ABB 611 series 2.0 IEC/CN Operation Manual

ABB 611 series 2.0 IEC/CN Operation Manual

Add to My manuals
140 Pages

advertisement

ABB 611 series 2.0 IEC/CN Operation Manual | Manualzz

RELION® PROTECTION AND CONTROL

611 series

Operation Manual

Document ID: 1MRS757453

Issued: 2019-04-10

Revision: C

Product version: 2.0

© Copyright 2019 ABB. All rights reserved

Copyright

This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

www.abb.com/relion

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties.

All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.

This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network.

It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses.

This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN

60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Safety information

Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantial property damage.

Only a competent electrician is allowed to carry out the electrical installation.

National and local electrical safety regulations must always be followed.

The frame of the protection relay has to be carefully earthed.

When the plug-in unit has been detached from the case, do not touch the inside of the case. The relay case internals may contain high voltage potential and touching these may cause personal injury.

The protection relay contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided.

Whenever changes are made in the protection relay, measures should be taken to avoid inadvertent tripping.

Table of contents

611 series

Operation Manual

Table of contents

Section 1 Introduction.......................................................................7

This manual........................................................................................ 7

Intended audience.............................................................................. 7

Product documentation.......................................................................8

Product documentation set............................................................8

Document revision history............................................................. 8

Related documentation..................................................................9

Symbols and conventions...................................................................9

Symbols.........................................................................................9

Document conventions..................................................................9

Functions, codes and symbols.................................................... 10

Section 2 Environmental aspects...................................................15

Sustainable development................................................................. 15

Disposal of a protection relay........................................................... 15

Section 3 611 series overview........................................................17

Overview...........................................................................................17

Local HMI......................................................................................... 17

Display.........................................................................................18

LEDs............................................................................................19

Keypad........................................................................................ 20

Local HMI functionality................................................................ 22

Protection and alarm indication.............................................. 22

Parameter management ........................................................23

Front communication..............................................................24

Web HMI...........................................................................................24

Command buttons....................................................................... 26

Authorization.....................................................................................27

Audit trail......................................................................................28

Communication.................................................................................30

Self-healing Ethernet ring............................................................30

Ethernet redundancy................................................................... 31

Secure communication................................................................33

PCM600 tool.....................................................................................34

Connectivity packages.................................................................34

PCM600 and relay connectivity package version........................34

Section 4 Using the HMI.................................................................37

Using the local HMI.......................................................................... 37

1

2

Table of contents

Logging in....................................................................................37

Logging out..................................................................................38

Turning the display backlight on..................................................38

Selecting local or remote use...................................................... 39

Identifying the device...................................................................39

Identifying relay's IEC 61850 version..................................... 40

Adjusting the display contrast......................................................40

Changing the local HMI language............................................... 41

Changing display symbols...........................................................41

Changing setting visibility............................................................ 41

Navigating in the menu................................................................42

Menu structure....................................................................... 42

Scrolling the display............................................................... 43

Changing the default view...................................................... 43

Browsing setting values...............................................................43

Editing values.............................................................................. 44

Editing numerical values........................................................ 44

Editing string values............................................................... 46

Editing enumerated values.....................................................46

Committing settings.....................................................................46

Clearing and acknowledging....................................................... 47

Using the local HMI help..............................................................48

Using the Web HMI.......................................................................... 48

Logging in....................................................................................48

Logging out..................................................................................49

Identifying device.........................................................................49

Navigating in menus....................................................................50

Menu structure....................................................................... 51

Showing parameters....................................................................52

Editing values.............................................................................. 55

Committing settings.....................................................................58

Clearing and acknowledging....................................................... 60

Selecting programmable LEDs view............................................61

Selecting event view....................................................................62

Selecting disturbance records view.............................................64

Saving disturbance records....................................................64

Triggering disturbance recorder manually..............................65

Deleting disturbance records..................................................66

Selecting phasor diagrams..........................................................66

Selecting fault records.................................................................69

Selecting signal configuration......................................................71

Import and export of settings.......................................................76

Exporting settings ..................................................................76

611 series

Operation Manual

611 series

Operation Manual

Table of contents

Importing settings .................................................................. 77

Exporting report summary........................................................... 79

Using Web HMI help....................................................................80

Section 5 IED operation ................................................................ 83

Normal operation.............................................................................. 83

Disturbance identification................................................................. 83

Disturbance recording triggering................................................. 84

Disturbance record analysis........................................................ 84

Disturbance reports..................................................................... 84

Relay self-supervision................................................................. 84

Relay parametrization.......................................................................85

Settings for relay functionality......................................................85

Settings for different operating conditions................................... 85

Section 6 Operating procedures.....................................................87

Monitoring.........................................................................................87

Indications................................................................................... 87

Monitoring indication messages............................................. 87

Monitoring an internal relay fault ........................................... 87

Monitoring condition monitoring data..................................... 88

Measured and calculated values.................................................88

Measured values.................................................................... 88

Using the local HMI for monitoring......................................... 89

Recorded data.............................................................................89

Creating disturbance recordings............................................ 89

Monitoring disturbance recorder data.....................................90

Controlling and reading of disturbance recorder data............ 90

Monitoring fault records..........................................................91

Monitoring events................................................................... 91

Remote monitoring...................................................................... 92

Monitoring protection relays remotely.................................... 92

Controlling........................................................................................ 92

Controlling via the control menu..................................................92

Controlling with the closing delay................................................ 93

Resetting IED................................................................................... 94

Clearing and acknowledging via the local HMI............................94

Changing the IED functionality......................................................... 95

Defining the setting group............................................................95

Activating a setting group....................................................... 95

Copying a setting group......................................................... 96

Browsing and editing setting group values.............................96

Activating programmable LEDs...................................................97

Setting autoscroll delay............................................................... 98

3

4

Table of contents

Section 7 Troubleshooting .............................................................99

Fault tracing......................................................................................99

Identifying hardware errors..........................................................99

Identifying runtime errors.............................................................99

Identifying communication errors.................................................99

Checking front communication link operation.........................99

Checking time synchronization.............................................100

Running the display test............................................................ 100

Indication messages.......................................................................100

Internal faults.............................................................................100

Warnings................................................................................... 102

Correction procedures.................................................................... 103

Rebooting the software..............................................................103

Restoring factory settings..........................................................103

Setting passwords..................................................................... 104

Identifying relay application problems....................................... 104

Inspecting wiring...................................................................105

Sample data interruptions.................................................... 105

Section 8 Commissioning.............................................................107

Commissioning checklist................................................................ 107

Checking the installation.................................................................107

Checking of the power supply................................................... 107

Checking CT circuits..................................................................108

Checking VT circuits..................................................................108

Checking binary input and output circuits..................................109

Checking binary input circuits...............................................109

Checking binary output circuits............................................ 109

Authorizations.................................................................................110

User authorization..................................................................... 110

Setting IED and communication..................................................... 111

Setting the communication between protection relays and

PCM600.....................................................................................111

Communication link options between PCM600 and protection relays................................................................... 111

Communication settings............................................................ 112

Serial communication ports and drivers............................... 113

Serial link diagnostics and monitoring.................................. 114

Defining Ethernet port settings............................................. 116

Defining serial port settings.................................................. 116

Setting communication protocol parameters........................ 117

Connecting jumper connectors.............................................117

Setting the local HMI................................................................. 117

611 series

Operation Manual

611 series

Operation Manual

Table of contents

Changing the local HMI language........................................ 117

Adjusting the display contrast...............................................117

Changing display symbols....................................................118

Changing the default view.................................................... 118

Setting the system time and time synchronization............... 118

Setting IED parameters............................................................. 120

Defining setting groups.........................................................120

Relay parametrization.......................................................... 122

Defining disturbance recorder channel settings................... 123

Configuring analog inputs.....................................................123

Testing protection relay operation.................................................. 123

Selecting the IED test mode......................................................123

Testing the digital I/O interface..................................................124

Testing functions....................................................................... 124

Selecting the internal fault test.................................................. 125

Selecting the IED blocked or IED test and blocked mode.........125

ABB Product Data Registration...................................................... 126

Section 9 Glossary....................................................................... 127

5

6

1MRS757453 C

Section 1 Introduction

1.1

1.2

Section 1

Introduction

This manual

The operation manual contains instructions on how to operate the protection relay once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the relay. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault.

