Inventor EVO-12 Service manual

Inventor EVO-12 Service manual

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Inventor EVO-12 Service manual | Manualzz
Table of Contents
Summary and features ..................................................................... 1
Part 1 1.Safety Precautions............ .................................................2
Part 2 SPECIFICATIONS...................................................................3
2.1
2.2
2.3
2.4
2.5
Unit Specifications...........
.................................................................................. 3
Operation Characteristic Curve............................................................... 7
CapacityVariationRatio AccordingtoTemperature ................................... 7
Operation Date........................................................................................ 8
Noise criteria curve tables for both models ............................................. 8
Part 3 Construction Views...............................................................9
3.1 Indoor Unit ................................................................... ...........................9
3.2 Outdoor Unit ............................................................................................9
Part 4 Refrigerant System Diagram...............................................10
Part 5 Schematic Diagram..............................................................11
5.1 ELECTRICAL DATA..................................................... ..........................11
5.2 Electrical wiring ......................................................................................11
5.3 Printed Circuit Board ..............................................................................13
Part 4
Function and Control...........................................................18
6.1 Remote Control Operations.....................................................................18
6.2 Changing batteries and notices ...............................................................21
6.3 Unit indlcation section ..............................................................................21
6.4 Unit ON/OFF button .................................................................................21
6.5 DESCRIPTION OF EACH CONTROL OPERATION ...............................22
of Temperature Sensor
6.6 Error Detection .........................................................................................24
6.7 Frequency Control ...................................................................................24
6.8 3-minutes Standby ...................................................................................24
6.9 Compressor Protection Function .............................................................24
6.10 Discharge Pipe Control ..........................................................................25
6.11 Input Current Control .............................................................................25
6.12 Freeze-up Protection Control .................................................................25
Table of Contents
6.13 Heating Peak-cut Control ......................................................................26
6.14 Defrost Control ......................................................................................26
6.15 Fan Control ...........................................................................................27
Part 7 INSTALLATION MANUAL.....................................................28
7.1
7.2
7.3
7.4
Tools Required for Installation ................................................................28
Installation Position Selection ..................................................................26
INSTALLATION OF INDOOR UNIT .........................................................26
INSTALLATION OF OUTDOOR UNIT .....................................................32
7.5 Test Operation ..........................................................................................33
Part 8 EXPLODED VIEWS AND PARTS LIST....................................34
8.1 Exploded View ............................................................ ...........................3 4
8.2 Parts Listt ................................................................................................3 7
Part 9 TROUBLESHOOTING.............................................................40
9.1 Precautions before Performing Inspection or Repair..............................40
9.2 Confirmation ............................................................................................40
9.3 Judgement by Flashing LED of Indoor/Outdoor Unit ...............................40
9.4 How to Check simply the main part ..........................................................42
9.5 2-way, 3-way Valve Appearance ..............................................................46
Part 10
Removal Procedure........ ...................................................53
10.1 Removal Procedure of Indoor Unit........................................................53
10.2 Removal Procedure of Outdoor Unit .....................................................67
Safety Precautions
1.Safety Precautions
Important!
or rubbish.
The unit should be installed according to the instructions
This air conditioning system meets strict safety and
operating standards. As the installer or service person,
in order to minimize the risk of damage from earthquakes,
typhoons or strong winds.
it is an important part of your job to install or service the
system so it operates safely and efficiently.
When the refrigerant touches the fire elc., it was decomposed
and a poisonous gas is generated.
To prevent injury to the user or other people and
Use only the specified refrigerant to charge the regrigerant
circuit.
property damage, the following instructions must
Do not mix it with any other refrigerant and do not allow air to
remain in the circuit.
be followed.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
About the pictograms:
Warning
Erroneous handing gives a high possibility to induce serious results such as
death or heavy injury.
Caution
Erroneous handing may induce serious
injury depending on the situation.
Warning
All electric work must be performed by licensed technician,according to local regulations and the instructions given in this
manual.
Air enclosed in the circuit can cause high pressure resulting
in a rupture and other hazards.
After completing installation work, make sure that refrigerant gas has not leaked.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance.
Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that
no metal scraps or bits of wiring have been left inside the unit
being serviced.
The unit must be properly earth connected.
Caution
Do not supply power to the unit until all wiring and tubing
Never indtall on the place where a combustible gas might
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
leak. The gas may ignite or explode when the gas leaks and
collects in surround of the unit.
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inad-
When the unit is installed at telecommunication centers or
hospitals, take a proper provision against noise.
equate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
When installing at a watery place, provide an electric leak
breaker.
Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
Do not wash the unit with water.
Be very careful about unit transportation.The unit shoukd not
There is risk of fire, electric shock, explosion, or injury.
be carried by only one person if it is more than 20kg. It occasionally causes the damage of th unit and health to be impaired.
Ask your dealer or specialized subcontractor for installation or
repair work.
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. The outdoor unit shoukd be installed in a
location where air and noise emitted by the unit will not
disturb the neighbours.
Properly insulate any tubing run inside a room to prevent
"sweating" that can cause dripping and water damage to
walls and floors.
The outdoor unit must be installed on stable, level surface,
in a place where there is no accumulation of snow, leaves
2
Do not touch the heat exchanger fins whth your bear hands.
Doing so may cut your hands.
Do not touch the compressor or refrigerant piping whithout
wearing glove on your hands. Touching directly such part can
cause a burn or frostbite as it becomes high or low temperature
according to the refrigerant state.
Do not operate the air conditioner without the air filter set
place. Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Specifications
2.SPECIFICATIONS
2.1 Unit Specifications
Models CEVI-09/CEVO-09, EVI-09/EVO-09
Model
Function
Rated Voltage
High
Frequency
(Inverter different Compressor Standard
Low
speed)
High
Total Capacity
(Inverter different Compressor Standard
Low
speed)
High
Power Input
(Inverter different Compressor Standard
Low
speed)
Rated Input
Rated Current
Air Flow Volume
H
M
L
Dehumidifying Volume
EER / C.O.P
Energy Class
Indoor unit
Fan Motor
Speed
H
M
L
Output
Capacitor
RLA
Type-Piece
Diameter-Length
Fan
CEVI-09/CEVO-09
COOLING
220-240V̚
78
53
15
3230 / 11000
2650 / 9000
450 / 1500
1350
800
200
1420
6.3
520
370
EVI-09/EVO-09
COOLING
HEATING
220-240V̚
78
98
53
72
15
24
3230 / 11000
4100 / 14000
2650 / 9000
3520 / 12000
450 / 1500
450 / 1500
1350
1450
800
950
200
200
1420
1550
6.3
6.8
520
370
280
280
mm
mm
0.8
3.3
A/A
CEVI-09
1100
900
700
10
1.2
0.16
Cross flow fan - 1
92X594
Aluminum fin-copper tube
7
2-1.4
0.8
3.3/3.7
A/A
EVI-09
1100
900
700
10
1.2
0.16
Cross flow fan – 1
92X594
Aluminum fin-copper tube
7
2-1.4
mm
610X294X24
610×294×24
W
A
dB (A)
dB (A)
dB (A)
dB (A)
dB (A)
dB (A)
mm
mm
kg
MP24BA
1.5
PCB 3.15A
38
30
24
48
40
34
770x283x201
844x342x261
8/11
MP24BA
1.5
PCB 3.15A
38
30
24
48
40
34
770×283×201
844×342×261
8/11
Hz
Hz
Hz
