Siemens SLG D10 ANT D5, SLG D11 ANT D5, SLG D12, SLG D10S ANT D5, SLG D11S ANT D5, SLG D12S read/write device Configuration, Installation and Service Manual
Below you will find brief information for SLG D10 ANT D5, SLG D11 ANT D5, SLG D12, SLG D10S ANT D5, SLG D11S ANT D5, SLG D12S. These read/write devices are designed for a range of storage, logistics, and distribution applications. Each model offers a different read/write distance, ranging from 150 mm to 600 mm, with a serial interface for communication with PCs or external PLCs. They also come equipped with various features like multitag capability, anti-collision speed, and a high degree of protection (IP65) for use in harsh industrial environments.
Advertisement
Advertisement
Read/Write Devices
5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-1
Read/Write Devices
5.1
Introduction
5.1.1
SLG with RS 232 Serial Interface
Application area
The SLG with the RS 232 serial interface represents the communication interface between practically any superordinate computer systems/PCs and the mobile data storage unit (MDS).
In accordance with customer-specific requirements, the following variants are available:
S SLG D10 ANT D5
S SLG D11 ANT D5
S SLG D12
A robust housing and the high degree of protection (IP65) permit deployment in the most severe industrial environments.
Design and functions
The SLG is connected via a serial interface (RS 232) of the PC, which permits communication with PCs or external PLCs. Commands and the data to be written or read are converted via a modulator/demodulator circuit.
The amount of data that can be transferred between SLG and MDS depends on the following factors.
S The speed at which the MDS moves through the SLG’s transmission window (antenna)
S The length of the transmission window
Use of the C++ library permits the SLG to be programmed quickly using applications under Windows 9x/2000 and NT 4.0.
Table 5-1 Table providing an overview of the SLG with an RS 232 serial interface
SLG Type Working distance S a
(depending on MDS)
Limit distance S
(dependent on a the MDS)
Temperature range
(during operation)
SLG dimensions
(L x W x H) in mm
Antenna dimensions
(L x W x H) in mm
SLG D10 ANT D5 0 to 380 mm 450 mm –20 to +55 ° C 320 x 145 x 100 340 x 325 x 38
SLG D11 ANT D5 0 to 240 mm 300 mm –20 to +70 ° C 160 x 80 x 40 340 x 325 x 38
SLG D12 0 to 120 mm 150 mm –20 to +70 ° C 160 x 80 x 40 –
Definition of IP65
– Protection against penetration of dust (i.e. dust-proof)
– Full protection against touch
– Protection against water jet
Protection rating
IP65
IP65
IP65
5-2
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Configuration
SLG – MDS
(via RS 232)
C library MDWAPI
(The library permits the use of several serial interfaces at the same time)
6GT2 080-2AA10
(MOBY Software)
Spacing kit
6GT2 690-0AB00
(accessories)
PC RS 232 connecting cable
6GT2 691-0BH50
(6GT2 691-0BN20)
MOBY wide-range power pack
6GT2 494-0AA00
SLG D10 ANT D5
6GT2 601-0AA00
Label / Transponder
Figure 5-1 SLG – MDS configuration via RS 232
SLG D12
6GT2 601-0AB00
24 V connecting cable
6GT2 491-1HH50
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-3
Read/Write Devices
Programming of the SLG D 10, SLG
D 11, and SLG D 12
Communication at the serial interface between the SLG and the superordinate computer system (host) takes place by means of an asynchronous 8-bit binary protocol. The frames are secured by means of a CRC 16.
Can be run on PC models as of the Pentium 2 processor with a serial interface and a Windows 9x/2000/NT 4.0 operating system.
The SLG is connected to a serial interface of the computer. Users work with the PC interfaces COM 1 and/or COM 2; 8 interfaces can be run with additional hardware.
A 32-bit library (MDWAPI for Windows 9x/2000 and NT 4.0) and a programming guide are available to the user for programming (Software MOBY
CD).
For computers that do not run under Windows (e.g. UNIX), the communication specification is described in the programming guide (MDWAPI).
Parameter defaults
The configuration parameters are described in the programming guide
(MDWAPI).
Table 5-2 Ordering data for the MOBY software
MOBY Software
Order No.
6GT2 080-2AA10
Note on MOBY software and licensing
When you purchase an ASM or SLG interface module, this does not include software or documentation. The “Software MOBY” CD-ROM, which contains all the available FBs/FCs for SIMATIC, C libraries for Windows, demo programs, etc., can be ordered additionally .
The CD-ROM also includes the complete set of MOBY documentation (German, English, and in some cases French) in PDF format. When you purchase an ASM or SLG interface module, the price for use of the software including documentation on the ”Software MOBY” CD-ROM is included. The purchaser obtains the right to make copies (duplication license) as needed for customer applications or system development for the plant.
