- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Toshiba
- RAV-SM 561AT-E
- Service manual
RAV-SM 1401AT-E | RAV-SM 1101AT-E | RAV-SM 801AT-E | TOSHIBA RAV-SM 561AT-E, 801AT-E, 1101AT-E, 1401AT-E split-system air conditioner Service Manual 77 Pages
RAV-SM 1401AT-E | RAV-SM 1101AT-E | RAV-SM 801AT-E | TOSHIBA RAV-SM 561AT-E, 801AT-E, 1101AT-E, 1401AT-E split-system air conditioner Service Manual
Add to My manuals77 Pages
Below you will find brief information for RAV-SM561AT-E, RAV-SM801AT-E, RAV-SM1101AT-E. This service manual describes the contents of the new outdoor unit. This air conditioner adopts the new refrigerant HFC R410A which does not damage the ozone layer.
advertisement
FILE NO. A05-001
SERVICE MANUAL
SPLIT TYPE
<NEW DIGITAL INVERTER>
OUTDOOR UNIT
RAV-SM561AT-E
RAV-SM801AT-E
RAV-SM1101AT-E
RAV-SM1401AT-E
INDOOR UNIT
This Service Manual describes contents of the new outdoor unit.
For the indoor unit, refer to the Service Manual with FILE NO. A03-003F.
R410A
PRINTED IN JAPAN, Apr.,2005 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
1. SPECIFICATIONS ........................................................................................................... 3
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ............................................................. 5
3. REFRIGERATING CYCLE DIAGRAM ............................................................................ 8
4. WIRING DIAGRAM ....................................................................................................... 11
5. SPECIFICATIONS OF ELECTRICAL PARTS ............................................................... 12
6. REFRIGERANT R410A ................................................................................................. 13
6-1. Safety During Installation/Servicing ................................................................................ 13
6-2. Refrigerant Piping Installation ....................................................................................... 13
6-3. Tools ................................................................................................................................... 17
6-4. Recharging of Refrigerant ................................................................................................ 18
6-5. Brazing of Pipes ................................................................................................................ 19
7. CONTROL SPECIFICATIONS ...................................................................................... 21
7-1. Outdoor Controls .............................................................................................................. 21
7-2. Outline of Main Controls ................................................................................................... 24
8. TROUBLESHOOTING .................................................................................................. 29
8-1. Summary of Troubleshooting ........................................................................................... 29
8-2. Check Code List ................................................................................................................ 31
8-3. Error Mode Judgment by LED Display of Outdoor Unit ................................................ 34
8-4. Contents of Error Display ................................................................................................. 35
8-5. Troubleshooting Procedure for Each Check Code ......................................................... 36
8-5. Other Function ................................................................................................................... 57
9. DETACHMENTS ............................................................................................................ 58
10. EXPLODED VIEWS AND PARTS LIST ........................................................................ 73
– 2 –
1. SPECIFICATIONS
RAV-SM561AT-E, RAV-SM801AT-E
Appearance
Power supply
Compressor
Refrigerant charged
Pole
Refrigerant control
Type
Motor
Pipe
Standard length
Max. total length (m)
Over 20m
(kW)
(kg)
Height difference
Outdoor lower (m)
Outdoor higher (m)
Height
Outer dimension Width
Depth
(mm)
(mm)
(mm)
(kg) Total weight
Heat exchanger
Fan unit
Connecting pipe
Fan
Standard air flow High
Motor
Gas side
Liquid side
(m³/h)
(W)
(mm)
(mm)
Protection device
Model name RAV-SM561AT-E RAV-SM801AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230 V (220 – 240 V) 50 Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1
1.6
4 poles
R410A 1.0
R410A 1.7
Pulse motor valve
20 (without additional charge)
30
Add 20 g/m (Max. 200 g) Add 40 g/m (Max. 400 g)
30
30
550
780
290
38 42
Finned tube
Propeller fan
2400 2700
43
Ø12.7 (1/2”)
Ø6.4 (1/4”)
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
Sound level
(Note 2)
High (Mid./Low)
(Cooling/Heating)
(dB•A) 46 / 48 48 / 50
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 3 –
RAV-SM1101AT-E, RAV-SM1401AT-E
Appearance
Power supply
Model name
Compressor
Refrigerant charged
Pole
Refrigerant control
Type
Motor
Standard length
Max. total length (m)
Pipe
(kW)
(kg)
Over 20m
Height difference
Outdoor lower (m)
Outdoor higher (m)
Outer dimension
Total weight
Heat exchanger
Fan unit
Connecting pipe
Protection device
Height
Width
Depth
Fan
Standard air flow High
Motor
Gas side
Liquid side
(mm)
(mm)
(mm)
(kg)
(m³/h)
(W)
(mm)
(mm)
RAV-SM1101AT-E RAV-SM1401AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230 V (220 – 240 V) 50 Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
2.5
3.0
4 poles
R410A 2.8
Pulse motor valve
30 (without additional charge)
50
Add 40 g/m (Max. 800 g)
30
30
795
780
320
77
Finned tube
Propeller fan
4500
100
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
Sound level
(Note 2)
High (Mid./Low)
(Cooling/Heating)
(dB•A) 53 / 54
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 4 –
RAV-SM561AT-E
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
A legs
Drain hole
(2-Ø20 × 88 long hole)
30
B legs
600
Drain hole (Ø25)
90
108 125
54
2-Ø11-14 U-hole
(For Ø8–Ø10 anchor bolts)
Connecting pipe port
(Flare Ø12.7 at gas side)
Connecting pipe port
(Flare Ø6.4 at liquid side)
8-Ø6 hole
(For fixing outdoor unit)
2-Ø11 × 14 long hole
(For Ø8–Ø10 anchor bolts)
69.5
147
483
108
257
157 79
25
22
31
145
143
54
32
Guard for air discharge
500
780
71
342
Charge port
4-Ø4.5 embossing (Ø4 STS used)
(For mounting air direction guide)
Earth terminal
600
54
38
11
R15
2-Ø6 hole
R5.5
Details of A legs
Product external line
Product external line
2-Ø6 hole
38
54
R15
600
R5.5
Details of B legs
Space required for service
2-Ø11 × 14 U-shape holes
(For Ø8–Ø10 anchor bolt)
Suction port
150 or more
150 or more
Anchor bolt mounting dimension
600
Suction port
300 or more
500 or more
(Minimum distance up to wall)
Discharge port
2-Ø11 × 14 long hole
(For Ø8–Ø10 anchor bolt)
– 5 –
RAV-SM801AT-E
69.5
147
A legs
Drain hole
(2-Ø20 × 88 long hole)
30
B legs
600
Drain hole (Ø25)
90
108 125
54
2-Ø11–14 U-hole
(For Ø8–Ø10 anchor bolts)
Connecting pipe port
(Flare Ø15.9 at gas side)
Connecting pipe port
(Flare Ø9.5 at liquid side)
8-Ø6 hole
(For fixing outdoor unit)
2-Ø11 × 14 long hole
(For Ø8–Ø10 anchor bolts)
483
108
257
157 79
25
22
31
145
143
54
32
Guard for air discharge
500
780
71
Charge port
342
4-Ø4.5 embossing (Ø4 STS used)
(For mounting air direction guide)
Earth terminal
600
54
38
11
R15
2-Ø6 hole
R5.5
Details of A legs
Product external line
Product external line
2-Ø6 hole
38
54
R15
600
R5.5
Details of B legs
Space required for service
2-Ø11 × 14 U-shape holes
(For Ø8–Ø10 anchor bolt)
Suction port
150 or more
150 or more
Anchor bolt mounting dimension
600
Suction port
300 or more
500 or more
(Minimum distance up to wall)
Discharge port
2-Ø11 × 14 long hole
(For Ø8–Ø10 anchor bolt)
– 6 –
RAV-SM1101AT-E, RAV-SM1401AT-E
Knockout
(For draining)
29 90
Drain hole (Ø20 × 88 Burring hole)
191
Suction port
20
Drain hole (Ø25 Burring hole)
Part B
Suction port
Knockout
(For draining)
26 60
150
314
Discharge port
300
900
Part A
95
43
Installation bolt hole
(Ø12 × 17 U-shape holes)
Details of B part
Details of A part
Installation bolt hole
(Ø12 × 17 U-shape holes)
Handles
(Both sides)
Refrigerant pipe connecting port
(Ø9.5 Flare at liquid side)
Refrigerant pipe connecting port
(Ø15.9 Flare at gas side)
2
Discharge guide mounting hole
(4-Ø4 Embossing)
28 320
300
1
27 58
161
400
2
Z
307
60
96
27
1
Knockout for lower piping
86 7
Z views
2 46
1
30 45
Space required for service
2-Ø12 × 17 U-shape holes
(For Ø8–Ø10 Anchor bolt)
600
Suction port
150 or more
150 or more
150 or more
Discharge port
(Minimum distance up to wall)
500 or more
Discharge port
2-Ø12 × 17 long hole
(For Ø8–Ø10 Anchor bolt)
– 7 –
3. REFRIGERATING CYCLE DIAGRAM
RAV-SM561AT-E
Indoor unit
TC sensor
Air heat exchanger
TCJ sensor
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
12.7mm
6.4mm
TS sensor
2-step muffler
Ø19.05 × 200L
Refrigerant pipe at gas side
Ø12.7
Packed valve
Packed valve
Outer dia. ØA
TO sensor
Refrigerant pipe at liquid side
Ø6.4
Packed valve
Min.
5m
Packed valve
Outer dia. ØB
Max.
30m
Outdoor unit
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
TD sensor
Strainer
Rotary compressor
(DA150A1F-20F)
4-way valve
(STF-0108Z)
Muffler
Ø19 × L160
Heat exchanger
Ø8 ripple, 2 rows,
14 steps
FP1.3, flat fin
TE sensor
Distributor
Cooling
Heating
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
Discharge Suction
(TD)
Pipe surface temperature (°C)
(TS)
Indoor heat Outdoor heat exchanger exchanger
(TC) (TE)
Compressor revolutions per second (rps)
*
Indoor fan
Indoor/Outdoor temp. conditions
(DB/WB) (°C)
Indoor Outdoor
Standard 3.50
0.97
35.7
9.9
Cooling Overload 3.90
1.08
39.8
11.0
Low load 1.90
0.70
19.4
7.1
Standard 2.31
0.61
13.6
6.2
Heating Overload 2.86
0.89
29.2
9.1
Low load 1.86
0.25
19.0
2.6
87
86
69
85
93
48
5
17
–14
14
26
7
40
47
31
12
17
5
1
11
–15
48
54
30
97
95
98
70
70
50
HIGH 27/19 35/–
HIGH
LOW
32/24 43/–
18/15.5
–5/–
HIGH
HIGH
HIGH
20/–
28/–
7/6
24/18
15/– –10/
(70%)
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 8 –
RAV-SM801AT-E
Indoor unit
Air heat exchanger
TCJ sensor
TC sensor
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm
9.5mm
TS sensor
TD sensor
Accumulator
(1000cc)
Rotary compressor
(DA150A1F-20F)
2-step muffler
Ø25 × 200L
Pd
Refrigerant pipe at gas side
Ø15.9
Packed valve
Packed valve
Outer dia. ØA
TO sensor
Refrigerant pipe at liquid side
Ø9.5
Packed valve
Min.
5m
Max.
50m
Packed valve
Outdoor unit
Outer dia. ØB
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
Ps
Strainer
4-way valve
(STF-0213Z)
TE sensor
Heat exchanger
Ø8 ripple,
2 rows, 20 steps
FP1.3, flat fin
Distributor
Cooling
Heating
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
Discharge Suction
(TD)
Pipe surface temperature (°C)
(TS)
Indoor heat Outdoor heat exchanger exchanger
(TC) (TE)
Compressor revolutions per second (rps)
*
Indoor fan
Indoor/Outdoor temp. conditions
(DB/WB) (°C)
Indoor Outdoor
Standard 3.28
0.86
33.4
8.8
Cooling Overload 3.59
1.00
33.6
10.2
Low load 1.85
0.83
18.9
8.5
Standard 2.53
0.62
25.8
6.3
Heating Overload 3.42
1.07
34.9
10.9
Low load 1.99
0.23
20.3
2.3
75
80
89
84
82
42
3
20
–19
11
17
8
42
54
34
10
16
6
2
17
–18
45
51
23
95
50
120
83
76
35
HIGH 27/19 35/–
HIGH
LOW
32/24 43/–
18/15.5
–5/–
HIGH
LOW
HIGH
20/–
28/–
7/6
24/18
15/– –10/
(70%)
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 9 –
SM801BT-E /
SM800AT-E, SM800UT-E,
SM800BT-E, SM800KRT-E
RAV-SM1101AT-E, RAV-SM1401AT-E
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm
9.5mm
Cooling: Low pressure
TS sensor
Indoor unit
TCJ sensor Distributor
(Strainer incorporated)
Strainer
Refrigerant pipe at gas side
Ø15.9
Ball valve
Ball valve
Outer dia. ØA
Strainer
TO sensor
Air heat exchanger
TC sensor
Outdoor unit
Refrigerant pipe at liquid side
Ø9.5
Packed valve
Min.
5m
Packed valve
Max.
