Rockwell Automation 1771 CFM Flowmeter Module Installation Instructions
Below you will find brief information for Flowmeter Module 1771 CFM. The 1771 CFM module is a configurable flowmeter module that accepts input from up to four channels, each of which can accept signals from various types of flowmeters. The device has four assignable outputs that can be configured for various applications. The module has a range of features, including rollover value, frequency scaler multiplier and divisor, total scaler multiplier and divisor, and configurable outputs. It is also capable of storing counts, scaling frequency and count to engineering units, and monitoring flow total, rate, and rate of change. To program the device, you will need to use BTW and BTR instructions in your ladder logic program. The device has an array of status indicators, including an active indicator, input indicators, output indicators, and a fault indicator.
Advertisement
Advertisement
Installation Instructions
Contents
This icon is used when additional information is available in the
Configurable Flowmeter
Module User Manual, publication 1771Ć6.5.99.
Important User Information
Configurable
Flowmeter Module
(Catalog Number 1771-CFM)
Use this document as a guide when installing a Configurable
Flowmeter module.
To
Important User Information
Calculate power requirements
Set the module operation jumpers
Set the input channel jumpers
Determine CFM module placement
Key the backplane connector
Install the module
Make connections to the field wiring arm
Ground the module
Configure the module
Interpret module status and input data
For this reference information
Diagnostics
Status indicators
Specifications
11
12
15
6
7
8
5
6
4
4
See page
1
See page
16
16
18
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Publication 1771ĆIN043B-EN-P - July 2002
2
Configurable Flowmeter Module
Allen–Bradley publication SGI–1.1, Safety Guidelines for
Application, Installation, and Maintenance of Solid–State Control
(available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard.
WARNING
!
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION
!
Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
ATTENTION
!
Environment andEnclosure
This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage
Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR
Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the
Allen–Bradley publication 1770–4.1, (“Industrial
Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
3
Publication 1771ĆIN043B-EN-P - July 2002
4
Configurable Flowmeter Module
ATTENTION
!
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
•
Touch a grounded object to discharge potential static.
•
Wear an approved grounding wriststrap.
•
Do not touch connectors or pins on component boards.
•
Do not touch circuit components inside the equipment.
•
If available, use a static–safe workstation.
•
When not in use, keep modules in appropriate static–safe packaging.
Calculate Power
Requirements
Setting the Module
Operational Jumper
Your CFM module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The maximum current drawn by the CFM module is 0.8A. Add this value to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.
ATTENTION
!
When using a 1771-P7 or 1771-PS7 power supply to power an I/O chassis, you cannot place more than four CFM modules in this chassis. The interaction between the four CFM modules and the 1771-P7 or 1771-PS7 power supply (not 16A limit) prevents the power supply from powering up.
If you are using the 1771ĆCFM as a replacement for a 1771ĆQRC module (no BTW / 3 word BTR) replacement for a 1771ĆQRD module (1 word BTW / 9 word BTR)
CFM module (software configurable)
Set the jumper to
QRC
QRD
CFM
CFM QRD
QRC
19807
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
Set the Input Channel
Jumpers
1
Remove the four screws securing the side cover to the module and remove the covers.
These jumpers Are usedto set flowmeter jumpers flowmeter for lowĆpass filter (70Hz)
(F0ĆF3) or highĆspeed operation gate jumpers
(G0ĆG3) gates for +5Ć12V or +12Ć30V operation
The CFM module is configured for high-speed operation. If any input channel will be accepting input from a mechanical switch, you need to set the flowmeter jumper for that input channel to filter operation.
The filter provides debouncing for the mechanical switch.
ATTENTION
!
The frequency of counting must be less than 70Hz when the filter mode is selected. If the frequency exceeds 70Hz, the
CFM module will not read the incoming pulse.
19805
2
Reposition the flowmeter and gate jumpers associated with each input channel according to your requirements
The flowmeter and gate jumpers
2 can be set independent ofeach other
(you can select the filter action for each flowmeter input and a voltage for each and gate input independently).
