LENNOX KCA 092, KCA 102, KCA 120, KCA 150 packaged cooling unit Service Literature
Below you will find brief information for packaged cooling unit KCA KCA092, packaged cooling unit KCA KCA102, packaged cooling unit KCA KCA120, packaged cooling unit KCA KCA150. KCA series packaged cooling units are available in standard cooling efficiency. Optional auxiliary electric heat is factory or field installed in KCA units. Electric heat operates in single or multiple stages depending on the kW input size. 7.5kW through 60kW heat sections are available for the KCA heat pump.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
42
KCA SERIES Corp. 1011−L9 Service Literature 7.5 to 12.5 ton 26.3 to 42 kW KCA092 through 150 The KCA 7.5, 8.5, 10 and 12.5 ton (092, 102, 120, 150) packaged cooling units are available in standard cooling efficiency. Optional auxiliary electric heat is factory or field installed in KCA units. Electric heat operates in single or multiple stages depending on the kW input size. 7.5kW through 60kW heat sections are available for the KCA heat pump. All KCA units are designed to accept any of several different energy management thermostat control systems with minimum field wiring. Factory or field provided control options connect to the unit with jack plugs. When "plugged in" the controls become an integral part of the unit wiring. CAUTION Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes. Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. WARNING If the unit must be lifted for service, rig unit by attaching four cables to the holes located in the unit base rail (two holes at each corner). Refer to the installation instructions for the proper rigging technique. Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency. Options / Accessories . . . . . . . . . . . . . . . . . . . . . . Page 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 Electrical / Electric Heat Data . . . . . . . . . . . . . . . Page 11 ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure. Electrical Heat Capacities . . . . . . . . . . . . . . . . . . . Page 15 Parts Arrangement . . . . . . . . . . . . . . . . . . . . . . . . Page 16 I− Unit Components . . . . . . . . . . . . . . . . . . . . . . Page 17 II− Placement and Installation . . . . . . . . . . . . . . Page 26 III− Start−Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 26 IV− Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 27 V− System Service Checks . . . . . . . . . . . . . . . . . Page 28 VI− Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28 VII− Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 29 VIII−Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . Page 36 Page 1 2010 Lennox Industries Inc. OPTIONS / ACCESSORIES Model Number Item Description Catalog Number Unit Model No 092 102 120 150 COOLING SYSTEM Compressor Crankcase Heater 208/230V- 3ph - K1CCHT02B-1Y 54W17 X X X 460V-3ph - K1CCHT02B-1G 54W18 X X X 575V-3ph - K1CCHT02B-1J 54W19 X X X PVC - LTACDKP09/36 76M18 X X X X Copper - LTACDKC09/36 76M19 X X X X Factory O O O O 74W42 X X X X Standard O O O O 54W16 X X X X R-410A O O O O Belt Drive - 2 hp Factory O O O O Belt Drive - 3 hp Factory O O O O Belt Drive - 5 hp Factory O O O O Kit #1 590-890 rpm Factory O O O O Kit #2 800-1105 rpm Factory O O O O Kit #3 795-1195 rpm Factory O O O O Kit #4 730-970 rpm Factory O O O O Kit #5 940-1200 rpm Factory O O O O Kit #6 1015-1300 rpm Factory O O O O Condensate Drain Trap Corrosion Protection Drain Pan Overflow Switch K1SNSR71AB1- Efficiency Low Ambient Kit K1SNSR33B-1 Refrigerant Type BLOWER - SUPPLY AIR Motors Drive Kits See Blower Data Tables for selection Kit #10 900-1135 rpm Factory O O O O Kit #11 1040-1315 rpm Factory O O O O Kit #12 1125-1425 rpm Factory O O O O Coil Guards K1GARD20B-1 55W08 X X X X Hail Guards K1GARD10B1 55W11 X X X X Factory O O O O K1HECK00B-1 51W25 X X X X C1CONV10B-1 54W96 X X X X --- X X X X CABINET Hinged Access Panels Horizontal Discharge Kit Return Air Adaptor Plate (for L Series and T-Class™ replacement) ® CONTROLS Commercial Controls L Connection® Building Automation System Smoke Detector - Supply or Return (Power board and one sensor) C1SNSR44B-1 53W80 X X X X Smoke Detector - Supply and Return (Power board and two sensors) C1SNSR43B-1 53W81 X X X X NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Page 2 OPTIONS / ACCESSORIES Model Number Item Description Catalog Number Unit Model No 092 102 120 150 INDOOR AIR QUALITY Air Filters Healthy Climate® High Efficiency Air Filters MERV 8 - C1FLTR15B-1 50W61 X X X X 20 x 25 x 2 (Order 4 per unit) Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media) Indoor Air Quality (CO2) Sensors MERV 13 - C1FLTR40B-1 C1FLTR30B-1- 52W41 Y3063 X X X X X X X X Sensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AE1L 77N39 X X X X Sensor - Wall-mount, off-white plastic cover, no display C0SNSR52AE1L 87N53 X X X X Sensor - Black plastic case with LCD display, rated for plenum mounting C0SNSR51AE1L 87N52 X X X X C0MISC19AE1 87N54 X X X X C0MISC19AE1- 85L43 X X X X C0MISC16AE1- 90N43 X X X X C1UVCL10B-1 54W62 X X X X Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting CO2 Sensor Duct Mounting Kit - for downflow applications Aspiration Box - for duct mounting non-plenum rated CO2 sensors (87N53 or 77N39) UVC Germicidal Lamps Healthy Climate® UVC Light Kit (208/230v-1ph) ELECTRICAL 1 Voltage 60 hz 208/230V - 3 phase Factory O O O O 460V - 3 phase Factory O O O O 575V - 3 phase Factory O O O O 80 amp - C1DISC080B-1 54W56 OX OX OX OX 150 amp - C1DISC150B-1 54W57 OX OX OX OX LTAGFIK10/15 74M70 OX OX OX OX 208/230V-3ph - C1EHO075B-1Y 56W38 X X 460V-3ph - C1EHO075B-1G 56W39 X X 575V-3ph - C1EHO075B-1J 56W40 X X 208/230V-3ph - C1EHO015B-1Y 56W41 X X X X 460V-3ph - C1EHO150B-1G 56W42 X X X X 575V-3ph - C1EHO150B-1J 56W43 X X X X 208/230V-3ph - C1EHO225B-1Y 56W44 X X X X 460V-3ph - C1EHO225B-1G 56W45 X X X X 575V-3ph - C1EHO225B-1J 56W46 X X X X 208/230V-3ph - C1EHO300B-1Y 56W47 X X X X 460V-3ph - C1EHO300B-1G 56W48 X X X X Disconnect Switch - See Electrical/Electric Heat tables for selection GFI Service Outlets ELECTRIC HEAT 7.5 kW 15 kW 22.5 kW 30 kW 45 kW 60 kW 575V-3ph - C1EHO300B-1J 56W49 X X X X 208/230V-3ph - C1EHO450B-1Y 56W50 X X X X 460V-3ph - C1EHO450B-1G 56W51 X X X X 575V-3ph - C1EHO450B-1J 56W52 X X X X 208/230V-3ph - C1EHO600B-1Y 55W02 X X 460V-3ph - C1EHO600B-1G 55W03 X X 575V-3ph - C1EHO600B-1J 55W04 X X Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s) 1 NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Page 3 OPTIONS / ACCESSORIES Model Number Item Description Catalog Number Unit Model No 092 102 120 150 ECONOMIZER Economizer K1ECON20B-1 54W55 OX OX OX OX Single Enthalpy Control C1SNSR64FF1 53W64 OX OX OX OX Differential Enthalpy Control (order 2) C1SNSR64FF1 53W64 X X X X LAGEDH03/15 53K04 X X X X Motorized Dampers with outdoor air hood C1DAMP20B-1 53W49 OX OX OX OX Manual Dampers with outdoor air hood C1DAMP10B-1 53W48 OX OX OX OX 208/230V-3ph - K1PWRE10B-1Y 53W44 X X X X 460V-3ph - K1PWRE10B-1G 53W45 X X X X 575V-3ph - K1PWRE10B-1J 53W46 X X X X 8 in. height C1CURB23B-1 54W46 X X X X 14 in. height C1CURB20B-1 54W47 X X X X 18 in. height C1CURB21B-1 54W48 X X X X 24 in. height C1CURB22B-1 54W49 X X X X 8 in. height C1CURB12B-1 54W44 X X X X 14 in. height C1CURB10B-1 54W43 X X X X 24 in. height C1CURB11B-1 54W45 X X X X C1CURB55B-1 54W50 X X X X X X X Economizer with Single Temperature Control - Downflow or Horizontal With Barometric Relief Dampers (downflow) and Air Hoods Economizer Controls Horizontal Barometric Relief Dampers With Exhaust Hood Horizontal Barometric Relief Dampers - Exhaust Hood Furnished OUTDOOR AIR Outdoor Air Dampers POWER EXHAUST Standard Static ROOF CURBS - DOWNFLOW Clip Curb Standard Adjustable Pitched Curb 14 in. height CEILING DIFFUSERS Step-Down - Order one Flush - Order one Transitions (Supply and Return) - Order one NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Page 4 RTD11-95 29G04 RTD11-135 29G05 RTD11-185 29G06 FD11-95 29G08 FD11-135 29G09 FD11-185 29G10 LASRT08/10 24L14 LASRT10/12 49K55 LASRT15 49K56 X X X X X X X X X SPECIFICATIONS General Data Cooling Performance Nominal Tonnage Model Number Efficiency Type Blower Type Gross Cooling Capacity - Btuh 1 Net Cooling Capacity - Btuh AHRI Rated Air Flow - cfm Total Unit Power - kW 1 EER (Btuh/Watt) 2 IEER (Btuh/Watt) Refrigerant Type Refrigerant Circuit 1 Charge Circuit 2 Furnished Electric Heat Available - See page 3 Compressor Type (number) Outdoor Net face area (total) - sq. ft. Coils Tube diameter - in. Number of rows Fins per inch Outdoor Motor - (No.) hp Coil Fans Motor rpm Total Motor watts Diameter - (No.) in. Number of blades Total Air volume - cfm Indoor Net face area (total) - sq. ft. Coils Tube diameter - in. Number of rows Fins per inch Drain connection - Number and size Expansion device type 3 Indoor Nominal motor output Blower and Maximum usable motor output Drive (US Only) Selection Motor - Drive kit number 7.5 Ton KCA092S4B Standard Constant Air Volume CAV 88,900 86,000 3,000 7.7 11.2 11.4 R-410A 7 lbs. 8 oz. 7 lbs. 0 oz. 8.5 Ton KCA102S4B Standard Constant Air Volume CAV 100,483 97,000 3,400 8.7 11.2 11.4 R-410A 8 lbs. 8 oz. 8 lbs. 8 oz. 10 Ton KCA120S4B Standard Constant Air Volume CAV 119,640 115,000 3,800 10.3 11.2 11.4 R-410A 10 lbs. 0 oz. 10 lbs. 0 oz. 12.5 Ton KCA150S4B Standard Constant Air Volume CAV 144,800 138,000 4,300 12.5 11 11.2 R-410A 14 lbs. 0 oz. 12 lbs. 0 oz. 7.5,15,22.5,30 & 45 KW 15,22.5,30,45 & 60 KW Scroll (2) Scroll (2) Scroll (2) Scroll (2) 20.42 24.5 28.0 28.0 3/8 3/8 3/8 3/8 2 2 2 3 20 20 20 20 (2) 1/3 (2) 1/3 (2) 1/3 (2) 1/2 1075 1075 1075 1075 670 670 670 830 (2) 24 (2) 24 (2) 24 (2) 24 3 3 3 3 7200 7400 7800 8,800 12.78 12.78 12.78 13.54 3/8 3/8 3/8 3/8 2 2 3 4 14 14 14 14 (1) 1 in. NPT coupling Balance port TXV, removable head 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hp 2 hp, 3 hp, 5 hp 2.3 hp, 3.45 hp, 2.3 hp, 3.45 hp, 2.3 hp, 3.45 hp, 2.3 hp, 3.45 hp, 5.75 hp 5.75 hp 5.75 hp 5.75 hp 2 hp 2 hp 2 hp 2 hp 4 Kit 1 590-890 rpm 4 Kit 1 590-890 rpm Kit 1 590-890 rpm Kit 1 590-890 rpm Kit 2 800-1105 rpm Kit 2 800-1105 rpm Kit 2 800-1105 rpm Kit 2 800-105 rpm Kit 3 795-1195 rpm Kit 3 795-1195 rpm Kit 3 795-1195 rpm Kit 3 795-1195 rpm 3 hp 3 hp 3 hp 3 hp 4 Kit 4 730-970 rpm Kit 4 730-970 rpm Kit 4 730-970 rpm Kit 4 730-970 rpm Kit 5 940-1200 rpm Kit 5 940-1200 rpm Kit 5 940-1200 rpm Kit 5 940-1200 rpm Kit 6 1015-1300 rpm Kit 6 1015-1300 rpm Kit 6 1015-1300 rpm Kit 6 1015-1300 rpm 5 hp 5 hp 5 hp 5 hp Kit 10 900-1135 rpm Kit 10 900-1135 rpm Kit 10 900-1135 rpm 4 Kit 10 900-1135 rpm Kit 11 1040-1315 rpm Kit 11 1040-1315 rpm Kit 11 1040-1315 rpm Kit 11 1040-1315 rpm Kit 12 1125-1425 rpm Kit 12 1125-1425 rpm Kit 12 1125-1425 rpm Kit 12 1125-1425 rpm Blower wheel nominal (1) 15 X 15 (1) 15 X 15 (1) 15 X 15 (1) 15 X 15 diameter x width - in. Filters Type of filter Disposable Number and size - in. (4) 20 x 25 x 2 Electrical characteristics 208/230V, 460V or 575V - 60 hertz - 3 phase NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.. 