Dinel CLM-36 Capacitive Level Meter Instructions Manual
Below you will find brief information for Capacitive Level Meter CLM-36. The CLM-36 is a capacitive level meter designed for continuous level measurement of liquids, powders and bulk-solid materials in vessels, tanks, sumps, containers, silos, etc. It consists of a stainless steel housing with an electronic module and a measuring electrode. The electronic part converts the capacity into a current signal (4 ... 20 mA) or voltage signal (0 ... 10 V). Sensitivity (SPAN) and initial capacity compensation (ZERO) can be fluently set. CLMs are offered in versions (N) for non-hazardous environments or (Xi) version to explosive areas up to zone 0 or zone 20, high temperature performance and several types of process coupling are also available.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
průmyslová elektronika
INSTRUCTIONS MANUAL
C apaCitive level meters
Clm – 36
Before level meters usage please read instructions in this service manual and keep it for further use. Service manual is for all types of level meters series CLM-36. Producer reserves the right to make changes without any previous announcement.
O
bsah
1 . Measuring principle .................................................................................................................3
2 . Range of applications ..............................................................................................................3
3 . Features of variants .................................................................................................................4
4 . Dimensions drawings ..............................................................................................................5
5 . Influence of the tank shape on a linearity of measurement .................................................7
6 . Installation and putting into operation ...................................................................................8
7 . Installation ................................................................................................................................8
8. Electrical connection ...............................................................................................................11
9. Preparing of level meter for measuring..................................................................................12
10. Setting .....................................................................................................................................13
11 . Use, manipulation and maintenance ....................................................................................15
12 . Order code ..............................................................................................................................16
13 . Correct specification examples ............................................................................................16
14 . Accessories ............................................................................................................................16
15 . Safety, protections, compatibility and explosion proof .....................................................17
16 . Marking of labels ....................................................................................................................18
17 . Specification ...........................................................................................................................20
18 . Table of relative permittivity .................................................................................................24
u
sed
syMbols
To ensure maximum safety of control processes, we have defined the following safety instructions and information. Each instruction is labeled with the appropriate pictogram.
all types
Alert, warning, danger
This symbol informs you about particularly important instructions for installation and operation of equipment or dangerous situations that may occur during the installation and operation. Not observing these instructions may cause disturbance, damage or destruction of equipment or may cause injury
Information
This symbol indicates particularly important characteristics of the device.
Note
This symbol indicates helpful additional information.
Valid for:
In the border are the types CLM, for which is intended the chapter.
s
afety
All operations described in this instruction manual have to be carried out only by trained personnel or an accredited person. Warranty and post warranty service must be exclusively carried out by the manufacturer.
Improper use, installation or set-up of the level meter can result in crashes in the application
(overfilling of the tank or damage of system components).
The manufacturer is not responsible for improper use, losses of work caused by either direct or indirect damage, and for expenses incurred during installation or use of the level meter.
1 . M
easuring
principle
Capacitive level meters CLM
®
are designed for continuous level measurement of liquids, powders and bulk-solid materials in vessels, tanks, sumps, containers, silos, etc. CLM consists of the stainless steel housing with electronic module and the measuring electrode. Type of measuring electrode is defined by kind of use and type of measured media.
The electronic part converts the capacity into the current signal (4 ... 20 mA) or voltage signal (0 ... 10 V). Sensitivity (SPAN) and initial capacity compensation (ZERO) can be fluently set. CLMs are offered in version (N) for non-hazardous environments or (Xi) version to explosive areas up to zone 0 or zone 20, high temperature performance and several types of process coupling are also available.
2 . r
ange
of
applications
Capacitive level meters are suitable for continuous level measurement of liquid and bulk-solid materials. CLMs are resistant to any changes in the atmosphere above the surface (vacuum, pressure, vapours, dust). It is also partially resistant to the formation of foam on the surface.
3 CLM–36 © Dinel, s.r.o.
3 . f
eatures
of
variants
CLM –36_–10
With uncoated rod electrode for level measurement of non-conductive liquids (oils, diesel, petrol) and powder or bulk-solid materials (flour, sand, cement, plastic granulates, etc.). Max. length 5 m.
CLM –36_–11
With fully (PFA) coated rod electrode for level measurement of water and conductive liquids incl. wasted liquids in metallic vessels, concrete sumps, reservoirs, etc., better behaviour against aggressive media, lower adhesion to some complicated media, chemical resistance. Max. length 3 m.
CLM –36_–12
CLM –36_–20
CLM –36_–22
CLM –36_–30
With fully (FEP) coated rod electrode for level measurement of water and conductive liquids incl. wasted liquids in metallic vessels, concrete sumps, reservoirs, etc., better behaviour against aggressive media, lower adhesion to some complicated media, chemical resistance. Max. length 3 m.
With uncoated rod electrode and reference tube for accurate level measurement of clean non-conductive liquids (oils, diesel, petrol). By means of reference tube the output signal does not depend on the dimensions and shapes of a vessel. Max. length 3 m.
With fully FEP coated rod electrode and reference tube for accurate level measurement of conductive liquids. Main use is for measurement in plastic vessels or tanks. Impossible to use for waste and high viscosity liquids and bulk-solid materials. Max. length 3 m.
