Advertisement
Advertisement
Bulletin No. CUB5-M
Drawing No. LP0584
Released 04/22
MODEL CUB
®
5 - MINIATURE ELECTRONIC 8-DIGIT DUAL
AND
CC
R
UL
US LISTED
IND. CONT. EQ.
E137808
LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING
0.46" (11.7 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARD
OPTIONAL SERIAL COMMUNICATIONS CARD (RS232 or RS485)
OPTIONAL USB PROGRAMMING CARD
OPERATES FROM 9 TO 28 VDC POWER SOURCE
PROGRAMMABLE SCALING FOR COUNT AND RATE
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION)
BUILT-IN BATCH COUNTING CAPABILITY
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The CUB ® 5 provides the user the ultimate in flexibility, from its complete user programming to the optional setpoint control and communication capability.
The meter can be programmed as a single or dual counter with rate indication capability. The display can be toggled either manually or automatically between the selected displays.
The CUB5 display has 0.46" (11.7 mm) high digits. The LCD is available in two versions, reflective (CUB5R000) and backlight (CUB5B000). The backlight version is user selectable for green or red backlighting with variable display intensity.
The counter is programmable for one of eight different count modes, including bi-directional and quadrature. When programmed as a dual counter, each counter has a separate scale factor and decimal points. In the counter/rate indicator mode, each have their own scaling and decimal point read-outs in different engineering units. The internal batch counter can be used to count setpoint output activations.
The meter has two separate inputs which provide different functions depending on which operating mode is selected. Input A accepts the signal for the Count and/or Rate displays, while Input B accepts the signal for the Count display or direction control. In the anti-coincidence mode, both inputs are monitored simultaneously so that no counts are lost. The resulting display can be chosen as the sum or difference of the two inputs. The Rate Indicator has programmable low (minimum) and high (maximum) update times to provide optimal display response at any input frequency. There is a programmable user input that can be programmed to perform a variety of functions.
The capability of the CUB5 can be easily expanded with the addition of option cards. Setpoint capability is field installable with the addition of the single setpoint relay output card or the dual setpoint solid state output card.
Serial communications capability for RS232 or RS485 is added with a serial option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the unit and sensors.
DIMENSIONS In inches (mm)
COUNTER
The CUB5 receives incoming pulses and multiplies them by the Count Scale
Factor to obtain the desired reading for the count display. Input A accepts the signal for the count and Input B is used for quadrature, dual counter, anticoincidence counting, or up/down control counting.
RATE
The rate indicator utilizes the signal at Input A to calculate the rate value using a time interval method (1/tau). The unit counts on the negative edge of the input pulses. After the programmed minimum update time elapses and the next negative edge occurs, the unit calculates the input rate based on the number of edges that occurred during the elapsed time. The input rate is then multiplied by the rate scaling value to calculate the rate display.
At slower rates, averaging can be accomplished by programming the rate minimum update time for the desired response. Extensive scaling capabilities allow practically any desired reading at very slow count rates.
SAFETY SUMMARY
All safety related regulations, local codes as well as instructions that appear in this document or on equipment must be observed to ensure personal safety and to prevent damage to either the device or equipment connected to it.
Do not use these products to replace proper safety interlocking. No softwarebased device (or any other solid-state device) should ever be designed to be responsible for the maintenance of personnel safety or consequential equipment not equipped with safeguards. Red Lion disclaims any responsibility for damages, either direct or consequential, that result from the use of this equipment in a manner not consistent with these specifications.
CAUTION: Risk of Danger.
Read complete instructions prior to installation and operation of the unit.
CAUTION: Risk of electric shock.
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
0.13 (3.3)
SEL
9876543.2
RST
2.95 (74.9)
1.54 (39.1)
0.15
(3.8)
1.71
(43.4)
1
1.29
(32.8)
2.62 (66.6)
ON ECE
1 2 3 4
1.29
(32.8)
o
rderinG
i
nforMation
TYPE
CUB5
Optional Plug-in Cards
Accessories
MODEL NO.
CUB5R
CUB5B
CUB5RLY
CUB5SNK
CUB5COM
CUB5USB
MLPS
CBLPRO
CBPRO
SFCRD
DESCRIPTION
Dual Counter & Rate Indicator with Reflective Display
Dual Counter & Rate Indicator with Backlight Display
Single Relay Option Card
Dual Sinking Open Collector Output card
RS485 Serial Communications Card
RS232 Serial Communications Card
USB Programming Card
+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out
Programming Cable RS232 (RJ11-DB9)
Communication Cable RS485 (RJ11-DB9)
Crimson PC Configuration Software, Free Download Available 1
CBLUSB USB Programming Cable CBLUSB00
1 Crimson software is a free download from http://www.redlion.net. System requirements for the software are listed on the download page.
PART NUMBER
CUB5R000
CUB5B000
CUB5RLY0
CUB5SNK0
CUB5COM1
CUB5COM2
CUB5USB0
MLPS1000
MLPS2000
CBLPROG0
CBPRO007
SFCRD200
G eneral
M eter
S pecificationS
1. DISPLAY : 8 digit LCD 0.46" (11.7 mm) high digits
CUB5R000 : Reflective LCD with full viewing angle
CUB5B000 : Transmissive LCD with selectable red or green LED backlight, viewing angle optimized. Display color change capability with output state when using an output module.
2. POWER : Input voltage range is +9 to +28 VDC with short circuit and input polarity protection. Must use an RLC model MLPS or an NEC Class 2 or
Limited Power Source (LPS) rated power supply.
DISPLAY COLOR
CUB5R000 ---
CUB5B000 Red (max intensity)
CUB5B000 Green (max intensity)
INPUT CURRENT
@ 9 VDC WITHOUT
CUB5RLY0
10 mA
85 mA
95 mA
INPUT CURRENT
@ 9 VDC WITH
CUB5RLY0
30 mA
115 mA
125 mA
3. COUNTER DISPLAYS :
Counter A : 8-digits, enabled in all count modes
Display Range: -9999999 to 99999999
Overflow Indication: Display flashes “
4. RATE DISPLAY : 6-digits, may be enabled or disabled in any count mode
Display Designator : “
Display Range : 0 to 999999
Over Range Display : “
R OLOLOL
”
”
Counter B : 7-digits, enabled in Dual Counter Mode or batch counting
Display Designator: “
Display Range: 0 to 9999999 (positive count only)
Overflow Indication: Display flashes “
Maximum Count Rates : 50% duty cycle
Without setpoint option card: 20 KHz (all count modes)
With setpoint option card: 20 KHz for any count mode except Dual Counter
(16 KHz), Quadrature x2 (14 KHz) and Quadrature x4 (13 KHz).
R b
Cnt OVEr
” to the left side of the display bCntOVEr
”
” to the left side of the display
Maximum Frequency : 20 KHz
Minimum Frequency : 0.01 Hz
Accuracy : ±0.01%
5. COUNT/RATE SIGNAL INPUTS (INP A and INP B):
Input A : DIP switch selectable to accept pulses from a variety of sources.
See Section 2.0 Setting the DIP Switches for Input A specifications.
Input B : Logic signals only
Trigger levels: V
IL
= 0.7 V max; V
Current sinking: Internal 10K Ω
= 2.4 V min; V
MAX
= 28 VDC
pull-up resistor to +9 to 28 VDC
Filter (LO Freq.): Damping capacitor provided for switch contact bounce.
