Below you will find brief information for RV generator KV. The KV series of generators includes a comprehensive control panel with start/stop functions, circuit breakers, and a fuse. The control panel also allows for optional remote control capabilities for added convenience. The generator is designed for reliable operation in various environments and includes features such as an altitude adjustment knob for optimal performance at different altitudes. Moreover, the manual provides valuable information on maintenance procedures, troubleshooting tips, and specifications.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

RV generator KV Operator Manual | Manualzz

Operator Manual

RV Generator set

KV

English 7−2009 981−0153 (Issue 5)

California

Proposition 65 Warning

Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.

!

!

The engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth

defects or other reproductive harm.

Table of Contents

SAFETY PRECAUTIONS

INTRODUCTION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

About this Manual

Nameplate

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Typical Genset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fuel Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Engine Oil Recommendations

Starting Batteries

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Genset Control Panel

Remote Control Panel

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Conducting the Pre-Start Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Starting the Genset

Stopping the Genset

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Restarting the Genset

Loading the Genset

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Resetting Circuit Breakers

Connecting Shore Power

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10

10

Operating in Cold Weather

Operating in Hot Weather

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Operating at High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating in Dusty Environments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

12

Breaking in a New Engine

Exercising the Genset

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

12

Storing the Genset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PERIODIC MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Conducting General Inspections

Checking Engine Oil Level

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Changing Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Replacing the Air Filter Element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Replacing the Spark Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cleaning the Spark Arrestor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

17

18

18

19

12

15

16

17

Replacing the Fuel Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Maintaining the Battery and Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

SPECIFICATIONS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INFORMATION FOR CALIFORNIA GENSET USERS

HOW TO OBTAIN SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE RECORD

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

24

25

26

20

20

21

23

9

9

8

9

8

8

7

7

6

6

5

6

4

4

2

4

1

Safety Precautions

Thoroughly read the OPERATOR’S MANUAL

before operating the genset. Safe operation and

top performance can be obtained only when equipment is operated and maintained properly.

The following symbols in this manual alert you to potential hazards to the operator, service person and equipment.

alerts you to an immediate hazard which will result in severe personal injury or death.

WARNING

alerts you to a hazard or unsafe practice which can result in severe personal injury or death.

CAUTION

alerts you to a hazard or unsafe practice which can result in personal injury or equipment damage.

When equipped with an integral or add−on Auto− matic Generator Starting System (AGS) control,exhaust carbon monoxide (CO), electric shock, andmoving parts hazards are possible due to unex− pected starting. Turn off AGS whenever performingmaintenance or service, when the vehicle is storedbetween uses, is awaiting service, or is parked in agarage or other confined area.

Electricity, fuel, exhaust, moving parts and batteries present hazards which can result in severe personal injury or death.

GENERAL PRECAUTIONS

• Keep children away from the genset.

• Do not use evaporative starting fluids. They are highly explosive.

• To prevent accidental or remote starting while working on the genset, disconnect the negative () battery cable at the battery.

S Let the engine cool down before removing the coolant pressure cap or opening the coolant drain. Hot coolant under pressure can spray out and cause severe burns.

• Keep the genset and its compartment clean.

Excess oil and oily rags can catch fire. Dirt and gear stowed in the compartment can restrict cooling air.

• Make sure all fasteners are secure and torqued properly.

• Do not work on the genset when mentally or physically fatigued or after consuming alcohol or drugs.

• You must be trained and experienced to make adjustments while the genset is running—hot, moving or electrically live parts can cause severe personal injury or death.

• Used engine oil has been identified by some state and federal agencies as causing cancer or reproductive toxicity. Do not ingest, inhale, or contact used oil or its vapors.

• Benzene and lead in some gasolines have been identified by some state and federal agencies as causing cancer or reproductive toxicity. Do not to ingest, inhale or contact gasoline or its vapors.

• Keep multi-class ABC fire extinguishers handy.

Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10)

• Genset installation and operation must comply with all applicable local, state and federal codes and regulations.

GENERATOR VOLTAGE IS DEADLY!

S Disable the automatic genset starting feature(AGS) of an inverter−charger or other automat−ic starting device before servicing the genset toavoid unexpected starting.

• Generator electrical output connections must be made by a trained and experienced electrician in accordance with applicable codes.

• The genset must not be connected to shore power or to any other source of electrical power. Back-feed to shore power can cause electric shock resulting in severe personal injury or death and damage to equipment. An approved switching device must be used to prevent interconnections.

2

• Use caution when working on live electrical equipment. Remove jewelry, make sure clothing and shoes are dry, stand on a dry wooden platform or rubber insulating mat and use tools with insulated handles.

ENGINE EXHAUST IS DEADLY!

• Learn the symptoms of carbon monoxide poisoning in this manual and never sleep in the vehicle while the genset is running unless the vehicle is equipped with a working carbon monoxide detector.

• The exhaust system must be installed in accordance with the genset Installation Manual.

Engine cooling air must not be used for heating the working or living space or compartment.

• Inspect for exhaust leaks at every startup and after every eight hours of running.

• Make sure there is ample fresh air when operating the genset in a confined area.

FUEL IS FLAMMABLE AND EXPLOSIVE

• Do not smoke or turn electrical switches ON or

OFF where fuel fumes are present or in areas sharing ventilation with fuel tanks or equipment. Keep flame, sparks, pilot lights, arc-producing equipment and switches and all other sources of ignition well away.

• Fuel lines must be secured, free of leaks and separated or shielded from electrical wiring.

Leaks can lead to explosive accumulations of gas. Natural gas rises when released and can accumulate under hoods and inside housings and buildings. LPG sinks when released and can accumulate inside housings and basements and other below-grade spaces. Prevent leaks and the accumulation of gas.

BATTERY GAS IS EXPLOSIVE

• Wear safety glasses.

• Do not smoke.

• To reduce arcing when disconnecting or reconnecting battery cables, always disconnect the negative () battery cable first and reconnect it last.

MOVING PARTS CAN CAUSE SEVERE

PERSONAL INJURY OR DEATH

S Disable the automatic genset starting feature(AGS) of an inverter−charger or other automat−ic starting device before servicing the genset toavoid unexpected starting.

