Advertisement
Advertisement
Compact performance
CPA pneumatics manual
Valve terminal with
CPA pneumatics
Type CPA...−VI
ÔÔ
Ô ÔÔ ÔÔ ÔÔ Ô Ô Ô Ô ÔÔ
ÔÔ Ô Ô Ô
ÔÔ ÔÔÔ Ô ÔÔ
ÔÔ Ô Ô Ô ÔÔ Ô Ô ÔÔ
Ô Ô Ô ÔÔ
Manual
173 515 en 0306d
ÓÓ
ÓÓ Ó Ó Ó Ó ÓÓ Ó ÓÓ
Ó Ó Ó Ó ÓÓ ÓÓ
Contents and general instructions
Author . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M. Simons
Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M. Holder
Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . German text
Layout . . . . . . . . . . . . . . . . Festo AG & Co. KG, Dept. KG−GD
Type setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DUCOM
Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . en 0306d
Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . P.BE−CPA−EN
Order no.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 515
AS−Interface ® is a registered trade mark of
AS−Interface Association
E (Festo AG&Co., D73726 Esslingen, Federal Republic of Germany, 2003)
Internet: http://www.festo.com
E−Mail: [email protected]
The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design registrations.
Festo P.BE−CPA−EN en 0306d
I
Contents and general instructions
II
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
Contents
1.
1.1
1.2
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group
Service
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1−1
1−4
1−7
VI
XI
V
V
V
2.
2.1
Fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1
Fitting onto a wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2
Hat rail fitting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2−1
2−4
2−5
2−6
3.
3.1
3.2
3.3
3.4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3−1
Preparing the compressed air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1
Operation with non−lubricated compressed air . . . . . . . . . . . . . . . .
3.1.2
Operation with lubricated compressed air . . . . . . . . . . . . . . . . . . . .
General connecting methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1
Laying the tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2
Basic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the CPA valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1
Auxiliary pilot air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2
CPA valve terminal with pressure zone separation . . . . . . . . . . . . .
3.3.3
Connecting the supply, exhaust and work lines . . . . . . . . . . . . . . .
3.3.4
Connecting the electric cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address assignment of the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3−8
3−9
3−9
3−12
3−14
3−20
3−24
3−4
3−4
3−5
3−7
3−7
Festo P.BE−CPA−EN en 0306d
III
Contents and general instructions
5.
5.1
5.2
5.3
4.
4.1
4.2
5.4
B.
B.1
B.2
C.
5.5
A.
A.1
A.2
IV
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4−1
Testing the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1
Checking the valve functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2
Checking the valve−cylinder combination
Eliminating faults
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1
Impairment of function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2
LED display of the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4−4
4−5
4−9
4−15
4−15
4−17
Maintenance and conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5−1
General precautionary measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dismantling the CPA valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing CPA valve terminal components . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1
Replacing valve sub−bases, blanking plates or additional supply plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2
Replacing the large surface−mounted silencer . . . . . . . . . . . . . . . .
5.3.3
Replacing the end plate, sub−base or manifold block . . . . . . . . . . .
Conversion work on the CPA valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1
Conversion from non−locking to locking/non−locking manual override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2
Conversion to internal or external pilot air . . . . . . . . . . . . . . . . . . . .
5.4.3
Converting the CPA valve terminal to different pressure zones . . .
5.4.4
Conversion of valve location for actuating one or two solenoid coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adding/removing valve locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−4
5−5
5−9
5−9
5−11
5−12
5−19
5−19
5−21
5−22
5−24
5−25
Technical appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A−1
A−3
A−4
Supplementary component summary and installation instructions . . . . .
Overview of end plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Separating the CPA valve terminal from the CPX terminal . . . . . . . . . . . . . . .
B−1
B−3
B−6
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C−1
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
Designated use
Target group
Service
The CPA valve terminals described in this manual are in tended for fitting into a machine or automated system. It is absolutely necessary to observe the safety instructions in this manual as well as the designated use of the relevant CPA valve terminal. CPA valve terminals may only be used as fol lows: as intended in industrial installations without any modifications by the user
Only those conversions or modifications which are de scribed in the information supplied with the product are permitted.
in faultless technical condition.
When used together with commercially available compo nents, such as actuators, the specified limits for pressures, temperatures, electrical data, torques etc. must be observed.
National and local safety regulations must also be observed.
This manual is directed exclusively at technicians trained in control and automation technology.
Please consult your local Festo repair service if you have any technical problems.
Festo P.BE−CPA−EN en 0306d
V
Contents and general instructions
Notes on the use of this manual
This manual contains specific information on fitting, installing, commissioning, servicing and converting the CPA valve termi nal. This manual deals exclusively with the pneumatic compo nents and refers to the valve terminal variants listed in the following tables.
CPA valve terminal with CPX terminal, type CPA...
Information on electric/electronic components: see manual CPX system, installation and com missioning"
ÓÓÓ
ÓÓ ÓÓÓ ÓÓ Ó
Ó ÓÓ Ó Ó ÓÓ Ó ÓÓ Ó
Ó ÓÓ Ó Ó Ó ÓÓ Ó
Tab.0/1: CPA valve terminal with CPX terminal
Connection variants of the CPA valve terminal
CPA valve terminal with IC connection
Information on electric/electronic components: in this manual
ÓÓÓ ÓÓ
ÓÓÓ ÓÓ Ó Ó Ó ÓÓ ÓÓÓ
Ó ÓÓ ÓÓÓ ÓÓ ÓÓ Ó Ó Ó ÓÓ Ó Ó
Ó Ó ÓÓ ÓÓ Ó
ÓÓ Ó
VI
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
Connection variants of the CPA valve terminal
CPA valve terminal with MP connection
Type CPA..−IMP.
Information on electric/electronic components: see information supplied with the product
CPA valve terminal with CP connection
Type CPA..−IFB−CP and CPA..−IFB−DN.
Information on electric/electronic components: see manual CP system, installation and commis sioning"
CPA valve terminal with AS−interface connection
Type CPA..−IFB−ASI and CPA..−IFB−ASI−Z.
Information on electric/electronic components: see information supplied with the product
CPA valve terminal with AS−interface connection
and 4 inputs
Type CPA..−GE−ASI−4E4A−Z
and 8 inputs
Type CPA..−GE−ASI−8E8A−Z
Information on electric/electronic components: see information supplied with the product
Ó ÓÓ Ó
ÓÓÓ
Ó Ó ÓÓÓ
ÓÓÓ
ÓÓÓ ÓÓ ÓÓ ÓÓ
Ó Ó
Ó Ó
Ó Ó
ÓÓÓ
ÓÓÓ
ÓÓ ÓÓÓ ÓÓÓ Ó Ó Ô Ó
ÓÓÓ ÔÓ ÓÓ ÓÓ
Ó Ó
Ó Ó
ÓÓÓ
Ó ÓÓ Ó ÓÓÓ ÓÓ Ó ÓÓÓ
ÓÓÓ Ó ÓÓ Ó ÓÓ Ó ÓÓÓ
ÓÓ Ó ÓÓ
ÓÓÓ
ÓÓÓ Ó ÓÓÓ Ó ÓÓ
Ó ÓÓ Ó Ó Ó ÓÓÓ Ó ÓÓ
Ó ÓÓ Ó Ó Ó
Tab.0/2: Connection variants of the CPA valve terminal
Festo P.BE−CPA−EN en 0306d
VII
Contents and general instructions
Information on further CP modules or CPX modules can be found in the manual for the relevant module. The following tables provide an overview.
Manuals on the CPA valve terminal with CPX terminal
Manual System manual," type: P.BE−CPX−SYS−...
Contents Overview of the structure, components and method of functioning of CPX terminals; instructions on installation and commissioning as well as basic information on parame trizing
Manual CPX field bus node" type: P.BE−CPX−FB...
CPX I/O modules" type: P.BE−CPX−EA−...
Valve terminal with CPA pneumatics" type: P.BE−
CPA−... or Valve terminal with Midi/Maxi pneu matics" type:
P.BE−MIDI/MAXI−03−...
Contents Instructions on fitting, in stalling, commissioning and diagnosing the relevant field bus node
Instructions on connections and fitting, installing and commissioning input and output modules of type
CPX−.... as well as CPA−...
and the Midi/Maxi pneuma tic interface
Information on fitting, in stalling and commissioning the relevant pneumatics
ÓÓ
ÓÓ Ó ÓÓ Ó Ó Ó ÓÓ Ó ÓÓ
ÓÓ Ó Ó Ó ÓÓ Ó Ó ÓÓ
Tab.0/3: Manuals on the CPA valve terminal with CPX terminal
VIII
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
Manuals on the CP system
Manual CP system, installation and commissioning" type: P.BE−CPSYS−...
Periph erals
Contents General basic information on the functioning, fitting, installation and commissioning of CP systems.
Manual CP field bus node, programming and di agnosis"
Type:P.BE−CP−FB...
or P.BE−VIFB...−10...
CPV valve terminal, pneumatics" or CPA valve terminal, pneu matics"
Type:P.BE−CPV−...
or P.BE−CPA−...
CP modules, elec tronics"
Type:P.BE−CPEA−...
Contents Special information on commissioning, pro gramming and diag nosing related to the node used
Information on fitting, installing and commis sioning CPA or CPV valve terminals
Information on fitting, installing and commis sioning CP I/O mod ules
Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö Ö
ÔÔ Ô Ô Ô Ô Ô
ÔÔ Ô
Tab.0/4: Manuals on the CP system
Festo P.BE−CPA−EN en 0306d
IX
Contents and general instructions
1
Valve plates
2
Sub−bases
3
End plates
The CPA valve terminal consists of pneumatic and electric components. The main pneumatic components are the valve plates, sub−bases and end plates (see diagram).
1
Ó ÓÓ ÓÓÓÓ
Ó ÓÓ ÓÓ ÓÓ ÓÓÓÓ Ó
Ó Ó ÓÓ ÓÓ
ÓÓÓÓ Ó Ó ÓÓ
Ó ÓÓ ÓÓÓÓ ÓÓ ÓÓ
Ó Ó ÓÓ
3 2 3
Fig.0/1: Main components of the CPA valve terminal
This manual contains the documentation of the valve plates with Ident. code B, E, G, H, J, K, M, N (see chapter System overview, description of components").
X
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto gram. A distinction is made between the following danger warnings:
Warning
This means that failure to observe this instruction may result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may result in personal injury or damage to property.
Please note
This means that failure to observe this instruction may result in damage to property.
The following pictogram marks passages in the text which describe activities with electrostatically sensitive compo nents.
Electrostatically sensitive components may be damaged if they are not handled correctly.
Festo P.BE−CPA−EN en 0306d
XI
Contents and general instructions
Marking special information
The following pictograms mark passages in the text contain ing special information.
Pictograms
Information:
Recommendations, tips and references to other sources of information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment−friendly use of Festo products.
Text markings
· The bullet indicates activities which may be carried out in any order.
1. Figures denote activities which must be carried out in the numerical order specified.
Hyphens indicate general activities.
XII
Festo P.BE−CPA−EN en 0306d
Contents and general instructions
The following product−specific terms and abbreviations are used in this manual:
Term Meaning
Sub−base
AS−interface
CP
CP cable
CP modules
CP system
CPA10:
CPA14:
CPA valve terminal
Pneumatic manifold sub−base with open or closed compressed air channel for single−solenoid, double−solenoid or mid−position valves, with work con nections 2 and 4.
Actuator−sensor interface
Compact Performance
Special cable for coupling the various CP modules
Common term for the various modules which can be incorporated in a CP system.
Complete system consisting of CP field bus node and CP modules
Designation of the CPA valve terminal sizes:
CPA valve terminal with micro valve locations
CPA valve terminal with mini valve plates
CPA valve terminal (type 12) for CPX terminal, field bus systems, IC, MP or
AS−interface connection.
CPA valve terminal variants which enable the valve terminal to be connected to the AS−interface bus.
CPA valve terminal with AS−interface connection
CPA valve terminal with CP connection
CPA valve terminal with individual con nection (IC connec tion)
CPA valve terminal variant with plug and socket which enables the CPA valve terminal to be connected to further CP modules.
CPA valve terminal variant on which each valve soleoid coil can be con nected individually with a special cable.
CPA valve terminal with multipin con nection (MP connec tion)
CPX modules
CPA valve terminal variant with Sub−D plug via which all valve solenoid coils are centrally connected.
Common term for the various modules which can be incorporated in a CPX terminal
CPX terminal Modular, electric terminal type 50
Festo P.BE−CPA−EN en 0306d
XIII
Contents and general instructions
Term
I/O
Electric sub−base
Electrical bridge
End plate
Manual override
Components
Pin−type
Meaning
Input/output modules
Sub−base with multipin, CP or AS−interface connection conducts the supply voltage from the sub−base to the solenoid coils on CPA valve terminals with MP, CP or AS−interface connection.
Extreme left and right−hand end plates of the CPA valve terminal with con nections for supplying the valves with compressed air and for conducting the exhaust air, as well as for connecting silencers.
Manual override
Common term for pneumatic sub−bases, valve plates, additional pressure supply plates, blanking plates, end plates, CPX adapters, electric sub−bases
(with IC, MP, CP or AS−interface connection), electric manifolds, sub−bases, end plate covers, silencers.
Plug connector (with/without inner thread) for connecting the supply lines to the CPA valve terminal pneumatic sub−base
Pneumatic manifold sub−base for valve plates, with work connections 2 and 4 and open or closed compressed air channel 1.
Pneumatic interface The pneumatic interface is the interface between the modular electric peripherals of the CPX terminal and the CPA pneumatics.
Blanking plate
Valve plate
Manifold sub−base
Plate without valve function, for reserving valve locations.
Plate with single−solenoid, double−solenoid or mid−position valve
Sub−base for electrically linking the valve solenoid coils with the elec tricsub−base or the CPX pneumatic interface.
Connecting the supply lines (tubing) to the CPA valve terminal Tubing
Additional pressure supply plate
Plate for supplying pressure zones which lie in the centre of the CPA valve terminal. In this plate, the compressed air is diverted from work connection
2 so that the relevant valve plates can be supplied with compressed air. The exhaust air can also be expelled via connection 4.
Tab.0/5: Product−specific terms and abbreviations
XIV
Festo P.BE−CPA−EN en 0306d
System summary
Chapter 1
Festo P.BE−CPA−EN en 0306d
1−1
1. System summary
Contents
1.
1−2
Festo P.BE−CPA−EN en 0306d
1. System summary
Contents of this chapter
Further information
This chapter provides an overview of the following on the CPA valve terminal: connection variants and components on the valve ter minal the maximum number of valve locations the identification code of the pneumatic components
Connecting, display and operating elements
Information on the electric multipin can be found in the brief description of the CPA valve terminal with multipin connec tion.
Festo P.BE−CPA−EN en 0306d
1−3
1. System summary
1.1
Overview of variants
Festo assists you in solving your automation task at the ma chine level with CPA valve terminals. The modular structure of the CPA valve terminal for the CP system enables you to adapt the CPA valve terminals optimally to your machine or system.
Due to their compact design, the CPA valve terminals can be fitted close to the actuators to be controlled. This enables short compressed air tubing to be used. System losses will therefore be minimized and the times required for pressuriz ing and exhausting the compressed air tubing will be redu ced. This is made possible by the use of very compact valves with sufficient flow, thereby helping to reduce costs.
CPA valve terminal with
CPX terminal
This CPA valve terminal is available with 2 to max. 22 single− solenoid valve locations or max. 11 double−solenoid valve locations. Maximum 22 valve coils can be controlled.