3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. 4 Standard motor and drive kit furnished with unit. Page 5 BLOWER DATA 092 AND 102 BELT DRIVE BLOWER − BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section, economizer, etc.) 3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 9 for blower motors and drives. See page 9 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 7.5 kW, 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm Total Air Volume cfm Total Static Pressure − in. w.g. 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2250 - - - - - - - - - - - - 707 0.14 753 0.50 800 0.84 847 1.15 892 1.38 934 1.53 979 1.65 1051 1.86 1126 2.12 1183 2.36 1238 2.62 2500 - - - - - - - - - - - - 714 0.29 758 0.64 803 0.97 849 1.26 893 1.48 936 1.63 983 1.75 1052 1.96 1124 2.22 1184 2.49 1241 2.77 2750 - - - - - - 680 0.11 721 0.45 763 0.78 807 1.09 852 1.37 896 1.58 940 1.74 989 1.88 1053 2.08 1121 2.34 1185 2.63 1244 2.93 3000 - - - - - - 689 0.29 728 0.61 770 0.93 812 1.23 856 1.49 901 1.70 947 1.87 996 2.02 1055 2.21 1120 2.47 1186 2.78 1248 3.10 3250 661 0.17 698 0.46 737 0.78 777 1.09 819 1.38 862 1.63 908 1.84 955 2.01 1004 2.17 1059 2.36 1122 2.62 1189 2.94 1252 3.28 3500 672 0.36 708 0.65 746 0.95 786 1.25 827 1.53 870 1.78 916 1.99 965 2.17 1013 2.33 1065 2.52 1126 2.79 1193 3.12 1257 3.47 3750 684 0.56 719 0.85 756 1.14 795 1.43 836 1.70 880 1.95 927 2.16 976 2.34 1023 2.51 1073 2.71 1133 2.98 1198 3.32 1263 3.67 4000 697 0.78 731 1.05 768 1.34 807 1.62 848 1.89 892 2.13 940 2.34 988 2.53 1034 2.71 1083 2.91 1141 3.19 1205 3.53 1270 3.89 4250 710 1.00 745 1.27 781 1.55 819 1.83 861 2.09 906 2.33 954 2.55 1001 2.74 1046 2.93 1094 3.14 1151 3.42 1214 3.76 1278 4.12 Page 6 BLOWER DATA 120 BELT DRIVE BLOWER − BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section, economizer, etc.) 3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 9 for blower motors and drives. See page 9 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm 60 kW - 4000 cfm Total Air Volume cfm Total Static Pressure − in. w.g. 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3000 - - - - - - 677 0.24 719 0.55 764 0.87 813 1.18 866 1.45 920 1.67 975 1.82 1026 1.96 1076 2.13 1126 2.35 1176 2.63 1225 2.92 3250 650 0.14 688 0.43 730 0.73 775 1.04 823 1.34 875 1.60 930 1.81 985 1.97 1036 2.12 1086 2.31 1136 2.54 1186 2.83 1235 3.13 3500 663 0.35 700 0.63 741 0.92 786 1.22 834 1.5 886 1.76 942 1.96 997 2.14 1048 2.31 1097 2.51 1147 2.75 1196 3.04 1245 3.35 3750 676 0.57 714 0.84 754 1.12 798 1.41 846 1.68 899 1.93 956 2.14 1010 2.32 1060 2.51 1109 2.72 1158 2.98 1207 3.27 1255 3.58 4000 691 0.79 728 1.05 768 1.33 812 1.61 860 1.88 914 2.12 971 2.34 1023 2.53 1072 2.73 1121 2.95 1169 3.22 1218 3.51 1266 3.83 4250 706 1.03 743 1.28 783 1.55 827 1.82 876 2.09 931 2.33 987 2.55 1037 2.76 1085 2.97 1133 3.20 1181 3.47 1229 3.76 1277 4.08 4500 722 1.27 759 1.52 799 1.78 844 2.05 894 2.31 949 2.56 1003 2.79 1052 3.00 1098 3.22 1145 3.46 1193 3.73 1241 4.03 1289 4.34 4750 739 1.53 776 1.77 817 2.03 862 2.30 913 2.56 968 2.81 1020 3.04 1066 3.27 1112 3.49 1158 3.74 1205 4.01 1253 4.30 1301 4.61 5000 757 1.79 794 2.04 835 2.30 882 2.56 934 2.83 988 3.08 1036 3.32 1081 3.55 1125 3.78 1171 4.02 1218 4.29 1265 4.59 1312 4.89 Page 7 BLOWER DATA 150 BELT DRIVE BLOWER − BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section, economizer, etc.) 3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 9 for blower motors and drives. See page 9 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm 60 kW - 4000 cfm Total Air Volume cfm Total Static Pressure − in. w.g. 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3750 689 0.68 731 0.97 775 1.27 820 1.56 865 1.81 911 2.02 957 2.19 1004 2.35 1051 2.53 1100 2.74 1151 2.99 1204 3.29 1258 3.61 4000 706 0.92 748 1.22 792 1.51 836 1.78 881 2.02 926 2.22 972 2.39 1018 2.57 1065 2.76 1113 2.98 1163 3.25 1217 3.55 1271 3.87 4250 725 1.18 766 1.47 810 1.75 854 2.02 899 2.25 943 2.44 988 2.61 1033 2.81 1079 3.01 1127 3.25 1178 3.52 1230 3.82 1284 4.14 4500 744 1.45 786 1.73 829 2.01 873 2.27 917 2.49 961 2.67 1005 2.87 1050 3.07 1096 3.29 1143 3.53 1193 3.81 1245 4.11 1298 4.43 4750 764 1.73 806 2.01 849 2.28 893 2.53 936 2.74 980 2.94 1023 3.15 1068 3.37 1113 3.60 1160 3.84 1210 4.12 1261 4.42 1314 4.74 5000 785 2.02 827 2.30 870 2.57 914 2.81 957 3.02 1000 3.23 1043 3.46 1087 3.69 1131 3.92 1178 4.17 1227 4.44 1278 4.74 1330 5.05 5250 807 2.33 850 2.61 893 2.87 937 3.11 979 3.33 1021 3.55 1064 3.80 1107 4.03 1151 4.27 1197 4.51 1245 4.78 1295 5.08 1347 5.38 5500 831 2.66 874 2.94 917 3.2 960 3.43 1002 3.67 1043 3.91 1085 4.16 1127 4.39 1171 4.63 1216 4.87 1264 5.14 1313 5.42 1364 5.72 5750 856 3.00 899 3.29 943 3.55 985 3.79 1026 4.04 1066 4.30 1107 4.55 1149 4.78 1192 5.00 1237 5.24 1284 5.50 - - - - - - - - - - - - 6000 883 3.38 927 3.66 970 3.93 1010 4.19 1050 4.46 1089 4.72 1129 4.95 1171 5.17 1213 5.40 1257 5.63 - - - - - - - - - - - - - - - 6250 912 3.78 956 4.07 997 4.35 1036 4.63 1074 4.90 1113 5.15 1152 5.37 1193 5.58 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 8 BLOWER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Nominal hp Maximum hp Drive Kit Number RPM Range 2 2.3 1 590 - 890 2 2.3 2 800 - 1105 2 2.3 3 795 - 1195 3 3.45 4 730 - 970 3 3.45 5 940 - 1200 3 3.45 6 1015 - 1300 5 5.75 10 900 - 1135 5 5.75 11 1040 - 1315 5 5.75 12 1125 - 1425 POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure Air Volume Exhausted in. w.g. cfm 0 3175 0.05 2955 0.10 2685 0.15 2410 0.20 2165 0.25 1920 0.30 1420 0.35 1200 FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g. Wet Indoor Coil MERV 8 MERV 13 Return Air Adaptor Plate 0.08 0.01 0.04 0.00 0.04 0.11 0.01 0.05 0.00 0.17 0.05 0.12 0.02 0.05 0.00 0.19 0.06 0.13 0.02 0.06 0.02 0.18 0.23 0.06 0.15 0.02 0.06 0.02 0.21 0.26 0.09 0.15 0.03 0.07 0.04 0.16 0.23 0.29 0.09 0.15 0.03 0.08 0.07 4000 0.17 0.25 0.31 0.09 0.19 0.04 0.08 0.09 4250 0.20 0.27 0.34 0.13 0.19 0.04 0.09 0.11 4500 0.21 0.30 0.37 0.14 0.22 0.04 0.09 0.12 4750 0.23 0.32 0.40 0.17 0.25 0.05 0.10 0.16 5000 0.26 0.35 0.43 0.20 0.29 0.06 0.10 0.18 5250 0.27 0.36 0.46 0.22 0.32 0.06 0.11 0.19 5500 0.29 0.40 0.50 0.25 0.34 0.07 0.12 0.22 5750 0.32 0.43 0.56 0.31 0.45 0.07 0.12 0.25 6000 0.33 0.46 0.59 0.33 0.52 0.08 0.13 0.27 Air Volume cfm 150 Electric Heat Economizer 092, 102 120 2250 0.07 0.10 0.13 0.04 2500 0.09 0.12 0.15 2750 0.09 0.12 3000 0.11 0.15 3250 0.13 3500 0.14 3750 Page 9 Filters BLOWER DATA CEILING DIFFUSERS AIR RESISTANCE - in. w.g. RTD11 Step-Down Diffuser Unit Size Air Volume cfm 092 Models 102 & 120 Models 150 Models 2 Ends Open 1 Side, 2 Ends Open All Ends & Sides Open FD11 Flush Diffuser 2400 0.21 0.18 0.15 0.14 2600 0.24 0.21 0.18 0.17 2800 0.27 0.24 0.21 0.20 3000 0.32 0.29 0.25 0.25 3200 0.41 0.37 0.32 0.31 3400 0.50 0.45 0.39 0.37 3600 0.61 0.54 0.48 0.44 3800 0.73 0.63 0.57 0.51 3600 0.36 0.28 0.23 0.15 3800 0.40 0.32 0.26 0.18 4000 0.44 0.36 0.29 0.21 4200 0.49 0.40 0.33 0.24 4400 0.54 0.44 0.37 0.27 4600 0.60 0.49 0.42 0.31 4800 0.65 0.53 0.46 0.35 5000 0.69 0.58 0.50 0.39 5200 0.75 0.62 0.54 0.43 4200 0.22 0.19 0.16 0.10 4400 0.28 0.24 0.20 0.12 4600 0.34 0.29 0.24 0.15 4800 0.40 0.34 0.29 0.19 5000 0.46 0.39 0.34 0.23 5200 0.52 0.44 0.39 0.27 5400 0.58 0.49 0.43 0.31 5600 0.64 0.54 0.47 0.35 5800 0.70 0.59 0.51 0.39 CEILING DIFFUSER AIR THROW DATA Model No. 092 Models 102, 120 Models 150 Models Air Volume 1 Effective Throw Range RTD11 Step-Down FD11 Flush cfm ft. ft. 2600 24 - 29 19 - 24 2800 25 - 30 20 - 28 3000 27 - 33 21 - 29 3200 28 - 35 22 - 29 3400 30 - 37 22 - 30 3600 25 - 33 22 - 29 3800 27 - 35 22 - 30 4000 29- 37 24 - 33 4200 32 - 40 26 - 35 4400 34 - 42 28 - 37 5600 39 - 49 28 - 37 5800 42 - 51 29 - 38 6000 44 - 54 40 - 50 6200 45 - 55 42 - 51 6400 46 - 55 43 - 52 6600 47 - 56 45 - 56 Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open. 1 Page 10 ELECTRICAL/ELECTRIC HEAT DATA 7.5 TON STANDARD EFFICIENCY (R-410A) 1 Voltage - 60hz Compressor 1 Rated Load Amps Locked Rotor Amps Compressor 2 Rated Load Amps Locked Rotor Amps Outdoor Fan Full Load Amps (total) Motors (2) Power Exhaust 7.5 TON 208/230V - 3 Ph 13.1 83.1 13.1 83.1 2.4 (4.8) 460V - 3 Ph 6.1 41 6.1 41 1.3 (2.6) KCA092S4 575V - 3 Ph 4.4 33 4.4 33 1 (2) Full Load Amps 2.4 1.3 1 (1) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor 15 2 7.5 15 2 3.4 15 2 2.7 Unit Only With (1) 0.33 HP 50 50 25 25 15 20 42 45 20 22 15 16 2 Maximum Overcurrent Protection Minimum 3 Circuit Power Exhaust Unit Only With (1) 0.33 HP Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 7.5 kW Maximum 15 kW Electric Heat Overcurrent 22.5 kW Protection 30 kW 45 kW 3 Unit+ 7.5 kW Minimum 15 kW Electric Heat Circuit 22.5 kW Ampacity 30 kW 45 kW 2 7.5 kW Unit+ Maximum 15 kW Electric Heat Overcurrent 22.5 kW and (1) 0.33 Protection 30 kW HP 45 kW Power Exhaust 3 Minimum Unit+ Circuit Electric Heat Ampacity and (1) 0.33 HP 7.5 kW 15 kW 22.5 kW 30 kW 45 kW Power Exhaust ELECTRICAL ACCESSORIES Disconnect 7.5 kW 15 kW 22.5 kW 30 kW 45 kW 1 2 3 208V 50 50 70 90 150 42 49 69 88 127 50 60 80 100 150 240V 50 60 80 100 150 42 55 78 100 145 50 60 90 110 150 480V 25 30 40 50 80 20 27 39 50 72 25 30 40 60 80 600V 15 25 35 40 60 15 22 31 40 58 20 25 35 45 60 45 52 72 91 130 45 58 81 103 148 22 29 40 51 74 16 23 32 41 59 54W56 54W56 54W56 54W57 54W57 54W56 54W56 54W56 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Page 