With uncoated stainless steel rope electrode and uncoated weight
for level measurement of bulk-solid materials (grains, sand, flour, cement, etc.). Max. length 20 m.
CLM –36_–31
CLM –36_–32
CLM –36_–40
With uncoated stainless steel rope electrode and coated dynamic
anchorage for level measurement of bulk-solid materials in higher silos.
Max. length 20 m.
With fully coated rope electrode and coated weight (rope insulation FEP, weight insulation PTFE), for level measurement of electrically conductive and non-conductive liquids. Max. length 20 m.
With two coated electrodes (rode insulation FEP, head fully PTFE), for level measurement of aggressive liquids. Performance for non-explosive areas only. Max. length 2 m.
© Dinel, s.r.o. CLM–36
4
5 CLM–36 © Dinel, s.r.o.
CLM–36_–31 High temperature variants
CLM–36_T
Housing with
Tri-clamp coupling
Rope electrode
Anchor with spherical joint
(KV–31, PR–31)**
Wall of container
Spring
** Anchor welding cylinder KV–31 or Dust-tight
bushing PR–31 (see accessories)
Fig. 2: Dimensional drawings of the capacitive level meters
© Dinel, s.r.o. CLM–36
6
5 . i
nfluence
of
the
tank
shape
on
a
linearity
of
MeasureMent
• In a curved tanks (most frequently horizontal cylinder) capacity change during measuring of electrically non-conductive material is non-linear.
CLM-36_-10, 11, 12
CLM-36_-30, 31, 32
• Linearity is done by reference tube
(CLM – 36_–20, 22), or by reference electrode (CLM – 36_–40).
CLM-36_-20, 22, 40
• In the tank with straight wall (for example vertical cylinder) and with the sensor placed parallely with the wall capacity change is linear.
all types
• For sensors with two electrodes (in the tank with straight or curved wall) is the capacity change linear.
7
CLM-36_-40
Fig. 3: Influence of the tank shape on a linearity of measurement
CLM–36 © Dinel, s.r.o.
6 . i
nstallation
and
putting
into
operation
Please follow next 4 steps:
• i nstallation
• e lectrical
connection
• p reparing
of
level
Meter
for
Measuring
• s etting
7 . i
nstallation
BASIC INFORMATION
Level meters with coated electrode have protection cover at the end of electrode, which is necessary take down before mounting.
Level meters mount in vertical position to upper lid of tank or reservoir by steel welding flange ON-36x2 (steel 11375), stainless steel welding flange NN-36x2 (stainless steel 1.4301), fixing nut UM-36x2 (stainless steel 1.4301) or Clamp flange.
For mounting level meter to the metal tank or reservoir is not necessary to ground housing again.
In case of installation in concrete sumps or silos it is properly to install level meter at metallic auxiliary construction (console, lid, etc.) and then connect with metal all the time submerged object, eventually with steel armouring.
For measuring of material in plastic and glass vessels by level meter without reference tube is necessary to connect grounding screw at housing with auxiliary electrode which is fixed by the appropriate method to the outer casing of vessels (or at inner wall). Material of auxiliary material.
electrode is necessary to choose with consideration to the working environment and properties of measured
METAL AND NON-METAL VESSESLS
CLM-36_-10, 11, 12 auxiliary electrode
width = min. 30 mm
(necessary only for non-metal vessels)
Fig. 4: Installation of level meter with rod electrode
© Dinel, s.r.o. CLM–36
E - the length of electrode
[mm] - the end of the electrode has to be dipped min. 20 mm below the lowest measured level
h - the distance from the bottom - min. 50 mm
a - the distance from the wall - min. approx. E/20
d - the diameter of auxiliary tube vessel - min. 40 + E/20
(smaller dimension has to be discussed with producer)
8
VARIANTS WITH REFERENCE TUBE
CLM-36_-20, 22
h
- the distance from the bottom
- min. 50 mm with respect on possibility of presence of heavy fraction (water) in oil products
k - the distance from the wall - optional
Fig. 5: Installation of level meter with reference tube
DEEP VESSELS, CONTAINERS AND SILOS
metal tank
CLM-36_-30, 32
connection to the armouring concrete silo
E – The length of electrode - the lower end of the electrode has to be
dipped - min. 20 mm below the lowest measured level
h – The distance from the bottom - min. 100 mm
a – The distance from the wall - at least E/20, as far as possible
from the walls, to the middle between the wall and the vertical inlet
Fig. 6: Installation of level meter with rope electrode
9 CLM–36 © Dinel, s.r.o.
ROPE ELECTRODE WITH ANCHOR
CLM-36_-31 steel anchor welding cylinder
(mat. 11375) or
dust-tight bushing
to be welded into the conical bottom wall
E - the length of electrode [mm]
c - the distance from the centre line of the silo - has to be as minimal as possible
t - the length of the conduction rod - approx. 500 mm
p - the length of the press spring - approx. 200 mm
Fig. 7: Installation of rope electrode with anchor
AGGRESSIVE LIQUIDS, NON-METALLIC VESSELS
CLM-36N_-40
E – The length of electrodes
the lower end of the electrodes
have to be dipped min. 20 mm
below the lowest measured level.
h – The distance from the bottom
min. 30 mm
a – The distance from the wall
(min. ca. E/20)
Fig. 8: Installation of level meter with reference electrode
For correct function of level type CLM-36N_-40 is necessary to ensure the impedance between of the measured medium and ground. This can be provided by:
1) The medium is isolated from all devices that may cause temporary grounding of the medium
(pumps, valves, connection with the grounded tank by flowing medium).
