Control gear for Supply and Exhaust Air Handling Units VS 10

Add to my manuals
67 Pages

advertisement

Control gear for Supply and Exhaust Air Handling Units VS 10 | Manualzz
Control gear for Supply
and Exhaust Air Handling Units
EN
VS 10-15 CG ACX36-1;
VS 21-150 CG ACX36-2 SUP;
VS 21-150 CG ACX36-2 SUP-EXH
VS 180-300 CG ACX36-2 SUP-EXH
VS 400-650 CG ACX36-2 SUP-EXH
Operation and Maintenance Manual
DTR-CG ACX36-ver.3.6 (05.2009)
EN
The control gear complies with European Standard
IEC/EN 60439-1 + AC Standard Switchboards and low-voltage control gears
www.vtsgroup.com
Table of Content
I. USER'S MANUAL ........................................................................... 3
1. DESCRIPTION OF CONTROLS ....................................................................................................... 3
1.1. Introduction ..................................................................................................................................... 3
1.2. Mains Switch .................................................................................................................................. 3
1.3. Communication port ....................................................................................................................... 3
1.4 Signalling controller status .............................................................................................................. 4
1.5. Advanced control panel VS 00 HMI Advanced ............................................................................. 4
1.6. Simplified control panel - VS 00 HMI Basic .................................................................................... 5
1.7. „SaphirScope” - diagnostic and control software ............................................................................ 6
2. SYSTEM START-UP......................................................................................................................... 6
3. SYSTEM OPERATION ..................................................................................................................... 9
4. TIME ZONES PROGRAMMING ..................................................................................................... 14
4.1 Setting current date and time ........................................................................................................ 15
4.2 Sample program/factory setting .................................................................................................... 15
II. ADVANCED MANUAL ..................................................................17
5. ADVANCED PARAMETERS AND FEATURES OF THE CONTROLLER..................................... 17
5.1 Access to advanced parameters ................................................................................................... 17
5.2 Advanced parameters ................................................................................................................... 17
6. DESCRIPTION OF CONTROL ALGORITHMS .............................................................................. 28
7. TECHNICAL DATA .........................................................................................................................34
7.1 Control gear ...................................................................................................................................34
7.2 ACX36.040 controller ....................................................................................................................35
8. CABLING ........................................................................................................................................ 36
Appendix 1 DESCRIPTION OF ALARM STATUSES ....................................................................... 41
Appendix 2 Circuit diagram of VS 10-15 CG ACX36-1 control gear .............................................43
Appendix 3 Circuit diagram of VS 21-150 CG ACX36-2 SUP control gear ..................................45
Appendix 4 Circuit diagram of VS 21-150 CG ACX36-2 SUP-EXH control gear ............................ 47
Appendix 5 Circuit diagram of VS 180-300 CG ACX-2 SUP-EXH ..................................................49
Appendix 6 Circuit diagram of VS 400-650 CG ACX-2 SUP-EXH .................................................. 52
VTS reserves the right to implement changes without prior notice
1
EN
Appendix 7 Circuit diagram of power and motor connection for VS 10-15 CG ACX-1 SUP and
SUPEXH control gears ......................................................................................................................56
Appendix 8 Circuit diagram of power and motor connection for VS 21-150 CG ACX36-2 SUP
control gear........................................................................................................................................ 57
Appendix 9 Circuit diagram of power and motor connection for VS 21-150 CG ACX36-2 SUPEXH control gear (used also for VS 180-300 supply) ....................................................................58
Appendix 10 Circuit diagram of power and motor connection for VS 180-300 CG ACX-2 SUPEXH control gear (used also for VS 400-650 supply) ....................................................................59
Appendix 11 Circuit diagram of power and motor connection for VS 400-650 CG ACX-2 SUPEXH control gear ...............................................................................................................................60
Appendix A Circuit diagram of motor connection depending on the type of the frequency
converter ............................................................................................................................................ 61
Appendix 12 The application control schemes .............................................................................. 62
Appendix 13 DESCRIPTION OF NETWORK VARIABLES ..............................................................63
EN
VTS reserves the right to implement changes without prior notice
2
I. USER'S MANUAL
1. DESCRIPTION OF CONTROLS
1.1. Introduction
Application:
Protection and control of supply and exhaust AHUs equipped
with up to:
○ two fan sets (up to 8 fans in total) and two air dampers
○ cooler, heater and heat recovery system
○ three filtration sections
Range of operation:
VS 21-150 CG ACX36-2 SUP
VS 21-150 CG ACX36-2 SUP-EXH
VS 10-15 CG ACX36-1
VS 180-300 CG ACX36-2 SUP-EXH
VS 400-650 CG ACX36-2 SUP-EXH
Systems equipped with Systems equipped with frequency
one-phase motors with converters and motors with up to
up to 1.75kW power
11kW power output
output
1.2. Mains Switch
O - OFF
I - ON
00' '
Switched off
*0/
Switched off Switched on
Switched on
Function:
Switching-on the Control Gear.
1.3. Communication port
RJ45 socket, dependent on the casing type, is placed
on the bottom or on the front of the control gear
Function:
Connecting the VS 00 HMI Advanced control panel to
the controller
VTS reserves the right to implement changes without prior notice
User’s Manual
3
EN
1.4 Signalling controller status
In a right lower corner of the controller there is a LED indicating the controller's operation mode:
1. LED switched off – controller is not connected to power supply
2. Green light blinking – correct operation, controller controls AHU operation
3. Green and red light blinking - program stopped (see program „Scope”)
4. Red light – controller error
!
1. All control boxes from the VS…CG ACX36 typeline need to be powered from the main switchgear
equipped with appropriate protection of wires powering the control box.
2. Connection and start-up of the control gear should by done by qualified staff only.
Without additional elements the control gears can work inside a building. Assembly outside in a
moderate climate is permissible if an additional heating module is assembled. The X0:4,N clamps are
designed for this module. (230V, 6A)
1.5. Advanced control panel VS 00 HMI Advanced
EN
LCD display
Displaying available
parameters and current values
Back
Going back to master page
or to the beginning of the
displayed page
Operation mode
Cyclic switching of the AHU
operation:
ƒ Auto (acc. to calendar)
ƒ ON system switched on
ƒ OFF system switched off
ƒ Stby (stand-by) system switches
on and off in cycles depending on
the temperature difference
The fan status is also signalled with
the green LED
ƒ Constant lighting-up – system in
ON mode
ƒ LED switched off – system in OFF
mode
ƒ LED blinking – fans switched off or
on, (Auto, Stby)
Main page
Going back to the main page
regardless of a current
display status
Navi buttons
Pushing a button allows
swapping parameters - up
and down
Information about alarms.
Pressing a key displays a window
with codes of current alarms. Next
pressing a key cancels the alarm.
Alarms indicated are with LED's
red light.
Confirmation
1. Moving to secondary pages.
2. Entering edit mode of
selected parameter value
Edit buttons
Increasing or decreasing value of
a selected parameter. Swapping
parameters right, left
Magnetic bottom
It allows for simple installation of the panel on flat
metal surface, e.g.: control gear door
VTS reserves the right to implement changes without prior notice
4
User’s Manual
Functions:
▪ Controller operation and parameterization
▪ Selection of control application
▪ Access to operation parameters of the AHU subassemblies
▪ Time zones setting
▪ Displaying and cancelling alarm statuses
!
Parameters available in the LCD window depends on a AHU type and automatic control
application. So in AHUs not equipped with heater, options related to the heating module will
not be available.
Optional element.
1.6. Simplified control panel - VS 00 HMI Basic
EN
Type of air handling
ƒ Cooling
ƒ Heating
LCD display
ƒ current temperature from
leading sensor
ƒ preset temperature
ƒ operation mode
ƒ alarm code
Operation mode
ƒ system switched off
ƒ operation according to calendar
ƒ by
ƒ system switched on - 2/3 output
power
ƒ system switched on - full output
power
ƒ OFF system switched off
STAND-BY system switches on and
Edit buttons
Increasing or decreasing preset
temperature
Temperature sensor
Built-in room temperature sensor.
Changing operation mode
buttons
Functions:
▪ Room temperature measurement
▪ Change and display of set temperature value
▪ Display temperature of the main control sensor
▪ Change of AHU operation mode
▪ Info on alarm status
Optional element
VTS reserves the right to implement changes without prior notice
User’s Manual
5
1.7. „SaphirScope” - diagnostic and control software
Program variables window
Access to all program variables.
Possibility of generating timebased charts of any variables
VS 00 HMI Advanced Emulator
Access to all program variables
with virtual panel
Calendar
Convenient programming of AHU
operation modes according to
annual calendar
EN
System requirements:
Pentium II 400 MHz CPU,
RS 232 serial port
Windows NT 4.0 (Service Pack 5), XP.
Information concerning program's operation and features are provided in a separate manual "SaphirScope
- user's manual"
2. SYSTEM START-UP
CAUTION!
!
Operation of the AHU is strictly arrested by the fire-protection alarm, activation of the thermal
protection of fans' motors, threefold activation of the protection of electric heater and threefold
activation of the anti-frost thermostat. Each of these events requires removing the cause of the
alarm and then canceling it (see more details in „Advanced Manual” chapter).
VTS reserves the right to implement changes without prior notice
6
User’s Manual
ÃÃÃÃÃ
Set Mode:
Status:
Temp Setp
Main Temp
STATUS
ÃÃÃÃÃ
On
Heating
22 oC
19 oC
ÆMENU
The number of the operating system is available in the advanced
parameters.
Operation mode: On Off Auto Stby
Info on selected AHU operation mode Description of available models
is presented in the following sections of this manual.
Status: Vent Off Heating Cooling PreHeating
Info on current operation mode of the AHU.
Vent – AHU switched on (only fans are running)
Off – centrala wyłączona
Heating – AHU switched on, heating process activated
Cooling – AHU switched on, cooling process activated
Switching on power
supply of the control gear
with the mains switch
(Q1M). Correct controller
operation is indicated by
blinking green LED in the
right lower corner of the
controller. If the LED is
blinking in red or does not
blink at all, contact the
service center.
The system is ready for
operation after about 25
seconds from switching on.
VS 00 HMI Advanced
ON (SWITCHED ON)
VS 00 HMI Basic
Switching on power supply
I - ON
Preliminary heating - this function is activated during AHU start-up and it
prevents supply air with external temperature from blowing into the duct. This
function is activated at external temperature below 8oC.
Temp Setp: 5...50oC
Info on preset air temperature. Upper and lower value of permissible preset
temperature can be determined in the ADVANCED TEMPERATURE tab
Main Temp: -64...64oC
Info on air temperature in the leading sensor area, which may be the room
temperature sensor as well as supply or exhaust duct sensor. The leading
sensor can be selected in the ADVANCED UNIT COFIG
MENU
Accessing the window with a list of available parameters and settings.
During first few seconds from switching on the device, the window
displays 888 and E15 in sequence. In case of correct communication
the window shows the temperature value from the leading temperature
sensor.
If the system did not start, check the F1 protection status
Correct device operation depends on the application settings. Choosing and setting up the application
should be done by qualified service provider, according to recommendations of part II "Advanced manual"
VTS reserves the right to implement changes without prior notice
User’s Manual
7
EN
The AHU can operate in one of the following
operation modes.
ÃÃÃ
OFF (switched off) – fans stopped,
dampers and control valves closed All
sensors and gauges are activated. Any
possible alarms are indicated
60% output – this option is available in
the VS 00 HMI Basic only. The system is
switched on and fans speed is reduced
to 60% of the value set in the VS 00 HMI
Advanced.
PL - POLSKI
RU - PYCCKU
EN - ENGLISH
PL
STATUS
ÃÃÃÃÃ
On
Off
22 oC
19 oC
1 sek..
OFF
VS 00 HMI Basic
Selection of operation mode
ÃÃÃÃÃ
Set Mode:
Status:
Temp Setp
Main Temp
ON (switched in) – AHU operates in line
with settings of the control panel
Stby (Stand-by) – system is activated if
the preset temperature is 2°C higher than
the measured one. In the same way the
system is deactivated if the measured
temperature is 2°C higher than the preset
one. The measured temperature is get
from the VS 00 HMI Basic, and if the
module is not supported, from the main
control sensor.
ÃÃÃPL / RU / ENÃÃÃ
ÃÃÃ
ÆMENU
Auto – AHU operates in line with defined
time settings. Programming of time zones
is described in I.4
EN
MENU
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
VS 00 HMI Advanced
Language selection
VS 00 HMI Advanced supports the following
languages:
EN English
PL Polish
RU Russian
English is set as a default language.
Stby
Auto
60 % output
ON
If both control panels are connected, any change entered in one of the panels updates
automatically the data in the other panel and controller.
In controller there is also a possibility to set temperature with a rheostat (see II Advanced manual,
parameter: MultiFuncAnaIn)
VTS reserves the right to implement changes without prior notice
8
User’s Manual
3. SYSTEM OPERATION
ÃÃÃ
MENU
PARAMETERS
TEMPERATURES
...