W / Btu/h
W / Btu/h
W / Btu/h
W
W
W
W
A
m 3/h
m 3/h
m 3/h
l/h
W/W
r/min
r/min
r/min
W
F
A
mm
Evaporator
Pipe Diameter
Row-Fin Gap
Coil length (l)×height (H)×
coil width (L)
Model
Output
Swing
Motor
Fuse (A)
Sound Pressure Level
Sound Power Level
Dimension (W×H×D) ( mm)
Dimension of Package (L×W×H)
Net Weight /Gross Weight
H
M
L
H
M
L
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
3
Specifications
CEVO-09
Outdoor Unit
Manufacturer/trademark
Model
Type
Compress
L.R.A. (A)
or
RLA(A)
Power Input(W)
A
DIT/daikin
1YC23AEXD
Rotary type
Rotary type
4
4
A
4
4
600W
600W
Overload Protector
Starting Method
ć
CS-7SA
CS-7SA
Capillary
Capillary
Transducer starting
Transducer starting
5~43
-7~43
Aluminum fin-copper tube
Aluminum fin-copper tube
7
7
Coil
Heat
Exchanger Pipe Diameter
Coil
Rows-Fin Gap
mm
mm
1-1.4
1-1.4
Coil length (l) x height (H) x coil width (L)
mm
647X528X19.05
647X528X19.05
rpm
930
930
W
30
30
A
0.236
0.236
F
2
2
Speed
Fan Motor
Output of Fan Motor
RLA
Capacitor
Air Flow Volume of Outdoor Unit
Fan
3
m /h
Type-Piece
Diameter
mm
1600
1600
Axial fan -1
Axial fan -1
370
370
Auto defrost
Auto defrost
T1
T1
I
I
IP24
IP24
Mpa
3.8
3.8
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side
Permissible Excessive Operating
Pressure for the Suction Side
Sound Pressure Level
Mpa
1.2
1.2
dB (A)
51
51
Sound Power Level
dB (A)
61
61
Dimension (W×H×D)
mm
658x550x275
658x550x275
Dimension of Package (L×W×H)
mm
771x348x592
771x348x592
Net Weight /Gross Weight
Refrigerant
kg
Name of refrigerant
Weight
Length (m)
Connection Gas additional charge
Pipe
Liquid Pipe Diameter
Gas Pipe Diameter
4
DIT/daikin
1YC23AEXD
W
Throttling Method
Working Temp Range
EVO-09
kg
m
27/31
28/32
R410A
R410A
0.74
0.74
5
5
g/m
20
20
mm
ž6(1/4”)
mm
ž6(1/4”)
ž9.52(3/8”)
Max. Interunit Height Difference
m
ž9.52(3/8”)
5
Max. Interunit Piping Length
m
15
5
15
Specifications
Models CEVI-12/CEVO-12, EVO-13/CEVO-12
Model
Function
Rated Voltage
High
Frequency
(Inverter different Compressor Standard
Low
speed)
High
Total Capacity
(Inverter different Compressor Standard
Low
speed)
High
Power Input
(Inverter different Compressor Standard
Low
speed)
Rated Input
Rated Current
Air Flow Volume
H
M
L
Dehumidifying Volume
EER / C.O.P
Energy Class
Indoor unit
Fan Motor
Speed
H
M
L
Output
Capacitor
RLA
Type-Piece
Diameter-Length
Fan
Hz
Hz
Hz
W / Btu/h
W / Btu/h
W / Btu/h
W
W
W
W
A
m 3/h
m 3/h
m 3/h
l/h
W/W
Swing
Motor
Fuse (A)
Sound Pressure Level
300
mm
mm
1.5
3.21
A/A
CEVI-12
1150
950
750
10
1.2
0.16
Cross flow fan - 1
92X594
Aluminum fin-copper tube
7
2-1.4
1.5
3.21/3.61
A/A
EVI-12
1150
950
750
10
1.2
0.16
Cross flow fan – 1
92X594
Aluminum fin-copper tube
7
2-1.4
mm
610X294X24
610×294×24
W
A
dB (A)
dB (A)
dB (A)
dB (A)
dB (A)
dB (A)
mm
mm
kg
MP24BA
1.5
PCB 3.15A
39
31
25
49
41
35
770x283x201
844x342x261
9/12
MP24BA
1.5
PCB 3.15A
39
31
25
49
41
35
770×283×201
844×342×261
9/12
r/min
r/min
r/min
W
F
A
mm
Sound Power Level
Dimension (W×H×D) ( mm)
Dimension of Package (L×W×H)
Net Weight /Gross Weight
H
M
L
H
M
L
EVO-12/CEVO-12
COOLING
HEATING
220-240V̚
92
108
72
78
15
24
3960 / 13500
5130 / 17500
3530 / 12000
4100 / 13990
600 / 2000
600 / 2000
1450
1550
1100
1135
220
220
1550
1650
6.5
7.8
560
410
300
Evaporator
Pipe Diameter
Row-Fin Gap
Coil length (l)×height (H)×
coil width (L)
Model
Output
CEVI-12/CEVO-12
COOLING
220-240V̚
92
72
15
3960 / 13500
3530 / 12000
600 / 2000
1450
1100
220
1550
6.5
560
410
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
5
Specifications
Outdoor Unit
CEVO-12
DIT/daikin
Manufacturer/trademark
Model
Power Input(W)
1YC23AEXD
Rotary type
Rotary type
A
4
4
A
4
4
W
Overload Protector
Throttling Method
Starting Method
Working Temp Range
ć
Coil
Heat
Exchanger Pipe Diameter
Coil
Rows-Fin Gap
Coil length (l) x height (H) x coil width (L)
Speed
Fan Motor
600W
CS-7SA
Capillary
Capillary
Transducer starting
Transducer starting
5~43
-7~43
Aluminum fin-copper tube
Aluminum fin-copper tube
mm
7
7
mm
2-1.4
2-1.4
mm
647X528X38.1
647X528X38.1
rpm
930
930
W
30
30
RLA
A
0.236
0.236
Capacitor
F
2
2
m 3/h
1600
1600
Axial fan -1
Axial fan -1
370
370
Auto defrost
Auto defrost
T1
T1
Type-Piece
Diameter
mm
Defrosting Method
Climate Type
Isolation
Moisture Protection
Permissible Excessive Operating
Pressure for the Discharge Side
Permissible Excessive Operating
Pressure for the Suction Side
Sound Pressure Level
Sound Power Level
I
I
IP24
IP24
Mpa
3.8
3.8
Mpa
1.2
1.2
dB (A)
53
53
dB (A)
63
63
Dimension (W×H×D)
mm
658x550x275
658x550x275
Dimension of Package (L×W×H)
mm
771x348x592
771x348x592
kg
29/33
30/34
Net Weight /Gross Weight
Refrigerant
R410A
R410A
kg
m
1.0
1.0
5
5
g/m
20
20
Name of refrigerant
Weight
Length (m)
Connection Gas additional charge
Pipe
Liquid Pipe Diameter
Gas Pipe Diameter
6
600W
CS-7SA
Output of Fan Motor
Air Flow Volume of Outdoor Unit
Fan
DIT/daikin
1YC23AEXD
Type
Compress
L.R.A. (A)
or
RLA(A)
EVO-12
mm
ž6(1/4”)
ž6(1/4”)
mm
ž9.52(3/8”)
5
15
Max. Interunit Height Difference
m
ž9.52(3/8”)
5
Max. Interunit Piping Length
m
15
Specifications
2.2 Operation Characteristic Curve
Cooling
Heating
8
10
9
7
8
6
7
5
Current(A)
Current(A)
6
5
4
3
Condition
Indoor:DB 27ć WB19ć
Indoor air flow: Super High
Pipe length:5m
Voltage:230V
2
4
3
Condition
Indoor:DB 20ć
Indoor air flow: Super High
Pipe length:5m
Voltage:230V
2
1
1
0
0
0
20
40
60
80
100
0
120
20
Compressor Speed(rps)
40
60
80
100
120
Compressor Speed(rps)
2.3CapacityVariationRatioAccordingtoTemperature
Heating
110
120
100
100
90
80
Capacity ratio(%)
Capacity ratio(%)
Cooling
80
70
60
Condition
Indoor:DB27℃ WB19℃
Indoor air flow: Super High
Pipe length:5m
50
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor temp. (°C)
60
40
Condition
Indoor:DB20℃
Indoor air flow: Super High
Pipe length:5m
20
0
-15
-10
-5
0
5
10
Outdoor temp. (°C)
7
Specifications
2.4 Operation Date
Cooling
Temp. Condition(ć)
Indoor
Outdoor
27/19
35/24
Model
Standard
Pressure(Mpa)
09K
0.9 to 1.1
12K
0.8 to 1.0
Indoor Fan
Mode
Outdoor
Fan Mode
Super High
930rpm
Compressor
Revolution(rps)
53
72
Heating
Temp. Condition(ᲇ)
Indoor
Outdoor
20/-
Model
Standard
Pressure(Mpa)
09K
2.3 to 2.5
12K
2.4 to 2.6
7/6
Indoor Fan
Mode
Outdoor
Fan Mode
Super High
930rpm
Compressor
Revolution(rps)
72
78
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U
bent. (Thermistor themometer)
(2) Connecting piping condition : 5 m
2.5 Noise criteria curve tables for both models
54
Indoor side noise when blowing
52
40
Heating
50
Noise dB(A)
12K
30
09K
48
46
Cooling
44
42
20
Low
Middle
Indoor fan motor rotating speed
High
40
20
30
40
50
60
70
Compressor frequency(Hz)
8
80
Constrction views
3. Construction Views
3.1 Indoor Unit
770
283
201
770
548.5
258.5
283
126.5
3.2 Outdoor Unit
274
551
658
317
299
708
470
9
Refrigerant System Diagram
4. Refrigerant System Diagram
(1)Cooling Only Models
INDOOR UNIT
OUTDOOR UNIT
GAS SIDE
3-WAY VALVE
Muffler
Discharge
HEAT
EXCHANGE
(EVAPORATOR)
Suction
Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
2-WAY VALVE
Strainer
Capillary
Strainer
COOLING
(2)Cooling & Heating Models
INDOOR UNIT
OUTDOOR UNIT
GAS SIDE
3-WAY VALVE
4-Way valve
Muffler
Discharge
HEAT
EXCHANGE
(EVAPORATOR)
Suction
Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
3-WAY VALVE
Strainer
Capillary
Strainer
COOLING
HEATING
Refrigerant pipe diameter
Liquid : 1/4" (6 mm)
Gas : 3/8" (9.52 mm)
10
Schematic Diagram
5. Schematic Diagram
5.1 ELECTRICAL DATA
Indoor Unit
Symbol
Color symbol
Symbol
Color symbol
WH
WHITE
BN
BROWN
YE
YELLOW
BL
BLUE
RD
RED
BK
BLACK
YEGN
YELLOW GREEN
PROTECTIVE EARTH
Outdoor Unit
Symbol
Parts name
Symbol
Color symbol
L1
REACROR
WH
WHITE
PCB1~PCB2
PRINTED CIRCUIT BOARD
YE
YELLOW
S10/S11S40/S70/S80/S90
CONNECTOR
RD
RED
SAT
OVERLOAD
BN
BROWN
COMP
COMPRESSOR
BL
BLUE
PROTECTIVE EARTH
BLACK
YELLOW GREEN
BK
YEGN
5.2 Electrical wiring
Indoor Unit
TUBE
TEM.SENSOR
ROOM
TEM.SENSOR
FAN
MOTOR
POWER
M1
0
RT2
BN
BU
YEGN
0
RT1
TUBE
ROOM
PG
PGF
AP2
N
COM-OUT
L-OUT
DISP1 DISP2 SWING-UD
HEALTH-L
HEALTH-N
XT
BU
N(1)
BK
2
3
BN
BU
BK
BN
YEGN
YEGN
OUTDOOR UNIT
AC-L
L
N
PE
EVAPORATOR
M2
AP1
DISPLAY
SWING
MOTOR
COOL PLASMA
GENERATOR
NOTE:The parts with broken line is applicable
to the models with cold-plasma function.
11
Schematic Diagram
Outdoor Unit
Models CEVI-09/CEVO-09 ,EVO-12/CEVO-12
L1
EXHAUST
OUTTUBE OUTROOM
TEM.SENSOR TEM.SENSOR TEM.SENSOR
RT3
0
OG
RT5
0
RT4
0
OG
HA1
S90
PCB2
HA2
BU
E1
PCB1
E2
BN
YEGN
YEGN
YEGN
YEGN
PE
YEGN
WH WH
PE
YEGN
PE
CLAPBOARD
SUB-ASSY
M
W
ELECTRICAL BOX
WARNING
FAN
PE MOTOR
SAT
PE
HN2
BK
2
3
BN
AC1
BU
N(1)
BK
S
HL2
BU
RD YE BU
X1
RD YE BU
V
BN
HN3
U V W
COMP.
S11
HL3
S70
S40
YEGN U
AC2
S10
XT
BU
INDOOR UNIT
HR1
HR2
Please don't touch any terminal when the voltage of
terminal DC+ and DC- at PCB2 is higher than 30V to
prevent the risk of electrical shock!
Models EVI-09/EVO-09 ,EVO-12/CEVO-12
EXHAUST
OUTTUBE OUTROOM
TEM.SENSOR TEM.SENSOR TEM.SENSOR
RT3
0
L1
4YV
OG
OG
RT5
0
RT4
0
HR1
S90
HA1
S80
BU
S70
S40
U V W
12
V
HL2
PE
W
SAT
M
FAN
PE MOTOR
CLAPBOARD
SUB-ASSY
E1
PCB1
YEGN
2
3
BN
AC1
E2
BK
BN
YEGN
YEGN
YEGN
BU
N(1)
BK
S
HN2
HN3
WH WH
YEGN
COMP.
HL3
BN
BU
RD YE BU
X1
RD YE BU
PE
S11
PCB2
HA2
YEGN U
AC2
S10
XT
BU
YEGN
PE
PE
ELECTRICAL BOX
WARNING
Please don't touch any terminal when the voltage of
terminal DC+ and DC- at PCB2 is higher than 30V to
prevent the risk of electrical shock!
INDOOR UNIT
HR2
Schematic Diagram
5.3 Printed Circuit Board
TOP VIEW
BOTTOM VIEW
13
Schematic Diagram
]HUROLQH
FRPPXQLFDWLRQ
ZLUH
ZLUHXQGHU
YROWDJH
ground
wire
GLVSDO\
ERDUG
LQIUDUHG
UHFHLYHU
14
Schematic Diagram
TOP VIEW
BOTTOM VIEW
15
Schematic Diagram
FRONT VIEW
BOTTOM VIEW
16
Schematic Diagram
TOP VIEW
BOTTOM VIEW
17
Function and Control
6. Function and Control
6.1 Remote Control Operations
Note: Be sure that there are no obstructions between receiver and remote control; Don't drop
or throw the remote control; Don't let any liquid in the remote control and put the remote control
directly under the sunlight or any place where is very hot.