2) If the first option is not possible, it is necessary to ground the medium permanently.
© Dinel, s.r.o. CLM–36
10
8 . e
lectrical
connection
The level meter is designed to be connected to supply unit or to controller through a cable with the outer diameter of 6 ÷ 8 mm (recommended cross-section of cores 0.5 ÷ 0.75 mm
2
) by means of connector which is included in delivery. The scheme and the inside of the connector are on pictures.
Procedure to connect the cable to the level meter:
1. Unscrew connector from the body of the level meter using a suitable screwdriver.
2. Use a flat screwdriver to remove the inner part of the connector (screwdriver into the gap marked by arrow).
3. Unscrew the cable gland and put the cable inside.
4. Connect the cable wires to the screw terminals as shown in Fig. 10 (current output 4-20 mA) or Fig. 12 (voltage output 0-10 V). Tighten the terminals firmly.
5. Push the terminals back into the connector so that the terminal no. 3 is oriented toward the cable entry. Tighten the cable gland.
6. Check the seal on the connector and connect the connector back to the body of the sensor.
Fig. 9: Connection scheme with current output
+U (
Brown
)
Shielding
(Green-Yellow)
0V (
Blue
)
Fig. 10: Connection scheme with current output
U out
(
Black
) +U (
Brown
)
Shielding
(Green-Yellow)
Fig. 11: Connection scheme with voltage output
0V (
Blue
)
Fig. 12: Connection scheme with voltage output
Electrical connection must be done in de-energized state!
11
The voltage source should be preferably realized as a stabilized power supply unit with safe voltage from
18 to 36 V DC (18 ÷ 30 V DC at version Xi(XiT)), which can be a part of the evaluation or display device.
In case of strong electromagnetic interferences (EMI), parallel cable ducting with power lines, or when cable length exceeds 30 m we recommended to use shielded cable.
CLM–36 © Dinel, s.r.o.
9 . p
reparing
of
level
Meter
for
Measuring
PREPERING OF LEVEL METER
1. For access to the adjustment elements disconnect a connector and unscrew a nut
(attention for inside connecting wires). Connector connect again.
2. Level meter connect to the supply unit through miliampermeter (controller, etc.).
3. Trimmer
1)
20 mA bring into the basic position (this position is set by producer): a) Turn out trimmer totally right wards (in clockwise).
b) Return back for 3 turns left wards.
ADJUSTMENT ELEMENTS OF LEVEL METER green-yellow wire
( )
blue wire
(-)
brown wire
(+)
trimmer 4 mA
(for compensation of initial capacity)
trimmer 20 mA
(for sensitive span adjustment)
DIP switches
(for range select)
brass tie
(for pull out of elecronic module)
Fig. 13: The top view on the internal electronic module with current outptu (variant –I)
green-yellow wire
( )
black wire
(Uout)
blue wire
(-)
brown wire
(+)
trimmer 0 V
(for compensation of initial capacity)
trimmer 10 V
(for sensitive span adjustment)
0V 10V
DIP switches
(for range select)
brass tie
(for pull out of elecronic module)
Fig. 14: The top view on the internal electronic module with voltage outptu (variant –U)
1) The trimmers are without backstops - approx. 15 turns.
© Dinel, s.r.o. CLM–36
12
10 . s
etting
CURRENT OUTPUT 4 ... 20 mA
1. Empty tank to the minimum level.
2. By DIP switches on level meter set range
3)
No. 2 (250 pF).
3. Turn by screwdriver in trimmer 4 mA and set quiescent current of the level meter to
4 mA. Turning right wards (in clockwise) increase the current, turning left wards
DIP switches to the nearest higher range and set up of current 4 mA perform at this range. decrease the current. When is impossible to set required current to 4 mA, then switch
4. Fill the tank to the maximum level. When it is impossible fill the tank to the maximum
state then we use some known (measurable) level and current for next setting calculate according to formula:
5. If the output current is less than 20 mA (or the value of I out), set to the lowest range No. 1. by DIP switches and continue to step 7. When the output current reaches
20 mA , continue on step 6.
6. By DIP switches step wise switch to higher ranges till the current is greater then
20 mA (or calculated value I out), through level meter then flows current e.g. 21 mA
Trimmer 20 mA is still in basic position.
4)
.
7. Then set by trimmer 20 mA current of level meter to 20 mA (or to calculated value I out
- see bellow).
8. To reach a maximum accuracy is useful to check over the setting of 4 mA
(compensation of initial capacity - quiescent current).
VOLTAGE OUTPUT 0 ... 10 V
1. Empty tank to the minimum level.
2. By DIP switches on level meter set range
3)
No. 2 (250 pF).