50m
Outer dia. ØB
PMV
(Pulse Motor Valve)
(UKV-25D22)
TD sensor
Accumulator
(2500cc)
Rotary
Muffler
4-way valve
(STF-0213Z) compressor
(DA420A3F – 21M)
Ø25 × L210
Ø25 × L180
TE sensor
Heat exchanger
Outer side Ø8, 2 rows, 20 steps
FP1.3, flat fin
Inner side Ø9.52, 1 row, 30 steps
FP1.5, flat fin
Distributor
Strainer
Cooling
Heating
RAV-SM1101AT-E
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
3.44
0.92
35.1
9.4
3.73
1.18
38.1
12.0
1.49
0.70
15.2
7.1
2.80
0.61
28.6
6.2
3.43
1.08
35.0
11.0
2.20
0.25
22.4
2.6
(TD)
82
Pipe surface temperature (°C)
Discharge Suction
(TS)
8
Indoor heat Outdoor heat exchanger exchanger
(TC)
10
(TE)
39
Compressor revolutions per second (rps)
*
47
82
39
80
82
76
15
8
0
14
–19
17
3
46
55
36
48
22
1
13
–16
42
30
48
24
55
Indoor fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/–
32/24 43/–
18/15.5
–5/–
20/–
30/–
7/6
24/18
15/– –10/
(70%)
RAV-SM1401AT-E
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
3.52
0.85
35.9
8.7
3.78
1.12
38.6
11.4
1.51
0.71
15.4
7.2
2.88
0.60
29.4
6.1
3.41
1.08
34.8 11.0
2.35
0.24
24.0
2.4
(TD)
87
Pipe surface temperature (°C)
Discharge Suction
(TS)
8
Indoor heat Outdoor heat exchanger exchanger
(TC)
9
(TE)
39
Compressor revolutions per second (rps)
*
54
84
40
85
81
80
15
7
1
14
–19
17
3
47
54
40
47
23
1
13
–16
45
30
61
24
73
Indoor fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/–
32/24 43/–
18/15.5
–5/–
20/–
30/–
7/6
24/18
15/– –10/
(70%)
*
4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 10 –
4. WIRING DIAGRAM
RAV-SM561AT-E, RAV-SM801AT-E
Compressor
RED
WHI
BLK
P04
P05
P06
Q200~205
IGBT
R221
P25
YEL
P24
YEL
BRW
P21
P22
P20
P35
YEL
P23
P34
R220
R219
L03
P.C. Board
(MCC-5009)
C13
F03
Fuse
T3.15A
AC250V
Reactor
P19
P18
P11
P08
Q404
Power relay
DB02
CT
C12 C14
Relay
P33
PUR
P32
CN701
P31 P30
CN300
BLK
WHI
RED
Fan motor
CN700
L01
Varistor
CN603
Surge absorber
Varistor
CN602
F01 Fuse
T25A, AC250V
P03 P10
ORN BLK
P02
WHI
CN601
CN600
Pulse motor valve
TS
(Suction pipe
Temp. sensor)
TO
(Outdoor
Temp. sensor)
TD
(Discharge pipe
Temp. sensor)
TE
(Condensor pipe
Temp. sensor)
P7
BLK
Coil for
4-way valve
To indoor unit
Power supply
220-240V~,
50Hz
Reactor
RAV-SM1101AT-E, RAV-SM1401AT-E
Reactor
1 2
1 2
1 2
1 2
Reactor
+
~
~
~
–
YEL BLU
RED
CN01
F01 Fuse
T25A, 250V~
RY01
WHI
CN02
CN03
Power factor control
P.C. Board
(MCC-1438)
CN09 RED
CN10 WHI
TO
CN11 BLK
W V U
CM
TD
Compressor
1
1
3
3
5
5
CN13
RED
1 2
1 2
CN05
WHI
1 2
1 2
3 4
3 4
5
5
CN06
RED
1
1
3
3
CN04
WHI
1
1
2
2
CN600
BLK
TS TE
1
RED
2
WHI
BLK
3 L
CN02
BLK
1 1
1
1
3 3
5 5
N
Power supply
220V~240V~,50Hz
3
3
5
5
CN01
RED
1 2
1 2
CN04
WHI
1 2
1 2
3 4
3 4
5
5
CN800
RED
CN03
WHI
1
1
3
3
TH
1
1
3
3
CN605
WHI
1
1
2
2
1
1
2
2
CN604
WHI
CN601
WHI
1
1
CN600
WHI
3
3
SUB P.C. Board
(MCC-1531)
1 2
1 2
3 4
3 4
5
5
6
6
CN702
WHI
CN301
WHI
PMV
Pulse motor valve
RED
BLK
1 2
1 2
FM
3
3
Fan motor
1 2
1 2
3 4
3 4
5
5
CN300
WHI
1 2
1 2
3 4
3 4
5
5
CN804
BLU
ORN
1
1
2
2
CN500
BLU
3 3
1 1
1 2
1 2
3 4
3 4
5
5
Optional
P.C.Board
MCC-1522
49C
1 2 3 4 5 6
CN801
7 8
CN700 YEL
3 3
RED
20SF
1 1
RED
Coil for 4-way valve
To indoor unit
– 11 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
RAV-SM561AT-E, RAV-SM801AT-E
5
6
3
4
No.
1
2
9
10
7
8
11
Parts name
Fan motor
Compressor
Reactor
Outdoor temp. sensor (To-sensor)
Heat exchanger sensor (Te-sensor)
Suction temp. sensor (Ts-sensor)
Discharge temp. sensor (Td-sensor)
Fuse (Switching power (Protect))
Fuse (Inverter, input (Current protect)
4-way valve solenoid coil
Compressor thermo. (Protection)
Type
ICF-140-43-4
DA150A1F-20F
CH-57
—
—
—
—
VHV-01AJ503C1
US-622
Specifications
Output (Rated) 43 W
3 phase, 4P, 1100 W
10 mH, 16A
10 k
Ω
at 25°C
10 k
Ω
at 25°C
10 k
Ω
at 25°C
50 k
Ω
at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
RAV-SM1101AT-E, RAV-SM1401AT-E
5
6
3
4
No.
1
2
9
10
7
8
11
Parts name
Fan motor
Compressor
Reactor
Outdoor temp. sensor (To-sensor)
Heat exchanger sensor (Te-sensor)
Suction temp. sensor (Ts-sensor)
Discharge temp. sensor (Td-sensor)
Fuse (Switching power (Protect))
Fuse (Inverter, input (Current protect))
4-way valve solenoid coil
Compressor thermo. (Protection)
Type
ICF-280-100-1
DA420A3F-21M
CH-56-2Z-T
—
—
—
—
VHV-01AJ503C1
US-622
Specifications
Output (Rated) 100 W
3 phase, 4P, 3750 W
6 mH, 18.5 A
10 k
Ω
at 25°C
10 k
Ω
at 25°C
10 k
Ω
at 25°C
50 k
Ω
at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
– 12 –
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
(6) When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
6-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant
R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
(4) When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 6-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 13 –
Nominal diameter
1/4
3/8
1/2
5/8
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Outer diameter (mm)
6.35
9.52
12.70
15.88
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6-
2-6 below.
R410A
0.80
0.80
0.80
1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
Table 6-2-2.
R22
0.80
0.80
0.80
1.00
Nominal diameter
1/4
3/8
1/2
5/8
Table 6-2-2 Minimum thicknesses of socket joints
Reference outer diameter of copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
– 14 –
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
ØD
A
Nominal diameter
1/4
3/8
1/2
5/8
Fig. 6-2-1 Flare processing dimensions
Table 6-2-3 Dimensions related to flare processing for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type
1.0 to 1.5
Wing nut type
1.5 to 2.0
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
2.0 to 2.5
2.0 to 2.5
Nominal diameter
1/4
3/8
1/2
5/8
Table 6-2-4 Dimensions related to flare processing for R22
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R22 clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
1.0 to 1.5
1.0 to 1.5
1.5 to 2.0
1.5 to 2.0
Nominal diameter
1/4
3/8
1/2
5/8
Table 6-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A
9.1
13.2
16.6
19.7
Dimension (mm)
B
9.2
C
6.5
13.5
16.0
19.0
9.7
12.9
16.0
D
13
20
23
25
Flare nut width (mm)
17
22
26
29
– 15 –
Nominal diameter
1/4
3/8
1/2
5/8
3/4
Table 6-2-6 Flare and flare nut dimensions for R22
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
A
9.0
13.0
16.2
19.4
23.3
B
Dimension (mm)
C
9.2
13.5
6.5
9.7
16.0
19.0
24.0
12.9
16.0
19.2
D
13
20
20
23
34
Flare nut width (mm)
17
22
24
27
36
45˚to 46˚
B A
C
D
43˚to 45˚
Fig. 6-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
NOTE:
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 6-2-7 shows reference values.
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Nominal diameter
1/4
3/8
1/2
5/8
Table 6-2-7 Tightening torque of flare for R410A [Reference values]
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
Tightening torque of torque wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
– 16 –
6-3. Tools
6-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditioner installation
Conventional air conditioner installation
No.
Used tool Usage
Existence of new equipment for R410A
Whether conventional equipment can be used
Whether new equipment can be used with conventional refrigerant
Flare tool Pipe flaring Yes *(Note 1) OK
Copper pipe gauge for adjusting projection margin
Flaring by conventional flare tool
Yes *(Note 1) *(Note 1)
Torque wrench
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
Yes
Yes
Yes
Yes
Yes
Yes
(Note 2)
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
OK
OK
NO GOOD
OK
NO GOOD
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by attaching vacuum pump adapter.
(2) Torque wrench
(3) Pipe cutter
(4) Reamer
(5) Pipe bender
(6) Level vial
(7) Screwdriver (+, –)
(8) Spanner or Monkey wrench
(9) Hole core drill (Ø65)
(10) Hexagon wrench
(Opposite side 4mm)
(11) Tape measure
(12) Metal saw
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter
(2) Thermometer
(3) Insulation resistance tester
(4) Electroscope
– 17 –
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Open fully both packed valves at liquid and gas sides.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
Never charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit) (Liquid side)
Opened
(Gas side)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve for charging
Closed
Service port
Electronic balance for refrigerant charging
Fig. 6-4-1 Configuration of refrigerant charging
– 18 –
(OUTDOOR unit)
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ]
Gauge manifold
OUTDOOR unit
[ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit cylinder ant Refriger
Refrigerant cylinder
Electronic balance
Electronic balance
Siphon
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.
Fig. 6-4-2
6-5. Brazing of Pipes
6-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of servicing, use the same type of brazing filler.
6-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler's surface tension, the brazing filler adheres better to the treated metal.
– 19 –
(2) Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid.
It is effective in case where the brazing temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type.
It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used brazing filler/flux
Piping material
Used brazing filler
Used flux
Copper - Copper Phosphor copper Do not use
Copper - Iron
Iron - Iron
Silver
Silver
Paste flux
Vapor flux
6-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/ cm²) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
Nitrogen gas cylinder
M
Flow meter
Stop valve
From Nitrogen cylinder
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Pipe
Rubber plug
Nitrogen gas
Fig. 6-5-1.
Circuit Configuration and Control Specifications
– 20 –
F01, 02, 25A fuse P.C. board earth lead
(Black)
L-phase power supply lead
(Black)
N-phase power supply lead
(White)
Serial lead (Orange)
Reactor lead connector
(White)
CN701:
4-way valve connector
RY701:
4-way valve relay
CN300:
Fan motor connector
CN602:
Outdoor temperature
(TO) sensor connector
CN806:
Optional connector
CN600:
Heat exchange temperature
(TE) sensor connector
CN603:
Suction temperature
(TS) sensor connector
CN601:
Discharge temperature
(TD) sensor connector
CN500:
Case thermo connector
CN700:
PMV connector
Fan drive circuit
Q300 to Q305:
FET (QTY: 6P)
CN605:
Sub SW board connector
J800 to 803, 806
Model switch jumper line
DB02:
High power factor diode
Q404:
High power factor circuit IGBT
Comp. drive circuit
Comp. lead
(Red) (White) (Black)
Q200 to Q205: IGBT (QTY: 6P)
IC200: Drive IG (QTY: 1P)
IGBT
(Compressor drive device)
Compressor output
CN09, CN10, CN11
Rectifier
Reactor connector DC15V output
(To MCC-1531)
CN05
Communication signal
(To MCC-1531)
CN06
AC output
(To MCC-1531)
CN13
TH sensor
CN600
Earth ground
CN03
DC320V output
(To MCC-1531)
CN04
Mains (Neutral) input
CN02
Mains (Live) input
CN01
Rectifier connectors
P29 (Red), P28 (Black),
P21 (Orange), P24 (Brown)
Reactor Connector Capacitor
Serial signal
(To terminal block)
CN02
AC input
(To MCC-1438)
CN01
4-way valve
CN700
EEPROM-IC
IC801
Refrigerant recovery Switch
SW802
Dip switch
SW801
Model selection jumpers
(Available only service P.C. board)
J800 to J803
P.M.V. CN702
Case thermo. switch
CN500
Communication signal
(To MCC-1438)
CN800
TD sensor
CN600
TO sensor
CN601
TE sensor
CN604
TS sensor
CN605
Optional connector
CN804
Fan motor revolution
CN300
Fan motor output
CN301
DC15V input
(To MCC-1438)
CN04
DC320V input
(To MCC-1438)
CN03
7-2. Outline of Main Controls
1. Pulse Modulating Valve (PMV) control
1) For PMV with 50 to 500 pulses during operation, respectively.
2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor.
3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE sensor.
4) For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.
5) When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor.
The aimed value is usually 103°C for SM561, SM801 and 92°C for SM1101, SM1401 in both cooling and heating operations.
REQUIREMENT
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance value an the refrigerating cycle of each sensor after repair and then start the operation.
2. Discharge temperature release control
1) This function controls the operation frequency, that is, lowers the operation frequency when the discharge temperature has not lower or the discharge temperature has rapidly risen during
PMV control. It subdivides the frequency control up to a unit of 0.6 Hz to stabilize the cycle.
2) When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts after 2 minutes 30 seconds. The error counter is cleared when it has continued the operation for 10 minutes.
If the abnormal stop zone has been detected by 4 times without clearing of counter, an error “P03” is displayed.
* The cause is considered as excessively little amount of refrigerant, defective PMV, or clogging of cycle.
