Owner` s Manual

40GJ*C

Cassette Ductless Split System

Sizes 12 to 24

Owner' s Manual

the environmentally sound refrigerant

NOTE: Read the entire instruction manual before starting the installation.

NOTE TO EQUIPMENT OWNER:

Please read this Owner’s Information Manual carefully before installing and using this appliance and keep this manual for future reference.

For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information, along with the installation data and dealer contact information, will be helpful should your system require maintenance or service.

UNIT INFORMATION

Model #

Serial #

DEALERSHIP CONTACT INFORMATION

Company Name:

Address:

INSTALLATION INFORMATION

Date Installed

Phone Number:

Technician Name:

4

User Notice

ƹ

When operating, the entire capacity of the cooperating indoor unit should be not larger than

150% of outdoor unit. Otherwise, it will cause the shortage of cooling (heating) capacity.

ƹ

A Breaker(or fuse) need to be installed in every indoor unit, and the capacity should in according with indoor unit’s electrical parameter; all the indoor units are required to be centralized controlled by a total Switch, this Switch can cut off the electric power supply in case of emergency. The Breaker(or fuse) on each indoor units have the function of short circuit prevention and abnormal overload avoiding, it should be connected in normal situation. The total switch controlling the power supply of all the indoor units. Before clearing and maintenance job being carried out to the indoor units, it is very important to turn off the total power supply switch.

ƹ

In order to turn on the units successfully, the main power switch should be opened 8 hours before the operation.

ƹ

After receiving the turn off signal, every indoor unit will continue to work for 20-70sec to make use of the rest cool air or the rest heat air in the heat exchanger, while preparing for the next operation.

And this is normal.

ƹ

When the selected operating mode of the indoor unit are clash with the operating mode of the outdoor unit, the malfunction light will blink after 5s on the indoor unit or remote controller showing that the operation clash, then the indoor unit will stop. At this time, change the operation mode of the indoor unit to the one that would not clash with the outdoor operating mode to make the operation normal. The cooling mode is not clash with the dry mode, while the fan mode is not clash with any mode.

ƹ

The appliance shall not be installed in the laundry.

ƹ

An all-pole disconnection switch having a contact separation of at least 3mm in all poles should

EHFRQQHFWHGLQ¿[HGZLULQJ ƹ

Information regarding transport/storage temperature (

-13 -131

°

F/

-

2

5~

55

°C ) is missing.

ƹ

Main switch provided by end user: main switch handle should be black or gray, it can be locked in “OFF” position with padlock.

ƹ

The main disconnection device should be explained in user manual and the height should be recommended at 0.6-1.7m. over current protection is required(UL 1995,CSA C22.2).

ƹ

The cooling range of the unit is the outdoor environment temp.

23-118.4 F(

-5~48°C

)

DB, the heating range of the unit( only for the heat pump type unit) is the outdoor environment temp.

5-80.6 F(

-15~27°C

)

WB.

This product must not be disposed together with the domestic waste. This product has to be disposed at an authorized place for recycling of electrical and electronic appliances.

Contents

Safety Information .................................................................................................... 1

Install of The Compact Panel Cassette Type Indoor Unit ......................................... 2

Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit ...... 10

Working Temperature Range .................................................................................. 11

Malfunction Debarring ............................................................................................ 12

Maintenance Method .............................................................................................. 14

Safety Information

Safety Information

Please read this manual carefully before use this unit, and operate it correctly according to the guide in this manual.

Please take specially note to the meaning of these two marks:

Warning!:

This mark means that it may cause casualty or badly heart if the operation is incorrect.

Note!:

This mark means that it may cause casualty or property loss if the operation is incorrect.

Warning:

ƹ Do not adopt fuse with unsuitable capacity or adopt iron thread instead of fuse, otherwise malfunction

RU¿UHPD\KDSSHQHG ƹ Cut down the main power switch immediately if malfunction (such as smell the burning odor etc.) happened.