3. Turn by screwdriver in trimmer 0 V and set voltage output of the level meter to
0 V. Turning right wards (in clockwise) increase the voltage, turning left wards
DIP switches to the nearest higher range and set up of voltage 0 V perform at this range.
decrease the voltage. When is impossible to set required voltage to 0 V, then switch
4. Fill the tank to the maximum level. When it is impossible fill the tank to the maximum
state then we use some known (measurable) level and voltage for next setting calculate according to formula:
U out = 0,1 x level in % [V]
5. If the output voltage is less than 10 V (or the value of U out), set to the lowest range No. 1. by DIP switches and continue to step 7. When the output voltage reaches
10 V, continue on step 6.
2) Sensitivity - minimal capacity change of electrode to reach output range 4 ÷ 20 mA or 0 ÷10 V.
3) Range = capacity of housing + activated electrode to reach output range 4 ÷ 20 mA or 0 ÷10 V.
(For example.: uncoated electrode 1000 mm immersion in fuel: 20 pF + 30 pF, coated electrode 1000 mm immersion in water: 20 pF + 500 pF)
4) In case of short of electrode on housing or setting of a very sensitive range can caused to current restriction of level meter on value max. 30 mA.
13 CLM–36 © Dinel, s.r.o.
6. By DIP switches step wise switch to higher ranges till the voltage is greater then
10 V (or calculated value U out), output voltage of the level meter is then e.g. 10,5 V.
Trimmer 10 V is still in basic position.
7. Then set by trimmer 10 V voltage of level meter to 10 V (or to calculated value U out
- see bellow).
8. To reach a maximum accuracy is useful to check over the setting of 0 V.
No.
Sensitivity
(S)
2)
Range
(R)
3)
Position of
DIP switch
5
6
3
4
1
1)
2
20 pF
30 pF
50 pF
100 pF
150 pF
300 pF
70 pF
250 pF
600 pF
1 200 pF
3 000 pF
7 000 pF
7 500 pF 18 000 pF
8 1 000 pF 36 000 pF
1) Range No. 1 (70 pF) is very sensitive and we recommend to use it only at level meters with short
electrode (approx. to 500 mm) and measured media with low permittivity.
Tab. 1:
Table of ranges
Medium Písek, zrniny
Typ 1 m 5 m
10 2 3
12 2 3
30 2 3
Cement
1 m 5 m
2 4
2 4
2 4
1 m
Mouka
5 m
1 3
1 3
1 3
Medium
Typ
10
12
20
22
32
3
3
3
-
1 m
Voda
2 m
-
4
4
4
-
Benzín, petrolej, nafta, oleje
1 m 2 m
1
2
1
1
2
Tab. 2: Tables of recommended ranges depending on the medium and the type of level meter
2
3
2
2
3
Note: Types 10, 12, 30, 31, 32 in distance 250 mm from conducting wall.
Showned ranges are orientation. Exact range for existing configuration electrode / tank must be set directly in application on mearured medium.
© Dinel, s.r.o. CLM–36
14
11 . u
se
,
Manipulation
and
Maintenance
The level meter does not require any personnel for its operation. Follow-up displaying device is used to inform the technological entity operating personnel on the measured substance level height during the operation.
MAINTAINCE OF LEVEL METER
Maintenance of this equipment consists in verification of integrity of the level meter and of the supply cable. Depending on the character of the substance measured, we recommend to verify at least once per year the clarity of the ultrasound transducer emitting field and to clean it, respectively. In case any visible defects are discovered, the manufacturer or reseller of this equipment must be contacted immediately.
The level meter must be installed to prevent tensile overload of the rope electrode.
It is forbidden to perform any modifications or interventions into the CLM–36 level meter without manufacturer's approval. Potential repairs must be carried out by the manufacturer or by a manufacturer authorized service organization only.
Installation, commissioning, operation and maintenance of the CLM–36 level meter has to be carried out in accordance with this instruction manual; the provisions of regulations in force regarding the installation of electrical equipment have to be adhered to.
REPLACEMENT OF DEFECTIVE ELECTRONIC
In case of detected electronic failure it is possible to replace the electronic module directly in process place of level meter by following procedure:
1. Disconnect connector and unscrew a nut (attention for inside connecting wires).
2. Defective electronic module pick up by pliers onto brass tie and remove by tensile from housing of level meter.
3. Check placing of white seal O-ring in housing and on pressure ring.
4. Repaired or new electronic module return back into housing of level meter and press down by clamping ring (attention that contact pin will be a little open before insertion and contact springs were not pressed under level of electronic casing).
5. Check placing of black seal O-ring on connector.
6. Screw a nut back (attention for inside connecting wires) and connect the connector.
trimmers brass tie
15 electronic module cover contact springs contact pin
Fig. 15: Side view of the electronic module
CLM–36 © Dinel, s.r.o.