Intended audience

This manual addresses the operator, who operates the protection relay on a daily basis.

The operator must be trained in and have a basic knowledge of how to operate protection equipment. The manual contains terms and expressions commonly used to describe this kind of equipment.

611 series

Operation Manual

7

Section 1

Introduction

1.3

1.3.1

Product documentation

Product documentation set

1MRS757453 C

8

1.3.2

Quick start guide

Quick installation guide

Brochure

Product guide

Operation manual

Installation manual

Connection diagram

Engineering manual

Technical manual

Application manual

Communication protocol manual

IEC 61850 engineering guide

Point list manual

Cyber security deployment guideline

GUID-0777AFDA-CADF-4AA9-946E-F6A856BDF75E V1 EN

Figure 1: The intended use of manuals in different lifecycles

Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion .

Document revision history

Document revision/date

A/2011-11-18

B/2016-02-22

Product series version

1.0

2.0

C/2019-04-10 2.0

History

First release

Content updated to correspond to the product series version

Content updated

Download the latest documents from the ABB Web site http://www.abb.com/substationautomation .

611 series

Operation Manual

1MRS757453 C

1.3.3

1.4

1.4.1

1.4.2

611 series

Operation Manual

Section 1

Introduction

Related documentation

Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation .

Symbols and conventions

Symbols

The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

Document conventions

A particular convention may not be used in this manual.

• Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using the push button icons.

9

Section 1

Introduction

1.4.3

10

1MRS757453 C

To navigate between the options, use and .

• Menu paths are presented in bold.

Select Main menu/Settings .

• WHMI menu names are presented in bold.

Click Information in the WHMI menu structure.

• LHMI messages are shown in Courier font.

To save the changes in nonvolatile memory, select Yes and press .

• Parameter names are shown in italics.

The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks.

The corresponding parameter values are "On" and "Off".

• Input/output messages and monitored data names are shown in Courier font.

When the function starts, the START output is set to TRUE.

• This document assumes that the parameter setting visibility is "Advanced".

Functions, codes and symbols

All available functions are listed in the table. All of them may not be applicable to all products.

Table 1:

Function

Protection

Functions included in the relays

IEC 61850

Three-phase non-directional overcurrent protection, low stage, instance 1

Three-phase non-directional overcurrent protection, high stage, instance 1

Three-phase non-directional overcurrent protection, high stage, instance 2

Three-phase non-directional overcurrent protection, instantaneous stage, instance 1

Non-directional earth-fault protection, low stage, instance 1

Non-directional earth-fault protection, low stage, instance 2

Non-directional earth-fault protection, high stage, instance 1

Non-directional earth-fault protection, instantaneous stage

Three-phase directional overcurrent protection, low stage, instance 1

Three-phase directional overcurrent protection, low stage, instance 2

Table continues on next page

PHLPTOC1

PHHPTOC1

PHHPTOC2

PHIPTOC1

EFLPTOC1

EFLPTOC2

EFHPTOC1

EFIPTOC1

DPHLPDOC1

DPHLPDOC2

IEC 60617

3I> (1)

3I>> (1)

3I>> (2)

3I>>> (1)

Io> (1)

Io> (2)

Io>> (1)

Io>>>

3I> -> (1)

3I> -> (2)

IEC-ANSI

51P-1 (1)

51P-2 (1)

51P-2 (2)

50P/51P (1)

51N-1 (1)

51N-1 (2)

51N-2 (1)

50N/51N

67-1(1)

67-1(2)

611 series

Operation Manual

1MRS757453 C

611 series

Operation Manual

Section 1

Introduction

Function

Three-phase directional overcurrent protection, high stage, instance 1

Directional earth-fault protection, low stage, instance 1

Directional earth-fault protection, low stage, instance 2

Directional earth-fault protection, high stage

Transient/intermittent earth-fault protection

Non-directional (cross-country) earth fault protection, using calculated Io

Negative-sequence overcurrent protection, instance 1

Negative-sequence overcurrent protection, instance 2

Negative-sequence overcurrent protection for machines, instance 1

Negative-sequence overcurrent protection for machines, instance 2

Phase discontinuity protection

Residual overvoltage protection, instance 1

Residual overvoltage protection, instance 2

Residual overvoltage protection, instance 3

Three-phase undervoltage protection, instance 1

Three-phase undervoltage protection, instance 2

Three-phase undervoltage protection, instance 3

Three-phase overvoltage protection, instance 1

Three-phase overvoltage protection, instance 2

Three-phase overvoltage protection, instance 3

Positive-sequence undervoltage protection, instance 1

Positive-sequence undervoltage protection, instance 2

Negative-sequence overvoltage protection, instance 1

Negative-sequence overvoltage protection, instance 2

Frequency protection, instance 1

Table continues on next page

IEC 61850

DPHHPDOC1

DEFLPDEF1

DEFLPDEF2

DEFHPDEF1

INTRPTEF1

EFHPTOC1

NSPTOC1

NSPTOC2

MNSPTOC1

MNSPTOC2

PDNSPTOC1

ROVPTOV1

ROVPTOV2

ROVPTOV3

PHPTUV1

PHPTUV2

PHPTUV3

PHPTOV1

PHPTOV2

PHPTOV3

PSPTUV1

PSPTUV2

NSPTOV1

NSPTOV2

FRPFRQ1

Uo> (2)

Uo> (3)

3U< (1)

3U< (2)

3U< (3)

I2> (2)

I2>M (1)

I2>M (2)

I2/I1>

Uo> (1)

IEC 60617

3I>> -> (1)

Io> -> (1)

Io> -> (2)

Io>> ->

Io> -> IEF

Io>> (1)

I2> (1)

3U> (1)

3U> (2)

3U> (3)

U1< (1)

U1< (2)

U2> (1)

U2> (2) f>/f<,df/dt (1)

59G (2)

59G (3)

27(1)

27(2)

27(3)

46 (2)

46M (1)

46M (2)

46PD

59G (1)

IEC-ANSI

67-2(1)

67N-1 (1)

67N-1 (2)

67N-2

67NIEF

51N-2 (1)

46 (1)

59(1)

59(2)

59(3)

47U+(1)

47U+(2)

47O-(1)

47O-(2)

81(1)

11

Section 1

Introduction

12

1MRS757453 C

Function

Frequency protection, instance 2

Three-phase thermal protection for feeders, cables and distribution transformers

Loss of load supervision

Motor load jam protection

Motor start-up supervision

Phase reversal protection

Thermal overload protection for motors

Circuit breaker failure protection

Three-phase inrush detector

Master trip, instance 1

Master trip, instance 2

High-impedance differential protection for phase A, instance 1

High-impedance differential protection for phase B, instance 2

High-impedance differential protection for phase C, instance 3

Switch onto fault

Other

Input switch group

Output switch group

Selector

Minimum pulse timer (2 pcs)

Minimum pulse timer (2 pcs, second resolution), instance 1

Move (8 pcs), instance 1

Control

Circuit-breaker control

Emergency start-up

Autoreclosing

Condition monitoring and supervision

Trip circuit supervision, instance 1

Trip circuit supervision, instance 2

Runtime counter for machines and devices

Phase segregated CT supervision function for phase A, instance 1

Phase segregated CT supervision function for phase B, instance 2

Phase segregated CT supervision function for phase C, instance 3

Table continues on next page

IEC 61850

FRPFRQ2

T1PTTR1

LOFLPTUC1

JAMPTOC1

STTPMSU1

PREVPTOC1

MPTTR1

CCBRBRF1

INRPHAR1

TRPPTRC1

TRPPTRC2

HIAPDIF1

HIBPDIF1

HICPDIF1

CBPSOF1

ISWGAPC

OSWGAPC

SELGAPC

TPGAPC

TPSGAPC

MVGAPC

CBXCBR1

ESMGAPC1

DARREC1

TCSSCBR1

TCSSCBR2

MDSOPT1

HZCCASPVC1

HZCCBSPVC1

HZCCCSPVC1

I <-> O CB

ESTART

O -> I

TCS (1)

