Amerex Hand Portable Water Pressure Extinguisher Owner's Manual

Amerex Hand Portable Water Pressure Extinguisher Owner's Manual

Amerex Hand Portable Water Pressure Extinguisher

The Amerex Hand Portable Water Pressure Extinguisher is a versatile and effective fire extinguishing device, designed to quickly and efficiently extinguish Class A fires involving ordinary combustibles such as wood, paper, and cloth. With its stored pressure design and easy-to-use operation, this extinguisher is ideal for a wide range of applications, including homes, offices, schools, and industrial facilities.

Key capabilities of the Amerex Hand Portable Water Pressure Extinguisher:

  • Fast and effective: Discharges a powerful stream of water to quickly extinguish flames.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Amerex Hand Portable Water Pressure Extinguisher Owner's Manual | Manualzz

OWNER’S SERVICE MANUAL

INSTALLATION, OPERATING,& SERVICING INSTRUCTIONS

NO. 05601

STORED PRESSURE STAINLESS STEEL

WATER FIRE EXTINGUISHER

MODEL 240

-

2

-

1/2 GALLON

All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire

Protection Association standard titled "Portable Fire Extinguishers", NFPA 10 and the requirements of local authorities having jurisdiction.

When maintenance is indicated it should be performed by trained persons having proper equipment. Fire extinguishers are pressure vessels and must be treated with respect and handled with care. They are mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional – your local authorized Amerex Distributor.

Amerex Corporation makes original factory parts available to insure proper maintenance – use of substitute parts releases Amerex of its warranty obligations. Amerex parts have machined surfaces and threads that are manufactured to exacting tolerances. O rings, hoses, nozzles, horns and all metal parts meet precise specifications and are subjected to multiple in house inspections and tests for acceptability.

There are substitute parts available that are incorrectly labeled as UL component parts, some are advertised as Amerex type. None of these meet UL requirements and all of them void the Amerex extinguisher warranty and UL listing. DO NOT SUBSTITUTE.

WARNING

Do not use this extinguisher on Class C fires involving energized electrical equipment,

Class D fires or any flammables that will react with water. Protect from freezing unless charged with an Amerex Model 506B Loaded Stream/Anti freeze Charge.

REFERENCES IN THIS MANUAL AVAILABLE FROM

NFPA 10 Portable Fire Extinguishers National Fire Protection Association

1 Batterymarch Park

Quincy, MA 02169 7471

CGA C 1 Methods for Hydrostatic Testing Compressed Gas Association of Compressed Gas Cylinders 14501 George Carter Way

CGA C 6 Standard for Visual Inspection Suite 103

Chantilly, VA 20151

P/N 05601

AMEREX CORPORATION – P.O. BOX 81 – TRUSSVILLE, ALABAMA 35173 0081

Phone: 205/655 3271 Fax: 800/654 5980 e mail: sales@amerex fire.com

Web Page: http://www.amerex

fire.com

06/2019

AMEREX CORPORATION DOES NOT SERVICE, MAINTAIN OR RECHARGE FIRE

EXTINGUISHERS. THE MAINTENANCE AND RECHARGE PORTION OF THIS MANUAL IS

PUBLISHED AS A GUIDE TO ASSIST SERVICE PERSONNEL IN THE INSPECTION,

MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY. NO

INSTRUCTION MANUAL CAN ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE

ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. AMEREX ASSUMES NO

LIABILITY FOR SERVICE, MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY

PUBLISHING THIS MANUAL .

INSPECTING THE EXTINGUISHER

This extinguisher should be inspected at regular intervals (monthly or more often if circumstances require) to insure that it is ready for use.

INSPECTION (NFPA 10) A “quick check” should be made of the extinguisher for the following:

1.

Located in designated place.

2.

No obstructions to access or visibility.

3.

Operating instructions on nameplate (label) and facing outward.

4.

Seals and tamper indicators not broken or missing.

5.

Determine fullness by weighing or "hefting".

6.

Examine for obvious physical damage, corrosion, leakage or clogged nozzle.

7.

Pressure gauge reading in the operable area.

MAINTENANCE – SERVICE PROCEDURE

MAINTENANCE (NFPA 10) At least once a year (or more frequently if indicated by an inspection), maintenance should be performed. Maintenance is a “thorough check” of the extinguisher. It is intended to give maximum assurance that an extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair or replacement. It will normally reveal the need for hydrostatic testing.

1.