12 . o
rder
code
CLM – 36 – – – E
Length electrode in mm
Output type:
I – current (4 ... 20 mA)
U – voltage (0 ... 10 V)
Process connection:
M – thread M36x2
G – thread G1" (G1½" for CLM – 36_–40)
Cl – Tri-clamp
Electrode performance:
10 – Uncoated St. steel rod electrode
11 – Fully coated St. steel rod electrode (PFA)
12 – Fully coated St. steel rod electrode (FEP)
20 – Uncoated St. steel rod electrode with reference tube
22 – Coated St. steel rod electrode with reference tube (FEP)
30 – Uncoated St. steel rope electrode and weight (max. 20 m)
31 – Uncoated St. steel rope electrode with anchor (max. 20 m)
32 – Fully coated rope electrode and weight (FEP + PTFE)
40 – Two fully coated St. steel rod electrode (FEP) (max. 2 m)
Performance:
N – normal (for non-explosive areas)
Xi – Explosion proof - intrisically safe for hazardous (explos
ive) areas, only with "I" output (except CLM-30_-40)
NT, XiT – High temperature performance
13 . c
orrect
specification
exaMples
CLM – 36N–10–G–I E1100
CLM – 36Xi–20–M–I E900
CLM – 36N–32–G–U E6000
CLM – 36NT–12–M–I E1500
CLM – 36Xi–30–M–I E12000
CLM – 36N–12–Cl–I E2000
14 . a
ccessories
Standard – included in the level meter price
• 1x of seal, other seals are on request (PTFE,
Al, etc.)
• 1x connector socket
• 1x screwdriver for adjustment (each
5 pcs)
• Distance element for rods longer than 50 cm (for CLM – 36_–40)
© Dinel, s.r.o. CLM–36
16
Optional (see datasheets "Accessories")
• Connector with protection class IP67
(GAN–DADE 7A) with 5 m cable (current output)
• Connector with protection class IP67
(GAN–DAAE 7A) with 5 m cable (voltage output)
• Steel welding flange ON–36x2
• St. steel welding flange NN–36x2
• St. steel fixing nut UM–36x2
• Anchor welding cylinder KV–31
(only CLM–36–31)
• Dust-tight bushing PR–31
(only CLM–36–31)
15 . s
afety
,
protections
,
coMpatibility
and
explosion
proof
Level meter CLM–36 is equipped with protection against electric shock on electrode, reverse polarity, output current overload, short circuit and short time over voltages.
Protection against dangerous contact is secured by low safety voltage that complies with
EN 33 2000-4-41.
Electromagnetic compatibility is provided by conformity with standards: EN 55022/B, EN 61326-1,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6.
Explosion proof of CLM–36Xi is examined by FTZÚ-AO 210 Ostrava - Radvanice certificate No.:
FTZÚ 02 ATEX 0235X.
Special conditions for safe use of variant CLM–70Xi
Equipment is designed to be connected to isolating repeater IRU-420
If other approved apparatus is used, which output parameters comply with above mentioned input parameters it is necessary to have an galvanic separation or in a case of apparatus without galvanic separation (Zener barriers) it is necessary to provide equipotential equalizing between sensor and barrier earthing point.
Design CLM-36Xi can be used in zone 0 or zone 20. With design CLM-36XiT can be only used in zone 0 and zone 20 electrode part and head with electronics can be used only in zone 1 or zone 21.
Maximum temperature of electrodes is equal to temperature of measured medium.
When used in zone 0 the present explosive atmosphere of air mixture and gases, vapours or mists must comply with: - 20°C < T amb
< 60°C 0,8 bar < p < 1,1 bar
17 CLM–36 © Dinel, s.r.o.
16 . M
arking
of
labels
Level meters label data
CLM–36N(T)–_ _–_–I:
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
1
2
U
0 V
CLM-36N_-__-__-I
U = 9 ... 36 V I = 4 ... 20 mA
E_____ No.: ______
IP65
IP67
Symbol of producer: logo Dinel
®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-N_-__-_-I, P/N include length of electrode: E in mm
Serial number: Ser. No.: ______ - (from the left: production year, serial production number)
Dinel
Dinel
Zlín, Czech Republic www.dinel.cz
i
= 9 ÷ 36 V DC
i
Compliance mark:
2
Protection class: IP 65 / IP 67 a
Electro-waste take-back system mark
:
CLM-36N_-__-__-U E_____ No.: ______
U out
CLM-36N_-__-__-I
= -40 ... +85 °C
U out
= 0 ÷ 10 V
I = 4 ... 20 mA
E_____ No.: ______
IP65
IP65
IP67
Dinel
Dinel, s.r.o.
Zlín, Czech Republic
Dinel [email protected]
U
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
U
3
2
3
2
V
V
U i
U out
U i
0 V
U out
0 V
CLM-36N_-__-__-U E_____ No.: ______
U out
CLM-36N_-__-__-U
= 0 ÷ 5 V
U out
= 0 ÷ 10 V
E_____ No.: ______
IP65
IP67
IP65
IP67
Symbol of producer: logo Dinel
®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U i
, U out
, 0V, GND
Type of level meter: CLM-36-N_-__-_-U, P/N include length of electrode: E in mm
Dinel
Serial number: Ser. No.: ______ - (from the left: production year, serial production number)
Supply voltage: U
Dinel
i
Output voltage range: U
2
out
Ambient temperature range: t
Protection class: IP 65 / IP 67
Compliance mark:
www.dinel.cz
a
U i
U out
0 V
= 0 ÷ 10 V (or 0 ÷ 5 V)
Electro-waste take-back system mark
:
II1G
II1D
U
ExiaII BT5Ga
ExiaII out
= 0 ÷ 5 V
E_____
ICT83°CDa
FTZÚ 02 ATEX 0235X
No.: ______
IP65
IP67
IP65
IP67
1026
Dinel
Dinel, s.r.o.