Limits input frequency to 50 Hz and input pulse widths to 10 msec min.
6. USER INPUT (USR): Programmable input. Connect to input common (INP
COMM) to activate function. Internal 10K Ω pull-up resistor to +9 to 28 VDC.
Threshold Levels : V
IL
= 0.7 V max; V
IH
= 2.4 V min; V
MAX
= 28 VDC
Response Time : 5 msec typ.; 50 msec debounce (activation and release)
7. MEMORY : Nonvolatile E 2 PROM memory retains all programming parameters and count values when power is removed.
8. CONNECTIONS : Wire clamping screw terminals
Wire Strip Length : 0.3" (7.5 mm)
Wire Gage : 30-14 AWG copper wire
Torque : 3.5 inch-lbs (0.395 N-m) max.
9. CONSTRUCTION : This unit rated for Type 4X/IP65 requirements for indoor/ outdoor use. Installation Category I, Pollution Degree 2. High impact plastic case with clear viewing window. Panel gasket and mounting clip included.
10 . ENVIRONMENTAL CONDITIONS :
Operating Temperature Range for CUB5R000 : -35 to 75 °C
Operating Temperature Range for CUB5B000 depends on display color and intensity level as per below :
Red Display
Green Display
INTENSITY LEVEL TEMPERATURE
1 & 2
3
4
5
1 & 2
3
4
5
-35 to 75°C
-35 to 70°C
-35 to 60°C
-35 to 50°C
-35 to 75°C
-35 to 65°C
-35 to 50°C
-35 to 35°C
Storage Temperature : -35 to 85 °C
Operating and Storage Humidity : 0 to 85% max. relative humidity (noncondensing)
Vibration to IEC 68-2-6 : Operational 5-500 Hz, 5 g
Shock to IEC 68-2-27 : Operational 40 g
Altitude : Up to 2000 meters
11.
CERTIFICATIONS AND COMPLIANCES :
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control, and laboratory use:
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring
Circuits
RoHS Compliant
UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Indoor/Outdoor Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Refer to EMC Installation Guidelines for additional information.
12. WEIGHT : 3.2 oz (100 g)
2
o ptional
p luG
in
c ardS
ADDING OPTION CARDS
The CUB5 meters can be fitted with optional output cards and/or serial communications cards. The details for the plug-in cards can be reviewed in the specification section below. The plug-in cards, that are sold separately, can be installed initially or at a later date.
WARNING: Disconnect all power to the unit before installing
Plug-in card.
SINGLE RELAY OUTPUT CARD (One setpoint only)
Type : Single FORM-C relay
Isolation To Sensor & User Input Commons : 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating : 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy : 100,000 minimum operations
Response Time:
Turn On Time: 4 msec. max.
Turn Off Time: 4 msec. max.
DUAL SINKING OUTPUT CARD (One or two setpoints)
Type : Non-isolated switched DC, N Channel open drain MOSFET
Current Rating : 100 mA max.
V
DS ON
: 0.7 V @ 100 mA
V
DS MAX
: 30 VDC
Offstate Leakage Current : 0.5 mA max.
RS485 SERIAL COMMUNICATIONS CARD
Type : RS485 multi-point balanced interface (non-isolated)
Baud Rate : 300 to 38.4k
Data Format : 7/8 bits; odd, even, or no parity
Bus Address : 0 to 99; max 32 devices per line
Transmit Delay : Selectable, 2 msec min. or 50 msec min.
RS232 SERIAL COMMUNICATIONS CARD
Type : RS232 half duplex (non-isolated)
Baud Rate : 300 to 38.4k
Data Format : 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type : USB virtual comms port
Connection : Type B
Baud Rate : 300 to 38.4k
Unit Address : 0 to 99
1.0 i nStallinG the
M eter
INSTALLATION
The meter meets NEMA Type 4X/IP65 requirements when properly installed.
The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz
[0.202 to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the keypad of the unit.
NUT FASTENER
PANEL
BEZEL MOUNTING SCREW
2.68
+.025
-.000
+.6
1.30
+.024
-.000
MOUNTING CLIP
PANEL
GASKET
2.0 S ettinG the dip S witcheS
To access the switches, remove the rear cover of the meter as described below. A bank of 4 switches is located in the upper right hand corner. After setting the switches, install any optional plug-in cards before replacing the rear cover (see next section).
SETTING THE INPUT DIP SWITCHES
The meter has four DIP switches for Input A and Input B that must be set before applying power.
Warning : Exposed line voltage exists on the circuit boards. Remove all power to the meter and load circuits before accessing inside of the meter.
REMOVE/REPLACE THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
SWITCH 1
LOGIC : Input A trigger levels V
V
IH
= 2.75 V min.; V
MAX
IL
= 1.25 V max.;
= 28 VDC
MAG : 200 mV peak input sensitivity; 100 mV hysteresis; maximum input voltage: ± 40 V peak
(28 Vrms); Must also have SRC switch ON.
(Not recommended with counting applications.)
SWITCH 2
SNK.
: Adds internal 7.8 K Ω pull-up resistor to +9 to
28 VDC, I
MAX
= 3.8 mA.
SRC.
: Adds internal 3.9 K Ω pull-down resistor,
7.2 mA max. @ 28 VDC max.
ON
1 2 3 4
Factory Setting
SWITCHES 3 and 4
HI Frequency : Removes damping capacitor and allows max. frequency.
LO Frequency : Adds a damping capacitor for switch contact bounce. Limits input frequency to 50 Hz and input pulse widths to 10 msec.
3
3.0 i nStallinG p luG -i n c ardS
The Plug-in cards are separately purchased option cards that perform specific functions. The cards plug into the main circuit board of the meter. After installing the cards, replace the rear cover before wiring the meter.
CAUTION: The Plug-in cards and main circuit board contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges.
Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
Comms or
Programming
Card
ON ECE
1 2 3 4 Setpoint Card
REMOVE/REPLACE THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd input terminals. To release the tab, insert a small, flat blade screwdriver between the tab and the plastic wall below the terminals. Inserting the screwdriver will provide enough pressure to release the tab locks. To replace the cover, align the cover with the input terminals and press down until the cover snaps into place.
Locking Tab
4.0 w irinG the M eter
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’s voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed
(stranded wires should be tinned with solder.) Insert the lead under the correct screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended:
Fair-Rite part number 0443167251 (RLC part number FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide varistor (MOV) across an AC inductive load is very effective at reducing
EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most RLC products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI.
Although the use of a snubber or varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/emi for more information on
EMI guidelines, Safety and CE issues as they relate to Red Lion Controls products.
4.1 POWER WIRING
DC Power
+9 to +28 VDC: +VDC
Power Common: -VDC
4.2 USER INPUT WIRING
Sinking Logic
INP COMM
USR
}
Connect external switching device between the
User Input terminal and Input Common.
The user input of the meter is internally pulled up to +9 to +28 V with 10 K resistance. The input is active when it is pulled low (<1 .0 V).
+
PWR COMMON +9-28 VDC
PWR COMMON +9-28 VDC
4
4.3 INPUT WIRING
CAUTION : Power common (PWR COMMON) is NOT isolated from input common (INP COMM). In order to preserve the safety of the meter application, the power common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not, hazardous voltage may be present at the Signal or User Inputs and input common terminals. Appropriate considerations must then be given to the potential of the input common with respect to earth ground; and the common of the plug-in cards with respect to input common.
