PEAD-RP·EA(2)

Add to my manuals
76 Pages

advertisement

PEAD-RP·EA(2) | Manualzz
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
March 2010
No. OCS11
REVISED EDITION-B
TECHNICAL DATA BOOK R410A INVERTER
<Indoor unit>
[Model names]
<Outdoor unit>
[Model names]
PLA-RP·BA/BA2/BA3
PEAD-RP·JA(L)
PEAD-RP·EA(2)
PEAD-RP·GA
PKA-RP·HAL
PKA-RP·KAL
PKA-RP·GAL
PKA-RP·FAL(2)
Revision :
• PLA-RP·BA3, PKA-RP·HAL/KAL
and PEAD-RP·JA(L) are added,
and the data of PUHZ-HRP·HA2
has been modified in REVISED
EDITION-B.
• Some descriptions have been
modified.
• Please void OCS11
REVISED EDITION-A.
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
CONTENTS
1. REFERENCE SERVICE MANUAL············································· 2
2. SPECIFICATIONS ······································································ 3
3. OUTLINES AND DIMENSIONS ··············································· 12
4. WIRING DIAGRAM··································································· 24
5. REFRIGERANT SYSTEM DIAGRAM ······································ 36
6. PERFORMANCE CURVES ······················································ 38
7. CORRECTION FACTORS ························································ 40
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ·········· 41
9. AIR FLOW DATA ······································································ 44
10. NOISE CRITERION CURVES ·················································· 60
11. OPTIONAL PARTS············································································74
Zubadan
1
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Model Name
Service Ref.
Service Manual No.
PLA-RP35/50/60/100/125BA
PLA-RP71/100/125BA2
PLA-RP35/50/60/100/125BA#2.UK
PLA-RP71/100/125BA2.UK
OCH412
OCB412
PLA-RP100BA3
PLA-RP100BA3
OCH459
OCB459
PKA-RP35/50HAL
PKA-RP35/50HAL
OCH453
OCB453
PKA-RP60/100KAL
PKA-RP60/100KAL.TH
OCH452
OCB452
PEAD-RP35/50/60/71/100/125JA(L)
PEAD-RP35/50/60/71/100/125JA(L).UK
PKA-RP35/50GAL
PKA-RP35/50GAL#1
OC330
PKA-RP60/100FAL
PKA-RP50FAL2
PKA-RP60/100FAL#1
PKA-RP50FAL2#1
OC331
PEAD-RP50/60/71/125EA
PEAD-RP35/100EA2
PEAD-RP50/60/71/125EA#1.UK
PEAD-RP35/100EA2#1.UK
HWE0521
PEAD-RP60/71/100GA
PEAD-RP60/71/100GA#1.UK
HWE0506
HWE08130
BWE08240
1-2. OUTDOOR UNIT
Model Name
Service Ref.
Service Manual No.
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2R1
PUHZ-HRP100/125YHA2R1
2
OCH425
OCB425
SPECIFICATIONS
2
2-1. CEILING CASSETTE TYPE
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Field drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
PLA-RP71BA2
PUHZ-HRP71VHA2
24,200
7.1 ( 4.9 - 8.1 )
1.94
3.66
A
0.73
27,300
8.0 ( 4.5 - 10.2 )
1.90
4.21
A
-
Btu/h
kW
kW
Btu/h
kW
kW
kW
Hz
V
A
CMM
CFM
Pa
32
14 - 16 - 18 - 21
495 - 565 - 635 - 740
28 - 30 - 32 - 34
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
258 (35)
10-3/16 (1-3/8)
23 (6)
51 (13)
PLA-RP100BA2
PUHZ-HRP100VHA2
34,100
10.0 ( 4.9 - 11.4 )
2.44
4.10
A
0.74
38,200
11.2 ( 4.5 - 14.0 )
2.54
4.41
A
1
50
230
40
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
0
32 - 34 - 37 - 40
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/8)
27 (6)
60 (13)
32
1-1/4
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
265
15.88
5/8
9.52
3/8
Max. 30
Max. 75
PLA-RP100BA3
PUHZ-HRP100VHA2
34,100
10.0 ( 4.9 - 11.4 )
2.44
4.10
A
0.74
38,200
11.2 ( 4.5 - 14.0 )
2.54
4.41
A
-
40
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
32 - 34 - 37 - 40
298 (35)
11-3/4 (1-3/8)
26 (6)
57 (13)
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
Single phase 230V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
3
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Field drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
Hz
V
A
CMM
CFM
Pa
dB(A)
PLA-RP100BA2
PUHZ-HRP100YHA2
34,100
10.0 ( 4.9 - 11.4 )
2.50
4.00
A
0.74
38,200
11.2 ( 4.5 - 14.0 )
2.60
4.31
A
-
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
0
32 - 34 - 37 - 40
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
27 (6)
60 (13)
PLA-RP100BA3
PLA-RP125BA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
34,100
42,700
10.0 ( 4.9 - 11.4 )
12.5 ( 5.5 - 14.0 )
2.50
3.79
4.00
3.30
A
A
0.74
0.71
38,200
47,800
11.2 ( 4.5 - 14.0 )
14.0 ( 5.0 - 16.0 )
2.60
3.57
4.31
3.92
A
A
3
50
400
16
20 - 23 - 26 - 30
22 - 25 - 28 - 31
710 - 810 - 920 - 1060 780 - 880 - 990 - 1090
0
0
32 - 34 - 37 - 40
34 - 36 - 39 - 41
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/8)
26 (6)
57 (13)
27 (6)
60 (13)
32
1-1/4
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
3 phase 400V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
4
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Field drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
Hz
V
A
CMM
CFM
Pa
dB(A)
PLA-RP100BA
PLA-RP100BA
PLA-RP125BA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
34,100
34,100
42,700
10.0 ( 4.9 - 11.4 )
10.0 ( 4.9 - 11.4 )
12.5 ( 5.5 - 14.0 )
3.02
3.02
3.87
3.31
3.31
3.23
A
A
A
0.74
0.74
0.71
38,200
38,200
47,800
11.2 ( 4.5 - 14.0 )
11.2 ( 4.5 - 14.0 )
14.0 ( 5.0 - 16.0 )
3.10
3.10
3.88
3.61
3.61
3.61
A
A
A
1
3
50
50
230
400
32
16
20 - 23 - 26 - 30
22 - 25 - 28 - 31
710 - 810 - 920 - 1060
780 - 880 - 990 - 1090
0
0
32 - 34 - 37 - 40
34 - 36 - 39 - 41
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
120
265
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
298 (35)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/8)
25 (6)
55 (13)
32
1-1/4
100
3,530
52
53
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
5
2-2. CEILING-CONCEALED TYPE
Model Name
Cooling
Indoor Unit
Outdoor Unit
Capacity
Heating
Total Input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total Input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - Middle - High)
External pressure
Sound level
(Low - Middle - High/50Pa)
External finish
Dimension
Weight
Field drain pipe O.D.
Outdoor Unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant
pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant
pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
PEAD-RP71JA(L)
PUHZ-HRP71VHA2
24,200
7.1 (3.3 - 8.1)
2.15 (2.13)
3.30 (3.33)
A
0.83
27,300
8.0 (3.5 - 10.2)
2.34
3.42
B
-
PEAD-RP100JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L)
PUHZ-HRP100VHA2 PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
34, 100
34, 100
42,700
10.0 (4.9 - 11.4)
10.0 (4.9 - 11.4)
12.5 (5.5 - 14.0)
3.06 (3.04)
3.06 (3.04)
3.89 (3.87)
3.27 (3.29)
3.27 (3.29)
3.21 (3.23)
A
A
A
0.82
0.82
0.84
38,200
38,200
47,800
11.2 (4.5 - 14.0)
11.2 (4.5 - 14.0)
14.0 (5.0 - 16.0)
3.10
3.10
3.88
3.61
3.61
3.61
A
A
A
1
3
50
50
230
400
32
40
16
17.5 - 21 - 25
24 - 29 - 34
24 - 29 - 34
29.5 - 35.5 - 42
618 - 742 - 883
847 - 1,024 - 1,201 847 - 1,024 - 1,201 1,042 - 1,253 - 1,483
35 / 50 / 70 / 100 / 150
26 - 30 - 34
29 - 34 - 38
29 - 34 - 38
33 - 36 - 40
Galvanized sheets
1,400
732
250
55-1/8
28-7/8
9-7/8
41 (40)
41 (40)
91 (89)
91 (89)
32
1-1/4
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330 + 30
1,350
37-3/8
13 + 1-3/16
53-1/8
1,100
43-5/16
33 (32)
73 (71)
120
265
43 (42)
95 (93)
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
3. Guaranteed voltage
2. Guaranteed operating range
Indoor unit : 198 ~ 264V, 50Hz
Indoor
Outdoor
Outdoor unit : 198 ~ 264V, 50Hz (V)
342 ~ 457V, 50Hz (Y)
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
4. Above data are based on the indicated voltage.
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Indoor unit
Single phase 230V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
Outdoor unit
(V) Single phase 230V 50Hz
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
(Y) 3 phase
400V 50Hz
* If optional air protect guide is installed : D.B.-18°C
6
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Unit drain pipe
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
PEAD-RP71EA
PUHZ-HRP71VHA
PUHZ-HRP71VHA2
PEAD-RP100EA2
PUHZ-HRP100VHA
PUHZ-HRP100VHA2
24,200
7.1 (4.9 - 8.1 )
2.15
3.30
A
0.83
27,300
8.0 ( 4.5 - 10.2 )
2.34
3.42
B
-
34,100
10.0 ( 4.9 - 11.4 )
3.06
3.27
A
0.86
38,200
11.2 ( 4.5 - 14.0 )
3.10
3.61
A
1
50
230
Hz
V
A
CMM
CFM
Pa
32
20 - 25
706 - 883
70
37-41
dB(A)
32 (VHA)/ 40 (VHA2)
33.5 - 42
1,183 - 1,483
70
44-50
Galvanized sheets
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
1,175
1,415
740
325
46-1/8
55-11/16
29-1/8
12-13/16
44
97
65
143
R1 (External thread)
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
100
3,530
52 (VHA)/ 51 (VHA2)
53 (VHA)/ 52 (VHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
265
15.88
5/8
9.52
3/8
Max. 30
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
Single phase 230V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
7
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Unit drain pipe
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
PEAD-RP100EA2
PUHZ-HRP100YHA
PUHZ-HRP100YHA2
PEAD-RP125EA
PUHZ-HRP125YHA
PUHZ-HRP125YHA2
34,100
10.0 ( 4.9 - 11.4 )
3.06
3.27
A
0.86
38,200
11.2 ( 4.5 - 14.0 )
3.10
3.61
A
-
42,700
12.5 ( 5.5 - 14.0 )
3.89
3.21
A
0.82
47,800
14.0 ( 5.0 - 16.0 )
3.88
3.61
A
3
50
400
16
Hz
V
A
CMM
CFM
Pa
33.5 - 42
1,183 - 1,483
70
44 - 50
dB(A)
33.5 - 42
1,183 - 1,483
70
44 - 50
Galvanized sheets
1,415
740
325
55-11/16
29-1/8
12-13/16
65
143
R1 (External thread)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
100
3,530
52 (YHA)/ 51 (YHA2)
53 (YHA)/ 52 (YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
134
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
Indoor unit:198~264V, 50Hz Outdoor unit:342~457V, 50Hz
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
3 phase 400V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
8
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Unit drain pipe
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
PEAD-RP71GA
PUHZ-HRP71VHA
PUHZ-HRP71VHA2
PEAD-RP100GA
PUHZ-HRP100VHA
PUHZ-HRP100VHA2
PEAD-RP100GA
PUHZ-HRP100YHA
PUHZ-HRP100YHA2
24,200
7.1 ( 4.9 - 8.1 )
2.15
3.30
A
0.83
27,300
8.0 ( 4.5 - 10.2 )
2.34
3.42
B
-
34,100
10.0 ( 4.9 - 11.4 )
3.08
3.25
A
0.86
38,200
11.2 ( 4.5 - 14.0 )
3.28
3.41
B
-
34,100
10.0 ( 4.9 - 11.4 )
3.08
3.25
A
0.86
38,200
11.2 ( 4.5 - 14.0 )
3.28
3.41
B
3
50
400
16
1
50
230
Hz
V
A
CMM
CFM
Pa
32
20-25
706-883
10/50/70
35-38/37-41/37-43
dB(A)
32 (VHA)/ 40 (VHA2)
26.5-33
935-1,165
10/50/70
40-43/42-45/42-46
Galvanized sheets
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1,171
1,411
740
275
46-1/8
55-9/16
29-1/8
10-13/16
42
93
50
111
R1 (External thread)
1-1/4
100
3,530
52 (VHA, YHA)/ 51 (VHA2, YHA2)
53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
265
15.88
5/8
9.52
3/8
Max. 30
Max. 75
134
295
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
9
2-3. WALL-MOUNTED TYPE
Model Name
Cooling
Indoor Unit
Outdoor Unit
Capacity
Heating
Total Input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
PKA-RP100KAL
PUHZ-HRP100VHA2
Total Input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - Middle - High)
External pressure
Sound level
(Low - Middle - High/50Pa)
External finish
Dimension
Weight
Field drain pipe O.D.
Outdoor Unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant
pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant
pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
34,100
10.0 (4.9 - 11.4)
2.93
3.41
A
0.73
38,200
11.2 (4.5 - 14.0)
3.10
3.61
A
-
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
1
50
230
40
Munsell 1.0Y 9.2/0.2
1,170
295
365
46-1/16
11-5/8
14-3/8
21
46
16
5/8
100
3,530
51
52
Ivory Munsell 3Y 7.8/1.1
950
330 + 30
1,350
37-3/8
13 + 1-3/16
53-1/8
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
Indoor
D.B. 35°C, W.B. 22.5°C
D.B. 19°C, W.B. 15°C
D.B. 28°C
D.B. 17°C
3
50
400
16
20 - 23 - 26
705 - 810 - 920
0
41 - 45 - 49
120
265
134
295
15.88
5/8
9.52
3/8
Max. 30
MAx. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
PKA-RP100KAL
PUHZ-HRP100YHA2
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
3. Guaranteed voltage
198~264V, 50Hz (V) / 342~457V, 50Hz (Y)
Outdoor
D.B. 46°C
D.B. -5°C
+1
D.B. 21°C, W.B. 15°C
D.B. -15°C, W.B. -15°C
10
4. Above data are based on the indicated voltage.
Indoor unit
Single phase 230V 50Hz
Outdoor unit
V : Single phase 230V 50Hz
Y : 3 phase 400V 50Hz
+1. If optional air protect guide is installed : D.B.-15
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Field drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
PKA-RP100FAL
PUHZ-HRP100VHA
PUHZ-HRP100VHA2
PKA-RP100FAL
PUHZ-HRP100YHA
PUHZ-HRP100YHA2
34,100
10.0 ( 4.9 - 11.4 )
2.93
3.41
A
0.77
38,200
11.2 ( 4.5 - 14.0 )
3.10
3.61
A
1
50
230
32 (VHA)/ 40 (VHA2)
34,100
10.0 ( 4.9 - 11.4 )
2.93
3.41
A
0.77
38,200
11.2 ( 4.5 - 14.0 )
3.10
3.61
A
3
50
400
16
22 - 28
780 - 990
0
41 - 46
White Munsell 3.4Y 7.7/0.8
1680
235
340
66-1/8
9-1/4
13-3/8
28
62
20
13/16
100
3,530
52 (VHA, YHA)/ 51 (VHA2, YHA2)
53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1,350
37-3/8
13 + 1-3/16
53-1/8
120
134
265
295
15.88
5/8
9.52
3/8
Max. 30
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F)
Heating
Indoor : D.B. 20°C (68°F)
Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
3. Guaranteed voltage
198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
Indoor
Outdoor
4. Above data are based on the indicated voltage.
Upper limit D.B. 32°C, W.B. 23°C
D.B. 46°C
Cooling
Indoor unit
Single phase 230V 50Hz
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C *
Outdoor unit
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Heating
* If optional air protect guide is installed : D.B.-18°C
Lower limit D.B. 17°C
D.B. -25°C, W.B. -25°C
11
OUTLINES AND DIMENSIONS
3
INDOOR UNIT
PLA-RP50BA
PLA-RP100BA2
PLA-RP60BA
PLA-RP100BA3
810
Detail connecting of Branch duct(Both aspects)
20~45
90
100
100
90
Cut out hole
860~910
620
605 +35
-5
Indoor power supply
terminal block(Option part)
Ceiling hole
+ +
Suspension bolt pitch
840
Branch duct hole
155
Remote controller
terminal block
Indoor unit/Outdoor unit
connecting terminal block
167
70°
160
(7.5)
100
Suspension bolt pitch
160
PLA-RP125BA
20~45
860~910
Fresh air
intake hole
PLA-RP100BA
Unit : mm
Ceiling hole
20~45
PLA-RP71BA
PLA-RP125BA2
130
PLA-RP35BA
PLA-RP71BA2
Branch duct hole
350
:175
14-:2.8
Burring hole
Burring hole pitch
:150
840
60
284
(
Connected the attached
Drain pipe
connected to VP-25 socket.