© Dinel, s.r.o. CLM–36
Czech Republic www.dinel.cz
U i
U i
CLM-36XiT-__-__-I
CLM-36Xi-__-__-I
II1/2D ExiaII
E_____
E_____
BT5Ga/Gb
ICT83°CDa/Db
No.: ______
No.: ______
II1D ExiaII
FTZÚ 02 ATEX 0235X
FTZÚ 02 ATEX 0235X
IP65
IP67
1026
1026
18
Dinel
Dinel, s.r.o.
Zlín
Czech Republic www.dinel.cz
U i
CLM-36XiT-__-__-I
II1/2G ExiaII BT5Ga/Gb
II1/2D ExiaII ICT83°CDa/Db
FTZÚ 02 ATEX 0235X
E_____ No.: ______
IP65
IP67
1026
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
1
2
U
0 V
CLM-36N_-__-__-I
U = 9 ... 36 V I = 4 ... 20 mA
E_____ No.: ______
IP65
IP67
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
U
3
2
V
U i
U out
0 V
CLM-36N_-__-__-U
U out
= 0 ÷ 10 V
E_____ No.: ______
IP65
IP67
1
2
U
3
2
V
U i
U out
0 V
U
0 V
CLM-36N_-__-__-I
U out
= 0 ÷ 5 V
E_____ No.: ______
U = 9 ... 36 V I = 4 ... 20 mA
CLM-36N_-__-__-U
IP65
IP67
E_____ No.: ______
IP65
IP67
Dinel
Dinel, s.r.o.
Zlín, Czech Republic www.dinel.cz
U
Level meters label data
CLM–36Xi:
3
2
V
U i
U out
0 V
CLM-36N_-__-__-U
U out
= 0 ÷ 10 V
E_____ No.: ______
IP65
IP67
Dinel www.dinel.cz
U
3
2
V
U i
CLM-36Xi-__-__-I
II1G
U i
U out
II1D
ExiaII
ExiaII
BT5Ga
E_____
U out
= 0 ÷ 5 V
No.: ______
E_____ No.: ______
IP65
IP67
IP65
IP67
1026
Symbol of producer: logo Dinel
®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-Xi-__-_, P/N include length of electrode: E in mm
Serial number: Ser. No.: ______ - (from the left: production year, serial production number)
Dinel
Dinel, s.r.o.
Zlín [email protected]
U i
CLM-36XiT-__-__-I
II1/2D
ExiaII
ExiaII
E_____
BT5Ga/Gb
No.: ______
Number of certificate of intrinsically safety: FTZÚ 02 ATEX 0235X
IP65
IP67
1026
= 370 nF, Limit operating parameters: U i
= 30 V DC, I
Dinel
i
Czech Republic [email protected]
Compliance mark:
U i
Ambient temperature range: t
Protection class: IP 65 / IP 67 a
II1G
II1D
Electro-waste take-back system mark
:
= 132 mA, P
ExiaII
ExiaII
BT5Ga
ICT83°CDa
FTZÚ 02 ATEX 0235X
i
= 0,99 W, C
IP65
IP67
1026
Level meters label data
GRLM–70XiT:
Dinel
Dinel, s.r.o.
Zlín
Czech Republic www.dinel.cz
U i
CLM-36XiT-__-__-I
II1/2G ExiaII BT5Ga/Gb
II1/2D ExiaII ICT83°CDa/Db
FTZÚ 02 ATEX 0235X
E_____ No.: ______
IP65
IP67
1026
19
Symbol of producer: logo Dinel
®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-XiT-__-_, P/N include length of electrode: E in mm
Serial number: Ser. No.: ______ - (from the left: production year, serial production number)
Label of non-explosive device:
Performance: II 1/2 G Ex ia IIB T5 Ga/Gb, II1/2D Ex ia IIIC T83°C Da/Db
No. of authorized person examining control of system quality: 1026
Number of certificate of intrinsically safety: FTZÚ 02 ATEX 0235X
Limit operating parameters:U
L i
= 0,9 mH i
= 30 V DC, I i
= 132 mA, P i
= 0,99 W, C i
= 370 nF,
Ambient temperature range: t a
Protection class: IP 65 / IP 67
= -40 ... +75 °C, t a
= -20 ... +60 °C (zone 0)
Compliance mark:
Electro-waste take-back system mark
:
CLM–36 © Dinel, s.r.o.
