Advertisement
Advertisement
Operation Manual
Mobile reverse osmosis system
AVRO-flex 400
Starting from software version V1.33
Edition November 2018
Order no. 095 752 946-inter
2
Mobile reverse osmosis system
AVRO-flex 400
Table of contents
A General .................................................................................................................................................................. 5
1 | Preface ..........................................................................................................................................................................................................5
2 | How to use this operation manual .................................................................................................................................................................6
3 | General safety information ............................................................................................................................................................................6
3.1
Symbols and notes ..................................................................................................................................................................................6
3.2
3.3
Operating personnel ...............................................................................................................................................................................7
Intended use ............................................................................................................................................................................................7
3.4
Protection from water damage ................................................................................................................................................................7
3.5
Indication of specific hazards ..................................................................................................................................................................7
4 | Shipping and storage .....................................................................................................................................................................................8
5 | Disposal .........................................................................................................................................................................................................8
5.1
Packaging ................................................................................................................................................................................................8
5.2
Product ....................................................................................................................................................................................................8
B Basic information ................................................................................................................................................. 9
1 | Laws, regulations, standards .........................................................................................................................................................................9
2 | Water .............................................................................................................................................................................................................9
3 | Functional principle of reverse osmosis ......................................................................................................................................................10
3.1
Functional principle of the AVRO system ..............................................................................................................................................11
C Product description ........................................................................................................................................... 12
1 | Type designation plate ................................................................................................................................................................................12
2 | Functional description ..................................................................................................................................................................................13
3 | Technical specifications ...............................................................................................................................................................................17
4 | Intended use ................................................................................................................................................................................................18
5 | Application limits ..........................................................................................................................................................................................19
6 | Scope of supply ...........................................................................................................................................................................................20
6.1
Standard equipment ..............................................................................................................................................................................20
6.2
Optional accessories .............................................................................................................................................................................21
6.3
Consumables .........................................................................................................................................................................................22
6.4
Wearing parts ........................................................................................................................................................................................22
D Installation .......................................................................................................................................................... 23
1 | General installation instructions ...................................................................................................................................................................23
1.1
Water connection ...................................................................................................................................................................................23
E Start-up................................................................................................................................................................ 24
1 | How to connect the system to the water supply ..........................................................................................................................................24
2 | How to flush the system ..............................................................................................................................................................................26
2.1
How to flush off the preserving agent ....................................................................................................................................................26
2.2
Filling mode ...........................................................................................................................................................................................26
2.3
Workshop mode ....................................................................................................................................................................................28
F Operation (control unit) ..................................................................................................................................... 29
1 | Preface ........................................................................................................................................................................................................29
2 | How to operate the control unit....................................................................................................................................................................30
2.1
Reading the operating status ................................................................................................................................................................31
2.2
How to set the time ................................................................................................................................................................................31
2.3
2.4
Access to the programming levels - change parameters ......................................................................................................................32
Software version Code 999 ...................................................................................................................................................................32
3 | Programming levels .....................................................................................................................................................................................33
3.1
Input logic Code 113 .............................................................................................................................................................................33
3.2
System parameters Code 290 ..............................................................................................................................................................33
3.3
3.4
Reference values / times Code 302 ......................................................................................................................................................34
Error memory / water volumes Code 245 ..............................................................................................................................................35
3.5
Diagnosis Code 653 ..............................................................................................................................................................................35
4 | Wiring diagram of mobile reverse osmosis system AVRO-flex 400 ............................................................................................................36
5 | Operation of reverse osmosis system AVRO-flex 400 ................................................................................................................................38
5.1
How to set the system recovery ............................................................................................................................................................38
G Troubleshooting ................................................................................................................................................. 40
H Maintenance and care ........................................................................................................................................ 42
1 | Basic information .........................................................................................................................................................................................42
2 | Inspection (functional check) .......................................................................................................................................................................42
3 | Maintenance ................................................................................................................................................................................................43
3.1
Operation log .........................................................................................................................................................................................44
4 | Operation log ...............................................................................................................................................................................................45
Maintenance work on mobile reverse osmosis system AVRO-flex 400 .................................................................... 46
Maintenance work on mobile reverse osmosis system AVRO-flex 400 .................................................................... 48
Maintenance work on mobile reverse osmosis system AVRO-flex 400 .................................................................... 50
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Publisher's information
All rights reserved.
© Copyright by Grünbeck Wasseraufbereitung GmbH
Printed in Germany
Effective with the date of edition indicated on the cover sheet.
-We reserve the right to modifications, especially with regard to technical progress-
Reprints, translations into foreign languages, electronic storage or copying only with explicit written approval of Grünbeck Wasseraufbereitung GmbH.
Any type of duplication not authorised by Grünbeck Wasseraufbereitung is a copyright violation and subject to legal action.
Responsible for contents:
Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1 89420 Hoechstaedt/Germany
Tel. +49 9074 41-0 Fax +49 9074 41-100 www.gruenbeck.com [email protected]
Print: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
3
Mobile reverse osmosis system
AVRO-flex 400
EU Declaration of Conformity
This is to certify that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and execution.
If the system is modified in a way not approved by us, this certificate is void.
Manufacturer: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1
89420 Hoechstaedt/Germany
Responsible for documentation: Markus Pöpperl
System designation: Mobile reverse osmosis system
System type: AVRO-flex 400
Serial no.:
Applicable directives:
Applied harmonised standards, in particular:
Refer to type designation plate
Machinery Directive (2006/42/EU)
EMC (2014/30/EU)
DIN EN ISO 12100:2011-03,
DIN EN 61000-6-2:2006-03
DIN EN 61000-6-3:2011-09
Applied national standards and technical specifications, in particular:
Place, date and signature:
Function of signatory:
Hoechstaedt, 30.04.2018
Head of Technical Product Design i. V._____________
M. Pöpperl
Dipl. Ing. (FH)
4
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
A General
Mobile reverse osmosis system
AVRO-flex 400
1 | Preface
Thank you for opting for a Grünbeck product. Backed by decades of experience in the area of water treatment, we provide customised solutions for all kind of processes.
Drinking water is classified as food and requires particular care.
Therefore, always ensure the required hygiene when operating and maintaining systems involved in the drinking water supply. This also applies to the treatment of water for industrial use if repercussions for the drinking water cannot completely be excluded.
All Grünbeck systems and devices are made of high-quality materials.
This ensures reliable operation over many years, provided you treat your water treatment systems with the required care. This operation manual assists you with important information.
Therefore, please read the entire operation manual before installing, operating or maintaining the system.
Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this system, possible extensions or general water and waste water treatment, our field staff, as well as the experts at our headquarters in
Hoechstaedt, are available to help you.
Advice and assistance For advice and assistance please contact your local representative
(see www.gruenbeck.com) or get in touch with our service centre which can be reached during office hours:
Phone: +49 9074 41-333
Fax: +49 9074 41-120
Email: [email protected]
We can connect you with the appropriate expert more quickly if you provide the required system data. In order to have the required data handy at all times, please copy it from the type designation plate to the overview in Chapter C-1.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
5
Mobile reverse osmosis system
AVRO-flex 400
2 | How to use this operation manual
This operation manual is intended for the operators of our systems. It is divided into several chapters which are listed in the “Table of contents” on page 2 in alphabetical order. In order to find the specific information you are looking for, check for the corresponding chapter on page 2.
