Lumel N12B Type Digital Panel Indicator User’s Manual
Below you will find brief information for Digital Panel Indicator N12B Type. This document details the N12B type programmable digital panel indicator, designed for installation in synoptic panel boards. It reads values transmitted via the RS-485 interface and displays them on a 5 or 4 digit read-out field. The device offers features like alarm signaling, measuring range overrunning, re-calculation of measuring quantities, programming of indication resolution and averaging, saving maximum and minimum values, parameter monitoring, password protection, highlighting specific units, MODBUS protocol support, and conversion of measured values into standard signals. The manual covers installation, connection, operation, programming, and technical specifications of the N12B type indicator.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
PROGRAMMABLE DIGITAL PANEL INDICATOR N12B TYPE USER’S MANUAL PROGRAMMABLE DIGITAL PANEL INDICATOR N12B TYPE USER’S MANUAL CONTENTS 1.APPLICATION........................................................................ 5 2.BASIC REQUIREMENTS, OPERATIONAL SAFETY............ 6 3.FITTING.................................................................................. 6 4.CONNECTION........................................................................ 7 5.OPERATION........................................................................... 7 6.PROGRAMMING.................................................................. 10 7.RS-485 INTERFACE............................................................. 20 7.1. Connection way of the serial interface...................................... 20 7.2. Description of the MODBUS protocol implementation.................. 22 7.3. Description of used functions................................................. 22 7.4. Register map of the N12B indicator......................................... 25 7.5. Registers for writing and read-out........................................... 26 7.6. Registers only for read-out.................................................... 32 8.TECHNICAL DATA............................................................... 35 9.BEFORE A FAILURE WILL BE DECLARED....................... 37 10.PROGRAMMING EXAMPLES OF N12B INDICATORS...... 38 11.EXECUTION CODES........................................................... 41 12.MAINTENANCE AND GUARANTEE................................... 42 1. APPLICATION N12B programmable digital panel indicators are destined to be installed in synoptic panel boards and display the value transmitted by the RS-485 interface. The 5 or 4 digit read-out field (14 or 20 mm high digits) in red or green colour ensures a good readability at a long distance. They realise other additional functions as: - signalling of the set alarm value overrunning, - signalling of the measuring range overrunning, - re-calculation of the measuring quantity into an optional quantity on the base of an individual, linear characteristic, - programming of the indication resolution, - programming of the averaging number of transmitted values, - saving of maximal and minimal values, - monitoring of set parameter values, - blocking of the parameter introduction by means of a password, - highlighting of any optional measuring unit as per the order, - servicing of the interface with a MODBUS protocol, both ASCII and RTU, - conversion of the measured quantity into a standard programmable current or voltage signal, - interception and display of the register value from the device connected to the bus - Master-asking of the device connected to the bus With the meter we deliver: - a guarantee certificate, - 2 holders to fix the indicator on a panel, - a connector with screw or self-locking connections (as per order), - a service manual, - a set of stickers with units. After unpacking the indicator, please check whether the type and execution code on the data plate correspond to the order. Symbols located in this service manual mean: Especially important, one must acquaint with this before connecting the meter. The non-observance of notices marked by these symbols can occasion the damage of the meter. One must take note of this when the meter is working inconsistently to the expectations. 2. BASIC REQUIREMENTS, OPERATIONAL SAFETY N12B indicators are destined to be mounted into panels and cubicles. In the range of operational safety they are in conformity with the EN 61010-1 standard requirements. The installation and indicator connection should be operated by a qualified personnel. One must take into consideration all accessible protection requirements. Before switching the instrument on, one must check the correctness of the network lead connection. Requirements in respect to the main lead must be in accordance with the EN 61010-1 standard. There must be a cut-off installed in the building. This cut-off should be installed near the device and easy accessible for the operator. In case of the protection terminal connection with a separate lead one must remember to connect it before the connection of network leads. Do not connect the instrument to the network through an auto-transformer. Before taking the indicator housing out one must turn the supply off. The removal of the indicator housing during the warranty contract period may cause its cancellation. 3. FITTING Prepare a (92+0.6 45+0.6) mm hole in the panel. The thickness of the material from which the panel is made can not exceed 15 mm. One should introduce the indicator from the front of the panel when the supply circuit is turned off. After introducing the indicator, fasten it by means of holders. Fig. 1. Overall dimensions 4. CONNECTION At the rear side of the indicator there are two terminal strip seats. A connector with screw terminals or a self-locking connector is added to the meter depending on the indicator type chosen in the ordering code. The fig. 2. shows the connection way of external signals. The description of the connector is also printed on the indicator housing. Fig. 2 Connection ways of the N12B indicator It is recommended to use screened leads on the indicator input. As a feeder cable one must use a two-wire cable and choose the lead cross-section such that in case of a short-circuit from the device side, the protection of the cable was ensured by means of the electric installation fuse. Requirements related to the feeder cable are regulated by the EN 61010-1 standard. 