• Do not wear loose clothing or jewelry near moving parts such as PTO shafts, fans, belts and pulleys.

• Keep hands away from moving parts.

• Keep guards in place over fans, belts, pulleys, and other moving parts.

MOBILE 7

3

Introduction

ABOUT THIS MANUAL

This manual covers the operation and maintenance of the KV series of generator sets (gensets). Each operator should study this manual carefully and observe all of its instructions and safety precautions.

Keep this manual and the Installation Manual with the other vehicle manuals.

Operation, Periodic Maintenance and Trouble-

shooting provide the instructions necessary for operating the genset and maintaining it at top performance. The owner is responsible for performing maintenance in accordance with the PERIODIC

MAINTENANCE SCHEDULE (Page 15). This man-

ual also includes genset specifications, information on how to obtain service and information for California users.

WARNING

This genset is not a life support system. It can stop without warning. Children, persons with physical or mental limitations, and pets could suffer personal injury or death. A personal attendant, redundant power or an alarm system must be used if genset operation is critical.

NAMEPLATE

Model and Serial Numbers: Have the model and

serial numbers handy (gray boxes, Figure 1) when

contacting an Onan dealer for parts, service or product information. Each character is significant. (The last character of the model number is the specification letter, which is important for obtaining the right parts.) Record these numbers in the boxes in Fig-

ure 1 so that they are handy when you need them.

Genuine Onan replacement parts are recommended for best performance and safety.

Federal Emissions Compliance Period: The

Federal Emissions Compliance Period referred to on the nameplate indicates the number of operating hours for which the engine has been shown to meet

Federal emissions requirements. Category

C = 250 hrs, B = 500 hrs, A = 1000 hrs.

2.8KVFA26100K

D000012345

[The engine family designation, engine displacement, statement of compliance with the applicable EPA and / or California emissions regulations, including the compliance period or category, appear in this block on the actual nameplate on the genset.]

RECORD NUMBERS HERE

MODEL NUMBER:

SERIAL NUMBER:

FIGURE 1. TYPICAL NAMEPLATE

4

TYPICAL GENSET

The control panel and the components requiring attention during periodic maintenance (see Periodic

Maintenance) are located behind a removable ac-

cess cover. See Figure 2.

Removing the access cover: Slide the cover latches up and pull the cover outward from the bottom. Lower the cover to remove it from the housing.

Securing the access cover: Position the tabs on the top of the access cover in the openings on the housing. Slide the latches up and push the bottom of the cover in place. Hold the cover in place firmly while releasing the latches to secure the cover.

WARNING

Operating the genset with the access cover removed can result in severe personal injury or equipment damage. Hot components are exposed when the access cover is removed and genset cooling air does not circulate properly. Do not operate the genset with the access cover removed.

The genset itself is usually located behind a door in a compartment somewhere around the perimeter of the vehicle.

REMOVABLE

ACCESS COVER

AIR FILTER

COVER

CARBURETOR ALTITUDE

ADJUST KNOB

(gasoline models only)

MUFFLER

(inside cover)

CONTROL PANEL

(see Figure 3 for details)

FUEL FILTER

(gasoline models only)

OIL FILL CAP

AND DIPSTICK

SPARK PLUG

ACCESS

FIGURE 2. TYPICAL GENSET

OIL DRAIN

(bottom)

5

FUEL RECOMMENDATIONS

WARNING

Gasoline and LPG are highly flammable and explosive and can cause severe per-

sonal injury or death. Do not smoke or turn elec-

trical switches ON or OFF where fuel fumes, tanks or equipment are present or in areas sharing ventilation. Keep flames, sparks, pilot lights, arc-producing equipment and switches and all other sources of ignition well away. Keep a type ABC fire extinguisher in the vehicle.

Gasoline Models

Use clean, fresh unleaded gasoline having a minimum octane rating (Anti-Knock Index) of 87.

CAUTION

Do not use gasoline or gasoline additives containing methanol because methanol can be corrosive to fuel system components.

Avoid using leaded gasoline because of the extra engine maintenance that will be required.

LPG Models

Use clean, fresh HD-5 grade liquified petroleum gas

(LPG) or equivalent product consisting of at least 90 percent propane. Commercial liquified petroleum gas fuels may contain more than 2.5 percent butane which can result in poor fuel vaporization and poor engine starting in low ambient temperatures (below

32° F (0° C).

Satisfactory performance on low-pressure LPG models requires that the LPG vapor be supplied at a pressure within the range indicated in Specifica-

tions.

WARNING

High LPG supply pressure can cause gas leaks which can lead to fire and severe personal injury or death. LPG supply pressure must be adjusted to Specifications by trained and experienced personnel.

ENGINE OIL RECOMMENDATIONS

Use API (American Petroleum Institute) performance Class SJ, SH or SG engine oil, which may be in combination with performance Class CH-4, CG-4 or CF-4 (for example: SJ/CH-4). Also look for the

SAE (Society of Automotive Engineers) viscosity

grade. Referring to Table 1, choose the viscosity

grade appropriate for the ambient temperatures expected until the next scheduled oil change.

Single-grade SAE 30 oil is preferable when temperatures are consistently above freezing. Multigrade oils are better when wide temperature variations are expected.

TABLE 1. OIL VISCOSITY VS. TEMPERATURE

EXPECTED AMBIENT

TEMPERATURES

32° F (0° C) and higher

10° F to 100° F (−12° C to 38° C)

0° F to 80° F (−18° C to 27° C)

−20° F to 50° F (−28° C to 10° C)

SAE VISCOSITY

GRADE

30

15W-40

(OnaMax

TM

)

10W-30

10W-40

5W-30

STARTING BATTERIES

The genset has a 12 volt, direct current (DC) engine cranking and control system. See Specifications

(Page 23) regarding minimum battery ratings for reliable genset cranking, especially in cold weather.

Also see PERIODIC MAINTENANCE SCHEDULE

(Page 15) and the battery manufacturer’s instructions regarding battery maintenance. Reliable genset starting and starter service life depend upon adequate battery system capacity and proper maintenance.

OnaMax is a trademark of the Onan Corporation.