377
Control wire entry
Ceiling
B
)
Cut out hole
:100
+
Ceiling
+
In case of standard grille : PLP-6BA / PLP-6BAMD
35
Power supply wire,
Indoor unit/Outdoor unit
connecting wire entry
190
156
105
140
+
17 +5
0
Suspension bolt
lower edge
Keep approximately
10 to 15mm space
between unit ceiling
and ceiling slab.
+ +
+
+
50~70
170
A
2
+
:125
120°
158
1
Burring hole pitch
3-:2.8
120°
160
Suspension bolt
M10 or W3/8
Burring hole
20~45
187.5
Detail drawing of fresh air intake hole
(7.5)
24
160
D
C
90
150
Cut out hole
Grille
597
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
597
Operation lamp
83
M
36
500
83
36
950
Indoor unit
1000mm
or more
Indoor unit
3000mm or more
Obstacle
Floor
Air intake grille
Vane motor
Air outlet hole
1500mm
or more
DEFROST/STAND BY lamp
Receiver
M
Grille
Ceiling
L.L Filter
Air intake grille
Ceiling
Auto Grille
Air intake grille up/down discharge
Emergency operation
switch<Cooling>and
Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
Auto vane
(Air outlet)
Air intake hole
500
Air outlet hole
950
M
In case of Auto-Grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM
1800mm or more
from floor
For high
attachment
Note1. Please choose the Grille from a standard grille, Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE).
Drain pump is included.
Raise is max 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions + marked on the figure.
3) The optional high efficiency filter must be used jointly with optional multi-functional casement,
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Water dew.)
8. As for necessary installation/service space, please refer to left figure.
Models
PLA-RP35/50BA
1
Refrigerant pipe
···:6.35
Flared connection
···1/4F
2
Refrigerant pipe
:6.35 / :9.52
Flared connection
1/4F / 3/8F
(compatible)
PLA-RP60BA
PLA-RP71BA,BA2
PLA-RP100,125BA
PLA-RP100BA3
PLA-RP100, 125,140BA2
12
Refrigerant pipe
···:9.52
Flared connection
···3/8F
A
B
Refrigerant pipe
···:12.7
Flared connection
···1/2F
C
D
E
80
74
241 258 87
400
Refrigerant pipe
···:15.88
Flared connection
···5/8F
85 77
281 298
440
Max. 4.0m
Air intake hole
M
Unit : mm
PEAD-RP35, 50, 60, 71, 100, 125JA
2xE-:2.9
Suspension bolt hole
4-14x30 Slot
18
Air
inlet
210
G
Air
outlet
A
B(Suspension bolt pitch)
C
D (Duct)
100x(E-1)=F
15
643 (Suspension bolt pitch)
32
238
10
Terminal block
(Remote controller transmission line)
175±5mm
(Actual length)
217
250
Control box
2×2-:2.9
136
67
356
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60•71•100•125•140JA
models,which have 2 fans. PEAD-RP35•50JA models have 1 fan.
4. In case of the inlet duct is used,remove the air filter
(supply with the unit), then install the filter
(field supply) at suction side.
Drain pipe(O.D.:32)
Terminal block
(Spontaneous draining) (Indoor/Outdoor connecting line)
Model
A
PEAD-RP35,50JA
900
PEAD-RP60,71JA
PEAD-RP100,125JA
PEAD-RP140JA
6
D
E
F
G
954 1000 860
9
800
858
B
C
1100 1154 1200 1060
1400 1454 1500 1360
1600 1654 1700 1560
11 1000 1058
14 1300 1358
16 1500 1558
J
Gas pipe Liquid pipe
:12.7
:6.35
:15.88
:9.52
Kx(L-1)=M
J
K
More than 20mm
Ceiling surface
112
112
N-:2.9
More than 10mm
Drain hose (I.D.:32)
<accessory>
11
1 Refrigerant piping
Flare connection (gas)
Less than 300mm
Less than 700mm
732
700
Drain pipe Drain pump
(O.D.:32)
41
57
178 (Duct)
100
33
23
40
122
2 Refrigerant piping
Flare connection (liquid)
23
10
58
40
57
21
20
30
100
Air Filter
Access door
Q
P
Make the access door at the appointed position properly for service maintenance.
Qx(R-1)=S
Model
777
50
H
Note2
Access door
50
250
~30 45
0
0
450 0
30
han
re t
Mo
Required space for service and maintenance
13
H
J
K
L
M
N
P
Q
R
S
PEAD-RP35,50JA
1000
54
260
4
780
10
40.5
273
4
819
PEAD-RP60,71JA
PEAD-RP100,125JA
PEAD-RP140JA
1200
1500
1700
49
54
54
330
320
370
4
5
5
990
1280
1480
10
12
12
40
40
40
340
330
380
4
5
5
1020
1320
1520
Unit : mm
PEAD-RP35, 50, 60, 71, 100, 125JAL
2xE-:2.9
Suspension bolt hole
4-14x30 Slot
210
G
Air
inlet
C
Air
outlet
A
18
B(Suspension bolt pitch)
D (Duct)
100x(E-1)=F
15
21
Terminal block
(Remote controller transmission line)
732
700
32
175±5mm
(Actual length)
217
250
10
33
2×2-:2.9
1 Refrigerant piping
Flare connection (gas)
Control box
136
67
356
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60•71•100•125•140JAL
models,which have 2 fans. PEAD-RP35•50JAL models have 1 fan.
4. In case of the inlet duct is used,remove the air filter
(supply with the unit), then install the filter
(field supply) at suction side.
Drain pipe(O.D.:32)
Model
A
PEAD-RP35,50JAL
900
PEAD-RP60,71JAL
PEAD-RP100,125JAL
PEAD-RP140JAL
6
D
E
F
G
954 1000 860
9
800
858
B
C
1100 1154 1200 1060
1400 1454 1500 1360
1600 1654 1700 1560
11 1000 1058
14 1300 1358
16 1500 1558
J
Gas pipe Liquid pipe
:12.7
:6.35
:15.88
:9.52
Kx(L-1)=M
J
K
More than 20mm
Ceiling surface
112
112
N-:2.9
More than 10mm
Drain hose (I.D.:32)
<accessory>
Terminal block
(Indoor/Outdoor connecting line)
11
23
40
122
100
178 (Duct)
643 (Suspension bolt pitch)
57
2 Refrigerant piping
Flare connection (liquid)
23
10
58
40
57 20
30
100
Air Filter
Access door
Q
Make the access door at the appointed position properly for service maintenance.
Qx(R-1)=S
P
Model
777
50
H
Note2
Access door
H
J
K
L
M
N
P
Q
R
S
PEAD-RP35,50JAL
1000
54
260
4
780
10
40.5
273
4
819
PEAD-RP60,71JAL
PEAD-RP100,125JAL
PEAD-RP140JAL
1200
1500
1700
49
54
54
330
320
370
4
5
5
990
1280
1480
10
12
12
40
40
40
340
330
380
4
5
5
1020
1320
1520
50
250
~30 45
0
0
re
Mo
Required space for service and maintenance
450 0
0
n3
tha
14
Unit : mm
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
Model
A
RP35,50 772
RP60
B
305
1012 280
+ Initial setting
C
D
E
-
830
804
F
G
R410A Outdoor unit : 6.35 + R410A Outdoor unit : 12.7 +
R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88
Outdoor unit (SUZ) : 6.35
15.88
290 1070 1044
R407C Outdoor unit : 9.52 +
Service space:500 or more
50~150 29
Refrigerant piping flare connection (liquid : F copper tube):HP
Refrigerant piping flare connection (gas :G copper tube):LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP-25(I.D. :32)
Filter
55
Access door
10- :3 (RP35,50)
12- :3 (RP60)
A
81
C
B
81
197
450
Lifting bolt hole
(1422)
C
13
243
277
45 80
85
24
282
288
256
176
Air inlet
7
E
13
D
30
10- :3 (RP35,50)
12- :3 (RP60)
6
40
2
179
10
35
1
227
109
10
3.5
21
In case of rear inlet
30
61
4
81
A
44 75
640
30
B
10
18
56
355
365~465
159
1
2
3
4
5
6
7
10
450
5
Air outlet
3.5
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
In case of bottom inlet
10- :3 (RP35,50)
12- :3 (RP60)
Air outlet
40
15
176
256
10
3.5
10
7
81
C
B
81
A
Air inlet
PEAD-RP71EA
PEAD-RP100EA2
PEAD-RP125EA
Service space:500 or more
Air inlet
375
44
243
6
5
7
Lifting bolt hole
(14x22)
12-:3
307
45 122
113
1
81
Air outlet
3
4
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
15
C
A
13
E
75
D
B
81
10
80
2
20
53
B
197
30
10
680
C
365~465
323
308
169
210
30
12-:3
A
81
81
35
7
140
6
282
5
3.5
30
4
40
3
55
Access door
Refrigerant piping flare connection (liquid :9.52 copper tube):HP
Refrigerant piping flare connection (gas :F copper tube):LP
Drain R1 (External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP25(I.D.:32)
Filter
319
261
181
2
3.5
1
C
D
E
F
290 1070 1044
15.88
370 1310 1284 R410A Outdoor unit : 15.88 +
470 1610 1584 R407C outdoor unit : 19.05
450
A
B
Model
RP71 1012 280
RP100,125 1252 360
RP140 1552 460
+ Initial setting
10
50~150 29
450
13
30
Unit : mm
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Model
A
B
C
D
E
F
G
8
H
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52 *
RP60
1125
1090
1050
1012
7
840
RP71
1125
1090
1050
1012
7
RP100 1365
1330
1290
1252
9
15.88
840
8
9.52
15.88
1080
10
9.52
R410A Outdoor unit : 15.88 *
R407C Outdoor unit : 19.05
* Initial setting
16
J
PKA-RP35HAL
PKA-RP50HAL
Unit : mm
192
Top side
197
387
Mount board
599
Front side
295
Right side
A
Left side
55
688
Knockout hole
for left piping
5
249
155
898
Knockout hole
for right piping
Front side (Grille open)
Sleeve
Through hole
(purchased locally)
:65~:80
Terminal block for outdoor unit
:65~:80
Terminal block for power supply (option)
Terminal block for
MA-remote controller (option)
457 Gas pipe 539 Liquid pipe 610 Drain hose 169
158
184
Under side
Vane (auto)
DEFROST/STAND BY lamp
Operation lamp
612
Emergency operation switch
(cooling/heating)
8
Size
Refrigerant pipe : :6.35
Liquid pipe Flared connection : 1/4F
Refrigerant pipe : :12.7
Gas pipe Flared connection : 1/2F
Drain hose
Louver (manual)
Knockout hole
for lower piping
O.D
Receiver
Knockout hole
for lower piping
C
:16
B
Knockout hole for piping
58
3.8
0
Center measurement hole :2.5
Mount board
200
225
238
265
291.5
327.5
356.3
372.3
125
70
70
15
0
15
125
225
200
291.5
265
372.3
356.3
327.5
231.5
Required space (Indoor unit)
Air inlet
Min.50
550mm or greater with optional
Min.220
drain pump installation.
17
Air outlet
Min.150
Min.250
Air inlet
449
281
115
140
167
180.3
193.5
0
Knockout hole for
left rear piping (70 × 310)
Min.50
Wall hole for
left piping
174
273.2
238
213
B
128.5
153.5
278.3
46
60
21.8
0
20
32.7
53.5
66
449
43
43
Min.7
250mm or greater with optional
drain pump installation.
6
A
59
D
43
Indoor unit outline
0
16
28.5
41
78.5
91
103.5
116
166
178.5
203.5
232.5
253.5
394
69
C
46
56
56
6
12.5
56
43
4-:9 Bolt hole
77-:5.1
Tapping
screw hole
Wall hole for
right rear piping
55mm or greater with left
or rear left piping or drain
pump installation.
PKA-RP60KAL
PKA-RP100KAL
Unit : mm
Top side
431.7
11
140.3
65.2
423.7
Left side
Right side
Front side
Mount board
365
Knockout hole
for left piping
C
74
A
(855)
295
241
5
Operation lamp
DEFROST/STAND BY lamp
1170
Receiver
Knockout hole for
right piping
Front side (Grille open)
Terminal block for outdoor unit
Terminal block for power supply (option)
Terminal block for
MA-remote controller (option)
Emergency operation switch
(cooling/heating)
30
35
444 (Gas pipe) 66
123
154
482 (Liquid pipe) 585 (Drain hose)
134
Under side
Piping connection department
Refrigerant pipe : 9.52
Flared connection : 3/8F
Gas pipe
Refrigerant pipe : 15.88
Flared connection : 5/8F
16
Drain hose
Sleeve
Through hole
(purchased locally)
75
Liquid pipe
75~ 80
O.D
Louver (manual)
Vane (auto)
B
B
54
0
Knockout hole
for lower piping
C
B
3
364
384.5
408.5
439
454
465.5
314
10
0
10
60
110
Indoor unit outline
54
32
25
77
7.8
77
87
0
0
37.5
62.5
50
75
100
117
125
142
192
67
65
77
7.8
67
25
10.7
Mount board
A
15.5
65
Center measurement hole W2.5
Temporarily fixing hole
314
75-W5.1
Tapping screw hole
454
439
408.5
384
364
Knockout hole for piping
517.4
4-W9 Bolt hole
60
110
65
104.5
129.5
167
217
242
279.5
292
264
292
308.5
311
Min. 220
550 mm or greater with optional
drain pump installation
Min. 50.5
108 mm or greater with left or
rear left piping or drain pump
installation
18
Wall hole for
right rear piping
585
439
449.2
Knockout hole for
left rear piping
(75×480)
339
349.2
384
0
189
339
384
439
430.5
585
Min. 48
Air outlet
Min. 72.4
Wall hole for
left rear piping
Min. 250
Min. 7
265 mm or greater with optional
drain pump installation
Air inlet
530.5
7.5
R3
Required space (Indoor unit)
216.5
32
18
53
Filter hook
12.5
12.5
87.5
229.5
495
Model
35, 50
Knockout hole for
left-rear piping
Left-rear
piping hole
49-:5hole
for tapping screw
300
360
Sleeve +1
:90
R52.5
Liquid pipe
Gas pipe
990
705 Air outlet
80
715 Air intake
400
12-Louvers(manual)
340 Air intake
581
449
225
40
86
54
70 35
190
160
235
233
153
: Initial flare nut size
GAS SIDE
LIQUID SIDE
60
Knockout hole for
right piping
Refrigerant pipe.