The headers and page numbers with chapter information make it easier to find your way around in the manual.
3 | General safety information
3.1 Symbols and notes Important information in this operation manual is characterised by symbols. Please pay particular attention to this information to ensure the hazard-free, safe and efficient handling of the system.
Danger!
Failure to adhere to this information will cause serious or life-threatening injuries, extensive damage to property or inadmissible contamination of the drinking water.
Warning! Failure to adhere to this information may cause injuries, damage to property or contamination of the drinking water.
Attention! Failure to adhere to this information may result in damage to the system or other objects.
Note: This symbol characterises information and tips to make your work easier.
Tasks with this symbol may only be performed by Grünbeck's technical service/authorised service company or by persons expressly authorised by Grünbeck.
Tasks with this symbol may only be performed by trained and qualified electrical experts according to the VDE guidelines or according to the guidelines of a similar local institution.
Tasks with this symbol may only be performed by the local water supply companies or approved installation companies. In Germany, the installation company must be registered in an installation directory of a water company as per §12(2) AVBWasserV (German Ordinance on
General Conditions for the Supply of Water).
6
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
3.2 Operating personnel
Only persons who have read and understood this operation manual are permitted to work with the system. The safety information in particular is to be strictly adhered to.
3.3 Intended use The system may only be used for the purpose outlined in the product description (Chapter C). The instructions in this operation manual as well as the applicable local guidelines concerning drinking water protection, accident prevention and occupational safety must be adhered to.
In addition, intended use also implies that the system may only be operated when it is in proper working order. Any malfunctions must be repaired at once.
3.4 Protection from water damage
Warning! In order to properly protect the installation site from water damage: a. a sufficient floor drain system must be available or b. a safety device (refer to Chapter C “Optional accessories”) must be installed.
3.5 Indication of specific hazards
Warning!
Floor drains with discharge to a lifting system do not work in case of a power failure.
Danger due to electrical energy! Do not touch electrical parts with wet hands! Unplug the mains plug before starting work on electrical parts of the system. Have qualified experts replace damaged cables immediately.
Danger due to mechanical energy! System parts may be subject to overpressure. Danger of injury and damage to property due to escaping water and unexpected movement of system parts. Check pressure pipes regularly. Depressurise the system before starting repair or maintenance work on the system.
Hazardous to health due to contaminated drinking water! The system may only be installed by a specialist company. The operation manual must be strictly adhered to! Ensure that there is sufficient flow. The pertinent guidelines must be followed for start-up after extended periods of standstill. Inspections and maintenance must be performed at the intervals specified!
Note: By concluding a maintenance contract, you ensure that all of the required tasks are performed on time. You may perform the interim inspections yourself.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
7
Mobile reverse osmosis system
AVRO-flex 400
4 | Shipping and storage
Attention! The system may be damaged by frost or high temperatures. In order to avoid damage of this kind:
Protect from frost during transportation and storage!
Do not install or store system next to objects which radiate a lot of heat.
5 | Disposal
5.1 Packaging
5.2 Product
Comply with the applicable national regulations.
Dispose of the packaging in an environmentally sound manner.
If this symbol (crossed out waste bin) is on the product, European
Directive 2012/19/EU applies to this product. This means that this product and the electrical and electronic components must not be disposed of as household waste.
Dispose of electrical and electronic products or components in an environmentally sound manner.
For information on collection points for your product, contact your municipality, the public waste management authority, an authorised body for the disposal of electrical and electronic products or your waste collection service.
8
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
B Basic information
Mobile reverse osmosis system
AVRO-flex 400
1 | Laws, regulations, standards
In the interest of good health, rules cannot be ignored when it comes to the processing of drinking water. This operation manual takes into consideration the current regulations and stipulates information that you will need for the safe operation of your water treatment system.
Among other things, the regulations stipulate that only approved companies are permitted to make major modifications to water supply facilities and that tests, inspections and maintenance on installed devices are to be performed at regular intervals.
2 | Water
There is no chemically pure water in nature. Even in the atmosphere, rain water absorbs various substances that change the properties of the water to a greater or lesser degree. This process continues as the water passes through the ground layers, with the result that the water is enriched with increasingly large quantities of materials. Carbon dioxide (CO
2
) is particularly important here, since this substance increases the dissolving capability of the water even more. Consequently, drinking water contains quantities of dissolved sodium, potassium, calcium, magnesium, iron, manganese, copper, zinc, chlorides, fluorides, sulphates and also nitrates, nitrites, phosphates and silicates that vary greatly from location to location.
Due to dynamic substance and water cycles, harmful elements, which are only partly and only slowly biodegradable are increasingly released into nature. Over time, these elements therefore accumulate in ground and surface water. Removing them from natural water bodies again represents a particular challenge. Grünbeck rises to this challenge and aims at generating unpolluted drinking and industrial water.
The water works provide us with pure drinking water that is suitable for consumption. However, if the water is to be used for technical purposes, further treatment is frequently required.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
9
Mobile reverse osmosis system
AVRO-flex 400
3 | Functional principle of reverse osmosis
Principle:
Pretreated feed water
Fig. B-1: Functional principle
Concentrate:
Permeate
Solution of high concentration
Solution of low concentration
Solution of high concentration
Solution of low concentration
Solution of high concentration
(concentrate)
Solution of low concentration
(permeate)
Fig. B-2: Reverse osmosis principle
In the osmosis process, watery solutions of different concentrations are separated by a semi-permeable membrane. In keeping with the law of nature, the concentrations try to equalise. On the side of the higher original concentration, the so-called "osmotic" pressure is generated. In case of reverse osmosis, this osmotic pressure is countered by a higher pressure. The consequence: the process proceeds in the reverse direction. A particular advantage of the reverse osmosis technology compared to other water treatment processes is the fact that - apart from the removal of dissolved salts - bacteria, germs, particles and dissolved organic substances are also reduced.
10
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
3.1 Functional principle of the AVRO system
Mobile reverse osmosis system
AVRO-flex 400
AVRO is an alternative anti-scaling process to the common traditional processes of "softening" or “antiscalant dosing”. Contrary to these processes, AVRO does not require any addition of auxiliary additives.
The chemical composition of the generated concentrate is not modified. There is only a doubling of the concentration (standard recovery
50 %).
Hydraulically, the AVRO is installed in the concentrate pipe downstream of the membrane.
The treatment unit consists of two inert special electrodes to which a low current is applied. Seed crystals (calcium carbonate) are generated at the cathode and are permanently directed via the concentrate recirculation. The salts of the supersaturated concentrate continue to grow on these seed crystals, and they are finally washed out to the drain with the residual concentrate flow. This reliably prevents scaling
(deposits of insoluble salts on the membrane). Some of the calcium carbonate remains on the cathode of the AVRO and due to increasing electrical resistance, limits the service life of the AVRO treatment unit to 3000 operating hours (permeate production) or 5 years.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
11
Mobile reverse osmosis system
AVRO-flex 400
C Product description
1 | Type designation plate
You may find the type designation plate at the housing of the mobile reverse osmosis system AVRO-flex 400. In order to speed up the processing of your inquiries or orders, please specify the data shown on the type designation plate of your system when contacting Grünbeck.