6

GENSET CONTROL PANEL

The genset control panel (Figure 3) is located be-

hind the access cover on the genset (Figure 2). It

has the following features:

Control Switch − This is a rocker switch which re-

turns to its neutral position when you let go. Hold the switch in its START position to crank and start the genset. Press the switch to its STOP position to stop the genset.

Control Fuse − This fuse provides short circuit

protection for the control and remote control circuits.

Line Circuit Breaker − The line circuit breaker pro-

tects the AC power leads connected to the genset from overloads and equipment short circuits.

Stop Start

5 Amp Fuse

AC Circuit Breaker

FIGURE 3. GENSET CONTROL PANEL

REMOTE CONTROL PANEL

The vehicle probably has a control panel inside the vehicle for remote control of the genset. Onan offers three remote control kits as follows:

Remote switch with indicator lamp only (Fig-

ure 4).

Remote switch with indicator lamp and hour

meter (Figure 5).

Remote switch with indicator lamp and DC volt-

meter (Figure 6).

The hour meter (time totalizing meter) records genset operating time in hours. It cannot be reset. See the PERIODIC MAINTENANCE SCHEDULE

(Page 15).

The DC voltmeter indicates whether voltage across the 12 VDC control system and battery is normal. If the indicator consistently stays above or below the normal zone, see MAINTAINING THE BATTERY

AND BATTERY CONNECTIONS (Page 20).

7

FIGURE 4. START/STOP

FIGURE 5. START/STOP & HOUR METER

FIGURE 6. START/STOP & DC VOLTMETER

Operation

WARNING

EXHAUST GAS IS DEADLY!

Exhaust gases contain carbon monoxide, an odorless, colorless gas. Carbon monoxide is poisonous and can cause unconsciousness and death. Symptoms of carbon monoxide poisoning include:

Dizziness

Muscular Twitching

Throbbing in Temples

Headache

Weakness and Sleepiness Inability to Think Clearly

Nausea

Vomiting

IF YOU OR ANYONE ELSE EXPERIENCES ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH

AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the genset and do not operate it until it has been inspected and repaired.

Never sleep in the vehicle with the genset running unless the vehicle is equipped with a working carbon monoxide detector. Primary protection against inhaling carbon monoxide, however, is proper installation of the exhaust system, daily (every eight hour) inspection for visible and audible exhaust system leaks.

CONDUCTING THE PRE-START CHECKS

Before the first start of the day and after every eight hours of operation, inspect the genset as instructed under CONDUCTING GENERAL INSPECTIONS

(Page 16). Keep a log of maintenance and the hours run and perform any maintenance that may be due.

See Returning the Genset to Service (Page 14) if the vehicle has been in storage.

Before each start:

1. Make sure all vehicle CO detectors are working.

2. Check for signs of fuel and exhaust leaks and for damage to the exhaust system.

3. To prevent overheating and to reduce fouling with dust and debris, make sure the genset’s normal ground clearance is not being reduced by sloping ground, curbs, logs or other objects.

Repark the vehicle if necessary and/or remove any objects blocking the air inlet or air outlet.

4. Turn off the air conditioner and other large appliances.

STARTING THE GENSET

Start the genset from the genset control panel or re-

mote control panel inside the vehicle (Page 7).

1. Push and hold the switch at START until the genset starts. (The remote START switch inside the vehicle should have a lamp which lights to indicate that the genset has started and is running.)

CAUTION

Cranking for longer than 10 seconds at a time can overheat and damage the starter. Do not crank for more than 10 seconds at a time and wait at least 30 seconds before trying again.

2. For top performance and engine life, especially in colder weather, let the engine warm up for two minutes before connecting appliances.

3. Check for fuel and exhaust leaks. Stop the genset immediately if there is a fuel or exhaust leak and have it repaired.

4. See Troubleshooting (Page 21) if the engine

does not crank or start after several tries.

5. Always secure the genset compartment door after starting the genset at the genset control panel.

WARNING

Proper engine cooling requires that the access cover be secured during operation. Also, hot engine parts can cause severe burns. Always secure the access cover as soon as the engine starts up.

8

STOPPING THE GENSET

Turn off the air conditioner and other large appliances and let the genset run for two minutes to cool down. This reduces backfiring and run-on.

Then press the switch to STOP to stop the genset.

RESTARTING THE GENSET

If the genset shuts down, disconnect or turn off as many appliances as possible and try restarting the genset. Reconnect only as many appliances as will not overload the genset or cause the circuit breaker to trip.

LOADING THE GENSET

The genset can power AC motors, air conditioners,

AC/DC converters and other appliances. How much appliance load* can be serviced depends upon the genset power rating. The genset will shut down or its circuit breakers will trip if the sum of the loads exceeds genset power.

To avoid overloading the genset and causing shutdowns, compare the sum of the loads of the appliances that are likely to be used at the same

time to the power rating of the genset. Use Table 2

or the ratings on the appliances themselves (if so marked) to obtain the individual appliance loads. It

may be necessary to run fewer appliances at the same time—the sum of the loads must not be greater than genset rating.

Note that the genset may shut down due to overload—even though the sum of the loads is less than genset rating—when a large motor or air conditioner is started last or cycles off and then on again. The reason for this is that motor startup load is much larger than running load. It may be necessary to

run fewer appliances when large motors and air conditioners are cycling on and off.

TABLE 2. TYPICAL APPLIANCE LOADS

Appliance

Air Conditioner

Battery Charger

DC Converter

Refrigerator

Microwave Oven

Electric Frying Pan or Wok

Electric Stove Element

Electric Water Heater

Electric Iron

Electric Hair Dryer

Coffee Percolator

Television

Radio

Electric Drill

Electric Broom

Electric Blanket

Load (watts)

1400-2000

Up to 800

300-500

600-1000

1000-1500

1000-1500

350-1000

1000-1500

500-1200

800-1500

550-750

200-600

50-200

250-750

200-500

50-200

Note also that air density decreases as altitude increases, causing genset engine power to decrease.** Power decreases approximately 3.5

percent of rated power each 1000 feet (305 m) of in-

crease in elevation. See Table 3 for typical calcula-

tions. It may be necessary to run fewer

appliances at higher altitudes.

