Carrier 48GS 018-060, 024-040, 030-040, 030-060, 036-060, 036-090, 042-060, 042-090, 048-090, 048-115, 048-130, 060-090, 060-115, 060-130, 48GX 024-060, 042-060, 042-090, 048-090, 048-115, 048-130, 060-090 Installation, Start-Up and Service Instructions
Below you will find brief information for Gas Heating/Electric Cooling Units 48GS 018-060, 48GX 024-060, 48GS 024-040, 48GS 030-040, 48GS 030-060. These units are fully self-contained, combination Category I gas heating/electric cooling units designed for outdoor installation. They can be installed either on a rooftop, a cement slab, or directly on the ground.
Advertisement
Advertisement
48GS018-060
48GX024-060
Single Package Gas Heating/
Electric Cooling Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . 1-3
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
RECEIVING AND INSTALLATION
. . . . . . . . . . . . 4-14
Step 1 — Check Equipment
. . . . . . . . . . . . . . . . .
4
• IDENTIFY UNIT
• INSPECT SHIPMENT
Step 2 — Provide Unit Support
. . . . . . . . . . . . . .
4
• ROOF CURB
• SLAB MOUNT
• GROUND MOUNT
Step 3 — Field Fabricate Ductwork
. . . . . . . . . .
4
Step 4 — Provide Clearances
. . . . . . . . . . . . . . .
4
Step 5 — Rig and Place Unit
. . . . . . . . . . . . . . . .
4
Step 6 — Connect Condensate Drain
. . . . . . . .
7
Step 7 — Install Flue Hood
. . . . . . . . . . . . . . . . . .
7
Step 8 — Install Gas Piping
. . . . . . . . . . . . . . . . .
7
Step 9 — Install Duct Connections
. . . . . . . . . . 10
• CONFIGURING UNITS FOR DOWNFLOW
(VERTICAL) DISCHARGE
Step 10 — Install Electrical Connections
. . . . 11
• HIGH-VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V
OPERATION
• CONTROL VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
• TRANSFORMER PROTECTION
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-29
MAINTENANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . 33,34
START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . CL-1
NOTE TO INSTALLER — Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COM-
PLETELY. Also, make sure the User’s Manual and Replacement Guide are left with the unit after installation. The furnace is NOT to be used for temporary heating of buildings or structures under construction.
Fig. 1 — Unit 48GS and 48GX
(Shown with Accessory Wire Grille)
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, fire, or an explosion which can result in personal injury or unit damage. Consult a qualified installer, service agency, or gas supplier for information or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product.
Before performing service or maintenance operations on unit, turn off gas supply then unit main power switch.
Electrical shock could cause personal injury.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
General —
The 48GS,GX units (see Fig. 1) are fully selfcontained, combination Category I gas heating/electric cooling units designed for outdoor installation. See Fig. 2 and 3 (pages 2 and 3) for unit dimensions. All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. Units may be installed either on a rooftop, a cement slab, or directly on the ground (if permitted by local codes). See Fig. 4 for roof curb dimensions.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1a 6a
PC 111 Catalog No. 534-732 Printed in U.S.A.
Form 48GS,GX-1SI Pg 1 1-99 Replaces: 48GS-1SI
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
UNIT
48GS018040
48GS024040/060
48GS030040/060
48GS036060/090
48GS042060/090
48GX024040/060
48GX030040/060
48GX036060/090
ELECTRICAL
CHARACTERISTICS
208/230-1-60
208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60, 460-3-60
UNIT WEIGHT lb
249.0
280.0
280.0
314.0
355.0
290.0
313.0
321.0
kg
113.2
127.3
127.3
142.7
161.4
639.3
690.0
707.7
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ’D CLEARANCES. in. (mm)
Between units, power entry side . . . . . . . . . . . . . . 42 (1066.8)
Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded surfaces, control box side . . . . . . . . . . . . . . . . . 42 (1066.8)
UNIT HEIGHT in. [mm]
‘‘A’’
35.02 [889.5]
35.02 [889.5]
35.02 [889.5]
35.02 [889.5]
35.02 [889.5]
35.02 [889.5]
39.02 [991.1]
35.02 [889.5]
X
20.0 [508.0]
CENTER OF GRAVITY in. [mm]
Y
14.0 [355.6]
Z
15.0 [381.0]
22.5 [571.5]
21.5 [546.1]
22.5 [571.5]
21.5 [546.1]
22.0 [558.8]
22.0 [558.8]
22.0 [558.8]
13.0 [330.2]
13.75 [349.3]
14.0 [355.6]
13.5 [342.9]
14.5 [368.3]
15.3 [387.4]
15.3 [387.4]
15.0 [381.0]
15.0 [381.0]
13.0 [330.2]
13.0 [330.2]
16.0 [406.4]
17.6 [447.0]
16.5 [419.1]
LEGEND
CG
— Center of Gravity
COND
— Condenser
EVAP
— Evaporator
NEC
— National Electrical Code
REQ’D — Required
NOTE: Dimensions are in mm [in.]
Fig. 2 — 48GS018-042 and 48GX024-036 Unit Dimensions
2
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall system, then the system performance may be compromised.
LEGEND
CG
— Center of Gravity
COND
— Condenser
EVAP
— Evaporator
NEC
— National Electrical Code
REQ’D — Required
NOTE: Dimensions are in mm [in.]
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ’D CLEARANCES. in. (mm)
Between units, power entry side . . . . . . . . . . . . . . 42 (1066.8)
Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded surfaces, control box side . . . . . . . . . . . . . . . . . 42 (1066.8)
FLUE HOOD
UNIT
48GS048090/115/130
48GS060090/115/130
48GX042060/090
48GX048090/115/130
48GX060090/115/130
ELECTRICAL
CHARACTERISTICS
208-230/1/60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60
UNIT WEIGHT lb
415
450
382
421
468
kg
188.6
204.5
842.2
928.2
1031.7
UNIT HEIGHT in. [mm]
‘‘A’’
38.98 [ 990.2]
38.98 [ 990.2]
38.98 [ 990.2]
38.98 [ 990.2]
42.98 [1091.7]
X
22 [558.5]
CENTER OF GRAVITY in. [mm]
16
Y
[406.4]
Z
17 [432.0]
22 [558.5]
23.0 [584.2]
21.5 [546.1]
23.5 [596.9]
16 [406.4]
16.3 [412.8]
16.6 [422.1]
16.3 [412.8]
17 [432.0]
16.6 [421.6]
18.0 [457.2]
17.6 [447.0]
Fig. 3 — 48GS048,060 and 48GX042-060 Unit Dimensions
3
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT — The unit model number and serial number are stamped on unit identification plate. Check this information against shipping papers and job data.
INSPECT SHIPMENT — Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original packages until installation.
Step 2 — Provide Unit Support
ROOF CURB — Install accessory roof curb in accordance with instructions shipped with curb. See Fig. 4 for roof curb dimensions. Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing can also result in air leaks and poor unit performance.
Curb should be level to within 1 ⁄
4 inch. This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
SLAB MOUNT — Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade.
The slab should be flush on the compressor end of the unit
(to allow condensate drain installation) and should extend
2 in. on the three remaining sides of the unit. See Fig. 5. Do not secure the unit to the slab except when required by local codes.
GROUND MOUNT — The unit may be installed either on a slab or placed directly on the ground if local codes permit.
Place the unit on level ground prepared with gravel for condensate discharge.
Step 3 — Field Fabricate Ductwork —
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed −.25 in. wg.
Step 4 — Provide Clearances —
The required minimum operating and service clearances are shown in
Fig. 2 and 3. Adequate combustion, ventilation, and condenser air must be provided, in accordance with section 5.3,
Air for Combustion and Ventilation, of the National Fuel Gas
Code ANSI (American National Standards Institute) Z223.1
(in Canada, sections 7.2, 7.3 or 7.4 or Can/CGA [Canadian
Gas Association] B149 Installation Codes), or applicable provisions of local building code.
Do not restrict condenser airflow. An air restriction at either the outdoor-air inlet or the fan discharge can be detrimental to compressor life.
The condenser pulls air through the condenser coil and discharges it through the top cover. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48-in. above the unit top.
The maximum horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting, tile, or other combustible materials. The unit may be installed on wood flooring or on
Class A, B, or C roof covering materials.