Drain pipe.
Wiring hole
Less than 15
(Right side piping
installation)
Terminal block for
power supply
(Heater (PKH-P35, 50GALH only))
Terminal block to
outdoor unit
Service panel
(Power supply access)
Knockout hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
235
Right side
—
:9.52
—
:15.88
:6.35
:9.52
:12.7
:15.88
P35, 50
RP35, 50
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
395
Auto vane
280 Air intake
700 (Flexible hose total length800)
Front view(to open the grille)
Filter grip
50
Lower side
(Left side piping
installation)
Unit drain pipe O.D.20
35
272
310
322
230
190
130
0
35
55
80
(Necessary clearance for
unit installation)
Less than 130
Right side
340
+1 Sleeves are available on the market.
+2 This size shows the lower end of through hole.
Right-rear
piping hole
R52.5
Through hole
:90~:100
Knockout hole for
right-rear piping
405
420
Unit center
75
32
20
0
35
0
14-:14hole
for bolts
190
Installation plate
balance point hole
95
Details of installation plate
135
R5
2.
5
150 or more
150
50 or more
205
170
190
245
70 21
245
70 21
30 or more
180 or more
260
53
79
Allowing clearances
Front view
245
5
2.
R5
230
210
320
345
Front view
80
60
425
198 Air intake
60
280
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
495
19
31
Left side
PKA-RP35GAL PKA-RP50GAL
Unit : mm
PKA-RP50FAL2
PKA-RP60FAL
Unit : mm
Display section
62.5
Top
45
235
235
45
235
45
Defrosting Initial heating lamp
13
235
Power lamp
Front
Right side
1400
Left side
Emergency switch(Heat)
Emergency switch(Cool)
Receiving
section
235
Knockout hole for right piping
Refrigerant pipe. Drain pipe
340
A
197
1090 Air intake
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Knockout hole for
left piping
C
Gas pipe
25
Drain hose for
left-hand side piping
58
42
Bolt
Drain hose O.D.20
Drain hose
1110
55 (Gas pipe) 107
120
111
183
(Liquid pipe)
Lower side
Liquid pipe :9.52(3/8F)
Gas pipe :15.88(5/8F)
Auto vanes
1120
240
552 Air outlet
552 Air outlet
Louvers (manual)
Under panel
Removable at left-hand
side piping
Knockout hole for under-piping
Sleeve +1
Through hole
:90
:90~ :100
+1 Sleeves are available on the market.
B
Use the current nuts meeting
the pipe size of the outdoor unit.
Refrigerant pipe. Drain pipe
Unit center
990
Knockout hole for wiring
32-ø12 hole for bolt
225
240
180
12-ø6 hole for
tapping screw
280
314
610
30
60
90
B
C
30
37
74
39
98 32
39
184
30
66-ø6 hole for
tapping screw
A
30
100
91
37
74
4
Drainage range
on right-hand side
37
65
on left-hand side
100
4 39
18
285
19
10
30
80
29
280
Wall fixture
10 91=(910)
900
18 Drainage range
245
455
Rear piping opening
Range for left rear piping opening
Available pipe size
LIQUID SIDE
GAS SIDE
RP50
:6.35
:9.52
:12.7
:15.88
: Initial flare nut size
20
RP60,71 / P60,71
:9.52
:15.88
PKA-RP100FAL
Unit : mm
Top
62.5
Display section
45
235
45
235
45
235
235
45
13
235
Receiving
section
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Power lamp
Front
Knockout hole for right piping
Right side
1680
Left side
235
1370 Air intake
340
197
A
Knockout hole for left piping
C
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Gas pipe
25
Drain hose O.D.20
Drain hose
Drain hose for left-hand side piping
58
42
Bolt
1110 Drain hose
183
Lower side
1400
55 (Gas pipe) 102
120
111
(Liquid pipe)
240
694 Air outlet
694 Air outlet
Available pipe size
RP100
LIQUID SIDE :9.52
P100
:9.52
GAS SIDE
:15.88
:19.05
:Initial flare nut size
Louvers (manual)
B
Under panel
(Removable at left-hand side piping)
:19.05
Use the current nuts meeting the pipe size
of the outdoor unit.
Auto vane
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
Unit center
1270
Knockout hole for wiring
Drainage range
91
on right-hand side
60
295
225
Range for left rear piping opening
240
180
280
750
314
30
41-ø12 hole
for bolt
90
Range for left rear piping opening
12-ø6 hole for tapping screw
21
Rear piping opening
A
30
B
C
30
100
Drainage range
on left-hand side
285
19
37
74
39
98 32
39
13 91=(1183)
900
37
74
4
18
37
65
18
184
30
84-ø6 hole for
tapping screw
245
595
10
30
80
29
280
Wall fixture
100
4 39
Unit out line
FREE
er
Ov
m
10m
m
0m
15
er
Ov
10
Service space
Over
Front piping hole
(Knockout)
92
W92
65
Power supply wiring hole
(2-W27Knockout)
Front trunking hole 40
45
(Knockout)
19
92
75
Right piping hole
(Knockout)
Piping Knockout Hole Details
55
W92
150
40
65
45
Right trunking hole
(Knockout)
Less than
92
W92
40
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Side Air Intake
Handle for moving
Handle for moving
Power supply wiring hole
(2-W27Knockout)
FOUNDATION
Rear Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
<Foundation bolt height>
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
Power supply wiring hole
(2-W27Knockout)
Air intake
Handle for moving
+1 ···Indication of STOP VALVE connection location.
500
Over
Over
3 FOUNDATION BOLTS
30
Dimensions of space needed
for service access are
shown in the below diagram.
···Refrigerant GAS pipe connection (FLARE)W15.88(5/8 inch)
···Refrigerant LIQUID pipe connection (FLARE)W 9.52(3/8 inch)
Example of Notes
O
10m
m
m
0m
00
r1
ve
er
Ov
55
27
63
23 27 92
73
Over
500
73 63
330
Handle for moving
Side Air Intake
30
322
220
175
145
145
145
Earth terminal
950
Air Discharge
Installation Feet
600
Rear Air Intake
42
Drain hole
(5-W33)
71
2
1
Handle for moving
Service panel
Terminal connection
Left···Power supply wiring
Right···Indoor/Outdoor wiring
2-12 x 36 Oval holes
(Foundation Bolt M10)
66
175
2-U Shaped notched holes
(Foundation Bolt M10)
417
2 SERVICE SPACE
1350
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
71
635
371
(19)
45
56
370
53
28
Rear piping cover
Front piping cover
1,079
930
HRP·YHA
A
HRP·VHA
Bottom piping hole
(Knockout)
+1 443
1 FREE SPACE (Around the unit)
73 63
23
55
27
A
30
23
219
81
+1 447
22
23
OUTDOOR UNIT
PUHZ-HRP71VHA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
Unit : mm
FREE
Ov
m
0m
15
er
er
10
mm
Ov
10
Over
Service space
Front piping hole
(Knockout)
92
92
65
Power supply wiring hole
(2- 27Knockout)
Front trunking hole 40
45
(Knockout)
19
92
75
55
92
Air intake
Right piping hole
(Knockout)
Piping Knockout Hole Details
500
Over
150
40
65
45
Less than
92
92
40
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Handle for moving
Side Air Intake
Handle for moving
Power supply wiring hole
(2- 27Knockout)
FOUNDATION
Rear Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
<Foundation bolt height>
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
Right trunking hole
(Knockout)
Power supply wiring hole
(2- 27Knockout)
Handle for moving
1 ···Indication of STOP VALVE connection location.
···Refrigerant LIQUID pipe connection (FLARE) 9.52(3/8 inch)
···Refrigerant GAS pipe connection (FLARE) 15.88(5/8 inch)
Example of Notes
mm
00
10
10
mm
er
Ov
er
Ov
Over
3 FOUNDATION BOLTS
30
Dimensions of space needed
for service access are
shown in the below diagram.
330
Handle
for
moving
Handle for moving
Side Air Intake
1350
30
322
220
175
145
145
145
Earth terminal
950
Air Discharge
Installation Feet
600
Rear Air Intake
42
Drain hole
(5- 33)
71
2
1
Handle for moving
Service panel
Terminal connection
Left ····Power supply wiring
Right··· Indoor/Outdoor wiring
2-12 x 36 Oval holes
(Foundation Bolt M10)
66
175
2-U Shaped notched holes
(Foundation Bolt M10)
417
2 SERVICE SPACE
71
The diagram below shows a
basic example.
Explanation of particular details is
given in the installation manuals etc.
55
27
63
23 27 92
73
635
371
(19)
45
56
370
53
28
Over
500
73 63
Front piping cover
930
HRP·YHA2
A
1,079
HRP·VHA2
Bottom piping hole
(Knockout)
Rear piping cover
+1 443
1 FREE SPACE (Around the unit)
73 63
23
55
27
A
30
23
219
81
+1 447
23
23
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
Unit : mm
4
WIRING DIAGRAM
4-1. INDOOR UNIT
PLA-RP35BA
PLA-RP50BA
PLA-RP71BA2
PLA-RP100BA2
PLA-RP60BA
PLA-RP100BA3
PLA-RP71BA
PLA-RP125BA2
PLA-RP100BA
PLA-RP125BA
<Table 1> SW1 (MODEL SELECTION)
SW1
MODELS
SETTING
[LEGEND]
SYMBOL
I.B
CN2L
CN32
CN41
CN51
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
DCL
DP
FS
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
FUSE (T6.3AL250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SWITCH (MODEL SELECTION) +See table 1
SWITCH (CAPACITY CODE) +See table 2
CONNECTOR (EMERGENCY OPERATION)
RELAY (DRAIN PUMP)
REACTOR
DRAIN PUMP
DRAIN FLOAT SWITCH
SYMBOL
MF
MV
TB2
TB4
TB5,TB6
TH1
TH2
TH5
OPTION PART
W.B
BZ
LED1
LED2
RU
SW1
SW2
NAME
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (Indoor unit Power (option))
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
(0 / 15k, 25 / 5. 4k DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0 / 15k, 25 / 5. 4k DETECT)
COND. / EVA. TEMP. THERMISTOR
(0 / 15k, 25 / 5. 4k DETECT)
PLA-RP·BA
1 2 3 4 5
PLA-RP71/100/125BA2
1 2 3 4 5
PLA-RP140BA2
PLA-RP100BA3
1 2 3 4 5
ON
OFF
SETTING
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
50
1 2 3 4 5
60
1 2 3 4 5
71
ON
OFF
ON
OFF
ON
OFF
100
125
140
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
The black square ( ) indicates a switch position.
Refer to tables 1 and 2
DCL
TB5
2
1
TRANSMISSION
WIRES
DC12V
2 1
TB6
ON
OFF
<Table 2> SW2 (CAPACITY CODE)
SW2
CAPACITY
SETTING
CAPACITY
35
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
ON
OFF
YLW
R.B
I.B
VANE CNV(WHT)
SW1
20 18 16 14 12 10 8 6 4 2
J41 J42
SW2
19 17 15 13 11 9 7 5 3 1
CN32
(WHT) 1
CN51(WHT)
Pair No.
5
CN2L
LED3
3
1
3
AUTO GRILLE
CN3G 1
(BLK)
WIRELESS
CN90
(WHT)
9
5
5
5
M
M
M
M
MV
MV
MV
MV
GRILLE
1
4
4
CNB
BZ
SW1
LED2
SW2
LED1
2 1
INDOOR/OUTDOOR
COMMUNICATION
CN3C
1
CN41(WHT)
4
LED1
RU
I-SEE
SENSOR
1
6
1 2
MT
I-SEE SENSOR
CORNER PANEL
(OPTION PART)
+
(BLU)
1
4
4
1 2
t°
t°
TH2 TH5
t°
TH1
1
7
FAN
CNMF
(WHT)
X1
4
MS
3
5
M
3 1
FUSE
–
(BLU)
FS
1
CN3G
1 D.U.M
1 3
CNP
(BLU)
5 3 1
TB4
YLW S1
ORN S2
S3
TO OUTDOOR
UNIT
ORN
BRN
M
3~
1~
MF
DP
CN3A
AUTOMATIC FILTER ELEVATION PANEL
(OPTION PART)
W.B
Notes:
1.SymboIs used in wiring diagram above are,
: Connector,
:
Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make
sure to match terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check
the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting
wires.(specification of 230V), adopting superimposed system for
power and signal.
+1:If indoor and outdoor units have separate power supplies,
refer to Fig. 1.
+2:For power supply system of this unit, refer to the caution label
located near this diagram.
YLW
ORN
+ Be sure to turn off the source power
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
U.B
3
Please set the voltage using the
remote controller.
For the setting method,please refer to
the indoor unit Installation Manual.
REMOCON
CN22
1
SWE
(BLK)
1 3
ON OFF
AUTO GRILLE
I-SEE
FLOAT SW LIQUID/PIPE INTAKE
POWER
I-SEE SENSOR SENSOR MOTOR
CN4F
CN44
CN20
CNAC
CN4Y
CN6Y
(WHT)
(WHT)
(RED)
(WHT)
(WHT)
(RED)
9
5
LED2
OUTDOOR 1 3 5
CN01
3
+1(Fig. 1)
CN01
I.B
(BLK)
YLW
5
ORN
3
1
RED
BLU
GRN/YLW
TB2
L
N
YLW TB4
ORN S1
ORN S2
BRN
S3
I.B
1 3 INDOOR/OUTDOOR
CN3C COMMUNICATION
(BLU)
24
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
25
TH5
FS
1
2
3
4
CN41
CN51
CN32
TH1
t˚
CNXB2
1
2
3
4
5
LED2
CNXC2
1
2
LED1
CN22
(Blue)
CN2A
(Black)
CN105
(Red)
4
3
2
1
(Blue)
CNXA2
2
1
M
1~
X01
(Blue)
CNXA1
1234
X10
F01
CND
5 (Red)
Fan motor
MS
3~
CNMF
7654
1
DC280-340V
Rectifier circuit
P.B.
NAME
Intake air temp. Thermistor
Pipe temp. Thermistor/liquid
Cond./eva.temp. Thermistor
AC reactor (Power factor improvement)
Float switch
Terminal block
(Indoor/outdoor connecting line)
Terminal block
(Remote controller transmission line)
ONLY FOR PEAD-RP·JA
SYMBOL
TH1
TH2
TH5
ACL
FS
TB4
TB15
U
ZNR01
3
CNXC1
12
DSA
U
ZNR02
1
CNXB1
12345
3
1
(Blue)
CNP
Drainpump
NAME
SYMBOL
NAME
I.B.
Indoor controller board
Indoor controller board
SW1 Switch (for model selection)
Connector (0-10V Analog input)
SW2 Switch (for capacity code)
Connector (Lossnay)
SW5 Switch (for model selection)
Connector (Remote switch)
SW6 Switch (for model selection)
Connector (HA terminal-A)
SWE Connector (emergency operation)
Connector (Centrally control)
P.B.
Connector (Wireless)
Power supply board
F01
Connector (IT terminal)
Fuse AC250V 6.3A
ZNR01, 02 Varistor
LED(Power supply)
DSA Arrester
LED(Remote controller supply)
X01
LED(Transmission indoor-outdoor)
Aux. relay
X10
Aux. relay
FOR PEAD-RP·JA
REFER TO "B" FOR PEAD-RP·JAL
B
1
2
3
4
CN4F
1
2
(Red) (Red)
CN20 CN2L
SWE
SW6
1
2
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
140
125
1 2 3 4 5
1 2 3 4 5
The black square (■) indicates a switch position.