TABLE 3. POWER VS. ALTITUDE

Elevation above Mean

Sea Level up to 500 feet

(152 m)

2500 ft (762 m)

5500 ft (1676 m) above 5500 ft

(1676 m)

Maximum Genset

Power*

2800 watts (rated)

2604 watts

2310 watts

2310 watts minus 98 watts each 1000 ft (305 m)

* This table does not take into account the effect circuit breakers may have in limiting maximum power.

* Appliance load and genset power are measured in terms of watts (W) or kilowatts (kW), where 1 kilowatt (kW) = 1000 watts (W).

** Power decreases even though the altitude adjust knob is set correctly (Page 11).

9

RESETTING CIRCUIT BREAKERS

If a circuit breaker in the main power distribution

panel of the vehicle or on the genset (Figure 7) trips,

either a circuit shorted or too many appliances were running. Note that the genset will continue to run after a circuit breaker trips.

If a circuit breaker trips, disconnect or turn off as many loads as possible and reset the circuit breaker. (Push the circuit breaker to OFF to reset it and then to ON to reconnect the circuit.) If the circuit breaker trips right away, either the electrical distribution system has a short or the circuit breaker is faulty. Call a qualified electrician.

If the circuit breaker does not trip, reconnect the appliances, one by one, up to a total load that does not overload the genset or cause the circuit breaker to trip. If a circuit breaker trips right away when an appliance is connected, the appliance probably has a short.

Electrical appliances and tools must be used and maintained properly and be properly grounded to cause the line circuit breakers to trip when short circuits occur.

WARNING

Short circuits in electrical appliances and tools can cause fire and electrical shock leading to severe personal injury or death. Read and follow the equipment and tool manufacturer’s instructions and warnings regarding use, maintenance and proper grounding.

CONNECTING SHORE POWER

A vehicle with provisions for connecting utility power must have an approved device to keep the genset and utility from being interconnected. See the genset Installation Manual for more information.

WARNING

Backfeed to shore power can cause electric shock resulting in severe personal injury or death and damage to equipment. The vehicle must have an approved device to prevent the genset from being interconnected with shore power.

FIGURE 7. AC CIRCUIT BREAKER

10

OPERATING IN COLD WEATHER

Pay particular attention to the following items when operating the genset in cold weather:

1. Make sure engine oil viscosity is appropriate for the ambient temperatures. Change oil if there is a sudden drop in temperature. See ENGINE

OIL RECOMMENDATIONS (Page 6).

2. Reset the carburetor (gasoline models only) for

altitude (Figure 8).

3. Perform spark plug maintenance (Page 18).

4. Perform battery maintenance (Page 20).

OPERATING IN HOT WEATHER

Pay particular attention to the following items when operating the genset in hot weather:

1. Make sure nothing blocks the airflow to and from the set.

2. Make sure engine oil viscosity is appropriate for the ambient temperatures. See ENGINE OIL

RECOMMENDATIONS (Page 6).

3. Keep the genset clean.

4. Perform maintenance due. See PERIODIC

MAINTENANCE SCHEDULE (Page 15).

5. Reset the carburetor (gasoline models only) for

altitude (Figure 8).

OPERATING AT HIGH ALTITUDE

(GASOLINE MODELS ONLY)

For best fuel economy and genset operation reset

the carburetor for the current altitude (Figure 8).

Look at road maps and road signs. For the effect of altitude on maximum power, see LOADING THE

GENSET (Page 9).

CAUTION

Operating the genset at low altitude with a high altitude setting can cause power loss, overheating and engine damage. Always reset when returning to lower altitudes.

ALTITUDE

ADJUST

KNOB

FIGURE 8.

ALTITUDE ADJUST KNOB

(GASOLINE MODELS ONLY)

11

OPERATING IN DUSTY ENVIRONMENTS

Pay particular attention to the following items when operating the genset in dusty environments:

1. Do not let dirt and debris accumulate inside the genset compartment. Keep the genset clean.

2. Perform air cleaner maintenance more often

(Page 15).

3. Change engine oil every 50 hours.

4. Keep containers of engine oil that have been opened tightly closed to keep out dust.

BREAKING IN A NEW ENGINE

Proper engine break-in on a new genset or on one with a rebuilt engine is essential for top engine performance and acceptable oil consumption. Run the genset at approximately 1/2 rated power for the first

2 hours and then at 3/4 rated power for 2 more

hours. See LOADING THE GENSET (Page 9).

Proper engine oil and oil level are especially critical during break-in because of the higher engine temperatures that can be expected. Change the oil if not appropriate for the ambient temperatures during

break-in (Page 6). Check oil level twice a day or

every 4 hours during the first 20 hours of operation and change the oil after the first 20 hours of operation.

EXERCISING THE GENSET

Exercise the genset at least 2 hours each month if use is infrequent. Run the genset at approximately

1/2 rated power. See LOADING THE GENSET

(Page 9). A single two hour exercise period is bet-

ter than several shorter periods.

Exercising a genset drives off moisture, re-lubricates the engine, replaces stale fuel in fuel lines and carburetor and removes oxides from electrical contacts and generator slip rings. The result is better starting, more reliable operation and longer engine life.

STORING THE GENSET

Proper storage is essential for preserving top genset performance and reliability when the genset cannot be exercised regularly and will be idle for more than 120 days.

Storing the Genset

1. Gasoline Models − Fill the fuel tank with fresh fuel and add a fuel preservative (OnaFresh

TM

), following the instructions on the container label. Unless a preservative (stabilizer) is added, the gasoline in the fuel system will deteriorate causing fuel system corrosion, gum formation and varnish-like deposits which can lead to hard starting and rough operation.

Then run the genset for about 10 minutes at approximately 1/2 rated power to fill the fuel lines with the fresh fuel and preservative.

WARNING

Gasoline preservatives (stabilizers) are toxic. Follow the instructions on the container label. Avoid skin contact.

Wash your hands with soap and water after dispensing the fluid.

2. Change the engine oil and attach a tag indicat-

ing its oil viscosity (Page 6).

3. Remove the air filter and restart the genset.

While the genset is running, spray an engine fogger (OnaGard

TM

) into the carburetor, following the instructions on the container label, and then stop the genset. The fogger leaves a protective coat of oil on the internal surfaces of the engine.

