- No category
advertisement
User’s
Manual
AXW
Magnetic Flowmeter
Remote Flowtube
IM 01E25D11-01EN
IM 01E25D11-01EN
2nd Edition
AXW
Magnetic Flowmeter
Remote Flowtube
IM 01E25D11-01EN 2nd Edition
Contents
Combination Remote Converters ...................................................................1-3
2. HANDLING PRECAUTIONS ..................................................................... 2-1
5.1 Changing Direction of Electrical Connection ................................................5-1
Excitation Coil and Insulation Resistance Check ........................................5-2
Disagreement Between Indication and Actual Flow ..........................5-5
STANDARD SPECIFICATIONS ........................................................................6-1
STANDARD PERFORMANCE ..........................................................................6-1
NORMAL OPERATING CONDITIONS ..............................................................6-2
i
2nd Edition: Sep. 2013 (KP)
All Rights Reserved, Copyright © 2012, Yokogawa Electric Corporation
IM 01E25D11-01EN
OPTIONAL SPECIFICATIONS .........................................................................6-5
OPTIONAL SPECIFICATIONS (continued) .....................................................6-6
ii
IM 01E25D11-01EN
1. INTRODUCTION
This instrument has been adjusted at the factory before shipment.
To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
NOTE
The ADMAG AXW remote flowtube is used in combination with the AXFA11 remote converter.
This manual describes the hardware configuration of the ADMAG AXW remote flowtube. For details of the AXFA11 remote converter, see IM 01E20C01-01E instruction manual.
When setting the parameter “C30” in the remote converter, select “ADMAG AXF” for ADMAG
AXW remote flowtube.
n
Regarding This User’s Manual
• This manual should be provided to the end user.
• Before use, read this manual thoroughly to comprehend its contents.
• The contents of this manual may be changed without prior notice.
• All rights are reserved. No part of this manual may be reproduced in any form without
Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this material, including, but not limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual.
However, if any errors or omissions are found, please inform Yokogawa.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• Please note that this user’s manual may not be revised for any specification changes, construction changes or operating part changes that are not considered to affect function or performance.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
<1. INTRODUCTION>
WARNING
A WARNING sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in injury or death of personnel.
IMPORTANT
An IMPORTANT sign denotes that attention is required to avoid damage to the instrument or system failure.
NOTE
A NOTE sign denotes information necessary for essential understanding of operation and features.
1-1
n
Safety and Modification Precautions
• The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. Yokogawa assumes no liability for the customer’s failure to comply with these requirements. If this instrument is used in a manner not specified in this manual, the protection provided by this instrument may be impaired.
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
• The following safety symbol marks are used in this user’s manual and instrument.
CAUTION
A CAUTION sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the product.
IM 01E25D11-01EN
Protective grounding terminal
Functional grounding terminal
(This terminal should not be used as a protective grounding terminal.)
Alternating current
Direct current
1.1 Using the Magnetic
Flowmeter Safely
(1) Installation
WARNING
• Installation of the magnetic flowmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation.
• The magnetic flowmeter must be installed within the specification conditions.
• The magnetic flowmeter is a heavy instrument.
Be careful that no damage is caused to personnel through accidentally dropping it, or by exerting excessive force on the magnetic flowmeter. When moving the magnetic flowmeter, always use a trolley, forklift, or crane and have at least two people carry it.
• When the magnetic flowmeter is processing hot fluids, the instrument itself may become extremely hot. Take sufficient care not to get burnt.
• Where the fluid being processed is a toxic substance, avoid contact with the fluid and avoid inhaling any residual gas, even after the instrument has been taken off the piping line for maintenance and so forth.
• Do not apply excessive weight, for example, a person stepping on the magnetic flowmeter.
• All procedures relating to installation must comply with the electrical code of the country where it is used.
<1. INTRODUCTION>
1-2
(2) Wiring
WARNING
• The wiring of the magnetic flowmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to wiring.
• When connecting the wiring, check that the supply voltage to the converter is within the range of the voltage specified for this instrument before connecting the power cable.
In addition, check that no voltage is applied to the power cable before connecting the wiring.
• The protective grounding must be connected securely at the terminal with the mark to avoid danger to personnel.
(3) Operation
WARNING
• When opening the cover, wait for more than 10 minutes after turning off the power. Only expert engineer or skilled personnel are permitted to open the cover.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• Be sure to set parameters as “Protect” on the write protect function after finish of parameter setting work.
Under extremely rare case, the infra-red switches may respond unexpectedly in such conditions as sticking ball of water or extraneous substances on the surface of display panel glass according to the principle of infra-red switch operation.
Its probability rises in such cases as sticking rain water by storm or other similar situation and washing up work near flowmeter installation place.
Either to illuminate or stop illuminating the infrared switches by the flashlight may cause the mis-reaction.
Refer to the manual for converter on how to use the write protect function in detail.
IM 01E25D11-01EN
(4) Maintenance
WARNING
• Maintenance of the magnetic flowmeter should be performed by the trained personnel having knowledge of safety standard. No operator shall be permitted to perform any operations relating to maintenance.
• When opening the cover, wait for more than 10 minutes after turning off the power.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• Always conform to maintenance procedures outlined in this manual. If necessary, contact
Yokogawa.
• Care should be taken to prevent the build up of dirt, dust or other substances on the display panel glass or data plate. If these surfaces do get dirty, wipe them clean with a soft dry cloth.
1.2 Warranty
• The terms of this instrument that are guaranteed are described in the quotation.
We will make any repairs that may become necessary during the guaranteed term free of charge.
• Please contact our sales office if this instrument requires repair.
• If the instrument is faulty, contact us with concrete details about the problem and the length of time it has been faulty, and state the model and serial number. We would appreciate the inclusion of drawings or additional information.
• The results of our examination will determine whether the meter will be repaired free of charge or on an at-cost basis.
<1. INTRODUCTION>
1-3
n
The guarantee will not apply in the following cases:
• Damage due to negligence or insufficient maintenance on the part of the customer.
• Problems or damage resulting from handling, operation or storage that violates the intended use and specifications.
• Problems that result from using or performing maintenance on the instrument in a location that does not comply with the installation location specified by Yokogawa.
• Problems or damage resulting from repairs or modifications not performed by Yokogawa or someone authorized by Yokogawa.
• Problems or damage resulting from inappropriate reinstallation after delivery.
• Problems or damage resulting from disasters such as fires, earthquakes, storms, floods, or lightning strikes and external causes.
n
Trademarks:
ADMAG and AXW are registered trademarks of
Yokogawa Electric Corporation.
Company names and product names used in this material are registered trademarks or trademarks of their respective owners.
1.3 Combination Remote
Converters
IMPORTANT
• The AXW remote flowtube (size 500 (20 in.) to 1800 mm (72 in.)) should be used in combination with AXFA11 remote converter.
Contact Yokogawa before using it in combination with converters other than
AXFA11.
IM 01E25D11-01EN
Blank Page
<2. HANDLING PRECAUTIONS>
2-1
2. HANDLING PRECAUTIONS
This instrument has been inspected carefully at the factory before shipment. When the instrument is delivered, visually check that no damage has occurred during transportation.
Read this section carefully as it contains important information on handling this instrument. Refer to the relevant sections for information not contained in this section. If you have any problems or questions, please contact Yokogawa sales office.
2.1 Checking Model and
Specifications
The model code and specifications are found on the data plate located on the outside of the case.
Check that the model code and specifications match what you have ordered.
Be sure you have your model number and serial number available when contacting Yokogawa.
KCC-
REM-
YHQ-
EEN
165
2.2 Storage Precautions
If the instrument is to be stored for a long period of time after delivery, observe the following points.
The instrument should be stored in its original packing condition in the storage location.
Select a storage location that fulfils the following conditions:
• A place where it will not be exposed to rain or water
• A place subject to minimal vibrations or shocks
• Temperature and humidity levels should be as follows:
Temperature: -10 to 70°C
Humidity: 5 to 80% RH (no condensation)
The preferred ambient temperature and humidity levels are 25°C and approximately 65% RH.
If the magnetic flowmeter is transferred to the installation site and stored without being installed, its performance may be impaired due to the infiltration of rainwater and so forth. Be sure to install and wire the magnetic flowmeter as soon as possible after transferring it to the installation location.
Figure 2.1.1 Data Plate
F0201.ai
2.3 Installation Location
Precautions
Select the installation location with consideration to the following items to ensure long-term stable operation of the instrument.
n
Ambient Temperature:
Avoid installing the instrument in locations with constantly fluctuating temperatures. If the location is subject to radiant heat from the plant, provide heat insulation or improve ventilation.
n
Atmospheric Condition:
Avoid installing the instrument in a corrosive atmosphere. In situations where this is unavoidable, consider ways to improve ventilation and to prevent rainwater from entering and being retained in the conduit pipes.
n
Vibrations or Shocks:
Avoid installing the instrument in a place subject to shocks or vibrations.
IM 01E25D11-01EN
Blank Page
3. INSTALLATION
WARNING
Installation of the magnetic flowmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation.
3.1 Piping Design Precautions
IMPORTANT
Design piping correctly, referring to the following to prevent damage to flowtubes and to assure accurate measuring.
(1) Location
IMPORTANT
Install the flowmeter in a location where it is not exposed to direct sunlight. The minimum ambient temperature is limited by the minimum fluid temperature of the flowtube (the lining). For more information, refer to Chapter 6 “OUTLINE”.
The flowmeter may be used in an ambient humidity where the relative humidity ranges from
0 to 100%. However, avoid long-term continuous operation at relative humidity above 95%.
(2) Noise Avoidance
IMPORTANT
The flowmeter should be installed away from electrical motors, transformers, and other power sources in order to avoid interference with measurement.
(3) Required Lengths of Straight Runss
To maintain accurate measurement, see JIS B7554
“Electro Magnetic Flowmeters” which explains the requirements for upstream piping conditions of magnetic flowmeters.
Based on JIS B7554 “Electro Magnetic Flowmeters” and our piping condition test data, we recommend the piping conditions as shown in the following
<3. INSTALLATION>
3-1
figures.
When installing two or more magnetic flowmeters on a single pipe, provide a run of at least 10D between them.
Gate valve fully open
Reducer pipe
D: Flowtube Size
Expander pipe
5D or more
Tee
Various valves
5D or more 0 is allowable.
5D or more 0 is allowable.
10D or more
2D
F0301.ai
Figure 3.1.1 Required Lengths of Straight Runs
*1: Do not install anything in the vicinity that may interfere with the magnetic field, induced signal voltages, or flow velocity distributions of the flowmeter.
*2: A straight run may not be required on the downstream side of the flowmeter. However, if a downstream valve or other fitting causes irregularity or deviation in flows, provide a straight run of 2D to 3D on the downstream side.
*3: The valves shall be mounted on the downstream side so that deviated flows do not occur in the flowtube and to avoid startup from an empty condition.
(4) Maintaining Stable Fluid Conductivity
IMPORTANT
Do not install the flowmeter where fluid conductivity tends to become uneven. If chemicals are fed near the upstream side of a magnetic flowmeter, they may affect the flow rate’s indications. To avoid this situation, it is recommended that the chemical feed ports be located on the downstream side of the flowmeter.
If it is unavoidable that chemicals must be fed on the upstream side, provide a sufficient length of straight run (approximately 50D) to ensure the proper mixture of fluids.
(Incorrect)
Upstream side
(Correct)
Downstream side
F0302.ai
Figure 3.1.2 Chemical Injection
IM 01E25D11-01EN
(5) Precautions for Use of Liquid Sealing
Compounds
IMPORTANT
Care must be taken in using liquid sealing compounds on the piping, as it may have a negative influence on the flow indications by flowing out and covering the surfaces of an electrode or grounding ring. In particular, care must be taken if a liquid sealing compound is used in the case of vertical piping.
(6) Service Area
Select locations where there is adequate space to service installing, wiring, overhauling, etc
(7) Bypass Line
It is recommended to install a bypass line to facilitate maintenance and zero adjustment.
Bypass valve
Block valve
Block valve
F0303.ai
Figure 3.1.3 Bypass Line
(8) Supporting the Flowmeter
CAUTION
Do not secure the flowmeter separately to prevent the vibrations, shocks, and expansion and contraction forces of the piping from affecting it. Fix the pipeline or its flanges first, then let them support the flowmeter.
For vertical, mounting, make sure that the weight of piping does not weigh on the flowmeter.
To release the load from tightening the flowmeter to the pipeline, set a expansive pipe in the downstream side.
<3. INSTALLATION>
(9) Mounting Positions
• Pipes must be fully filled with liquids.
