FX1S Series Programmable Controllers Hardware Manual

FX1S Series Programmable Controllers Hardware Manual

HARDWARE MANUAL

FX

1S

SERIES PROGRAMMABLE CONTROLLERS

FX1S Series Programmable Controllers

Foreword

• This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX

1S

Series Programmable Controllers. It should be read and understood before attempting to install or use the unit.

• Further information can be found in the FX Series Programming Manual II.

• If in doubt at any stage of the installation of an FX

1S

Series Programmable Controller always consult a professional electrical engineer who is qualified and trained to the local and national standards which apply to the installation site.

• If in doubt about the operation or use of FX

1S

Series Programmable Controller please consult the nearest

Mitsubisi Electric distributor.

• This manual is subject to change without notice.

FX1S Series Programmable Controllers

FX

1S

Series Programmable Controllers

Hardware Manual

Manual number : JY992D83901

Manual revision : E

Date : June 2001

i

FX1S Series Programmable Controllers

Guidelines for the Safety of the User and Protection of the FX

1S

.

This manual provides information for the use of the FX

1S

. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows: a) Any engineer who is responsible for the planning, design and construction of automatic equipment using the product associated with this manual, should be of a competent nature, trained and qualified to the local and national standards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to automated equipment.

b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely familiar with all associated documentation for said product. All maintenance should be carried out in accordance with established safety practices.

c) All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected with the actual operation of the completed equipment.

Note : The term ‘completed equipment’ refers to a third party constructed device which

contains or uses the product associated with this manual.

ii

FX1S Series Programmable Controllers

Notes on the Symbols Used in this Manual

At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the user’s personal safety and protect the integrity of equipment. Whenever any of the following symbols are encountered its associated note must be read and understood. Each of the symbols used will now be listed with a brief description of its meaning.

Hardware Warnings

1) Indicates that the identified danger WILL cause physical and property damage.

2) Indicates that the identified danger could POSSIBLY cause physical and property damage.

3) Indicates a point of further interest or further explanation.

Software Warnings

4) Indicates special care must be taken when using this element of software.

5) Indicates a special point which the user of the associate software element should be aware.

6) Indicates a point of interest or further explanation.

iii

FX1S Series Programmable Controllers

• Under no circumstances will Mitsubishi Electric be liable for any consequential damage that may arise as a result of the installation or use of this equipment.

• All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.

• Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.

iv

FX1S Series Programmable Controllers

Table of Contents

Guideline ..............................................................................................ii

1. Introduction............................................................................................1-1

1.1

Model Name ........................................................................................................ 1-4

1.2

World Specification .............................................................................................. 1-5

1.3

Serial Numbers .................................................................................................... 1-5

1.4

Configuration ....................................................................................................... 1-6

1.4.1 Unit Accessories........................................................................................................ 1-7

1.4.2 Limits of Expansion ................................................................................................... 1-8

1.5

Backup Data ........................................................................................................ 1-9

1.5.1 Data Backup .............................................................................................................. 1-9

1.5.2 Capacitor backup ...................................................................................................... 1-9

2. Terminal Layouts ...................................................................................2-1

2.1

FX1S-**MR-ES/UL .............................................................................................. 2-1

2.2

FX1S-**MR-DS .................................................................................................... 2-2

2.3

FX1S-**MT-DSS .................................................................................................. 2-3

2.4

FX1S-**MT-ESS/UL ............................................................................................ 2-4

v

FX1S Series Programmable Controllers

3. Installation Notes ...................................................................................3-1

3.1

Product Outline .................................................................................................... 3-2

3.2

FX

1S

RUN/STOP Control .................................................................................... 3-3

3.3

General Specifications......................................................................................... 3-4

3.4

PLC Mounting Arrangements .............................................................................. 3-5

3.5

DIN Rail Mounting ............................................................................................... 3-6

3.6

Termination of Screw Terminals .......................................................................... 3-6

3.7

Installing Optional Units ....................................................................................... 3-7

3.7.1 Special Function Boards ........................................................................................... 3-7

3.7.2 FX1N-5DM Display Module ....................................................................................... 3-8

4. Power Supply ........................................................................................4-1

4.1

Wiring Techniques ............................................................................................... 4-1

4.2

Wiring Cautions ................................................................................................... 4-1

4.3

Power Supply ...................................................................................................... 4-1

4.4

Power Supply Characteristics.............................................................................. 4-2

4.5

Power Supply Input Wiring .................................................................................. 4-3

4.6

Earthing / Grounding ........................................................................................... 4-5

vi

FX1S Series Programmable Controllers

5. Inputs.....................................................................................................5-1

5.1

24V DC Input Specifications ................................................................................ 5-1

5.2

Wiring Diagrams .................................................................................................. 5-2

5.2.1 Input Wiring ............................................................................................................... 5-2

5.2.2 Input Circuit Connection ............................................................................................ 5-3

5.2.3 Diodes and Inputs Connected in Series .................................................................... 5-3

5.2.4 Resistors and Inputs Connected in Parallel .............................................................. 5-4

6. Outputs ..................................................................................................6-1

6.1

Relay Output Example......................................................................................... 6-2

6.2

Reliability Tests ................................................................................................... 6-3

6.3

Response Times.................................................................................................. 6-4

6.4

Transistor Output Examples ................................................................................ 6-5

6.5

Applying Safe Loads............................................................................................ 6-6

vii

FX1S Series Programmable Controllers

7. Diagnostics ............................................................................................7-1

7.1

Preliminary Checks.............................................................................................. 7-1

7.2

ERROR LED ON (CPU ERROR) ........................................................................ 7-2

7.3

Common Errors ................................................................................................... 7-3

7.4

Maintenance ........................................................................................................ 7-3

7.5

Operation and Error Flags ................................................................................... 7-4

7.6

PLC Status Registers .......................................................................................... 7-5

7.7

Error Registers .................................................................................................... 7-6

7.8

Error Codes ......................................................................................................... 7-7

7.9

Instruction List ..................................................................................................... 7-8

7.10 Device List ......................................................................................................... 7-11

viii

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Introduction 1

FX1S Series Programmable Controllers

Introduction 1

FX1S Series Programmable Controllers

1.

