'Mode 2'.
YES
Standby button operation:
Standby button enabled.
DI1
NO
NON
DOR
ALO
ALC
NON
Standby button disabled.
Configurable digital input operation:
Digital input not activated.
Door switch input.
Alarm ('ALr' displayed) when contact opens.
Alarm ('ALr' displayed) when contact closes.
Configurable digital input operation:
Digital input not activated.
DI2
DOR
ALO
ALC
PSP
IISM
T3
DSP
Door switch input.
Alarm ('ALr' displayed) when contact opens.
Alarm ('ALr' displayed) when contact closes.
Allows control via potentiometer.
Operates 2 nd
parameter set when contact closes.
Allows for 3 rd
temperature probe function.
T3 probe function (only when 'DI2' = 'T3'):
T3 probe temperature displayed. T3
CND Condenser temperature measurement.
OS3 -
12.5 … 12.5
o
C T3 probe temperature offset (only when 'DI2' = 'T3'):
NON
65
0
NON
1
1
1
3
NON
6
YES
NON
NON
DSP
0
10
PSL
PSR
POF
LSM
OA1
OA2
OS1
-
50 … 70
NO
NON
MAN
D1O
D2O
D2C
NON
FAN o
0.0 … 15.0
YES
DEF
C o
C
Minimum setpoint adjusted by potentiometer (only when 'DI2' =
'PSP'):
Range of setpoint (hysteresis) for potentiometer (only when 'DI2' =
'PSP'):.
Potentiometer standby enabling operation (only when 'DI2' = 'PSP'):
Potentiometer standby enabled (when turned to minimum, controller set to standby).
Potentiometer standby disabled.
Light control mode (if 'OA1' = 'LGT'):
Light Control Mode disabled (always off).
Light output operation is activated / deactivated by button 'M'.
Light output is switched on when door is opened (if 'DI1' = 'DOR').
Light output is switched on when door is opened (if 'DI2' = 'DOR').
Light output is switched off when door is opened (if 'DI2' = 'DOR').
Auxiliary Relay 1 Operation:
Output disabled (always off).
Control of evaporator fan.
Control of defrost heater / device (activated when 'DTY' = 'ELE' or
'GAS').
Output enabled for light control. LGT
0-1
ALO
ALC
Contacts open/close with 'Standby'/'On' mode ('SB' = 'YES').
Contacts open when an alarm condition occurs.
Contacts close when an alarm condition occurs.
(Relay contacts open when in standby mode).
Auxiliary Relay 2 Operation:
NON Output disabled (always off).
FAN
DEF
Control of evaporator fan.
Control of defrost heater / device (activated when 'DTY' = 'ELE' or
'GAS').
Output enabled for light control. LGT
0-1
ALO
ALC
Contacts open/close with 'Standby'/'On' mode ('SB' = 'YES').
Contacts open when an alarm condition occurs.
Contacts close when an alarm condition occurs.
(Relay contacts open when in standby mode).
-
12.5 … 12.5
o
C Air temperature probe (T1) offset.
T2 probe enabling:
T2
OS2
TLD
SCL
SIM
ADR
YES T2 probe enabled.
NO T2 probe disabled.
-
12.5 … 12.5
o
C Evaporator temperature probe (T2) offset.
1 … 30 min
Delay for min. ('TLO') and max. ('THI') temperature logging.
1 o
C
2 o
C o
F
0 … 100
1…255
Readout scale:
Range -5
0 …. 110 o
C (0.1
o
C resolution within -9.9 to +19.9
o
C)
Range -
50 …. 110 o
C
Range -
58 …. 180 o
F
Display slowdown.
BIT25 address for PC communication
11
2
10
10
YES
MAN
NON
FAN
0
NO
0
10 o
C
5
1
Individual Model Parameter Settings
Parameter Description:
CSD
DFM
DFT
DFB
DLI
DTO
DTY
DPD
SPL
SPH
SP
C-H
HYS
CRT
CT1
CT2
DRN
DDM
DDY
FID
FDD
FTO
Minimum limit for 'SP' setting.