Min SupTemp W.....X
minimal acceptable temperature value in the supply
duct.
Max SupTemp W.....X
maximal acceptable temperature value in the supply
duct.
VS 00 HMI Advanced
Temp Offset
preset temperature value after correction. The
parameter can be changed only with VS 00 HMI
Basic in range of +/- 4.5oC
MENU
PARAMETERS
FAN
PARAMETERS ÃÃÃ
ÆTEMPERATURES
Æ FAN
ÆHEATER
ÆCOOLER
ÆRECOVERY
ÆAF DAMPER
ÃÃÃ
22.0 oC
-3.0 oC
16.0 oC
30.0 oC
HMI TempSetp
Temp Offset
Min SupTemp
Max SupTemp
EN
...
Modification of AHU output can be carried out by
changing voltage frequency feeding the fan motor.
100% output should correspond to the frequency at
which the AHU reaches its rated output. (see MENU
ADVANCED FAN SETTINGS SUPPLY…, ...
EXHAUST...
Sup Air Flow: W......X
Preset output on the supply side
Sup Fan Speed:
Preset speed of the supply fan. Uneditable
parameter, calculated basing on the preset frequency
and motor parameters.
Exh Air Flow: W......X
Preset output on the exhaust side
ÃÃÃ
VS 00 HMI Advanced
Changing AHU output
ÃÃÃ
ÃÃÃ TEMPERATURES
Range of HMI Temp Setp MinSupTemp,
MaxSupTemp, parameters acceptable for edition can
be changed in advanced parameters.
Temperature change is carried out with edit buttons
in range of +/- 4.5°C around the temperature set in
the controller with the VS 00 HMI Advanced or Scope
program.
ÃÃÃ
VS 00 HMI Basic
Changing temperature parameters
HMI Temp Setp W.....X
preset temperature value from VS 00 HMI Advanced.
MENU
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
ÃÃÃ
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
ÃÃÃ
PARAMETERS ÃÃÃ
ÆTEMPERATURES
ÆFAN
ÆHEATER
ÆCOOLER
ÆRECOVERY
ÃÃÃ
Exh Fan Speed:
Preset speed of the exhaust fan. Uneditable
parameter, calculated basing on the preset frequency
and motor parameters.
MENU
FAN ÃÃÃ
Sup Air Flow:
Sup Fan Speed:
62 %
1798 RPM
Exh Air Flow:
Exh Fan Speed
80 %
2320 RPM
Range of SupAirFlow and ExhAirFlow parameters
acceptable for edition can be changed in advanced
parameters.
VTS reserves the right to implement changes without prior notice
User’s Manual
9
MENU
PARAMETERS
HEATER
...
Heating Rate: 0...100 %
Percentage value of setting water heater valve or
heating level of the electric heater.
AirSideTherm.: OK
FLT
Info on the anti-frost thermostat status on the air
side
ÃÃÃ
OK – short contact, no alarm
FLT – open circuit, risk of freezing the water heater
WaterSideTherm: OK
FLT
Pump: ON
OFF
Info on a signal controlling the pump operation
ON – short contact – signal switching on the pump
Triggered if control percentage value of the
heater is over 5%.
OFF – open contact – pump switched off
ÃÃÃ
VS 00 HMI Advanced
Heater's parameters
OK – short contact, no alarm
FLT – open contact, risk of freezing the water
heater or/and hydraulic system
ÃÃÃ
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
Info on the anti-frost thermostat status on the water
side
EN
MENU
PARAMETERS ÃÃÃ
ÆTEMPERATURES
ÆFREQUENCY
ÆHEATER
ÆCOOLER
ÆRECOVERY
ÃÃÃ
HEATER ÃÃÃ
Heating Rate
AirSideTherm
WaterSideTherm
Pump
Pump Kick
PumpMinOutTemp
10 %
OK
OK
ON
OFF
5.0 oC
Pump 30sec/7days: WONXWOFFX
A parameter activating cyclic switch-on of the water
heater for 30 seconds every 7 days.
ON – activated function
OFF – deactibvated function
ÃÃÃ
HEATER ÃÃÃ
Heating Rate
Status
10 %
OK
PumpMinOutTemp: W -30...10 X oC
The temperature value below which the water
pump operates in a continuous manner, regardless
of heating requirements in the system.
Status: OK FLT
Info on a status of the protections' thermostat of the
electric heater
OK – short contact, no alarm
FLT – open contact, risk of electric heater
overheating.
VTS reserves the right to implement changes without prior notice
10
User’s Manual
MENU
PARAMETERS
COOLER
...
Cooling: 0...100 %
Control percentage of the water cooler valve
VS 00 HMI Advanced
Cooler's parameters
PARAMETERS ÃÃÃ
ÃÃÃ
RefrigUnit: OK FLT
Info on the cooling system status
OK – short contact, no alarm
FLT – open contact, incorrect operation status of
the cooling system
MinOutTemp: W 0...40 XoC
The temperature value under which the cooling
is blocked. Water valve is closed, refrigerator and
compressors of freon cooler are switched off.
ÆTEMPERATURES
ÆFAN
ÆHEATER
ÆCOOLER
ÆRECOVERY
COOLER ÃÃÃ
ÃÃÃ
Cooling Rate
RefrigUnitState
RefrigUnit
10 %
ON
OK
MinOutTemp
16 oC
ÃÃÃ
COOLER ÃÃÃ
OFF
Info on a signal controlling operation of the first
level cooling system of the freon cooler
ON – short contact – signal switching on the system.
OFF – open contact – system switched off
Stage 2: ON
ÃÃÃ
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
ON – short contact – signal switching on the
pump Triggered if control percentage value
of the cooler is over 5%.
OFF – open contact – cooling system switched off
Stage 1: ON
MENU
ÃÃÃ
RefrigUnitState: ON OFF
Info on a signal controlling operation of the cooling
system
Stage 1
Stage 2
ON
OFF
RefrigUnit
MinOutTemp
OK
16 oC
OFF
Info on a signal controlling operation of the second
level cooling system of the freon cooler
ON – short contact – signal switching on the system.
OFF – open contact – system switched off
VTS reserves the right to implement changes without prior notice
User’s Manual
11
EN
MENU
PARAMETERS
RECOVERY
...
RecRate: 0...100 %
Percentage value of opening of cross-flow exchanger,
recirculation damper, percentage value of the rotary
exchanger's speed.
AfterRecTemp -64...+64 oC
Temperature value measured behind the heat
recovery system on the exhaust side
ÃÃÃ
TempLimit W -10...20 XoC () 0 oC)
Minimal acceptable temperature value measured
behind the heat recovery system on the exhaust side.
It is recommended to set temperature higher than
0 oC.
ManMode: W ON XW OFF X () OFF)
The parameter for switching on or off the recirculation
damper on a constant level, set in the ManModeSetp
parameter.
ON – manual mode switched on
OFF – manual mode switched off
If the system is in a calendar mode, the mode
change is carried out in the calendar assembly's
window
ÃÃÃ
ÃÃÃ
PARAMETERS ÃÃÃ
ÆTEMPERATURES
ÆFAN
ÆHEATER
ÆCOOLER
ÆRECOVERY
VS 00 HMI Advanced
Parameters of heat recovery
MaxRecRate W 0...100 X % () 70 %)
Limit of recirculation level The system controls
automatically the recirculation damper, depending on
requirements of heating or cooling, from 0 to the value
set in this parameter.
EN
MENU
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
MaxRecRate W 0...100 X % () 30 %)
Recirculation level in the manual mode of recirculation
control.
MinFreq W 10...20 X Hz () 15 Hz)
Lower limit of the supply voltage frequency of the
rotary exchanger motor.
MaxFreq W 21...60 X Hz () 53 Hz)
Upper limit of the supply voltage frequency of the
rotary exchanger motor.
RRGFCStatus OK FLT
Status of the rotary exchanger drive
OK – no alarm
FLT – incorrect drive operation status
RECOVERY ÃÃÃ
ÃÃÃ
RecRate
AfterRecTemp
TempLimit
ÃÃÃ
100 %
16 oC
5 oC
RECOVERY ÃÃÃ
RecRate
MaxRecRate
ManMode
ManModeSetp
ÃÃÃ
100 %
30 %
Ma OFF
15 %
RECOVERY ÃÃÃ
RecRate
AfterRecTemp
TempLimit
MinFreq
MaxFreq
RRGFCStatus
100 %
16 oC
5 oC
30 Hz
10 Hz
OK
RRGCom
OK
RRGCom FLT
Communication status with the rotary exchanger drive
OK – communication ok
FLT – no communication
The MaxFreq i MinFreq parameter should be
adjusted in accordance with documentation of the
rotary exchanger drive.
VTS reserves the right to implement changes without prior notice
12
User’s Manual
MENU
PARAMETERS
AF DAMPER
...
SupAirRate: 0...100 %
Percentage value of supply damper opening.
ÃÃÃ
PARAMETERS ÃÃÃ
ÆTEMPERATURES
ÆFAN
ÆHEATER
ÆCOOLER
ÆAF DAMPER
TempLimit W -10...20 XoC () 0 oC)
Minimal acceptable temperature value measured
behind the heat recovery system on the exhaust
side. It is recommended to set temperature higher
than 0oC.
ÃÃÃ
AF DAMPER ÃÃÃ
SupAirRate
TempLimit
MENU
PARAMETRY
SEZON
ÃÃÃ
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
VS 00 HMI Advanced
Heat recovery parameters in one-phase systems
Change of water exchanger’s funfction
MENU
ÃÃÃ
...
100 %
5 oC
EN
MENU
PARAMETERS
CALENDAR
PL / RU / EN
PASSWORD
ADVANCED
DISPLAY
Operation Mode W Summer X W Winter X
Selecting functions of water exchanger in systems
with one coil operating as a cooler or heater.
PARAMETERS
TEMPERATURES
FAN
HEATER
COOLER
RECOVERY RATE
AIR SUP. DAMPER
SEASON
Change of operation mode is available by HMI
Advanced or by external switch, after suitable
configuration of universal digital input.
SEASON
Summer – cooling function
Operation mode
Summer
Winter – heating function
VTS reserves the right to implement changes without prior notice
User’s Manual
13
4. TIME ZONES PROGRAMMING
The calendar is divided into three ranges with different priorities.
Range
Priority
Annual
1 highest
Weekly
2
Daily
3 highest
Priority idea
Settings
Actual AHU operation on 09.10.2005
Range
Setting
Date
Annual
Switched on
09.10.2005 07:00 AM-08:00 PM Sunday
Weekly
Switched off
06:00 AM - 09:00 PM Sunday
Daily
Stand-by
06:00 AM - 10:00 PM
EN
MENU
CALENDAR
05:25 PM
08:30 PM
09:05 PM
Switched on
Switched off
Stand-by
...
MODE
Setting AHU operation mode. Available modes:
Switched on, switched off, stand-by
TEMPERATURES
Setting preset operation temperature
ÃÃÃ
Setting preset fan speed Setting range acceptable
for edition is specified in the advanced parameters
MAN MIX CMBR
Setting the mixing chamber in automatic or
manual mode.
MAN MIX CMBR STP
Setting recirculation level in manual operation
mode of the mixing chamber.
VS 00 HMI Advanced
Calendar parameters
FAN SPEED
MENU
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
ÃÃÃ
CALENDAR ÃÃÃ
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMAN MIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
ÆDATE/TIME
Set DefaultCal
MAX REC RATE STP
Setting maximal recirculation level in automatic
operation mode of the mixing chamber.
ÃÃÃ
No
DATE / TIME
Setting current date and time.
Set DefaultCal
Back to factory setting described in the „Sample
program/factory setting” section
VTS reserves the right to implement changes without prior notice
14
User’s Manual
4.1 Setting current date and time
ÃÃÃ
ÃÃÃ
MENU
ÃÃÃ
CALENDAR ÃÃÃ
ÃÃ DATE AND TIME ÃÃ
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCES
ÆLCD SETTINGS
Time
01:15:07
Date
09:12:2005
ÆDATE/TIME
Set DefaultCal
No
4.2 Sample program/factory setting
Date
Setting
Mode
Output
Temperature
Recirculation
20oC
70% Auto
Monday - Friday
07:00 AM-05:00 PM
Switched on
05:00 PM-07:00 AM
Stand-by
100%
o
100%
20 C
100% Auto
Saturday – Sunday
Saturday 07:00 AM- Saturday 03:00 PM
Switched on
80%
20 oC
70% Auto
Saturday 03:00 PM - Monday 07:00 AM
Stand-by
80%
20 oC
100% Auto
60%
16 oC
95%Auto
Holiday
25.12.2005 07:00 AM - 27.12. 2005 07:00 AM
ÃÃÃ
Stand-by
CALENDAR ÃÃÃ
ÃÃÃ
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
ÆDATE/TIME
Set DefaultCal
ÃÃÃ
Time
State
Active
ZONE 1 ÃÃÃ
ÃÃÃ
07:00
ON
Yes
Start
End
State
Active
No
Start
End
State
Active
WEEK 1 ÃÃÃ
Sa, 07:00
Sa, 15:00
ON
Yes
YEAR ÃÃÃ
25.12 7:00
27.12 7:00
Stby
Yes
7
Setting a mode
1
3
2
ÃÃÃ
MODE
ÆZONE 1
ÆZONE 2
ÆZONE 3
ÆZONE 4
ÆZONE 5
ÆZONE 6
ÃÃÃ
5
4
6
ÃÃÃ
Time
State
Active
ZONE 2 ÃÃÃ
ÃÃÃ
17:00
Stby
Yes
Start
End
State
Active
WEEK 2 ÃÃÃ
Sa, 15:00
Su, 07:00
Stby
Yes
ÆWEEK 1
ÆWEEK 2
ÆWEEK 3
ÆWEEK 4
ÆWEEK 5
ÆYEAR 1
ÆYEAR 2
ÆYEAR 3
If all zones are inactive, the system set in the calendar mode will be stopped.