5-12V
FILTER
1
HIGH SPEED
12-30V
G0
F1
F0
F3
F2 flowmeter jumpers
G1 gate jumpers
G2
G3
19806
1
2
In the filter position, the module will not read frequencies above 70Hz.
Jumpers are shown in default settings.
3
Reposition the cover and secure with the four screws removed in step 1.
5
19813
Publication 1771ĆIN043B-EN-P - July 2002
6
Configurable Flowmeter Module
Determine CFM Module
Placement
Use of data table
Input Image Bits
Output Image Bits
Read Block Words
Write Block Words
8
8
41 max
60 max
Place your module in any slot of the I/O chassis except for the extreme left slot. This slot is reserved for processors or adapter modules.
2Ćslot addressing 1Ćslot addressing
Place the CFM module in any module group with any 8Ćbit or block transfer module.
Place the CFM module in any module group with any 8Ćbit
6 b o b oc a s e od e
1/2Ćslot addressing
Key the Backplane
Connector
The CFM module's printed circuit board is slotted in two places on the rear edge. These slots are intended to mate with the plastic keying bands supplied with the I/O chassis.
ATTENTION
!
Observe the following precautions when inserting or removing keys:
• insert or remove keys with your fingers
• make sure that key placement is correct
Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.
Position the keying bands in the backplane connectors to correspond to the key slots on the CFM module.
Place the keying bands:
S between 2 and 4
S between 6 and 8
19808
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
Install the Module
WARNING
!
When you insert or remove the module while backplane power is on, or you connect or disconnect the wiring arm with field power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure power is removed or the area is nonhazardous before proceeding.
ATTENTION
!
Remove power from the 1771 I/O chassis backplane before you install the CFM module. Failure to remove power from the backplane could cause:
• injury
• equipment damage due to unexpected operation
• degradation of performance
At power-up, the active and fault indicators are on. An initial module self-check occurs.
If there is no fault, the fault indicator turns off. See page 16 for information on interpreting the status indicators.
The 1771–CFM module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 11W maximum.
1
Place the module in the card guides on the top and bottom ofthe chassis that guide the CFM module into position.
Important: Apply firm even pressure on the module to seat it into its backplane connector.
1771ĆA1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis
1771ĆA1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis
19809
Snap the chassis latch over the top ofthe module to secure it.
Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.
2
Attach the wiring arm (1771ĆWN) to the horizontal bar at the bottom ofthe I/O chassis.
1771ĆWN
17643
The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.
7
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
8
Make Connections to the
FieldWiring Arm
Connect your I/O devices to the 40-terminal field wiring arm (cat. no. 1771-WN) shipped with the CFM module.
ATTENTION
!
Remove power to all I/O devices before you connect them to the wiring arm.
Failure to remove power from your I/O devices could cause:
• injury
• damage to module circuitry
• equipment damage due to unexpected operation
The following tables and wiring diagrams represent wiring for a flowmeter input (F0), a gate input (G0), and an output (O0).
See the wiring-arm diagram for the terminals used in wiring F1-F3, G1-G3, and O1-O3.
F0 wiring signal input signal common
Terminal
12
11
For this threshold(ON/OFF) voltage
50 mV
500 mV
1.3 V
Jumper no jumper
11 Ć 10
11 Ć 9
Even Numbered
Terminals 2Ć40 not used not used
G0 RET
G1 RET
F0 (500mV)
F0 Input
F1 (500mV)
F1 Input dc source #1 @ 12mA RET
(- proximity pickup) dc source #2 @ 12mA RET
(- proximity pickup)
F2 (500mV)
F2 Input
F3 (500mV)
F3 Input
G2 RET
G3 RET
Output 0
Customer V dc #1 RET
(Outputs 0 & 1 RET)
Output 2
Customer V dc #2 RET
(Outputs 2 & 3 RET)
22
24
26
28
30
32
34
36
38
40
8
10
12
14
16
18
20
2
4
6
Odd Numbered
Terminals 1Ć39
25
27
29
31
17
19
21
23
33
35
37
39
9
11
13
15
1
3
5
7
Chassis GND
+5V dc RET
G0
G1
F0 (TTL)
F0 RET
F1 (TTL)
F1 RET
+24V dc source #1 @ 12mA
+24V dc source #2 @ 12mA
F2 (TTL)
F2 RET
F3 (TTL)
F3 RET
G2
G3
Customer V dc #1 (5 to 30V)
Output 1
Customer V dc #2 (5 to 30V)
Output 3
1771ĆWN
Actual wiring runs in this direction.