Maximum limit for 'SP' setting.
Temperature setpoint to be achieved.
Refrigeration / heating control mode.
Off / On thermostat differential.
Compressor rest time.
Thermostat run time with faulty T1 probe.
Thermostat off time with faulty T1 probe.
Compressor stop delay after door has been opened.
Defrost start mode.
Time interval between defrosts.
Defrost timer clock.
Defrost end temperature
Maximum defrost duration.
Defrost type.
Evaporator pump down. Timed pause at start of defrost.
Drain down period.
Defrost display mode.
Defrost display delay period.
Fans in defrost.
Evaporator fan restart temperature following defrost.
Maximum evaporator fan stop period following defrost (only when 'T2' =
'YES').
1
3
2
A
3
3
3
B
3
3
3
C
-21
-21
-21
D
1
3
1
E
1
3
1
F
0
10
3
G
-21
-19
-21
H
-21
-19
-21
REF
REF REF REF REF REF REF REF REF
3
3 3 3 3 3 3 3 3
2
6
4
6
4
6
4
6
2
6
2
6
4
6
2
6
2
6
4
1
TIM
6
4
1
TIM
6
4
1
TIM
6
4
1
NON
6
4
1
TIM
6
4
1
TIM
6
4
1
TIM
4
4
1
TIM
6
4
1
TIM
6
YES
YES YES YES YES YES YES YES YES
15
20
15
10
15
10
15
20
15
10
15
10
10
20
15
20
10
10
OFF
OFF OFF OFF OFF OFF OFF ELE ELE
0
0 0 0 0 0 0 0 0
2
3 3 2 2 2 3 2 2
DEF
DEF DEF DEF DEF DEF DEF DEF DEF
10
10 10 10 10 10 10 10 10
YES
YES YES NO YES YES YES NO NO
5
5 5 5 5 5 5 5 5
3
3 3 3 3 3 3 3 3
IISP
IIHY
IIFC
IIDF
SB
DI1
DI2
T3
ATD
ADO
AHM
AHT
ACC
IISM
IISL
IISH
OS3
PSL
PSR
FCM
FDT
FDH
FDS
FT1
FT2
FT3
ATM
ALA
AHA
ALR
AHR
ATI
Evaporator fan mode during thermostatic control.
Te-Ta difference for fans to turn off after compressor stopped.
Temperature differential for evaporator fan restart.
Minimum evaporator fan stop period (following door opening etc.).
Fan stop delay after compressor stop.
Timed fan stop following 'FT1'.
Timed fan run following 'FT2'.
Alarm threshold configuration.
Low temperature alarm threshold.
High temperature alarm threshold (the following parameter will be 'ATI').
Low temperature alarm differential.
High temperature alarm differential.
Alarm probe.
NON
-1
3
20
15
NON
-1
3
20
15
NON NON NON
-1
3
20
15
-1
3
20
15
-1
3
20
15
NON
-1
3
20
15
NON
-1
3
20
15
NON NON
-1
3
20
15
-1
3
20
15
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
REL
REL REL REL REL REL REL REL REL
-3
-3 -3 -3 -3 -3 -3 -3 -3
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
8
-5
5
T1
Delay before alarm temperature warning.
Delay before door open alarm warning (only when 'DI2' = 'DOR').
90
8
90
8
90
8
90
8
90
8
90
8
90
8
90
8
90
8
Operation in case of high condenser alarm (if 'DI2' = 'T3' and 'T3' = 'CND' ):
NON
NON NON NON NON NON NON NON NON
Condenser alarm temperature (if 'DI2' = 'T3').
65
65 65 65 65 65 65 65 65
Condenser cleaning period.
Switchover method to second parameter set.
Minimum limit for 'IISP' setting.
Maximum limit for 'IISP' setting.
0
0 0 0 0 0 0 0 0
NON
NON NON NON NON NON NON NON NON
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Temperature setpoint to be achieved in 'Mode 2'.
Off / On thermostat differential in 'Mode 2'.