ƹ Maintain ventilation to prevent oxygen leakage in room.

ƹ 'RQ¶WLQVHUW¿QJHURUVWLFNOLNHWKLQJVLQWRGLVFKDUJHYHQWRURXWOHWJULOO ƹ Please make sure that the unit is installed in the place that can bear the weight of it adequately. If the place is not strong enough, the air conditioner may drop and cause casualty event.

ƹ 'RQ¶WVSUD\RUVPHDUDQ\RLOSDLQWRULQVHFWLFLGHRQWKHVXUIDFHRIXQLWRWKHUZLVH¿UHPD\EHOHDGHG ƹ 'RQRWUH¿WWKHFRQGLWLRQHU3OHDVHFRQWDFWWKHDJHQF\RUSUHIHFWLRQDOSHUVRQQHOWRUHSDLURUPRYHWKH conditioner.

An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be

FRQQHFWHGLQ¿[HGZLULQJ

Note!:

ƹ Please check and make sure that the cord, drainage pipe and tubes are connected in the correct way to

SUHYHQWOHDNDJHRIZDWHUUHIULJHUDQWHOHFWULFVKRFNRU¿UH ƹ The main power must connectable to the earth in order to assure the conditioner earthing effectively and to prevent electric shock. Please don’t connect the earthing line with the gas pipe, water pipe, lightening rod or the connecting line of telephone.

ƹ The air conditioner should be turned off at least after 5 mins’ operation; otherwise it would affect the duration of the unit.

ƹ Don’t let the children operate the air conditioner.

ƹ Please don’t operate the unit by wet hand.

ƹ 3OHDVHWXUQRIIWKHPDLQSRZHURIWKHXQLWEHIRUHFOHDQLQJWKHFRQGLWLRQHURUFKDQJHWKH¿OWHU ƹ Please cut off the main power if the conditioner will be used for a long time.

1

Install of The Compact Panel Cassette Type Indoor Unit

Install of The Compact Panel Cassette Type Indoor Unit

ƾ

Schematic diagram of installation spaces

59 in

(1500 mm)

59 in

(1500 mm) in/mm

40GJQB12C--3

40GJQB18C--3

40GJQB24C--3

10 1/4 in

(260 mm) ƾ

Select install location of the indoor unit

2EVWUXFWVKRXOGSXWDZD\IURPWKHLQWDNHRURXWOHWYHQWRIWKHLQGRRUXQLWVRWKDWWKHDLUÀRZFDQEH blown though all the room.

2. Make sure that the installation had accord with the requirement of the schematic diagram of installation spaces.

3. Select the place where can stand 4 times of the weight of the indoor unit and would not increase the operating noise and oscillate.

4. The horizontally of the installation place should be guaranteed.

5. Select the place where easy drain condensated coagulated water, and easy connect with outdoor unit.

6. Make sure that there are enough space for care and maintenance. Make sure that the weight between the indoor unit and ground is above

70 6/7 in (1800 mm)

.

7. When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If

QRWUHLQIRUFHEHIRUHLQVWDOODWLRQ5HIHUWRWKHLQVWDOOFDUGERDUGDQG¿QGZKHUHVKRXOGEHUHLQIRUFHG

Note!

There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the water pump.

The following treatment should be taken under this circumstance:

1. Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of the lampblack by the air conditioner.

2. Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air conditioner.

ƾ

Important notice:

ƹ

To guarantee the good performance, the unit must be installed by professional personnel according with this instruction.

2

Install of The Compact Panel Cassette Type Indoor Unit

ƾ

Dimension of ceiling opening and location of the hoisting screw (M10)

25 3/5 in (650 mm)

22 4/9 in (570 mm)

15 3/4 in (400 mm)

26 7/9 in (680 mm)

33 in(8 40 mm)

35 in(8 90 mm)

37 2/5 in (950 mm)

40GJQB24C--3

Install dimension of mode

40GJQB12C--3,40GJQB18C--3

Fig.2

ƹ The drilling of holes in the ceiling must be done by the professional personnel.