Please copy the indicated information to the table below in order to have it handy whenever necessary.
Mobile reverse osmosis system AVRO-flex 400
Serial number:
Order number:
Fig. C-1: Type designation plate
12
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
2 | Functional description
Via a fine filter (filter element), the water is directed to the inlet of the feed water section. The water flows to the high-pressure pump via the inlet solenoid valve with a downstream “pressure switch for minimum pressure”. By means of a control valve, the pressure generated by the high-pressure pump is reduced to the required operating pressure and the water is directed to the membrane. The membrane separates the water into the partial flows permeate and concentrate. A partial flow of the concentrate is returned to the feed water via an orifice regulating independently of pressure and thus ensures a steady flow over the membrane and increases the economic efficiency of the reverse osmosis.
At the same time, the concentrate volume flow is run via an AVRO treatment module where seed crystals are formed at a cathode due to the application of direct current. These seed crystals are then washed out with the residual concentrate and thus the reverse osmosis membrane is protected from clogging. Whenever the system is switched off or in case of disturbances, the substances retained on the membrane are flushed off by means of the inlet solenoid valve and a solenoid valve switched in parallel to the control valve for concentrate.
The hydraulic set-up of the system is designed in a way that the concentrate volume and the permeate volume are registered by means of flow sensors and are displayed in the control unit. The system recovery can also be called up in the control unit.
Downstream of the membrane, the permeate produced can be delivered into the heating system with a counter-pressure of up to 3.5 bar.
Note: If the counter-pressure on the permeate side increases, the permeate output decreases.
Filling mode:
If "filling mode" is selected via the selector switch on the controller, three waves are visible in the controller. The pressure switch is interrogated as the start criterion.
Workshop mode:
If "workshop mode" is selected via the selector switch on the controller, one wave is visible in the controller. Selection of the operating switch is used as the start criterion. After 24 hours, permeate is produced over time. The workshop mode prevents germs from infecting the system, thereby ensuring a constant permeate quality.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
13
Mobile reverse osmosis system
AVRO-flex 400
14
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
1 Fine filter incl. pressure reducer
2 Inlet solenoid valve
Mobile reverse osmosis system
AVRO-flex 400
Pressure reducer preset to 2.5 bar, incl. pressure gauge.
During the permeate production, this valve is always open. Following the system stop (tank full), the valve remains open for the programmed flushing time of the membrane. Visual indica-
3 Pressure switch for minimum pressure of highpressure pump.
4 Flushing solenoid valve
To prevent the high-pressure pump from running dry. Switches
Opens after the pressure switch “switch-off pressure” has reached the set pressure. The solenoid valve also opens in the event of system malfunctions and always in conjunction with the
5 Needle valve, concentrate To set the feed water-dependent "concentrate" volume flow to the drain. During permeate production, this water constantly flows to the drain.
6 High-pressure pump Pump unit that generates the required operating pressure for the membrane and for the filling of heating water systems.
7
8
9
10
Membrane
AVRO treatment unit
Control unit
Flow sensor, concentrate
Reverse osmosis membrane to generate the permeate.
AVRO treatment unit to generate seed crystals.
Microprocessor controller that in conjunction with the respective units, regulates the permeate production and the supply of consumers downstream.
Records the concentrate volume and sends pulses to the controller. Visual indication of the concentrate volume in the con-
11 Flow sensor, permeate Records the permeate volume and sends pulses to the control-
12 Diaphragm expansion tank Permeate buffer to reduce the switching operations.
13 Pressure switch switch-off pressure
Switches the reverse osmosis on when water is required, and off again after water withdrawal ends.
14 Connection ¾“ (DN 20) male thread or GEKA
Concentrate to drain.
15 Connection ¾“ (DN 20) male thread or GEKA
Feed water.
Permeate/consumer. 16 Connection ¾“ (DN 20) male thread or GEKA
17 Control valve for operating pressure with pressure gauge
To set the operating pressure, with pressure gauge as visual indicator.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
15
Mobile reverse osmosis system
AVRO-flex 400
16
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
3 | Technical specifications
Table C-1: Technical specifications Mobile reverse osmosis system
AVRO-flex 400
Connection data
Nominal connection diameter of feed water pipe
Nominal connection diameter of permeate outlet
Nominal connection diameter of concentrate outlet
Min. drain connection required
Connected load, approx.
Power supply
Protection/protection class
Performance data
Permeate output at a feed water temperature of 10 °C / 15 °C
[kW]
[V/Hz]
[l/h]
Inlet flow pressure of feed water, min.
Nominal pressure
[bar]
Salt rejection
Total salt concentration of the feed water as NaCl max. [ppm]
Concentrate volume flow (at 15 °C) [l/h]
3/4“ (DN 20) male thread
3/4“ (DN 20) male thread
3/4“ (DN 20) male thread
DN 50
1.8
230/50
IP 54/I
340/400
2.5
PN 16
95 - 99 %
1000
400 1)
Feed water volume flow
(fresh water 15 °C) at a recovery of 50 %, max.
Recovery
Max. pressure of permeate into the heating system
Dimensions and weights
Dimensions (w x d x h)
Empty weight, approx.
Operating weight, approx.
Ambient data
Feed water temperature, min./max.
Ambient temperature, min./max.
[l/h]
[%]
[bar]
[mm]
[kg]
[kg]
[°C]
[°C]
Order no.
1) After a water analysis, the technical service can set a higher recovery.
2) If the feed water temperature is > 20 °C, special system dimensioning is required.
800
50
3.5
700 x 600 x 1450
70
80
10/30 2)
5/35
752 250
Note: Based on the permeate output of the reverse osmosis, a max. pressure of 3.5 bar can be reached. With increasing counter-pressure, the continuous permeate output will decrease.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
17
Mobile reverse osmosis system
AVRO-flex 400
4 | Intended use
The reverse osmosis system AVRO-flex 400 is designed for the demineralisation of drinking water and for the filling of heating systems / district heating networks and other systems with fully demineralised water as per the stipulations of VDI 2035, sheets 1 and 2.
If the demineralised water as per VDI 2035 is used to fill systems <
0.11°dH (0.196 °f; 0.0196 mmol/l), it may - subject to the feed water - be necessary to install a desaliQ:BA mixed bed cartridge downstream.
The continuous permeate output of the system is subject to the temperature and is defined at 15 °C. As the feed water temperature rises and falls, the permeate outputs can decrease by up to 3% per °C (falling temperature) or rise by the same amount (rising temperature).
The system is adjusted to the permeate requirements to be expected at the installation site, it is not suitable for major deviations.
The system may only be operated if all components are installed properly. Safety devices must NEVER be removed, bridged or otherwise tampered with.
Intended use of the device also implies that the information contained in this operation manual and all safety guidelines applying at the installation site be observed. Furthermore, the maintenance and inspection intervals have to be observed.
The reverse osmosis system AVRO-flex 400 is exclusively designed for use in the industrial and commercial sector.