Introduction

Introduction 1

This manual covers the hardware installation instructions for the FX

1S

Series Programmable

Logic Controller.

Table 1.1: AC Power, Relay Output Units

MODEL

FX1S-10MR-ES/UL

FX1S-14MR-ES/UL

FX1S-20MR-ES/UL

INPUT OUTPUT

QTY TYPE QTY TYPE

6 4

8 6

12

24V DC

Sink /

Source

8

Relay

FX1S-30MR-ES/UL 16 14

POWER

SUPPLY

85 - 264

VAC

DIMENSIONS mm (inches)

60

(2.4)

75

(3.0)

100

(3.9)

90

(3.5)

75

(3.0)

MASS (WEIGHT) kg (lbs)

0.30

(0.66)

0.40

(0.88)

0.45

(0.99)

Table 1.2: DC Power, Relay Output Units

MODEL

FX1S-10MR-DS

FX1S-14MR-DS

FX1S-20MR-DS

FX1S-30MR-DS

INPUT OUTPUT

QTY TYPE QTY TYPE

6

8

4

6

12

24V DC

Sink /

Source

8

Relay

16 14

POWER

SUPPLY

DIMENSIONS mm (inches)

24 VDC

+10, -15%

60

(2.4)

75

(3.0)

100

(3.9)

90

(3.5)

49

(1.9)

MASS (WEIGHT) kg (lbs)

0.22

(0.48)

0.30

(0.66)

0.35

(0.77)

1-1

FX1S Series Programmable Controllers

Table 1.3: DC Power Transistor Output Units

INPUT OUTPUT

MODEL

QTY TYPE QTY TYPE

FX1S-10MT-DSS

FX1S-14MT-DSS

6

8

4

6

FX1S-20MT-DSS 12

24V DC

Sink /

Source

8

POWER

SUPPLY

Transistor

(Source)

24 VDC

+10, -15%

FX1S-30MT-DSS 16 14

DIMENSIONS mm (inches)

60

(2.4)

75

(3.0)

100

(3.9)

90

(3.5)

49

(1.9)

Introduction 1

MASS

(WEIGHT) kg (lbs)

0.22

(0.48)

0.30

(0.66)

0.35

(0.77)

Table 1.4: AC Power Transistor Output Units

INPUT OUTPUT

MODEL

QTY TYPE QTY TYPE

FX1S-10MT-ESS/UL

FX1S-14MT-ESS/UL

6

8

4

6

FX1S-20MT-ESS/UL 12

24V DC

Sink /

Source

8

Transistor

(Source)

FX1S-30MT-ESS-UL 16 14

POWER

SUPPLY

85 - 264

VAC

DIMENSIONS mm (inches)

60

(2.4)

75

(3.0)

100

(3.9)

90

(3.5)

75

(3.0)

MASS

(WEIGHT) kg (lbs)

0.3

(0.66)

0.4

(0.88)

0.45

(0.99)

1-2

FX1S Series Programmable Controllers

Figure 1.1: FX

1S

Outline Drawing

W

W 8

75 (ES/UL) / 49 (DS, DSS)

L N

S/S

X0

X1

X2

X3

X4

X5

X6

X7

0 1

4 5

2 3

6 7

IN

24V

0V

COM0

Y0

COM1

Y1

COM2

Y2

Y3

Y4

Y5

POWER

RUN

ERROR

FX

1S

14MR

0 1

OUT

2 3

4 5

82 90

Introduction 1

2

φ

4.5

The distance between the vertical centerlines is 8mm (0.31”) less than the width of the unit.

Please see previous page for each model’s width measurement.

1-3

FX1S Series Programmable Controllers

1.1

Model Name

A)

B)

C)

F X

1 S

- 1 4 M R - E S / U L

Introduction 1

F)

E)

D)

Table 1.5: Model Table

C)

A)

PLC type: FX

1S

B)

Total number of I / O channels

Unit type

M MPU - main unit

D)

Output type

R Relay

T Transistor

E)

Features

Omit AC Power Supply, Japanese specification

D DC Power Supply, Japanese specification

DS

DC Power Supply, World specification, Relay Output, CE & UL Registered

DSS

DC Power Supply, World specification, DC source transistor output, CE & UL Registered

ES

ESS

AC Power Supply, World specification, relay output

AC Power Supply, World Specification, DC Source

Transistor Output

F)

UL CE, UL registered product

1-4

FX1S Series Programmable Controllers

1.2

1.3

World Specification

Table 1.6: World / Japanese Specifications

Input

Sink / Source

Outputs

Transistor

World spec models : SINK / SOURCE

Japanese models : ALWAYS SINK

World spec models : ALWAYS SOURCE

Japanese models : ALWAYS SINK

Serial Numbers

S E R I A L N O . : 9 X 3 2 6 7

1) e.g.

9=1999

0=2000

2)

1 - 9 = Jan - Sept

X = Oct

Y = Nov

Z = Dec

3)

Table 1.7: Notes on Serial Numbers

1)

2)

3)

Production year

Production month

Production serial number

Introduction 1

1-5

FX1S Series Programmable Controllers

1.4

Configuration

Figure 1.2: Schematic System

FX

1N

-5DM

FX

1N

-EEPROM-8L

B

1

FX

1N

-232-BD

FX

1N

-422-BD

FX

1N

-485-BD

FX

1N

-CNV-BD

FX1N-8AV-BD

FX

1N

-2AD-BD **

FX

1N

-1DA-BD **

FX

1N

-4EX-BD **

FX

1N

-2EYT-BD **

C

FX

0N

-232ADP *

FX

0N

-485ADP *

D

RS 422/RS 232 CONVERTER

FX-232AW(C)

