SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS March 2010 No. OCS11 REVISED EDITION-B TECHNICAL DATA BOOK R410A INVERTER <Indoor unit> [Model names] <Outdoor unit> [Model names] PLA-RP·BA/BA2/BA3 PEAD-RP·JA(L) PEAD-RP·EA(2) PEAD-RP·GA PKA-RP·HAL PKA-RP·KAL PKA-RP·GAL PKA-RP·FAL(2) Revision : • PLA-RP·BA3, PKA-RP·HAL/KAL and PEAD-RP·JA(L) are added, and the data of PUHZ-HRP·HA2 has been modified in REVISED EDITION-B. • Some descriptions have been modified. • Please void OCS11 REVISED EDITION-A. PUHZ-HRP71/100VHA PUHZ-HRP100/125YHA PUHZ-HRP71/100VHA2 PUHZ-HRP100/125YHA2 CONTENTS 1. REFERENCE SERVICE MANUAL············································· 2 2. SPECIFICATIONS ······································································ 3 3. OUTLINES AND DIMENSIONS ··············································· 12 4. WIRING DIAGRAM··································································· 24 5. REFRIGERANT SYSTEM DIAGRAM ······································ 36 6. PERFORMANCE CURVES ······················································ 38 7. CORRECTION FACTORS ························································ 40 8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ·········· 41 9. AIR FLOW DATA ······································································ 44 10. NOISE CRITERION CURVES ·················································· 60 11. OPTIONAL PARTS············································································74 Zubadan 1 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. INDOOR UNIT Model Name Service Ref. Service Manual No. PLA-RP35/50/60/100/125BA PLA-RP71/100/125BA2 PLA-RP35/50/60/100/125BA#2.UK PLA-RP71/100/125BA2.UK OCH412 OCB412 PLA-RP100BA3 PLA-RP100BA3 OCH459 OCB459 PKA-RP35/50HAL PKA-RP35/50HAL OCH453 OCB453 PKA-RP60/100KAL PKA-RP60/100KAL.TH OCH452 OCB452 PEAD-RP35/50/60/71/100/125JA(L) PEAD-RP35/50/60/71/100/125JA(L).UK PKA-RP35/50GAL PKA-RP35/50GAL#1 OC330 PKA-RP60/100FAL PKA-RP50FAL2 PKA-RP60/100FAL#1 PKA-RP50FAL2#1 OC331 PEAD-RP50/60/71/125EA PEAD-RP35/100EA2 PEAD-RP50/60/71/125EA#1.UK PEAD-RP35/100EA2#1.UK HWE0521 PEAD-RP60/71/100GA PEAD-RP60/71/100GA#1.UK HWE0506 HWE08130 BWE08240 1-2. OUTDOOR UNIT Model Name Service Ref. Service Manual No. PUHZ-HRP71/100VHA PUHZ-HRP100/125YHA PUHZ-HRP71/100VHA2 PUHZ-HRP100/125YHA2 PUHZ-HRP71/100VHA PUHZ-HRP100/125YHA PUHZ-HRP71/100VHA2R1 PUHZ-HRP100/125YHA2R1 2 OCH425 OCB425 SPECIFICATIONS 2 2-1. CEILING CASSETTE TYPE Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length PLA-RP71BA2 PUHZ-HRP71VHA2 24,200 7.1 ( 4.9 - 8.1 ) 1.94 3.66 A 0.73 27,300 8.0 ( 4.5 - 10.2 ) 1.90 4.21 A - Btu/h kW kW Btu/h kW kW kW Hz V A CMM CFM Pa 32 14 - 16 - 18 - 21 495 - 565 - 635 - 740 28 - 30 - 32 - 34 dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 258 (35) 10-3/16 (1-3/8) 23 (6) 51 (13) PLA-RP100BA2 PUHZ-HRP100VHA2 34,100 10.0 ( 4.9 - 11.4 ) 2.44 4.10 A 0.74 38,200 11.2 ( 4.5 - 14.0 ) 2.54 4.41 A 1 50 230 40 20 - 23 - 26 - 30 710 - 810 - 920 - 1060 0 32 - 34 - 37 - 40 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 298 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8) 11-3/4 (1-3/8) 27 (6) 60 (13) 32 1-1/4 100 3,530 51 52 Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 120 265 15.88 5/8 9.52 3/8 Max. 30 Max. 75 PLA-RP100BA3 PUHZ-HRP100VHA2 34,100 10.0 ( 4.9 - 11.4 ) 2.44 4.10 A 0.74 38,200 11.2 ( 4.5 - 14.0 ) 2.54 4.41 A - 40 20 - 23 - 26 - 30 710 - 810 - 920 - 1060 32 - 34 - 37 - 40 298 (35) 11-3/4 (1-3/8) 26 (6) 57 (13) 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit Single phase 230V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 3 Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW Hz V A CMM CFM Pa dB(A) PLA-RP100BA2 PUHZ-HRP100YHA2 34,100 10.0 ( 4.9 - 11.4 ) 2.50 4.00 A 0.74 38,200 11.2 ( 4.5 - 14.0 ) 2.60 4.31 A - 20 - 23 - 26 - 30 710 - 810 - 920 - 1060 0 32 - 34 - 37 - 40 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) 27 (6) 60 (13) PLA-RP100BA3 PLA-RP125BA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 34,100 42,700 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 ) 2.50 3.79 4.00 3.30 A A 0.74 0.71 38,200 47,800 11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 ) 2.60 3.57 4.31 3.92 A A 3 50 400 16 20 - 23 - 26 - 30 22 - 25 - 28 - 31 710 - 810 - 920 - 1060 780 - 880 - 990 - 1090 0 0 32 - 34 - 37 - 40 34 - 36 - 39 - 41 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 298 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8) 11-3/4 (1-3/8) 26 (6) 57 (13) 27 (6) 60 (13) 32 1-1/4 100 3,530 51 52 Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 134 295 15.88 5/8 9.52 3/8 Max. 30 Max. 75 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz) Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit 3 phase 400V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 4 Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) External pressure Sound level (Low-Medium2-Medium1-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW Hz V A CMM CFM Pa dB(A) PLA-RP100BA PLA-RP100BA PLA-RP125BA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA 34,100 34,100 42,700 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 ) 3.02 3.02 3.87 3.31 3.31 3.23 A A A 0.74 0.74 0.71 38,200 38,200 47,800 11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 ) 3.10 3.10 3.88 3.61 3.61 3.61 A A A 1 3 50 50 230 400 32 16 20 - 23 - 26 - 30 22 - 25 - 28 - 31 710 - 810 - 920 - 1060 780 - 880 - 990 - 1090 0 0 32 - 34 - 37 - 40 34 - 36 - 39 - 41 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 120 265 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 298 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8) 11-3/4 (1-3/8) 25 (6) 55 (13) 32 1-1/4 100 3,530 52 53 Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 134 295 15.88 5/8 9.52 3/8 Max. 30 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz) Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 5 2-2. CEILING-CONCEALED TYPE Model Name Cooling Indoor Unit Outdoor Unit Capacity Heating Total Input EER Energy label class SHF Capacity Power supply Indoor unit Total Input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - Middle - High) External pressure Sound level (Low - Middle - High/50Pa) External finish Dimension Weight Field drain pipe O.D. Outdoor Unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW [ Hz V A CMM CFM Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m PEAD-RP71JA(L) PUHZ-HRP71VHA2 24,200 7.1 (3.3 - 8.1) 2.15 (2.13) 3.30 (3.33) A 0.83 27,300 8.0 (3.5 - 10.2) 2.34 3.42 B - PEAD-RP100JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L) PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 34, 100 34, 100 42,700 10.0 (4.9 - 11.4) 10.0 (4.9 - 11.4) 12.5 (5.5 - 14.0) 3.06 (3.04) 3.06 (3.04) 3.89 (3.87) 3.27 (3.29) 3.27 (3.29) 3.21 (3.23) A A A 0.82 0.82 0.84 38,200 38,200 47,800 11.2 (4.5 - 14.0) 11.2 (4.5 - 14.0) 14.0 (5.0 - 16.0) 3.10 3.10 3.88 3.61 3.61 3.61 A A A 1 3 50 50 230 400 32 40 16 17.5 - 21 - 25 24 - 29 - 34 24 - 29 - 34 29.5 - 35.5 - 42 618 - 742 - 883 847 - 1,024 - 1,201 847 - 1,024 - 1,201 1,042 - 1,253 - 1,483 35 / 50 / 70 / 100 / 150 26 - 30 - 34 29 - 34 - 38 29 - 34 - 38 33 - 36 - 40 Galvanized sheets 1,400 732 250 55-1/8 28-7/8 9-7/8 41 (40) 41 (40) 91 (89) 91 (89) 32 1-1/4 100 3,530 51 52 Ivory Munsell 3Y 7.8/1.1 950 330 + 30 1,350 37-3/8 13 + 1-3/16 53-1/8 1,100 43-5/16 33 (32) 73 (71) 120 265 43 (42) 95 (93) 134 295 15.88 5/8 9.52 3/8 Max. 30 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 3. Guaranteed voltage 2. Guaranteed operating range Indoor unit : 198 ~ 264V, 50Hz Indoor Outdoor Outdoor unit : 198 ~ 264V, 50Hz (V) 342 ~ 457V, 50Hz (Y) Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling 4. Above data are based on the indicated voltage. Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Indoor unit Single phase 230V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating Outdoor unit (V) Single phase 230V 50Hz Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C (Y) 3 phase 400V 50Hz * If optional air protect guide is installed : D.B.-18°C 6 Model name Indoor unit Outdoor unit Cooling Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-High) External pressure Sound level (Low-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Unit drain pipe Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW PEAD-RP71EA PUHZ-HRP71VHA PUHZ-HRP71VHA2 PEAD-RP100EA2 PUHZ-HRP100VHA PUHZ-HRP100VHA2 24,200 7.1 (4.9 - 8.1 ) 2.15 3.30 A 0.83 27,300 8.0 ( 4.5 - 10.2 ) 2.34 3.42 B - 34,100 10.0 ( 4.9 - 11.4 ) 3.06 3.27 A 0.86 38,200 11.2 ( 4.5 - 14.0 ) 3.10 3.61 A 1 50 230 Hz V A CMM CFM Pa 32 20 - 25 706 - 883 70 37-41 dB(A) 32 (VHA)/ 40 (VHA2) 33.5 - 42 1,183 - 1,483 70 44-50 Galvanized sheets W : mm D : mm H : mm W : inch D : inch H : inch kg lbs 1,175 1,415 740 325 46-1/8 55-11/16 29-1/8 12-13/16 44 97 65 143 R1 (External thread) CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 100 3,530 52 (VHA)/ 51 (VHA2) 53 (VHA)/ 52 (VHA2) Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 120 265 15.88 5/8 9.52 3/8 Max. 30 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit Single phase 230V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 7 Model name Indoor unit Outdoor unit Cooling Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-High) External pressure Sound level (Low-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Unit drain pipe Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW PEAD-RP100EA2 PUHZ-HRP100YHA PUHZ-HRP100YHA2 PEAD-RP125EA PUHZ-HRP125YHA PUHZ-HRP125YHA2 34,100 10.0 ( 4.9 - 11.4 ) 3.06 3.27 A 0.86 38,200 11.2 ( 4.5 - 14.0 ) 3.10 3.61 A - 42,700 12.5 ( 5.5 - 14.0 ) 3.89 3.21 A 0.82 47,800 14.0 ( 5.0 - 16.0 ) 3.88 3.61 A 3 50 400 16 Hz V A CMM CFM Pa 33.5 - 42 1,183 - 1,483 70 44 - 50 dB(A) 33.5 - 42 1,183 - 1,483 70 44 - 50 Galvanized sheets 1,415 740 325 55-11/16 29-1/8 12-13/16 65 143 R1 (External thread) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs 100 3,530 52 (YHA)/ 51 (YHA2) 53 (YHA)/ 52 (YHA2) Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 134 295 15.88 5/8 9.52 3/8 Max. 30 Max. 75 CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage Indoor unit:198~264V, 50Hz Outdoor unit:342~457V, 50Hz Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit 3 phase 400V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 8 Model name Indoor unit Outdoor unit Cooling Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-High) External pressure Sound level (Low-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Unit drain pipe Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW PEAD-RP71GA PUHZ-HRP71VHA PUHZ-HRP71VHA2 PEAD-RP100GA PUHZ-HRP100VHA PUHZ-HRP100VHA2 PEAD-RP100GA PUHZ-HRP100YHA PUHZ-HRP100YHA2 24,200 7.1 ( 4.9 - 8.1 ) 2.15 3.30 A 0.83 27,300 8.0 ( 4.5 - 10.2 ) 2.34 3.42 B - 34,100 10.0 ( 4.9 - 11.4 ) 3.08 3.25 A 0.86 38,200 11.2 ( 4.5 - 14.0 ) 3.28 3.41 B - 34,100 10.0 ( 4.9 - 11.4 ) 3.08 3.25 A 0.86 38,200 11.2 ( 4.5 - 14.0 ) 3.28 3.41 B 3 50 400 16 1 50 230 Hz V A CMM CFM Pa 32 20-25 706-883 10/50/70 35-38/37-41/37-43 dB(A) 32 (VHA)/ 40 (VHA2) 26.5-33 935-1,165 10/50/70 40-43/42-45/42-46 Galvanized sheets W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 1,171 1,411 740 275 46-1/8 55-9/16 29-1/8 10-13/16 42 93 50 111 R1 (External thread) 1-1/4 100 3,530 52 (VHA, YHA)/ 51 (VHA2, YHA2) 53 (VHA, YHA)/ 52 (VHA2, YHA2) Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 120 265 15.88 5/8 9.52 3/8 Max. 30 Max. 75 134 295 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz(HRP100Y : 342~457V, 50Hz) Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 9 2-3. WALL-MOUNTED TYPE Model Name Cooling Indoor Unit Outdoor Unit Capacity Heating Total Input EER Energy label class SHF Capacity Power supply Indoor unit PKA-RP100KAL PUHZ-HRP100VHA2 Total Input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - Middle - High) External pressure Sound level (Low - Middle - High/50Pa) External finish Dimension Weight Field drain pipe O.D. Outdoor Unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW 34,100 10.0 (4.9 - 11.4) 2.93 3.41 A 0.73 38,200 11.2 (4.5 - 14.0) 3.10 3.61 A - Btu/h kW kW kW [ Hz V A CMM CFM Pa dB(A) 1 50 230 40 Munsell 1.0Y 9.2/0.2 1,170 295 365 46-1/16 11-5/8 14-3/8 21 46 16 5/8 100 3,530 51 52 Ivory Munsell 3Y 7.8/1.1 950 330 + 30 1,350 37-3/8 13 + 1-3/16 53-1/8 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m Indoor D.B. 35°C, W.B. 22.5°C D.B. 19°C, W.B. 15°C D.B. 28°C D.B. 17°C 3 50 400 16 20 - 23 - 26 705 - 810 - 920 0 41 - 45 - 49 120 265 134 295 15.88 5/8 9.52 3/8 Max. 30 MAx. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Cooling Lower limit Upper limit Heating Lower limit PKA-RP100KAL PUHZ-HRP100YHA2 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) 3. Guaranteed voltage 198~264V, 50Hz (V) / 342~457V, 50Hz (Y) Outdoor D.B. 46°C D.B. -5°C +1 D.B. 21°C, W.B. 15°C D.B. -15°C, W.B. -15°C 10 4. Above data are based on the indicated voltage. Indoor unit Single phase 230V 50Hz Outdoor unit V : Single phase 230V 50Hz Y : 3 phase 400V 50Hz +1. If optional air protect guide is installed : D.B.-15 Model name Indoor unit Outdoor unit Cooling Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-High) External pressure Sound level (Low-High) External finish (Panel) Dimension Unit (Panel) Weight Unit (Panel) Field drain pipe I.D. Outdoor unit Air flow Sound level at cooling Sound level at heating External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW Hz V A CMM CFM Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m PKA-RP100FAL PUHZ-HRP100VHA PUHZ-HRP100VHA2 PKA-RP100FAL PUHZ-HRP100YHA PUHZ-HRP100YHA2 34,100 10.0 ( 4.9 - 11.4 ) 2.93 3.41 A 0.77 38,200 11.2 ( 4.5 - 14.0 ) 3.10 3.61 A 1 50 230 32 (VHA)/ 40 (VHA2) 34,100 10.0 ( 4.9 - 11.4 ) 2.93 3.41 A 0.77 38,200 11.2 ( 4.5 - 14.0 ) 3.10 3.61 A 3 50 400 16 22 - 28 780 - 990 0 41 - 46 White Munsell 3.4Y 7.7/0.8 1680 235 340 66-1/8 9-1/4 13-3/8 28 62 20 13/16 100 3,530 52 (VHA, YHA)/ 51 (VHA2, YHA2) 53 (VHA, YHA)/ 52 (VHA2, YHA2) Ivory Munsell 3Y 7.8/1.1 950 330+30 1,350 37-3/8 13 + 1-3/16 53-1/8 120 134 265 295 15.88 5/8 9.52 3/8 Max. 30 Max. 75 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range 3. Guaranteed voltage 198~264V, 50Hz(HRP100Y : 342~457V, 50Hz) Indoor Outdoor 4. Above data are based on the indicated voltage. Upper limit D.B. 32°C, W.B. 23°C D.B. 46°C Cooling Indoor unit Single phase 230V 50Hz Lower limit D.B. 19°C, W.B. 15°C D.B. -5°C * Outdoor unit V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz Upper limit D.B. 28°C D.B. 21°C, W.B. 15°C Heating * If optional air protect guide is installed : D.B.-18°C Lower limit D.B. 17°C D.B. -25°C, W.B. -25°C 11 OUTLINES AND DIMENSIONS 3 INDOOR UNIT PLA-RP50BA PLA-RP100BA2 PLA-RP60BA PLA-RP100BA3 810 Detail connecting of Branch duct(Both aspects) 20~45 90 100 100 90 Cut out hole 860~910 620 605 +35 -5 Indoor power supply terminal block(Option part) Ceiling hole + + Suspension bolt pitch 840 Branch duct hole 155 Remote controller terminal block Indoor unit/Outdoor unit connecting terminal block 167 70° 160 (7.5) 100 Suspension bolt pitch 160 PLA-RP125BA 20~45 860~910 Fresh air intake hole PLA-RP100BA Unit : mm Ceiling hole 20~45 PLA-RP71BA PLA-RP125BA2 130 PLA-RP35BA PLA-RP71BA2 Branch duct hole 350 :175 14-:2.8 Burring hole Burring hole pitch :150 840 60 284 ( Connected the attached Drain pipe connected to VP-25 socket. 377 Control wire entry Ceiling B ) Cut out hole :100 + Ceiling + In case of standard grille : PLP-6BA / PLP-6BAMD 35 Power supply wire, Indoor unit/Outdoor unit connecting wire entry 190 156 105 140 + 17 +5 0 Suspension bolt lower edge Keep approximately 10 to 15mm space between unit ceiling and ceiling slab. + + + + 50~70 170 A 2 + :125 120° 158 1 Burring hole pitch 3-:2.8 120° 160 Suspension bolt M10 or W3/8 Burring hole 20~45 187.5 Detail drawing of fresh air intake hole (7.5) 24 160 D C 90 150 Cut out hole Grille 597 Drain hole Drain pump clean hole and Drain emergency drainage hole 597 Operation lamp 83 M 36 500 83 36 950 Indoor unit 1000mm or more Indoor unit 3000mm or more Obstacle Floor Air intake grille Vane motor Air outlet hole 1500mm or more DEFROST/STAND BY lamp Receiver M Grille Ceiling L.L Filter Air intake grille Ceiling Auto Grille Air intake grille up/down discharge Emergency operation switch<Cooling>and Emergency Up/Down switch<Up> Emergency operation switch<Heating>and Emergency Up/Down switch<Down> Auto vane (Air outlet) Air intake hole 500 Air outlet hole 950 M In case of Auto-Grille : PLP-6BAJ In case of wireless remote controller : PLP-6BALM 1800mm or more from floor For high attachment Note1. Please choose the Grille from a standard grille, Auto-Grille. 2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Raise is max 850mm from the ceiling. 3. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection. 5. The height of the indoor unit is able to be adjusted with the grille attached. 6. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Requires E or more space between transom and ceiling for the installation. 2) Add 135 mm to the dimensions + marked on the figure. 3) The optional high efficiency filter must be used jointly with optional multi-functional casement, 7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/Water dew.) 8. As for necessary installation/service space, please refer to left figure. Models PLA-RP35/50BA 1 Refrigerant pipe ···:6.35 Flared connection ···1/4F 2 Refrigerant pipe :6.35 / :9.52 Flared connection 1/4F / 3/8F (compatible) PLA-RP60BA PLA-RP71BA,BA2 PLA-RP100,125BA PLA-RP100BA3 PLA-RP100, 125,140BA2 12 Refrigerant pipe ···:9.52 Flared connection ···3/8F A B Refrigerant pipe ···:12.7 Flared connection ···1/2F C D E 80 74 241 258 87 400 Refrigerant pipe ···:15.88 Flared connection ···5/8F 85 77 281 298 440 Max. 4.0m Air intake hole M Unit : mm PEAD-RP35, 50, 60, 71, 100, 125JA 2xE-:2.9 Suspension bolt hole 4-14x30 Slot 18 Air inlet 210 G Air outlet A B(Suspension bolt pitch) C D (Duct) 100x(E-1)=F 15 643 (Suspension bolt pitch) 32 238 10 Terminal block (Remote controller transmission line) 175±5mm (Actual length) 217 250 Control box 2×2-:2.9 136 67 356 NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60•71•100•125•140JA models,which have 2 fans. PEAD-RP35•50JA models have 1 fan. 4. In case of the inlet duct is used,remove the air filter (supply with the unit), then install the filter (field supply) at suction side. Drain pipe(O.D.:32) Terminal block (Spontaneous draining) (Indoor/Outdoor connecting line) Model A PEAD-RP35,50JA 900 PEAD-RP60,71JA PEAD-RP100,125JA PEAD-RP140JA 6 D E F G 954 1000 860 9 800 858 B C 1100 1154 1200 1060 1400 1454 1500 1360 1600 1654 1700 1560 11 1000 1058 14 1300 1358 16 1500 1558 J Gas pipe Liquid pipe :12.7 :6.35 :15.88 :9.52 Kx(L-1)=M J K More than 20mm Ceiling surface 112 112 N-:2.9 More than 10mm Drain hose (I.D.:32) <accessory> 11 1 Refrigerant piping Flare connection (gas) Less than 300mm Less than 700mm 732 700 Drain pipe Drain pump (O.D.:32) 41 57 178 (Duct) 100 33 23 40 122 2 Refrigerant piping Flare connection (liquid) 23 10 58 40 57 21 20 30 100 Air Filter Access door Q P Make the access door at the appointed position properly for service maintenance. Qx(R-1)=S Model 777 50 H Note2 Access door 50 250 ~30 45 0 0 450 0 30 han re t Mo Required space for service and maintenance 13 H J K L M N P Q R S PEAD-RP35,50JA 1000 54 260 4 780 10 40.5 273 4 819 PEAD-RP60,71JA PEAD-RP100,125JA PEAD-RP140JA 1200 1500 1700 49 54 54 330 320 370 4 5 5 990 1280 1480 10 12 12 40 40 40 340 330 380 4 5 5 1020 1320 1520 Unit : mm PEAD-RP35, 50, 60, 71, 100, 125JAL 2xE-:2.9 Suspension bolt hole 4-14x30 Slot 210 G Air inlet C Air outlet A 18 B(Suspension bolt pitch) D (Duct) 100x(E-1)=F 15 21 Terminal block (Remote controller transmission line) 732 700 32 175±5mm (Actual length) 217 250 10 33 2×2-:2.9 1 Refrigerant piping Flare connection (gas) Control box 136 67 356 NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60•71•100•125•140JAL models,which have 2 fans. PEAD-RP35•50JAL models have 1 fan. 4. In case of the inlet duct is used,remove the air filter (supply with the unit), then install the filter (field supply) at suction side. Drain pipe(O.D.:32) Model A PEAD-RP35,50JAL 900 PEAD-RP60,71JAL PEAD-RP100,125JAL PEAD-RP140JAL 6 D E F G 954 1000 860 9 800 858 B C 1100 1154 1200 1060 1400 1454 1500 1360 1600 1654 1700 1560 11 1000 1058 14 1300 1358 16 1500 1558 J Gas pipe Liquid pipe :12.7 :6.35 :15.88 :9.52 Kx(L-1)=M J K More than 20mm Ceiling surface 112 112 N-:2.9 More than 10mm Drain hose (I.D.:32) <accessory> Terminal block (Indoor/Outdoor connecting line) 11 23 40 122 100 178 (Duct) 643 (Suspension bolt pitch) 57 2 Refrigerant piping Flare connection (liquid) 23 10 58 40 57 20 30 100 Air Filter Access door Q Make the access door at the appointed position properly for service maintenance. Qx(R-1)=S P Model 777 50 H Note2 Access door H J K L M N P Q R S PEAD-RP35,50JAL 1000 54 260 4 780 10 40.5 273 4 819 PEAD-RP60,71JAL PEAD-RP100,125JAL PEAD-RP140JAL 1200 1500 1700 49 54 54 330 320 370 4 5 5 990 1280 1480 10 12 12 40 40 40 340 330 380 4 5 5 1020 1320 1520 50 250 ~30 45 0 0 re Mo Required space for service and maintenance 450 0 0 n3 tha 14 Unit : mm PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA Model A RP35,50 772 RP60 B 305 1012 280 + Initial setting C D E - 830 804 F G R410A Outdoor unit : 6.35 + R410A Outdoor unit : 12.7 + R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88 Outdoor unit (SUZ) : 6.35 15.88 290 1070 1044 R407C Outdoor unit : 9.52 + Service space:500 or more 50~150 29 Refrigerant piping flare connection (liquid : F copper tube):HP Refrigerant piping flare connection (gas :G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP-25(I.D. :32) Filter 55 Access door 10- :3 (RP35,50) 12- :3 (RP60) A 81 C B 81 197 450 Lifting bolt hole (1422) C 13 243 277 45 80 85 24 282 288 256 176 Air inlet 7 E 13 D 30 10- :3 (RP35,50) 12- :3 (RP60) 6 40 2 179 10 35 1 227 109 10 3.5 21 In case of rear inlet 30 61 4 81 A 44 75 640 30 B 10 18 56 355 365~465 159 1 2 3 4 5 6 7 10 450 5 Air outlet 3.5 3 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. In case of bottom inlet 10- :3 (RP35,50) 12- :3 (RP60) Air outlet 40 15 176 256 10 3.5 10 7 81 C B 81 A Air inlet PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA Service space:500 or more Air inlet 375 44 243 6 5 7 Lifting bolt hole (14x22) 12-:3 307 45 122 113 1 81 Air outlet 3 4 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. 15 C A 13 E 75 D B 81 10 80 2 20 53 B 197 30 10 680 C 365~465 323 308 169 210 30 12-:3 A 81 81 35 7 140 6 282 5 3.5 30 4 40 3 55 Access door Refrigerant piping flare connection (liquid :9.52 copper tube):HP Refrigerant piping flare connection (gas :F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP25(I.D.:32) Filter 319 261 181 2 3.5 1 C D E F 290 1070 1044 15.88 370 1310 1284 R410A Outdoor unit : 15.88 + 470 1610 1584 R407C outdoor unit : 19.05 450 A B Model RP71 1012 280 RP100,125 1252 360 RP140 1552 460 + Initial setting 10 50~150 29 450 13 30 Unit : mm PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA Model A B C D E F G 8 H Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 * RP60 1125 1090 1050 1012 7 840 RP71 1125 1090 1050 1012 7 RP100 1365 1330 1290 1252 9 15.88 840 8 9.52 15.88 1080 10 9.52 R410A Outdoor unit : 15.88 * R407C Outdoor unit : 19.05 * Initial setting 16 J PKA-RP35HAL PKA-RP50HAL Unit : mm 192 Top side 197 387 Mount board 599 Front side 295 Right side A Left side 55 688 Knockout hole for left piping 5 249 155 898 Knockout hole for right piping Front side (Grille open) Sleeve Through hole (purchased locally) :65~:80 Terminal block for outdoor unit :65~:80 Terminal block for power supply (option) Terminal block for MA-remote controller (option) 457 Gas pipe 539 Liquid pipe 610 Drain hose 169 158 184 Under side Vane (auto) DEFROST/STAND BY lamp Operation lamp 612 Emergency operation switch (cooling/heating) 8 Size Refrigerant pipe : :6.35 Liquid pipe Flared connection : 1/4F Refrigerant pipe : :12.7 Gas pipe Flared connection : 1/2F Drain hose Louver (manual) Knockout hole for lower piping O.D Receiver Knockout hole for lower piping C :16 B Knockout hole for piping 58 3.8 0 Center measurement hole :2.5 Mount board 200 225 238 265 291.5 327.5 356.3 372.3 125 70 70 15 0 15 125 225 200 291.5 265 372.3 356.3 327.5 231.5 Required space (Indoor unit) Air inlet Min.50 550mm or greater with optional Min.220 drain pump installation. 