- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- LG
- CV-H 186BLB0
- Service manual
- 56 Pages
LG CV-H 186BLB0, 246BLB0 Room Air Conditioner SERVICE MANUAL
Below you will find brief information for Room Air Conditioner CV-H186BLB0, Room Air Conditioner CV-H246BLB0. This document provides detailed instructions on the operation and maintenance of these room air conditioners, specifically those models using the new R-407C refrigerant. The manual covers a range of topics, including installation, operation, troubleshooting, and component replacement. You'll find diagrams, illustrations, and clear explanations to help you understand the features of your air conditioning system.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Room Air Conditioner
(Convertible Type)
SERVICE MANUAL
MODEL: CV-H186BLB0
CV-H246BLB0
(Applied to new Refrigerant R-407C)
Contents
Functions .................................................................................................................................3
Product Specifications (Cooling & Heating).........................................................................5
Dimensions ..............................................................................................................................6
Refrigeration Cycle Diagram ..................................................................................................8
Wiring Diagram........................................................................................................................9
Operation Details ..................................................................................................................10
Display Function ...................................................................................................................18
Self-diagnosis Function........................................................................................................18
Installation .............................................................................................................................19
Operation ...............................................................................................................................36
Disassembly of the parts (Indoor Unit) ...............................................................................38
Cycle.......................................................................................................................................42
Cycle Troubleshooting Guide...............................................................................................45
Electronic Parts Troubleshooting Guide.............................................................................46
Electronic control device......................................................................................................50
Schematic Diagram ...............................................................................................................51
Exploded View and Replacement Parts List.......................................................................52
–2–
Functions
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (Thermistor)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 seconds at the starting.
Time Delay Safety Control
• Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
• High, Med, Low, Chaos
Operation indication Lamps (LED)
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode or Hot Start Mode (only Heating Model)
--- Lights up during compressor running
(only Cooling Model)
Soft Dry Operation Mode
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed.
Airflow Direction Control
• The louver can be set at the desired position or swing up and down, right and left (not on all models) automatically.
Auto Operation
• The setting temperature, indoor fan speed and desired operation made are automatically set by fuzzy rule.
–3–
Deice (defrost) control (Heating)
• Both the indoor and outdoor fan stops during deicing.
• Hot start after deice ends.
Hot-start Control (Heating)
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C.
Remote Controller
Operation ON/OFF
Operation Mode Selection
(Cooling model only)
(Heating model only)
Fan Speed Selection
Cooling Operation Mode.( )
Soft Dry Operation Mode.( )
(Low) (Med)
Auto Operation Mode.( )
Heating Operation Mode.( )
(High) (CHAOS)
Room Temperature Display
: High:39°C °Í LOW:11°C
Temperature Setting
TEMPERATURE
LOW HIGH
Cooling
Down to 18°C
Up to 30°C
Heating
Down to 16°C
Up to 30°C
Setting the Time or Timer
Timer Selection
ON OFF
: OFF, ON, OFF °Í ON
Timer Setting
SET
Timer Cancel
CANCEL
: Cancel Sleep Mode, Timer ON or Timer OFF.
Sleep Operation
: 1, 2, 3, 4, 5, 6, 7hr, Off Timer
Airflow Direction Control
Fan Operation Mode
Reset
: Fan Operates without cooling.
–4–
Product Specifications
Model Name
Item Unit
Cooling Capacity
Heating Capacity
Moisture Removal
Power Source
Btu/h(kcal/h)
Btu/h(kcal/h)
/h
ø, V, Hz
Air Circulation
Input
Running Current
Indoor
Outdoor
Cooling
Heating
Cooling
Heating m
3
/min
W
A
E.E.R.(Cooling)
C.O.P.(Heating)
Dimensions
(W x H x D)
Net. Weight
Service Valve &
Connecting Tube
Indoor
Outdoor
Indoor
Outdoor
Btu/h-W w/w mm kg
Refrigerant (R-410A)
Airflow Direction Control (Up & Down) g
Remocon Type
Liquid
Gas
Sleeping Operation
Drain Hose
Connecting Wire
Main Power Cable
Time Delay Safety Function
Air Circulation
Soft Dry
Fan Speed (Indoor)
Timer
Self-Diagnosis
Auto-Restart
CV-H186BLB0 CV-H246BLB0
19,000(4,788)
19,000(4,788)
2.5
3ø, 220-240V~, 50Hz
23,300(6,048)
23,300(6,048)
3.5
13.5
45
2,050
2,000
9.0
8.8
9.27
2.78
15
50
2,600
2,550
11.8
11.6
8.96
2.76
1,200 x 205 615
870 x 655 320
30
59
1,500 1,650
O
L.C.D Wiress
1/4"(6.35)
1/2"(12.7) 5/8"(15.88)
O
O
0.75mm
2
2.0mm
2
2.5mm
2
O
O
O
3 (Hi, Med, Low)
24Hrs
O
O
–5–
Dimensions
(1) Indoor Unit
1200mm
615mm
R
205mm
63mm
38mm
265mm
392mm
468mm
(Installation Plate)
175mm
36mm
–6–
1076mm
(Rear Side)
250mm
36mm
(2) Outdoor Unit
W
L7
MODEL
DIM
L6
L7
L8
L9
L10
L11
L2
L3
L4
L5
W
H
D
L1 mm mm mm mm mm mm mm mm mm mm mm mm mm mm
L6 L8 L9
–7–
CV-H186BLB0
CV-H246BLB0
546
162
162
54
74.5
79
25
340
630
25
870
655
320
370
Gas side
3-way valve
Liquid side
3-way valve
Refrigeration Cycle Diagram
• CV-H186BLB0
• CV-H246BLB0
INDOOR UNIT
LIQUID SIDE
OUTDOOR UNIT
CAPILLARY TUBE
HEAT
EXCHANGER
HEAT
EXCHANGER
GAS SIDE
COMPRESSOR
REVERSING
VALVE
COOLING
HEATING
MODEL
CV-H186BLB0
CV-H246BLB0
Pipe size(Diameter:ø)
Gas Liquid
1/2"
5/8"
1/4"
1/4"
Piping length(m)
Rated
7.5
7.5
Max
15
20
For installation over rated distance, 30g of refrigerant should be added for each meter.
ex) If 18K or 24K Model is installed at a distance of 15m, 300g of refrigerant should be added.