ÎÎÎÎ
ÎÎÎ ÎÎÎÎ
Î ÎÎ Î ÎÎÎÎ ÎÎÎ Î ÎÎ
ÎÎ ÎÎ ÎÎ Î ÎÎÎ Î ÎÎ
Î ÎÎ
1−4
Fig.1/1: CPA valve terminal with CPX terminal
Festo P.BE−CPA−EN en 0306d
1. System summary
Electrical connection vari ants of the CPA valve ter minal
The CPA valve terminals are available with the following electrical connections:
1
MP connection
2
IC connection
3
AS−interface connection
4
CP connection
5
AS−interface connection with inputs
1
ÎÎÎ
ÎÎÎ Î ÎÎÎ ÎÎ Î
ÎÎ Î Î Î ÎÎ Î ÎÎÎ ÎÎ
Î Î ÎÎ ÎÎ Î
2
ÎÎÎ Î Î ÎÎ
ÎÎÎ ÎÎ ÎÎÎ ÎÎ ÎÎÎ ÎÎ
Î ÎÎ Î Î Î ÎÎ ÎÎÎ Î
Î Î Î Î
5
ÎÎÎ
Î ÎÎÎ Î ÎÎ ÎÎÎ Î
ÎÎ ÎÎ ÎÎ Î ÎÎÎ Î ÎÎ
ÎÎ ÎÎ Î
4
ÎÎÎ
ÎÎÎ ÎÎÎ ÎÎ Î
ÑÑ Î Î Î ÎÎ Î ÎÎÎ ÎÎ
Î Î ÎÎ ÑÑ Î
3
ÎÎÎ
ÎÎÎ Î ÎÎ ÎÎ ÎÎÎ
Î ÎÎ Î ÎÎ Î ÎÎ ÎÎÎ Î
Î ÎÎ Î ÎÎ Î Î
Fig.1/2: Variants of the CPA valve terminal
CPA valve terminal with IC connection
This CPA valve terminal is available with 2 to maximum 22 valve locations. The electrical connection of the valve sole noid coils is made via individual connector plugs. Maximum
44 valve coils can be controlled.
Festo P.BE−CPA−EN en 0306d
1−5
1. System summary
CPA valve terminal with
MP connection
This CPA valve terminal is available with 2 to max. 22 single− solenoid valve locations or max. 11 double−solenoid valve locations. Maximum 22 valve coils can be controlled. The electrical connection of the valve solenoid coils is made cen trally via the multipin plug.
CPA valve terminal with CP connection
This CPA valve terminal is available with 2 to max. 16 single− solenoid valve locations or max. 8 double−solenoid valve locations. Maximum 16 valve coils can be controlled. Con nection to the higher−order field bus node is made via special ready−to−use CP cables.
CPA valve terminal with
AS− interface connection
This CPA valve terminal is switched onto the AS−interface bus via special AS−interface cables. It is available with the following electrical connnection variants: without additional power supply connection, type: CPA..−
IFB−ASI.
with additional power supply connection (load voltage can be switched off separately), type: CPA..−IFB−ASI−Z.
with 4 inputs and additional power supply connection
(load voltage can be switched off separately), type: CPA..−GE−ASI−4E4A−Z.
with 8 inputs and additional power supply connection
(load voltage can be switched off separately), type: CPA..−GE−ASI−8E8A−Z.
The first three above−mentioned variants (types:
CPA..−IFB−ASI. CPA..−IFB−ASI−Z and CPA..−GE−ASI−4E4A−Z) are available with 2 to max. 4 single−solenoid valve locations or max. 2 double−solenoid valve locations. Maximum 4 valve coils can be controlled.
The variant with 8 inputs (type: CPA..−GE−ASI−8E8A−Z) is avail able with 2 to max. 8 single−solenoid valve locations or max. 4 double−solenoid valve locations. Maximum 8 valve coils can be controlled.
1−6
Festo P.BE−CPA−EN en 0306d
1. System summary
1.2
Description of components
The CPA valve terminal consists of the following electric com ponents:
1 2 3 4
5
6
ÑÑÑ
Ñ Ñ Ñ ÑÑ ÑÑÑ ÑÑ
Ñ ÑÑ ÑÑ Ñ Ñ
ÑÑÑ Ñ ÑÑ Ñ
ÑÑ Ñ ÑÑÑ ÑÑ ÑÑ
ÑÑ ÑÑ Ñ
7
8
1
CPA valve terminals with AS−interface and inputs: AS−interface module
2
CPA valve terminal:
MP, CP or AS−interface sub−base
3
Adapter for electrical linking with CPX terminal or AS−interface with I/Os
4
Electric manifold sub−base (manifold sub−base EV1 occupies 1 address,
EV2 occupies 2 addresses)
5
Electric bridge with manual override actuation and LEDs
6
Sub−base
7
CPA valve terminals with CPX terminal:
CPX pneumatic interface
8
CPA valve terminals with CPX terminal or AS−interface with inputs:
Adapter for fitting the CPX pneumatic interface or the AS−interface module
Fig.1/3: Electric components on the CPA valve terminal
Festo P.BE−CPA−EN en 0306d
1−7
1. System summary
1 2
The CPA valve terminal consists of the following pneumatic components:
ÑÑÑ
ÑÑÑ Ñ Ñ ÑÑ
ÑÑ ÑÑ ÑÑÑ ÑÑ Ñ
ÑÑ Ñ
2
3
4
ÑÑÑ
Ñ ÑÑ ÑÑ Ñ ÑÑÑ Ñ
ÑÑ Ñ Ñ Ñ ÑÑ
5
1 end plate cover or large surface−mounted silencer
2 valve plates with single−solenoid or double−solenoid valves
3 right−hand end plate with supply and exhaust connections
4
Additional pressure supply plate or blanking plate
5 sub−base: with work connections with/without pressure zone separation in combination with supply plate for compressed air supply
6
Left−hand end plate with supply and exhaust connections
Fig.1/4: Pneumatic components on the CPA valve terminal
6
1−8
Festo P.BE−CPA−EN en 0306d
1. System summary
The table below shows the max. number of valve locations on the CPA valve terminal variants.
CPA valve terminal with
CPX terminal max. number of valve locations
IC con nection
MP con nection
CP con nection
AS−inter face con nection 1)
For use only with manifold sub−base
EV1 (for valve plate with one solenoid coil).
For use only with manifold sub−base
EV2 (for valve plate with two solenoid coils).
Maximum number of valve coils which can be controlled
22
11
22 44
2)
2)
22
11
22
16
8
16
4 (8)
2 (4)
4 (8)
1) Values in brackets for variant with 8 inputs type: CPA..−GE−ASI−8E8A−Z.
2) OOn CPA valve terminals with IC connection the maximum number of valve locations is limited to 22 due to the tie rod.
Tab.1/1: Maximum number of valve locations depending on the CPA valve terminal variant
Sizes of the CPA valve ter minal
All CPA valve terminal variants are available with micro valves (valve size 10 mm, CPA10) or with mini valves (valve size 14 mm, CPA14). Mixed fitting with both grid dimensions is not possible on a CPA valve terminal.
Festo P.BE−CPA−EN en 0306d
1−9
1. System summary
On the basis of the identification code, you can ascertain the plates with which your CPA valve terminal is fitted. This code is printed on the front of the valve plate.
Ident. code
E
G
H
B
D
N
T
Y
J
K
M
Pneumatic components
Valve plate, 5/3−way, mid−position pressurized
Additional supply plate, for supplying compressed air to three or more pressure zones
Valve plate, 5/3−way, mid−position exhausted
Valve plate, 5/3−way, mid−position blocked
Valve plate, two 3/2−way, control side 12 in basic position open, control side 14 in basic position closed
Valve plate, 5/2−way, double−solenoid
Valve plate, two 3/2−way, single solenoid, basic position blocked
Valve plate, 5/2−way, single−solenoid
Valve plate, two 3/2−way, single solenoid, basic position open
Sub−base for pressure zone separation, compressed air channel (1) blocked
Valve plate, 5/2−way, single−solenoid on two−coil valve location
Tab.1/2: Identification codes of the pneumatic components
Further information on the valve plates can be found in ap pendix A.
1−10
Festo P.BE−CPA−EN en 0306d
1. System summary
CPA valve terminal with IC connection
1
The following pneumatic connecting and operating elements can be found on the CPA valve terminal:
CPA valve terminal with MP, CP or AS−interface connection or with CPX terminal
1 2
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎ
ÎÎ Î ÎÎÎÎÎ ÎÎ ÎÎ
ÎÎÎ ÎÎ ÎÎ Î ÎÎÎÎ ÎÎ ÎÎÎÎÎ
ÎÎÎÎ Î ÎÎ ÎÎ Î ÎÎ Î
ÎÎ ÎÎ ÎÎÎÎ Î ÎÎ ÎÎ
Î ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎ ÎÎ Î
ÎÎ ÎÎ ÎÎÎÎÎ ÎÎ Î
ÎÎ Î ÎÎ ÎÎ ÎÎ Î ÎÎÎÎÎ Î
ÎÎ Î Î ÎÎ ÎÎ
Î ÎÎ
5 4 3 5 4
1
Manual override (locking or non−locking depending on pilot solenoid)
2
Clip (only with non−locking manual override)
3
Supply connections (1, 12/14) and exhaust connection (3/5) on the right−hand end plate
4
Work connections (2, 4), per valve plate
5
Supply connection (1) and exhaust connections (3/5, 82/84) on the left−hand end plate
Fig.1/5: Pneumatic connecting and operating elements on the CPA valve terminal
3
Festo P.BE−CPA−EN en 0306d
1−11
1. System summary
1−12
The following electrical connecting and display elements can be found on the CPA valve terminal with IC connection:
1
5
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎ
ÎÎÎÎÎ Î ÎÎ ÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎ
ÎÎ ÎÎ ÎÎÎÎÎÎ ÎÎ Î Î ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎ ÎÎ ÎÎÎÎÎÎ Î ÎÎ ÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ
2
3
4
1 ready−to−use cable with socket for connecting a valve solenoid coil
2
Clip with inscription field (per cable socket)
3 per cable socket yellow LED, shows signal states of the pilot solenoids
4
Connecting lugs of pilot solenoid coil 12
5
Connecting lugs of pilot solenoid coil 14
Fig.1/6: Electrical connecting and display elements of the
CPA valve terminal with IC connection
Festo P.BE−CPA−EN en 0306d
1. System summary
Festo P.BE−CPA−EN en 0306d
The following electrical connecting and display elements can be found on the CPA valve terminal with MP connection:
1 2
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎ ÎÎ
ÎÎÎÎÎ ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎÎÎÎ Î ÎÎ ÎÎ
ÎÎ ÎÎ Î ÎÎ ÎÎÎÎÎ Î ÎÎ ÎÎ
ÎÎ ÎÎ Î Î ÎÎ
ÎÎ ÎÎ Î
3
1
Inscription clips
2
Yellow LEDs, signal status display of the pilot solenoids
3
SUB−D multipin plug (25−pin)
Fig.1/7: Electrical connecting and display elements of the
CPA valve terminal with MP connection
1−13
1. System summary
1−14
The following electrical connecting and display elements can be found on the CPA valve terminal with CP connection:
1 2 3
6
5
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎ ÎÎ ÎÎ
ÎÎÎÎÎ ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎÎÎÎ ÑÑ ÎÎ Î
ÎÎ Î ÎÎÎÎÎ ÑÑ ÎÎ ÎÎ ÎÎ ÎÎ
ÑÑ ÎÎ ÎÎ ÎÎ Î
ÎÎ ÎÎ
4
1
Green LED, status display of the CP connection
2
Incoming CP cable
3
Yellow LEDs, signal status display of the pilot solenoids
4
Continuing CP cable
5
Earth/ground connection
6
Inscription clips
Fig.1/8: Electrical connecting and display elements of the
CPA valve terminal with CP connection
Festo P.BE−CPA−EN en 0306d
1. System summary
Festo P.BE−CPA−EN en 0306d
The following electrical connecting and display elements can be found on the CPA valve terminal with AS−interface connec tion:
1 2 3
8
7
6
5
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎ ÎÎÎÎÎ ÎÎÎÎÎÎ
Î ÎÎ ÎÎÎ ÎÎÎÎÎ ÎÎ ÎÎ ÎÎÎÎÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎÎ ÎÎ ÎÎ ÎÎÎÎÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎ
4
1
AS−interface cable cap
2
Inscription clips for the valve plates
3
Yellow LEDs, signal status display of the pilot solenoids
4
Inscription clips for the AS−interface connection
5
AS−interface bus socket with yellow bus cable
6
Earth/ground connection
7
Green LED, status display of the CP connection
8
Cable socket for additional supply with black additional supply cable (optional)
Fig.1/9: Electrical connecting and display elements of the
CPA valve terminal with AS−interface connection
1−15
1. System summary
2
3
4
5
6
1
The following electrical connecting and display elements can be found on the CPA valve terminal with AS−interface connec tion:
7
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎ ÎÎÎÎÎ Î ÎÎ
ÎÎ Î ÎÎÎÎÎ ÎÎ ÎÎ Î ÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎ Î ÎÎÎÎÎ Î
ÎÎ Î Î ÎÎ
Î ÎÎ
3
8
9
7
1
Sub−base for inputs with viewing window for LEDs
2
AS−interface LEDs:
ASI LED (green)
Fault LED (red)
AUX/PWR LED (green)
3
Status LEDs:
Inputs (green)
Valves (yellow)
4
Addressing socket
5
M12 connection AS−interface bus and additional supply
6
Flat cable connections AS−interface:
Bus: Bus connection (yellow cable)
24V DC: Additional supply
(black cable)
7
Inscription fields for addresses
8
Cover
9
DIL switch (under cover)
Fig.1/10: Electrical connecting and display elements of the CPA valve terminal with AS−in terface connection and inputs
1−16
Festo P.BE−CPA−EN en 0306d
1. System summary
The following electrical connecting and display elements can be found on the CPA valve terminal with CPX terminal:
1 2 3 4
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎÎÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎ ÎÎ ÎÎ ÎÎ Î ÎÎÎÎÎ
ÎÎ ÎÎ ÎÎ ÎÎ Î ÎÎ ÎÎ
Î ÎÎ ÎÎ
Festo P.BE−CPA−EN en 0306d
1
Red LED, fault display of the pneumatic interface
2
DIL switch for setting the valve address number
3
Inscription clips
4
Yellow LED, signal status display of the pilot solenoids
Fig.1/11: Electrical connecting and display elements of the
CPA valve terminal with CPX terminal
Detailed information on the CPX pneumatic interface can be found in the supplementary description CPX I/O modules
(P.BE−CPX−EA−..).
1−17
1. System summary
1−18
Festo P.BE−CPA−EN en 0306d
Fitting
Chapter 2
Festo P.BE−CPA−EN en 0306d
2−1
2. Fitting
Contents
2.
Fitting onto a wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting onto a hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2−2
Festo P.BE−CPA−EN en 0306d
2. Fitting
Contents of this chapter
Further information
This chapter describes how to fit and remove the complete
CPA valve terminal.
Special information on replacing or adding pneumatic compo nents can be found in chapter 5.
CPA valve terminal with CPX terminal
Information on fitting the CPA valve terminal with CPX terminal can be found in the manual for the CPX system.
Information on fitting and removing the module elec tronics and sub−bases can be found in the manual for the
CPX I/O modules and in the information supplied with the product in the case of modules and components or dered at a later stage.
Festo P.BE−CPA−EN en 0306d
2−3
2. Fitting
2.1
Fitting variants
Warning
Sudden unexpected movements of the connected actua tors and uncontrollable movements of loose tubing can cause injury to human beings and damage to property.
Before carrying out installation and/or maintenance work, switch off the following:
the compressed air supply
the operating and load voltage supplies
Please note
Handle all modules and components of the CPA valve ter minal with great care. Observe especially the following:
the specified torques must be observed
Electrostatically sensitive components
Do not touch any contact surfaces.