Magnetic Pickup
Input A
AC Inputs From Tach Generators, Etc.
Input A
Two Wire Proximity, Current Source
Input A
ON
1 2 3
*
4
MAGNETIC PICKUP
PWR COMMON
Current Sinking Output
+9-28 VDC
Input A
ON
1 2
*
3
*
4
Resistor to Limit Current to 2.5 mA MAX.
PWR COMMON
Current Sourcing Output
+9-28 VDC
AC
Input A
ON
1
*
2 3
*
4
2.2 k Ω
PWR COMMON
Interfacing With TTL
+9-28 VDC
Input A
ON
1
*
2 3
*
4
ON
*
1 2 3
*
4
ON
1 2 3 4
*
PWR COMMON +9-28 VDC
Switch or Isolated Transistor; Current Sink
Input A
PWR COMMON +9-28 VDC
Switch or Isolated Transistor; Current Source
Input A
PWR COMMON +9-28 VDC
Current Sink Output; Quad/Direction
+5 V
COMMON
ON
1
*
2 3
*
4
ON
1 2
*
3
*
4
PWR COMMON
PWR COMMON +9-28 VDC
Switch position is application dependent.
4.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
COM
N.O.
N.C.
+9-28 VDC
ON
1 2 3 4
PWR COMMON +9-28 VDC
Shaded areas not recommended for counting applications.
ELECTRICAL CONNECTIONS
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
COM
OSNK1
OSNK2
COM N.O.
N.C.
ELECTRICAL CONNECTIONS
OSNK 1(2)
(30 V MAX.)
4.5 SERIAL COMMUNICATION WIRING
SERIAL COMMUNICATIONS PLUG-IN CARD
COM
Note: Output Common is not isolated from DC Power Common. Load must be wired between OSNK terminal and V+ of the load supply.
4.6 USB PROGRAMMING
USB PROGRAMING PLUG-IN CARD
6 5 4 3 2 1 6 5 4 3 2 1
RS485 RS232
RJ11 CONNECTOR PIN OUTS
5
5.0 r eviewinG the f ront B uttonS and d iSplay
SEL RST
KEY
SEL
RST
DISPLAY MODE OPERATION
Index display through enabled values
Resets count display(s) and/or outputs
ENTERING PROGRAM MODE PROGRAMMING MODE OPERATION
Press and hold for 2 seconds to activate Store selected parameter and index to next parameter
Advances through the program menu/
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
“
R
” - To the left of the display is the rate value.
- Counter A has no designator.
“
b
” - To the left of the display is the Counter B value (dual count or batch).
“1” and “2” - Indicates setpoint 1 and 2 output status.
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between the rate and count values.
6.0 p roGraMMinG the M eter
DISPLAY
MODE
OVERVIEW
SEL
PROGRAMMING MENU
NO
Pro
Input Setup
Parameters
RST
Rate Setup
Parameters
Display and Front
Panel Key
Parameters
SEL
1-INPUt
SEL
2-rAtE
SEL
3-dSPLAY
Setpoint
Output
Parameters
SEL
4-SEtPt
Serial
Setup
Parameters
SEL
5-SEriAL
PROGRAMMING MODE ENTRY (SEL KEY)
It is recommended all programming changes be made off line, or before installation. The meter normally operates in the Display Mode. No parameters can be programmed in this mode. The Programming Mode is entered by pressing and holding the SEL key. If it is not accessible then it is locked by either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST KEYS)
The Programming Menu is organized into separate modules. These modules group together parameters that are related in function. The display will alternate between
Pro
and the present module. The RST key is used to select the desired module. The displayed module is entered by pressing the SEL key.
MODULE MENU (SEL KEY)
Each module has a separate module menu (which is shown at the start of each module discussion). The SEL key is pressed to advance to a particular parameter to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to continue by accessing additional modules.
Pro NO
. Programming may
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and the selections/value for that parameter. The RST key is used to move through the selections/values for that parameter. Pressing the SEL key, stores and activates the displayed selection/value. This also advances the meter to the next parameter.
For numeric values, press the RST key to access the value. The right hand most digit will begin to flash. Pressing the RST key again increments the digit by one or the user can hold the RST key and the digit will automatically scroll.
The SEL key will advance to the next digit. Pressing and holding the SEL key will enter the value and move to the next parameter.
PROGRAMMING MODE EXIT (SEL KEY)
The Programming Mode is exited by pressing the SEL key with
Pro NO displayed. This will commit any stored parameter changes to memory and return the meter to the Display Mode. (If power loss occurs before returning to the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 for counting or Module 2 for rate.
When programming is complete, it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code.
FACTORY SETTINGS
Factory settings may be completely restored in Module 3. This is useful when encountering programming problems.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will appear. This is used to illustrate the display alternating between the parameter on top and the parameter’s factory setting on the bottom. In most cases, selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
INP A-b
Cnt ud
Selection/Value
Factory Settings are shown.
6
6.1 Module 1 - i
nput
S
etup
p
araMeterS
(
1-INPUt
)
1-INPUt
SEL
INP A-b CntA dP CntA ScF
Count
Mode
Counter A
Decimal Point
Counter A
Scale Factor
CntA rSt
Counter A
Reset Action
CntA dir
Counter A
Count
Direction
PARAMETER MENU
CntA Ld
Dual Count or Batch
Only
Cntb bAt Cntb dP Cntb ScF RSt P-UP USEr INP
Dual Count or Batch
Only
USEr ASN
Counter A
Count Load
Value
Counter B
Batch Count
Enable
Counter B
Decimal Point
Counter B
Scale Factor
Counter Reset at Power-up
User Input
Function
User Input
Assignment
Shaded area selections only apply when Counter B is enabled (Dual Counter mode or batch counter).
INP A-b
Cnt ud
COUNT MODE
Cnt ud qUAd 1 Add Add
RAtE Cnt dUAL Cnt
qUAd 2
qUAd 4
Add Sub
Select the count mode that corresponds with your application. The input actions are shown in the boxes below. For simple counting applications, it is recommended to use Count with Direction for the count mode. Simply leave the direction input unconnected.
DISPLAY MODE
Cnt ud
Count with Direction
RAtE Cnt dUAL Cnt
qUAd 1
qUAd 2
qUAd 4
Rate/Counter
Dual Counter
Quadrature x1
Quadrature x2
Quadrature x4
INPUT A ACTION
Counter A
Rate only
Counter A Add
Count A
Count A
Count A
Counter A Add
INPUT B ACTION
Counter A Direction
Counter A Add
Counter B Add
Quad A
Quad A
Quad A
Counter A Add
Add Add
2 Input Add/Add
Add Sub
2 Input Add/Subtract Counter A Add Counter A Subtract
Note: The Rate indicator signal is derived from Input A in all count modes.
COUNTER A DECIMAL POSITION
CntA dP
0 0.00
0.0000
0
0.0
0.000
0.00000
This selects the decimal point position for Counter A. The selection will also affect Counter A scale factor calculations.
