Electricity Meters
Residential BS / IEC
British Standard
5235 Single Phase Credit Meter
Date: 20/11/08
Filename: 5235 User Manual
Q P u l s e N o : I B 0 4 7
© Landis+Gyr
User Manual & Technical Specification
Page 2 of 21 Issue: 4 5
Revision History
3.
4.
5.
Issue Date
1.
Comments
10/10/04 New document
2. 10/01/05 Added section on the No power read and Appendix B. Added Document number.
01/11/05
15/02/06
18/11/08
Added new amendments
Added D-L version removed F version (reactive energy still needs adding)
Revised manual to new branding guidelines and layout
Copyright notice
The material in this document is the property of Landis+Gyr. Our products are under continual improvement and we reserve the right to make changes without prior notice
Landis+Gyr
1 Lysander Drive,
Northfields Industrial Estate,
Market Deeping,
Peterborough
PE6 8FB www.landisgyr.com
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Table of Contents Issue: 4 Page 3 of 21
Table of Contents
8
8.1
8.2
8.3
7
7.1
7.2
7.3
5
5.1
5.2
5.3
6
6.1
6.2
9
10
10.1
4
4.1
4.2
4.3
3
3.1
3.2
3.3
3.4
1
1.1
1.2
1.3
1.4
1.5
2
2.1
2.2
Introduction____________________________________________________________ 5
Purpose _________________________________________________________________ 5
Meter Overview ___________________________________________________________ 5
Model versions ____________________________________________________________ 5
Reference Standards _______________________________________________________ 5
20 Year Certification Life ____________________________________________________ 5
Safety Information ______________________________________________________ 7
Responsibilities ___________________________________________________________ 7
Safety Regulations _________________________________________________________ 7
Operational Functions ___________________________________________________ 9
Measurement _____________________________________________________________ 9
Anti-creep _______________________________________________________________ 9
Meter Memory ____________________________________________________________ 9
Reverse / Export Energy registration __________________________________________ 9
User Interfaces ________________________________________________________ 11
Register Displays _________________________________________________________ 11
Pulsed Output (Option) ____________________________________________________ 11
Switching inputs (D model) _________________________________________________ 11
Installation____________________________________________________________ 13
Construction_____________________________________________________________ 13
Meter fixing _____________________________________________________________ 13
Wiring _________________________________________________________________ 13
Technical Summary ____________________________________________________ 15
Technical Summary _______________________________________________________ 15
Dimensions _____________________________________________________________ 16
Maintenance and Service ________________________________________________ 17
Meter Check _____________________________________________________________ 17
Meter Testing____________________________________________________________ 17
Post Installation Configuration Changes _______________________________________ 17
Measures in the Event of Faults __________________________________________ 18
Operating Faults _________________________________________________________ 18
Disconnecting the Meter ___________________________________________________ 18
Repairing the Meter _______________________________________________________ 18
Decommissioning and Disposal __________________________________________ 20
Glossary of Terms and Standards ________________________________________ 21
Acronyms _______________________________________________________________ 21
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 4 of 21
10.2
Issue: 4 5 Table of Contents
Measurement Units ______________________________________________________ 21
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Introduction Issue: 4 5 Page 5 of 21
1 Introduction
Introducing the 5235, single and multi-rate tariff options, Single Phase BS
Standard Credit Meter
1.1 Purpose
This document details the functions for the following variants of the 5235
Single Phase Credit Meters, active energy only.
Single Rate, kWh meter
Single Rate, kWh meter with class A pulse output
Multi-rate Externally switched meter
1.2 Meter Overview
The meter is a whole current static electricity meter capable of measuring kWh in single and two rate variants. An additional option to have a pulsed output is also available on the single rate version. The meter is approved to
IEC62052
– 11: 2003 & IEC62053 – 21:2003 classes 1.0 and 2.0 and has been given a 20 year certification life by OFGEM.
The meter is sealed for life by a liquid welding process and therefore does not carry an external wire seal.
All meter types feature an optical port used for reprogramming. The metrology LED is incorporated into this port and pulses at a rate of 1000 impulses per kWh.
All facia details are permanently laser etched directly onto the meter front.
Options would normally include property details, serial numbering and various barcode options. Other details may be printed such as customer l ogo’s and meter type codes etc.
