Pentair 48ES NXT, 51ES NXT Stager Controller Service Manual
Below you will find brief information for Stager Controller 48ES NXT, Stager Controller 51ES NXT. These documents are service manuals for Pentair's 48ES and 51ES NXT Stager Controllers, providing detailed instructions on configuring, operating, troubleshooting, and maintaining these devices.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
48ES and 51ES NXT Stager Controller
Service Manual
TABLE OF CONTENTS
NXT STAGER DIMENSIONS .................................................2
SYSTEM SPECIFICATIONS 48ES AND 51ES SERIES ........2
SYSTEM DEFINITIONS .........................................................3
SYSTEM OPERATION IN SERVICE
(SYSTEM 14-DEMAND) .........................................................4
TIMER DISPLAY FEATURES.................................................5
NETWORK/COMMUNICATION
CABLES & CONNECTIONS ..................................................5
TIMER OPERATION ..............................................................6
MASTER PROGRAMMING MODE FLOW CHART ...............7
USER PROGRAMMING MODE FLOW CHART ....................9
DIAGNOSTIC PROGRAMMING MODE FLOW CHART ........9
PLUMBING DIAGRAMS .........................................................11
SOLENOID USE.....................................................................14
STAGER CONTROLLER, 48ES, NEMA 4 24V/50-60Hz
ASSEMBLY ............................................................................15
STAGER CONTROLLER, 51ES, NEMA 4 24V/50-60Hz
ASSEMBLY ............................................................................16
WIRING DIAGRAM 48/51ES STAGER CONTROLLER ........17
TROUBLESHOOTING ...........................................................18
SERVICE ASSEMBLIES ........................................................19
IMPORTANT PLEASE READ:
• The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.
• This manual is intended as a guide for service of the controller only. System installation requires information from a number of suppliers not known at the time of control manufacture. This product should be installed by a plumbing professional.
• This product must be installed in compliance with all state and municipal plumbing and electrical codes.
Permits may be required at the time of installation.
• If daytime operating pressure exceeds 80 psi, nighttime pressures may exceed pressure limits. A pressure reducing valve must be installed if pressure exceeds 125 psi.
• Do not install the unit where temperatures may drop below 32°F (0°C) or above 110°F (43°C).
• Do not place the unit in direct sunlight. Black units will absorb radiant heat increasing internal temperatures.
• Do not strike the controller or any of the components.
• Warranty of this product extends to manufacturing defects. Misapplication of this product may result in failure to properly condition water, or damage to product.
• A prefilter should be used on installations in which free solids are present.
• Correct and constant voltage must be supplied to the controller to maintain proper function.
43037 Rev D AU11
NXT STAGER DIMENSIONS
11.13 [282.7]
8.91 [226.3]
Optional
Solenoid
10.50 [266.6]
5.25 [133.4]
1.41 [35.8]
(6X) 1/8" NPT PORT 60 APART
*
ø
0.733 [18.62 mm]
4 places
* ø
0.88
[22.4 mm]
1/8" NPT Drain
2.45 [62.2]
2.06 [52.3]
2.75 [69.9] 2.75 [69.9]
4.00 [101.6]
48ES STAGER
3.50 [88.9]
2.72 [69]
2.00 [50.8]
1/8" NPT Filtered Inlet
6.42 [163.1]
1.25 [31.7]
6.00 [152.4]
(4X) R.16 [4]
(4X) .19 [4.8]
11.13 [282.7]
.32 [8.1]
1/8" NPT Drain
SYSTEM SPECIFICATIONS 48ES AND
51ES SERIES
Generic Meter Guidelines
• Open collector output
• Pulse rate generated must not exceed 100 pulses per second (100 Hz), or 6,000 pulses per minute
• Support for meter outputs in the range of 1-255 gallons
(25.5 m
3
) for every 1-255 pulses
Example: 35 gallons/100 pulses
(=3.5 gallons/10 pulses, = 0.35 gallons/1 pulse)
• Meter must operate at 5 VDC
Electrical Rating
• 24 VAC Transformers
115 VAC ±20% input, 24 VAC output w/40 VA (maintain input voltage in this range)
230 VAC ±20% input, 24 VAC output w/108 VA (maintain input voltage in this range)
• Max Rated Power 15W
Humidity
• 95% RH, non-condensing
Temperature
• Maximum control fluid temperature 140°F (60°C)
• Operate where ambient temperatures are above 32°F and below 110°F
Pressure
• Maximum control fluid pressure 125 psi (8.5 bar)
• Control fluid can be either water or air and must be equal to or greater than system pressure.
1.75 [44.4]
1/8" NPT Filtered Inlet
(8X) 1/8" NPT - 45 APART
*
ø
0.733 [18.62 mm]
4 places
1/8" NPT Drain
*
ø
0.88
[22.4 mm]
51ES STAGER
*
NOTE: Drill as required. These holes
will only be drilled at factory if
required.
Figure 1
2 • NXT Stager Controller AU11
SYSTEM DEFINITIONS
System
Number
4
System
Description
Single Unit
# of
Tanks/
Controls
1
5 Interlocked
Type
Time Clock: No Meter
Immediate: One Meter
Delayed: One Meter
Remote Signal Start: No Meter
2, 3, or 4 Immediate: All Meters
Remote Signal Start: No Meter
6
7
9
14
Service Outlet Valve
Controlled by...
Operation Discussion
Stager
(no solenoid required)
Single tank configuration. During
Regeneration no water available to service unless optional bypass valve #2A installed.
Series
Regeneration
Twin
Alternating
Multiple Tank
Alternating
Demand
Recall
2, 3, or 4
2
2, 3, or 4
2, 3, or 4
Immediate: One Meter
Delayed: One Meter
Remote Signal Start: No Meter
Immediate: One Meter
Remote Signal Start: No Meter
Immediate: All Meters
Remote Signal Start: No Meter
Immediate: All Meters
Stager
(no solenoid required)
Stager
(no solenoid required)
Solenoid
(plug stager port 2)
Solenoid
(plug stager port 2)
Solenoid
(plug stager port 2)
All tanks in parallel supplying treated water.
Each unit in the system will have its own flow meter/sensor input. The control will delay the start of Regeneration if another unit is already in Regeneration. Once that unit has completed a Regeneration cycle, and has returned to Service,the unit with longest regeneration queue time will begin
Regeneration. No more than one unit will be in Regeneration at a time.
All tanks in parallel supplying treated water.
Only #1 control will monitor flow meter/ sensor input. When a regeneration is required for the system, it will regenerate valve address #1 first, immediately followed by #2, then #3, then #4 if installed. No more than one unit will be in Regeneration at a time.
One tank online supplying treated water, one tank in Standby. Only #1 control will monitor its flow meter/sensor input.
Regeneration of a unit will begin after the other control has left Standby and returned to Service. When the Regeneration cycle is complete, the regenerated unit will enter
Standby. Standby on each tank is controlled by a solenoid connected to the service outlet valve of that tank.
One, two, or three tanks online supplying treated water, one tank in Standby. Meter/ sensor input is required on each tank.