Installation stands for main body of the unit

Ceiling

6 2/7 in (160 mm)

Fig.3

Above

4/6 in (20 mm)

Notes: The dimension for the ceiling openings with * marks can be as large as

35 5/6 in (910 mm)

. But the overlapping sections of the ceiling and the decorated surface boards should be maintained at no less than

4/6 in (20 mm)

.

ƾ

Main body of hoisting air conditioner

1 The primary step for install the indoor unit.

ƹ When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and

ORZHURIWKHKRLVWLQJVWDQGWR¿[LW7KHXVHRIJDVNHWDQFKRUERDUGFDQSUHYHQWJDVNHWEUHDNRII

2 Use install cardboard.

ƹ Please refer to the install cardboard about the dimension of ceiling opening.

ƹ The central mark of the ceiling opening is marked on the install cardboard.

3

Install of The Compact Panel Cassette Type Indoor Unit

ƹ ,QVWDOOWKHLQVWDOOFDUGERDUGRQWKHXQLWE\EROWSLHFHDQG¿[WKHDQJO e of the drainage pipe at the outlet vent by bolt.

$GMXVWWKHXQLWWRWKHVXLWDEOHLQVWDOOSODFH5HIHUWRWKH¿J

4 Check if the unit is horizontal.

ƹ Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit

DUHKRUL]RQWDOE\ZDWHUOHYHU,IWKHXQLWLVVODQWWRZDUGWKHRSSRVLWHRIWKHFRDJXODWHZDWHUÀRZWKHUHPD\EH malfunction of the bobber switch and lead water drop.)

5 Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it.

6 Backout the install cardboard.

Fig.4

Note!

Please do tighten the nuts and bolts to prevent air conditioner break off.

ƾ

Connection of the refrigerant pipe

ƹ When connect the pipe to the unit or backout it from the unit, please do use both spanner and torque

ZUHQFKDVVKRZQLQ¿J ƹ

:KHQFRQQHFWVPHDUERWKLQVLGHDQGRXWVLGHRIWKHÀDUHQXWZLWKIUHH]HPRWRURLOVFUHZLWE\KDQG and then tighten it with spanner.

ƹ Refer to form 1 to check if the wrench had been tightened (too tight would mangle the nut and lead leakage).

ƹ Examine the connection pipe to see if it had gas leakage, then take the treatment of heat insulation, as

VKRZQLQWKH¿J ƹ Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation sheath of the gas collection tube.

4

Install of The Compact Panel Cassette Type Indoor Unit

Smear freeze motoroil here

Median sponge (attachment)

(entwine the wiring interface with seal mat)

Torque wrench

Thread fasten(x4)

Heat preservation sheath of liquid inlet tube (attachment) (for liquid tube)

Spanner

Wiring interface

Gas collection tube

Liquid inlet tube

Flare nut

Fig.5

Form 1: The tightening torque needed for tightening nut

Diameter ˄ Inch ˅ ij

’’ ij

’’ ij ’’ ij

’’ ij

’’

Heat preservation sheath of gas collection tube (attachment)(for gas tube)

Surface thickness ˄ in/mm

˅ Tightening torque ı

0.02 in (0.5 mm) 20.34~40.68 ft.lb(15~30 N.m) ı

0.03 in (0.71 mm) 40.68~54.24 ft.lb(30~40 N.m) ı

0.04 in (1 mm) 61.02~67.8 ft.lb(45~50 N.m) ı

0.04 in (1 mm) 81.36~88.14 ft.lb(60~65 N.m) ı

0.04 in (1 mm) 94.93~101.7 ft.lb(70~75 N.m) ƾ

Drainage hose

1. Install the drain hose ƹ

The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter of polythene pipe: Outer diameter

1 in (25 mm)

Surface thickness ı

0.06 in (1.5 mm) ƹ

Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble.