17 Air outlet Min.150 Min.250 Air inlet 449 281 115 140 167 180.3 193.5 0 Knockout hole for left rear piping (70 × 310) Min.50 Wall hole for left piping 174 273.2 238 213 B 128.5 153.5 278.3 46 60 21.8 0 20 32.7 53.5 66 449 43 43 Min.7 250mm or greater with optional drain pump installation. 6 A 59 D 43 Indoor unit outline 0 16 28.5 41 78.5 91 103.5 116 166 178.5 203.5 232.5 253.5 394 69 C 46 56 56 6 12.5 56 43 4-:9 Bolt hole 77-:5.1 Tapping screw hole Wall hole for right rear piping 55mm or greater with left or rear left piping or drain pump installation. PKA-RP60KAL PKA-RP100KAL Unit : mm Top side 431.7 11 140.3 65.2 423.7 Left side Right side Front side Mount board 365 Knockout hole for left piping C 74 A (855) 295 241 5 Operation lamp DEFROST/STAND BY lamp 1170 Receiver Knockout hole for right piping Front side (Grille open) Terminal block for outdoor unit Terminal block for power supply (option) Terminal block for MA-remote controller (option) Emergency operation switch (cooling/heating) 30 35 444 (Gas pipe) 66 123 154 482 (Liquid pipe) 585 (Drain hose) 134 Under side Piping connection department Refrigerant pipe : 9.52 Flared connection : 3/8F Gas pipe Refrigerant pipe : 15.88 Flared connection : 5/8F 16 Drain hose Sleeve Through hole (purchased locally) 75 Liquid pipe 75~ 80 O.D Louver (manual) Vane (auto) B B 54 0 Knockout hole for lower piping C B 3 364 384.5 408.5 439 454 465.5 314 10 0 10 60 110 Indoor unit outline 54 32 25 77 7.8 77 87 0 0 37.5 62.5 50 75 100 117 125 142 192 67 65 77 7.8 67 25 10.7 Mount board A 15.5 65 Center measurement hole W2.5 Temporarily fixing hole 314 75-W5.1 Tapping screw hole 454 439 408.5 384 364 Knockout hole for piping 517.4 4-W9 Bolt hole 60 110 65 104.5 129.5 167 217 242 279.5 292 264 292 308.5 311 Min. 220 550 mm or greater with optional drain pump installation Min. 50.5 108 mm or greater with left or rear left piping or drain pump installation 18 Wall hole for right rear piping 585 439 449.2 Knockout hole for left rear piping (75×480) 339 349.2 384 0 189 339 384 439 430.5 585 Min. 48 Air outlet Min. 72.4 Wall hole for left rear piping Min. 250 Min. 7 265 mm or greater with optional drain pump installation Air inlet 530.5 7.5 R3 Required space (Indoor unit) 216.5 32 18 53 Filter hook 12.5 12.5 87.5 229.5 495 Model 35, 50 Knockout hole for left-rear piping Left-rear piping hole 49-:5hole for tapping screw 300 360 Sleeve +1 :90 R52.5 Liquid pipe Gas pipe 990 705 Air outlet 80 715 Air intake 400 12-Louvers(manual) 340 Air intake 581 449 225 40 86 54 70 35 190 160 235 233 153 : Initial flare nut size GAS SIDE LIQUID SIDE 60 Knockout hole for right piping Refrigerant pipe. Drain pipe. Wiring hole Less than 15 (Right side piping installation) Terminal block for power supply (Heater (PKH-P35, 50GALH only)) Terminal block to outdoor unit Service panel (Power supply access) Knockout hole for under piping Refrigerant piping.Drain pipe. Wiring hole 235 Right side — :9.52 — :15.88 :6.35 :9.52 :12.7 :15.88 P35, 50 RP35, 50 Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size 395 Auto vane 280 Air intake 700 (Flexible hose total length800) Front view(to open the grille) Filter grip 50 Lower side (Left side piping installation) Unit drain pipe O.D.20 35 272 310 322 230 190 130 0 35 55 80 (Necessary clearance for unit installation) Less than 130 Right side 340 +1 Sleeves are available on the market. +2 This size shows the lower end of through hole. Right-rear piping hole R52.5 Through hole :90~:100 Knockout hole for right-rear piping 405 420 Unit center 75 32 20 0 35 0 14-:14hole for bolts 190 Installation plate balance point hole 95 Details of installation plate 135 R5 2. 5 150 or more 150 50 or more 205 170 190 245 70 21 245 70 21 30 or more 180 or more 260 53 79 Allowing clearances Front view 245 5 2. R5 230 210 320 345 Front view 80 60 425 198 Air intake 60 280 Knock out hole for left piping Refrigerant pipe.Drain pipe.Wiring hole. 495 19 31 Left side PKA-RP35GAL PKA-RP50GAL Unit : mm PKA-RP50FAL2 PKA-RP60FAL Unit : mm Display section 62.5 Top 45 235 235 45 235 45 Defrosting Initial heating lamp 13 235 Power lamp Front Right side 1400 Left side Emergency switch(Heat) Emergency switch(Cool) Receiving section 235 Knockout hole for right piping Refrigerant pipe. Drain pipe 340 A 197 1090 Air intake Terminal block for indoor/outdoor connecting line 15 Terminal block for heater (PKH only) Liquid pipe Knockout hole for left piping C Gas pipe 25 Drain hose for left-hand side piping 58 42 Bolt Drain hose O.D.20 Drain hose 1110 55 (Gas pipe) 107 120 111 183 (Liquid pipe) Lower side Liquid pipe :9.52(3/8F) Gas pipe :15.88(5/8F) Auto vanes 1120 240 552 Air outlet 552 Air outlet Louvers (manual) Under panel Removable at left-hand side piping Knockout hole for under-piping Sleeve +1 Through hole :90 :90~ :100 +1 Sleeves are available on the market. B Use the current nuts meeting the pipe size of the outdoor unit. Refrigerant pipe. Drain pipe Unit center 990 Knockout hole for wiring 32-ø12 hole for bolt 225 240 180 12-ø6 hole for tapping screw 280 314 610 30 60 90 B C 30 37 74 39 98 32 39 184 30 66-ø6 hole for tapping screw A 30 100 91 37 74 4 Drainage range on right-hand side 37 65 on left-hand side 100 4 39 18 285 19 10 30 80 29 280 Wall fixture 10 91=(910) 900 18 Drainage range 245 455 Rear piping opening Range for left rear piping opening Available pipe size LIQUID SIDE GAS SIDE RP50 :6.35 :9.52 :12.7 :15.88 : Initial flare nut size 20 RP60,71 / P60,71 :9.52 :15.88 PKA-RP100FAL Unit : mm Top 62.5 Display section 45 235 45 235 45 235 235 45 13 235 Receiving section Emergency switch(Heat) Emergency switch(Cool) Defrosting Initial heating lamp Power lamp Front Knockout hole for right piping Right side 1680 Left side 235 1370 Air intake 340 197 A Knockout hole for left piping C Terminal block for indoor/outdoor connecting line 15 Terminal block for heater (PKH only) Liquid pipe Gas pipe 25 Drain hose O.D.20 Drain hose Drain hose for left-hand side piping 58 42 Bolt 1110 Drain hose 183 Lower side 1400 55 (Gas pipe) 102 120 111 (Liquid pipe) 240 694 Air outlet 694 Air outlet Available pipe size RP100 LIQUID SIDE :9.52 P100 :9.52 GAS SIDE :15.88 :19.05 :Initial flare nut size Louvers (manual) B Under panel (Removable at left-hand side piping) :19.05 Use the current nuts meeting the pipe size of the outdoor unit. Auto vane Knockout hole for under-piping Refrigerant pipe. Drain pipe Unit center 1270 Knockout hole for wiring Drainage range 91 on right-hand side 60 295 225 Range for left rear piping opening 240 180 280 750 314 30 41-ø12 hole for bolt 90 Range for left rear piping opening 12-ø6 hole for tapping screw 21 Rear piping opening A 30 B C 30 100 Drainage range on left-hand side 285 19 37 74 39 98 32 39 13 91=(1183) 900 37 74 4 18 37 65 18 184 30 84-ø6 hole for tapping screw 245 595 10 30 80 29 280 Wall fixture 100 4 39 Unit out line FREE er Ov m 10m m 0m 15 er Ov 10 Service space Over Front piping hole (Knockout) 92 W92 65 Power supply wiring hole (2-W27Knockout) Front trunking hole 40 45 (Knockout) 19 92 75 Right piping hole (Knockout) Piping Knockout Hole Details 55 W92 150 40 65 45 Right trunking hole (Knockout) Less than 92 W92 40 Rear piping hole (Knockout) Rear trunking hole (Knockout) Side Air Intake Handle for moving Handle for moving Power supply wiring hole (2-W27Knockout) FOUNDATION Rear Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. <Foundation bolt height> 4 PIPING-WIRING DIRECTIONS Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally.) Power supply wiring hole (2-W27Knockout) Air intake Handle for moving +1 ···Indication of STOP VALVE connection location. 500 Over Over 3 FOUNDATION BOLTS 30 Dimensions of space needed for service access are shown in the below diagram. ···Refrigerant GAS pipe connection (FLARE)W15.88(5/8 inch) ···Refrigerant LIQUID pipe connection (FLARE)W 9.52(3/8 inch) Example of Notes O 10m m m 0m 00 r1 ve er Ov 55 27 63 23 27 92 73 Over 500 73 63 330 Handle for moving Side Air Intake 30 322 220 175 145 145 145 Earth terminal 950 Air Discharge Installation Feet 600 Rear Air Intake 42 Drain hole (5-W33) 71 2 1 Handle for moving Service panel Terminal connection Left···Power supply wiring Right···Indoor/Outdoor wiring 2-12 x 36 Oval holes (Foundation Bolt M10) 66 175 2-U Shaped notched holes (Foundation Bolt M10) 417 2 SERVICE SPACE 1350 The diagram below shows a basic example. Explanation of particular details are given in the installation manuals etc. 71 635 371 (19) 45 56 370 53 28 Rear piping cover Front piping cover 1,079 930 HRP·YHA A HRP·VHA Bottom piping hole (Knockout) +1 443 1 FREE SPACE (Around the unit) 73 63 23 55 27 A 30 23 219 81 +1 447 22 23 OUTDOOR UNIT PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA Unit : mm FREE Ov m 0m 15 er er 10 mm Ov 10 Over Service space Front piping hole (Knockout) 92 92 65 Power supply wiring hole (2- 27Knockout) Front trunking hole 40 45 (Knockout) 19 92 75 55 92 Air intake Right piping hole (Knockout) Piping Knockout Hole Details 500 Over 150 40 65 45 Less than 92 92 40 Rear piping hole (Knockout) Rear trunking hole (Knockout) Handle for moving Side Air Intake Handle for moving Power supply wiring hole (2- 27Knockout) FOUNDATION Rear Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. <Foundation bolt height> 4 PIPING-WIRING DIRECTIONS Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally.) Right trunking hole (Knockout) Power supply wiring hole (2- 27Knockout) Handle for moving 1 ···Indication of STOP VALVE connection location. ···Refrigerant LIQUID pipe connection (FLARE) 9.52(3/8 inch) ···Refrigerant GAS pipe connection (FLARE) 15.88(5/8 inch) Example of Notes mm 00 10 10 mm er Ov er Ov Over 3 FOUNDATION BOLTS 30 Dimensions of space needed for service access are shown in the below diagram. 330 Handle for moving Handle for moving Side Air Intake 1350 30 322 220 175 145 145 145 Earth terminal 950 Air Discharge Installation Feet 600 Rear Air Intake 42 Drain hole (5- 33) 71 2 1 Handle for moving Service panel Terminal connection Left ····Power supply wiring Right··· Indoor/Outdoor wiring 2-12 x 36 Oval holes (Foundation Bolt M10) 66 175 2-U Shaped notched holes (Foundation Bolt M10) 417 2 SERVICE SPACE 71 The diagram below shows a basic example. Explanation of particular details is given in the installation manuals etc. 55 27 63 23 27 92 73 635 371 (19) 45 56 370 53 28 Over 500 73 63 Front piping cover 930 HRP·YHA2 A 1,079 HRP·VHA2 Bottom piping hole (Knockout) Rear piping cover +1 443 1 FREE SPACE (Around the unit) 73 63 23 55 27 A 30 23 219 81 +1 447 23 23 PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 Unit : mm 4 WIRING DIAGRAM 4-1. INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP60BA PLA-RP100BA3 PLA-RP71BA PLA-RP125BA2 PLA-RP100BA PLA-RP125BA <Table 1> SW1 (MODEL SELECTION) SW1 MODELS SETTING [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 DCL DP FS NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1 SWITCH (CAPACITY CODE) +See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) REACTOR DRAIN PUMP DRAIN FLOAT SWITCH SYMBOL MF MV TB2 TB4 TB5,TB6 TH1 TH2 TH5 OPTION PART W.B BZ LED1 LED2 RU SW1 SW2 NAME FAN MOTOR VANE MOTOR TERMINAL BLOCK (Indoor unit Power (option)) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) PIPE TEMP. THERMISTOR/LIQUID (0 / 15k, 25 / 5. 