Ifmultiple power sources are used, do not exceed the specified isolation voltage.
10689ĆI
The sensor cable must be shielded. The shield:
• must extend the length ofthe cable, but be connected only at the 1771 I/O chassis
• must extend up to the point oftermination
Important: The shield should extend to the termination point, exposing just enough cable to adequately terminate the inner conductors. Use heat shrink or another suitable insulation where the wire exits the cable jacket.
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
9
Standard Magnetic Pickup
50mV threshold (F0)
Input
Device not used Ċ F0 (500mV)
F0 Input
+
-
À
6
8
2
4
10
12
Standard TTL or Open Collector
1.3V threshold (F0)
Important: To use a channel in TTL, jumper the appropriate TTL pin to the appropriate RET. To use Channel 0 in
TTL, jumper pin 9to pin 11.
Input
Device
+
not used Ċ F0 (500mV)
F0 Input
À
6
8
2
4
10
12
Wiring Examples
1771ĆWN
9
1
1
5
7
1
3
F0 (TTL) Ċ not used
F0 RET
Standard Magnetic Pickup
500mV threshold (F0)
Important: To use a channel for
500mV sensor, jumper the 500mV pin to the appropriate RET. For
Channel 0, jumper pin 10 to pin 11.
F0 (500mV)
F0 Input
Input
Device
+
-
À
Standard Prover/Store Count (G0)
6
8
2
4
10
12
1771ĆWN
5
7
1
3
9
11
F0 (TTL)
F0 RET
5-12V dc
OR
12-30V dc
-
+
S
1 external device
G0 RET
6
8
2
4
10
12
1771ĆWN
9
1
1
5
7
1
3
F0 (TTL) Ċ not used
F0 RET
1771ĆWN
5
7
1
3
9
11
G0
À
Standard Proximity using CFM Module Source (F0)
F0
Input
+24V dc source #1 @ 12mA RET (- proximity pickĆup)
+
-
Input
Device
+
not used Ċ F0 (500mV)
2
4
6
8
10
12
14
16
18
20
À
1771ĆWN
5
7
1
3
9
11
13
15
17
19
F0 (TTL) Ċ not used
F0 RET Ċ not used
+24V dc source #1 @ 12mA to power a proximity transducer
À
Publication 1771ĆIN043B-EN-P - July 2002
10
Configurable Flowmeter Module
Wiring Examples (continued)
Standard Output (O0)
External
Power Supply #1
5Ć30V dc @ 2A
+
-
+
-
À
Output 0
À
Customer V dc #1 RET
(Outputs 0 & 1 RET)
36
38
40
28
30
32
34
35
37
39
27
29
31
33
Customer V dc #1 (5 to 30V)
Output 1
+
-
À
1771ĆWN
À
For new installations, terminate the shields at the chassis. While not recommended, existing installations can continue to terminate the shields at the return (RET) terminal.
Ifmultiple power sources are used, do not exceed the specified isolation voltage.
Alternate Wiring Method- Low-signal amplitude or High-noise applications lowĆsignal amplitude or highĆnoise applications
For low-signal amplitude or high-noise applications, you can use this alternate wiring for your 1771-CFM/C module input or output signal
6
8
2
4
10
12
1771ĆWN
5
7
9
1
3
11 signal RET input device
+
conduit or other conductive enclosure
Publication 1771ĆIN043B-EN-P - July 2002
Groundthe Module
Use the following diagrams to ground your
I/O chassis and CFM module.
1
Remove a length ofcable jacket from the Belden 8761 cable.
