EVI Split Combo Air to Water Heat Pump Service Manual

EVI Split Combo Air to Water Heat Pump Service Manual

The EVI Split Combo Air to Water Heat Pump is a compact and efficient unit designed for both heating and cooling. This unit can be used for supplying sanitary hot water and house heating, and it can also be used with fan coil units. The unit features an electronic expansion valve, a water-side shell-tube heat exchanger, and an outdoor temperature probe for control and climatic compensation. The EVI Split Combo is reversible and can operate down to -20°C.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Heat Pump EVI Split Combo - Service Manual | Manualzz

 

Air to Water Heat Pump   

EVI Split Combo Type 

 

 

Service Manual 

 

 

 

 

Before operation this product, please read the instructions carefully and save this manual for future. 

 

 

Thank you for choosing our quality product.   

Please read this manual carefully before use and follow the instructions to operate the unit in order  to prevent damages on the device or injuries to staff. 

Specifications are subject to change with product improvements without prior notice. Please refer to  the specification sticker on the unit for upgraded specifications. 

Heat pumps stand out for their compactness and high performances: operation down to ‐20’c. They are reversible and  can be used for heating and for cooling in summer. They can also be used for fan coil units. 

Heat pump has indoor unit and outdoor unit. Outdoor unit is connected to indoor module by copper connective pipe. 

 

The outdoor unit has: 

‐ Air‐side heat exchanger with copper pipes and aluminum fins, complete with grid protection. 

 

‐ Axial fan 

The inside unit has: 

‐ Electronic expansion valve 

‐ Water‐side shell‐tube heat exchanger complete with water‐flow‐switch. 

‐ Outdoor temperature probe for control and climatic compensation of the water set point ( heat curve ). 

‐ LCD controller with thermostat function, displaying and setting the operating parameters. 

‐ Electronic control panel equipped with electrical terminal boards for connective external consents. 

‐ Structure in painted galvanised stell complete with condensation tray. 

‐ Compressor: scroll EVI hermetic compressor complete with thermal protection. 

‐ Circulation pump 

‐ Auxiliary electrical heater 

 

‐ 3‐way‐water‐valve: the motorised reversal valve with connector for sanitary hot water tank 

Optional: 

‐ Buffer tank: used to limit operation of the compressor in short cycles and to provide a reserve for the defrosting phase  on reversible air/water heat pump. 

 

▌Working temperature range: 

‐ in heating mode:   

Outside air: ‐20 ~45

°C

 

Water: +18/+55’c 

‐ in cooling mode :   

Outside air: +15 ~45

°C

 

Water: +7/+25

°C

 

 

Maximum operating water pressure: 7bar. 

When  install  the  unit,  be  sure  to  check  whether  the  selection  of  installation  place,  power  supply  specifications, usage limitation(piping length, height differences between indoor and outdoor units,  power supply voltage and etc.) and installation spaces

- 1 -

 

Content

 

 

 

24 

24 

24 

24 

24 

20‐21 

21 

22 

 

23 

 

14‐15 

15 

16 

16 

16‐18 

18 

19 

 

19‐20 

 

24‐25 

25 

25 

25 

 

10 

10 

 

11 

 

 

11 

12 

13‐14 

 

 

 

4 –5 

 

- 2 -

33 

33 

33 

33 

33 

 

33‐34 

35‐39 

40 

40 

31 

32 

32 

 

32 

26‐28 

28‐29 

 

29 

29‐30 

31 

31 

 

41 

42 

 

43 

44 

44 

45‐46 

- 3 -

 

1 Safety precautions 

 

If heat pump is not running in the winter, it is necessary to keep power supply connected for Anti‐freeze protection. 

In cold weather (≤ 0°C), if heat pump is no longer needed, do drain out all the water inside the system. 

1.1 Safety precautions 

  ‐ Warning      ‐ suggestion   

Once abnormality like burning smell  occurs, please cut off the power  supply immediately and then contact  with service center. 

 ‐ prohibition 

Be sure to pull out the power plug  and drain the indoor unit and water  tank when unit is not in use for a long  time. Otherwise, the accumulated  dust may cause overheating fire or  freeze of water tank or coaxial heater  exchanger in winter. 

Make sure to use a dedicated power  line for the heat pump only. Do not  add other appliances to the line. 

 

If the abnormality still exists, the unit  may be damaged and electric shock  or fire may result. 

Before installation, please see if the  voltage of local place accords with  that on nameplate of unit and  capacity of power supply, power cord  or socket is suitable for input power  of this unit.     

 

Don't operate the unit with wet hand. 

 

Otherwise, it may cause electric  shock. 

 

Before cleaning please cut off the  power supply. Otherwise, it may  cause electric shock or damage. 

The power supply must adopt special  circuit with leakage switch and  enough capacity. It is mandatory to  use a suitable circuit‐breaker for the  heat pump and make sure the power  supply to the heater corresponds to  the specifications. Otherwise the unit  might be damaged. 

 

Never damage the electric wire or use  the one which is not specified. 

 

Otherwise, it may cause Overheating  or fire. 

The unit must be earthed to avoid any 

risks caused by insulation defects. 

 

 

 

- 4 -

Please note whether the installation  stand is firm enough or not. 

Never insert any foreign matter into  unit to avoid damage. And never  insert your hands into the air outlet  of outdoor unit.     

Don't attempt to repair the unit by  yourself. 

 

If damaged, it may cause fall of the  unit and injury of people. 

Don't step on the top of the unit or  place anything on it. 

 

Never block the air inlet and outlet of    unit. 

Improper repair may cause electric  shock or fire, so you should contact  the service center to repair. 

Keep pressurized spray, gas holder 

  and so on away from the unit above 

1m. It may cause fire or explosion. 

 

It may reduce efficiency or cause stop  of the unit and even fire. 

 

There is the danger of fall of things or  people. 

Select an installation place where  noise and vibration when operation  do not bother your neighbors. 

Remove any snow from the units  after snowfalls. 

 

Make sure no water or other liquid  drips into the electric box of the unit 

Otherwise the unit might be  damaged. 

 

Check the water temperature before  supplying any hot water or taking a  shower. Could result in being burnt. 

Do not touch the faucet while hot  water is being supplied. 

Could result in being burnt by hot  water 

 

 

Do not touch the relief valve, drainage  pipe, drain outlet or drain elbow when  inspecting the relief valve or while  draining hot water. 

 

 

 

- 5 -

2 Working principle of a Heat Pump 

(refrigerant circuit):

 

The refrigerant system consists of 6 main components: 

EVI scroll type compressor, 4‐way‐valve, heat exchanger (condenser, refrigerant to water), electronic expansion  valve, evaporator (air to refrigerant), Economizer. 

 

Heat pump can absorb the heating from air source. This makes the heat pump a very environmentally friendly and 

  economically sound alternative for space heating. 

 

* Evaporator: low temperature, low pressure refrigerant go through evaporator, to boil and turn from liquid to gas. 

* Compressor: compressor absorb refrigerant, and compress to high temperature, high pressure status. 

 

* Condenser: refrigerant release heat energy to heat exchanger. Refrigerant temperature reduces, and it returns from 

  gas status to liquid status. 

The heat energy is absorbed by water, circulated by a circulation pump to indoor radiator or floor heating systems. 

* EEV: at last the refrigerant go through the electronic expansion valve, where its pressure is reduced, and then  continues to the evaporator. 