Step 5 — Rig and Place Unit
When installing the unit on a rooftop, be sure the roof will support the additional weight.
Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 6. Refer to
Table 1 and 2 for operating weight. Use extreme caution to
prevent damage when moving the unit. Unit must remain in an upright position during all rigging and moving opera-
tions. The unit must be level for proper condensate drainage; therefore, the ground-level pad or accessory roof curb must be level before setting the unit in place. When a fieldfabricated support is used, be sure that the support is level and properly supports the unit.
4
FLAT
CURB
UNIT SIZE
48GS018-042
48GX024-036
48GS048,060
48GX042-060
PART NUMBER
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required to unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Table lists only the dimensions per part number that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
A in. [mm]
8 [203]
14 [356]
8 [203]
14 [356]
B in. [mm]
11 27 ⁄
32
[301]
11 27 ⁄
32
[301]
15 27 ⁄
32
[402]
15 27 ⁄
32
[402]
C in. [mm]
30 5 ⁄
8
[778]
30 5 ⁄
8
[778]
42 1 ⁄
8
[1070]
42 1 ⁄
8
[1070]
D in. [mm]
28 3 ⁄
4
[730]
28 3 ⁄
4
[730]
40 1 ⁄
4
[1022]
40 1 ⁄
4
[1022]
SIDE PANEL
0.75"
3.0"
BASE PAN
BOTTOM SUPPLY
4.0"
SUPPORT RIB(S)
SEAL STRIP
(FACTORY SUPPLIED)
COUNTER FLASHING
(FIELD SUPPLIED)
ROOFING FELT
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
NAILER
INSULATION
(FIELD SUPPLIED)
ROOFING MATERIAL
(FIELD SUPPLIED)
FULL PERIMETER CURB
Fig. 4 — Roof Curb Dimensions
5
Fig. 5 — Slab Mounting Details
UNIT 48GS
Size
018
024
030
036
042
048
060
UNIT 48GX
Size
024
030
036
042
048
060 lb
271
MAXIMUM
WEIGHT kg
123.2
302
302
336
137.3
137.3
152.7
377
437
472
171.4
198.6
214.5
in.
20.0
22.5
21.5
22.5
21.5
22.0
22.0
A mm
508.0
571.5
546.1
571.5
546.1
558.5
558.5
lb
312
335
MAXIMUM
WEIGHT kg
688.0
738.7
343
404
443
490
756.4
890.9
976.9
1080.5
in.
22.0
22.0
22.0
23.0
21.5
23.5
A mm
558.5
558.5
558.5
584.2
546.1
596.9
Fig. 6 — Suggested Rigging in.
14.0
13.0
13.75
14.0
13.5
17.0
17.0
B mm
355.6
330.2
349.3
355.6
342.9
432.0
432.0
in.
14.5
15.3
15.3
16.3
16.3
16.3
B mm
368.3
388.6
388.6
414.0
414.0
414.3
6
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Models 48GS and GX dispose of condensate water through a
3
⁄
4 in. NPT fitting which exits through the compressor access panel. See Fig. 2 and 3 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. See Fig. 7. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage. See Fig. 7. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing.
Prime the trap with water. Connect a drain tube using a minimum of 3 ⁄
4
-in. PVC or 3 ⁄
4
-in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize the tube.
Pitch the drain tube downward at a slope of at least one in.
for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
Fig. 7 — Condensate Trap
Step 7 — Install Flue Hood —
The flue hood assembly is shipped screwed to the coil panel in the indoor blower compartment. Remove the service access panel to locate the assembly.
For units being installed in California Air Quality
Management Districts which require NO x be field installed.
emissions of
40 nanograms/joule or less, a field-installed low NO x kit must
For 40,000 and 60,000 Btuh input models, use kit part number CPLOWNOX002A00. This kit contains two NO x reduction baffles and one conversion label. For 90,000, 115,000 and 130,000 Btuh input models, use kit part number
CPLOWNOX003A00. This kit contains three NO tion baffles and one conversion label.
x reduc-
The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicated in this section of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1
(in Canada, CAN/CGA B149.1, and B149.2) or NFPA
(National Fire Protection Association) latest revision.
Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.
2. Remove flue hood from shipping location (inside the blower compartment). Place vent cap assembly over flue panel.
Orient screw holes in vent cap with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on the right side and the left side of the hood.
Step 8 — Install Gas Piping —
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1 ⁄
2
-in. FPT gas inlet on the manual shutoff or gas valve.
Install a gas supply line that runs to the heating section.
Refer to Table 3 and the NFGC for gas pipe sizing. Do not
use cast-iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wg maximum pressure drop. Never use pipe smaller than the
1 ⁄
2
-in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.
An 1 ⁄
8
-in. NPT plugged tapping accessible for test gage connection must be installed immediately upstream of the gas supply connection to the gas valve.
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI
Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA
B149.1, (2)-M86). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1 ⁄
4 inch in every 15 ft to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft.
For pipe sizes larger than 1 ⁄
2 in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Never use Teflon tape.
4. Install sediment trap in riser leading to heating section per Fig. 8. This drip leg functions as a trap for dirt and condensate.
5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft of heating section.
6. Install ground-joint union close to heating section between unit manual shutoff and external manual main shutoff valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (13.8 WC). Pressure test the gas supply piping system at pressures equal to or less than
0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.
7
Table 1 — Physical Data — Unit 48GS
UNIT SIZE 48GS
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows ...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (Hp)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)†
Throwaway
018040
1 1 ⁄
2
249
2.6
.034
1...17
6.1
3.5
.034
3.5
.034
3.65
.034
3.65
3.75
Acutrol™ Device
.034
.032
3.75
.032
5.7
.034
5.7
.034
2000
22
2400
22
2400
22
2400
22
2400
22
3000
22
3000
22
3000
22
3000
22
1 ⁄
8
(825) 1 ⁄
8
(825) 1 ⁄
8
(825) 1 ⁄
8
(825) 1 ⁄
8
(825) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100)
2...15
3.1
600
10 x 10
1 ⁄
4
2...45
2...50
20 x 20
024040
1
2
280
1...17
9.1
2...15
3.1
800
10 x 10
⁄
4
2...45
2...50
20 x 20
024060
1
2
280
1...17
9.1
2...15
3.1
800
10 x 10
⁄
4
2...38
2...46
20 x 20
030040
2
1
1 ⁄
⁄
4
2
280
1...17
9.1
2...15
3.1
1000
10 x 10
2...45
2...50
20 x 20
030060
2
1
1
⁄
4
⁄
2
280
2...15
3.1
1000
10 x 10
20 x 20
036060
Reciprocating
1
1...17
9.1
2...38
2...46
1
3
314
1...17
9.1
3...15
3.1
1200
11 x 10
⁄
2
2...38
2...46
20 x 24
036090
1
3
314
1...17
9.1
3...15
3.1
1200
11 x 10
⁄
2
3...38
3...46
20 x 24
042060
3 1 ⁄
2
355
1...17
9.1
4...15
3.1
1400
11 x 10
3 ⁄
4
2...38
2...46
20 x 24
042090
3 1 ⁄
2
355
1...17
9.1
4...15
3.1
1400
11 x 10
3 ⁄
4
3...38
3...46
20 x 24
UNIT SIZE 48GS
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (Hp)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)†
Throwaway
048090
415
6.0
.032
1...17
12.3
3...15
4.7
1600
3
4
⁄
4
3...38
3...46
24 x 30
048115
4
415
Scroll
1
6.0
.032
1...17
12.3
3...15
4.7
1600
11 x 10 11 x 10
3
⁄
4
3...33
3...42
24 x 30
048130 060090
4 5
415 450
6.0
Acutrol Device
.032
1...17
12.3
3...15
4.7
1600
11 x 10 11 x 10
3
⁄
4
3...31
3...41
24 x 30
8.0
.030
2...17
12.3
4...15
4.7
2000
1.0
3...38
3...46
24 x 30
060115
5
450
Reciprocating
1
8.0
.030
2...17
12.3
060130
5
450
2...17
12.3
3600
22
3600
22
3600
22
3600
22
3600
22
3600
22
1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100)
4...15
4.7
2000
11 x 10
1.0
3...33
3...42
24 x 30
8.0
.030
4...15
4.7
2000
11 x10
1.0
3...31
3...41
24 X 30
*Based on altitude of 0 to 2000 feet.
†Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
8
UNIT SIZE 48GX
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows ...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (Hp)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)†
Throwaway
1...17
9.1
2350
22
1 ⁄
8
(825)
3...15
3.1
800
10 x 10
1 ⁄
4
Table 2 — Physical Data — Unit 48GX
024040
2
290
024060
2
290
030040
2 1 ⁄
2
313
030060
2 1 ⁄
2
313
036060
3
321
Scroll
1
3.4
.034
3.4
.034
4.4
.030
4.4
.030
5.2
.032
1...17
9.1
2350
22
1 ⁄
8
(825)
3...15
3.1
800
10 x 10
1 ⁄
4
1...17
12.7
2350
22
1 ⁄
8
(825)
3...15
3.1
1000
10 x 10
1 ⁄
4
1...17
12.7
2350
22
1 ⁄
8
(825)
3...15
3.1
1000
10 x 10
1 ⁄
4
2...17
9.1
2350
22
1 ⁄
8
(825)
3...15
3.7
1200
11 x 10
1 ⁄
2
2...44
2...50
20 x 20
2...38
2...46
20 x 20
2...44
2...50
20 x 20
2...38
2...46
20 x 20
2...38
2...46
20 x 24
036090
3
321
042060
3 1 ⁄
2
382
042090
3 1 ⁄
2
382
5.2
.032
2...17
9.1
2350
22
1 ⁄
8
(825)
3...15
3.7
1200
11 x 10
1 ⁄
2
3...38
3...46
6.4
.034
2...17
12.3
3300
22
1 ⁄
4
(1100)
3...15
4.7
1400
11 x 10
3 ⁄
4
2...38
2...46
6.4
.034
2...17
12.3
3300
22
1 ⁄
4
(1100)
3...15
4.7
1400
11 x 10
3 ⁄
4
3...38
3...46
20 x 24 24 x 30 24 x 30
UNIT SIZE 48GX
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (Hp)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)†
Throwaway
048090
4
421
7.2
.034
2...17
12.3
048115
4
421
2...17
12.3
048130
4
421
7.2
060090
Scroll
1
5
468
8.1
Acutrol Device
.034
2...17
12.3
1600
11 x 10 11 x 10
3
⁄
4
.032
2...17
16.4
1750
1.0
060115
5
468
2...17
16.4
060130
5
468
2...17
16.4
3300
22
3300
22
3300
22
3300
22
3300
22
3300
22
1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100) 1 ⁄
4
(1100)
4...15
4.7
1600
11 x 10
3
⁄
4
3...38
3...46
24 x 30
7.2
.034
4...15
4.7
1600
11 x 10
3
⁄
4
3...33
3...42
24 x 30
4...15
4.7
3...31
3...41
24 x 30
4...15
4.7
3...38
3...46
24 x 30
8.1
.032
4...15
4.7
1750
11 x 10
1.0
3...33
3...42
24 x 30
8.1
.032
4...15
4.7
1750
11 x10
1.0
3...31
3...41
24 X 30
*Based on altitude of 0 to 2000 feet.
†Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of
300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
9
(Text continued from page 7)
Unstable operation may occur when the gas valve and manifold assembly are forced out of position while connecting improperly-routed rigid gas piping to the gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, the gas control piping.
If a flexible conductor is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and shall extend a minimum of 2 in. outside the unit casing.
Never use a match or other open flame when checking for gas leaks. Never purge gas line into combustion chamber. Failure to follow this warning could result in an explosion causing personal injury or death.
8. Check for gas leaks at the field-installed and factoryinstalled gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations).
Fig. 8 — Sediment Trap
Step 9 — Install Duct Connections —
The unit has duct flanges on the supply- and return-air openings on the side and bottom of the unit. For downshot applications the ductwork connects to the roof curb. See Fig. 2 and 3 for connection sizes and locations.
CONFIGURING UNITS FOR DOWNFLOW (VERTI-
CAL) DISCHARGE
Before performing service or maintenance operations on the system, turn off main power to unit or electrical shock could result.
1. Open all electrical disconnects before starting any service work.
2. Remove return duct cover located on duct panel by breaking connecting tabs with screwdriver and a hammer
(Fig. 9).
3. To remove supply duct cover, break front and right side connecting tabs with a screwdriver and a hammer. Push louver down to break rear and left side tabs (Fig. 10).
4. If unit ductwork is to be attached to vertical opening flanges on the unit basepan (jackstand applications only), do so at this time.
5. It is recommended that the basepan insulation around the perimeter of the vertical return-air opening be secured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass.
6. Cover both horizontal duct openings with the duct covers from the accessory duct cover kit. Ensure opening is airand watertight.
7. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and residence-type, NFPA 90B; and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped for horizontal duct installation.
2. Select and size ductwork, supply-air registers, and return-air grilles according to American Society of
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weathertight and airtight seal.
4. All units must have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Tables 1 and 2.
5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) and Air
Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
10
Table 3 — Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE,
SIZE
(in.)
1
3
1
1
⁄
2
⁄
4
1
1
1
⁄
⁄
4
2
INTERNAL
DIAMETER
(in.)
.622
.824
1.049
1.380
1.610
10
175
360
680
1400
2100
20
120
250
465
950
1460
30
97
200
375
770
1180
40
82
170
320
600
990
50
73
151
285
580
900
LENGTH OF PIPE, FT†
60
66
138
260
530
810
70
61
125
240
490
750
80
57
118
220
460
690
90
53
110
205
430
650
100
50
103
195
400
620
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.
†This length includes an ordinary number of fittings.
125
44
93
175
360
550
150
40
84
160
325
500
175
—
77
145
300
460
200
—
72
135
280
430
Step 10 — Install Electrical Connections
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground lug in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI/
NFPA (latest edition) (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1) and local electrical codes. Do not use gas piping as an elec-
trical ground. Failure to adhere to this warning could result in personal injury or death.
Fig. 9 — Supply and Return Duct Openings
Failure to follow these precautions could result in damage to the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes.
Refer to unit wiring diagram.
2. Use only copper conductor for connections between fieldsupplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
5. On 3-phase units, ensure phases are balanced within 2%.
Consult local power company for correction of improper voltage and/or phase imbalance (refer to Tables 4 and 5).
HIGH-VOLTAGE CONNECTIONS — The unit must have a separate electrical service with a field-supplied, waterproof, disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate for maximum fuse/ circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Tables 4 and 5 for electrical data.
The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See
Fig. 2 and 3 for acceptable location.
See unit wiring label and Fig. 11 for reference when making high voltage connections. Proceed as follows to complete the high-voltage connections to the unit.
Fig. 10 — Vertical Duct Cover Removed
11
Single phase units:
1. Run the high-voltage (L1, L2) and ground leads into the control box.
2. Connect ground lead to chassis ground connection.
3. Connect L1 to pressure lug connection 11 of the compressor contactor.
4. Connect L2 to pressure lug connection 23 of the compressor contactor.
Three phase units:
1. Run the high-voltage (L1, L2, L3) and ground leads into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side of the contactor.
4. Connect field L1 to black wire on connection 11 of the compressor contactor.
5. Connect field wire L2 to yellow wire on connection 13 of the compressor contactor.
6. Connect field wire L3 to Blue wire from compressor.
SPECIAL PROCEDURES FOR 208-V OPERATION
Make sure that the gas supply then the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death.
With disconnect switch open, move yellow wire from transformer ( 3 ⁄
16 in.) terminal marked 230 to terminal marked 200.
This retaps transformer to primary voltage of 208 vac.