(ˇ/ˉ)
Signal transmitter
●
FAN
(ˇ/ˉ) button
When press +button , the setting temp. will be
increased by 1ć ,When press -button,the
setting temp. will be decreased by 1 ć
The temp. will be changed quickly by pressing
AUTO
OPER
AIR HEALTH BLOW
HUMIDITY
the button continuously and setting temp. range
is ̚ćDŽ
FILTER
TURBO
TEMP.
HOUR
ON/OFF
FAN
ON/OFF
Remote control
MODE
●
FAN speed button
Press this button once, fan speed will change
as below:
Auto
Low speed
Middle speed
FAN
ON/OFF
BLOW
TEMP
TIMER
TURBO
SLEEP
LIGHT
High speed
Note:Under the Dry mode, the fan speed isn't
adjustable, low fan speed is imperative,
but when operating this button, the wireless
remote control will send this signal.
Swing up and down button
ON/OFF button
Simpleness swing mode is defaulted for wireless
remote control, in this mode, press this button,
● Press this button, the unit will be started or stopped,
could turn on or turn off the Up and down
which can clear the timer or sleeping function of
swing function.
last time.
●
When unit is turned off, synchronously press
"+" and Up and down swing buttons, it could
MODE
Mode button
be switched between the simpleness swing
● Press this button, the running mode will change as
mode and stationary swing mode, at this time,
below.
blinks 2 seconds.
●
●
In Stationary swing mode, press this button,the
angle for Up and down swing as show in below:
●
When up and down swing louver is working,
when turn off the unit, the siwng louver will
immediately stop at current position.
AUTO
COOL
DRY
FAN
HEAT (Note:no for coolling
only unit)
18
shows up and down swing louver swings back
and forth as show in the above figure.
Function and Control
FAN
AUTO
OPER
AIR HEALTH BLOW
HUMIDITY
TIMER
●
FILTER
TURBO
HOUR
ON/OFF
ON/OFF
Remote control
HEALTH SAVE
●
●
MODE
FAN
BLOW
TEMP
TIMER
TURBO
SLEEP
LIGHT
HEALTH SAVE button
HEALTH function:there is no this function
for this unit. If press this key, the main unit
will click, but it also runs under original status.
Save energy function: this unit has no this
function, press this button, the mian unit will
click, "SE" will be displayed on the LCD of
wireless remote control, fan speed automatically
rotates, when repress this button, the fan speed
will run at previous setting fan speed.
TURBO
●
Turbo button
Set turbo on or off(the characters of turbo
will appear or disappear ) by pressing this
key under cooling or heating mode.Once
energized, the unit will be defaulted to be
turbo off. This function can not be set under
auto, dehumidify or fan mode, and characters
On the status of the unit on, press this
button to set timer off. On the status of
the unit off, press this button to set timer
off. Press this key once, words Hour on(off)
will appear and flicker. In which case, press
+/- button to adjust time (press+/- button
continuously to change timing value quickly
the setting time range is from 0.5 to 24 hr.;
press this key once again to fix the time,
then remote controller will send out the signal
immediately and hour on/off will stop flickering.
If the time of that no press timer button
under flickering status is above 5s,the timer
setting will quit. If the timer has been set,
press this button once again to quit it.
TEMP
●
Timer button
Temp. display button
After powered on, displaying presetting
temperature is defaulted,(According to
customer requirements to display,if there
are no requirements,the presetting temperature displaying is defaulted, there is
no signal display on the remote control).
Press this button, (display
), display
the presetting temperature; (display
),
display indoor ambient temperature,
(display
), display ambient temperature,
If current display status is indoor ambient temp.
when received other remote control sginal,
then will display presetting temp., 5s later
return to ambient temp. display.
Other models haven't this function. But
pressing this button, the main unit will click
and keep the original status.
of turbo won't appear.
19
Function and Control
BLOW
Blow button
●
FAN
AUTO
OPER
AIR HEALTH BLOW
HUMIDITY
FILTER
TURBO
HOUR
ON/OFF
Remote controller
ON/OFF
MODE
LIGHT
●
FAN
BLOW
TEMP
TIMER
TURBO
SLEEP
LIGHT
SLEEP
●
●
Press this button, enter into SLEEP state,
when repressed, it will quit. The sleep function
will be canceled with the stop of the unit.
There is no SLEEP function under AUTO
and FAN mode.
is the icon for sleep
function.
At COOL mode: the SLEEP mode runs after
1hour, the setting temp. will be increased
by 1ć , 2 hour later, setting temp. will be
increased by 2ć and then will run at this
setting temperature.
At HEAT mode: the SLEEP mode runs
after 1hour, the setting temp will be
decreased by 1ć, 2 hours later setting temp.
will be decreased by 2ć ,then it will run
at setting temperature.
20
Light button
Press this button to select LIGHT on or off
in the displayer. When the LIGHT on is
set,the icon
will be displayed and the
indicator light in the displayer will be on.
When the LIGHT off is set, the icon
will
be displayed and the indicator light in the
displayer will be off.
Left and right swing button
Sleep button
●
Set Blow on (the characters of Blow will
appear)or off (the characters of Blow
disappears) by pressing this key under
cool or dehumidify mode. Once energized,
the unit will be defaulted to be Blow off.
This function can not be set under auto,
fan or heat mode, and the characters of
Blow won't appear.
●
●
Simpleness swing mode is defaulted for
wireless remote control,in this mode,
press this button, could turn on or turn
off the Left and right swing function
When unit is turned off, synchronously
press "+" and Left and right swing buttons,
it could be switched between the simpleness
swing mode and stationary swing mode,
at this time,
blinks 2 seconds.
●
In Stationary swing mode, press this button,the
angle for Left and right swing as show in below:
●
When left and right swing louver is working,
when turn off the unit, the siwing louver will
immediately stop at current position.
shows left and right swing louver swings
back and forth as show in the above figure.
Function and Control
6.2 Changing batteries and notices
Slightly to press the place with
1. , along the arrowhead direction to push the back cover of wireless
remote control. (As show in figure)
2 Take out the old batteries. (As show in figure)
3. Insert two new AAA1.5V dry batteries, and pay attention to the polarity.
(As show in figure)
4 Attach the back cover of wireless remote control. (As show in figure)
ƾ NOTE:
ƽ When changing the batteries, do not use the old or different batteries,
otherwise, it can cause the malfunction of the wireless remote control.
ƽ If the wireless remote control will not be used for a long time, please
take them out, and don't let the leakage liquid damage the wireless
remote control.
ƽ The operation should be in its receiving range.
ƽ It should be placed at where is 1m away from the TV set or stereo sound sets.
ƽ If the wireless remote control can not operate normally, please take them out,
after 30s later and reinsert, if they cannot normally run, please change them.
Sketch map for
changing batteries
6.3 Unit indlcation section
1.When the unit is energized, all the display marks will be shown and
only the power LED lights.
2.When the unit is turned on remotely, the power LED goes out while
the current setting running mode is displayed. 3.During defrosting, "H1" is displayed in "dual 8".
4.In normal situation, the setting temperature is displayed in "dual 8
" place.
5.When the signal of displaying indoor temperature or outdo or
temperature is received from the controller, the corresponding
temperature will be shown in "dual 8" place. It resumes displaying
setting temperature 5s later.
COOL light (blue)
DRY light (green)
RUN light (red)
HEAT light (orange)
ON/OFF
Unit ON/OFF button
6.4 Unit ON/OFF button
If the wireless remote control is lost or broken, please use the manual switch button. At this time, the unit will run at the
Auto mode, but the temperature and fan speed cannot be changed. The operation was shown as below:
To open the panel, the manual switch is on the displayer box.
Turn on the unit: At unit turned off, press the button,the unit will run at Auto mode immediately.The microcomputer will accord to
the indoor temperature to select (Cooling, Heating, Fan) and obtain the comfortable effect.
Turn off the unit: At unit turned on, press the button, the unit will stop working.
Operation of automatic buttons:
N H H S a V N H H S PRU HWK DQ V
OH VVWKDQ V RSHUDWLRQ
GXULQJVWRS
RSHUDWLRQ
GXULQJUXQQLQJ
RSHUDWLRQGXULQJVWRS
࡮VWDUWUXQQLQ
࡮ VWRSUXQQLQJ
࡮
VWDUWIRUFHUXQQLQJ
࡮VWRSUXQQLQJ
࡮ VWRSIRUFHUXQQLQJ
˄ LQFDVHRINH\FODPS˅
ˉ
DIWHUUXQQLQJDEQRUPDO
˄ F R P P X Q L F D W L R Q H U U R U˅
21
Function and Control
6.5 DESCRIPTION OF EACH CONTRO OPERATION
* Anti-cold air function
The rotational speed of indoor electromotor is decided based on the
1.When the unit is energized, all the display marks will be shown and only
the power LED lights.
2.When the unit is turned on remotely, the power LED goes out while the
current setting running mode is displayed.
3.During defrosting, "H1" is displayed in "dual 8".
4.In normal situation, the setting temperature is displayed in "dual 8" place.
5.When the signal of displaying indoor temperature or outdoor temperature
is received from the controller, the corresponding temperature will be shown
in "dual 8" place. It resumes displaying setting temperature 5s later.
indoor pipe temperature. The indoor fan can run at low speed or stop
running. This function will terminate after the unit runs for 3min or the
pipe temperature reached certain value.
During heating, if the indoor pipe temperature is lower than certain value.
The running speed of indoor fan will decrease automatically base on the
pipe temperature and ensure that the outlet air is hot.
* Residual heat blowing function
During heating, when the stopping condition for the compressor is reached,
the compressor and the outdoor fan motor stop running while the upper and
lower air deflector rotate to level L. the indoor fan will stop after running for
C
60s at setting speed.
B
A
Indoor temperature-setting temperature
1. In this mode, the fan motor runs at low fan speed while swing works
according to setting state. The range of setting temperature is 16~30 o C
(61~86¨H).
2. When outdoor malfunction or protection stoppage happen,
the indoor fan will remain the original running state and the error LED will light.
In this mode, the system selects the running mode (cooling, heating, and fan)
automatically according to the ambient temperature. The display shows the
actual running mode and setting temperature. There will be 30s delay for
mode conversion. The protection function is the same as that of other modes.
1. When T amb>=25o C, the cooling mode is selected.
2. for heat pump unit: when Tamb<=22o C, the unit runs in heating mode
3. for cooling only unit: when Tamb < 22o C, the unit runs in fan mode. .
4. When 22o C <T indoor amb< 25o C, upon initial startup, the unit will
enter auto mode and run in automatic fan mode. If the other mode
changes into auto mode, the previous running mode will remain.
1. In this mode, the indoor fan may run at high, medium, low and automatic
speed. The compressor, outdoor fan and 4-way valve all stop running.
o
2. In this mode, the range of setting temperature is 16~30 C (61~86¨H).
1. Heating mode
o
When setting temperature-indoor temperature<= -1.5 C,
the unit will stop heating. Both outdoor fan and indoor fan will stop later.
When setting temperature-indoor temperature>-1.5 oC and it lasts for a
certain period, the unit will start heating. In that case, indoor fan, outdoor fan
and compressor will start running. The indoor fan works according to the
anti-cold air.
o
* In this mode,
the range of setting temperature is 16~30 C (61~86¨H).
Cooling
operation
With no compressor capacity supplied
In auto fan speed mode, the rotational speed of the fan for indoor unit is
decided by the differential temperature between ambient temperature and
setting temperature. In dehumidifying mode, the automatic fan speed is
forced to be low.