[°C]
SM561, SM801
SM1101, SM1401 a
117
111
b
107
106
c
103
100
d
100
95
e
93
90 a b c d e
TD [˚C]
Error stop ("P03" display with 4 times of error counts)
As command is
Current [A]
Frequency down
Frequency holding
Frequency slow-up
(Up to command)
I
1
Frequency down
Hold
3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by T02 on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I
1–0.5
Objective model
1
1 value [A]
SM561
COOL HEAT COOL HEAT COOL HEAT COOL HEAT
10.1
12.0
SM801
12.2
14.0
SM1101
18.9
19.7
SM1401
19.7
19.7
Hold
Normal operation
– 24 –
4. Outdoor fan control
SM561
SM801
SM1101
SM1401
Allocations of fan tap revolutions [rpm]
W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE WF
200 300 350 410 480 500 530 560 640 670 700 750 800 840 840
200 300 350 410 480 500 530 560 640 670 700 750 840 940 980
250 280 320 360 410 460 520 580 640 700 760 860 860 900 930
250 280 320 360 410 460 520 580 640 700 760 860 860 900 970
1) Cooling fan control
The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the operation. The outdoor is controlled by every 1 tap of DC fan control (15 taps).
Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap which corresponds to the zone in the following table.
After then the fan is controlled by TE sensor temperature.
Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution frequency of the fan increases regardless of TE if temperature of TD sensor has risen.
SM561, SM801
SM1101, SM1101 a
36
29
b
32
26
TE [˚C]
TD [˚C]
Operation with WE
+1 tap/20 seconds a b rpm hold
–1 tap/20 seconds
85
80
75
65
Operation with maximum tap in each zone
Usual fan control
(The operation frequency differs according to the model type.)
Temp. range
29°C < TO
15 < TO < 29°C
5 < TO < 15°C
0 < TO < 5°C
TO < 0°C
TO error
Min
Below 30Hz
Max
W5
W3
W2
WA
W7
W5
W1
W1
W1
W3
W2
WF
Above 30 Hz below 45 Hz
Min Max
W7
W5
W4
WC
W9
W7
W3
W2
W1
W5
W4
WF
– 25 –
Above 45 Hz
Min Max
W9
W7
W6
WF
WB
W9
W4
W3
W1
W7
W5
WF
2) Heating fan control
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.
(From Min. W1 to Max. are controlled according to the following table.)
During 3 minutes after start-up, the fan is fixed with the maximum fan tap corresponding to
TE [˚C] zone in the following table. After then the fan is controlled by temperature of TE sensor.
–2 tap/20 seconds
STOP timer count
If status, TE
≥
24°C continues for 5 minutes, the operation stops. This status is same to the usual
24
–2 tap/20 seconds
Thermo-OFF which has no alarm display, and the
21 fan restarts after 2 minutes and 30 seconds. This
–1 tap/20 seconds
18 intermittent operation is not abnormal.
When the above status
occurs frequently, it is considered that the filter of suction part of the
15 rpm hold
+1 tap/20 seconds indoor unit is stain. Clean the filter and then restart the operation.
(The operation frequency differs according to the model type. The case of SM1101 is shown in the table below.)
Maximum
Temp. range
10°C < TO
5 < TO < 10°C
TO < 5°C
TO error
Below 33 Hz
W7
WA
WF
WF
Above 33 Hz below 51 Hz
W8
WB
WF
WF
Above 51 Hz
W9
WF
WF
WF
5. Coil heating control
1) This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.
2) As usual, turn on power of the compressor for the specified time before a test run after installation, otherwise a trouble of the compressor may be caused. As same as a test run, it is recommended to turn on power of the compressor beforehand when starting operation after power of the compressor has been interrupted for a long time.
3) A judgment for electricity is performed by TD and TO sensors. If TO sensor is defective, a backup control is automatically performed by TE sensor. For a case of defective TO sensor, judge it with the outdoor LED display.
4) Coil heating is controlled by TD and TE sensor.
5) For every model, the power is turned off when TD is 30°C or more.
(In trouble of TE sensor)
TO [˚C] TE [˚C]
Power-ON condition
TD < 30˚C
18
15
10
8
No power-ON
Continuous ON (L)
20
18
12
10
No power-ON
Continuous ON (L)
Continuous ON (M) Continuous ON (M)
* TO sensor is read in once per 15 minutes
(Object: SM561, SM801)
TE [˚C]
0
–1
–6
–7
No power-ON
Continuous ON (L)
Continuous ON (H)
L
M
SM1101, SM1401
20W and equivalent
40W and equivalent
L
H
SM561, SM801
10W and equivalent
30W and equivalent
– 26 –
NOTIFICATION
It is not an abnormal phenomenon that electro-noise may be heard while heating the coil.
6. Short intermittent operation preventive control
The compressor may not stop for preventing the compressor for 3 to 10 minutes after start of the operation even if Thermo-OFF signal has been received from the indoor. This phenomenon is not abnormal. (Continuous operation time of the compressor differs according to the operating status.)
If the equipment is stopped from the remote controller, the operation does not continue.
7. High-pressure suppression TE control (Only for SM1101, SM1401)
This control suppresses that voltage becomes abnormally higher during cooling operation.
Stop the compressor under condition of TE
≥
67°C, and count 1 on the error count.
After 2 minutes 30 seconds passed, if TE < 67°C, the compressor restarts and the error count is cleared when the operation continues for 10 minutes.
When TE
≥
67°C is detected again within 10 minutes, 1 is added to the error count and restart is repeated.
If the error counts 10 are recognized, it is determined as an error and restart is not performed. Error code ‘P04’ is displayed.
After restarting the compressor, continue controlling by using 70% to 90% of the control value of the current release control for minimum 30 minutes.
8. Over-current preventive control
This control function stops the compressor when over-current preventive circuit has detected an abnormal current.
The compressor restarts with error count 1 after 2 minutes 30 seconds.
If the error counts 8 are recognized, it is determined as an error and restart is not performed. Error code ‘H01’, ‘H02’ or ‘P26’ is displayed.
9. Current release value shift control (Cooling and Dry operation)
1) Object: SM1101, SM1401
This control function prevents troubles of the electron parts such as G-Tr of inverter of compressor drive system and troubles of the compressor during cooling operation.
This control function corrects the current release control value (
1
1) in item 7-2. by TO sensor value.
The value to be corrected is based upon the following control diagram and correction value table.
TO [˚C]
T+8
T+7
T+5
T+4
T+2
T+1
T
T-1
I
1 x a%
I 1 x b%
I
1 x c%
I
1 x d%
As
I
1
2) Object: SM561, SM801
The current release value of the models above are selected from the right table according to TO sensor value.
Corrected value
SM1101, SM1401
T a b c d
39°C 70% 80% 85% 90%
Current release value shift control
TO
45
≤
TO
40
≤
TO < 45
TO < 40
SM561
4.7
6.2
10.1
SM801
5.1
7.1
12.2
– 27 –
10. Defrost control
In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to D zone.
The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or it also is finished when condition of 7°C
≤
TE < 12°C has continued for 1 minute. The defrost operation is also finished when defrost operation has continued for 10 minutes even if TE sensor temperature has become 7°C or lower.
After defrost operation has finished, the compressor and the outdoor fan start heating operation after stopped for approx. 50 seconds.
Start of heating operation
TE [ºC]
0
–4 (–5)
–6 (–10)
–10 (–13)
–25 (–18)
10 15 c b a d [min.]
*
Numerals enclosed with parentheses represent numeral values of SM1101 and SM1401.
* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in memory as TE0.
A zone
B zone
C zone
D zone
Defrost operation is performed in this zone when TE0-TE
≥
3 continued for T seconds.
Defrost operation is performed in this zone when TE0-TE
≥
3 continued for T seconds.
Defrost operation is performed when this zone continued for T seconds.
Defrost operation is performed when this zone continued for T seconds.
a b c d
T
SM561, SM801
35
29
29
90
20
SM1101, SM1401
50
35
30
90
20
– 28 –
8. TROUBLESHOOTING
8-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
a) Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Does not thermostat turn off?
• Does not timer operate during fan operation?
• Is not outside high-temperature operation controlled in heating operation?
• Is not Thermo-OFF setup by “Application Control Kit” (TCB-PCOS1E) sold separately?
b) Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
c) Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
d) ON/OFF operation cannot be performed from remote controller.
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.)
Did you return the cabling to the initial positions?
Are connecting cables of indoor unit and remote controller correct?
3) Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble
→
Confirmation of check code display
→
Check defective position and parts.
NOTE :
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the remote controller to shield cables.
– 29 –
<Wireless remote controller type> (Only for 4-way air discharge cassette type models)
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, radio cutting pliers, nippers, etc.
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
a) Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Does not thermostat turn off?
• Does not timer operate during fan operation?
• Is not outside high-temperature operation controlled in heating operation?
• Is not Thermo-OFF setup by “Application Control Kit” (TCB-PCOS1E) sold separately?
b) Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3) Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4) ON/OFF operation cannot be performed from remote controller.
• Is not forced operation performed?
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
Did you return the cabling to the initial positions?
Are connecting cables between indoor unit and receiving unit correct?
2. Troubleshooting procedure
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.)
When a trouble occurred, check the parts along with the following procedure.
Trouble
→
Confirmation of lamp display
(When 4-way air discharge cassette type wireless remote controller is connected)
Check defective position and parts.
1) Outline of judgment
The primary judgment to check where a trouble occurred in indoor unit or outdoor unit is performed with the following method.
Method to judge the erroneous position by flashing indication on the display part of indoor unit
(sensors of the receiving unit)
The indoor unit monitors operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
– 30 –
8-2. Check Code List
Wireless sensor lamp display
Wired remote controller
Operation Timer Ready Check code
¥ l
¥
¥
¥
¥
¥
¥ l l l
¥ l
¥
¥ l
¡
¥
¥ l
¥ ¥ l l
¥
¥
¥
¥
¥
¥
¥
¥ l l
¥
¥ l l
¥
¥
¥
¥ l
¥
¥ l
¥
¥
¥ l l l l l l l
E03
E04
E08
L03
L07
L08
L09
L30
P01
P10
P12
P19
P31
F01
F02
F10
F29
E10
E18
Error mode detected by indoor unit
¥
: Flash,
¡
: Go on, l
: Go off
Diagnostic function
Cause of operation
Status of air conditioner
Condition
Judgment and measures
No communication from remote controller (including wireless) and communication adapters
The serial signal is not output from outdoor unit to indoor unit.
• Miswiring of inter-unit wires
• Defective serial sensing circuit on outdoor P.C. board
• Defective serial receiving circuit on indoor P.C. board
Stop
(Automatic reset)
Stop
(Automatic reset)
Displayed when error is detected
Displayed when error is detected
1. Check cables of remote controller and communication adapters.
• Handy remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code
1. Outdoor unit does not completely operate.
• Inter-unit wire check, correction of miswiring, case thermo operation
• Outdoor P.C. board check, P.C. board wires check
2. In normal operation
P.C. board (Indoor receiving/Outdoor sending) check
Duplicated indoor unit addresses
Duplicated indoor master units
There is group line in individual indoor units.
Unsetting of indoor group address
Stop
Displayed when error is detected
1. Check whether there is modification of remote controller connection (Group/Individual) or not after power has been turned on (finish of group configuration/address check).
• If group configuration and address are not normal when the power has been turned on, the mode automatically shifts to address setup mode. (Resetting of address)
Unset indoor capacity
Abnormal outside interlock input
Fan motor thermal protection
Float switch operation
• Disconnection, coming-off, defective float switch contactor of float circuit
Indoor DC fan error
Error in 4-way valve system
• Indoor heat exchanger temperature lowered after start of heating operation.
Own unit stops while warning is output to other indoor units.
Coming-off, disconnection or short of indoor heat exchanger sensor (TCJ)
Coming-off, disconnection or short of indoor heat exchanger sensor (TC)
Coming-off, disconnection or short of indoor heat exchanger sensor (TA)
Indoor EEPROM error
• EEPROM access error
Stop (Sub unit)
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Communication error between indoor MCU
• Communication error between fan driving MCU and main MCU
Regular communication error between master and sub indoor units or between main and sub indoor units
Stop
Stop
Stop
Stop
Stop
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
1. Set the indoor capacity. (DN=I1)
1. Check outside devices.
2. Check indoor P.C. board.
1. Check thermal relay of fan motor.
2. Check indoor P.C. board.
1. Defect of drain pump
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P.C. board.
1. Defective detection of position
2. Over-current protective circuit of indoor fan driving unit operates.
3. Lock of indoor fan
4. Check indoor P.C. board.
1. Check 4-way valve.
2. Check indoor heat exchanger (TC/TCJ) sensor.
3. Check indoor P.C. board.
1. Judge sub unit while master unit is in [E03], [L03], [L07], [L08].
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TCJ).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TC).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TA).
2. Check indoor P.C. board.
1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.
1. Check wires of remote controller.
2. Check power wires of indoor unit.
3. Check indoor P.C. board.
1. Check wires of remote controller.
2. Check indoor power wire.
3. Check indoor P.C. board.
Error mode detected by outdoor unit
¥
¥
¥
¥
¥
Wireless sensor lamp display
Wired remote controller
Operation Timer Ready Check code
l l l
¥
¥
¥
¥
¥
¥
¥
¥
¡
¡ l l l l l l
¥
¥
¥
¥
¥ l
¥ l
¥
¥ ¡
¥
¥
¡
¡
H01
H02
H03
L29
L31
P03
P04
P22
P26
P29
F04
F06
F08
¥
: Flash,
¡
: Go on, l
: Go off
Diagnostic function
Cause of operation
Status of air conditioner
Condition
Judgment and measures
Breakdown of compressor
• Displayed when error is detected
Compressor does not rotate.
• Over-current protective circuit operates after specified time passed when compressor had been activated.
Current detection circuit error
• Current value at AC side is high even during compressor-OFF.
• Phase of power supply is missed.