2
Pull the foil shield and bare drain wire from the insulated wires.
bare drain wire insulated wires foil shield
3
Twist the foil shield and drain wire together to form a single strand.
Configurable Flowmeter Module
Chassis Ground
When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top ofeach ground lug.
Torque the nut with captive washer to 18(+3) pound-inches.
11
ground lug nut nut and captive washer grounding stud
I/O chassis side plate star washer ground lug
À shield and drain twisted together
À
Use the cup washer ifcrimpĆon lugs are not used.
SingleĆpoint Grounding
Extend shield to termination point.
Expose just enough cable to adequately terminate inner conductors.
19480
4
Attach a ground lug.
20
When using shielded cable wire, ground the foil shield and drain wire only at one end ofthe cable. We recommend that you wrap the foil shield and drain wire together and connect them to a chassis mounting bolt. At the opposite end ofthe cable, tape exposed shield and drain wire with electrical tape to insulate it from electrical contact.
For additional grounding information, see the Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
Use heat shrink tubing or other suitable insulation where wire exits cable jacket.
shield and drain twisted together
#10 threadĆforming screw externalĆtooth washers
19923
Publication 1771ĆIN043B-EN-P - July 2002
12
Configurable Flowmeter Module
Configure the Module
To configure the CFM module, you enter
BTW and BTR instructions into your ladder logic, then you enter data into the BTW instruction. This data should conform to the input device and specific application that you have chosen.
You can configure the module using I/O configuration software or by editing bits in the BTW instruction.
Input Capabilities
The CFM module accepts input for up to four channels
(mode dependent). Each of the four input channels may accept these input signals:
• magnetic pickup — 50mV to 30V ac
•
3-30V dc pulses with open collector (TTL compatible)
• proximity probe inputs
–
compatible with Bently Nevada 3300
(5mm and 8mm) proximity transducer systems
–
provides two isolated 24V dc power supplies
(rated at 12mA) to power external devices
During normal operation, the processor transfers 1 to 60 words to the CFM module when you program a BTW instruction to the
CFM module’s address.
IMPORTANT
You must program at least one
BTW, with a word length of 4, to get useful data back from the
CFM module.
Your PLC processor gets data from the
CFM module using BTR instructions in your ladder logic program. The CFM module transfers up to 41 words to the PLC processor’s data table file. The words contain module status and input data from each channel.
You should program a block transfer read length of zero (0). When a BTR of 0 is programmed, the CFM module will determine the correct number of words (41) to return.
Output Capabilities
The CFM module has four assignable outputs. These outputs are designed for applications that require fast response. The outputs:
• are electronically current limited to 2A
• can be assigned to any input channel with user-selectable turn-on and turn-off values
• are current sourcing at 5-30V dc (1A maximum per output)
• must be connected to an external power supply
• are in groups of two — this lets you use two separate external power supplies if desired (one for outputs 0&1 and one for outputs 2&3)
Outputs may be forced on or off independent of count or frequency value. They may be forced on and off by setting bits in the BTW configuration block.
IMPORTANT
You can assign as many as four outputs to a given channel; however, you can not use the same output with two different channels.
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
13
Modes of Operation
Use this mode
Totalizer
Nonresettable Totalizer
To
You configure the CFM module for these modes of operation:
• accurately measure counts using a flowmeter or positive displacement meter
• trigger outputs directly from the CFM module
Ċ trigger on total, frequency, acceleration
• monitor flow total, rate, and rate of change independent ofyour PLC processor scan times
• store counts based on external input
• scale the frequency and count to engineering units
• interface to a prover operate in the Totalizer mode with the count reset function disabled to prevent loss of accumulated value
Indicators/
Alarms overrange overflow overspeed acceleration overrange overflow overspeed acceleration
Prover
√
√
HighĆresolution Frequency
1
(channels 0&1 or channels 2&3)
• monitor the frequency of an input with high accuracy (e.g. shaft)
• monitor the rate ofspeed change
• operate outputs based on speed or rate ofchange
• scale the frequency to engineering units overspeed overrange acceleration
Direction Sensor
1
(channels 0&1 or channels 2&3)
1
• monitor the direction ofshaft rotation
• monitor rate ofchange and frequency
• trigger outputs based on direction, frequency, rate ofchange
• scale the frequency and count to engineering units overspeed acceleration overrange
This mode uses two channels for one input (your input device is connected to F0 or F2, while F1 or F3 is unused).
