TOTAL ECLIPSE
Quick Start Guide
Chemical Management System
The TOTAL ECLIPSE Controller is an integral part of the TOTAL ECLIPSE Chemical Management System that also includes:
• The Machine Interface – Accepts washer signals and converts them to safe, low-voltage inputs.
• The Pump Module – Provides product transfer to the wash machine. The TOTAL ECLIPSE Controller is compatible with
any Nova Controls’ modular pumpstand. including the Eclipse, Orion or any of the Large Laundry dispensers.
• The Flush Manifold (optional) – Available for water flush chemical transfer applications.
Designed for maximum versatility in OPL or large laundry machines, the TOTAL ECLIPSE Controller’s selectable
Operating Modes allow the system to work with trigger signals from fully-programmable washers or with manually
triggered signals (or cycle time extenders) from non-programmable, fixed-time washers.
The Controller’s easy-to-understand, plain-text LCD display (available in a variety of languages), make operator training
simple. Installation time and cost is significantly reduced with the computer based Formula Editor program, allowing an
off-site technician to create sets of up to 20 industry-specific, efficient and cost-effective formulas that are loaded onto a
controller with a customer-supplied USB flash drive (16 GB or smaller). Summary Reports can be saved to the same USB
flash drive, providing usage and programming information to effectively analyze and manage each machine.
Components Supplied
TOTAL ECLIPSE Controller
Wall Mount Bracket, Kit
Quick Start Guide
(P/N 01-08500-00, Grey/Teal)
(P/N 01-08900-00, Black/Red)
(P/N 13-08462-00, Grey)
(P/N 13-08916-00, Black)
(P/N 20-09130-00)
Additional Support Download: http://www.novacontrols.com
•
Formula Editor Software — For Windows 2000/XP/Vista, Linux & Mac OS 10.4
(Minimum requirements: Java JRE 1.5 or higher [90 MB disc space]; 1024 x 768 screen resolution; 128 MB RAM; 10
MB disc space; USB 2.0 and a USB flash drive [16 GB or smaller] for data transfer to TOTAL ECLIPSE controller)
•
Additional Language Files — Two Types (for Formula Editor Software and for TOTAL ECLIPSE Controller Menus )
•
TOTAL ECLIPSE Reference Manual — Download at www.novacontrols.com/instructions.htm (P/N 20-09120-00)
How to use this Quick Start Guide
Use this Quick Start Guide if you are already familiar with installing and using dispensing systems. Please refer to the
TOTAL ECLIPSE Reference Manual for detailed instructions, including information on the optional Relay, Event,
Occurrence and Group Operating Modes. Refer also to the Installation and Operations manual that is included with your
pumpstand or upgrade kit for additional instructions.
IMPORTANT NOTE:
Quick Start instructions assume that Formula/Setup files will be loaded via a USB flash drive, which may override the following factory default settings:
Standard Operation; Eclipse Flush P.I.; Flush Time–0 sec.; Cycle Time–90 min.; Signal Filter Time–2 sec.; User Prime– Disabled; Bleach Defeat–Off; Units of
Measure = SAE. Default Passwords are Installer = 01234; Manager = 0123. It is recommended that default passwords are changed via the controller’s keypad
(and noted) after installation and system setup are complete. To change formulas, settings or passwords using controller keys, or to add a machine or
company name, see the Guide to Keypad and Menus (p. 7) and Initial Setup on Installer Menus (p. 8).
P/N 20-09130-00
Rev. B 9/10
© Hydro Systems, Inc. 2010
1
TOTAL ECLIPSE Controller Specifications
Size
Weight
Power Rating
Data Input Field Size
Pump Capacity
maximum
Environmental
Temperature
Humidity
Indoor Installation
Altitude
5’25” W x 4.0” H x 2.5” D (13.4 cm W x 10.2 cm H x 6.4 cm D)
0.65 lb. (0.30 kg)
SELV — Power source is pumpstand
15 characters maximum input for custom names
99.99 oz. (2999 ml.) 8 pump (with 3 amount settings per pump) IP Rating – 44 Pollution Category – 2 Installation Category – II
10° to 49° C (50° to 120° F) maximum
95% relative humidity, maximum
Approved for indoor use only. Must not be installed outdoors.
Install at or below 6,500 ft.