E

1

FX

1S

-10MR-ES/UL FX

1S

-10MT-ESS/UL

FX

1S

-14MR-ES/UL FX

1S

-14MT-ESS/UL

FX

1S

-20MR-ES/UL FX

1S

-20MT-ESS/UL

FX

1S

-30MR-ES/UL FX

1S

-30MT-ESS/UL

2

FX

1S

-10MR-DS

FX

1S

-14MR-DS

FX

1S

-20MR-DS

FX

1S

-30MR-DS

FX

1S

-10MT-DSS

FX

1S

-14MT-DSS

FX

1S

-20MT-DSS

FX

1S

-30MT-DSS

3

A

FX-10DU-E FX-40DU-ES

FX-20DU-E FX-40DU-TK -ES

FX-25DU-E FX-50DU-TKS-E

FX-30DU-E

F930GOT F940GOT

FX-10DM-E

G

FX-10P-E

FX-20P-E

GX-Developer

MELSEC MEDOC PLUS

FX-PCS/WIN-E

MELSEC MEDOC

FX-PCS/AT-EE

F

* Us ed with FX

1N

-CNV-BD

** Available for us e with

FX1S Vers ion 2.00 or above

H

Introduction 1

Note: The FX

1S can use one unit or communication board per square B or C, and G. To use equipment from square B and C - install module, use as required, remove and install next module.

1-6

FX1S Series Programmable Controllers

1.4.1

Unit Accessories

Table 1.8: Configuration Notes

A FX

1S

Controller Main Body

B FX

1N

Memory Cassette or Display Unit

C FX

1N

Expansion Boards

D FX

0N

Network Adaptors

E Programming Cables

F Programming Software

G HMI Devices, F900 GOT and FX-DU Series

H Dedicated Programming Tools

Table 1.9: Connection Ports

1

Memory Port

2

Extension Board Port

3

Programming Port

Introduction 1

1-7

FX1S Series Programmable Controllers

Introduction 1

1.4.2

Limits of Expansion

The following conditions cannot be accomplished the FX

1S

Series PLC:

The use of Special Function Blocks.

Supply a 5V DC service supply.

Use FX

1N

-422-BD + FX-2PIF.

Use the FX

1N

-5DM and the FX-10DM concurrently.

Use more than one FX-10DM at the same time. For example, the configuration

FX-10DM + (FX

1N

-422-BD + FX-10DM) is not allowed.

1-8

FX1S Series Programmable Controllers

Introduction 1

1.5

Backup Data

1.5.1

Data Backup

Data includes the Program, Comment, File Register (D1000 ~ D2499), and parameter data.

This will be stored as long as the EEPROM is not damaged.

If the PLC has been powered up for five minutes or more, the following data will be saved in the EEPROM at powerdown:

S10~S127, M384 ~ M511, C16 ~ C31, T63, and D128 ~ D255.

If the PLC is powered On for less than 5 minutes, the above data is not saved!

1.5.2

Capacitor backup

Only the RTC is backed up by the capacitor.

The capacitor backed memory will retain data for 10 days and the capacitor requires 30 minutes to recharge upon powerup.

1-9

FX1S Series Programmable Controllers

Introduction 1

1-10

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Terminal layouts 2

FX1S Series Programmable Controllers

Terminal layouts 2

FX1S Series Programmable Controllers

2.

Terminal Layouts

2.1

Terminal Layouts 2

The following selection of terminal layouts are taken from the FX

1S product range.

Note: All layouts are diagrammatic only and are intended to aid the creation of wiring diagrams.