Clean extinguisher to remove dirt, grease or foreign material. Check to make sure that the instruction nameplate is securely fastened and legible. Inspect the cylinder for corrosion, abrasion, dents or weld damage. If any of these conditions are found and you doubt the integrity of the cylinder, hydrostatically test, using the proof pressure method and a suitable cage, in accordance with CGA Pamphlet C 1 and NFPA Pamphlet 10.

2.

NOTE : When cleaning avoid use of solvents around the pressure gauge. They could seriously damage the plastic gauge face.

3.

Inspect the extinguisher for damaged, missing or substitute parts. Only factory replacement parts are approved for use on Amerex fire extinguishers.

4.

Weigh extinguisher and compare with weight printed on the Maintenance section of the nameplate (label). Recharge extinguisher if weight is not within the indicated allowable tolerances.

5.

Check the date of manufacture on the extinguisher cylinder hanger loop or on the extinguisher nameplate. Cylinder must be hydrostatically tested every 5 years to the test pressure indicated on the label.

P/N 05601 06/2019

6.

Visually inspect the pressure gauge: a.

If bent, damaged or improper gauge, depressurize and replace b.

If pressure is low, check for leaks

7.

Inspect the foot stand (base). If cracked or broken replace with proper foot stand.

8.

Check ring pin for freedom of movement by breaking the seal and removing the pin.

Replace the ring pin if bent or if removal is difficult.

9.

Inspect discharge lever for dirt or corrosion that might impair freedom of movement. Inspect carrying handle for proper installation. If lever, handle or rivets are damaged or distorted, replace with proper Amerex part (s).

10.

Remove hose assembly, inspect hose assembly for damage, replace as necessary. Blow air through hose assembly to insure passage is clear of foreign material.

11.

Examine the air pressurizing valve (Schrader) for damage. The cap should be in place to prevent leaking.

12.

Inspect the valve assembly for corrosion or damage to hose thread connections. Replace valve assembly or component parts as necessary following the proper depressurization and recharge procedures.

13.

Install hose and nozzle assembly.

14. Install new tamper seal and record service data on the extinguisher inspection tag.

15.

Rehang the extinguisher on the wall hanger bracket making sure that it fits the hanger bracket properly – replace the bracket if necessary. Note: When a Loaded Stream/Anti freeze charge is used to freeze protect this extinguisher, a complete discharge and maintenance is required annually. Use only the Amerex Model 506B charge and follow the instructions printed on the carton. Reuse of the 506B charge is permitted if the charge is reclaimed in a clean pail and the freeze point is verified. To verify the freeze point, pour the loaded stream solution into a 300 ml graduated container and check the specific gravity with a hydrometer. A minimum specific gravity of 1.270 will assure freeze protection to 40ºF. A lower specific gravity means that the charge should be replaced.

RECHARGE

RECHARGING (NFPA 10) The replacement of the extinguishing agent and includes the expellant for this type of extinguisher.

WARNING : a.

Before attempting to recharge be sure this extinguisher is completely depressurized.

b.

Use a regulated pressurizing source (either air or nitrogen). Set the regulator no more than 25 psi (175 kPa) higher than the gauge operating pressure.

c.

Check and calibrate regulator gauge at frequent intervals. The regulator gauge should be used to determine when the intended charging pressure has been reached. Do not use the extinguisher gauge for this purpose.

d.

Never leave an extinguisher connected to a regulator of a high pressure source for an extended period of time. A defective regulator could cause the cylinder to rupture due to excessive pressure .

P/N 05601 2 06/2019

RECHARGING PROCEDURE

1.

Complete the “Maintenance Service Procedure”, items 1 thru 12.

2.

Discharge all remaining pressure and water (or anti freeze solution) making sure that there is no remaining pressure.

3.

Remove the valve assembly and disassemble by removing downtube assembly (use a wrench on the brass retainer, not the plastic tube), spring and valve stem from the valve assembly. Remove the collar o ring from the valve assembly. Discard the valve stem & collar oring.

4.

Thoroughly rinse all parts with clean water and wipe dry with a soft cloth. Blow the valve out with air or nitrogen. Inspect the spring – replace parts if worn or damaged. Replace valve stem and collar o ring with new components. Lubricate the collar o ring and small o ring on the valve stem with Bluestar V 711 (do not lubricate the valve stem seal). Inspect the downtube. If it is cracked, deformed or does not have a threaded brass spring retainer replace the downtube. Inspect downtube o ring, replace if necessary.

5.

Rinse the cylinder with clean water and inspect the interior following CGA Visual Inspection

Standard, Pamphlet C 6.

6.

Firmly replace the plastic fill tube and fill cylinder with clean water until it overflows (2 ½ gallons [9 ½ liters]).