 

- 6 -

3 Explored view

 

3.1 indoor unit explored view 

1  Economizer 

2  Compressor 

3  Heat exchanger (condenser) 

4  Manometer 

5  Manometer bracket 

6  Accumulator 

7  Left plate 

8  Electrical control box 

9  4‐way‐valve 

10  Coil for EEV 

  15 

16  controller 

Controller bracket 

  29  Circulation pump 

  30  PCB 

17  Return water connector    31   

18  Top plate    32  Sensor 

19  connector to water tank    33  Transformer 

20  Connector to house 

21  Return connector 

22  Gas valve 

23  Liquid valve 

  24  Right plate 

11  Electronic expansion valve    25  Frame 

  34  Terminal 

  35  door 

   

   

   

   

 

 

 

 

- 7 -

 

12  filter 

13  Front plate 

14  Controller box 

  26  Electrical heater 

  27  3‐way‐water‐valve 

  28  Water‐flow‐switch 

3.2 Outdoor unit explored view 

     

     

     

1  Top panel 

2  Separate panel 

3  Evaporator 

4  Motor bracket 

5  Motor 

6  Fan blade 

7  Bottom plate heater 

8  Left handle 

9  Front panel 

10  Plastic net 

11  Near net 

12  SPM module 

13  Motor capacitor 

14  Main circuit board 

15  4‐way‐valve 

16  4‐way‐valve coil 

  17  Sensor 

18  Electronic expansion valve coil 

19  Electronic expansion valve 

20  Filter 

21  Right panel 

22  Right handle 

23   

24  Reactance  

25  Copper pipe 

26  Evaporator bottom heater 

27  Compressor 

28  Compressor heater 

29  Gas connector 

30  Liquid connector 

31  Valve plate 

32  Bottom plate 

- 8 -

 

3.3 main components 

 

2 compressor 

 

Pressure switch 

 

 

 

3 Shell tube heat exchanger 

 

Electronic expansion valve 

Fan blade  controller 

 

  evaporator 

 

4‐way‐valve 

 

 

Motor 

 

Switch board 

 

 

Main board 

 

 

 

Room temp. sensor / 

  Outside air temp. sensor 

 

Water tank/return/FEED/ temp. Sensor 

 

3‐way‐water‐valve 

 

 

Electrical heater and holder 

 

 

Water flow switch 

Circulation pump 

 

 

- 9 -

4. Applications 

  4.1 application: supply sanitary hot water, house heating 

Recommended installation order:   

1. Connect copper connective pipe between indoor unit and outdoor unit. 

2. Connect indoor unit to the climate system, cold and hot water lines as well as any external heat sources. 

3. Connect the load monitor, outdoor temperature sensor; any centralized load control and external contacts as well as  the cable between outdoor units. . 

4. Connect power supply to outdoor unit. . 

Installation requirements 

 

Max pressure for house heating 

Highest recommended FEED / return temperature at dimensioned outdoor temperature 

Max water outlet temperature with electrical heater 

Max FEED line temperature with compressor 

Min supply temperature cooling 

Max supply temperature cooling 

Max water flow for heat pump 

Min water flow for heat pump 

10kW  12kW  15kW 

5 Bar 

55/45°C 

+65°C 

+58°C 

+7°C 

+25°C 

0.8l/s  1.1l/s  1.3l/s 

0.4l/s  0.5l/s  0.6l/s 

 

- 10 -

5. Installation 

5.1 installation plan 

 

- 11 -

5.2 Installation Outdoor Unit 

Outdoor unit can be transported either vertically or horizontally. However it must be stored vertically and in dry  conditions. 

5.1.1 Select the Installation Place of Outdoor Unit 

* The outdoor unit should be installed on a solid wall and fastened securely. 

* The outdoor units should be installed close to the house, on a terrace, on the façade or in a garden. They are designed to operate in the rain  but can also be installed under cover as long as there is sufficient ventilation. There should be no obstacles to hinder the free circulation of air to the  exchanger inlet and outlet (see installation diagrams below). 

* The emplacement of the outdoor unit should be carefully chosen and protected from prevailing winds in order for it to be compatible with  environmental requirements: integration into the site, noise level. 

* We particularly recommend: 

• Not placing the outdoor unit close to sleeping areas 

• Not placing it opposite a glazed wall 

• Avoiding proximity to a terrace 

* Moreover, we recommend positioning the unit above the average depth of snowfall in the region in which it is installed. 

* It is necessary to provide clearance all around the appliance to carry out connection, commissioning and maintenance operations. 

* The following procedure must be observed before connecting the pipes or electric cables. 

1) Decide which the best position on the wall is and leave enough space to be able to carry out maintenance easily.   

2) Fasten the outdoor unit support to the wall using screw anchors which are particularly suited to that type of wall. 

3) Use a larger quantity of screw anchors than normally required for the weight they have to bear: during operation the machine vibrates and 

Has to remain fastened in the same position for years without the screws becoming loose. 

4) Mount the outdoor unit on the support using the four bolts supplied. 

 

 

   

 

- 12 -

 

 

 

* Please install the drain connector to the unit    when necessary. In some cold areas   

(temperature below 0°C), please don't use the   

drain connector; otherwise it may clogged by ice. 

 

5.3 Indoor Unit Installation 

* It is recommended that indoor unit is installed in a room with existing floor drainage, most suitably in a utility room or  boiler room. 

* The surface must be firm, preferably a concrete floor or foundation. 

* Install indoor unit with its back to an outside wall, ideally in a room where noise does not matter. If this is not possible,  avoid placing it against a wall behind a bedroom or other room where noise may be a problem. 

* The unit can be aligned using the adjustable feet. 

 

* Route pipes so they are not fixed to an internal wall that backs on to a bedroom or living room. 

* Ensure that there is approx. 500 mm free space in front of and 220 mm above the product for any future service. 

Dimensioning expansion tank 

 

The expansion tank’s volume must be at least 5 % of the total volume. 

Example table 

Total volume (l)  Volume Expansion tank (l) 

280  14 

320 

360 

16 

18 

Initial pressure and max height difference 

The initial pressure of the pressure expansion tank must be dimensioned according to the  maximum height (H) between the tank and the highest positioned radiator, see figure. An  initial pressure of 0.5 bars means a maximum permitted height difference of 5 m. 

If the standard initial pressure in the pressure tank is not high enough it can be increased by  filling via the valve in the expansion tank.   

Any change in the initial pressure affects the ability of the expansion tank to handle the  expansion of the water. 

 

- 13 -

5.5 Refrigeration Connection 

5.5.1 Refrigeration connection 

The commissioning of heat pump includes operations on the refrigeration circuit. Appliances must be installed, 

 

commissioned, maintained and repaired by qualified, authorized personnel, pursuant to the requirements of prevailing  directives, laws and regulations and in accordance with the codes of practice of the profession. 

* Before shipped out from manufacturer, the indoor unit has been filled with refrigerant. Additional refrigerant may  be filled when copper pipe is more than 5 meters. Outdoor unit do not have refrigerant inside. 

* Check the liquid valve and the gas valve of the outdoor unit. The valves shall be completely shut off.     

 

5.5.3 Refrigeration connection step 

1. Connect the copper  pipe to indoor unit. 

 

 

 

2. Wipe the quick  connectors with clean  cloth to prohibit dust  and impurity entering  the pipes. 

Align  the  centre  of  the  pipe  and  fully  screw  in  the  angular  nuts with Finger.  connect  other  side  of  copper  pipe  to  outdoor unit 

 

                   

 

     

 

- 14 -

4. A vacuum pump and manifold gauge are needed. 

Connect the pressure gauge to the vacuum pump. 