4k DETECT) COND. / EVA. TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) PLA-RP·BA 1 2 3 4 5 PLA-RP71/100/125BA2 1 2 3 4 5 PLA-RP140BA2 PLA-RP100BA3 1 2 3 4 5 ON OFF SETTING 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 50 1 2 3 4 5 60 1 2 3 4 5 71 ON OFF ON OFF ON OFF 100 125 140 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF ON OFF The black square ( ) indicates a switch position. Refer to tables 1 and 2 DCL TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 ON OFF <Table 2> SW2 (CAPACITY CODE) SW2 CAPACITY SETTING CAPACITY 35 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) ON OFF YLW R.B I.B VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 CN32 (WHT) 1 CN51(WHT) Pair No. 5 CN2L LED3 3 1 3 AUTO GRILLE CN3G 1 (BLK) WIRELESS CN90 (WHT) 9 5 5 5 M M M M MV MV MV MV GRILLE 1 4 4 CNB BZ SW1 LED2 SW2 LED1 2 1 INDOOR/OUTDOOR COMMUNICATION CN3C 1 CN41(WHT) 4 LED1 RU I-SEE SENSOR 1 6 1 2 MT I-SEE SENSOR CORNER PANEL (OPTION PART) + (BLU) 1 4 4 1 2 t° t° TH2 TH5 t° TH1 1 7 FAN CNMF (WHT) X1 4 MS 3 5 M 3 1 FUSE – (BLU) FS 1 CN3G 1 D.U.M 1 3 CNP (BLU) 5 3 1 TB4 YLW S1 ORN S2 S3 TO OUTDOOR UNIT ORN BRN M 3~ 1~ MF DP CN3A AUTOMATIC FILTER ELEVATION PANEL (OPTION PART) W.B Notes: 1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. +1:If indoor and outdoor units have separate power supplies, refer to Fig. 1. +2:For power supply system of this unit, refer to the caution label located near this diagram. YLW ORN + Be sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor) U.B 3 Please set the voltage using the remote controller. For the setting method,please refer to the indoor unit Installation Manual. REMOCON CN22 1 SWE (BLK) 1 3 ON OFF AUTO GRILLE I-SEE FLOAT SW LIQUID/PIPE INTAKE POWER I-SEE SENSOR SENSOR MOTOR CN4F CN44 CN20 CNAC CN4Y CN6Y (WHT) (WHT) (RED) (WHT) (WHT) (RED) 9 5 LED2 OUTDOOR 1 3 5 CN01 3 +1(Fig. 1) CN01 I.B (BLK) YLW 5 ORN 3 1 RED BLU GRN/YLW TB2 L N YLW TB4 ORN S1 ORN S2 BRN S3 I.B 1 3 INDOOR/OUTDOOR CN3C COMMUNICATION (BLU) 24 POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT 25 TH5 FS 1 2 3 4 CN41 CN51 CN32 TH1 t˚ CNXB2 1 2 3 4 5 LED2 CNXC2 1 2 LED1 CN22 (Blue) CN2A (Black) CN105 (Red) 4 3 2 1 (Blue) CNXA2 2 1 M 1~ X01 (Blue) CNXA1 1234 X10 F01 CND 5 (Red) Fan motor MS 3~ CNMF 7654 1 DC280-340V Rectifier circuit P.B. NAME Intake air temp. Thermistor Pipe temp. Thermistor/liquid Cond./eva.temp. Thermistor AC reactor (Power factor improvement) Float switch Terminal block (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line) ONLY FOR PEAD-RP·JA SYMBOL TH1 TH2 TH5 ACL FS TB4 TB15 U ZNR01 3 CNXC1 12 DSA U ZNR02 1 CNXB1 12345 3 1 (Blue) CNP Drainpump NAME SYMBOL NAME I.B. Indoor controller board Indoor controller board SW1 Switch (for model selection) Connector (0-10V Analog input) SW2 Switch (for capacity code) Connector (Lossnay) SW5 Switch (for model selection) Connector (Remote switch) SW6 Switch (for model selection) Connector (HA terminal-A) SWE Connector (emergency operation) Connector (Centrally control) P.B. Connector (Wireless) Power supply board F01 Connector (IT terminal) Fuse AC250V 6.3A ZNR01, 02 Varistor LED(Power supply) DSA Arrester LED(Remote controller supply) X01 LED(Transmission indoor-outdoor) Aux. relay X10 Aux. relay FOR PEAD-RP·JA REFER TO "B" FOR PEAD-RP·JAL B 1 2 3 4 CN4F 1 2 (Red) (Red) CN20 CN2L SWE SW6 1 2 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF 140 125 1 2 3 4 5 1 2 3 4 5 The black square (■) indicates a switch position. 71 60 50 1 2 3 4 5 100 SETTING ON OFF 1 2 3 4 5 35 1 2 3 4 5 ON OFF ON OFF ON OFF SW5 1 2 3 4 5 6 7 8 ON OFF SW1 1 2 3 4 5 <Table 2> SW2 (CAPACITY CODE) SW2 CAPACITY SETTING CAPACITY PEAD-RP·JA(L) MODELS <Table 1> SW1 (MODEL SELECTION) TO OUTDOOR UNIT ON OFF ON OFF SW6 1 2 TO CND 1 2 TO CN3C ACL 1 2 1 2 S1 S2 S3 L N TO OUTDOOR UNIT POWER SUPPLY ~ (1PHASE) 220-240V 50Hz THE REPLACEMENT WIRING) < A> (IN CASE OF CONNECT NOTE: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3). 3. Symbols used in wiring diagram above are, terminal block, connector. A S3 TB4 S1 S2 PEAD-RP60JA(L) SYMBOL I.B. CN2A CN2L CN32 CN41 CN51 CN90 CN105 LED1 LED2 LED3 SYMBOL EXPLANATION t˚ CN4F 1 2 3 4 ON OFF CN44 SW5 SW2 SW1 2 ACL TO MA REMOTE CONTROLLER PEAD-RP50JA(L) PEAD-RP125JA(L) TH2 t˚ LED3 CN90 1 CN3C 3 (Blue) I.B. 1 TB15 1 2 INSIDE SECTION OF CONTROL BOX PEAD-RP35JA(L) PEAD-RP100JA(L) PEAD-RP71JA(L) PEAD-RP35EA2 PEAD-RP100EA2 PEAD-RP50EA PEAD-RP125EA [LEGEND] NAME SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SW2 FUSE FUSE(T6.3AL250V) SWE ZNR VARISTOR X1 CN2L CONNECTOR(LOSSNAY) X4 X5 CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) X6 CN41 CONNECTOR(HA TERMINAL-A) P.B. CN51 CONNECTOR(CENTRALLY CONTROL) DRAIN PUMP DP CN90 CONNECTOR(WIRELESS) LED1 POWER SUPPLY(I.B.) DS LED2 POWER SUPPLY(REMOTE CONTROLLER) C LED3 TRANSMISSION(INDOOR·OUTDOOR) MF SW1 SWITCH(MODEL SELECTION) PEAD-RP60EA NAME SWITCH(CAPACITY CODE) SWITCH(EMERGENCY OPERATION) RELAY(DRAIN PUMP) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) INDOOR POWER BOARD (OPTIONAL PARTS) DRAIN PUMP DRAIN SENSOR CAPACITOR(FAN MOTOR) FAN MOTOR PEAD-RP71EA NAME SYMBOL TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TB5 TERMINAL BLOCK(REMOTE CONTROLLER) TH1 INTAKE AIR TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0 /15kΩ, 25/5.4kΩ DETECT) TH5 COND./EVA. TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) INSIDE SECTION OF CONTROL BOX DS TH1 TH2 TH5 1 B B L L U U 3 CN31 1 2 1 2 CN22 (BLU) CN20 (RED) I.B. 1 2 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 1 2 1 2 3 45 1 2 3 CN21 CN29 (WHT) (BLK) CN31 (WHT) CN90 (WHT) CN41 (WHT) CN24 (YLW) CN51 (WHT) CN32 (WHT) 1 2 1 2 SW1 CN2L (RED) SW2 SWE ON OFF LED1 LED2 LED3 2 1 WHT BLK X1 (BLU) CN3C O3B 1 R R N N X4 X5 X6 X5 CN2D (WHT) ZNR FUSE (ORN) CND W3B1 H L T K O3Y 1 R L N W X4 X1 (RED) CNDK 3 1 X6 7 5 3 1 (BLU) CNP W P P B H N N L T K K K (WHT) FAN <PEAD-RP35·50·60EA, 35EA2> External static pressure 30Pa W B H L T K 2 1 TB5 BL TO MA-REMOTE CONTROLLER DC8.7-13V U B L U 2 1 TB4 S3 S2 S1 TO OUTDOOR UNIT +A 2 1 B L K W H T CN2S (WHT) 3 1 CNSK (RED) <PEAD-RP71·100·125·140EA, 100EA2> External static pressure 70Pa DP P.B. <PEAD-RP35·50·60EA, 35EA2> External static pressure 70Pa Optional parts 1 2 3 4 5 6 Optional parts 1 2 3 4 5 6 (RED) (WHT) BRN ORN YLW MF MF C MODELS SW1 SW2 Model selection Capacity cord switch switch 12345 35EA(2) 12345 50EA 12345 60EA 71EA 100EA(2) 125EA 140EA 12345 12345 ON OFF 12345 12345 12345 (RED) 1 2 3 4 5 6 ON OFF ON OFF ON OFF ON OFF ON OFF The black square ( ■ ) indicates a switch position. <PEAD-RP71·100·125·140EA, 100EA2> External static pressure 130Pa <+A> (IN CASE OF CONNECTING THE REPLACEMENT WIRING) ON OFF ON OFF C L N 1 2 1 2 TO CND S1 S2 S3 1 2 POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT TO CN3C Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to +A. +2: For power supply system of this unit, refer to the caution label located near this diagram. 26 PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA [LEGEND] NAME NAME SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SW1 SWITCH(MODEL SELECTION) FUSE FUSE(T6.3AL250V) SW2 SWITCH(CAPACITY CODE) ZNR VARISTOR SWE SWITCH(EMERGENCY OPERATION) CN2L CONNECTOR(LOSSNAY) X1 RELAY(DRAIN PUMP) X4 RELAY(FAN MOTOR) CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) X5 RELAY(FAN MOTOR) CN41 CONNECTOR(HA TERMINAL-A) X6 RELAY(FAN MOTOR) CN51 CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) CN90 CONNECTOR(WIRELESS) MF LED1 POWER SUPPLY(I.B.) FAN MOTOR LED2 POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) LED3 TRANSMISSION(INDOOR·OUTDOOR) NAME SYMBOL TERMINAL BLOCK(REMOTE CONTROLLER) TB5 TH1 INTAKE AIR TEMP.THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0 /15kΩ, 25/5.4kΩ DETECT) TH5 COND./EVA. TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) INSIDE SECTION OF CONTROL BOX TH1 TH2 TH5 B B L L U U I.B. 1 2 1 2 1 2 1 2 CN22 (BLU) CN20 (RED) CN21 (WHT) CN29 (BLK) 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 CN90 (WHT) CN41 (WHT) CN31 (WHT) 1 2 CN24 (YLW) 1 2 3 4 5 1 2 3 CN51 (WHT) CN32 (WHT) 1 2 SW1 CN2L (RED) SW2 SWE ON LED1 LED2 LED3 2 1 WHT BLK OFF X1 (BLU) CN3C O3B1 R R N N ZNR (ORN) CND W3B1 H L T K O3Y1 R L N W 2 1 TB5 BL U B L U 2 1 TB4 S3 S2 S1 TO OUTDOOR UNIT +A 2 CN2S (WHT) B L K 3 3 1 (BLU) CNP P.B. 1 X4 X6 7 5 3 1 G Y Y B R L L L Y W W K B B O L L R U K G CNSK (RED) (WHT) FAN *External static pressure CONNECTOR COLOR 220V * 1 2 3 4 5 6 (WHT) 230V 240V BLU 5Pa 10Pa 20Pa WHT 35Pa 50Pa 60Pa RED 50Pa 70Pa 75Pa (INITIAL SETTING) MF C THE REPLACEMENT WIRING) L N 1 2 TO CND 1 W H T (RED) CNDK BRN ORN YLW <+A> (IN CASE OF CONNECT 1 2 X1 FUSE W B H L T K TO MA-REMOTE CONTROLLER DC8.7-13V X4 X5 X6 X5 CN2D (WHT) S1 S2 S3 1 2 TO CN3C POWER SUPPLY ~(1PHASE) 230V 50Hz MODELS 100GA SW2 12345 60GA 71GA TO OUTDOOR UNIT SW1 Model selection Capacity cord switch switch 12345 ON OFF 12345 12345 ON OFF ON OFF ON OFF The black square ( ■ ) indicates a switch position. Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to +A. +2: For power supply system of this unit, refer to the caution label located near this diagram. 27 PKA-RP35HAL PKA-RP50HAL [Explanation of symbols] Symbol Name I.B Indoor controller board CN2L Connector (LOSSNAY) CN32 Connector ( Remote switch) CN41 Connector (HA terminal-A) CN51 Connector (Centrally control) CN90 Connector (Remote operation adapter) FUSE FUSE(T3.15AL250V) LED1 Power supply (I.B) LED2 Power supply (R.B) LED3 Transmission (Indoor-outdoor) SW1 Switch (Model selection) +See table 1 SW2 Switch (Capacity code) +See table 2 Connector (Emergency operation) SWE X1 Relay (Drain pump (option)) Drain pump (option) power supply (Drain pump (option)) CNP CN4F Drain float switch (Drain pump (option)) R.B Wired remote controller(option) TB6 Terminal block (Remote controller transmission line) Symbol M MS S.W SWE2 TB2 TB4 TB5 TH1 Name Vane motor Fan motor Switch board Emergency operation Terminal block(Indoor unit Power (option)) Terminal block (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line(option)) Room temp. Thermistor (0/15kΩ, 25/5.4kΩ Detect) TH2 Pipe temp. Thermistor/liquid (0/15kΩ, 25/5.4kΩ Detect) TH5 Cond./eva. temp. Thermistor (0/15kΩ, 25/5.4kΩ Detect) PCB for wireless remote controller LED (Operation indication : Green) LED (Preparation for heating: Orange) Receiving unit REACTOR DRAIN PUMP (OPTION) DRAIN FLOAT SWITCH (OPTION) W.B LED1 LED2 REC1 DCL DP FS MS 3~ <Table 1> SW1 (MODEL SELECTION) DCL I.B CNMF 6 (WHT) FUSE 1 T11 SWE DB1 LED3 Refer to tables 1and 2 1 2 CN2L (RED) 1 CN151 (WHT) 5 9 CN90 (WHT) 1 CN20 (RED) 1 2 CN41 (WHT) 1 CN44 (WHT) 4 4 YLW 1 CN32 3 (WHT) 1 1 5 CN51 (WHT) CN4F (WHT) LDSWE(A) (BLU) CNRU (WHT) YLW ORN BLK 1 2 3 4 5 TO OUTDOOR UNIT MODELS M 1~ 2 S.W 1 2 3 4 5 RP50 LDSWE(B) SWE2 W.B 6 SETTING 1 2 3 4 5 RP35 ORN BRN ON OFF <Table 2> SW2 (CAPACITY CODE) DP 3 X1 1 CNP(BLU) CN3C 3 (BLU) 1 LED2 1 1 3 5 CN01 (BLK) LED1 ON OFF SETTING TB4 YLW S1 ORN S2 S3 ON OFF ON OFF The black square ( ) indicates a switch position. RU LD101(B) REC1 R.B BLU 4 LED1 CN22 1 (BLU) 2 BLU LED2 1 2 TB6 1 2 TB5 (OPTION PARTS) M t ○ t ○ TH1 t TH2 TH5 ○ When attaching When attaching drain drain pump(option), pump (option) remove the jumper 1 4 connector CN4F FLOAT SW CN4F and fit the drain (WHT) FS float switch (FS). +1(Fig. 1) CN01 I.B (BLK) 1 3 5 YLW ORN Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). I.B 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 1 3 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit CN3C(BLU) electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies , refer to Fig 1. +2: For power supply system of this unit, refer to the caution label located near this diagram. 28 RED BLU GRN/YLW YLW ORN ORN BRN TB2 L N POWER SUPPLY ~(1PHASE) 230V 50Hz TB4 S1 S2 S3 INDOOR/OUTDOOR COMMUNICATION TO OUTDOOR UNIT PKA-RP60KAL PKA-RP100KAL [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 CN90 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 CNP CN4F R.B TB6 NAME Indoor controller board Connector (LOSSNAY) Connector (Remote switch) Connector (HA terminal-A) Connector (Centrally control) Connector (Remote operation adapter) FUSE (T3.15AL250V) Power supply (I.B) Power supply (R.B) Transmission (Indoor-outdoor) Switch (Model selection) +See table 1 Switch (Capacity code) +See table 2 Connector (Emergency operation) Relay (Drain pump(option)) Drain pump (option) power supply (Drain pump(option)) Drain float switch (Drain pump (option)) Wired remote controller Terminal block (Remote controller transmission line) SYMBOL M MS S.W SWE2 TB2 TB4 TB5 TH1 TH2 TH5 W.B LED1 LED2 REC1 DCL DP FS NAME Vane motor Fan motor Switch board Emergency operation Terminal block (Indoor unit Power (option)) Terminal block (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line) Room temp. Thermistor (0 / 15k, 25 / 5. 4k Detect) Pipe temp. Thermistor/liquid (0 / 15k, 25 / 5. 4k Detect) Cond. / eva. temp. Thermistor (0 / 15k, 25 / 5. 