The CPA valve terminal has been prepared for inclusion in a system or machine in one of the following ways:
Fitting onto a wall
Fitting onto a hat rail
Please note
Mount the CPA valve terminal so that there is sufficient space for heat dissipation and so that the maximum limits for temperatures can be observed (see Technical Specifica tions).
2−4
Festo P.BE−CPA−EN en 0306d
2. Fitting
2.1.1
Fitting onto a wall
Fitting
The method of fitting the CPA valve terminal with CPX ter minal onto a wall is described in system manual P.BE−CPX−
SYS−...
Proceed as follows:
1. Make sure that the fastening surface can support the CPA valve terminal (weights see appendix A).
2. Make sure that there is sufficient space for connecting the supply lines and cables.
3. Drill four mounting holes in the fastening surface (dis tance between holes see diagrams) and fasten the CPA valve terminal with M4 screws (tightening torque 0.8 Nm).
4
4
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓÓ
ÓÓÓ
2 3
ÓÓ
ÓÓ
2
1
4
CPA10 terminal
1
66.3 mm
2
23 mm
3
10.6 mm x number of sub−bases
4
4 holes for fitting onto a wall
Fig.2/1: Fastening holes, CPA valve terminal
CPA14 terminal
1
76.1 mm
2
26 mm
3
14.6 mm x number of sub−bases
4
4 holes for fitting onto a wall
Festo P.BE−CPA−EN en 0306d
2−5
2. Fitting
1
1
Ó
Ó
Ó
Ó
1
ÓÓ
1
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
2
11 5
8,5 114,25
*) All specifications in millimetres
4
CPA10−GE−ASI−...−Z
1
Holes for wall fitting
2
66.3 mm
3
113.1 mm
4
46 mm + (10.6 mm x number of sub−bases)
CPA14−GE−ASI−...−Z
1
Holes for wall fitting
2
76.1 mm
3
122 mm
4
52 mm + (14.6 mm x number of sub−bases)
Fig.2/2: Holes for wall fitting, CPA valve terminal with AS−interface and inputs
3
2−6
Festo P.BE−CPA−EN en 0306d
2. Fitting
Dismantling
CPA variant
ÓÓ Ó
ÓÓ Ó
ÓÓ Ó
Proceed as follows:
1. Secure a hanging−mounted CPA valve terminal against falling down before you loosen it from the fastening sur face.
2. Loosen the fastening screws as shown in the diagram below and remove the CPA valve terminal from the fastening surface..
Fastening
CPA valve terminal:
Two screws each on the left−hand and right− hand end plates.
Ó
Ó
Ó
Ó
Ó
Ó
CPA valve terminals with AS−interface and inputs:
One screw on the left−hand end plate and two screws on the right−hand end plate of the CPA pneumatics.
Two screws each on the left−hand and right− hand sides of the AS−interface module.
ÓÓ Ó
ÓÓ Ó
ÓÓ Ó
CPA valve terminal with CPX terminal
One screw on the left−hand end plate and two screws on the right−hand end plate of the CPA valve terminal.
Two screws on the CPX pneumatic interface.
Two screws on the left−hand end plate of the
CPX terminal.
Tab.2/1: Removing the CPA valve terminal from a wall
Festo P.BE−CPA−EN en 0306d
2−7
2. Fitting
2.1.2
Fitting onto a hat rail
Please note
Hat rails which are fitted with CPA14 valve terminals can break if they are subjected to vibration in excess of the following values:
0.15 mm path at 10−58 Hz;
2 g acceleration at 58−150 Hz,
This can cause damage to your CPA valve terminal, system or machine.
· Use the wall fitting for CPA14 valve terminals.
Fitting the CPA valve terminal with CPX terminal onto a hat rail is described in system manual P.BE−CPX−SYS−...
In order to fit the CPA valve terminal onto a hat rail, you will require the appropriate mounting kit (see table).
CPA valve terminal ...
with CPX terminal
with AS−interface connection and inputs
with IC connection
with MP connection
with CP connection
with AS−interface connection
Mounting kit
CPX10/14−BG−NRH
CPA−BG−NRH
Scope of delivery
Three M4 x 10 screws
Three clamping elements
Two M4 x 10 screws
Two clamping elements
Tab.2/2: Hat rail mounting kits
Fitting Proceed as follows:
1. Make sure that the fastening surface can support the CPA valve terminal (weights see appendix A).
2. Fit the hat rail hat rail (support rail EN 50022 − 35x7.5; width 35 mm, height 7.5 mm). Make sure there is suffi cient space for connecting the supply cables and tubing.
2−8
Festo P.BE−CPA−EN en 0306d
2. Fitting
3. Fasten the hat rail to the fastening surface approximately every 100 mm.
4. Fit the hat rail clamping units to the end plates of the CPA valve terminal (see diagram).
5. Hang the CPA valve terminal onto the hat rail (see arrow
A).
6. Swing the CPA valve terminal onto the hat rail (see arrow
B). Make sure that the clamping element lies horizontally to the hat rail.
7. Secure the CPA valve terminal on both sides against slid ing down by tightening the locking screw with 1.3 Nm.
1
Hat rail
2
Self−cutting
M4x10 screw of the hat rail clamping unit
3
Clamping element for hat rail clamping unit
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
Fig.2/3: Fitting the CPA valve terminal onto a hat rail
ÔÔ
ÔÔ
ÔÔ
ÔÔ
ÔÔ
ÖÖ ÔÔ
ÖÖ ÔÔ
ÔÔ
ÔÔ ÔÔ ÔÔ ÔÔ ÔÔ
ÔÔ
ÔÔ
ÔÔ
ÔÔ
(A)
1
(B)
2
3
Festo P.BE−CPA−EN en 0306d
2−9
2. Fitting
Dismantling Proceed as follows:
1. Loosen the locking screw of the hat rail clamping unit on the left−hand and right−hand end plates(see diagram).
Make sure that the clamping element lies horizontally to the hat rail.
2. Swing the CPA valve terminal forwards from the hat rail
(see diagram, arrow B).
3. Lift the CPA valve terminal out of the hat rail (see diagram, arrow A).
1
Hat rail
2
Clamping element for hat rail clamping unit
3
Locking screw for hat rail clamping unit
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÒÒÒÒÒ
ÔÔ
ÔÔ
ÔÔ
ÔÔ
ÖÖ ÔÔ
ÖÖ ÔÔ
Ô ÔÔ
Ô ÔÔ Ô Ô Ô
ÔÔ
ÔÔ
ÔÔ
A
B
1
2
3
Fig.2/4: Dismantling the CPA valve terminal
2−10
Festo P.BE−CPA−EN en 0306d
Installation
Chapter 3
Festo P.BE−CPA−EN en 0306d
3−1
3. Installation
Contents
3.
Operation with non−lubricated compressed air . . . . . . . . . . . . . . . .
Operation with lubricated compressed air . . . . . . . . . . . . . . . . . . . .
Laying the tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the CPA valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pilot control of the valve solenoid coils (auxiliary pilot air) . . . . . . .
CPA valve terminal with pressure−zone separation . . . . . . . . . . . . .
Vacuum/low pressure operation . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the pneumatic tubing . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the electric cables
Address assignment of the valves
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3−2
Festo P.BE−CPA−EN en 0306d
3. Installation
Contents of this chapter
Further information
This chapter describes the tubing and cabling of the CPA valve terminal. The following belong here: general instructions on preparing the compressed air and the tubing instructions on operating with internal and external auxili ary pilot air instructions on operating CPA valve terminals with pres sure−zone separation fitting the pin−type inserts and QS screw connectors connecting the power supply earthing the CPA valve terminal with CP or AS−interface connection (not with CPA valve terminals with AS−interface and inputs) address assignment of the valves
Information on the power supply to the CPA valve terminal with CPX terminal can be found in the CPX system manual.
Instructions on connecting the electric components on the
CPA valve terminal with multipin or AS−interface connection can be found in the information supplied with the product.
Instructions on connecting the CPA valve terminal with CP connection can be found in the CPsystem manual.
Instructions on connecting the CPA valve terminal with CPX terminal can be found in the CPX system manual.
Festo P.BE−CPA−EN en 0306d
3−3
3. Installation
3.1
Preparing the compressed air
Caution
Non−filtered or incorrectly lubricated compressed air will reduce the service life of the valve terminal.
3.1.1 Operation with non−lubricated compressed air
Caution
Excessive residual oil content in the compressed air will reduce the service life of the valve terminal.
If bio oils are used (oils based on synthetic ester or na tive ester e.g. rape oil methylic ester), the residual oil content must not exceed 0.1 mg/m 3 (see ISO 8573−1 class 2).
If mineral oils are used (e.g. HLP oils as per
DIN 51524 parts 1 to 3) or corresponding oils on a poly alphaolefine basis (PAO), the residual oil content must not exceed 5 mg/m 3 (see ISO 8573−1 class 4).
In this way you will avoid malfunctioning of the valves.
A high residual oil content is not permitted, irrespective of the compressor oil, as otherwise the basic lubrication will be washed out in the course of time.
3.1.2 Operation with lubricated compressed air
If possible, operate your system with non−lubricated com pressed air. This will not pollute the environment. Pneumatic valves and actuators from Festo are designed so that, if used as designated, they will not require additional lubrication and will still achieve a long service life.
3−4
Festo P.BE−CPA−EN en 0306d
3. Installation
Lubricator setting
Check the setting
Festo P.BE−CPA−EN en 0306d
Caution
Operation with lubricated compressed air will lead to washing out" of the service life lubrication required for non−lubricated operation.
Note the following if lubricated compressed air has to be used.
The compressed air prepared with the compressor must correspond to the quality of non−lubricated compressed air. If possible, do not operate the complete system with lubricated compressed air. If possible, always fit the lubricator directly in front of the consuming actuator.
Caution
Incorrect additional oil and excessive residual oil content in the compressed air will reduce the service life of the valve terminal.
Use special oil OFSW−32 from Festo or the alternative oil listed in the Festo catalogue (corresponding to DIN
51524−HLP32, basic viscosity 32 CST at 40 °C).
The additional lubrication must not exceed 25 mg/m 3
(ISO 8573−1 class 5).
Make sure that the lubricator is set correctly (see follow ing section)
In this way you will avoid malfunctioning of the valves.
With machine running (typical operating status) 0.2 to max. 1 drop/min. or 0.5 to 5 drops/1000 l air.
The lubricator setting can be checked as follows.
Proceed as follows:
· Check the service units as regards condensate and lubri cator setting twice a week.
1. Ascertain the actuator which is furthest from the lubrica tor.
3−5
3. Installation
2. Ascertain the valve terminal which controls this actuator.
3. Remove the silencer on connection 3/5, if fitted.
4. Hold a piece of white cardbord 10 cm in front of the ex haust port.
5. Let the system operate for some time.
The cardboard may only assume a slightly yellow col ouring. If oil drops out, this clearly indicates over−lu brication.
A further indication of over−lubrication is the colouring or status of the exhaust silencer. A clearly yellow colouring of the filter element or oil drops on the silencer indicate a too high lubricator setting.
3−6
Festo P.BE−CPA−EN en 0306d
3. Installation
3.2
General connection methods
Warning
Sudden unexpected movements of the connected actua tors and uncontrollable movements of loose tubing can cause injury to human beings and damage to property.
Before carrying out installation and/or maintenance work, switch off the following:
the compressed air supply
the operating and load voltage supplies
Observe the following:
The components of the valve terminals contain electrostati cally sensitive elements. The components may be damaged if the contact surfaces of the plug connectors are touched and if the regulations for handling electrostatically sensitive el ements are not observed.
3.2.1
Laying the tubing
Connecting
If angled connectors or multiple distributors are used, the air flow will usually be reduced.
Proceed as follows:
1. Push the tubing as far as possible into the tubing connec tion of the pin−type 1
2. If necessary, pull the locking ring 2 over the tubing con nection.
3. For reasons of clarity bundle the tubing together with:
tubing straps or
multiple hose holders
Festo P.BE−CPA−EN en 0306d
3−7
3. Installation
1
Pin−type inserts
2
Locking ring
Fig.3/1: Fitting the tubing
Disconnecting
1
Proceed as follows:
2
Warning
When disconnected, pneumatic tubing still under pressure may perform sudden uncontrolled movements, thereby causing injury to human beings. Carry out the following steps before you loosen the pneumatic tubing on the valve terminal:
· Switch off the compressed air supply.
· Make sure that all pneumatic tubing is pressureless.
· Exhaust all actuators which are controlled by valves which are blocked in the basic or mid−positions.
Please note
In order to loosen the tubing in the pin types, use loosen ing fork type QSO from Festo or a screwdriver.
When using a screwdriver:
· Press down the locking ring only with the broad side of the blade.
1. Press down the locking ring 2 of the pin−type 1 .
2. Pull out the tubing.
3. Non−used connections must be sealed with blanking plugs 3 .
3−8
Festo P.BE−CPA−EN en 0306d
3. Installation
1
Pin−type insert
2
Locking ring
3
Blanking plugs
1
2
3
Fig.3/2: Disconnecting the tubing
3.3
Connecting the CPA valve terminal
On sub−bases fitted with reserve plates, seal work connec tions (2 or 4) with blanking plugs to protect the valve terminal from dirt.
In order to guarantee the optimum efficiency of the CPA valve terminal, we recommend that the supply air tubing and the exhaust air tubing be connected on both sides in the follow ing cases: when large volume cylinders are operated at high speed when several valves are switched to flow simultaneously.
Festo P.BE−CPA−EN en 0306d
3−9
3. Installation
3.3.1
Pilot control of the valve solenoid coils (auxiliary pilot air)
Caution
Operate the CPA valve terminal if possible with non−lu bricated auxiliary pilot air (connections 12/14). If lubri cated air must be used, observe the instructions in the section Preparing the compressed air".
In the case of CPA valve terminals with internally branched auxiliary pilot air, the above−mentioned in struction also applies to the supply air (connection 1).
In the case of CPA valve terminals with two pressure zones and internally branched auxiliary pilot air:
Due to the auxiliary pilot air branched internally in the right−hand end plate, the pressure in the right−hand pressure zone must be 3 − 8 bar.
Pilot control of the valve solenoid coils can be undertaken with internal or external auxiliary pilot air, depending on the right−hand end plate. You can ascertain the pilot control vari ant for which your CPA valve terminal is equipped by means of the type designation on the right−hand end plate (see table).
CPA valve terminal with auxiliary pilot air with internal pilot air
Right−hand end plates type
CPA..−EPR−S
CPA..−EPR
Tab.3/1: End plates for external or internal pilot air
Internal auxiliary pilot air If the operating pressure of your CPA valve terminal lies be tween 3 ... 8 bar, you can operate the pilot control of the valve solenoid coils with internally branched auxiliary pilot air. The auxiliary pilot air in the right−hand end plate is branched here from supply channel 1.
3−10
Festo P.BE−CPA−EN en 0306d
3. Installation
Please note
· Internal auxiliary pilot for all valve solenoid coils is branched centrally from supply connection 1 in the right− hand end plate. This also applies when the CPA valve terminal is operated with several pressure zones (see
If the CPA valve terminal with internal auxiliary pilot air is used, connection 12/14 must be sealed with a blanking plug
(see diagram).
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓÓÓÓ Ó ÓÓ
ÓÓÓÓÓ ÓÓ Ó ÓÓ
Ó ÓÓ ÓÓÓÓÓ Ó ÓÓ ÓÓ
ÓÓ ÓÓ Ó ÓÓ ÓÓÓÓÓ Ó
ÓÓ ÓÓ Ó Ó
Ó ÓÓ
1
1
Connection 12/14
Fig.3/3: Internal auxiliary pilot air
External auxiliary pilot air If the operating pressure lies below 3 bar or above 8 bar, you must operate the pilot control of the valve solenoid coils with external auxiliary pilot air. The auxiliary pilot air is supplied here externally via pilot connection 12/14.