√
Total reset
√
√
√
√
Scaler values
Rollover value
√
√
In this mode of operation
Totalizer
You can assign outputs that are programmable to trigger on total, rate, rate change (acceleration), total overflow or prover status
HighĆresolution
Frequency
Direction Sensor on frequency or frequency rate of change (acceleration) on either CLOCKWISE or COUNTERĆCLOCKWISE direction, acceleration or frequency (outputs are triggered ON only)
If you want to configure the module through I/O Configuration software (if you are using a PLCĆ5 family processor by editing bits at the address ofthe
BTW instruction
1
)
You enter the appropriate information on the
CFM module edit screens.
edit the data file addresses in the BTW instruction to match your particular application. Use the word assignments on page 14 to edit the bits that apply to your application(s).
1
See PLCĆ5 Programming Software I/O Configuration Manual, publication 6200Ć6.4.12, for supported processors.
Publication 1771ĆIN043B-EN-P - July 2002
14
Configurable Flowmeter Module
BTW WordAssignments
1
2
3
4
5, 15, 25, 35
6, 16, 26, 36
7, 17, 27, 37
8, 18, 28, 38
9, 19, 29, 39
10, 20, 30, 40
11, 21, 31, 41
12, 22, 32, 42
13, 23, 33, 43
14, 24, 34, 44
45, 49, 53, 57
46, 50, 54, 58
47, 51, 55, 59
48, 52, 56, 60
15 14
Header
13 12
Bit
Á
11 10
Block ID & Resets
09 08 07 06 05 04 03 02 01 00
Prover Run Initialize Overflow Reset Total Reset
Output 1 Trigger
Output 3 Trigger
Channel 3
Output 1 andOutput 0 Trigger & Select
Tie Output 1 to Channel
Output 3 andOutput 2 Trigger & Select
Tie Output 3 to Channel
Channel 0 (words 5Ć14)
Output 0 Trigger Tie Output 0 to Channel
Output 2 Trigger Tie Output 2 to Channel
Input Channel Operating Mode
Channel 2 Channel 1 Channel 0
Input Channel Configuration
Channel 1 (words 15Ć24) Channel 2 (words 25Ć34) Channel 3 (words 35Ć44)
Frequency in 10ths
Bandwidth
Limit
Sampling
Termination
Output 0 (words 45Ć48)
4 x
High Hz
Prover
Type
Debounce
Filtering
É ÉÉ É
Minimum Frequency Sampling Time
ÉÉÉÉ
Number ofPulses to Terminate Sampling
Acceleration Calculation Time
Highest Allowable Frequency
Acceleration Alarm Value (what rate to trigger on)
Frequency Scaler Multiplier
Â
Total Scaler Multiplier
Â
Total Scaler Divisor
Â
Rollover Value Ċ Most Significant Digit (0Ć999 x 10,000)
Rollover Value Ċ Least Significant Digit (0Ć9,999)
Frequency Scaler Divisor
Â
Output Configuration
Output 1 (words 49Ć52) Output 2 (words 53Ć56)
Output ON value Ċ Most Significant Digit (0Ć999 x 10,000)
Output ON value Ċ Least Significant Digit (0Ć9,999)
Output OFF value Ċ Most Significant Digit (0Ć999 x 10,000)
Output OFF value Ċ Least Significant Digit (0Ć9,999)
À
Á
Â
Valid BTW lengths are: 0, 1, 2, 3, 4, 14, 24, 34, 44, 48, 52, 56, 60.
ALL numeric values are in binary.
When scaling is used, all outputs are still controlled by the actual value not the scaled value.
Output 3 (words 57Ć60)
For detailed BTW descriptions, see chapter 4, (publication
1771Ć6.5.99).