5. OPERATION After switching the indicator on, its type and next the program version are displayed on the display. After ca 10 sec, the indicator transits automatically into the measuring mode and the input signal value is displayed. The indicator blanks automatically insignificant zeros. The exceeding of the alarm threshold is signalled by means of alarm diodes 1 and 2. The basic unit of the measured value is automatically highlighted by the indicator 1). a) b) Fig. 3. Description of the indicator faceplate: a) 5-digit execution b) 4-digit execution 1) No exist in the 4-digit (20 mm) execution Key functions: - acceptance key entry into the programming mode (hold down during ca 3 seconds), moving through the menu - choice of the level entry into the change mode of the parameter value, acceptation of the changed parameter value. - key to increase the value display of the maximal value, entry to the parameter group level, moving through the chosen level, change of the chosen parameter value - increase of the value, successive parameter in the monitoring mode. - key to decrease the value display of the minimal value, entry to the parameter group level, moving through the chosen level, change of the chosen parameter value - decrease of the value, successive parameter in the monitoring mode. - resignation key entry to the menu of parameter monitoring (hold down during ca 3 seconds), exit from the monitoring menu, resignation of the parameter change, absolute exit from the programming mode. The pressure of the key combination causes the erasing of alarm signalling. This operation exclusively acts when the support function is switched on. The pressure of the key combination causes the erasing of all minimal values. The pressure of the key combination causes the erasing of all maximal values. The pressure and holding down of the key during ca 3 sec. causes the entry into the programming matrix. The programming matrix is secured by the safeguard code. The pressure and holding down of the key during ca 3 sec. causes the entry into the previewing menu one must move through the previewing menu by means of and keys. In this menu, all programmable indicator parameters, except service parameters, are only accessible to the readout. The exit from the previewing menu takes place by means of the key. On the previewing menu, parameter symbols are alternately displayed together with their values. The fig. 4. shows the operation algorithm of the indicator. The appearance of the following symbols on the digital displays means: - Incorrectly introduced security code. - Exceeding of the upper measuring range - Exceeding of the lower measuring range - Exceeding of the waiting limit time for information 6. PROGRAMMING The key pressure and its holding down during ca 3 seconds causes the display of the security code symbol SEC alternately with the 0 value set up by the manufacturer. The writing of the correct code causes the entry, into the programming matrix. The transition matrix into the programming mode is shown on the fig. 5. We choose the level by means of the key, whereas the entry and moving through parameters of the chosen level is carried out by means of the and keys. Parameter symbols are displayed alternately with their actual values. In order to change the value, one must use the key. To resign of the parameter change one must press the key. To exit from the chosen level one must select the - - - symbol and press the key. In order to exit from the programming matrix into measurement, one must press the key. The inscription HEY occurs and after ca 5 sec., the indicator will automatically enter into the displaying mode of the value transmitted by the RS-485 interface. 10 11 Fig. 4. Operation algorithm of the N12B indicator (*) Concerns only SOUr = bUS or nnAS (1) Exists only when the individual characteristic is attached (Ind =0) (2) Exists only in the 5-digit executions. Fig. 5. Transition matrix into the programming mode 12 Way of changing the value of the chosen parameter In order to increase the value of the chosen parameter one must press the key. A single pressure of this key causes a value increase of 1. The hold of the pressed key causes a continuous increase of the value down to the display of the 0 value. The jump to the next digit follows after this value. The further change is similar. In any moment, the key release causes a jump to the first digit. It is similarly in case of the value decrease. A single pressure of the key causes a value decrease of one. The hold of the key pressure down causes a continuous decrease of the value down to the display of the 0 value. The jump to the next digit follows after this value. The further change is similar. The key release in any moment causes a jump on the first digit. In order to accept the set up parameter one must press the key. Then, the writing of the parameter and display of its symbol follows alternately with the new value. The pressure of the key during the change of the parameter causes the resignation of the saving. Table 1 Parameter symbol Description Range of changes d_P Setting of the decimal point. This setting acts both when the individual characteristic is switched off and when the characteristic is switched on. Optional. Cnt Number of averages of transmitted values In 4-digit execution: 0...9999 In 5-digit execution: 0...99999 The inscription of 0 cause the blanking of the display. Ind Switching off or on of the user’s individual linear characteristic ON - Characteristic switched on OFF - Characteristic switched off 13 Table 1 (continuation) Parameter symbol Description H1, Y1 Parameters of the individual H2, Y2 characteristic. On the base of co-ordinates of two