No. of
jumper
cap
Setting temperature- indoor temperature
C
2. Protection function: in heating mode, when the compressor stops as
a result of malfunction, the indoor fan blows residual heat.
3. Defrosting control: when the defrosting signal is revived, the
defrosting mark H1 will be shown. The e-heater and indoor fan stop.
22
Cooling
operation
With compressor capacity supplied
A
B
Heating
operation
XQLW
W\SH
1
09K
2
12K
PRGH
Rotational speed
during cooling
Rotational speed
during heating
Rotational speed
during cooling
Rotational speed
during heating
Super-high
High fan
fan speed
speed
1300
1300
1350
1350
1100
1140
1150
1190
Medium
Low fan
fan speed
speed
900
980
950
1020
700
820
750
850
Function and Control
Timer off: the timer off function can be set when the unit is on. When the
After energization, the motor of upper and lower swing will enable the air
deflector to be open and then be close completely. And the air outlet is close.
In heating mode, if the swing function is not set, the upper and lower air
deflector will rotate to maximum in clockwise direction. Then it will rotate
to place D. Under other state, the upper and lower air deflector will rotate to
level L. If the swing function is set when starting the unit, the air deflector
will swing between place L and D. there are 7 states for air deflector: in
Place L, Place A, Place B, Place C, Place D, and swing between Place L and
place D, stop in any place between Place L and place D. When the unit is
turned off, the air deflector will stay in place 0. The swing is available only
when the swing function is set and the indoor fan is running.
Note: When place L to B, place A to C, and place B and D is set, the air
deflector will swing between place L to D.
setting time for timer off is reached, the unit will stop. The timing interval is
0.5hour, and the setting range is 0.5~24hours.
Clock (start and stop time can be set. The accuracy is minute. E.g.: timer
on at 8:00a.m.; timer off at 17:30p.m.)
Timer on: if the timer on function is set when the system is on, the system
will go on running. If the timer on function is set when the system is off, the
system will start running in the previously set mode when the setting time is
reached.
Timer off: if the timer off function is set when the system is off, the system
will keep off even though the setting time is reached. If t he timer off
function is set when the system is on, the system will stop running when the
setting time is reached.
Timer modification: when the system is under timer state, start or stop of the
unit can be set via remote ON/OFF button and the timer can be reset. The
system runs according to the latest setting state.
When both the timer on and timer off are set: the system runs according to
the current setting state. When the setting time is reached, the unit will start
and stop running. In that case, the unit will run according to the previously
setting mode when the setting time for timer on is reached. The unit will stop
O(0°)
running while the setting time for timer off is reached.
If the setting time for timer on and timer off is the same, the unit will stop
running no matter what the current state is.
L
A
B
C
D
Memory: mode, up and down swing, light, setting temperature, setting fan
speed, general timer (not clock), Fahrenheit / Celsius. After de-energized,
the unit can run according to the memory if it is energized again. If the timer
function is not set in the last remote control, the system will run according to
the last remote control. If the timer function is set in the last control before it
is de-energized, the system will memorize the last timer setting. The setting
time is recalculated since the energization of the unit. If the timer function is
1. It is applicable to cooling mode, dehumidifying mode and heating mode.
2. In cooling mode or dehumidifying mode, 1 hour after the sleep curve is
set, the setting temperature will rise by 1 ¡æ. 2 hours later, the setting
temperature will rise by 2 ¡æ. After that, the setting temperature will not
change any more
Set temp. Tset
set
set in the last control and the setting time is reached before the unit is
de-energized, the unit will run according to the previous running mode after
it is energized again. But the timer function will terminate. The clock will
not be memorized.
(11) Turbo function
In cooling and heating mode (not available in auto, dehumidify, fan mode),
press the Turbo button, the fan speed displayed super high speed in the
remote controller and the indoor fan rotates at super high speed.
set
(12) Health function
set
When the indoor fan motor is running, the Health function is set by pressing
1h
2h
About 2h
3. In heating mode, 1 hour after the sleep curve is set, the setting temperature
will decrease by 1 ¡æ. 2 hours later, the setting temperature will decrease by
2 ¡æ. After that, the setting temperature will not change any more.
1h
2h
About 2h
remote controller (If there is no Health button on the remote controller, the
Health function opening is defaulted).
(13) I Feel function
If the remote controller receives the I Feel order, the controller will work at
the ambient temperature value which is sent by remote controller (Except the
set
defrosting and anti-cool wind, which still adopts the sampling value of AC
set
Set temp. Tset
set
itself ambient temperature sensor), the remote controller will send ambient
temperature value to controller at intervals. If the controller hasn’t received
the ambient temperature value from the remote controller for long time, then
it will run accroding to the current ambient temperature of AC. If the
The main board has general timer function and clock function. The timer
function has not been set, the ambient temperature will adopt the sensor
function can be selected by remote controller with different function
sampling value of AC itself. If power off happens, this function will not be
(1) General timer (start and stop time can be set. The accuracy is minute.
memorized.
E.g.: timer on for 1 hour; timer off for 1.5 hours.)
Timer on: after setting timer on, the unit will run at setting time according to
the original setting mode. The timing interval is 0.5hour, and the setting
range is 0.5~24hours.
23
Function and Control
Temperature ensor malfunction detection
(1) Indoor temperature sensor
Detect malfunctions of temperature sensor any time.
(2) Indoor pipe temperature sensor In defrosting period, the temperature sensor malfunction will not be detected. 5 min after finishing defrosting, the system begins to detect the temperature
sensor malfunction. In other times, the temperature sensor malfunction will be detected.
(3) Protection of temperature sensor
1. When short-circuit occurs to the temperature sensor for 30s:
The temperature sensor overheats. In this case, the complete unit will stop for protection. At the same time, the temperature protection and temperature
sensor malfunction will be shown.
2. When break-circuit occurs to the temperature sensor for 30s:
The unit will stop and the temperature sensor malfunction will be displayed
6.7 Fre uency Control
Outline
When starting the compressor, or when conditions are varied due to the change of the room, the frequency must be initialized according
to the D value of the indoor unit and the Q value of the indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
1. P control
Calculate
D value in each sampling time (20 seconds), and adjust the frequency according to its difference from the frequency
previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency up and down according to the
D value,
obtaining the fixed D value.
When the D value is small...lower the frequency.
When the
D value is large...increase the frequency.
3. Fre uency management
hen other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lo er limit of fre uency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or quiet commands come from indoor unit, the
upper limit frequency must be lowered than the usual setting.
6.8 3-minutes Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.(except when defrosting)
6.9 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as follows. (The function must not be used when
defrosting.)
Frequency
24
FCG 3
FCG 2
88
64
FCG 1
TCG1
TCG2
48
240
360
TCG3
180
FCG3
FCG2
FCG1
TCG 1sec
TCG 2sec
TCG 3sec
Time
Function and Control
6.10 Discharge Pipe Control
Outline
The discharge pipe temperature is used as the compressor’s internal temperature. If the discharge pipe temperature rises above a
certain level, the operating frequency upper limit is set to keep this temperature from going up further.
Detail
Divide the Zone
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
thermistor
temperature
Reset zone
Management within the Zones
Zone
Control contents
Stop zone
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone
Keep zone
Return / Reset zone
Start the timer, and the frequency will be drooping.
Keep the upper limit of frequency.
Cancel the upper limit of frequency.
6.11 Input Current Control
Outline
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency which
takes priority of the lower limit of four way valve activating compensation.
Detail
The frequency control will be made within the following zones.
2 Hz drooping
1.0second after
rushing in the
drooping zone
After 2.5 seconds
Compressor stops
1
Stop zone
2
Drooping zone
Keep zone
3
Reset zone
When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor operation stops.
If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the frequency will be 2 Hz drooping.
Repeating the above drooping continues until the current rushes on the drooping zone without change.
In the keep zone, the frequency limit will remain.
In the return / reset zone, the frequency limit will be cancelled.
imitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
2. In case the operation mode is heating
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
6.12 Free e-up Protection Control
Outline
25
Function and Control
During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent
freezing of the indoor heat exchanger. (The signal from the indoor unit must be divided into the zones as the followings.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from operation start.
Control in Each one
Heat exchanger
thermistor temperature
A
Return/Reset zone
Up zone
B
Keep zone
C
Drooping zone
D
Stop zone
E
6.13 Heating Peak-cut Control
Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating frequency limitation and prevent
abnormal high pressure. (The signal from the indoor unit must be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec. from operation start.
Control in Each one
The heat exchange intermediate temperature of indoor unit controls the following.
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
thermistor temperature
Reset zone
6.14 Defrost Control
Outline
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more
than its fixed value when finishing.
Detail
Conditions for Starting Defrost
The starting conditions must be made with the outdoor air temperature and heat exchanger temperature. Under the conditions that the
system is in heating operation, 6 minutes after the compressor is started and more than 44 minutes of accumulated time pass since
the start of the operation or ending the defrosting.
Conditions for Canceling Defrost
The judgment must be made with heat exchanger temperature. (39°F~72°F)
26
Function and Control
Frequency
PI control
0Hz
60sec.
50sec.
Compressor
600sec.
50sec.
ON
OFF
Four way valve
ON
OFF
5sec.
Fan
5sec.
ON
OFF
Electronic expansion
valve opening
450pps
350pps
450pps
Initial opening
6.15 Fan Control
Outline
Fan control is carried out according to the follo ing priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control in cooling operation
5. Tap control when drooping function is working
6. Fan control in forced operation
7. Fan control in indoor/outdoor unit silent operation
8. Fan control in powerful mode
9. Fan control in normal operation
Detail
Fan OFF Control
hen Stopped
* Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Tap Control in indoor/outdoor unit silent operation
1. When Cooling Operation
When the outdoor air temperature is lower than 99°F, the fan tap must be set to L.
2. When Heating Operation
When the outdoor air temperature is higher than 39°F, the fan tap must be turned to L (only for heat pump model).
27
Installation Manual
7. INSTALLATION MANUAL
Important Notices
1. The unit installation work must be done by qualified
personnel according to the local rules and this
manual.
2. Before installating, please contact with local
7.2 Installation Position Selection
(1)The air inlet and outlet vent should be far from the obstruction,
make sure that the air can be blown through the whole room.
(2)Select a position where the condensing water can be easily
drained out, and the place is easily connected for outdoor unit.
(3)Select a location where the children can not reach.
(4)Can select the place where is strong enough to withstand the
authorized maintenance center, if unit is not installed
full weight and vibration of the unit. And will not increase the noise.
(5)Be sure to leave enough space to allow access for routine
by the authorized maintenance center, the malfunction
may not solved, due to discommodious contacts.
maintenance. The height of the installed location should be
250cm or more from the floor.
3. When removing the unit to the o.ther place, please
firstly contact with the authorized Maintenance
Center in the local area.
(6)Select a place about 1m or more away from TVset or any other
electric appliances.
Basic Requirements For Installation
Position
(7)Select a place where the filter can be easily taken out.
(8)Make sure that the indoor unit installation should accord with
installation dimension diagram requirements.
(9)Do not use the unit in the immediate surroundings of a laundry a bath a shower or a swimming pool.
Install in the following place may cause malfunction. If it is
unavoidable contact with service center please:
(1)Select a location from which noise and outflow air emitted by
* Place where strong heat sources, vapors, flammable gas or
volatile object are emitted.
unit will not inconvenience neighbors, animals, plants.