1.3 Model versions
A character denotes meter version after the model number:
A - Single rate only active only
B - Single rate with pulsed output active only
D - Externally switched two-rate active only
1.4 Reference Standards
The meter has been tested by OFGEM and has the following certification.
IEC62052
– 11: 2003. IEC62053 – 21:2003.
Alternating current static watt-hour meters for active energy (Classes 1 & 2). Other standards are in the technical summary.
1.5 20 Year Certification Life
This meter has been given a certification life of 20 years by OFGEM the UK regulatory body. This has been achieved by proving the reliability of each of the components in the meter and by using mathematical models provided
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 6 of 21 Issue: 45 Introduction by OFGEM. This modelling has shown a reliability of better than 97% over twenty years. The OFGEM approval number for this meter is 986.
OFGEM certificates and lifetime reports are available upon request. Please contact [email protected]
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Safety Information Issue: 4 5 Page 7 of 21
2 Safety Information
Attention is drawn as follows in the individual chapters of this user manual with classified word symbols and pictographs to the relevant danger level, i.e. the severity and probability of any danger:
Definition of Danger
This symbol is used to indicate a possibly dangerous situation which could result in severe physical injury or a fatality.
Definition of Warning
This symbol is used to indicate a possibly dangerous situation which could result in minor physical injury or material damage.
Definition of Note
This symbol is used to indicate general details and other useful information.
In addition to the danger level, all safety information also describes the type and source of the danger, it’s possible consequences and measures to counteract the danger.
2.1 Responsibilities
The owner of the meters
– normally the utility – is responsible that all persons engaged on work with meters:
Have read and understood the relevant sections of the user manual.
Are sufficiently qualified for the work to be performed.
Strictly observe the safety regulations (according to section 1.6) and the operating information in the individual chapters.
In particular, the owner of the meters bears responsibility for the protection of persons, prevention of material damage and the training of personnel
(Landis+Gyr. provides training courses for this purpose on specific equipment; please contact the relevant agent if interested).
2.2 Safety Regulations
The following safety regulations must be observed at all times:
This equipment does not contain a disconnection device. Means for disconnection from the supply must be provided as part of the building installation. Do not work on the equipment unless the
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 8 of 21 Issue: 45 Safety Information supply is disconnected. If disconnection is done by removal of fuses or other cut-outs, the removed disconnection devices must be kept secure from replacement while work is performed. If disconnection is provided by a switch, the switch shall conform to the requirements of IEC 947-1 and IEC 947-3 or equivalent.
This equipment does not contain an overcurrent protection device.
Overcurrent protection must be provided as part of the building installation. Maximum overcurrent device rating is 100 Amp at 415
Volts, conforming to the requirements of BS1361, or equivalent.
The maximum rating of the meter is 100A and requires connecting conductors of 25mm
2
. Failure to do so could result in irreparable damage to the meter. If smaller connecting conductors are used an appropriate mains fuse must be used.
Only suitably trained and qualified personnel shall be allowed to work on the equipment. Local safety standards shall be observed and shall take precedence over these regulations in points of conflict.
The meters must be held securely during installation. They can cause injuries if dropped.
Meters that have fallen must not be installed, even if no damage is apparent, but must be returned for testing to the service and repair department responsible (or the manufacturer). Internal damage can result in functional disorders or short-circuits.
The meters must on no account be cleaned with running water or with high-pressure devices. Water penetrating can cause shortcircuits.
The meter terminal cover should be secured in place before any load is supplied.
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Operational Functions Issue: 4 5 Page 9 of 21
3 Operational Functions
The standard operational functions of the 5235
3.1 Measurement
The Meter is a 120V or 220-240Vac, 50Hz or 60Hz, 5 to 100A Single
Phase Credit Meter. It contains a measuring element capable of measuring active energy (kWh). The meter measures and registers kWh up to class
1.0. accuracy. The metrology LED is incorporated into the optical port and pulses at a rate of 1,000 impulses per kWh for energy registration. All variants offer a test mode, which shows 3 decimal places and is reset when voltage is removed.