Outdoor unit and other errors
• Communication error between CDB and IPDU
(Coming-off of connector)
• Heat sink temperature error
(Detection of temperature over specified value)
Phase detection protective circuit operates. (Normal models)
Discharge temperature error
• Discharge temperature over specified value was detected.
High-pressure protection error by TE sensor
(Temperature over specified value was detected.)
Outdoor DC fan error
Inverter over-current protective circuit operates. (For a short time)
Short voltage of main circuit operates.
IPDU position detection circuit error
Coming-off, disconnection or short of outdoor temperature sensor (TD)
Coming-off, disconnection or short of outdoor temperature sensor (TE/TS)
Coming-off, disconnection or short of outdoor temperature sensor (TO)
Stop
Stop
Stop
Stop
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
1. Check power voltage. AC200V ± 20V
2. Overload operation of refrigerating cycle
3. Check current detection circuit at AC side.
1. Trouble of compressor (Compressor lock, etc.) : Replace compressor.
2. Defective wiring of compressor (Phase missing)
3. Phase-missing operation of power supply (3-phase model)
1. Compressor immediately stops even if restarted. : Check IPDU.
2. Phase-missing operation of power supply
Check 3-phase power voltage and wires.
1. Check wires of CDB and IPDU.
2. Abnormal overload operation of refrigerating cycle
Operation continues.
(Compressor stops.)
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Operation continues.
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
1. Check power phase order (Reversed phase)/phase missing.
2. Check outdoor P.C. board.
1. Check refrigerating cycle. (Gas leak)
2. Trouble of PMV
3. Check Td sensor.
1. Overload operation of refrigerating cycle
2. Check outdoor temperature sensor (TE).
3. Check outdoor CDB P.C. board.
1. Defective detection of position
2. Over-current protective circuit of outdoor fan driving unit operates.
3. Lock of outdoor fan
4. Check outdoor CDB P.C. board.
1. Inverter immediately stops even if restarted. : Compressor motor rare short
2. Check IPDU. : Cabling error
1. Position detection circuit operates even if operating compressor by removing 3P connector. : Replace IPDU.
1. Check outdoor temperature sensor (TD).
2. Check outdoor CDB P.C. board.
1. Check outdoor temperature sensor (TE/TS).
2. Check outdoor CDB P.C. board.
1. Check outdoor temperature sensor (TO).
2. Check outdoor CDB P.C. board.
For an error mode detected in outdoor unit, the fan operates because sub unit of a group operation does not communicate with the outdoor unit.
Error mode detected by remote controller or network adapter
Wireless sensor lamp display
Operation Timer Ready
—
¥
¥
¥
¥
—
—
—
— l l l
¡
—
—
—
— l l l
¥
—
—
—
¥
: Flash,
¡
: Go on, l
: Go off
Wired remote controller
Check code
No check code is displayed.
(Remote controller does not operate.)
E01*2
E02
Cause of operation
No communication with master indoor unit
• Power of indoor unit is not turned on.
• Automatic address cannot be completed.
No communication with indoor master unit
Signal sending error to indoor unit
(Detected at remote controller side)
Diagnostic function
• Remote controller wire is not correctly connected.
• Disconnection of inter-unit wire between remote controller and master indoor unit (Detected at remote controller side)
E09
Multiple master remote controllers are recognized.
(Detected at remote controller side)
L20
Central remote controller
98
—
*3
Central remote controller
99
—
*3
Central remote controller
97
—
Central remote controller b7
Duplicated indoor central addresses on communication of central control system (AI-NET)
(Detected by central controller side)
Multiple network adapters on remote controller communication line
(Detected by central controller side)
Interruption of central control system (AI-NET) communication circuit
(Detected by central controller side)
Indoor Gr sub unit error (Detected by central controller side)
Status of air conditioner
Condition
Judgment and measures
Stop
Stop
(Automatic restart)
• When there is center, operation continues.
—
Displayed when error is detected
Remote controller power error, Defective indoor EEPROM
1. Check remote controller inter-unit wires.
2. Check remote controller.
3. Check indoor power wires.
4. Check indoor P.C. board.
5. Check indoor EEPROM. (including socket insertion)
: Phenomenon of automatic address repetition occurred.
Signal receiving of remote controller is defective.
1. Check remote controller inter-unit wires.
2. Check remote controller.
3. Check indoor power wires.
4. Check indoor P.C. board.
Stop
(Automatic restart)
• When there is center, operation continues.
Stop
(Sub unit continues operation.)
Displayed when error is detected
Displayed when error is detected
Signal sending of remote controller is defective.
1. Check sending circuit inside of remote controller.
: Replace remote controller.
1. Check there are multiple master units for 2 remote controllers
(including wireless).
: Master unit is one and others are sub units.
Stop
(Automatic restart)
Operation continues.
Operation continues.
(According to handy remote controller)
Continuation/stop
(Based on a case)
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
Displayed when error is detected
1. Check address setup of central control system network.
(Network adapter SW01)
2. Check network adapter P.C. board.
1. Check multiple network adapters.
2. Check inter-unit wire/miswiring of remote controller.
: Only one network adapter on remote controller communication line
1. Check communication line/miswiring. Check power of indoor unit.
2. Check communication. (XY terminals)
3. Check network adapter P.C. board.
4. Check central controller (such as central control remote controller, etc.).
Check the check code of corresponding unit by handy remote controller.
*2 Check code is not displayed by wired remote controller. (Usual operation of air conditioner is disabled.)
For wireless type models, E01 is notified by the display lamp.
*3 These errors are related to communication of remote controllers (A, B) and central system (AI-NET, X, Y), and [E01], [E02], [E03], [E09], or [E18] is displayed or no check code is displayed on the remote controller according to the error contents.
8-3. Error Mode Judgment by LED Display of Outdoor Unit
There provided Dip switch (SW801) and LED on the “Application Control Kit” (TCB-PCOS1E) sold separately for
SM56 and SM80 models, and on the outdoor unit P.C. board for SM110 and SM140 models respectively.
The status of the outdoor unit at that time can be known by switching this Dip switch. The lighting status of LED also notifies the judged stage before the outdoor error has been determined and displayed on the remote controller. An error of the outdoor temp. sensor (TO) may be confirmed only by LED display according to the indoor unit to be combined.
Model
SM56, 80
*
SM110, 140
(MCC-1531)
Dip SW
SW01
SW802
D01 (Red) D02 (Yellow)
LED
D03 (Yellow) D04 (Yellow)
D800 (Red) D801 (Yellow) D802 (Yellow) D803 (Yellow)
Bit 1 Bit 2
For error display, refer to
(Table A) on the next page.
OFF
ON
OFF
OFF
OFF
ON
² l
During timer short l l
During pump down operation
²
Protective operation count
In normal time, Count 1
Count 2, Count 3
Count 4, Count 5
Count 6, Count 7
Protective operation
² l
¡
² ²
PMV opening data (Lower 4 bit data) l
²
During backup control
¥
Add 16 pulses Add 8 pulses Add 4 pulses Add 2 pulses if this LED goes on.
if this LED goes on.
if this LED goes on.
if this LED goes on.
PMV opening data (Upper 4 bit data)
Add 256 pulses Add 128 pulses Add 64 pulses Add 32 pulses if this LED goes on.
if this LED goes on.
if this LED goes on.
if this LED goes on.
ON ON
The total pulse counts equivalent to lighting LED at each position represents PMV opening degree. For example, the case of
¡
ll
4 bit) represents 256 + 32 + 4 + 2 = 294 pulses.
¡
ll
¡¡
(Upper 4 bit, Lower
¡
: Go on l
: Go off
²
: 1Hz-flash
¥
: 5Hz-flash
*
For Models ROA-AP40 to AP80, the error mode judgment by the above LED display is available under condition which “Application Control Kit” (TCB-PCOS1E) sold separately is connected.
(Note)
Never touch part other than Dip switch of “Application Control Kit” (TCB-PCOS1E).
AC230V is applied to all the electronic products, so an electric shock may be caused.
– 34 –
8-4. Contents of Error Display
• When multiple errors are detected, the latest error is displayed.
• When LED display is
¡
(Go on), there is the main cause of trouble on the objective part of control at CDB side and the unit stops.
• When LED display is
¥
(Flash), there is the main cause of trouble on the objective part of control at IPDU side and the unit stops.
• When case thermostat operates, the communication is interrupted on the serial circuit. If continuing the case thermostat operation, a serial communication error occurs because serial sending to the indoor unit is interrupted.
Check code
No.
Item
3
4
1
2
5
6
7
8
9
10
11
12
13
14
15
16
17
TE sensor error
TD sensor error
TS sensor error
TO sensor error
Discharge temp. error
DC outdoor fan error
Communication error between IPDU
(with system suspended)
High-pressure release operation
Case thermo operation
EEPROM error
Communication error between IPDU
(without system suspended)
G-Tr short-circuit protection
Detection circuit error
Current sensor error
Comp. lock error
Comp. breakdown
TH sensor error
¡
: Go on l
: Go off
¥
: Flash (5Hz)
Type A
F06
F04
F06
F08
P03
P22
P26
P29
H03
H02
H01
L29
L29
P04
E04
—
—
Type B
18
19
18
1B
1E
1A
14
16
17
1D
1F
1C
1C
21
04
—
—
D800
(Red)
¡
¡ l l l
¡
¡ l l
¡ l
¥ l
¥ l
¥
¥
LED display
D801
(Yellow)
l
¡ l
¡
¡
¡ l
¡
¡
¡ l l
¥
¥ l l
¥
D803
(Yellow)
l l l l l l
¡
¡
¡
¡
¡ l l l l l l
D802
(Yellow)
l l
¡ l
¡
¡ l l l l
¡ l l l
¥
¥
¥
<<Check code>>
The check codes are classified into Type A and Type B according to the used remote controller. Be sure to check the remote controller which you use.
Type A :
Neutral 2-cores type wired remote controller such as RBC-AMT21E, RBC-AS21E, and wireless remote controller kit such as TCB-AX21U (W)-E
Type B :
Polarized 3-cores type wired remote controller such as RBC-SR1-PE, RBC-SR2-PE, and central control remote controller such as RBC-CR64-PE
– 35 –
8-5. Troubleshooting Procedure for Each Check Code
8-5-1. New Check Code/Present Check Code (Central Control Side)
[E01 error]/
*
[99 error]
*
: When central controller [99] is displayed, there are other causes of error.
Is inter-unit cable of A and B normal?
YES
NO
Is there no disconnection or contact error of connector on harness from terminal block of indoor unit?
NO
YES
NO
Is group control operation?
YES
Is power of all indoor units turned on?
YES
NO
Correct inter-unit cable of remote controller.
Correct connection of connector.
Check circuit cables.
Check power connection of indoor unit.
(Turn on power again.)
Is power supplied to remote controller?
AB terminal: Approx. DC18V
YES
NO
YES
Are two remote controllers set without header unit?
NO
Check indoor P.C. board.
Defect
®
Replace
Correct as a master unit/a sub unit
(Remote controller address connector)
Check remote controller P.C. board.
Defect
®
Replace
[E09 error]/
*
[99 error]
*
: When central controller [99] is displayed, there are other causes of error.
YES
Are two remote controllers set without header unit?
NO
Correct as a header unit/a follower unit
(Remote controller address connector)
Check remote controller P.C. board.
Defect
®
Replace
– 36 –
[E04 error]/[04 error]
Does outdoor unit operate?
YES
NO
NO
Is setup of group address correct?
YES
Are 1, 2, 3 inter-unit wires normal?
YES
NO
Check item code [14].
Correct inter-unit wire.
Are connections from connectors of inter-terminal blocks (1, 2, 3) of indoor/outdoor units normal?
YES
NO
Correct connection of connector.
Does voltage between
2 and 3 of inter-terminal blocks (1, 2, 3) of indoor unit vary?*
YES
NO
Check indoor P.C. board.
Defect
®
Replace
*
As shown in the following figure, perform measurement within
20 seconds after power ON.
S5277G
Black 3
White
2
1
Inter-terminal block
For SM56, SM80 main circuit on control
P.C. board
NO Is DC280V applied between terminals of electrolytic capacitor of IPDU main circuit?
YES
For SM56, SM80, check case thermo.
Replace IPDU.
Check indoor P.C. board .
Defect
®
Replace
Check CDB.
Defect
®
Replace
NO
Is DC7V power supplied to CDB?
Are cablings between Pin 2 and Pin 5 of CN800 and between IPDU and CDB normal?
YES
NO
NO
Is case thermo (CN500) connected?
YES
Does case thermo operate?
YES
Check/Correct charged refrigerant amount.
Replace IPDU.
Correct connection of connector.
Correct connection of connector.
– 37 –
[E10 error]/[CF error]
Check indoor control P.C. board.
Defect
®
Replace
[E18 error]/[97 error]
*
[99 error]
*
: When central controller [99] is displayed, there are other causes of trouble.
NO
Is inter-unit wire of A and B normal?
Correct inter-unit wire of remote controller.
YES
Is there no disconnection or contact error of connector on harness from terminal block of indoor unit?
NO
YES
YES
Is group control operation?
NO
Correct connection of connector.
Check circuit wires.
Is power of all indoor units turned on?
YES
NO
NO
Check indoor P.C. board.
Defect
®
Replace
Is Twin connection control?
YES
YES
Is there no contact error between indoor/outdoor inter-unit wires (signal lines)?
NO
Correct indoor/outdoor inter-unit wires
(serial signal lines).
Check power connection of indoor unit.
(Turn on power again.)
[E08, L03, L07, L08 error]/
*
[96 error] [99 error]
*
: When central controller [99] is displayed, there are other causes of trouble.
E08 : Duplicated indoor unit numbers
L03 : Two or more header units in a group control
L07 : One or more group addresses of [Individual] in a group control
L08 : Unset indoor group address (99)
If the above is detected when power has been turned on, the mode automatically enters in automatic address setup mode. (Check code is not displayed.)
However, if the above is detected during automatic address setup mode, the check code may be displayed.