11 ELECTRICAL/ELECTRIC HEAT DATA 8.5 TON STANDARD EFFICIENCY (R-410A) 1 Voltage - 60hz Compressor 1 Rated Load Amps Locked Rotor Amps Compressor 2 Rated Load Amps Locked Rotor Amps Outdoor Fan Full Load Amps (total) Motors (2) Power Exhaust 8.5 TON 208/230V - 3 Ph 14.5 98 14.5 98 2.4 (4.8) 460V - 3 Ph 6.3 55 6.3 55 1.3 (2.6) KCA102S4 575V - 3 Ph 6 41 6 41 1 (2) Full Load Amps 2.4 1.3 1 (1) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor 15 2 7.5 15 2 3.4 15 2 2.7 Unit Only With (1) 0.33 HP 50 60 25 25 20 25 45 48 21 22 19 20 2 Maximum Overcurrent Protection Minimum 3 Circuit Power Exhaust Unit Only With (1) 0.33 HP Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 7.5 kW Maximum 15 kW Electric Heat Overcurrent 22.5 kW Protection 30 kW 45 kW 3 Unit+ 7.5 kW Minimum 15 kW Electric Heat Circuit 22.5 kW Ampacity 30 kW 45 kW 2 7.5 kW Unit+ Maximum 15 kW Electric Heat Overcurrent and (1) 0.33 22.5 kW Protection 30 kW HP 45 kW Power Exhaust 3 Minimum Unit+ Circuit Electric Heat Ampacity and (1) 0.33 HP 7.5 kW 15 kW 22.5 kW 30 kW 45 kW Power Exhaust ELECTRICAL ACCESSORIES Disconnect 7.5 kW 15 kW 22.5 kW 30 kW 45 kW 1 2 3 208V 50 50 70 90 150 45 49 69 88 127 60 60 80 100 150 240V 50 60 80 100 150 45 55 78 100 145 60 60 90 110 150 480V 25 30 40 50 80 21 27 39 50 72 25 30 40 60 80 600V 20 25 35 40 60 19 22 31 40 58 25 25 35 45 60 48 52 72 91 130 48 58 81 103 148 22 29 40 51 74 20 23 32 41 59 54W56 54W56 54W56 54W57 54W57 54W56 54W56 54W56 54W57 57W57 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Page 12 ELECTRICAL/ELECTRIC HEAT DATA 10 TON STANDARD EFFICIENCY (R-410A) 1 Voltage - 60hz Compressor 1 Rated Load Amps Locked Rotor Amps Compressor 2 Rated Load Amps Locked Rotor Amps Outdoor Fan Full Load Amps (total) Motors (2) 10 TON KCA120S4 575V - 3 Ph 5.7 38.9 5.7 38.9 1 (2) 208/230V - 3 Ph 16 110 16 110 2.4 (4.8) 460V - 3 Ph 7.8 52 7.8 52 1.3 (2.6) Full Load Amps 2.4 1.3 1 (1) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor 15 3 10.6 15 3 4.8 15 3 3.9 60 60 30 30 20 25 52 54 25 27 19 20 Power Exhaust 2 Maximum Overcurrent Protection Minimum 3 Circuit Unit Only With (1) 0.33 HP Power Exhaust Unit Only With (1) 0.33 HP Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 15 kW Maximum Overcurrent Electric Heat Protection 3 Minimum Circuit Unit+ Electric Heat Ampacity 2 Maximum Unit+ Overcurrent Electric Heat Protection and (1) 0.33 HP 3 Minimum Power Exhaust Unit+ Circuit Electric Heat Ampacity and (1) 0.33 HP 208V 60 240V 60 480V 30 600V 25 22.5 kW 30 kW 45 kW 60 kW 15 kW 22.5 kW 30 kW 45 kW 60 kW 15 kW 22.5 kW 30 kW 45 kW 60 kW 80 100 150 150 53 72 92 131 139 60 80 100 150 150 90 110 150 175 59 81 104 149 158 70 90 110 175 175 40 60 80 80 29 40 52 74 79 35 45 60 80 80 35 45 60 70 23 32 41 60 63 25 35 45 70 70 15 kW 22.5 kW 30 kW 45 kW 60 kW 56 75 95 134 142 62 84 107 152 161 31 42 53 76 80 25 34 43 61 64 54W56 54W57 54W57 57W57 4 Not available 54W56 54W57 54W57 54W57 4 Not available 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 Power Exhaust ELECTRICAL ACCESSORIES Disconnect 15 kW 22.5 kW 30 kW 45 kW 60 kW Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Disconnect must be field furnished. 1 2 Page 13 ELECTRICAL/ELECTRIC HEAT DATA 12.5 TON STANDARD EFFICIENCY (R-410A) 1 Voltage - 60hz Compressor 1 Rated Load Amps Locked Rotor Amps Compressor 2 Rated Load Amps Locked Rotor Amps Outdoor Fan Full Load Amps (total) Motors (2) 12.5 TON KCA150S4 575V - 3 Ph 7.4 50 7.4 50 1.2 . (2.4) 208/230V - 3 Ph 19 123 19 123 3 . (6) 460V - 3 Ph 9.7 62 9.7 62 1.5 . (3) Full Load Amps 2.4 1.3 1 (1) 0.33 HP Service Outlet 115V GFI (amps) Indoor Blower Horsepower Full Load Amps Motor 15 5 16.7 15 5 7.6 15 5 6.1 70 70 35 35 25 25 53 56 27 29 22 23 Power Exhaust 2 Maximum Overcurrent Protection Minimum 3 Circuit Unit Only With (1) 0.33 HP Power Exhaust Unit Only With (1) 0.33 HP Power Exhaust Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Unit+ 15 kW Maximum 22.5 kW Electric Heat Overcurrent 30 kW Protection 45 kW 60 kW 3 Unit+ 15 kW Minimum Electric Heat 22.5 kW Circuit 30 kW Ampacity 45 kW 60 kW 2 15 kW Unit+ Maximum Electric Heat 22.5 kW Overcurrent 30 kW and (1) 0.33 Protection 45 kW HP 60 kW Power Exhaust 3 Minimum Unit+ Circuit Electric Heat Ampacity and (1) 0.33 HP 15 kW 22.5 kW 30 kW 45 kW 60 kW Power Exhaust ELECTRICAL ACCESSORIES Disconnect 15 kW 22.5 kW 30 kW 45 kW 60 kW 208V 70 4 70 4 90 4 125 150 53 64 84 123 130 70 4 70 4 90 150 4 150 240V 70 80 100 150 150 53 73 96 141 150 70 80 100 150 175 480V 35 40 50 80 80 27 37 48 71 75 35 40 50 80 80 600V 25 30 40 60 70 22 30 39 57 61 25 35 40 60 70 56 67 87 126 133 56 76 99 144 153 29 38 50 72 77 23 31 40 58 62 54W56 54W57 54W57 4 Not available 4 Not available 54W56 54W57 57W57 4 Not available 4 Not available 54W56 54W56 54W56 54W56 54W57 54W56 54W56 54W56 54W56 54W56 Extremes of operating range are plus and minus 10% of line voltage. HACR type breaker or fuse. Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 4 Disconnect must be field furnished. 1 2 3 Page 14 ELECTRIC HEAT CAPACITIES Volts Input 7.5 kW 15 kW 22.5 kW 30 kW 45 kW 60 kW kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of kW Btuh No. of Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages 208 5.6 19,100 1 11.3 38,600 1 16.9 57,700 2 22.5 76,800 2 33.8 115,300 2 45.0 153,600 2 220 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2 230 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2 240 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2 440 6.9 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2 460 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2 480 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2 550 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000 2 37.8 129,000 2 50.4 172,000 2 575 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2 600 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2 Page 15 KCA PARTS ARRANGEMENT ECONOMIZER (OPTIONAL) DISCONNECT / CIRCUIT BREAKER (FACTORY OR FIELD INSTALLED OPTION) EVAPORATOR COIL BLOWER MOTOR CONDENSER FANS CONDENSER COIL BLOWER BLOWER COMPRESSORS ELECTRIC HEAT CONDENSATE DRAIN FILTERS (FOUR − 20 X 25 X 2") FIGURE 1 KCA CONTROL BOX − Y, G, J−VOLT UNITS KCA CONTROL BOX − M VOLT CE UNITS K1 K2 K3 K65 K65 K2 K3 T1 T1 K10 K10 S42 S176 S177 K1 S42 K125 FIGURE 2 FIGURE 3 Page 16 I−UNIT COMPONENTS CONTACTOR All 7.5 through 12.5 ton (26.3 through 44 kW) units are configure to order units (CTO). The KCA unit components are shown in figure 1. All units come standard with removable unit panels. All L1, L2 and L3 wiring is color coded; L1 is red, L2 is yellow and L3 is blue. A−Control Box Components KCA control box components are shown in figure 2 and 3. The control box is located in the upper portion of the compressor compartment. FIGURE 5 7−Blower Contactor K3 1−Disconnect Switch S48 or CB10 (CB10 field−installed only) All units may be equipped with an optional disconnect switch S48 or circuit breaker CB10. S48 and CB10 are toggle switches, which can be used by the service technician to disconnect power to the unit. Blower contactor K3, used in all units, is a three-poledouble-break contactor with a 24VAC coil used to energize the indoor blower motor B3 in response to blower demand. K3 is energized by a thermostat cooling demand. On M−volt CE units, the contactor is CE approved by manufacturer (Siemens). See figure 5. 2−Control Transformer T1 all units 8−Power Exhaust Relay K65 (PED units) All use a single line voltage to 24VAC transformer mounted in the control box. Transformer supplies power to control circuits in the unit. The transformer is rated at 70VA and is protected by a 3.5 amp circuit breaker (CB8). The 208/230 (Y) voltage transformers use two primary voltage taps as 208/230V TRANSFORMER BLUE YELLOW shown in figure 4, while SECONDARY 460 (G) and 575 (J) voltage transformers 208 VOLTS use a single primary RED voltage tap. 230 VOLTS Power exhaust relay K65 is a DPDT relay with a 24VAC coil. K65 is used in all KCA units equipped with the optional power exhaust dampers. K65 is energized by the economizer enthalpy control A6, after the economizer dampers reach 50% open (adjustable) When K65 closes, exhaust fan B10 is energized. ORANGE PRIMARY BLACK FIGURE 4 3−Terminal Strip TB1 All indoor thermostat connections will be to TB1 located in the control area. For thermostats without occupied and unoccupied" modes, a factory installed jumper across terminals R and OC should be in place. 4−Condenser Fan Capacitors C1 & C2 Fan capacitors C1 and C2 are used to assist in the start up of condenser fans B4 and B5. Ratings will be on side of capacitor or outdoor fan motor nameplate. 9−Blower Motor Overload Relay Switch (S42) The blower motor overload relay is used in all units equipped with high efficiency motors. The relay (S42) is connected in line with the blower motor to monitor the current flow to the motor. When the relay senses an overload condition, a set of normally closed contacts open to de−energize 24VAC power to T1 transformer. Non−CE units will be equipped with a relay manufactured by Telemecanique figure 7 or Siemens figure 8. M−volt CE units will be equipped with a relay manufactured by Siemens. See figure 6. 