3.2 Anti-creep
Below starting current, the meter enters into an anti-creep mode. In this state the metrology LED is permanently lit and the registers do not increment. The LED remains lit until the meter current is increased in a forward direction beyond the starting current. The starting current is shown in the technical summary.
3.3 Meter Memory
All the meters data is to be recorded in a Ferroelectric Random Access
Memory (FRAM) under the control of the microprocessor. All the kWh registers are stored in the FRAM and will be updated periodically and on power-fail. The FRAM is able to be re-written throughout the life of the meter and will hold the information, if required for over twenty years.
3.4 Reverse / Export Energy registration
Three factory configurable reverse energy modes can be set as follows:
Export Energy Registration
A reverse / export energy register stores the value of kWh recorded by the meter in a reverse direction. The register may be configured as part of the display cycle of the meter. Alternately the register is held in memory and can be read from the meter via the IEC 1107 port. The Reverse energy register can be displayed with 0, 1 or 2 decimal places. Export energy will be recorded in the same way as forward (Import) flowing energy using identical starting currents etc.
F
A
B
E
D
C
Total Reverse
Reverse Energy Detection
A configurable option within the meter will alternate a warning message on the display should a fraud attempt be made by running current backwards
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 10 of 21 Issue: 45 Operational Functions through the meter. The reverse energy warning message is triggered when the reverse power exceeds a programmable threshold level of between 1-
10 Amps for a period of 10Wh. Once this level is reached the message below will be displayed which can only be reset via the IEC 1107 port.
Whilst in this mode the LED will remain lit whilst there is reverse energy detected.
Reverse Energy Detection Message
Unidirectional Register
An optional requirement is to accumulate both import and export energy into the same register. Basically this will be the sum of adding both forward and reverse energy resisters. The register would be shown as the normal kWh display as below:
F
A
B
E
D
C
Total Display
No Power Read (option)
This allows the user to take meter readings when there is no mains electricity supply. This is achieved by installing a battery supply board that powers the meter. The user applies a magnet to the outside of the meter case and the meter powers up for 20 to 30 seconds. During this time the meter displays the sign on and then displays the energy registers.
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
User Interfaces Issue: 4 5 Page 11 of 21
4 User Interfaces
The inputs and outputs of the 5235
4.1 Register Displays
Single rate version -versions A & B
Single rate meters display the total kWh reading only. The display is configurable to show either whole numbers, 1 or 2 decimal places. The meter is also factory configurable to display either 5 or 6 digits with roll over to zero at 99999 or 999999.
Two-rate meter (external time switch) - D version only kWh are recorded at a particular rate and displayed using the rate enunciators on the left hand side of the display. The rate registers are displayed between 0 and a maximum of 2 decimal places unless configured to 3 decimal places of testing purposes via the optical port.
The rate register range is 00000.00
– 99999.99 kWh unless factory configured to six digits. The diagram shows a display sequence for a fourrate meter and total register below. In the two rate variant the meter may be configured to operate between 1 and 2 rates via the Optical port.
Rate 1 display. Flashing enunciator indicates active rate
F
A
B
E
D
C
Rate 2 Display
4.2 Pulsed Output (Option)
The type B meter has an optically isolated, voltage free open collector
Pulse Output that is configurable to between 1 and 1000 pulses per kWh.
To maximise operation with external monitoring devises, the pulse width can also be configured to between 20 and 260 mS in 20 mS steps.
Configuration is made through the IEC 1107 port.
The output meets IEC62053-31: 1998 Class B, Maximum voltage 15Vdc.
4.3 Switching inputs (D model)
The configuration is factory set allowing the meter to operate as a single or two rate meter. Rate switching is achieved by switching neutral or live to the input terminal. See wiring diagram for the D model.
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 12 of 21 Issue: 45
5235D-L Live switching model
5235D-N Neutral switching model
User Interfaces
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Installation Issue: 4 5 Page 13 of 21
5 Installation
Construction, Mounting and wiring of the 5235
5.1 Construction
The Credit Meter case meets the requirements of BS5685 and is manufactured from following materials: -
Meter Base: Flame Retardant and UV stabilised Polycarbonate
Meter Top: Flame Retardant and UV Stabilised Polycarbonate
Terminal Cover: Flame Retardant and UV Stabilised Polycarbonate
Terminals: Solid Brass extrusion, 8.3mm diameter with 2 screws
5.2 Meter fixing
The meter is mounted using the two fixing holes found either side of the terminal housing. To aid terminal cover sealing, the screw boss has four raised indicators that should be aligned against the indicator on the cover.