71
60
50
1 2 3 4 5
100
SETTING
ON
OFF
1 2 3 4 5
35
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
SW5
1 2 3 4 5 6 7 8
ON
OFF
SW1
1 2 3 4 5
<Table 2> SW2 (CAPACITY CODE)
SW2
CAPACITY
SETTING
CAPACITY
PEAD-RP·JA(L)
MODELS
<Table 1> SW1 (MODEL SELECTION)
TO OUTDOOR UNIT
ON
OFF
ON
OFF
SW6
1 2
TO CND
1
2
TO CN3C
ACL
1
2
1
2
S1
S2
S3
L
N
TO OUTDOOR
UNIT
POWER SUPPLY
~ (1PHASE)
220-240V 50Hz
THE REPLACEMENT WIRING)
< A> (IN CASE OF CONNECT
NOTE: 1. Since the outdoor side electric wiring may change, be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities,
make wiring matching terminal numbers (S1,S2,S3).
3. Symbols used in wiring diagram above are,
terminal block,
connector.
A
S3
TB4
S1
S2
PEAD-RP60JA(L)
SYMBOL
I.B.
CN2A
CN2L
CN32
CN41
CN51
CN90
CN105
LED1
LED2
LED3
SYMBOL EXPLANATION
t˚
CN4F
1
2
3
4
ON
OFF
CN44
SW5
SW2
SW1
2
ACL
TO MA REMOTE
CONTROLLER
PEAD-RP50JA(L)
PEAD-RP125JA(L)
TH2
t˚
LED3
CN90
1 CN3C
3 (Blue)
I.B.
1
TB15
1
2
INSIDE SECTION OF CONTROL BOX
PEAD-RP35JA(L)
PEAD-RP100JA(L)
PEAD-RP71JA(L)
PEAD-RP35EA2
PEAD-RP100EA2
PEAD-RP50EA
PEAD-RP125EA
[LEGEND]
NAME
SYMBOL
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
SW2
FUSE FUSE(T6.3AL250V)
SWE
ZNR VARISTOR
X1
CN2L CONNECTOR(LOSSNAY)
X4
X5
CN24 CONNECTOR(HEATER)
CN32 CONNECTOR(REMOTE SWITCH)
X6
CN41 CONNECTOR(HA TERMINAL-A) P.B.
CN51 CONNECTOR(CENTRALLY CONTROL) DRAIN PUMP
DP
CN90 CONNECTOR(WIRELESS)
LED1 POWER SUPPLY(I.B.)
DS
LED2 POWER SUPPLY(REMOTE CONTROLLER) C
LED3 TRANSMISSION(INDOOR·OUTDOOR) MF
SW1 SWITCH(MODEL SELECTION)
PEAD-RP60EA
NAME
SWITCH(CAPACITY CODE)
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
INDOOR POWER BOARD
(OPTIONAL PARTS)
DRAIN PUMP
DRAIN SENSOR
CAPACITOR(FAN MOTOR)
FAN MOTOR
PEAD-RP71EA
NAME
SYMBOL
TB4
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TB5
TERMINAL BLOCK(REMOTE CONTROLLER)
TH1
INTAKE AIR TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15kΩ, 25/5.4kΩ DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
INSIDE SECTION OF CONTROL BOX
DS
TH1
TH2
TH5
1
B B
L L
U U
3
CN31
1 2
1 2
CN22
(BLU)
CN20
(RED)
I.B.
1 2
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
1 2
1 2 3 45
1 2 3
CN21 CN29
(WHT) (BLK)
CN31
(WHT)
CN90
(WHT)
CN41
(WHT)
CN24
(YLW)
CN51
(WHT)
CN32
(WHT)
1 2
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
OFF
LED1
LED2
LED3
2
1
WHT
BLK
X1
(BLU)
CN3C
O3B 1
R R
N N
X4 X5 X6
X5
CN2D
(WHT)
ZNR
FUSE
(ORN)
CND
W3B1
H L
T K
O3Y 1
R L
N W
X4
X1
(RED)
CNDK
3
1
X6
7 5 3 1
(BLU)
CNP
W P P B
H N N L
T K K K
(WHT)
FAN
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 30Pa
W B
H L
T K
2 1
TB5 BL
TO MA-REMOTE
CONTROLLER
DC8.7-13V
U B
L
U
2
1
TB4
S3
S2
S1
TO OUTDOOR UNIT
+A
2
1
B
L
K
W
H
T
CN2S
(WHT)
3
1
CNSK
(RED)
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 70Pa
DP
P.B.
<PEAD-RP35·50·60EA, 35EA2>
External static pressure 70Pa
Optional parts
1 2 3 4 5 6
Optional parts
1 2 3 4 5 6
(RED)
(WHT)
BRN
ORN
YLW
MF
MF
C
MODELS
SW1
SW2
Model selection Capacity cord
switch
switch
12345
35EA(2)
12345
50EA
12345
60EA
71EA
100EA(2)
125EA
140EA
12345
12345
ON
OFF
12345
12345
12345
(RED)
1 2 3 4 5 6
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
The black square ( ■ ) indicates
a switch position.
<PEAD-RP71·100·125·140EA, 100EA2>
External static pressure 130Pa
<+A> (IN CASE OF CONNECTING
THE REPLACEMENT WIRING)
ON
OFF
ON
OFF
C
L
N
1 2
1 2
TO CND
S1
S2
S3
1 2
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR
UNIT
TO CN3C
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification
of 230V), adopting superimposed system for power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to +A.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
26
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
[LEGEND]
NAME
NAME
SYMBOL
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
SW1 SWITCH(MODEL SELECTION)
FUSE FUSE(T6.3AL250V)
SW2 SWITCH(CAPACITY CODE)
ZNR VARISTOR
SWE SWITCH(EMERGENCY OPERATION)
CN2L CONNECTOR(LOSSNAY)
X1 RELAY(DRAIN PUMP)
X4 RELAY(FAN MOTOR)
CN24 CONNECTOR(HEATER)
CN32 CONNECTOR(REMOTE SWITCH)
X5 RELAY(FAN MOTOR)
CN41 CONNECTOR(HA TERMINAL-A)
X6 RELAY(FAN MOTOR)
CN51 CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD
C
CAPACITOR(FAN MOTOR)
CN90 CONNECTOR(WIRELESS)
MF
LED1 POWER SUPPLY(I.B.)
FAN MOTOR
LED2 POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
LED3 TRANSMISSION(INDOOR·OUTDOOR)
NAME
SYMBOL
TERMINAL BLOCK(REMOTE CONTROLLER)
TB5
TH1
INTAKE AIR TEMP.THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15kΩ, 25/5.4kΩ DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
INSIDE SECTION OF CONTROL BOX
TH1
TH2
TH5
B B
L L
U U
I.B.
1 2
1 2
1 2
1 2
CN22
(BLU)
CN20
(RED)
CN21
(WHT)
CN29
(BLK)
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
CN90
(WHT)
CN41
(WHT)
CN31
(WHT)
1 2
CN24
(YLW)
1 2 3 4 5
1 2 3
CN51
(WHT)
CN32
(WHT)
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
LED1
LED2
LED3
2
1
WHT
BLK
OFF
X1
(BLU)
CN3C
O3B1
R R
N N
ZNR
(ORN)
CND
W3B1
H L
T K
O3Y1
R L
N W
2 1
TB5 BL
U B
L
U
2
1
TB4
S3
S2
S1
TO OUTDOOR UNIT
+A
2
CN2S
(WHT)
B
L
K
3
3
1
(BLU)
CNP
P.B.
1
X4
X6
7 5 3 1
G Y Y B
R L L L
Y W W K
B B O
L L R
U K G
CNSK
(RED)
(WHT)
FAN
*External static pressure
CONNECTOR COLOR
220V
*
1 2 3 4 5 6
(WHT)
230V
240V
BLU
5Pa
10Pa
20Pa
WHT
35Pa
50Pa
60Pa
RED
50Pa
70Pa
75Pa
(INITIAL SETTING)
MF
C
THE REPLACEMENT WIRING)
L
N
1 2
TO CND
1
W
H
T
(RED)
CNDK
BRN
ORN
YLW
<+A> (IN CASE OF CONNECT
1 2
X1
FUSE
W B
H L
T K
TO MA-REMOTE
CONTROLLER
DC8.7-13V
X4 X5 X6
X5
CN2D
(WHT)
S1
S2
S3
1 2
TO CN3C
POWER SUPPLY
~(1PHASE)
230V 50Hz
MODELS
100GA
SW2
12345
60GA
71GA
TO OUTDOOR
UNIT
SW1
Model selection Capacity cord
switch
switch
12345
ON
OFF
12345
12345
ON
OFF
ON
OFF
ON
OFF
The black square ( ■ ) indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to +A.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
27
PKA-RP35HAL
PKA-RP50HAL
[Explanation of symbols]
Symbol
Name
I.B
Indoor controller board
CN2L
Connector (LOSSNAY)
CN32
Connector ( Remote switch)
CN41
Connector (HA terminal-A)
CN51
Connector (Centrally control)
CN90
Connector (Remote operation adapter)
FUSE
FUSE(T3.15AL250V)
LED1
Power supply (I.B)
LED2
Power supply (R.B)
LED3
Transmission (Indoor-outdoor)
SW1
Switch (Model selection) +See table 1
SW2
Switch (Capacity code) +See table 2
Connector (Emergency operation)
SWE
X1
Relay (Drain pump (option))
Drain pump (option) power supply (Drain pump (option))
CNP
CN4F
Drain float switch (Drain pump (option))
R.B
Wired remote controller(option)
TB6
Terminal block (Remote controller transmission line)
Symbol
M
MS
S.W
SWE2
TB2
TB4
TB5
TH1
Name
Vane motor
Fan motor
Switch board
Emergency operation
Terminal block(Indoor unit Power (option))
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line(option))
Room temp. Thermistor
(0/15kΩ, 25/5.4kΩ Detect)
TH2
Pipe temp. Thermistor/liquid
(0/15kΩ, 25/5.4kΩ Detect)
TH5
Cond./eva. temp. Thermistor
(0/15kΩ, 25/5.4kΩ Detect)
PCB for wireless remote controller
LED (Operation indication : Green)
LED (Preparation for heating: Orange)
Receiving unit
REACTOR
DRAIN PUMP (OPTION)
DRAIN FLOAT SWITCH (OPTION)
W.B
LED1
LED2
REC1
DCL
DP
FS
MS
3~
<Table 1>
SW1
(MODEL SELECTION)
DCL
I.B
CNMF
6
(WHT) FUSE
1
T11
SWE
DB1
LED3
Refer to
tables
1and 2
1 2
CN2L
(RED)
1
CN151
(WHT)
5
9
CN90
(WHT)
1
CN20
(RED)
1 2
CN41
(WHT)
1
CN44
(WHT)
4
4
YLW
1 CN32 3
(WHT)
1
1
5
CN51
(WHT)
CN4F
(WHT)
LDSWE(A)
(BLU)
CNRU
(WHT)
YLW
ORN
BLK
1 2 3 4 5
TO
OUTDOOR
UNIT
MODELS
M
1~
2
S.W
1 2 3 4 5
RP50
LDSWE(B) SWE2
W.B
6
SETTING
1 2 3 4 5
RP35
ORN
BRN
ON
OFF
<Table 2>
SW2 (CAPACITY CODE)
DP
3
X1
1
CNP(BLU)
CN3C 3
(BLU) 1
LED2
1
1
3
5
CN01
(BLK)
LED1
ON
OFF
SETTING
TB4
YLW
S1
ORN
S2
S3
ON
OFF
ON
OFF
The black square ( ) indicates
a switch position.
RU
LD101(B) REC1
R.B
BLU
4
LED1
CN22 1
(BLU) 2
BLU
LED2
1
2
TB6
1
2
TB5
(OPTION PARTS)
M
t
○
t
○
TH1
t
TH2 TH5
○
When attaching
When attaching drain
drain pump(option), pump (option)
remove the jumper
1
4
connector CN4F
FLOAT SW
CN4F
and fit the drain
(WHT)
FS
float switch (FS).
+1(Fig. 1)
CN01
I.B
(BLK)
1
3
5
YLW
ORN
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
I.B
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
1 3
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
CN3C(BLU)
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of
230V), adopting superimposed system for power and signal.
+1: If indoor and outdoor units have separate power supplies , refer to Fig 1.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
28
RED
BLU
GRN/YLW
YLW
ORN
ORN
BRN
TB2
L
N
POWER SUPPLY
~(1PHASE)
230V 50Hz
TB4
S1
S2
S3
INDOOR/OUTDOOR
COMMUNICATION
TO OUTDOOR
UNIT
PKA-RP60KAL
PKA-RP100KAL
[LEGEND]
SYMBOL
I.B
CN2L
CN32
CN41
CN51
CN90
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
CNP
CN4F
R.B
TB6
NAME
Indoor controller board
Connector (LOSSNAY)
Connector (Remote switch)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote operation adapter)
FUSE (T3.15AL250V)
Power supply (I.B)
Power supply (R.B)
Transmission (Indoor-outdoor)
Switch (Model selection) +See table 1
Switch (Capacity code) +See table 2
Connector (Emergency operation)
Relay (Drain pump(option))
Drain pump (option) power supply (Drain pump(option))
Drain float switch (Drain pump (option))
Wired remote controller
Terminal block (Remote controller transmission line)
SYMBOL
M
MS
S.W
SWE2
TB2
TB4
TB5
TH1
TH2
TH5
W.B
LED1
LED2
REC1
DCL
DP
FS
NAME
Vane motor
Fan motor
Switch board
Emergency operation
Terminal block (Indoor unit Power (option))
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line)
Room temp. Thermistor
(0 / 15k, 25 / 5. 4k Detect)
Pipe temp. Thermistor/liquid
(0 / 15k, 25 / 5. 4k Detect)
Cond. / eva. temp. Thermistor
(0 / 15k, 25 / 5. 4k Detect)
PCB for wireless remote controller
LED (Operation indication : Green)
LED (Preparation for heating : Orange)
Receiving unit
REACTOR
DRAIN PUMP (OPTION)
DRAIN FLOAT SWITCH (OPTION)
MF
+1(Fig. 1)
CN01
I.B
(BLK)
YLW
1
ORN
3
5
INDOOR/OUTDOOR
COMMUNICATION
The black square ( ) indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are,
:Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers
(S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric
wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V),
adopting superimposed system for power and signal.
+1 If indoor and outdoor units have separate power supplies , refer to Fig 1.
+2 For power supply system of this unit, refer to the caution label located near this diagram.
29
TB2
L
N
YLW TB4
ORN S1
ORN S2
BRN
S3
I.B
1 3
CN3C (BLU)
RED
BLU
GRN/YLW
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR
UNIT
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
PKA-RP50GAL
SYMBOL
C
MF
MV
TB2
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR <LOSSNAY>
CONNECTOR <REMOTE SWITCH>
CONNECTOR <HA TERMINAL-A>
CONNECTOR <CENTRALLY CONTROL>
SWITCH <MODEL SELECTION>+See Table 1.
SWITCH <CAPACITY CODE>+See Table 2.