4k Detect) PCB for wireless remote controller LED (Operation indication : Green) LED (Preparation for heating : Orange) Receiving unit REACTOR DRAIN PUMP (OPTION) DRAIN FLOAT SWITCH (OPTION) MF +1(Fig. 1) CN01 I.B (BLK) YLW 1 ORN 3 5 INDOOR/OUTDOOR COMMUNICATION The black square ( ) indicates a switch position. Notes: 1. SymboIs used in wiring diagram above are, :Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. +1 If indoor and outdoor units have separate power supplies , refer to Fig 1. +2 For power supply system of this unit, refer to the caution label located near this diagram. 29 TB2 L N YLW TB4 ORN S1 ORN S2 BRN S3 I.B 1 3 CN3C (BLU) RED BLU GRN/YLW POWER SUPPLY ~(1PHASE) 230V 50Hz TO OUTDOOR UNIT [LEGEND] SYMBOL P.B I.B FUSE ZNR CN2L CN32 CN41 CN51 SW1 SW2 SWE X4 BCR LED1 LED2 LED3 PKA-RP50GAL SYMBOL C MF MV TB2 NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V) VARISTOR CONNECTOR <LOSSNAY> CONNECTOR <REMOTE SWITCH> CONNECTOR <HA TERMINAL-A> CONNECTOR <CENTRALLY CONTROL> SWITCH <MODEL SELECTION>+See Table 1. SWITCH <CAPACITY CODE>+See Table 2. SWITCH <EMERGENCY OPERATION> RELAY <FAN MOTOR> FAN CONTROL ELEMENT POWER SUPPLY <I.B> POWER SUPPLY <R.B> TRANSMISSION <INDOOR-OUTDOOR> P.B CNDK (RED) TB4 TB5,TB6 TH1 TH2 TH5 1 2 3 TB4 YLW S1 S2 ORN S3 ORN BRN BLK WHT POWER POWER 1 2 1 3 VANE CNDK 1 3 CND 1 3 CN6V INDOOR/OUTDOOR (GRN) (RED) (ORN) POWER CN2D(WHT) COMMUNICATION CN3C(BLU) ZNR X4 THERMAL FUSE <10410A> THERMAL FUSE <8410A> HEATER HEATER THERMAL SWITCH HEATER CONTACTOR CN41 CN2L CN51 CN32 RED BLU GRN/YLW TO OUTDOOR UNIT I.B 6 FUSE X4 BCR YLW ORN RED WHT RED WHT BLK FAN 1 3 5 (WHT) NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED <RUN INDICATOR> LED <HOT ADJUST> SWITCH (HEATING ON/ OFF> SWITCH (COOLING ON/ OFF> WIRED REMOTE CONTROLLER BOARD +1 (Fig.1) 1 2 C I.B SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 R.B HEATER FS1 FS2 H1 26H 88H CN2S (WHT) 1 2 DC13.1V 3 MF NAME CAPACITOR <FAN MOTOR> FAN MOTOR VANE MOTOR TERMINAL BLOCK (HEATER) +PKH-P.GALH models only or option for PKA-RP.GAL models. TERMINAL BLOCK <INDOOR/ OUTDOOR CONNECTING LINE> TERMINAL BLOCK <REMOTE CONTROLLER TRANSMISSION LINE> <OPTION> ROOM TEMP.THERMISTOR <0/ 15k, 25/ 5.4k DETECT> PIPE TEMP.THERMISTOR/ LIQUID <0/ 15k, 25/ 5.4k DETECT> COND./ EVA.TEMP.THERMISTOR <0/ 15k, 25/ 5.4k DETECT> MV WIRELESS CN90 (WHT) TB2 L N POWER SUPPLY ~(1PHASE) 230V 50Hz YLW TB4S1 ORN S2 ORN S3 BRN YLW ORN PKA-RP35GAL 1 3 TO OUTDOOR UNIT 1 3 POWER INDOOR/OUTDOOR CND COMMUNICATION (ORN) CN3C (BLU) 9 LED3 LED2 LED1 SW2 SWE ON OFF SW1 INTAKE LIQUID PIPE CN20 CN21 CN29 (RED) (WHT) (BLK) 1 2 1 2 1 2 CNB BZ REMOCON CN22 (BLU) RU RECEIVER LED1 LED2 SW2 SW1 1 2 W.B Refer to tables 1 and 2 for service PCB. TH2 TH1 2 1 TH5 R.B TRANSMISSION WIRES DC12V 1 TB6 2 TB5 PKH-P35,50GALH models only 1 2 YLW YLW I.B HEATER CN24 (YLW) 6 H1 RED 88H 1 SW1 Service board 1 2 3 4 5 ON OFF 6 GRY 5 RED FS1 26H MODELS PKA-RP35GAL PKH-P35GALH FS2 RED WHT 1 2 RED 5 88H TB2 L 3 RED N BLU GRN/YLW SW2 Service board MODELS Service board 1 2 3 4 5 1 2 3 4 5 ON OFF PKA-RP50GAL PKH-P50GALH POWER SUPPLY ~(1PHASE) 230V 50Hz Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. ON OFF The black square ( ■ ) indicates a switch position. Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to Fig 1. +2: For power supply system of this unit, refer to the caution label located near this diagram. 30 [LEGEND] SYMBOL P.B I.B FUSE ZNR CN2L CN32 CN41 CN51 SW1 SW2 SWE X4 BCR LED1 LED2 LED3 PKA-RP60FAL NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE(T6.3AL250V) VARISTOR CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) SWITCH (MODEL SELECTION) +See Table 1. SWITCH (CAPACITY CODE) +See Table 2. SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR) FAN CONTROL ELEMENT POWER SUPPLY(I.B) POWER SUPPLY(R.B) TRANSMISSION(INDOOR-OUTDOOR) P.B CNDK (RED) SYMBOL C MF MV TB2 MF 1 2 3 NAME CAPACITOR(FAN MOTOR) FAN MOTOR VANE MOTOR TERMINAL BLOCK (HEATER) +PKH-P.FALH models only or option for PKA-RP.FAL models. TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE )(OPTION) ROOM TEMP.THERMISTOR (0/15k, 25/5.4k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0/15k, 25/5.4k DETECT) COND./EVA.TEMP.THERMISTOR (0/15k, 25/5.4k DETECT) TB4 TB5 TH1 TH2 TH5 1 2 TB4 YLW S1 S2 ORN S3 ORN BRN X4 BCR BLK WHT POWER POWER 1 2 1 3 VANE CNDK 1 3 CND 1 3 CN6V INDOOR/OUTDOOR (GRN) (ORN) (RED) POWER CN2D(WHT) COMMUNICATION CN3C(BLU) ZNR X4 CN41 CN2L CN51 CN32 NAME WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED(RUN INDICATOR ) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) WIRED REMOTE CONTROLLER BOARD(OPTION) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) HEATER FS1,2 THERMAL FUSE(117 10A:60,71FALH/ 117 16A:100FALH) HEATER H1 26H HEATER THERMAL SWITCH 88H HEATER CONTACTOR +1 (Fig.1) RED BLU GRN/YLW TO OUTDOOR UNIT I.B 6 FUSE FAN 1 3 5 (WHT) YLW ORN RED WHT RED WHT BLK C I.B SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 R.B TB6 Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual CN2S (WHT) 1 2 DC13.1V 3 PKA-RP100FAL 1 3 MV TB2 L N POWER SUPPLY (1PHASE) 230V 50Hz YLW TB4S1 ORN S2 ORN S3 BRN YLW ORN PKA-RP50FAL2 TO OUTDOOR UNIT 1 3 POWER INDOOR/OUTDOOR CND COMMUNICATION (ORN) CN3C (BLU) 9 WIRELESS CN90 (WHT) LED3 LED2 LED1 SWE ON OFF SW2 SW1 INTAKE LIQUID PIPE CN20 CN21 CN29 (RED) (WHT) (BLK) 1 2 1 2 1 2 CNB BZ REMOCON CN22 (BLU) RU RECEIVER LED1 LED2 SW2 SW1 1 2 W.B Refer to tables 1 and 2 for service PCB. TH2 TH1 Table 1 SW1 Service board 2 1 TH5 Service board MODELS MODELS PKA-RP50FAL2 1 2 3 4 5 1 2 3 4 5 PKA-RP71FAL ON ON PKA-RP60FAL OFF OFF PKH-P71FALH PKH-P60FALH The black square ( ■ ) indicates a switch position. HEATER 6 88H 1 2 3 4 5 MODELS PKA-RP100FAL ON OFF PKH-P100FALH Service board 1 2 3 4 5 ON OFF P100FALH models only FS1 RED 1 SW2 Service board H1 CN24 1 2 (YLW) YLW YLW I.B 1 TB6 2 TRANSMISSION WIRES DC12V TB5 Table 2 PKH-P60 R.B 6 GRY 5 RED FS2 26H RED WHT 1 2 RED 5 88H TB2 L 3 RED N BLU GRN/YLW POWER SUPPLY (1PHASE) 230V 50Hz Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to Fig 1. +2: For power supply system of this unit, refer to the caution label located near this diagram. 31 4-2. OUTDOOR UNIT PUHZ-HRP71VHA PUHZ-HRP100VHA SYMBOL P.B. TABU/V/W TABS/T TABP1/P2/P TABN1/N2/N DS2, DS3 IPM N.F. LI / LO NI / NO EI, E2 52C C.B. SW1 NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal <L/N-Phase> Connection Terminal<DC Voltage> Connection Terminal<DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Terminal<L-Phase> Connection Terminal<N-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> SW4 SW5 SYMBOL SW6 SW7 SW8 SW9 SWP CN31 SS CNM CNMNT NAME Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch Switch<Pump Down> Connector<Emergency Operation> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector CNVMNT <Connected to Optional M-NET Adapter Board> Connector CNDM < Connected for Option (Contact Input)> LED1,LED2 LED<Operation Inspection Indicators> Fuse< T6.3AL250V> F1~F4 X51,X52,X55 Relay When M-NET adapter is connected LEV-C LEV-A LEV-B M M TH33 TH32 TH7 TH6 TH3 TH4 M 5 C. B. t° t° t° 7 1 CNF2 (WHT) 3 63L 63H (RED) (YLW) 1 3 TRANS 2 1 3 6 1 LEV-B (RED) 1 CN2 (WHT) F1 3 1 21S4 3 (GRN) F4 4 14 LEV-C (BLU) 6 1 2 3 1 SV2 3 M-NET SUBSTRATE 2 1 CN2M (WHT) 3 1 3 A B S TB7 1 M-NET 5 (WHT) SV BLU WHT N. F. NO 2 CN52C (BLK) P. B. 1 CNAF (WHT) CNDC (PNK) 2 6 1 BLK TABN1 BLK E2 U 2 BLK W NI RED L1 L2 1 P N1 N2 BLK 6 RED L N S1 S2 BRN BLK WHT 4 ORN DCL EI U BLU RED MC M-NET ADAPTER NAME Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1st digit> Switch<Address setting : 2nd digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V> U LI GRN/YLW YLW V MS 3~ CN5 (RED) 1 CNAC1 (WHT) BLU U SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 2 1 3 RED RED 1 2 1 2 TABP CNAC2 (RED) WHT TABN2 WHT CB CN5 (RED) CN4 (WHT) TABN TABS WHT 1 TABW 2 DS2 TABP1 RED RED TABU t° 2 7 1 CN3 2 (WHT) TABT BLU 3 IPM WHT TABV BLK TH8 TABP2 CN2 (WHT) DS3 3 1 RED 7 2 1 52C LO 4 CND (WHT) 3 1 1 SS (BLU) 21S4 SW12 LED4 CN31 1 2 X52 2 3 1 5 CN52C (RED) 2 1 7 1 7 F3 CNAC (WHT) 1 3 CNM (WHT) 5 2 F2 1 CNVMNT CNMNT (WHT) (WHT) CN4 (WHT) CNDC 1 (PNK) CNS (WHT) 6 SW6 LEV-A (WHT) SW1 1 2 1 CNDM (WHT) 12 CN51 (WHT) 4 SW4 SWP SW8 1 LED3 +1 X51 1 2 3 X55 1 SW5 +1 CNF1 (WHT) TH33 TH32 TH7/6 TH3 TH4 (YLW) (BLK) (RED) (WHT) (WHT) MF2 1 MS 3~ 5 5 t° t° LED1 MF1 1 MS 3~ t° LED2 7 SW11 CN5 (WHT) SW1 1 LED2 5 3 SW7 63L SW9 63H LED1 NAME Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch Solenoid Valve (Bypass Valve) Thermistor<Outdoor Pipe> Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Electronic Expansion Valve Reactor Active Filter Module Main Smoothing Capacitor Capacitor LED5 [LEGEND] SYMBOL TB1 MC MF1, MF2 21S4 63H 63L SV TH3,TH32,TH33 TH4 TH6 TH7 TH8 LEV-A, LEV-B,LEV-C DCL ACTM CB CY1,CY2 CY1 CY2 S3 TB1 WHT Io +1MODEL SELECT ACTM INDOOR UNIT POWER SUPPLY ~/N 230V 50Hz The black square ( ■ ) indicates a switch position. MODEL 71V SW6 ON OFF ON 100V OFF 32 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SW5-6 +2 ON OFF ON OFF 1 2 3 4 5 6 1 2 3 4 5 6 PUHZ-HRP100YHA [LEGEND] SYMBOL TB1 TB2 MC MF1, MF2 21S4 63H 63L SV TH3,TH32,TH33 TH4 TH6 TH7 LEV-A, LEV-B, LEV-C ACL1~ACL4 CB1, CB2 CK CY1, CY2 RS PUHZ-HRP125YHA NAME Terminal Block<Power Supply> Terminal Block<Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch Solenoid Valve (Bypass Valve) Thermistor<Outdoor Pipe> Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Electronic Expansion Valve Reactor Main Smoothing Capacitor Capacitor Capacitor Rush Current Protect Resistor SYMBOL P.B. TB-U/V/W TB-L1/L2/L3 TB-P2 TB-C1 TB-N1 X52A N.F. LI1/LI2/LI3/NI LO1/LO2/LO3/NO GD1, GD3 CONV.B. L1-A1/IN L1-A2/OU L2-A2/OU L3-A2/OU N-IN CK-OU NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2/L3-Power Supply> Connection Terminal Connection Terminal Connection Terminal 52C Relay Noise Filter Circuit Board Connection Terminal<L1/L2/L3/N-Power Supply> Connection Terminal<L1/L2/L3/N-Power Supply> Connection Terminal<Ground> Converter Circuit Board Connection Terminal<L1-Power Supply> Connection Terminal<L1-Power Supply> Connection Terminal<L2-Power Supply> Connection Terminal<L3-Power Supply> Connection Terminal Connection Terminal SYMBOL C.B. SW1 NAME Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Adress> SW4 Switch<Test Operation> SW5 Switch<Function Switch> SW6 Switch<Model Select> SW7 Switch<Function Setup> SW8 Switch<Function Setup> SW9 Switch SWP Switch<Pump Down> CN31 Connector<Emergency Operation> LED1, LED2 LED<Operatiion Inspection Indicators> F1~F4 Fuse<T6.3AL250V> CNM Connector<A-Control Service Inspection Kit> Connector CNMNT <Connect to Optional M-NET Adapter Board> Connector CNVMNT <Connect to Optional M-NET Adapter Board> Connector CNDM < Connection for Option(Contact Input)> CN3S Connector< Connection for Option> CN51 Connector< Connection for Option> SS Connector< Connection for Option> X51,X52,X55 Relay M-NET ADAPTER TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 Terminal Block<M-NET connection > Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting: 1st digit> Switch<Address setting. 