VTS reserves the right to implement changes without prior notice
User’s Manual
15
EN
ÃÃÃ
ÃÃÃ
CALENDAR ÃÃÃ
ÃÃÃ
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
ÆDATE/TIME
Set DefaultCal
ÃÃÃ
No
07:00
20 oC
Yes
ÆDATE/TIME
Set DefaultCal
3
2
ÃÃÃTEMPERATURE ÃÃÃ
4
ÆZONE 1
ÆZONE 2
ÆZONE 3
ÆZONE 4
ÆZONE 5
ÆZONE 6
ÃÃÃ
YEAR ÃÃÃ
Start
End
Value
Active
ÆWEEK 1
ÆWEEK 2
ÆWEEK 3
ÆWEEK 4
ÆWEEK 5
ÆYEAR 1
ÆYEAR 2
ÆYEAR 3
ÆYEAR 4
25.12 7:00
27.12 7:00
16 oC
Yes
ÃÃÃ
ÃÃÃ
Start
End
Value
Active
ÃÃÃ FAN SPEEDÃÃÃ
ÆZONE 1
ÆZONE 2
ÆZONE 3
ÆZONE 4
ÆZONE 5
ÆZONE 6
WEEK 1 ÃÃÃ
Sa, 07:00
Su, 07:00
80 %
Yes
9
10
ÆWEEK 1
ÆWEEK 2
ÆWEEK 3
ÆWEEK 4
ÆWEEK 5
ÆYEAR 1
ÆYEAR 2
ÆYEAR 3
ÆYEAR 4
ÃÃÃ
Start
End
Value
Active
YEAR ÃÃÃ
25.12 7:00
27.12 7:00
60 %
Yes
If all zones are inactive and the system will be
set in the calendar mode, changing the preset
frequency will be possible with the VS HMI 00
Basic and VS HMI 00 Advanced
CALENDAR ÃÃÃ
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
Setting the recirculation level
07:00
100%
Yes
8
No
6
If all zones are inactive and the system will be
set in the calendar mode, changing the preset
temperature will be possible with the VS HMI 00
Basic and VS HMI 00 Advanced
ZONE 1 ÃÃÃ
7
5
Setting air output
Setting a temperature
1
EN
Time
Value
Active
ÆMODE
ÆTEMPERATURE
ÆFAN SPEED
ÆMIX CMBR
ÆMAN MIX CMBR STP
ÆMAX REC RATE STP
ZONE 1 ÃÃÃ
Time
Value
Active
CALENDAR ÃÃÃ
ÆDATE/TIME
Set DefaultCal
ÃÃÃ
Time
Value
Active
No
ZONE 1 ÃÃÃ
ÃÃÃ
07:00
70%
Yes
Start
End
Value
Active
1
WEEK 1 ÃÃÃ
Sa, 07:00
Sa, 15:00
70 %
Yes
7
ÃÃÃ
2
ÃÃÃMAX REC RATE STPÃÃÃ
ÆZONE 1
ÆZONE 2
ÆZONE 3
ÆZONE 4
ÆZONE 5
ÆZONE 6
3
5
4
6
ÃÃÃ
Time
Value
Active
ZONE 2 ÃÃÃ
Start
End
Value
Active
ÃÃÃ
17:00
100 %
Yes
Start
End
Value
Active
ÆWEEK 1
ÆWEEK 2
ÆWEEK 3
ÆWEEK 4
ÆWEEK 5
ÆYEAR 1
ÆYEAR 2
ÆYEAR 3
ÆYEAR 4
YEAR ÃÃÃ
25.12 7:00
27.12 7:00
95 %
Yes
WEEK 2 ÃÃÃ
Sa, 15:00
Mo 7:00
100 %
Yes
If all zones are inactive and the system will be set in the calendar mode, changing the preset frequency
will be possible with the VS HMI 00 Advanced
VTS reserves the right to implement changes without prior notice
16
User’s Manual
II. ADVANCED MANUAL
All works inside the control gear must be performed with power of all external systems
cooperating with the control gear switched off Even if the Q1M, mains switch is turned off,
some external circuits control voltage may be present on the terminal strip.
!
Further part of the manual is designed for experienced users and service men, who made themselves
acquainted with operation of the VS 00 HMI Advanced or/and use the SAPHIRScope application.
5. ADVANCED PARAMETERS AND FEATURES OF THE CONTROLLER
Pay utmost attention to selection of the automatic control application Inappropriate selection
may result in improper AHU operation and significant loss of energy.
!
5.1 Access to advanced parameters
Access to lists of
parameters:
SERVICE ACCESS
LCD SETTINGS
and alarms
cancellation is possible
after providing the
password.
ÃÃÃ
MENU
ÃÃÃ
ÃÃÃ
PASSWORD
ÃÃÃÃ
ÆPARAMETERS
ÆCALENDAR
ÆPL / RU / EN
ÆPASSWORD
ÆSERVICE ACCESS
ÆLCD SETTINGS
ÃÃÃ
ÃÃÃÃ
Enter
8ÃÃÃ
cd Enter
Ã8ÃÃ
cd Enter
ÃÃ8Ã
cd Enter
ÃÃÃ8
cd Enter
Factory password: 8888
Automatic
return to the
STATUS
window
Changing a password is possible with the SAPHIRScope program only. The password is available under the
parameter: ACX36 / EnableObjects / PWD-Config / PasswordLevel8
5.2 Advanced parameters
SERVICE ACCESS
MENU
PARAMETERS
CALENDAR
PL / RU / EN
PASSWORD
SERVICE ACCESS
LCD SETTINGS
UNIT CONFIG
FC CONFIG
DIGITAL INPUTS
DIGITAL OUTPUTS
ANALOGUE INPUTS
ANALOGUE OUTPUTS
Access to some parameters depends on a selected
code of the application.
TIMERS
PI CONTROLERS
FAN SETTINGS
TEMP PARAMITERS
USER PROG
MANUAL MODE
OS
6.24
VTS reserves the right to implement changes without prior notice
Advanced manual
17
EN
User's controller
MENU
Converter type
Leading sensor
Application code
Type of control gear
UNIT CONFIGÃ
...
Mode: W Run XW Conf X () Conf)
Current system status.
Run - controller in normal operation mode, it controls the unit in line with set parameters.
Conf - controller is in configuration mode, system control is stopped, the executive device is switched off.
Only in this state this is possible to change parameters of control gear, controller and frequency converters.
Applies to windows:
UNIT CONFIGÃ
FC PROG.Ã
!
EN
SERVICE ACCESS
After setting required parameters, go back to the Run mode. After confirming the status with the
ENTER button, the STATUS window will appear on the display after a while (about 5 seconds).
From that moment the system starts the configuration process and after next 25 seconds it is ready
to start operation with new settings.
Type of control gear: W 1 XW 3 X () 1)
Selection of control gear type.
1 – one-phase control gear: VS 10-15 CG ACX36-1
3 – three-phase control gear: VS 21-150 CG ACX36-2
One- and three-phase type of the control gear depending on a type of connected motor and not on the
method of supplying power to the control gear.
Application type W AS XW AP XW AR XXW AD X () AS)
Selection of application type. Type and code of the application are provided in the AHU technical data
specification
AS – for supply AHUs
AP – for supply-exhaust AHUs with cross-flow exchanger
AR – for supply-exhaust AHUs with rotary exchanger
AD – for supply-exhaust AHUs without heat recovery or with recirculation damper
Application code W 0 XW 0 XW 0 X () 000)
Selection of application code. Depending on selected application code the controller controls the freon
cooler, water cooler, electric heater, water heater or heater-cooler combination. Type and code of the
application are provided in the AHU technical data specification.
Code OK Yes No
A parameter providing info on whether the selected application code matches the previously determined
application type.
LeadingSensor W Room XW Exh XW Sup X () Sup)
Selection of a leading control sensor. (see point 2 „Temperature control”).
Room – sensor located in the room. If the HMI basic parameter = Yes, the leading sensor is
the one located in the VS 00 HMI Basic.
Exh – sensor located in the exhaust duct
Sup – sensor located in the supply duct.
Room sensor and exhaust duct sensor are optional elements.
HMI basic W Yes XW No X
() No)
A parameter allowing for activation of the VS 00 HMI Basic panel in the system.
Yes – active panel
No – inactive panel.
If the panel is active in the stand-by mode, regardless of the selected leading sensor, the system
operation is based on the sensor located in the VS 00 HMI Basic. If the panel is inactive, the system
operation is based on the leading sensor.
VTS reserves the right to implement changes without prior notice
18
Advanced manual
SupSideFCType W NoFC XW iC5 XW VL28 XW MicD XW iG5 X
Selection of a type of frequency converter of the supply fan.
NoFC – no converter.
iC5 – converter made by LG typ iC5
VL28 – converter made by Danfoss, type: VLT 2800
MicD – converter made by Danfoss, type: Micro Drive
() NoFC)
SupSide-MultiFans W NO XW 2 XW 3 XW 4 X () NO)
NO means the selection of an AHU with a single supply fan set. Settings 2, 3 and 4 means the number of
fans in MultiFans configuration and initiates communication of the control box with additional supply fan
inverters.
ExhSideFCType W NoFC XW iC5 XW VL28 XW MicD XW iG5 X
Selection of a type of frequency converter of the exhaust fan.
() NoFC)
ExhSide-MultiFans W NO XW 2 XW 3 XW 4 X () NO)
NO means the selection of an AHU with a single exhaust fan set. Settings 2, 3 and 4 means the number of
fans in MultiFans configuration
Transferring start permission signal, alarm states as well as reading out parameters from frequency
converters is carried out with the help of RS 485 communication bus.
If a frequency converter is installed in the system but for any reasons it is controlled omitting the Modbus
bus, then the converter’s type should be set at the NoFC.
RRG FCType W iC5 XW MicD X
() iC5)
Selection of a type of rotary regenerator’s frequency converter.
MultiFuncDigIn W NoFu XW SpNO XW SpNC XW FsNO XW Wint XW TeOc XW CON X () NoFu)
Selecting functions of the X1 (S6) multifunctional digital input
NoFu - signal sent to the input is ignored by the controller
SpNO - Permission to AHU start. Input configured for a normally open contact
SpNC - Permission to AHU start. Input configured for a normally short contact
FsNO - Forced AHU start. Input configured for a normally open contact
FsNC - Forced AHU start. Input configured for a normally short contact
Wint - Function for systems with one heat exchanger operating as a cooler or heater. Open contact is
interpreted by the system as the Summer and blocks the AHU heating cycle, short contact is interpreted as
the Winter and the cooling is blocked.
TeOc - Function forcing AHU operation in normal mode during one hour from the contact shorting
connected at the universal input. The function is activated by the positive edge
CON - Input signal influences the user's controller only
Except for the NoFu mode, you can use a current status of the universal input in the user's controller
MultiFuncAnaIn W NoFu XW TeSp XW ReRt XW FrSp XW CON X () NoFu)
Selecting functions of the X3 (B5) multifunctional analog input.
NoFu - signal sent to the input is ignored by the controller
TeSp - input signal is interpreted by the system as the preset temperature value omitting settings of both
control panels - VS 00 HMI Basic and VS 00 HMI Advanced. Input is adapted to operation with a passive
resistance element scaled as the input of PT 1000 temperature sensors, i.e. 1000 Ohm = 0 oC
ReRt - input signal is interpreted by the system as the preset recirculation level value omitting settings of
the HMI Advanced
FrSp - input signal is interpreted as the preset frequency value. The input receives voltage signal 010VDC, where 0V = minimal frequency, 10V = rated frequency.
(see MENU SERVICE ACCESS FAN SETTINGS SUPPLY... and ... EXHAUST)
If minimal frequency of supply and exhaust fan vary, then range of the proportional control is between
nominal frequency and minimal frequency with higher value. Further lowering of the signal causes lowering
of frequency only of the converter with lower minimal value of the preset frequency.