TCS (2)

OPTS

MCS 1I(1)

MCS 1I(2)

MCS 1I(3)

IEC 60617 f>/f<,df/dt (2)

IEC-ANSI

81(2)

3Ith>F 49F

3I<

Ist>

Is2t n<

I2>>

3Ith>M

37

51LR

49,66,48,51LR

46R

49M

3I>/Io>BF

3I2f>

51BF/51NBF

68

Master Trip (1) 94/86 (1)

Master Trip (2) 94/86 (2) dHi>(1) 87(1) dHi>(2) 87(2) dHi>(3)

SOTF

87(3)

SOTF

ISWGAPC

OSWGAPC

SELGAPC

TP

TPS (1)

MV (1)

ISWGAPC

OSWGAPC

SELGAPC

TP

TPS (1)

MV (1)

I <-> O CB

ESTART

79

TCM (1)

TCM (2)

OPTM

MCS 1I(1)

MCS 1I(2)

MCS 1I(3)

611 series

Operation Manual

1MRS757453 C

Section 1

Introduction

Function

Logging

Disturbance recorder

Fault recorder

Measurement

Three-phase current measurement, instance 1 1)

Sequence current measurement

Residual current measurement, instance 1

Three-phase voltage measurement, instance 1

IEC 61850

RDRE1

FLTRFRC1

CMMXU1

CSMSQI1

RESCMMXU1

VMMXU1

Three-phase voltage measurement, instance 2

Sequence voltage measurement, instance 1

Residual voltage measurement

VMMXU2

VSMSQI1

RESVMMXU1

Frequency measurement, instance 1 FMMXU1

Three-phase power and energy measurement, instance 1

PEMMXU1

IEC 60617 f

-

DR (1)

3I

I1, I2, I0

Io

3U

3U(B)

U1, U2, U0

Uo

P, E

1) In REB611, CMMXU is used for measuring differential phase currents

IEC-ANSI

DFR(1)

FR

3I

I1, I2, I0

In

3U

3U(B)

U1, U2, U0 f

Vn

P, E

611 series

Operation Manual

13

14

1MRS757453 C

Section 2 Environmental aspects

Section 2

Environmental aspects

2.1

2.2

611 series

Operation Manual

Sustainable development

Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the protection relay.

The choice of materials and the suppliers have been made according to the EU RoHS directive (2002/95/EC). This directive limits the use of hazardous substances which are the following:

Table 2: Maximum concentration values by weight per homogeneous material

Substance

Lead - Pb

Mercury - Hg

Cadmium - Cd

Hexavalent Chromium Cr (VI)

Polybrominated biphenyls - PBB

Polybrominated diphenyl ethers - PBDE

Proposed maximum concentration

0.1%

0.1%

0.01%

0.1%

0.1%

0.1%

Operational reliability and long life time have been assured with extensive testing during the design and manufacturing processes. Moreover, long life time is supported by maintenance and repair services as well as by the availability of spare parts.

Design and manufacturing have been done under a certified environmental system.

The effectiveness of the environmental system is constantly evaluated by an external auditing body. We follow environmental rules and regulations systematically to evaluate their effect on our products and processes.

Disposal of a protection relay

Definitions and regulations of hazardous materials are country-specific and change when the knowledge of materials increases. The materials used in this product are typical for electric and electronic devices.

All parts used in this product are recyclable. When disposing of a protection relay or its parts contact a local waste handler who is authorized and specialized in disposing of electronic waste. These handlers can sort the material by using dedicated sorting processes and dispose of the product according to the local requirements.

15

Section 2

Environmental aspects

1MRS757453 C

Table 3:

Protection relay

Case

Plug-in unit

Package

Attached material

Materials of the protection relay parts

Parts Material

Metallic plates, parts and screws Steel

Plastic parts

Electronics plug in module

Electronics plug in modules

Electronics LHMI module

Plastic parts

PC 1) , LCP

Various

Various

Various

PC, PBT 3)

2)

, LCP, PA 4)

Metallic parts

Box

Manuals

Aluminium

Cardboard

Paper

1) Polycarbonate

2) Liquid crystal polymer

3) Polybutylene terephthalate

4) Polyamide

16 611 series

Operation Manual

1MRS757453 C

Section 3 611 series overview

3.1

3.2

Section 3

611 series overview

Overview

The 611 series is part of ABB’s Relion® product family. The 611 series protection relays offer functionality within basic protection and control configurations. There are product variants for feeder, motor, busbar and voltage protection applications. The relays, characterized by their compactness and withdrawable-unit design, are designed for most utility substations and industrial power systems including radial, looped and meshed distribution networks that may also involve distributed power generation.

The 611 series relays support the Edition 1 and Edition 2 versions of the IEC 61850 standard for communication and interoperability of substation automation devices, including fast GOOSE messaging. The 611 series relays are able to use IEC 61850 and

Modbus® communication protocols simultaneously. The relays also support the parallel redundancy protocol PRP and the high-availability seamless redundancy

HSR protocol. IEEE 1588 v2 is available for high-accuracy time synchronization in all variants with an optional redundant Ethernet communication module.

Local HMI

The LHMI is used for setting, monitoring and controlling the protection relay. The

LHMI comprises the display, buttons, LED indicators and communication port.

611 series

Operation Manual

17

Section 3

611 series overview

1MRS757453 C

REF611

Overcurrent

Earth-fault

Phase unbalance

Thermal overload

AR sequence in progress

Disturb.rec.trigged

Trip circuit failure

Breaker failure

3.2.1

18

GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN

Figure 2: Example of the LHMI

Display

The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.

Table 4: Small display

Character size 1)

Small, mono-spaced (6 × 12 pixels)

Large, variable width (13 × 14 pixels)

1) Depending on the selected language

Rows in the view

5

3

Characters per row

20

8 or more

The display view is divided into four basic areas.

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview

1 2

3.2.2

611 series

Operation Manual

3

GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN

Figure 3: Display layout

1 Header

2 Icon

3 Content

4 Scroll bar (displayed when needed)

4

• The header area at the top of the display view shows the current location in the menu structure.

• The icon area at the upper right corner of the display shows the current action or user level.

Current action is indicated by the following characters.

U: Font/Firmware is being updated

S: Parameters are being stored

!: Warning and/or indication

Current user level is indicated by the following characters.

V: Viewer

O: Operator

E: Engineer

A: Administrator

• The content area shows the menu content.

• If the menu contains more rows than the display can show at a time, a scroll bar is displayed on the right.

The display is updated either cyclically or based on changes in the source data such as parameters or events.

LEDs

The LHMI includes three protection indicators above the display: Ready, Start and

Trip.

19

Section 3

611 series overview

3.2.3

1MRS757453 C

There are also 8 programmable LEDs on front of the LHMI. The LEDs can be configured with the LHMI, WHMI or PCM600.

Keypad

The LHMI keypad contains push buttons which are used to navigate in different views or menus. With the push buttons you can give open or close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.

20

GUID-A9613A2B-0084-4D1D-A4E3-D04E72A1728E V1 EN

Figure 4: LHMI keypad with object control, navigation and command push buttons and RJ-45 communication port

1 Close

2 Escape

3 Up

4 Enter

5 Uplink LED

6 Communication LED

7 Open

8 Left

9 Down

10 Right

11 Remote/Local

12 Help

13 Communication port

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview

Object control

If the control position of the IED is set to local with the R/L button, the IED can be controlled using the object control buttons.

Table 5:

Name

Close

Object control push buttons

Description

Closing the object.

Opening the object.

Open

Navigation

The arrow buttons are used for navigation. To scroll information, press the arrow button several times or simply keep it pressed down.

Table 6:

Name

ESC

Navigation push buttons

Description

Leaving setting mode without saving the values.

Cancelling certain actions.

Adjusting the display contrast in combination with or .

Changing the language in combination with .

Inserting a space in combination with when editing a string.

Clearing indications and LEDs. The first three-second press clears the indications. The second three-second press clears the programmable

LEDs. Requires appropriate user rights.