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
15
Interpret Module Status andInput Data
Your PLC processor gets data from the CFM module using BTR instructions in your ladder logic program. The CFM module transfers up to 41 words to the PLC processor’s data table file.
The words contain module status and input data from each channel.
You should program a block transfer read length of zero (0). When a
BTR of 0 is programmed, the CFM module will determine the correct number of words (41) to return.
BTR WordAssignments
1
2
3
4
5
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Block ID & Resets
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉ
Header
É ÉÉÉÉ É É É ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
PowerĆup bit
Output Status & Diagnostics
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉ
Output Status
Channel 3
ÉÉÉÉÉÉÉÉÉÉÉ
Mode Indication
ÉÉÉÉÉÉÉÉÉÉÉ
Channel 2
Channel 1 Status
Channel 1
Error Words & Diagnostics
Channel 0
Channel 0 Status
ÉÉÉ
Prover Status
É É É
Overrange
Alarm
Channel 3 Status
Overflow
Status
ÉÉÉ
Prover Status
ÉÉÉ
Overrange
Alarm
ÉÉÉ
Channel 0 (words 6Ć14)
Overflow
Status
Overspeed
Alarm
Overspeed
Alarm
Acceleration
Alarm
ÉÉ
ÉÉ
ÉÉ
Prover Status
Acceleration
Alarm
ÉÉ
Prover Status
Overrange
Alarm
Overflow
Status
Channel 2 Status
Overrange
Alarm
Overflow
Status
Overspeed
Alarm
Overspeed
Alarm
Acceleration
Alarm
Acceleration
Alarm
Input Channel Data
ÉÉ
Channel 1 (words 15Ć23) Channel 2 (words 24Ć32) Channel 3 (words 33Ć41)
6, 15, 24, 33
7, 16, 25, 34
8, 17, 26, 35
9, 18, 27, 36
10, 19, 28, 37
11, 20, 29, 38
Percent ofFull Scale (Rate % ofHigh RPM value)
Frequency (0Ć120 ) MSD
Frequency (0Ć999) LSD
Total MSD (0Ć999)
Total LSD (0Ć9,999)
Acceleration (rate ofchange offrequency)
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ 12, 21, 30, 39
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
13, 22, 31, 40 Prover Total Count Value or Store Count Value Ċ MSD (0Ć999)
14, 23, 32, 41 Prover Total Count Value or Store Count Value Ċ LSD (0Ć9,999)
Direction
ÉÉÉ not used
* Numeric values are in binary except for Diagnostics (word 2, bits 00Ć07)*
ÉÉÉ
For detailed BTR descriptions, see chapter 5, (publication
1771Ć6.5.99).
Publication 1771ĆIN043B-EN-P - July 2002
16
Configurable Flowmeter Module
Diagnostics and
Troubleshooting
The CFM module returns diagnostics to the PLC processor in words one and two of the BTR file. These diagnostics give you the word in the BTW configuration block that has caused an error to occur.
IMPORTANT
In the event that there are multiple incorrect
BTW words, the CFM module only returns the
first incorrect word.
word 1
Header (CFM module ID) must be 0010.
word 2
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 0 1 0
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
PowerĆup Bit indicates ifa valid BTW has occurred since powerĆup or since last switched from Program to Run mode.
VALUES: 1= no or invalid BTW
0 = yes
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
ÉÉÉÉÉ
ÉÉÉÉÉ
Output Status reflects current operating state ofoutputs.
b12 = Output 0 b13 = Output 1 b14 = Output 2 b15 = Output 3
VALUES:
0 = OFF
1 = ON
Error Words & Diagnostics displays invalid BTW word number (0Ć60 BCD).