(15-7.5) x 30g = 225g
Elevation(m)
Rated Max
5
5
8
8
–8–
Wiring Diagram
(1) Indoor Unit
CV-H186BLB0, CV-H246BLB0
TRANS -
FORMER
CAPACITOR
BR YL
GN/YL
MOTOR
OR
RD
BL
BK
DOOR S/W 1,2
GN/YL
CN - TRANS
CN - FAN
RY-L
RY-M
RY-H
FUSE
T3.15A
RY-COMP
CN-4WAY
RY-4WAY
1(L) 2(N)
THERMISTOR
CN-TH
MAIN PCB
ASSY
STEP
MOTOR
STEP
MOTOR
3 4 5 6
RY-FAN
GN/YL
7 8
TERMINAL
BLOCK
CN-DISP
DISPLAY PCB
ASSY
POWER
INPUT
TO OUTDOOR UNIT
WIRING DIAGRAM
3854A20125G
(2) Outdoor Unit
CV-H186BLB0, CV-H246BLB0
OUTDOOR WIRING DIAGRAM
R
COMP
S
C
BL CAPACITOR
RD
BR
WH
REVERSING
VALVE
FAN
MOTOR
YL
OR
BK
CAPACITOR
OR
BK
TB1 pipe TH
L1
D.P
TNS
NO NC NO NC
L2
BK
L3
BL
TB2
L4
GN/YL
TERMINAL
BLOCK
3 4 5 6 7
TO INDOOR UNIT
RD
BK
OR
BK
WH
1
2
3
4
5
6
7
8
9
FUSE T3.15A
3854A20128P
–9–
Operation Details
(1) The function of main control
1. Time Delay Safety Control
• 3min… The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 5sec… Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
• 30sec… The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Airflow Direction Control
• This function is to swing the louver up and down automatically and to set it at the desired position.
• The procedure is as the following.
1st ; Press the ON/OFF Button to operate the product.
2nd ; Press the Airflow Direction Control Button to swing the louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the louver as the desired position.
MODE 0
MODE 1
MODE 2
MODE 3
MODE 4
MODE
5
MODE
6
MODE
7
135
°
Cooling
MODE 9
(CLOSE)
For Heating Model
• Airflow direction control figure when installed on the floor.
• Airflow direction control figure when installed under the ceiling.
OPEN
MODE 1
MODE 2
Cooling
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
12
°
135
°
OPEN
MODE 1
MODE 2
Cooling
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
12
°
135
°
–10–
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
More than More than
Selecting fan speed
3 minutes 3 minutes
Selecting fan speed
COMPRESSOR ON OFF ON OFF
Selecting fan speed
ON
4. Cooling or Heating Mode with Sleep Mode Auto Operation
• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the operation diagram is as following.
â–
Cooling Mode with the Sleep Mode
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.
30 minutes 30 minutes
1°C
COMP. ON
(SET TEMP.+0.5°C)
1°C
COMP. OFF
(SET TEMP. -0.5°C)
INDOOR FAN
COMPRESSOR
Low
ON
More than
3 minutes
Low
OFF
More than
3 minutes
Low Low
ON OFF
Low
ON
â–
Heating Mode with the Sleep Mode. (Heating model only)
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Setting Temp. +3°C
(Compressor OFF)
Setting Temp.
(Compressor ON)
Indoor Fan
Compressor
Med.
ON
Med.
OFF
Med.
ON
–11–
Med.
OFF
Med.
ON
Med.
OFF
5. Auto Operation
• The operation procedure is as following. (Cooling & Heating Model)
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
Setting temperature
Intake-air temperature
Operation Mode are automatically decided by Fuzzy rule.
below 21°C
Heating
Over
21°C
~
Soft Dry below
24°C
Over 24°C
Cooling
• If initial mode is decided, that mode is continued without the room temperature changing.
• For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
â–
Auto Operation for Cooling.
Operation Condition Intake-air Temperature Setting temperature Fan speed Air Direction Control
When Auto Operation initial start
When pressing room temperature setting button during Auto Operation
Over 26°C
Over 24°C~below 26°C
25°C
Intake air -1°C
Over 22°C~below 24°C Intake air -0.5°C
Over 20°C~below 22°C intake air temperture below 20°C
Over 20°C~below 30°C
20°C
Fuzzy control
Controlled by Fuzzy logic below 20°C over 30°C
20°C
30°C
In this mode, when pressing the vertical air diretion control.
Button, louvers moves to 1/f rhythm (refer to page 17)
Intake-Air temp
Setting Temp. +0.5°C
(Compressor OFF)
Setting Temp.-0.5°C
(Compressor ON)
Indoor Fan
Compressor
ON OFF
–12–
Fuzzy Speed
ON OFF
â–
Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
â–
Auto Operation for Heating. (Heating model only)
Intake Air temp.
Setting temp.
20°C
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
Setting temp.
21.5°C
Intake air temp. +0.5°C
20.5°C
20°C
20°C 21°C
Intake-Air temp.
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, louver moves as following cycle.