VTS reserves the right to implement changes without prior notice
Advanced manual
19
EN
ManSetp 1,2; rated converter frequency
f
ManSetp 1
MinFreq 1,2 minimal converter frequency
ManSetp 2
U1 = 10*MinFreq1 / Setvalue 1
U2 = 10*MinFreq2 / Setvalue 2
FC1
FC2
ManSetpLoL1
Range of frequency control of both
converters is between U1 and 10V
ManSetpLoL2
0 Hz
0V
U2
10V
U1
CON - Input signal influences the user's controller only
Except for the NoFu mode, you can use a current status of the universal input in the user's controller
EN
Programming frequency converters
MultiFuncRelay W NoFu XW StaC XW HtgC XW ClgC XW Filt XW CON X
() NoFu)
Selection the function of the multifunctional converter Q6 (E5).
NoFu - inactive relay
StaC - confirmation of fans operation. The relay is short when both fans are switched on
HtgC - confirmation of heating mode. The relay is short when analog signal controlling the heater exceeds
5%
ClgC - confirmation of cooling mode. The relay is short when start signal for the cooling system is enabled
Filt - info on contaminated filters. The relay is short when at least one filter's pressure gauge is short
CON - the relay reacts to a signal from the user's controller
MENU
SERVICE ACCESS
FC CONFIGÃ
...
Mode: W Run XW Conf X
() Conf)
See: MENU SERVICE ACCESS
UNIT CONFIGÃ
Converter W Sup XW Exh XW RRG XW Sup2 XW Sup3 XW Sup4 XW Exh2 XW Exh3 XW Exh4 X () Sup)
Network address of each new converter equals 1. Depending on the fact if the converter operates on
the supply, exhaust side or inside the rotary exchanger's drive, the converter's address in the network is
changed during programming accordingly.
System element
Sup Converter on the supply side
Exh Converter on the exhaust side
RRG Converter of the rotary exchanger
Sup2 Second converter on the supply side
Sup3 Third inverter on the supply side
Sup4 Fourth inverter on the supply side
Exh2 Second converter on the exhaust side
Exh3 Third inverter on the exhaust side
Exh4 Fourth inverter on the exhaust side
ACX36 controller
Address in modbus network
2
3
4
5
6
7
8
9
10
0
SelectFCType
W iC5 XW VL28 XW MicD XW iG5 X
Selection of the programmable frequency converter type
iC5 – converter made by LG, type: iC5
VL28 – converter made by Danfoss, type: VLT 2800
MicD – converter made by Danfoss, type: Micro Drive
() iC5)
VTS reserves the right to implement changes without prior notice
20
Advanced manual
SelectMotor W .... X () 0.09)
Selection of power of the motor operating with the programmable converter.
Parameter value = motor power [kW] rounded to one decimal place.
Programming frequency converters
SelectPoles
W 2 X W 4 X () 2)
Selection of motor poles number operation with the programmable converter.
2 - two-pole motors with 2800-2950 rpm rated speed.
4 - four-pole motors with 1300-1490 rpm rated speed.
ActionStatus
W Rdy X W Err X W Snd X
Parameter initiating programming and providing information on programming process status
Rdy – Programming finished, last programming process successfully finished.
Err – Programming finished, last programming process completed with error.
Snd – initialization of programming process, a message displayed till transferring data to the converter is
finished.
ERROR
Nie user access
occured while
writing datapoint
If the Rdy or Err option is selected, the program selector displays a message
about setting not acceptable program selector operation mode.
EN
Programming instruction
Programming sequence of a converter
1. Connect a communication cable to the converter, switch on its power supply.
2. Set converter parameters in the MENU SERVICE ACCESS FC CONFIGÃ
3. Initiate programming (Snd)
Programming two converters sequence
1. Connect a communication cable to one of the converters, switch on its power supply
2. Set converter parameters in the MENU SERVICE ACCESS FC CONFIGÃ
3. Initiate programming (Snd)
4. Connect a communication cable to the other converter, switch on its power supply.
5. Set converter parameters in the MENU SERVICE ACCESS FC CONFIGÃ
6. Initiate programming (Snd)
7. Repeat steps from 4 to 6
!
In case of programming errors check the network connection quality and make sure that addresses
of converters subject to programming equal 1
VTS reserves the right to implement changes without prior notice
Advanced manual
21
Status of digital inputs
MENU
SERVICE ACCESS
On
– voltage signal are provided at the input
Off
– no voltage signal at the input
FireDetector On Off
AirSideTherm On Off
WaterSideTherm On Off
ElectricHeater On Off
RefrigUnit On Off
FilterExh On Off
FilterSup On
Off
Motor On
Off
Filters On
Off
MultiFuncDigIn On
EN
DIGITAL INPUTS
MENU
Off
SERVICE ACCESS
...
Input of anti-frost sensor
Input of anti-frost thermostat on the air side
Input of anti-frost thermostat on the water side
Input of alarm signal of electric heater
Input of alarm signal of cooling signal (cooler)
Input of pressure gauge of the filter on the exhaust side (three-phase
systems)
Input of pressure gauges of the filters on the supply side (three-phase
systems)
Input of motor thermostats on the supply and exhaust side (one-phase
systems)
Input of filters pressure gauges on the supply and exhaust side (one-phase
systems)
Universal input
DIGITAL OUTPUTS
...
Status of digital outputs
Auto – output status depends on a control algorithm and current conditions
Man – output status set manually.
On – St1 switched on - first level of cooling system of the freon cooler is switched on
Off – St2 switched off - second level of cooling system of the freon cooler is switched on
Pump Auto Man On Off
Damper Auto Man On Off
FAN Auto Man
On Off
CoolerComp Auto Man On Off
HtgStatus Auto Man On Off
Unit
Auto Man
Off St1 St2
MFunRel Auto Man On Off
AlarmRelay Auto
MENU
Man On
SERVICE ACCESS
Off
Output that controls the operation of water heater pump
Output that controls operation of air damper
Output that controls fans operation (one-phase systems)
Output enabling operation of the cooling system
Output enabling operation of the heating system
Output that controls operation of the cooling system
Universal output configured in the window: MENU
SERVICE ACCESS UNIT CONFIGÃ ...
Output that informs about the occurrence of alarm status
ANALOG INPUTS
...
Outside Temp -64…64 C
Supply Temp -64…64 oC
Room/Exh Temp -64…64 oC
Value measured by external temperature sensor
Value measured by a duct sensor of supply temperature
Value measured by the room temperature sensor or duct sensor of
exhaust temperature
AfterReco Temp -64…64 oC Value measured by the duct temperature sensor at the exhaust, behind
the heat recovery system
Values at analog inputs
o
Sensors with passive gauge PT 1000 (0oC=1000Ohm) are used for measurements
MultiFuncAnaIn oC / % Value measured by the universal analog input. Displayed units depend
on the selected output function. oC unit appears when the input has been
0 oC = 1000 Ohm
assigned temperature adjuster function. (0 oC = 1000 Ohm)
VTS reserves the right to implement changes without prior notice
22
Advanced manual
Values at analog outputs
MENU
SERVICE ACCESS
ANALOG OUTPUTS
...
Auto – output status depends on a control algorithm and current conditions
Man – output status set manually.
HtgStatus
Auto
Man
0…100%
Voltage signal value on the input that controls the
valve actuator of the water heater
CoolerComp Auto Man 0…100% Voltage signal value on the input that controls the
valve actuator of the water cooler
Voltage signal value on the input that controls:
RecRate Auto Man 0…100%
1. cross-flow exchanger damper actuator or recirculation
damper actuator. 3-phase systems
2. inlet damper (supply side) actuator. 1-phase systems with
cross-flow exchanger
0% = 0V
100% = 10V
MENU
SERVICE ACCESS
TIMERS
EN
...
Time systems Fans switch-on delay
StartDelay W 0...180 X s () 10 s)
AHU start delay - time between starting command and AHU start-up
PreHeating
W 30...600 X s () 180 s)
Duration of initial heating of the water heater.
FanOnDelay
W 0...180 X s () 20 s)
Fans switch-on delay - time between starting up the AHU and fans start-up. In this time heating or cooling systems
may start operation, depending on conditions.
FanOffDelay
W 0...120 X s () 10 s)
Fans switch-off delay - time between starting switching off the AHU and fans switch-off. During this time the electric
heater may be chilled
Stop
signal
Start
signal
AHU
switched off
Water heating
switched on
StartDelay
PreHeating
StageMinOn
Other
systems
switched on
Fans
switched on
AHU systems
switched off.
Fans switched on
AHU switched off
TIME
FanOnDelay
FanOffDelay
W 1...999 X s () 180 s)
Minimal acceptable operation time of the cooling system
StageMinOff
W 1...999 X s () 180 s)
Minimal acceptable standstill time of the cooling system
VTS reserves the right to implement changes without prior notice
Advanced manual
23
MENU
SERVICE ACCESS
PI CONTROLLERS
...
Kp - proportionality factor
Ti - integration time-constant
PI1
Kp.
W -30...30 X
Ti
W 0...7200 X
() 2 s)
() 1800 s)
Input
signal
Regulator
PI controllers
EN
Controlled element
PI 1
temperature control in heating mode
Tmain-Tset
PI 2
lower temperature limit in the supply
duct in the heating mode
Tsup-Tmin
PI 3
upper temperature limit in the supply
duct in the heating mode
Tsup-Tmax
PI 4
temperature control in the heat
recovery mode
Tmain-Tset
Cross-flow or
rotary exchanger or
recirculation damper
PI 5
anti-frost protection of the heat
recovery system
Trec - Tlim
Cross-flow or rotary
exchanger
PI 6
temperature control in cooling mode
Tmain-Tset
PI 7
lower temperature limit in the supply
duct in the cooling mode
PI 8
anti-frost protection of the heat
recovery system
Trec - Tlim
PI 9
lower temperature limit in the supply
duct in the recovery mode
Tsup-Tmin
PI 10
upper temperature limit in the supply
duct in the recovery mode
Tsup-Tmax
water or electric heater
Factory
setting
Kp
Ti
2
1800
4
60
-4
60
2
1800
4
60
-2
1800
4
60
4
60
4
60
-4
60
Water and freon cooler
Tsup-Tmin
Tset – preset temperature
Tmain – temperature measured by the leading sensor
Tsup – temperature in supply duct
Trec – temperature behind the heat regenerator
Damper on the supply
side in the systems with
cross-flow exchanger
without by-pass damper
Cross-flow or
rotary exchanger or
recirculation damper
Tmax – acceptable upper temperature in
the supply duct
Tmin – acceptable lower temperature in
the supply duct
Tlim – limit value
VTS reserves the right to implement changes without prior notice
24
Advanced manual
MENU SERVICE ACCESS FAN SETTINGS SUPPLY…
MENU SERVICE ACCESS FAN SETTINGS EXHAUST…
In systems equipped with many fans in the supply or exhaust section, given values (efficiency, limitation
settings) are common and value readouts (e.g. current) are given separately for each frequency
converter.
SupSideFCType NoFC iC5
ExhSideFCType NoFC iC5
Frequency converter mode
VL28
VL28
MicD
MicD
RampUpTime W 30...120 X s () 30 s)
Length of accelerating time ramp – time from the start signal or increasing preset frequency signal up to
reaching the preset speed.
Frequency limitations
RampDownTime
W 30...120 X s () 40 s)
Length of braking time ramp – time from decreasing speed signal up to reaching the preset speed.
After AHU switch-off signal the fans stop by rundown. Length of the braking time ramp does not
influence the rundown time.
ManSetpHiL W 21...100 X Hz () 80 Hz)
Upper limit of the acceptable range of preset frequency. While specifying the limit you have to take into
consideration rated parameters of the ventilation system and rated value of the motor current.
ManSetpHiL W 10...20 X Hz () 20 Hz)
Lower limit of the acceptable range of preset frequency.
ManSetp W … X Hz () 35 Hz)
Frequency value for which in user's settings (MENU PARAMETERS FAN...) will be assign value
100%. It should be frequency at which the AHU reaches its rated output.
Out Current …... A
Effective value of wire motor current
RPM ....rpm
Fan rotations. The value calculated from the current preset frequency taking into consideration rated
motor slip.
FC Status: OK FLT
Info on the fan drive status.
OK – no alarm
FLT – incorrect drive operation status
Comm Status: OK FLT
Info on communication between the controller and fan drive converter.
In case of communication loss both drives are stopped after about 12 seconds from the moment of the
communication loss and appropriate alarm code is displayed. Once the communication is restored the
drives start up automatically.
OK – communication is ok
FLT – no communication
VTS reserves the right to implement changes without prior notice
Advanced manual
25
EN
MENU
SERVICE ACCESS
TEMP. PARAMETERS
...
Min Sup Temp W -10...20 XoC () 16 oC)
Minimal acceptable temperature value in the supply duct.