FX

1S

-**MR-ES/UL

Figure 2.1: Terminal Layouts, Relay Outputs, AC Power

L

S/S X1

N X0 X2

X3

X4

X5

FX

1S

-10MR-ES/UL

0V

Y0 Y1 Y2 Y3

24V

COM0 COM1 COM2 COM3

L

S/S X1

N X0 X2

X3 X5

X4 X6

X7

FX

1S

-14MR-ES/UL

24V

0V Y0 Y1 Y2 Y4

COM0 COM1 COM2

Y3 Y5

L

S/S

N X0

X1

X2

X3 X5

X4 X6

X7 X11 X13

X10 X12

FX

1S

-20MR-ES/UL

0V Y0 Y1 Y2

24V

COM0 COM1 COM2

Y3 Y4

COM3 COM4

Y5

Y6

Y7

L N

S/S S/S

S/S

X0

X1 X3 X5

X2 X4 X6

X7 X11

X10

X13 X15

X12

X17

X14 X16

FX

1S

-30MR-ES/UL

24V

0V Y0 Y1 Y2 Y4

COM0 COM1 COM2

COM3

Y3 Y5 Y6

Y7 Y11

Y10

Y12

COM4

Y14

Y13 Y15

2-1

FX1S Series Programmable Controllers

2.2

FX

1S

-**MR-DS

Figure 2.2: Terminal Layouts, Relay Outputs, DC Power

+

S/S

X0

X1

X2

X3

X4

X5

+

Terminal Layouts 2

S/S

X0

X1

X2

X3 X5

X4 X6

X7 X11 X13

X10 X12

FX

1S

-10MR-DS

FX

1S

-20MR-DS

Y0 Y1 Y2 Y3

COM0 COM1 COM2 COM3

Y0 Y1 Y2 Y3 Y4

COM0 COM1 COM2 COM3 COM4

Y5

Y6

Y7

+

S/S

X0

X1

X2

X3 X5

X4 X6

X7

FX

1S

-14MR-DS

Y0 Y1 Y2 Y4

COM0 COM1 COM2

Y3 Y5

+

S/S S/S

-

S/S

X0

X1 X3

X2 X4

X5

X6

X7 X11

X10

X13 X15

X12

X17

X14 X16

FX

1S

-30MR-DS

Y0 Y1 Y2 Y4

COM0 COM1 COM2

COM3

Y3 Y5 Y6

Y7 Y11

Y10

Y12

COM4

Y14

Y13 Y15

2-2

FX1S Series Programmable Controllers

2.3

FX

1S

-**MT-DSS

Figure 2.3: Terminal Layouts, Transistor Outputs, DC Power

+

S/S

X0

X1

X2

X3

X4

X5

+

Terminal Layouts 2

S/S

X0

X1

X2

X3 X5

X4 X6

X7 X11 X13

X10 X12

FX

1S

-10MT-DSS

FX

1S

-20MT-DSS

Y0 Y1 Y2 Y3

+V0 +V1 +V2 +V3

Y0 Y1 Y2 Y3

+V0 +V1 +V2 +V3 +V4

Y4

Y5

Y6

Y7

+

S/S

X0

X1

X2

X3 X5

X4 X6

X7

FX

1S

-14MT-DSS

Y0 Y1 Y2 Y4

+V0 +V1 +V2

Y3 Y5

+

S/S S/S

-

S/S

X0

X1 X3

X2 X4

X5

X6

X7 X11

X10

X13 X15

X12

X17

X14 X16

FX

1S

-30MT-DSS

Y0 Y1 Y2 Y4

+V0 +V1 +V2

Y3 Y5

+V3

Y6

Y7 Y11

Y10

Y12

+V4

Y14

Y13 Y15

2-3

FX1S Series Programmable Controllers

2.4

FX1S-**MT-ESS/UL

Terminal Layouts 2

Figure 2.4: Terminal Layouts, Transistor Outputs, AC Power

L

S/S X1

N X0 X2

X3

X4

X5

L

S/S

N X0

X1

X2

X3 X5

X4 X6

X7 X11 X13

X10 X12

FX

1S

-20MT-ESS/UL

FX

1S

-10MT-ESS/UL

0V Y0 Y1 Y2 Y3

24V +V0 +V1 +V2 +V3

0V Y0 Y1 Y2 Y3

24V +V0 +V1 +V2 +V3 +V4

Y4

Y5

Y6

Y7

L

S/S X1

N X0 X2

X3 X5

X4 X6

X7

FX

1S

-14MT-ESS/UL

0V Y0 Y1 Y2 Y4

24V +V0 +V1 +V2 Y3 Y5

L

S/S S/S

N S/S X0

X1 X3

X2 X4

X5

X6

X7 X11

X10

X13 X15

X12

X17

X14 X16

FX

1S

-30MT-ESS/UL

0V Y0 Y1 Y2 Y4

24V +V0 +V1 +V2 Y3 Y5

+V3

Y6

Y7 Y11

Y10

Y12

+V4

Y14

Y13 Y15

2-4

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Installation notes 3

FX1S Series Programmable Controllers

Installation notes 3

FX1S Series Programmable Controllers

3.

Installation Notes

Installation Notes 3

The installation of FX

1S products has been designed to be safe and easy. When the products associated with this manual are used as a system or individually, they must be installed in a suitable enclosure. The enclosure should be selected and installed in accordance to the local and national standards.

3-1

FX1S Series Programmable Controllers

3.1

Product Outline

Figure 3.1: Features of the FX

1S

PLC

➀ ➁

Installation Notes 3

100 - 240

VAC L N

S/S

X0

X1

X2

X3

X4

X5

X6

X7

0 1 2 3

4 5 6 7

IN

POWER

RUN

ERROR

24V

0V

COM0

Y0

COM1

Y1

COM2

Y2

Y3

Y4

Y5

FX

1S

-14MR

0 1

OUT

2 3

4 5

14MR

- ES/UL

11

100 - 240

VAC L N

S/S

X0

X1

X2

X3

X4

X5

X6

X7

0 1 2 3

4 5 6 7

IN

POWER

RUN

ERROR

24V

0V

COM0

Y0

COM1

Y1

COM2

Y2

Y3

Y4

Y5

FX

1S

-14MR

0 1

4 5

OUT

2 3

14MR

- ES/UL

12

➂ ➆ ➀

Table 3.1: Feature Table

1

Direct Mounting Holes (4.5 mm Diameter)

2

3

4

Input LED Status Indicators

5

Input Terminals (24V DC) and Power Supply

Terminals

Output Terminals and Power Supply Source

Terminals

Output LED Status Indicators

7

8

9

DIN Rail Mounting Clip

Top Cover

Optional Equipment port - Memory Cassette, FX

1N

-

232, 422, 485, 8AV, and CNV BDs, FX

1N

-5DM

10

Programming Port

11

Analog Trim Pots. D8030 read from VR1, the top trim pot. D8031 read from VR2, the bottom trim pot.

6

PLC Status Indicators (POWER, RUN, ERROR) 12 Run/Stop Switch

3-2

FX1S Series Programmable Controllers

3.2

Installation Notes 3

FX

1S

RUN/STOP Control

RUN or STOP of the FX

1S can be controlled by:

Œ

The RUN/STOP switch mounted next to the programming port.



A standard input (X0 to X17) defined by the system parameters.

Ž

Remotely from a personal computer or other programming peripheral.

Note:The FX

1S

RUN/STOP switch works in parallel with the RUN input terminal. Please refer to Table 3.2.

During remote operation the FX

1S

RUN/STOP status is determined by the most recently operated control.

E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal computer, the PLC can only be restarted with the RUN/STOP switch by first moving the switch to STOP and then back to RUN.

Figure 3.2: RUN/STOP Input Wiring Diagram

RUN

S/S 0V 24V X0 X1 X2

Table 3.2: Run Status Table

Œ

RUN/STOP

SWITCH



RUN INPUT

TERMINAL

ü

ü

û

û

ü

û

û

ü

FX

1S

MPU

STATUS

RUN

RUN

STOP

RUN

3-3

FX1S Series Programmable Controllers

3.3

General Specifications

Installation Notes 3

Table 3.3: General Specifications

Item

Operating Temperature

Storage Temperature

Operating Humidity

Storage Humidity

Vibration Resistance

- Direct Mounting

Vibration Resistance

- DIN Rail Mounting

Shock Resistance

Noise Immunity

Dielectric Withstand Voltage

Insulation Resistance

Ground

Description

0 to 55 °C (32 to 131 °F)

-20 to 70 °C (-4 to 158 °F)

35 to 85% Relative Humidity, No condensation

35 to 90% Relative Humidity, No condensation

Conforms to IEC 68-2-6; 10 - 57 Hz: 0.075 mm Half Amplitude

57 - 150 Hz: 9.8 m/s

2

Acceleration

Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Conforms to IEC 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude

57 - 150 Hz: 4.9 m/s

2

Acceleration

Sweep Count for X, Y, Z: 10 times (80 min in each direction)

Conforms to IEC 68-2-27: 147m/s

2

Acceleration, Action Time: 11 ms

3 times in each direction X, Y, and Z

1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator

AC Power Supply Unit: 1500 VAC > 1 min, tested between all points, terminals, and ground

DC Power Supply Unit: 500 VAC > 1 min, tested between all points, terminals and ground

5 M

> at 500 V DC, tested between power terminals and ground

Class D (100

Ω or less)

3-4

FX1S Series Programmable Controllers

3.4

PLC Mounting Arrangements

Installation Notes 3

To prevent a rise in temperature, mount the units to walls. Never mount them to the floor or ceiling of an enclosure.