(2)Select a location where there should be sufficient ventilation.
* Place where high-frequency waves are generated by radio
equipment, welders and medical equipment.
(3)Select a location where there should be no obstructions cover
the inlet and outlet vent.
* Place where a lot of salinities such as coast exists.
* Place where the oil (machine oil) is contained in the air.
(4)The location should be able to withstand the full weight and
vibration of the outdoor unit and permit safe installation.
* Place where a sulfured gas such as the hot spring zones is
generated.
(5)Select a dry place, but do not expose under the direct sunlight
or strong wind.
* Other place with special circumstance.
(6)Make sure that the outdoor unit installation dimension should
accord with installation dimension diagram, convenient for
7.1 Tools Required for Installation
(not supplied)
1. Gauge manifold
2.Electronic balance for refrigerant charging
3. Phillips head screwdriver
4. Knife or wire stripper
5. Carpenter’s level
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Vacuum pump (For R410A)
17. Gas leakage detector
28
maintenance, repair.
(7)The height difference of connecting the tubing within 5m, the
length of connecting the tubing within 10m.
(8)Select a place where it is out of reach for the children.
(9)Select a place where will not block the passage and do not
influence the city appearance.
7.3 INSTALLATION OF INDOOR UNIT
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure
that the panel is completely level, and mark the boring points on
the wall.
2) Secure the mounting plate to the wall with screws.
Installation Manual
Recommended mounting plate retention spots and
urr removal
1.Completely remove all burrs from the cut cross section of
dimensions
Use tape measure
as shown.
Position the end of
a tape measure at.
Recommended mounting plate Place a leveler
retention spots (5 spots in all) on raised tab.
pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs
120.5
101
247
into the tubing.
241.7
241.7
203
Pipe
Reamer
41.3
41.3
54.5
160
50
330.5
160
Gas pipe end
331
Liquid pipe end
770
Throughthe-wall
hole φ65mm
Keep here the piece cut out
from the unit for piping
* The removed pipe port cover can be
kept in the mounting plate pocket.
Point down
54
Drain hose
position
Unit: mm
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Removed pipe
port cover
A
Mounting plate
Flare nut
Copper tube
• For walls containing metal frame or metal board, be sure to use
a wall embedded pipe and wall cover in the feed-through hole to
prevent possible heat, electrical shock, or fire.
1) Bore a feed-through hole of 65mm in the wall so it has a down
slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
Flaring
ork
Firmly hold copper pipe in a die in the dimension shown in
the table above.
Bar
Bar
Yoke
Cone
4) After completing refrigerant piping, wiring, and drain piping,
caulk pipe hole gap with putty.
Inside
Wall embedded pipe
(field supply)
Handle
"A"
• Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage.
Copper pipe
Outside
Clamp handle
Red arrow mark
Caulking
Carry out flaring work using flaring tool as shown below.
¶65
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
3.1 Flaring
ork
Flaring ork
Main cause for refrigerant leakage is due to defect in theflaring
work. Carry out correct flaring work using the follow-ing procedure.
Cut the pipes and the cable
1. Use the piping kit accessory or pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than the measured distance.
4. Cut the cable 1.5m longer than the pipe length.
Copper
pipe
90e
Outside diameter
mm
inch
A
mm
Ø6.35
1/4
0~0.5
Ø9.52
3/8
0~0.5
Ø12.7
1/2
0~0.5
Ø15.88
5/8
0~1.0
Ø19.05
3/4
1.0~1.3
Check
1.Compare the flared work with figure below.
2.If flare is noted to be defective, cut off the flared section and reflare it.
Smooth all round
Inside is shiny without scratches
= Improper flaring =
Slanted Uneven Rough
Even length
all round
Inclined Surface Cracked Uneven
damaged
thickness
29
Installation Manual
3.2 Connection of piping
1.Align the center of the pipes and sufficiently tighten the flare nut
5. Insert the connecting cable fully into the terminal block and
secure it tightly with screws.
by hand.
6. Tightening torque: 1.2 N•m (0.12 kgf•m).
7. Secure the connecting cable with the cord clamp.
8. Attach the terminal cover, rear plate bushing and air inlet grille
on the indoor unit.
Indoor unit tubing
Flare nut
Pipes
CAUTION
2.Tighten the flare nut with a wrench.
e sure to refer to the
Open-end wrench (fixed)
specific
Flare nut
Wrench
iring system diagram
labeled inside the front panel.
Check local electrical regulations for any
iring instructions or limitations.
Connection pipe
Indoor unit tubing
Terminal cover
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Torque
kg.m
1.8
4.2
5.5
6.6
6.6
Screw
Screw
Cord clamp
1
Terminal block
Earth wire
If drain hose extension or embedded drain piping is required,
use appropriate parts that match the hose front end.
Connecting cable
Insert drain hose into the handle of drain pan, and join
drain hose and connecting hose according to the figure by.
Shield pipe
1
Drain hose Inside the room
Terminal block
Extension drain hose
CAUTION
CAUTION
Insert the drain hose and drain cap into the drain port, making sure that it comes in contact with the back of the drain
port, and then mount it. If the drain hose is not connected
properly, leaking will occur.
• Attach the Insulation (Drain hose) to the drain hose.
Connecting cable
Insulation (Drain hose)
About 15 cm
Drain hose
70 mm
Wiring the connecting cable can be carried out
ing the front panel.
ithout remov-
10 mm
Earth line
1. Remove the air inlet grille. Open the air inlet grille upward and
pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (or as according to local regulations/codes) into the pipe hole on the wall.
4. Pull the connecting cable through the cable slot on the rear
panel so that it protrudes about 15 cm out of the front.
30
10 mm
50 mm
Installation Manual
In the case of bending or curing refrigerant pipes, keep the fol-
1.After making slits on the front panel with a knife or similar tool,
cut them out with a pair of nippers or an equivalent tool.
lowing precautions in mind.
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom
frame.
2) Do not strongly press the refrigerant pipes on the front grille,
either.
Slit
2.Overlap the connection pipe insulation material and the indoor
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
Plastic bands Insulation material
1)
2)
The piping can be lead out from right, right rear, left left rear.
Right-side, right-back, or right-bottom piping
1)After making slits on the front panel with a knife or similar tool,
cut them out with a pair of nippers or an equivalent tool.
Attach the drain hose to the underside of the refrigerant pipes
with an adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with an
3.Wrap the area which accommodates the rear piping housing
section with vinyl tape.
Indoor
unit pipe
Connection
pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Wrap with vinyl tape
insulation tape.
Pipe
Vinyl tape(wide)
Bind with vinyl tape
Drain hose
Indoor unit
Right piping
Bottom
piping
Pipe (top)
Rear piping
Indoor unit drain hose
(bottom)
eft-side, left-back, or left-bottom piping
• Interchange the drain cap and the drain hose.
CAUTION
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline insertion will cause water leakage.
(2) When inserting, be sure not to attach any material
besides water. If any other material is attached, it
will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bottom
of piping.
Auxiliary pipes
Connecting
cable
Installation
plate
4.Bundle the piping and drain hose together by wrapping them
with vinyl tape for enough to cover where they fit into the rear
piping housing section.
Indoor unit installation
1) Pass the drain hose and refrigerant pipes through the wall
hole, then set the indoor unit on the mounting plate hooks by
using the markings at the top of the indoor unit as a guide.
A Mounting plate
Marking
(5) Prevent drain water frozen under low temperature environment.
When installing indoor unit's drain hose outdoors, necessary
measure for frost protection should be taken to prevent drain
water frozen.
• Under low temperature environment (when outdoor temperature under 32 °F), after cooling operation is executed,
water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked
and water leakage may be resulted for indoor unit.
For left outlet piping, cut off the
piping outlet cutting groove
with a hacksaw.
Indoor unit
drain hose
Drain cap
Remove the drain cap by pulling
at the projection at the end of
the cap with pliers, etc.
2) Swing the indoor unit to right and left to confirm that it is firmly
hooked on the installation plate.
3)While pressing the indoor unit onto the wall, hook it at the
lower part on the installation plate.
Pull the indoor unit toward you to confirm that it is firmly
hooked on the installation plate.
31
Installation Manual
For detaching the indoor unit from the installation plate pull the
indoor unit toward you while pushing the bottom up at the specified places.
Push
Push
4)Run the drain hose at a downward sloped angle.
Do not rise the drain hose.
Do not form the drain hose
into the waved shape.
Finally, tighten the flare nut ith tor ue rench until the rench
clicks.
50 mm
or more
Outdoor unit
Liquid side piping
(Smaller diameter)
Do not put the
drain hose end
into water.
Do not put the drain
hose end in the
drainage ditch.
5)Put water in the drain pan and make sure that the water is
being drained outside.
Caution:
Torque wrench
Gas side piping
(Bigger diameter)
Install the drain pipe for proper drainage. Improper drainage can
result in water dripping inside the room.
7.4 INSTA
ATION OF OUTDOOR UNIT
* Holes are provided on the base plate of the outdoor unit to
2.Overlap the connection pipe insulation material and the indoor
ensure that the defrost water produced during heating operations is drained off efficiently.
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
* If a centralized drain is required when installing the unit on a
balcony or wall.
* If the drain port is covered by a mounting base or floor surface,
place additional foot bases of at least 30mm in height under the
After the piping has been connected to the indoor unit, perform
the air purge.
outdoor unit’s feet.
* In cold areas, do not use a drain hose with the outdoor unit.
AIR PURGE
(Otherwise, drain water may freeze, impairing heating
performance.)
unit using a vacuum pump.
Do not use the refrigerant in the outdoor unit.
Evacuate the air in the connecting pipes and in the indoor
For details, see the vacuum pump manual.
Drain-water hole
Bottom frame
Drain plug
air conditioner pipes hen the pump stops. (If oil inside the
vacuum pump enters into the air conditioner circuit hich uses
Remove the Valve cover from the unit by loosening the scre .
Align the center of the pipings and sufficiently tighten the flare
32
ith vacuum pump
e sure to use a vacuum pump ith counter-flo prevention
function so that oil inside the pump does not flo back into the
Hose (available commercially,
inner dia. 16mm)
nut by hand.
Air purging
R410A, trouble ith the refrigeration system may develop.)
1. Connect the charge hose from the manifold valve to the service
port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold
valve.
Installation Manual
4. Operate the vacuum pump to begin evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters (15
minutes for 20 meters) (assuming a pump capacity of 27 liters
1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the indoor and outdoor
per minute). Confirm that the compound pressure gauge reading is –101 kPa (–76 cmHg).
units so that the terminal numbers match. Tighten the terminal
screws securely.
5. Close the low pressure valve handle of gauge manifold.
6. Open fully the valve stem of the packed valves (both sides of
The screws are packed with the terminal board.
Terminal block
Gas and Liquid).
7. Remove the charging hose from the service port.
N(1)
2
3
8. Securely tighten the caps on the packed valves.
Compound
pressure
gauge
-101kPa
(-76cmHg)
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
Handle Lo
Charge hose
(For R410A only)
Charge hose
(For R410A only)
Connecting
pipe
Vacuum pump
adapter for
counter-flow
prevention
(For R410A only)
Packed valve
at liquid side
Vacuum
pump
Connecting cable
7.5 Test Operation
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully
open.