2nd digit > LED<Power Supply: DC5V> LED<Connection to Outdoor Unit> LED<Transmission: Sending> LED<Transmission: Receiving> LED<Power Supply: DC12V> LEV-C t° 5 5 CN2 (WHT) 7 1 1 CNDC (PNK) 14 CNM (WHT) LEV-C (BLU) 6 2 3 1 21S4 3 (GRN) BLK BLU 21S4 P.B. 3 1 SV2 (BLU) 3 CN51 (WHT) X51 X52 F4 3 4 2 1 1 SS (WHT) SV 1 3 3 TB7 1 M-NET 5 +1MODEL SELECT The black square (■) indicates a switch position. MODEL 7 SW6 ON 100Y OFF BLK TB-L2 WHT TB-L1 RED BLK TB-L3 + TB-P2 CB1 TB-N1 + CB2 3 3 1 CK CONV.B. L1-IN L1-A1 + TB-C1 1 2 3 4 5 6 7 8 +2. SW5 -1 to 5 : Function Switch L3-OU BLK RS ORN 3~ + RED WHT S3 V MS 2 2 1 ACL1 LI2 U BLK BLU LI3 NI RED U LO2 WHT U LO3 BLK U NO BLU GRN/YLW GD3 33 CNDC (PNK) 2 1 3 U -1 CNL (BLU) 3 WHT GD1 ACL2 + + U WHT N WHT LO1 BLK L3 LI1 BLK L2 RED BLU CNAC2 3 (RED) TB1 L1 POWER SUPPLY 3N~ 400V 50Hz CNCT (RED) 1 3 RED CNAC1 (WHT) 1 RED N.F. NO FUSE BREAKER ON OFF RED TB-U -- RED INDOOR UNIT S2 WHT SW5-6 +2 ON OFF 1 2 3 4 5 6 7 8 ON 125Y OFF W MC BLK U + BRN S1 TB-W + -- 2 CN5 1 (RED) X52A RED YLW TB2 7 TB-V 2 CN4 1 (WHT) CY2 CY1 2 CN2 (WHT) BLK 2 1 CN7 (WHT) 1 3 CN7 (WHT) CND (WHT) 3 1 A B S 1 3 L1-A2 1 SW12 LED3 LED4 M-NET SUBSTRATE BLK CK-OU F1 CNS (WHT) 3 F3 CNAC (WHT) 1 2 X55 7 F2 LED2 CN31 CN4 (WHT) 1 2 SW11 SW1 LED5 CN2M (WHT) LED1 1 1 RED 1 5 WHT TRANS 1 3 1 5 CNVMNT CNMNT (WHT) (WHT) L2-A2 3 (RED) 6 L1-OU RED 63L 1 63H (YLW) LEV-B (RED) N-IN 3 6 1 L3-A2 1 LEV-A (WHT) L2-OU WHT CNF2 (WHT) 1 SW6 1 2 21 TH3 TH4 (WHT) (WHT) SW1 1 4 TH7/6 (RED) SW5 1 3 1 2 TH33 TH32 (YLW) (BLK) 5 +1 SW7 +1 3 2 When M-NET adapter is connected) 5 3 CNDM CN3S (WHT) (WHT) 7 MS 3~ M SW4 SWP SW8 1 MF2 t° M LED1 MS 3~ t° t° M LED2 CNF1 7 (WHT) 1 MF1 t° t° LEV-B SW9 C.B. LEV-A CN5 (WHT) 63L 63H TH33 TH32 TH7 TH6 TH3 TH4 ACL4 ACL3 1 2 3 4 5 6 1 2 3 4 5 6 SW6 SW7 SW8 SW9 SWP LEV-C 1 1 CNDC (PNK) CN2 (WHT) 1 1 1 2 7 1 F1 3 1 2 21S4 3 F4 4 LEV-C (BLU) 1 SW7 SW9 SW6 2 1 1 SV1 CND (WHT) 3 1 CN31 3 3 (GRN) M-NET ADAPTER CN2M (WHT) 3 6 3 SW12 LED4 1 3 A B S TB7 1 F3 CNAC (WHT) 1 14 CNM (WHT) CN52C (RED) 5 CN4 (WHT) 2 7 F2 3 3 LED3 +1 CNDM (WHT) TRANS 2 CNS (WHT) 1 1 3 1 5 CNVMNT CNMNT (WHT) (WHT) SW5 +2 1 3 1 6 1 6 63HS LEV-A LEV-B (WHT) (WHT) (RED) NAME Terminal Block<M-NET connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Receiving> LED<Power Supply : DC12V> SW11 CN5 (WHT) SW1 1 LED2 5 63L 1 3 (RED) 63H (YLW) 3 5 CN51 (WHT) 7 MS 3~ SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 5 5 3 t° CNF2 (WHT) 1 M SW1 t° M-NET ADAPTER When M-NET adapter is connected SW4 SWP SW8 t° LEV-B M LED1 t° LEV-A X52 MS 3~ 3 M-NET 5 1 SS (WHT) (GRY) 21S4 2 P. B. 1 2 CN4 (WHT) 1 CN2 (WHT) CN52C 3 (RED) 1 7 52C 52C BLK 2 WHT CNDC (PNK) N2 3 CE E3 1 CNAC2 (RED) 1 P2 RED IGBT 3 E2 BLK 1 3 CNAC1 (WHT) RED WHT E4 W V U MS 3~ DCL1 EI NI U U LI BLK BLK L BLU RED MC CY1 CY2 N S1 BRN DCL ORN DCL2 GRN/YLW YLW W V U BLK WHT RED MF2 t° t° CNF1 4 1 2 21 7 (WHT) 1 3 1 2 1 TH33 TH32 TH7/6 TH3 TH4 (YLW) (BLK) (RED) (WHT) (WHT) LED2 C.B. 1 NAME Connector<Emergency Operation> SV1 Connector<Connection for Option> Connector<Connection for Option> SS CNM Connector<A-Control Service Inspection Kit> Connector CNDM < Connected for Option (Contact Input)> LED1,LED2 LED<Operation Inspection Indicators> Fuse< T6.3AL250V> F1~F4 X51,X52,X54 Relay M TH33 TH32 TH7 TH6 TH3 TH4 MF1 SYMBOL CN31 LED1 SW4 SW5 NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal <L-Phase> Connection Terminal<N-Phase> Recator Power Module Connection Terminal (Ground) Controller Circuit Board Switch<Manual Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch, Model Select> Switch<Model Select> Switch<Function Set up> Switch<Function Set up> Switch<Function Switch> Switch<Pump Down> 63HS 63L 63H SYMBOL P.B. U/V/W LI NI DCL1, DCL2 IGBT E1,E2,E3,E4 C.B. SW1 LED5 NAME Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor<Liquid> Thermistor<Discharge> Thermistor<2-Phase> Thermistor<Ambient> Thermistor<Suction> Thermistor<Ref. check> Electronic Expansion Valve Reactor Main Smoothing Capacitor Capacitor X51 [LEGEND] SYMBOL TB1 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH32 TH33 LEV-A, LEV-B,LEV-C DCL CE CY1,CY2 PUHZ-HRP100VHA2 X54 PUHZ-HRP71VHA2 S2 Ambient temp. 3°C or less (lnitial setting) SW9-3,4 +4 ON OFF 1 2 3 4 Ambient temp. 0°C or less SW9-3,4 +4 ON OFF 1 2 3 4 MODEL SW6 71V ON OFF 100V ON OFF S3 TB1 INDOOR UNIT +3 Setting of the starting ambient temp. of the flash injection. The black square (■) indicates a switch position. +1 MODEL SELECT The black square (■) indicates a switch position. 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Ambient temp. +4. SW9-1 to 2 : Function Switch 34 SW9-3,4 +4 ON OFF 1 2 3 4 ON OFF 1 2 3 4 5 6 1 2 3 4 5 6 +2 SW5 -1 to 5 : Function Switch POWER SUPPLY ~/N 230V 50Hz -3°C or less SW5-6 +2 ON OFF Ambient temp. -6°C or less SW9-3,4 +4 ON OFF 1 2 3 4 SYMBOL P.B. TB-U/V/W TB-L1/L2/L3 TB-P2 TB-C1 TB-N1 X52A N.F. LI1/LI2/LI3/NI LO1/LO2/LO3/NO GD1, GD3 CONV.B. L1-A1/IN L1-A2/OU L2-A2/OU L3-A2/OU N-IN CK-OU 1 2 14 CNM (WHT) LEV-C (BLU) SW7 SW6 1 3 3 7 ON 100Y OFF WHT V MS + CB1 + CB2 3 3 1 CK CONV.B. L1-IN L1-A1 + TB-N1 TB-C1 BLK TB-P2 2 2 1 CNAC2 3 (RED) BLU CNCT (RED) 1 3 RED CNAC1 (WHT) 1 RED N.F. ACL1 TB1 L1 L2 L3 N WHT LI2 U LI3 BLK NI BLU LO1 RED U LO2 WHT U LO3 BLK U NO BLU GRN/YLW CNDC (PNK) 1 2 3 ACL3 U -1 CNL (BLU) 3 WHT BLK GD3 BRN GD1 ACL2 + + U BLK POWER SUPPLY 3N~ 400V 50Hz RED LI1 ON OFF L1-A2 + RED WHT RED L3-A2 WHT TB-L1 BLK -- BLK TB-L2 1 2 3 4 5 6 7 8 ON OFF +2 SW5 -1 to 5 : Function Switch RED TB-L3 ON 125Y OFF 3~ U TB-U + RS ORN W MC BLK L3-OU BLK 2 CN5 1 (RED) WHT S3 TB-W + -- RED INDOOR UNIT S2 7 TB-V 2 CN4 1 (WHT) BRN S1 CN2 (WHT) X52A RED YLW TB2 1 1 2 3 4 5 6 7 8 CN7 (WHT) 1 3 CN7 (WHT) 2 M-NET +1 MODEL SELECT The black square (■) indicates a switch position. MODEL SW6 SW5-6 +2 P.B. 2 3 1 SS (WHT) 21S4 3 ACL4 +3 Setting of the starting ambient temp. of the flash injection. The black square (■) indicates a switch position. Ambient temp. 3°C or less (lnitial setting) SW9-3,4 +4 ON OFF 1 2 3 4 Ambient temp. 0°C or less SW9-3,4 +4 ON OFF NAME Terminal Block<M-NET connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Receiving> LED<Power Supply : DC12V> TB7 5 X51 1 SV1 (GRY) SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 A B S BLK CK-OU 3 4 1 21S4 3 (GRN) CND (WHT) 3 1 L1-OU RED 3 X54 1 F4 CN5 (WHT) 2 1 6 X52 F1 CNS (WHT) 3 SW12 LED3 LED4 M-NET ADAPTER 1 F3 CNAC (WHT) 1 2 LED2 CN31 7 F2 SW11 SW1 LED5 CN2M (WHT) LED1 CN2 (WHT) 7 1 CNDC (PNK) 1 5 CN4 (WHT) 1 2 1 3 1 5 CNVMNT CNMNT (WHT) (WHT) L2-OU WHT 63L 3 (RED) 1 3 1 6 1 6 63HS LEV-A LEV-B (WHT) (WHT) (RED) 1 SW9 3 5 +1 SW1 1 1 1 5 +2 63H (YLW) TRANS 5 3 5 CNF2 (WHT) 3 2 M t° CNDM (WHT) 7 M When M-NET adapter is connected CN51 (WHT) 1 MS 3~ LEV-B SW5 t° LEV-A LED1 t° M-NET ADAPTER M LED2 MS 3~ MF2 t° CNF1 4 1 2 21 7 (WHT) 1 3 1 2 1 TH33 TH32 TH7/6 TH3 TH4 (YLW) (BLK) (RED) (WHT) (WHT) 1 MF1 t° t° NAME Controller Circuit Board Switch<Manual Defrost, Defect History Record Reset, Refrigerant Address> SW4 Switch<Test Operation> SW5 Switch<Function Switch, Model select> SW6 Switch<Model Select> SW7 Switch<Function Set up> SW8 Switch<Function Set up> SW9 Switch<Function Switch> SWP Switch<Pump Down> CN31 Connector<Emergency Operation> Connector<Connection for Option> SV1 SS Connector< Connection for Option> LED1, LED2 LED<Operation Inspection Indicators> CNM Connector<A-Control Service Inspection Kit> Connector CNDM < Connection for Option(Contact Input)> F1~F4 Fuse<T6.3AL250V> X51,X52,X54 Relay LEV-C 63HS TH33 TH32 TH7 TH6 TH3 TH4 C.B. SYMBOL C.B. SW1 N-IN 63L 63H NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2/L3-Power Supply> Connection Terminal Connection Terminal Connection Terminal 52C Relay Noise Filter Circuit Board Connection Terminal<L1/L2/L3/N-Power Supply> Connection Terminal<L1/L2/L3/N-Power Supply> Connection Terminal<Ground> Converter Circuit Board Connection Terminal<L1-Power Supply> Connection Terminal<L1-Power Supply> Connection Terminal<L2-Power Supply> Connection Terminal<L3-Power Supply> Connection Terminal Connection Terminal RED NAME Terminal Block<Power Supply> Terminal Block<Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch High Pressure Sensor Thermistor<Liquid> Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Ambient> Thermistor<Suction> Thermistor<Ref. check> Electronic Expansion Valve Reactor Rush Current Protect Resistor Main Smoothing Capacitor Capacitor SW4 SWP SW8 [LEGEND] SYMBOL TB1 TB2 MC MF1, MF2 21S4 63H 63L 63HS TH3 TH4 TH6 TH7 TH32 TH33 LEV-A, LEV-B, LEV-C ACL1~ACL4 RS CB1, CB2 CK PUHZ-HRP125YHA2 L2-A2 PUHZ-HRP100YHA2 1 2 3 4 Ambient temp. -3°C or less +4. SW9-1 to 2 : Function Switch 35 SW9-3,4 +4 ON OFF 1 2 3 4 Ambient temp. -6°C or less SW9-3,4 +4 ON OFF 1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 5 REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT PLA-RP·BA/BA2/BA3 PKA-RP·FAL(2) PEAD-RP·EA(2) unit : mm PKA-RP·GAL PEAD-RP·JA(L) PEAD-RP·GA Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor with strainer(#50) Thermistor TH2 Pipe temperature (Liquid) Thermistor TH1 (Room temperature) Strainer(#50) PKA-RP·HAL PKA-RP·KAL Strainer (#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH2 Pipe temperature(Liquid) Thermistor TH5 (Cond./ Eva.temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Thermistor TH1 (Room temperature) Distributor with strainer (#50/#50: HAL) (#50/#100: KAL) 36 Strainer (#50) Unit : mm (inch) 5-2. OUTDOOR UNIT PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA Thermistor TH7 (Outdoor) Heat exchanger Refrigerant GAS pipe connection (5/8 inch) Thermistor TH6 (Outdoor 2-phase pipe) Solenoid valve (Four-way valve) Ball valve Strainer #50 Charge plug (High pressure) Charge plug (Low pressure) Muffler Thermistor TH3 (Outdoor pipe) High pressure switch 63H Low pressure switch 63L Linear expansion valve B Refrigerant LIQUID pipe Strainer connection #100 (3/8 inch) Stop valve (with service port) Thermistor TH33 (Outdoor pipe) Thermistor TH32 (Outdoor pipe) Strainer #100 Strainer #100 Distributor Strainer #100 Thermistor TH4 (Discharge) Bypass valve Linear expansion valve A Strainer #100 Compressor Power receiver Linear expansion valve C Replace filter Injection port Restrictor Strainer valve #100 Heat interchange circuit Refrigerant flow in cooling Refrigerant flow in heating PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 Heat exchanger Refrigerant GAS pipe connection (5/8 inch) Thermistor TH6 (Outdoor 2-phase pipe) Solenoid valve (Four-way valve) Ball valve High pressure sensor(63HS) Charge plug (High pressure) Strainer #50 Charge plug (Low pressure) Muffler Low pressure switch 63L Thermistor TH3 (Outdoor pipe) High pressure switch 63H Thermistor TH32 (Outdoor pipe) Strainer #100 Strainer #100 Linear expansion valve B Refrigerant LIQUID pipe Strainer connection #100 (3/8 inch) Stop valve (with service port) Thermistor TH7 (Outdoor) Distributor Thermistor TH33 (Outdoor pipe) Strainer #100 Thermistor TH4 (Discharge) Linear expansion valve A Strainer #100 Compressor Power receiver Linear expansion valve C Injection port Heat interchange circuit Refrigerant flow in cooling Refrigerant flow in heating 37 6 PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-HRP·VHA(2), PUHZ-HRP·YHA(2) Rated cooling capacity 1.4 Cooling capacity ratio Indoor intake air wet-bulb temperature <W.B. :> 1.2 22 1.0 20 18 0.8 0.6 16 -5 0 5 10 15 20 25 30 35 40 46 Outdoor intake air dry-bulb temperature <D.B. > Rated cooling input 22 20 18 16 Cooling input ratio 1.2 1.0 0.8 0.6 Indoor intake air wet-bulb temperature <W.B. :> 0.4 -5 0 5 10 15 20 25 30 35 40 Outdoor intake air dry-bulb temperature <D.B. > Note : This diagrams show the case where the operation frequency of a compressor is fixed. 38 46 Rated heating capacity 1.4 15 20 25 Capacity ratio 1.2 1.0 0.8 Indoor intake air dry-bulb temperature <: D.B.> 0.6 -25 -20 -15 -10 -5 0 5 10 15 Outdoor ambient temp.(˚CWB) Rated heating input 2.5 Input ratio 2.0 1.5 25 20 15 1.0 Indoor intake air dry-bulb temperature <: D.B.> 0.5 -25 -20 -15 -10 -5 0 5 Outdoor ambient temep.(ºCWB) 39 10 15 7 CORRECTION FACTORS PUHZ-HRP71, 100VHA(2) PUHZ-HRP100, 125YHA(2) Cooling capacity correction factors Outdoor unit Refrigerant piping length (one way) 5m 10m 20m 30m 40m 50m 55m 60m 70m 80m PUHZ-HRP71VHA(2) 1.00 0.988 0.966 0.946 0.929 0.913 0.905 0.897 0.876 0.870 PUHZ-HRP100VHA(2) PUHZ-HRP100YHA(2) 1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829 PUHZ-HRP125YHA(2) 1.00 0.981 0.946 0.914 0.885 0.858 0.845 0.834 0.812 0.792 Heating capacity correction factors Outdoor unit Refrigerant piping length (one way) 5m 10m 20m 30m 40m 50m 55m 60m 70m 80m PUHZ-HRP71VHA(2) 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955 PUHZ-HRP100VHA(2) PUHZ-HRP100YHA(2) 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955 PUHZ-HRP125YHA(2) 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955 40 8 APPLICABLE EXTENSION PIPE FOR EACH MODEL 8-1. PIPE LENGTH 8-1-1. 