Caution

• Units should not be installed in areas subject to the following conditions: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration.

• Take special care not to allow debris to fall inside the unit during installation e.g. cut wires, shavings etc. Once installation is complete remove the protective paper band to prevent overheating.

Figure 3.3: PLC Mounting Diagram

A

A

FX

1S

CPU

A

A > 50mm(1.97 inches)

A

3-5

FX1S Series Programmable Controllers

3.5

DIN Rail Mounting

Installation Notes 3

Units can be snap mounted to 35mm DIN rail (DIN EN 50022). To release, pull the spring loaded clips away from the rail and slide the unit off and up.

3.6

Termination of Screw Terminals

Cables terminating at a screw terminal of an FX

1S product should be fitted with insulated crimp terminals, see example shown. Terminals screws should be tightened to between 0.5 to 0.8

N

  m. Screw terminals must be secured to prevent a loose connection from causing a malfunction.

Figure 3.4: Terminal Crimp

Max.

6.2mm

0.24 in

To suit M3 (0.12in) screw terminals

Max.

6.2mm

0.24 in

3-6

FX1S Series Programmable Controllers

Installation Notes 3

3.7

Installing Optional Units

3.7.1

Special Function Boards

The following is a generic explanation of how to install a special function board to the FX

1S

PLC. For greater detail and specifications of each optional unit, please see the relevant products manual.

Always make sure the power is turned off, before installing a special function board. Only one board can be used at one time, do not try to stack multiple boards.

D)

A)

C)

D)'

C)

E)

A) Special function or optional equipment board.

B) Optional equipment connector port.

C) M3 screw to secure board.

D) Top cover for board.

E) M3 screw to secure top cover.

Note: Do not remove this screw.

• Remove base unit top cover.

B)

Note

• Plug board A) into connector B).

• Fix board to base unit using screws C).

• Attach top cover for board D) removing section D)’ to expose connector etc. (if applicable)

• Secure top cover with M3 screw E).

3-7

FX1S Series Programmable Controllers

3.7.2

FX

1N

-5DM Display Module

Always make sure the power is turned off, before installing the 5DM.

A) Top cover for DM

B) Optional equipment connector.

C) M3 screw to secure top cover.

A)

• Remove the base unit top cover.

• Attach the top cover for DM A), and secure with screw C) (if 5DM is to be permanently mounted)

• Plug in the 5DM at connector B)

B)

For further information please refer to the FX

1N

-5DM user’s manual.

C)

Installation Notes 3

3-8

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Power supply 4

FX1S Series Programmable Controllers

Power supply 4

FX1S Series Programmable Controllers

4.

Power Supply

4.1

4.2

Power Supply 4

Wiring Techniques

The wiring of FX

1S products has been designed to be safe and easy. If during the installation of these product or associated products concern is felt, please contact a professional electrician who is trained to the local and national standards applicable to the installation site.

Wiring Cautions

4.3

• Do not run input signals in the same multicore cable as output signals or allow them to share the same wire.

• Do not lay I/O signal cables next to power cables or allow them to share the same trunking duct. Low voltage cables should be reliably separated or insulated with regard to high voltage cabling.

• Where I/O signal lines are used over an extended distance consideration for voltage drop and noise interference should be made.

Power Supply

When wiring AC supplies the “Live” cable should be connected to the “L” terminal and the

“Neutral” cable should be connected to the “N” terminal. Do NOT connect the “Live” wire to the

“N” terminal, the user might receive a dangerous shock on powerup.

4-1

FX1S Series Programmable Controllers

4.4

Power Supply Characteristics

Power Supply 4

Table 4.1: AC Input Power Requirements, FX1S-**M*-ES/UL, ESS/UL

Description

Power supply

Max. allowable momentary power failure period

Fuse (size) rating

In-rush current

Power consumption *1

24V DC Service Supply

FX

1S

-10M FX

1S

-14M FX

1S

-20M FX

1S

-30M

100 - 240V AC, +10% -15%, 50/60 Hz

10ms; if less than 10ms, the PLC will continue operation.

If 10ms or more, the PLC will shut down

250V 1.0A 5

φ×

20mm (0.2

×

0.79 inches)

100V AC - Max. 15A for 5ms

200V AC - Max. 25A for 5ms

19W 19W 20W 21W

400 mA

*1 Includes the input current (5 or 7mA per point).

Table 4.2: DC Input Power Requirements, FX1S-**M*-DS, DSS

Description

Power supply

Max. allowable momentary power failure period

Fuse rating

In-rush current

Power consumption *1

FX

1S

-10M FX

1S

-14M FX

1S

-20M FX

1S

-30M

24 V DC +10% -15%

5 ms; if less than 5 ms, the PLC will continue operation.