Enter

Up

Down

• Entering parameter setting mode.

Confirming a new value of a setting parameter.

Moving up and down in menus.

Scrolling active digits of a parameter when entering a new setting value.

Left

Right

Moving left and right in menus.

Changing the active digit of a parameter when entering a new setting value.

Deleting a character when editing a string by pressing .

Logging out, when the user is currently logged in. Press for three seconds in the main menu.

611 series

Operation Manual

21

Section 3

611 series overview

3.2.4

3.2.4.1

1MRS757453 C

Commands

Table 7:

Name

R/L

Command push buttons

Description

Changing the control position (remote or local) of the device.

When the R LED is lit, remote control is enabled and local control disabled.

When the L LED is lit, local control is enabled and remote control disabled.

When none of the LEDs are lit, both control positions are disabled.

Showing context sensitive help messages.

Help

Local HMI functionality

Protection and alarm indication

Protection indicators

The protection indicator LEDs are Ready, Start and Trip.

Table 8:

LED state

Off

On

Flashing

Ready LED

Description

Auxiliary supply voltage is disconnected.

Normal operation.

Internal fault has occurred or the protection relay is in test mode. Internal faults are accompanied by an indication message.

Table 9:

LED state

Off

On

Flashing

Start LED

Description

Normal operation.

A protection function has started and an indication message is displayed.

• If several protection functions start within a short time, the last start is indicated on the display.

A protection function is blocked or the protection relay is in the test and blocked mode.

The blocking indication disappears when the blocking is removed or when the protection function is reset.

22 611 series

Operation Manual

1MRS757453 C

3.2.4.2

611 series

Operation Manual

Section 3

611 series overview

Table 10:

LED state

Off

On

Trip LED

Description

Normal operation.

A protection function has tripped and an indication message is displayed.

• The trip indication is latching and must be reset via communication.

If several protection functions trip within a short time, the last trip is indicated on the display.

Alarm indicators

The 8 matrix programmable LEDs are used for alarm indication.

Table 11:

LED state

Off

On

Alarm indications

Description

Normal operation. All activation signals are off.

Non-latched mode: activation signal is still on.

Latched mode: activation signal is still on, or it is off but has not been acknowledged.

Latched flashing mode: activation signal is still on but has been acknowledged.

Flashing

• Non-latched flashing mode: activation signal is still on.

Latched flashing mode: activation signal is still on, or it is off but has not been acknowledged.

Parameter management

The LHMI is used to access the relay parameters. Three types of parameters can be read and written.

• Numerical values

• String values

• Enumerated values

Numerical values are presented either in integer or in decimal format with minimum and maximum values. Character strings can be edited character by character.

Enumerated values have a predefined set of selectable values.

Changing the function block on or off affects the visibility of its parameters in the menu.

Changing the value of certain relay parameters affects the visibility or range of other parameters in the menu. This indicates which parameters or parameter values become obsolete due to the change.

23

Section 3

611 series overview

3.2.4.3

1MRS757453 C

The relay changes the visibility or range of these parameters immediately even before the changed values have been committed.

Some parameters may be hidden because the function is off or the setting visibility is set to “basic” instead of “advanced”.

Front communication

The RJ-45 port in the LHMI enables front communication. Two LEDs are located above the communication port.

• The green uplink LED on the left is lit when the cable is successfully connected to the port.

• The yellow communication LED on the right flashes when the protection relay communicates with the connected device.

1 2

3.3

24

A070816 V2 EN

Figure 5: RJ-45 communication port and indication LEDs

1 Uplink LED

2 Communication LED

When a computer is connected to the protection relay, the relay's DHCP server for the front interface assigns an IP address to the computer. The fixed IP address for the front port is 192.168.0.254.

Web HMI

The WHMI allows secure access to the protection relay via a Web browser. When the

Secure Communication parameter in the protection relay is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The

WHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview

WHMI is enabled by default. To disable the WHMI, select Main

Menu/Configuration/HMI/Web HMI mode via the LHMI. Reboot the protection relay for the change to take effect.

WHMI offers several functions.

• Programmable LEDs and event lists

• System supervision

• Parameter settings

• Measurement display

• Disturbance records

• Fault records

• Phasor diagram

• Signal configuration

• Importing/Exporting parameters

• Report summary

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

611 series

Operation Manual

GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V2 EN

Figure 6: Example view of the WHMI

The WHMI can be accessed locally and remotely.

• Locally by connecting the laptop to the protection relay via the front communication port.

• Remotely over LAN/WAN.

25

Section 3

611 series overview

3.3.1

1MRS757453 C

Command buttons

Command buttons can be used to edit parameters and control information via the

WHMI.

Table 12:

Name

Command buttons

Description

Enabling parameter editing

Disabling parameter editing

Writing parameters to the protection relay

Refreshing parameter values

Printing out parameters

Committing changes to protection relay's nonvolatile flash memory

Rejecting changes

Showing context sensitive help messages

Error icon

Clearing events

Triggering the disturbance recorder manually

Saving values to TXT or CSV file format

Freezing the values so that updates are not displayed

Receiving continuous updates to the monitoring view

Deleting the disturbance record

Deleting all disturbance records

Saving the disturbance record files

Viewing all fault records

Clearing all fault records

Importing settings

Exporting settings

Table continues on next page

26 611 series

Operation Manual

1MRS757453 C

3.4

Name Description

Selecting all

Clearing all selections

Refreshing the parameter list view

Section 3

611 series overview

Authorization

Four user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords.

The default passwords in the protection relay delivered from the factory can be changed with Administrator user rights.

User authorization is disabled by default for the LHMI and can be enabled with the Local override parameter via the LHMI path Main

Menu/Configuration/Authorization/Passwords . WHMI always requires authentication.

Table 13:

Username

VIEWER

OPERATOR

ENGINEER

ADMINISTRATOR

Predefined user categories

User rights

Read only access

Selecting remote or local state with (only locally)

Changing setting groups

Controlling

Clearing indications

Changing settings

Clearing event list

Clearing disturbance records

Changing system settings such as IP address, serial baud rate or disturbance recorder settings

Setting the protection relay to test mode

Selecting language

All listed above

Changing password

Factory default activation

For user authorization for PCM600, see PCM600 documentation.

611 series

Operation Manual

27

Section 3

611 series overview

3.4.1

28

1MRS757453 C

Audit trail

The protection relay offers a large set of event-logging functions. Critical system and protection relay security-related events are logged to a separate nonvolatile audit trail for the administrator.

Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of system and security-related events and changes in the protection relay. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in LHMI and WHMI and Event Viewer in PCM600.

The protection relay stores 2048 audit trail events to the nonvolatile audit trail.

Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. Nonvolatile memory is based on a memory type which does not need battery backup nor regular component change to maintain the memory storage.

Audit trail events related to user authorization (login, logout, violation remote and violation local) are defined according to the selected set of requirements from IEEE

1686. The logging is based on predefined user names or user categories. The user audit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.

Table 14: Audit trail events

Audit trail event

Configuration change

Firmware change

Firmware change fail

Attached to retrofit test case

Removed from retrofit test case

Setting group remote

Setting group local

Control remote

Control local

Test on

Test off

Reset trips

Setting commit

Time change

View audit log

Login

Logout

Description

Configuration files changed

Firmware changed

Firmware change failed

Unit has been attached to retrofit case

Removed from retrofit test case

User changed setting group remotely

User changed setting group locally

DPC object control remote

DPC object control local

Test mode on

Test mode off

Reset latched trips (TRPPTRC*)

Settings have been changed

Time changed directly by the user. Note that this is not used when the protection relay is synchronised properly by the appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).

Administrator accessed audit trail

Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or

LHMI.

Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or

LHMI.

Table continues on next page

611 series

Operation Manual

1MRS757453 C

611 series

Operation Manual

Section 3

611 series overview

Audit trail event

Password change

Firmware reset

Audit overflow

Violation remote

Violation local

Description

Password changed

Reset issued by user or tool

Too many audit events in the time period

Unsuccessful login attempt from IEC 61850-8-1 (MMS),

WHMI, FTP or LHMI.