Check the flare nut connections for gas leaks with a gas leak
detector and/or soapy water.
Packed valve at gas side
Service port
(Valve core (Setting pin))
Check places for
flare nut connections
(indoor unit)
Valve cover
CAUTION
IMPORTANT POINTS FOR PIPING WORK
1. Keep dust and moisture from entering the pipes.
2. Tighten connections carefully (between pipes and unit).
3. Evacuate the air in the connecting pipes using a VACUUM
PUMP.
Electric parts
Check places
for outdoor unit
4. Check for gas leaks at all connections.
Packed Valve handling precautions
• Open the valve stem all the way; but do not try to open it beyond
the stopper.
• Securely tighten the valve stem cap with torque in the following
table:
1)Switch on power, press “ON/OFF” button on the wireless remote control to start the operation.
Gas side (Ø9.52 mm)
33 to 42 N• m (3.3 to 4.2 kgf •m)
2)Press MODE button, to select the COOL, HEAT (Cooling only
unit is not available), FAN to check whether the operation is nor-
Liquid side (Ø6.35 mm)
14 to 18 N• m (1.4 to 1.8 kgf •m)
Service port
14 to 18 N• m (1.4 to 1.8 kgf • m)
mal or not.
Perform test operation and check items 1 and 2 below.
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
Cap
Hexagon wrench(4mm)
(4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the
neighbors?
(3) Is there any gas leakage?
33
Exploded Views and Parts list
8. EXPLODED VIEWS AND PARTS LIST
8.1 Exploded View
Indoor Unit
34
Exploded Views and Parts list
Outdoor Unit
(1) Cooling Only Models
35
Exploded Views and Parts list
(2) Cooling & Heating Models
36
Exploded Views and Parts list
8.2 Parts List
Indoor Unit
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Description
Decorative Strip
Front Panel
Filter Sub-Assy
Front Case
Guide Louver
Air Louver
Shaft of guide louver
Front Panel Assy
Drainage Pipe Sub-assy
Evaporator Support
Cross Flow Fan
Evaporator Assy
Helicoid tongue
Rear Case assy
Wall Mounting Frame
Electric Box
Electric Box
Motor Press
Electric Box
Cover
Assy
Plate
Cover Sub-Assy
Terminal Board
Crank
Step Motor
Pipe plug (outlet)
Electric Box
Motor Sub-Assy
Baffle Plate
Fan Motor
Front Case Assy
Remote Controller
Power Cord
Connecting Cable
Screw Cover
Main Board
XY Capacitor
Ambient Temperature Sensor
Fan Bearing
Damping washer sub-assy
Axile Bush sub-assy
Electric Box Sub-Assy
Part Code
CEVI-09
20192292
2001232501T
1112208201
20012324
10512119
10512160
1054202001
2001237601
0523204101
24212108
10352423
01002270
26112486
2220211901
0125201801
20122106
2020225303
26112191
20122109
42011233
73012005
1521210701
76712020
20112086
15002002
26112218
15012093
2001237501
30510061
400204643
400205236
24252019
30138124
33030013
EVI-09
20192292
2001232501T
1112208201
20012324
10512119
10512160
1054202001
2001237601
0523204101
24212108
10352423
01002270
26112486
2220211901
0125201801
20122106
2020225302
26112191
20122109
42011233
73012005
1521210701
76712020
20112086
15002002
26112218
15012093
2001237501
30510061
400204643
400205236
24252019
30138120
390000453
76512210
390000453
76512210
76512011
10542024
2020225703
76512011
10542024
2020225702
33030013
Qty
1
1
2
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
37
Exploded Views and Parts list
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
38
Description
Decorative Strip
Front Panel
Filter Sub-Assy
Front Case
Guide Louver
Air Louver
Shaft of guide louver
Front Panel Assy
Drainage Pipe Sub-assy
Evaporator Support
Cross Flow Fan
Evaporator Assy
Helicoid tongue
Rear Case assy
Wall Mounting Frame
Electric Box
Electric Box
Motor Press
Electric Box
Cover
Assy
Plate
Cover Sub-Assy
Terminal Board
Crank
Step Motor
Pipe plug (outlet)
Electric Box
Motor Sub-Assy
Baffle Plate
Fan Motor
Front Case Assy
Remote Controller
Power Cord
Connecting Cable
Screw Cover
Main Board
XY Capacitor
Ambient Temperature Sensor
Fan Bearing
Damping washer sub-assy
Axile Bush sub-assy
Electric Box Sub-Assy
Part Code
CEVI-12
20192292
2001232501T
1112208201
20012324
10512119
10512160
1054202001
2001237601
0523204101
24212108
10352423
01002745
26112486
2220211901
0125201801
20122106
2020225301
26112191
20122109
42011233
73012005
1521210701
76712020
20112086
15002002
26112218
15012093
2001237501
30510061
400204643
400205236
24252019
30138125
33030013
EVI-12
20192292
2001232501T
1112208201
20012324
10512119
10512160
1054202001
2001237601
0523204101
24212108
10352423
01002745
26112486
2220211901
0125201801
20122106
20202253
26112191
20122109
42011233
73012005
1521210701
76712020
20112086
15002002
26112218
15012093
2001237501
30510061
400204643
400205236
24252019
30138121
390000453
76512210
390000453
76512210
76512011
10542024
2020225701
76512011
10542024
20202257
33030013
Qty
1
1
2
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Exploded Views and Parts list
Outdoor Unit
(1) Cooling Only Models
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Description
Front Grill
Cabinet
Axial Flow Fan Sub-Assy
Fan Motor
Motor Support
Left Side Plate
Top Cover Sub-Assy
Electric Box Assy
Main Board
Relay
Clapboard
Chassis Sub-assy
Condenser Assy
Cut-off Valve Assy
Capillary Sub-Assy
Valve Support
Right Side Plate Sub-Assy
Handle assy
Thermal baffle
Discharge Tube
Cut-off valve Sub-Assy
Compressor and fittings
Overload Protector
Terminal cap
Part Code
CEVO-09
22413017
01433044P
1033300901
15013073
0170311101
20053001
0125304001
0260325603
30138099
44020382
01233088
0120390901P
01113463
07133164
03103936
01713089
0130318001
26233046
26113005
03713424
07133189
00103761
00181067
22243001
CEVO-12
22413017
01433044P
1033300901
15013073
01703111
20053001
0125304001
0260325602
30138100
44020382
01233088
0120390901P
01113501
07133602
03063056
01713089
0130318001
26233046
26113005
03733025
07133189
00103761
00181067
22243001
Qty
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
(2) Cooling & Heating Models
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Description
Front Grill
Front Plate
Axial Flow Fan Sub-Assy
Fan Motor
Motor Support
Left Side Plate
Top Cover Sub-Assy
Electric Box Assy
Main Board
Relay
Clapboard
Chassis Sub-assy
Condenser Assy
Cut-off Valve Assy
Capillary Sub-Assy
Valve Support
Right Side Plate Sub-Assy
Handle assy
Thermal baffle
Magnet Coil
4-way Valve Assy
Compressor and fittings
Overload Protector
Terminal cap
Drainage Joint
Part Code
EVO-09
22413017
01433044P
1033300901
15013073
0170311101
20053001
0125304001
02603256
30138087
44020382
01233088
0120390901P
01113463
07133164
03103936
01713089
0130318001
26233046
26113005
4300040050
0312323701
00103761
00181067
22243001
06123024
EVO-12
22413017
01433044P
1033300901
15013073
01703111
20053001
0125304001
0260325601
30138096
44020382
01233088
0120390901P
01113501
07133163
03103937
01713089
0130318001
26233046
26113005
4300040050
0312327201
00103761
00181067
22243001
06123024
Qty
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
39
Troubleshooting
9. TROUBLESHOOTING
9.1 Precautions before Performing Inspection or Repair
Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop
from high attitude.
* Static maintenance is the maintenance during de-energization of the air conditioner.
For static maintenance, make sure that the unit is de-energized and the plug is disconnected.
*dynamic maintenance is the maintenance during energization of the unit.
Before dynamic maintenance, check the electricity and ensure that there is ground wire on the site. Check if there is electricity on the housing and
connection copper pipe of the air conditioner with voltage tester. After ensure insulation place and the safety, the maintenance can be performed.
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power.
At times such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position.
Normally,diagnose troubles according to the trouble diagnosis procedure as described below.(Refer to the check points in servicing
written on the wiring diagrams attached to the indoor/outdoor units.)
No.
Troubleshooting procedure
1
Confirmation
2
Judgement by Flashing LED of Indoor/Outdoor Unit
3
How to Check simply the main part
Precautions when inspecting the control section of the outdoor
unit:
A large-capacity electrolytic capacitor is used in the outdoor unit controller
(inverter).Therefore,if the power supply is turned off,charge(charging voltage DC280V to 380V)remains and discharging takes a lot of time.. After
turning off the power source,if touching the charging section before
discharging, an electrical shock may be caused.
The outdoor unit can be open after the unit is de-energized for 20min
9.2 Confirmation
(1)Confirmation of Power Supply
Confirm that the power breaker operates(ON) normally;
(2)Confirmation of Power Voltage
Confirm that power voltage is AC 220–230–240 ± 10%.
If power voltage is not in this range, the unit may not operate normally.
9.3 Judgement by Flashing LED of Indoor/Outdoor Unit
40
Troubleshooting
code
malfunctio
Error display
n
Dual
8
Repair method
co
malfunction
Error display
de
LED
Dual 8
display
1
Storage
EE
slug
Repair method
LED
display
Heating LED-pause
Replace indoor main
3s
board
and
blink 15
15
Sync failure
H7
times
Heating
Check if the resistance
LED-pause 3s and
of
blink 7 times
resistance to ground is
compressor
normal.
and
If
the
compressor is normal,
the outdoor main boar
d may be wrong.
2
Heating LED-pause
Replace indoor main
PCB
3s
board
malfunctio
times
EE
Indoor
and
blink 15
16
Current
diction
malfunction
U5
of
Cooling
Replace outdoor main
LED-pause 3s and
board
blink 13 times
complete unit
n
3
4
Anti-freezi
E2
Running
LED-
ng
pause 3s and blink 2
protection
times
Overload
H4
of system
Outdoor
ambient
17
temperature is too low
18
Cooling
Is it loose? Measure
temperature sensor
LED-pause 3s and
the
malfunction
blink 3 times
with universal meter
Outdoor
ambient
E4
Discharge
Heating LED-pause
System is abnormal,
3s and blink 4 times
check if the evaporator
protection
and condenser is dirty
compressor
F3
of
resistance
value
Running
Is it loose? Measure
LED-pause 3s and
the
blink 4 times
with universal meter
resistance
value
and blocked
5
No motor
of
H6
Running
LED-
pause 3s and blink
indoor
Is
electromotor
19
mounted normally?