COUNTER A SCALE FACTOR
CmtA ScF
01.0000
00.0001
to
99.9999
The number of input counts is multiplied by the scale factor to obtain the desired process value. A scale factor of 1.0000 will result in the display of the actual number of input counts. (Details on scaling calculations are explained at the end of this section.)*
RSt P-UP
COUNTER RESET AT POWER-UP
NO
NO yES
NO
Count A
Count b both A-b
Pro
CmtA Ld
COUNTER A COUNT LOAD VALUE
-9999999
to
99999999
00000500
Counter A resets to this value if Reset to Count Load action is selected.
Cmtb bAt
COUNTER B BATCH COUNT ENABLE
NO SP2
NO
SP1 SP1-2
The Counter B batch count function internally counts the number of output activations of the selected setpoint(s). The count source for the batch counter can be SP1, SP2 or both. Batch counting is available in all count modes except
Dual Counter, which uses an external input signal for Counter B. This parameter only appears if a Setpoint Output option card is installed.
COUNTER B DECIMAL POSITION
Cntb dP
0 0.00
0.0000
0
0.0
0.000
0.00000
This selects the decimal point position for Counter B. The selection will also affect Counter B scale factor calculations.
COUNTER B SCALE FACTOR
Cntb ScF
01.0000
00.0001
to
99.9999
The number of input or batch counts is multiplied by the scale factor to obtain the desired process value. A scale factor of 1.0000 will result in the display of the actual number of input or batch counts. (Details on scaling calculations are explained at the end of this section.)*
CmtA rSt
to 2Ero
COUNTER A RESET ACTION
to 2Ero to CtLd
When Counter A is reset, it returns to Zero or Counter A Count Load value.
This reset action applies to all Counter A resets, except a setpoint generated
Counter Auto Reset programmed in Module 4.
CmtA dir
COUNTER A COUNT DIRECTION
NOr rEV
NOr
Reverse ( rEV
) switches the normal Counter A count direction shown in the
Count Mode parameter chart.
The selected counter(s) will reset at each meter power-up.
* For value entry instructions, refer to selection/value entry in the Programming
The Meter section.
7
SCALING FOR COUNT INDICATION
The CUB5’s scale factor is factory set to 1, to provide one count on the display for each pulse that is input to the unit. In many applications, there will not be a one-to-one correspondence between input pulses and display units.
Therefore, it is necessary for the CUB5 to scale or multiply the input pulses by a scale factor to achieve the desired display units (feet, meters, gallons, etc.)
The Count Scale Factor Value can range from 00.0001 to 99.9999. It is important to note that the precision of a counter application cannot be improved by using a scale factor greater than one. To accomplish greater precision, more pulse information must be generated per measuring unit. The following formula is used to calculate the scale factor.
WHERE:
Desired Display Units : Count display units acquired after pulses that occurred.
Number of Pulses : Number of pulses required to achieve the desired
display units.
Decimal Point Position :
0 = 1
0.0 = 10
0.00 = 100
0.000 = 1000
0.0000 = 10000
0.00000 = 100000
EXAMPLE : The counter display is used to indicate the total number of feet used in a process. It is necessary to know the number of pulses for the desired units to be displayed. The decimal point is selected to show the resolution in hundredths.
Scale Factor =
Desired Display Units x Decimal Point Position
Given that 128 pulses are equal to 1 foot, display total feet with a onehundredth resolution.
Scale Factor =
1.00 x 100
Scale Factor = 0.007812 x 100
Scale Factor = 0.7812
USEr INP
NO
USER INPUT FUNCTION
DISPLAY
NO
Pro Loc
Inhibit rESEt
StorE
Stor-rSt d-SELECt d-LEVEL d-COLOr
Prnt-r5t rESEt-1 rESEt-2 rESEt-12
MODE
No Function
Program Mode Lock-out
Inhibit
Maintained Reset
Store
Store and Reset
Display Select *
Display Intensity Level *
Backlight Color *
Print Request
Print and Reset *
Setpoint 1 Reset *
Setpoint 2 Reset *
Setpoint 1 and 2 Reset *
DESCRIPTION
User Input disabled.
See Programming Mode Access chart.
(Module 3)
Inhibit counting for the selected counter(s).
Level active reset of the selected counter(s).
Freeze display of selected counter(s) while allowing counts to accumulate internally.
Edge triggered reset of the selected counter(s) after storing the count.
Advance once for each activation
Increase intensity one level for each activation. (backlight version only)
Change backlight color with each activation
(backlight version only)
Serial transmit of the active parameters selected in the Print Options (Module 5)
Same as Print Request followed by a momentary reset of the selected counter(s).
Reset Setpoint 1 output
Reset Setpoint 2 output
Reset Setpoint 1 and 2 outputs
Note: * indicates Edge Triggered function. Other functions are Level Active
(maintained)
USEr ASN
Count A
USER INPUT ASSIGNMENT
Count A Count b both A-b
The User Input Assignment is only active when Counter B is enabled and the
User Input performs a Reset, Inhibit or Store function on one or both counters.
6.2 Module 2 - r
ate
S
etup
p
araMeterS
(
2-rAtE
)
2-rAtE
SEL
RAtE Enb RAtE dP
PARAMETER MENU
Pro
RAtE dSP RAtE INP LO-Udt HI-Udt
Rate
Enable
Rate Decimal
Point
Rate Scaling
Display Value
Module 2 is the programming for the rate parameters. For maximum input frequency, Rate Enable should be set to
R
” in the Display Mode.
NO when not in use. When set to
NO
, the remaining rate parameters are not accessible. The rate value is shown with an annunciator of “
RATE ENABLE
Rate Scaling
Input Value
RAtE dSP
Rate Low
Update Time
Rate High
Update Time
RATE SCALING DISPLAY VALUE
0
to
999999
001000
Enter the desired Rate Display Value for the Scaling Point.*
RAtE Enb
YES
NO YES
RATE DECIMAL POINT
RAtE dP
O
0.0
0 0.00
0.000
0.0000
0.00000
This selects the decimal point position for the rate display and any setpoint value assigned to rate. This parameter does not affect rate scaling calculations.
RATE SCALING INPUT VALUE
RAtE INP
01000.0
0.1
to
99999.9
Enter the corresponding Rate Input Value for the Scaling Point.*
*For value entry instructions, refer to selection/value entry in the Programming
The Meter section.
8
SCALING FOR RATE INDICATION
To scale the rate, enter a Scaling Display value with a corresponding Scaling
Input value. These values are internally plotted to a display value of 0 and input value of 0.0 Hz. A linear relationship is formed between these points to yield a rate display value that corresponds to the incoming input signal rate. The meter is capable of showing a rate display value for any linear process.
(
SCALING CALCULATION
If a display value versus input signal (in pulses per second) is known, then those values can be entered into Scaling Display (
RAtE INP
). No further calculations are needed.
RAtE dSP
) and Scaling Input
If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) is known, then it can be entered as the Scaling Input value and the Scaling Display value will be entered as the following:
RATE PER
Second
Minute
Hour
DISPLAY ( RAtE dSP ) INPUT ( RAtE INP )
1
60
3600
# of pulses per unit
# of pulses per unit
# of pulses per unit
NOTES:
1. If # of pulse per unit is less than 10, then multiply both Input and Display values by 10.
2. If # of pulse per unit is less than 1, then multiply both Input and Display values by 100.
3. If the Display value is raised or lowered, then Input value must be raised or lowered by the same proportion (i.e. Display value for per hour is entered by a third less (1200) then Input value is a third less of # of pulses per unit). The same is true if the Input value is raised or lowered, then
Display value must be raised or lowered by the same proportion.