If 5 ms or more, the PLC will shut down

6W 6.5W

0.8A

15A for 0.1 ms

7W 8W

4-2

FX1S Series Programmable Controllers

4.5

Power Supply Input Wiring

Figure 4.1: AC Input Example Wiring

FX

1S

Series

AC/DC

Converter

24+

24-

“

L

”

N

’

85-264V AC

50/60 Hz

Œ

MC

~

24V

0V

MC



Ž

PL





MC

‘

MC

‘

Power Supply 4

Œ

Power supply 100 - 240V AC, +10% -15%,

50/60 Hz



Circuit protector or Fuse

Ž

Emergency stop



Power supply switch



Power ON pilot indicator

‘

Power supply for loads

’

Grounding resistor 100

Ω or less (class D)

“

Fuse

”

Main unit

•

Breaker

4-3

FX1S Series Programmable Controllers

Figure 4.2: DC InputExampleWiring

FX

1S

Series

DC/DC

Converter

Power Supply 4

“

+

_

”

’

20.4 - 26.4V DC

Œ

~

MC

MC



Ž

PL





MC

‘

MC

‘

Œ

Power supply 24V DC, +10% -15%



Circuit protector or Fuse

Ž

Emergency stop



Power supply switch



Power ON pilot indicator

‘

Power supply for loads

’

Grounding resistor 100

Ω or less (class D)

“

Fuse

”

Main unit

•

Breaker

4-4

FX1S Series Programmable Controllers

4.6

Earthing / Grounding

Power Supply 4

Use a cable at least 0.2mm

2

(AWG24) to ground equipment. Ground resistance must be less than 100

(class D). Note that the ground cable must not be connected to the same ground as the power circuits. Grounding is recommended but if a proper ground cannot be provided the PLC will still operate correctly without being grounded.

4-5

FX1S Series Programmable Controllers

Power Supply 4

4-6

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Inputs 5

FX1S Series Programmable Controllers

Inputs 5

FX1S Series Programmable Controllers

5.

Inputs

5.1

24V DC Input Specifications

Table 5.1: FX

1S

Input Specifications

Input voltage

X0 - X7

FX

1S

Main Unit

X10 - X17

24V DC +/- 10%

Input current

Input switching current

Response time

Circuit isolation

Operation indication

24V DC,

7mA

OFF

à

ON >4.5mA

ON

à

OFF

Variable response time

24V DC, 5mA

>3.5mA

<1.5mA

10ms (default)

0 - 15ms for X000-X017 via use of the FX

1S digital filter.

Photocoupler

LED is lit

Inputs 5

5-1

FX1S Series Programmable Controllers

5.2

Wiring Diagrams

5.2.1

Input Wiring

Figure 5.1: Input Wiring Diagrams

FX

1S

-Source





PNP

24V 0V

Œ

S/S X0 X1 X2

FX

1S

-**M*-ES/UL, ESS/UL



1 24V DC Service Supply

2 PNP Sensor

3 NPN Sensor

4 Input Device Contact

5 FX

1S

Controller Main Body

FX

1S

-Sink

Ž



NPN

24V 0V

Œ

S/S X0 X1 X2

FX

1S

-**M*-ES/UL, ESS/UL



Inputs 5

5-2

FX1S Series Programmable Controllers

5.2.2

Input Circuit Connection

Figure 5.2: Input Circuit Diagrams (Source/Sink)

Source (-ve S/S) Sink (+ve S/S)

24V

X

24V DC

24V

X

24V DC

S/S

0V

S/S

0V

5.2.3

Diodes and Inputs Connected in Series

Figure 5.3: Diode Connection Diagram

24V

X

S/S

0V

Voltage drop across the diode is Max. 4V.

No more than 2 LEDs should be connected in series.

5-3

Inputs 5

FX1S Series Programmable Controllers

Inputs 5

5.2.4

Resistors and Inputs Connected in Parallel

Parallel resistance Rp: FX

1S

= 15k

. If resistance Rp is less than the stated value, then add the Rb value using the Equation 1 calculation.

Alternatively; Current leakage: FX

1S

= 1.5mA. If the current leakage is greater than the stated value, then add the Rb value using the equation 2 calculation.

Figure 5.4: Parallel LED Diagram

24V

Eqn 1 :

Rb

4Rp

15 - Rp

Eqn 2 :

Rb

6

I

- 1.5

Rp

Rb

X

S/S

0V

5-4

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Outputs 6

FX1S Series Programmable Controllers

Outputs 6

FX1S Series Programmable Controllers

6.

Outputs

Table 6.1: Output Specifications

Description

Switched voltages

(resistive load)

Rated current / N points

(resistive load)

Relay Output

240V AC,

30V DC

2A/1 point, 8A/COM

Transistor Output

5 - 30V DC

0.5A/1 point, 0.8A/COM

Max. Inductive load

Max. Lamp load (tungsten load)

Minimum load

80VA, 120/240 VAC, See table 6.2 for more details

100W (1.17A/85V AC, 0.4A/

250V AC)

When supply voltage < 5V

DC allow at least 2mA flow

12W/24V DC

0.9W/24V DC

------------------

Response time (approx.)

OFF

à

ON

ON

à

OFF

Circuit isolation

Open circuit current leakage

Operation indication

10ms

10ms

By Relay

----------------

< 0.2ms; <5

µ

< 0.2ms (I > 0.2 A); <5

PhotoCoupler s (Y0,Y1 only)

0.1mA/30V DC

LED is lit when coil is energized

µ s (Y0,Y1 only)

Outputs 6

6-1

FX1S Series Programmable Controllers

6.1

Relay Output Example

Figure 6.1: Typical Relay Wiring Diagram

Outputs 6



”



Ž

COM0

Y0

COM1

Y1

COM2

Y2 Y3 Y4 Y5

Œ

’



•



MC2 MC1

MC1



MC2

“

‘

Œ

Do not use this terminal



Fuse

Ž

Surge absorbing Diode

E x t e r n a l M e c h a n i c a l

Interlock

Z

Emergency Stop

[

Noise suppressor 0.1

µ

F capacitor + 100-120

Ω resistor

\

Valve

]

Incandescent Lamp

^

DC Power Supply

_

AC Power Supply

6-2

FX1S Series Programmable Controllers

6.2

Reliability Tests

Outputs 6

The test results in Table 6.2 were gathered from a 1 sec ON/OFF test cycle. Please note that the over current induced by in-rush greatly reduces the relay contacts service life. The rated life for an inductive AC load such as a contactor or solenoid valve is 500,000 operations at

20VA.