The enclosed contract also applies to the use of software products for a one-off charge.
5-4
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
5.1.2
SLG with RS 422 for SIMATIC S7 and PROFIBUS-DPV1
Application area The SLG D1xS provides inductive communication with the mobile data storage units (MDSs) and the serial link to the interface modules (ASMs).
Various SLGs – for short, medium, and long distances to the MDS – are available to meet customer requirements.
S SLG D10S ANT D5
S SLG D11S ANT D5
S SLG D12S
A robust housing and the high degree of protection (IP65) permit deployment in the most severe industrial environments.
Design and functions
The SLG executes commands received from the interface module. These commands and the data to be read or written are converted via an appropriate modulator/demodulator circuit.
Communication between MDS and the SLG takes place via inductive alternating fields.
The amount of data that can be transferred between SLG and MDS depends on the following factors.
S The speed at which the MDS moves through the transmission window of the SLG’s antenna
S The length of the transmission window
S The MDS type
Table 5-3 Table providing an overview of the SLG with an RS 422 interface
SLG Type Working distance S a
(depending on MDS)
Limit distance S
(depena dent on the MDS)
Temperature range
(during operation)
SLG dimensions
(L x W x H) in mm
Antenna dimensions
(L x W x H) in mm
Protection rating
SLG D10S ANT D5 0 to 380 mm 450 mm –20 to +55 ° C 320 x 145 x 100 340 x 325 x 38 IP65
SLG D11S ANT D5 0 to 240 mm 300 mm –20 to +70 ° C
SLG D12S 1 0 to 120 mm 150 mm –20 to +70 ° C
1 Integrated antenna
160 x 80 x 40
160 x 80 x 40
340 x 325 x 38
–
IP65
IP65
Definition of IP65
– Protection against penetration of dust (i.e. dust-proof)
– Full protection against touch
– Protection against water jet
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-5
Read/Write Devices
5.1.3
Troubleshooting
What should you do if nothing works?
1. Check the supply voltage directly on the SLG connector using a measuring instrument.
2. Check the cabling to the PC
– Do the SLG and PC have the same physical interface?
– Is the polarity of the connecting cable correct (RS 232)?
(RxD of the SLG must be connected to TxD of the PC and vice versa)
– Is the cable shield applied correctly?
Error messages are described in the programming guide (MDWAPI).
Error messages
SLG range too low If the SLG range is too low, check:
– The power supply unit/switched-mode power supply unit (see Section 3.4 on electrical interference)
– Whether there are monitors or other sources of interference in the vicinity (see Section 3.4)
– Whether there is metal in the immediate vicinity (see Section 3.3)
– To attain optimal read/write distances for the ANT D 5, a metal plate is required at a distance of 100 mm (see Table 3-8 and 3-9).
5-6
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
5.2
SLG D10 ANT D5
Application area
The SLG D10 ANT D5 is a high-performance read/write device with a serial interface and a separate antenna, designed specifically for storage, logistics, and distribution applications. It is designed for a range of up to 600 mm (depending on the label). The read/write device has an RS 232 serial interface
(RS 422 interface on request), which permits communication with PCs or external PLCs.
For simple and rapid programming there is a C library available to the user that can be used under Windows 9x, 2000, and NT. The SLG D10 ANT D5 is multitag capable.
Ordering data
Figure 5-2 Read/write device SLG D10 ANT D5
Table 5-4 Ordering data for the SLG D10 ANT D5
Read/write device SLG D10 ANT D5 with an RS 232 serial interface for standard PCs, with a separate antenna
Accessories:
Spacer kit for ANT D5
MOBY wide-range power pack
Cables and connectors
Order No.
6GT2 601-0AA00
6GT2 690-0AB00
6GT2 494-0AA00
See Section 3.6
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-7
Read/Write Devices
Technical data
5-8
Table 5-5 Technical data of the SLG D10 ANT D5
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
Output power
SLG - MDS read/write distances
Software functions
Programming
Multitag
Anti-collision speed
13.56 MHz
Transponder in accordance with ISO
15693 (e.g. I-Code, Tag-it, my-d)
RS 232 (RS 422 on request)
Asynchronous 8 bit
9600 bps to 115.2 kbps
(adjustable)
CRC 16
4 W
Typically 450 mm (see field data) 1
MDS: Read, write, initialize, access rights, multitag
Windows 9x, 2000, and NT, with available 32-bit DLL
Yes
Approx. 20 labels/s identifiable in parallel
24 VDC ± 5% Power supply
Current consumption
Operation
Transient making current
Line length, SLG – PC
With RS 232
With RS 422
Antenna line length
Digital inputs/outputs
Housing
Dimensions (in mm)
For antenna [L x W x H]
For electronic components
[L x W x H]
Color Antenna
SLG housing
Material Antenna
SLG housing
Connector
Antenna (can be connected to the SLG)
Mounting of SLG
Mounting of antenna
Ambient temperature in operation in transit and storage
0.9 A
2.8 A/50 ms
30 m
300 m
3.60 m
None
340 x 325 x 38
320 x 145 x 100 (without connector)
Black
Anthracite
Plastic ASA
Aluminum
TNC connector
4 M6 screws
4 M5 screws
–20
–25
°
°
C to +55
C to +70
°
°
C
C
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Table 5-5 Technical data of the SLG D10 ANT D5
Protection rating in accordance with EN 60529
SLG and antenna
Shock in accordance with
EN 60721-3-7 Class 7M2
Total shock response spectrum type II
Vibration in accordance with EN 60721-3-7
Class 7M2
Weight, approx.