5.3 Wiring
Terminal arrangement conforms to BS5685, Part1, 1979. Wiring diagrams can be put onto the terminal covers of the meters.
Meter
Element
Supply
L
N
Meter type 5235 A and F
Meter
Element
Wh
L
N
Load
Supply
L
N
Meter type 5235 B
L
N
Load
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 14 of 21 Issue: 45
Meter
Element
Supply
L
N
Meter type 5235 D - N
Meter
Element
Time switch
L
N
Load
Supply
L
N
Meter type 5235 D
– L
Time switch
L
N
Load
Installation
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Technical Summary Issue: 4 5 Page 15 of 21
6 Technical Summary
The technical specifications of the 5235
6.1 Technical Summary
System Voltage Single element meters
Current (Base)
Current (Max)
Starting Current
Max measuring range
Measuring Accuracy
Burdens
Supply Frequency
Temperature Range
Meter Constant
Pulse output
Display
Quality
Ofgem approval number
Certificated life
Reference standards
Construction
Terminal arrangement
Terminal size
Weight
Dimensions (mm)
Supply variation
Voltage withstand
Direct connection Ib
Imax
240Vac Phase to Neutral
230Vac Phase to Neutral
220Vac Phase to Neutral
210Vac Phase to Neutral
+15% to -20%
415V continuous
10kV impulse @105J
5A, 10A, or 20A
40A, 60A, 80A or 100A
(IEC)
IEC 62053-21
Voltage Circuit @ 230Vac
Current Circuit @ Ib
Nominal
Frequency Variation
Limit operating ranges
Storage range
0.4% of Ib
20mA up to 100A
Class 1 and 2
0.9W 7.7VA
0.1VA
50Hz or 60Hz
+/- 5%
-20°C to 55°C
-25°C to 70°C
1000 imp/kWh
The output meets IEC62053-31:
1998 Class B, Maximum voltage
15Vdc
Type
– 7 character, 7segment LCD
Character size
– 8
3.5 mm.
Manufactured to: ISO 9001:1994
986
20 years
IEC62052
– 11: 2003 & IEC62053 – 21:2003 Alternating current static watt-hour meters for active energy. (Classes 1 & 2)
BS5685: 1979: Part 1:Specification class 0.5, 1.0 and 2.0 Single phase and Polyphase, single rate and multi-rate watt-hour meters.
IEC62056
– 21: 2002.Data Exchange for Meter Reading, Tariff and Load
Control. Direct Local Exchange.
SI1566: 2003The Meters (Certification) Regulations 1990.
Flame Retardant and UV
Stabilised Polycarbonate
BS5685
Standard Terminal Cover
8.3 mm diameter.
304g
Extended Terminal Cover
Standard Terminal Cover
Extended Terminal Cover
338g
H 80 x W 125 x D 36
H 113 x W 126 x D 41
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 16 of 21
6.2 Dimensions
Issue: 45 Technical Summary
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Maintenance and Service Issue: 4 5 Page 17 of 21
7 Maintenance and Service
7.1 Meter Check
While it isn’t necessary, under normal circumstances, to perform any maintenance on the installed meter, the following are check points that should be observed during scheduled periodic meter visits.
Is the meter dry and clean, particularly the LCD display and the optical interface?
Does the meter display a legible and sensible display? i.e. does the meter appear in a serviceable condition.
Check all factory fitted and company fitted seals are in place secure and intact.
Observe display for any error messages or notifications
Confirm that the energy registers have changed to a reasonable degree since the last visit.
If irregularities are found, continue as in section 8.
7.2 Meter Testing
The testing of meters, either random sample or on all meters, should be carried out periodically according to national regulations. The meter must be removed as described in section 8.3 and replaced with a meter of similar type for the duration of the tests.
7.3 Post Installation Configuration Changes
With the aid of a laptop computer or other suitable hand held device a flag probe and Landis+Gyr specific software, it is possible to amend the factory configured options of the meter. It is beyond the scope of this manual to describe in any further detail the procedure. Landis+Gyr sales team would be happy to discuss specific requirements.