! WARNING/ADVERTENCIA:
Disconnect all power to the pumpstand during
installation, service, and/or any time pump
cabinet is opened. The TOTAL ECLIPSE should
be installed by a qualified technician only, in
accordance with all applicable electrical and
plumbing codes.
Desconecte toda la corriente eléctrica al
dosificador durante la instalación, servicio y / o
siempre que se abra el gabinete de la bomba.
El equipo TOTAL ECLIPSE debe ser instalado
sólo por técnicos calificados y de acuerdo con
todas las normas de plomería y eléctricas que
apliquen.
! WARNING/ADVERTENCIA:
Installation
STEP 1 : Install the Machine Interface (MI)
1. Route MI signal wires through 1/2 inch knock-out on washer (within the
wiring area). Secure MI to washer with lock nut (provided).
2. Plug J2 cable into MI. Bundle excess J2 cable outside washer and connect
other end to J2 connector on rear of Controller.
Keep MI and communication cable away from
high voltage wires and relays. NEVER parallel
the cable with high voltage lines.
Mantenga M.I. y los cables de comunicación
separados de los cables de alta tensión y relés.
NUNCA instale el cable paralelo con las líneas
de alta tensión.
3. Connect J1 cable from pump module to J1 connector on Controller. The
maximum distance for a J1 cable is 75 ft. (22.9 m.) unless using a break out box
and hard wiring. Contact Nova /Controls for additional cables, a coupler or
detailed instructions.
4. Secure J1 and J2 cables to controller tie-down posts with tie wraps.
STEP 2 : Connect Signal Wires
Voltage
The Machine Interface will work with any signal voltage between 24 – 240VAC
or 22 – 24VDC. With DC signals, polarity must be observed. Common is negative.
The signals should be positive voltages.
Supply Trigger Wiring
Identify the washer supply signals. In Standard or Group Mode of Operation, use
appropriate terminal connectors to connect the signal wires to the Machine Interface
wires, per table below. (Do not use this table for Event or Occurrence Modes; see
Manual.)
CAUTION/CUIDADO:
Always verify all voltage sources with a meter.
Electrical wiring connections for supply triggers
are to be done inside the junction box.
Siempre verifique la alimentación de corriente
con un voltímetro. Las conexiones eléctricas
a los disparadores de suministro (supply)
deben hacerse dentro del recinto donde se
encuentran los suministros (supply).
Trigger Signal Wiring Notes: • If one or more pump signals are not used, they do not need to be connected.
• If you are triggering more than one pump from a single signal, connect all MI signal wires for those pumps
to that signal.
• Wire nut unused wires. If washer has a single common, wire nut all commons together.
Trigger
Supply
Signal
Signal
Common
Connect to:
Stand ard (US)
Group (EU)
Signal 1
Signal 2
Signal 3
Signal 4
Signal 5
Signal 6
Black Wire
Brown Wire
Red Wire
Orange Wire
Yellow Wire
Blue Wire
White/Black
White/Brown
White/Red
White/Orange
White/Yellow
White/Blue
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
P/N 20-09130-00
Rev. B 9/10
Group 1
Group 1
Group 2
Group 2
Group 3
Group 4
© Hydro Systems, Inc. 2010
2
Installation
STEP 3 : Mount the Controller
1. Mount bracket with velcro-style strips, according the
directions at right. Install wall board screws or nuts and
allen bolts, if needed.
1 Attach Velcro-style Strips and Mount
2 (Optional)
Install Wall Board
Screws or Masonry
Nuts & Allen Bolts
2. Slide controller down onto mounting bracket until it
snaps in place.
3. Install pump module and make all electrical and plumbing
connections for the system, but do not apply power to the
TOTAL ECLIPSE until you are ready to select a language of
operation.
Mounting Bracket
3 With J1 and J2 cables
connected, slide Controller
onto mounting bracket until it snaps into place.
Controller Language Options
Each TOTAL ECLIPSE is shipped with two languages installed: English/Spanish. Additional languages, as they
become available, may be downloaded from the Nova website directly to your USB flash drive (16 GB or smaller). If
changing from a default languages, you will need your language-enabled USB flash drive for the next step.
STEP 4 : Select the Controller Menu Language
1. Apply power to pumpstand & power-up Controller. Two available LANGUAGES
are displayed. (Optional) To replace the non-English language, connect a
USB flash drive with the new language to the controller’s USB port (under
flap on right side of controller).
2.
