AC500 V2.1 ACSM1 Profibus DP
www.infoPLC.net
Application Example
AC500
Scalable PLC
for Individual Automation
Connect AC500 V2.1 to
ACSM1 with Profibus DP using
Drive Manager
Connect
AC500 V2.1
To
ACSM1
With
Profibus DP
www.infoPLC.net
Content
1
Disclaimer ..................................................................................................................3
1.1 For customers domiciled outside Germany/
Für Kunden mit Sitz außerhalb Deutschlands........................................................................ 3
1.2
2
Nur für Kunden mit Sitz in Deutschland ........................................................................ 3
Used equipment for example ...................................................................................4
2.1
Hardware overview.......................................................................................................... 4
2.2
AC500............................................................................................................................... 4
2.3
ACSM1 ............................................................................................................................. 4
2.4
Cables .............................................................................................................................. 4
2.5
Used documents: ............................................................................................................ 4
3
Configuration of ACSM1 ...........................................................................................6
4
Configuration of AC500 ............................................................................................8
4.1
Set IP-Address of PLC .................................................................................................... 8
4.2
Create new AC500 project .............................................................................................. 8
4.2.1
4.3
Add coupler CM572-DP into project......................................................................... 9
Add the ACSM1 drive to the project............................................................................. 10
4.3.1
Option 1: Add FPBA-01 ......................................................................................... 10
4.3.2
Option 2: Add ACSM1............................................................................................ 11
4.4
Configure PROFINET slave........................................................................................... 12
4.5
Start PLC with new configuration data ........................................................................ 13
CoDeSys ............................................................................................................................. 13
5
Drive Manager in Control Builder Plus v2.1 ..........................................................15
5.1
Connect to PLC with Control Builder Plus .................................................................. 15
5.2
Start Drive Manager ...................................................................................................... 16
5.3
Edit drive parameters.................................................................................................... 17
5.4
Drive parameters of the project.................................................................................... 17
5.5
Compare parameters between drive and project ........................................................ 18
Application Example
-1-
AC500/Issue: 11.2011
5.6
www.infoPLC.net
Drive Manager options.................................................................................................. 18
Drive Analog Input Settings..................................................................................................19
Drive Parameter Comparison Settings.................................................................................19
Refresh Parameters ..............................................................................................................19
Application Example
-2-
AC500/Issue: 11.2011
1 Disclaimer
www.infoPLC.net
1.1 For customers domiciled outside Germany/
Für Kunden mit Sitz außerhalb Deutschlands
"Warranty, Liability:
The user shall be solely responsible for the use of this application example described within this file.
ABB shall be under no warranty whatsoever. ABB's liability in connection with this application example or the
files included within this file, irrespective of the legal ground, shall be excluded. The exclusion of liability shall
not apply in the case of intention or gross negligence. The present declaration shall be governed by and
construed in accordance with the laws of Switzerland under exclusion of its conflict of laws rules and of the
Vienna Convention on the International Sale of Goods (CISG)."
"Gewährleistung und Haftung:
Der Nutzer ist allein für die Verwendung des in dieser Datei beschriebenen Anwendungsbeispiels
verantwortlich.
ABB unterliegt keiner Gewährleistung. Die Haftung von ABB im Zusammenhang mit diesem
Anwendungsbeispiel oder den in dieser Datei enthaltenen Dateien - gleich aus welchem Rechtsgrund - ist
ausgeschlossen. Dieser Ausschluß gilt nicht im Falle von Vorsatz oder grober Fahrlässigkeit. Diese
Erklärung unterliegt Schweizer Recht unter Ausschluß der Verweisungsnormen und des UN-Kaufrechts
(CISG)."
1.2 Nur für Kunden mit Sitz in Deutschland
"Gewährleistung und Haftung:
Die in diesem Anwendungsbeispiel enthaltenen Dateien beschreiben eine mögliche Anwendung der
Steuerung AC500 bzw. zeigen eine mögliche Einsatzart der Steuerung. Sie stellen nur Beispiele für
Programmierungen dar, sind aber keine fertigen Lösungen. Eine Gewähr kann nicht übernommen werden.
Der Nutzer ist für die ordnungsgemäße, insbesondere vollständige und fehlerfreie Programmierung der
Steuerungen selbst verantwortlich. Im Falle der teilweisen oder ganzen Übernahme der
Programmierbeispiele können gegen ABB keine Ansprüche geltend gemacht werden.