MODE0
MODE1
MODE2
Start
MODE3
MODE4
MODE5
MODE6
End
MODE9
(CLOSED)
–13–
6. Natural wind by CHAOS logic
For more fresh feeling than other fan speed mode, press the indoor fan Speed Selector and set to CHAOS mode.
In this mode, the wind blows like natural breeze by automatically changing fan speed according to the CHAOS logic.
Intake Air temp.
Setting CHAOS Natural wind
Cooling on temp.
(Setting temp.+0.5)
Setting temp.
Cooling off temp.
(Setting temp.-0.5)
INDOOR FAN
OUTDOOR FAN/COMP.
: Setting fan speed : CHAOS Natural wind : LOW : COMP ON
GRAPH of Natural wind by the CHAOS logis (During Cooling operation)
: COMP OFF
Intake Air temp.
Setting CHAOS Natural wind
Heating off temp.
(Setting temp.+3.0)
Heating on temp.
(Setting temp.) 30sec
INDOOR FAN
LOW OR STOP
OUTDOOR FAN/COMP.
: Setting fan speed : CHAOS Natural wind : LOW : COMP ON
GRAPH of Natural wind by the CHAOS logis (During Heating operation)
: COMP OFF
–14–
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
• For Heating Model
Indoor piping temp.
28
°
C
26
°
C
Intake Air temp.
Setting temp. +3.0ËšC
(Compressor OFF)
Setting temp.
(Compressor ON)
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
4-WAY VALVE
Fan
Stops minimum
1min.
ON
ON
Low
Fan
Selected
Fan minimum
3min.
OFF
OFF
Low Fan
ON
ON
Selected Fan minimum
30sec.
minimum
3min.
OFF
OFF
Low Fan
ON
8. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°….
• During heating operation, if piping temperatures falls below 26°C fan stops.
• The operation diagram is as following.
Fan Stop minimum
1min.
ON
ON
Low
Fan
Selected
Fan
PIPING
TEMPERATURE
28
°
C
26
°
C
1min
INDOOR FAN
COMPRESSOR
: Selected Fan : Low Fan
ON
: Fan Stop
–15–
9. Deice Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature.
• The first deicing starts only when the outdoor pipe temperature falls below -6°C after 30 minutes passed from starting of heating operation.
• Deicing ends after 5 minutes passed from starting of deice operation or when the outdoor pipe temperature rises over 12°C even if before 6 minutes.
• The second deicing starts only when the outdoor pipe temperture falls below -6°C after 30 minutes passed from ending of the first deicing.
The outdoor piping Temp.
More than 30 minutes of heating operation
Within
6 minutes
Deicing
More than 30 minutes of heating operation
Deicing
12
°
C
DEICE OFF
-6
°
C
DEICE ON
HOT-
START
INDOOR FAN ON OFF ON OFF
COMPRESSOR
ON ON
ON
ON
4-WAY VALVE
ON OFF ON OFF
10. Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the operation mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room temperature falls below compressor OFF temperature, Compressor OFF.
• In micom dehumidify mode, control of fan speed is as following.
Intake Air temp.
Setting temp. +1.0ËšC
(Compressor ON)
Setting temp.
Setting temp. -0.5ËšC
(Compressor OFF)
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
Cooling 2min.58sec.
10min.
7min.
10min.
Within 7min. Cooling 2min.58sec.
ON
ON
Selected
Fan
OFF
OFF
ON
ON
OFF
OFF
Low Fan
–16–
ON
ON
OFF
OFF
ON
ON
Selected
Fan
OFF
OFF
ON
ON
Low Fan
OFF
OFF
11. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
Operation Mode
FAN Speed
Setting Temp.
Room Temp°
√
24°C
Cooling
High
22°C
Heat pump Model
21°C °¥Room Temp°¬24°C
Soft Dry
Soft Dry Rule
Air Intake Temperature
Room Temp °¥21°C
Heating
High
24°C
• Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to intake Air temperature.
Forced
Operation Button
Press the Forced Operation Button.
R
• Press the Forced Operation Button once again to stop operation.
12. Protection of the evaporator pipe from frosting
If the te
mperature of the indoor coil is below -2°C after 7 minutes from starting the compressor, the compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor and the temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoperated.
Indoor fa
n operates at low speed (comp. OFF) or at selected speed (comp. ON)
13. Inlet grille open
Once the inlet grille is opened during operation of the unit, the unit automatically stops operation and the lamps will be turned-off. But memorized functions are still available.
When the inlet grille is closed again, the unit become waiting state for operation. From then, the unit can be operated by forced operation button or Start/Stop button of remote controller.
14. Test Operation
• When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan regardless of room temperature and resets in 18 min.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
15. Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance should be on the automatically operates in the mode on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)
• If no input by the remote controller or no switching of the slide switch within 7 hr after the appliance operates by the Auto Restarting operation, the appliance is forced to stop at the moment of 7-hr elapse.
–17–
Display Function
1. Heating Model
Operation Indicator
• Coolling, Soft Dry, Fan, Heating
Timer Indicator
• Timer Mode
Sleep Timer Indicator
• Sleep Mode
Deice Indicator
• Hot-start, Deice
Operation Indicator
• Coolling, Soft Dry, Fan, Heating
Timer Indicator
• Timer Mode
Sleep Timer Indicator
• Sleep Mode
Outdoor Unit Operation
• Outdoor Unit Operating
Note)
For normal operation after checking by test mode, you should press SW1 nine times for resetting or reconnect the power cord.