Evaporator fan mode during 'Mode 2' thermostatic control.
Time interval between defrosts in 'Mode 2'.
Standby button operation.
Configurable digital input 1 operation.
Configurable digital input 2 operation.
T3 probe function (only when 'DI2' = 'T3').
T3 probe temperature offset (only when 'DI2' = 'T3').
Minimum setpoint adjusted by potentiometer (only when 'DI2' = 'PSP').
Range of setpoint (hysteresis) for potentiometer (only when 'DI2' = 'PSP').
1
3
6
0
2
10
1
3
NON
NON NON NON NON NON NON NON NON
6
YES
YES YES YES YES YES YES YES YES
NON
NON NON NON NON NON NON NON NON
NON
NON DOR NON NON DOR NON NON NON
DSP
DSP DSP DSP DSP DSP DSP DSP DSP
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
1
3
6
0
2
10
13
POF
LSM
OA1
OA2
OS1
Potentiometer standby enabling operation (only when 'DI2' = 'PSP').
Light control mode (if 'OA1' = 'LGT').
Auxiliary Relay 1 Operation.
Auxiliary Relay 2 Operation.
Air temperature probe (T1) offset.
T2
OS2
TLD
SCL
T2 probe enabling.
Evaporator temperature probe (T2) offset.
Delay for min. ('TLO') and max. ('THI') temperature logging.
Readout scale.
SIM Display slowdown.
ADR BIT25 address for PC communication.
Yellow values highlight a difference from the controllers default setting.
YES
YES YES YES YES YES YES YES YES
NON
NON D2C NON NON D2C NON NON NON
NON
NON LGT NON NON LGT NON DEF DEF
FAN
FAN FAN FAN FAN FAN FAN FAN FAN
0
0 0 0 0 0 0 0 0
NO
NO
0
NO
0
NO
0
NO
0
NO
0
NO
0
YES
0
YES
0
0
10
2 o
C
2
10 o
C
10 10 10 10 10
2 o
C 2 o
C 2 o
C 2 o
C 2 o
10 10
C 2 o
C 2 o
C
5
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1
14
Wiring Diagram
– All models (including with light option)
15
Troubleshooting
Problem
Compressor will not start
The temperature is too cold
The temperature is not cold enough
Possible Cause
No voltage in socket
Electrical conductor or wires may be cut
Defective electrical component: thermostat, relay, thermal protector etc.
Solution
Use voltmeter to check
Use ohmmeter to check for continuity
Replace defective component
Compressor motor has a winding open or shorted
Measure ohmic resistance of main and auxiliary winding using ohmmeter. Compare with correct values
Change compressor Compressor stuck
Temperature control contacts are open
Incorrect wiring
Fuse blown or circuit breaker tripped.
Power cord unplugged
Controller set too high
Cabinet in defrost cycle
Controller is set at a very cold position
Controller does not disconnect the condensing unit
Control contacts are stuck closed
Defective or incorrect temperature control
Controller is set at a very warm position
Repair or replace the contacts
Check wiring diagram and correct
Replace fuse or reset circuit breaker
Plug in power cord.
Set controller to lower temperature.
Wait for defrost cycle to finish
Set to warmer position and check if the compressor stops according to controllers operating range.
Check the insulation of the thermostat. If problem persists, change the thermostat
Change the control. Check amperage load
Determine correct control and replace.
Adjust to colder setting
Condenser is dirty
The refrigerator has been placed at an inadequate location
Compressor is inefficient or there is a high pressure due to the air in the system
Iced up evaporator coil
Restriction in system
The refrigerator has been used improperly
Too many door openings
Clean condenser
The unit must not be near stoves, walls that are exposed to the sun, or places that lack sufficient air flow.
If there is air in the system, purge and recharge
Check temperature control, refrigerant charge, and defrost mechanism. Remove all ice manually and start over.
Locate exact point of restriction and correct
The shelves must never be covered with any type of plastic or other material that will block the circulation of cold air within the refrigerator.
Advise user to decrease if possible
16
Electrical Shocks
Noise
Extreme condensation inside the refrigerator
No illumination (Glass door models only)
Excessive heat load placed in cabinet
The refrigerator has been overcharged with the refrigerant gas
The refrigerant gas is leaking
The evaporator and/or condenser fans are not working
Blocking air flow
Fuse blown or circuit breaker tripped
Wires or electrical components are in direct contact with metallic parts.
Advise user not to put in products that are too hot.
Check to see if condensation or ice crystals have formed on the suction line. If so, charge with the correct amount of gas.
Find the location of gas leak in order to seal and replace the defective component. Change the drier.
Perform a good vacuum and recharge unit.
Check electrical connections and make sure that the fan blade isn’t stuck. Replace the fan motor if it doesn’t work.
Re-arrange product to allow for proper air flow. Make sure there is at least four inches of clearance from evaporator.
Replace fuse or reset circuit breaker.
Check for appropriate insulation on the connections of each component.
The refrigerator is not properly levelled
The condenser is not fastened correctly. Copper tubing is in contact with metal
The evaporator and/or condenser fans are loose
Compressor has an internal noise
Loose part(s)
Controller is set at a very cold position
The outside environment’s relative humidity is very high (over 75%)
The refrigerator door won completely
’t shut
The refrigerator had been placed at an inadequate location
The light switch is “off” position
Check if the noise goes away after you level the refrigerator
While the compressor is working, check to see if metal parts are in contact with one another and/or if the screws that fasten the condenser are tightened.
Check if the fans are securely fastened. Also, check if the fan blades are loose, broken or crooked.
If so, change the faulty blade.
If the noise persists after all other measures have been taken, it may be originating from the compressor.
Locate and tighten loose part(s)
Set the controller to a warmer position & check to see if compressor stops as should.
This type of occurrence is caused by local climatic conditions and not by the refrigeration unit.
Check the door and/or the magnetic gasket. Adjust the door hinges if needed; replace the gasket if broken.
The unit must not be near sources that produce too much heat.
Press the light switch to “on” position
False contact on the light switch, the fluorescent tube, or the ballast
Light switch, ballast and/or fluorescent tube are damaged
Inspect all connections
Replace the damaged component.
17
Condensing unit runs for long periods of time
Excessive amount of warm product placed in cabinet
Prolonged door opening or door ajar
Door gasket(s) not sealing properly
Advise user to leave adequate time for products to cool down
Advise user to ensure doors are closed when not in use and to avoid opening doors for long periods of time.
Ensure gaskets are snapped in completely. Remove gasket and wash with soap and water. Check condition of gasket & replace if necessary
Dirty condenser coil Clean condenser coil
Evaporator coil iced over
Unplug unit and allow coil to defrost.
Make sure thermostat is not set too cold. Ensure that door gasket(s) are sealing properly. Select manual defrost and ensure system works.
Notes
18
Foster European Operations
France
Foster Refrigerator France SA
Tel: (33) 01 34 30 22 22. Fax: (33) 01 30 37 68 74.
Email: [email protected]
Germany
Foster Refrigerator Gmbh,
Tel: (49) 781 990 7840. Fax (49) 781 990 7844.
Email: [email protected]
Foster Refrigerator
Oldmedow Road
Kings Lynn
Norfolk
PE30 4JU
Tel: 0843 216 8833
Fax: 0843 216 4707
Website: www.fosterrefrigerator.co.uk
Email: [email protected] a Division of ‘ITW (UK) Ltd’
UNDERCAB/BIT25/SM 12/11
19

Download
Advertisement
Key features
One piece foamed shell
Condensing unit on the base
ISO Climate Class 4
Microprocessor controller with digital display
Pivot hinges
Integral door handle
Magnetic door gasket
4mm roller castors
Adjustable leveling bolts
Interior light (glass door models)
Frequently asked questions
These cabinets conform to ISO Climate Class 4 (32°C with 40% RH).
These cabinets use a LAE microprocessor controller with digital temperature display.
Most models have automatic defrost systems, while some like the LR150-A require manual defrosting.