17 . s
pecification
t echnical
specification
(variants N, NT)
Supply voltage
CLM – 36N(T)–_ _–_–I
CLM – 36N(T)–_ _–_–U
Current output
Voltage output
Power consumption (off-load) CLM–36N(T)–_ _–_–U
Sensitivity ranges
Initial capacity regulation ratio
Nonlinearity
Temperature error
Voltage error for current and voltage output
Internal resistance / Electric strength (Electrode – Housing)
Coupling capacity / Electric strength (Housing – Supply leads)
Protection class
Standard
Optional (Connector GAN-DADE 7A / DAEE 7A)
Maximal load (serial) resistance for current output (U = 24 V)
Minimal load resistance for voltage output
Maximum tensile strength of the rope electrode
Recommended cable
Weight (exclude electrode)
Version N, Xi
Version NT, XiT
e lectrical
paraMeters
(variants Xi, XiT)
Supply voltage
9 ... 36 V DC
16 ... 36 V DC
4 ... 20 mA
0 ... 10 V approx. 8mA
20 ; 30 ; 50 ; 100 ; 150 ;
300 ; 500 ; 1000 pF min. 1:2 max. 1 % max. 0,05% / K max. 0,3 μA/V and 0,1 mV/V
1 MΩ / 250 V AC
51 nF / 250 V AC
IP67 (Housing), IP65 (Connector)
IP67
R max
= 750 Ω
R min
> 1 kΩ
1400 kg
PVC 2x0,75 mm
2
(3x0,5 mm
2
) approx. 0,5 kg approx. 1 kg
Max. internal values
Internal resistance / Electric strength (Electrode – Housing)
9 ... 30 V DC
Ui = 30 V DC; Ii = 132 mA;
Pi = 0,99 W; Ci = 370 nF;
Li = 0,9 mH
1 MΩ / 250 V AC
Coupling capacity / Electric strength (Housing – Supply leads)
Allowed temperature range in zone 0 (EN 50284)
Allowed pressure range in zone 0 (EN 50284)
p rocess
connection
Type
Metric thread
Pipe thread (except CLM–36–40)
Pipe thread for CLM–36–40)
Tri-clamp (standards DN 20)
© Dinel, s.r.o. CLM–36
Size
M36 x 2
G 1"
G 1½"
–
Marking
G
Cl
M
G
26 nF / 500 V AC
-20 ... +60°C
0,08 ... 0,11 MPa
20
21 CLM–36 © Dinel, s.r.o.
t eMperature
durability
Variants / Performance temperature t m temperature t p
CLM –36N–10, 20
CLM –36N–11, 12, 22
CLM–36N–30
CLM –36N–31 (incl. PR–31)
CLM –36N–31 (incl. KV–31)
CLM –36N–32
CLM –36N–40
CLM –36Xi–10, 20
CLM –36Xi–11, 12, 22
CLM–36Xi–30
CLM –36Xi–31 (incl. PR–31)
CLM –36Xi–31 (incl. KV–31)
CLM –36Xi–32
CLM –36NT–10, 20
CLM –36NT–11, 12, 22
-40°C ... +300°C
-40°C ... +200°C
-40°C ... +200°C
-40°C ... +130°C
-40°C ... +250°C
-40°C ... +130°C
-40°C ... +100°C
-40°C ... +200°C
-40°C ... +120°C
-40°C ... +105°C
-40°C ... +105°C
-40°C ... +105°C
-40°C ... +105°C
-40°C ... +300°C
-40°C ... +200°C
CLM –36NT–30
CLM –36NT–31 (incl. PR–31)
CLM –36NT–31 (incl. KV–31)
CLM –36NT–32
CLM –36XiT–10, 20
CLM –36XiT–11, 12, 22
CLM –36XiT–30
CLM –36XiT–31 (incl. PR–31)
-40°C ... +250°C
-40°C ... +130°C
-40°C ... +250°C
-40°C ... +130°C
-40°C ... +200°C
-40°C ... +120°C
-40°C ... +250°C
-40°C ... +130°C
-40°C ... +130°C
-40°C ... +130°C
-40°C ... +130°C
-40°C ... +130°C
-40°C ... +200°C
-40°C ... +200°C
-40°C ... +130°C
-40°C ... +130°C
CLM –36XiT–31 (incl. KV–31)
CLM –36XiT–32
-40°C ... +250°C
-40°C ... +130°C
-40°C ... +130°C
-40°C ... +130°C
Note: For correct function of the level meter must not be exceeded any of the temperature range (
t p, t m
or
t a
)
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +200°C
-40°C ... +200°C
1) The temperatures are clearly explained on Fig. 16.
temperature t a
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +85°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
-40°C ... +75°C
© Dinel, s.r.o. CLM–36
22
t a
– Ambient temperature range
(on housing)
t p –
Temperature in process connection place
t m –
Medium operating temperature
N, Xi variants
NT, XiT variants
CLM –36N–10, 20
CLM –36N–11, 12, 22
CLM–36N–30
CLM –36N–31
CLM –36N–32
CLM –36N–40
CLM –36Xi–10, 20
CLM –36Xi–11, 12, 22
CLM–36Xi–30
CLM –36Xi–31
CLM –36Xi–32
CLM –36NT–10, 20
CLM –36NT–11, 12, 22
CLM –36NT–30
CLM –36NT–31
CLM –36NT–32
CLM –36XiT–10, 20
CLM –36XiT–11, 12, 22
CLM –36XiT–30
CLM –36XiT–31
CLM –36XiT–32
23
Fig. 16: Points for temperature determination on the level meter
p ressure
durability
Variants / Performance
–
1 MPa
7 MPa
6 MPa
7 MPa
–
1 MPa
7 MPa
6 MPa
7 MPa
–
1 MPa
to 30°C
7 MPa
4 MPa
7 MPa
–
1 MPa
0,1 MPa
7 MPa
4 MPa
7 MPa
–
0,5 MPa
5 MPa
4 MPa
5 MPa
–
0,5 MPa
5 MPa
4 MPa
5 MPa
–
0,5 MPa
Maximal operation pressure for temperature t p to 85°C to 130°C to 160°C to 200°C
5 MPa – – –
2 MPa – – –
5 MPa
–
0,5 MPa
0,1 MPa
5 MPa
2 MPa
5 MPa
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
3 MPa
2 MPa
3 MPa
–
0,1 MPa
3 MPa
2 MPa
3 MPa
–
0,1 MPa
–
–
2 MPa
1,5 MPa
–
–
–
2 MPa
–
–
1 MPa
0,3 MPa
–
–
–
1 MPa
–
–
1,5 MPa
–
0,3 MPa
–
–
–
CLM–36 © Dinel, s.r.o.