SLG
Antenna
Certifications
IP65
30 g
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
3500 g
1000 g
Radio EN 300 330
CE
Safe for pacemakers
1 To ensure optimal field data in a metallic environment, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
Caution
The antenna cable is prepared in advance. If the cable is changed, the warranty and CE marking become invalid.
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-9
Read/Write Devices
Field data
Transmission window
Table 5-6 Field data of the SLG D10 ANT D5
Limit distance (S g
)
Working distance (S a
)
Length of the transmission window (L d
Width of the transmission window (W)
)
Minimum distance from ANT D5 to ANT D5
Max. 450 mm
(dependent on transponder)
0 to 380 mm
(dependent on transponder)
320 mm
128 mm
≥ 2 m
L d
ÓÓÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
S a, min.
1
S a, max.
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
1 At S a, min
ÓÓÓÓÓÓÓ the transmission window increases
S g
Top view
Transmission window
ÓÓÓÓÓÓÓ
ANT D5
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
S a
S g
ÓÓÓÓÓÓÓ
Spacing kit
100
ÓÓÓÓÓÓÓ
Side view
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
Metal plate
Figure 5-3
ÓÓÓÓÓÓÓ
Transmission window with the SLG D10 ANT D5
5-10
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Metal-free space
Metal-free space with flush mounting a = 150 mm
Metal a a a a
FCC information h = 100 mm (non-metallic spacers)
Figure 5-4 Metal-free space for the SLG D10 ANT D5
Made in Germany
SIEMENS MOBY D SLG D10
FCC ID NXW-MOBYD-SLGD10
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-11
Read/Write Devices
Definition of the distance D
D
D
Distance D ≥ 2 m
Figure 5-5 Distance D: SLG D10 ANT D5
5-12
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Dimensions
(in mm)
10
A
1
Minimal bending radius: 20 mm
4 x ∅ 5.5
Cable length 3.5 m
Anti-kink protection bendable in all directions
7
125
145
View A 300
325
100
25
25
52,5
60
31
7
Note:
The SLG must be grounded using the grounding screw provided.
1
Figure 5-6 Dimensioned drawing of the SLG D10 ANT D5
Note
In order to ensure optimal field data in surroundings where there is metal as well, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-13
Read/Write Devices
Spacing kit for the
MOBY D ANT D5 Table 5-7 Ordering data for the spacing kit MOBY D ANT D5
Order No.
6GT2 690-0AB00 Spacing kit for the ANT D5 made of aluminum with plastic spacers including fixing screws
Individual parts
Aluminum plate 380 x 380 x 2
Plastic bolts 100 x 20
Countersunk head screws M5 x 12
Cylinder head screws M5 x 15
Washer for M5
Spring lock washer for M5
Quantity
1
4
4
4
4
4
Aluminum plate:
10 R
∅ 6 ∅ 9
T = 2
Plastic bolts:
100
ÓÓÓÓ
ÓÓÓÓ
∅ 20
M5 x 20
Figure 5-7 Dimensioned drawing for the spacing kit for the MOBY D ANT D5
5-14
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
4
5
6
Figure 5-8 Mounting diagram for spacer kit
2
1
3
Holes for ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-15
Read/Write Devices
5.3
SLG D11 ANT D5
Application area
The SLG D11 ANT D5 is a medium-performance read/write device with a serial interface and a separate antenna, designed specifically for storage, logistics, and distribution applications. It is designed for a range of up to 300 mm
(depending on the label).
The read/write device has an RS 232 serial interface (RS 422 interface on request), which permits communication with PCs or external PLCs.
For simple and rapid programming there is a C library available to the user that can be used under Windows 9x, 2000, and NT. The SLG D11 ANT D5 is multitag capable.