ƹ

If drain hose cannot has enough drooping gradient, drain raising pipe should be added. ƹ

To prevent bent of the drain hose, the distance between hoisting stand should is

3.28 to 4.92 ft (1 to 1.5 m)

.

3.28 to 4.92 ft (1 to 1.5 m)

Fig.6

ƹ Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then tighten the clamp.

ƹ Entwine the big sponge on the clamp of drain hose to insulate heat.

ƹ Heat insulation should be done to indoor drain hose.

5

Clamp

Install of The Compact Panel Cassette Type Indoor Unit

Sponge(attachment)

Clamp(attachment)

Sponge (gray) Drain hose

Below

1/6 in (4 mm)

Fig.7

Drain stepup pipe note

ƹ

The install height of the drain raising pipe should less than

11 in (280 mm)

.

ƹ

The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond

300mm.

11 4/5 in (300 mm)

3.28-4.92 ft (1-1.5 m)

11 in (280 mm)

8 2/3 in (220 mm)

Instruction

ƹ

The slant gradient of the attached drain hose should be within

3 in (75 mm)

so that the drain hole doesn’t has to endure the unnecessary outside force.

ƹ

Please install the drain hose according to the following process if several drain hoses join together.

Fig.10

2 Check the smoothness of drain after installation.

ƹ Check the drain state by immitting

36 3/5 in

3

(600 cc)

water slowly from the outlet vent or test hole.

ƹ Check the drain in the state of refrigerating after installation of the electric circuit.

6

Install of The Compact Panel Cassette Type Indoor Unit

4 in (100 mm)

Fig.11

ƾ

Electrical wiring

Note:The power of the entire indoor unit must be connected in outdoor unit.

ƹ About the electrical wiring, please see the circuit diagram attached with the unit.

ƹ All the installation of electrical wiring must be done by professional personnel.

ƹ Please do take the earthing treatment.

Wiring method of connection unit and controller

ƹ Connection wiring (communication): ķ Open electric box cover, drag the wiring (communication)from the rubber plug A, and impact them well individually by impact fastener.

ĸ Wiring according to the indoor side circuit diagram.

ƹ Fix the impact fastener after connection.

ƹ Entwine the small sponge on the electric wire( do entwine it to prevent condensation).

ƹ Impact tightly by impact fastene UDIWHUFRQQHFWLRQDQGWKHQ¿WRQWKHHOHFWULFER[ ƹ Connect the 3 cord rubber wire to the counter terminal of the 3 way terminal board.

The power cord reference Power cord standard recommending table

Fig.12

Power cord standard recommending table

Model

40GJQB12C--3

40GJQB18C--3

40GJQB24C--3

Power supply

(V.Ph.Hz)

208~203V-1Ph-60Hz

208~203V-1Ph-60Hz

208~203V-1Ph-60Hz

Min. Sectional Area of Earth Wire(AWG)

UL1015 AWG 18*1

UL1015 AWG 18*1

UL1015 AWG 18*1

Min. Sectional Area of Power Cord(AWG)

UL1015 AWG 18*3

UL1015 AWG 18*3

UL1015 AWG 18*3

7

Install of The Compact Panel Cassette Type Indoor Unit

ƾ

Install the panel

6HWWKHSDQHOWRWKHLQGRRUXQLWERG\E\PDWFKLQJWKHSRVLWLRQRIWKHVZLQJÀDSPRWRURIWKHSDQHOWR

WKHSLSLQJSRVLWLRQRIWKHSDQHOWRWKHSLSLQJSRVLWLRQRIWKHLQGRRUXQLWDVVKRZQE\¿J

2. Install the panel ķ Install the panel on the indoor unit temporarily. When install, hang the latch on the hook that is located

RQWKHRSSRVLWHVLGHRIWKHVZLQJÀDSRQWKHSDQHORIWKHLQGRRUXQLWSRVLWLRQV ĸ Hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not to let the swing motor lead wire get caught in the sealing material.)