M aterial
Acetone
Acetylentetrachloride
Aminoplasts
Ammonia
Aniline
Ash
Benzaldehyde
Benzene
Benzol
Celluloide
Cement
Dioxane
Ebonit
Ethanol
Ethylacetate
Ethyleneglycol
Ethylenechloride
Flint crystal
Flour
Food salt (NaCl)
Freon R22
Fused quartz
Gasoline (benzin)
Glass
Glass organic
Glass silicate
Glazed carton
Glycerine
Grains
Hardened textile
Hexane
ε
r ... dielectric constant
© Dinel, s.r.o. CLM–36
18 . t
able
of
relative
perMittivity
ε r
24
6,0
38,7
10,5
4,5
2,5 ÷ 3,0
6,0
6,1
3,7
2,0 ÷ 2,2
3,7 ÷ 10
3 ÷ 3,6
16
3,5
47
3,0 ÷ 5,0
2 ÷ 6
1,9
19,5 ÷ 21,4
8,1
5 ÷ 8
15 ÷ 24
6,9
1,5 ÷ 1,7
18,3
2,28 ÷ 2,3
2,3
3,5 ÷ 6,2
4,0
2,235
2,5 ÷ 5
M ateriál
Chloroforme
Ice
Liquefied air
Liquefied CO2
Liquefied chlore
Liquefied propan
Marble
Methanol
Mica
Mikanite
Milk powder
Monochlorbenzene
Nitrobenzene
Ortonitrotoluene
Paper
Paraffin
Paraffin oil
Paraffinic oil
Petroleum
Polyacetal
Polyamide - PA
Polydichlorstyrole
Polyetheretherketone - PEEK
Polyetherimide - PEI
Polyethylene - PE
Polyfenylenesulfide - PPS
Polymethylmetakrylate
Polypropylene - PP
Polystyrole
Polysulphone - PSU
Polytetrafluorethylene - PTFE
ε r
ε r
27,4
1,6 ÷ 2,6
1,9 ÷ 2,5
1,9 ÷ 2,5
2,2
2,0 ÷ 2,2
3,6 ÷ 3,7
4,0 ÷ 5,0
2,7
3,2
3,0
2,16
3,3
2,56
2,0 ÷ 2,2
2,39
3,0
2,0 ÷ 2,1
4,81
3,1
1,5
1,6
2,0
1,6 ÷ 1,9
9,3 ÷ 11,6
32,7 ÷ 33,8
5 ÷ 8
4,5 ÷ 6
3,5 ÷ 4
4,0
35,7
24
M ateriál
Polyvinylacetate
Polyvinylchloride - PVC
Polyvinylidenefluoride
Porcelain
Pyridine
Rape-seed (colza) oil
Resin - acrylic
Resin - epoxy
Resin - melamine
Resin - phenolic
Resin - polyester
Resin - styrene
Resin - ureal
Rubber
Sand
Silicon caoutchouc
Succinite
Sugar
Sulphur
Toluene
Trichlorethylene
Trolitule
Vaseline
Water
Water solution
White beeswax
Wood - damp
Wood - dry
ε r
2,0 ÷ 6,0
3,0 ÷ 5,0
2,8 ÷ 3,3
2,9
3,0
3,4 ÷ 3,6
2,3 ÷ 2,38
3,43
2 ÷ 2,6
2,2 ÷ 2,9
81
50 ÷ 80
2,0 ÷ 2,9
10 ÷ 30
2 ÷ 6
2,7
2,51 ÷ 3,1
6,0 ÷ 7,4
4,5 ÷ 7
13,6
2,8
2,4 ÷ 4,5
2,5 ÷ 8,0
4,7 ÷ 10,2
4,0 ÷ 12,0
2,8 ÷ 8,1
2,3 ÷ 3,4
5,0 ÷ 8,0
25 CLM–36 © Dinel, s.r.o.
© Dinel, s.r.o. CLM–36
26
industrial electronics
Dinel, s.r.o.
U Tescomy 249
760 01 Zlín
Czech Republic
Tel.: +420 577 002 003
Fax: +420 577 002 007
E-mail: [email protected]
www.dinel.cz
The lastest version of this instruction manual can be found at www.dinel.cz
Version: 9/2014
advertisement
Key Features
- Continuous level measurement
- Suitable for liquids, powders, and bulk-solid materials
- Stainless steel housing with electronic module
- Current signal (4 ... 20 mA) or voltage signal (0 ... 10 V)
- Adjustable sensitivity and initial capacity compensation
- Non-hazardous and explosion-proof versions
- High temperature performance
- Various process coupling options