Ordering data
Figure 5-9 Read/write device SLG D11 ANT D5
Table 5-8 Ordering data for the SLG D11 ANT D5
Read/write device SLG D11 ANT D5 with an RS 232 serial interface for standard PCs, with a separate antenna
Accessories:
ANT D5 spacer kit
MOBY wide-range power pack
Cable and connector
Order No.
6GT2 601-0AC00
6GT2 690-0AB00
6GT2 494-0AA00
See Section 3.6
5-16
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Technical data Table 5-9
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
Technical data of the SLG D11 ANT D5
Output power
SLG - MDS read/write distances
Software functions
Programming
Multitag
Anti-collision speed
13.56 MHz
Transponder in accordance with
ISO 15693
(e.g. I-Code, Tag-it, my-d)
RS 232 (RS 422 on request)
Asynchronous 8 bit
9600 bps to 38.4 kbps
(adjustable)
CRC 16
1 W
Typically 300 mm (see field data) 1
MDS: Read, write, initialize, access rights, multitag
Windows 9x, 2000, and NT, with available 32-bit DLL
Yes
Approx. 20 labels/s identifiable in parallel
Power supply
Nominal value
Permissible range
Current consumption
Operation
Transient making current
Line length, SLG – PC
With RS 232
Antenna line length
Digital inputs/outputs
Housing
Dimensions (in mm)
For antenna [L x W x H]
For electronic components
[L x W x H]
Color Antenna
Material
SLG housing
Antenna
SLG housing
Connector
Antenna (can be connected to the SLG)
Mounting of SLG
Mounting of antenna
24 VDC
20 to 30 VDC
150 mA
600 mA
30 m
3.60 m
None
340 x 325 x 38
160 x 80 x 40 (without connector)
Black
Anthracite
Plastic ASA
Plastic (PA 12)
TNC connector
2 M5 screws
4 M5 screws
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-17
Read/Write Devices
Table 5-9 Technical data of the SLG D11 ANT D5
Ambient temperature in operation in transit and storage
Protection rating in accordance with EN 60529
SLG and antenna
–25
–25
IP65
°
°
C to +70
C to +70
°
°
C
C
Shock in accordance with EN 60721-3-7 Class
7M2
Total shock reply spectrum type II
Vibration in accordance with EN 60721-3-7
Class 7M2
Weight, approx.
SLG
Antenna
Certifications
30 g
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
600 g
1000 g
Radio EN 300 330
CE
Safe for pacemakers
1 To ensure optimal field data in a metallic environment, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
Caution
The antenna cable is prepared in advance. If the cable is changed, the warranty and CE marking become invalid.
5-18
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Field data
Transmission window
Table 5-10 Field data of the SLG D11 ANT D5
Limit distance (S g
)
Working distance (S a
)
Length of the transmission window (L d
Width of the transmission window (W)
)
Minimum distance from ANT D5 to ANT D5
Max. 300 mm
(dependent on transponder)
0 to 240 mm
(dependent on transponder)
300 mm
120 mm
≥ 2 m
L d
ÓÓÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
S a, min.
1
S a, max.
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
1 At S a, min
ÓÓÓÓÓÓÓ the transmission window increases
S g
Top view
Transmission window
ÓÓÓÓÓÓÓ
ANT D5
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
S a
S g
ÓÓÓÓÓÓÓ
Spacing kit
100
ÓÓÓÓÓÓÓ
Side view
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
Metal plate
ÓÓÓÓÓÓÓ
Figure 5-10 Transmission window with the SLG D11 ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-19
Read/Write Devices
Metal-free space
Metal-free space with flush mounting a = 150 mm
Metal a a a a
FCC information h = 100 mm (non-metallic spacers)
Figure 5-11 Metal-free space for the SLG D11 ANT D5
Made in Germany
SIEMENS MOBY D SLG D11
FCC ID NXW-MOBYD-SLGD11
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
5-20
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Definition of the distance D
D
D
Distance D ≥ 2 m
Figure 5-12 Distance D: SLG D11 ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-21
Read/Write Devices
Dimensions
(in mm)
100 Ferrite
Cable length 3.5 m
Minimal bending radius: 20 mm
4 x ∅ 5,5
Anti-kink protection bendable in all directions
A
12 33
80
View A
∅ 5.5
300
325
Figure 5-13 Dimensioned drawing of the SLG D11 ANT D5
Note
In order to ensure optimal field data in surroundings where there is metal as well, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
MOBY D ANT D5 spacer kit see Chapter 5.2
5-22
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
5.4
SLG D12
Application area
The SLG D12 is a medium-performance read/write device with a serial interface and an integrated antenna, designed for a range of up to 150 mm. The read/write device has an RS 232 serial interface (RS 422 interface on request), which permits communication with PCs or external PLCs.