IMPORTANT
It is essential that pipes remain fully filled at all times, otherwise flow rate indications may be affected and measurement errors may be caused.
3-2
Piping shall be designed so as to maintain the interior of the flowtube filled with fluids.
Vertical mounting is effective in such cases as when fluids tend to separate or solid matter may be precipitated. When employing vertical mounting, direct the fluids from the bottom to the top to ensure that the pipes remain fully filled.
(Correct) (Incorrect)
(Correct) (Incorrect) h h>0 h h>0
F0304.ai
Figure 3.1.4 Mounting Positions
• Avoid air bubbles.
IMPORTANT
If air bubbles enter a measurement pipe, flow rate indications may be affected and measurement errors may be caused.
In cases where fluids contain air bubbles, piping must be designed to prevent them from accumulating in the measurement pipe of a flowtube.
If a valve exists near the flowmeter, try to mount the flowmeter on the valve’s upstream side in order to prevent a possible reduction of pressure inside the pipe, thereby avoiding the possibility of air bubbles.
(Correct) (Incorrect)
(Correct)
(Incorrect)
Valve
F0305.ai
Figure 3.1.5 Avoiding Air Bubbles
IM 01E25D11-01EN
• Mounting orientation
IMPORTANT
If electrodes are perpendicular to the ground, air bubbles near the top or precipitates at the bottom may cause measurement errors. Ensure that the terminal box of a remote flowtube is mounted above the piping to prevent water from entering them.
Correct
Incorrect
Air bubble
Incorrect
Electrode
Electrode Precipitate
Water can seep into the terminal box.
F0306.ai
Figure 3.1.6 Mounting Orientation
3.2 Handling Precautions
WARNING
The magnetic flowmeter is a heavy instrument.
Be careful that no damage is caused to personnel through accidentally dropping it, or by exerting excessive force on the magnetic flowmeter. When moving the magnetic flowmeter, always use a trolley, forklift, or crane and have at least two people carry it.
3.2.1 General Precautions
(1) Precaution during Transportation
The magnetic flowmeter is packed tightly. When it is unpacked, pay attention to prevent damaging the flowmeter. To prevent accidents while it is being transported to the installing location, transport it to the site in its original packing.
CAUTION
When lifting the flowtube, use the lifting rings
(eye bolts or eye plates) as in Figure 3.2.1.
Never lift it using a bar passed through the flowtube as this damages the liner severely.
<3. INSTALLATION>
90 degrees or less
Eye bolt
3-3
90 degrees or less
Eye plate
F0307.ai
Figure 3.2.1 Lifting Flowtube
(2) Avoiding Shocks from Impact
CAUTION
Care should be taken not to drop the flowmeter or expose it to excessive shock. In particular, be careful not to subject the flange surface to shock.
This may lead to liner damage which will result in inaccurate readings.
(3) Flange Protection Covers
IMPORTANT
Keep the protective covering (i.e. the corrugated cardboard or other cushioning material) in place over the flange except when mounting the flowmeter to the pipe.
(4) Terminal Box Cover
IMPORTANT
As it is possible that the insulation will deteriorate, do not remove the wrapping of the terminal box nor open the terminal box cover until it is time to wire it.
(5) Long-term Non-use
IMPORTANT
It is not desirable to leave the flowmeter unused for a long term after installation. If this situation is unavoidable, take care of the flowmeter by observing the following.
IM 01E25D11-01EN
• Confirmation of sealing conditions for the flowmeter
Confirm that the terminal box screw and wiring ports are well sealed. Equip the conduit piping with drain plugs or waterproof glands to prevent moisture or water from penetrating into the flowmeter through the conduit.
• Regular inspections
Inspect the sealing conditions as mentioned above, and the inside of the terminal box at least once a year. Also, due to rain, etc. when it is suspected that water may have penetrated into the inside flowmeter perform supplementary inspections.
3.2.2 Flowmeter Piping
CAUTION
Misaligned or slanted piping can lead to leakage and damage to the flanges.
(1) Correct any misaligned or slanted piping, and any gaps that may exist between mounting flanges before installing the flowmeter (refer to
Figure 3.2.2).
Slanted
Misaligned
F0308.ai
Figure 3.2.2 Slanted and Misaligned Flowmeter
Piping
(2) Inside a newly installed pipeline, there may be some foreign substances such as residue from welding or wood chips. Remove them by flushing the piping before mounting the flowmeter. This prevents the lining from being damaged, as well as the occurrence of erroneous measured signals resulting from foreign substances passing through the flowtube during measurement.
<3. INSTALLATION>
3.3 Mounting Procedures
3-4
CAUTION
When attaching optional grounding rings to the flowtube with lining material natural hard rubber or fluorocarbon PTFE, gaskets must be placed between each grounding ring and the flowtube. Fluid leakage will happen without these gaskets. These gaskets are to be supplied by customer. Do not forget those gaskets also when ordering and attaching the grounding rings later additionally.
NOTE
The tightening torque value varies depending on the type of lining and gasket as shown in the tables in this section.
IMPORTANT
Use bolts and nuts in compliance with the flange ratings. When choosing the gaskets, be sure to choose sheet gaskets designed to fit for flange standard.
(1) Mounting Direction
Mount the flowmeter so that the flow direction of the fluid to be measured is in line with the direction of the arrow mark on the flowmeter. It may be especially difficult to move large size flowtubes after bringing them into the pit. Check directions before bringing.
IMPORTANT
If it is impossible to match the direction of the arrow mark, the direction of the electrical connection can be changed. Refer to Section 5.1 to do this properly.
In case the fluid being measured flows against the arrow direction, refer to the parameter
J20:
Flow Direction in the user’s manual of the
AXFA11 Magnetic Flowmeter Remote Converter
(IM 01E20C01-01E).
IM 01E25D11-01EN
(2) Carrying Flowtube
90 degrees or less
Eye bolt
90 degrees or less
Eye plate
F0309.ai
Figure 3.3.1 Carrying Flowtube
CAUTION
• When carrying the flowtube, use the lifting rings (eye bolts or eye plates).
• To assure safety, keep lifting angle less than
90 degrees as shown in Figure 3.3.1
(3) Positioning Flowtube
Bring in the flowtube, place it and use a jack to adjust its position.
IMPORTANT
Apply the jack to the flanges of the flowtube.
In addition, adjust any misalignment when the flowtube is brought in, as the jack can adjust vertical position, but not horizontal one.
(4) Applying Gasket and optional Grounding
Rings
Gasket:
Necessary gaskets for piping connection are as below depending on the choice of grounding rings.
Use sheet gaskets designed to fit for flange standard. The GF type-1 gaskets by JIS G
3443-2 should be used for the JIS F12 flange models in sizes 1100 mm (44 in.) and above. In this case, the gasket groove is required on the customer pipe flanges.
The thickness of gasket should be 2mm
(0.08in.) to 5mm (0.2in.) for sizes up to 1000 mm (40 in.), and 5 mm (0.2 in.) or more for larger sizes. The type of gasket should be a kind of soft rubber, or its equivalent in hardness.
<3. INSTALLATION>
1. Standard (no grounding rings)
3-5
Customer pipe
Customer pipe
A A
Gaskets A supplied by customer
F0310.ai
Figure 3.3.2 Installation without Grounding
Rings
When using the GF type-1 gaskets, the gasket groove is required as mentioned above.
2. With optional grounding rings (code GR1)
Optional grounding rings
Customer pipe
Customer pipe
A B
B A
Gaskets A and B supplied by customer
F0311.ai
Figure 3.3.3 Installation with Grounding Rings
GR1
It is recommended to use the same gasket for A and B. Both gaskets A and B are to be supplied by customer.
When polyurethane or natural soft rubber lining, the gaskets B are not necessary.
3. With optional grounding rings (code GR2)
Customer pipe
Optional grounding rings with integrated gaskets B included
B
B
Customer pipe
A A
Gaskets A supplied by customer
F0312.ai
Figure 3.3.4 Installation with Grounding Rings
GR2
This is available for the models with process connection JIS F12 (JIS 75M) in sizes 1100 mm (44 in.) and above. Only gaskets A are to be supplied by customer.
The grounding rings are installed and locked onto the flowtube with gaskets B when shipped from factory.
Mounting Procedure (no Grounding Rings):
Connect the flowtube’s flange and the customer’s pipe which contact process fluid by some wire supplied by customer.
IM 01E25D11-01EN
Mounting Procedure (with optional
Grounding Rings GR1 for sizes up to
1000 mm (40 in.)):
1. Handles of the grounding ring have some holes which correspond to outer diameter of each flange type. There are printings near each hole. The printings show types of flange. See the table below.
Printing
ASME
AWWA
PN10
PN16
10K
AS
F12
Process
Connection Code Flange Standard
-CA1
ASME B16.5
Class 150, ASME
-CB1
-CE1
B16.47 Class 150
AWWA C207
Class D
EN1092-1 PN10
-CE2
-CJ1
EN1092-1 PN16
JIS B2220 10K
-CG1 JIS F12 (JIS 75M)
2. Confirm the centering pin is fixed to the hole corresponding to flange or fix the centering pin to the correct hole.
3. Hang the grounding rings with their flange type printings outer side of the flowtube. Set the angle of both handles symmetrically to be 45 degree from top. If there are any bolt-holes under the handles, turn the grounding rings clockwise in order to locate handles between bolt-holes.
Center the grounding ring to the center of the flowtube.
4. Connect the wire from the grounding ring to the screw of the flowtube’s flange and fix the wire by the nut. This procedure (item 1 to 4) must be done for the both sides of the flowtube.
<3. INSTALLATION>
3-6
5. Install the flowtube into the customer’s pipe with the gaskets A.
Centering Pin
Screw & Nut : Connect the wire from the grounding ring or the customer’s pipe
Centering Pin
Handle
Printing of
Flange Type
Flowtube
Clockwise
F12
10K
Hole
Handle
Gasket B
Grounding Ring
Printed
Surface
F0313.ai
Note : Gasket A and B are also placed concentrically with the flowtube.
Figure 3.3.5 Mounting Procedure with Grounding
Rings GR1 for sizes up to 1000 mm
(40 in.)
Mounting Procedure (with optional
Grounding Rings GR1 for sizes 1100mm (44 in.)) and above :
1. The grounding ring is temporarily fixed onto the flowtube by four bolts. Hang the grounding ring up using a crane or a hoist so that it would not fall down from the flowtube while setting the gasket B.
2. Unfasten the bolts and remove the grounding ring off from the flowtube.
3. Place the gasket B to the flowtube. Cut out holes on the gasket B if necessary, so that the bolts can go through. Fix the grounding ring to the flowtube by the four bolts again.
4. Connect the wire from the grounding ring to the screw at the flowtube flange and fix the wire by the nut. This procedure (item 1 to 4) must be done for the both sides of the flowtube.
IM 01E25D11-01EN
5. Install the flowtube into the customer’s pipe with the gaskets A.
Screw & Nut : Connect the wire from the grounding ring or the customer’s pipe.
Hang the grounding ring up with this point.
<3. INSTALLATION>
3-7
Unfasten the bolts and remove the grounding rings.
Cut out some holes on the gasket B when necessary.
Wire
Flowtube
Grounding Ring
F0314.ai
Note : Gasket A and B should be placed concentrically with the flowtube.
Figure 3.3.6 Mounting Procedure with Grounding
Rings GR1 for sizes 1100 mm (44 in.) and above
Mounting Procedure (with optional
Grounding Rings GR2):
The grounding rings are installed and locked onto the flowtube with gaskets B when shipped from factory. Install the flowtube into the customer’s pipe with gaskets A supplied by customer.
(5) Tightening Nuts
Pass the bolts from pipe line side, not flowtube side, and tighten the bolts according to the torque values for the metal piping in Table 3.3.1 or 3.3.2
CAUTION
• Be sure to tighten the nuts according to the prescribed toeque values. Tighten them diagonally with the same torque values, step by up to the prescribed torque value.