Festo P.BE−CPA−EN en 0306d
3−11
3. Installation
Please note
· If you use closed−loop controlled auxiliary pilot air
(3 ... 8 bar), reliable, faultless operation of the CPA valve terminal is then possible, even with fluctuating operat ing pressure.
· The external auxiliary pilot air for all valve solenoid coils is supplied centrally via pilot connection 12/14 on the right−hand end plate. This also applies when the CPA valve terminal is operated with several pressure zones
· If your CPA valve terminal is fitted with valve plates with
Ident. code H, K or N (3/2−way valves), the external aux iliary pilot air must be set according to the operating pressure with which these valves are operated (see dia grams).
1
Pilot pressure of the external auxiliary pilot air at connection
12/14 [bar]
2
Operating pressure at connection 1
[bar]
1
3
Start−up pressure of the pilot control
2
Fig.3/4: Diagram for CPA10: External auxiliary pilot air depending on operating pres sure for valve plates with Ident. code N, K and H
3
3−12
Festo P.BE−CPA−EN en 0306d
3. Installation
1
Pilot pressure of the external auxiliary pilot air at connection
12/14 [bar]
2
Operating pressure at connection 1
[bar]
1
3
Start−up pressure of the pilot control
2
Fig.3/5: Diagram for CPA14: External auxiliary pilot air depending on operating pres sure for valve plates with Ident. code N, K and H
3
3.3.2
CPA valve terminal with pressure−zone separation
The CPA valve terminal can be equipped with the following number of pressure zones depending on the connection vari ant:
Electrical connection variant
IC, MP or
CPX
Pressure zones 1 ... 12
CP
1 ... 9
AS−interface
1 ... 3
Tab.3/2: Maximum number of pressure zones
The pressure zones are implemented with special sub−bases which block the compressed air channel (1).
Festo P.BE−CPA−EN en 0306d
3−13
3. Installation
3−14
Please note
Note the following in the case of CPA valve terminals which are operated with internal auxiliary pilot air and which have two or more pressure zones:
· The auxiliary pilot for all valve solenoid coils is branched centrally from supply connection 1 in the right− hand end
· The pressure zone on the outside right (supplied via connecton 1 on the right−hand end plate) must be oper ated with a pressure between 3 ... 8 bar.
Please note
Valve terminals on sub−bases with pressure zone separ ation are supplied with the compressed air which is sup
plied on the left−hand side of the sub−bases (see Fig.3/6).
You can ascertain the number of pressure zones on your CPA valve terminal by the identification on the special sub−base
(grey dot above work connection 2).
CPA valve terminal with 2 pressure zones
These CPA valve terminals have a sub−base with pressure zone separation. The left−hand pressure zone is supplied with compressed air via connection 1 on the left−hand end plate; the right−hand pressure zone is supplied via connection 1 on the right−hand end plate.
CPA valve terminals with more than 2 pressure zones
For each pressure zone you will require a sub−base with pres sure zone separation. The pressure zones on the outside are supplied with compressed air via connection 1 on the end plates; the remaining pressure zones are supplied via con nection 2 on the sub−bases which are fitted with additional pressure supply plates (see diagram). In order to expel the
Festo P.BE−CPA−EN en 0306d
3. Installation exhaust air, you can fit a silencer to connection 4 on these sub−bases. If connection 4 is not used, it must be sealed with a blanking plug.
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ Ó
Ó ÓÓÓ ÓÓÓ
Ó ÖÖÖÖÖÖÖÖÖÖ
ÖÖÖÖÖÖÖÖÖÖÖ ÎÎÎÎ ÎÎ ÎÎÎÎ ÖÖÖÖÖÖÖÖÖÖ
ÖÖ ÖÖÖÖ ÖÖÖÖ
3 4 5
1
2
1
Additional pressure supply plate
2
Identification of the sub−bases with pressure zone separation (grey dot)
3
Pressure zone 1 (compressed air supply via connection 1 on the left−hand end plate)
4
Pressure zone 2 (compressed air supply via connection 2 on the sub−base with additional pressure supply plate)
5
Pressure zone 3 (compressed air supply via connection 1 on the right−hand end plate)
Fig.3/6: Example: Pressure zone separation and external pilot air
Festo P.BE−CPA−EN en 0306d
3−15
3. Installation
3.3.3
Vacuum/low pressure operation
The CPA valve terminal can be operated with vacuum or low pressure > −0.9 ... < 3 bar under the following conditions:
Please note
Valve plates with 3/2−way valves (Ident. code N, K or H) are not suitable for operation with vacuum or low pressure.
· Operate these valves in a separate pressure zone.
· The operating pressure for this pressure zone must be
set according to the diagram in Fig.3/4 (CPA10) or
The following conditions must be fulfilled, in order that you can operate your CPA valve terminal at supply connection 1 with vacuum or low pressure between 0.9 ... 3 bar:
Pilot control of the valve solenoid coils must be operated with closed−loop controlled external auxiliary pilot air.
The valve terminal must be fitted with the following valve plates:
5/2−way valve, single−solenoid (Ident. code M)
5/2−way valve, double−solenoid (Ident. code J)
5/3−way valves pressurized in mid−position (Ident.
code B), blocked (Ident. code G) or exhausted (Ident.
code E)
3.3.4
Connecting the pneumatic tubing
Please note
· Seal connections which are not required for the function ing of the CPA valve terminal with blanking plugs.
3−16
Festo P.BE−CPA−EN en 0306d
3. Installation
Fit the screw connectors as described below. Then lay the tubing.
Please note
On CPA valve terminals with large surface−mounted si lencers, the exhaust air at 3/5 and 82/84 is expelled via the large surface mounted silencer. Connection 82/84 on the left−hand end plate is then sealed with a blanking plug.
ÓÓÓÓÓÓ
ÓÓÓÓÓÓ
ÓÓÓÓÓÓ
ÓÓÓÓÓÓ ÓÓÓÓÓÓ ÓÓ ÓÓ
ÓÓÓÓÓÓ ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ ÓÓÓÓÓÓ ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ ÓÓ ÓÓ ÓÓÓÓÓÓ ÓÓ
ÓÓ ÓÓ ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ
3/5
12/14
3/5 82/84 1
Fig.3/7: Pneumatic connections on the CPA valve terminal
1
Festo P.BE−CPA−EN en 0306d
3−17
3. Installation
Proceed as follows:
1. Refer to the following table for selecting the correct pin− type inserts:
Connection code ISO
5599
1
3/5
2 or 4
12/14
82/84
CPA14 ter minal:
Values in brackets for
12/14 or
82/84
Tubing CPA10 terminal
Pin−type size
Compressed air/ vacuum, exhaust
Work air/ vacuum, additional pressure sup ply exhaust pilot air
Tubing connection:
QSP14−6
QSP14−8
QSP14−1/4−U
QSP14−5/16−U
Blanking plugs:
QSP14−PTB
Tubing connection:
QSP10−4
QSP10−6
QSP10−5/32−U
QSP10−3/16−U
Blanking plugs:
QSP10−PTB
Silencers:
UC−QS−6H
UC−QS−..H
CPA14 terminal
Pin−type size
Tubing connection:
QSP18−8
QSP18−10
QSP18−5/16−U
QSP18−3/8−U
Blanking plugs:
QSP18−PTB
Tubing connection:
QSP14−6 (QSP10−4)
QSP14−8 (QSP10−6)
QSP14−1/4−U (QSP10−5/32−U)
QSP14−5/16−U(QSP10−3/16−U)
Blanking plugs:
QSP14−PTB (QSP10−PTB)
Tab.3/3: Pin−type inserts
2. Check whether the seal of the pin type is greased. If necessary grease the seal with Festo F2 grease.
3. Press the pin−type inserts into the connecting holes.
4. Make sure that the pin−type inserts are seated as far as possible in the holes. Measure the distance between the connecting plane and the locking ring of the pin−type (see diagram).
3−18
Festo P.BE−CPA−EN en 0306d
3. Installation
1
ÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓ
ÓÓÓÓÓÓÓÓÓÓ
1
5.5 mm (CPA10) or 6.5 mm (CPA14)
Fig.3/8: Checking the pin−type fitting
Festo P.BE−CPA−EN en 0306d
3−19
3. Installation
1
Clamping springs
2
Pin−type inserts
5. Fasten the pin−type inserts with the clamping springs (see diagram).
2 1
ÓÓ
ÓÓ ÓÓÓÓÓ
ÓÓ ÓÓÓÓÓ
ÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ
Ó
Ó
Ó
Ó
Fig.3/9: Fitting and fastening the pin−type inserts
6. Fit the tubing as shown in Fig.3/1.
3−20
Festo P.BE−CPA−EN en 0306d
3. Installation
1
CPA valve terminal 1
2 common 3/5
3 central 82/84
4 central 3/5
5
CPA valve terminal 2
6 common 82/84
Observe the following instructions on installing the pneuma tic components. Only then can you guarantee faultless oper ation.
Please note
In the case of several systems with centrally ducted ex haust:
· Use non−return valves in the common exhaust lines 3/5 or 82/84, in order to avoid impairment of function due to back pressures.
1 3 4
2
5
6 2
6
2
Fig.3/10: Common lines with non−return valves
Festo P.BE−CPA−EN en 0306d
3−21
3. Installation
3.3.5
Connecting the electric cables
Warning
Use only power units which guarantee reliable isolation of the operating voltages as per IEC 742/EN 60742/VDE 0551 with at least 4 kV isolation resistance (Protected Extra Low
Voltage PELV). Switch power packs are permitted, provid ing they guarantee reliable isolation in accordance with EN
60950/VDE 0805.
Note:By the use of PELV power units, protection against elec tric shock (protection against direct and indirect contact) is guaranteed with Festo valve terminals in accordance with EN
60204−1 / IEC 204. Safety transformers with the adjacent symbol must be used for supplying PELV networks. The valve terminals must be earthed to ensure that they function cor rectly (e.g. EMC).
Please note
Check your EMERGENCY STOP circuit in order to ascertain the measures necessary for switching your machine/sys tem into a safe state in the event of an EMERGENCY STOP
(e.g. switching off the load voltage, compressed air supply, etc.).
CPA valve terminal with CPX terminal
Instructions on connecting the electric components and on earthing the valve terminal can be found in the manual for the
CPX system, chapter 3.
3−22
Festo P.BE−CPA−EN en 0306d
3. Installation
Festo P.BE−CPA−EN en 0306d
CPA valve terminal with CP connection
Instructions on connecting the electric components, on the connecting cables and power consumption can be found in the manual CP system, installation and commissioning," chapter 3.
CPA valve terminal with MP or AS−interface connection
Instructions on the electrical connections can be found in the information supplied with the product.
CPA valve terminal with IC connection
With this variant of the CPA valve terminal, each valve sole noid coil is connected separately.
Use the connecting socket type KMYZ−7−24−...−LED from Festo for connecting the valve solenoid coils. The holding current reduction for the valve solenoid coil and an LED are built into the transparent plug of this connecting socket. This LED indi cates the switching status of the valve solenoid coils.
Please note
If the CPA valve terminal with IC connection is used at maximum operating temperature and 100% ED, it must be operated with current reduction. Use here the connecting socket type KMYZ−7−24−...−LED.
Connect the valve solenoid coils as follows:
1. Insert the socket into the connecting lug of the relevant pilot control solenoid or intermediate plug. The socket can be turned 180 0 . Make sure that the centring bolt grips between the connecting lugs in the hole of the socket (see diagram).
2. Tighten the socket with the locking screw with 0.2 Nm.
3−23
3. Installation
1
Connecting socket
2
Connecting lug of the valve solenoid
ÓÓÓÓÓ
ÓÓÓÓÓ ÓÓ
ÓÓÓÓÓ Ó ÓÓ ÓÓ ÓÓ
Ó ÓÓ ÓÓ ÓÓ ÓÓ ÓÓÓÓÓ ÓÓÓÓÓ
ÓÓÓÓÓ Ó ÓÓ ÓÓ Ó ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ ÓÓ ÓÓ ÓÓÓÓÓ Ó ÓÓ ÓÓ
Ó ÓÓ ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ
1
2
Fig.3/11: Fitting the individual connecting sockets
Earth the CPA valve terminal with CP or AS−interface connection
It is not necessary to earth the CPA valve terminal with AS−in terface and inputs .
Please note
Earth your CPA valve terminal.
· Connect the earth connection on the electric sub−base
(see diagram) with low impedance (short cable with large cross−sectional area) to the earth potential.
You can thereby avoid faults due to electromagnetic in fluences and ensure electromagnetic compatibility in ac cordance with EMC guidelines.
3−24
Festo P.BE−CPA−EN en 0306d
3. Installation
1
ÓÓÓÓ Ó
ÓÓÓÓ Ó ÓÓÓÓ ÓÓ Ó
Ó Ô ÓÓÓÓ
ÓÓÓÓ
ÓÓÓÓ
Ó Ó ÓÓÓÓ Ô ÓÓ ÓÓ
ÓÓ Ó
ÓÓ Ó
Ô ÓÓ ÓÓ Ó Ó
ÓÓ ÓÓ
1
Earth/ground connection
Fig.3/12: Earthing the CPA valve terminal with CP connection
Festo P.BE−CPA−EN en 0306d
3−25
3. Installation
3.4
Address assignment of the valves
CPA valve terminal with MP, CP, AS−interface connection or
CPX terminal
In the case of the addressing of the CPA valve terminal with
AS−interface and inputs, note also the supplementary instruc tions in the information supplied with the product.
Addresses must be assigned in ascending order without gaps.
A valve location occupies one address (CPA..−EV1) or two addresses (CPA..−EV2), depending on the manifold sub− base.
By means of the identification on the manifold sub−base
(see diagram), you can ascertain the manifold sub−bases with which your CPA valve terminal is equipped.
ÓÓÓÓÓ ÓÓ
ÓÓ ÓÓ ÓÓÓÓÓ ÓÓ Ó
ÓÓÓÓÓ ÓÓ Ó ÓÓ ÓÓ ÓÓ ÓÓÓÓÓ
Ó Ó ÓÓÓÓÓ ÓÓ Ó ÓÓ ÓÓ
Ó Ó ÓÓÓÓÓ ÓÓ ÓÓ ÓÓ ÓÓ
ÓÓ ÓÓ ÓÓ Ó Ó
ÓÓ ÓÓ
3−26
1
Fig.3/13: Identifying the manifold sub−bases
Counting begins from left to right, on the individual valves from the rear to the front (see diagram).
Festo P.BE−CPA−EN en 0306d
3. Installation
If a manifold sub−base occupies 2 addresses, the follow ing assignment applies: solenoid coil 14 occupies the lower−value address solenoid coil 12 occupies the higher−value address
1
Valve plate with 2 solenoid coils
2
Blanking plate with manifold sub−base EV2
3
Blanking plate with manifold sub−base EV1
4
Valve plate with one solenoid coil
5
Addresses of coil
12
6
Addresses of coil
14
6
5
1
ÓÓ
14 14
12
ÓÓ
ÓÓ
1 3
1 1 2
ÓÓ
ÓÓ
0 2 4 5 7 8
ÓÓÓ
10 12
ÓÓÓ
ÓÓ
12
14 14 14
12
6
ÓÓÓ
ÓÓÓ
9
ÓÓÓ
11
ÓÓÓ
ÓÓÓ
ÓÓ
3
ÓÓÓ
4 4
Fig.3/14: Example: Address assignment of the CPA valve terminal with MP connection and 8 valve locations (top view)
Festo P.BE−CPA−EN en 0306d
3−27
3. Installation
1
Valve plate with 2 solenoid coils
2
Valve plate with one solenoid coil
3
Blanking plate
CPA valve terminal with IC connection
· The address assignment is in ascending order without gaps
· Counting begins from left to right, on the individual valves from the rear to the front (see diagram).