For simple and rapid programming there is a C library available to the user that can be used under Windows 9x, 2000, and NT. The SLG D12 is multitag capable.
Ordering data
Figure 5-14 Read/write device SLG D12
Table 5-11 Ordering data for the SLG D12
Read/write device SLG D12
With an RS 232 serial interface for standard PCs, with an integrated antenna
Accessories:
MOBY wide-range power pack
Cables and connectors
Order No.
6GT2 601-0AB00
6GT2 494-0AA00
See Section 3.6
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-23
Read/Write Devices
Technical data
5-24
Table 5-12 Technical data of the SLG D12
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
SLG - MDS read/write distances
Software functions
Programming
Multitag
Anti-collision speed
13.56 MHz
Transponder in accordance with ISO
15693
(e.g. I-Code, Tag-it, my-d)
RS 232 (RS 422 on request)
Asynchronous 8 bit
9600 bps to 38.4 kbps
(adjustable)
CRC 16
Typically 150 mm (see field data)
MDS: Read, write, initialize, access rights, multitag
Windows 9x, 2000, and NT, with available 32-bit DLL
Yes
Approx. 20 labels/s identifiable in parallel
Power supply
Nominal value
Permissible range
Current consumption
Operation
Transient making current
Line length, SLG – PC
With RS 232
Digital inputs/outputs
Housing
Dimensions (L x B x H) in mm, without connector
Color
Material
Mounting
Ambient temperature in operation in transit and storage
Protection rating in accordance with
EN 60529
Shock in accordance with EN 60721-3-7
Class 7 M2
Total shock reply spectrum type II
Vibration in accordance with EN 60721-3-7
Class 7M2
24 VDC
20 to 30 VDC
150 mA
600 mA
30 m
None
160 x 80 x 40
Anthracite
Plastic (PA 12)
2 M5 screws
–25
–25
IP65
30 g
°
°
C to +70
C to +70
°
°
C
C
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Field data
Transmission window
Table 5-12 Technical data of the SLG D12
Weight, approx.
Certifications
500 g
Radio EN 300 330
CE
Safe for pacemakers
Table 5-13 Field data SLG D12
Limit distance (S g
) Max. 150 mm
(dependent on transponder)
Working distance (S a
) 0 to 120 mm
(dependent on transponder)
Length of the transmission window (L d
)
Width of the transmission window (W)
120 mm
48 mm
Minimum distance from SLG D12 to SLG D12 ≥ 500 mm
Transmission window Transponder
Side view
SLG D12
Top view
Standard
Configuration: lengthwise x-axis (L x
)
1
1 At S a, min
the transmission window can be enlarged in comparison to the standard configuration
Figure 5-15 Transmission window of the SLG D12
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-25
Read/Write Devices
Metal-free space
Metal h h = Physical height of the SLG = 40 mm b a b a
FCC information
Metal a, b = Metal-free distances = 50 mm
Figure 5-16 Metal-free space of SLG D12
Made in Germany
SIEMENS MOBY D SLG D12
FCC ID NXW-MOBYD-SLGD12
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
5-26
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Definition of distance D
D
D
Figure 5-17 Distance D: SLG D12
Distance D ≥ 0.5 m
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-27
Read/Write Devices
Dimensions
(in mm)
80
5
X
70
Y
∅ 5.5
5
A
26
12 33
Figure 5-18 Dimensioned drawing of the SLG D12
View A
90
160
40
5-28
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
5.5
SLG D10S ANT D5
Application area
The SLG D10S ANT D5 is a high-performance read/write device with a serial interface and a separate antenna, designed specifically for storage, logistics, and distribution applications. It is designed for a range of up to 600 mm
(depending on the label). The read/write device has an RS 422 serial interface, which permits communication via interface modules (ASM 452,
ASM 473 und ASM 475) to the SIMATIC S7 or PROFIBUS-DPV1.
FC 45 is available to the user for simple and rapid programming.
Due to the high degree of protection (IP65) and the use of high-quality materials, the SLG D10S ANT D5 ensures trouble-free use even under the most extreme industrial conditions.
Figure 5-19 Read/write device SLG D10S ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-29
Read/Write Devices
Ordering data
Technical data
Table 5-14 Ordering data for the SLG D10S ANT D5
Read/write device SLG D10S ANT D5
With an RS 422 serial interface for connecting to an ASM 452, ASM 473, and ASM 475, with separate antenna
Accessories:
ANT D5 spacer kit
MOBY wide-range power pack
Cables and connectors
Order No.