Max Sup Temp W 21...50 XoC () 34 oC)
Maximal acceptable temperature value in the supply duct.
Temperature limitation
Acceptable temperature of electric motors work under rated load is 40oC
MinOutTemp W 0...40 XoC () 16 oC)
The temperature value under which the cooling is blocked. Water valve is closed, cooler and compressors
are switched off.
Min Temp Set W 5...20 XoC () 16 oC)
Lower limit of the temperature value preset in the VS 00 HMI Advanced in the
MENU PARAMETERS TEMPERATURES window or via the universal input.
Max Temp Set W 21...50 XoC () 30 oC)
Upper limit of the temperature value preset in the VS 00 HMI Advanced in the
MENU PARAMETERS TEMPERATURES window or via the universal input.
ExtTempSetp W On XW Off X () Off)
Activation of temperature adjuster connected to the universal input.
On – value of preset temperature is read out from the analog universal input.
0oC=1000 Ohm. The MENU PARAMETERS TEMPERATURES HMI Temp Setp parameter
is inactive
Off – inactive input.
EN
PumpMinOutTemp W -30...10 XoC () 5 oC)
The temperature value below which the water pump operates in a continuous manner, regardless of
heating requirements in the system.
Configuration of the user controller
MENU
SERVICE ACCESS
USER PROG.
Signal source
MFAI X universal analog input (B5)
W B1 X temp. sensor in supply duct
W B2 X temp. sensor in room or exhaust duct
W B3 X external temp. sensor
W B4 X temp.sensor behind recovery system
W HtgR X heating adjustment”
W ClgR X cooling adjustment
W RecR X recovery adjustment
Setpoint Source
MFAI X universal analog input (B5)
W Cnst constant value
...
Comparator
Compare type
<X
W>X
W=X
W True X
W False X
Hysteresis
W0X
Binary Block
AND X
W NAND X
WOR X
W NOR X
W XOR
output relay (E5)
Binary source
MFDI X universal digital output (S6)
W StaC X AHU switched on
W Stby X AHU in stand-by mode
W Htg X AHU in heating mode
W Clg X AHU in cooling mode
W Rec X AHU in recovery mode
W FLT X alarm
W True X constant value 1
W False X constant value 0
Constant value
W0X
VTS reserves the right to implement changes without prior notice
26
Advanced manual
Example of setting the user's controller
Requirement:
Switching on additional pump in the hydraulic system if
the heating requirement is greater than 50%.
ÃÃÃ USER.PROG
SetpointSource
ConstatSetpoint
Hysteresis
CompareType
SignalSource
BinaryBlock
BinarySource
ÃÃÃ
Cnst
50
2
>
HtgR
OR
False
MENU SERVICE ACCESS UNIT
CONFIGÃ MultiFuncRealy parameter
should be in CON mode
Requirement:
Switching on nozzle humidifier if the measured relative
humidity is less then 30%. Switching off the nozzle
humidifier should occur at humidity 34%.
In this example it is assumed that 0V = 0%, 10V = 100%
ÃÃÃ USER.PROG
SetpointSource
ConstatSetpoint
Hysteresis
CompareType
SignalSource
BinaryBlock
BinarySource
ÃÃÃ
Cnst
30
1
>
MFAI
AND
StaC
Parametr MENU
SERVICE ACCESS
UNIT CONFIGÃ MultiFuncRealy and
MultiFuncAnaIn parameter should be in CON
mode
MENU
!
SERVICE ACCESS
MANUAL MODE
...
Incompetent use of the manual mode can lead to damage of AHU subassemblies or/and cause
significant energy loss.
DIGITAL INPUTS
Parameters as in the window: MENU
SERVICE ACCESS
DIGITAL INPUTS
Manual mode
DIGITAL OUTPUTS
Parameters as in the window: MENU SERVICE ACCESS DIGITAL OUTPUTS
In the window there is a possibility of setting any outputs in manual mode in switched on or off status.
Pump
W Auto X W Man X () Auto) W On X W Off X
() Off) On Off
.
.
.
Auto – output in a mode of automatic control in line with selected application
Man – output in manual mode Actual output status receives value preset in the field on the right
On – switch on the output in manual mode
Off – switch off the output in manual mode
On – current output status. Output switched on
Off – current output status. Output switched off
ANALOGUE INPUTS
Parameters as in the window: MENU SERVICE ACCESS ANALOGUE INPUTS
ANALOGUE OUTPUTS
Parameters as in the window: MENU SERVICE ACCESS ANALOGUE OUTPUTS
In the window there is a possibility of free setting the value of any analog output
Heating
W Auto X W Man X () Auto) W 0...100 X % () 0%)
0...100 %
.
.
.
Auto – output in a mode of automatic control in line with selected application
Man – output in manual mode Actual output status receives value preset in the field on the right
0...100 % – setting output in manual mode
0...100 % – current output status
VTS reserves the right to implement changes without prior notice
Advanced manual
27
EN
Brightness and contrast settings
MENU
LCD SETTINGS
...
Brightness W 0...31 X () 20)
Display backlight intensity
Contrast W 0...31 X () 20)
Intensity of text display on the display
Reset Time W 3...30 X
() 10)
Time measured from the last pushing the button after which the STATUS window appears again on the
display.
S1
ON
1. Stop the system (Operation mode: OFF)
S1
OFF
2. Right switch S1 (on the left of RJ 45, see 3.1.2) - turn ON
3. After 20 seconds turn the switch off (OFF) again.
ON
6. DESCRIPTION OF CONTROL ALGORITHMS
Condition
Temperature control
EN
) Restoring factory settings
OFF
Measurement elements
Room sensor
Sensor in the air-supply
duct
Sensor in the air-exhaust
duct
VS 00 HMI Basic control
panel is equipped with
temperature sensor
Heating
Cooling
c
d
d
c
Tset > Tmain
Tset<Tmain
Tset = Tmain
Fans switched on
Tset – preset temperature
Tmain – temperature measured by the leading sensor
The system never operate with heating and cooling status simultaneously.
Tset = Tmain – preset state the control system aims at. Heating or cooling
level does not change, meeting accurately energetic requirements of a
building.
Leading sensor – temperature sensor, which value influences the
temperature control. Depending on the requirements, each of sensors
listed aside can be the leading sensor.
VTS reserves the right to implement changes without prior notice
28
Advanced manual
Protection of a room and people against too low or too high temperature of
supply air.
Condition
Tmin>Tsup
Tmax<Tsup
Tmin<Tsup<Tmax
Fans switched on
Heating
c
d
Tsup – temperature in supply duct
Tmax – acceptable upper temperature in the supply duct
Room
Protections
Measurement
elements
Temperature sensor
in the air-supply duct
External temperature
sensor
Tmin – acceptable lower temperature in the supply duct
Preliminary heating - this function is activated during AHU start-up and it
prevents supply air with external temperature from blowing into the duct.
The valve opening degree is calculated basing on the proportion
Condition
Water
pomp
Water
valve
cX%
Tout< 8°C
Fans
1
2
Dampers
Stop
Start
EN
Closed
Open
AHU start-u
The valve opening degree is calculated basing on the proportion
Tout ≥ 8 oC
o
X = 0%
Tout ≤ -15 C
X = 100%
1. Duration is set in the window: MENU
PreHeating
SERVICE ACCESS
TIMERS
2. Duration: 1 min.
protection elements
Protections
Tout – external temperature
Measurement
elements
Fire-protection control
box
Is not supplied with
the automatic control
set provided by VTS
Protection of a building and people against feeding fire.
Condition
No signal on the
X2 (S1F) controller
input
Fans switched on
Fans
Dampers
Heating/cooling
Stopped
Closed
Switched off
VTS reserves the right to implement changes without prior notice
Advanced manual
29
External temperature sensor
Condition
Water pomp
Tout<Tlim
Fans switched on or off
Tout – external temperature
Tlim – protection activation threshold
Water heater
Measurement
elements
External temperature
sensor
Anti-frost thermostat
on the air side
Anti-frost thermostat
on the water side
EN
Anti-frost thermostat on the air side
Condition
Water pomp Water valve
Tsup<Tlim
c 100%
Fans switched on or off
Fans
Stop
Dampers
Closed
Anti-frost thermostat on the water side and external temperature
sensor
Condition
Water pomp
Water valve
Tout<10C and Tx<Tlim
c 100%
Fans switched off
Tx return water temperature
Protections
Pump protection
Cyclic starting the pump for 30 seconds every 7 days. The function can be
blocked in the VS 00 HMI Advanced or Scope program.
!
The protections are active if the mains switch is turned on and the
control circuits are live.
Electric Heater
Condition
Alarm from electric
heater
Fans switched on
Measurement
elements
Fan pressure gauge
Electric heater
thermostat
Condition
Third alarm from the
electric heater within
an hour
Fans switched on
Heating
Fans
blockage
Stop
Heating
Fans
blockage
Stop
Gauges are connected directly to the control module of the electric heater.
The control system responds only to alarm signal from the electric heater
module.
VTS reserves the right to implement changes without prior notice
30
Advanced manual
Water cooler system
Condition
Measurement
elements
External temperature
sensor
Tout<Tlim or cooling
system alarm
Fans switched on
blockage
0%
Threshold value of the protection activation also influences operation of
the system in the „free cooling” mode.
tpmin>tp
Freon cooler system
Water valve
The cooling system should be equipped with normally closed (NC) alarm
contact
Condition
Tout<Tlim or
compressor alarm
twmin>tw
Protections
Cooling system
start
Compressor start
Compressor stop
blockage
-
-
blockage
blockage
-
Fans switched on
Measurement
elements
twmin – minimal acceptable operation time of the cooling system
External temperature
sensor
tw – system operation time related to the temperature control
tpmin – minimal acceptable break time in operation of the cooling system
tw – system operation break time related to the temperature control
The cooling system should be equipped with normally closed (NC) alarm
contact
Filtration system
Recovery system
Threshold value of the protection activation also influences operation of
the system in the „free cooling” mode.
Measurement
elements
Temperature sensor
behind the recovery
module
Condition
By-pass damper
Trec<Tlim
c
Fans switched on
Trec – temperature behind the heat regenerator
Protection is not activated in AHUs with the recirculation system
Measurement
elements
Condition
Due to initiation of the pressure gauge in
the system only information about filters
contamination and their replacement notice are
generated
ΔP<ΔPlim
pressure gauge
VTS reserves the right to implement changes without prior notice
Advanced manual
31
EN
Carried out smoothly via energy regeneration system.
Cross-flow exchanger
Condition
Heating requirement;
Tout<Tmain-2oC
Fans switched on
By-pass damper
d 100…0%
Control signal 0…10V
Measurement elements
External temperature sensor
Executive elements
By-pass actuator of the cross-flow
exchanger or drive module of the rotary
exchanger or recirculation damper
actuator
Rotary exchanger
Condition
Heating requirement;
Tout<Tmain-2oC
Fans switched on
Rotor
c 0…~10 min-1
Modbus control signal
Systems with recirculation
Condition
Recirculation damper
Heating requirement;
c 0…Max
Tout<Tmain-2oC
Fans switched on, constant recirculation level
switched off
Control signal 0…10V
Tmain – temperature measured by the leading sensor
Tout – external temperature
Condition
Heating requirement;
II heating level
EN
Heating cycle
Water valve or electric heater module
I heating level
Leading sensor
I heating level = max or
Tout>Tmain
Fans switched on
II heating level
c 0…100%
Control signal 0…10V
In systems without heat regeneration, heat requirements
are met only via the II heating level.
VTS reserves the right to implement changes without prior notice
32
Advanced manual
Carried out smoothly via energy regeneration system.
Cross-flow exchanger
Condition
Cooling requirement
Tout>Tmain+2oC
Fans switched on
By-pass damper
d 100…0%
Control signal 0…10V
I cooling level
Rotary exchanger
Condition
Cooling requirement
Tout>Tmain+2oC
Fans switched on
Rotor
c 0…~10 min-1
Modus control signal
Systems with recirculation
Cooling cycle
Condition
Recirculation damper
Cooling requirement
c 0…Max
Tout>Tmain+2oC
Fans switched on, constant recirculation level
switched off
Measurement elements
Main control sensor
External temperature sensor
Executive elements
Water valve or contact for switching
on the I and II level of freon cooler
By-pass actuator of the cross-flow
exchanger or drive module of the rotary
exchanger or recirculation damper
actuator
Control signal 0…10V
!
The I cooling level can be activated only in AHUs
adapted for heat recovery in cooling status.
Condition
Cooling requirement; I
cooling level = max or
Tout<Tmain
II cooling level
c 0…100%
II cooling level
Fans switched on
Control signal: 0…10V for water valve; 2 relays for
switching on the I and II section of the freon cooler.
In systems without heat regeneration, cooling
requirements are met only via the II cooling level.
”Free cooling” – Function of saving energy. Blocking of
the II level of cooling at appropriate parameters of external
air.