[L09 error]/[46 error]
Is capacity of indoor unit unset?
NO
YES
Set capacity data of indoor unit.
(Setup item code (DN) = 11)
Check indoor P.C. board.
Defect
®
Replace
– 38 –
[L20 error]/[98 error]
Are wire connections to communication line X, Y normal?
YES
Is central controller [98] displayed?
YES
Is indoor remote controller
[L20] displayed?
YES
Are not multiple same central control network addresses connected?
NO
NO
NO
YES
Check central controller
(including network adapter).
Defect
®
Replace.
[L30 error]/[B6 error]
Are outside devices of connector CN80 connected?
YES
NO
Do outside devices normally operate?
YES
NO
Check operation cause.
[b7 error] (Central controller)
NO
Is group operation performed?
YES
Is check code displayed on follower unit of header or follower remote controller?
YES
NO
Check corresponding indoor/outdoor units.
– 39 –
Correct wire connection
Check indoor P.C. board.
Defect
®
Replace
Correct central control network address.
Check indoor P.C. board.
Defect
®
Replace
Check outside devices.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
[P01 error]/[11 error]
Is there no connection error/disconnection of CN076 connector?
NO
Is capacitor normal?
YES
Is there no mechanical lock of fan motor?
NO
YES
NO
YES
Correct connector connection/wire circuit.
Replace capacitor.
Replace fan motor
Check indoor P.C. board.
Defect
®
Replace
[P10 error]/[Ob error]
Is connection of float switch connector
(Indoor control P.C. board CH34) normal?
YES
NO
Does float switch operate?
NO
YES
Is circuit cabling normal?
YES
Correct connection of connector.
NO
Does drain pump operate?
YES
Is power of drain pump turned on?
YES
NO
Check drain pipe, etc.
Replace drain pump.
Check cabling.
NO
Check and correct cabling/wiring.
Check indoor P.C. board.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
[F10 error] [0C error]
Is connection of TA sensor connector
(indoor P.C. board CN104) normal?
YES
Are characteristics of TA sensor resistance value normal?
YES
Check indoor P.C. board.
Defect
®
Replace
NO
NO
* Refer to Characteristics-1.
– 40 –
Correct connection of connector.
Replace TA sensor.
[P12 error]/[11 error]
Turn off the power.
Are not there connections errors or disconnection on connectors CN333 and CN334 of indoor unit P.C. board?
NO
YES
Remove connectors CN333 and
CN334 of indoor unit P.C. board.
Correct connection of connector.
Does the fan rotate without trouble when handling the fan with hands?
YES
Are resistance values between phases at fan motor connector CN333 motor side of indoor P.C. board correct? *1
YES
Is resistance value of fan motor connector CN333 at motor side of indoor P.C. board correct? *2
YES
Is signal output of indoor fan motor position detection correct? *3
YES
NO
NO
Replace indoor fan motor.
Replace indoor fan motor.
*
1
• Are not coil windings between (Red lead) and (White lead), between
3
(White lead) and (Black lead), between
(Black lead) and (Red lead) opened or shorted?
®
For resistance, see the following values.
RAV-SM56
RAV-SM110
*
*
, SM80
*
UT
®
Approx. 70 to 100
W
, SM140
*
UT
®
Approx. 35 to 50
W
• Is not earthed between cabinet and 1, 3, 5
®
10M
W
or more
NO
Replace indoor fan motor.
*
2
Check resistance of fan motor position detection circuit.
Is not coil winding between (Yellow lead) and (Pink lead) opened or shorted?
®
Resistance: Approx. 5 to 20k
W
NO
Replace indoor fan motor.
*
3
Check fan motor position detection signal.
indoor P.C. board (MCC-1402) under condition that CN333 and
CN334 are mounted and the power is turned on.
®
Rotate the fan slowly with hands, and check the pin voltage swings between 0 to 5V voltage.
CN333
Check indoor P.C. board.
Defect
®
Replace
CN334
– 41 –
[P22 error]/[1A error]
In case of RAS-SM56, SM80
Is connection of CN300 of P.C. board normal?
YES
Does fan rotate by hands without trouble when removing CN300 from P.C. board?
YES
Are 18 to 30
W
applied for the resistance between
1
(Red lead) and
2
(White lead)
2
(White lead) and
3
(Black lead)
3
(Black lead) and
1
(Red lead) of connector CN300 (Motor winding) at motor side?
YES
Fan motor – Normal
(Control (Main) P.C. board error)
NO
NO
NO
Fan motor – Error
Correct connection of connector.
Fan motor winding connector
CN300 (AP40
*
CN301 (AP140
*
to AP80
*
)
, AP160
*
)
In case of RAS-SM110, SM140
Are connections of CN300 and
CN301 of P.C. board normal?
YES
Does fan rotate by hands without trouble when removing CN300 and CN301 from P.C. board?
YES
Are 12 to 22
W
applied for the resistance between
1
(Red lead) and
2
(White lead)
2
(White lead) and
3
(Black lead)
3
(Black lead) and
1
(Red lead) of connector CN301 (Motor winding) at motor side?
Are 10k to 12 k
W
applied for the resistance between
1 (Yellow lead) and 4 (Pink lead) of connector CN300 (Connector for detection motor position) at motor side?
YES
NO
NO
Connector for detection of motor position
CN300 (AP140
*
, AP160
*
)
Fan motor – Normal Fan motor – Error
Correct connection of connector.
(Control (Main) P.C. board error)
NOTE)
However, GND circuit error inside of the motor is rarely detected as OK by the above check.
When GND circuit does nor become normal even if P.C. board has been replaced, replace the outdoor fan motor.
Objective P.C. board
Fan motor winding connector
Motor position detection connector
Fan motor name
Fan motor winding resistance value
SM56 SM80
Control (Main) P.C. board
MCC-5009
Control (Main) P.C. board
CN300
MCC-1513
No connector for position detection
ICF-140-43
18 to 30
W
SM110, SM140
CDB P.C. board
MCC-1531
CN301
CN300
ICF-280-100
12 to 22
W
– 42 –
[P19 error]/[08 error]
In case of SM56, SM80
Is 230V applied to terminal of 4-way valve coil in heating operation?
YES
NO
Check 4-way valve.
Defect
®
Replace
Is operation of
4-way valve normal?
YES
NO
Outdoor P.C. board error
®
Replace
Is flow of P.M.V. normal?
NO
YES
In case of SM110, SM140
Is there continuity to coil of 4-way valve?
YES
NO
4-way valve coil
Defect
®
Replace
Is 230V applied to terminal of 4-way valve coil in heating operation?
NO
YES
Check 4-way valve.
Defect
®
Replace
Check and replace P.M.V.
NO Are characteristics of TC sensor resistance value normal?
* Refer to Characteristics-2.
YES
Is wiring normal?
Especially wiring connection of
( ) of IPDU P.C. board (Red leads)
YES
Check CDB P.C. board.
NO
No problem
NO
Check wiring.
Correct
Check CDB P.C. board.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
Replace TC sensor.
• In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].
[F02 error]/[0d error]
Is connection of TC sensor connector
(Indoor P.C. board CN101) normal?
YES
NO
Are characteristics of
TC sensor resistance value normal?
YES
NO
* Refer to Characteristics-2.
Check indoor P.C. board.
Defect
®
Replace
– 43 –
Correct connection of connector.
Replace TC sensor.
[F01 error]/[0F error]
Is connection of TCJ sensor connector
(Indoor P.C. board CN102) normal?
YES
NO
Are characteristics of
TCJ sensor resistance value normal?
YES
NO
* Refer to Characteristics-2.
Check indoor P.C. board.
Defect
®
Replace
Correct connection of connector.
Replace TCJ sensor.
[P26 error]/[14 error]
NO
Is power voltage normal?
YES
Are connections of wiring/connector normal?
YES
NO
Are not “14” errors output when an operation is performed by removing 3P connector of compressor?
YES
NO
NO
Is compressor normal?
YES
Check IPDU.
Defect
®
Replace
* Replace control P.C. board of SM56, SM80.
Improve the power supply line.
Check and correct circuit wires.
Correct connection of connector.
Check and correct reactor connection.
Replace IPDU.
* Replace control P.C. board of SM56, SM80.
Check rare short of compressor trouble.
Defect
®
Replace
– 44 –
[P29 error]/[16 error]
Are connections of wire/connector normal?
YES
NO
NO
Is compressor normal?
YES
YES
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2
W
?)
NO
YES
YES
Is not winding opened?
NO
Check and correct circuit wiring such as wiring to compressor.
Compressor trouble
Compressor trouble
Compressor trouble
®
®
®
Replace
Replace
Replace
Check IPDU P.C. board.
Defect
®
Replace
* For SM56, SM80, replace control P.C. board.
[H03 error]/[17 error]
Are wirings of power and current sensor normal?
YES
Check IPDU.
Defect
®
Replace
NO
* For SM56, SM80, replace control P.C. board.
Check and correct circuit wires.
– 45 –
[F06 error]/[18 error]
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
YES
NO
Correct connection of connector.
Are characteristics of TE/TS sensor resistance values normal?
YES
* (For SM56, SM80, CN600 TE sensor and CN603 TS sensor)
NO
Replace TE and TS sensors.
Check CDB.
Defect
®
Replace
* Refer to Characteristics-3.
* For SM56, SM80, replace control P.C. board.
[F04 error]/[19 error]
Is connection of TD sensor connector of CDB CN600 normal?
YES
NO
* (For SM56, SM80, CN601 TD sensor)
NO
Are characteristics of TD sensor resistance value normal?
YES
Check control P.C. board.
Defect
®
Replace
* Refer to Characteristics-4.
* For SM56, SM80, replace control P.C. board.
Correct connection of connector.
Replace TD sensor.
[F08 error]/[1b error]
Is connection of TO sensor connector of CDB CN601 normal?
YES
NO
* (For SM56, SM80, CN602 TO sensor)
NO
Are characteristics of TO sensor resistance value normal?
YES
Check CDB.
Defect
®
Replace
* Refer to Characteristics-5.
* For SM56, SM80, replace control P.C. board.
Correct connection of connector.
Replace TO sensor.
– 46 –
[L29 error]/[1C error]
In case of RAS-SM56, SM80
Is power supply voltage normal?
YES
Is compressor normal?
YES
NO
NO
Modify power supply line.
Check compressor error and rear short.
Defect
®
Replace
Check outdoor control P.C. board.
Defect
®
Replace
In case of RAS-SM110, SM140
Are connections of
CDB CN800 and CDB IPDU CN06 connectors normal?
YES
NO
YES
Was the error just after power ON determined?
NO
Are cabling/connector normal?
YES
NO
Correct connection of connector.
Check cabling between IPDU and CDB and connector.
IPDU P.C. board error
Defect
®
Replace
YES
Is there no abnormal overload?
NO
Is IPDU P.C. board come to closely contact with heat sink?
YES
NO
Improve and eliminate the cause.
Correct mounting.
IPDU P.C. board error
Defect
®
Replace
[H02 error]/[1d error]
Is power voltage normal?
YES
NO
NO
Are connections of wire/connector normal?
YES
NO
Is compressor normal?
YES
Improve power line.
Check and correct circuit wiring such as cabling to compressor
(phase missing) and connector.
Compressor lock
®
Replace
Is there no slackened refrigerant?
YES
Does P.M.V.
normally operate?
YES
Check IPDU and CDB.
Defect
®
Replace
NO
NO
Check TE and TS sensors.
®
Replace
Check P.M.V.
®
Replace
* For SM56, SM80, replace control P.C. board.
– 47 –
[P03 error]/[1E error]
Is protective control such as discharge temprelease control normal?
YES
NO
Are connections of wire/connector normal?
YES
NO
Correct the wiring and connection of connector.
Check parts.
Defect
®
Replace
Is charged refrigerant amount normal?
YES
NO
YES
Is not abnormal overload?
NO
Are characteristics of
TD sensor resistance value normal?
YES
NO
* Refer to Characteristics-4.
Check and correct the charged refrigerant amount.
Improve and delete the cause
Replace TD sensor.
Check CDB.
Defect
®
Replace
* For SM56, SM80, replace control P.C. board.
[H01 error]/[1F error]
Is power voltage normal?
YES
Is not abnormal overload?
YES
NO
YES
Improve power line.
Improve and delete the cause.
Check IPDU.
Defect
®
Replace
* For SM56, SM80, replace control P.C. board.
– 48 –
[P04 error]/[21 error]
Is high-voltage protective operation by
TE sensor normal?
YES
NO
Is connection of wiring connector normal?
YES
NO
Correct connection of wiring connector.
Check TE sensor.
Defect
®
Replace
Does cooling outdoor fan normally operate?
YES
NO
Is connection of connector normal?
YES
NO
Correct connection of connector.
NO
Check TE, TC, TS sensors.
Replace P.M.V.
NO
Does PMV normally operate?
YES
Is fan motor normal?
YES
Do not TD and TO sensors come off the detection part?
YES
NO
Replace fan motor.
Correct coming-off.
Are characteristics of
TD, TO, TC sensor resistance values normal?
YES
NO
Replace TD, TO, and TC sensors.
* Refer to Characteristics-3 and 4.
Check charged refrigerant amount.
Check liquid/gas valves.
Check abnormal overload.
Check CDB.
Defect
®
Replace
* For SM56, SM80, replace control P.C. board.
– 49 –
[97 error] (Central controller)
NO
Is X, Y communication line normal?
YES
Correct communication line.
Are connections between connectors
CN02, CN03 of network adapter P.C. board and connectors CN309, CN41 of indoor P.C. board normal?
YES
NO
NO
Is A, B communication line normal?
YES
YES
Is there no connection error of power line?
NO
YES
Is not power of source power supply turned on?
NO
YES
Did a power failure occur?
NO
Is the network address changed form remote controller?
NO
YES
YES
Is there no noise source, etc.?