10−Compressor Overload Relays S176, S177 (M−volt CE units) Relays are wired in series with the appropriate compressor contactor and monitor the current flow to the compressor motor. When the relay senses an overload condition, N.C. contacts open to de−energize the compressor. Relays are manufactured by Siemens; see figure 6. COMPRESSOR OVERLOAD RELAYS 5−Compressor Contactor K1 & K2 All compressor contactors are three-pole-double-break contactors with 24VAC coils. In all KCA units, K1 and K2 energize compressors B1 and B2 in response to thermostat demand. On CE M−volt units, contactor is CE approved by manufacturer (Siemens). See figure 5. SET RELAYS TO MAXIMUM OVERLOAD SETTING 6−Condenser Fan Relay K10 Outdoor fan relay K10 is a DPDT relay with a 24VAC coil. K10 energizes condenser fans B4 and B5. FIGURE 6 Page 17 LINE VOLTAGE IN TELEMECANIQUE OVERLOAD RELAY TRIP INDICATION WINDOW AMP SETTING POINTER CLEAR COVER (SHOWN CLOSED) DETAIL SHOWING RESET BUTTON ADJUSTED TO MANUAL POSITION STOP BUTTON (RED) Lift clear cover and turn adjustment screw counterclockwise. Reset screw will pop out when pointer is in M (manual position). Close cover to lock reset screw into position. AMP SETTING CONTROL (BLUE DIAL) RED TEST BUTTON (Push To Test) LOAD VOLTAGE OUT BLUE RESET SCREW (Shown in AUTO position as shipped from the factory) Lift clear cover to adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95. Cover must also be lifted to adjust control mode from automatic reset to manual reset (see detail above) and to test the control. Control must be in the manual reset mode to perform a test. Use a pointed object to press the small red test button. A yellow marker should appear in the trip indication window to the right of the amp setting control. Press the blue reset screw to reset the relay. The red STOP button opens the normally closed contacts which power the blower motor. This button stops blower motor operation as long as it is pressed in. FIGURE 7 SIEMENS OVERLOAD RELAY BLUE RESET BUTTON IN FACTORY-SET AUTO MODE (Turn clockwise to H for manual reset) GREEN TRIP INDICATOR (Flush with surface −− not tripped; Above surface −− tripped) RED TEST BUTTON AMP ADJUSTMENT DIAL Adjust relay amp setting according to value given on the blower motor nameplate. Proper relay amp setting equals motor nameplate FLA X service factor of 1.15 X .95. Use small slotted screwdriver to adjust control mode from automatic reset (A) to manual reset (H). Control must be in the manual reset mode (H) to perform a test. Press the red test button. Green trip indicator should pop out. Press the blue reset screw to reset the relay. FIGURE 8 Page 18 KCA092,102, 120, 150 PLUMBING AND COMPRESSOR CIRCUITS DETAIL OUTDOOR COIL STAGE 2 INDOOR COIL STAGE 2 INDOOR COIL STAGE 1 DRIERS OUTDOOR COIL STAGE 1 COMPRESSOR 2 COMPRESSOR 1 COMPRESSOR 2 S8 THERMAL PROTECTOR COMPRESSOR 1 S5 THERMAL PROTECTOR SUCTION LINE SUCTION LINE DISCHARGE LINE DISCHARGE LINE S7 HIGH PRESSURE SWITCH S4 HIGH PRESSURE SWITCH PRESSURE TAP PRESSURE TAP FIGURE 9 Page 19 B−Cooling Components 2−Thermal Protectors S5, S8 All units use independent cooling circuits consisting of separate compressors, condenser coils and evaporator coils. See figure 9. Two draw−through type condenser fans are used in KCA092/150 units. All units are equipped with beltdrive blowers which draw air across the evaporator during unit operation. Some compressors have thermal protectors located on top of the compressor. The protectors open at 248F + 9F (120C + 5C) and close at 169F + 18F (76C + 10C). Cooling may be supplemented by a factory- or fieldinstalled economizer. The evaporators are slab type and are stacked. Each evaporator uses a thermostatic expansion valve as the primary refrigerant metering device. Each evaporator is also equipped with enhanced fins and rifled tubing. In all units each compressor is protected by S49 and S50 freezestats and S4 and S7 high pressure switches (on each evaporator). Low ambient switches (S11, S84) are available as an option for additional compressor protection. On 150 units, each compressor is protected by a crankcase heater. 1−Compressors B1 and B2 All KCA092/150 units use two scroll compressors. Compressor capacity may vary from stage to stage. In all cases, the capacity of each compressor is added to reach the total capacity of the unit. See SPECIFICATIONS" and ELECTRICAL DATA" (table of contents) or compressor nameplate for compressor specifications. 3−Freezestats S49 and S50 Each unit is equipped with a low temperature switch (freezestat) located on a return bend of each evaporator coil. S49 (first circuit) and S50 (second circuit) are located on the corresponding evaporator coils. Freezestats are wired in series with compressor contactors. Each freezestat is a SPST N.C. auto−reset switch which opens at 29F + 3F (-1.7C + 1.7C) on a temperature drop and closes at 58F + 4F (14.4C + 2.2C) on a temperature rise. To prevent coil icing, freezestats open during compressor operation to temporarily disable the respective compressor until the coil temperature rises. If the freezestats are tripping frequently due to coil icing, check the airflow/filters, economizer position and unit charge before allowing unit back in operation. Make sure to eliminate conditions which might promote evaporator ice buildup. 4−High Pressure Switches S4 and S7 The high pressure switch is a manual reset SPST N.C. switch which opens on a pressure rise. S4 (first circuit) and S7 (second circuit)are located in the compressor discharge line and wired in series with the respective compressor contactor coils. When discharge pressure rises to 640 ± 10 psig (4413 ± 69 kPa) (indicating a problem in the system) the switch opens and the respective compressor is de−energized (the economizer can continue to operate). WARNING Electrical shock hazard. Compressor must be grounded. Do not operate without protective cover over terminals. Disconnect power before removing protective cover. Discharge capacitors before servicing unit. Failure to follow these precautions could cause electrical shock resulting in injury or death. 5−Low Ambient Switches S11 & S84 (optional) The low ambient switch is an auto-reset SPST N.O. pressure switch which allows for mechanical cooling operation at low outdoor temperatures. In all models a switch is located in each liquid line prior to the indoor coil section. Each compressor is energized by a corresponding compressor contactor. In the KCA092/150, S11 and S84 are wired in parallel with outdoor fan relay K10. NOTE−Refer to the wiring diagram section for specific unit operation. When liquid pressure rises to 450 ± 10 psig (3102 ± 69 kPa), the switch closes and the condenser fans are energized. When discharge pressure in both refrigerant circuits drops to 240 ± 10 psig (1655 ± 69 kPa), the switches open and the condenser fans are de−energized. This intermittent fan operation results in higher evaporating temperature allowing the system to operate without icing the evaporator coil and losing capacity. If Interlink compressor replacement is necessary, call 1−800−4−LENNOX (1−800−453−6669). IMPORTANT Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system rises above 40 psig. DO NOT REPLACE COMPRESSOR. 6−Crankcase Heaters HR1, HR2 150S units use insertion type heaters. Heater HR1 is installed around compressor B1 and heater HR2 is installed around compressor B2. Crankcase heater wattage varies by compressor manufacturer. Page 20 C−Blower Compartment The blower compartment in all KCA092/150S units is located between the evaporator coil and the condenser coil section. The blower assembly is accessed by disconnecting the blower motor .See Blower Access in the Operation/ Adjustment section. The blower pulls out as shown in figure 10. 1−Blower Wheels All KCA092/150 units have one 15 in. x 15 in. (381 mm x 381 mm) blower wheel. 2−Indoor Blower Motor B3 All units use three-phase single-speed blower motors. CFM adjustments are made by adjusting the motor pulley (sheave). Motors are equipped with sealed ball bearings. All motor specifications are listed in the SPECIFICATIONS (table of contents) in the front of this manual. Units may be equipped with motors manufactured by various manufacturers, therefore electrical FLA and LRA specifications will vary. See unit rating plate for information specific to your unit. OPERATION / ADJUSTMENT Blower Operation Initiate blower demand at thermostat according to instruc- tions provided with thermostat. Unit will cycle on thermostat demand. The following steps apply to applications using a typical electro−mechanical thermostat. 1− Blower operation is manually set at the thermostat subbase fan switch. With fan switch in ON position, blowers will operate continuously. 2− With fan switch in AUTO position, the blowers will cycle with demand. Blowers and entire unit will be off when system switch is in OFF position. Determining Unit CFM 1− The following measurements must be made with a dry indoor coil. Run blower without a cooling demand. Measure the indoor blower shaft RPM. Air filters must be in place when measurements are taken. 2− With all access panels in place, measure static pressure external to unit (from supply to return). Measure static below roof curb if roof curb is used. 3− Refer to blower tables in BLOWER DATA (table of contents) in the front of this manual. Use static pressure and RPM readings to determine unit air volume. BLOWER ASSEMBLY TO INCREASE BELT TENSION SIDE VIEW 1− Loosen four bolts securing motor mounting base to frame. 2− Turn adjusting bolt to the right, or clockwise, to move the motor away from the blower housing. MOTOR IMPORTANT − Gap between end of frame and motor mounting base should be equal at both ends, i.e. parallel along gap. PULLEY 3− Tighten four bolts securing motor mounting base to frame. BLOWER HOUSING 4− Relieve tension on two adjusting bolts. MOTOR MOUNTING BASE BELT ADJUSTING BOLTS − TURN CLOCKWISE TO TIGHTEN BELT GAP BETWEEN EDGES SHOULD BE PARALLEL ON BOTH ENDS BEFORE TIGHTENING MOTOR MOUNTING BASE IN PLACE REMOVE TWO SCREWS TO COMPLETELY SLIDE BLOWER OUT OF UNIT ALLEN SCREW MOTOR BLOWER FRAME LOOSEN BEFORE ADJUSTING BELT TENSION (TWO EACH SIDE) REMOVE TWO SCREWS ON EACH SIDE TO SLIDE FRAME PARTIALLY OUT OF UNIT FOR SERVICE ACCESS FIGURE 10 Page 21 4− The blower RPM can be adjusted at the motor pulley. Loosen Allen screw and turn adjustable pulley clockwise to increase CFM. Turn counterclockwise to decrease CFM. See figure 10. Do not exceed minimum and maximum number of pulley turns as shown in table 1. TABLE 1 MINIMUM AND MAXIMUM PULLEY ADJUSTMENT Belt Minimum Turns Open Maximum Turns Open A Section No minimum 5 B Section 1* 6 Check Belt Tension Overtensioning belts shortens belt and bearing life. Check belt tension as follows: 1− Measure span length X. See figure 12. Blower Belt Adjustment Maximum life and wear can be obtained from belts only if proper pulley alignment and belt tension are maintained. Tension new belts after a 24−48 hour period of operation. This will allow belt to stretch and seat grooves. Make sure blower and motor pulley are aligned as shown in figure 11. 