4.1 Standstill of the system
If the system is out of operation for more than 14 days, the reverse osmosis system must be preserved by Grünbeck's technical service/ authorised service company. The maximum time, the system can remain in the preserved condition is 6 months.
In case the downtime is longer, the system must be preserved again in regular intervals by Grünbeck's technical service/authorised service company. Prior to resuming operation, the preserving agent must be flushed from the system.
18
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
5 | Application limits
With regard to the application of the mobile reverse osmosis system
AVRO-flex 400, the limit values for admissible substances contained in water which are stipulated in the German Drinking Water Ordinance do represent the upper limits for the system.
< 22° dH (39.2 °f; 3,92 mmol/l) without water analysis
Free chlorine not detectable
Iron < 0.10 mg/l
Manganese < 0.05 mg/l
Silicate < 15 mg/l
Chlorine dioxide not detectable
Turbidity < 1 FTU
Colloid index < 3
pH range 3 - 9
A water analysis is required in case of a total hardness > 22 °dH or sulphate > 500 mg/l.
Note : The permeate originating from the reverse osmosis system is not potable but requires additional treatment (blending, hardening) if it is to be used as drinking water.
Attention!
In case of an admissible excess of the sulphate concentration due to geogenic conditions, the recovery with regard to the standard settings according to layout might need to be reduced.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
19
Mobile reverse osmosis system
AVRO-flex 400
6 | Scope of supply
6.1 Standard equipment
Mobile, stand-alone aluminium rack to house all aggregates and control elements.
Microprocessor controller with LC display, voltage-free collective fault signal and voltage-free signal contact (maintenance interval, various pre-warnings), installed in a switch cabinet. Selector switch for operating modes - filling mode - workshop mode.
Centrifugal pump made of stainless steel with motor as high pressure pump to supply the membrane, incl. control valve for operating pressure and pressure gauge.
Adjustable pressure switch and diaphragm expansion tank to supply consumers downstream.
Hydro distributor block for the water supply within the membrane system. Integrated valves and measuring instruments for easier system calibration.
Fine filter with integrated pressure reducer, preset to 2.5 bar.
Ultra-low pressure reverse osmosis membranes incl. pressure pipe.
AVRO treatment unit, installed in a pressure pipe made of highstrength PE.
Flow sensor to measure the volume of the system flows permeate and concentrate.
Two pressure-resistant, metal fabric hoses and GEKA couplings.
¾" double nipple for connection to a desliQ:BA mixed bed cartridge.
Operation manual.
20
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
6.2 Optional accessories
Note: It is possible to retrofit existing systems with optional components. Please contact your local Grünbeck representative or
Grünbeck’s headquarters in Hoechstaedt for more information.
Order no.
126 400 The safety device protectliQ:A20 is a product to protect one- and two-family homes from water damage.
For more sizes, please inquire.
GENO-therm filling device Basic
Consisting of: Dirt trap, shut-off flap, system separator acc. to DIN EN 1717, adjustable pressure reducer (0.2 - 4 bar), water meter, housing insulation and fastening material.
Filling group
Consisting of: Dirt trap for coarse dirt, shut-off flap, system separator, pressure reducer, nonreturn valves. desaliQ:BA mixed bed cartridge
Mixed bed cartridge for full demineralisation
(max. 400 l/h) by means of ion exchange, installed downstream of the AVRO-flex 400.
GENO-therm filling cartridge 110
Full demineralisation cartridge for full demineralisation by means of ion exchange, installed downstream of the AVRO-flex 400.
Drain connection DN 50 acc. to DIN EN 1717
Connection material for DIN-compatible waste water connection DN 50
707 120
707 700
707 450
(for larger capacities, please inquire)
707 150
187 840
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
21
Mobile reverse osmosis system
AVRO-flex 400
6.3 Consumables Only use genuine consumables in order to ensure the reliable operation of the system.
Order no.
103 061 GENO-replacement filter element with protective cylinder
Packing unit: 2 pcs
Reverse osmosis membrane
Packing unit: 1 pc
AVRO treatment unit with seals
Packing unit: 1 pc
Water test kit "Total hardness“
Packing unit: 1 pc
Water test kit "Carbonate hardness“
Packing unit: 1 pc
752 685e
720 050
170 187
170 169
6.4 Wearing parts Seals and valves are subject to a certain wear and tear. Wearing parts are listed below.
Note: Although these parts are wearing parts, we grant a limited warranty period of 6 months. a. Solenoid valves, control valve for concentrate, seals b. High-pressure pump
Fig. C-4: Valves Fig. C-5: High-pressure pump
22
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
D Installation
Mobile reverse osmosis system
AVRO-flex 400
1 | General installation instructions
The installation site must provide adequate space. A foundation of a sufficient size and adequate load carrying capacity has to be provided. The required connections must be provided prior to the installation of the system. For dimensions and connection data, please refer to table C-1.
Note: For the installation of systems with optional accessories (refer to Chapter C, item 6.3), also observe the operation manuals supplied with these components.
1.1 Water connection Certain binding rules must always be observed when installing a mobile reverse osmosis system AVRO-flex 400. Additional recommendations are given in order to facilitate the handling of the system. The installation instructions described below are also illustrated in fig. E-2.
Binding rules
The installation of a mobile reverse osmosis system AVRO-flex 400 represents a major interference with the drinking water system.
Therefore, only authorised experts may install such systems.
Observe local installation guidelines and general regulations.
Install a drinking water filter (e. g. BOXER KD) upstream of the system.
Install a system separator upstream – not required when using a
GENO-therm filling device.
Install an activated carbon filter upstream, if required.
Provide a drain connection (minimum DN 50) to discharge the concentrate.
Note: If the concentrate is directed to a lifting system, the delivery rate of the lifting system should at least be 800 l/h.
Warning! The installation site must have a floor drain. If no floor drain is available, an adequate safety device needs to be installed (refer to
Chapter C, item 6.3 “Optional accessories”).
Warning!
Floor drains that discharge to a lifting system do not work in case of a power failure.
Recommendation
If the mobile reverse osmosis system AVRO-flex 400 is not connected to the optional filling device GENO-therm, a sampling valve should be installed directly upstream and downstream of the mobile reverse osmosis system AVRO-flex 400. This simplifies the sampling for the regular quality control (functional check).
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
23
Mobile reverse osmosis system
AVRO-flex 400
E Start-up
The work described below may only be performed by trained experts.
We recommend having Grünbeck‘s technical service/authorised service company start up the system.
1 | How to connect the system to the water supply
Connect the feed water / raw water hose to the system
(refer to fig. E-1, item 3).
Connect the permeate hose to the system and to the system to be filled (refer to fig. E-1, item 2).
Connect the concentrate hose to the system (refer to fig. E-1, item
1). Run the hose with a gradient to the drain and connect in accordance with EN 1717 (free outlet).
24
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Fig. E-1: Connections of mobile reverse osmosis system AVRO-flex 400
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
25
Mobile reverse osmosis system
AVRO-flex 400
2 | How to flush the system
For the duration of storage and transport, the membrane is protected by means of a preserving agent. This preserving agent must be flushed off before starting up the system for the first time. To do so, the concentrate hose (refer to fig. E-1, item 1) and the permeate hose
(refer to fig. E-1, item 2) have to be routed to the drain.