Condition
Cooling requirement;
Tout<Tlim
Fans switched on
II cooling level
Blockage 0%
VTS reserves the right to implement changes without prior notice
Advanced manual
33
EN
7. TECHNICAL DATA
7.1 Control gear
Construction
Casing with external mains switch and RJ 45 port for connecting the VS 00 HMI Advanced control panel
- short-circuit and overload protection assembly
- connection units
- ACX 36.04 controller
main internal elements
VS 10-15 CG ACX36–1
weight
VS 21-150 CG ACX36-2 SUP
VS 21-150 CG ACX36-2 SUP-EXH VS 400-650 CG ACX36-2 SUP-EXH
VS 180-300 CG ACX36-2 SUP-EXH
10kg
450x460x170
dimensions
10kg
450x460x170
10kg
450x640x170
Operation parameters
Parameter
VS 10-15 CG ACX36–1
EN
system
VS 21-150 CG ACX36-2 SUP
VS 21-150 CG ACX36-2 SUP-EXH
VS 180-300 CG ACX36-2 SUP-EXH
VS 400-650 CG ACX36-2 SUP-EXH
TN
U3 rated power supply voltage
In control box rated current
1x230V
3x400V
21 A
56 A
Ui rated insulation voltage
400 V
Uimp rated impulse withstand voltage
2.5 kV
rated short-time withstand current Icw for
respective circuits - effective value of alternatingcurrent component withstood during 1 second,
i.e.: short-circuit current expected at connecting
voltage of
rated peak withstand current (ipk) at cosφ= 0.5
6 kA
10.2 kA
rated short-circuit current
6 kA
coincidence factor
0.9
rated frequency
50 Hz ± 1Hz
protection class
IP54
acceptable operating temperature
0 ÷ 40 oC
supply voltage of control circuits
24 V AC
EMC environment
1
Parameters of protection units
F1 (B6)
Protection of lighting circuit
F1M (C16)
F1M (C10)
Protection of power supply circuit of water heater pump and rotary exchanger (for VS 21-150 CG
ACX36-2 SUP, VS 21-150 CG ACX36-2 SUP-EXH, VS 180-300 CG ACX36-2 SUP-EXH and VS
400-650 CG ACX36-2 SUP-EXH)
Protection of supply circuits of water heater pump (for VS 10-15 CG ACX36-1)
F2
Glass or ceramic fuse element of size 5x20mm, type T 0,63A
VTS reserves the right to implement changes without prior notice
34
Advanced manual
7.2 ACX36.040 controller
Resources
Relay output Q1...Q6
Universal input/output
IO1...IO8
Digital inputs
DI1...DI5
Analog output
AO1, AO2
AC12...250V, max 4A
Reference potential G0;
Inputs DC 4...20mA, DC 0-10V, Pt 1000, Ni 1000, NTC
Outputs, DC 0-10V (1mA)
DC 16V(5mA) max 50Hz
0...10V, max (2mA)
RS 485 communication port
Modbus protocol, 1200m
RS 232 communication port
RJ 45 standard connection, 8 pins, 15m
PPS2 communication port
Connection for QAX... (VS 00 HMI Basic) two-wire connection, DC12V
(max 12mA), 50m
LON
Two-wire connection shielded galvanically, 1=CLA, 2=CLB
Operation parameters
Power supply
Ambient temperature
Protection class
EN
24 VAC (± 10%), 50/60Hz, 20VA
operation: 0...+50oC, storage: -30...+70oC
IP 20
Controller picture
Block of analog outputs
Block of digital inputs
Controller's power
supply port
LON
Block of universal
inputs/outputs
LON port
LED indicating
controller status
LON network
identification button
(service pin)
RS 485 port
RJ45 serial communication port
Block of digital outputs
(relay-type)
ACX36
Pin1 (GND)
Pin2 (RxD)
Pin3 (RTS)
Pin4 (TxD)
Pin5 (CTS)
Pin6,7 +12V
Pin8 (GND)
VS 00 HMI Basic port
Factory settings recovery
switch (right)
<>
<<
>>
>>
<<
PC (SubD)
Pin5 (GND)
Pin3 (TxD)
Pin8 (CTS)
Pin2 (RxD)
Pin7 (RTS)
Parameters of the control panels and executive elements are described in the VTS product catalogue
VTS reserves the right to implement changes without prior notice
Advanced manual
35
8. CABLING
Connect power leads of the control gear and frequency converter of the fan drive according to the
Electric diagram. The wire cross-sections has been selected for long-term current capacity according
to the Picture, for two load conductors. Due to the protection selectivity, length, cable placement
method and short-circuit currents, revise the feeders' cross-sections in the table below.
Wire type
Wire description
Parameters
[1]
Control wires with copper
cores with a shield. PCV
isolation.
Nominal voltage: 300/500 V
Ambient temperature:
-30 to 80°C
[2]
Copper cores. PCV
isolation.
Nominal voltage: 450/750V
Ambient temperature: from -40 to 70°C
[3]
Copper cores with a
shield. PCV isolation.
Nominal voltage: 150 V
Ambient temperature; -20… 60°C¬
[4]
Flat communication
cable without shield
Nominal voltage 150V
Ambient temperature: -20… 60°C
EN
Wire picture
VTS reserves the right to implement changes without prior notice
36
Advanced manual
Name of element / connection point
1-faze control gear
3-faze control gear
Wire
type
Section
[mm2]
Control gear
VS 10-15 CG ACX36-1
VS 21-150 CG ACX36-2 SUP
VS 21-150 CG ACX36-2 SUP-EXH
VS 180-300 CG ACX36-2 SUP-EXH
VS 400-650 CG ACX36-2 SUP-EXH
controller
fire alarm switch
multi-function switch
supply air temperature sensor
Room/ exhaust air temperature sensor
external air temperature sensor
After recovery air temperature sensor
multi-function analog reference
HW anti-frost water side thermostat
N1
S1F
S6
B1
B2
B3
B4
B5
S3F
VTS-E-0005
ter. 07:09 AM
S2F
Y1
VTS-E-0005
ter. 01:08 PM
M1
N1
S1F
S6
B1
B2
B3
B4
B5
S3F
VTS-E-0005
ter. 07:09 AM
S2F
Y1
VTS-E-0005
ter. 01:08 PM
M1
[2]
[2]
[1], [2]
[1], [2]
[1], [2]
[1], [2]
[1], [2]
[2]
2x1
2x1
2x0,5
2x0,5
2x0,5
2x0,5
2x0,5
2x1
[2]
2x1
[2]
[2]
2x1
2Y1
[2]
2x1
[2]
3x1.5
S5F
S5F
[2]
2x1
E1
E2.1
E2.2
Y2
not supported
not supported
not supported
not supported
Y3
Y4
Y5
E3.1
E3.2
E4
E5
N2
N3
E1
E2.1
E2.2
Y2
U1
via Modbus comm.
via Modbus comm.
via Modbus comm.
Y3
Y4
Y5
E3.1
E3.2
E4
E5
N2
N3
[2]
[2]
[2]
[2]
[1]
2x1
2x1
2x1
2Y1
3x1.5
[3]
2x2
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[4]
2Y1
2Y1
2Y1
2x1
2x1
2x1
2x1
2x0.5
8x0.1
1S1H
1S2H
1S1H
1S2H
[2]
[2]
2x1
2x1
1S3H
1S3H
[2]
2x1
1M1F
1M1
not supported
not supported
not supported
not supported
1U1
1U2
[2]
[2]
[3]
[3]
2x1
3x1.5
TAB A
TAB A
HE alarm switch
HW anti-frost air side thermostat
HW analog controlled valve
HE power rate control input
HW circulating pump contactor
chiller / refrigerating unit / heat pump
alarm switch
chiller start input
refrigerating unit start input - I stage
refrigerating unit start input - II stage
CW analog controlled valve
RHE frequency converter
RHE alarm switch
RHE start input
RHE speed reference input
recirculation damper actuator
cross-flow bypass actuator
CWHW analog controlled valve
CWHW “cooling” command
CWHW “heating” command
AHU alarm
AHU start confirmation
Room Unit – reduced function interface
HMI – full function interface
supply elements
pressure control - primary filter, supply
pressure control - primary filter, supply
pressure control - compression
monitoring for HE-Module
supply motor protective relay
supply motor contactor
supply frequency converter
second supply fan frequency converter
[2]
VTS reserves the right to implement changes without prior notice
Advanced manual
37
EN
frequency converter of the third supply
fan
frequency converter of the fourth
supply fan
intake damper actuator
exhaust elements
pressure control - primary filter,
exhaust
exhaust motor protective relay
exhaust motor contactor
exhaust frequency converter
second exhaust fan frequency
converter
frequency converter of the third
exhaust fan
frequency converter of the fourth
exhaust fan
outlet damper actuator
not supported
1U3
[3]
TAB A
not supported
1U4
[3]
TAB A
1Y1
1Y1
[2]
2Y1
2S1H
2S1H
[2]
2x1
2M1F
2M1
not supported
not supported
not supported
2U1
[2]
[2]
[1]
2x1
3x1.5
TAB A
not supported
2U2
[3]
TAB A
not supported
2U3
[3]
TAB A
not supported
2U4
[3]
TAB A
2Y1
2Y1
[2]
3x0.5
TABLE A
EN
Motor/
converter
power
Rated
motor
current
[kW]
[A]
Δ - 3x230V/50Hz
0,75
3
1,1
4,5
1,5
6
2,2
8
Δ – 3x400V/50Hz
3,0
6
4,0
8
5,5
11
7,5
15
11,0
21
1x230V/50Hz
1,3
6
1,75
7,6
Converter
protection
1x230V/50Hz
MicroDrv
VLT
gG16/1
gG16/1
gG25/1
gG25/1
3x400V/50Hz
gG16/3
gG16/3
gG20/3
gG25/3
gG35/3
Control gear feeder [2]
Converter
feeder [2]
Motor
feeder [1]
[mm2]
[mm2]
3x1,5
3x1,5
3x2,5
3x2,5
4x1,5
4x1,5
4x1,5
4x1,5
5x2,5
5x2,5
5x4
5x4
4x2,5
4x2,5
4x2,5
4x2,5
4x4
4x2,5
4x2,5
4x2,5
4x2,5
4x4
5x4
5x4
5x4
5x6
5x6
-
*3x1,5/4x1,5
*3x1,5
3x1,5
3x2,5
Air
supply
Air supply air exhaust
Control gear rated current
Air supply
[mm2]
Air supply
- air
exhaust
[A]
5 / 1,5 / 7
7 / 1,5 / 7
8 / 1,5 / 7
11 / 1,5 / 7
5xTABELA C
3xTABELA C
8 / 7,5 / 13
10 / 9,5 / 15
13 / 12,5 / 18
17 / 16,5 / 22
23 / 22,5 / 28
12
13
TABELA B
TABELA B
VTS reserves the right to implement changes without prior notice
38
Advanced manual
EN
TABLE B
Motor
power
0,75
1,1
1,5
L1
L2
L3 L1 L2 L3
0,75
6,5
7
7
1,1
6,5
11,5
7
8 8,5
7
1,5
6,5
13
7
8
10
8
12
2,2
L1
L2 L3
7
9,5
10
7
7
9,5
12
7
L1
3
L2 L3
11,5 14
L1
L2
4
L3
L1
L2
5,5
L3
7,5
L1
L2
L3
L1
L2
L3
34
37
43
2,2
6,5
15
7
3
12,5
10
13 14 10 13 15,5
10 13 17,5 10 13
7
15,5
16
19
4
14,5
12
15 16 12 15 18,5
12
15 19,5 12 15
17,5
18
21
19,5
20
23
5,5
17,5
15
18 19 15 18 20,2
15 18 22,5 15 18
20,5
21
24
22,5
23
26
25,5
26
29
7,5
21,5
19
22 23 19 22 24,5
19 22 26,5 19 22
24,5
25
28
26,5
27
30
29,5
30
33
33,5
11
27,5
25
28 29 25 28 30,5
25 28 32,5 25 28
30,5
31
34
32,5
33
36
35,5
36
39
39,5
40
2x 7,5
38
37,5
43
40
39,5
45
43
42,5
48
47
46,5
52
2x 11
50
49,5
55
52
51,5
57
55
54,5
60
59
58,5
64
3x7,5
3x11
4x7,5
4x11
1,3
1,75
VTS reserves the right to implement changes without prior notice
Advanced manual
39
Motor
power
11
L1
2x 7,5
L2
L3
46
49
L1
L2
3x7,5
2x 11
L3
L1
L2
L3
91
3x11
4x7,5
4x11
1,3
1,75
L
L
0,75
1,1
1,5
2,2
3
4
5,5
7,5
EN
11
45,5
2x 7,5
53
52,5 58 63,5 64
67
2x 11
65
64,5 70 75,5
79 87,5 88
76
3x7,5
96,5
94
97
3x11
114,5
112
115
4x7,5
111,5
109
4x11
135,5
133
132,5
130
133
112
129,5
127
130
126,5 124
127
136
153,5
151
154
150,5 148
153
174,5 172 175
1,3
20
1,75
21
22
TABELA C
Motor
power
0,75
1,1
1,5
2,2
3
4
5,5
7,5
11
2x 7,5
2x 11
3x7,5
3x11
4x7,5
4x11
1,3
1,75
0,75 1,1 1,5 2,2
4
4
4
6
6
6
6
10
10
4
4
6
6
6
6
10
10
4
6
6
6
6
10
10
6
6
6
10
10
10
3
4
5,5 7,5
11
6
6
10
10
10
16
16
6
10
10
10
16
25
10
10
16
16
25
16
25
35
10
16
25
25
2x
7,5
2x
11
35
35
35
3x7,5
3x11
4x7,5 4x11 1,3 1,75
2x25
2x25
2x25
2x35
2x35
2x35
1x25,1x35 1x25, 1x35 2x35 2x35
4
4
4
4
VTS reserves the right to implement changes without prior notice
40
Advanced manual
Appendix 1 DESCRIPTION OF ALARM STATUSES
Requires manual cancellation
Does not require manual
cancellation
Alarm code
VS 00
VS 00 HMI
HMI
Advanced
Basic
Fire detector
90.01
Air Side
Thermostat
Electric Heater
Water Side
Thermostat
RefrigUnit
60.02
60.03
Motor
80.01
SupSideFCAlr
SupSideComm
80.02
ExhSideFCAlr
ExhSideComm
Filters
Description
Input
Fire alarm
X3
80.03
30.01
30.02
FilterExh
30.03
RRGFCStatus
50.01
HMI Basic
70.04
Main Temp
70.06
Comment
Requires manual cancellation, if the faulty status
was generated three times within an hour. After
the third time the code of the breakdown takes the
80.04 value.