UNIT
SIZE
48GS
018
024
030
036
042
048
060
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208-230/1/60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
187
187
414
187
187
414
197
187
414
187
187
414
VOLTAGE
RANGE
Min Max
187
187
187
187
253
253
253
253
253
506
253
253
506
253
253
506
253
253
506
253
COMPRESSOR
5.8
18.6
10.7
5.3
25.3
13.5
6.7
28.9
18.6
8.5
RLA
9.0
12.8
14.4
12.6
15.1
10.9
40.0
105.0
85.0
42.0
131.0
108.0
47.5
147.0
125.0
66.5
LRA
45.0
61.0
73.0
68.0
81.0
78.0
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Fuse or HACR Breaker.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation from average voltage average voltage
Table 4 — Electrical Data — Unit 48GS
OUTDOOR FAN
MOTOR
FLA
0.8
0.8
0.8
0.8
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
INDOOR FAN
MOTOR
FLA
1.8
2.0
2.0
2.0
3.6
3.6
1.9
3.8
3.8
2.0
3.8
3.8
2.0
6.2
6.2
3.2
POWER SUPPLY FUSE OR
HACR BRKR
MCA MOCP*
13.9
18.8
20.8
13.2
20
30
30
20
22.3
11.3
43.9
31.1
14.7
24.1
18.8
10.1
27.5
18.8
9.5
37.0
35
25
15
45
25
15
60
35
15
60
45
20
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452
1
464
1
455
3
=
1371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
12
UNIT
SIZE
48GX
024
030
036
042
048
060
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
187
414
187
187
414
187
187
414
VOLTAGE
RANGE
Min
187
Max
253
187
187
187
253
253
253
187
187
414
253
253
506
253
506
253
253
506
253
253
506
COMPRESSOR
RLA
10.3
13.5
9.0
16.7
11.2
5.4
17.9
12.4
6.1
19.5
12.4
5.8
28.8
17.3
9.0
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Fuse or HACR Breaker.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance.
% Voltage imbalance
= 100 x max voltage deviation from average voltage average voltage
LRA
56.0
73.0
63.0
97.0
75.0
37.5
104.0
88.0
44.0
104.0
88.0
44.0
169.0
123.0
62.0
Table 5 — Electrical Data — Unit 48GX
OUTDOOR FAN
MOTOR
FLA
0.8
0.8
0.8
0.8
0.9
1.6
1.6
0.9
0.8
0.9
1.6
1.6
1.6
1.6
0.9
INDOOR FAN
MOTOR
FLA
2.0
2.1
2.1
3.6
2.0
4.1
4.1
2.0
3.6
1.9
4.1
4.1
6.2
6.2
3.2
POWER SUPPLY FUSE OR
HACR BRKR
MCA
15.7
MOCP*
25
19.8
14.2
25.3
30
20
40
18.4
9.6
28.1
21.2
10.5
30.1
21.2
10.2
43.8
29.4
15.4
25
15
45
30
15
45
30
15
60
45
20
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452
1
464
1
455
3
=
1371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
13
PRE-START-UP
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
GND
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
WHT(W1)
YEL(Y)
GRN(G)
RED(R)
BRN(C)
W
Y
G
R
C
THERMOSTAT
(TYPICAL)
SPLICE BOX
LEGEND
Field Control-Voltage Wiring
Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.
Fig. 11 — High- and Control-Voltage Connections
CONTROL VOLTAGE CONNECTIONS
NOTE: Do not use any type of power-stealing thermostat.
Unit control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG colorcoded, insulated (35 C minimum) wires.
Standard Connection — Remove knockout hole located in the flue panel adjacent to the control access panel. See
Fig. 2 and 3. Remove the rubber grommet from the installer’s packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel.
Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box.
Locate five 18-gage wires leaving control box. These lowvoltage connection leads can be identified by the colors red, green, yellow, brown, and white. (See Fig. 11.) Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Stripped yellow wire is located in connection box. Route leads through hole in bottom of control box and make low-voltage connections as shown in Fig. 11. Secure all cut wires, so that they do not interfere with operation of unit.
HEAT ANTICIPATOR SETTING — The room thermostat heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an ammeter between the W and R terminals to determine the exact required setting.
NOTE: For thermostat selection purposes, use 0.18 amp for the approximate required setting.
Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.
TRANSFORMER PROTECTION — The transformer is of the energy-limiting type. It is set to withstand a 30-second overload or shorted secondary condition.
14
Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protective goggles and gloves when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminal cover until all electrical sources are disconnected.
4. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and gloves.
Proceed as follows: a. Shut off gas supply and then electrical power to unit.
b. Relieve and recover all refrigerant from system using both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.
Proceed as follows to inspect and prepare the unit for initial start-up:
1. Remove access panel.
2. Read and follow instructions on all WARNING, CAU-
TION, and INFORMATION labels attached to, or shipped with, unit.
3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak.
c. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, see Check for
Refrigerant Leaks section on page 15.
d. Inspect all field and factory-wiring connections. Be sure that connections are completed and tight.
e. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
Do not purge gas supply into the combustion chamber. Do not use a match or other open flame to check for gas leaks. Failure to follow this warning could result in an explosion causing personal injury or death.
a. Before lighting the unit for the first time, perform the following with the gas valve in the ‘‘OFF’’ position: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loosened, and the supply line be allowed to purge until the odor of gas is detected.
Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union.
Allow 5 minutes to elapse, then light unit.
b. Make sure that condenser-fan blade is correctly positioned in fan orifice. Leading edge of condenser-fan blade should be 1 ⁄
2 in. maximum from fan orifice.
c. Ensure fan hub is
1
⁄
8 in. max from motor housing (see
Fig. 12).
d. Make sure that air filter(s) is in place.
e. Make sure that condensate drain trap is filled with water to ensure proper drainage.
f. Make sure that all tools and miscellaneous loose parts have been removed.
MOTOR
FAN GRILLE
1/8" MAX BETWEEN
MOTOR AND FAN HUB
MOTOR SHAFT
Fig. 12 — Fan Blade Clearance
START-UP
Check for Refrigerant Leaks —
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pressure has been relieved and refrigerant recovered from both high- and low-pressure ports.
2. Repair leak following standard Refrigerant Service procedures.
NOTE: Install a filter drier whenever the system has been opened for repair.
3. Add a small charge of R-22 refrigerant vapor to system and leak-test unit.
4. Evacuate and recover refrigerant from refrigerant system if additional leaks are not found.
5. Charge unit with R-22 refrigerant, using a volumetriccharging cylinder or accurate scale. Refer to unit rating
plate for required charge. Be sure to add extra refrigerant to compensate for internal volume of filter drier.
Start Up Heating Section and Make
Adjustments
Complete the required procedures given in Pre-Start-Up section on page 14 before starting the unit.
Do not jumper any safety devices when operating the unit.
Make sure that burner orifices are properly aligned. Unstable operation may occur when the burner orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section operation label (located inside the burner or blower access door) to start the heating section.
NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks.
CHECK HEATING CONTROL — Start and check the unit for proper heating control operation as follows. (See furnace lighting instructions located inside burner or blower access panel.)
1. Place the room thermostat SYSTEM switch in the HEAT position and the fan switch in the AUTO. position.
2. Set the heating temperature control of the thermostat above room temperature.
3. The induced-draft motor will start.
4. After a call for heating, the main burner should light within 5 seconds. If the burners do not light, there is a
22-second delay before another 5-second try. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the
24-v power to W.
5. The evaporator fan will turn on 45 seconds after the flame has been established. The evaporator fan will turn off
45 seconds after the thermostat has been satisfied.
CHECK GAS INPUT — Check gas input and manifold pressure after unit start-up. (See Table 6.) If adjustment is required proceed as follows.
The rated gas inputs shown in Table 6 are for altitudes from sea level to 2000 ft above sea level. These inputs are based on natural gas with a heating value of
1050 Btu/ft
3 at 0.65 specific gravity, or propane gas with a heating value of 2500 Btu/ft
3 at 1.5 specific gravity.
For elevations above 2000 ft, reduce input 4% for each
1000 ft above sea level. When the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size.
These units are designed to consume the rated gas inputs using the fixed orifices at specified manifold pressures as shown in Table 6. DO NOT REDRILL THE
ORIFICES UNDER ANY CIRCUMSTANCES.
15
Table 6 — Heating Inputs
HEATING
INPUT
(Btuh)*
40,000
60,000
90,000
115,000
130,000
NUMBER
OF
ORIFICES
2
2
3
3
3
Min
4.0
4.0
4.0
4.0
4.0
GAS SUPPLY PRESSURE
(in. wg)
Natural Propane†
Max Min Max
13.0
13.0
13.0
13.0
13.0
4.0
4.0
4.0
4.0
4.0
13.0
13.0
13.0
13.0
13.0
* When a unit is converted to propane, different size orifices must be used. See separate naturalto-propane conversion kit instructions.
†Based on altitudes from sea level to 2000 ft above sea level. For altitudes above 2000 ft, reduce input rating 4% for each additional 1000 ft above sea level. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10%.
ADJUST GAS INPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure must be measured to determine the input of propane gas units.