2.1 How to flush off the preserving agent
Note: For more detailed information on the handling of the control unit, refer to Chapter F.
Switch on the mains switch and switch the operating mode selector switch to the "OFF" position.
Open both solenoid valves ("DEAERATE") via Code 113, parameter
EnL: 1 and flush off the preserving agent from the system for a duration of 30 min. To do so, open parameter with P button, set ENL: 1 with ▲ button and confirm with P button.
Complete program step “DEARATE”: Open parameter with P button, set EnL:0 with ▼ button and confirm with P button.
Exit the “EnL” program by simultaneously pressing the buttons ▼and
▲.
2.2 Filling mode
In filling mode (refer to fig. E-2), e.g. heating / cooling water systems, direct the hose supplied with the system from the permeate connection of the reverse osmosis system to the filling valve or to the GENO-therm filling device.
The pressure switch is set to a switch-off pressure of 2.5 bar
= system pressure. If a higher or lower system pressure is required, this can be set via the pressure switch (refer to fig. C-2, item 13).
Then switch on the reverse osmosis system via the selector switch at the controller housing. The system produces permeate. Close the filling valve and monitor at which pressure the system switches off. Use the adjusting screws to set to the desired switch-off pressure/system pressure.
Note: Based on the permeate output of the reverse osmosis, a max. pressure of 3.5 bar can be reached. With an increasing counter-pressure, the continuous permeate output will decrease.
26
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Off
Workshop Filling mode mode
Mobile reverse osmosis system
AVRO-flex 400
1
2
Drinking water filter BOXER KD (option)
Mobile reverse osmosis system AVRO-flex
3
4
GENO-therm filling device Basic (option)
GENO-therm filling cartridge (option) 1)
Fig. E-2: Installation drawing of mobile reverse osmosis system AVRO-flex 400 - filling mode
1) Note: If the demineralised water as per VDI 2035 is used to fill systems < 0.11°dH (0.196 °f; 0.0196 mmol/l), it may – subject to the feed water – be necessary to install a GENO-therm filling cartridge 110
(order no. 707 150) downstream.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
27
Mobile reverse osmosis system
AVRO-flex 400
2.3 Workshop mode
To prevent damage to the membrane due to germs (bio-fouling), the mobile reverse osmosis system AVRO-flex 400 must be run in workshop mode during the entire periods of standstill (refer to fig. E-3). In this case, the permeate line as well as the concentrate line are connected as per DIN EN 1717. In the workshop mode, water is rejected for a certain time set in the controller (factory setting 15 min.) every day.
Note: The system must be connected to the power supply as well as to the water/waste water network for the entire period of standstill
(transports up to 48 h excluded).
Note: open!
If installed, the shut-off valve on the permeate side must be
Off
Workshop Filling mode mode
1
2
BOXER KD
Euro system separator GENO-DK 2-Mini
3 Mobile reverse osmosis system AVRO-flex 400
Fig. E-3: Installation drawing of mobile reverse osmosis system AVRO-flex 400 - workshop mode
28
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
F Operation (control unit)
1 | Preface
Mobile reverse osmosis system
AVRO-flex 400
Note: Instructions in bold are absolutely essential to ensure that work can continue. All other instructions can be ignored if the value shown in the display remains unchanged.
Settings in the technical service programming level may only be performed by Grünbeck's technical service/authorised service company or by persons expressly authorised by Grünbeck.
Warning!
Incorrect settings may lead to hazardous operating conditions which cause injury, health problems or damage to property.
The operation manual must be strictly adhered to! Only make the settings described there!
Fig. F-1: Control unit
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
29
Mobile reverse osmosis system
AVRO-flex 400
2 | How to operate the control unit
Symbols displayed:
Operation indicator
Appears when the system is switched on via the selector switch (workshop or filling mode)
High-pressure pump
Appears when the high-pressure pump produces permeate.
Appears, without action/function
Inlet solenoid valve (feed water)
Appears when permeate is being produced or during system flushing.
Flushing solenoid valve
Appears when the system flushing is in progress
±
Indication of operating mode
Top wave: system runs in filling mode
Bottom wave: system runs in workshop mode
No wave: system is switched off
Bars for water meter pulses
Flash with every 5th pulse of the w ater meters for p ermeate or c oncentrate
Indicates the state of the pressure switch for minimum pressure (bar appears when there is pressure) and operational release (bar appears when permeate is being delivered into the heating system)
AVRO treatment module is active (always at the same time permeate is being delivered into the heating system)
Function of buttons
Basic function:
Acknowledgement of malfunctions.
Access to time programming
(keep button pressed > 2.5 sec).
+
+
Display operating values of Info level.
Access to the code-protected programming levels
(Code request C 000).
Fig. 2 Operating panel, control unit AVRO-flex 400
Numeric display
Indicates the time and operating parameters in the Info level
Indicates the parameters of the Code levels
Indicates symbols in addition to the fault message
Bars for signal and fault signal contact
appears when the maintenance interval has elapsed
Er appears with all malfunctions Er0, Er1, Er4 and Er8
P
Flashes when the pressure switch for minimum pressure drops out during permeate production (lack of feed water pressure)
Extended function in programming levels:
Open parameter for editing (value is flashing).
Save and close parameter.
Decrease numerical value.
Return to previous menu item.
Increase numerical value.
Go to the next menu item.
Close open parameters without saving
(previous value is maintained).
Return to basic display time.
30
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Operating modes selector switch
Workshop mode
Filling mode
Off
2.1 Reading the operating status
When the system is switched on (symbol ), permeate is produced for 15 minutes at the same time every day.
When the system is switched on (symbol l ), it produces subject to the pressure switch for operational release.
Various operating parameters can be displayed within the Info level.
The Info level is accessed by pressing the ▲ button.
Button Display
00:00
Parameters
Basic display, time
Pressing this button for the first time switches the system on, if still necessary!
365 Remaining time of maintenance interval [d]
3000 Remaining time of AVRO maintenance interval [h]
P0200 Permeate flow [l/h] c0200 Concentrate flow [l/h]
A 050 System recovery [%] l.200 Actual current of AVRO treatment module [mA]
S00.00 Sum of permeate [m³] during filling mode for billing. Counter reading is deleted again in this display by the combination of buttons P and ▲
(> 5 sec).
2.2 How to set the time
Requirement:
The basic display time is currently being indicated.
1. Press button P for > 2.5 seconds. Only the hours 00: will still be displayed
2. Press P button to change the hours (value is flashing, now set the desired value with buttons ▼ or ▲ and save with the P button) or press▲ button to advance to the minutes :00
3. Press P button to change the minutes (value is flashing, now set the desired value with buttons ▼ or ▲ and save with the P button)
4. Return to the basic display time by simultaneously pressing buttons
▼ and▲
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
31
Mobile reverse osmosis system
AVRO-flex 400
2.3 Access to the programming levels - change parameters
1. Simultaneously pressing the buttons P and ▼ (> 1 sec) causes the code request C 000 to appear.
2. Set the required code with buttons ▼ or ▲ and confirm with P button.
3. Within the programming level, select the desired parameter with buttons ▼ or ▲and open it for editing with the P button (value starts flashing).