Use  Vacuum  pump  to  remove  the  air  from  outdoor  unit  and copper pipe. 

 

6. Use a 4mm hex wrench to open two valves of outdoor  unit. 

   

   

 

 

 

5.  When  vacuuming  the  outdoor  unit  and  copper  pipe,  please  turn  on  gas/liquid  valve  on  outdoor  unit ;  but  do  not  turn  on  gas/liquid  valve  on  indoor  unit,  otherwise  refrigerant  leakage.  Vacuum  the  unit  for  at  least  15  minutes till negative value shown on the pressure gauge,  and close the manifold gauge. 

 

7. Remove the service pipe of pressure gauge. Put copper  nut back. Tighten them with a wrench. 

Connect  the  electric  cable  as  per  wiring  diagram,  and  bundle it with the connecting pipe. 

 

 

6. Use a 4mm hex wrench to open two valves of outdoor  unit. 

   

 

- 15 -

8. After confirming that there is no  leakage from the system, when the  compressor is not in operation, charge  additional R410a refrigerant with specified  amount to the unit through the service  connector on liquid valve. 

Be sure to charge the specified amount of  refrigerant in liquid state to the liquid  pipe. Since R410a is a mixed refrigerant,  adding it in gas form may cause the  refrigerant composition to change, 

 

preventing normal operation. 

5.5.4 Return refrigeration 

If heat pump want to disconnect. Please return refrigerant R410a from outdoor unit back to indoor unit as following: 

Run heat pump on ROOMCOOL operation mode. 

 

4‐way‐valve switch ON, circulation pump switch ON, compressor start, fan start. 

1. Remove the cap of two valves on indoor unit with the spanner. 

 

 

 

 

2. Tighten the core of the liquid  valve (the smaller one) with valve  key at first. After about 20 seconds, 

  you can hear a special sound from  compressor; tighten the core of the  gas (the bigger one) with valve key. 

3. Press    to stop heat pump

 

 

4. Tighten the cap of two valves. 

 

 

- 16 -

 

6. Loose the nut of the connect pipe to the outdoor unit valve  with 2 spanner, disconnect the connect pipe and the two valves. 

 

 

 

5.5.2 Maximum distances and quantity of refrigerant fluid to be loaded 

5kW  7kW  10kW  12kW  15kW  18kW 

Ø gas pipe  1/2 "  5/8"  5/8"  3/4"  3/4"  3/4" 

 

Ø liquid pipe  1/4 "  3/8"  3/8"  1/2"  1/2"  1/2"  max pipe length  20 m  20 m  20 m  20 m  20 m  20 m 

 

The refrigerant R410a inside heat pump is suitable for 5 meter copper pipe. If the refrigerant link between outdoor unit  and indoor unit is more than 5 meter, 

Please fill 10g per meter for 5kW, 7kW; 30g per meter for 9kW, 12kW, 15kW, 18kW. 

 

- 17 -

5.6 Electrical connection 

 

Electrical installation and service must be carried out under the supervision of a qualified electrician. Electrical installation  and wiring must be carried out in accordance with the stipulations in force: maximum amperage on the outdoor unit 

(thermodynamic unit). See the table below, distance of the appliance from the original power supply, upstream  protection, and neutral operating conditions.

 

 

1.It is recommended to use a suitable    breaker for the heat pump and make    sure the power supply to the heater   

Corresponds to the specifications.   

Otherwise the unit might be damaged. 

2.The power supply to the heat pump    unit must be grounded. 

3.Cable should be fixed tightly, to ensure    it won't get loosen. 

Connecting power supply

 

Incoming power supply cable is connected    to terminal block from top cable clamp.   

 

The cable must be dimensioned according    to the applicable norms.

 

 

 

Connect the power cable as following:

 

 

 

- 18 -

Connecting signal supply from indoor unit to outdoor unit

 

Connect cable on outdoor unit

 

 

Connect cable on indoor unit 

 

 

 

- 19 -

 

When the cable is connected to terminal, a screwdriver is  used to open the terminal, see figure : 

Connect room/outdoor temperature sensor 

 

5.4 Room temperature sensor installation

 

When customer choose fan coil mode, he should install the room temperature senor as following: 

1. Take the room temperature sensor out from the indoor unit. 

 

 

2. Distance between the indoor unit and the remote room temperature senor should be less than 15 meter due to length  of the connection c able of remote air temperature sensor.     

3. Height from floor is approximately 1.5 meter;   

4. Remote room temperature sensor can not be located where the area may be hidden when door is open;       

5. Remote room temperature sensor can not be located where external thermal influence may be applied;   

6. Remote room temperature sensor should be installed where space heating is mainly applied;       

- 20 -

5.7 Pipe connection 

5.7.1 General 

Pipe installation must be carried out in accordance with current norms and directives. Heat pump can operate with a  return temperature of up to 50°C and outgoing temperature from the unit of 55°C. 

Heat pump is not equipped with shut off valves; these must be installed outside the heat pump to facilitate any future  servicing. 

Heat pump can be connected to the radiator system, floor heating system and/or fan coil units. 

Install the safety valve and manometer. 

 

 

Indoor module is equipped with circulation pump, water‐flow‐switch, 3‐way‐water‐vave, electrical heater backup. 

Note:  this heat pump is split type with refrigeration link between outdoor unit and indoor module, it is not necessary to  add glycol to the installation. 

 

Buffer tank: 

The installation of buffer tank is recommended for installations. 

It is intended: 

‐ Increase the water volume in an installation in order to limit the short‐cycle operation of the compressor. The greater 

  the water volume, the lower the number of start‐ups of the compressor and the longer its useful life. 

‐ Guarantee on energy reserve for the defrosting phases. 

Example of heat pump installations 

‐ Heat pump split compact    ‐ DHW production by independent tank   ‐ Buffer tank for house heating 

 

Connection of extra circulation pump 

When connecting additional circulation pump, to achieve a higher flow capacity, see alternative "Underfloor heating  systems" on page 25. Respective maximum flows must not be exceeded. 

- 21 -

Connecting the hot water tank 

The water tank must be supplied with necessary set of valves. 

* There must be a mixing valve if the temperature exceeds 60 °C. 

* The safety valve must have a maximum 10.0 bar opening pressure and be installed on the incoming domestic water line  according to outline diagram. The entire length of the overflow water pipe from the safety valves must be inclined to  prevent water pockets and must also be frost proof. 

* See section Dockings on page 23 for outline diagram. 

 

5.7.2 Filling and venting the heating medium system 

1. Check the water system for leakage. 

2. Connect the filling pump and return line on the heating system's service connections as shown in figure. 

3. Close the valve between the service connections. 

4. Open the valves on the service connections (AV1, AV2). 

5. Pushing the white manual lever down to bottom. (This has already been done when the machine leaves factory), then  three way valve's water tank port is closed (the "B" port), room heat port is open (the "A" port). 

6. Start the filling pump, and fill until there is fluid in the return pipe. 

7. Open up Power ON from control panel to start machine, then heat medium water pump is running, the valve will  return to the up position when power is restored. 

8. Firmly pushing the white manual lever down to midway and in.

 

in this position both the 'A' and 'B' ports are open. 

9. The filling pump and the heating medium pump are now operational. The fluid should circulate via the container with  tap water until it emerges from the return hose without being mixed with air. 

10. Stop machine, heat medium water pump stop running. Depressing the white manual lever lightly and then pulling the  lever out, pushing the while manual lever down to bottom position, and then "A" port open, "B" port is closed. 