points given by the user, the indicator assigns coefficients of the individual characteristic a and b Y= aH+b, where: H1 and H2 - value transmitted by the RS-485 interface, Y1 and Y2 - expected value on the display Range of changes In 4-digit execution: -1999...9999 In 5-digit execution: -19999...99999 PrL1 PrL2 Alarm lower threshold In 4-digit execution: -1999...9999 In 5-digit execution: -19999...99999 PrH1 PrH2 Alarm upper threshold In 4-digit execution: -1999...9999 In 5-digit execution: -19999...99999 tYP1 tYP2 Alarm type The fig. 6. shows the graphical illustration of alarm types nor - normal On - switched on OFF - switched off H_On - manually switched on, till the time of the alarm type change, the alarm output is switched on for good. H_OF - manually switched off, till the time of the alarm type change, the alarm output is switched off for good. dLY1 dLY2 Delay of alarm operation. The parameter is defined in number of received values i.e. one must give after how many values from the RS-485 interface the alarm operation follows. The alarm switching off follows without delay. The parameter takes in account the number of averages of Cnt values, i.e. the whole averaging cycle is treated as a single value. In 4-digit execution: 0...9999 14 In 5-digit execution: 0...99999 The introduction of 0 causes the operation at the moment of alarm occurrence. Table 1 (continuation) LEd1 LEd2 Support of the alarm signalling. On - support switched on In the situation when the function OFF - support switched off of support is switched on after the withdrawal of the alarm state, the signalling diode is not blank. It signals the alarm state till the moment of its blanking by means of the combination of keys. This function only and exclusivey concerns the alarm signalling and then the relay contacts will act without support, according the chosen alarm type. tYPA Type of analogue output. PrAd - current nAP - voltage AnL Lower threshold of the analogue output. It is the parameter defining the value on the display for which we want obtain 0 on the analogue output. In the 4-digit execution: -1999... 9999 Upper threshold of the analogue output. It is the parameter defining the value on the display for which we want obtain the max. value (20 mA or 10 V ) on the analogue output. In the 4-digit execution: -1999... 9999 AnH bAuD Baud rate of the RS-485 interface In the 5-digit execution: -19999... 99999 In the 5-digit execution: -19999... 99999 2400 - 2400 bps 4800 - 4800 bps 9600 - 9600 bps trYb Kind of transmission through the RS-485 interface. OFF - interface switched off A8n1 -ASC II 8N1 A7E1 -ASCII 7E1 A7o1 - ASCII 7O1 r8n2 - RTU 8N2 r8E1 - RTU 8E1 r8o1 - RTU 8O1 Adr Device address 0... 247 15 Parameter symbol ToUt SOUr Table 1 (continuation) Description Range of changes Waiting time limit to obtain information (in seconds) after which „- - - -” have to be displayed on the display. The write of the „0” value will cause the switching parameter action off. In case when SOUr=nnAS, the write of the „0” value will cause the index operation switching as master off. In the 4-digit execution: 0... 999,9 Choice of indicator kind of work Syn - display of value transmitted through the interface to the register 7648 In the 5-digit execution: 0... 9999,9 BUS - interception and display of the register value from the device connected to the bus interception parameters are set in ToUt, Dadr, DrEJ, TrEJ, FFOr. nnAS - indicator work as master. Parameters of the questioned device are set in ToUt, Dadr, DrEJ, TrEJ, FFOr. DAdr Device address from which the register value has to be intercepted or the address of the questioned device. 1... 247 - this address must be different from the indicator address itself. DrEJ Register address to intercept or question. In the 4-digit option: 1...9999 In the 5-digit option: 1...65535 TrEJ Type of intercepted or questioned register. 32b - 32-bit registers of float type 16b - 2x16-bit registers of float type 32S - 32-bit registers of signed long type 32U - 32-bit registers of unsigned long type 16S - 16-bit registers of signed int type 16U - 16-bit registers of unsigned int type 16 Table 1 (continuation) FFOr Format of the transmitted register by the MODBUS protocol. Where TrEJ = 32b, 16b, 32S, 32U 3210 - as the first, oldest byte is sent or the byte including the character and exponent. 1032 - words with exchanged places. 0123 - float transmitted in inversed sequence. 2301 - returned bytes in words. Where TrEJ = 16U, or 16S 0010 - as first, the oldest byte is transmitted. 0001 - as first, the youngest byte is transmitted. SEt Writing down of manufacturers settings. Parameter values set up by the manufacturer are shown in the table 2. A pressure of the key causes the writing down of standard parameters into the meter. The execution of this operation is signalled by the inscription End. SEC Introduction of a new password In the 4-digit execution: -1999...9999 In the 5-digit execution: -19999...99999 tSt Display test. The test consists on the consecutive switching of digital display segments on. Alarm diodes and highlighting diodes of the unit should flicker. The continuous lighting of the alarm diodes signals that the relay is switched on. The pressure of the key causes the test switching on. The key ends the test. JEd Unit highlighting switching on. On - highlighting switched on OFF - highlighting switched off --- Exit from the parameter group of the chosen level. The pressure of the key causes the exit from the parameter group of the chosen level. 