Measure Gas Flow (Natural Gas Units) — Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner orifices following the recommendations of national and local codes.
NOTE: All other appliances that use the same meter must be turned off when gas flow is measured at the meter.
Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (see Fig. 13) then connect manometer at this point. Turn on gas to unit.
3. Record number of seconds for gas meter test dial to make one revolution.
4. Divide number of seconds in Step 3 into 3600 (number of seconds in one hour).
5. Multiply result of Step 4 by the number of cu ft shown for one revolution of test dial to obtain cu ft of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 6. (Consult the local gas supplier if the heating value of gas is not known.)
EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 32 seconds, and the heating value of the gas is 1050 Btu/ft
3
. Proceed as follows:
1. 32 seconds to complete one revolution.
2. 3600 ÷ 32 = 112.5.
3. 112.5 x 1 = 112.5 ft
3 of gas flow/hr.
4. 112.5 x 1050 = 118,125 Btuh input.
If the desired gas input is 115,000 Btuh, only a minor change in the manifold pressure is required.
Natural
3.5
3.5
3.5
3.5
3.5
MANIFOLD
PRESSURE
(in. wg)
Propane†
3.5
3.5
3.4
3.7
3.5
Fig. 13 — Burner Assembly
Observe manifold pressure and proceed as follows to adjust gas input:
1. Remove cover screw over regulator adjustment screw on gas valve.
2. Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counterclockwise to decrease input. Manifold pressure must be between 3.4 and 3.6 in. wg.
Unsafe operation of the unit may result if manifold pressure is outside this range. Personal injury or unit damage may result.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks.
16
Measure Manifold Pressure (Propane Units) — The main burner orifices on a propane gas unit are sized for the unit rated input when the manifold pressure reading matches the level specified in Table 6.
Proceed as follows to adjust gas input on a propane gas unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold (see Fig. 13), then connect manometer at this point.
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on gas valve.
5. Adjust regulator adjustment screw to the correct manifold pressure, as specified in Table 6. Turn adjusting screw clockwise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold pressure.
6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks.
CHECK BURNER FLAME — With burner access panel removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same for each burner.
Propane will have blue flame with yellow tips. See Fig. 14.
Refer to Maintenance section for information on burner removal.
Fig. 14 — Monoport Burners
AIRFLOW AND TEMPERATURE RISE — The heating section for each size unit is designed and approved for heating operation within the temperature-rise range stamped on the unit rating plate.
Table 7 shows the approved temperature-rise range for each heating input, and the air delivery cfm at various temperature rises. The heating operation airflow must produce a temperature rise that falls within the approved range.
Refer to Indoor Airflow and Airflow Adjustments section on page 22 to adjust heating airflow when required.
Table 7 — Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input
HEATING
INPUT
(Btuh)
40,000
60,000
90,000
115,000
130,000
20
1500
2250
—
—
—
25
1200
1800
—
—
—
30
1000
1500
2250
—
—
35
857
1286
1929
2464
2786
TEMPERATURE RISE °F
40
750
1125
1688
2156
2438
45
667
1000
1500
1917
2167
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
50
600
900
1350
1725
1950
55
545
818
1227
1568
1773
60
500
750
1125
1438
1625
65
—
692
1038
1327
1500
70
—
—
964
1232
—
17
HEATING SEQUENCE OF OPERATION — See Fig. 15-
17 and unit wiring label.
On a call for heating, terminal ‘‘W’’ of the thermostat is energized, starting the induced-draft motor. When the halleffect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC).
The evaporator-fan motor is energized 45 seconds after flame is established. When the thermostat is satisfied and ‘‘W’’ is deenergized, the burners stop firing and the evaporator-fan motor shuts off after a 45-second time-off delay.
An LED (light-emitting diode) indicator is provided on the control board to monitor operation. The control board is located by removing the burner access panel. During normal operation, the LED is continuously on. See Table 8 for error codes.
Table 8 — LED Indications
ERROR CODE
Normal Operation
Hardware Failure
Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
Four Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
LED INDICATION
On
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will be displayed in numerical sequence.
3. This chart is on the wiring diagram located inside the burner access panel.
LIMIT SWITCHES — Normally closed limit switch (LS) completes the control circuit through the thermostat R circuit. Should the leaving-air temperature rise above the maximum allowable temperature, the limit switch opens and the R control circuit ‘‘breaks.’’Any interruption in the R control circuit instantly closes the gas valve and stops gas flow to the burners and pilot. The blower motor continues to run until LS resets.
When the air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and completes the R control circuit. The electricspark ignition system cycles and the unit returns to normal heating operation. When this fault occurs the IGC LED will display FAULT CODE 2.
AUXILIARY LIMIT SWITCH (ROLLOUT) — The function of the switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the auxiliary switch reaches the maximum allowable temperature, the R control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor continue to run until switch is reset. The IGC
LED will display FAULT CODE 7.
Start Up Cooling Section and Make
Adjustments
Complete the required procedures given in the Pre-
Start-Up section on page 14 before starting the unit.
Do not jumper any safety devices when operating the unit.
Do not operate the compressor when the outdoor temperature is below 40 F (unless accessory low-ambient kit is installed).
Do not rapid-cycle the compressor. Allow 5 minutes between ‘‘on’’ cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION — Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO. position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO. position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 30 seconds.
3. When using an auto.-changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions.
Observe that unit operates in Heating mode when temperature control is set to ‘‘call for heating’’ (above room temperature) and operates in Cooling mode when temperature control is set to ‘‘call for cooling’’ (below room temperature).
IMPORTANT: Three-phase, scroll compressor units
(48GS048 and 48GX030-060) are direction-oriented.
These units must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressors emit elevated noise levels, and the difference between compressor suction and discharge pressures may be dramatically lower than normal.
(Text continued on page 22.)
18
LEGEND
AHA
BR
C
CAP
—
Adjustable Heat Anticipator
—
Blower Relay
—
Contactor
—
Capacitor
COMP —
Compressor Motor
CR —
Combustion Relay
EQUIP —
Equipment
FS —
Flame Sensor
FU
GND
GVR
HS
HV
TRAN
I
IDM
—
Fuse
—
Ground
—
Gas Valve Relay
—
Hall Effect Sensor
—
High Voltage Transformer
IFM
IGC
LS
MGV
NEC
OFM
—
Ignitor
—
Induced-Draft Motor
—
Indoor-Fan Motor
—
Integrated Gas Unit Controller
—
Limit Switch
—
Main Gas Valve
—
National Electrical Code
—
Outdoor-Fan Motor
QT
RS
—
—
Quadruple Terminal
Rollout Switch
ST —
Thermistor Sensor
TRAN —
Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not to Represent Wiring
NOTES:
1. If any of the original wires furnished are replaced, it must be replaced with type
90 degree C wire or its equivalent.
2. See price pages for thermostat and subbases.
3. Use 75 degree C copper conductors for field installation.
4. For high speed IFM, disconnect RED wire from IGC terminal BM and connect
BLK wire from IFM. For medium speed, disconnect RED wire from IGC terminal
BM and connect BLU wire from IFM.
5. Models 48GS018-042 and 48GX024-036 have LS1 and LS2 wired in series.
Models 48GS048,060 and 48GX042-060 have LS1 only.
Fig. 15 — 208/230-1-60 Wiring Diagram, Unit 48GS and 48GX
LEGEND
AHA
BR
C
CAP
— Adjustable Heat Anticipator
— Blower Relay
— Contactor
— Capacitor
COMP
— Compressor Motor
CR
— Combustion Relay
IDM
IFC
IFM
IGC
L1
LS
LS1
MGV
I
CS
— Centrifugal Switch
EQUIP — Equipment
FS
FU
GND
GV
GVR
HS
HV
— Fusible Link
— Fuse
— Ground
— Gas Valve
— Gas Valve Relay
— Hall Effect Sensor
— High Voltage
— Ignitor
— Induced-Draft Motor
— Indoor-Fan Contactor
— Indoor-Fan Motor
— Integrated Gas Unit Controller
— Line
— Limit Switch
— Limit Switch
— Main Gas Valve
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
QT
RS
— Quadruple Terminal
— Rollout Switch
SEN
— Sensor
SW
— Switch
TRAN — Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not to Represent Wiring
NOTES:
1. If any of the original wires furnished are replaced, they must be replaced with type 90 degree C wire or its equivalent.