SWITCH <EMERGENCY OPERATION>
RELAY <FAN MOTOR>
FAN CONTROL ELEMENT
POWER SUPPLY <I.B>
POWER SUPPLY <R.B>
TRANSMISSION <INDOOR-OUTDOOR>
P.B CNDK
(RED)
TB4
TB5,TB6
TH1
TH2
TH5
1 2 3
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
BLK
WHT
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(RED)
(ORN)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
ZNR
X4
THERMAL FUSE <10410A>
THERMAL FUSE <8410A>
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
CN41
CN2L
CN51
CN32
RED
BLU
GRN/YLW
TO
OUTDOOR
UNIT
I.B
6
FUSE
X4
BCR
YLW
ORN
RED
WHT
RED
WHT
BLK
FAN 1 3 5
(WHT)
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED <RUN INDICATOR>
LED <HOT ADJUST>
SWITCH (HEATING ON/ OFF>
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
+1 (Fig.1)
1
2
C
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
HEATER
FS1
FS2
H1
26H
88H
CN2S
(WHT)
1
2 DC13.1V
3
MF
NAME
CAPACITOR <FAN MOTOR>
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) +PKH-P.GALH
models only or option for PKA-RP.GAL models.
TERMINAL BLOCK <INDOOR/ OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER
TRANSMISSION LINE> <OPTION>
ROOM TEMP.THERMISTOR
<0/ 15k, 25/ 5.4k DETECT>
PIPE TEMP.THERMISTOR/ LIQUID
<0/ 15k, 25/ 5.4k DETECT>
COND./ EVA.TEMP.THERMISTOR
<0/ 15k, 25/ 5.4k DETECT>
MV
WIRELESS
CN90
(WHT)
TB2
L
N
POWER
SUPPLY
~(1PHASE)
230V 50Hz
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
PKA-RP35GAL
1 3
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
LED3 LED2 LED1
SW2
SWE
ON
OFF
SW1
INTAKE LIQUID PIPE
CN20 CN21
CN29
(RED) (WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
TH2
TH1
2
1
TH5
R.B
TRANSMISSION WIRES DC12V
1
TB6
2
TB5
PKH-P35,50GALH models only
1 2
YLW
YLW
I.B
HEATER
CN24
(YLW)
6
H1
RED
88H
1
SW1
Service board
1 2 3 4 5
ON
OFF
6
GRY
5 RED
FS1
26H
MODELS
PKA-RP35GAL
PKH-P35GALH
FS2
RED
WHT
1
2
RED 5
88H
TB2
L
3 RED
N
BLU
GRN/YLW
SW2
Service board
MODELS
Service board
1 2 3 4 5
1 2 3 4 5
ON
OFF
PKA-RP50GAL
PKH-P50GALH
POWER SUPPLY
~(1PHASE)
230V 50Hz
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
ON
OFF
The black square ( ■ ) indicates a switch position.
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
30
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
PKA-RP60FAL
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) +See Table 1.
SWITCH (CAPACITY CODE) +See Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
P.B CNDK
(RED)
SYMBOL
C
MF
MV
TB2
MF
1 2 3
NAME
CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) +PKH-P.FALH
models only or option for PKA-RP.FAL models.
TERMINAL BLOCK(INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )(OPTION)
ROOM TEMP.THERMISTOR
(0/15k, 25/5.4k DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0/15k, 25/5.4k DETECT)
COND./EVA.TEMP.THERMISTOR
(0/15k, 25/5.4k DETECT)
TB4
TB5
TH1
TH2
TH5
1
2
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
X4
BCR
BLK
WHT
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(ORN)
(RED)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
ZNR
X4
CN41
CN2L
CN51
CN32
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR )
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIRED REMOTE CONTROLLER BOARD(OPTION)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
HEATER
FS1,2 THERMAL FUSE(117 10A:60,71FALH/
117 16A:100FALH)
HEATER
H1
26H HEATER THERMAL SWITCH
88H HEATER CONTACTOR
+1 (Fig.1)
RED
BLU
GRN/YLW
TO
OUTDOOR
UNIT
I.B
6
FUSE
FAN 1 3 5
(WHT)
YLW
ORN
RED
WHT
RED
WHT
BLK
C
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
TB6
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
CN2S
(WHT)
1
2 DC13.1V
3
PKA-RP100FAL
1 3
MV
TB2
L
N
POWER
SUPPLY
(1PHASE)
230V 50Hz
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
PKA-RP50FAL2
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
WIRELESS
CN90
(WHT)
LED3 LED2 LED1
SWE
ON
OFF
SW2
SW1
INTAKE LIQUID PIPE
CN20 CN21
CN29
(RED) (WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
TH2
TH1
Table 1
SW1
Service board
2
1
TH5
Service board
MODELS
MODELS
PKA-RP50FAL2 1 2 3 4 5
1 2 3 4 5
PKA-RP71FAL
ON
ON
PKA-RP60FAL
OFF
OFF PKH-P71FALH
PKH-P60FALH
The black square ( ■ ) indicates a switch position.
HEATER
6
88H
1 2 3 4 5
MODELS
PKA-RP100FAL
ON
OFF PKH-P100FALH
Service board
1 2 3 4 5
ON
OFF
P100FALH models only
FS1
RED
1
SW2
Service board
H1
CN24
1 2 (YLW)
YLW
YLW
I.B
1
TB6
2
TRANSMISSION WIRES DC12V
TB5
Table 2
PKH-P60
R.B
6
GRY
5 RED
FS2
26H
RED
WHT
1
2
RED 5
88H
TB2
L
3 RED
N
BLU
GRN/YLW
POWER SUPPLY
(1PHASE)
230V 50Hz
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for
power and signal.
+1: If indoor and outdoor units have separate power supplies, refer to Fig 1.
+2: For power supply system of this unit, refer to the caution label located near this diagram.
31
4-2. OUTDOOR UNIT
PUHZ-HRP71VHA
PUHZ-HRP100VHA
SYMBOL
P.B.
TABU/V/W
TABS/T
TABP1/P2/P
TABN1/N2/N
DS2, DS3
IPM
N.F.
LI / LO
NI / NO
EI, E2
52C
C.B.
SW1
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal <L/N-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<N-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
SW4
SW5
SYMBOL
SW6
SW7
SW8
SW9
SWP
CN31
SS
CNM
CNMNT
NAME
Switch<Model Select>
Switch<Function Setup>
Switch<Function Setup>
Switch
Switch<Pump Down>
Connector<Emergency Operation>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
CNVMNT
<Connected to Optional M-NET Adapter Board>
Connector
CNDM
< Connected for Option (Contact Input)>
LED1,LED2 LED<Operation Inspection Indicators>
Fuse< T6.3AL250V>
F1~F4
X51,X52,X55 Relay
When M-NET adapter is connected
LEV-C
LEV-A
LEV-B
M
M
TH33 TH32 TH7 TH6 TH3 TH4
M
5
C. B.
t°
t° t°
7
1
CNF2
(WHT)
3
63L
63H (RED)
(YLW)
1
3
TRANS
2
1
3
6
1
LEV-B
(RED)
1
CN2
(WHT)
F1
3
1
21S4 3
(GRN)
F4
4
14
LEV-C
(BLU)
6
1
2
3
1 SV2
3
M-NET SUBSTRATE
2
1
CN2M
(WHT)
3
1
3
A B S
TB7
1
M-NET
5
(WHT)
SV
BLU
WHT
N. F.
NO
2
CN52C
(BLK)
P. B.
1
CNAF
(WHT)
CNDC
(PNK) 2
6
1
BLK
TABN1
BLK
E2
U
2
BLK
W
NI
RED
L1
L2
1
P
N1
N2
BLK
6
RED
L
N
S1
S2
BRN
BLK
WHT
4
ORN
DCL
EI
U
BLU
RED
MC
M-NET ADAPTER
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1st digit>
Switch<Address setting : 2nd digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
U
LI
GRN/YLW
YLW
V
MS
3~
CN5
(RED)
1
CNAC1
(WHT)
BLU
U
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
2
1
3
RED
RED
1
2
1
2
TABP
CNAC2
(RED)
WHT TABN2
WHT
CB
CN5
(RED)
CN4
(WHT)
TABN
TABS WHT
1
TABW
2
DS2
TABP1 RED
RED TABU
t° 2
7
1 CN3
2 (WHT)
TABT BLU
3
IPM
WHT TABV
BLK
TH8
TABP2
CN2
(WHT)
DS3
3
1
RED
7
2
1
52C
LO
4
CND
(WHT)
3 1
1 SS
(BLU)
21S4
SW12
LED4
CN31
1 2
X52
2
3
1
5
CN52C
(RED)
2 1
7
1
7
F3
CNAC
(WHT)
1
3
CNM
(WHT)
5
2
F2
1
CNVMNT CNMNT
(WHT) (WHT)
CN4
(WHT)
CNDC 1
(PNK)
CNS
(WHT)
6
SW6
LEV-A
(WHT)
SW1
1
2 1
CNDM
(WHT)
12
CN51
(WHT)
4
SW4 SWP SW8
1
LED3
+1
X51
1 2
3
X55
1
SW5
+1
CNF1
(WHT)
TH33 TH32 TH7/6 TH3 TH4
(YLW) (BLK) (RED) (WHT) (WHT)
MF2 1
MS
3~
5
5
t°
t°
LED1
MF1 1
MS
3~
t°
LED2
7
SW11
CN5
(WHT) SW1
1
LED2
5
3
SW7
63L
SW9
63H
LED1
NAME
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Low Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heatsink>
Electronic Expansion Valve
Reactor
Active Filter Module
Main Smoothing Capacitor
Capacitor
LED5
[LEGEND]
SYMBOL
TB1
MC
MF1, MF2
21S4
63H
63L
SV
TH3,TH32,TH33
TH4
TH6
TH7
TH8
LEV-A, LEV-B,LEV-C
DCL
ACTM
CB
CY1,CY2
CY1
CY2
S3 TB1
WHT
Io
+1MODEL SELECT
ACTM
INDOOR
UNIT
POWER SUPPLY
~/N 230V 50Hz
The black square ( ■ ) indicates a switch position.
MODEL
71V
SW6
ON
OFF
ON
100V OFF
32
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW5-6 +2
ON
OFF
ON
OFF
1 2 3 4 5 6
1 2 3 4 5 6
PUHZ-HRP100YHA
[LEGEND]
SYMBOL
TB1
TB2
MC
MF1, MF2
21S4
63H
63L
SV
TH3,TH32,TH33
TH4
TH6
TH7
LEV-A, LEV-B, LEV-C
ACL1~ACL4
CB1, CB2
CK
CY1, CY2
RS
PUHZ-HRP125YHA
NAME
Terminal Block<Power Supply>
Terminal Block<Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Low Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Electronic Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
Capacitor
Rush Current Protect Resistor
SYMBOL
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
X52A
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
GD1, GD3
CONV.B.
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
N-IN
CK-OU
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal<L1/L2/L3-Power Supply>
Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board
Connection Terminal<L1/L2/L3/N-Power Supply>
Connection Terminal<L1/L2/L3/N-Power Supply>
Connection Terminal<Ground>
Converter Circuit Board
Connection Terminal<L1-Power Supply>
Connection Terminal<L1-Power Supply>
Connection Terminal<L2-Power Supply>
Connection Terminal<L3-Power Supply>
Connection Terminal
Connection Terminal
SYMBOL
C.B.
SW1
NAME
Controller Circuit Board
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Adress>
SW4
Switch<Test Operation>
SW5
Switch<Function Switch>
SW6
Switch<Model Select>
SW7
Switch<Function Setup>
SW8
Switch<Function Setup>
SW9
Switch
SWP
Switch<Pump Down>
CN31
Connector<Emergency Operation>
LED1, LED2 LED<Operatiion Inspection Indicators>
F1~F4
Fuse<T6.3AL250V>
CNM
Connector<A-Control Service Inspection Kit>
Connector
CNMNT
<Connect to Optional M-NET Adapter Board>
Connector
CNVMNT
<Connect to Optional M-NET Adapter Board>
Connector
CNDM
< Connection for Option(Contact Input)>
CN3S
Connector< Connection for Option>
CN51
Connector< Connection for Option>
SS
Connector< Connection for Option>
X51,X52,X55 Relay
M-NET ADAPTER
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
Terminal Block<M-NET connection >
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting: 1st digit>
Switch<Address setting. 2nd digit >
LED<Power Supply: DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission: Sending>
LED<Transmission: Receiving>
LED<Power Supply: DC12V>
LEV-C
t°
5
5
CN2
(WHT) 7
1
1
CNDC
(PNK)
14
CNM
(WHT)
LEV-C
(BLU)
6
2
3
1 21S4 3
(GRN)
BLK
BLU
21S4
P.B.
3
1 SV2
(BLU)
3
CN51
(WHT)
X51
X52
F4
3 4
2
1
1 SS
(WHT)
SV
1
3
3
TB7
1
M-NET
5
+1MODEL SELECT
The black square (■) indicates a switch position.
MODEL
7
SW6
ON
100Y OFF
BLK
TB-L2
WHT
TB-L1
RED
BLK
TB-L3
+
TB-P2
CB1
TB-N1
+
CB2
3
3
1
CK
CONV.B.
L1-IN
L1-A1
+
TB-C1
1 2 3 4 5 6 7 8
+2. SW5 -1 to 5 : Function Switch
L3-OU BLK
RS
ORN
3~
+
RED
WHT
S3
V MS
2
2 1
ACL1
LI2 U
BLK
BLU
LI3
NI
RED
U
LO2
WHT
U
LO3
BLK
U
NO
BLU
GRN/YLW
GD3
33
CNDC
(PNK)
2
1
3
U -1 CNL
(BLU)
3
WHT
GD1
ACL2
+
+
U
WHT
N
WHT
LO1
BLK
L3
LI1
BLK
L2
RED
BLU
CNAC2
3 (RED)
TB1
L1
POWER SUPPLY
3N~
400V 50Hz
CNCT
(RED) 1
3
RED
CNAC1
(WHT) 1
RED
N.F.
NO FUSE
BREAKER
ON
OFF
RED
TB-U
--
RED
INDOOR
UNIT
S2
WHT
SW5-6 +2
ON
OFF
1 2 3 4 5 6 7 8
ON
125Y OFF
W MC
BLK
U
+
BRN
S1
TB-W
+
--
2 CN5
1 (RED)
X52A
RED
YLW
TB2
7
TB-V
2 CN4
1 (WHT)
CY2
CY1
2
CN2
(WHT)
BLK
2
1
CN7
(WHT)
1 3
CN7
(WHT)
CND
(WHT)
3 1
A B S
1
3
L1-A2
1
SW12
LED3
LED4
M-NET SUBSTRATE
BLK CK-OU
F1
CNS
(WHT)
3
F3
CNAC
(WHT)
1 2
X55
7
F2
LED2
CN31
CN4
(WHT)
1 2
SW11
SW1
LED5 CN2M
(WHT)
LED1
1
1
RED
1
5
WHT
TRANS
1 3 1
5
CNVMNT CNMNT
(WHT) (WHT)
L2-A2
3 (RED)
6
L1-OU RED
63L
1
63H
(YLW)
LEV-B
(RED)
N-IN
3
6 1
L3-A2
1
LEV-A
(WHT)
L2-OU WHT
CNF2
(WHT)
1
SW6
1 2 21
TH3 TH4
(WHT) (WHT)
SW1
1
4
TH7/6
(RED)
SW5
1 3 1 2
TH33 TH32
(YLW) (BLK)
5
+1
SW7
+1
3
2
When M-NET adapter is connected)
5
3
CNDM CN3S
(WHT) (WHT)
7
MS
3~
M
SW4 SWP SW8
1
MF2
t°
M
LED1
MS
3~
t° t°
M
LED2
CNF1
7 (WHT)
1
MF1
t°
t°
LEV-B
SW9
C.B.