Move the selection box by using the UP or DOWN ARROWS until
the correct language is contained within the box.
3.
Press Enter to select a language. All menu and application items are
translated into the new language. Text input by the installer (pump and
formula name, etc.) remains in the original language and is not translated.
EXIT
UP
LEFT
ENTER
RIGHT
DOWN
TOTAL ECLIPSE Keypad
(Press & Hold=Auto-Key Repeat)
STEP 5 : Set the Current Date and Time
1. After the language is set, the DATE & TIME menu appears as YYYY-MM-DD
(Year-Month-Day) and HH:MM (Hour:Minute) with the first number of the
year selected as the active digit, indicated by the double-arrow cursor ▲
.
▼
2.
3.
Press the UP or DOWN ARROW to change the active digit. Press
the RIGHT
ARROW to move the cursor to the next digit. Set all digits
until the current Year-Month-Date and Hour:Minute display.
Press ENTER to save the setting and display the Home Screen.
P/N 20-09130-00
Rev. B 9/10
© Hydro Systems, Inc. 2010
3
Installation
STEP 6 : Program the Controller via USB Flash Drive
The easiest way to program the controller is to load previously created set-up files from a USB flash drive onto the
controller. Settings that are not transferred via a USB drive are: Passwords (Installer & Manager); Machine Name;
Company Name; Calibration.
1. Connect the USB flash drive containing set up files that were created in either the Formula Editor or on another
controller.
2.
From the Home Screen, press ENTER to launch the MAIN MENU.
3.
Move the selection box to INSTALLER MENU by pressing and holding the DOWN ARROW.
4.
Press ENTER and input the default Installer Password of 01234, using the UP
number and the RIGHT
ARROW to move the cursor.
5.
Press ENTER to accept the password input. Select DATA TRANSFER from the Installer Menu and follow the
sequence below:
1. Select Installer Menu
2. Input Password
3. Select Data Transfer
NOVA CONTROLS
F01
MAIN MENU
INSTL PASSWORD
INSTALLER MENU
6. Remove USB flash drive. Press EXIT
(required).
01234
EMERGENCY PUMP STOP
LOAD SIZE: 200 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
OK
EXIT
INSTALLER SERVICE
INITIAL SYSTEM SETUP
PROGRAM FORMULAS
DATA TRANSFER
SET UNITS OF MEASURE
4. Display Files on USB
DATA TRANSFER
WRITE REPORTS
READ SETUP
WRITE SETUP
UPDATE FIRMWARE
WRITE ACTIVITY LOG
OK
EXIT
5. Send File to Controller
SETUP FILE
POG Restaurants
BLS Services
Eclipse Hotel
Hospital Settings
International Hotel
AA School District
Default Home Screen
ARROW to increment the
to return to the Installer Menu, in order to prime pumps and calibrate
STEP 7 : Prime Pumps
Press Enter
to start and stop prime. After priming is complete, press the EXIT
1. Select Installer Service
2. Select Service Pumps
3. Select Prime Pump
5. Select Pump to Prime
INSTALLER MENU
INSTALLER SERVICE
SERVICE PUMPS
SET PRIME PUMP
INSTALLER SERVICE
INITIAL SYSTEM SETUP
PROGRAM FORMULAS
DATA TRANSFER
SET UNITS OF MEASURE
SERVICE PUMPS
VIEW LOAD WEIGHT
VIEW AMOUNT PUMPED
CLEAR DATA LOG
PRIME PUMP
PUMP CALIBRATION
NAME PUMPS
ENTER PRODUCT COSTS
DATE TUBE CHANGED
P1
P2
P3
P4
P5
P6
KEY until you reach the Home Screen.
P2
6. Start/Stop Prime
PRIME
START/STOP
EXIT
STEP 8 : Calibrate the Pumps
You must calibrate all pumps to be used; programmed formulas will not run if pumps are not calibrated. Use CALIBRATE
(VOLUME) only for medium (12 or 18 oz. / 355 or 532 ml. per minute) pumps.