2. See price pages for thermostat and subbases.
3. Use 75 degree C copper conductors for field installation.
4. For high speed IFM, disconnect RED wire from IGC terminal BM and connect BLK wire from IFM. For medium speed, disconnect RED wire from IGC terminal BM and connect BLU wire from IFM.
Fig. 16 — 208/230-3-60 Wiring Diagram, Unit 48GS and 48GX
20
AHA
BR
C
CAP
— Adjustable Heat Anticipator
— Blower Relay
— Contactor
— Capacitor
COMP
— Compressor Motor
CR
— Combustion Relay
I
CS
— Centrifugal Switch
EQUIP — Equipment
FS
FU
GND
GV
GVR
HS
HV
— Fusible Link
— Fuse
— Ground
— Gas Valve
— Gas Valve Relay
— Hall Effect Sensor
— High Voltage
— Ignitor
IDM
IFC
IFM
IGC
— Induced-Draft Motor
— Indoor-Fan Contactor
— Indoor-Fan Motor
— Integrated Gas Unit Controller
L1
LS
— Line
— Limit Switch
LS1
— Limit Switch
MGV
— Main Gas Valve
LEGEND
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
QT
RS
SW
— Quadruple Terminal
— Rollout Switch
SEN
— Sensor
— Switch
TRAN — Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not to Represent Wiring
NOTES:
1. If any of the original wires furnished are replaced, they must be replaced with type 90 degree C wire or its equivalent.
2. See price pages for thermostat and subbases.
3. Use 75 degree C copper conductors for field installation.
4. For high speed IFM, disconnect RED wire from IGC terminal BM and connect BLK wire from IFM. For medium speed, disconnect RED wire from IGC terminal BM and connect BLU wire from IFM.
Fig. 17 — 460-3-60 Wiring Diagram, Unit 48GS and 48GX
21
CHECKING AND ADJUSTING REFRIGERANT CHARGE
— The refrigerant system is fully charged with R-22 refrigerant, tested, and factory-sealed.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the service access panel. The chart includes the required suction line temperature at given suction line pressures and outdoor ambient temperatures.
An accurate superheat, thermocouple- or thermistor-type thermometer, and a gage manifold are required when using the superheat charging method for evaluating the unit charge.
Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.
When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
Proceed as follows:
1. Remove caps from low and high pressure 1 ⁄
4 in. Schrader service fittings.
2. Using hoses with valve core depressors, attach low and high pressure gage hoses to low and high pressure service fittings, respectively.
3. Start unit in Cooling mode and let unit run until system pressures stabilize.
4. Measure and record the following: a. Outdoor ambient-air temperature (F db).
b. Suction-tube temperature (F) at low-side service fitting.
c. Suction (low-side) pressure (psig).
5. Using ‘‘Cooling Charging Charts’’ compare outdoor-air temperature (F db) with the suction line pressure (psig) to determine desired system operating suction line temperature. See Fig. 18-30.
6. Compare actual suction-tube temperature with desired suction-tube temperature. Using a tolerance of ± 3° F, add refrigerant if actual temperature is more than 3° F higher than proper suction-tube temperature, or remove refrigerant if actual temperature is more than 3° F lower than required suction-tube temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section on page 15.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
For cooling operation, the recommended airflow is
350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
Table 7 shows the temperature rise at various airflow rates.
Tables 9 and 10 shows both heating and cooling airflows at various external static pressures. Refer to these tables to determine the airflow for the system being installed. See
Tables 11A and 11B for wet coil pressure drop.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.
Shut off gas supply then disconnect electrical power to the unit before changing blower speed. Electrical shock can cause personal injury or death.
Airflow can be changed by changing the lead connections of the blower motor.
Unit 48GS two- or three-speed motors (except size 030) are factory wired for low speed operation. Unit 48GS030 is factory wired for medium speed.
All 48GX units are factory wired for low speed and may need to be wired for medium or high speed in the field.
For 208/230-v Motors — The motor leads are color-coded as follows:
3-SPEED black = high speed blue = medium speed red = low speed
2-SPEED black = high speed red = low speed
To change the speed of the blower motor (BM), remove the fan motor speed leg lead from the blower relay (BR).
This wire is attached to IGC terminal BM for single-phase and 3-phase units. To change the speed, remove and replace with lead for desired blower motor speed. Insulate the re-
moved lead to avoid contact with chassis parts.
For 460-v GE Motors — The motor leads are color coded as follows:
3-SPEED black = high violet = jumper orange = medium red = low
To change the speed of the blower motor (BM), remove fan motor speed lead from the blower relay (BR) and replace with the lead for the desired blower motor speed. The motor speed lead is attached to terminal BM. For low and medium speeds black must be connected to the jumper wire.
Insulate removed lead end to avoid contact with chassis parts.
To select high speed on 460-v GE motors, separate the black female quick connect (QC) from the jumper lead male quick connect (QC) and connect the black lead to the BR. Insulate
the jumper to avoid contact with any chassis parts.
22
Fig. 18 — Cooling Charging Chart,
48GS018 Units
Fig. 20 — Cooling Charging Chart,
48GS030 Units
Fig. 19 — Cooling Charging Chart,
48GS024 Units
Fig. 21 — Cooling Charging Chart,
48GS036 Units
23
Fig. 22 — Cooling Charging Chart,
48GS042 Units
Fig. 23 — Cooling Charging Chart,
48GS048 Units
Fig. 24 — Cooling Charging Chart,
48GS060 Units
24
Fig. 25 — Cooling Charging Chart,
48GX024 Units
Fig. 27 — Cooling Charging Chart,
48GX036 Units
Fig. 26 — Cooling Charging Chart,
48GX030 Units
Fig. 28 — Cooling Charging Chart,
48GX042 Units
25
Fig. 29 — Cooling Charging Chart,
48GX048 Units
Fig. 30 — Cooling Charging Chart,
48GX060 Units
26
Table 9 — Dry Coil Air Delivery* — Horizontal and Downflow Discharge —
Unit 48GS018-060 (Deduct 10% for 208 Volts)
230 AND 460 VOLT
Unit
48GS
Motor
Speed
018
024
030
036
042
048
060
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
576
1430
680
1720
810
1800
—
—
—
—
—
—
—
1475
280
950
380
1220
485
1475
0.00
227
1082
—
—
287
1270
280
950
380
1220
485
—
—
—
—
—
1033
2105
1084
2318
—
—
0.1
212
1016
—
—
275
1179
275
880
375
1150
475
1440
275
880
375
1150
475
1440
566
1403
671
1630
800
1745
675
1454
886
1515
—
—
727
1678
853
1914
979
2150
949
2057
1054
2248
—
—
0.2
196
929
—
—
266
1054
270
825
365
1090
470
1350
270
825
365
1090
470
1350
556
1365
660
1538
790
1660
660
1387
855
1458
—
—
712
1639
836
1870
959
2100
864
2009
1024
2179
1184
2349
*Air delivery values are without air filter and are for dry coil. (See Table 11A — Wet Coil Pressure Drop table.)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
1600
821
1825
943
2050
836
1943
994
2110
1152
2278
—
253
932
267
750
360
1025
460
0.3
177
796
—
External Static Pressure (in. wg)
0.4
0.5
0.6
165
668
—
153
428
—
—
—
—
—
242
780
264
670
355
970
455
—
234
633
262
580
350
860
445
—
226
372
260
400
344
760
437
512
1157
604
1346
766
1547
640
1275
1200
264
670
355
970
455
1200
795
1350
950
1488
688
538
1263
624
1439
782
1600
650
1326
1275
267
750
360
1025
460
1275
825
1406
1000
1551
700
1125
262
580
350
860
445
1125
497
1068
620
1267
742
1465
630
1204
778
1285
925
1424
666
481
973
602
1167
723
1360
620
1142
1025
260
400
344
760
437
1025
765
1224
910
1360
644
466
900
558
1126
709
1270
610
1081
750
1163
890
1296
622
925
—
—
335
620
430
925
0.7
—
—
—
—
—
—
—
—
335
620
430
1561
807
1780
927
2000
822
1909
971
2058
1120
2207
1500
782
1711
897
1922
808
1876
955
2000
1102
2124
1440
756
1642
868
1845
772
1823
928
1932
1084
2041
1379
730
1573
838
1767
737
1770
897
1885
1056
2000
450
827
534
1018
688
1163
595
995
735
1091
875
1233
595
750
—
—
312
450
415
750
0.8
—
—
—
—
—
—
—
—
312
450
415
1289
699
1470
802
1600
705
1698
867
1829
1029
1960
718
1013
855
1148
569
435
704
512
858
661
967
580
918
400
—
—
—
—
385
400
0.9
—
—
—
—
—
—
—
—
—
—
385
1198
667
1367
766