17 a) nor PrH > PrL b) nor PrH £ PrL c) OFF c) On Fig. 6. Alarm type: a) and b) normal, c) switched off, d) switched on 18 CAUTION In case of On and OFF alarm types, the writing down of PrL>PrH will cause an automatic transcription of the value from the threshold PrL into PrH and from PrH into PrL. The alarm type will not change. In case of a measuring range exceeding the relay reaction is concordant with written down PrL, PrH and tYP parameters. In spite of displaying the exceeding, the indicator will carry out the measurement as before. In case of an individual characteristic switching on (Ind=On) the measurement result is transformed linearly in accordance with introduced H1, Y1, H2, Y2 parameters. The indicator currently checks up the value of the actually introduced parameter. In case when the introduced value exceeds the upper range of changes given in the table 1, the indicator will automatically carry out the change into the minimal value. Similarly, in case when the introduced value exceeds the lower range of changes given in the table 1, the indicator will automatically carry out the change into the maximal value. Standard parameters of the indicator Parameter symbol d_P Cnt Ind H1,Y1,H2,Y2 PrL1, PrL2 PrH1,PrH2 tYP1, tYP2 dLY1, dLY2 LEd1, LEd2 tYPA AnL AnH bAud trYb Adr toUt Level in the matrix 1 1 1 1 2,3 2,3 2,3 2,3 2,3 4 4 4 4 4 4 4 Table 2. Standard value 0.00 1 OFF 0 -19.99 or -199.99 99.99 or 999.99 OFF 0 OFF PrAd -19.99 or -199.99 99.99 or 999.99 9600 r8n2 1 10.0 19 Standard parameters of the indicator Parameter symbol Level in the matrix Table 2 (continuation) Standard value SOUr dAdr drEJ trEJ FFOr SEC 5 5 5 5 5 6 SYn 2 7505 32 b 3210 0 JEd 6 On 7. RS-485 INTERFACE N12B programmable digital indicator series have their serial link in the RS-485 standard to communicate in computer systems and with other devices fulfilling the Master function. The MODBUS asynchronous character communication protocol has been implemented on the serial link. The transmission protocol describes the ways of information exchange between devices through the serial link. 7.1. Connection way of the serial interface The RS-485 standard enables the direct connection to 32 devices on a single serial link of 1200 m long. For the connection of a greater quantity of devices it is necessary to apply additional intermediate-separating systems. The lead out of the interface line is given in the paragraph 4. To obtain a correct transmission it is necessary to connect lines A and B in parallel with their equivalents in other devices. The connection must be carried out with a screened lead. The screen must be connected to the protective grounding in a single point. The GND line serves to an additional protection of the interface line for long connections. One must connect it to the protective grounding (this is not necessary for the interface correct work). In order to obtain the connection with an IBM PC computer, an RS-485 interface card or a RS-232/RS-485 converter is indispensable. On the Fig. 7. and Fig. 8 the device connection is shown. 20 Fig. 7. Way of the RS-485 interface connection in the master mode Fig. 8. Way of RS-485 interface connection in the slave mode The marking of the transmission line for the card in the PC computer depends on the card producer. 21 7.2. Description of the MODBUS protocol implementation The implemented protocol is compatible with the PI-MBUS-300 Rev G Modicon Company. Setting-up of meter serial link parameters in the MODBUS protocol: - meter address 1... 247 - baud rate 2400, 4800, 9600 bps - working modes ASCII, RTU - information unit ASCII: 8N1, 7E1, 7O1 RTU: 8N2, 8E1, 8O1 The parameter configuration of the serial link is described in the further parts of this service manual. It consists on the settlement of the baud rates (bAud parameter), device address (Adr parameter) and the information unit type (trYb parameter). Notice: Each indicator or meter connected to the communication network must have: * a unique address, different from addresses of other devices connected in the network, * an identical baud rate and information unit type. 7.3. Description of used functions Following functions of the MODBUS protocol have been implemented in meters of N12 series and in N12B indicators: Code of functions Code 0x03 0x06 0x10 0x11 Table 3 Meaning Read-out of n-register Writing of a single register Writing of n-registers Identification of the slave device Read-out of n-registers (code 03 h) The function is inaccessible in the publication mode. Example: readout of 2 registers beginning from the register with 1 DBDh (7613) address. Request: Device address Function code 01 03 22 Register address Hi 1D Register address Lo BD Number of registers Hi 00 Number of registers Lo 02 Checksum CRC 52 43 Response: Device address Function code Number of bytes 01 03 08 Value from the register 1DBD (7613) 3F 80 00 00 Value from the register 1DBE (7614) 40 00 00 00 Checksum CRC 42 8B Caution! It is possible to readout simultaneously up to 28 registers. Write of values in the register (code 06h) The function is accessible in the publication mode. Example: record of the register of 1DBDh (7613) address. Request: Device address Function 01 06 Register address Hi 1D Register address Lo BD Register address Hi 1D Register address Lo BD Value from the register 1DBD (7613) 3F 80 00 00 Checksum CRC 85 AD Response: Device address Function 01 06 Value from the register 1DBD (7613) 3F 80 00 00 Checksum CRC 85 AD Record into n-registers (code 10h) The function is accessible in the publication mode Example: write of 2 registers beginning from the register with 1DBDh (7613) address. Device address Function Request: 01 10 Register address Hi Lo 1D BD Number of registers Hi Lo 00 02 Number Value for the register Value for the register of bytes 1DBD (7613) 1DBE (7614) 08 3F 80 00 00 40 00 00 00 Checksum CRC 03 09 Response: Device address Function Register address Hi Register address Lo 01 10 1D BD Number of Number of registers registers Hi Lo 00 02 Checksum (CRC) D7 80 Caution! It is possible to readout simultaneously up to 28 registers. 