11. Stop the filling pump and clean the particle filter. 

12. Start the filling pump; open the valve between the service connections. 

13. Close the valve on the service connection's return line. Now pressurize the system (to max 3 bars) with the filling  pump. 

14. Close the valve (AV2) on the service connection. 

15. Stop the filling pump. 

16. Select the auto operating mode using the operating mode button. 

 

 

Push the white gear onto the position  of middle, and then use your thumb to  press it inside, this time both port A  and port B are in open state. 

 

Please use screwdriver to unclench  the white gear of the three way valve. 

Then the white fear will move back to 

  the original position. The three way  valve will turn to port B automatically. 

- 22 -

 

A mesh filter must be installed in front of the water inlet of  the unit and water tank, for keeping the water quality and  collecting impurity contained in the water. Take care to keep  the water filter mesh towards the bottom. Check valve is  recommended to be installed at both sides of the filter, so as  to clean or change the filter in an easier way. 

 

5.7.3 Drainage 

1) drain of heating system 

Close the shut‐off valves in heating medium system. Open 

  the drain valve. A small amount of water runs out. 

2) drain chassis of heat pump 

 

- 23 -

 

 

 

5.74 Circulation pump capacity diagram on heating medium side 

Adjustment, charge flow 

Adjusting the temperature difference (ΔT) between the flow temperature and the return temperature during hot water  charging or at high load.   

This is easily done by using the temperatures measured in Channel T2 (flow temperature) less Channel T3 (return  temperature), this temperature difference (ΔT) is adjusted using circulation pump. Adjustment is performed with stable  operation about 5 minutes after start, or about 5 minutes after defrosting with a cold outdoor temperature.

 

The  temperature difference must be less than 5’c. 

10kW, 12kW  15kW, 18kW 

 

 

Adjust water flow

 

 

 

- 24 -

6 switch board 

When install or maintain heat pump, compressor, hot water pump and outdoor fan motor can be start forcibly by switch  board. 

 

A0 1:    control compressor 

AA M:  control hot water pump 

BA M:    control outdoor fan motor 

 

After testing, switch board will set OFF. 

 

- 25 -

6 Control panel 

6.1 description of control panel 

 

 

To be able to select the desired menu and increase or reduce preset values, you will use the five buttons. 

Up button with a plus 

Down button with a minus 

right button 

left button 

Power ON/OFF button 

8.2 Symbols 

 

Heat pump is running. 

 

Electrical heater is activated.   

The figure indicates capacity step. 

Warm water mode is activated. 

 

Empty symbol, indicates warm Water    temperature sensor is less than  setting temperature. 

 

 

Full symbol, indicates warm water  temperature reach to setting  temperature. 

House heat/cool mode is activated. 

 

 

8.3 General information 

8.3.1 Menu Navigation

 

Press    to next menu or select parameter. Press    to previous menu. Press  parameters of a menu. 

  and    to navigate 

A cursor (arrow) on the left‐hand side of the display indicates which menu can be opened. Press  also to increase or reduce parameter value. 

 

8.3.2 Display of current operating mode

 

  and   

- 26 -

During normal operation, the screen will display following information: 

z Current room temperature : 18°c  z Heat pump operation mode: OFF (heat pump stop)   

Press    to start/stop heat pump. 

If heat pump set OPERATION OFF mode for long time during winter,  please remember to remove out all the water the heating system to 

  avoid any damage caused by freezing. 

z Which day of the week,        clock  z Current activated operation mode 

8.4 Menus 

84.1 main‐menu INFORMATION 

Press    or    to main‐menu INFORMATION. 

Press    and    to navigate sub‐menu. 

Press    enter to sub‐menu. 

 

 

84.2 Sub‐Menu OPERATION 

This menu is used to select operation modes: 

 

 

 

 

ROOMCOOL :   

ROOMHEAT1 : ( heat curve ) 

FEED  setting  water  temperature  will  change  according  to  outside  air  temperature.  The  screen  will  display 

“OPER. ROOMHEAT1 “. HEATCURVE can change by CURVE value, ROOM value, part HEATCURVE. Heat pump 

(compressor, electrical heater) run/stop according to Calculation Integral.

 

ROOMHEAT2:   

FEED setting water temperature is fixed. The screen will display “OPER. ROOMHEAT2 “. Heat pump run/stop  according to setting FEED. 

WARMWATER : 

Warm water mode activate or inactivate. The screen will display “OPER. WARMWATER “. 

 

- 27 -

 

Select HEAT PUMP ON/OFF: heat pump activate or inactivate. 

Select ADD. HEAT ON/OFF: The electrical heater activate or inactivate. 

 

If you want to change operation mode:  a.  Press    to main menu INFORMATION. Press    and    to navigate to sub‐menu OPERATION.  b.    Press    to enter sub‐menu OPERATION. Press    and    to navigate to desired mode.  c.  Press    to select or cancel. The symbol    display or disappear.  d.    Press    to exit setting. And press    to the top OPERATION, and press 

  to back to main menu. 

 

 

8.4.3 Sub‐Menu HEAT CURVE 

This menu is used to set parameter of heat curve for operation mode ROOMHEAT1. 

Operation mode ROOMHEAT1 should be activated. 

 

 

Menu Text  Description  Adjustable by 

CURVE 

MIN 

MAX 

FEED setting water temperature when the outside air temperature is 0°C  User 

Min FEED temperature allowed.  User   

Max FEED temperature allowed.  User   

CURVE 5 

CURVE 0 

Part HEATCURVE 5 when outside air temperature is +5°C. 

Part HEATCURVE 0 when outside air temperature is 0°C.   

CURVE – 5  Part HEATCURVE ‐5 when outside air temperature is ‐5°C.   

HIGH T°STOP  Heat pump stops when outside air temperature ≥ value on right. 

LOW T°STOP  Heat pump stops when outside air temperature ≤ value on right. 

User   

User   

User   

User, if require 

User, if require 

- 28 -

 

 

 

8.4.3 Sub‐Menu TEMPERATURE 

This menu shows temperatures of sensor. 

Menu Text 

OUT 

ROOM 

Outside air temperature 

Description 

 

Room temperature. And set ROOM value in HEATROOM1. 

 

FEED  supply line temperature of heating system;   

In brackets is set point value in HEATROOM2. 

In brackets is setting FEED value according to OUT in HEATROOM1 

 

RETURN  Return temperature of heating system.   

WARMWT  Warm water temperature in water tank;   

In brackets is the setting temperature for warm water. 

 

All temperatures change from last 60 minutes is stored in PCB and some  temperatures can be viewed in curve. 

Press following temperature 3 second to see history curve. 

* FEED 

* RETURN 

* WARMWT 

Adjustable by 

‐‐‐‐‐‐‐ 

Installation contractor. To be    adapted to each individual unit 

Installation contractor. To be    adapted to each individual unit 

Not adjustable. 

Installation contractor. To be    adapted to each individual unit 

 

8.4.5 Sub‐Menu INTEGRAL

 

 

 

 

Electrical heater has three steps (2.5kW + 2.5kW + 2.5kW). 

Menu Text  Description 

OFF 

CMP.A 

When calculation integral ≥ OFF (setting value), heat pump stop. 

When calculation integral < CMP.A (start value), compressor start. 

And calculation integral ≥ OFF (stop valve), compressor stop. 

ADD1 

ADD2 

When calculation integral < ADD1 (start value), electrical heater 1 start. 

And calculation integral ≥ CMP.A (stop value), electrical heater 1 stop. 