2. Select Service Pumps
INSTALLER MENU
INSTALLER SERVICE
INSTALLER SERVICE
INITIAL SYSTEM SETUP
PROGRAM FORMULAS
DATA TRANSFER
SET UNITS OF MEASURE
SERVICE PUMPS
VIEW LOAD WEIGHT
VIEW AMOUNT PUMPED
CLEAR DATA LOG
3. Select Pump Calibration
SERVICE PUMPS
PRIME PUMP
PUMP CALIBRATION
NAME PUMPS
ENTER PRODUCT COSTS
DATE TUBE CHANGED
Use CALIBRATE (TIME) for large displacement pumps or
for a flush installation. Press START
and the timer
counts down 20 seconds. DO NOT stop the pump; run it
for a full 20 seconds, then enter the amount pumped.
P/N 20-09130-00
Rev. B 9/10
4. Select Calibration Method
PUMP CALIBRATION
VIEW CALIBRATION
CALIBRATE (TIME)
CALIBRATE (VOLUME)
5. Select Pump to Calibrate
CALIBRATE (TIME)
P1
P2
P3
P4
P5
P6
© Hydro Systems, Inc. 2010
5. Select Pump to Calibrate
CALIBRATE (VOL.)
P1
P2
P3
P4
P5
P6
P2
STOP PUMP AT 8 OZ
WARNING! PLACE
CONTAINER AT OUTPUT!
START/STOP
EXIT
6. Run Pump Full 20 Seconds
CALIBRATE
P2
6. Collect 8 oz [250 ml]
CALIBRATE
20.0
0.0
WARNING! PLACE
CONTAINER AT OUTPUT!
START/STOP
EXIT
6.1 Input Amount Collected
DISPENSED VOLUME
ENTER AMOUNT PUMPED
00.0 OZ
1. Select Installer Service
OK
EXIT
4
Description of Controls and Operator Menu
Home Screen
The Home Screen appears after the controller language has been selected or whenever the controller is active. If no key
is pressed for 15 minutes, Power Save turns off the display’s backlight. Press any key to turn the backlight on and resume
normal operation. If the controller is powered off, the last formula selected is the active formula on the Home Screen
when power is turned back on. See the following graphic for an explanation of the information and symbols that may
appear on the Home Screen.
HOME SCREEN (IDLE)
Company Name (can be changed during System Setup)
NOVA CONTROLS
F03 TOWELS
Pumps
1 2 _
5 6
_ _ _ _ _ _
Current Formula (or Next Formula to Run)
(Formula number appears if no name is input during System Setup)
NON-ACTIVE Pump – Not programmed or calibrated; not in formula
READY Pump – Calibrated and has amount(s) programmed
ERROR in Pump – Amount(s) programmed; not calibrated
Hot Keys: Formula Quick-Select
Main Menu
HOME SCREEN (RUNNING)
NOVA CONTROLS
F03 RUNNING...
Trigger
Signals
Non-Active
Signal
1 2 _
5 6
_ 2 _ 4 _ _
Signal
Receiving
Signal
Running Formula – Note that formula name is not shown
when running
ACTIVE Pump – Currently running
Complete – Box indicates that pump has finished its programmed run
Hot Keys: Formula Quick-Select
Formula Quick-Select
Formula Quick-Select
To prevent errors in data logging or chemical dispensing: Select the correct
formula before washer operation starts and be sure that all programmed pumps are
triggered during the cycle. (Note: A NO CHEMICAL selection exists after Formula
20 that will allow logging of the load count for special operations).
1.
From the Home Screen, press the EXIT key (also called FORMULA SELECT).
2.
Press the UP or DOWN ARROW to move the selection box to the correct formula. All formulas appear, but only formulas with programmed pumps are selectable.
3.
Press ENTER to start the formula and return to the Home Screen.
4. (Optional) Press ENTER
Main Menu
to reach the load size or bleach defeat settings.
NOVA CONTROLS
F03 TOWELS
1 2 3 4 5 6
_ _ 3 _ _ _
SELECT FORMULA
F01 PADS
F02 CURTAINS
F03 TOWELS
F04 BED LINEN
F05 BLANKETS
F06 TABLE LINEN
Press to
Move
Selection
Box
P/N 20-09130-00
Rev. B 9/10
© Hydro Systems, Inc. 2010
Press to
Select
Formula
5
Description of Controls and Operator Menu
Operator Main Menu
To reach the Main Menu from the Home Screen, press any key (except the EXIT key).
Main Menu
•
•
MAIN MENU
EMERGENCY PUMP STOP
LOAD SIZE
075 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
•
Emergency Pump Stop (stops all pumps and formulas)
Load Size Menu (displays default load weight for formula.
Input actual weight at start of each load).