Self-diagnosis Function
1. Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below -2°C after 7 mins from starting the compressor, the compressor and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
2. Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
–18–
Installation
1. Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
R
More than
20cm
More than eye-level
(Ceiling installation)
More than
20cm
More than
20cm
R
More than
20cm
2) Outdoor unit
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
(Floor/Wall installation)
More than 10cm More than 10cm
3) Piping length and the elevation
MODEL
18K BTU
24K BTU
Pipe Size
GAS
1/2"
5/8"
LIQUID
1/4"
1/4"
Length A(m)
Rated
Max.
7.5
7.5
15
20
Elevation B(m)
Rated
Max.
* Additional refrigerant
(g/m)
5
5
8
8
30
30
• If 18K or 24K Model is installed at a distance of 15m, 225g of refrigerant should be added .........................................................(15-7.5) x 30g
–19–
More than 70cm
Indoor unit
B
A
Outdoor unit
2. Indoor unit installation
â–
Before Installing, prepare Installation Plates
• 'Installation Plates' are attached at the bottom of indoor unit.
Detach them by removing each 3 screws at both sides.
• Detach 'Side Plate (R,L)' by removing each 2 screws on both sides.
• Pull the upper right and left side of 'Inlet Grille' to the front, and it will stop at slightly tilted position.
• Unhook the 'Inlet hanger' from the 'Hanger screw' on the both left and right side.
• Detach the 'Inlet Grille' from the Indoor Unit.
1) Installation on the ceiling
• Measure and mark the position for the Suspension bolts and the piping hole.
• Drill the hole for anchor nut on the ceiling.
Install Plate
1)
Inlet Grille
1076
Before secure the Installation Plates, select the bent direction of the Installion Plate to the inside or the outside according to the installation circumstances.
2)
R
Side Plate
Inlet hanger
Hanger screw
265
1236
Suspension bolt
Center-line for the piping hole
265
• Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Indoor
WALL
Outdoor
5~7mm
–20–
• Insert the nuts and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
• Mount the suspension bolts to the anchor-nuts firmly.
• Secure the Installation plates onto the Suspension bolts (adjust level roughly.) using nuts, washers and spring washers.
1)
Suspension bolts
Spring washer max.
12mm
Nut
Washer
Ceiling
Anchor nut
Nut
Suspension bolts
Washer
2)
• Engage 2 hooks on the both left and right side of the unit to the lower slot of Installation Plates.
• Adjust a level with a level gauge on the direction of left-right, back-forth by adjusting suspension bolts.
• Move the hooks on the unit to the upper slot of
Installation Plates. Then the unit will be declined to the bottomside so as to drain well.
Lower slot
Level gauge
R
Suspension bolt
Adjust a level
Installation plate
R
Upper slot
R
–21–
CAUTION
1. Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 7mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bottomside.
Front of view
• The unit must be horizontal or declined to the drain hose connected when finished installation.
Ceiling
Drain hose
Ceiling
Side of view
• The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
–22–
• Secure the unit to the Installation Plates with four M8 bolts and washers.
R
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
• Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 28, 31.
Inlet hanger
R
• Fit the projection hooks of the side plates to the 'Side
Panel' and the 'Front Panel' by lifting it.
• Fasten the screws.
Hook
Cabinet Bottom
1
R
2
R
–23–
2) Installation on the Wall
• Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor nut on the wall.
more than
260
1076
265
• Drill the piping hole on the wall slightly tilted to the outdoor side using a ø70 hole-core drill.
Indoor
Wall
Outdoor
• Secure the 'Install Plate' onto the wall with four anchor bolts, washers and spring washers.
Nut
Spring washer
Wall
Washer
Anchor nut
Less than
12mm
Before secure the Install Plates, select the bent direction of the 'Install Plate' to the inside or outside according to the installation circumstances.
1236
–24–
Install the Indoor unit onto Installation Plate.
• Insert 2 hooks on the both left and right side of the unit to the inner slot (wall side) of the Installation Plate.
• Secure the unit to the Installation Plate with four M8 bolts and washers.
R
Inner slot
• Hook up the Inlet Grille Hook to the cabinet.
• Hang the Inlet Hanger to the screw.
• Before working, refer to "Connecting pipe
and cable to Indoor Unit" on page 29, 31.
2
1
• Fit the projection hooks of the side plates to the 'Side
Panel' and the 'Front Panel' by lifting it.
• Fasten the screws.
–25–
3) Installation on the floor
Installation of Mount Bracket.
• Select and mark the position for Mount Brackets and the piping hole.
• Drill the hole for the anchor nut on the wall.
• Drill the piping hole using a ø70 hole-core drill.
• Secure the Mount Brackets on the wall with four M4 screws.
Install the indoor unit onto the Mount Brackets.
• Engage the slot at the back of the unit with Mount
Bracket.
Slot
Floor mount bracket
From the left wall more than 760mm
From the right wall more than 840mm
•
Drill the piping hole with 70mm dia, hole core drill.
• Piping hole should be slightly slant to the outdoor side.
Indoor
Wall
Outdoor
After Installing, reassemble detached parts.
• Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the
Hanger Screw.
• Assemble the 'Side Plates(R,L)' with 2 screws on both left and right side.
Slot
Wall
Floor mount bracket
Install plate
Piping hole
–26–
2. Piping and Drainage of Indoor Unit
2-1. Preparation of Piping
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m longer than the length of the pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end toward down to avoid the metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
Point down
Pipe cutter
90
Pipe
Slanted Rough
Reamer
3. Flaring the pipes.
• Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. (When the flare nuts are removed from the indoor unit.) Some gas may leak, as some gas is charged to prevent the inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool about 0~1.0mm higher. (See illustration)
• Flare the pipe ends.
• Carry out flaring work using dedicated flaring tool for R-410A.