When calculation integral < ADD2 (start value), electrical heater 2 start. 

And calculation integral ≥ ADD1 (stop value), electrical heater 2 stop. 

ADD3  When calculation integral < ADD3 (start value), electrical heater 3 start. 

And calculation integral ≥ ADD2 (stop value), electrical heater 3 stop. 

Adjustable by 

USER 

USER 

USER 

USER 

USER 

 

- 29 -

 

The relation between those parameter is:    OFF > CMP.A > ADD1 > ADD2 > ADD3  a.  on sub‐menu INTEGRAL.   

Press    and    to navigate to OFF.  b.    Press    to enter OFF setting. Press  to change setting value, each press is 10. 

  and     

 

8.4.5.1 Calculation Integral (CI) 

CI = (current FEED – setting FEED) * 1 minute 

 

CI 

... 

‐11 ~ ‐20 

Corresponding valve 

... 

‐20 

‐1 ~ ‐10 

1 ~ 10 

11 ~ 20 

‐10 

10 

20 

...  ... 

 

1) FEED is less than setting FEED 

For example, outside air temperature = ‐8 °C, setting FEED = 48°C. PCB will calculate CI every 1 minute. 

Compressor start 1 minute later, setting FEED = 48°C, return = 30°C, FEED = 31°C; so CI = (31‐48)*1 = ‐17      = ‐20. 

Compressor start 2 minute later, setting FEED = 48°C, return = 30°C, FEED = 33°C; so CI = (33‐48)*1 + (‐20)  = ‐40. 

Compressor start 3 minute later, setting FEED = 48°C, return = 30°C, FEED = 35°C; so CI = (35‐48)*1 + (‐40)  = ‐60. 

...... 

Compressor start 25 minute later, setting FEED = 48°C, return = 30°C, FEED = 35°C; so CI = (35‐48)*1 + (‐480)  = ‐500. 

Compressor start 26 minute later, setting FEED = 48°C, return = 30°C, FEED = 35°C; so CI = (35‐48)*1 + (‐500)  = ‐520. 

Æ ADD1 switch ON 

Compressor start 26 minute later, setting FEED = 48°C, return = 30°C, FEED = 36°C; so CI = (36‐48)*1 + (‐500)  = ‐520. 

Compressor start 27 minute later, setting FEED = 48°C, return = 30°C, FEED = 36°C; so CI = (36‐48)*1 + (‐520)  = ‐540. 

Compressor start 28 minute later, setting FEED = 48°C, return = 30°C, FEED = 36°C; so CI = (36‐48)*1 + (‐540)  = ‐560. 

Æ ADD2 switch ON 

- 30 -

 

Compressor start 29 minute later, setting FEED = 48°C, return = 30°C, FEED = 37°C; so CI = (37‐48)*1 + (‐560)  = ‐580. 

Compressor start 30 minute later, setting FEED = 48°C, return = 30°C, FEED = 37°C; so CI = (37‐48)*1 + (‐520)  = ‐600. 

Compressor start 31 minute later, setting FEED = 48°C, return = 30°C, FEED = 37°C; so CI = (37‐48)*1 + (‐540)  = ‐620. 

Æ ADD3 switch ON 

 

2) FEED is more than setting FEED 

For example, outside air temperature = ‐8 °C, setting FEED = 48°C. PCB will calculate CI every 1 minute. 

    0 minute, previous CI = ‐570, FEED = 55°C. 

    1 minute later, setting FEED = 48°C, FEED = 55°C; so CI = (55‐48)*1 + (‐570) = ‐560 

    2 minute later, setting FEED = 48°C, FEED = 55°C; so CI = (55‐48)*1 + (‐560) = ‐550 

Æ ADD3 switch OFF 

    ... 

    7 minute later, setting FEED = 48°C, FEED = 54°C; so CI = (54‐48)*1 + (‐510) = ‐500 

Æ ADD2 switch OFF 

    ... 

    51 minute later, setting FEED = 48°C, FEED = 53°C; so CI = (53‐48)*1 + (‐70) = ‐60 

Æ ADD1 switch OFF 

    ... 

    57 minute later, setting FEED = 48°C, FEED = 52°C; so CI = (52‐48)*1 + (‐10) = 0   

Æ Compressor stop 

 

8.4.5.2 INTEGRAL

   

The heat demand in the house depends  on the season and weather conditions and is  not constant. The heat demand can be  expressed as temperature difference over  time and can be calculated giving an integral  value as a result (heat demand). To calculate  the integral value, the control system uses  several parameters. 

A heat deficit is needed to start the  heat pump, and there are four integral  values, COM.A (default value = ‐60), which  starts the compressor and ADD1 (electrical  heater 1, factory set = ‐500), ADD2 (electrical  heater 2, factory set = ‐550), ADD3 (electrical  heater 3, factory set = ‐600) which starts the  auxiliary electrical heater. During heat  production, the deficit reduces and when  the heat pump stops, the inertia in the  system causes a surplus of heat. 

The integral value is a measurement of  the area under the time axis and is  expressed in degree minutes. The figure  below shows the factory settings for the  integral values that the heat pump has. 

When the integral value reduces to set value  for INTEGRAL COMP.A, the compressor  starts. If the integral value continues to  reduce to ADD1, ADD2, and ADD3 for  electrical heater 1, 2, 3 switch ON. 

Symbol explanation : 

1 Heat surplus, heat pump stop 

2 Heat deficit, heat pump stop 

3 compressor running area 

4 electrical heater 1 running area 

8 electrical heater 1 start 

9 electrical heater 2 start 

10 electrical heater 3 start 

11 electrical heater 3 stop 

5 electrical heater 2 running area    12 electrical heater 2 stop 

6 electrical heater 3 running area    13 electrical heater 1 stop 

 

7 compressor start

 

14 compressor stop

 

- 31 -

 

8.4.5 Sub‐Menu OPERATION TIME

 

Menu Text  Description 

HEAT PUMP  Total operating hours of heat pump since installation.   

Operating time will not reset to zero. 

ADD 1 

ADD 2 

Total operating hours of electrical heater (3kW) since installation.   

Operating time will not reset to zero. 

Total operating hours of electrical heater (6kW) since installation.   

Operating time will not reset to zero. 

ADD 3  Total operating hours of electrical heater (9kW) since installation.   

Operating time will not reset to zero. 

 

 

8.4.6 Sub‐Menu RESET 

Reset to factory setting value. 

.  On main‐menu INFORMATION.   

Adjustable by: 

USER 

USER 

USER 

USER 

Press    and    navigate to sub‐menu RESET.  b.    Press    3 second, the screen will display "RESET...”.  c.  A few seconds later, screen return to main menu,    all parameter reset to factory setting value. 

 

 

8.4.8 Sub‐Menu MAN TEST

 

a.  On main menu INFORMATION.   

Press    and    navigate to sub‐menu MAN TEST.  b.    Press    3 second to sub‐menu MAN TEST. 

 

c.  You can select ON/OFF to test each part. 

 

 

 

- 32 -

 

8.4.5 Sub‐Menu DEFROST 

Defrost has two mode :   

* Intelligent defrost:    start temp and exit temp set by PCB. 

 

* Manual defrosts:        all defrost parameter set by customer. 

DEF. TIME: range of setting defrost time: (2 ~~ 20 min). Default is 15 min. 

INTERVAL: range of setting defrost interval: (25 ~~ 70 min). Default is 30 min. 

START TEMP: range of start defrost temperature: (‐8 ~~ ‐15°C). Default is ‐4°C. 

