Eaton Power Defense Frame 3 reverse feed connector kit Cat Num PDG3X3(2)(4)TA400HRF Instructions
Eaton Power Defense Frame 3 reverse feed connector kit Cat Num PDG3X3(2)(4)TA400HRF is designed to be used on Eaton PDG3 Frame Circuit Breakers, Molded Case Switches, and Motor Circuit Protectors. It allows for the connection of cables to the breaker from the opposite side of the breaker, which can be useful in situations where space is limited or where it is difficult to access the breaker from the front. The kit includes all of the necessary hardware to install the connector, including lugs, screws, and a terminal cover.
Advertisement
Advertisement
Instruction Leaflet
IL012252EN
Eaton Circuit Breakers
Reverse Feed Connector Kit
Catalog No. PDG3X3(2)(4)0TA400HRF
Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Power
™
Instruction Leaflet IL012252EN Eaton Circuit Breakers
Reverse Feed Connector Kit
Catalog No. PDG3X3(2)(4)TA400HRF
For use on Eaton PDG3 Frame Circuit Breakers,
Molded Case Switches, and Motor Circuit Protectors.
DANGER:
DO NOT INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT
WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY
(INCLUDING BURN), OR SUBSTANTIAL PROPERTY DAMAGE CAN
RESULT FROM CONTACTWlTH ENERGIZED EQUIPMENT.
ALWAYSVERIFY THAT NO VOLTAGEIS PRESENT BEFORE PROCEED-
ING WITH THE TASK.
Fig. 1.
The installation and use of Eaton products should be in accordance with the provisionsof the U.S.National Electrical Code and/or ther government regulations, local codes, or industry standards that are pertinent to the particular end use installation or use not in accordance with these codes and standards could be hazardous to personnel equipment.
2 EATON CORPORATION www.eaton.com
Eaton Circuit Breakers
Reverse Feed Connector Kit
Catalog No. PDG3X3(2)(4)TA400HRF
Installation Instructions
To Install the Lugs:
1. Align the lugs so that the side with the step faces against the breaker’s conductor. You will notice that the step locks to limit rotation. This is critical to provide additional protection in the case of a high fault.
2. Insert the 1/2” socket head cap screw and lock washer through the breaker conductor and into the terminal. Tighten to 200 lbs
(22.6 N·m).
3. Repeat steps 1 and 2 until all lugs are installed.
4. Install the terminal cover and tighten the terminal cover screws to 6 - 8 in-lbs (0.7 - 0.9 N·m).
To Install Cable:
1. Choose the correct cable size for the application. Each lug can accommodate a cable from #3 - 500 mcm.
2. Prepare the cable. a. If using multi-stranded, flexible wire, the use of a ferrule on the end of the cable is recommended to ensure the strongest connection and reduce fatigue over time.
3. Insert the prepared cable(s) into the reverse lug.
4. Torque the terminal screw(s) to 375 in-lbs (42.4 N·m).
Instruction Leaflet IL012252EN
EATON CORPORATION www.eaton.com
3
Instruction Leaflet IL0121252EN
The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility.
This Instruction Booklet is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative.
The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract.
The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS
CONTAINED HEREIN.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein.
Eaton Circuit Breakers
Reverse Feed Connector Kit
Catalog No. PDG3X3(2)(4)TA400HRF
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2012 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL012252EN
Part No. IL012252EN H01
Eaton is a registered trademark of Eaton
Corporation.
All other trademarks are property of their respective owners.

Public link updated
The public link to your chat has been updated.
Advertisement