4. Change the parameter setting to the desired value with buttons
▼ or ▲ .
5. Save the new parameter setting with the P button (value stops flashing) or reject the change by simultaneously pressing the buttons ▼ and ▲, and close the parameter again (value stops flashing, previous setting remains saved).
6. Return to the basic display time by simultaneously pressing buttons
▼ and ▲.
7. If no button is pressed within a parameter level for more than 5 minutes, the system automatically returns to the basic display time.
Any open parameters (value flashing) are closed and the previously saved value is kept.
2.4 Software version Code 999
Display
P1.25
Parameters
Software version of RO-matic controller
32
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
3 | Programming levels
3.1 Input logic Code 113
Display / factory setting
EHP: 2
Parameters
Type of contact
Pressure switch for minimum pressure
(high-pressure pump)
Setting range
0 ... 3
Comment
0 = Normally open contact (NOC)
1 = Normally closed contact (NCC)
2 = NOC with automatic restart
3 = NCC with automatic restart
1)
1)
EPS: 1 Type of contact
PS pressure switch
0 ... 1 0 = NOC (setting for systems without pressure switch
1 = NCC (setting for systems with pressure switch)
EnL: 0 Flush system (inlet and flushing solenoid valves)
0 ... 1 1 = Open solenoid valves (only possible if the system is switched off)
0 = Close solenoid valves again
1) If error Er 1 occurs during ongoing permeate production (pressure switch minimum pressure of high-pressure pump), the system attempts a restart at the following intervals:
5 ... 10 ... 20 ... 40 ... 80 ... 160 minutes
If sufficient pressure is present, permeate is produced until the pressure switch for operational release responds and the error is acknowledged automatically.
3.2 System parameters Code 290
Display / factory setting
5. 2
D. 15
E. 0
Parameters Setting range
0 ... 2
Comment
Reaction to return of power for error Er 0
(power failure > 5 minutes)
0 = Irrespective of whether the system was switched on or off prior to the power failure, it remains switched off after power is restored and error Er 0 is emitted (symbol is still switched on)
1 = Error Er 0 is deactivated
2 = After power is restored, the system is switched on or off like prior to the power failure, and error Er 0 is emitted
Run time of workshop mode [minutes]
15 ... 99 In workshop mode, permeate is produced for this time at a 24 h interval after the system is switched on. Operation is irrespective of the status of the pressure switch for operational release.
Reserved function 0 .... 1 0 = Factory setting
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
33
Mobile reverse osmosis system
AVRO-flex 400
3.3 Reference values / times Code 302
Display / factory setting
1. 2
Parameters
2,0000
3,0000
Operating mode
AVRO-flex 400
Reference value permeate flow [l/h]
Reference value concentrate flow [l/h]
Setting range
Display only
0 ... 9999
0 ... 9999
6. 5.0
7. 3
9. 5
A. 3 b. 000 d. 40
E. 3000
F. 03
G. 0.0
Comment
Note : The parameters 2. and 3. must be measured and gauged while the high-pressure pump is running.
Duration of flushing
[minutes]
System run-down time [seconds]
Start-up delay of high-pressure pump
[seconds]
Delay time of pressure switch of highpressure pump
[seconds]
Duration of maintenance interval [days]
0 ... 99.9 Inlet (feed water) and flushing solenoid
1 ... 99
3 ... 99
3 ... 99 valves.
After pressure switch for minimum pressure responds = operational release.
After inlet solenoid valve opens.
Minimum AVRO treatment current
[mA]
AVRO maintenance interval [h]
Delay time of PS pump after start of permeate production
[sec]
Flushing delay after activation of pressure switch for operational release [minutes]
0 ... 365 0 = Service interval deactivated.
Acknowledgement of the maintenance interval (bar above the "screw wrench" symbol) by reprogramming of the maintenance interval.
0 .... 200 Treatment current is requested at the end of the permeate production. In case the threshold programmed there is undershot,
Er4 is emitted.
0.3000 Acknowledgement of the maintenance interval by reprogramming the value.
1 .... 99 Without function in case of AVRO-flex 300
0.0 .... 99.9 Filling mode: If the pressure switch has responded uninterrupted this long, the system flushes. If the pressure switch drops out, the permeate production starts.
34
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
3.4 Error memory / water volumes Code 245
Display
1.Er_x
...
9.Er_y
A.0372
Parameters
Error memory of the 9 most recent errors
Comment
1.Er_ = most recent error
9.Er_ = least recent error ▼
I.0085
L. 00
Concentrate volume produced so far [m³]
3.5 Diagnosis Code 653 b.0231 c.0097 d. 00
E.0068
F. 00
G.0103
H. 00
Operating time [hours] in workshop mode
Run time filling mode
[days]
Run time HP pump
[hours]
No function
Permeate volume produced so far [m³]
Time during which the HP pump is operating in workshop mode.
Filling mode c = thousands … ones d = ten thousands
No function
No function
G = thousands … ones
H = ten thousands
I = thousands … ones
L = ten thousands
In this code of the customer service programming level, it is possible to request the states of the inputs and to switch the outputs separately.
Access requirement: System is switched off via ▼ button.
E.PA:
E.Pb:
E.Pc:
E.HP:
E.PS:0
E.CL:
A.St:0
A.YE:0
A.YS:0
A.Yr:0
A.HP:0
A.PS:0
A.PF:0
Motor protection switch of highpressure pump
Switch for workshop mode
Switch for filling mode
Pressure switch for minimum pressure of high-pressure pump
Pressure switch
System ON - Filling mode
Input always 1
Motor protection switch PS pump
Physical state of the input signals:
0 = no voltage applied
1 = 24 VDC voltage applied
Voltage-free fault signal contact
Inlet solenoid valve
Flushing solenoid valve
Physical state of the output signals:
Reserved
High-pressure pump
0 = output switched off
1 = output switched on
No function
Voltage-free signal contact
Attention!
Make sure there is an inflow of water when switching the pumps - risk of running dry!
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
35
Mobile reverse osmosis system
AVRO-flex 400
4 | Wiring diagram of mobile reverse osmosis system AVRO-flex 400
36
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
37
Mobile reverse osmosis system
AVRO-flex 400
5 | Operation of reverse osmosis system AVRO-flex 400
5.1 How to set the system recovery
A certain part of the feed water must be rejected in order to prevent the membrane from clogging due to scaling. The ratio of the produced permeate volume to the feed water volume is called recovery.
5.1.1 How to set the permeate volume
Switch on the system via the ▲ button at the control unit.
With the control valve for the operating pressure (refer to fig. F-3, item
1), throttle the high-pressure pump in a way that the system-specific permeate flow of 400 l/h is attained.
Note: The current permeate flow can be displayed via the controller
(refer to Chapter F, paragraph 2.1 “Reading the operating status”).
1 Control valve for operating pressure
Fig. F-3: Control valve for operating pressure at the high-pressure pump
38
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
5.1.2 How to set the concentrate volume
Set the concentrate flow at the concentrate needle valve (refer to fig.
F-4, item 1).
To safeguard against the valve changing its position, it features a safety screw which is centrally located at the green cap.
The concentrate flow in a standard system has to be set in a way, that a recovery of 50 % is attained (400 l/h of permeate flow, 400 l/h of concentrate flow).