IM 01E25D11-01EN
<3. INSTALLATION>
3-8
Table 3.3.1 Tightening Torque Values for Metal Piping (N-m)
Lining type
Gasket type
Size connection mm (inch)
Process
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Unit: N-m
PTFE / Natural hard rubber / Natural soft rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
EN1092-1 PN10
JIS B2220 10K
EN 1092-1 PN16
AWWA C207
Class D
AS2129 Table D, E
AS4087 PN16
99 to 166
144 to 240
85 to 140
108 to 175
143 to 238
218 to 363
151 to 233
239 to 331
168 to 281
259 to 432
274 to 457
274 to 457
176 to 266
212 to 302
206 to 338
277 to 422
180 to 300
236 to 393
224 to 373
307 to 512
176 to 293
246 to 410
258 to 430
286 to 477
240 to 333
400 to 612
399 to 604
422 to 587
Lining type
Gasket type connection
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Unit: N-m
Polyurethane rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
71 to 118
EN1092-1 PN10
JIS B2220 10K
60 to 99
EN 1092-1
PN16
74 to 123
AWWA C207
Class D
AS2129 Table
D, E
AS4087 PN16
76 to 123
JIS F12
(JIS 75M)
131 to 218
97 to 162
125 to 208
82 to 126
135 to 202
101 to 168
146 to 244 120 to 200
118 to 171
167 to 242
124 to 206
202 to 337
176 to 294
170 to 283
175 to 291
160 to 229
151 to 251
206 to 314
190 to 316
178 to 296
220 to 367
169 to 281
161 to 268
165 to 275
218 to 348
200 to 317
253 to 370
197 to 328
221 to 369
218 to 363
Unit: N-m
Natural hard rubber
Polyurethane rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Lining type
Gasket type
Size mm (inch)
Process connection
1100 (44)
1200 (48)
1350 (54)
1400 (56)
1500 (60)
1600 (64)
1800 (72)
EN1092-1 PN6
180 to 300
233 to 388
238 to 397
291 to 485
EN1092-1 PN10
327 to 546
379 to 632
532 to 886
552 to 919
AWWA C207
Class D
298 to 497
AS2129 Table D, E
AS4087 PN16
400 to 582
JIS F12
(JIS 75M)
285 to 476
281 to 468
397 to 662
421 to 702
532 to 887
468 to 779
IM 01E25D11-01EN
<3. INSTALLATION>
3-9
Table 3.3.2 Tightening Torque Values for Metal Piping (lbf-in)
Size
Lining type
Gasket type connection mm (inch)
Process
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Unit: lbf-in
PTFE / Natural hard rubber / Natural soft rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
EN1092-1 PN10
JIS B2220 10K
EN 1092-1 PN16
AWWA C207
Class D
AS2129 Table D, E
AS4087 PN16
880 to 1467
1275 to 2125
748 to 1239
955 to 1546
1266 to 2110
1928 to 3214
1332 to 2062
2113 to 2932
1490 to 2483
2292 to 3820
2426 to 4043
2426 to 4043
1561 to 2357
1880 to 2671
1821 to 2991
2450 to 3739
1594 to 2657
2085 to 3475
1980 to 3301
2717 to 4528
1558 to 2596
2176 to 3627
2285 to 3809
2534 to 4224
2123 to 2943
3538 to 5413
3535 to 5346
3734 to 5265
Lining type
Gasket type connection
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Unit: lbf-in
Polyurethane rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
ASME
B16.5 (500, 600)
B16.47 (700-1000)
Class 150
626 to 1044
EN1092-1 PN10
JIS B2220 10K
527 to 876
EN 1092-1
PN16
652 to 1087
AWWA C207
Class D
AS2129 Table
D, E
AS4087 PN16
674 to 1089
JIS F12
(JIS 75M)
1159 to 1931
862 to 1436
1106 to 1843
1562 to 2603
1505 to 2508
1546 to 2577
727 to 1113
1193 to 1791
1420 to 2024
1340 to 2218
1824 to 2781
894 to 1490
1295 to 2159
1680 to 2800
1571 to 2619
1951 to 3251
1061 to 1769
1494 to 2491
1422 to 2370
1459 to 2432
1043 to 1512
1478 to 2142
1926 to 3076
1773 to 2808
2239 to 3274
1095 to 1825
1788 to 2980
1739 to 2899
1958 to 3263
1928 to 3213
Unit: lbf-in
Natural hard rubber
Polyurethane rubber
Soft rubber gasket, or the equivalent in hardness (supplied by customer)
Lining type
Gasket type
Size mm (inch)
Process connection
1100 (44)
1200 (48)
1350 (54)
1400 (56)
1500 (60)
1600 (64)
1800 (72)
EN1092-1 PN6
1594 to 2657
2060 to 3434
2109 to 3515
2576 to 4293
EN1092-1 PN10
2898 to 4830
3358 to 5597
4705 to 7842
4883 to 8138
AWWA C207
Class D
2639 to 4398
AS2129 Table D, E
AS4087 PN16
3539 to 5149
JIS F12
(JIS 75M)
2527 to 4211
2484 to 4139
3517 to 5862
3729 to 6215
4713 to 7854
4138 to 6897
IM 01E25D11-01EN
Blank Page
4. WIRING
4.1 Wiring the Remote Flowtube
This section describes the wiring of the remote flowtube only. For information relating to the wiring of the converter, refer to the user’s manual of the
AXFA11 Magnetic Flowmeter Remote Converter
(IM 01E20C01-01E).
WARNING
The wiring of the magnetic flowmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to wiring.
CAUTION
Once all wiring is complete, check the connections before applying power to the instrument. Improper arrangements or wiring may cause a unit malfunction or damage.
4.1.1 Wiring Precautions
Be sure to observe the following precautions when wiring:
CAUTION
• In cases where the ambient temperature exceeds 50°C (122°F), use external heatresistant wiring with a maximum allowable temperature of 70°C (158°F) or above.
• Do not connect cables outdoors in wet weather in order to prevent damage from condensation and to protect the insulation, e.g. inside the terminal box of the flowtube.
• Do not splice the cable between the flowtube terminal and the converter if it is too short.
Replace the short cable with a cable that is the appropriate length.
• All the cable ends must be provided with round crimp-on terminals and be securely wired.
<4. WIRING>
4-1
• The signal cables must be routed in separate steel conduit tubes 16 (JIS C 8305) or flexible conduit tubes 15 (JIS C 8309).
• Keep conduits or flexible tubes watertight using sealing tape.
• Ground the remote flowtube and the converter separately.
• Cover each shield of the signal cable with vinyl tube or vinyl tape to avoid contact between two shields or between a shield and a case.
• When waterproof glands or union equipped waterproof glands are used, avoid tightening the glands with an excessive torque.
• Be sure to turn the power off before opening the terminal box cover.
• Before turning the power on, tighten the terminal box cover securely.
• When opening the terminal box cover, use a hexagonal wrench (nominal size 3 mm). For handling the locking screw, refer to Figure
4.1.7.
• Be sure to lock the cover using a hexagonal wrench (nominal size 3 mm) after installing the cover. For handling the locking screw, refer to
Figure 4.1.11.
• When submersible type or optional code DHC is selected, waterproof glands, signal and excitation cables are attached.
In order to preserve the effectiveness of waterproof features, the terminal box cover and waterproof glands must not be detached from flowmeter.
IMPORTANT
Prepare the signal cable and the excitation cable almost the same length. It is recommended to lay them together closely.
IM 01E25D11-01EN
4.1.2 Cables
(1) Dedicated Signal Cable (AXFC)
Conductors (A and B)
Shields (SA and SB)
Tape
Outer jacket
10.5 (0.413")
Shield (C)
Insulation
Insulation
F0401.ai
Figure 4.1.1 Dedicated Signal Cable AXFC
The flow signal is transmitted via this dedicated cable. The cable is constructed with double shielding over the two conductors, and heatresistant vinyl is used for the outer jacket material.
10.5 mm (0.413”) Finished diameter:
Maximum length:
Combination with the AXFA11 converter:
200 m (660 ft)
Maximum temperature: 80°C (176°F)
IMPORTANT
If the cable is longer than required, cut off any extra length rather than coiling it up, and terminate the conductors as shown in Figure
4.1.2. Avoid using junction terminal boards to extend the cable length, as this will interrupt the shielding.
Unit : mm
(approx. inch)
<4. WIRING>
4-2
CAUTION
• As crimp terminals A, B, SA, SB and C have their own electrical potentials, securely insulate them so as not to come in contact with one another.
• To prevent a shield from coming in contact with another shield or the case, cover each shield with a vinyl tube or wrap it in vinyl tape.
NOTE
Conductors A and B carry the signal from the electrodes, and C is at the potential of the liquid
(signal common). Shields SA and SB are kept at the same potentials as the individual electrodes
(these are actively driven shields.) This is done to reduce the effect of the distributed capacitance of the cable at long cable length. Note that, since the signals from the individual electrodes are impedance converted inside the converter, errors will result if they come in contact with any other component. Great care must be taken in the cable finish treatment.
(2) Excitation Cable
JIS C 3401 control cable equivalent
JIS C 3312 power cable equivalent
14 AWG Belden 8720 equivalent
Outer Diameter: 6.5 to 12 mm (0.26 to 0.47 in.)
10.5 or 11.5 mm (0.41 to 0.45 in.) for optional code EG, EU and EW.
Nominal Cross Section:
Single wire: 0.5 to 2.5 mm
2
Stranded wire: 0.5 to 1.5 mm
2
White Black Red
White Black
Red
On the converter side
On the flowtube side
L (Specified Dimensions)
20 (0.8)
AXFC
F0402.ai
Figure 4.1.2 Treatment of Dedicated Signal Cables
IM 01E25D11-01EN
85 (3.35)
Unit : mm
(approx. inch)
Crimp terminal
85 (3.35)
On the converter side On the flowtube side
F0403.ai
Figure 4.1.3 Finish Treatment of Excitation Cable
NOTE
• For excitation cables, always use a crimp terminal with an insulation cover.
• Use crimp tools from the manufacturer of the crimp terminal you want to use to connect the crimp terminal and cable.
• Use crimp tools that are appropriate for the diameter of the cable to be connected.
<4. WIRING>
4-3
4.1.3 Wiring Ports
This instrument is of watertight construction as stipulated in JIS C0920. It is shipped with a wiring bracket (waterproof gland or waterproof gland with union), only in cases where an optional specification is selected for the wiring port.
When submersible type or option code DHC is selected, waterproof glands and a 30-meter (or customer designated) length cable are attached with resin filled in the terminal box. In this case, wiring at this terminal box is not necessary and do not open it.
IMPORTANT
The wiring port is sealed with a cap (not waterproof). Do not remove the cap from the wiring port until wiring a cable. If waterproof property is necessary, please use waterproof glands.
(1) When waterproof property is unnecessary
(When there are no particular optional specifications)
The wiring port is sealed with a cap (not waterproof) that must be removed before wiring. When wiring, handle the wiring with proper procedures for necessary protection.
(2) When waterproof property is necessary
(Wiring using waterproof glands)
IMPORTANT
To prevent water or condensation from entering the terminal box, waterproof glands are recommended. Do not over-tighten the glands or damage to the cables may result. Tightness of the gland can be checked by confirming that the cable is held firmly in place.
For working on the electric wire tubes or the flexible tubes (G1/2), remove the waterproof gland and attach them directly to the wiring port.
Be sure to use the washers and gaskets as shown in the drawings. Check and see that the cable is firmly fixed realizing waterproofness.
IM 01E25D11-01EN
Washer
Gasket
Waterproof gland
Cable
F0404.ai
Figure 4.1.4 Waterproof Gland (Optional code EG)
Gasket
<4. WIRING>
4.1.4 Wiring Connections
4-4
WARNING
Before wiring, be sure that the power supply for
AXFA11 converter has been turned off to prevent an electrical shock.
(1) Removing Cover
Loosen the cover locking screw clockwise using a hexagonal wrench (nominal size 3 mm) to unlock the cover. (Upon shipment from the manufacturing plant, the cover is unlocked.) Remove the cover by turning it in the direction of the arrow as shown below.
PF1/2
Washer
Tightening gland
Cable
When working on conduit pipes or flexible pipes (G1/2 only)
F0405.ai
Figure 4.1.5 Waterproof Gland with Union Joint
(Optional code EU)
(3) Conduit Wiring
When wiring the conduits, pass the conduit through the wiring connection port, and utilize the waterproof gland to prevent water from flowing in. Place the conduit pipe on an angle as shown in Figure 4.1.6.
Install a drain valve at the low end of the vertical pipe, and open the valve regularly.
F0407.ai
Figure 4.1.7 Removing the Terminal Box Cover
(2) Terminal Configuration
When the cover is removed, the connection terminals will be visible.
Drain valve
Figure 4.1.6 Conduit Wiring
F0406.ai
A
B
C
EX1
EX2
Description
Flow signal output
Excitation current input
Protective grounding
(Outside of the terminal)
F0408.ai
Figure 4.1.8 Terminal Configuration
IM 01E25D11-01EN
(3) Wiring the Remote Flowtube with AXFA11
Converters
Connect wiring as shown in the figure below.