1:1 SYSTEM Pipe length <Table 1> Maximum pipe length Liquid pipe (mm) Gas pipe (mm) OD Thickness OD Thickness :9.52 t0.8 :15.88 t1.0 Standard size 50m + [30m] :12.7 t0.8 HRP71~125 :19.05 t1.0 :12.7 t0.8 :19.05 :15.88 t1.0 t1.0 50m [30m] 50m [20m] <Marks in the table> : It can be used. : Additional refrigerant charge is required when the pipe length exceeds 20m. 50m [20m] 50m [30m] + The maximum length is 75m in case of new pipes. The maximum pipe length Charge-less pipe length 8-1-2. TWIN SYSTEM (1) TWIN SYSTEM <Table 2> Maximum pipe length HRP71(RP35%2) Main pipe (mm) [A] Liquid pipe :6.35 :12.7 Gas pipe Liquid pipe :6.35 Gas pipe :12.7 Branch pipe Liquid pipe :9.52 (mm) Gas pipe :15.88 [B, C] Liquid pipe :9.52 Gas pipe HRP100(RP50%2) :9.52 :9.52 :15.88 :15.88 Standard size Standard size 50m 50m + [30m] [30m] 50m [30m] 50m [30m] :9.52 :19.05 :12.7 :19.05 50m [30m] 50m [20m] 50m [30m] 50m [20m] HRP125(RP60%2) :9.52 :15.88 :9.52 :19.05 :12.7 :19.05 Standard size 50m + [30m] 50m [30m] 50m [20m] :19.05 + The maximum length is 75m in case of new pipes. Indoor unit side h Indoor unit Indoor unit B C H Outdoor unit Distribution pipe Outdoor unit side A <TWIN SYSTEM> Total length A + B + C Max. 75 m Height difference H(Indoor unit-Outdoor unit) h(Indoor unit-Indoor unit) Max. 30m Max. 1m Distance between indoor and indoor units Pipe length |B-C| Max. 8m Number of bends (one way) Max. 15 (Max. 8 points between main pipe A and each branch pipe(B, C)) 41 8-2. ADJUSTING THE AMOUNT OF REFRIGERANT • Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter. <Table 5> Required additional charge when the liquid pipe is one size larger than the standard diameter (1:1 SYSTEM) Outdoor unit Liquid pipe O.D. Refrigerant amount to be added (Exceeding 20m) PUHZ-HRP71-125 :12.7 100 g per 1 m <Table 6> Required additional charge when the liquid pipe is one size larger than the standard diameter (TWIN SYSTEM) Outdoor unit When the extension pipe length (main piping + branch piping) exceed 20 m PUHZ-HRP71-125 Additional refrigerant amount W(g) = (100 % L1) + (60 % L2) + (30 % L3) - 2000 If the calculation produces a negative number ( W 0), additional charging is not necessary. L1: :12.7 liquid pipe length (m) L2: :9.52 liquid pipe length (m) L3: :6.35 liquid pipe length (m) <Table 7> Additional refrigerant charging amount for pipe of standard diameter Additional refrigerant charging amount Permitted Amount of unit for pipe length exceeding 30 m (kg) Type Outdoor unit pipe length filling refrigerant (kg) 31 – 40m 41 – 50m 51 – 60m 61 – 70m 71 – 75m 1:1 0.6kg 1.2kg 1.8kg 75m or less 5.5kg 2.4kg system PUHZ-HRP71-125 Type Outdoor unit Twin system PUHZ-HRP71-125 Permitted pipe length Amount of unit filling refrigerant (kg) 75m or less 5.5kg Additional refrigerant charging amount for pipe length exceeding 30 m (kg) 31 – 40m 41 – 50m 51 – 60m 0.6kg 1.2kg 1.8kg 42 61 – 70m 71 – 75m 2.4kg 8-3. CAPACITY CORRECTION CURVES Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is one size smaller than standard size. Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m) [Sample calculation] Indoor unit RP60 o 2 units (Twin system) Outdoor unit HRP125 o 1 • Condition Using existing pipes. • Outdoor unit side Liquid pipe [12.7 / Gas pipe [19.05 pipe length (A) 20m • Indoor unit side Liquid pipe [9.52 / Gas pipe [15.88 pipe length (B) 20m + (C) 15m 1) Farthest piping length 20m + 15m = 35m Number of bends : 10 2) Corrected piping length 35m + 0.3 o 10 = 38m 3) Capacity correction Outdoor unit side’s gas pipe [19.05 Standard [15.88 → 1 size up Refer to 1Capacity curves <Standard size> 4) Capacity Cooling capacity = Standard cooling capacity o 0.89 Heating capacity = Standard heating capacity o 0.98 1 Capacity curves for PUHZ-HRP · HA(2) model <Standard size> 100 Heating HRP71-125 Capacity ratio [%] 95 90 Cooling HRP71 model 85 Cooling HRP100 model 80 Cooling HRP125 model 75 Cooling Note: The permitted pipe length is up to 80m. Heating 70 5 10 15 20 25 30 35 40 45 50 55 60 65 70 Corrected pipe length [m] 2 When gas pipe is one size larger than standard size for PUHZ-HRP71-125. 1 Capacity can be obtained by referring to capacity curves of standard size. 43 75 80 9 AIR FLOW DATA 9-1. OUTLET AIR SPEED AND COVERAGE RANGE Air flow Air speed Coverage range PLA-RP100BA PLA-RP125BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2 PLA-RP100BA3 PLA-RP36BA PLA-RP50BA PLA-RP60BA m3/min. 15 18 18 21 30 31 m/sec. 2.6 3.2 3.2 3.7 5.3 5.4 m 4.1 4.8 4.8 5.6 8 8.2 PKA-RP35GAL PKA-RP50GAL Air flow Air speed Coverage range m3/min. 12 12 m/sec. 5.3 5.3 10 (32.8) 10(32.8) m (ft) PKA-RP50FAL2 PKA-RP100FAL PKA-RP60FAL Air flow Air speed Coverage range m3/min. m/sec. m (ft) 20 28 4.9 5.4 12.4(40.7) 15.3 (50.2) PKA-RP35HAL PKA-RP50HAL Air flow Air speed Coverage range m3/min. m/sec. m (ft) 12 12 6.1 6.1 10.8 (35.4) 10.8 (35.4) PKA-RP60KAL PKA-RP100KAL Air flow Air speed Coverage range m3/min. m/sec. m (ft) 22 26 6.0 6.8 14.3 (46.9) 16.1 (52.8) w The air coverage range is the distance to which the 0.25 m/sec air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 44 9-2. PLA-RP·BA/BA2/BA3 9-2-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. Fresh air intake hole Fresh air intake hole diagram Branch duct hole 3-:2.8 burring hole :125 burring hole pitch 120 120 Indoor unit *158 :100 cut out hole Ceiling Drain pipe Refrigerant pipe 100 100 90 130 90 Branch duct hole diagram (view from either side) 100 350 :175 burring hole pitch Fig. 1 45 *167 70 *155 14-:2.8 burring hole :150 cut out hole 3. Fresh air intake volume & static pressure characteristics PLA-RP35~60BA PLA-RP71BA2 At using multi-function casement, standard filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 1 - inlet -200 0 1 2 3 4 5 6 Air flow rate [m3/min] At using multi-function casement, high efficiency filter 50 0 0 Static pressure[Pa] Static pressure[Pa] Direct intake to unit 50 -50 -100 -150 -200 0 1 2 3 4 5 -50 -100 -150 -200 6 2 - inlet 1 - inlet 0 1 2 3 Air flow rate [m3/min] 3 Air flow rate [m /min] 4 5 6 PLA-RP100BA/BA2/BA3, 125BA(2) At using multi-function casement, standard filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 1 - inlet -200 0 2 4 Air flow rate [m3/min] 6 8 At using multi-function casement, high efficiency filter Direct intake to unit 50 50 0 Static pressure[Pa] Static pressure[Pa] 0 -50 -100 -150 -50 -100 2 - inlet -150 1 - inlet -200 0 2 4 Air flow rate [m3/min] 6 8 -200 46 0 2 4 Air flow rate [m3/min] 6 8 4. Change of outlet numbers The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. Indoor unit When the air outlets are closed, close the vane by removing the vane connector. Button Outlet concave portion Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers + Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet + Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position + The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air Air outlet outlet closed closed position position Air intake Air outlet closed position 47 PLA-RP71BA2 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 Duct Static pressure [Pa] Static pressure [Pa] 30 20 10 High Duct 20 10 High Low Low 0 0 0 2 4 6 Airflow rate [m3/min] 0 8 3-way airflow (horizontal vane) Round duct 2 80 70 70 Duct Duct 60 Close Static pressure [Pa] Static pressure [Pa] 60 50 40 30 Close 50 40 30 High 20 20 High Low 10 0 Low 10 2 4 6 8 Airflow rate [m3/min] 0 10 2-way airflow (horizontal vane) Round duct 0 2 4 6 8 Airflow rate [m3/min] 10 2-way airflow (horizontal vane) Rectangular duct 100 100 90 90 Duct 80 Duct 80 Close Close 70 60 50 40 30 High 20 Close Close Static pressure [Pa] Static pressure [Pa] 8 3-way airflow (horizontal vane) Rectangular duct 80 0 4 6 Airflow rate [m3/min] 70 60 50 40 30 20 Low Low High 10 10 0 0 0 2 4 6 8 10 Airflow rate [m3/min] 0 12 2 4 6 8 10 Airflow rate [m3/min] • Use 1 of the 2 duct holes on the indoor unit. • Airflow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP71BA2. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 48 12 PLA-RP125BA(2) 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 30 Duct 20 Static pressure [Pa] Static pressure [Pa] Duct 10 Low 10 2 4 Airflow rate [m³/min] 6 8 3-way airflow (horizontal vane) Round duct 0 2 4 Airflow rate [m³/min] 6 8 3-way airflow (horizontal vane) Rectangular duct 80 80 70 60 Duct Duct Close Close 60 Static pressure [Pa] 70 50 40 High 50 40 High 30 30 20 20 Low Low 10 10 0 0 0 2 4 6 Airflow rate [m³/min] 8 0 10 2-way airflow (horizontal vane) Round duct 2 4 6 Airflow rate [m³/min] 8 10 2-way airflow (horizontal vane) Rectangular duct 100 100 90 90 Duct 80 Duct 80 Close 70 Close 70 Close Close 60 Static pressure [Pa] 60 Static pressure [Pa] High Low High 0 0 0 Static pressure [Pa] 20 50 40 High 30 50 High 40 Low 30 Low 20 20 10 10 0 0 0 2 4 6 8 Airflow rate [m³/min] 10 0 12 2 4 6 8 10 12 Airflow rate [m³/min] • Use 1 of the 2 duct holes on the indoor unit. • Airflow rate of PLA-RP100BA/BA2/BA3 can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP125BA(2). • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow. 49 9-3. PEAD-RP·JA(L) Fan performance PEAD-RP35JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP35JA(L) (External static pressure 35Pa) 220-240V 50Hz 120 60 110 Rated point 100 Limit External static pressure (Pa) External static pressure (Pa) 50 40 Rated point High 30 Middle 20 Low 10 Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 0 7 9 11 13 15 17 19 0 21 7 9 11 Airflow rate(m3/min) 13 PEAD-RP35JA(L) (External static pressure 50Pa) 220-240V 50Hz 17 19 21 PEAD-RP35JA(L) (External static pressure 150Pa) 220-240V 50Hz 70 170 160 Rated point 150 60 140 Limit External static pressure (Pa) External static pressure (Pa) 15 Airflow rate(m3/min) Rated point 50 High 40 Middle 30 Low 20 Limit 130 High 120 110 100 Middle 90 80 70 Low 60 50 40 30 10 20 10 0 7 9 11 13 15 17 19 0 21 Airflow rate(m3/min) 90 80 External static pressure (Pa) Rated point Limit High 60 50 Middle 40 Low 30 20 10 0 7 9 11 13 15 9 11 13 15 Airflow rate(m3/min) PEAD-RP35JA(L) (External static pressure 70Pa) 220-240V 50Hz 70 7 17 19 21 Airflow rate(m3/min) 50 17 19 21 PEAD-RP50JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP50JA(L) (External static pressure 35Pa) 220-240V 50Hz 130 70 120 110 60 50 High 40 Rated point Middle 30 Low 20 Rated point Limit 100 External static pressure (Pa) External static pressure (Pa) Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 10 0 9 14 0 19 9 14 19 Airflow rate(m3/min) Airflow rate(m3/min) PEAD-RP50JA(L) (External static pressure 50Pa) 220-240V 50Hz PEAD-RP50JA(L) (External static pressure 150Pa) 220-240V 50Hz 180 80 170 160 70 External static pressure (Pa) External static pressure (Pa) Rated point 50 High 140 High 60 Middle 40 30 Rated point 150 Limit Low 20 Limit 130 120 110 Middle 100 90 80 Low 70 60 50 40 10 30 20 0 9 14 10 19 0 Airflow rate(m3/min) 9 14 Airflow rate(m3/min) PEAD-RP50JA(L) (External static pressure 70Pa) 220-240V 50Hz 100 90 External static pressure (Pa) 80 Limit Rated point 70 High 60 50 Middle 40 30 Low 20 10 0 9 14 19 Airflow rate(m3/min) 51 19 PEAD-RP60JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP60JA(L) (External static pressure 35Pa) 220-240V 50Hz 120 60 110 50 Rated point 100 External static pressure (Pa) External static pressure (Pa) Limit 40 Rated point 30 High 20 Middle 90 Limit High 80 70 Middle 60 50 Low 40 30 Low 10 20 10 0 10 15 20 25 0 10 30 15 Airflow rate(m3/min) 20 PEAD-RP60JA(L) (External static pressure 50Pa) 220-240V 50Hz 170 160 Rated point 150 Limit 140 Rated point 50 External static pressure (Pa) External static pressure (Pa) 30 PEAD-RP60JA(L) (External static pressure 150Pa) 220-240V 50Hz 70 60 25 Airflow rate(m3/min) High 40 Middle 30 20 Low High 130 Limit 120 110 100 Middle 90 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 90 80 Rated point External static pressure (Pa) Limit High 60 50 Middle 40 30 Low 20 10 0 10 15 20 15 20 Airflow rate(m3/min) PEAD-RP60JA(L) (External static pressure 70Pa) 220-240V 50Hz 70 10 25 30 Airflow rate(m3/min) 52 25 30 PEAD-RP71JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP71JA(L) (External static pressure 35Pa) 220-240V 50Hz 70 130 120 60 High 110 Rated point 50 External static pressure (Pa) External static pressure (Pa) 100 Limit High 40 Rated point 30 Middle 20 Low Limit 90 Middle 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 10 15 Airflow rate(m3/min) 20 25 30 Airflow rate(m3/min) PEAD-RP71JA(L) (External static pressure 50Pa) 220-240V 50Hz PEAD-RP71JA(L) (External static pressure 150Pa) 220-240V 50Hz 90 180 170 High 160 80 Rated point 150 140 External static