Die Haftung von ABB, gleich aus welchem Rechtsgrund, im Zusammenhang mit den Anwendungsbeispielen
oder den in dieser Datei enthaltenen Dateien wird ausgeschlossen. Der Haftungsausschluß gilt jedoch nicht
in Fällen des Vorsatzes, der groben Fahrlässigkeit, bei Ansprüchen nach dem Produkthaftungsgesetz, im
Falle der Verletzung des Lebens, des Körpers oder der Gesundheit oder bei schuldhafter Verletzung einer
wesentlichen Vertragspflicht. Im Falle der Verletzung einer wesentlichen Vertragspflicht ist die Haftung
jedoch auf den vertragstypischen, vorhersehbaren Schaden begrenzt, soweit nicht zugleich ein anderer der
in Satz 2 dieses Unterabsatzes erwähnten Fälle gegeben ist. Eine Änderung der Beweislast zum Nachteil
des Nutzers ist hiermit nicht verbunden.
Es gilt materielles deutsches Recht unter Ausschluß des UN-Kaufrechts."
Application Example
-3-
AC500/Issue: 11.2011
www.infoPLC.net
2 Used equipment for example
2.1 Hardware overview
Ethernet
Profibus
PC
AC500
Profibus
Profibus
Drive
Control Builder Plus
v2.1
PLC
PM5xx
CM572
DP
FPBA-01
ACSM1
Terminal base TB511
2.2 AC500
AC500 PM583v2.1 ETH – Firmware
CM572 DP (PROFIBUS) – Firmware
ABB Control Builder Plus (PS501)
includes CoDeSys
Terminal Base
V 2.1.3
V 1.097
V 2.1
V 2.3.9.22
TB511 ..R0270
2.3 ACSM1
ACS355 Motion – Firmware
ACS355 Motion – Drive Rating ID
FPBA-01 – Firmware
1510
ACSM1-02A5-4
210B
2.4 Cables
Standard Profibus cable with sub-D connectors. See manuals for pin assignments.
Standard Ethernet patch-cable (RJ45)
2.5 Used documents:
Drive Manager:
Control Builder Plus v2.1 - Help
Contents
Drive Manager
CM579 Profibus coupler:
CoDeSys v2.3.9.22 - Help
Contents
Target System
Hardware AC500
Communication modules
CM572-DP
Note the AC500 help files are only included in CoDeSys help content when an AC500
project is open.
ACSM1 and FPBA-01
www.abb.com
Application Example
-4-
AC500/Issue: 11.2011
www.infoPLC.net
Products and services
Drives (for electric motors)
Low Voltage AC Drives
Machinery drives
High Performance Machinery Drives
Manual
ACSM1 list of hyperlinks to all manuals:
ACSM1 Motion Control Program Firmware Manual
and
FPBA-01 PROFIBUS DP Adapter Module User's Manual
Application Example
-5-
AC500/Issue: 11.2011
www.infoPLC.net
3 Configuration of ACSM1
To establish a fieldbus connection between AC500 PLC and an ACSM1 drive mount the FPBA-01
communication module on the drive. Set following Parameters with the “Drive Studio” software tool or with
the Assistant Control Panel of the ACSM1 drive:
50
50.01
…
Fieldbus
FBA ENABLE
51
51.01
51.02
51.03
51.04
51.05
51.06
…
51.27
FBA
FBA
FBA
FBA
FBP
FBP
FBP
SETTINGS
TYPE
PAR2
PAR3
PAR4
PAR5
PAR6
FBP PAR REFRESH
Enable
PROFIBUS-DP
2
1500
6
0
100
0
REFRESH
The following parameters have to be set to map data to the Fildbus variables for a cyclic data exchange
that will be used later.
52
52.01
52.02
52.03
FBA
FBA
FBA
FBA
DATA
DATA
DATA
DATA
IN
IN1
IN2
IN3
4
5
6
53
53.01
53.02
53.03
FBA
FBA
FBA
FBA
DATA
DATA
DATA
DATA
OUT
IN1
IN2
IN3
1
2
3
Set Parameter 51.27 to REFRESH after all Parameters in group 51 have been set
Parameter 51.01:
Is set automatically by drive after installation of the communication
module
Parameter 51.02:
The value 2 defines Profibus note address #2.