I+
CURRENT OUT
4-20mA out
I– SO1+ SO2+ COM
STATUS OUT
AL+ AL–
ALARM OUT
C SA A
SIGNAL
B
FUSE
2.5A 250V
Shortbar
N/– L/+
POWER SUPPLY
EX1 EX2
EXCIT ATION
P+ P–
PULSE OUT
SI1+ SI2+
STATUS IN
COM
SB
AXFA11 converter
A
B
C
AXFC dedicated signal cable
Excitation cable
EX2
Converter
SA
A
B
SB
C
EX1
EX2
Remote flowtube
Taping*
A
B
Taping*
C
EX1
EX2
EX1
Remote flowtube
* Individually tape and insulate the shields corresponding to
SA and SB on the remote flowtube side.
F0409.ai
Figure 4.1.9 Wiring Diagram
(4) Grounding
CAUTION
Be sure to connect the protective grounding of the remote flowtube with a cable of 2 mm
2
or larger cross section in order to avoid electrical shock to the operators and maintenance engineers and to prevent the influence of external noise.
Connect the grounding wire to the mark.
The grounding should satisfy Class D requirements (ground resistance, 100 Ω or less).
600 V vinyl insulated electric cable
(2 mm
2
or larger)
<4. WIRING>
4-5
• Class D requirements (ground resistance.
100 Ω or less).
Without optional grounding rings.
(Available only for metal piping)
With optional grounding rings.
F0410.ai
Figure 4.1.10 Protective Grounding Terminal Location
(5) Installing the Cover
Install the cover to the flowtube by turning it in the direction of the arrow as shown below. Tighten the cover locking screw counterclockwise using a hexagonal wrench (nominal size 3 mm) to lock the cover.
IMPORTANT
Improper grounding can have an adverse affect on the flow measurement. Ensure that the instrument is properly grounded.
The electromotive force of the magnetic flowmeter is minute and it is easy to be affected by noise. And also that reference electric potential is the same as the measuring fluid potential. Therefore, the reference electric potential (terminal potential) of the flowtube and the converter also need to be the same as the measuring fluid. Moreover, that the potential must be the same with ground.
Be sure to ground according to Figure 4.1.10.
Refer to Figure 3.3.5 or 3.3.6 for wiring to the flanges of remote flowtube when optional grounding rings are not used.
F0411.ai
Figure 4.1.11 Installing the Terminal Box Cover
IM 01E25D11-01EN
Blank Page
5. MAINTENANCE
WARNING
• Maintenance work must be carried out by the trained personnel having knowledge of safety standard and not by operators.
• When opening the cover, wait for more than 10 minutes after turning off the power.
Furthermore, opening of the cover must also be carried out by the trained personnel having knowledge of safety standard.
CAUTION
• When opening the cover, use a hexagonal wrench (nominal size 3 mm).
• Be sure to lock the cover using a hexagonal wrench (nominal size 3 mm) after installing the cover.
<5. MAINTENANCE>
5-1
F0501.ai
(4) Using the hexagonal wrench, loosen the screw in the neck.
(5) Turn the terminal box in the desired direction.
NOTE
The terminal box can be turned –140 degree to
+180 degree from the arrow mark indicating the flow direction. Do not exceed these angle.
(6) Using the hexagonal wrench, retighten the neck screw.
-140º +180º
5.1 Changing Direction of
Electrical Connection
IMPORTANT
The following types can not be changed direction of electrical connection after delivery.
• Submersible Type.
• Optional code DHC (for district heating and cooling or condensation-proof).
(1) The following tools are required to change the direction of the electrical connection:
• Hexagonal wrench (nominal size 1.5 mm)
• Wrench
(2) Turn off the power to the flowmeter.
(3) Using the wrench, loosen the hexagonal nut at the neck of the instrument.
F0502.ai
(7) Using the wrench, retighten the hexagonal nut at the neck. After that, check that the terminal box is fixed.
IM 01E25D11-01EN
5.2 Regular Inspection Items
(1) Inspection of moisture-proofing inside the terminal box: Once/year
(2) Retightening of piping joint screws: About twice/year
(3) Inspection of electrodes and lining (in case of adhesive and/or abrasive fluids, etc.)
Determine the period of regular inspection as necessary.
5.3 Excitation Coil and
Insulation Resistance Check
WARNING
• Before checking of the excitation coil and the insulation resistance, be sure that the power supply for AXFA11 converter has been turned off.
• Before checking, be sure to disconnect the cables from the terminals of the remote flowtube.
(1) Excitation Coil Check
Check that there is continuity between terminals
EX1 and EX2 in the terminal box. If there is no continuity, the coils may be broken and replacement or repair of the flowtube is necessary. The coil resistance is designed to be 150 Ω or less. If it is not, this may be an abnormal condition. Consult
Yokogawa’s sales or service offices.
(2) Insulation Resistance Check
Check the insulation resistances in the terminal box in accordance with the tables below. If any of them falls below the values listed in the tables, consult Yokogawa’s sales or service offices for investigation. If the insulation resistance cannot be restored, replacement or repair of the flowtube is needed. In case of submersible type flowmeters, undo the wiring connection on the converter side and measure resistance at the cable terminals.
<5. MAINTENANCE>
5-2
Coil Circuit
Checking is possible even if the pipe is filled with fluid.
Test Terminals
Between terminals
EX1 and C
Test Voltage
500 V DC (Use an insulation tester or the equivalent.)
Specification
1 MΩ or more
Signal Circuit
Before testing, be sure to empty and dry the interior of the pipe, checking that there is no adhesive material. Also undo the wiring connection on the converter side before testing.
Test Terminals
Between terminals
A and C
Between terminals
B and C
Test Voltage
500 V DC (Use an insulation tester or the equivalent.)
Specification
100 MΩ or more for each
IM 01E25D11-01EN
<5. MAINTENANCE>
5-3
5.4 Troubleshooting
Although magnetic flowmeters rarely require maintenance, failures may occur when the instrument is not operated correctly. This section describes troubleshooting procedures where the cause of the breakdown is identified through receiver indication.
5.4.1 No Indication
START
Is an error being displayed? Check the converter display.
Is an error being displayed?
NO
Is anything else being displayed?
YES
YES
NO
Refer to the “Alarm Functions” in the AXFA11.
Does the arrow on the tube match the flow direction?
YES
NO
Check whether the flowtube is filled with fluid.
Perform either of the following: a. Reinstall the flowtube in order to make the arrow and flow direction match.
b. Reverse the setting for the flow direction.
Is the flowtube full of fluid?
YES
Check the resistance between the flowtube’s A, B, and C terminals using a circuit tester.
NO
Is the resistance between A-C or B-C
100 MΩ or more?
YES
NO
Remove the tube and inspect the inside of the pipe.
Is foreign matter adhering to the walls?
YES
Remove the foreign matter.
NO
Change the piping or the mounting condition so that the tube fills with the fluid.
Contact a service center.
F0503.ai
IM 01E25D11-01EN
5.4.2 Unstable Zero
START
Investigate whether or not the flowtube is filled with fluid and that it is free of bubbles.
*1
Is the flowtube completely full of fluid?
NO
YES
Are there bubbles in the fluid?
NO
Check for the presence of valve leakage.
YES
Are valves leaking?
NO
● Confirm the flowmeter grounding.
● Confirm whether or not the grounding wire is disconnected from the earth flange.
YES
Is the flowmeter properly grounded?
YES
Recheck the fluid to be measured.
NO
<5. MAINTENANCE>
*1: When checking for bubbles, it is convenient if there is a gas vent hole on the flowtube’s downstream side.
Particular care must be taken in the case of horizontal mounting. In order to ensure complete filling of the tube, either adjust the mounting position or switch to vertical mounting.
Install a defoaming device on the flowtube’s upstream side.
Replace the valve(s).
Completely ground the converter and flowtube (Refer to the section on grounding in the relevant user's manual.)
● Does the fluid’s
conductivity vary?
● Is the fluid conductivity
within the limits?
NO
YES
Is the fluid likely to contain deposits?
NO
YES
Is the flowmeter located near motors, transformers, or electric equipment?
NO
YES
Contact a service center.
● Ensure that the fluid’s conductivity changes as little as possible.
● Do not use the meter when fluid conductivity is out of limits.
● Whenever possible, reduce the flow velocity to being in the vicinity of the lower conductivity limit.
● Remove dirt and scale of and near electrodes.
● Use a soft brush or cloth to perform scale removal, and make sure that the lining is not damaged.
Provide the meter with sufficient shielding or move it away from the electrical equipment
F0504.ai
5-4
IM 01E25D11-01EN
5.4.3 Disagreement Between Indication and Actual Flow
START
<5. MAINTENANCE>
Are parameters set correctly?
NO
YES
Examine the condition of the fluid in the flowtube, of bubbles, and of grounding.
Was zero adjustment carried out correctly?
YES
Is the tube filled completely with fluid?
YES
NO
NO
Does the fluid contain bubbles?
NO
Is the flowmeter completely grounded?
YES
YES
NO
NO
YES
Does the conductivity stay within the specified range?
YES
Is the fluid likely to contain deposits?
NO
Confirm that a valve is located immediately upstream of the flowtube
(i.e., on the upstream side).
NO
YES
Is a valve located immediately upstream of the flowtube?
YES
NO
Remove the flowtube and examine the insulation resistance.
Set the parameters correctly.
Execute zero adjustment when the flowtube is filled completely with fluid and when the fluid is not moving.
● Change the mounting position or piping so that the flowtube is completely filled with fluid.
● Switch to vertical mounting.
Install a defoaming device on the flowtube’s upstream side.
Completely ground the converter and flowtube (Refer to the section on grounding in the relevant user's manual.)
Fully terminate the signal cable using
PVC tubing or insulation tape, thus insuring that conductors, inner shields, and outer shields do not make contact with each other or with the case.
Use within the specified conductivity range.
● Remove scales. Especially clean the electrodes and their vincinity.
● Use a soft brush or cloth to perform scale removal, and make sure that the lining is not damaged.
● If any valve located immediately upstream of the flowtube is used in a half-open condition, the indication may be affected by turbulence in the flow.
● Relocate the valve to the downstream side.
● If the valve must be located on the upstream side, ensure that the minimum distance to the flowmeter is 10 times the flow-tube diameter; alternatively, use the valve fully open.
Signal terminals A-C and B-C:
100 MΩ or more?
Excitation terminals EX1-C:
1 MΩ or more?*
1
YES
Examine the operation of the converter using an AM012 calibrator in order to determine whether the fault lies in the converter or in the flowtube.
NO
Dry the tube fully to restore insulation resistance.
*1: Refer to Section 5.3 for how to check the resistance of the flowtube.
Contact a service center.
F0505.ai
5-5
IM 01E25D11-01EN
Blank Page
6. OUTLINE
n
STANDARD SPECIFICATIONS
Protection:
General-purpose type: IP66, IP67
Submersible type: IP68 (conforms to continuous immersion under the following test condition)
Test Condition: 50 m below the surface of the water, equivalent to
0.5 MPa hydraulic pressure, for one month.Cable should be protected at customer site.
Material (non-wetted parts):
Flowtube:
Housing: Carbon steel
Flange: Carbon steel
Pipe: Stainless steel
Terminal box: Aluminum alloy
Material (wetted parts):
Lining:
Fluorocarbon PTFE
Natural hard rubber (plus EPDM for sealing)
Natural soft rubber
Polyurethane rubber
Contact Yokogawa office for others.
Electrode:
JIS SUS316L(AISI 316L SS Equivalent)
Hastelloy C276 Equivalent
Grounding ring (option):
JIS SUS304 or SUSF304 (AISI 304 SS
Equivalent)
Gasket (for option GR2):
Mixture of SBR and NR
Coating:
General-purpose type:
Pipe, Housing, Flange, Terminal Box:
Corrosion-resistant coating
Coating color: Mint green
Submersible type:
Pipe, Housing, Flange, Terminal Box:
Non-tar epoxy coating (black)
Wiring:
Electrical connection:
ANSI 1/2 NPT female
ISO M20 x 1.5 female
JIS G1/2 (PF1/2) female
Direction of Electrical Connection:
The direction can be changed even after delivery except for submersible type and DHC option type.
Wiring Terminal:
M4 screw
<6. OUTLINE>
6-1
Grounding:
Grounding resistance 100 Ω or less
Combined Converter:
AXFA11 converter
Signal Cable:
AXFC, Maximum cable length to AXFA11 converter up to 200m (660 ft) n
STANDARD PERFORMANCE
Accuracy (Pulse Output):
0.35% of rate for sizes 500 mm (20 in.) to 1000 mm (40 in.)
0.5% of rate for sizes 1100 mm (44 in.) to 1800 mm (72 in.)
Size mm(in.)