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 18 of 21 Issue: 45 Measures in the Event of Faults
8 Measures in the Event of Faults
8.1 Operating Faults
If the LCD window is illegible or the data readout does not function, the following points should be checked.
Is the mains voltage present?
– Are the preliminary fuses intact?
Has the minimum or maximum recommended ambient temperature been exceeded?
Is the LCD window clear of all debris?
– Not misted over, painted over or soiled in any way.
If none of the above are causing the fault the meter should be disconnected as per section 8.2, replaced if required as detailed in section 5 and returned to Landis+Gyr as described in section 8.3.
8.2 Disconnecting the Meter
Remove preliminary fuses before continuing
The connecting conductors should not be Live when removing the meter.
Electrically Live parts are a life threatening hazard. Preliminary fuses should be removed and kept in a safe place until all work is complete, where they cannot be replaced by anyone unnoticed.
Proceed as follows:
Remove the company seal on the terminal cover (if fitted).
Release the two terminal cover screws and remove terminal cover.
Check with a suitable voltage testing device that the phase connections are not live. If they are live then remove the preliminary fuses and keep in a safe place until all work is complete, where they cannot be replaced by anyone unnoticed.
Remove the signal inputs and outputs by releasing the auxiliary terminal screws.
Remove the phase connections by releasing the main terminal screws.
If required fit a suitable replacement meter as described in section
5.
8.3 Repairing the Meter
There are no user serviceable parts inside the meter. Breaking factory calibration seals will invalidate the calibration status of the meter. In the event of a meter requiring repair, proceed as follows.
Remove the meter from the installation as detailed in section 8.2.
Attach a label, which describes the fault as accurately as possible, to the meter and include name and contact details of person responsible in case of inquiries.
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Measures in the Event of Faults Issue: 4 5 Page 19 of 21
Package the meter to ensure no further damage can occur during transit.
Send the meter back to Landis+Gyr.
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr
Page 20 of 21 Issue: 45 Decommissioning and Disposal
9 Decommissioning and Disposal
The procedure for the safe removal of the meter from the installation is described in section 8.3. Please ensure that ALL SAFETY PRECAUTIONS are met before proceeding.
Based on the environmental certificate ISO 14001, the components used to manufacture the meter can, in the main, be broken down into constituent parts and sent for suitable recycling or disposal.
The following are general guidelines and should NOT take priority over local disposal and environmental policies which should be adhered to without compromise.
Component Parts
Printed Circuit Boards
LCD Display
Metal Components
Plastic Components
Disposal
Treated as per disposal of Electronic Equipment
Sorted and delivered to collective recycling point
Sorted and delivered for re-granulation if at all possible
© Landis+Gyr 5235 Single Phase Credit Meter
– User Manual & Technical Specification
Glossary of Terms and Standards Issue: 4 5 Page 21 of 21
10 Glossary of Terms and Standards
10.1 Acronyms
10.2 Measurement Units
mO ms
Nm o
C
UN
UT
V
A
Hz
Iref
Kg kVAh kvarh kWh mm
Acronym
BS
DFS
DIN
ECD
EEPROM
IEC
ISO
LCD
LED
MD
MID
NPR
OFGEM
PTR
RED
Definition
British Standard
Direct Field Sensor
Deutsches Institut für Normung (German Institute For
Standardisation)
External Connection Diagram
Electrically Erasable Programmable Read Only Memory (E2)
International Electrotechnical Commission
International Standards Organisation
Liquid Crystal Display
Light Emitting Diode
Maximum Demand
Metering Industry Directive
No Power Read
The Office of Gas and Electricity Markets
Photo-transistor
Reverse Energy Detected
Ampere (unit of current)
Hertz (unit of frequency)
MID reference current
Kilogramme (unit of weight)
Kilo Volt Ampere hour kilo Volt Amps reactive hour kilo Watt-hour millimetre (unit of distance) milliohm (unit of resistance) millisecond
Newton meter (unit of torque)
Degree Celsius (unit of temperature)
Rated supply voltage of meter
Rated external switch voltage
Volt
5235 Single Phase Credit Meter
– User Manual & Technical Specification
© Landis+Gyr