0 2 4 5 7 8
1 3 6 9
1 2 3
Fig.3/15: Address assignment of the CPA valve terminal with IC connection and 8 valve locations (top view)
3−28
Festo P.BE−CPA−EN en 0306d
Commissioning
Chapter 4
Festo P.BE−CPA−EN en 0306d
4−1
4. Commissioning
Contents
4.
Preparing for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure build−up of the complete supply . . . . . . . . . . . . . . . . . . . .
Checking the valves and the valve−actuator combination . . . . . . . . . . . . . . .
Impairment of function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating states of the pneumatic system . . . . . . . . . . . . . . . . . . .
4−2
Festo P.BE−CPA−EN en 0306d
4. Commissioning
Contents of this chapter
Further information
This chapter deals with the commissioning of the CPA valve terminal. The following belong here: checking the valve functions operating the manual overrides checking the valve−actuator combination trouble shooting assignment of the LEDs
The commissioning of the CP system is described in the rel evant manual for the CP node.
The commissioning of the CPX terminal is described in the relevant manual for the CPX field bus node.
Festo P.BE−CPA−EN en 0306d
4−3
4. Commissioning
4.1
General instructions
4.1.1
Preparing for commissioning
· Switch off the power supply before connecting or discon necting plugs (this will prevent functional damage).
· Commission only a valve terminal which is fitted and wired completely.
· Make sure there is a sufficient supply of fresh air (cooling) for the following operating conditions:
when the maximum number of valves is fitted
when the maximum operating voltage is applied
when the solenoid coil is constantly stressed
· Note the following instructions on building up the com plete pressure supply.
4.1.2
Pressure build−up of the complete supply
Warning
If the build up of auxiliary pilot air is too slow or delayed, this may lead to sudden unexpected movements of the actuators under the following conditions:
when the compressed air is switched on via a safety start−up valve (slow build−up of pressure) and
when there are electric signals (e.g. after EMERGENCY
STOP).
This may cause damage to the machine or system and injury to human beings.
· Operate the valve terminal with external auxiliary pilot air (3 ... 8 bar). Branch the auxiliary pilot air in front of the safety start−up valve (see diagram).
4−4
Festo P.BE−CPA−EN en 0306d
4. Commissioning
Festo P.BE−CPA−EN en 0306d
The auxiliary pilot air must be applied with a pressure of 3 ...
8 bar immediately after being switched on. Otherwise it can not be guaranteed that the valve will switch directly (see dia gram).
If the pressure is less than 3 bar, there may be a delay before the valve switches, in spite of an electric signal. The slow build−up of pressure in the complete system then has no ef fect on the actuator. The actuator would react suddenly (e.g.
a cylinder would extend or retract suddenly, depending on the valve function).
82/84
4 2
14
12/14
1
5 3
2
12
3
2
1
12/14
1
1
Externally supplied auxiliary pilot air (3 to 8 bar), branched in front of the safety start−up valve
2
Safety start−up valve (slow pressure build−up of the complete supply)
Fig.4/1: Example of valve−cylinder combination with slow pressure build−up of the complete system
4−5
4. Commissioning
The effects of slow start−up pressurization when there are electric signals is shown in the following table:
External auxi liary pilot air
Pressure build−up of the complete supply branched after the safety start−up valve slowly branched before the safety start−up valve slowly fast
Pressure build− up of the auxi liary pilot air
(12/14) slowly
Time point when the valve switches
Movement of the actuator after pressure in crease at (1) fast before pressure increase at (1) slowly
Tab.4/1: Effects of slow start−up pressurization
4.2
Manual override
You should use the manual override principally when commis sioning the pneumatic system in order to check the functional ability and effects of the valve or valve−actuator combination.
By actuating the manual override you can switch the valve without an electric signal. Only the compressed air supply needs to be switched on.
The manual override has been designed to be used as fol lows:
4−6
Festo P.BE−CPA−EN en 0306d
4. Commissioning
Manual override design
Manual override non−locking
Manual override locking
Manual override covered
Functioning method
The manual override is reset au tomatically by spring force.
The manual override remains ac tive until it is reset by hand.
No manual override function
Tab.4/2: Variants of manual override actuations
The following manual override variants are available for CPA valve terminals with MP, CP, AS−interface connection or CPX terminal:
2 4
1
Slide of the locking manual override to pilot solenoid 14
3
Slide of the non−locking manual override to pilot solenoid 14
2
Slide of the locking manual override to pilot solenoid 12
4
Slide of the non−locking manual override to pilot solenoid 12
Fig.4/2: Manual override variants of the CPA valve terminal with MP, CP, AS−interface connection or CPX terminal
Festo P.BE−CPA−EN en 0306d
4−7
4. Commissioning
The manual overrides on CPA valve terminals with IC connec tion can be actuated in locking or non−locking mode.
The assignment of the manual override to the valve solenoid coils is shown below.
1
2
1
Locking/non−locking manual override to pilot solenoid
14
2
Locking/non−locking manual override to pilot solenoid
12
Fig.4/3: Position of the manual override on CPA valve ter minals with IC connection
4−8
Festo P.BE−CPA−EN en 0306d
4. Commissioning
4.3
Checking the valves and the valve−actuator combination
Please note
Before commissioning the CPA valve terminal, note the specifications on medium, see chapter Installation, section
Pilot control of the valve solenoid coils (auxiliary pilot air)".
Proceed as follows when commissioning the CPA valve ter minal:
Commissioning variants
Preliminary check of the pneu matic tubing
Complete commissioning of the complete system
Activity
Checking the valve−actuator combination by means of the manual override
Installing and connecting the complete system.
Program control by PLC/indu strial PC
Tab.4/3: Commissioning variants
The commissioning of the pneumatic components by means of the manual override is described below.
The commissioning of the CPX terminal is described in the relevant manual for the CPX field bus node.
Festo P.BE−CPA−EN en 0306d
4−9
4. Commissioning
4−10
Warning
Before actuating the manual override:
Unmonitored control of valve solenoid coils can cause actuators to perform sudden unexpected movements.
These can result in injury to human beings and damage to property.
· Disconnect the operating voltage supply to the valve solenoid coils at the relevant connections on the CPA valve terminal.
In this way you will avoid undesired movement of the valve solenoid coils.
Before applying the operating voltage:
Manual override actuations which are in the switched posi tion can cause actuators to perform sudden unexpected movements during commissioning. These could lead to injury to human beings and damage to property.
· Make sure that all manual override actuations are reset to their basic positions.
In this way you will avoid undefined switching states of the valves.
Proceed as follows:
Warning
Before checking the valve−actuator combination:
Make sure that nobody is in the danger zone.
Please note
A valve, which has been switched by an electric signal, cannot be reset by the manual override. The electric signal is dominant in this case.
· Reset the electric signal before actuating the manual override.
1. Switch on the compressed air supply.
Festo P.BE−CPA−EN en 0306d
4. Commissioning
2. Check the functioning and effect of each valve−actuator combination by actuating the manual override, as shown in the following diagrams.
Please note
If the non−locking manual override is operated incorrectly, the functioning of the manual override may be impaired or it may be damaged.
· Use a blunt object for actuating the non−locking manual override.
· Actuate the manual override with max. 30 N.
3. On CPA valve terminals with locking manual override actuations: After checking the valves, make sure that all manual override actuations are reset to their basic posi tions.
4. Switch off the compressed air supply after testing the valves.
Festo P.BE−CPA−EN en 0306d
4−11
4. Commissioning
Manual override with non−locking function (automatic: reset)
CPA valve terminal with MP, CP, AS−in terface connection or CPX terminal
CPA valve terminal with IC connection
Operation Reaction of the valve
Press down the plunger of the manual override until the valve switches.
Please note:
On CPA valve terminals with IC connection: Do not turn the pres sed−down plunger, as the manual override will then lock.
The valve:
assumes the switch position
Hold the plunger of the manual override pressed down.
Release the plunger (spring re sets the plunger of the manual override to the basic position).
remains in the switch position
returns to the basic position
(not with double−sole noid valve type
J)
Tab.4/4: Operating the non−locking manual override
4−12
Festo P.BE−CPA−EN en 0306d
4. Commissioning
Manual override with locking function (manual: reset)
CPA valve terminal with MP, CP, AS−in terface connection or CPX terminal
CPA valve terminal mit IC connection
Operation Reaction of the valve
CPA valve terminal with MP, CP,
AS−interface connection or CPX terminal
· Push the slide of the manual override as far as possible into the switch position.
The valve:
assumes the switch position
CPA valve terminal with IC con nection
· Press down the plunger of the manual override until the valve
· switches.
Then turn the plunger in a clockwise direction as far as possible.
· Leave the slide or plunger in position.
remains in the switch position
CPA valve terminal with MP, CP,
AS−interface connection or CPX terminal
· Push the slide of the manual override as far as possible into the basic position again.
returns to the basic position
(not with double−sole noid valve type
J) CPA valve terminal with IC con nection
·
·
Then turn the plunger in an anti−clockwise direction as far as possible.
Then release the plunger.
Tab.4/5: Operating the locking manual override
Festo P.BE−CPA−EN en 0306d
4−13
4. Commissioning
Caution
Manual override actuations which are in the switched posi tion can cause actuators to perform sudden unexpected movements during commissioning. These could lead to injury to human beings and damage to property. When the manual override is actuated, it is not possible to reset the valve to its basic position with an electric signal. The man ual override is dominant in this case.
· Make sure that double−solenoid valves (Ident. Code J) are reset to their basic positions. Actuate here the man ual override 12 of the relevant valve or apply current to pilot control solenoid 12.
· Reset the locking manual override actuations to the basic position. Valve plates with Ident. code H, K and N are each fitted with two valves. With manual override 14 you can control the valve on control side 14; with man ual override 12 you can control the valve on control side
12 (see switching symbols for valve plates in Appendix
B).
In this way, you can avoid undefined switching states when commissioning the machine/system.
4−14
Festo P.BE−CPA−EN en 0306d
4. Commissioning
4.4
LED display of the valves
There is a yellow LED for every valve solenoid coil. This LED shows the switching status of the valve solenoid coil.
The position of the LED for the manual override actuations on
CPA valve terminals with MP, CP, AS−interface connection or
CPX terminal is shown below.
Note the assignment of the LED to the relevant manual over ride:
Left−hand LED in the electric bridge to front manual over ride (12)
Right−hand LED in the electric bridge to rear manual over ride (14)
1
LED and manual override for pilot solenoid 14
2
LED and manual override for pilot solenoid 12
2
1
Fig.4/4: Assignment of the LED to the manual override actuations on CPA valve ter minals with MP, CP, AS−interface connection or CPX terminal
Festo P.BE−CPA−EN en 0306d
4−15
4. Commissioning
The position of the LED for the manual override actuations on
CPA valve terminals with IC connection is shown below.
1
LED and manual override for pilot solenoid 14
2
LED and manual override for pilot solenoid 12
1
2
Fig.4/5: Assignment of the LED to the manual override actuations on CPA valve ter minals with IC connection
The LEDs show the switching status of the valve solenoid coils. The following table explains the meanings.
LED Switch position of the valve
Meaning yellow out yellow alight *)
Basic position
Switch position or
basic position logical 0 (no signal) logical 1 (signal present) logical 1 but:
the operating voltage of the outputs lies below the permitted tolerance range (20.4
V to 26.4 V DC)
Compressed air supply not OK or
pilot exhaust blocked or
servicing required
*) The LEDs light up on double−solenoid valves (Ident. code J) only when there are electric pulses.
Tab.4/6: Meaning of the LED display
4−16
Festo P.BE−CPA−EN en 0306d
4. Commissioning
4.5
Trouble shooting
4.5.1
Impairment of function
When the compressed air supply has been switched on or when the valves are subsequently checked, you can learn the following about the operating status of the pneumatic sys tem:
Operating status of the pneumatic system
Air escapes from...
common line or work line connections
between the modules
Treatment of faults when the compressed air supply has been switched off
· Check the tubing
· After switching on again, set external auxiliary pilot air to 3 ... 8 bar).
Valve or pneumatic system...
does not react as expected
does not react
·
·
Check the tubing
Check the electric cables
· Bring the locking manual override into the basic position
·
·
After switching on again check the operating pressure (if necessary for each pressure zone)
Set the operating pressure in accordance with the instructions in chapter 3.
In the case of valve terminals which are operated with closed−loop controlled auxiliary pilot air and which are fitted with 3/2−way valves:
· check the pilot pressure after switching on again (if necessary set as a factor of the operat
· ing pressure, see chapter 3) servicing required
Tab.4/7: Impairment of function of the pneumatic system
Festo P.BE−CPA−EN en 0306d
4−17
4. Commissioning
4.5.2
Operating states of the pneumatic system
The following conditions should be fulfilled in order that the desired pneumatic operating states listed below can be achieved:
Desired pneuma tic operating sta tus
Condition Remarks free of leakage fast reaction faultless
tubing connected correctly
closed−loop controlled auxiliary pilot air sufficient pressure supply via pres sure supply points
Non−return valves in common ex haust line two or more pressure zones
Limiting the pressure zones by means of separator plates
Vacuum operation/ low−pressure opera tion separately supplied closed−loop con trolled auxiliary pilot air (3 ... 8 bar)
· Exhaust the CPA valve terminal at the left and right−hand end plates
(3/5) applies if several systems with cen trally ducted exhaust are used conversion possible at a later date
(see chapter 5)
Vacuum/low−pressure operation not with 3/2−way valves
EMERGENCY STOP of pressure zones
Guarantees the controller function for the auxiliary pilot air, despite complete supply being switched off
The controller regulates the auxiliary pilot air of all the valve plates on a
CPA valve terminal
Slow start up after
EMERGENCY STOP
If control signals are present, the au xiliary pilot air must have a pressure of 3 ... 8 bar immediately after being switched on
Tab.4/8: Pneumatic operating states
4−18
Festo P.BE−CPA−EN en 0306d
Maintenance and conversion
Chapter 5
Festo P.BE−CPA−EN en 0306d
5−1
5. Maintenance and conversion
Contents
5.
General precautionary measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dismantling the CPA valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning the large surface−mounted silencer
Converting the CPA valve terminal
. . . . . . . . . . . . . . . . .
Replacing CPA valve terminal components . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing valve plates, blanking plates or additional pressure
Replacing the large surface−mounted silencer
supply plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
Replacing the end plate, sub−base or manifold sub−base . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conversion from locking to locking/non−locking manual override . 5−19
Conversion to internal or external auxiliary pilot air . . . . . . . . . . . . 5−21
Conversion of the CPA valve terminal to different pressure zones . 5−23
Adding/removing valve locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−2
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
Contents of this chapter
Further information
This chapter describes maintenance and conversion of the
CPA valve terminal. The following belong here:
Cleaning the large surface−mounted silencer
Replacing or removing components in valve locations such as valve plates, blanking plates or additional pres sure supply plates.
Replacing the large surface−mounted silencer
Replacing end plates, sub−bases or manifold sub−bases
Modifying the manual override
Converting the auxiliary air supply to internal or external supply
Converting valve locations for controlling one or two valve solenoid coils
Adding or removing valve locations
Information on fitting/removing the CPA valve terminal with
CPX terminal can be found in the CPX system manual.
Instructions on connecting the electric components on the
CPA valve terminal with CPX terminal can be found in the CPX system manual.
Instructions on connecting the electric components on the
CPA valve terminal with multipin or AS−interface connection can be found in the information supplied with the product.