4. Both values must be greater than 0.0.
EXAMPLE:
1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling Display
= 60.0 Scaling Input = 15.1.
2. With 0.25 pulses per gallon, show whole gallons per hour. (To have greater accuracy, multiply both Input and Display values by 10.) Scaling Display
= 36000 Scaling Input = 2.5.
RATE LOW UPDATE TIME
LO-Udt
01.0
0.1
to
99.9
seconds
The Low Update Time is the minimum amount of time between display updates for the rate display. Values of 0.1 and 0.2 seconds will update the display correctly but may cause the display to appear unsteady.
HI-Udt
RATE HIGH UPDATE TIME
0.2
to
99.9
seconds
02.0
The High Update Time is the maximum amount of time before the rate display is forced to zero. (For more explanation, refer to Rate Value
Calculation.) The High Update Time must be higher than the Low Update Time and higher than the desired slowest readable speed (one divided by pulses per second). The factory setting of 2.0, will force the display to zero for speeds below 0.5 Hz or a pulse every 2 seconds.
INPUT FREQUENCY CALCULATION
The meter determines the input frequency by summing the number of falling edges received during a sample period of time. The sample period begins on the first falling edge. At this falling edge, the meter starts accumulating time towards Low Update and High Update values. Also, the meter starts accumulating the number of falling edges. When the time reaches the Low Update Time value, the meter looks for one more falling edge to end the sample period. If a falling edge occurs (before the High Update Time value is reached), the Rate display will update to the new value and the next sample period will start on the same edge. If the High Update Time value is reached (without receiving a falling edge after reaching Low Update Time), then the sample period will end but the Rate display will be forced to zero. The High Update Time value must be greater than the Low Update Time value. Both values must be greater than 0.0. The input frequency calculated during the sample period, is then shown as a Rate value determined by the scaling calculation.
9
6.3 Module 3 - d
iSplay and
f
ront
p
anel
K
ey
p
araMeterS
(
3-dSPLAY
)
3-dSPLAY
SEL
PARAMETER MENU
Backlight Unit Only
Pro d-Scro
L
L
L
L SEL Enb RSt Enb d-COLOr d-LEVEL Pro CodE CodE UEr FACt SEt
Front Panel
Display Select
Enable
Front Panel
Counter
Reset Enable
Display Scroll
Enable
Display
Color
Display
Intensity
Level
Programming
Security
Code
Software
Version
Display
Load Factory
Default
Settings
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
SEL Enb
yES
yES NO
The displays.
yES
selection allows the SEL button to toggle through the enabled
FRONT PANEL COUNTER RESET ENABLE (RST)
RSt Enb
YES
yES NO both A-b
NO Count A
Count b dSPLAy
The yES
selection allows the or batch counter).
RST button to reset the selected counter(s). The shaded selections are only active when Counter B is enabled (Dual Count mode
d-ScroLL
DISPLAY SCROLL ENABLE
NO
yES NO
The yES selection allows the display to automatically scroll through the enabled displays. Each display is shown for 4 seconds.
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
d-COLOr
rEd
rEd 6rn
Enter the desired display color, red or green. This parameter is active for backlight units only.
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
d-LEVEL
5
1
to
5
Enter the desired Display Intensity Level (1-5). The display will actively dim or brighten as levels are changed. This parameter is active for backlight units only.
PROGRAMMING SECURITY CODE
Pro CodE
000
0
to
999
The Security Code determines the programming mode and the accessibility of programming parameters. This code can be used indepentently or along with the Program Mode Lock-out ( parameter (Module 1).
Pro Loc ) selection in the User Input Function
Two programming modes are available. Full Programming mode allows all unit parameters to be viewed and modified. Quick Programming mode permits only user selected values to be modified, but allows direct access to these values without having to enter Full Programming mode.
Entering a Security Code from 1-99 enables Quick Programming mode, and displays a sublist to select what values appear in the Quick Programming menu.
All applicable values set to
YES
in the sublist will be accessible in Quick
Programming. The sublist includes Setpoint values (
Time-out values (
SP2 tOUt the Display Intensity Level (
Pro CodE
SP1 tOUt
, d-LEVEL
SP1 VAL
) for backlight units.
,
SP2 VAL
), Counter A Count Load value (
), Output
CntA Ld
prompt in order to access Full Programming mode. Quick
Pro CodE
prompt.
) and
Programming any Security Code other than 0, requires this code to be entered at the
Programming mode, if enabled, is accessed before the
USER INPUT
FUNCTION
USER INPUT
STATE
SECURITY
CODE
MODE WHEN “SEL”
KEY IS PRESSED
0 Full Programming not Pro Loc
Pro Loc
______
Active
Not Active
1-99
100-999
0
1-99
100-999
0-999
FULL PROGRAMMING
MODE ACCESS
Immediate Access
Quick
Programming
Pro CodE prompt
After Quick Programming with correct code entry at Pro CodE prompt *
With correct code entry at
Pro CodE prompt *
Programming
Lock
Quick
Programming
No Access
No Access
Pro CodE prompt
Full Programming
With correct code entry at
Pro CodE prompt *
Immediate Access
* Entering Code 222 allows access regardless of security code.
SOFTWARE VERSION DISPLAY
CodE UEr
NO
NO yES
Select
YES to momentarily display the meter software version before advancing to the next parameter. The software version is also displayed at power-up.
LOAD FACTORY DEFAULT SETTINGS
FACt SEt
MO
NO yES
The yES
selection will return the meter to the factory default settings. The meter will display been changed.
rESEt
and then return to
Pro
, at which time all settings have
10
6.4 Module 4 - S
etpoint
o
utput
p
araMeterS
(
4-SEtPt
)
SEL
4-SEtPt
SP2 Only
PARAMETER MENU PPrroo
Setpoint
Select
SPn P-UP
Setpoint Output
Power-up
State
Setpoint 2
Enable
SPn tYPE
Setpoint
Boundary
Type
Setpoint
Assignment
SPn StbY
Setpoint
Standby
Operation
The Setpoint Output Parameters are only active when an optional Setpoint
Output Module is installed in the meter. Some parameters in the menu will not appear depending on the Setpoint Assignment and Setpoint Output Action. The
Setpoint Parameter Availability chart below illustrates this.
SETPOINT SELECT
SPt SEL
NO
NO SP1 SP2
"
n
Select the Setpoint Output to be programmed, starting with Setpoint 1. The
" in the following parameters reflects the chosen Setpoint number. After
Setpoint 1 is completely programmed, the display returns to
Select
NO
SPt SEL
steps for Setpoint 2 if both Setpoints are used in the application.
. Repeat
to exit the Setpoint programming module. The number of Setpoints available is dependent on the Setpoint option module installed.
SETPOINT 2 ENABLE (SP2 Only)
Setpoint
Output
Action
SPn AUtO
Counter
Auto Reset
SP2 Enb
NO
NO YES
Select
YES
to enable Setpoint 2 and access the setup parameters. If selected, the unit returns to
SPt SEL
and Setpoint 2 is disabled.