4. Disconnect the battery cables, negative () cable first, from the starting battery and store the battery according to the battery manufac-

turer’s recommendations (Page 20).

5. Plug the exhaust tail pipe to keep out dirt, moisture, rodents and such.

6. Close the fuel supply valve (if so equipped).

7. Turn OFF the AC circuit breaker (Page 10).

OnaFresh and OnaGard are trademarks of Onan Corporation.

12

WARNING

Do not open the carburetor drain when the engine is hot. Close the drain immediately after draining. Failure to heed this warning can lead to fire resulting in severe personal injury or death.

8. Gasoline Models − Draining the carburetor float bowl prevents deposits of gum from clogging the tiny passages in the carburetor as the gasoline in the bowl evaporates during storage.

If the carburetor has a drain (Figure 9), drain it

as follows:

A. Let the engine cool down thoroughly.

B. Place paper towels under the drain to absorb all of the drainage (less than 1/2 cup).

C. Open the drain valve by turning counterclockwise with a screwdriver.

D. Immediately close the drain valve after draining by turning clockwise with a screwdriver until just snug.

9. LPG Models − Check local ordinances if the vehicle is to be garaged. Generally, ordinances require that the LPG system be leak-free, that the LPG container not be filled beyond specified limits, that the container shutoff valve be closed and that the vehicle not be parked near sources of heat or ignition.

WARNING

LPG leaks can lead to explosive accumulations in pits, sumps or other below-grade locations. Comply with all local ordinances regarding the garaging of vehicles with LPG engine fuel systems.

FLOAT BOWL

DRAIN VALVE

FIGURE 9. CARBURETOR DRAIN VALVE

13

Returning The Genset To Service

1. Check the oil tag on the genset and change the oil if the viscosity indicated is not appropriate for

the temperatures expected (Page 6).

2. Reconnect the starting battery, negative () ca-

ble last (Page 20).

3. Remove the plug from the exhaust tailpipe.

4. Change the air filter element if it is dirty.

5. Open the fuel supply valve (if so equipped).

6. Inspect the genset (Page 16).

7. Start the genset. There may be smoke and rough operation for a few minutes until the oil from the fogger burns off. If the engine does not start, clean or replace the spark plug, which may have been fouled by the fogger.

8. Turn ON the AC circuit breaker (Page 10) when

the genset is ready to power appliances.

14

Periodic Maintenance

Periodic maintenance is essential for top perfor-

mance and long genset life. Use Table 4 as a guide

for normal periodic maintenance. In hot and dusty environments some maintenance procedures should be performed more frequently, as indicated by the footnotes in the table. Keeping a log of maintenance performed and hours run will help you keep genset maintenance regular and provide a basis for

supporting warranty claims (Page 26).

Maintenance, replacement or repair of emission control devices and systems may be performed by any engine repair establishment or individual. However, warranty work must be completed by an authorized Onan dealer.

MAINTENANCE

PROCEDURE

TABLE 4. PERIODIC MAINTENANCE SCHEDULE

MAINTENANCE FREQUENCY

Every Day or Every 8

Hours

After First

20 Hours

Every

Month

Every 50

Hours

Every 150

Hours

Every 200

Hours

Every 450

Hours g e

P a

General Inspection

Check Engine Oil Level

Clean and Check Battery

Clean Spark Arrestor

Change Engine Oil

Replace Air Filter Element

Clean Engine Cooling Fins

Replace Spark Plug

X

X

X

1

X

3

X

X

2, 3, 4

Replace Fuel Filter

Adjust Valve Lash

Clean/Replace Cylinder Head

1 − As a part of engine break-in, change the engine oil after the first 20 hours of operation.

2 − Perform more often when operating in dusty environments.

3 − Perform more often when operating in hot weather.

4 − Perform at least once a year.

5 − Perform sooner if engine performance deteriorates.

6 − Must be performed by a qualified mechanic (authorized Onan dealer).

X

2

X

2

X

5

X

5

X

6

X

6

17

18

18

16

17

20

19

20

15

CONDUCTING GENERAL INSPECTIONS

Inspect the genset before the first start of the day and after every eight hours of operation.

Oil Level

Check engine oil level (Page 17).

Exhaust System

Look and listen for exhaust system leaks while the genset is running. Shut down the genset if a leak is found and have it repaired before operating the genset again.

Look for openings or holes between the genset compartment and vehicle cab or living space if the genset engine sounds louder than usual. Have all such openings or holes closed off or sealed to prevent exhaust gases from entering the vehicle.

Replace dented, bent or severely rusted sections of the tailpipe and make sure the tailpipe extends at least 1 inch (25.4 mm) beyond the perimeter of the vehicle.

Park the vehicle so that the genset exhaust gases can disperse away from the vehicle. Barriers such as walls, snow banks, high grass, brush and other vehicles can cause exhaust gases to accumulate in and around the vehicle.

Do not operate power ventilators or exhaust fans while the vehicle is standing with the genset running. The ventilator or fan can draw exhaust gases into the vehicle.

Check all CO monitors to assure proper operation.

WARNING

EXHAUST GAS IS DEADLY! Do not operate the genset if there is an exhaust leak or any danger of exhaust gases entering or being drawn into the vehicle.

WARNING

Do not park the vehicle in high grass or brush. Contact with the exhaust system can cause a fire.

Fuel System

Check for leaks at the hose, tube and pipe fittings in the fuel supply system while the genset is running and while it is stopped. Do not use a flame to check

for LPG leaks. Check flexible fuel hose sections for cuts, cracks, and abrasions. Make sure the fuel line is not rubbing against other parts. Replace worn or damaged fuel line parts before leaks occur.

If you smell gas, close the LPG container shutoff valve and have the genset serviced before using it again.

WARNING

Gasoline and LPG are highly flammable fuels and can cause severe personal injury or death. Repair leaks right away.

Battery Connections

Check the battery terminals for clean, tight connections. Loose or corroded connections have high electrical resistance which makes starting harder. See MAINTAINING THE BATTERY AND

BATTERY CONNECTIONS (Page 20).