6GT2 602-0AA00
6GT2 690-0AB00
6GT2 494-0AA00
See Section 3.6
Table 5-15 Technical data of the SLG D10S ANT D5
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
Output power
SLG-MDS read/write distances
Software functions
Programming
Transmission protocol
Multitag
Power supply
13.56 MHz
S I-Code1
(e. g. MDS D139, MDS D160)
S Transponder in accordance with ISO
15693
(e. g. I-Code SLI, Tag-it HFI, my-d SRF 55V10P)
RS 422
Asynchronous 8 bit
19.2 bps to 115.2 kbps
(ASM-dependent)
CRC 16
4 W
Typically 450 mm (see field data) 1
Read, write, initialize MDS
The command Repeat is not permissible.
The user has a maximum buffer of
256 bytes in the SLG for pipelining.
Hence, a command string can only contain as many individual commands as such that the sum of the header and user data fields lengths of the individual messages does not exceed this value. The
FC 45 limits the length of the user data fields to 233 bytes per individual message.
FC 45
3964 R in preparation
24 VDC + 5%
5-30
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Table 5-15 Technical data of the SLG D10S ANT D5
Current consumption
Operation
Transient making current
Line length (SLG – SIMATIC S7)
With RS 422
Antenna line length
Digital inputs/outputs
Housing
Dimensions (in mm)
For antenna [L x W x H]
For electronic components
[L x W x H]
Color Antenna
SLG housing
Antenna Material
SLG housing
Connector
Antenna (can be connected to the
SLG)
Mounting of SLG
Mounting of antenna
Ambient temperature in operation in transit and storage
Protection rating in accordance with
EN 60529
SLG and antenna
Shock in accordance with EN 60721-3-7
Class 7M2
Total shock response spectrum type II
Vibration in accordance with EN
60721-3-7 Class 7M2
Weight, approx.
SLG
Antenna
Certifications
0.9 A
2.8 A/50 ms
300 m
3.60 m
None
340 x 325 x 38
320 x 145 x 100 (without connector)
Black
Anthracite
Plastic ASA
Aluminum
TNC connector
4 M6 screws
4 M5 screws
–20
–25
IP65
30 g
°
°
C to +55
C to +70
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
3500 g
1000 g
°
°
C
C
Radio EN 300 330
CE
Safe for pacemakers
1 To ensure optimal field data in a metallic environment, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-31
Read/Write Devices
Caution
The antenna cable is prepared in advance. If the cable is changed, the warranty and CE marking become invalid.
Note
After the ANT D5 antenna is removed from the SLG and connected again
(screwed on), an init_run must be executed.
5-32
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Field data
Transmission window
Table 5-16 Field data of the SLG D10S ANT D5
Limit distance (S g
)
Working distance (S a
)
Length of the transmission window (L d
Width of the transmission window (W)
)
Minimum distance from ANT D5 to ANT D5
Max. 450 mm
(dependent on transponder)
0 to 380 mm
(dependent on transponder)
320 mm
128 mm
≥ 2 m
L d
ÓÓÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
S a, min.
1
S a, max.
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
1 At S a, min
ÓÓÓÓÓÓÓ the transmission window increases
S g
Top view
Transmission window
ÓÓÓÓÓÓÓ
ANT D5
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
S a
S g
ÓÓÓÓÓÓÓ
Spacing kit
100
ÓÓÓÓÓÓÓ
Side view
ÓÓÓÓÓÓÓ Metal plate
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
Figure 5-20 Transmission window with the SLG D10S ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-33
Read/Write Devices
Metal-free space
Metal-free space with flush mounting a = 150 mm
Metal a a a a
FCC information h = 100 mm (non-metallic spacers)
Figure 5-21 Metal-free space for the SLG D10S ANT D5
Made in Germany
SIEMENS MOBY D SLG D10S
FCC ID NXW-MOBYD-SLGD10
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
5-34
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Definition of the distance D
D
D
Distance D ≥ 2 m
Figure 5-22 Distance D: SLG D10S ANT D5
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-35
Read/Write Devices
Dimensions
(in mm)
10
A
1
Minimal bending radius: 20 mm
4 x ∅ 5.5
Cable length 3.5 m
Anti-kink protection bendable in all directions
7
125
145
View A 300
325
100
31
60
7
25
25
52,5
Note:
The SLG must be grounded using the grounding screw provided.
1
Figure 5-23 Dimensioned drawing of the SLG D10S ANT D5
Note
In order to ensure optimal field data in surroundings where there is metal as well, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
MOBY D ANT D5 spacer kit
5-36 see Chapter 5.2
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
5.6
SLG D11S ANT D5
Application area
The SLG D11 ANT D5 is a medium-performance read/write device with a serial interface and a separate antenna, designed specifically for storage, logistics, and distribution applications. It is designed for a range of up to 300 mm
(depending on the label).
The read/write device has an RS 422, serial interface, which permits communication via interface modules (ASM 452, ASM 473 und ASM 475) to the
SIMATIC S7 or PROFIBUS-DPV1.