"A"; ø15.88 mm (5/8")
ø12.7 mm (1/2")
ø9.52 mm (3/8")
ø6.35 mm (1/4")
1.0 mm
0.5 mm
0.5 mm
0.5 mm
Bar
Bar
Handle
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
= Improper flaring =
4. Tape the flaring portion to protect it from the dust or damages.
Inclined Surface damaged
Cracked Uneven thickness
When properly flared, the internal surface of the flare will evenly shine and be of even thickness.
After the flare part comes into contact with the connectors, carefully check the flare finish.
–27–
2-2. Installation on the ceiling
1) Connecting the pipes to the indoor unit
The pipe can be connected to right side, bottom or back of the unit.
1. For the Right Side Piping
• After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
Drain hose should be go through under the Hose
Bracket as shown in figure .
• Hang the drain hose on the hose hanger and fix it to the hole of the hose bracket with a screw.
2. For the Bottom Side Piping
• Remove the knock-out on the bottomside of Inlet Grille
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
• Hang the drain hose on the hose hanger and fix it to the hole of cabinet bottom with a screw.
2) Connecting the Drain Hose
• The drain hose can be connected to not only the right side but also left side of the unit.
• If the drain hose is connected to the left side, it should go through the cabinet bottom.
• Hang the drain hose on the hose hanger and fix it to the hole of cabinet bottom with a screw.
R
2
R
R
4
Piping
Drain Hose
Hose Hanger
5
Hose
Hanger
1
Hose
Bracket
3
Hose Hanger
Drain Hose
BOTTOM
–28–
2-3. Installation on the wall or floor
1) Connecting the pipes to the indoor unit
1. For the Right Rear Piping
• Remove the knock-out at the back side of the cabinet.
• After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
• Tape the Drain Hose to the pipings to avoid coming off the drain-outlet.
2. For the Right Side Piping
• After bending an end of the connecting tube, align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
• Tape the Drain Hose to the pipings to avoid coming off the drain-outlet.
3. For the Right Bottom Piping
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• Connect the Drain Hose insulated to the drain outlet.
Piping
Taping
Drain Hose
Taping
Drain Hose
Taping
Drain Hose
Connecting
Cable
2) Connecting the Drain Hose
• The drain hose can be connected to not only right side but also left side of the unit.
Piping
Piping
Drain Hose
REAR
BOTTOM
–29–
3. Connecting Pipes to the Outdoor Unit
1) Connecting the pipes to the Outdoor unit
1. Align the center of the pipings and sufficiently tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Pipe Size
1/4"
Liquid Side
3/8"
Gas Side
1/2"
5/8"
Torque
1.8kg·m
4.2kg·m
5.5kg·m
6.6kg·m
Gas side piping
(Bigger Dia.)
Liquid side piping
(Smaller Dia.)
Torque wrench
4. Checking the Drainage
1) Checking the Drainage
1. Remove the Air Filter.
• To remove air filter, take hold of tab and pull slightly upwards.
R
2. Check the drainage.
• Spray one or two glasses of water upon the evaporator.
• Ensure that water flows drain hose of indoor unit without any leakage.
R
–30–
5. Connecting Cables between Indoor Unit and Outdoor Unit
1) Connecting cables to the Indoor Unit
1) Remove the Air guide - L by loosening 2 screws after removing the Inlet grille from the Indoor unit.
2) Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
• Cooling only type
Terminals on the indoor unit 1(L) 2(N) 3 4
POWER
INPUT
Terminals on the outdoor unit 3 4
• Cooling & Heating type
Terminals on the indoor unit 1(L) 2(N) 3 4 5 6
GN/YL
7 8
POWER
INPUT
GN/YL
AIR GUIDE-L
INDOOR UNIT
Clamp
1
R
Control
Panel
Terminals on the outdoor unit 3 4 5 6 7
2
2) Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 0.75mm
2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.
4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of live pin on the power plug should be over 1.8m.
The power cord connected to the indoor unit should be complied with the following specifications
(Type H05VV-F(Indoor) approved by HAR or SAA).
NORMAL CROSS-
SECTIONAL AREA
• 2.5mm
2
(24K)
• 2.0mm
2
(18K)
CAUTION
The power connecting cable
connected between the indoor and outdoor unit should be complied with the following specifications
(Type H07RN-F approved by HAR or SAA).
NORMAL CROSS-
SECTIONAL AREA
• 2.5mm
2
(24K)
• 2.0mm
2
(18K)
The connecting cable connected between the indoor and outdoor unit should be complied with the following specifications
(Type H07RN-F approved by HAR or SAA).
NORMAL
CROSS-
SECTIONAL
AREA
0.75mm
2
–31–
3) Connecting the cable to Outdoor Unit
1. Remove the Cover control from the unit by loosening a screw.
Connect the wires to the terminals on the control board individually as following.
2. Secure the cable onto the control board with the holder (clamper).
3. Refix the cover control to the original position with the screw.
4. Use a recongnized circuit breaker 20A(18K, 24K) between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
Outdoor unit
Terminal block
Over 5mm
Holder for power supply cord
Cover control Holder for connecting cable
Power supply cord
Connecting cable
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
–32–
4) Form the pipings
1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two
Plastic Bands. (for the right pipings)
• If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
In case of the Outdoor unit being installed below position of the Indoor unit.
2. Tape the Pipings, drain hose and Connecting
Cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Taping
Drain hose
Plastic Band
Pipings
Connecting cable
Power supply cord
Trap is required to prevent water from entering into electrical parts.
In case of the Outdoor Unit being installed above position of the Indoor Unit.
2. Tape the Pipings and Connecting cable from bottom to top.
3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.
4. Fix the pipings onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Trap
–33–
6. Air Purging of the Pipes and Indoor Unit
The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor.