WARNING

Arcing at battery terminals or light switch or other equipment or flames and sparks can ignite battery gas causing severe personal injury—Ventilate battery area before working on or near battery—Wear safety glasses—Do not smoke—Switch trouble light ON / OFF away from battery—Do not disconnect battery cables while genset is running or vehicle battery charging system is on—Always disconnect negative (−) cable first and reconnect it last.

Mechanical

Look for mechanical damage and listen for unusual noises. Check the genset mounting bolts.

Check to see that the genset air inlet and outlet openings are not clogged with debris or blocked.

Clean accumulated dust and dirt from the genset.

Do not clean the genset while it is running or still hot.

Protect the generator, air cleaner, control panel, and electrical connections from water, soap and cleaning solvents.

WARNING

Always wear safety glasses when using compressed air, a pressure washer or a steam cleaner to avoid severe eye injury.

16

CHECKING ENGINE OIL LEVEL

Park the vehicle on level ground and stop the genset before checking engine oil level.

WARNING

Crankcase pressure can blow hot engine oil out the fill opening causing severe burns. Always stop the genset before removing the oil fill cap.

1. Unscrew the oil fill cap and wipe oil off the dip-

stick (Figure 10). Reinsert the dipstick, but do

not screw the cap down. Remove the dipstick

again and check the oil level on the dip stick.

2. Add or drain oil as necessary. See ENGINE OIL

RECOMMENDATIONS (Page 6). Keep the

oil level between the FULL and ADD marks.

CAUTION

Too much oil can cause high oil consumption. Too little oil can cause severe engine damage. Keep the oil level between the FULL and ADD marks.

3. Screw the oil fill cap back on securely.

CHANGING ENGINE OIL

WARNING

State and federal agencies have determined that contact with used engine oil can cause cancer or reproductive toxicity. Try to avoid skin contact and breathing of vapors. Use rubber gloves and wash exposed skin.

Refer to Table 4 for scheduled engine oil change.

Change oil more often in hot and dusty environments.

1. Run the engine until warm, stop it and remove

the oil fill cap (Figure 10).

2. Place a pan under the oil drain plug and remove

the plug (Figure 11) with a 14 mm socket. Let

all oil drain from the engine and then secure

the drain plug. If you have a torque wrench, tighten the plug to 21 lbs-ft (27 N-m).

3. Refill with 1 quart (0.95 l) of oil. See ENGINE

OIL RECOMMENDATIONS (Page 6). Check

the oil level and add or drain oil as necessary.

4. Screw the oil fill cap on securely.

5. Dispose of the used oil in accordance with local environmental regulations.

OIL FILL CAP AND

DIPSTICK

FILL TO HERE

DO NOT RUN GENSET IF THE OIL

LEVEL IS BELOW THIS MARK

FIGURE 10. CHECKING ENGINE OIL LEVEL

OIL DRAIN PLUG

FIGURE 11. OIL DRAIN PLUG

17

REPLACING THE AIR FILTER ELEMENT

Refer to Table 4 for scheduled air filter replacement.

Under dusty operating conditions inspect and change the air filter element more often. To change

the air filter element (Figure 12), lift the filter cover

out of the scroll housing and pull the filter retainer straight out. Install the new filter with the open end of the filter facing the carburetor, as shown.

REPLACING THE SPARK PLUG

Refer to Table 4 for scheduled spark plug replace-

ment. (The genset has one spark plug, Figure 13).

The spark plug must be in good condition for proper engine starting and performance. A spark plug that fouls frequently or has heavy soot deposits indicates that the engine needs service. See Trouble-

shooting (Page 21).

Always thread the spark plug in by hand until it seats, to prevent crossthreading, and torque to

13 lbs-ft (17 N-m). If you don’t have a torque wrench, turn the spark plug an additional 1/4 turn, if being reused, or 3/8 to 1/2 turns if new.

RETAINER

FILTER COVER AIR FILTER

FIGURE 12. AIR FILTER ELEMENT

.

GAP

FIGURE 13. SPARK PLUG

18

CLEANING THE SPARK ARRESTOR

Refer to Table 4 for scheduled cleaning of the spark

arrestor muffler (which meets U.S. Forest Service requirements). Cleaning is required for maximum genset performance.

WARNING

A hot muffler can cause severe burns. Let the muffler cool down before removing the spark arrestor screen.

The spark arrestor screen is mounted inside the

muffler outlet (Figure 14). Clean as follows:

1. Loosen the U-bolt clamp that secures the tailpipe to the muffler (inside the genset housing) and move the tailpipe aside.

2. Remove the screw that secures the spark arrestor tube/screen inside the muffler outlet.

3. Remove the spark arrestor tube and inspect the screen inside for damage and clogging.

Replace if damaged.

4. Lightly tap the spark arrestor and remove any remaining deposits with a wire brush. Use a commercial solvent to loosen hard deposits.

(Carefully follow the solvent manufacturer’s instructions and safety precautions.)

5. Reinstall the spark arrestor and tail pipe.

MOUNTING

SCREW

SPARK ARRESTOR

TUBE

FIGURE 14. SPARK ARRESTOR

19

REPLACING THE FUEL FILTER

Refer to Table 4 for scheduled replacement of the

fuel filter (Figure 15, gasoline models only).

Take care to spill as little fuel as possible when disconnecting the filter from the fuel line. Close any shut off valve in the fuel line and let the engine cool down before disconnecting the fuel line so that it cannot ignite any fuel that is spilled. The filter is removable by loosening the hose clamps shown.

WARNING

Gasoline is highly flammable and can cause severe personal injury or death—Let the engine cool and close any fuel line shutoff valve before disconnecting the fuel line from the filter—Do not smoke or turn electrical switches

ON or OFF where fuel fumes, tanks or equipment are present or in areas sharing ventilation.

Keep flame, sparks, pilot lights, arc-producing equipment and switches and all other sources of ignition well away. Keep a type ABC fire extinguisher in the vehicle.

MAINTAINING THE BATTERY AND

BATTERY CONNECTIONS

WARNING

Arcing at battery terminals or light switch or other equipment or flames and sparks can ignite battery gas causing severe personal injury—Ventilate battery area before working on or near battery—Wear safety glasses—Do not smoke—Switch trouble light ON / OFF away from battery—Do not disconnect battery cables while genset is running or vehicle battery charging system is on—Always disconnect negative (−) cable first and reconnect it last.