Ĺ Screw the 4 hexagon head screws under the latches in about

3/5 in (15 mm)

. (The panel would rise) ĺ $GMXVWWKHSDQHOE\WXUQLQJLWWRZDUGWKHGLUHFWLRQSRLQWHGE\WKHDUURZDVVKRZQLQ¿JVRWKDWWKH adjust board connect the ceiling well.

Ļ Tighten the screws until the thickness of the sealing material between panel and indoor unit reduced to

5-8mm.

1/5 in to 1/3 in (5 mm to 8 mm)

Fig.13

Notes:

,PSURSHUVFUHZLQJRIWKHVFUHZVPD\FDXVHWKHWURXEOHVVKRZQLQ¿J

Air leak

Air leak from ceiling

Water condensatation, water drop

Fig.14

8

Install of The Compact Panel Cassette Type Indoor Unit

2. If gap still exist between ceiling and decoration panel after tightening the screws, readjust the height of

WKHLQGRRUXQLW$VVKRZQLQ¿J

If the raising lever and drain hose are not affect, can adjust the height of indoor unit by the hole on the corner of panel.

Gaps are not allowed

Fig.15

Ć $IWHU¿[LQJEHVXUHQRJDSOHIW between the ceiling and the panel.

3. Wiring of the decoration panel (Fig.16)

&RQQHFWWKHMRLQWVIRUVZLQJÀDSPRWRUOHDGZLUHDWSODFHVLQVWDOOHGRQWKHSDQHO

At body At pane

At body At pane

Fig.16

9

Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit

Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit

40GJQB12C--3

40GJQB18C--3

40GJQB24C--3

10

Working Temperature Range

Working Temperature Range

O O

80.6 F(27 C)

O O

89.6 F(32 C)

O O

69.8 F(21 C)

O O

68 F(20 C)

O O

80.6 F(27 C)

O O

68 F(20 C)

O O

66.2 F(19 C)

O O

73.4 F(23 C)

O O

59 F(15 C)

O O

59 F(15 C)

O O

59 F(15 C)

O O

95 F(35 C)

O O

118.4 F(48 C)

O O

64.4 F(18 C)

O O

44.6 F(7 C)

O O

75.2 F(24 C)

O

5 F(

-

O

15 C)

O O

75.2 F(24 C)

O O

78.8 F(26 C)

O O

42.8 F(6 C)

O O

64.4 F(18 C)

3

.

2

O

F(

-

O

16 C)

11

Malfunction Debarring

Malfunction Debarring

Warning!

ƹ Cut down the main power switch immediately if malfunction (such as smell the burning odor etc.) happened, and then contact service center. If the abnormal state is maintained, the unit may be damaged or

HOHFWULFVKRFNRU¿UHPD\EHKDSSHQHG ƹ 'RQRWUH¿WWKHFRQGLWLRQHU3OHDVHFRQWDFWVHUYLFHFHQWHUWRUHSDLURUPRYHWKHFRQGLWLRQHU ƾ

Check the following items before contacting maintenance center

Phenomena Reason Remedial Measures

Blow of fuse or breaker Change fuse or close breaker

Power cut

Air conditioner doesn’t run at all

Air conditioner runs but stops immediately

Don’t connect with power

Low batteries of wireless remote controller

Wireless remote controller exceed remote control area

Blockage in inlet or outlet vent of indoor or outdoor unit

Blockage in inlet or outlet vent of indoor or outdoor unit

Improper of temp. setting

Abnormal cooling or heating

Low setting of fan speed

Incorrect of wind direction

Door or window opened

Direct sun burn

Restart when there is power supply

Connect power well

Change new batteries

Signal could be received within 8m

Clean out blockage

Clean out blockage

Adjust settings in wireless remote controller

Adjust settings in wireless remote controller

Adjust settings in wireless remote controller

Close

Hang curtain or jalousie before windows

Too many people in room

Too many heater in room

Filter blocked by dirt

&OHDQ¿OWHU

12

Malfunction Debarring

ƾ

Instruction

If problem still cannot found out after above checking, please contact service center and instruct phenomena and model.