F2
Indoor
pipe
cooling LED- pause
Is it loose? Measure
3s and blink 2 times
the
resistance
20
Break-circuit
and
short-circuit
value
F4
of
outdoor condenser
with universal meter
temperatur
e
F5
of
cooling
LED-
Is it loose? Measure
pause 3s and blink
the
5 times
with universal meter
resistance
value
temperature sensor
feedback
6
and
outdoor discharge
11 times
unit
Break-circuit
short-circuit
cooling
LED-
Is it loose? Measure
pause 3s and blink
the
18 times
with universal meter
resistance
value
temperature sensor
sensor
malfunctio
n
7
F1
Internal
ambient
Cooling LED- pause
Is it loose? Measure
3s and blink 1 times
the
21
Overheat of carbon
P8
fin
value
with universal meter
temperatur
e
resistance
heating
LED-
Is
outdoor
ambient
pause 3s and blink
temperature
is
19 times
high?
radiator
Is
too
mounted correctly?
sensor
malfunctio
n
8
Heating and cooling
Replace indoor main
passage
LED blinks 7 times
board
abnormal
at the same time
UF
Zero
22
DC overcurrent
UU
Heating
and
cooling LED blink
11 times at the
same time
9
H3
Overload
of
Temperature sensor
Inspect
3s and blink 3 times
state of the overload
malfunction
wire.
carbon fin
compresso
connection
23
heating LED- pause
P7
heating
LED-
pause 3s and blink
of
Replace outdoor main
board.
18 times
r
10
Startup
Lc
failure
heating LED- pause
Check if the resistance
3s
of
and
blink
11
compressor
24
Lack of Freon or
F0
block protection
and
normal.
If
LED-
10 times
resistance to ground is
times
cooling
pause 3s and blink
the
compressor is normal,
the outdoor main boar
d may be wrong.
11
Heating and cooling
This malfunction may
of outdoor
LED blink 8 times at
happen when outdoor
unit
the same time
DC
No motor
UH
13
DC input voltage is
PH
too high
cooling
LED-
pause 3s and blink
Is voltage of AC power
supply normal?
11 times
is
used.
feedback
12
electromotor
25
Overcurren
E5
Running
LED-
t
pause 3s and blink 5
protection
times
U7
4-way
3s
and
conversion
times
electric
network
26
variable?
DC input voltage is
PL
too low
Heating
LED-
pause 3s and blink
Is voltage of AC power
supply normal?
21 times
cooling LED- pause
valve
Is
Replace 4-way valve.
27
Communication
E6
malfunction
blink 20
Running
LED-
Is outdoor connecting
pause 3s and blink
wire
6 times
connected?
reliably
abnormal
14
Heating LED- pause
Replace outdoor main
current
3s
board.
detection
times
U1
Phase
malfunctio
n
and
blink 13
28
and
Outdoor unit is not
indoor and outdoor
cooling LED blink
matched with indoor
unit abnormal
12 times at the
unit.
Setting
error,
UA
Heating
same time
of
compresso
r
remarks
4min after protection stop of compressor, the malfunction is shown in error code. In other situation, the malfunction will be displayed by press the light button for 6 times within
4s.
41
Troubleshooting
9.4 How to Check simply the main part
(1)Malfunction of power supply from indoor unit to outdoor unit
Main inspection point:
Inspect the power supply plug seat with AC voltage gauge to check if the voltage between L and N is within 200VAC~240VAC;
Check with AC voltage gauge if the voltage between N 1and 3 of indoor wiring block is within 200VAC~240VAC;
Check with AC voltage gauge if the voltage between L and N of outdoor wiring block is within 200VAC~240VAC;
Energize the unit
and wait for 3min
Measure voltage between
N 1and 3 of indoor
wiring block
Voltage > 200V?
Measure voltage
between L and N
of outdoor wiring
block
Y
N
Normal wiring?
Voltage > 200V?
N
Y
Indoor main board error
N
Y
Outdoor electric
box error
Adjust wiring
Replace main board
of indoor unit
Replace outdoor
electric box
indoor and outdoor
wiring error
Replace indoor
and outdoor wiring
Remove malfunction
(2) Indoor fan does not rotate without feedback
Main detection point:
z
Is the control panel reliably connected with the electromotor? Is it loose? Is the connecting sequence correct?
z
Is the input voltage within the normal range (measure the voltage between L and N of the wiring block XT with AC voltage gauge.)?
Malfunction diagnosis process:
42
Troubleshooting
Energize the
unit and start it
9ROWDJHEHWZHHQ
/DQG1RI
LQGRRUZLULQJ
EORFN
9ROWDJH!9"
Y
&KHFNWKH
FRQQHFWLQJ
VWDWHRIWKH
FRQQHFWLQJ
WHUPLQDO
5HOLDEOH
FRQQHFWLRQ
N
N
$GMXVW
FRQQHFWLQJ
VWDWH
Y
&KHFNSRZHU
VXSSO\
5HSODFHPDLQ
ERDUGRILQGRRU
XQLW
N
5HPRYHWKH
HUURU"
N
UHPRYHWKH
HUURU"
Y
5HSODFHPRWRU
Y
)LQLVK
(3) Temperature sensor malfunction
Main detection point:
z
Is outdoor ambient temperature within the normal range?
z
Is indoor and outdoor fan running normally?
z
Is the radiating environment inside and outside the unit good enough?
Malfunction diagnosis process:
(QHUJL]HWKH
XQLWDQGVWDUW
LW
,QGRRUXQLW
GLVSOD\))
&KHFNFRQQHFWLQJ
VWDWHRILQGRRU
WHPSHUDWXUH
VHQVRU
Y
N
UHOLDEOH
FRQQHFWHG"
,QGRRUXQLW
GLVSOD\))
N
$GMXVW
FRQQHFWLQJVWDWH
Y
&KHFNFRQQHFWLQJ
VWDWHRIRXWGRRU
WHPSHUDWXUHVHQVRU
Y
5HOLDEOH
FRQQHFWHG"
N
5HSODFH
WHPSHUDWXUH
VHQVRU
N
$GMXVW
FRQQHFWLQJVWDWH
Y
5HSODFH
WHPSHUDWXUH
VHQVRU"
N
5HPRYHHUURU"
5HPRYHHUURU"
5HPRYHHUURU"
Y
N
5HPRYHHUURU"
5HSODFHPDLQ
ERDUGRILQGRRU XQLW
N
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
Y
Y
Y
ILQLVK
43
Troubleshooting
Energize the
unit and start it
(4) Malfunction diagnosis of startup failure
Main detection points:
z
Is wiring of compressor correct˛
z
Is the stop time of compressor enough?
z
Is compressor damaged?
Is the stop time
of compressor more
than 3min£¿
N
Start it 3 min later
Y
Malfunction diagnosis process:
N
Startup failure?
Y
Is compressor wire connected correctly?
Connect it according
to line chart
N
Y
Replace parts if outdoor
electric box
Remove the error?
Y
N
Replace
compressor
finish
(5) Diagnosis of losing synchronism for compressor
Main detection points:
z
Is pressure of the system too high?
z
Is voltage too low?
Malfunction diagnosis process:
/RVLQJV\QFKURQLVP
XSRQVWDUWXSRI
WKHXQLW
,VWKHVWRSWLPH
RIFRPSUHVVRUPRUH
WKDQPLQ˛
N
/RVLQJV\QFKURQLVP
GXULQJUXQQLQJ
,VRXWGRRUIDQQRUPDO"
N
,VIDQZHOO
FRQQHFWHG"
Y
Y
,VZLUHRIFRPSUHVVRU
ZHOOFRQQHFWHG"
N
Y
$GMXVW
FRQQHFWLQJZLUH
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
Y
5HPRYH
VWXII
N
,VRXWGRRUIDQ
EORFNHGE\
VWXII"
5HOLDEOH
FRQQHFWHG"
Y
N
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
Y
5HPRYHHUURU"
5HPRYHHUURU"
N
Y
5HPRYHHUURU"
N
5HSODFH
FRPSUHVVRU
N
5HSODFH
FRPSUHVVRU
)LQLVK
)LQLVK
44
Y
5HSODFH
RXWGRRUIDQ
Troubleshooting
(6) Diagnosis of overload and discharge malfunction
PLQDIWHU
GHHQHUJL]DWLRQ
RIFRPSOHWHXQLW
Main detection points:
z
Is electric expansion valve well connected? Is it damaged?
z
Is refrigerant leaked?
z
Is overload wire connection normal?
,VHOHFWULF
H[SDQVLRQYDOYH
ZHOOFRQQHFWHG"
Malfunction diagnosis process:
N
Y
,VRYHUORDGZLUH
UHOLDEO\FRQQHFWHG"
N
Y
5HSODFHHOHFWULF
H[SDQVLRQYDOYH
5HPRYH
PDOIXQFWLRQ"
$GMXVW
FRQQHFWLQJZLUH
Y
N
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
5HPRYHPDOIXQFWLRQ"
Y
N
5HIULJHUDQWOHDNDJH
UHFKDUJHWKH
UHIULJHUDQW
)LQLVK
(7) Process of communication circuit detection
(FRPPXQLFDWLRQ
HUURULV
GLVSOD\HG
,VFRQQHFWLQJ
ZLUHUHOLDEO\
FRQQHFWHG"
N
Y
5HSODFHPDLQ
ERDUGRILQGRRU
XQLW
5HPRYHPDOIXQFWLRQ"
$GMXVW
FRQQHFWLQJZLUH
Y
N
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
)LQLVK
45
Troubleshooting
9.5 2-way, 3-way Valve Appearance
2-way Valve (Liquid Side)
Hexagonal wrench (4mm)
Flare nut
3-way Valve (Gas Side)
Valve cap
Open position
Flare nut
Closed position
Open position
Closed position
To
piping
connection
To
piping
connection
To outdoor unit
Works
Shipping
1.
Air purging
(Installation)
Operation
46
Pin
Service Service
port cap port
To outdoor unit
Shaft position
Shaft position
Service port
Closed
(with valve cap)
Closed
(with valve cap)
Closed
(with cap)
Closed
(clockwise)
Closed
(clockwise)
Open
(with vacumm pump)
Open
(with valve cap)
Open
(with valve cap)
Closed
(with cap)
Closed
(clockwise)
Open
Open
(counter-clockwise) (connected manifold
gauge)
2.
Pumping down
(Transfering)
Open
Open
3.
Evacuation
(Servicing)
Open
(with charging
cylinder)
Open
Open
4.
Gas charging
(Servicing)
Open
(with charging
cylinder)
5.
Pressure check
(Servicing)
Open
Open
Open
(with charging cylinder)
6.
Gas releasing
(Servicing)
Open
Open
Open
(with charging cylinder)
Troubleshooting
Liquid side
Indoor unit
Clsed
Outdoor unit
2-way
valve
Gas side
Clsed
3-way
valve
Vacuum pump
Lo
OPEN
CLOSE
* Procedure
(1)Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
(2)Connect the charge hose to the port of the vacuum pump.
(3) Open fully the low pressure side handle of the gauge manifold valve.
(4)Operate the vacuum pump to begin evacuating. Perform
evacuating for about 15 minutes if the piping length is 20 meters
CAUTION:
If gas leakage are discovered in step 5 above, take the
following mesures :
If the gas leaks stop when the piping connections are
tightened further, continue working from step 6. If the
gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge
all of the gas through the service port, and then recharge
with the specified amount of gas from a gas cylinder.
(15 minutes for 20 meters) (assuming a pump capacity of 27
liters per minute). Confirm that the compound pressure gauge
reading is –101 kPa (–76 cmHg).
(5)Close the low pressure valve handle of gauge manifold.
– Check the flare connections for gas leakage.
(6)Use torque wrench to tighten the service port nut to a torque
of 1.8kg.cm.
(7)Set the 3-way valve to the back seat.
(8)Mount the valve stem nuts to the 2-way and 3-way valves.