SINCE TIME: Show last value of defrost time.      Not adjustable. 

BETW.DEFR: Show last value of defrost interval. Not adjustable. 

8.4.5.1 Intelligent defrost: 

1st defrost start condition (the first defrost period is 40 minutes): 

 

Heat pump first to run, when compressor run continuously for 40 minutes, PCB check if evaporator temperature < ‐4°C,  then start defrosting. 

During defrost 

 

 

 

Electrical heater switch ON, circulation pump run. 

Defrost exit condition: 

When evaporator temperature reach to 12°C, or max defrost running time = 15 minutes, Defrost exist. 

 

Next defrost start condition: 

The next defrost period will be changed according to last defrosting status, the calculation as following: 

Defrost running time (minutes)  1~2  3~4  5~6  7~8  9~10  11~12  13~15 

Defrost INTERVAL (minutes) 

 

6.14.2 Manual defrost: 

Defrost start condition: 

60  55  50  45  40  35  30 

 

When compressor runs continuously for 30 minutes, PCB checks if evaporator temperature < ‐4°C, then start defrost. 

 

 

Defrost exit condition: 

When evaporator temperature reach to 12°C, or max defrost running time = 15 minutes, Defrost exist. 

- 33 -

8.4.5 Setting for operation mode WARMWATER 

The setting range of water tank temperature is 20°C ~70°C. 

  a.  On sub‐menu OPERATION, select WARMWATER mode.  b.  On sub‐menu TEMPERATURE, press    and    to navigate to WARMWT.  c.    Press    to enter water tank temperature setting,  water tank temperature. 

  flesh. Press    and    to increase, reduce setting  d.    Press 

  to exit water tank temperature setting. 

 

 

8.4.5 Setting for operation mode ROOMHEAT2 

The setting FEED temperature is fixed. The max setting FEED temperature is 45°C. 

  a.  On sub‐menu OPERATION, select ROOMHEAT2 mode.  b.  On sub‐menu TEMPERATURE, press    and    to navigate to FEED.  c.    Press    to enter FEED setting,    flesh. Press    and    to increase, reduce setting FEED temperature.  d.    Press    to exit FEED setting. 

 

 

8.4.5 Heat curve for operation mode ROOMHEAT1

 

The heat curve calculates the supply temperature depending on the outdoor temperature. The lower the outdoor  temperature, the higher the supply temperature. In other words, the supply temperature of the water fed to the  heating system will increase linearly as the outdoor air temperature falls. 

The heat curve will be adjusted in connection with installation. It must be adapted later on, however, to obtain a  pleasant indoor temperature in any weather conditions. A correctly set heat curve reduces maintenance and saves  energy. 

 

Select ROOMHEAT1 mode, the setting FEED water temperature will change according to outside air temperature.   

Heat curve is changed by CURVE value, ROOM value and part HEATCURVE : 

- 34 -

 

8.4.6 Adjustment of CURVE value 

If you change heat curve by CURVE value, the gradient will change. CURVE value is setting FEED water temperature  at outside air temperature = 0°C. 

And the setting return water temperature at outside air temperature ‐8°C change at the same time. 

 

a.  On sub‐menu HEATCURVE, press    and    to navigate to CURVE.  b.    Press    to CURVE value setting. Press    and    to increase, reduce CURVE value.  c.    Press    return to sub‐menu HEATCURVE. 

8.4.6 Adjustment of ROOM value

 

If you change heat curve by ROOM value, the gradient  does not change. The whole curve move upwards or  downwards based on ROOM value.   

Factory setting of ROOM value is 0°C. 

The range ROOM valve is ‐9°C ~ 9°C. 

 

- 35 -

 

a.  On sub‐menu TEMPERATURE, press    and    to navigate to ROOM.  b.    Press    to enter ROOM value setting, press    or    to increase or reduce ROOM value.  c.    Press    to exit to sub‐menu TEMPERATURE. Press    to exit to main‐menu INFORMATION.  d.  press    and    to navigate to HEATCURVE, press    to enter sub‐menu HEATCURVE. 

  e.  press    and    to navigate to CURVE, press 

  to enter CURVE valve setting. 

If ROOM value reduce ‐5, the gradient does not change. The whole curve move downwards ‐5°C. 

If ROOM value reduce 5, the gradient does not change. The whole curve move upwards ‐5°C. 

 

 

8.4.6 Adjustment of Par t Heat Curve: 

You can change partly HEATCURVE at outside air temperatures ‐5°C, 0°C and +5°C. 

The gradient does not change. Only part of HEATCURVE change. 

There are three setting on menu: part HEATCURVE 5, part HEATCURVE0, part HEATCURVE ‐5. 

The setting range of part HEATCURVE is ‐3°C ~ 3°C. Factory setting value is 0°C. 

 

 

The right picture is CURVE valve 40°C    at outside air temperature 0°C 

  a.  Press    to exit to sub‐menu HEATCURVE. 

- 36 -

 

 

  b.  Press    and    to navigate to CURVE 5.    press    to enter part HEATCURVE 5  c.  Press    or    to increase or reduce part HEATCURVE 5 value.  d. Press    exit to sub‐menu HEATCURVE. 

 

 

8.4.7 sub‐menu SETTING: 

 

 

8.4.8 sub‐menu STERILIZE: 

- 37 -

 

 

8.4.9 Alarm: 

  If any error on heat pump, the screen will display an alarm message. 

 

Table: Alarm Messages 

Message  Signification 

LOW PRESS ERROR  Low pressure switch. Compressor stop. 

HIGH PRESS ERROR  High pressure switch. Compressor stop. 

MOTOR P ERROR 

ADD ERROR 

OUT SENSOR 

The relay of compressor or outdoor fan motor is overloaded. Compressor stop. 

Over‐heating protection. 

Fault in outside air temperature sensor.   

The value 0°C will be used for calculation of supply line set point value for HEATCURVE. 

FEEDLINE SENSOR 

RETURN SENSOR 

WARM WATER 

ROOM SENSOR 

Fault in supply line sensor. All operation stops, except hot water pump. 

Return line sensor fault. 

Error warm water sensor. No warm water production. 

Room temperature fault. The value 20°C will be used for ROOM value on HEATCURVE. 

POWER SUPPLY 

HIGH RETURN 

Alarm that indicates that there is an incorrect phase sequence to the compressor. 

Alarm that indicates that high return temperature prevents the compressor’s operation. 

CMPAIR OVER 

 

 

1) Message:    LOW PRESS ERROR 

Cause  Troubleshooting 

Lack of    refrigerant. 

Compressor exhaust temperature is more than 105°C. Compressor over‐heat protection. 

Using manometer apparatus and  thermometer, check that the unit’s  overheating is correct for the specific  refrigerant.  remedy 

Follow the correct procedure (depending on type of   

  refrigerant) to add the correct amount of refrigerant. 

If there appears to be a leak in the refrigerant circuit,   

Electronic    expansion    valve    defective or  incorrectly set. 

Cable break or  loose cable on  low pressure    switch 

 

 

* Using manometer apparatus and   

Thermometer check what the over heating  reading of the unit is. 

* Also check that bulb and capillary tube are 

  undamaged and that the bulb is correctly  installed. 

* Check that both cables are connected to 

  the pressure switch. 

* Using the buzzer, check that there are no  cable breaks. In order to do this, disconnect  the cables from the pressure switch and    carry out leak tracing and any necessary corrective  action. 