D1
Risk of electric heater
overheating or lack of fan pileup
Requires manual cancellation, if the faulty status
was generated three times within an hour. After
the third time the code of the breakdown takes the
80.05 value. Check information on a display of the
heater control module.
Low temperature of heating
medium
Incorrect operation status of the
water cooler refrigerator
Incorrect operation status of the
freon cooler system
Incorrect operation status of the
cooler operating as a heater
Overheating of 1-phase motor
on the supply and/or exhaust
side
Incorrect operation status of the
motor on the supply side
D2
EN
D3
D4
Check information on a display of the frequency
converter
3
RS 485
3
3
If the communication is established again, the
system starts up automatically.
Limit contamination of the filter
on the supply and/or exhaust
side
Limit contamination of one of
the filters on the supply side
Limit contamination of the filter
on the exhaust side
Incorrect operation status of the
drive motor of rotary exchanger
Error while measuring
temperature at the HMI Basic
Leading sensor faulty or not
connected
If the communication is established again, the
system starts up automatically.
Check information on a display of the frequency
converter
No communication with the
converter on the exhaust side
No communication with the
rotary exchanger’s converter.
1
3
No communication with the
converter on the supply side
Incorrect operation status of the
motor on the exhaust side
FilterSup
RRGComm
3 Only in 3-phase systems
1 Only in 1-phase systems
Fans stop
Fans do not stop
Risk of freezing the water
heater
60.01
1/2
D5
1
D4
D5
3
3
RS 485
Check information on a display of the frequency
converter
3
If the communication is established again, the
system starts up automatically
PPS2
-
VTS reserves the right to implement changes without prior notice
Advanced manual
41
Appendix 1 DESCRIPTION OF ALARM STATUSES
70.01
70.02
70.03
70.05
Temperature sensor faulty
or not connected
X7
X6
X5
X4
The alarm is displayed as a code, where temperature is indicated.
30.01, 30.02 and 30.03 alarms are displayed alternately with the
temperature value from the main control sensor.
The panel does not support cancellation of alarm statuses.
An alarm can be cancelled using VS 00 HMI Advanced or by
switching off and on again power supply of the control gear.
VS 00 HMI Basic
AfterRecTemp
Outside Temp
Room/Exh Temp
Supply Temp
2/2
30:0
Access to list of current alarms is available from
each panel’s window by pressing the key with a
bell.
Cancelling alarm status
1. Enter password in the tab:
MENU PASSWORD ...
2. Go to the Alarm list window
3. Press the key with a bell
ÃÃÃ
ALARM LIST
AlarmList Entries
Alarm history
+ 13.01
20:19: 38
Motor
ÃÃÃ
1
or
ÃÃÃ ALARM HISTORYÃÃÃ
1.
2.
Turn off power supply of the control gear
for about 30 seconds
Turn on the power again
Status of alarm LED
1. Off – no alarm
2. Blinking – new alarm has appeared
3. Steady light – attempting cancelling alarm,
which cause has not disappeared
VS 00 HMI Advanced
EN
Number of
current
alarms
AlarmHistoryEntries
- 13.01
20:30: 15
Motor
+ 13.01
20:19: 38
Motor
15
Date and time of
failure
Alarm
description or
determining
faulty
Number of alarms
stored in the
controller's memory
Information about
cancelled alarm or
abating incorrect
status, which does not
require cancellation
!
In a sequence of alarm cancellation with power supply, turning power again on should be done no
sooner than the frequency converters displays are cleared - about 30 seconds from switching off.
!
Switching on the system again after cancelling motor alarm can be done as soon as the motors are
cold, i.e.: 10 minutes after the alarm occurred.
Alarm LED is blinking also in case of alarm status, which appeared and abated and which does not require
cancellation. Turning off the LED in such a case is carried out with alarm cancellation procedure.
VTS reserves the right to implement changes without prior notice
42
Advanced manual
10
10
VS 10-15 CG ACX36-1
2/1
PE
T1
L1
F2
230V
7
24V
8
30
31
9
Appendix 2 Circuit diagram of VS 10-15 CG-ACX-1 control gear
L
3
2
1
M
1~
N
PE
X0
L
2
4
L
1
2
1
M
1~
1M1
PE
L
1x230V
Q1M
0
L
N
L
PE
1
X0
PE
N
N
K1M
2
2
1
1F1M
2
1
<T
PE
PE
N
N
2F1M
2M1
L
3
3
M
1~
2
3
4
1
<T
4
5
1M2
N
L
F1M
PE
2
5
K2M
6
1
6
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
43
10
9
2
M
5
1
30
1Y1/2Y1
4
6
5
3
34
X0
K1M
6
31
G0
Q2
M
Q3
Q4
A2
K1M
A1
A1
A2
X6
M
X4
Q6
X7
M
M
PPS2
XG
1
24VAC
X8
XG0
3
2
1
RS485
Analog Outputs
Y2
GND
Q53 Q54 Q63 Q64
Q5
Universal Inputs/Outputs
X5
X2
Digital Outputs AC 24-230V 4(3) A
X3
Q13 Q14 Q23 Q24 Q33 Q34 Q43 Q44
Q1
AC 24V
K2M
GND
N1
XG0
GND
15
2
D1
M
S1
XG
24VAC
16
M
X10
Digital Inputs
D2
24VAC
14
+24V
A+
D3
13
+24V
B-
G
32
Y1
G0
J1
35
17
CLB
LON
CLA
9
12
X1
33
M
A+
44
B-
EN
HMI
11
N3
36
9
10
VS 10-15 CG ACX36-1
T<
8
2M1F
7
T<
X0
19
1M1F
18
Appendix 2 Circuit diagram of VS 10-15 CG-ACX-1 control gear
2/2
VTS reserves the right to implement changes without prior notice
Advanced manual
D5
M
D4
Q1M
0
45
L1 L2 L3
3x400V
N
PE
PE
1L3
1L2
N
X0
1L1
PE
N
1U1
X0
1F1M
1L1
1M1
N
2
1
2
1L2
M
3~
4
3
6
5
PE
3
4
1L3
1M2
PE
PE
X0
N
M
1~
N
X0
K1M
F1M
5
1L3
2L3
Advanced manual
3L3
1
L
1
2
1
2
1
1L2
6
1L1
7
N
N
L
2
1
X0
N
X0
1L2
1L1
2
VS 21-150 CG ACX36-2 SUP
PE
X0
F1
8
10
9
PE
N
10
10
Appendix 3 Circuit diagram of VS 21-150 CG-ACX-2 control gear
1/2
EN
VTS reserves the right to implement changes without prior notice
1L3
9
9
9
1L1
PE
N
T1
230V
24V
30
31
N1
14
G0
Q2
M
Q3
Q4
K1M
A1
A2
X6
M
X4
Q6
X7
M
M
24VAC
XG
3
2
1
RS485
Y2
PPS2
Analog Outputs
XG0
X8
GND
Q53 Q54 Q63 Q64
Q5
Universal Inputs/Outputs
X5
X2
Digital Outputs AC 24-230V 4(3) A
X3
X1
Q13 Q14 Q23 Q24 Q33 Q34 Q43 Q44
Q1
AC 24V
XG0
16
1
2
17
D1
M
S1
XG
24VAC
M
X10
Digital Inputs
D2
GND
15
+24V
A+
D3
13
+24V
B-
F2
12
Y1
G0
G
32
M
A+
46
B-
EN
18
CLB
LON
CLA
D5
D4
VS 21-150 CG ACX36-2 SUP
J1
HMI
11
M
10
N3
19
Appendix 3 Circuit diagram of VS 21-150 CG-ACX-2 control gear
2/2
VTS reserves the right to implement changes without prior notice
Advanced manual
Q1M
0
Advanced manual
47
L1 L2 L3
3x400V
N
PE
PE
1L3
1L2
N
X0
1L1
PE
N
1U1
X0
1F1M
1L1
1M1
N
2
1
2
1L2
M
3~
4
3
6
5
PE
2U1
X0
2F1M
3
1L1
2M1
N
2
1
1L2
M
3~
4
3
6
5
4
PE
1L3
1M2
PE
PE
X0
N
M
1~
N
X0
K1M
F1M
5
1L3
2L3
3L3
1
L
1
2
1
2
1
1L2
1M3
U1
X0
6
N
M
3~
PE
X0
2
1L1
7
N
N
L
2
1
X0
N
X0
1L2
1L1
1L3
3
10
9
PE
N
VS 21-150 CG ACX36-2 SUP-EXH
PE
X0
F1
8
10
10
Appendix 4 Circuit diagram of VS 21-150 CG-ACX-2 control gear
1/2
VTS reserves the right to implement changes without prior notice
EN
1L3
9
9
9
1L1
PE
N
T1
230V
24V
30
31
N1
14
G0
Q2
M
Q3
Q4
K1M
A2
A1
X6
M
X4
Q6
X7
M
M
16
24VAC
XG
3
2
1
RS485
Y2
PPS2
Analog Outputs
XG0
X8
GND
Q53 Q54 Q63 Q64
Q5
Universal Inputs/Outputs
X5
X2
Digital Outputs AC 24-230V 4(3) A
X3
X1
Q13 Q14 Q23 Q24 Q33 Q34 Q43 Q44
Q1
AC 24V
XG0
GND
15
+24V
A+
1
2
17
D1
M
S1
XG
24VAC
M
X10
Digital Inputs
D2
13
+24V
B-
F2
12
Y1
G0
G
32
M
A+
48
18
CLB
LON
CLA
D5
D4
N3
19
VS 21-150 CG ACX36-2 SUP-EXH
J1
HMI
EN
B-
D3
11
M
10
Appendix 4 Circuit diagram of VS 21-150 CG-ACX-2 control gear
2/2
VTS reserves the right to implement changes without prior notice
Advanced manual
Appendix 5 Circuit diagram of VS 180-300 CG ACX-2 SUP-EXH
1/3
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
49
Appendix 5 Circuit diagram of VS 180-300 CG ACX-2 SUP-EXH
2/3
EN
VTS reserves the right to implement changes without prior notice
50
Advanced manual
Appendix 5 Circuit diagram of VS 180-300 CG ACX-2 SUP-EXH
3/3
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
51
1/4
Appendix 6 Circuit diagram of VS 400-650 CG ACX-2 SUP-EXH
EN
VTS reserves the right to implement changes without prior notice
52
Advanced manual
2/4
Appendix 6 Circuit diagram of VS 400-650 CG ACX-2 SUP-EXH
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
53
3/4
Appendix 6 Circuit diagram of VS 400-650 CG ACX-2 SUP-EXH
EN
VTS reserves the right to implement changes without prior notice
54
Advanced manual
4/4
Appendix 6 Circuit diagram of VS 400-650 CG ACX-2 SUP-EXH
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
55
Appendix 7 Circuit diagram of power and motor connection for VS 10-15 CG ACX-1 SUP and SUPEXH control gears
VS 10-15 CG ACX36-1 SUP
Q1M
X0
PE
L1
L2
N PE
1
N
N
PE
PE
N
L
1M1
1~
1x230V
EN
N PE
3
L3
L
L
PE
2
POWER
PE
1M2
1~
VS 10-15 CG ACX36-1 SUP-EXH
Q1M
X0
PE
L1
L2
1
N PE
N
N PE
N PE
3
L3
N
L
L
2
PE
1M1
1~
1x230V
POWER
PE
L
N
2M1
1~
PE
L
N
PE
1M2
1~
VTS reserves the right to implement changes without prior notice
56
Advanced manual
Appendix 8 Circuit diagram of power and motor connection for VS 21-150 CG ACX36-2 SUP control
gear
1x230V power supply, frequency converter with 1×230V supply
X0
Q1M
N
L1
L2
X0
PE
X0
1F1M N
PE
N
1
PE 2
N
PE F1:2 N
L3
1x230V
L1
N
L1
L2
PE
W
PE
PE
U
POWER
V
V
PE
L
HEATER
PUMP
W
1M1
~3
N
1M2
1~
3x230V
U
N
L
EN
LAMP
3x400V power supply, frequency converter with 1×230V or 3x400V supply