Regeneration of a unit will begin after the other control has left Standby and returned to Service. When the Regeneration cycle is complete, the regenerated unit will enter
Standby. Standby on each tank is controlled by a solenoid connected to the service outlet valve of that tank.
Meter input is required on each tank. Unit
#1 will begin In Service with #2, #3, and
#4 (if installed) will begin in Standby. At least one unit is In Service at all times.
When flow rate to the Primary Service Unit increases to a user specified rate, the next unit in sequence will move from Standby to
Service. As the flow rate falls below the user specified rate subsequent tanks will return to Standby. When the Primary Service Unit regenerates, the next unit in sequence will become the new Primary Service Unit.
As each units capacity is reached the controller will initiate a Regeneration of that unit. Depending on the number of units in the system, and flow rate demand the regenerated unit will then be placed either into Standby or Service. Only one unit will be in Regeneration at a time.
NXT Stager Controller AU11 • 3
SYSTEM OPERATION IN SERVICE
(SYSTEM 14-DEMAND)
The system operates as part of a multi-tank regeneration system. This example applies to either a 2, 3 or 4 tank system.
Each tank in the system will have an active flow meter input, even in Standby.
The number of tanks In Service depends on the flow rate.
Examples of a Four-Unit System:
1. One Tank is In Service at all times (the "primary tank").
5. The third tank returns to Standby as demand decreases past the second trip point.
1 2 3 4
1 2 3 4
In Service
(Primary Tank)
Standby
2. The total flow rate to the primary tank increased past the first trip point programmed rate. The flow stayed past the trip point delayed time. The next tank (least volume remaining) changes from Standby to In Service. This then splits the total flow between two meters.
Flow Split Between
Two Meters
Standby
6. Tanks return to Standby due to decreased total flow rate and trip points programmed. The tank with the most remaining volume will be the first to go into Standby.
1
Full Capacity
4th in Standby
(Primary Valve) order.
2
3/4 Capacity
3rd in Standby
3
1/2 Capacity
2nd in Standby
7. The primary tank regenerates. The next tank with the least remaining volume becomes the new primary tank. The tank with the next least volume remaining will be the first trip point programmed rate. Tanks continue operating in this
System Operation in Regeneration:
4
1/4 Capacity
1st in Standby
1 2 3 4
First Trip Point
(Primary Valve)
In Service
Standby
Total Flow Split
Between Two Meters
3. The flow rate demand decreased below the first trip point.
The tank returns to Standby.
1 2 3 4
Flow Rate Demand
Below First Trip Point
(Primary Valve)
Standby
4. Total flow rate demand increased past a second trip point programmed rate. The second and third tank (least volume remaining) changes from Standby to In Service. The total flow is split between the three meters.
1 2 3 4
Full Capacity
4th in Standby
3/4 Capacity
3rd in Standby
1/2 Capacity
First Trip Point
Programmed Rate
1/4 Capacity
New Primary Tank
If two tanks are In Service and both reach
Volume Remaining = 0, the other two tanks will shift from
Standby to In Service. The lead tank with
Volume Remaining = 0 will start Regeneration. The second tank with Volume Remaining = 0 will enter Standby. If flow increases past the trip point a third tank needs to enter In
Service. The tank in Standby with Volume Remaining = 0 will shift into In Service to maintain a steady flow. Operating for extended periods in this mode may degrade the water quality.
1 2 3
Flow Split Between
Three Meters
4
Standby
4 • NXT Stager Controller AU11
TIMER DISPLAY FEATURES
Valve State
(SBY, SRV, INI, LCK)
Valve
Address
System
Number
Flow
Indicator
Time of Day
Display Screen
Time of Day alternates with Error Screen
Example: Valve #, Volume
Remaining, Errors
Volume Remaining
Diagnostic Button
View Flow Rate, Peak Flow
Rate, Totalizer, Hours
Between Last Two
Regenerations, Hours Since
Last Regeneration, Adjustable
Volume Remaining, Valve
Position, Send & Receive
Errors, Software Version
Extra Cycle Button
Cycle Valve in
Regeneration/Cycle
Programming Steps
Shift Button
Adjusts Values to the Left
Up Button
Adjusts Values Up
Status LED
Down Button
Adjusts Values Down
Figure 1
Valve State
INI (Initializing) - INI will display on the screen for 30 to
45 seconds when initializing after a power failure reset or programming.
RGQ (Regeneration Queued) -RGQ indicates that the reserve has been entered in a delayed system and regeneration has been queued. When in the main screen, press the Extra Cycle button to toggle service (SRV) with RGQ.
Service (SRV) - SRV will display when the unit is In Service.
LCK (Lock) - Lock will be displayed when contact closure is applied across the interlock terminals on the circuit board. See the “Network/Communication Cables & Connections” section of this manual.
LED Status Lights
Blue LED - Illuminates while the unit is In Service and no errors exist. The unit will always be In Service unless a regeneration trigger has occurred (green LED light will be displayed). A blinking blue light indicates the timer is In Service, and queued for regeneration.
Green LED - Illuminates when the unit is in Regeneration mode. A blinking green light indicates the timer is in Standby, and not in Regeneration.
Red LED- Illuminates when there is an error.
Flow Indicator
A rotating line (appearing as a rotating star shape) will display on the screen when flow is going through the meter.
NETWORK/COMMUNICATION CABLES
& CONNECTIONS
Use a CAT5 Network/Communication cable.
Connect the network/communication cable to either port before programming.
The maximum cable length between timers is 100 feet.
Connect units together from one communication port to the next communication port. The order is not important.
Ground
Lock Regen
Communication Ports
Figure 2 Current NXT Circuit Board
NXT Stager Controller AU11 • 5
TIMER OPERATION
Set Time of Day
Hold the Up or Down button to change time. While in time change mode press Shift to adjust next digit over. On multiple tank systems change time on #1 control only. All other controls in system will mirror the time on control #1.
Manually Initiating a Regeneration
1. When timer is In Service or Stand By, press the Extra Cycle button on the main screen for five (5) seconds to force a manual regeneration if another unit is not in Regeneration.
2. The timer reaches Regeneration cycle Step #1.
3. Press the Extra Cycle button once to advance valve to the next Regeneration cycle.
Timer Operation During Regeneration
In the Regeneration cycle step display, the timer shows the current Regeneration cycle number the valve is in, or has reached, and the time remaining in that step. Once all regeneration steps are complete the timer returns to In Service and resumes normal operation.
Example: 12 minutes remaining in Cycle 1
Press the Extra Cycle button during a
Regeneration Cycle to immediately advance the valve to the next cycle and resume normal timing.
Flow Meter Equipped Timer
During normal operation the Time of Day screen alternates with the Error screen (if errors are present).
As treated water is used, the Volume Remaining display counts down from the calculated system capacity to zero. When zero is reached a Regeneration cycle begins if no other units are in regeneration.