If the overheating reading does not correspond with  the instructions for the specific refrigerant, adjust the  expansion valve until the correct value is obtained. 

See separate instructions for cooling techniques. 

 

If overheating cannot be adjusted with the expansion  valve or if the capillary tube/bulb is damaged, replace  it. 

If a cable has come loose, reconnect it. 

 

If there is a cable break, replace the cable. 

- 38 -

circuit board. 

2) Message:   

HIGH PRESS ERROR 

Low pressure switch cut out. Compressor is stopped. No warm water is produced. 

Cause 

Closed or  partially closed  thermostats/  valves in the  heating system. 

The circulation  pump that is  defective or has  jammed. 

Troubleshooting 

Check that the thermostats/valves in the  heating system is open. 

Is there voltage to the circulation pump?  remedy 

Open closed thermostats/valves. 

Cable break or  loose cable to  high pressure  switch 

* Check that both cables are connected  to the pressure switch. 

* Using the buzzer, check that there are no  cable breaks. In order to do this,    disconnect the cables from the pressure  switch and circuit board. 

Use SWITCH BOARD to check that the circulation 

  pump is active. 

Check if there is voltage to the circulation pump, if  there is, and it does not run, the circulation pump is  jammed. If this is the case, open the bleed screw and 

  try to release the paddle wheel using a screwdriver  for example. 

If there is no voltage to the circulation pump, check  if there is voltage from the main board, see wiring  diagram. If there is voltage from the main board,  check the components between the main board and  the circulation pump. 

 

If a component is defective, replace it. 

If a cable has come loose, reconnect it. 

 

If there is a cable break, replace the cable. 

Overfilled  refrigerant  circuit. 

Blocked  condenser on the  water side. 

Using manometer apparatus and  thermometer, check that the unit’s  overheating is correct for the specific  refrigerant. 

If there is no strainer in the heating system,  there is a risk of dirt sticking in the  condenser and blocking it. Unfortunately  there is no easy way of checking if the 

  condenser is blocked. 

You can carry out a test by allowing the  compressor and circulation pumps to  remain in operation and after a while, 

Follow the correct procedure (depending on type of  refrigerant) to add the correct amount of  refrigerant. 

 

If there appears to be a leak in the refrigerant  circuit, carry out leak tracing and any necessary  corrective action. 

If the condenser is thought to be blocked, try  flushing it. If this does not work, it must be replaced. 

- 39 -

Blocked  condenser on the  refrigerant side.  check that the pressure pipe becomes hot  and that the circulation pumps work (for  circ.pumps with a bleed screw, unscrew it  and feel if the pump rotor rotates using a  screwdriver). 

 

Then read the temperature on both  connection pipes to the condenser: 

If the temperature difference is <5°C, the  condenser is not blocked. 

If the temperature difference is >13°C, the  condenser is probably blocked. 

Using manometer apparatus and  thermometer, check that the unit’s  overheating is correct for the specific  refrigerant. 

 

3)  Alarm sensor ( all ) 

Cause 

Sensor fault 

Troubleshooting 

* When reading the resistance of the  alternatively  cable fault.  sensors, the sensor leads must first be  disconnected from the control equipment  or terminal block. 

* First take a reading from the sensor    including cable and check against the  temperature sensor resistance table. 

* If the read off value does not correspond    with the table, only measure the sensor   

Cause  and check the table. 

 

4) Message: POWER SUPPLY 

Troubleshooting 

The incoming  phases have the  incorrect  sequence (only  applies to 

3‐phase  heat pumps). 

* If the text POWER SUPPLY. appears in the  display when the heat pump is powered, 

(only appears in the first 10 minutes) this  means that the phases have the incorrect  sequence. 

* When the compressor is running, check 

  the pressure pipe temperature by feeling 

  the pressure pipe. If the phases are    correctly sequenced it should be hot (not    just warm) even a distance from the    compressor. 

* When the compressor runs with the    phases incorrectly sequenced a strange    noise may be heard (loud, rattling) when    the compressor runs backwards. 

If the condenser is thought to be blocked by oil for  example, try blowing nitrogen through it to release  the oil. If this does not work, it must be replaced  remedy 

If the sensor gives a correct value, the cable is  defective. 

If the sensor does not give a correct value, the  sensor is defective.  remedy 

If the phases are in the incorrect order, switch two  incoming phases at the main terminal block and  recheck according to the troubleshooting window. 

- 40 -

 

 

5) Message: 

ADD ERROR

 

Cause 

Water flow  switch fault. 

No or insufficient  water circulation  in the heating  system. 

Troubleshooting 

Check what the water‐flow‐switch shows. Is  it a plausible/actual value? 

Measure the resistance of the sensor, check  against the ohm table in Measurement  points. 

Check: 

* That the circulation pump spins 

* That the shut‐off valves are open. 

* That the strainer is not blocked. 

* That there is no air in the heating system.  remedy 

If the water‐flow‐switch is defective, replace it. 

The circulation pump may have jammed. If so, open  the bleed screw and try to release the paddle wheel  using a screwdriver for example. 

Open closed valves or taps. 

Check, and, if necessary, clean the strainer. 

If necessary, bleed the heating system according to  the installation instructions 

Check insufficient water‐flow or block on heating  system. 

Check this sensor. 

A over‐heat  sensor 100°C on  electrical heater  holder switch 

* Water temperature inside electrical    heater holder is more than 100°C. 

* this sensor fault 

 

OFF 

5) Message: CMPAIR OVER 

Cause 

Compressor 

Troubleshooting 

Check what the sensor shows. Is it a  exhaust sensor  fault  plausible/actual value? 

Measure the resistance of the sensor, check  against the ohm table in Measurement  points. 

Using manometer apparatus and  Lack of  refrigerant, not  enough  refrigerant in the  system.  thermometer, check that the unit’s  overheating is correct for the specific  refrigerant.  remedy 

If the sensor is defective, replace it. 

Follow the correct procedure (depending on type of  refrigerant) to add the correct amount of  refrigerant. 

If there appears to be a leak in the refrigerant  circuit, carry out leak tracing and any necessary  corrective action. If leak tracer is not available,  brush soap water on the suspected leak and look for  bubbles. Also check for oil as this can come out from  the refrigerant circuit. 

6.16 4‐way‐valve:

 

 

4‐way‐valve switch ON on heating mode, switch OFF on cooling mode, defrosting. 

6.17 3‐way‐water‐valve:

 

3‐way‐water‐valve switches ON on ROOM HEATING/COOLING mode, switch OFF on WATER TANK HEATING, 

  cycle‐refrigerant, defrosting. When heat pump stop, 3‐way‐water‐valve switch OFF. 

- 41 -

6.18 circulation pump:

 

In WATER TANK HEATING mode, circulation pump stop when water tank temperature reach to setting temperature. 

Circulation pump start when water tank temperature drop down, compressor start. 

 

In ROOM HEATING/COOLING mode, circulation pump run all time. And circulation pump stop when error occur. 

In floor heating mode, when Outlet water over‐heat protection, circulation pump run.