ƾ

The following circumstance are not malfunction

“Malfunction” Reason

Air conditioner doesn’t run

Mist is blown from air conditioner

Noise is heard from air conditioner

Dust be blown for air conditioner

Odor gives out from air conditioner

Start up unit immediately after turned off

The overload protects switch makes it run after 3 minutes delay.

When opening power

When cooling

Slight click sound heard once begin running

Hissing sound heard continuously when cooling

Hissing sound heard when staring or stopping

Slight hissing sound heard when running or after running

Run for about 1 minute without other actions

The high humidity air in room is cooled rapidly

Sound of initialization for electric expand valve

7KHVRXQGIRUJDVUHIULJHUDQWÀRZLQJ in the unit

The sound for gas refrigerant stops

ÀRZ

Sound for running of drainage system

Creak sound heard when running or after running

The grating sound caused by expands of panel and other parts for the change of temperature

Started up after long time’s doesn’t runs

When running

Dust in indoor unit be blown out

This is because when air conditioning, odors or cigarette smoke from the room that was sucked in is discharged again.

ƾ

After-sales Service

When having quality or other problems when purchasing air conditioner, please contact the local service center.

13

Maintenance Method

Maintenance Method

When air conditioner won’t be used for a long time, please cut off the main power supply of air conditioner.

ƹ

Warning!

Do turn off the unit and cut off the main power supply when cleaning the air conditioner, otherwise electric shock or harm may happen.

ƹ It is forbidden to wash air conditioner by water rinsing, otherwise electric shock may happen.

ƾ

&OHDQLQJDLU¿OWHU

$LU¿OWHUVVKRXOGEHFOHDQHGE\SURIHVVLRQDOVZLWKSURSHURSHUDWLRQWRHQVXUHSHUVRQDOVDIHW\

:KHQWKHXVDJHHQYLURQPHQWKDVORWVRIGXVWDLU¿OWHUVKRXOGEHFOHDQHGPRUHIUHTXHQWO\DERXWRQFH months).

1. Open air inlet grille

Loosen two screws on the air inlet grille with a screwdriver. And pull the 2 handle on air inlet grille at

WKHVDPHWLPHZLWKWKHGLUHFWLRQVKRZHGE\DUURZLQ¿JSXOOGRZQVORZO\5HYHUVHZKHQFORVLQJ

'LVDVVHPEO\DLU¿OWHU

$VVKRZQLQ¿JSXOOWKHKDQGOHEHKLQGDLULQOHWJULOOHUDLVHLWDQGGLVDVVHPEO\7KHQGLVFKDUJHWKH

SXUL¿HU¿[HGRQ¿OWHU purifier

Fig.17 Fig.18

3. Clean

$GRSWVFOHDQHURUZDWHUWRZDVK¿OWHULIWKH¿OWHULVWRRGLUW\OLNHRLOVWDLQRQLWDGRSWVZDUPZDWHU lower than

O O

113 F(45 C) with neutral scourer to clean it, then dry it in the shade.

Note

ʽ

'RQRWFOHDQWKH¿OWHUE\KRWZDWHUZKRVHWHPSLVKLJKHUWKDQ

O O

113 F(45 C) to prevent fade or deformation.

'RQRWEXUQLWRQ¿UHRUWKH¿OWHUZRXOGFDWFKHV¿UHRUGHIRUPDWLRQ

,QVWDOODLU¿OWHU

)L[WKHSXUL¿HUVRQ¿OWHULQVWDOO¿OWHURQWKHVHYHUDOEXOJHVRQWRSRIDLULQOHWJULOOHSXOOWKHKDQGOH

EHKLQGDLULQOHWJULOOHWRZDUGLQVLGHWR¿[¿OWHU$VVKRZQLQ¿J

5. Close air inlet grille (Refer to the 1 st

step)

Maintenance Method

14

Maintenance Method

Fig.19 Fig.20

ƾ

Clean air inlet grille

1. Open air inlet grille (the same with the 1st step of Clean Air Filter)

7DNHRXWDLU¿OWHUWKHVDPHZLWKWKHQGVWHSRI&OHDQ$LU)LOWHU

3. Take out air inlet grille

Open air inlet grille for an angle of 45

ƒDVVKRZQLQ¿JULVHLW

4. Clean

Clean it by pubescence brush, water and neutral cleaning, then throw water or dry it.