Note: The current concentrate flow and the recovery can be displayed via the controller (refer to Chapter F, paragraph 2.1 “Reading the operating status”).
Attention!
If the set recovery is not met, scaling (precipitation of dissolved salts) occurs on the reverse osmosis membrane.
Fig. F-4: Needle valve, concentrate
Example for the calculation of the recovery
Recovery [%]
Permeate flow
Permeate fow [l/h]
[l/h] x 100%
Concentrat e flow [l/h]
Concentrat e flow [l/h]
Permeate flow [l/h] x
Concentrat e recovery
100
[%]
Permeate flow [l/h]
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
39
Mobile reverse osmosis system
AVRO-flex 400
G Troubleshooting
Even carefully designed and manufactured technical systems that are operated properly, may experience malfunctions. Table G-1 provides an overview of possible problems that may occur during the operation of the systems and indicates the causes and their elimination.
The systems are equipped with an error detection and reporting system. If an error message is displayed:
1. Press P button (= acknowledge malfunction).
2. Watch the display.
If the message reappears, compare it with table G-1.
3. If necessary, notify Grünbeck’s technical service.
Note: The technical service definitely must be notified (refer to gruenbeck.de) in case of malfunctions that cannot be remedied with the information given in table G-1! When contacting the technical service, please indicate the system designation, serial number and the error message displayed.
Table G-1: Troubleshooting
This is what you observe This is the cause
Water quality deteriorated by 50 %.
Membrane clogged.
Solenoid valve does not open .
Solenoid valve does not close .
This is what to do
Replace or flush the membrane 1) .
Feed water values deteriorated. Check feed water values.
Coil defective or fuse F1 blown on circuit board.
Replace coil or fuse T1A.
Valve contaminated. Clean valve.
Bar appears in the display above Symbol
Close.
High-pressure pump:
Thermostat contact has responded, pump has overheated.
Upstream hardness monitoring or water treatment locks the system.
Bar appears in the display above screw wrench symbol (without further indications of a malfunction).
Service interval has elapsed.
Wait until the pump has cooled down again, the system will then automatically continue to produce.
Inspect system installed upstream.
Have maintenance performed.
40
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Continuation Table G-1: Troubleshooting
This is what you observe This is the cause
Er 0 Power failure > 5 minutes
Refer to Chapter F / paragraph
3.2 / parameter A:
Depending on the setting, the system either continues to run or remains switched off.
Er 1
This is what to do
Check power supply for failures.
Pressure drop at pressure switch for minimum pressure of highpressure pump:
Restore primary pressure of feed water.
Refer to Chapter F / paragraph
3.1 / parameter EHP:
Depending on the setting, the system has previously undertaken 6 unsuccessful start attempts.
Er 4
Er 5
Minimum AVRO treatment current undershot.
Have the AVRO treatment module replaced immediately by
Grünbeck’s technical service/authorised service company. The malfunction can be acknowledged once and a maximum of 5 m³ of permeate can still be produced.
Gauge and reset the system.
Er 6
System recovery too high:
Recovery was above 60 % for more than 1 h
AVRO maintenance interval has elapsed.
Er 7
Er 8
Er 9
No function
Motor protection switch of highpressure pump has responded.
In workshop mode, a shut-off valve is closed on the permeate side.
Notify Grünbeck’s technical service/authorised service company to have the AVRO treatment module replaced promptly.
Notify Grünbeck’s technical service/authorised service company to have the high-pressure pump checked and replaced, if necessary
Open shut-off valve and acknowledge malfunction.
1) Separate flushing instructions for membranes are available for authorised service personnel, order no. 700 950.
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
41
Mobile reverse osmosis system
AVRO-flex 400
H Maintenance and care
1 | Basic information
In order to guarantee the reliable function of the systems over a long period of time, some maintenance work has to be performed at regular intervals. All regulations and guidelines which apply at the installation site must be strictly adhered to.
Check the quality and the system volume flows every day.
Maintenance has to be performed by Grünbeck’s technical service/authorised service company or by a specialised company.
Maintenance is subject to the load but at the latest has to be performed once a year.
An operation log and the corresponding test log must be kept in order to document the maintenance work performed.
Note: By concluding a maintenance contract you ensure that all maintenance work will be performed in due time.
The maintenance work performed must be documented in the checklist, refer to appendix "Operation log".
2 | Inspection (functional check)
You may perform the daily inspections yourself.
Please refer to the following summary for the tasks to be performed within the framework of an inspection.
Summary: Inspection work
Read the recovery
Note: Minor deviations are normal and cannot be prevented technically. In case of considerable deviations from the standard, notify
Grünbeck's technical service.
Take the remaining time of the AVRO treatment unit’s maintenance interval into consideration (refer to Chapter F, paragraph 2.1). If the remaining time is < 100 hours, notify Grünbeck’s technical service/ authorised service company to have the treatment module replaced.
Take the remaining time of the maintenance interval [d] into consideration (refer to Chapter F - paragraph 2.1 “Reading the operating state”). In case the remaining time of the maintenance interval is <
30 days, inform Grünbeck's technical service about the impending service.
42
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
Mobile reverse osmosis system
AVRO-flex 400
Check the system’s tightness to the drain. Solenoid valves are not tightened, visible in the display (refer to fig. F-2, items 9 and 10). In this state, no water must creep to the drain.
3 | Maintenance
Note : Leaky solenoid valves will cause the system to consume more water. The recovery will be reduced.
According to DIN 1988 part 8 / A 12, maintenance work at the systems may only be performed by Grünbeck’s technical service/authorised service company or an approved specialist company.
For this kind of systems, an operation log - a checklist has to be kept.
In this operation log, the customer service technician records all maintenance and repair work performed. In case of malfunctions, this log helps to identify possible sources of error. In addition, the log documents the proper system maintenance.
Note: Make sure that all maintenance work is recorded in the operation log as well as in the corresponding test log.
Summary: Maintenance work
Replace the filter element.
If necessary, replace the filter element of the activated carbon filter.
Check the permeate quality; flush or replace the membrane, if necessary. So-called flushing instructions (order no. 700 950) are available for authorised service personnel.
Replacement of AVRO treatment unit, if necessary
(limit value: 3000 h or 5 years)
Solenoid valves – check function, clean if necessary.
Check the flow volumes and recalibrate the water meters.
Check the state of the entire system and check the entire system for tightness.
Mechanical resp. electrical functional and performance check of all aggregates (pumps, valves).
Prepare a written maintenance log on the state and function of the system and the maintenance work performed, incl. evaluation and assessment of the operating values and water analysis results.
Note: The maintenance work performed must be documented in the checklist, refer to appendix "Operation log".
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
43
Mobile reverse osmosis system
AVRO-flex 400
3.1 Operation log The operation log is located in Chapter H, paragraph 4 of this operation manual. When starting up the system, make sure to record all data on the cover sheet of the operation log and fill in the first column of the checklist.
The customer service technician will fill in a column of the check list whenever maintenance is performed. This document provides evidence of proper maintenance.
44
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
4 | Operation log
Mobile reverse osmosis system
AVRO-flex 400
Customer
Name: .......................................................................................
Address: ...................................................................................