NO
Can central remote controller control normally other indoor units?
Is handling of central remote controller reflected on the operation status of indoor unit?
YES
NO
(Same as others)
Correct connection of connector.
Check connections of A, B terminal blocks.
Correct communication line of remote controller.
Correct power cable.
Turn on the source power supply.
Clear the check code.
Eliminate noise, etc.
Check central controller.
Defect
®
Replace
Does network adapter P.C. board
LED (D01) go on?
YES
NO
Can handy remote controller control normally other indoor units?
YES
NO
Check network adapter P.C. board and power transformer.
Defect
®
Replace
Check indoor P.C. board.
Defect
®
Replace
– 50 –
[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal sent from the main remote controller (and central controller).
In this case, check the communication cables of the remote controllers A and B, the central control system X and Y. As communication is disabled, [E03] is not displayed on the main remote controller and the central controller. [E01] is displayed on the main remote controller and [97 error] on the central controller, respectively.
If [E03] occurs during an operation, the air conditioner stops.
[F29 error] / [12 error]
[F29 error] or [12 error] indicates detection of trouble which occurred on IC10 non-volatile memory (EEPROM) on the indoor unit P.C. board during operation of the air conditioner. Replace the service P.C. board.
* If EEPROM has not been inserted when the power was turned on or if EEPROM data never be read/written, the automatic address mode is repeated. In this time, the central controller displays [97 error].
(Power ON)
(Approx. 3 minutes)
[SET] is displayed on main remote controller.
(Approx. 1 minute)
[SET] goes off.
LED (D02) on indoor unit P.C. board flashes with 1Hz for approx. 10 seconds.
(Repetition)
Reboot
(Reset)
[P31 error] (Sub indoor unit)
When the master unit of a group operation has detected [E03], [L03], [L07], or [L08] error, the sub unit of the group operation detects [P31 error] and then it stops. There is no display of the check code or alarm history of the main remote controller.
(In this model, the mode enters in automatic address set mode when the master unit has detected [E03], [L03],
[L07], or [L08] error.)
– 51 –
8-4-2. Relational Graph of Temperature Sensor Resistance Value and Temperature
Resistance
(k )
10
20
0
10 20
40
TA sensor
Caracteristics-1
30
Resistance
(k )
20
30 40
Temperature [˚C]
50
TC, TCJ sensor
Caracteristics-2
10
0
–10 0 10 20 30 40 50 60 70
Temperature [˚C]
20
TE, TO, TS sensor
200
Caracteristics-3
Resistance
(k )
(10˚C or lower)
100
Resistance
(k )
(10˚C or higher)
10
0
200
-10 0 10 20 30 40
Temperature [˚C]
50 60 70
0
TD sensor
Caracteristics-4
Resistance
(k )
(50˚C or lower)
100
20
Resistance
(k )
(50˚C or higher)
10
0
0
50
Temperature [˚C]
100
– 52 –
8-4-3. Troubleshooting with CHECK Display of Central Remote Controller
1. Operation for CHECK display
When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section.
ON
MONITOR
SET
ZONE
ALL UNIT
ON
OFF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
CENTER
LOCKED
MODE
FAN ONLY
COOL
DRY
HEAT
AUTO
AUX. TYPE
TIMER No.
FAN
AUTO
HIGH
MED.
LOW
FIX
TEMP.
1
2
LOUVER
MANUAL
STANDBY
FILTER
CHECK
˚C
MONITOR/SET ALL/ZONE ZONE UNIT ON CENTER/LOCKED MODE TEMP.
FILTER RESET CHECK
ZONE SET/ENTER SELECT OFF TIMER ON FAN LOUVER
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
RESET switch
Push the switch in the hole with pin.
The remote controller resets initialized.
(All data is cleared.)
2. Reading of CHECK monitor display
<7 segment display>
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Hexadecimal notation
Decimal notation
<Display on CHECK monitor>
Unit line No. (Network address No.)
MONITOR
SET
1
ZONE
ALL UNIT
ON
OFF
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
CENTER
LOCKED
MODE
FAN ONLY
COOL
DRY
HEAT
AUTO
AUX. TYPE
TIMER No.
FAN
AUTO
HIGH
MED.
LOW
FIX
TEMP.
1
2
LOUVER
MANUAL
STANDBY
FILTER
CHECK
˚C
Check code detected at first
Check code detected at last
(Example)
There is no check data.
UNIT
TEMP.
CHECK
<CHECK data>
(Example)
In No.1 unit, first the interconnection wire (bus communication line) of indoor/outdoor has failed.
Next, the room temp. sensor is defective.
For No.16 unit, the high pressure switch at the inverter unit side operates.
UNIT UNIT UNIT
TEMP.
CHECK
1
TEMP.
CHECK
2
TEMP.
CHECK
1
– 53 –
8-4-4. Check Code Table
Block display
[MODE]
[TIMER] lamp
5Hz flash
[MODE] lamp
5Hz flash
Check code A
Error mode detected by indoor unit (1)
Operation of diagnostic function
Check code B
Cause of operation
The serial signal is not output from outdoor unit to indoor unit.
• Miswiring of inter-unit wires
• Defective serial sending circuit on outdoor P.C.
board
• Defective serial receiving circuit on outdoor P.C.
board
• Compressor case thermo operation
Status of air conditioner
Operation continues
Condition
Judgment and measures
Displayed when error is detected
1. Outdoor unit does not completely operate.
• Inter-unit wire check, correction of miswiring
• Outdoor P.C. board check, P.C.
board wires check
• Compressor case thermo check
2. In normal operation
When outdoor sending serial LED
(Green) flashes, the receiving serial
LED (Orange) also flashes. : Indoor
P.C. board (Main P.C. board) check
When the receiving serial LED
(Orange) does not flash: Outdoor
P.C. board check
*
BUS communication circuit error
* BUS communication was interrupted over the specified time.
Network address miss-setting
• Addresses of central controllers (Central control remote controller, etc.) are duplicated.
Operation continues
(According to remote controller of indoor unit)
Displayed when error is detected
1. Communication line check, miswiring check
Power supply check for central controller (Central control remote controller, etc.) and indoor unit
2. Communication check (XY terminal)
3. Indoor P.C. board check
4. Central controller check
(Communication P.C. board)
Operation continues
Displayed when error is detected
1. Check central control system network address setting. (SW02)
2. Indoor P.C. board check
3. Central controller check
(Communication P.C. board)
Error in 4-way valve system
• Indoor heat exchanger temperature rise after start of cooling operation.
• Indoor heat exchanger temperature fall after start of heating operation.
Error in other cycles
• Indoor heat exchanger temp (TC) does not vary after start of cooling/heating operation.
Operation continues
Operation continues
Displayed when error is detected
1. Check 4-way valve.
2. Check 2-way valve and non-return valve.
3. Check indoor heat exchanger sensor (TC).
4. Check indoor P.C. board
(Main P.C. board).
Displayed when error is detected
1. Compressor case thermo operation
2. Coming-off of detection part of indoor heat exchanger sensor
3. Check indoor heat exchanger sensor (TC).
4. Check indoor P.C. board
(Main P.C. board).
Coming-off, disconnection or short of indoor temp sensor
(TA)
Coming-off, disconnection or short of indoor temp sensor
(TC)
Coming-off, disconnection or short of indoor temp sensor
(TCJ)
Operation continues
Operation continues
Operation continues
Displayed when error is detected
1. Check indoor temp sensor (TA).
2. Check indoor P.C. board
(Main P.C. board).
Displayed when error is detected
1. Check indoor temp sensor (TC).
2. Check indoor P.C. board
(Main P.C. board).
Displayed when error is detected
1. Check indoor temp sensor (TCJ).
2. Check indoor P.C. board
(Main P.C. board).
*
: No display in the setting at shipment
– 54 –
Block display
[MODE] lamp
5Hz flash
Check code A
Error mode detected by indoor unit (1)
Operation of diagnostic function
Check code B
Cause of operation
Status of air conditioner
Error in indoor fan system
Revolutions frequency error of fan
All stop
Condition
Judgment and measures
Displayed when error is detected
1. Check indoor fan motor connector circuit (CN210).
2. Check indoor fan.
Error in indoor unit or other positions
1. EEPROM access error
Operation continues
3. Check indoor P.C. board (Main P.C.
board).
Displayed when error is detected
1. Check indoor P.C. board
(EEPROM and peripheral circuits)
(Main P.C. board).
Outside error input
Detected by input voltage level from outside devices
Operation continues
Outside interlock input
Detected by input voltage level from outside devices
All stop
Displayed when error is detected
1. Check outside devices.
2. Check indoor P.C. board
(Main P.C. board).
Displayed when error is detected
1. Check outside devices.
2. Check indoor P.C. board
(Main P.C. board).
Error mode detected by indoor unit (2)
Check code
Operation of diagnostic function
Cause of operation
Status of air conditioner
Serial return signal is not sent from
No. 1 indoor unit to remote controller.
• Miswiring of inter-unit wire between remote controller and indoor unit
• Miss-setting of indoor unit No.
(Group address)
ON/OFF
Condition
Displayed when error is detected
Judgment and measures
1. Indoor unit does not completely operate.
• Check inter-unit wire.
• Check indoor P.C. board. (Main/Sub P.C. boards)
• Check remote controller.
2. In normal operation
• Check setting of indoor unit No.
(SW01) (Sub P.C. board)
• Check remote controller.
– 55 –
Check code A
Error mode detected by outdoor unit (3)
Check code B
Operation of diagnostic function
Cause of operation
Inverter over-current protective circuit operates. (For a short time)
Status of air conditioner
Condition
Judgment and measures
All stop Displayed when error is detected
1. Inverter immediately stops even if restarted.
• Compressor rare short
2. Check IPDU.
• Cabling error
Error on current detection circuit
• Current value is high at AC side even while compressor stops.
• Phase of power supply is missed.
Coming-off, disconnection or short of outdoor temp sensor
All stop Displayed when error is detected
1. Compressor immediately stops even if restarted.
: Check IPDU.
2. Phase-missing operation of power supply
• Check power voltage of R, S, T.
All stop Displayed when error is detected
1. Check outdoor temp sensor (TE, TS).
2. Check CDB.
Coming-off, disconnection or short of outdoor temp sensor
All stop Displayed when error is detected
1. Check outdoor temp sensor (TD).
2. Check CDB.
Compressor drive output error
• Tin thermistor temp, Tin error
(IPDU heat sink temp. is high.)
Communication error between IPDU
• Connector coming-off between
CDB and IPDU
Compressor does not rotate.
(Over-current protective circuit works when constant time passed after activation of compressor.)
Discharge temp error
• Discharge temp over specified value was detected.
Compressor breakdown
• Operation frequency lowered and stops though operation had started.
All stop Displayed when error is detected
1. Abnormal overload operation of refrigerating cycle
2. Loosening of screws and contact error of
IPDU and heat sink
3. Cooling error of heat sink
4. Check wiring of CDB and IPDU.
All stop Displayed when error is detected
1. Compressor error (Compressor lock, etc.)
: Replace compressor.
2. Wiring trouble of compressor (Phase missing)
All stop Displayed when error is detected
1. Check refrigerating cycle. (Gas leak)
2. Error of electron control valve
3. Check pipe sensor (TD).
All stop Displayed when error is detected
1. Check power voltage. (AC200V ± 20V)
2. Overload operation of refrigerating cycle
3. Check current detection circuit at AC side.
All stop Displayed when error is detected
1. Overload operation of refrigerating cycle
2. Check outdoor temp sensor (TE).
High-voltage protection error by TE sensor
• TE temp over specified value was detected.
DC outdoor fan motor error
• IDC operation or lock was detected by DC outdoor fan driving.
Error on IPDU position detection circuit
Coming-off, disconnection or short of outdoor temp. sensor
All stop Displayed when error is detected
1. Position detection error
2. Over-current protection circuit operation of outdoor fan drive unit
• Check CDB.
• Refer to Judgment of outdoor fan.
All stop Displayed when error is detected
1. Position detection circuit operates even if driving by removing 3P connector of compressor.
• Replace IPDU.
Operation continues
Displayed when error is detected
1. Check outdoor temp sensor (TO).
2. Check P.C. board.
– 56 –
8-5. Other Function
1. Recovery method of refrigerant
RAV-SM561AT-E, RAV-SM801AT-E
• When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant recovery switch on the terminal block of the outdoor unit.
<Work procedure>
1. Turn on the power supply.
2. Using the remote controller, set FAN operation to the indoor unit.
3. Pushing the refrigerant recovery switch on the terminal block of the outdoor unit starts the forced cooling operation. (Max. 10 minutes), and then the refrigerant is recovered by operation of the valve.
4. After recovery of the refrigerant, push the refrigerant recovery switch together with closing the valve. The operation stops.
5. Turn off the power supply.
1 2 3 L N
ON
1 2 3
Refrigerant recovery switch
DANGER
Take care for an electric shock because the control P.C. board is electrified.
WARNING
Never touch these switches. Otherwise the air conditioner may not operate normally.
RAV-SM1101AT-E, RAV-SM1401AT-E
• When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant recovery switch SW802 on the cycle control P.C. board of the outdoor unit.
<Work procedure>
1. Turn on the power supply.
2. Using the remote controller, set FAN operation to the indoor unit.
3. Pushing the refrigerant recovery switch SW802 on the cycle control P.C. board of the outdoor unit starts the forced cooling operation. (Max. 10 minutes), and then the refrigerant is recovered by operation of the valve.
4. After recovery of the refrigerant, push the refrigerant recovery switch SW802 together with closing the valve. The operation stops.
5. Turn off the power supply.
Outdoor unit cycle control
P.C. board
SW802
Refrigerant recovery
SW
DANGER
Take care for an electric shock because the control P.C. board is electrified.
SW801
CN804
Optional connector
2. Applicable Control of Outdoor Unit
You can response to the following items by attaching the parts sold separately “Application control kit” (TCB-PCOS1E).