FC 45 is available to the user for simple and rapid programming.
A robust housing and the high degree of protection (IP65) permit deployment in the most severe industrial environments.
Ordering information
Figure 5-24 Read/write device SLG D11S ANT D5
Table 5-17 SLG D11S ANT D5 ordering information
Read/write device SLG D11S ANT D5
With an RS 422 serial interface for connecting to an
ASM 452, ASM 473 and ASM 475, with separate antenna
Accessories:
Spacer kit for ANT D5
MOBY DC 24 V wide-range power pack
Cables and connectors
Order No.
6GT2 602-0AC00
6GT2 690-0AB00
6GT2 494-0AA00
See Section 3.6
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-37
Read/Write Devices
Technical data Table 5-18 SLG D11S ANT D5 technical data
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
Output power
SLG – MDS read/write distances
Software functions
13.56 MHz
S I-Code1
(e. g. MDS D139, MDS D160)
S Transponder in accordance with
ISO 15693
(e. g. I-Code SLI, Tag-it HFI, my-d SRF 55V10P)
RS 422
Asynchronous 8 bit
19.2 kBaud
CRC 16
1 W
Typically 300 mm (see field data) 1
MDS read, write, initialize
Command strings are not permitted.
The Repeat command has not been implemented.
The greatest possible length of the user data field in a command is
233 bytes.
FC 45
3964 R
No
Programming
Transmission protocol
Multitag
Power supply
Operation
Permissible range
Current consumption
Operation
Transient making current
Line length (SLG – SIMATIC S 7)
With RS 422
Antenna line length
Digital inputs/outputs
24 VDC
20 V to 30 VDC
150 mA
600 mA
300 m
3.60 m
None
5-38
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Field data
Table 5-18 SLG D11S ANT D5 technical data
Housing
Dimensions (in mm)
For antenna [L x W x H]
Color for the electronics
[L x B x H]
Antenna
Material
SLG housing
Antenna
SLG housing
Connector
Antenna (can be connected to the SLG)
Mounting of SLG
Mounting of antenna
Ambient temperature in operation in transport and storage
Protection rating in accordance with EN 60529
SLG and antenna
340 x 325 x 38
160 x 80 x 40 (without connector)
Black
Anthracite
Plastic ASA
Plastic (PA 12)
TNC connector
2 M5 screws
4 M5 screws
–25 ° C to +70 ° C
–25 ° C to +70 ° C
IP65
Shock in accordance with
EN 60721-3-7 Class 7M2
Total shock reply spectrum type II
Vibration in accordance with EN 60721-3-7
Class 7M2
Weight, approx.
SLG
Antenna
Certifications
30 g
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
Approx. 600 g
Approx. 1000 g
Radio EN 300 330
CE
Safe for pacemakers
1 To ensure optimal field data in a metallic environment, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
Table 5-19 SLG D11S ANT D5 field data
Limit distance (S g
)
Working distance (S a
)
Length of the transmission window (L d
)
Max. 300 mm
(dependent on transponder)
0 to 240 mm
(dependent on transponder)
300 mm
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-39
Read/Write Devices
Transmission window
Table 5-19 SLG D11S ANT D5 field data
Width of the transmission window (W)
Minimum distance from ANT D5 to ANT D5
120 mm
≥ 2 m
L d
Top view
ÓÓÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
S a, min.
1
S a, max.
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓÓÓ
1 At S a, min
the transmission window increases
S g
Transmission window
ANT D5
Spacing kit
Side view
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
S a
S g
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
100
ÓÓÓÓÓÓÓ
Metal plate
ÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓ
Figure 5-25 SLG D11S ANT D5 transmission window
5-40
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Metal-free space
Metal-free space with flush mounting a = 150 mm
Metal a a a a
FCC information h = 100 mm (non-metallic spacers)
Figure 5-26 SLG D11S ANT D5 metal-free space
Made in Germany
SIEMENS MOBY D SLG D11S
FCC ID NXW-MOBYD-SLGD11
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-41
Read/Write Devices
Definition of the distance D
D
D
Distance D ≥ 2 m
Figure 5-27 Distance D: SLG D11S ANT D5
5-42
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Dimensions (in mm)
100 Ferrite
Cable length 3.5 m
Minimal bending radius: 20 mm
4 x ∅ 5.5
Anti-kink protection bendable in all directions
A
12 33
80
View A
∅ 5.5
300
325
Figure 5-28 SLG D11S ANT D5 dimensioned drawing
Note
In order to ensure optimal field data in surroundings where there is metal as well, the ANT D5 is calibrated at the factory at a distance of 100 mm from metal.