99 = invalid BTW length
Status Indicators
Indicators
ACTIVE
INPUTS/OUTPUTS
F0 F1 F2 F3
G0 G1 G2 G3
O0 O1 O2 O3
STATUS
S0 S1 S2 S3
S4 S5 S6 S7
FAULT
The CFM module provides these status indicators:
If indicator
ACTIVE
INPUTS
(F0ĆF3 & G0ĆG3)
OUTPUTS
(O0ĆO3)
S1
STATUS
FAULT
S2
S3
Is ON the CFM module is successfully receiving power and operational a signal is present at the designated input terminal the module has commanded an output on
PowerĆup Bit (BTR word 1, bit 00) is ON
(=1) Ċ BTW hasn't occurred since powerĆup, or invalid BTW, or
PLC processor in Program mode
BTW is occurring
BTR is occurring
1. Turn off power to the I/O chassis backplane and wiring arm.
2. Reseat the CFM module in the I/O chassis.
3. Restore power to the I/O chassis backplane and wiring arm.
Important Ifthe fault LED remains on, there may be an internal problem. Contact your local
AllenĆBradley representative for additional assistance.
Is OFF a. Check FAULT LED Ċ ifon, follow the steps listed under ifFAULT is ON.
b. Check the power supply.
a signal is not present at the designated input terminal the output is off
PowerĆup Bit (BTR word 1, bit 00) is OFF (=0) Ċ valid BTW has occurred since powerĆup or since last switched from Program to Run mode
BTW is not occurring
BTR is not occurring normal operation
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
Hazardous Locations
The following information applies when operating this equipment in hazardous locations:
Products marked CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B,
C, and D Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T" number) may be used to help determine the overall temperature code ofthe system. Combinations ofequipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
!
EXPLOSION HAZARD -
•
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•
Substitution ofcomponents may impair suitability for Class I, Division 2.
•
Ifthis product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un systéme, le code de température le plus défavorable (code de température le plus faible) peut eatre utilisé pour déterminer le code de température global du systéme. Les combinaisons d'equipements dans le systéme sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
!
RISQUE D'EXPLOSION -
•
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
•
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe 1, Division 2.
•
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
17
Publication 1771ĆIN043B-EN-P - July 2002
18
Configurable Flowmeter Module
Specifications
Number ofInput Channels
Module Location
Maximum Count Value
BTW Processing Time (worst case)
Module Scan Time
Maximum Input Frequency
Inputs per Channel
Flowmeter (F0-F3) Input Voltage
Flowmeter (F0-F3) Input Impedance
Gate (G0-G3) Voltage
Gate (G0-G3) Current
Number ofOutputs
Maximum Output OffĆstate Leakage Current
Maximum OnĆstate Voltage Drop
Output Control
Output Voltage
Output Current
Output Switching Time
Filtering (F0ĆF3 inputs)
Ċ jumper selectable
Debouncing (G0ĆG3 inputs)
Ċ software selectable
Module dc Source Output
Backplane Current
Customer Supply
Isolation Voltage
Module Power Dissipation
Module Thermal Dissipation
Maximum Adjacent Slot Power Dissipation
Input Conductors
Output Conductors
Wire Type
Category
Length
Wire Size
Category
4
1771ĆA1B, ĆA2B, A3B, ĆA3B1, ĆA4B (series A and B) I/O chassis
1771ĆAM1, ĆAM2 I/O chassis with integral power supply, adapter
0-9,999,999 (programmable)
5.5ms Ċ on a configuration change
1.3-5ms (depending on configuration and frequency)
100kHz @ flowmeter Input (maximum frequency is 120kHz Ć
100kHz @ gate input overrange occurs at 100kHz)
2 - flowmeter input Ċ used for all modes gate input Ċ used in Totalizer and Nonresettable Totalizer modes
50mVĆ30V ac Ċ Magnetic Pickup
5Ć30V dc (TTL compatible)
Bently 3300 5 & 8 mm Ċ Proximity Pickups
5KΩ ± 30% resistive
5-12 and 12-30V dc
22mA maximum
4 less than 300μA @ 30V dc
0.6Ω x current
Any number ofoutputs are assignable to any of4 channels.
One turn-on" value and one turn-off" value per output.