<Demand control>
• It saves the capacity of the outdoor unit by outside Demand signal to correspond to the temporary peak cut.
• The capacity saving can be adjusted with three steps, 75%, 50%, and operation stop.
<Night operation control (Sound reduction)>
Sound is controlled to 45dB or less in inputting a timer point contact.
<Compressor operation output>
The check of the compressor operation time required of a maintenance etc.
– 57 –
9. DETACHMENTS
RAV-SM561AT-E, RAV-SM801AT-E
No.
Part name
Common procedure
Procedure
REQUIREMENT
Never forget to put on the gloves at working time; otherwise an injury will be caused by the parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and turn off switch of the breaker.
2) Remove the valve cover.
(ST1T Ø4 × 10, 1 pc.)
• After taking off screws, remove the valve cover while pulling downward.
3) Remove the wiring cover (ST1T Ø4 × 8,
2 pcs.), and remove the power supply cable and indoor/outdoor connecting cables.
4) Remove the upper cabinet.
(ST1T Ø4 × 8, 5 pcs.)
• After taking off screws, remove the front side of the upper cabinet while pulling upward.
2. Attachment
1) Attach the waterproof cover.
REQUIREMENT
Be sure to attach a waterproof cover to prevent entering of rainwater, etc.
2) Attach the upper cabinet.
(ST1T Ø4 × 8, 5 pcs)
• Hook the rear side of the upper cabinet, and then cover the front cabinet with upper cabinet.
3) Connect the power cable and indoor/ outdoor connecting cables to the terminal, and then fix them with cord clamp.
(ST1T Ø4 × 10, 3 pcs)
4) Attach the wiring cover.
(ST1T Ø4 × 8, 2 pcs)
5) Attach the valve cover.
(ST1T Ø4 × 10, 1 pc)
Remarks
Valve cover
Wiring cover
Upper cabinet
Waterproof cover
– 58 –
No.
Part name
Front cabinet
Procedure
1. Detachment
1) Perform work of item 1 of
.
2) Remove screws of the front cabinet and the inverter cover. (ST1T Ø4 × 8, 2 pcs)
3) Take off screws of the front cabinet and the bottom plate. (ST1T Ø4 × 8, 3 pcs)
4) Take off screws of the front cabinet and the motor support. (ST1T Ø4 × 8, 2 pcs)
* The left side of the front side is made to insert to the side cabinet (Left), so remove it while pulling upward.
2. Attachment
1) Insert hook at the left side of the front side into the side cabinet (Left).
2) Insert hook at the right side of the side cabinet into square hole of the front cabinet.
3) Attach the removed screws at the original positions.
Remarks
Motor support
Front cabinet
Front cabinet (Left side)
Square hole Hook
Square hole Hook
– 59 –
No.
Part name
Inverter assembly
Procedure
1. Turn off the power supply.
1) Perform work of item 1 of
.
2) Take off screws fixing the upper part of the front cabinet and the inverter cover.
(ST1T Ø4 × 8, 2 pcs)
• If removing the inverter cover under this condition, P.C. board can be checked.
The control circuits (including 5V and 12V of each sensor circuit, PMV circuit, etc.) of this control P.C. board are high-voltage circuits. Before work, be sure to turn off the power supply. Be careful sufficiently also for an electric shock at electrified portions of the control circuits and their parts.
3) Using resistance for discharge (approx.
100
Ω
/40W) or plug of soldering iron, electrify + , – electrodes between + and – terminals of 3-phase: C10, 11 and single phase: C12, 13, 14 (printed as
“CAUTION HIGH VOLTAGE”) electrolytic capacitor of P.C. board for discharge.
The electrolytic capacitor may not normally discharge according to error condition and the voltage may remain.
Be sure to discharge the capacitor.
NOTE :
The electrolytic capacitor has a large capacity. Therefore it is very dangerous to short-circuit between + , – electrodes with screwdrivers for discharge because big spark generates.
4) Perform work item 1 of
.
5) Take off screws fixing the main unit and the inverter box. (Wiring port side)
(ST1T Ø4 × 8, 2 pcs)
6) Take off screws fixing the partition board and the inverter box. (ST1T Ø4 × 8, 1 pc)
7) Remove various lead wires from the upper part of the inverter.
8) Pull up the inverter upward. In this time, cut off the bundling bands binding each lead wire.
9) Disconnect connectors of various lead wires.
NOTE :
When disconnecting each connector, avoid removing the connector by holding the lead wire, but by holding the connector.
Screws
Remarks
Inverter assembly
Remove the connectors with locking function by pushing the part indicated by the arrow mark.
Front cabinet
Inverter cover
Plug of soldering iron
(Discharging period
10 seconds or more)
Cord clamp
Screws
– 60 –
No.
Part name
Control P.C.
board assembly
Procedure
1) Remove the sub-board base from the inverter assembly. (ST1T Ø4 × 8, 2 pcs)
* Remove connector at control P.C. board assembly side.
2) Remove lead wires and connectors connected from the control P.C. assembly to the other parts.
1. Lead wires
* Connection with power terminal block:
3 wires
(Black, White, Orange: Single phase,
Red, White, Black, Orange: Three phase)
* Earth wire (Black): 1 wire
2. Connectors
Connection with compressor:
(3P: Relay connector, White) *(Note 1)
Reactor (2P: Relay connector, White)
CN300: Outdoor fan (3P: White) *(Note 1)
CN701: 4-way valve (3P: Yellow)
*(Note 1) (Note 2)
CN700: PMV coil (6P: White)
CN601: TD sensor (3P: White)
CN603: TS sensor (3P: White) *(Note 1)
CN600: TE sensor (2P: White) *(Note 1)
CN602: TO sensor (2P: White)
CN500: Case thermo. (2P: Blue) *(Note 1)
*(Note 1)
For connectors, unlock the lock of the housing section, and then remove connectors.
(Note 2)
It is not provided for a cooling-only model.
3) Remove the inverter box (Metal sheet).
4) Remove the control P.C. board assembly from P.C. board support.
(Remove heat sink and control P.C. board assembly as they are screwed.)
(Note3)
Remove 4 hooking claws of P.C. board support, and remove the heat sink with hands upward.
5) Take off 2 screws fixing the heat sink with the control P.C. board assembly.
6) Install a new control P.C. board assembly.
(Note 4)
When installing a new control P.C. board assembly, be sure to insert the board correctly in the board groove.
Install it so that the heat sink comes to contact surely with the metal sheet.
– 61 –
Remarks
Power supply cable
Take off earth screws.
Inverter box
(Metal sheet)
P.C. board assembly
P.C. board base
Control P.C. board assembly
P.C. board base
Hooking claws
(4 positions)
Inverter box
(Metal sheet)
Heat sink
No.
Part name
Fan motor
Procedure
1) Perform works of items 1 of
and
.
2) Remove the flange nut fixing the fan motor and propeller fan.
• The flange nut is loosened by turning it clockwise.
(Turn it counterclockwise to tighten it.)
3) Remove the propeller fan.
4) Disconnect connector for fan motor from the inverter.
5) Take off the fixing screws (2 pcs) while supporting the fan motor so that it does not fall.
* Caution when assembling fan motor
Tighten the flange nut with torque
4.9 Nm (50kgf/cm).
Remarks
Flange nut
Loosen the nut by turning clockwise
Propeller fan
Fan motor
– 62 –
No.
Part name
Compressor
Procedure
1) Perform works of items 1 of and
.
, 1 of
,
2) Recover refrigerant gas.
3) Remove the partition board.
(ST1T Ø4 × 8, 3 pcs)
4) Take off screws of the motor base and the bottom plate. (ST1T Ø4 × 8, 2 pcs)
5) Remove the noise-insulator.
6) Remove the terminal cover, and then disconnect the lead wires of the compressor.
7) Using a burner, remove the pipes connected to the compressor.
NOTE :
Pay attention to that flame does not involve 4way valve or PMV.
(If doing so, a malfunction may be caused.)
8) Take off screws of the bottom plate and the heat exchanger. (ST1T Ø4 × 8, 1 pc)
9) Take off the fixing screws of the bottom plate and the valve clamping plate.
(ST1T Ø4 × 8, 2 pcs)
10) Pull out the refrigerating cycle with the heat exchanger.
11) Take off compressor bolts fixing the compressor to the bottom plate. (3 pcs)
Remarks
Partition board
Compressor lead
Case thermo
Heat exchanger
Screw
Reactor
Compressor bolt
(3 pcs)
Screws
(2 pcs)
Valve support board
1) Perform woks of item 1 of
and 1 of
.
2) Take off screw fixing the reactor.
(ST1T Ø4 × 8)
Partition board
Reactor
– 63 –
No.
Part name
Pulse Modulating
Valve (PMV) coi
Procedure
1. Detachment
1) Perform works of items 1 of
.
and 1 of
2) Remove the side cabinet (Right).
3) Pull upward the coil, and remove the coil from PMV body.
2. Attachment
1) Fix the projection for coil positioning surely to pipe of PMV body and fix it.
PMV coil
Remarks
P.M.V. coil
Fan guard
1. Detachment
1) Perform works of items 1 of
.
and 1 of
REQUIREMENT
Perform works on a corrugated cardboard, cloth, etc. to prevent flaw on the product.
2) Remove the front cabinet, and then put it downward on the floor.
3) Take off the hooking claw of the fan guard by pushing with minus screwdriver, etc.
2. Attachment
1) Insert the hooking claw of the fan guard into hole of the front cabinet. Fix claw while pushing the hooking claws
(10 positions) with hands.
REQUIREMENT
Check that all the hooking claws are fixed to the specified positions.
Minus screwdriver
Hooking claw Front cabinet
Front cabinet
Fan guard
– 64 –
RAV-SM1101AT-E, RAV-SM1401AT-E
No.
Part name
Common procedure
Procedure
REQUIREMENT
Never forget to put on the gloves at working time; otherwise an injury will be caused by the parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and turn off switch of the breaker.
2) Remove the front panel.
(Hex. screw Ø4 × 10, 3 pcs)
* After taking off screws, remove the front panel while pulling downward.
3) Disconnect the power supply cable and indoor/outdoor connecting cables from the cord clamp and terminals.
4) Remove the ceiling plate.
(Hex. screw Ø4 × 10, 6 pcs)
2. Attachment
1) Attach the ceiling plate.
(Hex. screw Ø4 × 10, 6 pcs)
2) Connect the power supply cable and indoor/outdoor connecting cable to the terminal, and then fix them with cord clamp.
REQUIREMENT
Using bundling band sold at a market, be sure to fix the power cables and indoor/ outdoor connecting cables along the interunit cable so that they do not come to contact with the compressor, valve at gas side, pipe at gas side, and discharge pipe.
3) Attach the front panel.
(Hex. screw Ø4 × 10, 3 pcs) and then cover the front cabinet with upper cabinet.
Remarks
Front panel
Ceiling panel
– 65 –
No.
Part name
Discharge port cabinet
Procedure
1. Detachment
1) Perform work of item 1 of
.
2) Take off screws of the air outlet cabinet and the partition board.
(ST1T Ø4 × 8, 3 pcs)
3) Take off screws of the air outlet cabinet and the bottom plate.
(Hex. screw Ø4 × 10, 2 pcs)
4) Take off screws of the air outlet cabinet and the heat exchanger.
(ST1T Ø4 × 8, 1 pc)
5) Take off screws of the air outlet cabinet and the motor base.
(ST1T Ø4 × 8, 2 pcs)
6) Take off screws of the air outlet cabinet and the fin guard.
(Hex. screw Ø4 × 10, 2 pcs)
2. Attachment
1) Put the upper left side of the air outlet cabinet on the end plate of the heat exchanger, and then fix it with screw.
(ST1T Ø4 × 8, 1 pc)
2) Attach the removed screws to the original positions.
Remarks
Heat exchanger
Fin guard Motor base
Air outlet cabinet
Upper side of end plate of heat exchanger
Air outlet cabinet
Side cabinet 1) Perform work of item 1 of
.
2) Take off screw fixing the inverter and the side cabinet. (ST1T Ø4 × 8, 1 pc)
3) Take off screws of the side cabinet and the valve support plate. (ST1T Ø4 × 8, 2 pcs)
4) Take off screws of the side cabinet and the piping panel (Rear).
(HEX. screw Ø4 × 10, 1 pc)
5) Take off screws of the side cabinet and the bottom plate (Rear).
(HEX. screw Ø4 × 10, 1 pc)
6) Take off screws of the side cabinet and the fin guard (Heat exchanger).
(HEX. screw Ø4 × 10, 2 pcs)
Inverter Side cabinet
Valve support plate Piping panel
(Rear)
– 66 –
No.
Part name
Inverter assembly
Procedure
1) Perform works of items of 1 of
, 1 of
, and
.
2) Disconnect connectors connected from the cycle P.C. board to other parts.
CN600: TD sensor (3P: White)
CN601: TO sensor (2P: White)
CN604: TE sensor (2P: White) *(Note 1)
CN605: TS sensor (3P: White) *(Note 1)
CN301: Outdoor fan (3P: White) *(Note 1)
CN300: Position detection (5P: White)
CN500: Case thermo (2P: Blue) *(Note 1)
CN700: 4-way valve (3P: Yellow) *(Note 1)
CN702: PMV coil (6P: White) *(Note 1)
*(Note 1)
Unlock the lock of housing part, and then disconnect the connectors.
3) Cut the tie lap fixing various lead wires to the inverter assembly.
4) Remove the rubber sheet and noise-proof plate (upper).
5) Remove terminal cover of the compressor and Comp. lead wire.
6) Pull upward the hook (Rear left) with the partition board as if removing it.
• Caution when attaching inverter assembly
When installing the inverter assembly to the partition board, attach hook (Rear left) of the partition board surely.