Unsuccessful login attempt from IEC 61850-8-1 (MMS),

WHMI, FTP or LHMI.

PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in

PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.

Audit trail events can be configured to be visible also in LHMI/WHMI Event list together with process related events.

To expose the audit trail events through Event list, define the

Authority logging level parameter via Configuration/

Authorization/Security . This exposes audit trail events to all users.

Table 15:

Audit trail event

Comparison of authority logging levels

Configuration change

Firmware change

None

Configurati on change

Authority logging level

Setting group

Setting group, control

● ●

Firmware change fail

Attached to retrofit test case

Removed from retrofit test case

Setting group remote

● Setting group local

Control remote

Control local

Test on

Test off

Reset trips

Setting commit

Time change

View audit log

Login

Table continues on next page

Settings edit

All

29

Section 3

611 series overview

3.5

3.5.1

30

1MRS757453 C

Audit trail event

Logout

Password change

Firmware reset

Violation local

Violation remote

Authority logging level

Communication

The protection relay supports a range of communication protocols including IEC

61850 and Modbus ® . Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the protection relays, is only enabled by the IEC

61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file format. The protection relay can send and receive binary signals from other devices

(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. The protection relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard.

The protection relay can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus.

All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The protection relay can be connected to

Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber-optic LC connector (100Base-FX). An optional serial interface is available for

RS-485 communication.

Self-healing Ethernet ring

For the correct operation of self-healing loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The protection relay itself does not support link-down detection or RSTP.

The ring recovery process is based on the aging of the MAC addresses, and the linkup/link-down events can cause temporary breaks in communication. For a better performance of the self-healing loop, it is recommended that the external switch

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview furthest from the protection relay loop is assigned as the root switch (bridge priority

= 0) and the bridge priority increases towards the protection relay loop. The end links of the protection relay loop can be attached to the same external switch or to two adjacent external switches. A self-healing Ethernet ring requires a communication module with at least two Ethernet interfaces for all protection relays.

Client A Client B

Manag ed Eth ernet switch with RSTP su pport

Manag ed Eth ernet switch with RSTP su pport

Network

Network

3.5.2

611 series

Operation Manual

GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V2 EN

Figure 7: Self-healing Ethernet ring solution

Ethernet redundancy

IEC 61850 specifies a network redundancy scheme that improves the system availability for substation communication. It is based on two complementary protocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocol

PRP and high-availability seamless redundancy HSR protocol. Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection. Therefore, both are able to overcome the failure of a link or switch with a zero-switchover time, thus fulfilling the stringent real-time requirements for the substation automation horizontal communication and time synchronization.

PRP specifies that each device is connected in parallel to two local area networks.

HSR applies the PRP principle to rings and to the rings of rings to achieve costeffective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for all 611 series protection relays.

IEC 62439-3:2012 cancels and replaces the first edition published in

2010. These standard versions are also referred to as IEC 62439-3

31

Section 3

611 series overview

1MRS757453 C

Edition 1 and IEC 62439-3 Edition 2. The protection relay supports

IEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.

PRP

Each PRP node, called a double attached node with PRP (DAN), is attached to two independent LANs operated in parallel. These parallel networks in PRP are called

LAN A and LAN B. The networks are completely separated to ensure failure independence, and they can have different topologies. Both networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid communication failures. Non-PRP nodes, called single attached nodes (SANs), are either attached to one network only (and can therefore communicate only with

DANs and SANs attached to the same network), or are attached through a redundancy box, a device that behaves like a DAN.

Managed

Ethernet switch

IEC 61850 PRP

Managed

Ethernet switch

32

GUID-AA005F1B-A30B-48F6-84F4-A108F58615A2 V1 EN

Figure 8: PRP solution

In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an

Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames. In some cases, default

PC workstation adapters are not able to handle the maximum-length Ethernet frames with the PRP trailer.

There are different alternative ways to connect a laptop or a workstation as SAN to a

PRP network.

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview

• Via an external redundancy box (RedBox) or a switch capable of connecting to

PRP and normal networks

• By connecting the node directly to LAN A or LAN B as SAN

• By connecting the node to the protection relay's interlink port

HSR

HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames, one over each port. Both frames circulate in opposite directions over the ring and each node forwards the frames it receives, from one port to the other. When the originating node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring protocol is needed. Individually attached nodes, SANs, such as laptops and printers, must be attached through a “redundancy box” that acts as a ring element. For example, a 615 or 620 series protection relay with HSR support can be used as a redundancy box.

Devices not supporting HSR

Ethernet switch

Redundancy box

Redundancy box

Redundancy box

X

X

IEC 61850 HSR

X

Unicast traffic

Message is recognized as a duplicat e and is immediately forwarded

Sending device removes the message from t he ri ng

3.5.3

611 series

Operation Manual

GUID-B24F8609-0E74-4318-8168-A6E7FCD0B313 V1 EN

Figure 9: HSR solution

Secure communication

The protection relay supports secure communication for WHMI and file transfer protocol. If the Secure Communication parameter is activated, protocols require TLS based encryption method support from the clients. In this case WHMI must be connected from a Web browser using the HTTPS protocol and in case of file transfer the client must use FTPS.

As a factory default, Secure Communication is “ON”.

33

Section 3

611 series overview

3.6

1MRS757453 C

PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all stages of the protection relay life cycle.

• Planning

• Engineering

• Commissioning

• Operation and disturbance handling

• Functional analysis

The whole substation configuration can be controlled and different tasks and functions can be performed with the individual tool components. PCM600 can operate with many different topologies, depending on the customer needs.

For more information, see the PCM600 documentation.

3.6.1

3.6.2

34

Connectivity packages

A connectivity package is a software component that consists of executable code and data which enables system tools to communicate with a protection relay. Connectivity packages are used to create configuration structures in PCM600. The latest PCM600 and connectivity packages are backward compatible with older protection relay versions.

A connectivity package includes all the data which is used to describe the protection relay. For example, it contains a list of the existing parameters, data format used, units, setting range, access rights and visibility of the parameters. In addition, it contains code which allows software packages that use the connectivity package to properly communicate with the protection relay. It also supports localization of text even when it is read from the protection relay in a standard format such as COMTRADE.

Update Manager is a tool that helps in defining the right connectivity package versions for different system products and tools. Update Manager is included with the products that use connectivity packages.

PCM600 and relay connectivity package version

• Protection and Control IED Manager PCM600 Ver.2.7 or later

• REB611 Connectivity Package Ver.2.0 or later

• REF611 Connectivity Package Ver.2.0 or later

• REM611 Connectivity Package Ver.2.0 or later

• REU611 Connectivity Package Ver.2.0 or later

611 series

Operation Manual

1MRS757453 C

Section 3

611 series overview

Download connectivity packages from the ABB Web site http://www.abb.com/substationautomation or directly with Update

Manager in PCM600.

611 series

Operation Manual

35

36

1MRS757453 C

Section 4 Using the HMI

4.1

4.1.1

Section 4

Using the HMI

Using the local HMI

To use the LHMI, logging in and authorization are required. Password authorization is disabled by default and can be enabled via the LHMI.

To enable password authorization, select Main menu/

Configuration/Authorization/Passwords . Set the Local override parameter to “False”.

Logging in

1.

Press or or to activate the login procedure.

2.

Press or to select the user level.

GUID-7B40EC73-2324-4E9A-9DF7-CC742744EC1B V1 EN

Figure 10: Selecting access level

3.

Confirm the selection with .

4.

Enter the password when prompted digit by digit.

Activate the digit to be entered with

Enter the character with and .

and .

GUID-C8BDDF55-EB8B-42AD-8184-3939BF51B4C4 V1 EN

Figure 11: Entering password

5.

Press to confirm the login.

To cancel the procedure, press .

611 series

Operation Manual

37

Section 4

Using the HMI

1MRS757453 C

4.1.2

4.1.3

38

GUID-39601B65-8E32-49F7-AE8A-C16B71770D69 V1 EN

Figure 12: Error message indicating wrong password

The current user level is shown on the display's upper right corner in the icon area.