23 Report identifying devices (code 11h) Example: Data readout identifying the device for NA5 with a universal input. Request: Device address 01 Function code 11 Checksum (CRC) C0 2C Response: Device Function Quantity Device address code of bytes identifier 01 11 08 Device state 65 Field depending Control on the device type total FF XXXXXX Device address - depending on the set value Function - function No: 0x11; Number of bytes - 0x08; Device identifier - 0x65 - N12B Device state - 0xFF; Field depending on the device type - XXXXXX Device name - transmitted as ASCII character and defines the indicator type: B - 0x42, 42 X X X X X Number of display - Field depending on the number of indicator display digits - 0x04 - 4-digit indicators, X 04 X X X X - 0x05 - 5-digit or indicators, X 05 X X X X No of the program ming version - programming version implemented in the meter or indicator X X _ _ _ _ - 4-byte variable of float type Control total - 2 bytes in the case of work in the RTU mode 1 byte in the case of work in the ASCII mode 24 Example: Working in the RTU mode, e.g.: trYb=r8n2. N12B indicator Execution with a 4- digit display, No of the programming version 1.00, Device address set on Adr=0x01, For this type of meter the frame will have the following shape: Device address Function Number of bytes Device identifier Device state Field depending on the device type Control total (crc) 01 11 08 60 FF 42 04 3F 80 00 00 CF B1 7.4. Register map of N12B indicators Register map of the N12B indicators Address range Value type Table 4 Description 7000-7200 float (32 bits) The value is placed in two successive 16-bit registers. Registers include the same data as 32-bit registers from the 7500 area. Registers are only for read-out. 7200 - 7400 float (32 bits) The value is placed in two successive 16-bit registers. Registers include the same data as 32-bit registers from the 7600 area. Registers can be read out and written in. 7500 - 7600 float (32 bits) The value is placed in a 32-bit register. Registers are only for read-out . 7600 - 7700 float (32 bits) The value is placed in a 32-bit register. Registers can be read out and written in. 25 7.5. Registers for writing and read-out N12B - indicators 7200 7600 Symbol Identifier writing (w) / read-out (r) The value is placed in 32-bit registers The value is placed in two successive 16-bit registers. Registers include the same data as 32-bit register from the 7600 area. Table 5 r Description Range Device identifer 0x6504...6505 Value 7202 7601 no occurs 1) 7204 7602 no occurs 1) 7206 7603 no occurs 1) 7208 7604 no occurs 1) 7210 7605 no occurs 1) 7212 7606 no occurs 1) 7214 7607 no occurs 1) 7216 7608 no occurs 1) 7218 7609 no occurs 1) 7220 7610 no occurs 1) 7226 7613 d_P w/r 6504 4 digit execution 6505 5 digit execution Decimal point 0... 4 Value 7228 7614 Cnt w/r 0...3 4 digits execution 0...4 5 digits execution Number of measurements 0... 99999 Value 26 0...9999 4 digits execution 0...99999 5 digits execution 7230 7615 Ind w/r Individual characteristic 0... 1 Value 0 Character. switched off Character. switched on 1 7232 7616 H1 w/r Parameters of the individual characteristic -19999... 99999 Value -1999...9999 4-digit indicators -19999...99999 5-digit indicators The range of H1, H2, Y1, Y2, PrL1, PrH1, PrL2, PrH2, AnL, AnH parameters depends only the set up decimal point d_P. The writing of the value with a higher number of significant places after the decimal point will cause its round-off. Values beyond the range cause the return of the error code 03 (not allowed data value). 7234 7617 Y1 w/r Parameters of the individual characteristic -19999... 99999 Value -1999...9999 4-digit indicators -19999...99999 5-digit indicators Change of range as for the H1 parameter 7236 7618 H2 w/r -19999... 99999 7238 7619 Y2 w/r -19999... 99999 7240 7620 7242 7621 PrL1 w/r Parameters of the individual characteristic Change of range as for the H1 parameter Parameters of the individual characteristic Change of range as for the H1 parameter No occurs 1) Lower threshold of alarm 1 -19999... 99999 Change of range as for the H1 parameter 7244 7622 PrH1 w/r Upper threshold of alarm 1 -19999... 99999 Change of range as for the H1 parameter 7246 7623 tYP1 w/r Type of alarm 1 0... 4 Value 0 1 2 3 4 Normal Switched on Switched off Manually switched on Manually switched off 27 7248 7624 dLY1 w/r Delay of alarm 1 0... 99999 Value 7250 7625 LEd1 w/r 0... 1 0...9999 4-digit indicators 0...99999 5-digit indicators Support of alarm 1 signalling Value 7252 7626 7254 7627 0 Support switched off 1 Support switched on no occurs 1) PrL2 w/r Lower threshold of alarm 2 -19999... 99999 Change of range as for the H1 parameter 7256 7628 PrH2 w/r Upper threshold of alarm 2 -19999... 99999 Change of range as for the H1 parameter 7258 7629 tYP2 w/r Type of alarm 2 0... 4 Value 0 1 2 3 4 7260 7630 dLY2 w/r Normal Switched on Switched off Manually switched on Manually switched off Delay of alarm 2 0... 99999 Value 7262 7631 LEd2 w/r 0... 1 0...9999 4-digit indicators 0...99999 5-digit indicators Support of alarm 2 signalling Value 7264 7632 no occurs 1) 7266 7633 no occurs 1) 7268 7634 7270 7635 0 Support switched off 1 Support switched on no occurs 1) tYPa w/r Type of analogue output 0... 1 Value 28 0 Current 1 Voltage 7272 7636 AnL w/r -19999... 99999 Lower threshold of the analogue output 7274 7637 AnH w/r -19999... 99999 Upper threshold of the analogue output 7276 7638 7278 7639 Change of range as for the H1 parameter Change of range as for the H1 parameter no occurs 1) Jed w/r 0... 1 Switching on or switching off on the unit highlighting Value 0 Highlighting switched off 1 Highlighting switched on Occurs only in 5-digit meters 7280 7282 7640 7641 Del_min Del_maks w/r w/r 0... 1 0... 1 7284 7642 no occurs 1) 7286 7643 no occurs 1) 7288 7644 no occurs 1) 7290 7645 no occurs 1) 7292 7646 no occurs 1) 7294 7647 7296 7648 Erasing in of the minimal value Value 0 Lack of operation 1 Erasing of the minimal value Erasing in of the maksimal value Value 0 Lack of operation 1 Erasing of the maximal value no occurs 1) Synoptic w/r Value to display on the display The range of this parameter only depends on the set up decimal point d_P . The writing of the value with a greater number of significant places after the decimal point will cause its round-off. Values beyond the range cause the return of the error code 03 (not allowed data value). The number value for this register must be included in the interval from -8388608 to 8388608 7298 7649 no occurs 1) 29 7300 7650 SOUr w/r 0... 2 Choice of kind of indicator work Value 7302 7651 dAdr w/r 1... 247 0 Display of transmitted value through the interface into the register 7648 1 Interception and display of the register value from the device connected to the bus. Caution! The indicator intercepts response frames (code 03h) transmitted to the master device. 2 The indicator works as Master. Device address from which the register value is to be intercepted, or the device address to ask Caution! The address must be different from the indicator address. 7304 7652 DrEJ w/r Register address to intercept 1... 65536 Value 7306 7653 TrEJ w/r 0... 1 1...9999 4-digit indicator 1...65536 5-digit indicator Type intercepted or asked address Value 0 32-bit float type 1 2x16 bit float type 2 32 bit signed long 3 32 bit unsigned long 4 16 bit signed int 5 30 16 bit unsigned int 7308 7654 FFOr w/r 0... 3 Format of sent register by the Modbus protocol Value For trEJ = 0, 1, 2, 3 0 3210 - as the first the oldest byte or the byte including the character and exponent is sent (in case of float type). 1 1032 - words changed in places 2 0123 - float sent in inversed sequence 3 2301 - bytes inversed in words Dla trEJ = 4 or 5 7310 7655 ToUt w/r 0... 9999.9 0 10 - as the first the most significant byte to sent 1... 3 01 - as the first the less significant byte to sent For SoUr=0 or 1. The waiting time limit to obtain information (in seconds) after which „_ _ _ _” are displayed. For SoUr=2. Interval time between asking frames sent from the device in Master mode. Value 0... 999.9 4-digit indicators 0... 9999.9 5-digit indicators Caution! For SoUr=0 or 1. The write of „0” value will cause the switching of the parameter operation off. For SoUr=2. The write of „0” value will cause the switching of master device off. 1) In case of registers no occurring in the indicator, their values are equal 1E+20 31 The value is placed in two successive 16-bit registers. Registers include the same data as 32-bit register from the 7600 area. The value is placed in 32 bit registers 7.6. Registers only for read-out Name 7000 7500 Identifier _ 7002 7501 Status _ 7004 7502 Control % 7006 7503 Minimum _ Minimal value of the currently displayed value 7008 7504 Maximum _ Maximal value of the currently displayed value 7010 7505 Displayed value _ 7012 7506 No occurs 1) 7014 7507 No occurs 1) 7016 7508 No occurs 1) 7018...7096 7509...7548 No occurs 1) Unit Quantity name Constant identifying the device 0×65 - N12B 1) Status is the register describing the current state of the indicator. It is the register describing the control of the analogue output (rzeczywista jest tylko w zakresie 0...120%). Currently displayed value In case of registers no occuring in the given series of meters, their value are equal 1E+20 Caution! At the moment of the upper or lower range exceeding, „minimum”, „maximum” and „Displayed value” parameters are 1E + 20 (unbelievable measurement result). For the parameter Cnt = 0 (blanking of the displays), parameters „minimum”, „maximum” and „displayed value” are set up on the value 1E + 20. 32 Signalling the range lower overrunning bits 15 14 13 12 11 10 9 8 7 6 5 MSB Individual characteristic or lack of it Relay state (alarm) 1 Relay state (alarm) 2 Position of the decimal piont Baud rate X X X X X X X X X X X X X X X Working mode and information unit X Kind of output (voltage, current) Compensation error of lead resistance Kind of display Signalling the range upper overrunning Description of the status register 4 3 2 1 0 LSB Bit-15 Kind of display 0 - meter or indicator with a 4-digit display 1 - meter or indicator with a 5-digit display Bit-14 Reserved Bit-13 Kind of output (voltage, current) 0 - current 1 - voltage 33 Bit-12...10 Working mode and information unit 000 - interface switched off 001 - 8N1 - ASCII 010 - 7E1 - ASCII 011 - 7O1 - ASCII 100 - 8N2 - RTU 101 - 8E1 - RTU 110 - 8O1 - RTU Bit-9...8 Baud rate 00 - 2400 bit/s 01 - 4800 bit/s 10 - 9600 bit/s Bit-7...5 Position of the decimal point 000 - lack 001 - 0.0 010 - 0.00 011 - 0.000 100 - 0.0000 (only for 5-digit meter or indicator executions) Bit-4 Signalling of the range upper overrunning 0 - normal work 1 - range overruning Bit-3 Signalling of the range lower overrunning 0 - normal work 1 - range overrunning Bit-2 Relay state (alarm 2) 0 - switched off 1 - switched on Bit-1 Relay state (alarm 1) 0 - switched off 1 - switched on Bit-0 Individual characteristic 0 - Individual characteristic switched off 1 - Individual characteristic switched on 34 8. technicAL DATA Panel indicator dimensions 96 48 93 mm Protection index ensured by the housing front IP 50 Protection index ensured from the terminal side IP 20 Rated operating conditions: l supply voltage depended on the execution code 85... 253 V a.c. d.c. 20... 40 V a.c. d.c. l supply voltage frequency 40... 440 Hz l ambient temperature 0... 500C l relative air humidity < 75% (water vapour condensation inadmissible) Power consumption max 5 VA Storage temperature -200C...+850C Display field N12B4 indicator N12B5 indicator four 7-segment LED displays and two alarm diodes five 7-segment LED displays, two alarm diodes, and two diodes to the unit highlighting Indication range of the digital display: N12B4 indicator -1999...9999 N12B5 indicator -19999...99999 Servicing cztery przyciski Relay outputs • programmable alarm thresholds, • three types of alarms (see chapter 6), • hysteresis defined by means of the lower and upper alarm threshold, • signalling of alarm action by means of diodes, • programmable delay of the alarm operation, • two relay outputs, • voltageless - make contacts - maximal load capacity: • voltage: 250 V a.c., 150 V d.c. 35 • current: 5 A 30 V d.c., 250 V a.c. • resistance load: 1250 VA, 150 W Analogue output: • current programmable load resistance 500 • voltage programmable load resistance 500 • galvanic insulation, • resolution • basic error 0/4...20 mA 0...10 V 0.01% of the range ±(0.2% of the range) Digital output: • RS-485 interface, • MODBUS transmission protocol: • ASCII: 8N1, 7E1, 7O1 • RTU: 8N2, 8E1, 8O1, • Baud rate: 2400, 4800, 9600 bauds, • Maximal response time for query frame: 600 ms Electromagnetic compatibility: • immunity • emission Safety requirements: according EN 61010-1 standard: • installation category • level of pollution • maximal voltage in relation to the earth acc. EN 61000-6-2 acc. EN 61000-6-4 III 2 300 V a.c. Protection level: • ensured by the housing • ensured by the terminals IP 50 IP 20 Weight 200 g Time of the display restoring 36 programmed, min. 20 ms 9. BEFORE A FAILURE WILL BE DECLARED SYMPTOMS PROCEDURE 1. The indicator does not operate Check the connection of the feeder cable 2. Only the diodes are lighting The number of transmitted averaged values which has been introduced = 0 The indicator operates in the SLEEP mode. The display is blanked. 