Selection Box – Move box to select menu item.
Press ENTER
to launch selected menu
•
Print Manager Reports – Input Manager password, then FROM
and TO date range.
•
Installer Programs and Settings – Input Installer password.
•
View Load Count – View the number of loads run for each wash
formula. The View Load Count text appears on the screen when
the selection box is moved down the screen with the DOWN
ARROW key.
To Return to the Home Screen: Press EXIT
or wait 15 seconds without pressing a key.
Limited Warranty
SELLER warrants solely to BUYER the Products will be free from defects in material and workmanship under normal use and service for a period of one year
from the date of completion of manufacture. This limited warranty does not apply to (a) hoses; (b) and products that have a normal life shorter than one year;
or (c) failure in performance or damage caused by chemicals, abrasive materials, corrosion, lightning, improper voltage supply, physical abuse, mishandling
or misapplication. In the event the Products are altered or repaired by BUYER without SELLER’S prior written approval, all warranties will be void. NO OTHER
WARRANTY, ORAL, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE, IS MADE FOR THESE
PRODUCTS, AND ALL OTHER WARRANTIES ARE HEREBY EXPRESSLY EXCLUDED.
SELLER’S sole obligation under this warranty will be, at SELLER’S option, to repair or replace F.O.B. SELLER’S facility in Cincinnati, Ohio any Products found to
be other than as warranted.
Limitation of Liability
SELLER’S WARRANTY OBLIGATIONS AND BUYERS REMEDIES ARE SOLELY AND EXCLUSIVELY AS STATED HEREIN. SELLER SHALL HAVE NO OTHER LIABILITY, DIRECT OR
INDIRECT, OF ANY KIND, INCLUDING LIABILITY FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OR FOR ANY OTHER CLAIMS FOR DAMAGE OR LOSS
RESULTING FROM ANY CAUSE WHATSOEVER, WHETHER BASED ON NEGLIGENCE, STRICT LIABILITY, BREACH OF CONTRACT OR BREACH OF WARRANTY.
P/N 20-09130-00
Rev. B 9/10
© Hydro Systems, Inc. 2010
6
TOTAL ECLIPSE Operator Menus
Home Screen
Formula Select
SELECT FORMULA
123X56788
_ 2 _ _ _ _
Main Menu (Emergency Pump Stop)
MAIN MENU
EMERGENCY PUMP STOP
LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
STOP ALL PUMPS
AND FORMULAS
STOP
EDIT
VALUE
EXIT
EMERGENCY PUMP STOP
LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
Main Menu (Manager Reports)
EMERGENCY PUMP STOP
LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
Main Menu (View Load Count)
EMERGENCY PUMP STOP
LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
or
UP/DOWN
LEFT/RIGHT
Arrows Input Arrows Move
Value (0-9, A-Z)
Cursor
LOAD WEIGHT
MENU
SYMBOLS
220 LB
(SINGLE LOAD)
OK
EXIT
HOME
SCREEN
Select Pump to Prime (if enabled)
P1 PRE-WASH
P2 DETERGENT
P3 LIQUID BLEACH
P4 BLEACH ALTERNATIVE
P5 SOUR/CONDITI
P6 ENZYME LIFT
F02 FO3
FO4 Pumping
(Flush Off)
Flushing
EXIT
Only
Pumping &
Flushing
Trigger Signal Icon
Pump Icon
Installer Menu Access
PRIME
MAIN MENU
P3 LIQUID BLEACH
START/STOP
ENTER
Saves
& Exits
Steady On
More Items
Start / Stop Prime Pump
SET PRIME PUMP
EMERGENCY PUMP STOP LOAD SIZE
180 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
EXIT
INSTL PASSWORD
Start/Stop Flush (if flush enabled)
MANUAL FLUSH
01234
OK
START/STOP
Input Manager Password
MGR PASSWORD
Set Date for Report Header
Set “SAVE AS” File Name & Date
REPORT DATE
REPORT NAME
00-00-00
0123
OK
EXIT
EXIT
Main Menu (User Manual Flush)
ENTER also
Starts/Stops
Action
350 LBS =
WASH23 12-10-08
MAIN MENU
EMERGENCY PUMP STOP LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
P/N 20-09130-00
Rev. B 9/10
EMERGENCY STOP
UP/DOWN
ENTER Key
Arrows Move
Launches
Selection Box Menu Item
EXIT
OK
Main Menu (User Prime Pump)
VIEW LOAD COUNT
Emergency Pump Stop
EMERGENCY PUMP STOP LOAD SIZE
275 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENU
VIEW LOAD COUNT
MAIN MENU
SELECTION
BOX
MAIN MENU
MAIN MENU
=
Input Actual Load Weight
Main Menu (Load Size)
MAIN MENU
Guide to Keypad & Menus
Select
& Return
to Home
Screen
F02 CURTAINS
F01 PADS
F02 CURTAINS
F03 TOWELS
F04 BED LINEN
F05 BLANKETS
F06 TABLE LINEN
NOVA CONTROLS
EXIT
INSERT USB DRIVE
OK
EXIT
View Load Count
TOTAL LOAD COUNT
F01 PADS
F02 CURTAINS
F03 TOWELS
F04 BED LINEN
F05 BLANKETS
F06 TABLE LINEN
0
0
0
0
0
0
Display returns to Main Menu after data transfer is complete.