 

- 42 -

8. Wiring diagram: 

* Outdoor wiring diagram for 380V‐50Hz‐3phase 

 

- 43 -

 

* Outdoor wiring diagram for 230‐50Hz‐1phase 

 

* Outdoor wiring diagram for all model

 

 

- 44 -

9. Temperature sensor resistance table: 

9.1 compressor exhaust temperature sensor resistance    t °c ‐‐ kΩ    50 k 

‐16 

‐15 

‐14 

‐13 

‐20 

‐19 

‐18 

‐17 

‐12 

‐11 

‐10 

‐24 

‐23 

‐22 

‐21 

‐28 

‐27 

‐26 

‐25  t °c 

‐30 

‐29 

‐9 

‐8 

R(KΩ

866.96 

815.70 

479.34 

452.68 

427.67 

404.17 

382.11 

361.35 

341.86 

323.53 

767.71 

722.87 

680.87 

641.59 

604.82 

570.34 

538.03 

507.74 

306.29 

290.06 

274.78 

260.4 

246.85 

10 

11 

12 

13 

‐1 

‐5 

‐4 

‐3 

‐2  t °c 

‐7 

‐6 

14 

15 

R(KΩ

234.08 

222.02 

140.00 

133.21 

126.79 

120.72 

114.96 

109.51 

104.34 

99.456 

210.69 

199.98 

189.86 

180.34 

171.33 

162.81 

154.78 

147.19 

94.826 

90.426 

86.262 

82.312 

78.561 

30 

31 

32 

33 

26 

27 

28 

29 

34 

35 

36 

22 

23 

24 

25 

18 

19 

20 

21  t °c 

16 

17 

37 

38 

R(KΩ

75.001 

71.625 

47.857 

45.817 

43.877 

42.027 

40.265 

38.585 

36.987 

35.462 

68.416 

65.368 

62.474 

59.719 

57.104 

54.620 

52.253 

50.000 

34.007 

32.619 

31.297 

30.034 

28.827 

53 

54 

55 

56 

49 

50 

51 

52 

57 

58 

59 

45 

46 

47 

48 

41 

42 

43 

44  t °c 

39 

40 

60 

61 

R(KΩ

27.677 

26.578 

18.635 

17.932 

17.260 

16.616 

16.001 

15.410 

14.844 

14.302 

25.528 

24.524 

23.566 

22.648 

21.773 

20.935 

20.134 

19.368 

13.782 

13.284 

12.807 

12.384 

11.909 

76 

77 

78 

79 

72 

73 

74 

75 

80 

81 

82 

68 

69 

70 

71 

64 

65 

66 

67  t °c 

62 

63 

83 

84 

R(KΩ

11.487 

11.083 

8.0903 

7.8193 

7.5586 

7.3077 

7.0667 

6.8345 

6.6109 

6.3960 

20.694 

10.321 

9.9628 

9.6187 

9.2882 

8.9706 

8.6655 

8.3723 

6.1890 

5.9894 

5.7976 

5.6126 

5.4346  t °c 

85 

86 

99 

100 

101 

102 

95 

96 

97 

98 

103 

104 

105 

91 

92 

93 

94 

87 

88 

89 

90 

106 

107 

R(KΩ

5.2629 

5.0974 

3.8506 

3.7351 

3.6238 

3.5162 

3.4123 

3.3120 

3.2150 

3.1214 

4.9379 

4.7842 

4.6359 

4.4931 

4.3552 

4.2222 

4.0939 

3.9700 

3.0310 

2.9435 

2.8589 

2.7772 

2.6982 

 

‐15   

‐14   

‐13   

‐12   

‐11   

‐10   

‐9   

‐8    t °c 

‐20   

‐19   

‐18   

‐17   

‐16   

9.2 water/ambient/evaporator temperature sensor resistance    t °c – kΩ    5 k 

50   

51   

52   

53   

54   

55   

56   

57    t °c 

45   

46   

47   

48   

49   

3.1943 

3.0815 

2.9733 

2.8694 

2.7697 

2.6740 

2.5821 

2.4939 

R(KΩ

3.8354 

3.6961 

3.5626 

3.4346 

3.3120 

37   

38   

39   

40   

41   

42   

43   

44    t °c 

32   

33   

34   

35   

36   

5.1978 

5.0000 

4.8109 

4.6300 

4.4569 

4.2912 

4.1327 

3.9808 

R(KΩ

6.3328 

6.0846 

5.8475 

5.6210 

5.4046 

24   

25   

26   

27   

28   

29   

30   

31    t °c 

19   

20   

21   

22   

23   

8.7999 

8.4377 

8.0925 

7.7635 

7.4498 

7.1506 

6.8652 

6.5928 

R(KΩ

10.9023 

10.4393 

9.9987 

9.5794 

9.1801 

11   

12   

13   

14   

15   

16   

17   

18    t °c 

 

 

 

 

10   

R(KΩ

19.6768 

18.7693 

17.9092 

17.0937 

16.3203 

15.5866 

14.8903 

14.2293 

13.6017 

13.0055 

12.4391 

11.9008 

11.3890 

 

 

 

‐2   

‐1   

 

 

  t °c 

‐7   

‐6   

‐5   

‐4   

‐3   

R(KΩ

37.4111   

35.5384 

33.7705 

32.1009 

30.5237 

29.0333 

27.6246 

26.2927 

25.0330 

23.8412 

22.7133 

21.6456 

20.6345 

2.0320 

1.9651 

1.9007 

1.8387 

1.7790 

1.7216 

1.6663 

1.6131 

R(KΩ

2.4091 

2.3276 

2.2493 

2.1740 

2.1017  t °c 

58   

59   

60   

61   

62   

 

 

63    1.3319 

64    1.2908 

65    1.2511 

66   

 

 

1.2128 

 

 

 

 

R(KΩ

1.5618 

1.5123 

1.4647 

1.4188 

1.3746 

- 45 t °c 

108 

109 

122 

123 

124 

125 

118 

119 

120 

121 

 

 

 

114 

115 

116 

117 

110 

111 

112 

113 

 

 

R(KΩ

2.6218 

2.5479 

1.9814 

1.9280 

1.8764 

1.8263 

1.7778 

1.7308 

1.6852 

1.6411 

2.4764 

2.4072 

2.3403 

2.2755 

2.2128 

2.1522 

2.0934 

2.0365 

 

 

 

 

 

10. Dimension 

* Outdoor Unit Dimension 

Model  5kW  7kW  9kW  12kW  15kW  18kW 

No of fan  1  1  1  2  2  2 

840 

285 

610 

830 

310 

710 

880 

360 

770 

830 

310 

1200 

930 

390 

1220 

930 

390 

1220 

 

* Indoor Unit Dimension 

       

- 46 -

advertisement

Key Features

  • Compact design and high performance
  • Reversible operation for heating and cooling
  • Electronic expansion valve
  • Water-side shell-tube heat exchanger
  • Outdoor temperature probe for control
  • LCD controller with thermostat function
  • Auxiliary electrical heater
  • Optional buffer tank for defrosting

Frequently Answers and Questions

What is the operating temperature range of the EVI Split Combo?
The operating temperature range in heating mode is -20°C to 45°C for outside air and +18°C to +55°C for water. In cooling mode, the operating temperature range is +15°C to 45°C for outside air and +7°C to +25°C for water.
What is the maximum operating water pressure for the EVI Split Combo?
The maximum operating water pressure is 7 bar.
What is the recommended installation order?
The recommended installation order is 1. Connect the copper connective pipe between the indoor unit and outdoor unit. 2. Connect the indoor unit to the climate system, cold and hot water lines, and any external heat sources. 3. Connect the load monitor, outdoor temperature sensor, any centralized load control, and external contacts, as well as the cable between outdoor units. 4. Connect the power supply to the outdoor unit.
Does the EVI Split Combo require glycol?
No, because the heat pump is split-type with a refrigeration link between the outdoor unit and the indoor module, it is not necessary to add glycol to the installation.

Related manuals

Download PDF

advertisement