Timer Operation During Programming
The timer enters the Program Mode in Standby or Service
Mode as long as it is not in regeneration. While in the Program
Mode the timer continues to operate normally monitoring water usage. Timer programming is stored in memory permanently.
Timer Operation During A Power Failure
During a power failure all timer displays and programming are stored for use upon power re-application. The timer retains all values, without loss. The timer is fully inoperative and any calls for regeneration are delayed. The timer, upon power re-application, resumes normal operation from the point that it was interrupted.
NOTE: A flashing Time of Day display indicates a power outage. Hold the Up or Down button to reset time.
Remote Lockout
The timer does not allow the unit/system to go into
Regeneration until the regeneration lockout input signal to the unit is cleared. This requires a contact closure to activate the lockout. The recommended gauge wire is 20 with a maximum length of 500 feet.
Regeneration Day Override Feature
If the Day Override option is turned on and the actual number of days since last regeneration exceeds the set regeneration day override value, the Regeneration cycle starts. If other units are in regeneration, it is added to a regeneration queue. This occurs regardless of the remaining volume available.
WARNING:
This unit is not designed to drive/power external devices. Transformer must be grounded. Ground wire must be terminated to the back plate where grounding label is
located.
Auxiliary Relay Output
The Auxiliary Relay Output on the circuit board can be programmed to be closed during a window of time within the regeneration sequence. The Aux Relay Output Start time sets the turn-on time referenced to the start of regeneration. The
Aux Relay Output End time sets the turn-off time referenced to the start of regeneration. The Auxiliary Relay Output shares the same relay as the Chemical Pump Output. See wiring diagram for connection information.
Chemical Pump Output
When the Chemical Pump Output feature is enabled, the control will calculate volume of water used and close the relay when the set CPO Aux Relay Volume is reached. Once activated, the relay will stay closed for the amount of time set in CPO Aux Relay Time. The Chemical Pump Output only functions while in service, and the CPO volume is reset to zero each regeneration. The Chemical Pump Output shares the same relay as the Auxiliary Relay Output. See wiring diagram for connection information.
6 • NXT Stager Controller AU11
MASTER PROGRAMMING MODE FLOW
CHART
CAUTION
Before entering Master Programming, please contact your local professional water dealer.
When the Master Programming Mode is entered, parameters can be set to make the timer(s) function as needed.
NOTE: Depending on current option settings, some displays cannot be viewed or set.
Entering Master Programming Mode
1. Press and hold the Shift and Up buttons for 5 seconds.
OR
2. Set the time of day display to 12:01 PM or 12:01HR. Press and hold Up or Down buttons to set the time. Then press the Up and Down buttons at the same time for 5 seconds.
Exiting Master Programming Mode
1. Press the Extra Cycle button once per display until all are viewed. Master Programming Mode is exited and the normal display screen appears.
2. To exit the Master Programming Mode without saving changes, press the Diagnostic button.
NOTE: If no keypad activity is made for 5 minutes while in the Master Programming Mode, or if there is a power failure, no changes will be saved, and the unit will go back to the main display screen.
Resets
Soft Reset: Press and hold the Up and Down buttons for 25 seconds until 12:00PM (or 12:00HR) appears. This resets all parameters except for the flow meter totalizer volume.
Master Reset: Hold the Extra Cycle button while powering up the unit. This resets all of the parameters in the unit. Check and verify the choices selected in Master Programming Mode.
1 to 997 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to change each decimal position.
NOTE: This screen will only display for System 14.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2: gpm
2 to 998 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3: gpm
3 to 999 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
REGENERATION DAY
OVERRIDE:01 DAYS
Example:
Off
(Default for Meter)
On
(Default for Time Clock)
Example:
1 Day
Options: Off (Default for Meter) or On (Default for Time Clock)
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override is on.
CYCLE 1 00:10:00
Example: Backwash
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 2 01:00:00
Example: Brine
01:00:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager (Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00
Example: Fast Rinse
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF
CYCLE 4 00:12:00
Example:
Off
(Default 48-00 Stager)
Example: Refill
00:12:00
(Default 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 5 OFF
Example:
Off
(Default 51-09 Stager)
NOTE: This screen will only display when cycle 4 is not OFF.
AUXILIARY RELAY:
DISABLED
Options: Enabled
Disabled
(Default)
Example:
Auxiliary Relay is Disabled
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Range: 00:00:00 to 18:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
SYSTEM TYPE: 4
SINGLE UNIT
Example:
System Type 4, Single Unit
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
VALVE ADDRESS:
#2
Example:
Valve Address #2 (Second Control Valve)
(Default)
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Example:
2 Valves in the System
(Default)
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
REGEN TYPE:
TIME CLK DELAYED
Example:
Time Clock Delayed
(Default)
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
VALVE TYPE:
STAGER-NOTCH CAM
Example:
Stager - Notch Cam
(Default)
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam
(Default)
REMOTE SIGNAL
START:OFF
Example:
Off
(Default)
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 14.
DISPLAY FORMAT:
US-GALLONS
Example:
U.S. Gallons
(Default)
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
UNIT CAPACITY:
0300000 GRAINS
Example:
0300000 Grains
(Default)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO
3
Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
CAPACITY SAFETY
FACTOR: 00%
Example:
00%
(Default)
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Example:
15 GPG (U.S. Format)
(Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCO s
/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
CPO AUX RELAY
TIME: 00:00:00
Range: 00:00:00 to 02:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle
1.0 Turbine
1.5 Paddle
1.5 Turbine
2.0 Paddle
3.0 Paddle
Generic
NOTE: Default flow meter type is based on the valve type. This screen will only display on the lead unit for System Types 6 & 7. All other system types it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
1 to 997 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to change each decimal position.
NOTE: This screen will only display for System 14.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2: gpm
NXT Stager Controller AU11 • 7
2 to 998 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3: gpm
3 to 999 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
REGENERATION DAY
OVERRIDE:01 DAYS
Example:
Off
(Default for Meter)
On
(Default for Time Clock)
Example:
1 Day
Options: Off (Default for Meter) or On (Default for Time Clock)
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override is on.
CYCLE 1 00:10:00
Example: Backwash
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 2 01:00:00
Example: Brine
01:00:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager (Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00
Example: Fast Rinse
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF
CYCLE 4 00:12:00
Example:
Off
(Default 48-00 Stager)
Example: Refill
00:12:00
(Default 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 5 OFF
Example:
Off
(Default 51-09 Stager)
NOTE: This screen will only display when cycle 4 is not OFF.
AUXILIARY RELAY:
DISABLED
Options: Enabled
Disabled
(Default)
Example:
Auxiliary Relay is Disabled
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Range: 00:00:00 to 18:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
SYSTEM TYPE: 4
SINGLE UNIT
Example:
System Type 4, Single Unit
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
VALVE ADDRESS:
#2
Example:
Valve Address #2 (Second Control Valve)
(Default)
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Example:
2 Valves in the System
(Default)
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
REGEN TYPE:
TIME CLK DELAYED
Example:
Time Clock Delayed
(Default)
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
VALVE TYPE:
STAGER-NOTCH CAM
Example:
Stager - Notch Cam
(Default)
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam
(Default)
REMOTE SIGNAL
START:OFF
Example:
Off
(Default)
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 14.