© Hydro Systems, Inc. 2010
7
_ _
SYSTEM SETUP
0
0
0
0
0
0
P1
P1A
P1B
P1C
SAE / IMPERIAL (LB/OZ)
METRIC (KG/ML)
UNITS-MEASURE
OK
2009-02-08
5. Set Units of Measure
EXIT
REPORTEXIT
DATE
TO: OK
2009-01-08
FROM:
HI CAP WASH
INSERT USB DRIVE
OK
EXIT
SETUP FILE
POG Restaurants
BLS Services
Eclipse Hotel
Hospital Settings
International Hotel
AA School District
EXIT
OK
OK
EXIT
EXIT
P2 DETERGENT
P3 LIQUID BLEACH
P4 BLEACH ALT
P5 SOUR/CONDITI
P6 ENZYME LIFT
P7
EXIT
HH:MM
17:06
OK
NEW NAME
EXIT
3.4 Edit Formula Name
NAME F01
OK
20 0 9 - 07 - 28
YYYY-MM-DD
3.3 Set Count Pump
F01 COUNT PUMP
OK
EXIT
2.13 Set Date & Time
DATE & TIME
OK
NOVA CONTROLS
2.6 Edit Company Name
COMPANY NAME
50
2.12 Adjust Screen Contrast
LCD CONTRAST
OK
HOUSEKEEPING 01
2.5 Edit Machine Name
MACHINE NAME
EXIT
HOTEL 17
SETUP NAME
Overwrites file of same
name on USB flash drive.
Does not transfer passwords,
machine name, company
name or calibrations.
INSERT USB DRIVE
OK
EXIT
EXIT
DO NOT attempt firmware
update unless you have your
PC Update Program and
proper computer cable.
WARNING!
OK
STOP!!! DO NOT
PROCEED WITHOUT
PC UPDATE PROGRAM!
UPDATE FIRMWARE
4.3 Write Setup - Name File being sent
(from Controller to USB flash drive) 4.4 Update Firmware
EXIT
0 0 0 LB
3.2 Default Load Weight
F01 LOAD SIZE
OK
DISABLE
ENABLE
LIMITED 30 SEC
EXIT
2.11 User Prime Enable
SET USER PRIME
OK
Overwrites ALL settings &
formulas, except passwords,
machine name, company
name & calibrations.
REPORT NAME
ZERO DATA LOG
WARNING! ALL LOGS
(LOADS & VOLUMES)
WILL BE CLEARED!