MOBY D ANT D5 spacer kit
See Chapter 5.2
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-43
Read/Write Devices
5.7
SLG D12S
Application area
The SLG D12 is a medium-performance read/write device with a serial interface and an integrated antenna, designed for a range of up to 150 mm (depending upon the label). The read/write device has an RS 422 serial interface, which permits communication via interface modules (ASM 452, ASM 473 und ASM 475) to the SIMATIC S7 or PROFIBUS-DP-V1.
FC 45 is available to the user for simple and rapid programming.
A robust housing and the high degree of protection (IP65) permit deployment in the most severe industrial environments.
Ordering information
Figure 5-29 SLG D12S read/write device
Table 5-20 SLG D12S ordering information
SLG D12S read/write device
With an RS 422 serial interface for connecting to an
ASM 452, ASM 473 und ASM 475, with integrated antenna
Accessories:
MOBY DC 24 V wide-range power pack
Cables and Connectors
Order No.
6GT2 602-0AB00
6GT2 494-0AA00
See Section 3.6
5-44
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Technical data Table 5-21 SLG D12S technical data
Inductive interface to MDS
Transmission frequency
Supported transponders
Serial interface to user
Transmission protocol
Data transmission speed
Data backup
Output power
SLG – MDS read/write distances
Software functions
Programming
Transmission protocol
Multitag
Power supply
Operation
Permissible range
Current consumption
Operation
Transient making current
Line length (SLG – SIMATIC S 7)
With RS 422
Digital inputs/outputs
Housing
Dimensions (L x B x H) in mm, without connectors
Color
Material
Mounting
Ambient temperature in operation in transit and storage
24 VDC
20 V to 30 VDC
150 mA
600 mA
300 m
None
160 x 80 x 40
Anthracite
Plastic (PA 12)
2 M5 screws
–25 ° C to +70 ° C
–25 ° C to +70 ° C
13.56 MHz
S I-Code1
(e. g. MDS D139, MDS D160)
S Transponder in accordance with
ISO 15693
(e. g. I-Code SLI, Tag-it HFI, my-d SRF 55V10P)
RS 422
Asynchronous 8 bit
19.2 kBaud
CRC 16
1 W
Typically 150 mm (see field data)
MDS read, write, initialize
Command strings are not permitted.
The Repeat command has not been implemented.
The greatest possible length of the user data field in a command is 233 bytes.
FC 45
3964 R
No
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-45
Read/Write Devices
Field data
Table 5-21 SLG D12S technical data
Protection rating in accordance with
EN 60529
Shock in accordance with EN 60721-3-7
Class 7 M2
Total shock response spectrum Type II
Vibration in accordance with EN 60721-3-7
Class 7M2
Weight, approx.
Certifications
IP65
30 g
1 g (9 to 200 Hz)/
1.5 g (200 to 500 Hz)
600 g
Radio EN 300 330
CE
Safe for pacemakers
Table 5-22 SLG D12S field data
Limit distance (S g
)
Working distance (S a
)
Max. 150 mm
(dependent on transponder)
0 to 120 mm
(dependent on transponder)
Length of the transmission window (L d
)
Width of the transmission window (W)
120 mm
48 mm
Minimal distance from SLG D12S to SLG D12S ≥ 500 mm
5-46
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Transmission window
Read/Write Devices
Transmission window Transponder
Side view
SLG D12S
Top view
Standard
Configuration: lengthwise x-axis (L x
)
1
1 At S a, min
the transmission window can be enlarged in comparison to the standard configuration
Figure 5-30 Transmission window of the SLG D12S
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-47
Read/Write Devices
Metal-free space
Metal h h = Physical height of the SLG = 40 mm b a b a
FCC information
Metal a, b = Metal-free distances = 50 mm
Figure 5-31 SLG D12S metal-free space
Made in Germany
SIEMENS MOBY D SLG D12S
FCC ID NXW-MOBYD-SLGD12
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS:
(1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Caution
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
5-48
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Read/Write Devices
Definition of the
Distance D
D
D
Figure 5-32 Distance D: SLG D12S
Distance D ≥ 0.5 m
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618 5-49
Read/Write Devices
Dimensions (in mm)
80
5
X
70
Y
∅ 5.5
5
A
26
12 33
Figure 5-33 Dimensioned drawing SLG D12S
View A
90
160
40
5-50
MOBY D Configuration, Installation and Service Manual
(4) J31069-D0147-U001-A3-7618
Advertisement
Key features
- Read/write distances from 150mm to 600mm
- Serial interface (RS 232 or RS 422)
- Multitag capability
- Anti-collision speed
- High degree of protection (IP65)
- C library for programming under Windows
- Power supply 24 VDC
- FC 45 for programming under SIMATIC S7 or PROFIBUS
- Robust housing
- Designed for storage, logistics, and distribution