DISPLAY FORMAT:
US-GALLONS
Example:
U.S. Gallons
(Default)
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
UNIT CAPACITY:
0300000 GRAINS
Example:
0300000 Grains
(Default)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO
3
Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
CAPACITY SAFETY
FACTOR: 00%
Example:
00%
(Default)
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Example:
15 GPG (U.S. Format)
(Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCO s
/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
CPO AUX RELAY
TIME: 00:00:00
Range: 00:00:00 to 02:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle
1.0 Turbine
1.5 Paddle
1.5 Turbine
2.0 Paddle
3.0 Paddle
Generic
NOTE: Default flow meter type is based on the valve type. This screen will only display on the lead unit for System Types 6 & 7. All other system types it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
1 to 997 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to change each decimal position.
NOTE: This screen will only display for System 14.
TRIP DELAY 1:
30 SECONDS
MASTER PROGRAMMING MODE FLOW
CHART continued
NOTE: This screen will only display for System 14.
TRIP POINT 2: gpm
2 to 998 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3: gpm
3 to 999 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
REGENERATION DAY
OVERRIDE:01 DAYS
Example:
Off
(Default for Meter)
On
(Default for Time Clock)
Example:
1 Day
Options: Off (Default for Meter) or On (Default for Time Clock)
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override is on.
CYCLE 1 00:10:00
Example: Backwash
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 2 01:00:00
Example: Brine
01:00:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager (Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00
Example: Fast Rinse
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF
Example:
Off
(Default 48-00 Stager)
CYCLE 4 00:12:00
Example: Refill
00:12:00
(Default 51-09 Stager)
(Hours:Minutes:Seconds)
8 • NXT Stager Controller AU11
CYCLE 5 OFF
Example:
Off
(Default 51-09 Stager)
NOTE: This screen will only display when cycle 4 is not OFF.
AUXILIARY RELAY:
DISABLED
Options: Enabled
Disabled
(Default)
Example:
Auxiliary Relay is Disabled
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Range: 00:00:00 to 18:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
SYSTEM TYPE: 4
SINGLE UNIT
Example:
System Type 4, Single Unit
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
VALVE ADDRESS:
#2
Example:
Valve Address #2 (Second Control Valve)
(Default)
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Example:
2 Valves in the System
(Default)
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
REGEN TYPE:
TIME CLK DELAYED
Example:
Time Clock Delayed
(Default)
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
VALVE TYPE:
STAGER-NOTCH CAM
Example:
Stager - Notch Cam
(Default)
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam
(Default)
REMOTE SIGNAL
START:OFF
Example:
Off
(Default)
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 14.
DISPLAY FORMAT:
US-GALLONS
Example:
U.S. Gallons
(Default)
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
UNIT CAPACITY:
0300000 GRAINS
Example:
0300000 Grains
(Default)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO
3
Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
CAPACITY SAFETY
FACTOR: 00%
Example:
00%
(Default)
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Example:
15 GPG (U.S. Format)
(Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCO s
/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
CPO AUX RELAY
TIME: 00:00:00
Range: 00:00:00 to 02:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle
1.0 Turbine
1.5 Paddle
1.5 Turbine
2.0 Paddle
3.0 Paddle
Generic
NOTE: Default flow meter type is based on the valve type. This screen will only display on the lead unit for System Types 6 & 7. All other system types it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
1 to 997 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to change each decimal position.
NOTE: This screen will only display for System 14.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2: gpm
2 to 998 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 3 or 4 to appear. Use the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3: gpm
3 to 999 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
REGENERATION DAY
OVERRIDE:01 DAYS
Example:
Off
(Default for Meter)
On
(Default for Time Clock)
Example:
1 Day
Options: Off (Default for Meter) or On (Default for Time Clock)
Range: 1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override is on.
CYCLE 1 00:10:00
Example: Backwash
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 2 01:00:00
Example: Brine
01:00:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager (Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00
Example: Fast Rinse
00:10:00
(Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 4 OFF
CYCLE 4 00:12:00
Example:
Off
(Default 48-00 Stager)
Example: Refill
00:12:00
(Default 51-09 Stager)
(Hours:Minutes:Seconds)
CYCLE 5 OFF
Example:
Off
(Default 51-09 Stager)
NOTE: This screen will only display when cycle 4 is not OFF.
AUXILIARY RELAY:
DISABLED
Options: Enabled
Disabled
(Default)
Example:
Auxiliary Relay is Disabled
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output Start 1 at
0 hours, 0 minutes, & 0 seconds
Range: 00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Range: 00:00:00 to 18:00:00
Example:
Auxiliary Relay Output End 1 at
0 hours, 0 minutes, & 0 seconds
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options: Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 9
Example:
Energize Chemical Pump relay every 50 gals (50)
Energize Chemical Pump relay every 200 L (200)
Range: 1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
SELECT LANGUAGE:
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
English
SYSTEM TYPE: 4
SINGLE UNIT
Example:
System Type 4, Single Unit
Options: System 4 (single unit)
System 5 (2-4 units) - Parallel Interlock
System 6 (2-4 units) - Parallel Series Regeneration
System 7 (2 units) - Alternating
System 9 (2-4 units) - Alternating
System 14 (2-4 units) - Demand Recall
VALVE ADDRESS:
#2
Example:
Valve Address #2 (Second Control Valve)
(Default)
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Example:
2 Valves in the System
(Default)
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
REGEN TYPE:
TIME CLK DELAYED
Example:
Time Clock Delayed
(Default)
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
VALVE TYPE:
STAGER-NOTCH CAM
Example:
Stager - Notch Cam
(Default)
Options: 2750
2850
2900
3150
3900
Stager - Notch Cam
(Default)
REMOTE SIGNAL
START:OFF
Example:
Off
(Default)
Options: 00:06:00 (Hours:Munutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 14.
DISPLAY FORMAT:
US-GALLONS
Example:
U.S. Gallons
(Default)
Options: U.S. - Gallons (Default)
EU-Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
UNIT CAPACITY:
0300000 GRAINS
Example:
0300000 Grains
(Default)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1.0 to 190,000 grams CaCO
3
Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
CAPACITY SAFETY
FACTOR: 00%
Example:
00%
(Default)
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Example:
15 GPG (U.S. Format)
(Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
2 to 199 miligrams CaCO s
/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
CPO AUX RELAY
TIME: 00:00:00
Range: 00:00:00 to 02:00:00
Example:
Each time chemical pump relay is on, run for
30 seconds (00:00:30)
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options: 1.0 Paddle
1.0 Turbine
1.5 Paddle
1.5 Turbine
2.0 Paddle
3.0 Paddle
Generic
NOTE: Default flow meter type is based on the valve type. This screen will only display on the lead unit for System Types 6 & 7. All other system types it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range: 20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range: 1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
USER PROGRAMMING MODE FLOW
CHART
Entering User Programming Mode
Hold the Up and Down buttons for 5 seconds.