NO
is
SPn tOUt SPn SPn SPn
Setpoint
Output
Time-out
Setpoint
Value
Setpoint
Output Logic
Setpoint
Annunciator
Backlight
Unit Only
SP1 Only SP2 Only
SP1 OFF2 SP2 OFF1
SP1 Output
Off at SP2
Output
SP2 Output
Off at SP1
Output
Setpoint
Output Reset with Manual
Reset
Change Display
Color with
Output State
SPn ACt
LAtCH
SETPOINT OUTPUT ACTION
LAtCH t-OUt bOUNd
The parameter selects the action of the Setpoint Output as described in the chart. Boundary output action is not applicable for Counter B assignment.
SPT ACTION DESCRIPTION
LAtCH
Latched Output Mode
t-OUt bOUNd
Timed Output Mode
Boundary Mode
(High Acting Type)
Boundary Mode
(Low Acting Type)
OUTPUT ACTIVATES OUTPUT DEACTIVATES
When Count =
Setpoint
When Count =
Setpoint
When Count
Setpoint
≥
When Count
Setpoint
≤
At Manual Reset
(if SPn rSt = YES )
After Setpoint
Output Time-Out
When Count
< Setpoint
When Count
> Setpoint
SETPOINT ASSIGNMENT
SPn ASN
Count A
Count A Count b rAtE
Select the display to which the Setpoint is assigned.
SETPOINT PARAMETER AVAILABILITY
PARAMETER
SPn tOUt
DESCRIPTION
Setpoint Output Time-out Value
SPn VAL
Setpoint Value
SPn OUt
Setpoint Output Logic
SPn LIt
Setpoint Annunciator
SPn P-UP
Setpoint Output Power-up State
SPn tYPE
Setpoint Boundary Type
SPn StbY
Standby Operation (Low acting only)
SPn AUtO
Counter Auto Reset
SP1 OFF2
SP1 Output Off at SP2 (SP1 only)
COUNTER ASSIGNMENT (A or B) *
TIMED OUT t-OUt
BOUNDARY bOUNd
LATCH
LAtCH
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
No
No
SP2 OFF1
SPn rSt
SPn ChC
SP2 Output Off at SP1 (SP2 only)
Output Reset with Manual Reset
Change Display Color w/ Output State
Yes
Yes
Yes
No
No
Yes
* BOUNDARY Setpoint Action not applicable for Counter B Assignment
No
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
RATE ASSIGNMENT
TIMED OUT t-OUt
BOUNDARY bOUNd
LATCH
LAtCH
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Yes
11
SETPOINT OUTPUT TIME-OUT
SPn tOUt
001.00
0.01
to
599.99
seconds
This parameter is only active if the Setpoint Action is set to time out (
Setpoint Value is reached.
t-OUt
).
Enter the value in seconds that the Setpoint output will be active, once the
SETPOINT VALUE
SPn VAL
00000100
Count A:
Count B:
Rate:
-
9999999
to
99999999
0
to
9999999
0
to
999999
Enter the desired Setpoint value. To enter a negative setpoint value, increment digit 8 to display a “-” sign (Counter A only).
SPn OUt
NOr
SETPOINT OUTPUT LOGIC
NOr rEV
Normal ( deactivated. Reverse ( deactivated.
NOr
) turns the output “on” when activated and “off” when rEV ) turns the output “off” when activated and “on” when
SPn LIt
NOr
SETPOINT ANNUNCIATOR
NOr rEV
Normal ( output is “on”. Reverse ( is “off”.
NOr
) displays the setpoint annunciator when the corresponding rEV
) displays the setpoint annunciator when the output
SETPOINT OUTPUT POWER-UP STATE
OFF ON SAVE
SPn P-UP
OFF
SAVE
will restore the output to the same state it was at before the meter was powered down.
ON
will activate the output at power up. output at power up.
OFF
will deactivate the
SETPOINT BOUNDARY TYPE
SPn tYPE
HI-ACt
HI-ACt LO-ACt
High Acting Boundary Type activates the output when the assigned display value (
SPn ASN
) equals or exceeds the Setpoint value. Low Acting activates the output when the assigned display value is less than or equal to the Setpoint.
COUNTER AUTO RESET
SPn AUtO
NO
NO @2Ero-Str
2Ero-End
CtLd-Str
CtLd-End
(“
This parameter automatically resets the counter to which the setpoint is assigned ( can occur at output start, or at output end if the Setpoint Output Action is programmed for timed output mode. The Reset-to-Count Load selections
CtLd-
SPn ASN
) each time the setpoint value is reached. The automatic reset
”) only apply to Counter A assignment. This reset may be different from the Counter A Reset Action selected in Module 1.
SELECTION ACTION
NO
No Auto Reset.
2Ero-Str
Reset to Zero at the start of output activation.
CtLd-Str
Reset to Count Load value at the start of output activation.
2Ero-End
Reset to Zero at the end of output activation (timed out only).
CtLd-End
Reset to Count Load value at the end of output activation
(timed out only).
SETPOINT 1 OUTPUT OFF AT SETPOINT 2 (SP1 Only)
SP1 OFF2
NO
NO Out2-Str Out2-End
This parameter will deactivate Setpoint 1 output at the Start or End of
Setpoint 2 output (O1 off at O2). The “
-End
” setting only applies if Setpoint 2
Output Action is programmed for timed output.
SETPOINT 2 OUTPUT OFF AT SETPOINT 1 (SP2 Only)
SP2 OFF1
NO
NO
NO
NO Out1-Str
YES
Out1-End
This parameter will deactivate Setpoint 2 output at the Start or End of
Setpoint 1 output (O2 off at O1). The “
-End
” setting only applies if Setpoint 1
Output Action is programmed for timed output.
SETPOINT OUTPUT RESET WITH MANUAL RESET
SPn rSt
YES
YES NO
Selecting
YES
causes the Setpoint output to deactivate (reset) when the
Setpoint Assigned Counter is reset. The counter reset can occur by the RST button, User Input, Counter Reset at Power-up or a serial Reset Counter command.
This output reset will not occur when the Assigned Counter is reset by a
Setpoint generated Counter Auto Reset.
CHANGE DISPLAY COLOR WITH OUTPUT STATE
SPn ChC
This parameter enables the backlight CUB5 to switch the backlight color when the output state changes. This parameter is only active for the backlight version.
SETPOINT STANDBY OPERATION
SPn StbY
NO
NO YES
This parameter only applies to Low Acting Boundary Type setpoints. Select
YES
to disable a Low Acting Setpoint at power-up, until the assigned display value crosses into the output “off” area. Once in the output “off” area, the
Setpoint will then function per the description for Low Acting Boundary Type.
12
6.5 Module 5 - S
erial
c
oMMunicationS
p
araMeterS
(
5-SEriAL
)
5-SEriAL
SEL
bAUd dAtA PAritY
PARAMETER MENU
Addr Abbr
Pro
Baud Rate Data Bit Parity Bit Meter
Address
Abbreviated
Printing
Prnt OPt
Options
COPY
Copy Program
Settings
The Serial Setup Parameters are only active when one of the optional serial communication/programming cards is installed in the meter.
Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements. This section replaces the bulletin shipped with the RS232 and RS485 serial communications plug-in cards. Discard the separate bulletin when using those serial plug-in cards with the CUB5B and
CUB5R.
BAUD RATE
bAUd
9600
300
600
1200
2400
4800
9600
19200
38400
Set the baud rate to match that of other serial communications equipment.
Normally, the baud rate is set to the highest value that all of the serial communications equipment is capable of transmitting and receiving.