Note

ʽ

Do not use water above

O O

113 F(45 C) to wash the panel to prevent fade or deformation.

5. Install air inlet grille (refer to 3rd step)

,QVWDOODLU¿OWHUUHIHUWRWKHWKVWHSRI&OHDQ$LU)LOWHU

7. Close air inlet grille (refer to the 1st step) ƾ

,QVWDOODQGFKDQJHRIDLUSXUL¿HU

1. Open air inlet grille (the same the 1st step of Clean Air Filter)

'LVDVVHPEO\SXUL¿HU

$VVKRZQLQ¿JGLVDVVHPEO\DLU¿OWHUVFUHZRXW¿[LQJEROWV¿[HGRQSXUL¿HURQ¿OWHUWKHQSXUL¿HU could be disassembly.

7DNHRXWWKHSDFNDJHVDFNRIVWDWLF¿EHUQHW¿OWHUWKHQLQVWDOOWKH¿OWHULQVWDQGRISXUL¿HUDQG¿[

SXUL¿HURQDLU¿OWHU

,QVWDOODLU¿OWHUWKHVDPHZLWKWKHWKVWHSRI&OHDQ$LU)LOWHU

Air filter

Purifier filter

Stand for purifier

Fix bolt of purifier

Fig.21

15

Maintenance Method

Function and usage period for air purifying

ƹ Could adsorb CO, CO

2

, benzene, aldehydes and odor of gasoline etc..

ƹ &RXOGDGVRUEGHOHWHULRXVPDWHULDOWKDWLVVPDOOHUWKDQȝPLQDLUDVGXVWSROOHQEDFWHULDDQGYLUXV ƹ Usage period is 6 months to 1 year. If it is necessary to be changed, purchase new purifier in the nearest Gree special engaged maintenance center.

ƾ

Clean Outlet vent and Surface Panel

ƹ Clean the surface panel by soft dry cloth or wet cloth with neutral scourer.

ƹ It is forbidden to clean surface panel by gasoline, benzene, diluents, cleansing powder etc..

ƹ If the guide louver is too dirty, it may be removed to be cleaned. (As narrated below)

Disassembly and install of guide louver

1. Disassembly guide louver

Screw bolts in both end of guide louver to loose.

Note

ʽ

'RQRWZLSHJXLGHORXYHUSRZHUIXOO\ZKHQFOHDQLQJRWKHUZLVHÀXIIRQVXUIDFHZRXOGIDOORII

2. Install guide louver

Rotate guide louver slightly could install the protruding edge of both end into grooves on both end of guide louver, and then tighten bolts. ƾ

Maintenance before or after usage season

Check before the usage season

ƹ Check if there is blockage in inlet or outlet vent of air conditioner.

ƹ Check if the earthing wire had earthed reliably.

ƹ &KHFNLIWKHDLU¿OWHUKDGEHHQLQVWDOOHGZHOO ƹ In order to start up the air conditioner smoothly after long time’s turned off, turn on the main power supply 8 hours before turning on the air conditioner.

Maintenance after usage season

ƹ &OHDQ¿OWHUDQGERG\RIDLUFRQGLWLRQHU ƹ Cut off the main power supply of air conditioner.

ƹ The cooling or heating capacity and sound level are tested before leaving factory.

ƹ If the parameter changed, refer to the data offered on nameplate.

16

Copyright 2014 Carrier Corporation

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Edition Date: 11/14

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 40GJC-01OM

Replaces: New