Parameter 51.03:
The value 1500 defines the Profibus transfer rate of 1500 baud.
Parameter 51.04:
The value 6 corresponds to PPO type 6. The PPO type that will be used will be
defined by the Profibus master device.
Parameter 51.05:
The value 0 refers to the PROFIdrive profile.
Parameter 51.06:
Defines the T16 scale. The values will not be used with PROFIdrive profile.
Parameter 52.01:
Maps the value of “STATUSWORD” to the first PZD variable that will be read
from the PLC
Parameter 52.02:
Maps the the value of “ACT1” to the second PZD variable that will be read from
the PLC
Parameter 52.03:
Maps the the value of “ACT2” to the third PZD variable that will be read from
the PLC
Parameter 53.01:
Maps the the value of “CONTROLWORD” to the first PZD variable that will be
Application Example
-6-
AC500/Issue: 11.2011
www.infoPLC.net
send from the PLC
Parameter 53.02:
Maps the the value of “REF1” to the second PZD variable that will be send from
the PLC
Parameter 53.03:
Maps the the value of “REF2” to the third PZD variable that will be send from
the PLC
You can find more Information about Profibus DP communication settings in ACSM1
parameter groups 50, 51 and 52 in the FPBA-01 communication module manual.
Application Example
-7-
AC500/Issue: 11.2011
www.infoPLC.net
4 Configuration of AC500
Please start your Control Builder Plus v2.1 (PS501v2.1) Installation.
4.1 Set IP-Address of PLC
To set the IP-Address of your PLC select:
Control Builder Plus v2.1
Tools
IP config tool:
Make sure that your PLC is powered and connected to your PC with an ethernet network switch or hub. You
can also have a point-to-point connection with a standart Ethernet patch-cable.
Press “Scan” to search for connected AC500 PLCs on your network, select your PLC and change the IPaddress if needed. Then press the “Send configuration” button to send new configuration data to your PLC.
The PLC can be found during network scan when it is in run- or in stop-mode, but has to be in stop-mode
while sending configuration data. After all data is transferred and processed it will restart automatically.
In case of an unused PLC its default address is 192.168.0.10 / 255.255.255.0. Even if you
do not want to change this setting you have to send configuration once.
In order to login to the PLC later on, check if the IP address and subnet mask of your PCs Ethernet adapter
matches to the one you have set for the PLC.
4.2 Create new AC500 project
To create a new project, please go to menu:
Control Builder Plus v2.1
File
New Project…
Then select a target that corresponds to your PLC.
Application Example
-8-
AC500/Issue: 11.2011
www.infoPLC.net
Once a project is made you still can change the type of PLC. Just select the PLC entry in
the object tree, open the context menu and select “update device”.
4.2.1 Add coupler CM572-DP into project
To insert the CM572-DP Profibus DP communication module right-click on the slot that carries the
Profinet IO communication module and select “plug device”. Then select the coupler and press “Plug
Device” button.
To configure the CM572-DP Profibus module double-click on “CM572_Master (CM572-Master)” entry in your
project tree.
Application Example
-9-
AC500/Issue: 11.2011
www.infoPLC.net
In this example you can keep all default values, there are no changes to be made.
To remove a communication module. Open its context menu and select “plug device”.
Then chose “Dummy module”.
4.3 Add the ACSM1 drive to the project
There are two different ways to integrate the ACSM1 with Profibus DP to your project:
1. Insert the FPBA-01 communication module to your project
2. Insert the complete ACSM1 drive to your project
Option 1 is for a standard profibus slave configuration where you can define network settings and the PPO
type. Further more you can set the PKW and PZD mapping corresponding to the used PPO type.
Option 2 is recommended to use. It includes all settings of option 1, but it also enables you to make changes
in the parameter settings of the drive itself without being on-site to the drive by using the Drive Manager.
In the next subsections is an introduction to both options.
In Control Builder Plus v2.1 commonly used slave devices are already included. To use
other devices for your project you have to install the GSD (Generic Station Description) file
of the product into the device repository. Go to: CBPv2.1 => Tools => Device Repository
4.3.1 Option 1: Add FPBA-01
In the object tree open the context menu of the “CM579-PNIO-Master” object and select “Add Device”.
Then chose “ABB Oy” as Vendor and select “ABB Drives FPBA-01 DP-V1” like in the figures shown
below.