DIAGNOSTIC PROGRAMMING MODE
FLOW CHART
Entering Diagnostic Programming Mode
1. Push and release the "D" button.
2. Press the Extra Cycle button once per display until all displays are viewed and Normal Display is resumed.
3. Push and release the"D" button at anytime during diagnostic mode and the timer will exit the mode.
4. Depending on the current controller programming, certain displays may not be able to be viewed or set.
FEED WATER
HARDNESS: gpg
Options:
U.S. Format
Metric Format
[gpg]
[mgL]
REGENERATION DAY
OVERRIDE: OFF
Options:
U.S. Format
Metric Format
[OFF] = default
[OFF] = default
REGENERATION DAY
OVERRIDE:99 DAYS
REGENERATION
TIME: 02:00AM
Options:
U.S. Format
Metric Format
[02:00AM] = default
[02:00] = default
CURRENT FLOW
RATE: 0 gpm
Explaination:
Flow rate at this time.
PEAK FLOW RATE:
0 gpm
Explaination:
Peak flow since last regeneration.
TOTALIZER:
130 g
Explaination:
Gallons at the outlet since installation.
LAST TWO REGENS:
0 HOURS
Explaination:
Hours between the last regeneration and the one before it.
LAST REGEN
0 HOURS
Explaination:
Hours since last regeneration.
VOLUME REMAIN:
1000 g
Explaination:
Volume remaining; can be adjusted.
VALVE ADDRESS
#2
Explaination:
Controller unit number.
VERSION:
X.XX
Explaination:
Installed software level of the controller in use.
NXT Stager Controller AU11 • 9
10 • NXT Stager Controller AU11
Stager Operation
Stagers are motor driven, rotary multi-port valves used to control a set of valves in a predefined sequence. They function by internally connecting inlet pressure to a defined set of control ports and allowing other control ports be vented through a drain. Control ports are used to open and close valves in a preset sequence. As the stager advances to various positions, different valves are open and closed in a system. The control port pressure and vent sequence is preset at the factory and cannot be field altered.
Stager Installation
1. Connect a constant pressure water or air source to the 1/8"
NPT stager inlet. Control fluid pressure must be equal to or greater than system pressure. To ensure long trouble free operation, a 100 micron filter in the control pressure line is recommended.
2. Stager drain port should be left open or discharged to unrestricted or open drain. DO NOT plug or restrict drain port.
3. Connect the 1/8" NPT control ports to appropriate valves.
Refer to tubing schematic provided in the Plumbing
Diagrams section of this manual. Tubing inside diameter should be 1/8" or larger.
Inverted Type Stagers
Stagers that are ordered inverted would be used on systems with all normally closed valves. Inverted Stagers send pressure signals to open valves and vent signals to close valves.
PLUMBING DIAGRAMS
4 Position Softener (48-00 Stager)
Optional Hard
Water Bypass Valve
Drain Line Flow
Control not shown
B
A
Note A: All valves normally open except optional valve 2A.
Note B: Inverted Stager types will have these ports pressurized.
Inverted Stager to be used with all valves normally closed except optional valve 2A.
NXT Stager Controller AU11 • 11
PLUMBING DIAGRAMS continued
4 Position Filter (48-00 Stager) 5 Position Softener w/Timed Brine Refill
(51-09 Stager)
Customer
Supplied Valve
Optional Hard
Water Bypass Valve
Optional Hard
Water Bypass Valve
4 POSITION FILTER
Drain Line Flow
Control not shown
Installer to plug (with
PN1071903)for filter operation
Plugs installed at factory
Drain Line Flow
Control not shown
B
A
B
A
C
Note A: All valves normally open except optional valve 2A.
Note B: Inverted Stager types will have these ports pressurized.
Inverted Stager to be used with all valves normally closed except optional valve 2A.
Note C: Program Cycle 2 time to 00:00:00 for filter operation.
Note A: All valves normally open except optional valve 2A.
Note B: Inverted Stager types will have these ports pressurized.
Inverted Stager to be used with all valves normally closed except optional valve 2A.
12 • NXT Stager Controller AU11
PLUMBING DIAGRAMS continued
Multiple Tank 4 Position Softener (48-00 Stager)
EJECTOR
RAW WATER
5A
BRINE
INLET
2A
1A
4A
3A
6A
5B
2B
1B
4B
3B
To Additional Tanks
As Required
6B
UNIT A
NOTE: All valves normally open, pressure to close.
NOTE: Valve 2 for each tank is controlled by solenoid for system 7, 9, 14
DRAIN
Multiple Tank 5 Position Softener (51-09 Stager)
Customer Supplied
Check Valve
Ejector
To Brine Tank
3A
Customer Supplied
Check Valve
To Brine Tank
Ejector
SERVICE
UNIT B
5A
INLET
7A
To Brine Refill
2A
1A
4A
To Brine Refill
6A
5B
7B
2B
1B
4B
DRAIN LINE FLOW
CONTROL NOT SHOWN
3B
To Additional Tanks
As Required
6B
UNIT A
DRAIN
NOTE: All valves normally open, pressure to close.
NOTE: Valve 2 for each tank is controlled by solenoid for system 7, 9, 14
SERVICE
UNIT B
DRAIN LINE FLOW
CONTROL NOT SHOWN
NXT Stager Controller AU11 • 13
SOLENOID USE
Solenoids only required for Systems 7, 9 and 14
Series 48-00/51-09 Stager
Installer to
Plug Port 2
Solenoid
Valve
Drain
3
Inlet Pressure
1 2
2
3
2
3
1
Flow
1
Flow
Solenoid De-energized Solenoid Energized
Energized To Close
The NXT Stager control can operate an optional 24 VAC solenoid to control when a tank is off line. This solenoid is electrically connected to the "lower drive" connection on the circuit board, and control pressure is run through the solenoid to the service outlet diaphragm valve.
The solenoid installed at the factory is a universal type. It is plumbed in an energize to close configuration when service outlet valve is normally open.
When a tank enters Regeneration or Standby the solenoid is energized. Pressure from solenoid port 1 passes to port 2. The diaphragm valve #2 will close.
When a tank enters In Service the solenoid is de-energized.
The inlet pressure to solenoid port 2 is stopped. The diaphragm valve is vented through solenoid port 2 to port 3
(drain). The valve #2 opens.
Inverted Stagers Only - Energize to Open
If the service outlet vavle is normally closed, connect constant pressure source to solenoid port 3. Connect solenoid port 2 to service outlet valve. Solenoid port 1 is drain.