Accuracy
500(20) to 1000(40)
1100(44) to 1800(72)
Flow Velocity
V m/s (ft/s)
V < 0.3 (1.0)
0.3 ≤ V ≤ 10
(1.0) (33)
V < 0.3 (1.0)
0.3 ≤ V < 1
(1.0) (3.3)
1 ≤ V ≤ 10
(3.3) (33)
±2.0mm/s
±0.35% of rate ±1.0mm/s
±3.0mm/s
±0.4% of rate ±1.8mm/s
±0.5% of rate ±1.0mm/s
For sizes 500mm (20 in.) to 1000mm (40 in.)
% of rate
1.2
1.0
0.8
0.6
0.4
0.2
0.0
0 1 2 3
Pulse Output Accuracy
4 5
V [m/s]
6 7 8
For sizes 1100mm (44 in.) to 1800mm (72 in.)
% of rate
1.2
1.0
0.8
0.6
0.4
0.2
0.0
0 1 2 3
Pulse Output Accuracy
4 5
V [m/s]
6 7 8
9 10
F0601.ai
9 10
F0602.ai
IM 01E25D11-01EN
Note: The accuracy of a product before shipment is defined as totalized value at the result of calibration test in our water actual flow test facility.
Calibrated conditions in our water actual test facility are as follows:
Fluid temperature: 20 ± 10°C
Ambient temperature: 20 ± 5°C
Length of straight runs:
10 D or more on the upstream side
5 D or more on the downstream side
Reference conditions:
Similar to BS EN29104, ISO 9104
Accuracy (Current Output):
Accuracy (Pulse Output) plus ±0.05% of span
Repeatability:
±0.2% of rate (V ≥ 1m/s (3.3ft/s))
±0.1% of rate ± 1mm/s (V < 1m/s (3.3ft/s))
Maximum Power Consumption:
Combined with AXFA11: 20W
Insulation Resistance:
Between excitation current terminal and signal
/ common terminals : 100MΩ at 500V DC
Between signal terminals : 100MΩ at 500V DC
Between signal terminals and common terminal (C) : 100MΩ at 500V DC
CAUTION
*1: When performing the Insulation Resistance
Test, please obey the following caution.
• Following the relevant test, wait for more than 10 seconds after the power supply has been turned off before removing the cover.
• Remove all wires from terminals before testing.
• After testing, be sure to discharge by using a resistance and return all wires to its correct position.
• Screws must be tightened to a torque of
1.18 N-m or more.
• After closing the cover, the power supply can be restored.
EMC Conformity Standards:
EN61326-1 Class A, Table2 (For use in industrial locations)
EN61326-2-3
EN61000-3-2 Class A
EN61000-3-3
CAUTION
This instrument is a class A product, and it is designed for use in the industrial environment.
Please use this instrument in the industrial environment only.
<6. OUTLINE>
6-2
n
NORMAL OPERATING CONDITIONS
Ambient Temperature:
–10 to +60°C (+14 to +140°F)
Note: Minimum temperature should also be limited according to minimum fluid temperature of flow tube’s specification. Refer to description of “Fluid Temperature and Pressure”. Contact Yokogawa office for lower temperature.
Ambient Humidity:
0 to 100%
Note: Lengthy continuous operation at 95% or more is not recommended.
Fluid Conductivity:
20 µS /cm or larger for sizes 1000 mm and below
50 µS /cm or larger for sizes 1100 mm and above
Measurable Flow Rate Range:
Size mm (in.)
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
Min. Span
0.1m/s (0.33ft/s)
0 to 70.69 m
3
/h
(0 to 311.3 GPM)
0 to 101.79
(0 to 448.2)
0 to 138.55
(0 to 610.0)
0 to 180.96
(0 to 796.8)
0 to 229.03
(0 to 1,009)
0 to 282.75
(0 to 1,245)
Max. Span
10m/s (33ft/s)
0 to 7,068 m
3
/h
(0 to 31,122 GPM)
0 to 10,178
(0 to 44,815)
0 to 13,854
(0 to 60,999)
0 to 18,095
(0 to 79,672)
0 to 22,902
(0 to 100,835)
0 to 28,274
(0 to 124,488)
Size mm (in.)
1100 (44)
1200 (48)
1350 (54)
1400 (56)
1500 (60)
1600 (64)
1800 (72)
Min. Span
0.3 m/s (1 ft/s)
0 to 1,026.4 m
3
/h
(0 to 4,519 GPM)
0 to 1,221.5
(0 to 5,378)
0 to 1,545.9
(0 to 6,807)
0 to 1,662.5
(0 to 7,320)
0 to 1,908.6
(0 to 8,403)
0 to 2,171.5
(0 to 9,561)
0 to 2,748.3
(0 to 12,101)
Max. Span
10 m/s (33 ft/s)
0 to 34,211 m
3
/h
(0 to 150,630 GPM)
0 to 40,715
(0 to 179,262)
0 to 51,529
(0 to 226,879)
0 to 55,418
(0 to 243,997)
0 to 63,617
(0 to 280,098)
0 to 72,382
(0 to 318,689)
0 to 91,608
(0 to 403,341)
Fluid Temperature and Pressure:
Note: The following values show maximum allowable fluid pressure for the flowtube. Further fluid pressure should also be limited according to flange rating.
Lining Material Fluid Temperature Fluid Pressure
Fluorocarbon PTFE -10 to 120°C
(14 to 248°F)
Natural hard rubber
-5 to 80°C
(23 to 175°F)
Natural soft rubber
Polyurethane rubber
-10 to 70°C
(14 to 158°F)
-10 to 40°C
(14 to 104°F)
0 to 1 MPa
(0 to 145 psi)
0 to 1 MPa
(0 to 145 psi)
0 to 1 MPa
(0 to 145 psi)
-0.1 to 1 MPa
(-14.5 to 145 psi)
IM 01E25D11-01EN
<6. OUTLINE>
6-3
n
MODEL AND SUFFIX CODE
For Process Connections other than JIS F12 (JIS 75M)
Model Suffix Code Description
AXW500
AXW600
AXW700
AXW800
AXW900
AXW10L
AXW12L
AXW14L
AXW16L
AXW18L
Use
Converter
Power Supply
Lining (*1)
Electrode Material (*1)
G
W
Electrode Structure
Grounding Structure (*2)
Process Connection
(*4)
-N
N
D
U
F
H
L
H
1
N
-CA1
Size 500 mm (20 in.) Remote Flowtube
Size 600 mm (24 in.) Remote Flowtube
Size 700 mm (28 in.) Remote Flowtube
Size 800 mm (32 in.) Remote Flowtube
Size 900 mm (36 in.) Remote Flowtube
Size 1000 mm (40 in.) Remote Flowtube
Size 1200 mm (48 in.) Remote Flowtube
Size 1400 mm (56 in.) Remote Flowtube
Size 1600 mm (64 in.) Remote Flowtube
Size 1800 mm (72 in.) Remote Flowtube
General-purpose type
Submersible type
Remote Flowtube for Combined Use with AXFA11
Remote Flowtube
Fluorocarbon PTFE
Natuarl Hard Rubber
Natuarl Soft Rubber
Polyurethane Rubber
JIS SUS316L (AISI 316L SS Equivalent)
Hastelloy C276 Equivalent
Non-replaceable
None (*3), available as optional feature (GR1)
ASME B16.5 Class 150 Flange (Carbon Steel)
ASME B16.47 Series A Class 150 Flange
(Carbon Steel)
-CB1 AWWA C207 Class D (Carbon Steel)
Available Size / Model
See “Proces Connection”.
See “Proces Connection”.
See “Proces Connection”.
See “Proces Connection”.
500 mm (20 in.) and 600 mm (24 in.) for lining code F/H/D/U
700 mm (28 in.) to 1000 mm (40 in.) for lining code F/H/D/U
700 mm (28 in.) to 1000 mm (40 in.) for lining code F/H/D/U
1200 mm (48 in.) for lining code H
-CEJ
-CEK
EN1092-1 PN6 Flange (Carbon Steel)
EN1092-1 PN10 Flange (Carbon Steel)
(fluid pressure up to 0.6 MPa)
1200 mm (48 in.) to 1800 mm (72 in.) for lining code H
-CE1
EN1092-1 PN10 Flange (Carbon Steel)
(fluid pressure up to 1 MPa)
500 mm (20 in.) to 1000 mm (40 in.) for lining code F/H/D/U
1200 mm (48 in.) to 1800 mm (72 in.) for lining code H
500 mm (20 in.) to 1000 mm (40 in.) for lining code F/H/D/U
Lay Length
Electrical Connection
Indicator
Calibration
Optional Specifications
-CE2
-CJ1
-CS1
-CS2
-CT1
N
-0
-2
-4
N
B
EN1092-1 PN16 Flange (Carbon Steel)
(fluid pressure up to 1 MPa)
JIS B2220 10K Flange (Carbon Steel)
AS2129 Table D (Carbon Steel)
AS2129 Table E (Carbon Steel)
AS4087 PN16 (Carbon Steel)
Standard
JIS G1/2 female
ANSI 1/2 NPT female
ISO M20 x 1.5 female
None
Standard
/ Optional code
500 mm (20 in.) to 1000 mm (40 in.) for lining code F/H/D/U
1200 mm (48 in.) for lining code H
Not available for Submersible type
Not available for Submersible type
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and hightemperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*2: Select optional grounding rings (code GR1) if necessary. For example, grounding rings are necessary for plastic piping.
*3: “None” is applicable only for metal piping and wiring for grounding will be necessary so that the electric potentials between flowtube and piping flange should be the same.
*4: Contact Yokogawa office for ISO flange connection.
IM 01E25D11-01EN
<6. OUTLINE>
6-4
For Process Connection JIS F12 (JIS 75M)
Model
AXW500
Suffix Code Description
Size 500 mm (20 in.) Remote Flowtube
AXW600 Size 600 mm (24 in.) Remote Flowtube
AXW700
AXW800
AXW900
AXW10L
AXW11L
AXW12L
AXW13L
AXW15L
AXW16L
AXW18L
Use
Converter
Power Supply
Lining (*1)
G
W
Electrode Material (*1)
Electrode Structure
Grounding Structure (*2)
Process Connection
Lay Length
Electrical Connection
Indicator
Calibration
Optional Specifications
-N
N
U
L
H
1
N
-CG1
N
-0
-2
-4
N
B
/
Size 700 mm (28 in.) Remote Flowtube
Size 800 mm (32 in.) Remote Flowtube
Size 900 mm (36 in.) Remote Flowtube
Size 1000 mm (40 in.) Remote Flowtube
Size 1100 mm (44 in.) Remote Flowtube
Size 1200 mm (48 in.) Remote Flowtube
Size 1350 mm (54 in.) Remote Flowtube
Size 1500 mm (60 in.) Remote Flowtube
Size 1600 mm (64 in.) Remote Flowtube
Size 1800 mm (72 in.) Remote Flowtube
General-purpose type
Submersible type
Remote Flowtube for Combined Use with
AXFA11
Remote Flowtube
Polyurethane Rubber
JIS SUS316L (AISI 316L SS Equivalent)
Hastelloy C276 Equivalent
Non-replaceable
None (*3), available as optional feature
(GR1 or GR2)
JIS F12 (JIS 75M) Flange (Carbon Steel)
Standard
JIS G1/2 female
ANSI 1/2 NPT female
ISO M20 x 1.5 female
None
Standard
Optional code
Available Size / Model
Not available for Submersible type
Not available for Submersible type
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and hightemperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*2: Select optional grounding rings (code GR1 or GR2) if necessary. For example, grounding rings are necessary for plastic piping.
The code GR1 is optional only for sizes 500 mm (20 in.) to 1000 mm (40 in.).
The code GR2 is optional only for sizes 1100 mm (44 in.) to 1800 mm (72 in.).
*3: “None” is applicable only for metal piping and wiring for grounding will be necessary so that the electric potentials between flowtube and piping flange should be the same.
IM 01E25D11-01EN
<6. OUTLINE>
6-5
n
OPTIONAL SPECIFICATIONS
Item Specifications
Grounding Rings (*1) JIS SUS304 (AISI 304 SS Equivalent), a set of two rings
Grounding Rings (*2) SUSF304 (AISI 304 SS Equivalent), a set of two rings with gaskets “B”.
For District Heating and Cooling or
Condensation-proof
User-specified Signal and Excitation Cable
Length
Urethane resin potting is applied in the terminal box of a remote flowtube. Select JIS
G1/2 for the electrical connections. 30-meter dedicated signal and excitation cables are pre-wired and waterproof glands with union joints are attached at factory.