Application Example
- 10 -
AC500/Issue: 11.2011
www.infoPLC.net
Open the context menu of the FPBA-DP module and select “Add device” to add PPO type 6 (0 PKW + 10
PZD) for a cyclic data exchange.
4.3.2 Option 2: Add ACSM1
Open the Select the context menu of the CM579_Master entry and select “Add Device”. Then chose “ABB
Oy” as Vendor and select “ACSM1 Motion PROFINET IO” as slave device.
Check or change the used firmware version of the drive by right-click on the “Drive Parameters xxxx”
entry of the drive in the object tree and select “update”.
Application Example
- 11 -
AC500/Issue: 11.2011
www.infoPLC.net
4.4 Configure PROFINET slave
Depening on the option you have taken in the previous chapter either double-click on the “ABB Drives FPBA01 DP-V1” or on the “ACSM1 Motion PROFIBUS” object to edit the Profinet slave. Please select die DPParameters tab. There you have to change the station address to the value “2”.
Obejct
Tab
Parameter
Value / Description
ABB Drives FPBA-01
DP-V1
DP Parameters
Station address
Station address of the
Profibus slave device. In this
example “2” is used.
DP Parameters
Station address
Station address of the
Profibus slave device. In this
example “2” is used.
Or
ACSM1 Motion
PROFINET IO
According to the chosen PPO type you map cyclic data to your variables in CoDeSys.
Obejct
Tab
Parameter
Value / Description
PPO-06
DP-Module I/O
Mapping
Input
Cyclic PZD data
transferred from drive to
PLC e.g. Statusword
Output
Cyclic PZD data
transferred from PLC to
drive e.g. Controlword
PKW xxx in
Acyclic PKW data
transferred from drive to
PLC for parameters
PKW xxx out
Acyclic PKW data
transferred from PLC to
drive for parameters
Double-click on the “PPO Type 6” object and define cyclic data to be transferred between Profibus master
and slave. As an example see the following figure.
Application Example
- 12 -
AC500/Issue: 11.2011
www.infoPLC.net
When you create new configuration data and login to the PLC, you will find the mapped
variables in CoDeSys – Resources tab – Global Variables. See the next chapter.
4.5 Start PLC with new configuration data
CoDeSys
In Control Builder Plus double-click on the “AC500” entry of the object tree. This will create new
configuration data and opens CoDeSys 2.3.9.22. You can also open the context menu of the “AC500”
object and select “Create configuration data” only.
Confirm that you want to create new configuration data.
In CoDeSys select:
online
Communication Paramters
Press “New ...” button, select the communication protocol “Tcp/Ip – 3S Tcp/Ip driver” and press OK
Application Example
- 13 -
AC500/Issue: 11.2011
www.infoPLC.net
If you want to get access to a PLC through an other PLC please select the Tcp/Ip (Level 2)
driver.
Enter the address you have chosen for your PLC in chapter 3.1. Set port to “1201” and Motorola bytorder
“Yes”. Then confirm the settings by pressing the OK button.
To login to your PLC with CoDeSys go to:
online
Login
This will upload your configuration data to the PLC an gives you remote control. Select:
online
Run
The Profibus DP Fieldbus is now operational.
Application Example
- 14 -
AC500/Issue: 11.2011
www.infoPLC.net
5 Drive Manager in Control Builder Plus v2.1
As a new feature Control Builder Plus v2.1 software has a Drive Manager included. To use this feature it
requires to add “ACSM1 Motion PROFINET IO” as Profinet slave device, which is descriped as option 2 in
the previous chapter.
5.1 Connect to PLC with Control Builder Plus
Switch back to Control Builder Plus and set up a second Ethernet connection. Right-click on the PLC
entry to open its context menu. Then select “Set Gateway”
Press “New ...” button, select the communication protocol “Tcp/Ip – 3S Tcp/Ip driver” and press OK.
Enter the address you have already chosen for your PLC bevor. Set port to “1201” and Motorola bytorder
“Yes”. Then confirm the settings by pressing the OK button.
Application Example
- 15 -
AC500/Issue: 11.2011
www.infoPLC.net
After setting the connection parameters you can connect to your PLC with Control Builder Plus. Rightclick on the PLC (e.g. “AC500 PM573-ETH V2.1”) entry to open its context menu. Then select “Login”.
