DIR 1000719R0807 Version 02 - 140G-G-TLC_, 140G-H-TLC_, 140G-I-TLC_, 140G-J-TLC_
Cu/Copper terminal lug installation 140G-G, 140G-H, 140G-I, 140G-J
Cu/Terminali anteriori per cavi in rame (Cu)
Cu/Vorderseitige Anschlüsse für Kabel aus Kupfer (Cu)
Cu/Prises avant pour câbles en cuivre (Cu)
Cu/Terminales frontales para cables de cobre (Cu)
Installation - Installazione - Instalación
Instalação - -
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.
(Follow NFPA70E requirements).
AVVERTENZA: Per prevenire infortuni, togliere tensione prima dell'installazione o manutenzione. Installare in custodia idonea. Tenere lontano da contaminanti.
(Seguire i requisiti NFPA70E).
WARNUNG: Vor Installations- oder Servicearbeiten Stromversorgung zur
Vermeidung von elektrischen Unfällen trennen. Die Geräte müssen in einem passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden. (Befolgen
Sie die Anforderungen nach NFPA70E).
AVERTISSEMENT: Avant le montage et la mise en service, couper l'alimentation secteur pour éviter toute décharge. Prévoir une mise en coffret ou armoire appropriée.
Protéger le produit contre les environnements agressifs. (Vous devez respecter la norme NFPA70E).
ADVERTENCIA: Desconéctese de la corriente eléctrica, antes de la instalación o del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una caja apropiada.
Manténgalo libre de contaminantes. (Cumpla con los requisitos NFPA70E).
ATENÇÃO: Para evitar choques, desconectar da corrente elétrica antes de fazer a instalação ou a manutenção. Instalar em caixa apropriada. Manter livre de contaminantes. (Cumpra as exigências da norma NFPA70E).
警告:感電事故防止のため、取付けまたは修理の際は電源から取り外してく
ださい。適切なケース内に取付けてください。また、汚染物質がないことを
確認してください。( NFPA70E の要件に従ってください)
警告:为了防止触电,在安装或维修之前必须先切断电源。安装在合适的设备
物
140G-G
1
CLACK
Bul. 140G/140MG
140G-I
Lug
End cap kit
140G-H 140G-J
1
CLACK
140G-G
3p 4p x3 x3
/ x4 x4
/
140G-H
3p 4p x3
/ x3 x4
/ x4
CH 4
LENGTH M
21 mm (0.83") M 8
140G-I
3p
4p x3
/ x3 x4
/ x4
/ x3
140G-J
3p 4p x3 x4
CH 5
LENGTH M
25 mm (0.98") M 8
/ x4
DIR 1000719R0807 Version 02
1 2
2
1
140G-G
3
2
1
2
2
- If present
- Se presente
- Falls vorhanden
- Si présent
- Si lo hay
140G-H
140G-I
140G-J
4
1 dia. MAX A
1
CH 4
140G-G 62 lb-in/7 Nm
140G-H ≤ 1/0 AWG or < 50mm² 62 lb-in/7 Nm
140G-H ≥ 50mm² 75 lb-in/8,5 Nm
2
140G-I 124 lb-in/14 Nm
140G-J 124 lb-in/14 Nm
CH 5
3
140G-G
MIN
MAX
140G-H
MIN
MAX
140G-I
140G-J
MIN
MAX
Stranded Cable
AWG/kcmil mm
2
Flexible cable mm
2
14 AWG 2.5
-
1/0 AWG
14 AWG
1/0 AWG
10 AWG
250 kcmil
70
2.5
95
6
185 -
-
-
-
-
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
A
B
140G-G 140G-H 140G-I
0.47"
12 mm
0.47"
12 mm
0.55"
14 mm
0.55"
14 mm
0.71"
18 mm
0.78"
20 mm
140G-J
0.71"
18 mm
0.78"
20 mm
4
4
- If present
- Se presente
- Falls vorhanden
- Si présent
- Si lo hay
Rockwell Automation maintains current product environmental compliance information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/ sustainability-ethics/product-environmental-compliance.page
Publication 140G-IN092C-MU-P - May 2016 DIR 1000719R0807 Version 02 (B0600) - B0910
Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. Printed in Italy.