Logging out

An automatic logout occurs 30 seconds after the backlight timeout.

1.

Press for three seconds in the main menu.

2.

To confirm logout, select Yes and press .

GUID-65BD2160-B3FF-4FD0-8028-C5F0CB67FE54 V1 EN

Figure 13: Logging out

To cancel logout, press .

Turning the display backlight on

The display backlight is normally off. It turns on during the display test at power up.

• To turn on the backlight manually, press any LHMI push button.

The backlight turns on and the panel is ready for further operations.

If the panel has not been used for a predefined timeout period, the backlight is switched off. The user is logged out from the current user level 30 seconds after the display backlight has turned off.

The display returns to the default view and all unconfirmed operations such as parameter editing and breaker selection are cancelled.

611 series

Operation Manual

1MRS757453 C

4.1.4

4.1.5

Section 4

Using the HMI

Change the backlight timeout period in Main menu/

Configuration/HMI/Backlight timeout .

Selecting local or remote use

The control position of the protection relay can be changed with the R/L button. In local position primary equipment, such as circuit breakers or disconnectors, can be controlled via the LHMI. In remote position, control operations are possible only from a higher level, that is from a control center.

Press for two seconds.

When the L LED is lit, local control is enabled and remote control disabled.

When the R LED is lit, remote control is enabled and local control disabled.

When neither of the LEDs is lit, both control positions are disabled.

When the L and R LEDs are lit, both remote and local control are enabled.

By default, the control position cannot be local and remote simultaneously. See the technical manual for more information on local and remote control.

To control the protection relay, log in with the appropriate user rights.

Identifying the device

The Information menu includes detailed information about the device, such as revision and serial number.

The protection relay information is shown on the display for a few seconds when the device starts. The same information is also found in the protection relay menu.

1.

Select Main menu/Information .

2.

Select a submenu with and .

611 series

Operation Manual

39

Section 4

Using the HMI

1MRS757453 C

4.1.5.1

4.1.6

40

GUID-36916877-1917-4472-AA11-37897C5FD709 V1 EN

Figure 14: Selecting a submenu

3.

Enter the submenu with .

4.

Browse the information with and .

GUID-2437E75E-0B00-4B47-89D2-FD4E5690BCC6 V1 EN

Figure 15: Protection relay information

Identifying relay's IEC 61850 version

The relay's IEC 61850 version information identifies if the relay is configured as

Edition 1 or Edition 2 device.

1.

Select Main menu/Information/System identifiers .

2.

Enter the submenu with .

GUID-D8F6EB65-75D5-4EE6-BC96-1153FC832AB3 V1 EN

Figure 16: Identifying IEC 61850 version

Adjusting the display contrast

Adjust the display contrast anywhere in the menu structure to obtain optimal readability.

To increase the contrast, press simultaneously

To decrease the contrast, press simultaneously

and

and

.

.

611 series

Operation Manual

1MRS757453 C

4.1.7

Section 4

Using the HMI

The selected contrast value is stored in the non-volatile memory if you are logged in and authorized to control the protection relay. After an auxiliary power failure, the contrast is restored.

Changing the local HMI language

1.

Select Main menu/Language and press .

2.

Change the language using or .

3.

Press to confirm the selection.

4.

Commit the changes.

4.1.8

4.1.9

611 series

Operation Manual

GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN

Figure 17: Changing the LHMI language

To change the language using a shortcut, press and simultaneously anywhere in the menu.

Changing display symbols

Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and

IEC-ANSI.

1.

Select Main Menu/Configuration/HMI/FB naming convention and press

.

2.

Change the display symbols with or .

3.

Press to confirm the selection.

The protection relay has to be rebooted if the WHMI display symbols are changed. With the LHMI, the change takes effect immediately.

Changing setting visibility

The basic settings contain the most used parameters. The advanced settings contain all parameters.

41

Section 4

Using the HMI

1MRS757453 C

1.

Select Main Menu/Configuration/HMI/Setting visibility and press .

2.

Change the setting visibility with or to select which parameters are shown.

Basic

Advanced

3.

Press to confirm the selection.

4.1.10

4.1.10.1

42

GUID-ECF76371-3DF5-4833-966A-447D52FCF492 V1 EN

Figure 18: Viewing basic parameters

Navigating in the menu

Navigate the menus and change the display views on the screen with the keypad.

• To move up or down in a menu, press or .

• To move downwards in the menu tree, press .

To move upwards in the menu tree, press .

• To enter setting mode, press .

To leave setting mode without saving, press .

Menu structure

The Main menu contains main groups which are divided further into more detailed submenus.

• Control

• Events

• Measurements

• Disturbance records

• Settings

• Configuration

• Monitoring

• Tests

• Information

• Clear

• Language

611 series

Operation Manual

1MRS757453 C

4.1.10.2

Section 4

Using the HMI

Scrolling the display

If a menu contains more rows than the display can show at a time, a scroll bar is displayed on the right.

4.1.10.3

4.1.11

GUID-3DB7835C-EA13-46C3-AAF5-455C07D454EC V1 EN

Figure 19: Scroll bar on the right

• To scroll the view upwards, press .

• To scroll the view downwards, press .

• To jump from the last row to the first row, press again.

• Press to jump from the first row to the last row.

To scroll parameter names and values that do not fit the screen, press

once to return to the beginning.

. Press

Changing the default view

The default view of the display is Measurements unless set otherwise.

1.

Select Main menu/Configuration/HMI/Default view and press .

2.

Change the default view with or .

3.

Press to confirm the selection.

Browsing setting values

1.

Select Main menu/Settings/Settings and press .

2.

Select the setting group to be viewed with or .

611 series

Operation Manual

43

Section 4

Using the HMI

1MRS757453 C

4.1.12

4.1.12.1

44

GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN

Figure 20: Selecting a setting group

3.

Press to confirm selection.

4.

To browse the settings, scroll the list with and and to select a submenu press . To move back to the list, press .

GUID-E1C19F9C-079D-479C-BAF0-71E6E2FAF112 V1 EN

Figure 21: Example of submenus in the Settings menu

Editing values

• To edit values, log in with the appropriate user rights.

Changing the function block on or off affects to the visibility of its parameters in the menu. Setting function block off hides the function parameters. When changing function block on or off the parameters' visibility changes immediately. Commit the settings for the activation of the function.

Changing the value of certain relay parameters affects the visibility or range of other parameters in the menu. This indicates which parameters or parameter values become obsolete due to the change.

The relay changes the visibility or range of these parameters immediately. Commit the settings for the activation of the function.

Editing numerical values

1.

Select Main menu/Settings and then a setting.

The last digit of the value is active.

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

When the symbol in front of the value is ↑, the active value can only be increased.

When the symbol is ↓, the active value can only be decreased.

When the symbol in front of the value is ↕, the active value can either be increased or decreased.

GUID-91310FC1-E8FB-452E-B9B6-4D65C874278C V1 EN

Figure 22: Last digit is active and it can only be increased

2.

Press to increase or to decrease the value of an active digit.

One press increases or decreases the value by a certain step. For integer values, the change is 1, 10, 100 or 1000 (...) depending on the active digit. For decimal values, the change can be fractions 0.1, 0.01, 0.001 (...) depending on the active digit.

For parameters with defined steps, digits smaller than the step value cannot be edited.

3.

Press or to move the cursor to another digit.

4.

To select the minimum or maximum value, select the arrow symbol in front of the value.

To set the value to the maximum, press

To set the value to the minimum, press .

.

GUID-604A2ED9-E1A7-4986-8CDD-92E43188CA48 V1 EN

Figure 23: Arrow symbol is active, the value is set to the maximum

After pressing , the previous value can be restored by pressing once, and vice versa. Another press of or sets the value to the lower or higher limit.

The symbol in front of the value is ↕, when the previous value is shown.

611 series

Operation Manual

45

Section 4

Using the HMI

1MRS757453 C

4.1.12.2

4.1.12.3

4.1.13

GUID-F65419AD-767F-488E-9915-4BBEB859D15A V1 EN

Figure 24: Restoring the previous value

Editing string values

1.

Activate the setting mode and select a setting.