Refer to Table 4 for scheduled battery maintenance,

referring to the battery manufacturer’s instructions.

Have the battery charging system serviced if DC system voltage is consistently low or high. Always:

1. Keep the battery case and terminals clean and dry and the terminals tight.

2. Remove battery cables with a battery terminal puller.

3. Make sure which terminal is positive (+) and which is negative () before making battery connections, always removing the negative () cable first and reconnecting it last to reduce arcing.

FIGURE 15. FUEL FILTER

20

Troubleshooting

Table 5 provides basic troubleshooting guidance. If

you fail to resolve the problem after taking the corrective actions suggested, contact an authorized

Onan dealer. See How to Obtain Service (Page 25).

TABLE 5. TROUBLESHOOTING

WARNING

Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions.

Problem

1.

Engine fails to crank

2.

Engine cranks slowly

3.

Engine cranks but fails to start

4.

Engine runs but stops or surges

5.

Genset stalls or circuit breakers trip

6.

No electrical power when genset running

7.

DC voltmeter (Page 7)

indicates low voltage

8.

Black smoke out tailpipe

Corrective Action

a.

Try starting at the genset rather than at the remote control.

b.

Clean and tighten the positive (+) and negative () battery cable connections at the battery and at the genset.

c.

Recharge the battery. Refer to the battery manufacturer’s recommendations.

a.

Disconnect the air conditioner and other large loads.

b.

Clean and tighten the positive (+) and negative () battery cable connections at the battery and at the genset.

c.

Recharge the battery. Refer to the battery manufacturer’s recommendations.

d.

Change the engine oil to oil having the proper viscosity for the ambient tem-

perature (Pages 6 and 17).

a.

Gasoline Models − Check the fuel tank and fill if necessary.

b.

LPG Models − Check and fill the LPG container, as necessary. On cold days

the LPG container may have to be kept at least half full to provide the rate of vaporization necessary to keep up with genset fuel demand.

c.

LPG Models − Regap the spark plug to 0.020 inch.

d.

Open any closed fuel shut off valve.

e.

Check engine oil level and add or drain oil, as necessary (Page 17).

f.

Service the air cleaner (Page 18).

g.

Secure the spark plug lead on the spark plug.

h.

Replace the spark plug (Page 18).

i.

Gasoline Models − Replace the fuel filter (Page 20).

a.

Gasoline Models − Check the fuel tank and fill if necessary.

b.

LPG Models − Check and fill the LPG container, as necessary. On cold days

the LPG container may have to be kept at least half full to provide the rate of vaporization necessary to keep up with genset fuel demand.

c.

Check engine oil level and add or drain oil, as necessary (Page 17).

d.

Gasoline Models − Reset the carburetor for altitude (Page 11).

e.

Secure the spark plug lead on the spark plug.

f.

Replace the spark plug (Page 18).

a.

Connect fewer appliances (Page 9).

b.

LPG Models − Check the fuel tank and fill as necessary. On cold days the

LPG container may have to be kept at least half full to provide the rate of vaporization necessary to keep up with the genset fuel demand.

a.

Reset tripped circuit breakers (Page 10).

b.

Unless there is an automatic power transfer switch, plug the vehicle power cord into the genset power output receptacle (if so equipped) or turn the vehicle power selector switch to its genset position (if so equipped).

a.

Clean and tighten the positive (+) and negative () battery cable connections at the battery and the genset.

b.

Recharge the battery. Refer to the battery manufacturer’s recommendations.

Service the air cleaner (Page 18).

21

FAULT CODE BLINKING

At fault shutdown, the status indicator light will repeatedly blink sets of 1, 2, 3 or 4 blinks.

S One blink indicates shutdown due to high engine coolant temperature.

S Two blinks indicate shutdown due to a loss of engine oil pressure.

S Three blinks indicate a service fault. Press

Stop once to cause the two-digit, second-level

shutdown code to blink. (Pressing Stop again will stop the blinking.) The two-digit code consists of 1, 2, 3, 4 or 5 blinks, a brief pause, and then 1 to 9 blinks. The first set of blinks represents the tens digit and the second set of blinks the units digit of the shutdown code number.

For example, shutdown code No. 36 appears as: blink-blink-blink—pause—blink-blink-blink-blink-blink-blink—

long pause—repeat

S Four blinks indicate that cranking time exceeded 35 seconds.

Fault Code Nos. 1, 2, 3, and 4 are first level faults.

Pay close attention to the pause sequence to avoid interpreting first level faults as second-level Fault

Codes Nos. 11, 22, 33, or 44.

To avoid the possibility of anyone misinterpreting

Code Nos. 3 and 4 as Code Nos. 33 and 44, the latter have not been assigned faults.

RESTORING FAULT CODE BLINKING

The fault code stops blinking after five minutes.

Press Stop three times within three seconds to restore fault code blinking.

Note: The last fault logged will blink even though the condition that caused the shutdown may have been corrected.

22

Specifications

FUEL CONSUMPTION:

No load

Half load

Full load

GASOLINE MODELS

2.8 KY 2.0 KY

Gasoline

0.16 gph (0.6 l/h)

0.28 gph (1.1 l/h)

0.46 gph (1.7 l/h)

Gasoline

0.16 gph (0.6 l/h)

0.23 gph (0.9 l/h)

0.32 gph (1.2 l/h)

2.5 KY

LPG MODELS

GENERATOR: 2-Pole Revolving Field, Self-Excited, Electronically Regulated, 1-Phase

Power

Frequency

Voltage

2800 watts

60 Hertz*

120 volts

2000 watts

50 Hertz

220 volts

Current

Speed

23.3 amperes

3600 rpm

9.1 amperes

3000 rpm

2500 watts

60 Hertz*

120 volts

20.8 amperes

3600 rpm

LPG

1.0 lbs/h (0.44 kg/h)

1.5 lbs/h (0.68 kg/h)

2.5 lbs/h (1.1 kg/h)

2.0 KY

2000 watts

50 Hertz

220 volts

9.1 amperes

3000 rpm

LPG

0.9 lbs/h (0.40 kg/h)

1.3 lbs/h (0.59 kg/h)

2.1 lbs/h (.92 kg/h)