14 • NXT Stager Controller AU11
STAGER CONTROLLER, 48ES, NEMA 4
24V/50-60Hz ASSEMBLY
41
39
38
47
1
2
3
7
4
23
16
3
3
27
51
49
17
5
22
21
18
19
11
6
9
15
8
14
12
20
10
12
13
BOTTOM DETAIL VIEW
SCALE 1:2
Item No. QTY Part No. Description
1 .................. 1 ......... 43001 ................... Motor, 24V, 50/60Hz, 5/8 RPM
2 .................. 1 ......... 1070436 ............... Plate, Motor MTG, Stagers
3 .................. 6 ......... 1075746 ............... Screw, 6-32 x 1/4", Phil
4 .................. 4 ......... 1072371 ............... Screw, 6-32 x .375, RD.HD, SS
5 .................. 1 ......... 1075737 ............... Gasket, Stager MTG, 48
6 .................. 1 ......... 1071667 ............... O-ring, 2-010, Nitrile
7 .................. 1 ......... 1075454* .............. Thumb Wheel, Molded
8 .................. 1 ......... 1074074 ............... Washer, 302, SS
9 .................. 1 ......... 1070448 ............... Shaft, Stem Assy, 48 Series
10 ................ 1 ......... 1074784 ............... Backplate, 48-00, Brass
11 ................ 1 ......... 1074793 ............... Bonnet, 48, Brass
12 ................ 1 ......... 1074825 ............... Inlet Strainer, Assy
13 ................ 3 ......... 1075759 ............... Screw, Pan Head, 6-32 x .88"
14 ................ 1 ......... 1076234 ............... Spring, Wave, 17-7 SS, 48 STGR
15 ................ 1 ......... 1074845 ............... Stemplate, 48, -00
16 ................ 1 ......... 1076245* .............. Cam, Cycle, Machined
17 ................ 1 ......... 1070437 ............... Plate, Bottom MTG, Stager
18 ................ 2 ......... 1075499 ............... Switch, Micro
19 ................ 1 ......... 1075455 ............... Switch Spacer, Insulator
20 ................ 1 ......... 1084171 ............... Gasket, Backplate, 48 Nitrile
21 ................ 2 ......... 1073593 ............... Washer, Lock, Internal, #4, SS
22 ................ 2 ......... 1075757 ............... Machine Screw, 4-40 x 1.00, SS if 2 switches
2 ......... 1072389 ............... Screw, 4-40 x 1-3/8" if 3 switches
23 ................ 1 ......... 1075453* .............. Cam, Auxiliary, Blank
24 ................ 2 ......... 3014200 ............... Screw, Slotted HX HD, 10-32
25 ................ 2 ......... 1078992 ............... Washer, Lock, Internal, #10, SS
26 ................ 1 ......... 14202-01 .............. Screw, Hex Washer #8-32 x 5/16
27 ................ 1 ......... 43077-00 .............. Label, Dial, STGR, 2 3/8 x 7/8
28 ................ 2 ......... 17967-01 .............. Nut, Liquid Tight, HeyCo 3169
29 ................ 2 ......... 17967-02 .............. Fitting, Liquid Tight, Black
30 ................ 1 ......... 1075538 ............... Terminal Block, 10
31 ................ 2 ......... 1072369 ............... Screw, Pan HD, 4-40 x 5/8, SS
32 ................ 1 ......... 1076219 ............... Label, Ground, .75 Dia.
31
24
30 33
34
48
25
28
29
AUX 1 (RED)
35
26
50
32
47
44
43
CYCLE (WHITE)
36
45
46
KIT BR61764
SCALE 1:4
40
42
37
61803 Rev D
Item No. QTY Part No. Description
33 ................ 1 ......... 1073732 ............... Label, Terminal Strip, 1-10
34 ................ 1 ......... 43094-01 .............. Enclosure, 48ES, NEMA 4
35 ................ 1 ......... 43093 ................... Panel, A10P, 8" x 6" Modified
36 ................ 1 ......... 43046* .................. Keypad Label Assy, XT, NEMA 4
37 ................ 1 ......... 1070649 ............... Solenoid, N1, 24/60
38 ................ 4 ......... 42827-04 .............. Stand-off, Plastic, .625"
39 ................ 1 ......... 42753U* ............... Circuit Board, XT, ML
40 ................ 4 ......... 43092 ................... Screw, FLT HD, #6-20, TYP-B
41 ................ 1 ......... 40941 ................... Harness, Upper Drive
42 ................ 1 ......... 43090 ................... Washer, Sealing, Conduit, 1/2"
43 ................ 1 ......... 43140 ................... Fitting, NPT 1/2, Conduit
44 ................ 1 ......... 43141 ................... Washer, Lock, 7/8, INT Tooth
45 ................ 1 ......... 61764 ................... Cable Assy, COM, CAT 5E, NEMA 4
46 ................. 1 ..........19121-09 ...............Meter Cable Assy, NT, 99.5"
47 ................. 4 ..........1081780 ................Mount, Cable Tie, 4-Way
48 ................. 1 ..........1072379 ................Screw, 10-32 x 5/8", RND HD, SS
49 ................. 1 ..........1071660 ................Nut, Hex, 10-32, KEPS
50 ................. 1 ..........43177 ....................Washer, Lock, #8, INT, 18-8 SS
51 ................. 1 ..........1071648 ................Nut
Not Shown
1 ......... 61500-48/51LNE .. Line Drawing
9 ......... 1073701 ............... Tie, Cable, HeyCo VNT#4-18
2 ......... 1073702 ............... Wire Tie
3 ......... 1073955 ............... Terminal, Ring, #10, 16-14 GA
1 ......... 1073875 ............... Wire, Black, 18 AWG
1 ......... 1073880 ............... Wire, White, 18 AWG
1 ......... 1073874 ............... Wire, Green, 14 AWG
1 ......... 43163 ................... Literature, 3214 NXT Stager,S/M
1 ......... 43012 ................... Wiring Diagram, 48/51ES
1 ......... 61784 ................... Service Kit, 48/51, Timer
1 ......... 61783 ................... Service Kit, 48/51, Solenoid
1 ......... 1071903 ............... 1/8" NPT Pipe Plug Brass
*Only sold as Service Assembly
NXT Stager Controller AU11 • 15
STAGER CONTROLLER, 51ES, NEMA 4
24V/50-60Hz ASSEMBLY
30
AUX 1 (Red)
20 23
39
36
21
29
27
3
5
13
8
4
1
2
50
6
3
17
12
11
9
10
38
52
14
35
15
37
18
19
24
51
16
22
36
32
33
34
CYCLE (White)
25
ISO FRONT VIEW
SCALE 1:4
28
31
26
KIT BR61764
SCALE 1:4
43
40
41
44
46
47
48
45
42
7
42
BOTTOM DETAIL VIEW
SCALE 1:2
49
Item No. QTY Part No. Description
1 .................. 1 ......... 43001 ................... Motor, 24V, 50/60Hz, 5/8 RPM
2 .................. 1 ......... 1070436 ............... Plate, Motor MTG, Stagers
3 .................. 6 ......... 1075746 ............... Screw, 6-32 x 1/4", Phil
4 .................. 2 ......... 1072371 ............... Screw, 6-32 x .375, RD.HD, SS
5 .................. 1 ......... 1075454* .............. Thumb Wheel, Molded
6 .................. 1 ......... 1075674 ............... Gasket, Stager MTG, 51, 96
7 .................. 1 ......... 1074825 ............... Inlet Strainer, Assy
8 .................. 1 ......... 1076243* .............. Cam, Cycle, Machined
9 .................. 2 ......... 1075499 ............... Switch, Micro
10 ................ 1 ......... 1075455 ............... Switch Spacer, Insulator
11 ................ 2 ......... 1073593 ............... Washer, Lock, Internal, #4, SS
12 ................ 2 ......... 1075757 ............... Machine Screw, 4-40 x 1.00, SS
13 ................ 1 ......... 1075453* .............. Cam, Auxiliary, Blank
14 ................ 2 ......... 3014200 ............... Screw, Slotted HX HD, 10-32
15 ................ 2 ......... 1078992 ............... Washer, Lock, Internal, #10, SS
16 ................ 1 ......... 14202-01 .............. Screw, Hex Washer #8-32 x 5/16
17 ................ 1 ......... 43078-09 .............. Label, Dial, STGR, 2 3/8 x 7/8
18 ................ 2 ......... 17967-01 .............. Nut, Liquid Tight, HeyCo 3169
19 ................ 2 ......... 17967-02 .............. Fitting, Liquid Tight, Black
20 ................ 1 ......... 1075538 ............... Terminal Block, 10
21 ................ 2 ......... 1072369 ............... Screw, Pan HD, 4-40 x 5/8, SS if 2 switches
2 ......... 1072389 ............... Screw, 4-40 x 1-3/8" if 3 switches
22 ................ 1 ......... 1076219 ............... Label, Ground, .75 Dia.
