Red Lion CUB5 USB Panel Meter Product Manual
Red Lion CUB5 USB lets you configure and program CUB5 meters using Crimson software from your PC. It's compatible with Windows 2000 or later. The plug-in card installs into the main circuit board of the meter and requires drivers which are included with the Crimson Programming software. Once installed, the card appears as a Virtual communications port. Use CUB5 USB for easy programming, data logging, and monitoring applications.
Advertisement
Advertisement
Bulletin No. CUB5USB-C
Drawing No. LP0770
Released 04/22
MODEL CUB5USB - USB PROGRAMMING OPTION CARD
DESCRIPTION
This bulletin serves as a guide for the installation, configuration and operation of the CUB5 USB Programming plug-in card for the CUB5. The plug-in card is a separately purchased option card that plugs into the main circuit board of the meter. The CUB5USB requires installation of drivers which are included with the Crimson Programming software. Following installation of the drivers, the card appears as a Virtual communications port.
Crimson is a Windows ® based program that allows configuration of the CUB ®
5 meters from a PC. Crimson offers standard drop-down menu commands, that make it easy to program the CUB5 meters. The CUB5 program can then be saved in a PC file for future use. A CUB5 USB plug-in card is required to program the meter using the software. Crimson software is available as a no charge download from Red Lion's website.
INSTALLING PLUG-IN CARDS
The card plugs into the main circuit board of the meter as shown.
Perform USB driver installation below prior to powering the
CUB5 and connecting CUB5USB to a PC USB port.
USB Card
ON ECE
1 2 3 4
SPECIFICATIONS
CUB5USB PROGRAMMING CARD
Type : USB Virtual Comms Port
Baud Rate : 300 to 38.4k
Unit Address : 0 to 99
CRIMSON 2 SYSTEM REQUIREMENTS
• Windows 2000 or later
• RAM and free disk space as required by the chosen operating system.
• A display of at least 800 by 600 pixels
• A USB port for downloading to the CUB5
ORDERING INFORMATION
MODEL NO. DESCRIPTION
CUB5USB CUB5 USB Programming Card
CBLUSB Type A to B USB Cable
PART NUMBER
CUB5USB0
CBLUSB00
WARNING: Disconnect all power to the unit before installing Plug-in card.
CAUTION : The Plug-in cards and main circuit board contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
USB DRIVER INSTALLATION
1. Download and install the latest Crimson 2 build on your Windows ® compatible
PC. Earlier builds may not have the RLC Virtual Comm port drivers. Crimson software is available as a free download at http://www.redlion.net.
2. Install CUB5USB card into CUB5 meter and apply power to the CUB5.
3. Connect Type A USB cable to computer and CUB5USB option card.
Windows will prompt you for the location of the drivers for the device. The default location for these drivers is “C:\Program Files\Red Lion controls\
Crimson 2.0\Device.” When the hardware setup appears, choose “Install from a list or Specific location,” click Next, and then check “Include this location...” and click the Browse button. Point the Wizard at the location specified above or whatever other location you specified during installation of the software. It is important that you perform this step correctly, or you may have to manually remove the drivers using the Device Manager, and repeat the installation once more.
Note: Crimson’s USB drivers have not been digitally signed by Microsoft ® , and you will therefore see a dialog offering you the chance to stop the installation. You should be sure to select the Continue option to indicate that you do indeed wish to install the drivers.
4. Windows will automatically assign a comms port to the CUB5USB. To determine the port assigned, open “System Properties” from within Windows ®
Control Panel. Select the Hardware tab, and click the “Device Manager” button. Expand the “Ports” line. Take note of which Comms port is assigned to “RLC Virtual Comm port”. It must be Com4 or lower to operate with
Crimson 2. If higher, right-click on the entry and select “Properties,” “Port
Settings” tab, and then “Advanced” button. Select a Coms port that is COM4 or lower and is not physically being used.
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all
Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net
) current at the time of shipment of the Products (the “Warranty Period”).
EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY
MAKES NO WARRANTY WHATSOEVER WITH RESPECT
TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF
MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR
A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST
INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF
A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW,
COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE
OF TRADE OR OTHERWISE.
Customer shall be responsible for determining that a Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such
Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL
BE THE CUSTOMER’S SOLE AND EXCLUSIVE REMEDY AND
COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE
LIMITED WARRANTY SET FORTH IN PARAGRAPH (a) .
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS
OF THIS WARRANTY, AS WELL AS ALL OTHER DISCLAIMERS
AND WARRANTIES IN THIS DOCUMENT.
1
MODULE 5 - S
EriaL
C
OMMUniCatiOnS
P
araMEtErS
(
5-SEriAL
)
5-SEriAL
PARAMETER MENU
Pro
SEL
bAUd dAtA PAritY Addr Abbr Prnt OPt
Baud Rate Data Bit
*
Parity Bit
*
Meter
Address
Abbreviated
Printing
*
Options
Module 5 is the programming module for the Serial Communications
Parameters. The only paramters of concern when utilizing the CUB5USB programming option card to communicate with Crimson 2 programming software is the Baud Rate and Meter Address. The Parameters are only accessible when an optional CUB5USB, RS232 or RS485 serial communications card is installed in the meter.
Indicates Program Mode Alternating Display.
Parameter
bAUd
9600
Selection/Value
Factory Settings are shown.
ABBREVIATED PRINTING *
Abbr
NO YES
NO
This parameter determines the formatting of data transmitted from the meter in response to a Transmit Value command or a Block Print Request. Select parameter data. Select
YES
NO for a full print transmission, consisting of the meter address, mnemonics, and
for abbreviated print transmissions, consisting of the parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent during a full transmission.)
BAUD RATE
bAUd
9600
300 1200
600 2400
4800
9600
19200
38400
Set the baud rate to match that of other serial communications equipment.
Normally, the baud rate is set to the highest value that all of the serial communications equipment is capable of transmitting and receiving.
DATA BIT *
dAtA
7-bit 8-bit
7-bit
Select either 7- or 8-bit data word length. Set the word length to match the other serial communications equipment on the serial link.
PRINT OPTIONS *
Prnt OPt
NO
NO YES
This parameter selects the meter values transmitted in response to a Print
Request. A print request is also referred to as a block print because more than one parameter can be sent to a printer or computer as a block.
Selecting
YES displays a sublist for choosing the meter parameters to appear in the print block. All active parameters entered as transmitted during a block print. Parameters entered as
The “Print All” ( P-ALL
YES
in the sublist will be
NO
will not be sent.
) option selects all meter values for transmitting ( without having to individually select each parameter in the sublist.
YES ),
Note: Inactive parameters will not be sent regardless of the print option setting. For example, the Setpoint value(s) will not be sent unless an optional setpoint card is installed in the meter.
* - Disregard these parameters when configuring unit to upload or download with
Crimson software.
PARITY BIT*
PArity
Odd
NO Odd EVEN
This parameter only appears when the Data Bit parameter is set to a
7-bit data word length. Parity is automatically
NO
if dAtA is set for 8 bit.
Set the parity bit to match that of the other serial equipment on the serial link. The meter ignores parity when receiving data and sets the parity bit for outgoing data. If parity is set to to 10 bits.
NO
, an additional stop bit is used to force the frame size
RED LION CONTROLS TECHNICAL
SUPPORT
If for any reason you have trouble operating, connecting, or simply have questions concerning your new product, contact Red Lion’s technical support.
Support: support.redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.
20 Willow Springs Circle York, PA 17406
METER ADDRESS
Addr
00
0 to 99
Enter the serial node address. With a single unit, an address is not needed and a value of zero can be used (RS232 applications). Otherwise, with multiple bussed units, a unique address number must be assigned to each meter. The node address applies specifically to RS485 applications.
COPYRIGHT