1. Confirm that both the liquid side valve and the gas side valve are set to the closed position.
2. After connecting the piping, check the joints for gas leakage with gas leak detector.
3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose.
4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below -76cmHg.
5. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench.
6. Tighten the valve stem nuts of the 2-way valve and 3-way valve.
7. Disconnect the charge hose and fit the nut to the service port.
(Tightening torque: 1.8kg.m)
Indoor unit
Liquid side
2-way valve/
3-way valve
Closed Outdoor unit
Gas side
3-way valve
Closed
Vaccum pump
OPEN CLOSE
–34–
7. Test running
1) Connection of power supply
1. Connect the power supply cord to the independent power supply.
• Circuit breaker is required.
2. Prepare the remote control.
• Insert two batteries provided.
Remove the battery cover from the remote controller.
• Slide the cover according to the arrow direction.
Insert the two batteries.
(Two "R03" or "AAA" dry-cell batteries or equivalent.)
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
3. Operate the unit for fifteen minutes or more.
2) Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is more than 8°C
(Cooling) or reversely (Heating).
3) Selection of the slide switch according to installation method (Heating model only)
1. In case the indoor unit is installed on the floor, please change the side switch which is on the
Main PCB Assembly to the 'BOTTOM' state.
2. In case the indoor unit is installed under the ceiling, please change the slide switch which is on the Main PCB Assembly to the ' CEILING' state.
The initial state of the slide switch is set for the bottom installation.
–35–
Thermometer
R
Operation
(1) Name and Function-Remote controller
1) Cooling Model
3
4
5
6
Remote Controller
Signal transmitter.
Transmits the signals to the room air conditioner.
ON OFF
SET CANCEL
1
7
2
8
9
10
11
1
OPERATION DISPLAY
Displays the operation conditions.
2
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
3
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
4
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
5
TIME SETTING BUTTONS
Used to adjust the time.
6
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
7
AIR FLOW DIRECTION START/STOP BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
8
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
9
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating (turns indoor fan on/off).
10
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
11
RESET BUTTON
Used prior to resetting time or after replacing batteries.
–36–
3
4
5
6
2) Heat Pump Model
Remote Controller
Signal transmitter.
Transmits the signals to the room air conditioner.
ON OFF
SET CANCEL
7
2
1
8
9
10
11
1
OPERATION DISPLAY
Displays the operation conditions.
2
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
3
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
4
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
5
TIME SETTING BUTTONS
Used to adjust the time.
6
TIMER SET/CANCEL BUTTONS
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
7
AIR FLOW DIRECTION START/STOP BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
8
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
9
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating (turns indoor fan on/off).
10
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
11
RESET BUTTON
Used prior to resetting time or after replacing batteries.
–37–
Disassembly of the parts (Indoor unit)
Warning :
Disconnect the unit from power supply before making any checks.
Be sure the power switch is set to “OFF”.
1. Remove the air filter.
• Pull the inlet grille slightly toward you.
• Pull out the air filter. (2 pieces)
Inlet Grille
2. Remove the girlle from chassis
• Remove the screws securing the side plate and push to the bottom-side.
• Unhook the hanger from the hanger screw at the left and the right side.
• Pick out the inlet grille.
R
4
Hanger
3
Hanger
Screw
2
1
3. Remove the lower air guide
• Remove a screw of both side fixing "barrier airguide".
• Remove the screws of both sides of the lower airguide.
• Remove the lower air-guide toward “arrow mark” by turning upwards as shown in figure.
R
Barrier Air guide
Lower Air guide
–38–
4. Remove air guide upper, crossflow fan and motor.
• Remove the screws of both sides and center securing the upper air-guide.
• Remove 2 screws fastening the bracket of door switch.
Door
Switch
R
• Remove a bearing assembly by removing a screw and the bearing cover.
• Remove 4 screws securing the motor cover.
• Loosen the screw securing the crossflow fan to the fan motor shaft. (do not remove)
• Remove the crossflow fan by sliding it out from the shaft of fan motor.
Motor
Cover
Bearing
Cover
R
Bearing
5. Remove the control box Assembly.
• Disconnect the step motor connector, fan motor connector, display PCB connector, thermistor connector and door switch connector from the main PCB.
• If necessary, disconnect power supply cord and connecting cable from the terminal block and remove the cord clamp screw.
• Remove 2 screws securing the control box and pick out the control box carefully.
–39–
R
6. Remove the front panel.
• Remove the screws of both sides fixing the front panel.
• Push the upper side of front panel strongly to pull out the front panel from the inner hook of diffuser frame.
• Pull down the front panel carefully not so as to harm the display PCB wires and thermistor wires.
Diffuser frame
Front
Panel
R
Diffuser frame
Hook
Front
Panel
7. Remove the diffuser assembly.
• Remove the screws of both side of diffuser assembly. (4 pieces)
• Push the upper side of cabinet strongly to pull out the inner hook of diffuser frame from the cabinet hole.
• Take up the diffuser frame carefully not so as to harm the display PCB wires and the step motor wires.
Diffuser frame
Hook
Cabinet
8. Remove display PCB assembly.
• Remove the screws at the both side of display cover.
• If necessar y, disconnect the display PCB connector from PCB assembly.
• Remove 2 screws of PCB assembly.
R
Display Cover
–40–
9. Remove the vane-upper, vane-lower and step motor.
• Remove 2 screws securing the step motor assembly and pull it out from the vanes carefully.
• Unhook the vanes from the vane supporter and remove the upper vane and lower vane by pulling the center of vanes with care.
Step Motor
Vane Supporter
10. Remove the drain pan assembly.
• Remove the both side of screws. (4 pieces)
• Pull out the drain pan assembly.