Remarks
Cycle P.C. board Inverter assembly
Rubber sheet Noise-proof plate
(Upper)
Comp. lead
There is a hook with the partition board at rear side.
– 67 –
No.
Part name
Cycle P.C.
board
Procedure
1) Perform the work in item 1 of
.
2) Disconnect connectors and lead wires connected from cycle P.C. board to other parts.
1. Connector
CN600: TD sensor (3P: White)
CN601: TO sensor (2P: White)
CN604: TE sensor (2P: White) *(Note 1)
CN605: TS sensor (3P: White) *(Note 1)
CN301: Outdoor fan (3P: White) *(Note 1)
CN300: Position detection (5P: White)
CN500: Case thermo (2P: Blue) *(Note 1)
CN700: 4-way valve (3P: Yellow)
*(Note 1)
CN702: PMV coil (6P: White) *(Note 1)
CN800: Connection with IPDU P.C. board
(5P: Red) *(Note 1)
CN01: Connection with IPDU P.C. board
(5P: Red) *(Note 1)
CN02: Indoor/outdoor connecting terminal block (3P: Black)
*(Note 1)
CN03: Connection with IPDU P.C. board
(3P: White) *(Note 1)
CN04: Connection with IPDU P.C. board
(2P: White) *(Note 1)
*(Note 1)
Unlock the lock of housing part, and then disconnect the connectors.
3) Remove claws fixing P.C. board at four corners, and then remove the cycle P.C.
board.
4) Install a new cycle P.C. board.
Remarks
Cycle P.C. board
P.C. board fixing hooks (4 positions)
– 68 –
No.
Part name
IPDU P.C.
board
Procedure
1) Perform the works in item
.
2) Take off screws of the inverter assembly, and then classify the inverter assembly.
(M4 × 8, 3 pcs. hooks at two positions)
3) Disconnect connectors and lead wires connected from IPDU P.C. board to other parts.
1. Connector
CN04: Connection with cycle P.C. board
(3P: White) *(Note 1)
CN05: Connection with cycle P.C. board
(2P: White) *(Note 1)
CN06: Connection with cycle P.C. board
(5P: Red)
CN13: Connection with cycle P.C. board
(5P: Red) *(Note 1)
CN600: Heat sink sensor (2P: Black)
*(Note 1)
2. Lead wire
CN01: Connection with power supply terminal block (Red)
CN02: Connection with power supply terminal block (White)
CN03: Connection with power supply terminal block (Black)
CN07: Earth wire (Black)
CN14: Connection with reactor (White)
CN15: Connection with reactor (White)
CN09: Connection with compressor
(Red)
CN10: Connection with compressor
(White)
CN11: Connection with compressor
(Black)
*Note 1)
Unlock lock of the housing part, and then disconnect the connectors.
4) Remove lead wires of 3-phase rectifier.
(5 pcs)
5) Remove cover of the heat sink.
(M4 × 8, 3 pcs)
6) Take off screws (2 pcs) fixing the heat sink with IGBT, remove claws (4 positions) of P.C.
board support, and then remove IPDU P.C.
board.
7) Install a new IPDU P.C. board.
Screw
Remarks
Hooks
Screws
IPDU P.C. board
3-phase rectifier Gray
Orange
Heat sink cover
Black, Brown, Red from rear side
Screw
Screw
Heat sink
– 69 –
No.
Part name
Fan motor
Procedure
1) Perform the works in item 1 of
and 1 of
.
2) Take off flange nut fixing fan motor with propeller fan.
• The flange nut is loosened by turning it clockwise.
(Turn it counterclockwise to tighten it.)
3) Remove the propeller fan.
4) Disconnect connector for fan motor from the inverter.
5) Take off the fixing screws (4 pcs) while supporting the fan motor so that it does not fall.
* Caution when assembling fan motor
• Tighten the flange nut with torque
4.9Nm (50kgf/cm).
• Pay attention that the reactor at rear side of the inverter does not come to contact with the fan motor lead.
REQUIREMENT
Using bundling band sold at a market, be sure to fix the fan motor lead wires to the motor base so that they do not come to contact with the propeller fan.
Flange nut
Remarks
Loosened by turning clockwise
Propeller fan
Fan motor
Motor base Fix with bundling band
– 70 –
No.
Part name
Compressor
Procedure
1) Recover the refrigerant gas.
2) Perform the works in item 1 of
, 1 of
, and
,
.
3) Remove the piping panel (Front).
Take off screws of the piping panel (Front) and the bottom plate.
(HEX. screw Ø4 × 10, 2 pcs)
Take off screws of piping panel (Front) and piping panel (Rear).
(HEX. screw Ø4 × 10, 1 pc)
4) Remove the valve fixing plate.
Take off screws of the valve fixing plate and the partition board. (ST1T Ø4 × 8, 2 pcs)
Take off screws of valve fixing plate and valves at liquid and gas sides. (M6, 4 pcs)
5) Remove the partition board.
Take off screws of the partition board and bottom plate. (ST1T Ø4 × 8, 1 pc)
Take off screws of the partition board and the end plate of the heat exchanger.
(ST1T Ø4 × 8, 2 pcs)
6) Remove the noise-proof plate.
7) Remove terminal cover of the compressor, and then remove case thermo of the compressor.
8) Remove the sensor and pipe cover fixed to the discharge pipe.
9) Using a burner, remove pipe connected to the compressor.
NOTE :
Pay attention to that flame does not involve 4way valve or PMV.
(If doing so, a malfunction may be caused.)
10) Pull out the discharge pipe and the suction pipe of the refrigerating cycle upward.
11) Take off the compressor bolts fixing the compressor to the bottom plate. (3 pcs)
12) Pull out the compressor toward you.
PMV coil
1. Detachment
1) Perform the works in item 1 of
and
.
2) Pull the coil upward while turning it, and then remove the coil from PMV body.
2. Attachment
1) Be sure to match the projection for coil positioning with the concave part of PMV body, and then fix the coil.
Remarks
Piping panel (Front)
Partition board
Valve fixing plate Valves
Sensor/pipe cover
Case thermo Remove
(Suction pipe)
Remove
(Discharge pipe)
Compressor bolts
(3 pcs)
Projection for positioning
PMV body Concave part
– 71 –
No.
Part name
Fan guard
Procedure
1. Detachment
1) Perform works of items 1 of
and 1 of
.
REQUIREMENT
Perform works on a corrugated cardboard, cloth, etc. to prevent flaw on the product.
2) Remove the front cabinet, and then put it downward on the floor.
3) Take off screws fixing the bell mouth.
(ST1T Ø4 × 8, 2 pcs)
4) Remove the bell mouth.
5) Take off the hooking claw of the fan guard by pushing with minus screwdriver, etc.
2. Attachment
1) Insert the projection at upper side of the fan guard into square hole of the discharge port cabinet, and then insert the hooking claw. Fix hooking claws while pushing them (5 positions) with hands.
REQUIREMENT
Check that all the hooking claws are fixed to the specified positions.
2) Attach the fan guard by hooking claws
(3 positions) at upper side of the bell mouth to the square holes of the discharge port cabinet.
3) After attachment, fix it with screws.
(ST1T Ø4× 8, 2 pcs)
Bell mouth
Remarks
Discharge port cabinet
Bell mouth
Take off screws (2 pcs)
Minus screwdriver
Discharge port cabinet
Fan guard
Hooking claw
Discharge port cabinet
Square hole (3 positions)
Claw (3 positions) Bell mouth
– 72 –
10. EXPLODED VIEWS AND PARTS LIST
RAV-SM561AT-E, RAV-SM801AT-E
Location
No.
13
14
15
4
5
6
1
2
3
7
8
9
10
11
12
16
17
Part Description
43005619 Cabinet, Front
43005616 Cabinet, Upper
43005617 Cabinet, Side, Right
43005569 Cabinet, Side, Left
4301V035 Guard, Fan
4301V053 Guard, Fin
43042479 Base, Ass’y
43119471 Cover, Valve, Packed
43062230 Cover, Wiring, Ass’y
43041627 Compressor, Ass’y,
DA150, A1F-20F
43043730 Condenser, Ass’y
(SM561AT-E)
43043720 Condenser, Ass’y
(SM801AT-E)
43046392 Valve, Packed, 6.35
(SM561AT-E)
43046393 Valve, Packed, 12.7
(SM561AT-E)
43146584 Valve, Packed, 9.52 DIA
(SM801AT-E)
43146670 Valve, Packed, 15.9
(SM801AT-E)
43147196 Bonnet, 1/4 IN (SM561AT-E)
– 73 –
Location
No.
18
19
20
21
22
30
31
32
33
34
35
23
24
25
26
27
28
29
36
37
38
Part Description
43147195 Bonnet, 1/2 IN (SM561AT-E)
43194029 Bonnet (SM801AT-E)
43047401 Bonnet, 3/8 IN (SM801AT-E)
43046439 Valve, 4-Way, STF-0108Z
(SM561AT-E)
43146619 Valve, 4-Way, STF-0213Z
(SM801AT-E)
43046348 Coil, Solenoid,
43146662 Valve, Pulse, Modulating
43046411 Coil, PMV, CAM-MD12TF-1
43058270 Reactor
4302C048 Motor, Fan, ICF-140-43-4
43020329 Fan, Propeller, PJ421
43047667 Nut, Flange
43032441 Nipple, Drain
43089160 Cap, Waterproof
43050407 Thermostat, Bimetal
43063339 Holder, Sensor (TO)
43049749 Rebber, Cushion
43063321 Holder, Sensor
43063322 Holder, Sensor
43063325 Holder, Sensor
43063317 Holder, Thermostat
705
707
708
706
Location
No.
Part Description
701 43050410 Sensor, TD
702 43050412 Sensor, TE
703 43050413 Sensor, TS
704 43050415 Sensor, TO
705 43062228 Base, P.C. Board
– 74 –
Location
No.
Part Description
706 4306A116 Terminal Block, 6P
707 4316V254 P.C. Board, Ass’y, SW,
MCC-1530
708 4316V268 P.C. Board, Ass’y, MCC-5009
701
702
703
704
RAV-SM1101AT-E, RAV-SM1401AT-E
Location
No.
9
10
11
12
13
14
15
7
8
5
6
3
4
1
2
16
17
18
19
Part Description
43050406 Cabinet, Air Outled
43191636 Cabinet, Front, Ass’y
43191635 Cabinet, Side, Ass’y
43005491 Panel, Upper
43191633 Guard, Fin
43191651 Guard, Fan
43122065 Bell Mouth
43047667 Nut, Flange
43120224 Fan, Propeller, PE492
43121734 Motor, Fan, ICF-280-100-1
4314G178 Condenser, Ass’y
43191515 Panel, Front, Piping
43191605 Panel, Back, Piping
43119390 Hanger
43041774 Compressor, Ass’y,
DA420A3F-21M
43050407 Thermostat, Bimetal
43063317 Holder, Thermostat
43100248 Base, Ass’y
43197157 Bolt, Compressor
Location
No.
20
21
22
30
31
32
33
34
35
36
23
24
25
26
27
28
29
37
Part Description
43149324 Rubber, Cushion, EPDM
43146619 Valve, 4-WAY, STF-0213Z
43146611 Coil, Solenoid,
VHV-01AJ502E1
43146634 Valve, Pulse, Modulating
43146663 Coil, PMV, UKV-U048E
43148170 Accumulator, Ass’y
43146584 Valve, Packed, 9.52 DIA
43146613 Valve, Ball
43047401 Bonnet, 3/8 IN
43194029 Bonnet
43158190 Reactor
43019904 Holder, Sensor
43063188 Holder, TC Sensor
43063332 Holder, Sensor
43147611 Strainer
43148176 Strainer
43089160 Cap, Waterproof
43032441 Nipple, Drain
– 75 –
707
706
708
704
701
TD
TO
TS
TE
702
703
705
Location
No.
Part Description
701 43050354 Sensor TD
702 43050382 Sensor TC (F6)
703 43060750 Terminal Block, 3P
704 43150259 Rectifier
705 43160502 Terminal Block
– 76 –
Location
No.
Part Description
706 4316V255 P.C. Board, Ass’y, CDB,
MCC-1531
707 4316V264 P.C. Board Ass’y, IPDU,
MCC-1438
708 43050398 Sensor TG (F4)
TOSHIBA CARRIER CORPORATION
2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN
Copyright © 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
advertisement
Key Features
- New Digital Inverter technology
- R410A refrigerant
- Pulse Motor Valve (PMV) control
- Outdoor Unit only
- Indoor Unit information in separate manual (FILE NO. A03-003F)
- Detailed specifications
- Refrigerating cycle diagram
- Wiring diagrams
- Troubleshooting guide
Frequently Answers and Questions
What type of refrigerant does this air conditioner use?
Where can I find information about the indoor unit?
What are the key features of the PMV control?
Related manuals
advertisement
Table of contents
- 3 1. SPECIFICATIONS
- 5 2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 8 3. REFRIGERATING CYCLE DIAGRAM
- 11 4. WIRING DIAGRAM
- 12 5. SPECIFICATIONS OF ELECTRICAL PARTS
- 13 6. REFRIGERANT R410A
- 13 6-1. Safety During Installation/Servicing
- 13 6-2. Refrigerant Piping Installation
- 17 6-3. Tools
- 18 6-4. Recharging of Refrigerant
- 19 6-5. Brazing of Pipes
- 21 7. CONTROL SPECIFICATIONS
- 21 7-1. Outdoor Controls
- 24 7-2. Outline of Main Controls
- 29 8. TROUBLESHOOTING
- 29 8-1. Summary of Troubleshooting
- 31 8-2. Check Code List
- 34 8-3. Error Mode Judgment by LED Display of Outdoor Unit
- 35 8-4. Contents of Error Display
- 36 8-5. Troubleshooting Procedure for Each Check Code
- 57 8-5. Other Function
- 58 9. DETACHMENTS
- 73 10. EXPLODED VIEWS AND PARTS LIST