LEV-A
CN5
(WHT)
63L
63H
TH33 TH32 TH7 TH6 TH3 TH4
ACL4
ACL3
1 2 3 4 5 6
1 2 3 4 5 6
SW6
SW7
SW8
SW9
SWP
LEV-C
1
1
CNDC
(PNK)
CN2
(WHT)
1
1
1 2
7
1
F1
3
1
2
21S4 3
F4
4
LEV-C
(BLU)
1
SW7
SW9
SW6
2
1
1 SV1
CND
(WHT)
3 1
CN31
3
3
(GRN)
M-NET ADAPTER
CN2M
(WHT)
3
6
3
SW12
LED4
1
3
A B S
TB7
1
F3
CNAC
(WHT)
1
14
CNM
(WHT)
CN52C
(RED)
5
CN4
(WHT)
2
7
F2
3
3
LED3
+1
CNDM
(WHT)
TRANS
2
CNS
(WHT)
1
1 3 1
5
CNVMNT CNMNT
(WHT) (WHT)
SW5
+2
1 3 1
6 1
6
63HS
LEV-A
LEV-B
(WHT)
(WHT)
(RED)
NAME
Terminal Block<M-NET connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Receiving>
LED<Power Supply : DC12V>
SW11
CN5
(WHT) SW1
1
LED2
5
63L
1 3 (RED)
63H
(YLW)
3
5
CN51
(WHT)
7
MS
3~
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
5
5
3
t°
CNF2
(WHT)
1
M
SW1
t°
M-NET ADAPTER
When M-NET adapter is connected
SW4 SWP SW8
t°
LEV-B
M
LED1
t°
LEV-A
X52
MS
3~
3
M-NET
5
1 SS
(WHT)
(GRY)
21S4
2
P. B.
1
2
CN4
(WHT)
1
CN2
(WHT)
CN52C
3 (RED)
1
7
52C
52C
BLK
2
WHT
CNDC
(PNK)
N2
3
CE
E3
1
CNAC2
(RED)
1
P2
RED
IGBT
3
E2
BLK
1
3
CNAC1
(WHT)
RED
WHT
E4
W V U
MS
3~
DCL1
EI
NI U
U
LI
BLK
BLK
L
BLU
RED
MC
CY1
CY2
N
S1
BRN
DCL
ORN
DCL2
GRN/YLW
YLW
W V U
BLK
WHT
RED
MF2
t°
t°
CNF1
4 1 2 21
7 (WHT) 1 3 1 2 1
TH33 TH32 TH7/6 TH3 TH4
(YLW) (BLK) (RED) (WHT) (WHT)
LED2
C.B.
1
NAME
Connector<Emergency Operation>
SV1
Connector<Connection for Option>
Connector<Connection for Option>
SS
CNM
Connector<A-Control Service Inspection Kit>
Connector
CNDM
< Connected for Option (Contact Input)>
LED1,LED2 LED<Operation Inspection Indicators>
Fuse< T6.3AL250V>
F1~F4
X51,X52,X54 Relay
M
TH33 TH32 TH7 TH6 TH3 TH4
MF1
SYMBOL
CN31
LED1
SW4
SW5
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal <L-Phase>
Connection Terminal<N-Phase>
Recator
Power Module
Connection Terminal (Ground)
Controller Circuit Board
Switch<Manual Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch, Model Select>
Switch<Model Select>
Switch<Function Set up>
Switch<Function Set up>
Switch<Function Switch>
Switch<Pump Down>
63HS
63L
63H
SYMBOL
P.B.
U/V/W
LI
NI
DCL1, DCL2
IGBT
E1,E2,E3,E4
C.B.
SW1
LED5
NAME
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Low Pressure Switch
High Pressure Sensor
Thermistor<Liquid>
Thermistor<Discharge>
Thermistor<2-Phase>
Thermistor<Ambient>
Thermistor<Suction>
Thermistor<Ref. check>
Electronic Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
X51
[LEGEND]
SYMBOL
TB1
MC
MF1, MF2
21S4
63H
63L
63HS
TH3
TH4
TH6
TH7
TH32
TH33
LEV-A, LEV-B,LEV-C
DCL
CE
CY1,CY2
PUHZ-HRP100VHA2
X54
PUHZ-HRP71VHA2
S2
Ambient temp.
3°C or less
(lnitial setting)
SW9-3,4 +4
ON
OFF
1 2 3 4
Ambient temp.
0°C or less
SW9-3,4 +4
ON
OFF
1 2 3 4
MODEL
SW6
71V
ON
OFF
100V
ON
OFF
S3 TB1
INDOOR
UNIT
+3 Setting of the starting ambient temp. of the flash injection.
The black square (■) indicates a switch position.
+1 MODEL SELECT
The black square (■) indicates a switch position.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Ambient temp.
+4. SW9-1 to 2 : Function Switch
34
SW9-3,4 +4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4 5 6
1 2 3 4 5 6
+2 SW5 -1 to 5 : Function Switch
POWER SUPPLY
~/N 230V 50Hz
-3°C or less
SW5-6 +2
ON
OFF
Ambient temp.
-6°C or less
SW9-3,4 +4
ON
OFF
1 2 3 4
SYMBOL
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
X52A
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
GD1, GD3
CONV.B.
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
N-IN
CK-OU
1
2
14
CNM
(WHT)
LEV-C
(BLU)
SW7
SW6
1
3
3
7
ON
100Y OFF
WHT
V MS
+
CB1
+
CB2
3
3
1
CK
CONV.B.
L1-IN
L1-A1
+
TB-N1
TB-C1
BLK
TB-P2
2
2 1
CNAC2
3 (RED)
BLU
CNCT
(RED) 1
3
RED
CNAC1
(WHT) 1
RED
N.F.
ACL1
TB1
L1
L2
L3
N
WHT
LI2 U
LI3
BLK
NI
BLU
LO1
RED
U
LO2
WHT
U
LO3
BLK
U
NO
BLU
GRN/YLW
CNDC
(PNK)
1
2
3
ACL3
U -1 CNL
(BLU)
3
WHT
BLK
GD3
BRN
GD1
ACL2
+
+
U
BLK
POWER SUPPLY
3N~
400V 50Hz
RED
LI1
ON
OFF
L1-A2
+
RED
WHT
RED
L3-A2
WHT
TB-L1
BLK
--
BLK
TB-L2
1 2 3 4 5 6 7 8
ON
OFF
+2 SW5 -1 to 5 : Function Switch
RED
TB-L3
ON
125Y OFF
3~
U
TB-U
+
RS
ORN
W MC
BLK
L3-OU BLK
2 CN5
1 (RED)
WHT
S3
TB-W
+
--
RED
INDOOR
UNIT
S2
7
TB-V
2 CN4
1 (WHT)
BRN
S1
CN2
(WHT)
X52A
RED
YLW
TB2
1
1 2 3 4 5 6 7 8
CN7
(WHT)
1 3
CN7
(WHT)
2
M-NET
+1 MODEL SELECT
The black square (■) indicates a switch position.
MODEL
SW6
SW5-6 +2
P.B.
2
3
1 SS
(WHT)
21S4
3
ACL4
+3 Setting of the starting ambient temp. of the flash injection.
The black square (■) indicates a switch position.
Ambient temp.
3°C or less
(lnitial setting)
SW9-3,4 +4
ON
OFF
1 2 3 4
Ambient temp.
0°C or less
SW9-3,4 +4
ON
OFF
NAME
Terminal Block<M-NET connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1s digit>
Switch<Address setting : 10s digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Receiving>
LED<Power Supply : DC12V>
TB7
5
X51
1 SV1
(GRY)
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
A B S
BLK CK-OU
3 4
1 21S4 3
(GRN)
CND
(WHT)
3 1
L1-OU RED
3
X54
1
F4
CN5
(WHT)
2
1
6
X52
F1
CNS
(WHT)
3
SW12
LED3
LED4
M-NET ADAPTER
1
F3
CNAC
(WHT)
1 2
LED2
CN31
7
F2
SW11
SW1
LED5 CN2M
(WHT)
LED1
CN2
(WHT) 7
1
CNDC
(PNK)
1
5
CN4
(WHT)
1 2
1 3 1
5
CNVMNT CNMNT
(WHT) (WHT)
L2-OU WHT
63L
3 (RED)
1 3 1
6 1
6
63HS
LEV-A
LEV-B
(WHT)
(WHT)
(RED)
1
SW9
3
5
+1
SW1
1
1
1
5
+2
63H
(YLW)
TRANS
5
3
5
CNF2
(WHT)
3
2
M
t°
CNDM
(WHT)
7
M
When M-NET adapter is connected
CN51
(WHT)
1
MS
3~
LEV-B
SW5
t°
LEV-A
LED1
t°
M-NET ADAPTER
M
LED2
MS
3~
MF2
t°
CNF1
4 1 2 21
7 (WHT) 1 3 1 2 1
TH33 TH32 TH7/6 TH3 TH4
(YLW) (BLK) (RED) (WHT) (WHT)
1
MF1
t°
t°
NAME
Controller Circuit Board
Switch<Manual Defrost, Defect History Record
Reset, Refrigerant Address>
SW4
Switch<Test Operation>
SW5
Switch<Function Switch, Model select>
SW6
Switch<Model Select>
SW7
Switch<Function Set up>
SW8
Switch<Function Set up>
SW9
Switch<Function Switch>
SWP
Switch<Pump Down>
CN31
Connector<Emergency Operation>
Connector<Connection for Option>
SV1
SS
Connector< Connection for Option>
LED1, LED2 LED<Operation Inspection Indicators>
CNM
Connector<A-Control Service Inspection Kit>
Connector
CNDM
< Connection for Option(Contact Input)>
F1~F4
Fuse<T6.3AL250V>
X51,X52,X54 Relay
LEV-C
63HS
TH33 TH32 TH7 TH6 TH3 TH4
C.B.
SYMBOL
C.B.
SW1
N-IN
63L
63H
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal<L1/L2/L3-Power Supply>
Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board
Connection Terminal<L1/L2/L3/N-Power Supply>
Connection Terminal<L1/L2/L3/N-Power Supply>
Connection Terminal<Ground>
Converter Circuit Board
Connection Terminal<L1-Power Supply>
Connection Terminal<L1-Power Supply>
Connection Terminal<L2-Power Supply>
Connection Terminal<L3-Power Supply>
Connection Terminal
Connection Terminal
RED
NAME
Terminal Block<Power Supply>
Terminal Block<Indoor/Outdoor >
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Low Pressure Switch
High Pressure Sensor
Thermistor<Liquid>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Ambient>
Thermistor<Suction>
Thermistor<Ref. check>
Electronic Expansion Valve
Reactor
Rush Current Protect Resistor
Main Smoothing Capacitor
Capacitor
SW4 SWP SW8
[LEGEND]
SYMBOL
TB1
TB2
MC
MF1, MF2
21S4
63H
63L
63HS
TH3
TH4
TH6
TH7
TH32
TH33
LEV-A, LEV-B, LEV-C
ACL1~ACL4
RS
CB1, CB2
CK
PUHZ-HRP125YHA2
L2-A2
PUHZ-HRP100YHA2
1 2 3 4
Ambient temp.
-3°C or less
+4. SW9-1 to 2 : Function Switch
35
SW9-3,4 +4
ON
OFF
1 2 3 4
Ambient temp.
-6°C or less
SW9-3,4 +4
ON
OFF
1 2 3 4
1 2 3 4 5 6
1 2 3 4 5 6
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·BA/BA2/BA3
PKA-RP·FAL(2)
PEAD-RP·EA(2)
unit : mm
PKA-RP·GAL
PEAD-RP·JA(L)
PEAD-RP·GA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Distributor
with strainer(#50)
Thermistor TH2
Pipe temperature (Liquid)
Thermistor TH1
(Room temperature)
Strainer(#50)
PKA-RP·HAL
PKA-RP·KAL
Strainer (#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH2
Pipe temperature(Liquid)
Thermistor TH5
(Cond./ Eva.temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Thermistor TH1
(Room temperature)
Distributor with strainer
(#50/#50: HAL)
(#50/#100: KAL)
36
Strainer (#50)
Unit : mm (inch)
5-2. OUTDOOR UNIT
PUHZ-HRP71VHA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
Thermistor TH7
(Outdoor)
Heat exchanger
Refrigerant
GAS pipe
connection
(5/8 inch)
Thermistor
TH6
(Outdoor
2-phase pipe)
Solenoid valve
(Four-way valve)
Ball valve
Strainer
#50
Charge plug
(High pressure)
Charge plug
(Low pressure)
Muffler
Thermistor TH3
(Outdoor pipe)
High pressure
switch 63H
Low pressure
switch 63L
Linear
expansion valve B
Refrigerant
LIQUID pipe
Strainer
connection
#100
(3/8 inch) Stop valve
(with service port)
Thermistor TH33
(Outdoor pipe)
Thermistor
TH32
(Outdoor pipe)
Strainer
#100
Strainer
#100
Distributor
Strainer
#100
Thermistor TH4
(Discharge)
Bypass
valve
Linear expansion valve A
Strainer
#100
Compressor
Power
receiver
Linear
expansion valve C
Replace
filter
Injection port
Restrictor
Strainer
valve
#100
Heat interchange circuit
Refrigerant flow in cooling
Refrigerant flow in heating
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
Heat exchanger
Refrigerant
GAS pipe
connection
(5/8 inch)
Thermistor
TH6
(Outdoor
2-phase pipe)
Solenoid valve
(Four-way valve)
Ball valve
High pressure
sensor(63HS)
Charge plug
(High pressure)
Strainer
#50
Charge plug
(Low pressure)
Muffler
Low pressure
switch 63L
Thermistor TH3
(Outdoor pipe)
High pressure
switch 63H
Thermistor
TH32
(Outdoor pipe)
Strainer
#100
Strainer
#100
Linear
expansion valve B
Refrigerant
LIQUID pipe
Strainer
connection
#100
(3/8 inch) Stop valve
(with service port)
Thermistor TH7
(Outdoor)
Distributor
Thermistor TH33
(Outdoor pipe)
Strainer
#100
Thermistor TH4
(Discharge)
Linear expansion valve A
Strainer
#100
Compressor
Power
receiver
Linear
expansion valve C
Injection port
Heat interchange circuit
Refrigerant flow in cooling
Refrigerant flow in heating
37
6
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-HRP·VHA(2), PUHZ-HRP·YHA(2)
Rated cooling capacity
1.4
Cooling capacity ratio
Indoor intake air wet-bulb temperature <W.B. :>
1.2
22
1.0
20
18
0.8
0.6
16
-5
0
5
10
15
20
25
30
35
40
46
Outdoor intake air dry-bulb temperature <D.B. >
Rated cooling input
22 20
18
16
Cooling input ratio
1.2
1.0
0.8
0.6
Indoor intake air wet-bulb temperature <W.B. :>
0.4
-5
0
5
10
15
20
25
30
35
40
Outdoor intake air dry-bulb temperature <D.B. >
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
38
46
Rated heating capacity
1.4
15
20
25
Capacity ratio
1.2
1.0
0.8
Indoor intake air dry-bulb temperature <: D.B.>
0.6
-25
-20
-15
-10
-5
0
5
10
15
Outdoor ambient temp.(˚CWB)
Rated heating input
2.5
Input ratio
2.0
1.5
25
20
15
1.0
Indoor intake air dry-bulb temperature <: D.B.>
0.5
-25
-20
-15
-10
-5
0
5
Outdoor ambient temep.(ºCWB)
39
10
15
7
CORRECTION FACTORS
PUHZ-HRP71, 100VHA(2)
PUHZ-HRP100, 125YHA(2)
Cooling capacity correction factors
Outdoor unit
Refrigerant piping length (one way)
5m
10m
20m
30m
40m
50m
55m
60m
70m
80m
PUHZ-HRP71VHA(2)
1.00
0.988
0.966
0.946
0.929
0.913
0.905
0.897
0.876
0.870
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
1.00
0.985
0.957
0.931
0.908
0.886
0.876
0.865
0.846
0.829
PUHZ-HRP125YHA(2)
1.00
0.981
0.946
0.914
0.885
0.858
0.845
0.834
0.812
0.792
Heating capacity correction factors
Outdoor unit
Refrigerant piping length (one way)
5m
10m
20m
30m
40m
50m
55m
60m
70m
80m
PUHZ-HRP71VHA(2)
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
PUHZ-HRP125YHA(2)
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
40
8
APPLICABLE EXTENSION PIPE FOR EACH MODEL
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM
Pipe length
<Table 1> Maximum pipe length
Liquid
pipe
(mm)
Gas
pipe
(mm)
OD
Thickness
OD
Thickness
:9.52
t0.8
:15.88
t1.0
Standard size
50m +
[30m]
:12.7
t0.8
HRP71~125
:19.05
t1.0
:12.7
t0.8
:19.05
:15.88
t1.0
t1.0
50m
[30m]
50m
[20m]
<Marks in the table>
: It can be used.