23 ................ 1 ......... 1073732 ............... Label, Terminal Strip, 1-10
24 ................ 1 ......... 43093 ................... Panel, A10P, 8" x 6" Modified
25 ................ 1 ......... 43046* .................. Keypad Label Assy, ST, NEMA 4
26 ................ 1 ......... 1070649 ............... Solenoid, N1, 24/60
27 ................ 1 ......... 42753U* ............... Circuit Board, XT, ML
28 ................ 4 ......... 43092 ................... Screw, FLT HD, #6-20, TYP-B
29 ................ 4 ......... 42827-04 .............. Stand-off, Plastic, .625"
30 ................ 1 ......... 40941 ................... Harness, Upper Drive
31 ................ 1 ......... 43090 ................... Washer, Sealing, Conduit, 1/2"
32 ................ 1 ......... 43141 ................... Washer, Lock, 7/8, INT Tooth
61804 Rev D
Item No. QTY Part No. Description
33 ................ 1 ......... 43140 ................... Fitting, NPT 1/2, Conduit
34 ................ 1 ......... 61764 ................... Cable Assy, COM, CAT 5E, NEMA 4
35 ................ 1 ..........19121-09 ...............Meter Cable ASSY, NT, 99.5"
36 ................ 4 ..........1081780 ................Mount, Cable Tie, 4-Way
37 ................ 1 ..........1072379 ................Screw, 10-32 x 5/8", RND HD, SS
38 ................ 1 ..........1071660 ................Nut, Hex, 10-32, KEPS
39 ................ 1 ......... 43094-02 .............. Enclosure, 51ES, NEMA 4
40 ................ 1 ......... 1075241 ............... Washer, 302, SS
41 ................ 1 ......... 1070438 ............... Shaft, Stem Assy, 51 Series
42 ................ 2 ......... 1071903 ............... Male Pipe Plugs
43 ................ 1 ......... 1074883 ............... Bonnet, 51, Brass
44 ................ 1 ......... 1075647* .............. Stemplate, 96, Alpha
45 ................ 1 ......... 1075242 ............... Spring, Compression
46 ................. 1 ..........1084172 ................Gasket, Backplate, 51 & 96 STGRS
47 ................. 1 ..........1074866* ...............Backplate, D.V. Nest
48 ................. 1 ..........1071716 ................O-ring, EP, ORE-011
49 ................. 4 ..........1075760 ................Screw, Machine, #6-32 x 1 1/8
50 ................. 1 ..........1077824 ................MTG Plate, BTM, STGR, 51ES
51 ................. 1 ..........43177 ....................Washer, Lock, #8, INT, 18-8 SS
52 ................. 1 ..........1071648 ................Nut
Not Shown
1 ......... 61500-48/51LNE .. Line Drawing
9 ......... 1073701 ............... Tie, Cable, HeyCo VNT#4-18
2 ......... 1073702 ............... Wire Tie
3 ......... 1073955 ............... Terminal, Ring, #10, 16-14 GA
1 ......... 1073875 ............... Wire, Black, 18 AWG
1 ......... 1073880 ............... Wire, White, 18 AWG
1 ......... 1073874 ............... Wire, Green, 14 AWG
1 ......... 43163 ................... Literature, 3214 NXT Stager,S/M
1 ......... 43012 ................... Wiring Diagram, 48/51ES
1 ......... 61784 ................... Service Kit, 48/51, Timer
1 ......... 61783 ................... Service Kit, 48/51, Solenoid
*Only sold as Service Assembly
16 • NXT Stager Controller AU11
WIRING DIAGRAM 48/51ES STAGER
CONTROLLER
RT TA
UT
TE MO
CK
D
RE
LO
GN
LOWPER DRIVE
N
ITE
CK
WH
BLA
CK
EE
BLA
GR
W
BLK
CK
GE
LE
AN
RP
LLO
WT/
BLA
YE
OR
PU
OW ELL N/Y EE GR
CK BLA
OW ELL N/Y EE GR
LE RP PU
CK BLA
N.C
N.O
C
1 SW
GE AN OR
N.C
N.O
CK BLA C
2 SW
N.O
N.C
C
3 SW
E
E
BLU
BLU
OW ELL N/Y EE GR
W
EL
N
EE
R
G
GR
EE
N/
YE
LL
OW
NXT Stager Controller AU11 • 17
TROUBLESHOOTING
Detected Errors
If a communication error is detected, an Error Screen will alternate with the main (time of day) screen every few seconds.
• All units In Service remain in the In Service position.
• All units in Standby go to In Service.
• Any unit in Regeneration when the error occurs completes Regeneration and goes to In Service.
• No units are allowed to start a Regeneration Cycle while the error condition exists, unless they are manually forced into Regeneration.
• When an error is corrected and the error no longer displays (it may take several seconds for all of the units in a system to stop displaying the error message), the system returns to normal operation.
NOTE: During the error condition the control continues to monitor the flow meter and update the volume remaining. Once the error condition is corrected all units return to the operating status they were in prior to the error. Regeneration queue is rebuilt according to the normal system operation.
Or, if more than one unit has been queued for regeneration, then the queue is rebuilt according to which one communicates first.
Message Displayed
Flashing time
Detected Error = No Message #1
Detected Error = No Message #2
Detected Error = No Message #3
Detected Error = No Message #4
Detected Error = E2 Reset Unit
Test Mode
Black Squares on screen
INI on screen for more than 2 minutes
CHG on screen for more than 2 minutes
Power outage.
Cause For Error Correction
Program time by holding UP on Unit #1.