1535
674
1627
835
1740
997
1853
700
932
833
1071
—
—
—
496
781
627
876
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.0
—
—
—
—
640
1270
730
1419
642
1531
803
1638
965
1745
27
Table 10 — Dry Coil Air Delivery* — Horizontal and Downflow Discharge —
Unit 48GX024-060 (Deduct 10% for 208 Volts)
230 AND 460 VOLT
Unit
48GX
Motor
Speed
024
030
036
042
048
060
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Low
Med
High
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
Cfm
Watts
643
1626
—
—
—
—
614
1591
—
—
—
—
—
—
—
778
1854
—
—
834
2016
941
2379
—
—
0.00
281
899
—
—
—
—
246
982
343
1233
—
0.1
282
828
—
—
—
—
244
860
339
1170
—
—
470
1463
—
—
—
—
625
1614
—
—
—
—
588
1549
756
1837
—
—
813
1955
889
2233
—
—
0.2
281
757
—
—
—
—
243
808
336
1109
—
—
458
1406
514
1497
—
—
614
1579
—
—
—
—
577
1518
738
1804
—
—
782
1898
851
2124
960
2497
605
1532
—
—
—
—
572
1490
—
445
1344
501
1428
646
1491
969
—
—
241
736
332
1038
—
719
1759
—
—
746
1840
822
2038
949
2224
0.3
278
691
375
External Static Pressure (in. wg)
0.4
0.5
0.6
276
619
370
—
—
363
—
—
357
897
—
—
—
—
328
953
441
1202
430
1273
487
1348
636
1412
593
1478
726
1731
—
—
566
1460
699
1705
896
1956
712
1781
797
1964
920
2075
824
468
994
—
—
322
855
432
1111
415
1188
471
1255
626
1325
574
1421
695
1672
—
—
556
1421
676
1643
862
1879
680
1717
772
1892
883
1986
744
457
913
—
—
317
754
421
549
1361
661
1610
—
—
539
1372
1021
399
1091
455
1152
614
1228
650
1577
829
1797
652
1646
745
1814
845
1915
*Air delivery values are without air filter and are for dry coil. (See Table 11B — Wet Coil Pressure Drop table.)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
0.7
—
—
352
649
444
826
—
—
—
—
410
623
1508
800
1709
626
1566
714
1727
812
1831
518
1295
625
1541
790
1699
517
1312
929
384
983
438
1042
602
1120
485
1218
591
1456
766
1602
491
1242
826
—
—
422
929
589
1003
596
1440
775
1615
—
—
679
1626
783
1721
0.8
—
—
—
—
431
730
—
—
—
—
400
454
1120
561
1345
742
1494
—
—
—
—
—
—
—
—
—
572
1375
752
1514
—
—
639
1511
753
1588
0.9
—
—
—
—
—
—
—
—
423
620
—
—
—
540
1193
713
1367
—
—
—
—
—
—
—
—
—
555
1315
728
1406
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.0
—
—
—
28
Table 11A — 48GS Wet Coil Pressure Drop
UNIT SIZE
48GS
018
024
030
036
042
048
060
AIRFLOW
(cfm)
500
600
700
700
800
900
900
1000
1100
1100
1200
1300
1300
1400
1500
1500
1600
1700
1900
2000
2100
PRESSURE DROP
(in. wg)
0.049
0.070
0.095
0.077
0.100
0.127
0.065
0.080
0.097
0.084
0.100
0.177
0.103
0.120
0.138
0.088
0.100
0.113
0.108
0.120
0.132
Table 11B — 48GX Wet Coil Pressure Drop
UNIT SIZE
48GX
024
030
036
042
048
060
1300
1300
1400
1500
1500
1600
1700
1900
2000
2100
AIRFLOW
(cfm)
700
800
900
900
1000
1100
1100
1200
PRESSURE DROP
(in. wg)
0.0535
0.067
0.123
0.0687
0.083
0.150
0.084
0.100
0.177
0.099
0.177
0.204
0.199
0.137
0.156
0.108
0.120
0.132
COOLING SEQUENCE OF OPERATION — With the room thermostat SYSTEM switch in the COOL position and the
FAN switch in the AUTO. position, the cooling sequence of operation is as follows:
When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and blower relay coil (BR) (through unit wire G) across the
24-v secondary of transformer (TRAN).
The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally open contacts of energized relay BR close and complete the circuit through evaporator blower (indoor) fan motor (IFM).
29
NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.
The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat
‘‘breaks’’ the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and relay coil BR. The condenser and compressor motors stop. After a 30-second delay, the blower motor stops.
The unit is in a ‘‘standby’’ condition, waiting for the next
‘‘call for cooling’’ from the room thermostat.
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This combination heating/cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot heating or cooling of units, refer to tables at the back of the book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO HEED THIS WARN-
ING COULD RESULT IN SERIOUS PERSONAL
INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.
Failure to follow these warnings could result in serious personal injury:
1. Turn off gas supply, then turn off electrical power to the unit before performing any maintenance or service on the unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in contact with, the unit.
4. Should overheating occur, or the gas supply fail to shut off, shut off the external main manual gas valve to the unit, then shut off the electrical supply.
Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnection when servicing.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary. Certain geographical locations may require more frequent inspections.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean when necessary. For first heating and cooling season, inspect blower wheel bimonthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.
5. Check and inspect heating section before each heating season. Clean and adjust when necessary.
6. Check flue hood and remove any obstructions if necessary.
Air Filter
Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed.
See Tables 1 and 2 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during each heating and cooling season or whenever the filter(s) becomes clogged with dust and lint.
Evaporator Blower and Motor
NOTE: All motors are prelubricated. Do not attempt to lubricate these motors.
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
Turn off the gas supply, then disconnect and tag electrical power to the unit before cleaning the blower motor and wheel. Failure to adhere to this warning could cause personal injury or death.
To clean the blower motor and wheel:
1. Remove and disassemble blower assembly as follows: a. Remove unit access panel.
b. Disconnect motor lead from blower relay (BR).
Disconnect yellow lead from terminal L2 of the contactor.
c. On all units remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.
d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft, remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft.
f. Reinstall unit access panel.
3. Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.
Flue Gas Passageways —
To inspect the flue collector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section below.
2. Remove the 3 screws holding the blower housing to the flue collector box cover (see Fig. 31).
3. Remove the 12 screws holding the flue collector box cover
(Fig. 31) to the heat exchanger assembly. Inspect the heat exchangers.
4. Clean all surfaces as required using the wire brush.
Fig. 31 — Blower Housing and Flue
Collector Box
Combustion-Air Blower —
Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows:
1. Remove unit access panel. (See Fig. 32.)
2. Remove the 7 screws that attach induced-draft motor mounting plate to blower housing. (See Fig. 31.)
3. Slide the motor and blower wheel assembly out of the blower housing. (See Fig. 33.) Clean the blower wheel.
If additional cleaning is required, continue with Steps 4 and 5.
4. To remove blower, remove 2 setscrews. (See Fig. 33.)
5. To remove motor and cooling fan assembly, remove
4 screws that hold blower housing to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Limit Switch —
Remove unit access panel. Limit switch is located on the blower partition.
30
Fig. 32 — Unit Access Panel
BLOWER
HOUSING
When servicing gas train, do not hit or plug orifice spuds.
REMOVAL OF GAS TRAIN
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Remove unit access panel. (See Fig. 32.)
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack to the basepan. (See Fig. 31.)
8. Slide the burner rack out of the unit. (See Fig. 31 and 34.)
9. To reinstall, reverse the procedure outlined above.
2 SETSCREWS
(HIDDEN)
Fig. 33 — Removal of Motor and Blower Wheel
Burner Ignition —
Unit is equipped with a direct spark ignition 100% lockout system. Ignition module is located in the control box. Module contains a self-diagnostic
LED. During servicing, refer to label diagram for LED interpretation.
If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit, or turning selector switch to OFF position at the thermostat.