When editing string values, the cursor moves to the first character.

2.

Press or to change the value of an active character.

One press changes the value by one step.

3.

Press to move the cursor to the right. Press to delete the character on the left side of the cursor.

Editing enumerated values

1.

Activate the setting mode and select a setting.

When editing an enumerated value, the selected value is shown inverted.

2.

Press or to change the value of an active enumerated value.

One press changes the enumerated value by one step in the parameter specific order.

Committing settings

Editable values are stored either in RAM or in non-volatile flash memory. Values stored in flash memory are in effect also after reboot.

Some parameters have an edit-copy. If editing is cancelled, the values with an editcopy are immediately restored to the original value. The values without an edit-copy, such as string values, are restored to the original value only after a reboot even though the edited value is not stored in the flash memory.

1.

Press to confirm any changes.

2.

Press to move upwards in the menu tree.

3.

To save the changes in non-volatile memory, select Yes and press .

46 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.1.14

611 series

Operation Manual

GUID-2366EB35-75C9-48AC-8D11-E2B058BCF996 V1 EN

Figure 25: Confirming settings

To exit without saving changes, select No and press .

If the parameter has an edit-copy, the original parameter value is restored.

If the parameter does not have an edit-copy, the edited parameter value remains visible until the protection relay is rebooted.

However, the edited value is not stored in non-volatile memory and the reboot restores the original value.

To cancel saving settings, select Cancel and press .

After certain parameters are changed, the protection relay has to be restarted.

Clearing and acknowledging

The Clear view is used to reset, acknowledge or clear all messages and indications, including LEDs and latched outputs as well as registers and recordings. Events and alarms assigned to programmable LEDs are cleared in the Clear view as well.

1.

Select Main menu/Clear to activate the clear menu.

GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN

Figure 26: Clear view

2.

Select the item to be cleared with or .

3.

Press , change the value with or and press again.

The item is now cleared.

4.

Repeat steps 2 and 3 to clear other items.

47

Section 4

Using the HMI

4.1.15

4.2

4.2.1

48

1MRS757453 C

Use the button as a shortcut for clearing. The first three-second press clears the indications. The second three-second press clears the programmable LEDs.

Using the local HMI help

1.

Press to open the help view.

2.

Scroll the text with or if the help text exceeds the display area.

3.

To close the help, press .

Using the Web HMI

WHMI is enabled by default. As secure communication is enabled by default, the

WHMI must be accessed from a Web browser using the HTTPS protocol.

If the WHMI was previously disabled, it can be enabled again via the LHMI.

1.

To enable the WHMI, select Main menu/Configuration/HMI/Web HMI mode via the LHMI.

2.

Reboot the relay for the change to take effect.

3.

Log in with the proper user rights to use the WHMI.

To establish a remote WHMI connection to the protection relay, contact the network administrator to check the company rules for IP and remote connections.

Disable the Web browser proxy settings or make an exception to the proxy rules to allow the protection relay's WHMI connection, for example, by including the relay's IP address in Internet Options/

Connections/LAN Settings/Advanced/Exceptions .

Logging in

1.

Open Internet Explorer.

2.

Type the protection relay's IP address in the Address bar and press ENTER.

3.

Type the username with capital letters.

4.

Type the password.

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.2

4.2.3

A070923 V5 EN

Figure 27: Entering username and password to use the WHMI

5.

Click OK .

The language file starts loading and the progress bar is displayed.

Logging out

The user is logged out after session timeout. The timeout can be set in Main menu/

Configuration/HMI/Web HMI timeout .

• To log out manually, click Logout on the menu bar.

Identifying device

The Information menu includes detailed information about the device, for example, revision and serial number.

1.

Click the Information menu in the left navigation bar.

2.

Click a submenu to see the data.

611 series

Operation Manual

49

Section 4

Using the HMI

1MRS757453 C

4.2.4

GUID-0526D2B8-9C7C-4C29-9E1C-C9DF549B2970 V1 EN

Figure 28: Device information

Navigating in menus

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

• Use the menu bar to access different views.

The

The

General

Events

view shows the protection relay version and status.

view contains a list of events produced by the application configuration.

The Programmable LEDs view shows the status of programmable LEDs.

The Phasor diagrams view shows phasor diagrams.

The Disturbance records view shows the list of disturbance records.

Signal configuration

Logout ends the session.

50 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.4.1

GUID-C08AA4D5-0F4E-4DC5-9194-8338A19761AC V1 EN

Figure 29: Navigating in Web HMI menus

Menu structure

The Main menu contains main groups which are divided further into more detailed submenus.

• Control

• Events

• Measurements

• Disturbance records

• Settings

• Configuration

• Monitoring

• Tests

• Information

• Clear

• Language

• Parameter list

• WHMI settings

611 series

Operation Manual

51

Section 4

Using the HMI

4.2.5

1MRS757453 C

Showing parameters

Some function blocks have a function-specific On/Off setting. When the function setting is “Off”, all settings are hidden and when the function setting is “On”, all settings are visible based on the other visibility and hiding rules.

Switch a function block on or off via the Operation parameter under the required function block.

GUID-F6EDA317-5965-463D-9335-0FD22A315D28 V1 EN

Figure 30: Function block On

52 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

611 series

Operation Manual

GUID-9C2AD6B3-594A-4BCC-A2B9-5A875962D368 V1 EN

Figure 31: Function block Off

The Parameter list page offers filtering functionality where only chosen parameters are displayed, saved or printed. There are various options for filtering.

• Enabled settings hides settings of disabled function blocks.

• Writable settings displays only writable settings. This option is checked by default.

• Basic settings displays only basic settings.

• Setting group displays only settings of the selected setting group. With “All” selected, all setting groups are displayed.

Options can be combined. For example, with the Enabled settings and Writable settings selected, only enabled and writable settings are displayed. If none of the options is selected, all settings are displayed.

The values “Basic” or "Advanced" of the Setting visibility parameter in Main Menu/Configuration/HMI have no effect on the Parameter list page. This page has its own Basic settings option which can be used to hide or show the advanced settings on the Parameter list page.

GUID-B0106F5F-4798-475B-9DFB-58921B167310 V1 EN

Figure 32: Parameter list filter

1.

Click Parameter list in the left navigation bar.

53

Section 4

Using the HMI

1MRS757453 C

GUID-93613E3F-4CD3-4578-9F97-424282B1228B V2 EN

Figure 33: Displaying parameters

2.

Select only those settings that are wanted to be shown and click Refresh . If nothing is selected, all settings are shown.

54 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.6

GUID-C2331A22-4BC6-4D24-9B8F-A8EB7A22CCCA V1 EN

Figure 34: Enabled settings

3.

Select text (.txt) or comma separated values (.csv) file format and click Save to save the settings.

4.

Click Print to print all the selected parameters.

Editing values

1.

Select a menu in the left navigation bar.

2.

Click a submenu to see function blocks.

3.

Click a function block to see the setting values.

4.

Click Enable Write .

Some parameters, for example the Web HMI mode, cannot be set via the WHMI.

611 series

Operation Manual

55

Section 4

Using the HMI

1MRS757453 C

56

GUID-C6FA8F5E-19CC-47AD-A000-8DFF91B3FFE7 V2 EN

Figure 35: Enable writing to edit a value

The selected setting group is shown in the Setting Group drop-down list. The active setting group is indicated with an asterisk *.

5.

Edit the value.

The minimum, maximum and step values for a parameter are shown in the

Min., Max. and Step columns.

Setting group values are indicated with .

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-35C049F6-D716-451D-9886-CFC607295675 V2 EN

Figure 36: Editing a value

• If the entered value is within the accepted value range, the selection is highlighted in green. If the value is out of range, the row is highlighted in red and a warning dialog box is displayed. Write to IED is unavailable.

611 series

Operation Manual

GUID-12C28E34-2871-423A-B9D9-A03FB55362AC V2 EN

Figure 37: Warning indicating that the entered value is incorrect

If writing values fails, a warning dialog box is displayed.