2− Apply perpendicular force to center of span (X) with enough pressure to deflect belt 1/64" for every inch of span length or 1.5mm per 100mm of span length. Example: Deflection distance of a 40" span would be 40/64" or 5/8". Example: Deflection distance of a 400mm span would be 6mm. 3− Measure belt deflection force. For a used belt, the deflection force should be 5 lbs. (35kPa). A new belt deflection force should be 7 lbs. (48kPa). PULLEY ALIGNMENT ALIGNED BELT IMPORTANT − Align top edges of blower motor base and mounting frame base parallel before tightening two bolts on the other side of base. Motor shaft and blower shaft must be parallel. 3− Tighten bolts on side of base. *No minimum number of turns open when B belt is used on pulleys 6" O.D. or larger. BLOWER PULLEY To loosen belt tension − Turn the adjusting bolt to the left, or counterclockwise to loosen belt tension. A force below these values indicates an undertensioned belt. A force above these values indicates an overtensioned belt. MOTOR PULLEY MEASURE BELT TENSION NOT ALIGNED FIGURE 11 FORCE 1− Loosen four bolts securing motor base to mounting frame. See figure 10. 2− To increase belt tension − Turn adjusting bolt to the right, or clockwise, to move the motor outward and tighten the belt. This increases the distance between the blower motor and the blower housing. Page 22 DEFLECTION 1/64" PER INCH OF SPAN OR 1.5mm PER 100mm OF SPAN FIGURE 12 D−Optional Electric Heat Components Table 2 shows electric heat fuse ratings. See Options/Accessories section (see table of contents) for KCA to EHA match− ups. See Electrical/Electric Heat Data section (see table of contents) of this manual for electrical ratings and capacities. All electric heat sections consist of electric heating elements exposed directly to the air stream. See figure 14. EHA parts arrangement is shown in figures 14 and 15. Multiple-stage elements are sequenced on and off in response to thermostat demand. 1−Contactors K15, K16 Contactors K15 and K16 are three−pole double−break contactors located on the electric heat vestibule. All contactors are equipped with a 24VAC coil. The coils in the K15 and K16 contactors are energized by a W2 thermostat demand, K9, and DL2. Contactor K15 energizes the first stage heating elements, while K16 energizes the second stage heating elements. On M−volt units, contactors are CE approved by manufacturer (Siemens). See figure 5. 2−High Temperature Limits S15 (Primary) S15 is a SPST N.C. auto-reset thermostat located on the back panel of the electric heat section below the heating elements. S15 is the high temperature limit for the electric heat section. When S15 opens, indicating a problem in the system, contactor K15 is de-energized. When K15 is de-energized, first stage and all subsequent stages of heat are de-energized. For EHA102/150 units, the electric heat section thermostat is factory set to open at 170_F + 5_F (76_C + 2.8_C) on a temperature rise and automatically reset at 130_F + 6_F (54.4_C + 3.3_C) on a temperature fall. For EHA100 units, the electric heat section thermostat is factory set to open at 160_F + 5_F (71.0_C + 2.8_C) on a temperature rise and automatically reset at 120_F + 6_F (49.0_C + 3.3_C) on a temperature fall. The thermostat is not adjustable. 3−High Temperature Limit S20, S157, S158, S15, S160 & S161 (Secondary) Limits are SPST N.C. manual-reset thermostat . Like the primary temperature limit, S20 is wired in series with the first stage contactor coil (K15) and second stage contactor coil (K16). When S20 opens, contactors (K15, K16) are de-energized. When the contactors are de-energized, first stage and all subsequent stages of heat are de-energized. The thermostat is factory set to open at 220_F + 6_F (104_C + 3.3_C) on a temperature rise and can be manually reset when temperature falls below 160_F (71.0_C). 4−Terminal Strip TB2 Terminal strip TB2 is used for single point power installations only. TB2 distributes L1, L2 and L3 power to TB3. Units with multi−point power connections will not use TB2. 5−Terminal Strip TB3 Electric heat line voltage connections are made to terminal strip TB3 located in the upper left corner of the electric heat vestibule. TB3 distributes power to the electric heat components. 6−Heating Elements HE1 through HE6 Heating elements are composed of helix wound bare nichrome wire exposed directly to the air stream. Three elements are connected in a three-phase arrangement. The elements in 208/230V units are connected in a Delta" arrangement. Elements in 460 and 575V units are connected in Wye" arrangement. Each stage is energized independently by the corresponding contactors located on the electric heat vestibule panel. Once energized, heat transfer is instantaneous. High temperature protection is provided by primary and redundant high temperature limits and overcurrent protection is provided by fuses. 7−Fuse F3 Fuse F3 are housed in a fuse block which holds three fuses. Each F3 fuse is connected in series with each leg of electric heat. Figure 15 and table 2 show the fuses used with each electric heat section. For simplicity, the service manual labels the fuses F3 − 1, 2 and F4 − 1, 2. 8−Unit Fuse Block F4 Three line voltage fuses F4 provide short circuit and ground fault protection to all cooling components in the KCA units with electric heat. The fuses are rated in accordance with the amperage of the cooling components. ELECTRIC HEAT CONTROL ASSEMBLY 1−Electric Heat Relay K9 All KCA series units with electric heat use an electric heat relay K9. K9 is a N.O. DPDT pilot relay intended to electrically isolate the unit’s 24V circuit from the electric heat 24V circuit. K9 is energized by CMC1. K9−1 closes, energizing timer DL2. K9 is located in the electric heat control assembly. See figure 13. 2−Time Delay DL2 DL2 is a factory−installed solid state timer used in 22.5 to 60 kW electric heat units. DL2 allows staging by providing a timed−interval between the first and second heating elements. When the timer is energized, the contacts are delayed for 30 seconds before closing. When the timer is de−energized, the contacts are delayed 1 second before opening. DL2 is located in the electric heat control assembly. See figure 13. Page 23 ELECTRIC HEAT CONTROL ASSEMBLY ELECTRIC HEAT CONTROL ASSEMBLY ELECTRIC HEAT SECTION K9 DL2 FIGURE 13 EHA QUANTITY & SIZE EHA100−7.5 EHA100−15 EHA100−22.5 EHA100−30 EHA100−45 EHA102−7.5 EHA150−15 EHA360−22.5 EHA150−30 EHA150−45 EHA150−60 TABLE 2 KCA ELECTRIC HEAT SECTION FUSE RATING FUSE (3 each) VOLTAGES F3 − 1 F3 − 2 F3 − 3 F3 − 4 208/230V 25 Amp 250V −−−−− −−−−− −−−−− 460V 15 Amp 600V −−−−− −−−−− −−−−− 575V 10 Amp 600V −−−−− −−−−− −−−−− 208/230V 50 Amp 250V −−−−− −−−−− −−−−− 460V 25 Amp 600V −−−−− −−−−− −−−−− 575V 20 Amp 600V −−−−− −−−−− −−−−− 208/230V 50 Amp250V −−−−− −−−−− 25 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 15 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 10 Amp 600V 208/230V 50 Amp 250V −−−−− −−−−− 50 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 25 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 20 Amp 600V 208/230V 50 Amp 250V −−−−− 60 Amp 250V 60 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 50 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 40 Amp 600V 208/230V 25 Amp 250V −−−−− −−−−− −−−−− 460V 15 Amp 600V −−−−− −−−−− −−−−− 575V 10 Amp 600V −−−−− −−−−− −−−−− 208/230V 50 Amp 250V −−−−− −−−−− −−−−− 460V 25 Amp 600V −−−−− −−−−− −−−−− 575V 20 Amp 600V −−−−− −−−−− −−−−− 208/230V 50 Amp 250V −−−−− −−−−− 25 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 15 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 10 Amp 600V 208/230V 50 Amp 250V −−−−− −−−−− 50 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 25 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 20 Amp 600V 208/230V 50 Amp 250V −−−−− 60 Amp 250V 60 Amp 250V 460V 25 Amp 600V −−−−− −−−−− 50 Amp 600V 575V 20 Amp 600V −−−−− −−−−− 40 Amp 600V 208/230V 60 Amp 250V 60 Amp 250V 60 Amp 250V 60 Amp 250V 460V 50 Amp 600V −−−−− −−−−− 50 Amp 600V 575V 40 Amp 600V −−−−− −−−−− 40 Amp 600V Page 24 EHA 7.5, 15, 22.5, 30, 45, 60KW ELECTRIC HEAT SECTION PARTS ARRANGEMENT ELECTRIC HEAT VESTIBULE SECONDARY LIMIT S20 SECONDARY LIMIT S20 HEATING ELEMENTS HE1 − HE6 SECONDARY LIMIT S20 SECONDARY LIMIT S20 SECONDARY LIMIT S20 SECONDARY LIMIT S20 ELECTRIC HEAT THERMOSTAT S19 PRIMARY ELECTRIC HEAT LIMIT S15 P2 CONTROL WIRE HARNESS FIGURE 14 ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT TERMINAL STRIP (TB3) FUSE F3 F3 - 1 FUSE F3 F3−2 FUSE F4 F4 - 2 FIRST STAGE ELECTRIC HEAT CONTACTOR K15 SECOND STAGE ELECTRIC HEAT CONTACTOR K16 FIGURE 15 Page 25 FUSE F4 F4 - 1 II−PLACEMENT AND INSTALLATION Three Phase Scroll Compressor Voltage Phasing Make sure the unit is installed in accordance with the installation instructions and all applicable codes. See accessories section for conditions requiring use of the optional roof mounting frame (LARMF18/36 or LARMFH18/24). Three phase power supplied to the unit disconnect switch must be phased sequentially to ensure the scroll compressor and indoor blower rotate in the correct direction. Compressor and blower are wired in phase at the factory. Power wires are color−coded as follows: line 1−red, line 2−yellow, line 3−blue. III−STARTUP − OPERATION A−Preliminary and Seasonal Checks 1− Observe suction and discharge pressures and blower rotation on unit start−up. 1− Make sure the unit is installed in accordance with the installation instructions and applicable codes. 2− Suction pressure must drop, discharge pressure must rise and blower rotation must match rotation marking. 2− Inspect all electrical wiring, both field and factory installed for loose connections. Tighten as required. Refer to unit diagram located on inside of unit compressor access panel. 3− Check to ensure that refrigerant lines are in good condition and do not rub against the cabinet or other refrigerant lines. 4− Check voltage at the disconnect switch. Voltage must be within the range listed on the nameplate. If not, consult the power company and have the voltage corrected before starting the unit. If pressure differential is not observed or blower rotation is not correct: 3− Disconnect all remote electrical power supplies. 4− Reverse any two field−installed wires connected to the line side of K2 contactor or disconnect switch if installed. Do not reverse wires at blower contactor. 