Instructions on connecting the CPA valve terminal with CP connection can be found in the CP system manual.
Festo P.BE−CPA−EN en 0306d
5−3
5. Maintenance and conversion
5.1
General precautionary measures
Warning
Sudden unexpected movements of the connected actua tors and uncontrollable movements of loose tubing can cause injury to human beings and damage to property.
Before carrying out installation and/or maintenance work, switch off the following:
· the compressed air supply
· the operating and load voltage supplies
Please note
Handle the components of the CPA valve terminal with great care. When fitting components, pay attention in par ticular to the following:
· screws must be fitted correctly (otherwise threads may be damaged)
· screws must be tightened at first only by hand. Screws must be inserted so that the self−boring threads can be used
· the specified torques must be observed
· screws must be fitted without offset and mechanical stress
· the seals must be checked for damage (IP 65)
· connecting surfaces must be dry and clean (sealing ef fect, avoid leakage and contact faults)
5−4
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.2
Dismantling the CPA valve terminal
If the CPA valve terminal is easily accessible, it will not be necessary to dismantle it under the following conditions:
Adding or removing components in valve locations
Adding components when it is not necessary to replace or insert sub−bases or manifold sub−bases
Loosening the electrical connections
Connection variant
CP connection
MP connection
AS−interface connection
IC connection
CPX terminal
Proceed as follows:
1. Mark the incoming and continuing CP cables.
2. Loosen the union nuts of the CP cables.
3. Pull the CP cables away from the sub−base.
1. Loosen the diagonally offset fastening screws of the sub−D multipin plug.
2. Pull the sub−D plug away from the sub−base.
1. Loosen the fastening screws of the AS−interface bus socket and, if necessary, also the fastening screws of the additional supply.
2. Pull the sockets away from the sub−base.
Note the following in the case of AS−interface with inputs:
3. Loosen the union nuts of the cables at the inputs.
4. Pull the cables away from the inputs.
1. Mark all connecting plugs of the valve solenoids.
2. Loosen the locking screws of the connecting plugs.
3. Pull the plugs carefully away from the connecting lugs.
1. Mark all electrical connecting cables.
2. Loosen and remove these cables.
Tab.5/1: Loosen the electrical connections.
Festo P.BE−CPA−EN en 0306d
5−5
5. Maintenance and conversion
Loosening the pneumatic connections
Loosening the pneumatic connections is described in chapter 3.
Removing the CPA valve terminal
Removing the CPA valve terminal from the fastening surface is described in chapter 2.
5−6
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.3
Servicing the CPA valve terminal
5.3.1
Cleaning the large surface−mounted silencer
Festo P.BE−CPA−EN en 0306d
Caution
Dirt on the large surface−mounted silencer can cause an increase in pressure in exhaust channels 3 and 5.
· Clean the insert of the large surface−mounted silencer if it is coloured yellow/black or dark or replace it with a new insert.
· Do not use TRI for cleaning, but benzine or petroleum.
· Observe the safety regulations for easily inflammable cleaning agents.
You then guarantee faultless functioning of the large sur face−mounted silencer and avoid malfunctioning of the valves.
Proceed as follows:
1. Loosen the 4 fastening screws of the large surface− mounted silencer and remove it from the end plate.
2. Clean the large surface−mounted silencer with benzine or petroleum.
3. Check the seal between the end plate and the large sur face−mounted silencer for damage. If necessary, replace the seal.
4. Make sure that the seal is fitted correctly. It must lie in the recess in the end plate.
5. Fasten the large surface−mounted silencer only with the original screws. Tighten these in diagonally opposite se quence with:
CPA10: 0.7 Nm (±0.1 Nm)
CPA14: 0.8 Nm (±0.1 Nm)
5−7
5. Maintenance and conversion
5.4
Replacing CPA valve terminal components
Components on sub−bases can easily be replaced for main tenance and conversion work.
The following components can be fitted on one sub−base: one valve plate or one blanking plate or one additional pressure supply plate
Please note
On a valve location with manifold sub−base EV1 only one valve plate with a soleonoid coil (single−solenoid valve,
Ident. code M) can be fitted. Valve plates with two solenoid coils may only be fitted onto a valve location with manifold sub−base EV2.
5.4.1
Replacing valve plates, blanking plates or additional pressure sup ply plates
Dismantling Proceed as follows:
1. Loosen the fastening screws of the relevant components
(position of the fastening screws see diagram). In order to do this, use a screwdriver with a narrow blade.
2. Remove the components from the sub−base of the CPA valve terminal.
5−8
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
1
CPA valve terminal with MP,
CP, AS−interface connection or
CPX terminal
2
CPA valve terminal with IC connection
1 2
ÔÔ
ÔÔ Ô ÔÔ Ô Ô
ÔÔ ÔÔ Ô Ô ÔÔ Ô ÔÔ
ÔÔ ÔÔ Ô
ÔÔÔ Ô Ô ÔÔ
ÔÔÔ Ô ÔÔ ÔÔÔ ÔÔ ÔÔ Ô ÔÔ
Ô Ô Ô ÔÔ ÔÔ Ô ÔÔÔ ÔÔ
Ô Ô ÔÔ
Fig.5/1: Removing valve plates
Fitting Proceed as follows:
1. Check the seal for damage.
2. If necessary, replace damaged seals.
3. Make sure that the seal is fitted correctly. It must lie in the recess in the sub−base.
Festo P.BE−CPA−EN en 0306d
5−9
5. Maintenance and conversion
4. Fitting valve plates onto CPA valve terminals with MP, CP,
AS−interface connection or CPX terminal. Clip the electric bridge carefully onto the new valve plate. Make sure that the connector plugs of the solenoid coils are not bent.
5. Place the component on the sub−base.
6. Screw the component at first by hand and then tighten with the following torque:
CPA10: 0.25 Nm (±0.05 Nm)
CPA14: 0.3 Nm (±0.05 Nm)
You must carry out the following tasks before a valve plate can be fitted onto a CPA valve terminal with IC connection:
1. Insert carefully the marked IC connector plug into the connecting lugs of the relevant solenoid coils.
2. Tighten the locking screws on the connector plugs with
0.2 Nm.
5.4.2
Replacing the large surface−mounted silencer
Dismantling
Fitting
Proceed as follows:
1. Loosen the four fastening screws in the large surface− mounted silencer.
2. Remove the large surface−mounted silencer from the end plate.
Proceed as follows:
1. Check the seal between the end plate and the large sur face−mounted silencer for damage. If necessary, replace the seal.
2. Replace the large surface−mounted silencer.
3. Make sure that the seal is fitted correctly. It must lie in the recess in the end plate.
5−10
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
4. Place the new large surface−mounted silencer on the end plate.
5. Fasten the large surface−mounted silencer only with the original screws. Tighten these in diagonally opposite se quence with:
CPA10: 0.7 Nm (±0.1 Nm)
CPA14: 0.8 Nm (±0.1 Nm)
5.4.3
Replacing the end plate, sub−base or manifold sub−base
Dismantling
Please note
Removing the CPA valve terminal with CPX terminal is de scribed in appendix A.
Proceed as follows:
1. Loosen the electrical and pneumatic connections and re move the CPA valve terminal from the fastening surface
(see this chapter, Dismantling the CPA valve terminal").
2. Place the CPA valve terminal on a flat working surface.
3.
Replacing a sub−base
Remove the pin−type inserts from the sub−base to be re placed. Unlock the pin−type inserts by using a screwdriver to remove the clamping spring. Pull the pin−type inserts out of the sub−base (see diagram). In order to do this use a screwdriver.
Festo P.BE−CPA−EN en 0306d
5−11
5. Maintenance and conversion
1
Clamping spring
2
Pin−type inserts
Fig.5/2: Removing the pin−type inserts
Ô ÔÔÔÔ ÔÔ
Ô ÔÔÔÔ ÔÔ
Ô ÔÔÔÔ ÔÔ
ÔÔÔÔ
ÔÔ
ÔÔ
ÔÔ
1
2
5−12
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
1
CPA valve terminal with MP,
CP, AS−interface connection or
CPX terminal
2
CPA valve terminal with IC connection
4. Loosen the fastening screws of all components on all sub− bases by approximately 2 turns. In this way you will avoid distorting the CPA valve terminal as soon as you loosen the tie rods (see diagram).
1 2
ÔÔÔ
Ô Ô ÔÔÔ
Ô ÔÔ Ô Ô ÔÔ Ô ÔÔ
ÔÔ Ô ÔÔ ÔÔ ÔÔ
ÔÔÔ ÔÔ
ÔÔÔ ÔÔ Ô Ô Ô ÔÔ ÔÔÔ
Ô ÔÔ ÔÔÔ ÔÔ Ô Ô ÔÔ Ô ÔÔ Ô Ô
Ô ÔÔ ÔÔ Ô Ô
Fig.5/3: Loosening components on sub−bases
5.
Replacing a sub−base or a manifold sub−base
Remove the components on the sub−base to be replaced
(see this chapter, Replacing valve plates, blanking plates or additonal pressure supply plates").
Festo P.BE−CPA−EN en 0306d
5−13
5. Maintenance and conversion
6. Depending on the component to be replaced, loosen the tie rod screws in the left−hand or right−hand end plate (see diagram).
ÔÔÔ
ÔÔÔ ÔÔÔ Ò ÔÔ
Ò ÔÔ ÔÔ Ô ÔÔ Ô ÔÔÔ Ô
ÔÔ Ô Ô ÔÔ Ô
Fig.5/4: Loosening the tie rod screws
7. Remove the relevant end plate from the tie rods.
8.
Replacing the end plate
Loosen the 4 fastening screws of the electric sub−base or manifold and remove it from the relevant end plate (see diagram).
1
Fastening screws of the electric sub−base
2
Fastening screws of the sub−base
ÔÔ Ô ÔÔÔÔ
ÔÔÔ Ô ÔÔ ÔÔ Ô ÔÔÔÔ ÔÔ
ÔÔÔ Ô ÔÔ Ô ÔÔ Ô ÔÔ ÔÔ
ÔÔ Ô ÔÔÔ ÔÔ Ô ÔÔ
ÔÔ ÔÔ Ô ÔÔ
ÔÔ
1
2
Fig.5/5: Loosening the sub−base or manifold
5−14
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
1
Sub−base to be replaced
9.
Replacing a sub−base or a manifold sub−base
Remove the relevant sub−bases from the tie rods (see
sub−base or manifold sub−base to be replaced.
ÔÔÔ
Ô ÔÔÔ ÔÔ Ô
ÔÔ ÔÔ Ô Ò Ô ÔÔÔ
Ô Ò ÔÔ
1
Ò ÒÒÒ
Ò ÒÒ ÒÒ Ò Ò ÒÒÒ
ÒÒ Ò Ò Ò ÒÒ
Fig.5/6: Removing sub−bases
1
Unlocking the manifold sub−base
2
Removing the manifold from the sub−base
1 2
Fig.5/7: Removing the manifold sub−base
Fitting Proceed as follows:
Festo P.BE−CPA−EN en 0306d
5−15
5. Maintenance and conversion
Fitting the sub−base and the manifold sub−base
1. Push the manifold sub−base onto the guide rail of the new sub−base until it clips in to position.
2. Check the seals for damage. If necessary, replace dam aged seals. Place the seals in the relevant grooves of the sub−base and manifold.
3. Push the sub−bases onto the tie rods.
Fitting the end plate.
4. CPA valve terminal with MP, CP, AS−interface connection or
CPX terminal
When you have replaced the end plate, screw the electric sub−base or manifold onto the new end plate. Make sure that the electric sub−base or manifold is flush with the
relevant end plate (see Fig.5/8).
Tighten the screws as follows (position see Fig.5/5):
CPA10: 0.7 Nm (±0.1 Nm)
CPA14: 0.8 Nm (±0.1 Nm)
5−16
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
Festo P.BE−CPA−EN en 0306d
ÔÔÔÔÔÔ
ÔÔÔÔÔÔ
ÔÔÔÔÔÔ
ÔÔÔÔÔÔ
Fig.5/8: Fitting the electric sub−base
5. Place the end plate on the tie rods and screw the tie rod screws several turns into the tie rods.
6. Align the CPA valve terminal on a flat surface so that the components are not offset.
7. Tighten the screws of the tie rods in 2 stages as follows:
Stage
1
2
CPA10
0.5 Nm
1.5 Nm
Tab.5/2: Tightening torques of the tie rods
CPA14
0.5 Nm
2 Nm
5−17
5. Maintenance and conversion
8. On sub−bases with dismantled components, check that the seals on the sub−base are correctly positioned. They must lie correctly in the relevant seal grooves.
9. Place the removed seals on the relevant sub−bases again and tighten them slightly.
10. Tighten the fastening screws of all components on the sub−bases as follows:
CPA10: 0.25 Nm (± 0.05 Nm)
CPA14: 0.3 Nm (± 0.05 Nm)
11. Where applicable, place missing pin−type inserts in the sub−bases (see chapter 3 Installation, connecting the supply, exhaust and work lines").
12. Mount the CPA valve terminals on the fastening surface
(see chapter 2 Fitting, onto a wall" or onto a hat rail").
13. Then complete the pneumatic and electrical connections
(see chapter 3 Installation, connecting the CPA valve terminal").
5−18
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.5
Converting the CPA valve terminal
The following conversion work can be undertaken on the CPA valve terminal: conversion to locking or non−locking manual override with
CPA valve terminals with MP, CP, AS−interface connection or CPX terminal conversion of the CPA valve terminal to internal or exter nal auxiliary pilot air conversion of the CPA valve terminal to different pressure zones
Converting valve locations for controlling one or two valve solenoid coils
5.5.1
Conversion from locking to locking/non−locking manual override
CPA valve terminals with MP, CP or AS−interface connection can be converted from locking to locking/non−locking manual override if the locking clip is removed.
The manual overrides on CPA valve terminals with IC connec tion can be actuated in locking or non−locking mode. Conver sion is not necessary.
Proceed as follows:
If you wish to use the locking clip again
· Use a thin object (e.g. a spatula) in order to lift the lock
ing clip out of its fastening (Fig.5/9,
1 )
Festo P.BE−CPA−EN en 0306d
5−19
5. Maintenance and conversion
If you do not wish to use the locking clip again
· Press with a screwdriver in the centre of the locking clip
(Fig. 5/10, 2 ). The locking clip will then bend and snap out of the fastening.
1
1
Removing the locking clip by lifting it out (the Clip can be used again)
Fig.5/9: Converting the manual override
2
Removing the locking clip by pressing it out
2
5−20
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.5.2
Conversion to internal or external auxiliary pilot air
Pilot control of the valve solenoid coils can be undertaken with internal or external auxiliary pilot air, depending on the right−hand end plate. You can ascertain the pilot control vari ant for which your CPA valve terminal is equipped by means of the type designation on the right−hand end plate (see table).
CPA valve terminal with auxiliary pilot air with internal pilot air
Right−hand end plate type
CPA..−EPR−S
CPA..−EPR
Tab.5/3: End plates for external or internal pilot air
Please note
Mixed operation of the CPA valve terminal with internal and external auxiliary pilot air is not permitted. The sub−base for pressure zone separation does not divide the auxiliary pilot air channel.
The available right−hand end plates are listed in the following table. Check whether the right−hand end plate, with which your CPA valve terminal is fitted, is intended for pilot control with internal or external auxiliary pilot air.
Festo P.BE−CPA−EN en 0306d
5−21
5. Maintenance and conversion
The following right−hand end plates are available for pilot control of the CPA valve terminal:
Right−hand end plate Type
Pilot control with internal auxiliary pilot air
CPA..−EPR
Description
Connection 12/14 in the right−hand end plate is not marked and is sealed with a blanking plug.
The auxiliary pilot air branched inter nally from connection 1.
Pressure zone separation is permitted.
Non−used connections must be sealed.
Pilot control with external auxiliary pilot air
CPA..−EPR−S Connection 12/14 in the right−hand end plate for connecting the auxiliary pilot air is marked.
Pressure zone separation is permitted.
Non−used connections must be sealed.
Tab.5/4: Right−hand end plate
The method of fitting the relevant end plate into your CPA valve terminal is described in this chapter under Replacing the end plate, sub−base or manifold sub−base."
5−22
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.5.3
Conversion of the CPA valve terminal to different pressure zones
For conversion you will require:
Components
For converting the CPA valve terminal to two pressure zones:
one sub−base with pressure zone separation
For each further pressure zone you will require:
one sub−base with pressure zone separation
one additional pressure supply plate
Type
CPA..−AW−ZP
CPA..−AW−ZP
CPA..−DP−U
Tab.5/5: Separator plates
In the case of CPA valve terminals with MP, CP, AS−interface connection or CPX terminal, we recommend that conversion be carried out from the right−hand side. The tie rod screws are more easily accessible on the right−hand end plate.
The method of replacing the sub−bases and fitting the addi tional pressure supply plate is described in this chapter under Replacing the end plate, sub−base or manifold sub− base" or Replacing valve plates, blanking plates or addi tional pressure supply plates."
Festo P.BE−CPA−EN en 0306d
5−23
5. Maintenance and conversion
The following diagram shows the layout of pressure zones using a CPA valve terminal as an example.
ÔÔÔÔÔ ÔÔ
ÔÔÔÔÔ ÔÔ ÔÔ Ô
ÔÔÔÔÔ ÔÔ
ÔÔÔÔÔ Ô ÔÔ ÔÔ
ÔÔ Ô ÔÔÔÔÔ ÔÔ ÔÔ Ô
ÔÔ Ô ÔÔ Ô
ÔÔ Ô
ÔÔ ÔÔ ÔÔÔÔÔ Ô ÔÔ ÔÔ
Ô ÔÔ ÔÔ ÔÔ ÔÔ
ÔÔ ÔÔ
7
6
1 2 3 4 5
1
Connection 1 of the left−hand end plate for pressure supply to the 1st. pressure zone.
2
Valve plates of the 1st. pressure zone
3
One sub−base with pressure zone separation
4
Valve plates of the 2nd. pressure zone
5
Sub−base with pressure zone separation and fitted additional pressure supply plate. Compressed air supply of the 2nd. pressure zone via connection 2 on the sub−base
6
Connection 1 of the right−hand end plate for compressed air supply to the 3rd.
pressure zone.
7
Valve plates of the 3rd. pressure zone
Fig.5/10: Example of CPA valve terminal with three pressure zones
5−24
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.5.4
Conversion of valve location for controlling one or two solenoid coils
The manifold sub−base determines the valves which can be fitted on a valve location (with one or two solenoid coils).
In order that a valve location can support one or two solenoid coils, you must replace the manifold on the relevant sub− base.
For conversion you will require:
Components manifold sub−base for controlling one solenoid coil or manifold sub−base for controlling two solenoid coils
Type
CPA..−EV1
CPA..−EV2
Tab.5/6: Manifold sub−base
By means of the identification on the manifold sub−base (see diagram), you can ascertain the manifold sub−bases with which your CPA valve terminal is equipped.
1
EV1:
Manifold sub−base for controlling one solenoid coil
EV2:
Manifold sub−base for controlling two solenoid coils
ÔÔÔÔ
ÔÔ ÔÔ ÔÔÔÔ
ÔÔ ÔÔ ÔÔÔÔ ÔÔ Ô ÔÔ
ÔÔ Ô ÔÔ ÔÔ ÔÔ ÔÔÔÔ ÔÔ
ÔÔ ÔÔ ÔÔ ÔÔ ÔÔÔÔ ÔÔ Ô
ÔÔ ÔÔ ÔÔÔÔ ÔÔ Ô Ô
ÔÔ Ô Ô ÔÔ
Ô
1
Fig.5/11: Identifying the manifold sub−bases
Festo P.BE−CPA−EN en 0306d
5−25
5. Maintenance and conversion
Caution
If valve locations are converted for controlling one or two solenoid coils, the address assignment will be modified.
This can lead to unexpected movement of the actuators.
· Check the address assignment in your PLC control pro gram and, if necessary, update the address assignment.
Please note:
manifold sub−base CPA..−EV1 occupies 1 address
manifold sub−base CPA..−EV2 occupies 2 addresses
The method of replacing a manifold sub−base is described in this chapter under Replacing an end plate, sub−base or manifold sub−base."
5−26
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
5.6
Adding/removing valve locations
The number of valve locations on the CPA valve terminal can easily be extended or reduced.
The following diagram shows as an example the extension of a CPA valve terminal with 6 valve locations to 8 or 9 valve locations.
ÔÔÔ ÔÔ
Ô ÔÔ Ô ÔÔ ÔÔÔ Ô
Ô ÔÔ Ô Ô ÔÔ
ÔÔÔÔ Ô ÔÔ ÔÔ
ÔÔ ÔÔ ÔÔÔÔ ÔÔ ÔÔ
ÔÔ ÔÔ Ô
1 2 3 4 5 6
1
Basis tie rod for 6 valve locations
2
Tie rod extension for 2 valve locations
3
7. and 8th. new valve location
4
9. New valve location
5
Short tie rod screw (extension of this
CPA valve terminal to 8 valve locations)
6
Long tie rod screw (extension of this CPA valve terminal to 9 valve locations)
Fig.5/12: Extending the CPA valve terminal
Festo P.BE−CPA−EN en 0306d
5−27
5. Maintenance and conversion
A valve location consists of a sub−base and a manifold. The number of valve locations determines the length of the tie rods and the tie rod screws.
Components for adding valve locations
You will require:
Components Type
Sub−base or
Sub−base for pressure zone separation
Manifold sub−base (for supporting one solenoid coil) or
Manifold sub−base (for controlling two solenoid coils)
Basis tie rod
(division: 2, 4, 6 to 22)
CPA..−AW
CPA..−AW−ZP
CPA..−EV1
CPA..−EV2
CPA..−ZA−2
.
.
CPA..−ZA−22
Tie rod extension if necessary (for two additional valve locations) CPA..−ZA−2Z
Short tie rod screw, if necessary (for valve terminals with even number of valve locations) CPA..−ZA−SK
Long tie rod screw, if necessary (for valve terminals with odd number of valve locations) CPA..−ZA−SL
Tab.5/7: Tie rod extension
5−28
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
The tie rod components, which you will require for adding valve locations, are listed in the following table.
Number
* )
+ 1
Starting basis: Valve terminals with even number of valve locations
Starting basis: Valve terminals with odd number of valve locations
2longtie rod screws
+ 2 2Tie rod extensions
+ 3 2Tie rod extensions and
2longtie rod screws
> + 3 2Basis tie rod if necessary
2longtie rod screws
* ) Number of valve locations to be added
2Tie rod extensions and
2shorttie rod screws
2Tie rod extensions
2Basis tie rod and
2shorttie rod screws
2Basis tie rod if necessary
2shorttie rod screws
Tab.5/8: Tie rod reduction
Components for removing valve locations
When valve locations have been removed, the tie rods must be adapted.
You will require:
Components
Basis tie rod
(division: 2, 4, 6 to 22)
Type
CPA..−ZA−2
.
.
CPA..−ZA−22
Short tie rod screw, if necessary (for valve terminals with even number of valve locations) CPA..−ZA−SK
Long tie rod screw, if necessary (for valve terminals with odd number of valve locations) CPA..−ZA−SL
Tab.5/9: Tie rods and tie rod screws
The following table lists the tie rod components which you will require in order to adapt the tie rod length.
Festo P.BE−CPA−EN en 0306d
5−29
5. Maintenance and conversion
Number
* )
Starting basis: Valve terminals with even number of valve locations
Starting basis: Valve terminals with odd number of valve locations
2shorttie rod screws − 1 2Basis tie rod and
2longtie rod screws
2Basis tie rod − 2
− 3 2Basis tie rod and
2longtie rod screws
>
− 3 2Basis tie rod if necessary
2longtie rod screws
* ) Number of valve locations to be removed
2Basis tie rod
2Basis tie rod
2shorttie rod screws
2Basis tie rod if necessary
2shorttie rod screws
Tab.5/10: Adapting the length of the tie rod
Dismantling Proceed as follows:
1. Loosen the CPA valve terminal from the fastening surface
(see this chapter, Dismantling the CPA valve terminal").
2. Unclamp the CPA valve terminal. Loosen the fastening screws of all components on the valve locations by 2 turns. Remove all the components, which you wish to replace from the valve locations (see this chapter, Re placing valve plates, blanking plates or additional pres sure supply plates").
3. Remove the relevant end plate and pull the valve loca tions away from the tie rods. Remove the relevant valve locations (see this chapter, Replacing end plates, sub− bases or manifold sub−bases").
4. Adapt the tie rods to the new number of valve locations
(see tables of the tie rod components and Fig.5/11).
5−30
Festo P.BE−CPA−EN en 0306d
5. Maintenance and conversion
Fitting Proceed as follows:
Please note
In the case of an extension of the CPA valve terminal with tie rod extension, make sure that this lies flush with the basis tie rod.
Use the tie rod extension only for two additional valve loca tions. Further tie rod extensions are not permitted. In this case use appropriately longer basis tie rods.
1. If you wish to add valve locations, fit the relevant manifold
(EV1 or EV2) to the sub−base. Then fit all valve locations and the end plate (see this chapter, Replacing end plates, sub−bases or manifold sub−bases").
2. Fit the relevant components onto the empty valve loca tions (see this chapter, Replacing valve plates, blanking plates or additional pressure supply plates").
3. Fit the CPA valve terminals onto the fastening surface (see chapter 2 Fitting, onto a wall" or onto a hat rail").
Festo P.BE−CPA−EN en 0306d
5−31
5. Maintenance and conversion
5−32
Festo P.BE−CPA−EN en 0306d
Technical appendix
Appendix A
Festo P.BE−CPA−EN en 0306d
A−1
A. Technical appendix
Contents
A.
A−2
Festo P.BE−CPA−EN en 0306d
A. Technical appendix
A.1
Technical specifications
General specifications
Permitted temperature range
storage
operation
medium
Protection class as per EN 60 529
Relative humidity
Protection against corrosion
Mounting position
Torques
Fastening for foot mounting
Hat rail clamping unit
Locking screw for IC connection
Components on valve locations
Components on end plates
Tie rods
Type CPA10/14
−20 ... +40 o C
−5 ... +50 o C
−5 ... +50 o C
IP 65 (fitted completely, with appropriate cable from the
Festo accessories)
90 % against industrial climate (as per FN940070) as desired
0.8 Nm
1.3 Nm
0.2 Nm
CPA10: 0.25 Nm (± 0.05 Nm)
CPA14: 0.3 Nm (± 0.05 Nm)
CPA10: 0.7 Nm (± 0.1 Nm)
CPA14: 0.8 Nm (± 0.1 Nm)
1. Step 0.5 Nm (CPA10/CPA14)
2. Step 1.5 Nm (CPA10) or 2.0 Nm (CPA14)
2.0 Nm (±0.4 Nm) Fastening for CPA valve terminal on
CPX terminal
Materials
Plates, covers
Valve plate
Seals
PPS, PA6T/X−GF40
AL−DG, PPS, ST, AL
NBR
Festo P.BE−CPA−EN en 0306d
A−3
A. Technical appendix
General specifications
Vibration and shock 1)
vibration 2)
Type CPA10/14
shock 2) tested as per DIN/IEC68 / EN60068 parts 2 − 6, class 2 tested as per DIN/IEC68 / EN60068 parts 2 −27, class 2
Permanent shock tested as per DIN/IEC68 / EN60068 parts 2 −29, class 1
1) Explanations of the severity classes see following table.
2) Specifications on vibration and shock of the CPA valve terminal with CPX terminal can be found in the system manual for the CPX terminal.
Tab.A/1: Technical specifications: General specifications
Sever ity class
Vibration
1
2 shock Permanent shock
0.15 mm path at 10−58 Hz;
2 g acceleration at 58−150 Hz
±15 g at 11 ms duration;
5 shocks in each direction
0.35 mm path at 10−60 Hz;
5 g acceleration at 60−150 Hz
±30 g at 11 ms duration;
5 shocks in each direction
±15 g at 6ms duration;
1000 shocks in each direction
−−−−−
Tab.A/2: Values for vibration and shock as per DIN/IEC68
A−4
Festo P.BE−CPA−EN en 0306d
A. Technical appendix
General specifications
Approximate weights (in g):
Connection variants
MP, CP, AS−interface connec tion or CPX terminal
IC connection
Pneumatics CPA10:
Basic weight
per valve plate
Pneumatics CPA14:
Basic weight
per valve plate
CPX terminal
Pneumatic interface
per complete CPX module
Left−hand end plate (CPX ter minal)
AS−interface with inputs
AS−interface module approx. 280 g approx. 120 g approx. 460 g approx. 190 g approx. 320 g approx. 210 g approx. 80 g approx. 210 g approx. 100 g approx. 300 g approx. 150 g approx. 240 g
Tab.A/3: Technical specifications: Weight specifications for the CPA valve terminal
Please note
The valves can be used at temperatures from −5 o C. In order to prevent the condensate and humidity from freez ing, we recommend that a drier be fitted with which con densate and humidity can be removed.
Caution
Operate the CPA valve terminal if possible with non−lu bricated auxiliary pilot air (connections 12/14). If lubri cated air must be used, observe the instructions in the section Preparing the compressed air.
In the case of CPA valve terminals with internally branched auxiliary pilot air, the above−mentioned in struction also applies to the supply air (connection 1).
Festo P.BE−CPA−EN en 0306d
A−5
A. Technical appendix
Pneumatics
Medium
Type CPA10/14 compressed air, filtered (< 40 m), lubricated (oil: VG 32) or non−lubricated/vacuum
Valve plates with spool valves Design
Pressure range
Pilot control with internal auxiliary pilot air (auxiliary pilot air branched from supply channel 1).
Pilot control with external auxiliary pilot air (auxiliary pilot air supplied via connection 12/14)
Manual override
Valve plate Ident. code J:
1; 12/14: 2 ... 8 bar
Valve plates Ident. code M, N, K, H, B, E, G:
1; 12/14: 3 ... 8 bar
Valve plates Ident. code B, E, G, J, M:
1: − 0,9 ... 10 bar
12/14: 3 ... 8 bar
Valve plates Ident. code N, K, H:
1: 3 ... 10 bar
12/14: siehe diagrams locking or non−locking
Tab.A/4: Technical specifications: Medium and pressure ranges
A−6
Festo P.BE−CPA−EN en 0306d
A. Technical appendix
1
Control pressure
12/14 (bar)
2
Work pressure P1
(bar)
3
Start−up control pressure
1
3
2
Fig.A/1: External pilot air diagram for valve plates CPA10 Ident. code N, K, H
1
Control pressure
12/14 (bar)
2
Work pressure P1
(bar)
3
Start−up control pressure
1
3
2
Fig.A/2: External pilot air diagram for valve plates CPA14 Ident. code N, K, H
Festo P.BE−CPA−EN en 0306d
A−7
A. Technical appendix
Please note
The screw connectors of the pneumatic connections will cause a reduction in the flow of the valves.