: Additional refrigerant charge is required when
the pipe length exceeds 20m.
50m
[20m]
50m
[30m]
+ The maximum length is 75m in case of new pipes.
The maximum pipe length
Charge-less pipe length
8-1-2. TWIN SYSTEM
(1) TWIN SYSTEM
<Table 2> Maximum pipe length
HRP71(RP35%2)
Main pipe
(mm)
[A]
Liquid pipe
:6.35
:12.7
Gas pipe
Liquid pipe
:6.35
Gas pipe
:12.7
Branch
pipe Liquid pipe :9.52
(mm) Gas pipe :15.88
[B, C]
Liquid pipe :9.52
Gas pipe
HRP100(RP50%2)
:9.52
:9.52
:15.88
:15.88
Standard size Standard size
50m
50m +
[30m]
[30m]
50m
[30m]
50m
[30m]
:9.52
:19.05
:12.7
:19.05
50m
[30m]
50m
[20m]
50m
[30m]
50m
[20m]
HRP125(RP60%2)
:9.52
:15.88
:9.52
:19.05
:12.7
:19.05
Standard size
50m +
[30m]
50m
[30m]
50m
[20m]
:19.05
+ The maximum length is 75m in case of new pipes.
Indoor unit side
h
Indoor unit
Indoor unit
B
C
H
Outdoor unit
Distribution pipe
Outdoor unit side
A
<TWIN SYSTEM>
Total length A + B + C
Max. 75 m
Height difference
H(Indoor unit-Outdoor unit)
h(Indoor unit-Indoor unit)
Max. 30m
Max. 1m
Distance between indoor and indoor units
Pipe length |B-C|
Max. 8m
Number of bends (one way)
Max. 15 (Max. 8 points between main pipe A and each branch pipe(B, C))
41
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
• Check additional refrigerant charging amount referring to table 5, 6 when liquid pipe is one size larger than standard diameter.
<Table 5> Required additional charge when the liquid pipe is one size larger than the standard diameter (1:1 SYSTEM)
Outdoor unit
Liquid pipe O.D.
Refrigerant amount to be added (Exceeding 20m)
PUHZ-HRP71-125
:12.7
100 g per 1 m
<Table 6> Required additional charge when the liquid pipe is one size larger than the standard diameter (TWIN SYSTEM)
Outdoor unit
When the extension pipe length (main piping + branch piping) exceed 20 m
PUHZ-HRP71-125
Additional refrigerant amount
W(g) = (100 % L1) + (60 % L2) + (30 % L3) - 2000
If the calculation produces a negative number ( W 0), additional charging is not necessary.
L1: :12.7 liquid pipe length (m)
L2: :9.52 liquid pipe length (m)
L3: :6.35 liquid pipe length (m)
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Additional refrigerant charging amount
Permitted
Amount of unit
for pipe length exceeding 30 m (kg)
Type
Outdoor unit
pipe length filling refrigerant (kg)
31 – 40m 41 – 50m 51 – 60m 61 – 70m 71 – 75m
1:1
0.6kg
1.2kg
1.8kg
75m or less
5.5kg
2.4kg
system PUHZ-HRP71-125
Type
Outdoor unit
Twin
system PUHZ-HRP71-125
Permitted
pipe length
Amount of unit
filling refrigerant (kg)
75m or less
5.5kg
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
31 – 40m
41 – 50m
51 – 60m
0.6kg
1.2kg
1.8kg
42
61 – 70m
71 – 75m
2.4kg
8-3. CAPACITY CORRECTION CURVES
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m)
[Sample calculation]
Indoor unit RP60 o 2 units (Twin system)
Outdoor unit HRP125 o 1
• Condition
Using existing pipes.
• Outdoor unit side
Liquid pipe [12.7 / Gas pipe [19.05
pipe length (A) 20m
• Indoor unit side
Liquid pipe [9.52 / Gas pipe [15.88
pipe length (B) 20m + (C) 15m
1) Farthest piping length
20m + 15m = 35m
Number of bends : 10
2) Corrected piping length 35m + 0.3 o 10 = 38m
3) Capacity correction
Outdoor unit side’s gas pipe [19.05
Standard [15.88 → 1 size up
Refer to 1Capacity curves <Standard size>
4) Capacity
Cooling capacity = Standard cooling capacity o 0.89
Heating capacity = Standard heating capacity o 0.98
1 Capacity curves for PUHZ-HRP · HA(2) model <Standard size>
100
Heating HRP71-125
Capacity ratio [%]
95
90
Cooling HRP71 model
85
Cooling HRP100 model
80
Cooling HRP125 model
75
Cooling
Note: The permitted pipe length is up to 80m.
Heating
70
5
10
15
20
25
30
35
40
45
50
55
60
65
70
Corrected pipe length [m]
2 When gas pipe is one size larger than standard size for PUHZ-HRP71-125.
1 Capacity can be obtained by referring to capacity curves of standard size.
43
75
80
9
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
Air speed
Coverage range
PLA-RP100BA
PLA-RP125BA
PLA-RP71BA2 PLA-RP100BA2
PLA-RP125BA2
PLA-RP100BA3
PLA-RP36BA
PLA-RP50BA
PLA-RP60BA
m3/min.
15
18
18
21
30
31
m/sec.
2.6
3.2
3.2
3.7
5.3
5.4
m
4.1
4.8
4.8
5.6
8
8.2
PKA-RP35GAL PKA-RP50GAL
Air flow
Air speed
Coverage range
m3/min.
12
12
m/sec.
5.3
5.3
10 (32.8)
10(32.8)
m (ft)
PKA-RP50FAL2
PKA-RP100FAL
PKA-RP60FAL
Air flow
Air speed
Coverage range
m3/min.
m/sec.
m (ft)
20
28
4.9
5.4
12.4(40.7)
15.3 (50.2)
PKA-RP35HAL PKA-RP50HAL
Air flow
Air speed
Coverage range
m3/min.
m/sec.
m (ft)
12
12
6.1
6.1
10.8 (35.4)
10.8 (35.4)
PKA-RP60KAL PKA-RP100KAL
Air flow
Air speed
Coverage range
m3/min.
m/sec.
m (ft)
22
26
6.0
6.8
14.3 (46.9)
16.1 (52.8)
w The air coverage range is the distance to which the 0.25 m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
44
9-2. PLA-RP·BA/BA2/BA3
9-2-1 FRESH AIR INTAKE AND BRANCH DUCT
1. Branch duct hole and fresh air intake hole (Fig. 1)
At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Fresh air intake hole
Fresh air intake hole diagram
Branch duct hole
3-:2.8 burring hole
:125 burring hole pitch
120
120
Indoor unit
*158
:100 cut out hole
Ceiling
Drain pipe
Refrigerant pipe
100
100
90
130
90
Branch duct
hole diagram
(view from
either side)
100
350
:175 burring hole pitch
Fig. 1
45
*167
70
*155
14-:2.8 burring hole
:150 cut out hole
3. Fresh air intake volume & static pressure characteristics
PLA-RP35~60BA
PLA-RP71BA2
At using multi-function casement, standard filter
50
Static pressure[Pa]
0
-50
2 - inlet
-100
-150
1 - inlet
-200
0
1
2
3
4
5
6
Air flow rate [m3/min]
At using multi-function casement, high efficiency filter
50
0
0
Static pressure[Pa]
Static pressure[Pa]
Direct intake to unit
50
-50
-100
-150
-200
0
1
2
3
4
5
-50
-100
-150
-200
6
2 - inlet
1 - inlet
0
1
2
3
Air flow rate [m3/min]
3
Air flow rate [m /min]
4
5
6
PLA-RP100BA/BA2/BA3, 125BA(2)
At using multi-function casement, standard filter
50
Static pressure[Pa]
0
-50
2 - inlet
-100
-150
1 - inlet
-200
0
2
4
Air flow rate [m3/min]
6
8
At using multi-function casement, high efficiency filter
Direct intake to unit
50
50
0
Static pressure[Pa]
Static pressure[Pa]
0
-50
-100
-150
-50
-100
2 - inlet
-150
1 - inlet
-200
0
2
4
Air flow rate [m3/min]
6
8
-200
46
0
2
4
Air flow rate [m3/min]
6
8
4. Change of outlet numbers
The optional air outlet is necessary.
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
Indoor unit
When the air outlets are closed, close the vane by
removing the vane connector.
Button
Outlet concave
portion
Vane motor
Up/down vanes
Connector
Air outlet shutter plate
(Option)
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
+ Branch duct should be connected to one of the branch duct holes on the main unit.
<4- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
+ Close the outlet on the side of branch duct and air flows in 3 directions.
<3- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
+ The outlet on the side of branch duct and one of the other outlets are closed.
Air flows in 2 directions.
<2- way air flow and branch duct>
Branch
duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air
outlet
closed
position
47
PLA-RP71BA2
4-way airflow (horizontal vane) Round duct
4-way airflow (horizontal vane) Rectangular duct
30
Duct
Static pressure [Pa]
Static pressure [Pa]
30
20
10
High
Duct
20
10
High
Low
Low
0
0
0
2
4
6
Airflow rate [m3/min]
0
8
3-way airflow (horizontal vane) Round duct
2
80
70
70
Duct
Duct
60
Close
Static pressure [Pa]
Static pressure [Pa]
60
50
40
30
Close
50
40
30
High
20
20
High
Low
10
0
Low
10
2
4
6
8
Airflow rate [m3/min]
0
10
2-way airflow (horizontal vane) Round duct
0
2
4
6
8
Airflow rate [m3/min]
10
2-way airflow (horizontal vane) Rectangular duct
100
100
90
90
Duct
80
Duct
80
Close
Close
70
60
50
40
30
High
20
Close
Close
Static pressure [Pa]
Static pressure [Pa]
8
3-way airflow (horizontal vane) Rectangular duct
80
0
4
6
Airflow rate [m3/min]
70
60
50
40
30
20
Low
Low
High
10
10
0
0
0
2
4
6
8
10
Airflow rate [m3/min]
0
12
2
4
6
8
10
Airflow rate [m3/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP71BA2.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
48
12
PLA-RP125BA(2)
4-way airflow (horizontal vane) Round duct
4-way airflow (horizontal vane) Rectangular duct
30
30
Duct
20
Static pressure [Pa]
Static pressure [Pa]
Duct
10
Low
10
2
4
Airflow rate [m³/min]
6
8
3-way airflow (horizontal vane) Round duct
0
2
4
Airflow rate [m³/min]
6
8
3-way airflow (horizontal vane) Rectangular duct
80
80
70
60
Duct
Duct
Close
Close
60
Static pressure [Pa]
70
50
40
High
50
40
High
30
30
20
20
Low
Low
10
10
0
0
0
2
4
6
Airflow rate [m³/min]
8
0
10
2-way airflow (horizontal vane) Round duct
2
4
6
Airflow rate [m³/min]
8
10
2-way airflow (horizontal vane) Rectangular duct
100
100
90
90
Duct
80
Duct
80
Close
70
Close
70
Close
Close
60
Static pressure [Pa]
60
Static pressure [Pa]
High
Low
High
0
0
0
Static pressure [Pa]
20
50
40
High
30
50
High
40
Low
30
Low
20
20
10
10
0
0
0
2
4
6
8
Airflow rate [m³/min]
10
0
12
2
4
6
8
10
12
Airflow rate [m³/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Airflow rate of PLA-RP100BA/BA2/BA3 can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP125BA(2).
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way airflow.