(9)Check for gas leakage.
– At this time, especially check for gas leakage from the 2-way
and 3-way valve’s stem nuts, and from the service port nut.
47
Troubleshooting
Liquid side
Indoor unit
2-Way
valve
Open
Outdoor unit
Gas side
Closed
3-Way
valve
Lo
CLOSE
CLOSE
Purge the air
• Procedure
(1) Confirm that both the 2-way and 3-way valves are set to
the open position.
– Remove the valve stem caps and confirm that the valve stems
(7) Immediately set the 3-way valve to the closed position.
– Do this quickly so that the gauge ends up indicating 3 to 5kg/
cm2g.
are in the raised position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(8) Disconnect the charge set, and mount the 2-way and 3(2) Operate the unit for 10 to 15 minutes.
way valve’s stem nuts and the service port nut.
– Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Stop operation and wait for 3 minutes, then connect the
charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set slightly to air
purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling cycle and stop it
when the gauge indicates 1kg/cm2g.
48
Troubleshooting
Liquid side
Indoor unit
3-Way
valve
Closed
Outdoor unit
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R410A
OPEN
CLOSE
• Procedure
(1) Confirm that both the liquid side valve and the gas side
balve are set to the closed position.
(6) Disconnect the charge set and the gas cylinder, and set
the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(2) Connect the charge set and a gas cylinder to the service
port of the Gas side valve.
– Leave the valve on the gas cylinder closed.
(8) Mount the valve stem nuts and the service port nut.
– Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Air purging.
– Open the valves on the gas cylinder and the charge set. Purge
the air by loosening the flare nut on the liquid side valve approximately 45o or 3 seconds then closing it for 1 minute;repeat
3 times.
– After purging the air, use a torque wrench to tighten the flare
CAUTION: Do not leak the gas in the air during Air Purging.
nut on liquid side valve.
(4) Check for gas leakage.
– Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.
49
Troubleshooting
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Lo
OPEN
CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
50
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indicates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm2G), discharge the refrigerant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be necessary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will
also be discharged.
Troubleshooting
Evacuation
(All amount of refrigerant leaked)
Liquid side
Indoor unit
Outdoor unit
3-Way
valve
Open
Gas side
3-Way
valve
Open
Vacuum pump
Lo
OPEN
CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
51
Troubleshooting
Gas Charging
(After Evacuation)
Liquid side
Indoor unit
3-Way
valve
Open
Outdoor unit
Gas side
Open
3-Way
valve
Check valve
Charging
cylinder
Lo
(1)
OPEN
CLOSE
• Procedure
\
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-connected from the vacuum pump to the valve at
the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the system can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the specified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
52
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping partway will allow the gas to be discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Removal Procedure
10. Removal Procedure
10.1 Removal Procedure of Indoor Unit
Warning
Be sure to wait 10 minutes or more after turning
off all power supplies before disassembling work.
1. External features
If ON/OFF button is kept pushing
for 5 seconds, aforced cooling operation willbe carried out for
approx. 15minutes.
2. Removing air filters
1
Pull protrusions on left
and right sides of panel
with fingers and open
front grille all the way.
2
Lift center section of air
filter and disengage
hooks.
Air filter
Left and right filters are
interchangeable.
To re-install, insert air filter
along the guide.
Hooks
3
Remove air filter by
pulling forward.
53
Removal Procedure
Support the front panel by one
3. Opening and shuttingfront panel
1
hand, while remove the rotation
axis at the upper center by the
Pull down horizontal blade
by pulling forward.
other hand.
And pull out the front panel
forward to remove.
Horizontal blade
2
Remove horizontal blade by
pulling forward.
3
Hook a finger onto the
projection part provided
on the both sides of the
unit’s panel and open
Left and right filters are
interchangeable.
up the panel to the
position higher than it
To re-install, insert air filter
along the guide.
will stop.
Right
Left
4
Remove the front panel
from the unit.
54
Rotary shaft
Rotary shaft
Removal Procedure
4. Opening and closing of service cover
1
screws
Remove a service
cover mounting screw.
Open service cover
upward.
A switch for field setting is
not provided in particular.
screws
5. Removal of front grille assembly
1
2
Remove the 3 screws,
in the right and the left,
which fix the main body
Screw stoppers inside the
flap which were equipped in
with the front grille.
the existing models are not
provided.
Disengage the 3 hooks
Hooks
on the upper part.
In case that the hooks
are not pressed from
above, remove the front
panel and then remove
the grille while pushing
the hook through a
clearance between the
front grille and the heat
exchanger.
At the upper part there are 2
Left
Center
Right
hooks in the left and the
right.
Disengage the hooks by
3
The front grille can be
removed in a manner to
pressing knobs with a
screwdriver.
pull out the upper part
forward and lift up the
lower part.
55
Removal Procedure
6. Remove the Vertical blade
1
Unfasten the hooks at
the upper 2 positions.
Hook
A set of vertical blade has 6
fins as on ASSY.
(It is impossible to replace
only one fin.)
The set of vertical blades is
not marked for difference
between right and left.
2
Unfasten the 3 hooks at
the shaft mounting part
by pressing them with a
flat screwdriver.
Repeat the same procedure
to remove the vertical blade
on the other side.
Hook
3
Remove the vertical
blade.
Vertical blade
56
Removal Procedure
7. Remove electrical box
1
Disconnect the Cable
clamp
Pay attention to the direction
of the retainer of the
thermistor so that the
retainer will not touch the
harness (same as the
existing models.)
Terminal board
2
Disconnect the
connection wires.
Connecting
wires
Heat exchanger thermistor
3
Remove Temperature Sensor
Take care not to lose the clip
of thermistor.
Clip
Heat exchanger
thermistor
(R11268)
(R11244)
4
Remove a screw on the
terminal board.
Screw
Earth wire
The electrical box can be
removed instead of
disengaging the terminal
board.
57
Removal Pr ocedur e
5
Remove fan motor Signal
Wire
6
Remove a screw on the
electrical box.
7
Pull up the electrical
box forward to remove.
fan motor Signal Wire
Bottom frame
Hook
58
Removal Procedure
8. Remove the shield plate.
1
Unfasten the hooks at
the upper 2 positions of
the shield plate.
Hook
Remove the electrical box according
to the “Removal of Electrical Box”.
shield plate (1)
2
Unfasten the hook at
the lower position, and
remove the shield plate
(1).
Hook
3
Lift the shield plate (2)
and unfasten the 2
hooks.
Hook
4
Slide the shield plate
(2) and remove it.
Shield plate (2)
59
Removal Procedure
2
Take off Wiring terminal
Display PCB ASSY
3
Remove Display PCB
Sub-Assy.
4
Remove Swing motor.
Swing motor
60
Removal Procedure
5
6
The control PCB is
To remove the control
PCB, unfasten the 2
hooks at the upper part
from the rear side.
integrated with the power
supply PCB.
Lift up the upper part of
the control PCB, and
remove it.
Control PCB
61
Removal Pr ocedur e
9. Disconnect the refrigerant piping.
1
CAUTION
If gas leaks, repair the spot of
Lift the indoor unit by a
wooden base.
leaking, then collect all
refrigerant from the unit. After
conducting vacuum drying,
recharge proper amount of
refrigerant.
CAUTION
Wooden base
Do not contaminate any gas
(including air) other than the
specified refrigerant (R-410A)
into refrigerant cycle.
2
(Contaminating of air or other
gas causes abnormal high
Place a plastic sheet
under the drain pan as
remaining drain may
leak.
pressure in refrigerating
cycle, and this results in pipe
Drain hose
breakage or personal
injuries.)
Extension drain hose
Connecting wires
Pay attention so that the
residual water in the drain
will not make the floor wet.
3
Disconnect the flare nut
for gas piping by 2
wrenches.
In case that a drain hose is
buried inside a wall, remove
it after the drain hose in the
wall is pulled out.
4
Disconnect the flare nut
for liquid piping by 2
wrenches.
Use two wrenches to
disconnected pipes.
When disconnecting pipes,
cover every nozzle with caps
so as not to let dust and
moisture in.
62
Removal Pr ocedur e
9. Remove the indoor unit.
1
When the pipings are
disconnected, protect the
both openings from entering
moisture.
Remove the indoor unit
from the installation
plate.
Liquid piping
Gas piping
(R8019)
Auxiliary piping
2
Piping fixture
Release the hook of the
piping fixture on the
back of the unit.
63
Removal Procedure
3
Loosen the 2 screws,
in the right and the left,
which fix the Evaporator
Assy.
Auxiliary piping
64
4
Widen the auxiliary
piping to the extent of
10°~20°.
5
Pull the heat exchanger
to the front side to undo
the hooks completely,
and then lift it.
Heat exchanger
Removal Procedure
10. Remove Cross Flow Fan Fan
Motor
1
Remove Cross Flow Fan
Fan Motor
11. Remove Ring of Bearing
Bearing
12. Remove Cross Flow Fan and
Motor Sub-Assy screw.
65
Removal Procedure
13. Remove Motor Sub-Assy
1
Remove Motor Sub-Assy
14. Remove Fan Motor
66
Removal Procedure
2
Remove the 4 tapping screws
fixing the motor. Pull out the
lead-out wire and remove the
M4×16
Fan motor fixing frane
motor. Remove the 2 tapping
DC fan motor
screws fixing the motor
support. Lift to remove
the motor support.
Fan motor
5.Remove the electrical box.
Electrical box
1
Remove the 2 screws fixing
the cover of electric box. Lift to
remove the cover. Remove the
screws fixing the electric box
subassembly. Loosen the wire
and disconnect the terminal.
Lift to remove the electric
box subassembly.
6.Remove the partition plate.
1
Loosen the 2 screws.
The partition plate is fixed to
the bottom frame with a hook.
2
The partition plate has
a hook on the lower
side. Lift and pull the
partition plate to remove.
Partition plate
69
Removal Procedure
7.Remove the sound blanket.
Since the piping ports on
1
Lift and remove the
the sound blanket are
sound blanket (top).
torn easily, remove the
blanket carefully.
2
Untie the strings and
open the sound blanket.
3
Lift and remove the
sound blanket (body) as
it is opened.
4
Pull the sound blanket
Since the piping ports on
(inner) out.
the sound blanket are
torn easily, remove the
blanket carefully.
Sound blanket.
8.Remove the partition plate.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
1
Loosen the screw of the
four way valve coil.
influence peripheries.
Be careful so as not to break
the pipes by pressing it
excessively by pliers when
withdrawing it.
Caution
Be careful about the four way
valve, pipes and so on, which
were heated up by a gas
brazing machine, so as not
to get burnt your hands.
70
Removal Procedure
Disassemble the compressor
Solder off the welding spot of
1
capillary and valve and outlet
pipe of condenser.
2
Remove the 2 screws fixing
the gas valve. Solder off the
welding spot connecting gas valve
and air return pipe and remove
the gas valve.
(Note: it is necessary to warp
the gas valve when soldering
off the welding spot.)
Remove the 2 screws fixing
liquid valve. Solder off the
welding spot connecting liquid
valve and remove the liquid valve.
3
Solder off the pipe connected
with the compressor.
Remove the 3 footing screws
of the compressor and
remove the compressor.
4
Remove the 3 footing
screws of the compressor
and remove the compressor.
.
71

advertisement

Related manuals

Download PDF

advertisement