Available for the submersible type and a model with optional code DHC. The cable length is limited up to 200 meters combined with an AXFA11 converter. Following “L,” specify the cable length in three digits as a multiple of 1 meter (e. g., 001, 002, or 005) for a length up to 5 meters, or as a multiple of 5 meters (i.e., 005, 010, 015, or the like) for a length of 5 meters or more. If this optional code is not selected, a 30-meter length cable is attached.
Mass Unit Setting
G3/4 Female
Waterproof Glands
Waterproof Glands
The flow rate span, transmission pulse weight, and totalizer display pulse weight can be set in terms of mass unit.
Specify the density of the process fluid when ordering in addition to the mass flow rate span, transmission pulse weight (for mass unit), and totalizer display pulse weight (for mass unit).
When ordering a remote flowtube, parameters for 'Mass Unit Setting' will be set in the corresponding converter before shipment.
1. Density a. Available density Numerics:
Specify the numeric within the value of 500 to 2000 kg/m
3
, 4.2 to 16.7 lb/gal, or 31.2 to 124.8 lb/cf. And it can be up to five digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place.
b. Available density units: kg/m
3
, lb/gal, lb/cf
Example: A water density is about 1000 kg/m
3
. In this case specify “1000kg/m
3
”.
However a density is changed by temperature. Specify the actual density.
(The 1000 kg/m
3
is equivalent to 8.345lb/gal and 62.43lb/cf.)
2. The mass flow rate span, transmission pulse weight, and totalizer display pulse weight a. Available density Numerics:
Specify the numeric within the value of 0.0001 to 32000. And it can be up to five digits, to a maximum of 32000 ignoring the decimal point. A fraction is limited to the fourth decimal place.
b. Mass Units Available mass units: t, kg, g, klb, lb
Available time units: /d, /h, /min, /s
Note1: In case of specifying the mass flow span, calculate the volumetric flow span by the setting density, and specify the available value in the mass flow span.
Note2: In case of transmission pulse weight and totalizer display pulse weight, specify the mass unit which was specified as the flow unit.
Waterproof glands for G3/4 conduits or flexible tubes are attached to the electrical connections. Available only for JIS G1/2 electric connections.
Waterproof glands are attached to the electrical connections. Available only for JIS G1/2 electric connections.
○
: Available – : Not available
Applicable Model
General Submersible
AXW***G AXW***W
○ ○
○ ○
Code
GR1
GR2
○
○
○
○
○
–
○
○
–
–
DHC
L***
MU
EW
EG
Waterproof Glands with Union Joints
Stainless Steel Tag
Plate
Direction Change of
Electrical
Connection (*3)
Material Certificate
Waterproof glands with union joints are attached to the electrical connections. Available only for JIS G1/2 electric connections.
A pendant tag plate of stainless steel (AISI 304 SS equivalent) is provided in addition to the standard nameplate with the tag number inscribed on it.
Dimension (Height x Width): Approx. 12.5 (4.92) x 40 (15.7) mm (inch)
+90 degrees rotated terminal box to change the direction of the electrical connection.
+180 degrees rotated terminal box to change the direction of the electrical connection.
–90 degrees rotated terminal box to change the direction of the electrical connection.
Material certificates are provided for pipe, electrodes, flanges, and also optional grounding rings when specified.
○
○
○
○
○
○
–
○
○
○
○
○
EU
SCT
RA
RB
RC
M01
*1: This is not available for models with process connection JIS F12 (JIS 75M) of sizes 1100 mm (44 in.) to 1800 mm (72 in.). Refer to the section on “Mounting Procedures” on necessary gaskets.
*2: This is available only for models with process connection JIS F12 (JIS 75M) of sizes 1100 mm (44 in.) to 1800 mm (72 in.). Refer to the section on “Mounting Procedures” on necessary gaskets.
*3: Refer to the image below.
Standard
+90 degree rotation
Optional Code RA
+180 degree rotation
Optional Code RB
–90 degree rotation
Optional Code RC
Electrical
Connection
Electrical
Connection
IM 01E25D11-01EN
<6. OUTLINE>
6-6
n
OPTIONAL SPECIFICATIONS (continued)
Item
Hydrostatic Test
Specifications
The test verifies the absence of leaks by applying the following water pressures (which are determined under process connection conditions) to lining for ten minutes. Test results are described in the Note column of a test certificate(QIC).
○
: Available – : Not available
Applicable Model
General Submersible
AXW***G AXW***W
Code
Calibration Certificate
Five-point Calibration in User-specified
Span
Process Connection:
EN PN6, EN PN10 (code CEK)
ASME Class 150, EN PN10 (code CE1), EN PN16, JIS 10K
AS2129 Table E, AS4087 PN16, JIS F12 (JIS 75M)
AWWA C207 Class D
AS2129 Table D
Level 2: The Declaration and the Calibration Equipment List are issued.
Level 3: The Declaration and the Primary Standard List are issued.
Water Pressure:
0.9 MPa
1.5 MPa
1.5 MPa
1.25 MPa
1.05 MPa
Level 4: The Declaration and the Yokogawa Measuring Instruments Control System are issued.
A flow test near 0, 25, 50, 75, and 100% of the user-specified span is performed instead of the flow test of the standard 2m/s span and a test certificate (QIC) is submitted.
Specify the span (100% flow span) whose corresponding flow velocity lies between 0.5 to 10 m/s and that is less than the maximum line capacity. Selectable range of flow rate span is shown below.
Size : mm (in.)
500 (20)
600 (24)
700 (28)
800 (32)
900 (36)
1000 (40)
1100 (44)
1200 (48)
1350 (54)
1400 (56)
1500 (60)
1600 (64)
1800 (72)
Selectable range of flow rate span : m
3
/h
(Flow rate span velocity : m/s)
354 (0.5) to 7068 (10.00)
509 (0.5) to 8200 (8.06)
693 (0.5) to 8200 (5.92)
905 (0.5) to 8200 (4.53)
1146 (0.5) to 8200 (3.58)
1414 (0.5) to 8200 (2.90)
1711 (0.5) to 8200 (2.40)
2036 (0.5) to 8200 (2.01)
2577 (0.5) to 30000 (5.82)
2771 (0.5) to 30000 (5.41)
3181 (0.5) to 30000 (4.71)
3620 (0.5) to 30000 (4.14)
4581 (0.5) to 30000 (3.27)
○
○
○
○
○
○
○
○
○
○
T01
L2
L3
L4
SC
IM 01E25D11-01EN
n
DIMENSIONAL DRAWINGS
AXW500 to AXW10L, Sizes 500 mm (20 in.) to 1000 mm (40 in.)
Ground Terminal
(M4)
ø 86 (3.38)
48 (1.89)
Eye Bolt
<6. OUTLINE>
111 (4.37)
θ°
N- ø h
6-7
øC
øD
(ød)
L (*)
*: The thickness of optional grounding rings (4mm per one) and customer supplied gaskets are not included in “L” here.
F0603.ai
(1) ASME Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner Diameter ød Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
ASME B16.5 Class150
500 600
500 (20) 600 (24)
700
700 (28)
ASME B16.47 Class150
800 900
800 (32) 900 (36)
10L
1000 (40)
600 (23.62)
700 (27.56)
720 (28.35)
815 (32.09)
H, F, U, D
840 (33.07)
927 (36.50)
960 (37.80) 1080 (42.52) 1200 (47.24)
1060 (41.75) 1168 (46.00) 1289 (50.75)
635 (25.00) 749.3 (29.50) 863.6 (34.00) 977.9 (38.50) 1086 (42.75) 1200 (47.25)
477 (18.78) 578 (22.76) 675 (26.57) 777 (30.59) 878 (34.57) 976 (38.43)
469 (18.46)
9°
31.8 (1.25)
20
760 (29.92)
408 (16.06)
812 (31.97)
35 (1.38)
212 (467)
570 (22.44)
9°
34.9 (1.37)
20
875 (34.45)
459 (18.07)
921 (36.26)
35 (1.38)
305 (672)
667 (26.26)
6.4°
35.1 (1.38)
28
998 (39.29)
509 (20.04)
CA1
769 (30.28)
6.4°
41.1 (1.62)
28
1150 (45.28)
560 (22.05)
870 (34.25)
5.6°
Unit: mm (approx. in.)
41.1 (1.62)
32
1278 (50.31)
611 (24.06)
968 (38.11)
5°
41.1 (1.62)
36
1399 (55.08)
662 (26.06)
1027 (40.43) 1144 (45.04) 1249 (49.17) 1361 (53.58)
40 (1.57) 50 (1.97) 60 (2.36) 60 (2.36)
479 (1056) 680 (1499) 882 (1944) 1125 (2480)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-8
(2) AWWA Flange Type
Unit: mm (approx. in.)
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner Diameter ød Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
700
700 (28)
840 (33.07)
927 (36.50)
863.6 (34.00)
675 (26.57)
667 (26.26)
6.4°
34.9 (1.375)
28
987 (38.86)
509 (20.04)
1027 (40.43)
35 (1.38)
288 (635)
CB1
AWWA C207 Class D
800 900
800 (32) 900 (36)
960 (37.80)
H, F, U, D
1080 (42.52)
1060 (41.75)
977.9 (38.50)
1168 (46.00)
1086 (42.75)
777 (30.59)
769 (30.28)
6.4°
41.3 (1.625)
28
1131 (44.53)
560 (22.05)
1144 (45.04)
40 (1.57)
387 (853)
878 (34.57)
870 (34.25)
5.6°
41.3 (1.625)
32
1239 (48.78)
611 (24.06)
1249 (49.17)
40 (1.57)
485 (1069)
10L
1000 (40)
1200 (47.24)
1289 (50.75)
1200 (47.25)
976 (38.43)
968 (38.11)
5°
41.3 (1.625)
36
1379 (54.29)
662 (26.06)
1361 (53.58)
50 (1.97)
659 (1453)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(3) EN PN10 Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
670 (26.38)
620 (24.41)
477 (18.78)
469 (18.46)
9°
26 (1.02)
20
730 (28.74)
408 (16.06)
797 (31.38)
35 (1.38)
170 (375)
600
600 (24)
720 (28.35)
780 (30.71)
725 (28.54)
578 (22.76)
570 (22.44)
9°
30 (1.18)
20
840 (33.07)
459 (18.07)
903 (35.51)
35 (1.38)
232 (511)
CE1
EN1092-1 PN10
700
700 (28)
7.5°
30 (1.18)
24
H, F, U, D
840 (33.07)
895 (35.24)
840 (33.07)
675 (26.57)
667 (26.26)
955 (37.60)
509 (20.04)
1011 (39.80)
35 (1.38)
285 (628)
800
800 (32)
960 (37.80)
1015 (39.96)
950 (37.40)
777 (30.59)
769 (30.28)
7.5°
33 (1.30)
24
1086 (42.76)
40 (1.57)
380 (838)
900
Unit: mm (approx. in.)
900 (36)
1080 (42.52)
1115 (43.90)
1050 (41.34)
878 (34.57)
870 (34.25)
6.4°
33 (1.30)
28
1186 (46.69)
560 (22.05) 611 (24.06)
1122 (44.17) 1223 (48.15)
40 (1.57)
491 (1082)
10L
1000 (40)
1200 (47.24)
1230 (48.43)
1160 (45.67)
976 (38.43)
968 (38.11)
6.4°
36 (1.42)
28
1320 (51.97)
662 (26.06)
1331 (52.40)
50 (1.97)
646 (1424)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-9
(4) EN PN16 Flange Type (fluid pressure up to 1 MPa)
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
715 (28.15)
650 (25.59)
477 (18.78)
469 (18.46)
9°
33 (1.30)
20
775 (30.51)
408 (16.06)
820 (32.28)
35 (1.38)
230 (507)
600
600 (24)
720 (28.35)
840 (33.07)
770 (30.31)
578 (22.76)
570 (22.44)
9°
36 (1.42)
20
900 (35.43)
459 (18.07)
933 (36.73)
35 (1.38)
350 (772)
840 (33.07)
910 (35.83)
840 (33.07)
675 (26.57)
667 (26.26)
7.5°
36 (1.42)
24
970 (38.19)
509 (20.04)
1018 (40.08)
35 (1.38)
330 (728)
CE2
EN1092-1 PN16
700 800
700 (28)
H, F, U, D
800 (32)
960 (37.80)
1025 (40.35)
950 (37.40)
777 (30.59)
769 (30.28)
7.5°
39 (1.54)
24
900
Unit: mm (approx. in.)