Pneumatics Type CPA10/14
J
Ident. code of the valve plate
M
J
N, K, H,
B
G
E
M
N, K, H,
B
G
E
Valve
5/2−way valve (single−solenoid)
5/2−way valve (double−solenoid) all 3/2−way valves
5/3 valve, pressurized
5/3 valve, closed
5/3 valve, exhausted
5/2−way valve (single−solenoid)
5/2−way valve (double−solenoid) all 3/2−way valves
5/3 valve, pressurized
5/3 valve, closed
5/3 valve, exhausted
Rated flows [I/min]
(always without screw connector)
Values of the mid−position in brackets
Micro valves (CPA10)
1 ⇒ 2 or 1 ⇒ 4
280
280
220
220 (130)
330
200
2 ⇒ 3/5 or 4
280
280
220
220
330
⇒
200 (130)
3/5
Mini valves (CPA14)
1 ⇒ 2 or 1 ⇒ 4
600
600
550
550 (400)
550
550
2 ⇒ 3/5 or 4
600
⇒
600
550
600
550
550 (400)
3/5
Tab.A/5: Technical specifications: Rated flows
A−8
Festo P.BE−CPA−EN en 0306d
A. Technical appendix
Pneumatics Type CPA10/14
J
J
Ident. code of the valve plate
M
N, K, H,
B
G
E
M
N, K, H,
B
G
E
Valve
5/2−way valve (single−solenoid)
5/2−way valve (double−solenoid) all 3/2−way valves
5/3 valve, pressurized
5/3 valve, closed
5/3 valve, exhausted
5/2−way valve (single−solenoid)
5/2−way valve (double−solenoid) all 3/2−way valves
5/3 valve, pressurized
5/3 valve, closed
5/3 valve, exhausted
Valve switching times in [ms]
(measuring method 0 − 10 %) (as per FN
942032)
Micro valves (CPA10)
Off: 18 On: 11
Switch: 7
On: 8
On: 13
On: 13
On: 13
Off: 18
Off: 17
Off: 17
Off: 20
Mini valves (CPA14)
Off: 29 On: 17
Switch: 10
On: 9
On: 13
On: 13
On: 13
Off: 28
Off: 39
Off: 30
Off: 39
Tab.A/6: Technical specifications: Valve switching times
Festo P.BE−CPA−EN en 0306d
A−9
A. Technical appendix
Electric CPA valve terminal with IC, MP or CP connection
Electromagnetic compatibility (EMC)
CPA valve terminal with CP connection
Interference emitted
Immunity against interference tested as per EN 61000−6−4 (industry 1) tested as per EN 61000−6−2 (industry)
Protection against electric shock
(protection against direct and indirect contact as per EN
60204−1 /IEC 204)
Operating voltage
Operating voltage range
Residual ripple by connection to a PELV power unit
(Protected Extra Low Voltage)
24 V DC
20.4 26.4 V
4 Vpp
Current consumption per valve solenoid coil
Rated current in heavy current phase (I
20
as per VDE 0580)
Rated current in holding current phase approx. 35 mA approx. 15 mA
Power consumption
Input current consumption of electronics
CPA valve terminal with CP connection max. 1 W
20 mA
1) The CP valve terminal is intended for industrial use.
2) The maximum signal cable length with CPA valve terminals with MP connection is 10 m.
Tab.A/7: Technical specifications: Electric components
Technical specifications on the electric components of the
CPA valve terminal with MP or AS−interface connection can be found in the information supplied with the product.
Further data on the electric components of the CPA valve ter minal with CP connection can be found in the relevant manual for the CP field bus node.
A−10
Festo P.BE−CPA−EN en 0306d
A. Technical appendix
A.2
Festo accessories
Accessories
General specifications
Hat rail mounting kit
Inscription clip
Pin−type blanking plugs
Loosening fork for disconnecting tubing
CPA valve terminal with AS−interface connection
AS−interface combi power unit
AS−interface bus cable (yellow)
AS−interface additional supply cable (black)
Cable socket
Cable cap / cable sleeve
Addresser / adapter cable
Flat cable distributor
Adapter for flat cable on round cable
T−piece for round cable
CPA valve terminal with CP connection
CP cable
Type designation
CPA−BG−NRH
IBS6x10
QSP..−PTB
QSO
ASI−CNT−115/230VAC−B
KASI−1,5−Y−100
KASI−1,5−Z−100
ASI−SD−FK / ASI−SD−FK180
ASI−KK−FK / ASI−KT−FK
ASI−PRG−ADR / KASI−ADR
ASI−KVT−FK−S / ASI−KVT−FK
ASI−SD−FK−M12 / ASI−SD−PG−M12
FB−TA−M12−5POL
KVI−CP−1...
KVI−CP−2... (suitable for use as drag chain)
CPA valve terminal with IC connection
Individual connector plug with LED and holding current reduction
CPA valve terminal with MP connection
Ready−to−use multipin cable with socket
Multipin socket
KMYZ−7−24−...−LED
KEA−1−25P−... (IP65), KMP4−25P−... (IP65)
KMP6−25P−... (IP20)
SD−SUB−D−BU25 (IP65)
Tab.A/8: Festo accessories for the CPA valve terminal
Festo P.BE−CPA−EN en 0306d
A−11
A. Technical appendix
A−12
Festo P.BE−CPA−EN en 0306d
Supplementary component summary and installa tion instructions
Appendix B
Festo P.BE−CPA−EN en 0306d
B−1
B. Supplementary component summary and installation instructions
Contents
B.
Supplementary component summary and installation instructions . . . . .
Removing the electronic components from the CPA valve terminal . . . . . . .
B−2
Festo P.BE−CPA−EN en 0306d
B. Supplementary component summary and installation instructions
B.1
Overview of the valve plates
Please note
The numbers on the following switching symbols are the designations of the connections, coils and manual override actuations. For example, designation 14 stands for manual override 14 or for coil 14. They are not logical designa tions.
Valve plates
82/84 4
14
12/14 5
82/84 4
14
1
2
3
2
12
Ident. code: K
Function:
Two single−solenoid 3/2−way valves, basic position blocked
12
Ident. code: N
Function:
Two single−solenoid 3/2−way valves, basic position open
14
12/14
82/84 4
5 1
2
3
12
Ident. code: H
Function:
single−solenoid 3/2−way valve, on control side
14 in basic position blocked and
single−solenoid 3/2−way valve, on control side
12 in basic position open
12/14 5 1 3
Tab.B/1: Valve plates with 3/2−way valves
Festo P.BE−CPA−EN en 0306d
B−3
B. Supplementary component summary and installation instructions
Valve plates
14
82/84 4 2
12/14
5 3
1
82/84 4 2
14 12
12/14 5 3
1
Tab.B/2: Valve plates with 5/2−way valves
Ident. code: M
Function:
single−solenoid 5/2−way valve
Please note:
Number of assigned outputs:
Valve location with manifold sub−base EV1: 1A
Valve location with manifold sub−base EV2: 2A
Ident. code: J
Function:
5/2−way double−solenoid valve
B−4
Festo P.BE−CPA−EN en 0306d
B. Supplementary component summary and installation instructions
Valve plates
82/84 4 2
Ident. code: B
Function:
5/3−way valve, in mid−position pressurized
14 12
12/14
82/84
5 3
1
4 2 Ident. code: G
Function:
5/3−way valve, in mid−position blocked
14 12
12/14
82/84
5 3
1
4 2
14 12
12/14
5 3
1
Tab.B/3: Valve plates with 5/3−way valves
Ident. code: E
Function:
5/3−way valve, in mid−position exhausted
Festo P.BE−CPA−EN en 0306d
B−5
B. Supplementary component summary and installation instructions
1
6
5
4
3
B.2
Removing the electronic components from the CPA valve terminal
The CPX terminal and the AS−interface module (with inputs) are connected to the CPA valve terminal by means of a pneu matic adapter. The method of removing the CPX terminal from the CPA valve terminal is described below. The AS−interface module is removed in the same way.
ÎÎÎÎ
ÎÎÎÎ Î ÎÎ ÎÎ ÎÎÎÎ
Î ÎÎ Î ÎÎ Î ÎÎ ÎÎÎÎ Î
Î ÎÎ Î ÎÎ Î ÎÎ Î
Î ÎÎ
2
1
CPA valve terminal with sub−base for
CPX
2
Pneumatic adapter
3
Pneumatic interface
4
5
6
Electrical bridge (plug connector)
Dowel pins
M4 x 35 screws (CPA10),
M4 x 40 (CPA14)
Fig.B/1: Pneumatic interface and pneumatic adapter
Dismantling Proceed as follows:
1. Loosen the electrical and pneumatic connections and re move the CPA valve terminal from the fastening surface
(see this chapter, Dismantling the CPA valve terminal").
B−6
Festo P.BE−CPA−EN en 0306d
B. Supplementary component summary and installation instructions
2. Remove the dowel pins by knocking them out (see dia gram).
ÎÎÎ ÎÎ
ÎÎÎ ÎÎ
ÎÎ ÎÎ
ÎÎ ÎÎ
ÎÎ ÎÎ
ÎÎ
Fig.B/2: Removing the CPA valve terminal from the CPX ter minal
Festo P.BE−CPA−EN en 0306d
B−7
B. Supplementary component summary and installation instructions
3. Loosen and remove the fastening screws.
ÎÎÎÎÎ
ÎÎÎÎÎ ÎÎ
ÎÎ ÎÎ ÎÎÎÎÎ Î ÎÎ ÎÎ
Î ÎÎ ÎÎ ÎÎ ÎÎ
ÎÎ ÎÎ ÎÎ
B−8
Fig.B/3: Removing the CPA valve terminal from the CPX ter minal
4. Carefully pull the CPA valve terminal away from the CPX terminal without tilting it.
ÎÎÎ Î
ÎÎ Î ÎÎÎ Î ÎÎ Î
Î ÎÎ Î ÎÎ Î
ÎÎ Î
Fig.B/4: Removing the CPA valve terminal from the CPX ter minal
Festo P.BE−CPA−EN en 0306d
B. Supplementary component summary and installation instructions
Fitting
Instructions on replacing the CPA pneumatic interface can be found in the manual for the CPX system.
5. Check the pneumatic adapter on the left−hand end plate of the CPA valve terminal for damage. If necessary, re place the pneumatic adapter. The method of removal is described in the section Replacing end plates, sub−bases or manifold sub−bases."
Proceed as follows:
1. Insert the electrical bridge in the terminal strip of the CPX terminal (this step is not necessary with the CPA valve terminal with AS−interface module).
Festo P.BE−CPA−EN en 0306d
Fig.B/5: Fitting the elctrical bridge
2. Push the CPA valve terminal together with the CPX ter minal. Check that the electrical bridge is positioned cor rectly in the terminal strips.
B−9
B. Supplementary component summary and installation instructions
ÎÎÎ Î
ÎÎ Î ÎÎÎ Î ÎÎ Î
Î ÎÎ Î ÎÎ Î
Fig.B/6: Fitting the CPA valve terminal onto the CPX ter minal
3. Press and hold the CPA valve terminal against the CPX terminal.
4. Place the dowel pins in the locating holes of the pneuma tic adapter. Knock the dowel pins as far as possible into the holes.
B−10
Festo P.BE−CPA−EN en 0306d
B. Supplementary component summary and installation instructions
Festo P.BE−CPA−EN en 0306d
ÎÎÎÎ ÎÎ
ÎÎÎÎ Î Î Î ÎÎ
Î ÎÎ ÎÎÎÎ ÎÎÎ Î
Î ÎÎ Î
ÎÎ Î
Fig.B/7: Fitting the dowel pins
5. Insert the fastening screws into the appropriate holes and tighten them with 2.0 Nm.
6. Fasten the CPX valve terminal to the fastening surface
(see manual for CPX system).
7. Connect the CPX terminal electrically and pneumatically.
Information on this can be found: in the manual for the CPX system (electric compo nents) in chapter 3 of this manual (pneumatic components)
Instructions on connecting the electrical components of the
CPA valve terminal with AS−interface and inputs can be found in the documentation supplied with the product.
B−11
B. Supplementary component summary and installation instructions
B−12
Festo P.BE−CPA−EN en 0306d
Index
Appendix C
Festo P.BE−CPA−EN en 0306d
C−1
C. Index
Contents
C.
C−2
Festo P.BE−CPA−EN en 0306d
C. Index
C.1
Index
Festo P.BE−CPA−EN en 0306d
A
Abbreviations, product−specific . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address assignment, Outputs . . . . . . . . . . . . . . . . . . . . .
Auxiliary pilot air branched internally conversion
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . supplied externally . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C
Compressed air, requirements
. . . . . . . . . . . . . . . . . . . . . 3−4
CPA valve terminal with CP connection
. . . . . . . . . . . .
CPA valve terminal with CPX terminal
CPA valve terminal with IC connection
. . . . . . . . . . . . .
. . . . . . . . . . . .
CPA valve terminal with MP connection . . . . . . . . . . .
Connections, pneumatic . . . . . . . . . . . . . . . . . . . . . . . . .
Conversion of valve location for controlling one solenoid coil for controlling two solenoid coils
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
CP connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPA valve terminal
Address assignment of the outputs
Components
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthing the valve terminal . . . . . . . . . . . . . . . . . . . . .
Loosen the AS−interface module
Loosen the CPX terminal
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
Overview of variants . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C−3
C. Index
C−4
CPA valve terminal with IC connection , Connecting the valve solenoid coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display elements
CPA valve terminal with AS−interface connection . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPA valve terminal with CP connectio
CPA valve terminal with CPX terminal
. . . . . . . . . . . . .
. . . . . . . . . . . . .
CPA valve terminal with IC connection
CPA valve terminal with MP connection
. . . . . . . . . . . .
. . . . . . . . . . .
E
EMERGENCY STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External auxiliary pilot air . . . . . . . . . . . . . . . . . . . . . . . .
F
Fastening accessories
Fastening profile for fitting onto a wall
Hat rail
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting kit, Hat rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting variants
Fitting onto a hat rail
Foot mounting
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Foot mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H
Hat rail
Clamping unit
Fitting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo P.BE−CPA−EN en 0306d
C. Index
Festo P.BE−CPA−EN en 0306d
I
Identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impairment of function . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . .
Internal auxiliary pilot air . . . . . . . . . . . . . . . . . . . . . . . . .
L
Large surface−mounted silencer cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low−pressure operation . . . . . . . . . . . . . . . . . . . . . . . . . .
M
Manual override conversion
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Designs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . non−locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manuals on the CP system . . . . . . . . . . . . . . . . . . . . . . . . .
Manuals on the CPX terminal . . . . . . . . . . . . . . . . . . . . . .
Micro valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mini valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting kit, for hat rail fitting . . . . . . . . . . . . . . . . . . . . .
MP connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
N
Notes on the use of this manual . . . . . . . . . . . . . . . . . . . . .
C−5
C. Index
C−6
O
Operating elements, pneumatic . . . . . . . . . . . . . . . . . . .
Operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P
Pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pilot control
External auxiliary pilot air
Internal auxiliary pilot air
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
Pin−type inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position of the LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure zones . . . . . . . . . . . . . . . . . . . . . . .
Common pneumatic line
. . . . . . . . . . . . . . . . . . . . . . .
conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R
Rated flows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remove the additional pressure supply plate.
. . . . . . . . .
Remove the blanking plate . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the end plate . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo P.BE−CPA−EN en 0306d
C. Index
Festo P.BE−CPA−EN en 0306d
S
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sizes of the pneumatic screw connectors,
Pin−type inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−up pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . .
Support rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching status display . . . . . . . . . . . . . . . . . . . . . . . . .
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tie rods, adapting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tubing
Disconnecting
Fitting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
Vacuum operation . . . . . . . . . . . . . . . . . . . . . . . . .
Valve locations, adding . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve locations, removing . . . . . . . . . . . . . . . . . . . . . . . .
Valve locations, Division . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification code
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview removing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve switching times . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C−7
C. Index
C−8
Festo P.BE−CPA−EN en 0306d

Public link updated
The public link to your chat has been updated.
Advertisement