3. Only the horizontal dashes are displayed on the display. Transmitted values are beyond the indicator range. 4. Lack of possibility to enter into the programming mode. The inscription Err is displayed. The programming mode is protected by the password. If the user forgets which password has been introduced one must contact the nearest authorised service workshop. 5. Lack of certainty if all display segments are efficient Enter into the service mode and switch on the display test. Simultaneously the same segments should be lighted on all displays. The state with blanked displays does never occur. Otherwise, submit the defect to the nearest authorised service workshop. 6. During operations in the programming mode, parameter values inconsistent with the range of changes given in the table 1 appear on the display Enter into the service mode and accept the SEt parameter. The indicator will introduce values in accordance with the table 2. 7. A result inconsistent with our expectations appears on the display. Check if the individual characteristic is not switched on. In case of necessity enter into the service mode and accept the SEt parameter. The indicator will introduce parameters in accordance with the table 2. 8. H1, Y1, H2, Y2, d_P parameter symbols are not displayed in the programming mode. In case of switched individual characteristic off, mentioned symbols are omitted 9. Despite of the alarm threshold exceeding neither the alarm relay nor the signalling diode is switched on. Check the introduced delay of the alarm operations into the indicator. If need be, correct the dLY parameter 37 10. Despite of the relay switching off, the alarm diode does not go out. Check if the alarm signalling support is not switched on. LEd parameter. In case of need, switch it off 11. When the parameter of the alarm signalling support is switched on, lack of possibility to erase the signalling diode by means of the key combination. (Fig.4). The alarm still lasts. The erased diode is immediately re-lighted 12. Despite the fact that the alarm still remains, the signalling diode does not light up. Check if a delay of the alarm operation has not been introduced dLY parameter. 13. Instead to display the measurement result, the indicator displays the parameter symbol alternately with its value despite we were not entered into the programming mode. The indicator works in the previewing mode. 14. A delay of the alarm operation has been introduced, e.g. 30 averages, however after this time the alarm has not operate. The lasting alarm state was shorter than the programmed, e.g. during the lasting time of the alarm the state of alarm withdrawal has occurred. In that case the indicator starts counting the measurements from the beginning 15. The indicator does not establish the communication with the computer Check if the interface leads (A, B, GND) have been correctly connected. Then, check in the programming matrix the interface setting (trYb, bAud, Adr). These parameters must be the same as in the used software. 10. PROGRAMMING EXAMPLES OF N12B METERS Example 1 - Programming of an individual characteristic. If we want to programme so that to the value 4.00 is to correspond the value 0.00 on the display, whereas to the value 20.00 is to correspond the value 100.00 one must: enter to the programming mode and choose the d_P parameter responsible for the decimal point. Set up the point on the 000.00 position choose the Ind parameter, and switch the individual characteristic on 38 choose the parameter H1 and introduce the value 4.00 pass on the Y1 parameter and introduce the value 0.00 pass on the H2 parameter and introduce the value 20.00 pass on the Y2 parameter and introduce the value 100.00 Example 2 - Programming of an inverse individual characteristic. If we want to programme so that to the value 4.00 is to correspond the value 120.50 on the display, whereas to the value 20.00 is to correspond the value 10.80, one must: enter to the programming mode and choose the d_P parameter responsible for the decimal point. Set up the point on the 000.00 position choose the Ind parameter and switch the individual characteristic on, choose the H1 parameter and introduce the value 4.00 pass on the Y1 parameter and introduce the value 120.50 pass on the H2 parameter and introduce the value 20.00 pass on the Y2 parameter and introduce the value 10.80 Example 3 - Programming of the alarm with hysteresis If we want to programme the alarm 1 operation so that the alarm will be switched on at the value 850, whereas switched off at the value 100, and the alarm 2 so that at the value 1000 the alarm will be switched off whereas switched on at the value -199, one must: enter into the programming mode and choose the level with the ALr1 symbol, enter on the level Alr1, choose PrL parameter and introduce the value 100 pass on the PrH1 parameter and introduce the value 850 pass on the tYP parameter and choose the function designed as nor, exit from the ALr1 level and pass on the ALr2 level, choose the PrL parameter and introduce the value1000 pass on the PrH parameter and introduce the value -199 pass on the tYP parameter and choose the function nor. Example 4 - Programming of an alarm operating in the given interval with delay. If we want that the alarm 1 is to be switched on in the interval from 100 up to 300 and is to operate only after 10 