DATA BIT
dAtA
7-bit 8-bit
7-bit
Select either 7- or 8-bit data word length. Set the word length to match the other serial communications equipment on the serial link.
PRINT OPTIONS
Prnt OPt
NO YES
NO
(
This parameter selects the meter values transmitted in response to a Print
Request. A print request is also referred to as a block print because more than one parameter can be sent to a printer or computer as a block.
Selecting
YES displays a sublist for choosing the meter parameters to appear in the print block. All active parameters entered as
YES transmitted during a block print. Parameters entered as
YES
The “Print All” (
Prnt ALL
NO
in the sublist will be
will not be sent.
) option selects all meter values for transmitting
), without having to individually select each parameter in the sublist.
Note: Inactive parameters will not be sent regardless of the print option setting. For example, Counter B or Scale Factor B will only be sent if Counter
B is enabled (Dual Counter mode or batch count). Likewise, the Setpoint value(s) will not be sent unless an optional setpoint card is installed in the meter.
DISPLAY DESCRIPTION
Count A
Count b
RAtE
CntA ScF
Cntb ScF sSP1
SP2
Counter A
Counter B
Rate Value
Scale Factor A
Scale Factor B
Setpoint 1
Setpoint 2
CntA Ld
Counter A Count Load
FACTORY
SETTING
YES
NO
NO
NO
NO
NO
NO
NO
MNEMONIC
CTA
CTB
RTE
SFA
SFB
SP1
SP2
CLD PARITY BIT
PAritY
Odd
NO Odd EVEN
This parameter only appears when the Data Bit parameter is set to a
7-bit data word length. Parity is automatically
NO the parity bit to match that of the other serial equipment on the serial link. The meter ignores parity when receiving data and sets the parity bit for outgoing data. If parity is set to to 10 bits.
NO
if dAtA
is set for 8 bit.
Set
, an additional stop bit is used to force the frame size
METER ADDRESS
Addr
0
to
99
00
Enter the serial node address. With a single unit, an address is not needed and a value of zero can be used (RS232 applications). Otherwise, with multiple bussed units, a unique address number must be assigned to each meter. The node address applies specifically to RS485 applications.
ABBREVIATED PRINTING
Abbr
NO YES
NO
This parameter determines the formatting of data transmitted from the meter in response to a Transmit Value command or a Block Print Request. Select parameter data. Select
YES
NO for a full print transmission, consisting of the meter address, mnemonics, and
for abbreviated print transmissions, consisting of the parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent during a full transmission.)
COPY
COPY PROGRAM SETTINGS
NO YES
NO
This parameter is used to copy all the program settings from one CUB5 meter directly to another CUB5 meter, through the serial communications cards
(RS232 or RS485). The USB programming card cannot be used for the copy procedure. No PC connection or additional software is required. Copying program settings eliminates the need for repetitive programming when multiple meters use identical settings.
Copy Requirements:
To copy program settings from one meter to another requires the following:
1. Both meters must have the same software version (Version 3.1 or later). The version is displayed during the meter power-up sequence, or in Module 3 at the Software Version Display parameter. (See Module 3 for details)
2. The meter receiving the program settings (receiver) must have the Baud Rate set to 9600 baud. Since this is the factory default setting, a new meter will arrive ready for copying. The meter sending the program settings (master) should be set to the desired Baud Rate for the application (if different than
9600). This Baud Rate setting will then be copied to the receiver.
Copy Connections:
To connect the meters for copying, install a serial communications card of the same type into each meter (RS232 or RS485). Connect the meters using the proper cable listed in the chart.
TYPE
RS232
RS485
DESCRIPTION
Copy Cable RS232 10’ (RJ12-RJ12)
Copy Cable RS485 10’ (RJ12-RJ12)
PART NUMBER
CBLRLC02
CBLRLCS2
13
Copy Procedure:
1. Connect the master and receiver using the appropriate copy cable.
2. Apply power to the meters. The receiving meter must be operating in the normal display mode (not programming mode).
3. On the master meter, enter programming mode and proceed to the Copy
Program Settings parameter in Module 5. Select returns to normal operating mode, programmed with all the same settings as the master meter. The master remains at the another receiver for copying.
YES
to begin copying.
4. During the copy process (~ 2 sec.), the master meter displays an upload message (
UP-LOAd
) while the receiver displays a download message (
This indicates successful communication between the master and receiver. If the receiver message is not displayed, be sure the proper cable is connected.
5. When copying is complete, the receiver displays the power-up sequence and
COPY dn-LOAd
).
prompt, ready to connect
MASTER
SEL
UP-LOAd
RST
RECEIVER
SEL
dn-LOAd
RST
Sending Serial Commands and Data
When sending commands to the meter, a string containing at least one command character must be constructed. A command string consists of a command character, a value identifier, and numerical data (if writing data to the meter) followed by a command terminator character, * or $.
Command Chart
Command
N
T
V
R
P
Description
Node (meter)
Address Specifier
Transmit Value
(read)
Value Change (write)
Reset
Block Print Request
(read)
Notes
Address a specific meter. Must be followed by one or two digit node address. Not required when node address = 0.
Read a register from the meter. Must be followed by a register ID character.
Write to register of the meter. Must be followed by a register ID character and numeric data.
Reset a count value or setpoint output. Must be followed by a register ID character
Initiates a block print output. Registers in the print block are selected in Print Options.
Register Identification Chart
ID Value Description Transmit Details (T and V)
A Counter A
B Counter B
C Rate
D Scale Factor A
E Scale Factor B
F Setpoint 1
(Reset Output 1)
G Setpoint 2
(Reset Output 2)
H Counter A Count
Load Value
CTA
CTB
RTE
SFA
SFB
SP1
SP2
CLD
T, V, R
T, V, R
T
T, V
T, V,
T, V, R
T, V, R
T, V
8 digit positive/7 digit negative (with minus sign)
7 digit, positive only
6 digit, positive only
6 digit, positive only
6 digit, positive only per setpoint Assignment, same as Counter or Rate per setpoint Assignment, same as Counter or Rate
8 digit positive/7 digit negative (with minus sign)
Command String Construction
The command string must be constructed in a specific sequence. The meter does not respond with an error message to illegal commands. The following procedure details construction of a command string:
1. The first 2 or 3 characters consist of the Node Address Specifier (N) followed by a 1 or 2 character node address number. The node address number of the meter is programmable. If the node address is 0, this command and the node address itself may be omitted. This is the only command that may be used in conjunction with other commands.
2. After the optional address specifier, the next character is the command character.
3. The next character is the register ID. This identifies the register that the command affects. The P command does not require a register ID character. It prints all the active selections chosen in the Print Options menu parameter.
4. If constructing a value change command (writing data), the numeric data is sent next.
5. All command strings must be terminated with the string termination characters
* or $. The meter does not begin processing the command string until this character is received. See Command Response Time section for differences in meter response time when using the * and $ terminating characters.
Command String Examples:
1. Node address = 17, Write 350 to the Setpoint 1 value
String: N17VF350*
2. Node address = 5, Read Counter A, response time of 50 msec min
String: N5TA*
3. Node address = 0, Reset Setpoint 1 output
String: RF*
4. Node address = 31, Request a Block Print Output, response time of 2 msec min
String: N31P$
Transmitting Data to the Meter
Numeric data sent to the meter must be limited to transmit details listed in the
Register Identification Chart. Leading zeros are ignored. Negative numbers must have a minus sign. The meter ignores any decimal point and conforms the number to the scaled resolution. (For example: The meter’s scaled decimal point position is set for 0.0 and 25 is written to a register. The value of the register is now 2.5. In this case, write a value of 250 to equal 25.0).