As long as you are logged in you will see this symbol in front of all items that have
information transferred with the PLC
5.2 Start Drive Manager
In the object tree double-click on the object “Drive Parameters xxxx” as shown in the figure below to open
the Drive Manager.
Make sure that your PLC is in run-mode. Then press the “Connect” button to connect to the drive. You can
open multiple Drive Manager windows for different drives which should be configured at the same time.
Application Example
- 16 -
AC500/Issue: 11.2011
www.infoPLC.net
Note that you can only connect to drive and read its parameters when the PLC is in runmode.
5.3 Edit drive parameters
When connected to the drive you can edit all parameters. To get a list of drive parameters click on the green
“Drive” button.
After editing a parameter the value will be directly transferred to drive and becames active except an
additional refresh action is necessary.
Note, that all changes to the drive paramters are written momentary and will be reset by the next powerup.
To make changed parameter values permanent you have to press the button “make changes permanent”.
You can save all active drive parameters in a file by pressing the “Export to .dsp” button.
5.4 Drive parameters of the project
Press the yellow “Project” button to get a list of all parameters that will be stored in the project. You can also
save these parameters in a file by pressing the “Export to .dsp” button.
To load parameters from a file click on selection box “import values” and open a file. Its values will be
displayed beside the project values and enables you to select certain parameters you want to copy to your
project.
Differences in the parameters of file and the project will marked with bold letters.
Application Example
- 17 -
AC500/Issue: 11.2011
www.infoPLC.net
5.5 Compare parameters between drive and project
Press on the “Compare” button to show differences between the parameters of the project and the drive.
You can copy parameters from the project to the drive and from the drive to the project.
If you want to write parameters from a file to the drive, you have to copy the parameters into the project
first, then you can copy the parameters from the project to the drive. Then, they will be updated to the
drive automatically.
The following figure shows the available actions you can take to manage the drive parameters:
read
ACSM1
ACS355
ACS850
write momentary
„Drive“
write permantent
parameters
compare
copy
export
„Project“
parameters
compare
copy
.dsp file
export
.dsp file
.dsp file
5.6 Drive Manager options
Drive rating
To configure the drive rating for the respective drive, use the Drive
Manager window. tab Parameter list and item Drive rating. Drive
rating affects to certain limits and setting range of the parameters.
Application Example
- 18 -
AC500/Issue: 11.2011
www.infoPLC.net
Drive Analog Input Settings
Configure the drive's analog input channel settings for
current/voltage configuration based on the hardware (jumper/DIP
switch) settings of the drive.
Based on the analog input settings, the drive parameters related to
analog inputs will be updated automatically for correct units (mA/V).
The user must re-check and verify that the analog signal parameter
values are correct based on the change in the units.
The analog input settings can be done using Drive Manager by
clicking on the Settings... button and then selecting the Analog
inputs tab.
Drive Parameter Comparison Settings
You can define the comparison settings to be used when
comparing the drive online parameters to the offline (project view)
settings. With these settings you can define to ignore the
differences in parameters related to Fieldbus settings and Motor
Data settings. Both options’ default settings are to ignore the
respective parameters in the comparison.
If changes to these parameters are made accidentally,
communication might be lost (fieldbus parameters) or a new ID run
will have to be performed (motor parameters).
If you ignore the Motor data parameters using the settings, the
comparison report will not give the difference in Motor data
parameters in the online values and the offline values and the
difference in the values cannot be downloaded to the drive.
To set the comparison settings, use the Safeguard settings tab in
settings window.
Refresh Parameters
To refresh the drive parameters completely, use the refresh button
provided in the Drive Manager window. You can also see when the
last complete refresh using this button has been performed.
To update the drive parameters of all the parameter groups or only
a selected parameter group, right-click the parameter window
inside the Drive Manager and select Update all parameters or
Update all parameters in this group.
Application Example
- 19 -
AC500/Issue: 11.2011
www.infoPLC.net
Application Example
- 20 -
AC500/Issue: 11.2011
www.infoPLC.net
No. o. p.:
Helpline document
21
Title:
Lang.:
Connect AC500 V2.1 to ACSM1 with Profibus DP using Drive Manager
EN
Manual No. 2CDC 125 185 M0201
Doc. kind:
ABB Automation Products GmbH
Wallstadter Str. 59
D-68526 Ladenburg
Tel. : +49 62 21 / 701-1444
Fax : +49 62 21 / 701-1382
E-Mail : [email protected]
www.abb.com/plc