ENGINE: 1-Cylinder, 4-Cycle, Spark-Ignited, OHV, Air Cooled

Bore 2.64 inch (67 mm)

Stroke

Displacement

2.2 inch (56 mm)

12 inch

3

(197 cc)

Compression Ratio

Oil Capacity**

Intake Valve Clearance (Cold)

Exhaust Valve Clearance (Cold)

Spark Plug Gap

8.5 : 1

1 quart (0.95 l)

0.002 inch (0.05 mm)

0.002 inch (0.05 mm)

0.025 inch (0.64 mm)

13 lbs-ft (17 N-m) Spark Plug Tightening Torque

Ignition Timing (magneto type ignition)

LPG Vapor

Supply Pressure (Range)

25° BTDC, non-adjustable

DC SYSTEM:

Nominal Battery Voltage

Minimum Battery Cold Cranking

Capacity

Control Fuse

12 volts

360 amperes

5 amperes

* − 60 Hertz models are Listed by CSA and the U.S. Testing Company.

** −See Periodic Maintenance for oil filling instructions.

2.64 inch (67 mm)

2.2 inch (56 mm)

12 inch

3

(197 cc)

8.5 : 1

1 quart (0.95 l)

0.002 inch (0.05 mm)

0.002 inch (0.05 mm)

0.020 inch (0.51 mm)

13 lbs-ft (17 N-m)

25° BTDC, non-adjustable

9 to 13 inch (229 to 330 mm)

W.C. (water column)

12 volts

360 amperes

5 amperes

23

Information for California Genset Users

This genset meets the requirements of California’s

Exhaust Emissions Standards as stated on the

nameplate. Figure 1 (Page 4) illustrates where

this information appears on the nameplate.

As a California user of these gensets, please be aware that unauthorized modifications or replacement of fuel, exhaust, air intake, or speed control system components that affect engine emissions are prohibited. Unauthorized modification, removal or replacement of the genset label is prohibited.

You should carefully review Operator (Owner),

Installation and other manuals and information you receive with your genset. If you are unsure that the installation, use, maintenance or service of your genset is authorized, you should seek assistance from an approved Onan dealer.

California genset users may use Table 6 as an aid in

locating information related to the California Air Resources Board requirements for emissions control.

Genset Warranty Information

Engine Valve Lash

Engine Ignition Timing

Engine Fuel Requirements

Engine Lubricating Oil Requirements

Engine Fuel Mixture Settings

Engine Adjustments

TABLE 6. EMISSIONS CONTROL INFORMATION

Engine Emission Control System

The California emissions control warranty statement is located in the same packet of information as this manual when the genset is shipped from the factory.

See Specifications (Page 23).

See Specifications (Page 23).

Gasoline Models: The engine is certified to operate on un-

leaded gasoline. See Fuel Recommendations (Page 6).

LPG Models: The engine is certified to operate on LPG vapor.

See Fuel Recommendations (Page 6).

See ENGINE OIL RECOMMENDATIONS (Page 6).

Gasoline Models: These genset engines have precisionmanufactured carburetors which are not adjustable except for

altitude (Figure 8, Page 11).

LPG Models: These genset engines have precision-manufactured carburetors which are not adjustable.

None.

The engine emissions control system consists of inherent engine design.

24

How to Obtain Service

When you need service, parts, or product literature

(such as the Service Manual) for your genset, contact the nearest authorized distributor. Onan has factory-trained representatives to handle your needs for genset parts and service.

Call 1-800-888-ONAN to contact the nearest Cummins/Onan or Onan-only distributor in the United

States or Canada. (This automated service utilizes touch-tone phones only). Select OPTION 1

(press 1) to be automatically connected to the distributor nearest to you.

If you are unable to contact a distributor using the automated service, consult the Yellow Pages. Typically, our distributors are listed under:

GENERATORS − ELECTRIC,

ENGINES − GASOLINE OR DIESEL, or

RECREATIONAL VEHICLES − EQUIPMENT,

PARTS AND SERVICE.

If you are outside North America, call Onan Corporation at 1−763−574−5000 from 7:30 AM to

4:00 PM, Central Standard Time, Monday through

Friday, or fax 1−763−528−7229.

Before calling for service, have the following information available:

1. The complete genset model number and serial

number. See Model Identification (Page 4).

2. The date of purchase

3. The nature of the problem. See Trouble-

shooting (Page 21).

If you have difficulty in arranging service or resolving a problem, please contact the Service Manager at the nearest Cummins/Onan distributor for assistance.

WARNING

Improper service or replacement of parts can result in severe personal injury, death, and/or equipment damage. Service personnel must be trained and experienced in performing electrical and/or mechanical service.

25

Maintenance Record

Record all periodic and unscheduled maintenance and service. See Periodic Maintenance (Page 15).

DATE

HOUR

METER

READING

MAINTENANCE OR SERVICE PERFORMED

Record the name, address, and phone number of your authorized Onan service center.

26

Cummins Power Generation

1400 73rd Ave. NE

Minneapolis, MN 55432 USA

Phone 1 763 574 5000

Toll-free 1 800 888 6626

Fax 1 763 574 5298

Email www.cumminsonan.com/contact www.cumminsonan.com

Cummins

R

, Onan

R

, the “C” logo, and “Performance you rely on.” are trademarks of Cummins Inc.

E2009 Cummins Power Generation, Inc. All rights reserved.

advertisement

Key Features

  • Start/stop function
  • Circuit breakers
  • Control panel
  • Remote control
  • Altitude adjustment
  • Preventive maintenance guidelines

Frequently Answers and Questions

How do I start the RV generator?
To start the generator, locate the control panel and press and hold the START switch until the generator starts. Ensure that the remote START switch inside the vehicle is lit to confirm the generator has begun running.
How do I stop the RV generator?
To stop the generator, first turn off all appliances and let it run for two minutes to cool down. Then press the switch on the control panel to STOP.
How do I reset the circuit breakers on the generator?
If the circuit breaker trips, disconnect or turn off as many appliances as possible and then reset the circuit breaker by pressing it to OFF and then to ON. If the circuit breaker continues to trip immediately, it might indicate a short circuit or a faulty breaker. Contact a qualified electrician for assistance.