900 (36)
10L
1000 (40)
1080 (42.52) 1200 (47.24)
1125 (44.29) 1255 (49.41)
1050 (41.34)
878 (34.57)
1170 (46.06)
976 (38.43)
870 (34.25)
6.4°
39 (1.54)
28
968 (38.11)
6.4°
42 (1.65)
28
1096 (43.15)
560 (22.05)
1196 (47.09) 1345 (52.95)
611 (24.06) 662 (26.06)
1127 (44.37) 1228 (48.37)
40 (1.57)
427 (941)
40 (1.57)
535 (1179)
1344 (52.91)
50 (1.97)
742 (1636)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(5) JIS 10K Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
675 (26.57)
620 (24.41)
477 (18.78)
469 (18.46)
9°
27 (1.06)
20
735 (28.94)
408 (16.06)
800 (31.50)
35 (1.38)
156 (344)
600
600 (24)
720 (28.35)
795 (31.30)
730 (28.74)
578 (22.76)
570 (22.44)
9°
33 (1.30)
20
855 (33.66)
459 (18.07)
911 (35.87)
35 (1.38)
223 (492)
CJ1
JIS B2220 10K
700
700 (28)
800
800 (32)
7.5°
33 (1.30)
24
35 (1.38)
H, F, U, D
840 (33.07)
905 (35.63)
840 (33.07)
675 (26.57)
667 (26.26)
965 (37.99)
509 (20.04)
1016 (40.00)
310 (683)
960 (37.80)
1020 (40.16)
950 (37.40)
777 (30.59)
769 (30.28)
6.4°
33 (1.30)
900
Unit: mm (approx. in.)
900 (36)
1080 (42.52) 1200 (47.24)
1120 (44.09) 1235 (48.62)
1050 (41.34) 1160 (45.67)
878 (34.57)
870 (34.25)
6.4°
33 (1.30)
10L
1000 (40)
976 (38.43)
968 (38.11)
6.4°
39 (1.54)
28
1091 (42.95)
28
560 (22.05) 611 (24.06)
1124 (44.25) 1225 (48.23)
28
1191 (46.89) 1325 (52.17)
662 (26.06)
1334 (52.2)
40 (1.57)
408 (899)
40 (1.57)
522 (1151)
50 (1.97)
689 (1519)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-10
(6) AS2129 Table D Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
705 (27.76)
641 (25.24)
477 (18.78)
469 (18.46)
11.3°
26 (1.02)
16
765 (30.12)
408 (16.06)
815 (32.09)
35 (1.38)
157 (346)
600
600 (24)
720 (28.35)
825 (32.48)
756 (29.76)
578 (22.76)
570 (22.44)
11.3°
30 (1.18)
16
885 (34.84)
459 (18.07)
926 (36.46)
35 (1.38)
225 (496)
700
CS1
800
700 (28)
H, F, U, D
800 (32)
840 (33.07)
910 (35.83)
845 (33.27)
675 (26.57)
667 (26.26)
9°
20
AS2129 Table D
30 (1.18)
970 (38.19)
509 (20.04)
1018 (40.08)
35 (1.38)
290 (639)
960 (37.80)
1060 (41.73)
984 (38.74)
777 (30.59)
769 (30.28)
9°
36 (1.42)
20
1080 (42.52) 1200 (47.24)
1175 (46.26) 1255 (49.41)
1131 (44.53) 1265 (49.80)
560 (22.05) 611 (24.06)
1144 (45.04)
40 (1.57)
433 (977)
900
24
Unit: mm (approx. in.)
900 (36)
1092 (42.99)
878 (34.57)
870 (34.25)
7.5°
36 (1.42)
1253 (49.33)
50 (1.97)
594 (1310)
10L
1000 (40)
1175 (46.26)
976 (38.43)
968 (38.11)
7.5°
36 (1.42)
24
1345 (52.95)
662 (26.06)
1344 (52.91)
50 (1.97)
728 (1605)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(7) AS2129 Table E Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining H, F, D
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
705 (27.76)
641 (25.24)
477 (18.78)
469 (18.46)
11.3°
26 (1.02)
16
765 (30.12)
408 (16.06)
815 (32.09)
35 (1.38)
184 (406)
600
600 (24)
720 (28.35)
825 (32.48)
756 (29.76)
578 (22.76)
570 (22.44)
11.3°
33 (1.30)
16
885 (34.84)
459 (18.07)
926 (36.46)
35 (1.38)
288 (635)
CS2
AS2129 Table E
700
700 (28)
900
900 (36)
50 (1.97)
703 (1550)
10L
1000 (40)
H, F, U, D
840 (33.07)
910 (35.83)
845 (33.27)
675 (26.57)
667 (26.26)
9°
33 (1.30)
20
970 (38.19)
960 (37.80)
1060 (41.73)
984 (38.74)
777 (30.59)
769 (30.28)
9°
36 (1.42)
20
1080 (42.52) 1200 (47.24)
1175 (46.26)
1092 (42.99)
878 (34.57)
870 (34.25)
7.5°
36 (1.42)
24
1131 (44.53) 1265 (49.80)
1255 (49.41)
1175 (45.67)
976 (38.43)
968 (38.11)
7.5°
39 (1.54)
24
1345 (52.95)
509 (20.04)
1018 (40.08)
35 (1.38)
354 (780)
800
800 (32)
560 (22.05) 611 (24.06)
1144 (45.04) 1253 (49.33)
40 (1.57)
508 (1120)
Unit: mm (approx. in.)
662 (26.06)
1344 (52.91)
50 (1.97)
832 (1834)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-11
(8) AS4087 PN16 Flange Type
Unit: mm (approx. in.)
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Lining H, F, D
Lining U
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
705 (27.76)
641 (25.24)
477 (18.78)
469 (18.46)
11.3°
26 (1.02)
16
765 (30.12)
408 (16.06)
815 (32.09)
35 (1.38)
184 (406)
600
600 (24)
720 (28.35)
825 (32.48)
756 (29.76)
578 (22.76)
570 (22.44)
11.3°
30 (1.18)
16
885 (34.84)
459 (18.07)
926 (36.46)
35 (1.38)
288 (635)
CT1
AS4087 PN16
700
700 (28)
H, F, U, D
840 (33.07)
910 (35.83)
845 (33.27)
675 (26.57)
667 (26.26)
9°
30 (1.18)
20
970 (38.19)
509 (20.04)
800
800 (32)
960 (37.80)
1060 (41.73)
984 (38.74)
777 (30.59)
769 (30.28)
9°
36 (1.42)
20
1131 (44.53)
560 (22.05)
1018 (40.08) 1144 (45.04)
35 (1.38) 40 (1.57)
374 (825) 520 (1146)
900
900 (36)
10L
1000 (40)
1080 (42.52) 1200 (47.24)
1175 (46.26) 1255 (49.41)
1092 (42.99)
878 (34.57)
870 (34.25)
7.5°
36 (1.42)
24
716 (1579)
1175 (45.67)
976 (38.43)
968 (38.11)
7.5°
36 (1.42)
24
1265 (49.80) 1345 (52.95)
611 (24.06) 662 (26.06)
1253 (49.33) 1344 (52.91)
50 (1.97) 50 (1.97)
826 (1821)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(9) JIS F12 (JIS 75M) Flange Type
Unit: mm (approx. in.)
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Inner
Diameter ød
Lining U
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H1
Height H2
Height Hr
Inner Diameter of Eye Bolt
Approx. Weight, Unit: kg (lb)
500
500 (20)
600 (23.62)
706 (27.80)
639 (25.16)
469 (18.46)
15°
27 (1.06)
12
766 (30.16)
408 (16.06)
816 (32.13)
35 (1.38)
168 (370)
600
600 (24)
720 (28.35)
810 (31.89)
743 (29.25)
570 (22.44)
11.3°
27 (1.06)
16
870 (34.25)
459 (18.07)
919 (36.18)
35 (1.38)
228 (503)
JIS G3443-2 F12
700
700 (28)
840 (33.07)
928 (36.54)
854 (33.62)
667 (26.26)
11.3°
33 (1.30)
16
988 (38.90)
509 (20.04)
CG1
U
800
800 (32)
960 (37.80)
1034 (40.71)
960 (37.80)
1028 (40.47) 1132 (44.57)
35 (1.38)
319 (703)
769 (30.28)
9°
33 (1.30)
20
1105 (43.50)
560 (22.05)
40 (1.57)
404 (891)
900
900 (36)
1080 (42.52)
1156 (45.51)
1073 (42.24)
870 (34.25)
9°
33 (1.30)
611 (24.06)
1245 (49.02)
40 (1.57)
540 (1190)
10L
1000 (40)
1200 (47.24)
1262 (49.69)
1179 (46.42)
968 (38.11)
7.5°
33 (1.30)
20 24
1227 (48.31) 1352 (53.23)
662 (26.06)
1349 (53.11)
50 (1.97)
703 (1550)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
Optional Grounding Rings (GR1) for sizes 500 mm (20 in.) to 1000 mm (40 in.)
ø25 (0.98)
6-12
øD
(ød)
Process Connection Code
Size Code
Size
Lining Code
Ring Outer Diameter øD
Ring Inner Diameter ød
Length L1
Length L2
Thickness
Approx. Weight, Unit: kg (lb)
500
500 (20)
590 (23.23)
485 (19.09)
410 (16.14)
390 (15.35)
3.1 (6.8)
L2
L1
F0604.ai
Unit: mm (approx. in.)
CA1, CB1, CE1, CE2, CJ1, CS1, CS2, CT1, CG1
600
600 (24)
700
700 (28)
800
800 (32)
900
900 (36)
10L
1000 (40)
690 (27.17)
586 (23.07)
3.7 (8.1)
H, F, U, D
799 (31.46)
683 (26.89)
477.5 (18.80) 517.5 (20.37)
457.5 (18.01) 497.5 (19.59)
906 (35.67)
787 (30.98)
586 (23.07)
566 (22.28)
4.6 (10.2)
4 (0.16)
5.4 (12.0)
1006 (39.61)
888 (34.96)
640 (25.20)
620 (24.41)
6.0 (13.3)
1116 (43.94)
986 (38.82)
697.5 (27.46)
677.5 (26.67)
7.3 (16.1)
IM 01E25D11-01EN
<6. OUTLINE>
AXW11L to AXW18L, Sizes 1100 mm (44 in.) to 1800 mm (72 in.)
Ground Terminal (M4)
Eye Plate
ø86 (3.38)
48 (1.89)
4-M8
(for Grounding Ring)
(Except for JIS F12 flange models)
111 (4.37)
θ°
N-øh
6-13
øC2 (M8)
øC1 (øh)
øD
(ød)
L (*)
T
*: The thickness of optional grounding rings (5 mm for GR1 and
25 mm for GR2 per one) and customer supplied gaskets are not included in “L” here.
F0605.ai
(1) AWWA Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Flange Bolt Circle Diameter øC1
Ring Bolt Circle Diameter øC2
Inner
Diameter ød
Lining H
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
Unit: mm (approx. in.)
CB1
AWWA C207 Class D
12L
1200 (48)
H
1440 (56.69)
1511.3 (59.50)
1422.4 (56.00)
1426 (56.14)
1189 (46.81)
4.1°
41.3 (1.625)
44
770 (30.31)
1580 (62.20)
60 (2.36)
930 (2050)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-14
(2) EN PN6 Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
12L
1200 (48) 1400 (56)
CEJ
EN1092-1 PN6
14L 16L
Unit: mm (approx. in.)
1600 (64)
18L
1800 (72)
H
1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04)
1405 (55.31) 1630 (64.17) 1830 (72.05) 2045 (80.51)
Flange Bolt Circle Diameter øC1 1340 (52.76) 1560 (61.42) 1760 (69.29) 1970 (77.56)
Ring Bolt Circle Diameter øC2 1356 (53.39) 1572 (61.89) 1772 (69.76) 1981 (77.99)
Inner
Diameter ød
Lining H
Bolt Hole Pitch Half Angle θ
1195 (47.05) 1398 (55.04) 1586 (62.44) 1784 (70.24)
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
5.6°
33 (1.30)
32
770 (30.31)
1527 (60.12)
60 (2.36)
620 (1367)
5°
36 (1.42)
36
873 (34.37)
1742 (69.49)
70 (2.76)
920 (2028)
4.5°
36 (1.42)
40
969 (38.15)
1938 (76.30)
70 (2.76)
1310 (2888)
4.1°
39 (1.54)
44
1068 (42.05)
2145 (84.45)
80 (3.15)
1670 (3682)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(3) EN PN10 Flange Type (fluid pressure up to 0.6 MPa)
Process Connection Code
Flange Type
Size Code
Size
12L
1200 (48)
Unit: mm (approx. in.)