HOTEL ECLIPSE - 67
4.2 Read Setup - Select File to
load from USB to Controller
TO TEST
0 0 0 SEC
00.00 OZ
00.00 OZ
00.00 OZ
F01 P1
DELAY
AMOUNT
AMOUNT
AMOUNT
REPORT DATE
WRITE REPORTS
READ SETUP
WRITE SETUP
UPDATE FIRMWARE
WRITE ACTIVITY LOG
EXIT
3.1.3 Pump Settings
(0 = OFF)
OK
0
2.10 Auto-Formula Select
AFS TRIGGER
STANDARD
RELAY
EVENT
GROUP
OCCURRENCE
0.0
0.0
0.0
0.0
0.0
0.0
1.4 Clear Data Log
2.4 Edit Account Name
ACCOUNT NAME
P1 PRE-WASH
P2 DETERGENT
P3 LIQUID BLEAC
P4 BLEACH ALT
P5 SOUR/CONDITI
P6 ENZYME LIFT
PUMPED (GAL)
1.3 View Amount Pumped
INSTALLER SERVICE
INITIAL SYSTEM SETUP
PROGRAM FORMULAS
DATA TRANSFER
SET UNITS OF MEASURE
INSTALLER MENU
Installer Top Level Menu
2.3 Set-up Operating Mode
OPERATION MODE
DATA TRANSFER
P1 PRE-WASH
P2 DETERGENT
P3 LIQUID BLEACH
P4 BLEACH ALT
P5 SOUR/CONDITI
P6 ENZYME LIFT
3.1.2 Add Pumps to Formula
F01 PUMPS
2 SECONDS
10 SECONDS
20 SECONDS
30 SECONDS
60 SECONDS
90 SECONDS
EXIT
0123
2.9 Set Trigger Signal Filter
TRIGGER FILTER
OK
2.2 Edit Manager Password
MGR PASSWORD
F01 PADS
F02 CURTAINS
F03 TOWELS
F04 BED LINEN
F05 BLANKETS
F06 TABLE LINEN
TOTAL WEIGHT
4.1.2 Set “SAVE AS” File Name
PUMP SETTINGS
SET DEFAULT WEIGHT
SET COUNT PUMP
EDIT NAME
CLEAR FORMULA
EXIT
3.1 Set Formula
F01
OK
(0 = OFF)
9 0 MINUTES
EXIT
1.2 View Load Weight
OK
4.1 Set Report “FROM / TO” Date
EXIT
01234
2.8 Set Cycle Time Limit
CYCLE TIME LIMIT
OK
2.1 Edit Installer Password
INST PASSWORD
01234
INSTL PASSWORD
Input Installer Password
4. Upload / Download Data
F01
F02 CURTAINS
F03 TOWELS
F04 BED LINEN
F05 BLANKETS
F06 TABLE LINEN
PROGRAM FORMULAS
3. Formula Programming
SET PUMP INTERFACE
SET CYCLE TIME
SIGNAL FILTER TIME
SET AFS TRIGGER
SET USER PRIME
SET LCD CONTRAST
SET DATE AND TIME
CLEAR SETTINGS
VIEW SOFTWARE ID
EDIT INST PASSWORD
EDIT MGR PASSWORD
OPERATION MODE
EDIT ACCOUNT NAME
EDIT MACHINE NAME
EDIT COMPANY NAME
2. Initial System Setup
PRIME PUMP
PUMP CALIBRATION
NAME PUMPS
ENTER PRODUCT COSTS
DATE TUBE CHANGED
SERVICE PUMPS
SERVICE PUMPS
VIEW LOAD COUNT
VIEW LOAD WEIGHT
VIEW AMOUNT PUMPED
CLEAR DATA LOG
1.1 Pump Maintenance /Service
INSTALLER SERVICE
EMERGENCY PUMP STOP LOAD SIZE:
175 LB
USER PRIME PUMPS
USER MANUAL FLUSH
MANAGER REPORTS
INSTALLER MENUS
MAIN MENU
Main Menu
1. Service / Routine Maintenance
_ 2 _ 4 _ _
1 2 3
NOVA CONTROLS
F03 TOWELS
Home Screen
(factory default settings shown in selection boxes)
Top Level Installer Menus
TOTAL ECLIPSE
© Hydro Systems, Inc. 2010
Up / Down Arrow
- Moves Selection Box
- Changes digit value
EXIT
EXIT
ABBA
REPORT NAME
4.5 Diagnostic Activity Log
OK
WARNING! FORMULA
WILL BE CLEARED TO
FACTORY DEFAULT!
3.5 Clear Formula
CLEAR F01
OK
WARNING! ALL SETUPS
WILL BE CLEARED TO
FACTORY DEFAULTS!
2.14 Clear Controller Settings
CLEAR SETTINGS
NON-FLUSH
ECLIPSE FLUSH P. I.
ORION I I FLUSH P. I.
8-PUMP FLUSH P. I.
2.7 Set Pump Interface
(and Flush Time, if needed)
PUMP INTERFACE
Enter / Save Key
- Launches selected menu
- Saves new input & exits
Right / Left Arrow
During input, moves the
cursor ( ) to the next digit
INSERT USB DRIVE
OK
EXIT
P/N 20-09130-00
Rev. B 9/10
8