.................................................................................................
.................................................................................................
Mobile reverse osmosis system AVRO-flex 400
Order no. 752 250
Serial number
.................................................................................
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
45
Mobile reverse osmosis system
AVRO-flex 400
Maintenance work on mobile reverse osmosis system AVRO-flex 400
Checklist
Please enter measured values. Confirm checks with OK or enter repair work performed.
Maintenance performed without replacement of module
Maintenance performed with replacement of module
Maintenance performed with replacement of AVRO treatment module
Module no. .......................... Treatment module no. …………………..
Measured values
Water volumes and water qualities before the replacement of the module / after the replacement of the module or in case of maintenance
Pump pressure
[bar]
before/after
Conductivity
[ S/cm]
before/after
Total hardness
[ dH]
before/after
Carbonate hardness:
[ KH]
Temperature
[ C]
Volume flow
[l/h]
Recovery
[%]
before/after before/after before/after
/
Feed water
/ / / /
Permeate
/ / / /
Concentrate
/ / / / . . . . . % / . . . . %
Confirmation Remarks
Water meter reading upstream of the system [m³]
Inlet water pressure (2.5 - 4 bar) checked
Filter elements replaced
(incl. activated carbon)
Settings of electronics checked
Water meter configured
(code 302, par. 2 + 3)
Run time in workshop mode
(code 290, par. d)
AVRO treatment current (Chapter F, 2.1)
Operating period in workshop mode
(code 245, par. A)
Run time in filling mode
(code 245, par. b)
Run time of high-pressure pump
(code 245, par. c/d )
No function
(code 245, par. E/F )
Permeate volume produced
(code 245, par. G/H )
Concentrate volume generated
(Code 245, par. I/L )
Error memory
(code 245, par. 1..9
)
[l/h]
[min.]
[mA]
[h]
[T]
[h]
[h]
[m³]
[m³]
[Er]
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
46
All electrical lines checked for external damage
All hoses and connections checked for external damage
Inlet solenoid valve checked for tightness - cleaned, if necessary
Pressure switch of high-pressure pump checked for function
Pressure switch - switching hysteresis
Mobile reverse osmosis system
Confirmation Remarks
AVRO-flex 400
Pressure booster checked/adjusted
Visual check of the control unit
System checked for tightness
Miscellaneous
Remarks: ........................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
Start-up technician / CS technician: .............................................
Company: ....................................................................................
.....................................................................................................
.....................................................................................................
Work time certificate (no.) ............................................................
Date/signature ..............................................................................
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
47
Mobile reverse osmosis system
AVRO-flex 400
Maintenance work on mobile reverse osmosis system AVRO-flex 400
Checklist
Please enter measured values. Confirm checks with OK or enter repair work performed.
Maintenance performed without replacement of module
Maintenance performed with replacement of module
Maintenance performed with replacement of AVRO treatment module
Module no. .......................... Treatment module no. ………………
Measured values
Water volumes and water qualities before the replacement of the module / after the replacement of the module or in case of maintenance
Pump pressure
[bar]
before/after
Conductivity
[ S/cm]
before/after
Total hardness
[ dH]
before/after
Carbonate hardness:
[ KH]
Temperature
[ C]
Volume flow
[l/h]
Recovery
[%]
before/after before/after before/after
/
Feed water
/ / / /
Permeate
/ / / /
Concentrate
/ / / / . . . . . % / . . . . %
Confirmation Remarks
Water meter reading upstream of the system [m³]
Inlet water pressure (2.5 - 4 bar) checked
Filter elements replaced
(including activated carbon)
Settings of electronics checked
Water meter configured
(code 302, par. 2 + 3)
Run time in workshop mode
(code 290, par. d)
AVRO treatment current (Chapter F, 2.1)
[l/h]
[min.]
[mA]
Operating period in workshop mode
(code 245, par. A)
Run time in filling mode
(code 245, par. b)
Run time of high-pressure pump
(code 245, par. c/d )
No function
(code 245, par. E/F )
Permeate volume produced
(code 245, par. G/H )
Concentrate volume generated
(Code 245, par. I/L )
Error memory
(code 245, par. 1..9
)
[h]
[T]
[h]
[h]
[m³]
[m³]
[Er]
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
48
All electrical lines checked for external damage
All hoses and connections checked for external damage
Inlet solenoid valve checked for tightness - cleaned, if necessary
Pressure switch of high-pressure pump checked for function
Pressure switch - switching hysteresis
Mobile reverse osmosis system
Confirmation Remarks
AVRO-flex 400
Pressure booster checked/adjusted
Visual check of the control unit
System checked for tightness
Miscellaneous
Remarks: ........................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
Start-up technician / CS technician: .............................................
Company: ....................................................................................
.....................................................................................................
.....................................................................................................
Work time certificate (no.) ............................................................
Date/signature ..............................................................................
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
49
Mobile reverse osmosis system
AVRO-flex 400
Maintenance work on mobile reverse osmosis system AVRO-flex 400
Checklist
Please enter measured values. Confirm checks with OK or enter repair work performed.
Maintenance performed without replacement of module
Maintenance performed with replacement of module
Maintenance performed with replacement of AVRO treatment module
Module no. .......................... Treatment module no. ……………….
Measured values
Water volumes and water qualities before the replacement of the module / after the replacement of the module or in case of maintenance
Pump pressure
[bar]
before/after
Conductivity
[ S/cm]
before/after
Total hardness
[ dH]
before/after
Carbonate hardness:
[ KH]
Temperature
[ C]
Volume flow
[l/h]
Recovery
[%]
before/after before/after before/after
/
Feed water
/ / / /
Permeate
/ / / /
Concentrate
/ / / / . . . . . % / . . . . %
Confirmation Remarks
Water meter reading upstream of the system [m³]
Inlet water pressure (2.5 - 4 bar) checked
Filter elements replaced
(including activated carbon)
Settings of electronics checked
Water meter configured
(code 302, par. 2 + 3)
Run time in workshop mode
(code 290, par. d)
AVRO treatment current (Chapter F, 2.1)
[l/h]
[min.]
[mA]
Operating period in workshop mode
(code 245, par. A)
Run time in filling mode
(code 245, par. b)
Run time of high-pressure pump
(code 245, par. c/d )
No function
(code 245, par. E/F )
Permeate volume produced
(code 245, par. G/H )
Concentrate volume generated
(Code 245, par. I/L )
Error memory
(code 245, par. 1..9
)
[h]
[T]
[h]
[h]
[m³]
[m³]
[Er]
Order no. 095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
50
All electrical lines checked for external damage
All hoses and connections checked for external damage
Inlet solenoid valve checked for tightness - cleaned, if necessary
Pressure switch of high-pressure pump checked for function
Pressure switch - switching hysteresis
Mobile reverse osmosis system
Confirmation Remarks
AVRO-flex 400
Pressure booster checked/adjusted
Visual check of the control unit
System checked for tightness
Miscellaneous
Remarks: ........................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
.......................................................................................................................................................................
Start-up technician / CS technician: .............................................
Company: ....................................................................................
.....................................................................................................
.....................................................................................................
Work time certificate (no.) ............................................................
Date/signature ..............................................................................
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
51
Advertisement