Note: Since the meter does not issue a reply to value change commands, follow with a transmit value command for readback verification.
Receiving Data From The Meter
Data is transmitted from the meter in response to either a transmit command
(T), a block print request command (P) or a User Input print request. The response from the meter is either a full field transmission or an abbreviated transmission, depending on the selection chosen in Module 5.
Full Field Transmission
Byte
1, 2
3
Description
2 byte Node Address field [00-99]
<SP> (Space)
4-6
7-18
19
20
21
22
23
3 byte Register Mnemonic field
12 byte data field; 10 bytes for number, one byte for sign, one byte for decimal point
<CR> (carriage return)
<LF> (line feed)
<SP>* (Space)
<CR>* (carriage return)
<LF>* (line feed)
* These characters only appear in the last line of a block print.
The first two characters transmitted are the meter address. If the address assigned is 0, two spaces are substituted. A space follows the meter address field. The next three characters are the register mnemonic, as shown in the
Register Identification Chart.
The numeric data is transmitted next. The numeric field (bytes 7 to 18) is 12 characters long. When a requested counter or rate value exceeds the meter’s display limits, an * (used as an overflow character) replaces a space in byte 7.
Byte 8 is always a space.
The remaining ten positions of this field consist of a minus sign (for negative values), a floating decimal point (if applicable), and eight positions for the requested value. The data within bytes 9 to 18 is right-aligned with leading spaces for any unfilled positions.
The end of the response string is terminated with a <CR> and <LF>. After the last line of a block print, an extra <SP>, <CR> and <LF> are added to provide separation between the print blocks.
14
Abbreviated Transmission
Byte
1-12
13
Description
12 byte data field, 10 bytes for number, one byte for sign, one byte for decimal point
<CR> (carriage return)
14
15
16
17
<LF> (line feed)
<SP>* (Space)
<CR>* (carriage return)
<LF>* (line feed)
* These characters only appear in the last line of a block print.
The abbreviated response suppresses the node address and register ID, leaving only the numeric part of the response.
Meter Response Examples:
1. Node address = 17, full field response, Counter A = 875
17 CTA 875 <CR><LF>
2. Node address = 0, full field response, Setpoint 1 = -250.5
SP1 -250.5<CR><LF>
3. Node address = 0, abbreviated response, Setpoint 1 = 250, last line of block print
250<CR><LF><SP><CR><LF>
Command Response Time
The meter can only receive data or transmit data at any one time (half-duplex operation). During RS232 transmissions, the meter ignores commands while transmitting data, but instead uses RXD as a busy signal. When sending commands and data to the meter, a delay must be imposed before sending another command. This allows enough time for the meter to process the command and prepare for the next command.
At the start of the time interval t
1
, the computer program prints or writes the string to the com port, thus initiating a transmission. During t
1
, the command characters are under transmission and at the end of this period, the command terminating character (* or $) is received by the meter. The time duration of t is dependent on the number of characters and baud rate of the channel.
1
t
1
= (10 times the # of characters) / baud rate
At the start of time interval t
2
, the meter starts the interpretation of the command and when complete, performs the command function. This time interval t
2
varies. If no response from the meter is expected, the meter is ready to accept another command.
If the meter is to reply with data, the time interval t
2
is controlled by the use of the command terminating character. The ‘*’ terminating character results in a response time of 50 msec. minimum. This allows sufficient time for the release of the sending driver on the RS485 bus. Terminating the command line with ‘$’ results in a response time (t
2
) of 2 msec. minimum. The faster response time of this terminating character requires that sending drivers release within 2 msec. after the terminating character is received.
At the beginning of time interval t character of the reply. As with t
1
is dependent on the number of characters and baud rate of the channel. At the end of t ready to receive the next command.
3
, the meter responds with the first
, the time duration of t
3
3
, the meter is
t
3
= (10 times the # of characters) / baud rate
The maximum serial throughput of the meter is limited to the sum of the times t
1
, t
2
and t
3
.
NO REPLY FROM METER
Ready
Command
String
Transmission t
1
Meter
Response
Time t
2
Ready
Communication Format
Data is transferred from the meter through a serial communication channel.
In serial communications, the voltage is switched between a high and low level at a predetermined rate (baud rate) using ASCII encoding. The receiving device reads the voltage levels at the same intervals and then translates the switched levels back to a character. The voltage level conventions depend on the interface standard. The table lists the voltage levels for each standard.
LOGIC
1
INTERFACE STATE mark (idle)
RS232*
TXD,RXD; -3 to -15 V
0 space (active)
* Voltage levels at the Receiver
TXD,RXD; +3 to +15 V
RS485* a-b < -200 mV a-b > +200 mV
Data is transmitted one byte at a time with a variable idle period between characters (0 to
∞
). Each ASCII character is “framed” with a beginning start bit, an optional parity bit and one or more ending stop bits. The data format and baud rate must match that of other equipment in order for communication to take place. The figures list the data formats employed by the meter.
Character Frame Figure
Start Bit and Data Bits
Data transmission always begins with the start bit. The start bit signals the receiving device to prepare for reception of data. One bit period later, the least significant bit of the ASCII encoded character is transmitted, followed by the remaining data bits. The receiving device then reads each bit position as they are transmitted.
Parity Bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to a zero or a one, so that the total number of ones contained in the transmission
(including the parity bit) is either even or odd. This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission.
However, a single parity bit cannot detect errors that may occur to an even number of bits. Given this limitation, the parity bit is often ignored by the receiving device. The CUB5 meter ignores the parity bit of incoming data and sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop Bit
The last character transmitted is the stop bit. The stop bit provides a single bit period pause to allow the receiver to prepare to re-synchronize to the start of a new transmission (start bit of next byte). The receiver then continuously looks for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2 stop bits are sent from the meter.
RESPONSE FROM METER
Ready t
1
Command
Terminator
Received t
2
First
Character of Reply t
3
Reply
Transmission
Time
Timing Diagram Figure
Ready
15
RED LION CONTROLS TECHNICAL SUPPORT
If for any reason you have trouble operating, connecting, or simply have questions concerning your new product, contact Red Lion’s technical support.
Support: support.redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.
20 Willow Springs Circle York, PA 17406
16
This page intentionally left blank.
17
This page intentionally left blank.
18
COPYRIGHT
©2022 Red Lion Controls, Inc. All rights reserved. Red Lion and the Red Lion logo are trademarks of Red Lion Controls, Inc. All other company and product names are trademarks of their respective owners.
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net
) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR
THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT
TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF
FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF
INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW,
COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE.
Customer shall be responsible for determining that a Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii)
Customer alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET
FORTH IN PARAGRAPH (a) .
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL
OTHER DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT.
19
cuB5 proGraMMinG QuicK overview
Counter B Scale Factor
Counter B Batch Count
Software Ve
Default Settings
User Input Assignment
Display Colo
SP2 Output Of
Print Option
Standby Operatio
Meter Address
Baud Rate
Setpoint Select
20

Public link updated
The public link to your chat has been updated.
Advertisement