5− Make sure the connections are tight. Discharge and suction pressures should operate at their normal start-up ranges. 5− Recheck voltage and amp draw with unit running. If voltage is not within range listed on unit nameplate, stop unit and consult power company. Refer to unit nameplate for maximum rated load amps. REFRIGERANT CIRCUITS 092/150 (BOTH FANS ARE ENERGIZED WITH A Y1 DEMAND) B−Cooling Startup EVAPORATOR COIL STAGE 2 1− Initiate first and second stage cooling demands according to instructions provided with thermostat. 2− First−stage thermostat demand will energize compressor 1. Second−stage thermostat demand will energize compressor 2. On units with an economizer, when outdoor air is acceptable, a first−stage demand will energize the economizer; a second−stage demand will energize compressor 1. 3− Units contain two refrigerant circuits or stages. See figure 16. 2 1 EVAPORATOR COIL STAGE 1 4− Each refrigerant circuit is separately charged with refrigerant. See unit rating plate for correct amount of charge. NOTE − Refer to IV−CHARGING for proper method to check refrigerant charge. FIGURE 16 C−Safety or Emergency Shutdown Turn off power to unit. Page 26 TABLE 4 KCA102 NORMAL OPERATING PRESSURES IV−CHARGING WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. WARNING−Do not exceed nameplate charge under any condition. This unit is factory charged and should require no further adjustment. If the system requires additional refrigerant, reclaim the charge, evacuate the system and add required nameplate charge. NOTE − System charging is not recommended below 60°F (15°C). In temperatures below 60°F (15°C) , the charge must be weighed into the system. If weighing facilities are not available, or to check the charge, use the following procedure: 1− Attach gauge manifolds and operate unit in cooling mode with economizer disabled until system stabilizes (approximately five minutes). Make sure outdoor air dampers are closed. Outdoor Coil Entering Air Temp 655 F 755 F 855 F 955 F 1055 F 1155 F 4− Apply the outdoor temperature to tables 3 through 6 to determine normal operating pressures. Pressures are listed for sea level applications at 80°F dry bulb and 67°F wet bulb return air. CIRCUIT 2 DisSuction charge +5 psig +10 psig 270 129 310 131 353 134 399 136 448 139 501 142 TABLE 5 KCA120 NORMAL OPERATING PRESSURES Outdoor Coil Entering Air Temp 655 F 755 F 855 F 955 F 1055 F 1155 F CIRCUIT 1 DisSuction charge +5 psig +10 psig 275 135 313 137 355 140 400 142 447 145 499 148 CIRCUIT 2 DisSuction charge +5 psig +10 psig 282 136 323 138 366 141 414 143 464 145 517 148 TABLE 6 KCA150 NORMAL OPERATING PRESSURES 2− Check each system separately with all stages operating. 3− Use a thermometer to accurately measure the outdoor ambient temperature. CIRCUIT 1 DisSuction charge +5 psig +10 psig 262 128 299 131 342 134 386 137 434 140 487 143 Outdoor Coil Entering Air Temp 655 F 755 F 855 F 955 F 1055 F 1155 F CIRCUIT 1 DisSuction charge +5 psig +10 psig 279 132 318 134 360 136 406 138 456 141 508 145 CIRCUIT 2 DisSuction charge +5 psig +10 psig 283 136 323 138 364 139 411 140 462 142 515 145 5− Compare the normal operating pressures to the pressures obtained from the gauges. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Correct any system problems before proceeding. Charge Verification − Approach Method − AHRI Testing 6− If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refrigerant to the system. Approach Temperature = Liquid temperature minus ambient temperature. S Add or remove charge in increments. S Allow the system to stabilize each time refrigerant is added or removed. 7− Use the following approach method along with the normal operating pressures to confirm readings. TABLE 3 KCA092 NORMAL OPERATING PRESSURES Outdoor Coil Entering Air Temp 655 F 755 F 855 F 955 F 1055 F 1155 F CIRCUIT 1 DisSuction charge +5 psig +10 psig 260 130 301 133 343 135 388 138 435 140 481 142 CIRCUIT 2 DisSuction charge +5 psig +10 psig 269 132 311 133 354 136 401 139 449 141 497 144 1− Using the same thermometer, compare liquid temperature (at condenser outlet) to outdoor ambient temperature. 2− Approach temperature should match values shown in table 7. An approach temperature greater than this value indicates an undercharge. An approach temperature less than this value indicates an overcharge. 3− The approach method is not valid for grossly over or undercharged systems. Use tables 3 through 6 as a guide for typical operating pressures. TABLE 7 APPROACH TEMPERATURE Liquid Temp. Minus Ambient Temp. Unit 1st Stage 2nd Stage 092 9°F + 1 (5.0°C + 0.5) 8°F + 1 (4.4°C + 0.5) 102 7°F + 1 (3.9°C + 0.5) 6°F + 1 (3.3°C + 0.5) 120 8°F + 1 (4.4°C + 0.5) 6°F + 1 (3.3°C + 0.5) 150 6°F + 1 (3.3°C + 0.5) 6°F + 1 (3.3°C + 0.5) Page 27 V− SYSTEMS SERVICE CHECKS A−Cooling System Service Checks A−Filters KGA units are factory charged and require no further adjustment; however, charge should be checked periodically using the approach method. The approach method compares actual liquid temperature with the outdoor ambient temperature. See section IV− CHARGING. NOTE−When unit is properly charged discharge line pressures should approximate those in tables 3 through 6. Units are equipped with four 20 X 25 X 2" filters. Filters should be checked and replaced when necessary with filters of like kind and size. Take note of air flow direction marking on filter frame when reinstalling filters. See figure 17. Filters must be U.L.C. certified or equivalent for use in Canada. B−Lubrication All motors are lubricated at the factory. No further lubrication is required. REMOVE FILTERS IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non−compliance. VI−MAINTENANCE The unit should be inspected once a year by a qualified service technician. PULL TO REMOVE FILTERS ! WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. FIGURE 17 C−Evaporator Coil CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. WARNING Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown on unit nameplate or contact your supervisor. Inspect and clean coil at beginning of each cooling season. Clean using mild detergent or commercial coil cleanser. Flush coil and condensate drain with water taking care not to get insulation, filters and return air ducts wet. D−Condenser Coil Clean condenser coil annually with detergent or commercial coil cleaner and inspect monthly during the cooling season. Condenser coils are made of one, two and three formed slabs. Dirt and debris may become trapped between the slabs. To clean between slabs, carefully separate coil slabs and wash them thoroughly. See figure 18. Flush coils with water following cleaning. Note − Remove all screws and gaskets prior to cleaning procedure and replace upon completion. E−Supply Blower Wheel Annually inspect supply air blower wheel for accumulated dirt or dust. Turn off power before attempting to remove access panel or to clean blower wheel. Page 28 CLEAN CONDENSER COIL TOP VIEW ENDPLATE IS SECURED TO MULLION 1− Remove unit top panel and condenser section access panel. 2− Remove screws securing coil end plate to mullion. 3− Remove clips connecting coils slabs and separate slabs 3−4" (76−102mm). 4− Clean coils with detergent or commercial coil cleaner. 5− Rinse thoroughly with water and reassemble. EVAPORATOR COIL BLOWER CONDENSER COILS CONDENSER ACCESS PANEL FIGURE 18 VII−ACCESSORIES ASSEMBLED ROOF MOUNTING FRAME The accessories section describes the application of most of the optional accessories which can be factory or field installed to the KCA units. OPTIONAL ACCESSORIES section (see table of contents) show specific size per unit. SUPPLY AIR OPENING RETURN AIR OPENING A−LARMF Mounting Frames When installing units on a combustible surface for downflow discharge applications, the Lennox C1CURB roof mounting frame is used. The roof mounting frames are recommended in all other applications but not required. If the KCA units are not mounted on a flat (roof) surface, they MUST be supported under all edges and under the middle of the unit to prevent sagging. The units MUST be mounted level within 1/16" per linear foot or 5mm per meter in any direction. The assembled C1CURB mounting frame is shown in figure 19. Refer to the roof mounting frame installation instructions for details of proper assembly and mounting. The roof mounting frame MUST be squared to the roof and level before mounting. Plenum system MUST be installed before the unit is set on the mounting frame. Typical roof curbing and flashing is shown in figure 20. Refer to the roof mounting frame installation instructions for proper plenum construction and attachment. B−Transitions FIGURE 19 TYPICAL FLASHING DETAIL UNIT BASE BOTTOM UNIT BASE RAIL FIBERGLASS INSULATION (Furnished) COUNTER FLASHING (Field Supplied) NAILER STRIP (Furnished) Optional supply/return transitions LASRT08/10 is available for use with the KCA 7.5 ton units and LASRT10/12 is available for the 8.5 and 10 ton units, utilizing optional C1CURB roof mounting frames. KCA 12.5 ton units will use LASRT15 with C1CURB roof mounting frame. Transition must be installed in the C1CURB mounting frame before mounting the unit to the frame. Refer to the manufacturer’s instructions included with the transition for detailed installation procedures. Page 29 CANT STRIP (Field Supplied) RIGID INSULATION (Field Supplied) ROOF MOUNTING FRAME (Extends around entire perimeter of unit) FIGURE 20 ROOFING MATERIAL LAOAD(M) MOTORIZED OUTDOOR AIR DAMPER MOTORIZED DAMPER COVER PANEL HORIZONTAL SUPPLY AIR OPENING COMPRESSOR SECTION HORIZONTAL RETURN AIR OPENING LOWER PANEL MANUAL OUTDOOR AIR DAMPER COVER PANEL MANUAL DAMPER HORIZONTAL SUPPLY AIR OPENING COMPRESSOR SECTION HORIZONTAL RETURN AIR OPENING LOWER PANEL FIGURE 21 Page 30 ECONOMIZER ACCESSORY PANEL MULLION ECONOMIZER DIVIDER PANEL (Attach with two provided screws) BOTTOM OF COMPRESSOR SECTION FLANGED RETURN AIR OPENING FIGURE 22 TABLE 8 C−LAOAD(M) Outdoor Air Dampers Field or Factory Installed Dampers will modulate to 55°F discharge air (RT6) when: Sensors Optional manual and motorized outdoor air dampers provide up to 25 percent fresh air for return. Motorized damper opens to minimum position simultaneously with