NOTE: THE AMEREX WARRANTY DOES NOT COVER STAINLESS STEEL

EXTINGUISHERS FILLED WITH WATER WHICH CONTAINS IN EXCESS OF 40

PPM OF CHLORIDES. IN MANY AREAS WATER INCLUDES HIGH LEVELS OF

CHLORIDES.

7.

Install a “Verification of Service” collar around neck of cylinder. Install valve assembly to the cylinder and properly align. CAUTION: Hand tighten the valve collar nut to 100 125 in. lbs. max (1.15 – 1.44 KG/m). Over tightening with a wrench will damage the valve.

8.

Remove cap from the air pressurizing valve on the side of the valve body and pressurize with 100 psi (690 kPa) using air or nitrogen. NOTE: A 02141 fill adapter may also be used by installing to the female valve outlet (where the hose assembly attaches).

The pressure regulator should be set to no more than 25 psi (175 kPa) higher than the gauge operating pressure. Replace pressure valve cap. The cap must be in place to insure that the valve will not leak.

9.

Check the collar, gauge, cylinder welds and valve orifice for leaks using a leak detection fluid or a solution of soapy water. Remove leak detection fluid from the valve assembly by blowing out with air and wipe exterior of the extinguisher to dry.

10.

Install hose assembly into the operating valve.

11.

Install ring pin with ring facing front of the extinguisher. Install new tamper seal. Record recharge date and attach new recharge tag.

12.

Weigh assembled extinguisher and confirm that the total weight is within the allowable tolerances indicated in the Maintenance section on the extinguisher nameplate.

P/N 05601 3 06/2019

TROUBLESHOOTING GUIDE

WARNING : Determine the source of a leak before the extinguisher is depressurized.

EXTINGUISHER MUST BE COMPLETELY DEPRESSURIZED BEFORE

ANY ATTEMPT IS MADE TO DEVALVE IT AND CORRECT ANY LEAKAGE

PROBLEM . To depressurize – hold the extinguisher in an Inverted position and slowly squeeze the discharge handle. Some liquid remaining in the and valve removal.

downtube will be discharged so care should be taken in the area used for depressurization. Thoroughly clean all valve parts after depressurization

PROBLEM CORRECTIVE ACTION

1.

2.

3.

4.

5.

Leak at collar o

Leak around gauge threads

ring

Leak through valve

Defective gauge

Leak in the cylinder

Remove valve assembly, clean collar thoroughly and install new o ring.

Lubricate the o ring with Bluestar

V 711

Install new valve stem assembly.

Check valve seat for scratches or foreign matter.

Remove gauge * and reinstall using

Teflon tape on the gauge threads.

Remove defective gauge* and install a new gauge using Teflon tape on the gauge threads.

Contact Amerex if under warranty, otherwise mark "Rejected" and return to owner.

* Pressure gauge threads are coated with a special epoxy at the factory. For easy removal, soak the valve assembly in hot water (180°F) for two to four minutes. Remove gauge with a thin 7/16” open end wrench

P/N 05601 4 06/2019

6

3

4A

2

1

10

11

12

4

7A

7

9

8A

8

5

5A

14

15

PARTS LIST

for

2 1/2 GALLON STAINLESS STEEL

STORED PRESSURE WATER EXTINGUISHER

(BRASS VALVE)

ITEM

NO.

PART

NO.

DESCRIPTION

1

2

3

4

13281 Valve Ass'y – 240

06978 Hose Gasket (O-Ring)

06999 Hose & Nozzle Ass'y

00155 Pressure Valve & Cap Ass'y

4A

5

5A

6

7

00158 Cap only for Pressure Valve

00160 Ring Pin, Stainless Steel

00532 Chain (Nylon) for Ring Pin

01387 Lock Wire Seal (Yellow)

07762 Lever & Rivet

7A

8

8A

9

10

11

12

01563

09020

01564

06479

05240

06093

00383

Rivet Only for Lever

Handle & Rivets

Collar O-ring

Valve Stem Ass'y

Spring

Rivet Only for Handle (2 required)

13

14

02595 Fill Tube

05690 O-Ring – Downtube/Retainer

15 15943 Downtube/Retainer Ass'y – 240

16 03576 Foot Stand w/clip (Black)-240

Gauge 100 psi (Stainless Steel Tube)

*

*

24874

Model 506B Loaded Stream antifreeze charge – Model 240 only

06247 Bluestar Lubricant (5 oz. tube)

NOTE: SEE PARTS BOOK FOR BRACKETS AND

ADAPTERS

* PART NOT PICTURED

13

16

P/N 05601 5 06/2019

advertisement

Related manuals

Download PDF

advertisement