Table 6.2: Relay Life Cycle Data

Description

Load capacity

Life of contact (cycles)

Example load (Mitsubishi contactor)

20VA

0.2A/100VAC

0.1A/200VAC

35VA

0.35A/100V AC

0.17A/240V AC

80VA

0.8A/100V AC

0.4A/240V AC

3,000,000 1,000,000 200,000

S-K10 ~ S-K95 S-K100 ~ S-K150 S-K180,S-K400

6-3

FX1S Series Programmable Controllers

6.3

Response Times

Outputs 6

OFF times increase as the load current decreases.

For improved response times use a 'dummy' resistor, see Figure 6.2. If a response time of 0.5

ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal line has a current greater than 60mA/24V DC.

Figure 6.2: Dummy load

+V

Y

5 to 24V

Dummy load Load

Y000 and Y001 are high speed response outputs with the following characteristics:

10 - 100 mA at 5 - 24V DC, 100 kHz maximum output signal.

If the high speed response is required, a current of 10 - 100mA must be used.

6-4

FX1S Series Programmable Controllers

6.4

Transistor Output Examples

Figure 6.3: Transistor Output Wiring Diagram



+V0 Y0 +V1

‘

Y1 +V2

 

Y2 Y3 Y4 Y5

Œ

MC1 MC2

’

MC2 MC1



Ž

Ž

Figure 6.4: Japanese Model Transistor Output

COM0



Y0

COM1

‘

Y1

COM2

 

Y2 Y3 Y4 Y5

Œ

MC1 MC2

’

MC2 MC1



Ž

Ž

Outputs 6

Œ

Do not use this terminal



Emergency Stop

Ž

Fuse

E x t e r n a l M e c h a n i c a l

Interlock

Z

Output Terminal Y0

[

Output Terminal Y1

\

DC Power Supply

6-5

FX1S Series Programmable Controllers

6.5

Applying Safe Loads

Outputs 6

Ensure all loads are applied to the same side of each PLC output, see previous figures.

Loads which should NEVER simultaneously operate (e.g. direction control of a motor), because of a safety critical situation, should not rely on the PLC's sequencing alone.

Mechanical interlocks MUST be fitted to all safety critical circuits, see previous figures.

6-6

FX1S Series Programmable Controllers

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Diagnostics 7

FX1S Series Programmable Controllers

Diagnostics 7

FX1S Series Programmable Controllers

7.

7.1

Diagnostics

Preliminary Checks

Table 7.1: Preliminary Checks

POWER

RUN

ERROR

Check power supply, ground and I/O cables are wired correctly.

POWER

RUN

ERROR

Turn the power supply on. Check the power LED is lit. Down load a small test program into the PLC. Verify the program to ensure it has been written to the PLC correctly. Using the programming device forcibly turn ON/OFF each output. Check the output LEDs for operation.

POWER

RUN

ERROR

Put the PLC into RUN. Check the RUN LED is lit. Check the previously down loaded program works correctly. Once all checks are complete take the PLC out of run and turn OFF the power supply.

Diagnostics 7

During this testing stage take extreme care not to touch any live or hazardous parts.

7-1

FX1S Series Programmable Controllers

7.2

ERROR LED ON (CPU ERROR)

Table 7.2: Error LED Checks

POWER

RUN

ERROR

Fault

ERROR

LED ON

Remedy

Reset PLC.

Turn power

OFF, then

ON and trigger RUN input.

Possible results

LED OFF

LED is lit

A

Diagnostics 7

Has the memory cassette been installed or removed while the unit was still powered On?

A

B

Remedy

Power OFF

Disconnect earth/ground terminal

Possible results

LED is lit

LED is flashing

Power ON

B

Check for programming error. Ensure the earth/ ground cable is correctly rewired.

PLC M/C M/C PLC M/C

ü

PLC

ü û

Remedy

Possible program/scan time error.

Check D8012 for program scan time,

(units 0.2 ms must be less than 0.2

sec, i.e. - data value <2000).

Possible results

D8012 > D8000

7-2

FX1S Series Programmable Controllers

7.3

7.4

Common Errors

Diagnostics 7

Corroded contact points at some point in an I/O line.

An I/O device has been used outside its specified operating range.

An input signal occurs in a shorter time period than that taken by one program scan.

Maintenance

Check interior temperature of the panel.

Check panel air filters if fitted.

Check for loosening of terminals or mounting facilities (due to vibration).

7-3

FX1S Series Programmable Controllers

7.5

Operation and Error Flags

Table 7.3: Operation and Error Flags

M8004

(ref. 8004)

M8035

Error occurance

(ON when M8060-7 are ON)

Forced RUN mode

M8036

Forced RUN signal

M8037

M8039

(ref. D8039)

Forced STOP signal

Constant scan mode

Diagnostics 7

M8061

(ref. D8061)

M8063

(ref. D8063)

M8064

(ref. D8064)

PLC hardware error

Parallel link error

Parameter error

M8065

(ref. D8065, D8069)

Syntax error

M8066

(ref. D8066, D8069)

Program (circuit) error

M8067

(ref. D8067, D8069)

Program execution error

M8068

(ref. D8068)

Execution error latch

7-4

FX1S Series Programmable Controllers

7.6

PLC Status Registers

Table 7.4: PLC Status Registers

D8000

(default 200msec)

Watchdog timer

PLC version

D8001

22100 = FX

1S

Version 1.00

22 = FX

1S

, 100 = Version 1.00

Memory capacity

D8002

0002=2K steps

D8003

D8004

Memory type

02H=EEPROMprotect switch OFF

0AH=EEPROM protect switch ON

10H=MPU memory

Error flag number

8060=M8060, (8060-8068)