Main Burners —
At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust if necessary.
Fig. 34 — Burner Rack Removed
Condenser Coil, Evaporator Coil, and Condensate Drain Pan —
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
31
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-andwater solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils.
Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘‘plumbers snake’’ or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
Condenser Fan
Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.
1. Remove 6 screws holding condenser grille and motor to top cover.
2. Turn motor/grille assembly upside down on top cover to expose the fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.
5. When replacing fan blade, position blade so that the hub is
1
⁄
8 in. away from the motor end (
1
⁄
8 in. of motor shaft will be visible). See Fig. 12.
6. Ensure that setscrew engages the flat area on the motor shaft when tightening.
7. Replace grille.
Electrical Controls and Wiring —
Inspect and check the electrical controls and wiring annually. Be sure to turn
off the gas supply, and then the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace the access panel. Start the unit, and observe at least one complete heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation in this publication as an aid in determining proper control operation.
Refrigerant Circuit —
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually.
Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leakdetector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section on page 15.
If no refrigerant leaks are found and low cooling performance is suspected, refer to Checking and Adjusting Refrigerant Charge section on page 22.
Gas Input —
The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to Start-Up section on page 15.
Evaporator Airflow —
The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from
obstructions, and that the air filter is clean. When necessary, refer to Indoor Airflow and Airflow Adjustments section on page 22 to check the system airflow.
Metering Device — Acutrol™ Device —
This metering device is a fixed orifice and is located in the header to the evaporator coil.
Liquid Line Strainer —
The liquid line strainer (to protect metering device) is made of wire mesh and located in the liquid line on the inlet side of the metering device.
32
SYMPTOM
Compressor and condenser fan will not start.
Compressor will not start but condenser fan runs.
TROUBLESHOOTING
Cooling
CAUSE
Power failure
Fuse blown or circuit breaker tripped
Defective thermostat, contactor, transformer, or control relay
Insufficient line voltage
Incorrect or faulty wiring
Thermostat setting too high
Faulty wiring or loose connections in compressor circuit
Compressor motor burned out, seized, or internal overload open
Defective run/start capacitor, overload, start relay
One leg of 3-phase power dead
Scroll compressor is rotating in the wrong direction
REMEDY
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker.
Determine cause.
Correct the direction of rotation by reversing the
3-phase power leads to the unit. Shut down unit to allow pressures to equalize.
Three-phase scroll compressor (48GS048 and 48GX030-060 only) makes excessive noise, and there may be a low pressure differential.
Compressor cycles
(other than normally satisfying thermostat).
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure.
Suction pressure too low.
Refrigerant overcharge or undercharge
Defective compressor
Insufficient line voltage
Blocked condenser
Defective run/start capacitor, overload or start relay
Defective thermostat
Faulty condenser-fan motor or capacitor
Restriction in refrigerant system
Dirty air filter
Unit undersized for load
Thermostat set too low
Low refrigerant charge
Leaking valves in compressor
Air in system
Condenser coil dirty or restricted
Dirty air filter
Dirty condenser coil
Refrigerant overcharged
Air in system
Condenser air restricted or air short-cycling
Low refrigerant charge
Compressor valves leaking
Restriction in liquid tube
High heat load
Compressor valves leaking
Refrigerant overcharged
Dirty air filter
Low refrigerant charge
Metering device or low side restricted
Insufficient evaporator airflow
Temperature too low in conditioned area
Outdoor ambient below 40 F
Field-installed filter-drier restricted
Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace filter.
Clean coil.
Recover excess refrigerant.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks, repair and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Recover excess refrigerant.
Replace filter.
Check for leaks, repair and recharge.
Remove source of restriction.
Increase air quantity. Check filter — replace if necessary.
Reset thermostat.
Install low-ambient kit.
Replace.
33
SYMPTOM
Burners will not ignite.
Inadequate heating.
Poor flame characteristics.
CAUSE
Water in gas line
No power to furnace
No 24-v power supply to control circuit
Heating
Miswired or loose connections
Burned-out heat anticipator in thermostat
Broken thermostat wire
Misaligned spark electrodes
No gas at main burners
Dirty air filter
Gas input to furnace too low
Unit undersized for application
Restricted airflow
Blower speed too low
Limit switch cycles main burners
Incomplete combustion results in:
Aldehyde odors, carbon monoxide, sooting flame, floating flame
REMEDY
Drain. Install drip leg.
Check power supply fuses, wiring, or circuit breaker.
Check transformer.
NOTE: Some transformers have internal overcurrent protection that requires a cool-down period to reset.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wire if necessary.
Check flame ignition and sense electrode positioning.
Adjust as necessary.
1. Check gas line for air. Purge as necessary.
NOTE: After purging gas line of air, wait at least
5 minutes for any gas to dissipate before attempting to light unit.
2. Check gas valve.
Clean or replace filter as necessary.
Check gas pressure at manifold. Match with that on unit nameplate.
Replace with proper unit or add additional unit.
Clean or replace filter. Remove any restriction.
Use faster speed tap if available, or install alternate motor.
Check rotation of blower, thermostat heat anticipator settings, temperature rise of unit. Adjust as necessary.
1. Tighten all screws around burner compartment.
2. Cracked heat exchanger. Replace.
3. Unit overfired. Reduce input (change orifices or adjust gas line or manifold pressure).
4. Check burner alignment.
SYMPTOM
Hardware failure.
(LED OFF)
Fan ON/OFF delay modified (LED/
FLASH)
Limit switch fault.
(LED 2 flashes)
Flame sense fault.
(LED 3 flashes)
4 consecutive limit switch faults.
(LED 4 flashes)
Ignition lockout.
(LED 5 flashes)
Induced-draft motor fault.
(LED 6 flashes)
Rollout switch fault.
(LED 7 flashes)
Internal control fault.
(LED 8 flashes)
LED Troubleshooting — Error Code
CAUSE
Loss of power to control module (IGC).
REMEDY
Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
High limit switch opens during heat exchanger warm-up period before fan-on delay expires.
Limit switch opens within three minutes after blower-off delay timing in Heating mode.
High temperature limit switch is open.
The IGC sensed flame that should not be present.
Inadequate airflow to unit.
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft motor is operating.
Rollout switch has opened.
Microprocessor has sensed an error in the software or hardware.
Ensure unit’s external static pressure is within application guidelines.
Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
Check operation of indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1
— White, PIN 2 — Red, PIN 3 — Black.
Rollout switch will automatically reset, but IGC will continue to lockout unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
If error code is not cleared by resetting unit power, replace the IGC.
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.
IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshooting analysis.
LEGEND
IGC
— Integrated Gas Unit Controller
LED — Light-Emitting Diode
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1a 6a
PC 111 Catalog No. 534-732 Printed in U.S.A.
Form 48GS,GX-1SI Pg 34 1-99 Replaces: 48GS-1SI
I. PRELIMINARY INFORMATION
MODEL NO.:
DATE:
START-UP CHECKLIST
(Remove and Store in Job File)
SERIAL NO.:
TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
M CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
M CHECK GAS PIPING FOR LEAKS
M CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
M VERIFY THAT UNIT INSTALLATION IS LEVEL
M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2
COMPRESSOR AMPS L1
COMPRESSOR AMPS L1
INDOOR (EVAPORATOR) FAN AMPS
L2-L3
L2
L2
L3-L1
L3
L3
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
GAS HEAT SUPPLY AIR
DB
DB
DB
WB
WB
PRESSURES
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
IN. WG
IN. WG
PSIG
PSIG
SUCTION LINE TEMP*
DISCHARGE TEMP†
M VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
M VERIFY THAT 3-PHASE SCROLL COMPRESSOR (48GS048 AND 48GX030-060) IS ROTATING IN
CORRECT DIRECTION
*Measured at suction inlet to compressor.
†Measured at liquid line leaving condenser.
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1a 6a
PC 111 Catalog No. 534-732 Printed in U.S.A.
Form 48GS,GX-1SI Pg CL-1 1-99 Replaces: 48GS-1SI
Advertisement
Key features
- Self-contained
- Outdoor installation
- Rooftop, slab, or ground mount
- Category I gas heating
- Electric cooling
- Horizontal and downflow configurations
- Factory-shipped with downflow duct openings covered
- Multiple unit sizes
- Gas and electric connection
- Condensate drain