the blower during the occupied period and remains closed during the unoccupied period. Manual damper assembly is manually operated; damper position is manually set at installation and remains in that position. See figure 21. D−Supply and Return Diffusers Single OA Sensible OA temperature (S175) is lower than free cooling setpoint. Single OA Sensible OA temperature and humidity (A7) is lower than free cooling setpoint. Differential Enthalpy − 1 in OA and 1 in RA OA temperature and humidity (A7) is lower than RA temperature and humidity (A62). IAQ Sensor CO2 sensed (A63 ) is higher than CO2 setpoint. Optional flush mount diffuser/return FD11 and extended mount diffuser/return RTD11 are available for use with all KCA units. Refer to manufacturer’s instructions included with transition for detailed installation procedures. MIXED AIR SENSOR (R1) LOCATION R1 MIXED AIR SENSOR E−K1ECON20B Economizer (Field or Factory Installed) Economizers use outdoor air for free cooling when temperature and/or humidity is suitable. See figure 22. The mixed air temperature sensor (R1) measures the supply air sensible temperature. See figure 23. The outdoor air sensible control is the default economizer control. An outdoor air single sensible sensor, S175, is also provided. See table 8 for outdoor and return air (OA and RA) sensor options. Refer to instructions provided with sensors for installation. An IAQ sensor is used when demand control ventilation (DCV) is specified. Damper minimum position can be set lower than traditional minimum air requirements resulting in cost savings. The IAQ sensor allows the A6 to open dampers to traditional ventilation requirements as room occupancy (CO2) increases. Page 31 FIGURE 23 A6 Enthalpy Control LED’S TABLE 9 ENTHALPY CONTROL SETPOINTS A steady green Free Cool LED indicates that outdoor air is suitable for free cooling. When an optional IAQ sensor is installed, a steady green DCV LED indicates that the IAQ reading is higher than setpoint requiring more fresh air. See figure 24. A6 ENTHALPY CONTROLLER Control Setting Free Cooling Setpoint At 50% RH A 73° F (23° C) B 70° F (21° C) C 67° F (19° C) D 63° F (17° C) Damper Minimum Position 2V EXH Set 10V EXH Open 2V Min Pos DCV Max 10V DAMPER MINIMUM POSITION IAQ MAXIMUM POSITION 1− Set thermostat to occupied mode if the feature is available. Make sure jumper is in place between TB1 terminals R and OC if using a thermostat which does not have the feature. (set higher than minimum position) IAQ READING IS ABOVE SETPOINT DCV 2V NOTE − A jumper is factory−installed between TB1 R and OC terminals to maintain occupied status (allowing minimum fresh air). When using an electronic thermostat or energy management system with an occupied/unoccupied feature, remove jumper. 2− Rotate MIN POS SET potentiometer to approximate desired fresh air percentage. DCV Set 10V Note − Damper minimum position can be set lower than traditional minimum air requirements when an IAQ sensor is specified. Dampers will open to DCV MAX setting (if CO2 is above setpoint) to meet traditional ventilation requirements. IAQ SETPOINT Free Cool B C A D OUTDOOR AIR SUITABLE LED 3− Measure outdoor air temperature. Mark the point on the bottom line of chart 1 and label the point A" (40_F, 4_C shown). FREE COOLING SETPOINT; A=Completely counterclockwise D=Completely clockwise 4− Measure return air temperature. Mark that point on the top line of chart 1 and label the point B" (74_F, 23_C shown). FIGURE 24 Free Cooling Setpoint Outdoor air is considered suitable when temperature and humidity are less than the free cooling setpoints shown in table 9. Setting A is recommended. See figure 24. At setting A, free cooling will be energized when outdoor air is approximately 73°F (23°C) and 50% relative humidity. If indoor air is too warm or humid, lower the setpoint to B. At setting B, free cooling will be energized at 70°F (21°C) and 50% relative humidity. When an optional A62 differential sensor is installed, turn A6 enthalpy control free cooling setpoint potentiometer completely clockwise to position D". 5− Measure mixed air (outdoor and return air) temperature. Mark that point on the top line of chart 1 and label point C" (70_F, 21_C shown). 6− Draw a straight line between points A and B. 7− Draw a vertical line through point C. 8− Draw a horizontal line where the two lines meet. Read the percent of fresh air intake on the side. 9− If fresh air percentage is less than desired, adjust MIN POS SET potentiometer higher. If fresh air percentage is more than desired, adjust MIN POS SET potentiometer lower. Repeat steps 3 through 8 until calculation reads desired fresh air percentage. Page 32 CHART 1 CALCULATE MINIMUM FRESH AIR PERCENTAGE MIXED AND RETURN AIR TEMPERATURE _F _C 0 −20 −29 −10 −23 0 −18 10 −12 20 −7 30 −1 40 4 50 10 60 16 70 21 C 80 27 90 32 100 _F 38 _C B 0 10 10 20 20 30 30 40 40 50 50 60 60 70 70 80 80 90 90 A 100 _F −20 _C −29 −10 −23 0 −18 10 −12 20 −7 30 −1 40 4 100 50 10 60 16 70 21 80 27 90 32 100 _F 38 _C OUTDOOR AIR TEMPERATURE DCV Set and Max Settings Adjust settings when an optional IAQ sensor is installed. Outdoor Air Not Suitable: During the unoccupied time period dampers are closed. The DCV SET potentiometer is factory−set at approximately 50% of the potentiometer range. Using a standard 1−2000ppm CO2 sensor, dampers will start to open when the IAQ sensor reads approximately 1000ppm. Adjust the DCV SET potentiometer to the approximate setting specified by the controls contractor. Refer to figure 24. During the occupied time period a cooling demand will open dampers to minimum position and mechanical cooling functions normally. During the occupied time period dampers will open to DCV MAX when IAQ reading is above setpoint (regardless of thermostat demand or outdoor air suitability). The DCV MAX potentiometer is factory−set at approximately 50% of the potentiometer range or 6VDC. Dampers will open approximately half way when CO2 rises above setpoint. Adjust the DCV MAX potentiometer to the approximate setting specified by the controls contractor. Refer to figure 24. Outdoor Air Suitable: See table 10 for economizer operation with a standard two− stage thermostat. During the occupied period, dampers will open to DCV MAX when IAQ reading is above setpoint (regardless of thermostat demand or outdoor air suitability). DCV MAX will NOT override damper full−open position. When an R1 mixed air sensor for modulating dampers is installed, DCV MAX may override damper free cooling position when occupancy is high and outdoor air temperatures are low. If R1 senses discharge air temperature below 45_F (7_C), dampers will move to minimum position until discharge air temperature rises to 48_F (9_C). Note − DCV Max must be set higher than economizer minimum position setting for proper demand control ventilation. Economizer Operation The occupied time period is determined by the thermostat or energy management system. TABLE 10 ECONOMIZER OPERATION − OUTDOOR AIR IS SUITABLE FOR FREE COOLING −− FREE COOL LED ON" ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁ ÁÁÁÁÁÁÁÁÁÁÁ THERMOSTAT DEMAND DAMPER POSITION MECHANICAL COOLING UNOCCUPIED OCCUPIED OFF CLOSED CLOSED NO G CLOSED MINIMUM NO Y1 OPEN* OPEN* NO Y2 OPEN* OPEN* STAGE 1 * Dampers will open to maintain 55°F (13°C) supply air when an R1 mixed air sensor is installed. Page 33 B−Outdoor Air Dampers F−Gravity Exhaust Dampers Optional manual and motorized outdoor air dampers provide fresh outdoor air. The motorized damper assembly opens to minimum position during the occupied time period and remains closed during the unoccupied period. Manual damper assembly is set at installation and remains in that position. Dampers are used in downflow (see figure 26) and horizontal (see figure 27) air discharge applications. Horizontal gravity exhaust dampers are installed in the return air duct. The dampers must be used any time an economizer and a power exhaust fan is applied to KCA series units. Gravity exhaust dampers allow exhaust air to be discharged from the system when an economizer and/or power exhaust is operating. Gravity exhaust dampers also prevent outdoor air infiltration during unit off cycle. See installation instructions for more detail. Set damper minimum position in the same manner as economizer minimum position. Adjust motorized damper position using the thumbwheel on the damper motor. See figure 25. Manual damper fresh air intake percentage can be determined in the same manner. NOTE− GED is optional except required with power exhaust dampers. GRAVITY EXHAUST DAMPERS − DOWNFLOW DAMPER MOTOR THUMBWHEEL HOOD TOP DAMPER ASSEMBLY HOOD TOP SUPPORT FIGURE 25 FIGURE 26 GRAVITY EXHAUST DAMPERS − HORIZONTAL RETURN AIR PLENUM 13 (330) 29−1/2 (749) FIGURE 27 Page 34 6−1/2 (165) G−Power Exhaust Fan H−Control Systems The power exhaust fan (PEF) requires an optional gravity exhaust damper and economizer and is used in downflow applications only. See figure 28. The PEF provides exhaust air pressure relief and also runs when return air dampers are closed and the supply air blower is operating. See installation instructions for more detail. Three different types of control systems may be used with the KCA series units. All thermostat wiring is connected to TB1 located in the control area. Each thermostat has additional control options available. See thermostat installation instructions for more detail. 1− Electro-mechanical thermostat (13F06) The electro-mechanical thermostat is a two stage heat / two stage cool thermostat with dual temperature levers. A non-switching or manual system switch subbase may be used. GED AND PEF INSTALLATION 2− Electronic thermostat (see price book) Any two stage heat / two stage cool electronic thermostat may be used. P18 GED GRAVITY EXHAUST DAMPERS 3− Honeywell T7300 thermostat (60L59) The Honeywell T7300 thermostat is a programmable, internal or optional remote temperature sensing thermostat. The T7300 provides occupied and unoccupied changeover control. PEF POWER EXHAUST FAN ASSEMBLY (ORDERED SEPARATELY) I−Smoke Detectors A171 and A172 FIGURE 28 Power Exhaust Setpoint Adjustment Locate the A6 enthalpy control in the control area. The EXH SET potentiometer is factory−set at approximately 50% of the dial range. See figure 29. Power exhaust fans will be energized 30 seconds after dampers are 50% open. Adjust the EXH SET potentiometer higher (clockwise toward 10V) to energize fans when dampers are further open. Adjust the EXH SET potentiometer lower (counterclockwise toward 2V) to energize fans when dampers are further closed. (Thirty−second delay allows dampers to partially open before exhaust fan starts.) A6 ENTHALPY CONTROLLER 2V EXH Set 10V EXH Open 2V Photoelectric smoke detectors are a field installed option. The smoke detectors can be installed in the supply air section (A172), return air section (A171), or in both the supply and return air section. J−Drain Pan Overflow Switch S149 (optional) The overflow switch is used to interrupt cooling operation when excessive condensate collects in the drain pan. The N.O. overflow switch is controlled by K220 and DL46 relays, located in the unit control panel. When the overflow switch closes, 24VAC power is interrupted and after a five− second delay unit compressors are de−energized. Once the condensate level drops below the set level, the switch will open. After a five−minute delay the compressor will be energized. ADJUST POWER EXHAUST FAN SETPOINT Min Pos DCV Max 10V ENERGIZED WHEN DAMPER POSITION IS HIGHER THAN EXHAUST FAN SETPOINT DCV 2V DCV Set 10V Free Cool B C A D FIGURE 29 Page 35 VIII−Wiring Diagrams and Sequence of Operation KCA092/150 UNIT DIAGRAM 24V POWER TO L1 P2 IS USED ON KCA UNITS ONLY IMPORTANT: TO PREVENTMOTOR BURNOUT, NEVER CONNECTMORETHAN ONEMOTORLEADTO ANY ONE CONNECTION. TAPE UNUSED MOTOR LEADS TO 380−420V N UNITS S42 USED ON "M" VOLTAGEUNITS AND UNITS WITH HIGH EFFICIENCY MOTORS CONNECT A172 SENSOR TO J261 ON SUPPLY AI R SMOKE DETECTOR ONLY S48 OR CB10 MAY BE USED JUMPER WHEN S11 AND S84 ARE NOT USED ECONOMIZER 3 BLOWER(G) HEAT 1(W1) HEAT 2(W2) DESCRIPTION KEY 5 COMPONENT A42 MONITOR, PHASE PROTECTION A144 MODULE, VOLTAGE REDUCTION COOL 1(Y1) COOL 2 (Y2) 7 K220 A B B K2 2 A A K1 L2 460V − 575V U N I T S A K10 A K3 BLACK A171 1 L1 T18 220−240V WHITE 8 6 B B B MODULE, CONTROL SMOKE DETECTION B1 COMPRESSOR 1 B2 COMPRESSOR 2 B3 MOTOR, BLOWER B4 MOTOR, OUTDOOR FAN 1 B5 MOTOR, OUTDOOR FAN 2 B10 MOTOR, EXHAUST FAN 1 C1 CAPACITOR, OUTDOOR FAN 1 C2 CAPACITOR, OUTDOOR FAN 2 C6 CAPACITOR, EXHAUST FAN 1 CB8 CIRCUIT, BREAKER T1 DL46 DELAY, OVERFLOW SWITCH HR1 HEATER COMPRESSOR 1 HR2 HEATER COMPRESSOR 2 J2 JACK, HEAT J11 JACK, GFI, RECEPTICLE DISCONNECT ALL POWER BEFORE SERVICING. J18 JACK, EXHAUST FAN COMPT J24 JACK, EXHAUST FAN J35 JACK, TEST J36 JACK, TEST COOL J86 JACK, OUTDOOR FANS 1 J132 JACK, BLOWER , EXHAUST FAN MOTOR 1 J250 JACK, SMOKE DETECTOR ONE J251 JACK, SMOKE DETECTOR ONE J252 JACK, SMOKE DETECTOR TWO J253 JACK, SMOKE DETECTOR TWO J255 JACK, MODULE, CONTROL SMOKE DETECTION 4 T3 K65−1 T3 6 9 7 K65−2 L3 K10−2 K2−1 T3 L3 J11 4 9 6 6 B2 120/ 60/1 SENSOR TWO, SMOKE, SUPPLY AIR A173 WARNING − ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY DEATH OR UNIT MUST BE GROUNDEDIN ACCORDANCEWITH NATIONAL AND LOCAL CODES L3 H A172 24V COMMON NOTE − IF ANY WIRE IN THIS APPLIANCEIS REPLACEDIT MUST BE REPLACEDWITH WIRE OF LIKE SIZE, RATING, TERMINATION AND INSULATION THICKNESS 2 SENSOR ONE, SMOKE, RETURN AIR B3 HR2 HR1 7 5 2 3 N GROUND P86 PLUG, OUTDOOR FANS 1 P132 PLUG, EXHAUST FAN MOTOR 1 P250 JACK, SMOKE DETECTOR ONE P251 JACK, SMOKE DETECTOR ONE P252 JACK, SMOKE DETECTOR TWO P253 JACK, SMOKE DETECTOR TWO P255 PLUG, MODULE, CONTROL SMOKE DETECTION S3 SWITCH, LIMIT LOW COMPRESSOR 1 S4 SWITCH, LIMIT HI PRESS COMP 1 S5 SWITCH, LIMIT HI TEMP COMPRESSOR 1 S7 SWITCH, LIMIT HI PRESS COMP 2 S8 SWITCH, LIMIT HI TEMP COMPRESSOR 2 S11 SWITCH, LOW PRESS, LOW AMBIENT KIT S30 SWITCH, LIMIT LOW COMPRESSOR 2 S42 SWITCH, OVERLOAD RELAY BLOWER MOTOR S48 SWITCH, DISCONNECT S49 SWITCH, FREEZESTAT COMP 1 S50 SWITCH, FREEZESTAT COMP 2 S84 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 2 S149 SWITCH, OVERFLOW T1 TRANSFORMER, CONTROL J261 JACK, SMOKE DETECTOR JUMPER K1,−1 CONTACTOR, COMPRESSOR 1 K2,−1 CONTACTOR, COMPRESSOR 2 K3, −1 CONTACTOR, BLOWER K10,−1,2 RELAY, OUTDOOR FAN K65−1,2 3 2 1 B4 3 2 RELAY, EXHAUST FAN K220, −1 RELAY, OVERFLOW DELAY 1 B5 DENOTES OPTIONAL COMPONENTS LINE VOLTAGE FIELD INSTALLED P2 JACK, HEAT P18 PLUG, EXHAUST FAN COMPT P24 PLUG, EXHAUST FAN P35 JACK, TEST P36 PLUG, TEST COOL COOLING REV. 0.0 Lennox Commercial Page 36 KCA092/150 Sequence of Operation Power: the thermostat. G energizes blower. 24VAC is routed through TB1 passing N.C. freezestat S49 and optional N.C. high pressure switch S4. Compressor contactor K1 is energized. N.O. contacts K1 close energizing compressor B1. 1− Line voltage from unit disconnect energizes transformer T1. T1 provides 24VAC power to terminal strip TB1. TB1 provides 24VAC to the unit cooling, heating and blower controls. Blower Operation: 2− Indoor thermostat terminal G energizes blower contactor K3 with 24VAC. N.O. K3 closes, energizing blower B3. 6− Optional N.O. low ambient switch S11 closes to energize condenser fan relay K10. N.O. contacts K10−1 and K10−2 close energizing condenser fans B4 and B5. N.C. contacts K10−1 open de−energizing crankcase heaters HR1 and HR2. 2nd Stage Cooling (compressor B2 is energized) Economizer Operation: 3− The economizer control module receives a demand and energizes exhaust fan relay K65 with 24VAC at 50% outside air damper open (adjustable). 4− N.O. K65−1 and N.O. K65−2 both close, energizing exhaust fan motor B10. 1st Stage Cooling (compressor B1) 5− First stage cooling demand Y1 and G are energized by 7− 24VAC is routed through TB1 and proves N.C. freezestat S50 and optional N.C. high pressure switch S7. Compressor contactor K2 is energized. N.O. K2 contacts close energizing compressor B2. 8− Optional N.O. low ambient switch S84 closes to energizing condenser fan relay K10. N.O. contacts K10−1 and K10−2 close energizing condenser fans B4 and B5. N.C. contacts K10−1 open de−energizing crankcase heaters HR1 and HR2. Page 37 ELECTRONIC OR ELECTROMECHANICAL THERMOSTAT 24V POWER ECONOMIZER BLOWER(G) HEAT 1(W1) HEAT 2(W2) COOL 1(Y1) COOL 2(Y2) k65 A B 24V COMMON 24V POWER COOL 1 (Y1) KEY A2 A63 CMC3 J3 K65 P3 R1 RT2 TB1 DESCRIPTION COMPONENT SENSOR, ELECTRONIC THERMOSTAT SENSOR, CO2 CLOCK, TIME JACK, UNIT ECONOMIZER RELAY, EXHAUST FAN PLUG, ECONOMIZER BYPASS SENSOR, MIXED AIR OR SUPPLY AIR SENSOR, REMOTE THERMOSTAT TERMINAL STRIP, CLASS II VOLTAGE COOL 2 (Y2) 24V COMMON CONNECTION SCHEME FOR KCA, KGA AND KHA 092 THROUGH 150 UNITS WITHOUT ECONOMIZER ONLY REMOVEP3 WHEN ECONOMIZERIS USED, ONLY ON KCA, KGA AND KHA 180 THROUGH 300 UNITS. ACCESSORIES TOUCHSCREEN THERMOSTAT REV. 2.0 Lennox Commercial POWER: 1− Terminal strip TB1 energizes thermostat components with 24VAC. OPERATION: 2− TB1 receives data from the electronic thermostat A2 (Y1, Y2, W1, W2, G, OCP). The 24VAC signal from TB1 energizes the appropriate components for heat or cool demand. Page 38 ECONOMIZER SEQUENCE OF OPERATION POWER: 1− Terminal strip TB1 energizes the economizer components with 24VAC. OPERATION: 2− Enthalpy sensor A7 and A62 (if differential enthalpy is used) communicates to the economizer control module A6 when to power the damper motor B7. 3− Economizer control module A6 supplies B7 with 0 − 10 VDC to control the positioning of economizer. 4− The damper actuator provides 2 to 10 VDC position feedback. Page 39 EHA−7.5, 15, 22.5, 30, 45 & 60kW Y VOLTAGE KCA SERIES UNITS 5 5 6 9 1 4 11 7 10 Page 40 3 11 EHA−7.5, 15, 22.5, 30, 45 & 60kW G, J VOLTAGE KCA SERIES UNITS P2 2 DESCRIPTION KEY COMPONENT DL2 DELAY−ELECTRIC HEAT F3 FUSE−ELECTRIC HEAT F4 FUSE−UNIT F42 FUSE−ELECTRIC HEAT 2 7 4 1 7 6 1 5 K9−1 HE1 ELEMENT−ELECTRIC HEAT 1 HE2 ELEMENT−ELECTRIC HEAT 2 HE3 ELEMENT−ELECTRIC HEAT 3 HE4 ELEMENT−ELECTRIC HEAT 4 J7 JACK−ELECT HT SUB−BUS KIT K9,−1 RELAY−HEAT K15,−1 CONTACTOR−ELECTRIC HT 1 K16,−1 CONTACTOR−ELECTRIC HT 2 P2 PLUG−HEAT P7 PLUG−ELECT HT SUB−BASE KIT S15 SWITCH LIMIT, PRIMARY, ELECT HT S19 J7 P7 7 9 8 8 6 5 B S19 THERMOSTAT−ELECTRIC HEAT LIMIT S20 SWITCH−LIMIT, SECONDARY ELECT HT S157 SWITCH LIMIT, SECONDARY ELECT HT 2 S158 SWITCH LIMIT, SECONDARY ELECT HT 3 S159 SWITCH LIMIT, SECONDARY ELECT HT 4 TB2 TERMINAL STRIP−UNIT TB3 TERMINAL STRIP−ELECTRIC HEAT 3 A 9 5 6 9 A A B B 4 3 11 1 F42 L1 L2 L3 T1 T2 T3 T1 T2 T3 S159 L3 S158 L2 S157 4 L1 7 11 10 HEATING−ELETRIC REV. 0.0 Lennox Commercial Page 41 Sequence of Operation −EHA 7.5, 15, 22.5, 30, 45, 60 kW − Y and G, J, M NOTE: This sequence of operation is for all Electric Heat kW ratings Y through J voltages. Each step of operation is numbered and can be followed in sequence on the diagrams. Operation for G, J, and M voltages will be the same. HEATING ELEMENTS: SECOND STAGE HEAT: 2− Heating demand initiates at W1 in thermostat. 3− 24VAC W2 signal is routed through from the thermostat to TB1. After S15 N.C. primary limit and S20 secondary limit is proved, the electric heat contactor K15 is energized. 1− Terminal Strip TB3 is energized when the unit disconnect closes. TB3 supplies line voltage to electric heat elements HE1 through HE7. Each element is protected by fuse F3. Page 42
advertisement
Key Features
- Standard cooling efficiency
- Optional auxiliary electric heat
- Factory or field installed
- Single or multiple stages
- 7.5kW through 60kW heat sections
- Energy management thermostat control systems
- Factory or field provided control options
- Removable unit panels
- Color coded wiring
Frequently Answers and Questions
What is the purpose of the KCA packaged cooling units?
The KCA packaged cooling units provide cooling and optional heating for commercial or industrial applications.
What are the different sizes available for the KCA units?
The KCA units are available in 7.5, 8.5, 10, and 12.5 ton models.
How does the electric heat system work in the KCA units?
The electric heat system can operate in single or multiple stages, depending on the kW input size. The heat sections range from 7.5kW to 60kW.
What types of thermostat control systems can the KCA units accept?
The KCA units are designed to accept various energy management thermostat control systems.
Where is the control box located in the KCA units?
The control box is located in the upper portion of the compressor compartment.