Diagnostics 7

7-5

FX1S Series Programmable Controllers

7.7

Error Registers

Table 7.5: Error Registers

D8061

D8063

D8064

D8065

D8066

D8067

D8068

D8069

Error code for PLC hardware error

Error code for parallel link fault

Parameter error code

Syntax error code

Program (circuit) error code

Program execution error code

Latched step number of execution error

Step number of errors associated with error flags M8065-M8067

Diagnostics 7

7-6

FX1S Series Programmable Controllers

7.8

Error Codes

Table 7.6: Error Codes

D8061

Check cable connections

D8062

0000

6101

6102

6103

0000

6201

6202

6203

6204

6205

No error

RAM error

Operation circuit error

I/O bus error (M8069 = ON)

Check the programmer / PLC connections

No error

Parity/overrun/framing error

Character error

Data sum check error

Data format error

Command error

Diagnostics 7

D8063

0000

6301

6302

6303

6304

6305

6306

Check both power and communications connections

No error

Parity/overrun/framing error

Character error

Data sumcheck error

Data format error

Command error

Watchdog timer error

7-7

FX1S Series Programmable Controllers

7.9

Instruction List

Diagnostics 7

Table 7.7: Numerically Sorted

000

010

020

030

040

050

060

070

080

PROGRAMFLOW

HIGH-SPEED

HANDY INSTR. 1

FX I/O DEVICES

CJ

0

TRANSFERS, COMP

+-

×÷

, LOGICS

CMP

ADD

SHIFT

DATA OPERATION 1 ZRST

REF

IST

FX SER DEVICES RS

1

CALL

ZCP

SUB

2

SRET

MOV

MUL

3

IRET

DIV

EI

4

INC

SFTR

DI

5 6 7

FEND WDT

BMOV

DEC WAND WOR

SFTL

8

FOR

9

NEXT

BCD

WXOR

BIN

SFWR SFRD

DECO ENCO

MTR

ABSD

DSW

HSCS HSCR

INCD

SEGL

PRUN ASCI HEX CCD

SPD

ALT

VRRD VRSC

PLSY

RAMP

PWM

PID

PLSR

150

160

POSITIONING

REAL TIME CLOCK TCMP

220

230

240

IN-LINE COMPARE LD

OR=

TZCP

OR>

TADD

AND=

OR<

TSUB

LD=

ABS ZRN

TRD

PLSV

TWR

DRVI DRVA

HOUR

LD>

AND> AND<

OR

OR

LD<

AND

OR

AND

LD

AND

LD

7-8

FX1S Series Programmable Controllers

Table 7.8: Alphabetically sorted

A

B

Symbol FNC No.

D P

ABS

ABSD

155

062

ADD

ALT

AND

¨

ASCI

BCD

BIN

020

066

232-238

082

018

019

C

BMOV

CALL

CCD

CJ

CMP

015

001

084

000

010

D

Symbol FNC No. D P

DEC

DECO

025

041

DI

DIV

005

023

E

F

DRVA

DRVI

DSW

EI

ENCO

FEND

FOR

159

158

072

004

042

006

008

Diagnostics 7

H

Symbol FNC No. D P

HEX 083

HOUR 169

HSCR

HSCS

054

053

I

INC

INCD

IRET

IST

024

063

003

060

L

LD

MOV

224-230

012

M

N

O

MTR

MUL

052

022

NEXT 009

OR

¨

240-246

7-9

FX1S Series Programmable Controllers

Diagnostics 7

P

Symbol FNC No.

D P

PID

PLSR

PLSV

088

059

157

PLSY

PRUN

057

081

PWM

RAMP

058

067

R

S

REF

RS

SEGL

SFRD

SFTL

SFTR

050

080

074

039

035

034

S

Symbol FNC No. D P

SFWR 038

SPD

SRET

056

002

T

SUB

TADD

TCMP

TRD

TSUB

TWR

TZCP

021

162

160

166

163

167

161

V

Symbol FNC No. D P

VRRD

VRSC

WAND

085

086

026

W

WDT

WOR

WXOR

ZCP

Z

ZRN

ZRST

007

027

028

011

156

040

7-10

FX1S Series Programmable Controllers

7.10

Device List

Diagnostics 7

Table 7.9: Device List

Program capacity

Input (X) relay

Output (Y) relay

Auxiliary relay

State relay

(128 pts)

Timer

(64 pts)

Device Type

(512 pts + 256 pts)

General Auxiliary Relays

Latched Relays

Special function

Initial State Relay

Latched State Relay

100 ms

10 ms

1 ms

Description

2K steps by FX

1S internal EEPROM or

2K steps by FX

1N

-EEPROM-8L

X0 - X17 (16 pts)

Y0 - Y15 (14 pts)

(X + Y)

30 pts Max.

M0-M383 (384 pts)

M384-M511 (128 pts)

M8000-M8255 (256 pts)

S0-S9 (10 pts), same as latched state relay

S10-S127 (118 pts)

T0-T62 (63 pts)

If M8028 is On, T32 - T62 are 10ms timers

(31 pts)

T63 (1 pt)

7-11

FX1S Series Programmable Controllers

Counter

Device Type

(32 normal and 21 High

Speed counters)

General Counter

Latched Counter

High Speed Counter

General Use Register

Data register

(1500 pts, + 256 pts)

Pointers

Latched Register

File Register

Diagnostic Register

Index

Pointer

Interupt Pointer

Nest Level

Numbers

K

H

16 bit

-32,768 to 32,767

0 to FFFFH

Diagnostics 7

Description

C0-C15 (16 pts)

C16-C31 (16 pts)

C235-C255

D0-D127 (128 pts)

D128-D255 (128 pts)

D1000-D2499 (1500 pts)

D8000-D8255 (256 pts)

V0-V7, Z0-Z7 (16 pts)

P0-P63 (64 pts)

I00

¨

- I50

¨

(6 pts)

N0 - N7 (8 pts)

32 bit

-2,147,483,648 to 2,147,483,647

0 to FFFFFFFFH

7-12

FX

1S

Series Programmable Controllers

HARDWARE MANUAL

FX

1S

SERIES PROGRAMMABLE CONTROLLERS

HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX: J24532 CABLE MELCO TOKYO

HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN

JY992D83901E

(MEE0106)

Effective June 2001

Specifications are subject to change without notice.

Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project