49
9-3. PEAD-RP·JA(L)
Fan performance
PEAD-RP35JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP35JA(L)
(External static pressure 35Pa) 220-240V 50Hz
120
60
110
Rated point
100
Limit
External static pressure (Pa)
External static pressure (Pa)
50
40
Rated point
High
30
Middle
20
Low
10
Limit
90
High
80
70
Middle
60
50
Low
40
30
20
10
0
7
9
11
13
15
17
19
0
21
7
9
11
Airflow rate(m3/min)
13
PEAD-RP35JA(L)
(External static pressure 50Pa) 220-240V 50Hz
17
19
21
PEAD-RP35JA(L)
(External static pressure 150Pa) 220-240V 50Hz
70
170
160
Rated point
150
60
140
Limit
External static pressure (Pa)
External static pressure (Pa)
15
Airflow rate(m3/min)
Rated point
50
High
40
Middle
30
Low
20
Limit
130
High
120
110
100
Middle
90
80
70
Low
60
50
40
30
10
20
10
0
7
9
11
13
15
17
19
0
21
Airflow rate(m3/min)
90
80
External static pressure (Pa)
Rated point
Limit
High
60
50
Middle
40
Low
30
20
10
0
7
9
11
13
15
9
11
13
15
Airflow rate(m3/min)
PEAD-RP35JA(L)
(External static pressure 70Pa) 220-240V 50Hz
70
7
17
19
21
Airflow rate(m3/min)
50
17
19
21
PEAD-RP50JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP50JA(L)
(External static pressure 35Pa) 220-240V 50Hz
130
70
120
110
60
50
High
40
Rated point
Middle
30
Low
20
Rated point
Limit
100
External static pressure (Pa)
External static pressure (Pa)
Limit
90
High
80
70
Middle
60
50
Low
40
30
20
10
10
0
9
14
0
19
9
14
19
Airflow rate(m3/min)
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 50Pa) 220-240V 50Hz
PEAD-RP50JA(L)
(External static pressure 150Pa) 220-240V 50Hz
180
80
170
160
70
External static pressure (Pa)
External static pressure (Pa)
Rated point
50
High
140
High
60
Middle
40
30
Rated point
150
Limit
Low
20
Limit
130
120
110
Middle
100
90
80
Low
70
60
50
40
10
30
20
0
9
14
10
19
0
Airflow rate(m3/min)
9
14
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 70Pa) 220-240V 50Hz
100
90
External static pressure (Pa)
80
Limit
Rated point
70
High
60
50
Middle
40
30
Low
20
10
0
9
14
19
Airflow rate(m3/min)
51
19
PEAD-RP60JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP60JA(L)
(External static pressure 35Pa) 220-240V 50Hz
120
60
110
50
Rated point
100
External static pressure (Pa)
External static pressure (Pa)
Limit
40
Rated point
30
High
20
Middle
90
Limit
High
80
70
Middle
60
50
Low
40
30
Low
10
20
10
0
10
15
20
25
0
10
30
15
Airflow rate(m3/min)
20
PEAD-RP60JA(L)
(External static pressure 50Pa) 220-240V 50Hz
170
160
Rated point
150
Limit
140
Rated point
50
External static pressure (Pa)
External static pressure (Pa)
30
PEAD-RP60JA(L)
(External static pressure 150Pa) 220-240V 50Hz
70
60
25
Airflow rate(m3/min)
High
40
Middle
30
20
Low
High
130
Limit
120
110
100
Middle
90
80
70
60
Low
50
40
30
10
20
10
0
10
15
20
25
0
30
Airflow rate(m3/min)
90
80
Rated point
External static pressure (Pa)
Limit
High
60
50
Middle
40
30
Low
20
10
0
10
15
20
15
20
Airflow rate(m3/min)
PEAD-RP60JA(L)
(External static pressure 70Pa) 220-240V 50Hz
70
10
25
30
Airflow rate(m3/min)
52
25
30
PEAD-RP71JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP71JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
130
120
60
High
110
Rated point
50
External static pressure (Pa)
External static pressure (Pa)
100
Limit
High
40
Rated point
30
Middle
20
Low
Limit
90
Middle
80
70
60
Low
50
40
30
10
20
10
0
10
15
20
25
0
30
10
15
Airflow rate(m3/min)
20
25
30
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 50Pa) 220-240V 50Hz
PEAD-RP71JA(L)
(External static pressure 150Pa) 220-240V 50Hz
90
180
170
High
160
80
Rated point
150
140
External static pressure (Pa)
External static pressure (Pa)
70
Limit
60
High
Rated point
50
Middle
40
30
Low
20
130
Middle
Limit
120
110
100
90
80
Low
70
60
50
40
30
10
20
10
0
10
15
20
25
0
30
Airflow rate(m3/min)
100
90
High
External static pressure (Pa)
80
Limit
Rated point
70
Middle
50
40
Low
30
20
10
0
10
15
20
15
20
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 70Pa) 220-240V 50Hz
60
10
25
30
Airflow rate(m3/min)
53
25
30
PEAD-RP100JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP100JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
150
140
Limit
130
60
External static pressure (Pa)
External static pressure (Pa)
120
50
40
Rated point
30
High
Middle
20
Low
High
Limit
110
Rated point
100
90
Middle
80
70
Low
60
50
40
30
10
20
10
0
10
15
20
25
30
35
40
0
45
Airflow rate(m3/min)
90
External static pressure (Pa)
External static pressure (Pa)
Limit
70
High
Rated point
50
Middle
40
Low
30
20
25
30
35
40
45
PEAD-RP100JA(L)
(External static pressure 150Pa) 220-240V 50Hz
100
60
15
Airflow rate(m3/min)
PEAD-RP100JA(L)
(External static pressure 50Pa) 220-240V 50Hz
80
10
20
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
High
Rated point
Limit
Middle
Low
30
20
10
0
10
0
10
15
20
25
30
35
40
45
PEAD-RP100JA(L)
(External static pressure 70Pa) 220-240V 50Hz
120
110
External static pressure (Pa)
100
Limit
High
90
80
Rated point
Middle
70
60
Low
50
40
30
20
10
0
10
15
20
25
30
35
40
10
15
20
25
30
Airflow rate(m3/min)
Airflow rate(m3/min)
45
Airflow rate(m3/min)
54
35
40
45
PEAD-RP125JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP125JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
180
170
Limit
160
High
60
External static pressure (Pa)
External static pressure (Pa)
High
140
50
Low
40
Limit
150
Middle
Rated point
30
20
130
120
110
100
90
80
Middle
Rated point
Low
70
60
50
40
30
10
20
10
0
15
20
25
30
35
40
0
45
15
20
Airflow rate(m3/min)
90
High
External static pressure (Pa)
External static pressure (Pa)
Limit
70
Middle
50
Rated point
Low
40
30
20
10
0
15
20
25
30
35
40
45
PEAD-RP125JA(L)
(External static pressure 70Pa) 220-240V 50Hz
150
140
130
External static pressure (Pa)
High
Limit
110
100
90
Middle
80
70
Rated point
Low
60
50
40
30
20
10
0
15
20
25
30
35
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
40
45
High
Limit
Middle
Rated point
Low
15
20
25
30
35
Airflow rate(m3/min)
Airflow rate(m3/min)
120
35
PEAD-RP125JA(L)
(External static pressure 150Pa) 220-240V 50Hz
100
60
30
Airflow rate(m3/min)
PEAD-RP125JA(L)
(External static pressure 50Pa) 220-240V 50Hz
80
25
40
45
Airflow rate(m3/min)
55
40
45
9-4. PEAD-RP·EA,EA2,GA
Corrected Airflow
120
100
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
9-4-1. FAN PERFORMANCE AND CORRECTED AIR FLOW
PEAD-RP35EA2
Fan Performance <30Pa>
140
PEAD-RP50EA
80
60
40
20
6
Cooling
1.0
0.9
0.8
8
10
10 12 14 16 18 20
Airflow (CMM)
Fan Performance <70Pa>
160
12 14 16 18
Airflow (CMM)
20
22
12 14 16 18
Airflow (CMM)
20
22
Heating
1.3
140
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
8
1.1
Capacity
input
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
8
20
8
10
10 12 14 16 18 20 22
Airflow (CMM)
Fan Performance <30Pa>
120
Correction factor
100
80
60
40
20
8
140
External static pressure (Pa)
(1Pa 0.1mmAq)
Corrected Airflow
10 12 14 16 18 20 22 24
Airflow (CMM)
1.1
Capacity
input
Cooling
1.0
0.9
0.8
12 14 16 18 20 22
Airflow (CMM)
24 26
Heating
Fan Performance <70Pa>
1.3
120
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
PEAD-RP60EA
100
80
60
40
1.2
1.1
1.0
0.9
0.8
12 14 16 18 20 22 24
Airflow (CMM)
20
10 12 14 16 18 20 22 24 26
Airflow (CMM)
56
26
PEAD-RP71EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
Hi
Lo
120
100
80
60
40
20
180
160
140
120
80
60
40
20
12 16 20 24 28 32
12 16 20 24 28 32
Airflow (CMM)
Airflow (CMM)
Corrected Airflow
Heating
1.3
1.2
Correction factor
Correction factor
Capacity
Input
Cooling
1.1
1.0
0.9
0.8
12
16
20
24
28
1.1
1.0
0.9
32
Airflow (CMM)
0.8
12
16
PEAD-RP100EA2
PEAD-RP125EA
External static pressure (Pa)
(1Pa = 0.1mmAq)
200
180
160
140
120
100
Hi
80
Lo
20
200
180
160
140
120
100
1.2
Cooling
1.1
Correction factor
Capacity
Input
1.0
0.9
36
38
40
60
40
Lo
20
Airflow (CMM)
Corrected Air Flow
34
Hi
80
32 34 36 38 40 42 44 46
Airflow (CMM)
Correction factor
32
220
32 34 36 38 40 42 44 46 48
0.8
32
28
Recommended range
220
40
24
Fan performance <70Pa>
Recommended range
60
20
Airflow (CMM)
Fan performance <130Pa>
External static pressure (Pa)
(1Pa = 0.1mmAq)
Hi
Lo
100
42
Airflow (CMM)
44
46
48
Heating
1.1
1.0
0.9
0.8
32
34
36
38
40
42
44
Airflow (CMM)
57
46
48
PEAD-RP60GA
PEAD-RP71GA
58
PEAD-RP100GA
59
NOISE CRITERION CURVES
10
10-1. INDOOR UNIT
PLA-RP35BA
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
LINE
PLA-RP50BA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
250
500
1000
2000
4000
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
BAND CENTER FREQUENCIES, Hz
PLA-RP60BA
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
LINE
PLA-RP71BA2
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
1000
2000
4000
8000
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
LINE
90
80
10
500
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
250
500
1000
2000
4000
10
8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
60
4000
8000
PLA-RP100BA
PLA-RP100BA2
PLA-RP100BA3
NOTCH SPL(dB)
High
40
Medium1
37
Medium2
34
Low
32
PLA-RP125BA
PLA-RP125BA2
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
36
Low
34
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
UNIT
CEILING
1.5m
MICROPHONE
61
4000
8000
PEAD-RP·JA(L)
Ceiling concealed
2m
Aux.duct
1.5m
2m
Measurement location
Noise level at anechoic room (Low-Middle-High) Unit: dB(A)
Model
Exrernal static pressure
35Pa
50Pa
70Pa
100Pa
150Pa
PEAD-RP35JA(L)
23-26-29
23-27-30
24-28-31
26-29-33
29-33-37
PEAD-RP50JA(L)
25-30-34
26-31-35
28-32-36
29-33-37
31-35-39
PEAD-RP60JA(L)
25-28-32
25-29-33
26-30-34
27-31-35
29-34-38
PEAD-RP71JA(L)
25-29-34
26-30-34
27-31-35
28-32-36
30-35-39
PEAD-RP100JA(L)
28-33-38
29-34-38
30-35-39
31-36-40
34-40-43
PEAD-RP125JA(L)
31-36-40
33-36-40
33-37-41
34-39-42
37-41-45
62
PEAD-RP35JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
63
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP50JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
64
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP60JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
65
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP71JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
66
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP100JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
67
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP125JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
2000
4000
8000
4000
8000
68
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP35EA2
PEAD-RP50EA
(External static
pressure 30Pa)
PEAD-RP35EA2
PEAD-RP50EA
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
70
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
8000
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
OCTAVE BAND CENTER FREQUENCIES (Hz)
250
500
1000
2000
4000
8000
(External static
pressure 70Pa)
PEAD-RP60EA
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
125
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 30Pa)
PEAD-RP60EA
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
(External static
pressure 70Pa)
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
OCTAVE BAND CENTER FREQUENCIES (Hz)
69
8000
70
SOUND LEVELS
Low-Middle-High
Model
Sound level dB (A)
PKA-RP35, 50HAL
36 - 40 - 43
PKA-RP60KAL
39 - 42 - 45
PKA-RP100KAL
41 - 45 - 49
PKA-RP35HAL
PKA-RP50HAL
PKA-RP60KAL
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
70.0
70.0
High
Low
60.0
NC-60
55.0
50.0
NC-50
45.0
40.0
NC-40
35.0
30.0
20.0
NC-30
Approximate minimum
audible limit on
continuous noise
NC-20
15.0
10.0
63
125
250
500
1k
2k
Octave band center frequencies (Hz)
4k
60.0
50.0
NC-50
45.0
40.0
NC-40
35.0
30.0
NC-30
25.0
20.0
Approximate minimum
audible limit on
continuous noise
15.0
10.0
8k
NC-60
55.0
63
NC-20
125
250
500
1k
2k
Octave band center frequencies (Hz)
4k
8k
PKA-RP100KAL
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
UNIT
70.0
WALL
High
Low
65.0
Octave band pressure level (dB) 0dB=20μPa
25.0
High
Low
65.0
Octave band pressure level (dB) 0dB=20μPa
65.0
Octave band pressure level (dB) 0dB=20μPa
External static pressure : 0Pa
Power source : 220, 230, 240V, 50Hz
1m
1m
MICROPHONE
60.0
NC-60
55.0
50.0
NC-50
45.0
40.0
NC-40
35.0
30.0
NC-30
25.0
20.0
Approximate minimum
audible limit on
continuous noise
15.0
10.0
63
125
250
NC-20
500
1k
2k
Octave band center frequencies (Hz)
71
4k
8k
PKA-RP35GAL
PKA-RP50GAL
NOTCH SPL(dB)
43
High
Medium1
41
38
Medium2
Low
36
LINE
PKA-RP50FAL2
PKA-RP60FAL
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar)
80
20
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
BAND CENTER FREQUENCIES, Hz
250
500
PKA-RP100FAL
WALL
1m
MICROPHONE
2000
4000
8000
NOTCH SPL(dB)
High
46
Low
41
LINE
90
UNIT
1m
1000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
NOTCH SPL(dB)
High
45
Low
39
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
72
4000
8000
10-2. OUTDOOR UNIT
MODE SPL(dB)
COOLING
52
HEATING
53
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
PUHZ-HRP71VHA
PUHZ-HRP100VHA
PUHZ-HRP100YHA
PUHZ-HRP125YHA
BAND CENTER FREQUENCIES, Hz
UNIT
1.5m
GROUND
73
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
MICROPHONE
1m
MODE SPL(dB)
COOLING
51
HEATING
52
8000
11
OPTIONAL PARTS
11-1. INDOOR UNIT
Part Name
Model Name
Remote sensor
Remote operation adapter
Multiple remote controller adapter
PAC-SE41TS-E
PAC-SF40RM-E (+1)
Remote on/off adapter
Power supply terminal kit
L/N/Earth
L/N
Decoration panel
Decoration panel with Wireless remote controller
Decoration panel with Wired remote controller
Automatic filter elevation panel
i-see sensor corner panel
Wireless signal receiver
Space panel
Air outlet shutter plate
Multi-function casement
Flange for fresh air intake
High-efficiency filter element (PAC-SH53TM-E is needed.)
Wired remote controller kit
(with terminal bed)
Drain pump
Motor
(for high external static pressure)
Drain lift up mechanism
Insulation kit
Filter box
Applicable model
PAC-SA88HA-E (1 pc.) All models
PAC-725AD (10 pcs.)
PAC-SE55RA-E
PEAD-RP•EA(2)
PAC-SG96HR-E
PKA-RP•GAL/FAL(2)
PAC-SG94HR-E
PKA-RP•HAL/KAL
PAC-SH52HR-E
PAC-SG97HR-E
PLA-RP•BA/BA2/BA3
PEAD-RP•GA/JA(L)
PLP-6BA
PLP-6BALM
PLP-6BAMD
PLP-6BAJ
PAC-SA1ME-E
PAR-SA9FA-E
PLA-RP•BA/BA2/BA3
PAC-SH48AS-E
PAC-SH51SP-E
PAC-SH53TM-E
PAC-SH65OF-E
PAC-SH59KF-E
PAR-21MAAT-E
PKA-RP•GAL/FAL(2)
PKA-RP•HAL/KAL
PAC-SH75DM-E
PAC-SH94DM-E
PKA-RP•HAL
PKA-RP•KAL
PKA-RP•FAL(2)
PEAD-RP125EA
PEAD-RP100EA2
PEAD-RP•EA,EA2
PEAD-RP•GA
PAC-SE90DM-E
PAC-SK003MT-F
PAC-KE03DM-F
PAC-SK010DK
PAC-KE92TB-E
PAC-KE93TB-E
PAC-KE94TB-E
(+1) Unable to use with wireless remote contoller (except for PKA-RP·HAL/KAL).
74
PEAD-RP35, 50JA(L)
PEAD-RP60, 71JA(L)
PEAD-RP100, 125JA(L)
11-2. OUTDOOR UNIT
Part Name
Model Name
Applicable model
M-NET adapter
PAC-SF81MA-E
PUHZ-HRP71-125
A-control service tool
PAC-SK52ST
PUHZ-HRP71-125
Drain socket
PAC-SG61DS-E
PUHZ-HRP71-125
Air outlet guide (HRP71/100/125 needs 2 pieces.)
PAC-SG59SG-E
PUHZ-HRP71-125
Air protect guide (HRP71/100/125 needs 2 pieces.)
PAC-SH63AG-E
PUHZ-HRP71-125
Drain pan
PAC-SG64DP-E
PUHZ-HRP71-125
Filter dryer
(:9.52)
PAC-SG82DR-E
PUHZ-HRP71-125
Distribution pipe
Joint pipe (Unit
(Twin)
MSDD-50TR-E
PUHZ-HRP71-125
PAC-SG75RJ-E
PUHZ-HRP71-125
PAC-IF011B-E
PAC-IF012B-E
PAC-SE60RA-E
PUHZ-HRP71-125
PUHZ-HRP71-125
PUHZ-HRP71-125·HA2R1
Extension pipe)
(:15.88
:19.05)
Interface (cased)
Drain hose heater
75
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2010 No.OCS11 REVISED EDITION-B PDF 4
Distributed in Sep. 2008 No.OCS11 REVISED EDITION-A PDF 6
Distributed in Oct. 2007 No.OCS11 PDF 7
Made in Japan
New publication, effective Mar. 2010
Specifications subject to change without notice.