transmitted values, one must: enter into the programming mode and choose the ALr1 level, pass on the PrL parameter and introduce the value 100 39 pass on the PrH parameter and introduce the value 300 pass on the tYP parameter and choose the On function, pass on the dLY parameter Assuming that the Cnt parameter has not been changed and is equal 1 (acc. the manufacturer setting), after the dLY parameter we must introduce the value 10. If e.g. Cnt = 2, then dLY = 5. introduce the value 10 under the dLY parameter. exit from the programming mode. In case of the alarm state duration for a time longer than 10 transmitted values, the indicator will switch the alarm relay on and the alarm diode will be lighted. Example 5 - Programming of an analogue output If we want to program so that to the 0.00 value is to correspond the 4 mA value on the current analogue output, whereas to the 20.00 value is to correspond the 20 mA value, one must: enter into the programming mode and choose the tYPA parameter responsible for the type of the analogue output. Choose the PrAd current output, pass on the tYPA parameter responsible for the analog output type. Choose the PrAd current output. under the AnL parameter, one must write down the value for which we want 0 mA on the analogue output. For this reason one must calculate the AnL parameter: (20 - 0 )/(20 - 4 ) = 1.25 => 0 -(4*1.25) = - 5 choose the AnL parameter and introduce the value - 5.00 choose the AnH parameter and introduce the value 20.00 40 11. EXECUTION CODES N12 DIGITAL METERS X X X X X XX X XXX Inputs: temperature programmable input.......................T 1 V d.c., 10 V d.c., 20 mA d.c., 200 mA d.c....... S 600 V d.c., 1 A d.c., 5 A d.c................................ H rotations, frequency, period, pulse number....... O single-phase parameters................................... P indicator for synoptic pannel . ........................... B acc. order *........................................................ X unit symbol*) Number of digits on the display: 4 digits, digit height = 20 mm........................4 5 digits, digit height = 14 mm........................5 Display colour: - red.....................................................................0 - green.................................................................1 Supply voltage: 230 V a.c. d.c............................................................. 1 24 V a.c. d.c............................................................... 2 Kind of terminals: - socket plug with screw connections................................ 0 - socket-plug with self-locking connections....................... 1 Execution: - standard execution.................................................................00 - custom-made execution **.................................................... XX Acceptance tests: - without a quality inspection certificate............................................ 8 - with a quality inspection certificate................................................. 7 - acc. customer’s agreement............................................................X Unit symbol............................................................................................XXX * Introduce the unit symbol which is to be highlighted. ** The code number is established by the manufacturer. 41 Order example: N12B 4 1 1 0 00 7 means: a N12B indicator for synoptic panels, with 4 displays in green colour, voltage supply: 230 V a.c., d.c., kind of terminal: socket-plug with screw connection, standard execution, with a quality acceptance test. In case of any meter failure one must contact the nearest authorized service workshop. 12. MAINTENANCE AND GUARANTEE The N12B indicator does not require any periodical maintenance. In case of some incorrect unit operations: 1. From the shipping date, during the period given in the annexed guarantee card. One should take the instrument down from the installation and return it to the Manufacturer’s Quality Control Dept. If the instrument has been used in compliance with the instructions, the Manufacturer guarantees to repair it free of charge. 2. After the guarantee period: One should turn over the instrument to repair in a certified service workshop. The disassembling of the housing causes the cancellation of the granted guarantee. Spare parts are available for the period of ten years from the date of purchase. The Manufacturer’s policy is one of continuous improvement and we reserve the right to make changes in design and specifications of any products as engineering advances or necessity requires and revise the above specification without notice. 42 43 SALES PROGRAMME MEASUREMENT DIGITAL and BARGRAPH PANEL METERS CONTROL MEASURING TRANSDUCERS RECORDING ANALOG PANEL METERS (DIN INSTRUMENTS) ANALOG and DIGITAL CLAMP-ON METERS PROCESS and HOUSEHOLD CONTROLLERS CHART AND PAPERLESS RECORDERS POWER CONTROL UNITS and SOLID-STATE RELAYS AUTOMOTIVE DASHBOARD INDICATORS 1-PHASE AND 3-PHASE WATT-HOUR METERS NUMERICAL AND ALPHANUMERICAL LARGE SIZE DISPLAYS ACCESSORIES FOR MEASURING INSTRUMENTS (SHUNTS AND MODULES) MEASURING SYSTEMS (ENERGY, HEAT, CONTROL) CUSTOM-MADE ELECTRONIC SUBASSEMBLIES ACC. TO ORDERS WE ALSO OFFER OUR SERVICES IN THE PRODUCTION OF: ALUMINIUM ALLOY PRESSURE CASTINGS PRECISION ENGINEERING AND THERMOPLASTICS PARTS PRESSURE CASTING DIES AND OTHER TOOLS CUSTOM-MADE ELECTRONIC SUB-ASSEMBLIES QUALITY PROCEDURES: According ISO 9001 and ISO 14001 international requirements. All our instruments have CE mark. For more information, please write to or phone our Export Department. Lubuskie Zak³ady Aparatów Elektrycznych LUMEL S.A. ul. Sulechowska 1, 65-022 Zielona Góra, Poland Export Department: Tel.: (48-68) 329 53 02 or 04 Fax: (48-68) 325 40 91 e-mail: [email protected] N12-07C/4 Tel.: (48-68) 329 51 00 (exchange) Fax: (48-68) 329 51 01 e-mail:[email protected] http://www.lumel.com.pl
advertisement
Key Features
- 5 or 4 digit read-out field
- RS-485 interface
- MODBUS protocol support
- Alarm signaling
- Parameter monitoring
- Password protection
- Conversion to standard signals