5 to 30V dc, customer supplied
1A per channel sourced out ofmodule
All outputs can be on simultaneously without derating.
outputs triggered by Total: turn ON < 100μs; turn OFF < 100μs all other turn ON and OFF times < 1ms highĆspeed or lowĆpass filter jumper (filter = below 70Hz)
1s (approximate) between transitions with no minimum pulse width Ċ
Totalizer and Nonresettable Totalizer modes only
24V dc; 12mA; ripple: ±5%; noise: 240mV peakĆtoĆpeak
0.8A maximum, 5V dc
5 to 30V dc
Tested to withstand - for 60s
500V between input and backplane,
1500V between output and backplane,
500V between isolated channels,
1500V between isolated outputs and gates
13W (maximum); 2W (minimum)
54.2 BTU/hr (maximum); 6.8 BTU/hr (minimum)
11W
Belden 8761
Category 2
1
304.8m (1000ft)
14AWG (2.5mm
2
Category 2
1
) solid or stranded copper wire rated @ 60 o
C or greater
Publication 1771ĆIN043B-EN-P - July 2002
Configurable Flowmeter Module
Environmental Conditions
Operating
Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Nonoperating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
32 to 131°F (0 o to 60 o
C)
IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)
-40 to 185°F (-40 to 85 o
C)
IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)
5 to 95%, noncondensing
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g
50g
Vibration
ESD Immunity
Radiated RF Immunity
IEC 60068-2-6 (Test Fc, Operating)
2g @ 10-500Hz
IEC 61000-4-2
4kV contact discharges
IEC 61000-4-3
10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
10V/m, with 200Hz 50% Pulse 100%AM from at 900MHz
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Emissions
Enclosure Type Rating
Keying (lower backplane connector)
IEC 61000-4-4
+1kV @ 5kHz on signal ports
IEC 61000-4-5
+2kV line-earth (CM) on signal ports
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
CISPR 11
Group 1, Class A (with appropriate enclosure)
None (open-style)
Between 2 and 4
Between 6 and 8
Field Wiring Arm
Wiring Arm Screw Torque
User Manual
Catalog Number 1771ĆWN
9 pound-inches (1.0Nm)
Publication 1771-6.5.99 (See User Manuals on page 20.)
1
2
Certifications
(when product is marked)
UL
CSA
CSA
EEx
CE
2
2
C-Tick
2
UL Listed Industrial Control Equipment
CSA Certified Process Control Equipment
CSA Certified Process Control Equipment for Class I,
Division 2 Group A, B, C, D Hazardous Locations
European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres,
Protection n"
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2, Industrial Immunity
EN 61236, Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2, Industrial Immunity
EN 61000-6-4, Industrial Emissions
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial
Automation Wiring and Grounding Guidelines.
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details
19
Publication 1771ĆIN043B-EN-P - July 2002
20
Configurable Flowmeter Module
European Zone 2 Certification
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/CE.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction ofCategory 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021 (1999).
IMPORTANT
Observe the following additional Zone 2 certification requirements:
• This equipment is not resistant to sunlight or other sources ofUV radiation.
• The secondary ofa current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
• Equipment oflesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I,
Zone 2 environments.
• This equipment shall be used within its specified ratings defined by
Allen-Bradley.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances ofmore than 40% when applied in
Class I, Zone 2 environments.
User Manuals
Thank you for purchasing this product. This product has a user manual associated with it. Ifyou would like a manual, you can:
S download a free electronic version from the internet:: www.ab.com/manuals or www.theautomationbookstore.com
S purchase a printed manual by:
–
contacting your local distributor or Rockwell
Automation representative,
–
visiting www.theautomationbookstore.com and placing your order
–
calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)
The publication number ofthe user manual for your product is listed under Specifications."
CSA logo is a registered trademark ofthe Canadian Standards Association
PLC is a registered trademark ofAllenĆBradley Company, Inc.
PLCĆ2/02, PLCĆ2/05, PLCĆ2/16, and PLCĆ2/17 are trademarks ofAllenĆBradley Company, Inc.
PN957689-89
Copyright 2002 Rockwell Automation, Inc. Printed in USA
Advertisement
Key features
- Configurable inputs
- Assignable outputs
- Prover mode
- Totalizer mode
- High-resolution frequency mode
- Direction sensor mode
- Rollover value