Program each unit with unique valve address number in Master Programming.
Confirm Master Programming for each unit.
No power to Control #1.
Power Control #1.
Communication Cable to Valve Address #1 bad or missing.
Connect or replace Communication Cable.
No power to Control #2.
Power Control #2.
Communication Cable to Valve Address #2 bad or missing.
Connect or replace Communication Cable.
No power to Control #3.
Power Control #3.
Communication Cable to Valve Address #3 bad or missing.
Connect or replace Communication Cable.
No power to Control #4.
Power Control #4.
Communication Cable to Valve Address #4 bad or missing.
Connect or replace Communication Cable.
This message appears after a software reset.
Reprogram control using Master
Programming section.
Circuit Board was not programmed at factory.
Bad Circuit Board.
Replace Circuit Board.
Replace Circuit Board.
Circuit board not getting feedback from cycle switch.
Inspect Motor - should be rotating.
Connect wire harness to cycle switch.
Check Cycle Micro Switch.
Control programmed incorrectly as 2900 or 3900 valve type. Reprogram unit as Stager Valve type.
18 • NXT Stager Controller AU11
SERVICE ASSEMBLIES
48-00 ES Stager Assembly
61808-01 ....................Stager Assy, 48-00, NXT 24VAC, HMG
No 2nd Aux Switch
61808-02 ....................Stager Assy, 48-00, NXT 24VAC, SA,
2nd Aux Notched in Service
61808-03 ....................Stager Assy, 48-00, NXT 24VAC, SC,
2nd Aux Notched In Backwash
61808-10 ....................Stager Assy, 48-00, Inverted, NXT
24VAC, HMG No 2nd Aux Switch
61808-20 ....................Stager Assy, 48-00, Inverted, NXT
24VAC, SA, 2nd Aux Notched in Service
61808-30 ....................Stager Assy, 48-00, Inverted, NXT
24VAC, SC, 2nd Aux Notched In
Backwash
1074817......................Kit, Internal Parts, 48-00 Stager
61817-01 ....................Cam Assy, 48-00 NXT, HMG, no 2nd
Aux Cam
61817-02 ....................Cam Assy, 48-00 NXT, SA, 2nd Aux
Notched in Service
61817-03 ....................Cam Assy, 48-00 NXT, SC, 2nd Aux
Notched in Backwash
51-09 ES Stager Assembly
61809-01 ....................Stager Assy, 51-09, NXT 24VAC, HMG,
No 2nd Aux Switch
61809-02 ....................Stager Assy, 51-09, NXT 24VAC, SA,
2nd Aux Notched in Service
61809-03 ....................Stager Assy, 51-09, NXT 24VAC, SD,
2nd Aux Notched in Backwash
61809-04 ....................Stager Assy, 51-09, NXT 24VAC, SH,
2nd Aux Notched in Refill
61809-10 ....................Stager Assy, 51-09, Inverted, NXT
24VAC, HMG, No 2nd Aux Switch
61809-20 ....................Stager Assy, 51-09, Inverted, NXT
24VAC, SA, 2nd Aux Notched in Service
61809-30 ....................Stager Assy, 51-09, Inverted, NXT
24VAC, SD, 2nd Aux Notched in
Backwash
61809-40 ....................Stager Assy, 51-09, Inverted, NXT
24VAC, SH, 2nd Aux Notched in Refill
1074888......................Kit, Internal Parts, 51-09 Stager
61818-01 ....................Cam Assy, 51-09 NXT, HMG, No 2nd
Aux Switch
61818-02 ....................Cam Assy, 51-09 NXT, SA, 2nd Aux
Notched in Service
61818-03 ....................Cam Assy, 51-09 NXT, SD, 2nd Aux
Notched in Backwash
61818-04 ....................Cam Assy, 51-09 NXT, SH, 2nd Aux
Notched in Refill
Meter Assembly, In Line
60613..........................Meter Assy, 1", Elec., Brass Body, PDL
60614..........................Meter Assy, 1-1/2", Elec., Brass Body,
PDL
60616..........................Meter Assy, 2", Elec., Brass Body, PDL
60617..........................Meter Assy, 3", Elec., Brass Body, PDL
60625..........................Meter Assy, 2", Elec., Plastic, PDL
61560-01 ....................Meter Assy, 1", Elec., Plastic, Turbine
61560-07 ....................Meter Assy, 1", Elec., Brass THDS,
Turbine
61560-09 ....................Meter Assy, 1-1/2", Elec., Brass THDS,
Turbine
61560-13 ....................Meter Assy, 1-1/2", Elec., Plastic,
Turbine
Service Parts Common To Both 48ES & 51 ES Stager Control
61783..........................Kit, 48/51 ES NEMA4, Solenoid
61784..........................Kit 48/51 ES, 3214 NXT, CKT Board &
Keypad
61764..........................Cable Assy, Communication, CAT 5,
5 Meters Long
42469..........................Transformer, 120V/24V, 40VA
41049..........................Transformer, 220/24V/EUR/108VA
41050..........................Transformer, 220/24V/AUST/108VA
19121-09 ....................Meter Cable, 99.5", Paddle Wheel
19121-10 ....................Meter Cable, 303.5", Paddle Wheel
19791-04 ....................Meter Cable, 100", Turbine
19791-05 ....................Meter Cable, 304", Turbine
1075499......................Switch, Micro
40941..........................Wire Harness, Upper Drive
1075502......................Wire Harness, 2nd Aux Switch
43001..........................Motor
NXT Stager Controller AU11 • 19
© 2011 Pentair Residential Filtration, LLC 43037 Rev D AU11
advertisement
Key Features
- Multiple Tank Support
- Demand Recall System
- Remote Signal Start
- Regeneration Day Override
- Chemical Pump Output
- Auxiliary Relay Output
- Flow Meter Integration
- Diagnostic Programming Mode
- Master Programming Mode
- User Programming Mode
Frequently Answers and Questions
What are the maximum operating temperature limits for the Stager Controller?
What is the maximum control fluid pressure limit for the Stager Controller?
What types of flow meters are compatible with the Stager Controller?
What is the purpose of the Chemical Pump Output feature on the Stager Controller?
Related manuals
advertisement
Table of contents
- 2 NXT STAGER DIMENSIONS
- 2 SYSTEM SPECIFICATIONS 48ES AND 51ES SERIES
- 3 SYSTEM DEFINITIONS
- 4 (SYSTEM 14-DEMAND)
- 5 TIMER DISPLAY FEATURES
- 5 CABLES & CONNECTIONS
- 6 TIMER OPERATION
- 7 MASTER PROGRAMMING MODE FLOW CHART
- 9 USER PROGRAMMING MODE FLOW CHART
- 9 DIAGNOSTIC PROGRAMMING MODE FLOW CHART
- 11 PLUMBING DIAGRAMS
- 14 SOLENOID USE
- 15 ASSEMBLY
- 17 WIRING DIAGRAM 48/51ES STAGER CONTROLLER
- 18 TROUBLESHOOTING
- 19 SERVICE ASSEMBLIES