CEK
EN1092-1 PN10
14L
1400 (56)
16L
1600 (64)
18L
1800 (72)
Lining Code
Lay Length L
H
1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04)
Flange Outer Diameter øD 1455 (57.28) 1675 (65.94) 1915 (75.39) 2115 (83.27)
Flange Bolt Circle Diameter øC1 1380 (54.33) 1590 (62.60) 1820 (71.65) 2020 (79.53)
Ring Bolt Circle Diameter øC2
Inner
Diameter ød
Lining H
1391 (54.76) 1596 (62.83) 1822 (71.73) 2022 (79.61)
1195 (47.05) 1398 (55.04) 1586 (62.44) 1784 (70.24)
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
5.6°
39 (1.54)
32
770 (30.31)
1552 (61.10)
60 (2.36)
790 (1742)
5°
42 (1.65)
36
873 (34.37)
1765 (69.49)
70 (2.76)
1120 (2469)
4.5°
48 (1.89)
40
969 (38.15)
1981 (77.99)
70 (2.76)
1720 (3792)
4.1°
48 (1.89)
44
1068 (42.05)
2180 (85.83)
80 (3.15)
2130 (4696)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-15
(4) EN PN10 Flange Type
Unit: mm (approx. in.)
Process Connection Code
Flange Type
CE1
EN1092-1 PN10
Size Code
Size
Lining Code
12L
1200 (48)
14L
1400 (56)
16L
1600 (64)
18L
1800 (72)
H
1440 (56.69) 1680 (66.14) 1920 (75.59) 2160 (85.04) Lay Length L
Flange Outer Diameter øD
Flange Bolt Circle Diameter øC1 1380 (54.33) 1590 (62.60) 1820 (71.65) 2020 (79.53)
Ring Bolt Circle Diameter øC2 1391 (54.76) 1596 (62.83) 1822 (71.73) 2022 (79.61)
Inner
Diameter ød
Lining H
1455 (57.28) 1675 (65.94) 1915 (75.39)
1189 (16.81) 1390 (54.72) 1582 (62.28)
2115 (83.27)
1776 (69.92)
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
5.6°
39 (1.54)
32
770 (30.31)
5°
42 (1.65)
36
873 (34.37)
4.5°
48 (1.89)
40
969 (38.15)
4.1°
48 (1.89)
44
1068 (42.05)
1552 (61.10) 1765 (69.49) 1981 (77.99) 2180 (85.83)
60 (2.36) 70 (2.76) 70 (2.76) 80 (3.15)
920 (2028) 1340 (2954) 1860 (4101) 2510 (5534)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
(5) AS2129 Table D, AS2129 Table E, AS4087 PN16 Flange Type
Process Connection Code CS1 CS2
Unit: mm (approx. in.)
CT1
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Flange Bolt Circle Diameter øC1
Ring Bolt Circle Diameter øC2
Inner
Diameter ød
Lining H
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
AS2129 Table D AS2129 Table E
12L 12L
1200 (48) 1200 (48)
H
1440 (56.69)
1490 (58.66)
1410 (55.51)
1426 (56.14)
1440 (56.69)
1490 (58.66)
1410 (55.51)
1426 (56.14)
1189 (46.81)
5.6°
36 (1.42)
32
770 (30.31)
1570 (61.81)
60 (2.36)
1050 (2315)
1189 (46.81)
5.6°
39 (1.54)
32
770 (30.31)
1570 (61.81)
60 (2.36)
1210 (2668)
AS4087 PN16
12L
1200 (48)
1440 (56.69)
1490 (58.66)
1410 (55.51)
1426 (56.14)
1189 (46.81)
5.6°
36 (1.42)
32
770 (30.31)
1570 (61.81)
60 (2.36)
1180 (2601)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
6-16
(6) JIS F12 (JIS 75M) Flange Type
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Lay Length L
Flange Outer Diameter øD
Bolt Circle Diameter øC
Grounding
Ring Inner
Diameter ød
Lining U
Unit: mm (approx. in.)
CG1
JIS G3443-2 F12
11L
1100 (44)
12L
1200 (48)
13L
1350 (54)
15L
1500 (60)
16L
1600 (64)
18L
1800 (72)
U
1320 (51.97) 1440 (56.69) 1620 (63.78) 1800 (70.87) 1920 (75.59) 2160 (85.04)
1366 (53.78) 1470 (57.87) 1642 (64.65) 1800 (70.87) 1915 (75.39) 2115 (83.27)
1283 (50.51) 1387 (54.61) 1552 (61.10) 1710 (67.32) 1820 (71.65) 2020 (79.53)
1071 (42.17) 1172 (46.14) 1322 (52.05) 1469 (57.83) 1565 (61.61) 1759 (69.25)
Bolt Hole Pitch Half Angle θ
Bolt Hole Diameter øh
Number of Bolt Holes N
Height H2
Height Hr
Inner Diameter of Eye Plate
Approx. Weight, Unit: kg (lb)
7.5°
33 (1.30)
24
6.4°
33 (1.30)
28
6.4°
39 (1.54)
28
5.6°
39 (1.54)
32
5°
39 (1.54)
36
4.1°
39 (1.54)
44
720 (28.35) 770 (30.31) 873 (34.37) 921 (36.26) 969 (38.15) 1068 (42.05)
1457 (57.36) 1560 (61.42) 1723 (67.83) 1875 (73.82) 1981 (77.99) 2180 (85.83)
60 (2.36)
910 (2006)
60 (2.36)
1060 (2337)
70 (2.76)
1430 (3153)
70 (2.76)
1770 (3902)
70 (2.76)
2090 (4608)
80 (3.15)
2890 (6371)
Note: When submersible type or option code DHC is selected, waterproof glands and a 30-meter length cable are attached. Add 9.5 kg
(20.9 lb) to the weight in the table.
IM 01E25D11-01EN
<6. OUTLINE>
Optional Grounding Rings (GR1) for sizes 1200 mm (48 in.) to 1800 mm (72 in.)
ø35 (1.38)
6-17
øD
øC
(ød)
ø11 (0.43)
L1 L1
F0606.ai
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Ring Outer Diameter øD
CB1, CS1,
CS2,CT1
AWWA C207-D
AS2129-D,E
AS4087 PN16
12L
1200
(48)
Ring Inner Diameter ød
Bolt Circle Diameter øC
Length L1
1370
(53.94)
1195
(47.05)
1426
(56.14)
735
(28.94)
815
(32.09)
Length L2
Thickness
Approx. Weight,
Unit: kg (lb)
14.6
(32.2)
12L
1200
(48)
1300
(51.18)
1201
(47.28)
1356
(53.39)
700
(27.56)
780
(30.71)
8.2
(18.1)
CEJ
EN PN6
14L
1400
(56)
1516
(59.69)
1404
(55.28)
1572
(61.89)
808
(31.81)
888
(34.96)
10.7
(23.6)
16L
1600
(64)
18L
1800
(72)
H
1925
(75.79)
1716
(67.56)
1592
(62.68)
1772
(69.76)
908
(35.75)
988
(38.90)
1790
(70.47)
1981
(77.99)
1012.5
(39.86)
1092.5
(43.01)
13.3
(29.3)
5 (0.20)
16.2
(35.7)
12L
1200
(48)
1335
(52.56)
1195
(47.05)
1391
(54.76)
717.5
(28.25)
797.5
(31.40)
11.6
(25.6)
Unit: mm (approx. in.)
CEK, CE1
EN PN10
14L
1400
(56)
16L
1600
(64)
18L
1800
(72)
1540
(60.63)
1396
(54.96)
1596
(62.83)
820
(32.28)
900
(35.43)
1766
(69.53)
1588
(62.52)
1822
(71.73)
933
(36.73)
1013
(39.88)
1966
(77.40)
1782
(70.16)
2022
(79.61)
1033
(40.67)
1113
(43.82)
13.7
(30.2)
19.2
(42.3)
22.1
(48.7)
IM 01E25D11-01EN
<6. OUTLINE>
Optional Grounding Rings (GR2) for sizes 1100 mm (44 in.) to 1800 mm (72 in.)
Unit: mm (approx. in.)
Process Connection Code
Flange Type
Size Code
Size
Lining Code
Thickness
Approx. Weight,
Unit: kg (lb)
11L
1100
(44)
59.3
(131)
12L
1200
(48)
65.7
(145)
CG1
JIS F12 (JIS 75M)
13L
1350
(54)
15L
1500
(60)
U
25 (0.98)
75.8
(167)
88.3
(195)
16L
1600
(64)
92.4
(204)
18L
1800
(72)
114.2
(252)
*: Optional grounding rings (GR2) have no protruding brackets and are installed and locked onto the flowtube with gaskets B when shipped from factory. Refer to “CAUTIONS FOR INSTALLATION”.
6-18
IM 01E25D11-01EN
Note: Unless otherwise specified, refer to the following table for tolerance in the dimensions.
<6. OUTLINE>
6-19
General tolerance in the dimensional outline drawing.
Unit: mm (approx. in.)
Category of basic dimension
Above
3 (0.12)
6 (0.24)
10 (0.39)
18 (0.71)
30 (1.18)
50 (1.97)
80 (3.15)
120 (4.72)
180 (7.09)
250 (9.84)
315 (12.40)
400 (15.75)
Equal or below
3 (0.12)
6 (0.24)
10 (0.39)
18 (0.71)
30 (1.18)
50 (1.97)
80 (3.15)
120 (4.72)
180 (7.09)
250 (9.84)
315 (12.40)
400 (15.75)
500 (19.69)
Tolerance
±0.7 (±0.03)
±0.9 (±0.04)
±1.1 (±0.04)
±1.35 (±0.05)
±1.65 (±0.06)
±1.95 (±0.08)
±2.3 (±0.09)
±2.7 (±0.11)
±3.15 (±0.12)
±3.6 (±0.14)
±4.05 (±0.16)
±4.45 (±0.18)
±4.85 (±0.19)
Category of basic dimension
Above
500 (19.69)
630 (24.80)
800 (31.50)
1000 (39.37)
1250 (49.21)
1600 (62.99)
2000 (78.74)
2500 (98.43)
Equal or below
630 (24.80)
800 (31.50)
1000 (39.37)
1250 (49.21)
1600 (62.99)
2000 (78.74)
2500 (98.43)
3150 (124.02)
Remarks: The numeric is based on criteria of tolerance class IT18 in JIS B 0401.
n
SIZING DATA
Note: Measurable flow velocity is from 0 m/s.
10.0
SI Units
Tolerance
±5.5 (±2.17)
±6.25 (±0.25)
±7.0 (±0.28)
±8.25 (±0.32)
±9.75 (±0.38)
±11.5 (±0.45)
±14.0 (±0.55)
±16.5 (±0.65)
Size: mm
500 600 700 800 900100
0
13501400150016001800
1.0
0.3
0.1
10 100 1,000
Flowrate (m 3 /h)
English Units
10,000
20 24 28 32 36 40 44 48 54 56 64 72
100,000
F0607.ai
Size: inch
33
10
1
0.33
10 100 1,000
Flowrate (GPM)
10,000 100,000 1,000,000
F0608.ai
IM 01E25D11-01EN
Blank Page
Revision Information
Title : AXW Magnetic Flowmeter Remote Flowtube
Manual No. : IM 01E25D11-01EN
1st
Edition
2nd
Data
Mar. 2012
Sep. 2013
Page
–
–
Revised Item
New publication
Addition of sizes from 1100 mm (44 in.) to 1800 mm (72 in.).
Addition of lining material and flange standard.
i
IM 01E25D11-01EN
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 INTRODUCTION
- 7 Using the Magnetic Flowmeter Safely
- 7 Warranty
- 7 Combination Remote Converters
- 8 HANDLING PRECAUTIONS
- 8 Checking Model and Specifications
- 8 Storage Precautions
- 8 Installation Location Precautions
- 9 INSTALLATION
- 9 Piping Design Precautions
- 9 Handling Precautions
- 9 General Precautions
- 9 Flowmeter Piping
- 9 Mounting Procedures
- 10 WIRING
- 10 Wiring the Remote Flowtube
- 10 Wiring Precautions
- 10 Cables
- 10 Wiring Ports
- 10 Wiring Connections
- 11 MAINTENANCE
- 11 Changing Direction of Electrical Connection
- 11 Regular Inspection Items
- 11 Excitation Coil and Insulation Resistance Check
- 11 Troubleshooting
- 11 No Indication
- 11 Unstable Zero
- 11 Disagreement Between Indication and Actual Flow
- 12 OUTLINE
- 12 STANDARD SPECIFICATIONS
- 12 STANDARD PERFORMANCE
- 12 NORMAL OPERATING CONDITIONS
- 12 MODEL AND SUFFIX CODE