pressure (Pa) External static pressure (Pa) 70 Limit 60 High Rated point 50 Middle 40 30 Low 20 130 Middle Limit 120 110 100 90 80 Low 70 60 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 100 90 High External static pressure (Pa) 80 Limit Rated point 70 Middle 50 40 Low 30 20 10 0 10 15 20 15 20 Airflow rate(m3/min) PEAD-RP71JA(L) (External static pressure 70Pa) 220-240V 50Hz 60 10 25 30 Airflow rate(m3/min) 53 25 30 PEAD-RP100JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP100JA(L) (External static pressure 35Pa) 220-240V 50Hz 70 150 140 Limit 130 60 External static pressure (Pa) External static pressure (Pa) 120 50 40 Rated point 30 High Middle 20 Low High Limit 110 Rated point 100 90 Middle 80 70 Low 60 50 40 30 10 20 10 0 10 15 20 25 30 35 40 0 45 Airflow rate(m3/min) 90 External static pressure (Pa) External static pressure (Pa) Limit 70 High Rated point 50 Middle 40 Low 30 20 25 30 35 40 45 PEAD-RP100JA(L) (External static pressure 150Pa) 220-240V 50Hz 100 60 15 Airflow rate(m3/min) PEAD-RP100JA(L) (External static pressure 50Pa) 220-240V 50Hz 80 10 20 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 High Rated point Limit Middle Low 30 20 10 0 10 0 10 15 20 25 30 35 40 45 PEAD-RP100JA(L) (External static pressure 70Pa) 220-240V 50Hz 120 110 External static pressure (Pa) 100 Limit High 90 80 Rated point Middle 70 60 Low 50 40 30 20 10 0 10 15 20 25 30 35 40 10 15 20 25 30 Airflow rate(m3/min) Airflow rate(m3/min) 45 Airflow rate(m3/min) 54 35 40 45 PEAD-RP125JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP125JA(L) (External static pressure 35Pa) 220-240V 50Hz 70 180 170 Limit 160 High 60 External static pressure (Pa) External static pressure (Pa) High 140 50 Low 40 Limit 150 Middle Rated point 30 20 130 120 110 100 90 80 Middle Rated point Low 70 60 50 40 30 10 20 10 0 15 20 25 30 35 40 0 45 15 20 Airflow rate(m3/min) 90 High External static pressure (Pa) External static pressure (Pa) Limit 70 Middle 50 Rated point Low 40 30 20 10 0 15 20 25 30 35 40 45 PEAD-RP125JA(L) (External static pressure 70Pa) 220-240V 50Hz 150 140 130 External static pressure (Pa) High Limit 110 100 90 Middle 80 70 Rated point Low 60 50 40 30 20 10 0 15 20 25 30 35 230 220 210 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 40 45 High Limit Middle Rated point Low 15 20 25 30 35 Airflow rate(m3/min) Airflow rate(m3/min) 120 35 PEAD-RP125JA(L) (External static pressure 150Pa) 220-240V 50Hz 100 60 30 Airflow rate(m3/min) PEAD-RP125JA(L) (External static pressure 50Pa) 220-240V 50Hz 80 25 40 45 Airflow rate(m3/min) 55 40 45 9-4. PEAD-RP·EA,EA2,GA Corrected Airflow 120 100 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 9-4-1. FAN PERFORMANCE AND CORRECTED AIR FLOW PEAD-RP35EA2 Fan Performance <30Pa> 140 PEAD-RP50EA 80 60 40 20 6 Cooling 1.0 0.9 0.8 8 10 10 12 14 16 18 20 Airflow (CMM) Fan Performance <70Pa> 160 12 14 16 18 Airflow (CMM) 20 22 12 14 16 18 Airflow (CMM) 20 22 Heating 1.3 140 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 8 1.1 Capacity input 120 100 80 60 40 1.2 1.1 1.0 0.9 0.8 8 20 8 10 10 12 14 16 18 20 22 Airflow (CMM) Fan Performance <30Pa> 120 Correction factor 100 80 60 40 20 8 140 External static pressure (Pa) (1Pa 0.1mmAq) Corrected Airflow 10 12 14 16 18 20 22 24 Airflow (CMM) 1.1 Capacity input Cooling 1.0 0.9 0.8 12 14 16 18 20 22 Airflow (CMM) 24 26 Heating Fan Performance <70Pa> 1.3 120 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) PEAD-RP60EA 100 80 60 40 1.2 1.1 1.0 0.9 0.8 12 14 16 18 20 22 24 Airflow (CMM) 20 10 12 14 16 18 20 22 24 26 Airflow (CMM) 56 26 PEAD-RP71EA Fan performance <70Pa> Fan performance <130Pa> Recommended range External static pressure (Pa) (1Pa = 0.1mmAq) External static pressure (Pa) (1Pa = 0.1mmAq) Recommended range 200 180 160 140 Hi Lo 120 100 80 60 40 20 180 160 140 120 80 60 40 20 12 16 20 24 28 32 12 16 20 24 28 32 Airflow (CMM) Airflow (CMM) Corrected Airflow Heating 1.3 1.2 Correction factor Correction factor Capacity Input Cooling 1.1 1.0 0.9 0.8 12 16 20 24 28 1.1 1.0 0.9 32 Airflow (CMM) 0.8 12 16 PEAD-RP100EA2 PEAD-RP125EA External static pressure (Pa) (1Pa = 0.1mmAq) 200 180 160 140 120 100 Hi 80 Lo 20 200 180 160 140 120 100 1.2 Cooling 1.1 Correction factor Capacity Input 1.0 0.9 36 38 40 60 40 Lo 20 Airflow (CMM) Corrected Air Flow 34 Hi 80 32 34 36 38 40 42 44 46 Airflow (CMM) Correction factor 32 220 32 34 36 38 40 42 44 46 48 0.8 32 28 Recommended range 220 40 24 Fan performance <70Pa> Recommended range 60 20 Airflow (CMM) Fan performance <130Pa> External static pressure (Pa) (1Pa = 0.1mmAq) Hi Lo 100 42 Airflow (CMM) 44 46 48 Heating 1.1 1.0 0.9 0.8 32 34 36 38 40 42 44 Airflow (CMM) 57 46 48 PEAD-RP60GA PEAD-RP71GA 58 PEAD-RP100GA 59 NOISE CRITERION CURVES 10 10-1. INDOOR UNIT PLA-RP35BA NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 LINE PLA-RP50BA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 250 500 1000 2000 4000 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 BAND CENTER FREQUENCIES, Hz PLA-RP60BA NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 LINE PLA-RP71BA2 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 1000 2000 4000 8000 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 LINE 90 80 10 500 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 90 NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 250 500 1000 2000 4000 10 8000 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 60 4000 8000 PLA-RP100BA PLA-RP100BA2 PLA-RP100BA3 NOTCH SPL(dB) High 40 Medium1 37 Medium2 34 Low 32 PLA-RP125BA PLA-RP125BA2 LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 90 NOTCH SPL(dB) High 41 Medium1 39 Medium2 36 Low 34 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz UNIT CEILING 1.5m MICROPHONE 61 4000 8000 PEAD-RP·JA(L) Ceiling concealed 2m Aux.duct 1.5m 2m Measurement location Noise level at anechoic room (Low-Middle-High) Unit: dB(A) Model Exrernal static pressure 35Pa 50Pa 70Pa 100Pa 150Pa PEAD-RP35JA(L) 23-26-29 23-27-30 24-28-31 26-29-33 29-33-37 PEAD-RP50JA(L) 25-30-34 26-31-35 28-32-36 29-33-37 31-35-39 PEAD-RP60JA(L) 25-28-32 25-29-33 26-30-34 27-31-35 29-34-38 PEAD-RP71JA(L) 25-29-34 26-30-34 27-31-35 28-32-36 30-35-39 PEAD-RP100JA(L) 28-33-38 29-34-38 30-35-39 31-36-40 34-40-43 PEAD-RP125JA(L) 31-36-40 33-36-40 33-37-41 34-39-42 37-41-45 62 PEAD-RP35JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 63 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP50JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 64 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP60JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 65 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP71JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 66 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP100JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 67 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP125JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 4000 8000 68 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP35EA2 PEAD-RP50EA (External static pressure 30Pa) PEAD-RP35EA2 PEAD-RP50EA 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa 70 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 8000 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 OCTAVE BAND CENTER FREQUENCIES (Hz) 250 500 1000 2000 4000 8000 (External static pressure 70Pa) PEAD-RP60EA 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa 125 OCTAVE BAND CENTER FREQUENCIES (Hz) (External static pressure 30Pa) PEAD-RP60EA High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 (External static pressure 70Pa) Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCIES (Hz) 69 8000 70 SOUND LEVELS Low-Middle-High Model Sound level dB (A) PKA-RP35, 50HAL 36 - 40 - 43 PKA-RP60KAL 39 - 42 - 45 PKA-RP100KAL 41 - 45 - 49 PKA-RP35HAL PKA-RP50HAL PKA-RP60KAL External static pressure : 0Pa Power source : 220, 230, 240V, 50Hz 70.0 70.0 High Low 60.0 NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 20.0 NC-30 Approximate minimum audible limit on continuous noise NC-20 15.0 10.0 63 125 250 500 1k 2k Octave band center frequencies (Hz) 4k 60.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 25.0 20.0 Approximate minimum audible limit on continuous noise 15.0 10.0 8k NC-60 55.0 63 NC-20 125 250 500 1k 2k Octave band center frequencies (Hz) 4k 8k PKA-RP100KAL External static pressure : 0Pa Power source : 220, 230, 240V, 50Hz UNIT 70.0 WALL High Low 65.0 Octave band pressure level (dB) 0dB=20μPa 25.0 High Low 65.0 Octave band pressure level (dB) 0dB=20μPa 65.0 Octave band pressure level (dB) 0dB=20μPa External static pressure : 0Pa Power source : 220, 230, 240V, 50Hz 1m 1m MICROPHONE 60.0 NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 25.0 20.0 Approximate minimum audible limit on continuous noise 15.0 10.0 63 125 250 NC-20 500 1k 2k Octave band center frequencies (Hz) 71 4k 8k PKA-RP35GAL PKA-RP50GAL NOTCH SPL(dB) 43 High Medium1 41 38 Medium2 Low 36 LINE PKA-RP50FAL2 PKA-RP60FAL 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar) 80 20 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 BAND CENTER FREQUENCIES, Hz 250 500 PKA-RP100FAL WALL 1m MICROPHONE 2000 4000 8000 NOTCH SPL(dB) High 46 Low 41 LINE 90 UNIT 1m 1000 BAND CENTER FREQUENCIES, Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 90 NOTCH SPL(dB) High 45 Low 39 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 72 4000 8000 10-2. OUTDOOR UNIT MODE SPL(dB) COOLING 52 HEATING 53 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA BAND CENTER FREQUENCIES, Hz UNIT 1.5m GROUND 73 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz MICROPHONE 1m MODE SPL(dB) COOLING 51 HEATING 52 8000 11 OPTIONAL PARTS 11-1. INDOOR UNIT Part Name Model Name Remote sensor Remote operation adapter Multiple remote controller adapter PAC-SE41TS-E PAC-SF40RM-E (+1) Remote on/off adapter Power supply terminal kit L/N/Earth L/N Decoration panel Decoration panel with Wireless remote controller Decoration panel with Wired remote controller Automatic filter elevation panel i-see sensor corner panel Wireless signal receiver Space panel Air outlet shutter plate Multi-function casement Flange for fresh air intake High-efficiency filter element (PAC-SH53TM-E is needed.) Wired remote controller kit (with terminal bed) Drain pump Motor (for high external static pressure) Drain lift up mechanism Insulation kit Filter box Applicable model PAC-SA88HA-E (1 pc.) All models PAC-725AD (10 pcs.) PAC-SE55RA-E PEAD-RP•EA(2) PAC-SG96HR-E PKA-RP•GAL/FAL(2) PAC-SG94HR-E PKA-RP•HAL/KAL PAC-SH52HR-E PAC-SG97HR-E PLA-RP•BA/BA2/BA3 PEAD-RP•GA/JA(L) PLP-6BA PLP-6BALM PLP-6BAMD PLP-6BAJ PAC-SA1ME-E PAR-SA9FA-E PLA-RP•BA/BA2/BA3 PAC-SH48AS-E PAC-SH51SP-E PAC-SH53TM-E PAC-SH65OF-E PAC-SH59KF-E PAR-21MAAT-E PKA-RP•GAL/FAL(2) PKA-RP•HAL/KAL PAC-SH75DM-E PAC-SH94DM-E PKA-RP•HAL PKA-RP•KAL PKA-RP•FAL(2) PEAD-RP125EA PEAD-RP100EA2 PEAD-RP•EA,EA2 PEAD-RP•GA PAC-SE90DM-E PAC-SK003MT-F PAC-KE03DM-F PAC-SK010DK PAC-KE92TB-E PAC-KE93TB-E PAC-KE94TB-E (+1) Unable to use with wireless remote contoller (except for PKA-RP·HAL/KAL). 74 PEAD-RP35, 50JA(L) PEAD-RP60, 71JA(L) PEAD-RP100, 125JA(L) 11-2. OUTDOOR UNIT Part Name Model Name Applicable model M-NET adapter PAC-SF81MA-E PUHZ-HRP71-125 A-control service tool PAC-SK52ST PUHZ-HRP71-125 Drain socket PAC-SG61DS-E PUHZ-HRP71-125 Air outlet guide (HRP71/100/125 needs 2 pieces.) PAC-SG59SG-E PUHZ-HRP71-125 Air protect guide (HRP71/100/125 needs 2 pieces.) PAC-SH63AG-E PUHZ-HRP71-125 Drain pan PAC-SG64DP-E PUHZ-HRP71-125 Filter dryer (:9.52) PAC-SG82DR-E PUHZ-HRP71-125 Distribution pipe Joint pipe (Unit (Twin) MSDD-50TR-E PUHZ-HRP71-125 PAC-SG75RJ-E PUHZ-HRP71-125 PAC-IF011B-E PAC-IF012B-E PAC-SE60RA-E PUHZ-HRP71-125 PUHZ-HRP71-125 PUHZ-HRP71-125·HA2R1 Extension pipe) (:15.88 :19.05) Interface (cased) Drain hose heater 75 HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Mar. 2010 No.OCS11 REVISED EDITION-B PDF 4 Distributed in Sep. 2008 No.OCS11 REVISED EDITION-A PDF 6 Distributed in Oct. 2007 No.OCS11 PDF 7 Made in Japan New publication, effective Mar. 2010 Specifications subject to change without notice.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project