• Be careful not to harm to the EPS packing of drain pan and the tubings of evaporator.
Lower Vane
Upper Vane
11. Remove the evaporator.
• Remove the screws of both sides securing the
EVA barrier-R/L on the side cabinet.
• Remove the screws which fasten the barrier on the evaporator and take out the barrier assembly.
• Remove the evaporator assembly by sliding toward arrow mark. (As shown in figure)
EVA. Barrier-L
EVA. Barrier-R
–41–
Side Cabinet
Cycle
1. Installation (Connecting the piping between indoor and outdoor unit)
Indoor unit
Liquid side
2(3)-Way valve
Outdoor unit
Gas side
3-Way valve
Gas cylinder
Lo
R-407C
Purge the air
• Installation
(1) Connect the piping between the indoor and outdoor unit firmly.
– Incorrect connection may cause the leakage and incomplete vacuuming.
(2) Attach the charging hose (manifold gage) to the service port.
– Charging hose is necessary to check the pressure and to inject N
2 for leakage test.
– The valve of charging hose must be closed before being connected.
(3) Inject the 100~300g N
2 through the charging hose opening the valve.
(4) Check the joint part using a gas detector or soapy water for leakage.
– On checking, the service valve of main service port must be closed, this test is only for checking whether pipe connection is OK or not.
(5) If there is no leakage, discharge N
2 in piping completely into tank for retrieving.
– Completely discharge is needed for vacuuming.
– If leakage is found, please fasten the joint more tightly.
(6) After closing the valve of charging hose, disconnect the tank and connect the vacuum pump to charging hose and open the valve again for vacuuming.
(7) Turn on the vacuum pump until the pressure drops below 0 kg/cm
2
.
(8) After vacuuming, disconnect the vacuum pump and open the spindle of service port (liquid-side) slightly for 30 sec and then open the spindle of service port (gas side) with hexagonal wrench.
(9) Open the liquid side completely first and then the gas side fully in order.
–42–
2. Disconnection (on moving)
Indoor unit
Liquid side
Closed
2(3)-Way valve
Gas side
3-Way
Closed valve
Retrieving Tank
Lo
Outdoor unit
• Disconnection
(1) Attach the charging hose (manifold gage) to the service port.
– Connect the manifold gage once to the service port not stopping. Stopping in the middle of process may cause the leakage.
(2) Purge the air in hose into special device such as retrieving tank opening the valve of charging- hose (gas side) slightly and then close it tightly.
(3) Operate the air conditioner for 10~15 min until cycle is stabilized.
(4) Close the spindle of service port (liquid sidehigh pressure) and wait till pressure of gas side (low pressure) drops below 0 kgf/cm
2
.
(5) After the needle of gage indicates below
0 kgf/cm
2
, close the valve of gas side quickly and turn off the power.
(6) Disconnect the piping between indoor and outdoor unit and then put on service cap to the service port.
–43–
3. Gas Charging
(After Evacuation)
Indoor unit
Liquid side
2(3)-Way
Open valve
Outdoor unit
Charging cylinder
Check valve
(1)
OPEN
Lo
Gas side
3-Way valve
Open
CLOSE
• Procedure
(1) Connect the charge hose to the charging cylinder.
– Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged in liquid state.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and charge the system with liquid refrigerant.
– If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately
150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
\
This is different from previous procedures.
Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
(4) Immediately disconnect the charge hose from the 3-way valve’s service port.
– Stopping par tway will allow the gas to be discharged.
– If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service port nut.
– Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
–44–
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. difference : approx. 0°C
Current : less than 80% of rated current
All amount of refrigerant leaked out
Check refrigeration cycle
Temp. Difference
Temp. difference : approx. 8°C
Current : less than 80% of rated current
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Operating Current
Temp. difference : less than 8°C
Current : over the rated current
Excessive amount of refrigerant
Temp. difference : over 8°C
Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
Temperature
(Compared with the normal value) the normal value)
High
Higher
Normal
Cause of Trouble
Defective compressor
Defective 4-way reverse valve
Excessive amount of refrigerant
Description
Current is low
Lower Higher
Insufficient amount of
Clogging
High pressure does not quickly rise at the beginning of operation
Current is low
Current is low
NOTICE :
1. The suction pressure is usually 8.5~9.5 kg/cm 2 G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
–45–
Electronic Parts Troubleshooting Guide
Possible Trouble 1
: The unit does not operate.
Is the input voltage of transformer AC220V?
YES
Is the output voltage of transformer about AC14V?
YES
NO
NO
NO
Is the input voltage of IC01D DC14V?
YES
Is the output voltage of IC01D DC12V?
YES
NO
NO
Is the output voltage of IC02D DC5V?
YES
Is the PIN 29 of
Micom DC5V?
YES
NO
NO
Is the PIN 55,64 of
Micom DC5V?
YES
Exchange Micom
Is shorted the transformer output?
YES
NO
Check the FUSE and the wiring diagram
Check the RY-COMP PIN 3 and CN-4WAY PIN 1
Check the main P.C.B
pattern
Exchange the transformer
Exchange D01D-D05D
Exchange IC01D
Exchange IC02D
Exchange IC01A
Check the 5V P.C.B
pattern
–46–
Possible Trouble 2
: The indoor fan does not operate.
Is it DRY mode?
NO
YES
Does the temperature set all right?
YES
NO
Adjust set temperature
Is it the HOT mode?
NO
YES
Does the temperature set all right?
YES
NO
Adjust set temperature
Is IC02M operated normally?
YES
NO
Is the each S.S.R
any problem?
NO
YES
Check the fan motor and connector.
(CN-FAN)
Exchange IC02M
Exchange S.S.R
–47–
Possible Trouble 3
: Up/Down Air direction louver does not operate.
NO
Is IC01M operated normally?
YES
Is the PIN 1 of
CN-UP/DOWN DC12V?
YES
Check the step motor and connector
(CN-UP/DOWN 1,2)
NO
Exchange IC01M
Check the main P.C.B
DC12V pattern
Possible Trouble 4
: Remote controller does not operate.
Is the battery consumed much?
NO
YES
NO
Is the PIN 8 of CN-DISP
DC5V?
YES
Is the connection of
CN-DISP all right?
YES
Exchange receiver ass'y
NO
–48–
Exchange the battery
Check the main P.C.B
DC5V pattern
Connect CN-DISP exactly
Possible Trouble 5
: Ineffective Heating
Is 4way-valve operated?
YES
NO
NO
Is IC02M operated normally?
YES
Check the RY-4WAY and 4way-valve
Check RY-4WAY
Exchange IC02M
Possible Trouble 6
: The unit does not operate by forced operation switch.
Is the F/OP key any problem?
NO
Check P.C.B pattern check
YES
Exchange F/OP key
–49–
Electronic control device
(1) MAIN P.C.B ASM (CV-H186BLB0, CV-H246BLB0)
(2) DISPLAY P.C.B ASM (P/No.: 6871AQ3263A)
–50–
Schematic Diagram
–51–
Exploded View and Replacement Parts List
1. Indoor Unit
–52–
Parts List (Heat Pump Models)
LOCATION
NO.
166000
235450
237900
261704
263230
267110
268712
330870
130911
135314
137213
137213
146811
152302
159911
159911
342800
346811
352115
35211A
352150
354211
359010
W0CZZ
738280
738281
DESCRIPTION
CABINET ASSY
GRILLE ASSY, INLET SUB
PANEL ASSY, SIDE
PWB(PCB) ASSY, MAIN
MOTOR ASSY, STEP
FILTER(MECH), A/C
VANE ASSY, HORIZONTAL
VANE ASSY
SWITCH, PUSH
DISPLAY ASSY (MECH)
WINDOW, DISPLAY
TRANSFORMER, POWER
THERMISTOR ASSY
REMOTE CONTROLLER ASSY
PWB(PCB) ASSY, DISPLAY
DRAIN PAN ASSY
BEARING
MOTOR ASSY, INDOOR
TUBE ASSY, EVA-IN
TUBE ASSY, SUCTION INDOOR
HOSE ASSY, DRAIN
EVAPORATOR ASSY
FAN ASSY, CROSS FLOW
CAPACITOR
MANUAL, OWNERS
MANUAL, SERVICE
CV-H186BLB0
3091AP2533A
5237A10002K
3720AP2767P
6871A20042H
4681AR2727G
5230AP7093A
5991AP2867B
5991AP7334C
6600AP2059B
3545AP7224A
3790AP7080A
6171AQ3198E
6323AQ2333Y
6711A20010K
6871AQ3263A
3087AP7233A
3H02821B
4681AP2306G
5211AP2810J
5211AP2813B
5251AP2460B
5421AP2812A
5901AR2351E
3H00671A
3828A20147D
3828A20059X
PART No.
CV-H246BLB0
3091AP2533A
5237A10002K
3720AP2767P
6871A20042H
4681AR2727G
5230AP7093A
5991AP2867B
5991AP7334C
6600AP2059B
3545AP7224A
3790AP7080A
6171AQ3198E
6323AQ2333Y
6711A20010K
6871AQ3263A
3087AP7233A
3H02821B
4681AP2306E
5211AP2810J
5211AP2813A
5251AP2460B
5421AP2812A
5901AR2351E
3H00671A
3828A20147D
3828A20059X
REMARK
–53–
2. Outdoor Unit
–54–
Parts List (Heat Pump Models)
LOCATION
NO.
552203-1
552203-2
554031
554160
559010
561410
649950
W0CZZ-1
W0CZZ-2
349480
435311
435512
437210
437212
546810
552111
552202
DESCRIPTION
ORIFICE
GRILLE, DISCHARGE
COVER ASSY, TOP(OUTDOOR)
PANEL ASSY, FRONT
PANEL ASSY, REAR
MOTOR ASSY, OUTDOOR
TUBE ASSY, CAPILLARY
VALVE, REVERSING
VALVE, SERVICE
VALVE, SERVICE
CONDENSER ASSY, BENT
COMPRESSOR SET
FAN ASSY, PROPELLER
COIL ASSY, REVERSING VALVE
CONTROL BOX ASSY, OUTDOOR
CAPACITOR, DRAWING
CAPACITOR, DRAWING
CV-H186BLB0
4948AP2527A
3530A20007B
3H03266K
3721A20005Q
3720AP0003D
4681A20013T
5211A10039T
3A02027A
2H01890D
2H02479F
5403A20022F
2520UWFP2AA
1A00195B
3A02028Y
4995A20027M
3A00988B
2A00986D
PART No.
CV-H246BLB0
4948AP2527A
3530A20007B
3H03266K
3721A20005Q
3720AP0003D
4681A20013X
5211A30331R
3A02027A
2A00392E
2H02479F
5403A20022F
2520UWJP2BA
1A00195B
3A02028Y
4995A20027N
6120AR2094T
2A00986D
REMARK
–55–
P/No.: 3828A20059X
June, 2003
Printed in Korea
advertisement
Key Features
- Convertible Type
- Cooling & Heating
- Soft Dry Operation Mode
- Sleep Mode Auto Control
- Self-diagnosis Function
- Auto Restarting Operation
- Deice Control
- Hot-Start Control
- Airflow Direction Control
- Room Temperature Control