Q1M
X0
N
L1
L2
X0
PE
1F1M N
PE
N
PE
L2
1
N
PE 2
N
PE F1:2 N
L3
L1 L2 L3
L1
X0
L3
N
PE
L
N
PE
L
N
Appendix A
1M2
1~
POWER
HEATER
PUMP
LAMP
VTS reserves the right to implement changes without prior notice
Advanced manual
57
Appendix 9 Circuit diagram of power and motor connection for VS 21-150 CG ACX36-2 SUP-EXH
control gear (used also for VS 180-300 supply)
1x230V power supply, frequency converter with 1×230V supply
Q1M
N
L1
L2
1F1M N
PE
X0
X0
X0
X0
2F1M N
PE
PE
N
1
PE 2
N
PE F1:2 N
L3
1x230V
1x230V
L1
N
L1
L2
PE
W
PE
L1
L2
PE
W
PE
N
L
PE
U
POWER
V
3x230V
EN
U
V
U
V
V
U
HEATER
PUMP
W
2M1
~3
1M1
~3
L
N
PE
L
N
1M2
1~
3x230V
W
PE
LAMP
RRG
3x400V power supply, frequency converter with 1×230V or 3x400V supply
Q1M
X0
N
L1
L2
PE
1F1M N
PE
2F1M
N
PE
N
PE
L1 L2 L3
N
PE
L2
N
1
PE 2
N
PE F1:2 N
L3
L1 L2 L3
L1
X0
X0
X0
L3
N
PE
Appendix A
Appendix A
POWER
L
N
PE
L
N
PE
L
N
1M2
1~
HEATER
PUMP
RRG
LAMP
VTS reserves the right to implement changes without prior notice
58
Advanced manual
Advanced manual
59
L2
L1
L3
L3
POWER
L2
L1
Q1M
N
N
X0
PE
PE
N
Appendix A
L1 L2 L3
1F1M N
X0
PE
PE
N
Appendix A
L1 L2 L3
2F1M N
X0
PE
PE
N
N
A p p e n d ix A
L1 L2 L3
1F2M
X0
PE
PE
L
Appendix A
HEATER
PUMP
1M2
1~
N
PE
L
PE
N
L1 L2 L3
PE 2
PE
2F2M N
N
X0
X0
1
RRG
N
N
PE
N
LAMP
L
PE F1:2 N
Appendix 10 Circuit diagram of power and motor connection for VS 180-300 CG ACX-2 SUP-EXH control gear (used also for VS
400-650 supply)
3x400V power supply, frequency converter with 1×230V or 3x400V supply
EN
VTS reserves the right to implement changes without prior notice
1
L2
L1
L3
L3
60
1M2
1~
N
X0
PE
L
N
N
L3
L3
N
PE
N
LAMP
L
PE
N
N
A p p en d i x A
L1 L2 L3
1F3M N
X0
Appendix A
L1 L2 L3
1F1M N
N
PE
X0
X0
PE F1:2 N
POWER
L2
L2
Q2M
RR G
L1
L1
PE 2
HEATER
PUMP
L
N
POWER
L2
L1
Q1M
PE
PE
PE
PE
N
N
Appendix A
L1 L2 L3
2F3M N
X0
Appendix A
L1 L2 L3
2F1M N
X0
PE
PE
PE
PE
N
N
N
N
A p pen di x A
L1 L2 L3
1F4M
X0
Appendix A
L1 L2 L3
1F2M
X0
PE
PE
PE
PE
N
N
Appendix A
L1 L2 L3
2F4M N
X0
Appendix A
L1 L2 L3
2F2M N
X0
Appendix 11 Circuit diagram of power and motor connection for VS 400-650 CG ACX-2 SUP-EXH control gear
3x400V power supply, frequency converter with 1×230V or 3x400V supply
EN
VTS reserves the right to implement changes without prior notice
Advanced manual
PE
PE
PE
PE
Appendix A Circuit diagram of motor connection depending on the type of the frequency
converter
Frequency converters with 1×230V supply or with 3x400 supply
X0
X0
xFyM N
PE
xFxM N
L1 L2 L3
OR
1x230V
L1
U
V
PE
3x400V
L2
PE
W
PE
R S T
V
U
3x230V
PE
W
PE
3x400V
V
U
U
W
V
EN
W
xMy
~3
xMy
~3
y = 1 or 2; 1 - for supply, 2 – for exhaust (according to the table D)
x = 1…4 - the next noumber of motor in AHU(according to the table D)
TABLE D
1F1M 2F1M 1F2M 2F2M 1F3M 2F3M 1F4M 2F4M
VS 21-150 CG ACX-2 SUP
1M1
VS 21-150 CG ACX-2 SUP-EXH
1M1
2M1
VS 21-150 CG ACX-2 SUP-EXH
(sup for VS 180-300)
1M1
1M2
VS 180-300 CG ACX-2 SUP-EXH
1M1
2M1
1M2
2M2
VS 180-300 CG ACX-2 SUP-EXH
(sup for VS 400-650)
1M1
1M3
1M2
1M4
VS 400-650 CG ACX-2 SUP-EXH
1M1
2M1
1M2
2M2
1M3
2M3
1M4
2M4
VTS reserves the right to implement changes without prior notice
Advanced manual
61
Appendix 12 The application control schemes
The control schemes for separate application are on the CD plate delivered with AHUs.
In order to print the proper application scheme as the first one should find the application code on the
AHU’s technical data, next select „Control Aplication” from menu „AUTOMATICS” of CD plate and
next choose suitable code and leading sensor.
EN
VTS reserves the right to implement changes without prior notice
62
Advanced manual
Appendix 13 DESCRIPTION OF NETWORK VARIABLES
Operation mode
presetting
Type:
Structure 2 Bytes
Fixed-Point Scalar
unsigned short
A parameter from VS 00 HMI Advanced
1/3
Range
Resolution:
Unit
value: 0..100
state: -1,0,1
value: 0,5
state: 1
-
Network variable
Parameter description
Set Mode
nviSwitch00
(0:off, 1: Auto, 2: Stby, 3:On)
no present
nviSwitch00.state
always value 1
Operation mode
confirmation
Type:
Bitfield
AHU operation mode
(only presetting)
Range:
0..65565
A parameter from VS 00 HMI Advanced
Network variable
Parameter description
not present
nviUniState2:0
Operation mode change is executed
when bit changes from 1 to 0
AHU status
Type:
Fixed-Point Scalar
unsigned short
A parameter from VS 00 HMI Advanced
Resolution:
Unit
0...100
0,5
-
Network variable
Parameter description
nvoOpMode
(0:VENT, 1: Heating, 2:
Current AHU status
Cooling 3:PreHeating, 4: OFF)
Status
Flow
Range
Type:
Fixed-Point Scalar
signed long
A parameter from VS 00 HMI Advanced
Range
0...65535
Resolution:
0,01
Network variable
Unit
Parameter description
SupAirFlow
nviPerc00
Supply fan speed [%]
SupFanSpeed
nviFlow00
Supply fan speed [Hz]
ExhAirFlow
nviPerc01
Exhaust fan speed [%]
ExhFanSpeed
nviFlow01
Exhaust fan speed [Hz]
Type:
Limits and settings Fixed-Point Scalar
signed long
A parameter from VS 00 HMI Advanced
Range
-273,13...327,66,
Network variable
Resolution:
0,01
Unit
o
C
Parameter description
Min Sup Temp
nviTemp00
Minimal acceptable temperature in
supply duct
Max Sup Temp
nviTemp01
Maximal acceptable temperature in
supply duct
MinOutTemp
nviTemp02
Limit temperature of AHU operating
in cooling mode
PumpMinOutTemp
nviTemp03
Temperature under which water
heater pump operates apart from
AHU operation status
HMI Temp Setp
nviTemp04
Preset temperature
Temp Setp
nvoTemp05
Preset temperature making
allowance for a correction from the
VS 00 HMI Basic adjuster
VTS reserves the right to implement changes without prior notice
Advanced manual
63
EN
Appendix 13 DESCRIPTION OF NETWORK VARIABLES
Digital inputs
Type:
Range
Bitfield
0...18446744073709551615
A parameter from VS 00 HMI
Advanced
EN
2/3
Network variable
Parameter description
FireDetector
nvoAlarm:0
Fire protection unit
AirSideTherm/ElectricHeater
nvoAlarm:1
Anti-frost thermostat/
overheating thermostat
WaterSideTherm
nvoAlarm:2
Anti-frost thermostat on the
water side
ChillerStatus/RefrigUnit/CWHW_AL
nvoAlarm:3
Status of cooling system
Motor
nvoAlarm:4
Status of 1-phase motor
Filters
nvoAlarm:5
Status of filters (1-phase
systems)
FilterSup
nvoAlarm:6
Status of supply filters
FilterExh
nvoAlarm:7
Status of exhaust filters
MultiFunDigIn
nvoUniState1:6
Status of universal input
(range and type as follows)
Type:
Bitfield
Digital outputs
Range
0...65565
A parameter from VS 00 HMI
Advanced
Network variable
Parameter description
Pump
nvoUniState1:0
Water heater pump
Fan/Damper
nvoUniState1:1
Air damper
CoolerComp/Chiller/St1
nvoUniState1:2
Cooling system
HtgStatus/St2
nvoUniState1:3
AHU in heating mode/Second
operation level of the cooling
system
AlarmRelay
nvoUniState1:4
Alarm relay
MultiFunRelay
nvoUniState1:5
Universla relay
Analog inputs
Type: Fixed-Point
Scalar signed long
A parameter from VS 00 HMI
Advanced
Range
Resolution:
Unit
-273,13...327,66,
0,01
o
Network variable
C
Parameter description
Supply Temp
nvoTemp00
Temperature in supply duct
Room/Exh Temp
nvoTemp01
Room temperature
Outside Temp
nvoTemp02
External temperature
AfterReco Temp
nvoTemp03
Temperature behind the
recovery system on the exhaust
side
MultiFunAnaIn
nvoTemp04
Universal input
not present
nvoTemp06
Temperature measured by the
HMI Basic
VTS reserves the right to implement changes without prior notice
64
Advanced manual
Appendix 13 DESCRIPTION OF NETWORK VARIABLES
Analog output
Type:
Fixed-Point Scalar
unsigned short
3/3
Range
Resolution:
Unit
0...100
0,5
%
A parameter from VS 00 HMI
Advanced
Network variable
Parameter description
HeatingRate
nvoPerc00
Heating rate
CoolingRate
nvoPerc01
Cooling rate
RecoveryRate
nvoPerc02
Recovery rate
nvoPerc03
Opening rate of supply
damper in systems with crossflow exchanger without bypass damper
SupAirRate
Alarm statuses
Type:
Range
Bitfield
0...18446744073709551615
A parameter from VS 00 HMI
Advanced
Network variable
Parameter description
SupFCStatus
nvoAlarm:8
Status of frequency converter
on the supply side
ExhFCStatus
nvoAlarm:9
Status of frequency converter
on the exhaust side
FCRRGStatus
nvoAlarm:10
Status of frequency converter
of the rotary exchanger
SupplyTempErr
nvoAlarm:11
Failure of temperature sensor
on the supply side
Room/ExhTempErr
nvoAlarm:12
Failure of temperature sensor
in a room
OutsideTempErr
nvoAlarm:13
Failure of external
temperature sensor
AfterRecoTempErr
nvoAlarm:14
Failure of temperature sensor
behind the recovery system
RoomUnitErr
nvoAlarm:15
Failure of the VS 00 HMI
Basic panel
Type:
Range
Fixed-Point Scalar
signed long
Year:
Time synchronization
Month:
0...12
Day:
0...31
Fixed-Point Scalar
unsigned short
Hour
A parameter from VS 00 HMI
Advanced
Date/Time
0...3000
0...23
Minutes
0...59
Seconds
0...59
Network variable
nviActTime
Parameter description
Current date and time
VTS reserves the right to implement changes without prior notice
Advanced manual
65
EN

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement