Below you will find brief information for Breathing Air Panel BA100BA-S1. The Breathing Air Panel BA100BA-S1 is a four-stage filtration system designed to remove or reduce select contaminants found in compressed air lines while monitoring for carbon monoxide through the CO monitor. The panel can be connected directly to shop air from a standard compressed air source to help provide breathing quality air to face masks, helmets, hoods, and other supplied air breathing apparatus. The panel includes a pressure regulator to adjust air pressure going to the respirator, as well as a carbon monoxide monitor, which continuously checks the carbon monoxide levels per OSHA/CSA requirements and displays the amount present in PPM (parts per million). An audible alarm/strobe will alert operators if levels of carbon monoxide exceed OSHA/CSA requirements.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Breathing Air Panel BA100BA-S1 Service Manual | Manualzz

SERVICE MANUAL

MODEL BA100BA-S1

BREATHING AIR PANEL

******************************************************************************

WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device.

******************************************************************************

10/11

2

GENERAL OPERATION MANUAL

WARNING: The MST Breathing Air Panel Models

:

1) WILL NOT remove Carbon Monoxide.

2) SHALL NOT be used when the air entering the filtering system is oxygen deficient. The

MST Breathing Air Panel will not increase the oxygen content of the air.

3) SHALL NOT be used in an Immediately Dangerous to Life and Health Atmosphere

(IDLH) unless it is used in conjunction with a Back-Up Escape system or a supplied air

Self-Contained Breathing Apparatus (SCBA), where applicable.

4) CARBON MONOXIDE MONITOR will alarm if Carbon Monoxide levels exceed requirements for Grade "D" Breathing Air set forth by OSHA/CSA. If alarm should sound, remove respirator or activate SCBA and immediately move to safe breathable atmosphere. Have the proper qualified personnel examine the equipment and make the appropriate corrections before using again.

5) SHALL NOT have air inlet pressure greater than 150 PSIG static (10.4bar). Personal injury could result.

6) SHALL NOT have air outlet pressure that exceeds Manufacturers' Respirator/Hose

Assembly pressure requirements. Personal injury could result.

The MST Breathing Air Panel is a Four Stage Filtration System designed to remove or reduce select contaminates found in compressed air lines while monitoring for carbon monoxide through the CO

Monitor. The Breathing Air Panel can be connected directly to shop air from a standard compressed air source to help provide breathing quality air to face masks, helmets, hoods and other supplied air breathing apparatus.

3

GENERAL FILTER SYSTEM DESCRIPTION

(Refer to Figure No.1)

Air entering the MST Breathing Air Panel at the inlet (A) is usually contaminated with oil, water, dirt, rust, scale and gaseous Hydrocarbons. As the air passes through the First Stage (B) of the MST

Prefilter, particulate matter is trapped and retained down to 0.3 microns. The air then enters the

Second Stage (C) of the Prefilter which coalesces liquid contaminates down to 0.75 microns with an efficiency rating of 99.97% (meets Underwriters Laboratories Specification UL 586 for High

Efficiency, Particulate, Air Filter Units). The liquid contaminates are trapped in the lower chamber of the prefilter and expelled out through the Automatic Float Drain (D). The Third and Fourth

Stages (E & F) contain a deep bed of odor absorbing activated charcoal which collects various gaseous Hydrocarbons (such as oil fumes, benzene, etc.). The air is then passed through the Air

Pressure Regulator (G), which is used to adjust the air pressure going to the respirator. A sample of the filtered air is taken at (H) and passed through the Carbon Monoxide Monitor (I). The Carbon

Monoxide Monitor continuously checks the carbon monoxide levels per OSHA/CSA requirements and digitally displays the amount present in PPM, (parts per million). An audible alarm/strobe will alert operators if levels of carbon monoxide exceed OSHA/CSA requirements.

FIGURE NO.1

4

GENERAL INSTRUCTIONS

The MST Breathing Air Panel, a compressed air purifier, when used in accordance with the following instructions, will remove or reduce selected contaminants from compressed air lines.

******************************************************************************

WARNING:

The MST Breathing Air Panels should not be used when the air entering the

filter is oxygen deficient (air with a low oxygen content). The MST Breathing Air Panel will not increase the oxygen content of oxygen deficient air.

******************************************************************************

MST, Inc. strongly recommends that a complete safety program be initiated to ensure that the respiratory air is in compliance with all OSHA standards and other applicable laws regulating the use of supplied air respiratory systems. MST, Inc. recommends that the air quality be tested upon installation and periodically re-tested to ensure that the minimum requirements for breathing air are maintained.

******************************************************************************

WARNING:

The MST Breathing Air Panels will not remove Carbon Monoxide.

******************************************************************************

The Carbon Monoxide Monitor in the Breathing Air Panel Model BA100BA-S1 is a standard nonintrinsically safe version. For purposes of this paragraph, "non-intrinsically safe" monitor is defined as one which must not be used in explosive atmospheres. Refer to the Monitor Information Manual for charging, calibration, and operating instructions. MST, Inc. will not assume any liability for accidents or personal injury resulting from the improper use of this equipment. Service on this equipment should only be performed by qualified personnel.

This system is to be used only by trained qualified personnel in accordance with a respirator program as outlined in OSHA Regulation 29 CFR 1910.134(b).

The air supply entering The MST Breathing Air Panel must meet two (2) criteria to ensure maximum efficiency of the MST filter system:

1) Temperature range should be between 68-150 o

F (20-65 o

C)

2) Liquid size range should be between 2-8 microns.

Conditioning equipment may be necessary, prior to the filter, to achieve this temperature range and bulk liquid removal.

5

******************************************************************************

WARNING:

Maximum pressure supplied to this unit IS NOT to exceed 150 PSIG. Personal

injury could result.

******************************************************************************

The Regulator 80075 is used to adjust the air pressure supplied to the operator(s) to maintain the correct air exchange inside the mask. Consult instructions on your particular breathing mask or hood for pressure requirements per NIOSH.

******************************************************************************

WARNING:

DO NOT Exceed mask and hose assembly manufacturer's requirements for

outlet pressure. Personal injury could result.

******************************************************************************

The filter cartridges used in the Breathing Air Panel Model BA100BA-S1 have an average life expectancy of (1) one month, (depending on the quality of the air in your compressed air lines) under normal conditions. MST, Inc. recommends changing all three (3) filter cartridges after one month of use unless conditions warrant more or less frequent replacement.

******************************************************************************

WARNING: If the Monitor's alarm should sound, remove mask or hood immediately and move to a safe breathable atmosphere. Have a proper qualified personnel examine the equipment and make the appropriate corrections before using again.

******************************************************************************

The Carbon Monoxide Alarm will sound to alert the operator that a problem has developed. The

Monitor Alarm will sound due to one or more of the following conditions:

A) Carbon Monoxide levels exceeding a pre-determined alarm set level is passing through the

Breathing Air Panel. The Breathing Air Panel does not remove or reduce the Carbon Monoxide content in the compressed air. Examine the air compressor, the air compressor intake air quality, and the complete system. Have the proper qualified personnel make the appropriate corrections before using again.

B) Monitor out of Calibration. Calibrate Carbon Monoxide Monitor as outlined in the Monitor

Information Manual.

C) The monitor's carbon monoxide sensor may be bad. See the Monitor Manual for further maintenance on monitor.

6

AIR SAMPLE TO

MONITOR ADJUSTMENT

******************************************************************************

WARNING : SERIOUS INJURY could result if the AIR SAMPLE METERING VALVE is not properly adjusted. Proper sample air flow to ‘CO’ monitor is required for monitor to give correct ‘CO’ level readout.

******************************************************************************

AIR SAMPLE METERING VALVE ADJUSTMENT

A) Pressurize system and set regulator for proper air flow to respirator(s).

B) Adjust Air Sample Metering Valve’s adjustment knob so the black floating ball is within the

GREEN BOXED area etched on valve body. Proper air sample is now being metered to the

‘CO’ Monitor. Periodically check to be sure ball is floating in this area.

7

SERVICE INSTRUCTIONS

(Refer to Figure No.2)

******************************************************************************

WARNING:

Always turn off air supply and bleed air pressure before disassembling unit or

SERIOUS INJURY COULD RESULT.

******************************************************************************

MST, Inc. recommends replacing all three (3) filter cartridges after one (1) month of use unless conditions warrant more or less frequent replacement. To refill or replace the filter cartridges in the

Breathing Air Panels, follow these steps:

1. PREFILTER FIRST/SECOND DUAL STAGE ELEMENT REPLACEMENT

A) First unscrew Prefilter bowl Assembly (2). Clean in mild soap and water and blow dry with low pressure air.

B) Remove Dual Stage Element (3) by unscrewing End Cap Retaining Nut (4) .

C) Inspect the Prefilter Manifold (5) for dirt/contaminates and clean as required. Inspect "O"-

Ring (6) for cuts, etc. and replace if required.

D) Install new Dual Stage Element and tighten End Cap Retaining Nut. Be sure Element is seated squarely on Manifold boss and End Cap.

E) Apply light film of petroleum jell on Bowl's beveled edge to provide good seal between Bowl

and "O"-Ring. HAND TIGHTEN ONLY.

F) Dispose of used Dual Stage Element according to local, state and federal regulations.

2. THIRD/FOURTH STAGE CARTRIDGE REPLACEMENT

A) Loosen Bracket Screw (7) from Bracket (8) .

B) Loosen the five Manifold Bolts (9) and remove the front two Bolts. Now slide out the

Third (10) and Fourth (11) Stage Aluminum Tube Assemblies.

C) Remove the End Cap (12) from Third Stage Aluminum Tube Assembly and slide old Third

Stage Filter Cartridge (13) out of aluminum tube. Clean aluminum tube in mild soap and

water, dry and install new Third State filter cartridge. Be sure the Flow Direction Arrow on

Third Stage Filter Cartridge is pointing down. Remove End Sealing Label (14) and install

new End Cap.

D) Follow same procedure for the Fourth Stage Filter Cartridge (15) replacement as in step (C).

Be sure the Flow Direction Arrow on Fourth Stage Filter Cartridge is pointing up. Also be sure to remove End Sealing Label before installing new End Cap.

E) Now slide the Third and Fourth Stage Aluminum Tube Assemblies back in place and

install the front two Manifold Bolts.

F) Tighten Manifold Bolts in sequence from center outward to 100 inch-pounds (1.15 Kg-M).

Repeat sequence and re-torque bolts to 250 inch-pounds (2.88 Kg-M).

G) Dispose of used cartridges according to local, state and federal regulations.

8

3. FINAL CHECK AND CALIBRATION

A) Pressurize system and check for leaks.

B) Flush system with compressed air for five (5) minutes.

C) Calibrate Carbon Monoxide Monitor as outlined in Monitor Information Manuals.

FIGURE NO.2

9

RECORD KEEPING

Record all periodical air quality checks, monitor calibration dates, filter cartridge change intervals and any other service performed on the MST Breathing Air Panel.

MST INC. SHALL NOT BE LIABLE FOR ANY INJURY, LOSS OR DAMAGE, (DIRECT

OR CONSEQUENTIAL), ARISING OUT OF THE USE OF OR THE INABILITY TO USE

THIS PRODUCT, BEYOND THE REPLACEMENT Of DEFECTIVE MATERIALS OR

WORKMANSHIP. USER OF SUPPLIED AIR RESPIRATORS SHOULD EVALUATE

THEIR OWN PARTICULAR APPLICATION AND PERFORM THEIR OWN TESTS FOR

AIR QUALITY TO DETERMINE THE SUITABILITY FOR USE OF THIS PRODUCT.

For further information, or questions about service or maintenance care of this unit, contact your local distributor or MST, Inc. at (800) 542-6646.

10

MST, INC.

SERVICE RECORD

BREATHING AIR PANEL MODEL BA100BA-S1

DATE OF SERVICE SERVICE PERFORMED

12

SPECIFICATIONS

BREATHING AIR PANEL

MODEL BA100BA-S1

INLET PRESSURE (MAX.) 150 PSIG STATIC (10.4 BAR)

RATED AIR FLOW (MAX.) 100 SCFM (47.2L/s)

OPERATING PRESSURE 100 PSIG DYNAMIC (6.9 BAR)

OUTLET PRESSURE RANGE 0-125 PSIG (0-8.6 BAR)

OPERATING TEMP. RANGE 68-150

O

F (20-65

O

C)

OUTSIDE DIMENSIONS 24" L x 24" W x 5.5"

(610 mm x 610 mm x 140 mm)

WEIGHT (LESS MONITOR) 25 LBS. (11.3 Kg.)

REPLACEMENT FILTER SET FB100

13

BREATHING AIR PANEL

MODEL BA100BA-S1 PARTS

3

4

1

2

80347, (1), 3/4" BALL VALVE

S608-009, (2), HEX N IPPLE -3/4"

8 01 04 , (1 ), P RE FIL TE R-1 00 SC FM

80051, (1), TUBE LOCKING COLLAR

7

8

9

5

6

S711-020, (1), DRAIN TUBE

80001, (1), BLUE BASE

80005, (1), A1 TUBE THIRD STAGE

80005, (1), AL TUBE FOURTH STAGE

80114, (1) BASE BRACKET

10 80083, (1), BLUE MAN IFOLD

11 80009, (1), MANIFOLD BRACKET

12 S006-148, (3), BRACKET BOLTS

13 S011-040, (5), MAN IFOLD BOLT S

14 12021, (5), MANIFOLD W ASHERS

15 S608-008, (2), HEX N IPPLE - 1/2"

16 80348, (1), CROSS - 1/2"

17 S638-008, (1), 1/2" X 1/4" HEX BUSHING

18 80014, (1), PRESSURE RELIEF VALVE

19 S623-004, (1),1/2" x 90 o

ST. ELBOW

20 S638-008, (1), 1/2" x 1/4" HEX BUSHING

21 S608-002, (1), 1/8" x 1/4" HEX NIPPLE

22 80213, (1), FLOWMETER

23 80261, (1) 90

O

TUBE LOCK FITTING

24 80076, (1), PRESSURE GUA GE, 0-160

25 80075, (1), REGULATOR

26 80077, (1), OTOX 2002 MONITOR

27 8066901, (1), REMOTE ALARM/STROBE

28 80111, (1), MOUNTING BO ARD

advertisement

Key Features

  • Four-stage filtration
  • CO Monitor
  • Pressure regulator
  • Automatic drain
  • Alarm/strobe
  • Replaceable filter cartridges
  • OSHA/CSA compliant
  • Direct connection to shop air
  • Provides breathing quality air
  • Easy to install and maintain

Frequently Answers and Questions

How does the Breathing Air Panel work?
The Breathing Air Panel consists of a four-stage filtration system to remove contaminants. It includes a prefilter for particulate matter, a coalescer for liquid contaminants, activated carbon for gaseous hydrocarbons, and a carbon monoxide monitor to alert operators of dangerous levels of CO in the air.
What types of contaminants does the panel remove?
The panel is designed to remove oil, water, dirt, rust, scale, gaseous hydrocarbons, and carbon monoxide. It does not remove oxygen deficiency.
How often should I replace the filter cartridges?
MST, Inc. recommends replacing all three filter cartridges after one month of use, but replacement frequency may vary depending on the quality of the air in your compressed air lines.
What do I do if the carbon monoxide monitor alarm sounds?
If the monitor's alarm sounds, immediately remove your mask or hood, move to a safe breathable atmosphere, and contact qualified personnel to examine and correct the equipment.
What is the maximum inlet pressure for the panel?
The maximum inlet pressure for the panel is 150 PSIG (10.4 Bar). Exceeding this pressure could result in personal injury.
What is the operating temperature range?
The operating temperature range for the panel is 68-150°F (20-65°C). You may need to utilize conditioning equipment before the filter to achieve this temperature range.