57

Section 4

Using the HMI

1MRS757453 C

4.2.7

GUID-E85F77ED-C27F-426B-AAAD-9C6E10994A7C V2 EN

Figure 38: Warning indicating that the values were not written to the

IED

If writing is enabled accidentally, click Disable Write . Disable

Write cannot be selected when a value has already been written to the protection relay. After clicking Write to IED , click either Commit or

Reject .

Committing settings

Editable values are stored either in RAM or a nonvolatile flash memory. Values stored in the flash memory are in effect also after a reboot.

Some parameters have an edit-copy. If editing is cancelled, the values with an editcopy are immediately restored to the original value. The values without an edit-copy, such as string values, are restored to the original value only after a reboot even though the edited value is not stored in the flash memory.

1.

Click Write to IED after editing parameter values to put the values into protection relay's database for use.

58 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

611 series

Operation Manual

GUID-F286D262-E9AB-4168-8BF1-FC37688D91BF V1 EN

Figure 39: Writing values to protection relay

The values are not stored to the flash memory.

2.

Click Commit to write the values to the flash memory.

• Click Reject to cancel saving settings.

If the parameter has an edit-copy, the original parameter value is restored.

If the parameter does not have an edit-copy, the edited parameter value remains visible until the protection relay is rebooted.

However, the edited value is not stored in the nonvolatile memory and thus the reboot restores the original value.

GUID-88F499E6-799A-44D0-869A-1F01E7ED6722 V2 EN

Figure 40: Committing changes

Committing values takes a few seconds.

59

Section 4

Using the HMI

4.2.8

1MRS757453 C

If the values are not committed, they are not taken into use and they are lost after a reboot.

Clearing and acknowledging

All messages and indications, including LEDs and latched outputs as well as registers and recordings, can be reset, acknowledged or cleared using the Clear menu.

1.

Click Clear in the left navigation bar.

GUID-BD2CC4E6-6363-4EEA-9402-415901CC74FA V2 EN

Figure 41: Selecting clear menu

2.

In the New Value list, select Clear to choose the item to be cleared.

3.

Click Write to IED .

60 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.9

GUID-3CAE395C-EC4D-409A-99EB-C3434680BB61 V2 EN

Figure 42: Clearing indications and LEDs

Selecting programmable LEDs view

The programmable LEDs view shows the status of the programmable LEDs. These are the same LEDs that are located on the upper right side of the LHMI panel.

• Click Programmable LEDs on the menu bar.

611 series

Operation Manual

61

Section 4

Using the HMI

1MRS757453 C

4.2.10

GUID-20C268F8-B2BA-41E1-A17D-5DBAE8CEFA2F V2 EN

Figure 43: Monitoring programmable LEDs

Selecting event view

The event view contains a list of events produced by the application configuration.

When the event page is opened, it displays up to 100 latest events at one time. The event list is updated automatically.

1.

Click Events on the menu bar.

62 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-4E351C8C-EE76-46F5-B83B-14230676BCE8 V2 EN

Figure 44: Monitoring events

2.

Click Freeze to stop updating the event list.

3.

Select a page from the drop-down list to view older events or select View all to show all events on the same page.

611 series

Operation Manual

GUID-4FD2F9CC-D690-4A68-8E17-E6DE420ADED9 V2 EN

Figure 45: Events view

4.

To save the events in TXT or CSV file formats, select the file format from the drop-down list and click Save .

63

Section 4

Using the HMI

4.2.11

1MRS757453 C

The CSV file can be opened with a spreadsheet program such as

OpenOffice.org Calc or Microsoft Excel.

5.

Click Clear events to clear all events from the protection relay.

6.

Click Print to print all the selected events.

Selecting disturbance records view

Disturbance records are listed in the disturbance records view.

• Click Disturbance records on the menu bar.

4.2.11.1

GUID-FD3ED365-053B-4613-B290-2F3F46D04A0D V1 EN

Figure 46: Selecting disturbance records view

Saving disturbance records

1.

Click Disturbance records on the menu bar.

2.

To save the disturbance record files, click the icon in the Download Files column of the record.

64 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.11.2

GUID-76B94DE7-6020-4466-833A-2A22DB6A4367 V1 EN

Figure 47: Saving a disturbance record

3.

Open the disturbance record files with a suitable program.

Triggering disturbance recorder manually

1.

Click Disturbance records on the menu bar.

2.

Click Manual trigger .

611 series

Operation Manual

GUID-BD629C96-3A49-47C3-B09B-B2776C9CF467 V2 EN

Figure 48: Manual triggering

65

Section 4

Using the HMI

4.2.11.3

1MRS757453 C

Deleting disturbance records

1.

Click Disturbance records on the menu bar.

2.

Delete records.

Click Delete all to delete all records.

Select one or more recordings and click Delete to delete selected records.

4.2.12

GUID-9B5D6FB6-68F0-472F-B23D-6369158D6BD7 V2 EN

Figure 49: Deleting disturbance records

3.

Click OK to confirm or Cancel to cancel the deletion.

Selecting phasor diagrams

Install or enable the SVG plugin to view the phasor diagrams, if needed.

1.

Click Phasor diagrams on the menu bar.

66 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-BC13067A-6C27-4532-9BD8-FD9BA724BFFF V1 EN

Figure 50: Monitoring phasors

2.

Toggle the diagram visibility by selecting the diagram from the drop-down menu.

611 series

Operation Manual

GUID-91F00B72-85EE-4577-B828-7B6E158F4CBF V1 EN

Figure 51: Toggling the diagram visibility

67

Section 4

Using the HMI

Visible diagrams are indicated with an asterisk *.

3.

Change the size of the diagram by changing the zoom value.

1MRS757453 C

GUID-D1C26F94-FCD1-4A0B-AE94-A3E4DACB8682 V1 EN

Figure 52: Zooming the diagram

4.

Click Freeze to stop updating the phasor diagram.

No updates are displayed in the diagram.

68 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.13

GUID-8BA2E56F-8828-4C5E-807C-F1F780F6E0C8 V1 EN

Figure 53: The arrow extends outside the circle if the current value is too high

Selecting fault records

1.

Fom the main menu, select Monitoring/Recorded data/Fault record or click

Fault records on the menu bar to view a list of all available fault records.

2.

Click a record from the Fault records list to open the fault record details view.

3.

To go back to the list view, click Fault records on the menu bar or click the View all button.

4.

To save the records in TXT or CSV file formats, select the format from the File format drop-down list and click Save .

When the fault record details view is shown, only the shown fault record is saved.

When fault record list view is shown, all fault records are saved.

5.

To clear all fault records from the protection relay, click Clear records .

This can be done only when the fault record list view is shown.

6.

To print all fault records, click Print when the fault record list view is shown.

7.

To print only one record, open it in the details view and click Print .

611 series

Operation Manual

69

Section 4

Using the HMI

1MRS757453 C

GUID-2D4814EC-F4F7-4FF6-9E40-65D8C7F83487 V1 EN

Figure 54: Fault record list view

70

GUID-0E215160-B6E8-4ACB-B91A-DEAC98501FFC V1 EN

Figure 55: Fault record details view

611 series

Operation Manual

1MRS757453 C

4.2.14

Section 4

Using the HMI

Selecting signal configuration

The signal configuration view provides an easy tool to manage the application configuration, simplifying the configuration work. The signal configuration is done with three switch group functions including input switch group ISWGAPC, output switch group OSWGAPC and selector switch group SELGAPC.

1.

Click Signal configuration on the menu bar to open the overview page.

The switch groups used in the protection relay are categorized into four logical groups.

Binary inputs

GOOSE

Internal signals

Binary outputs and LEDs

Each group is represented by an area enclosed in a rectangle with a general description text.

611 series

Operation Manual

GUID-3DC3C22C-ED52-4C1C-A9E8-5559DEA5724D V2 EN

Figure 56: Overview

2.

Click the corresponding area to view a specific logical group.

The switch groups included in the logical group are shown as a matrix view on the respective page. This view allows to change or map the connections from binary inputs to functions, GOOSE signals to functions, functions to functions, functions to binary outputs and functions to LEDs through corresponding switch group functions.

71

Section 4

Using the HMI

1MRS757453 C

GUID-EAB8BB7D-C914-436D-8DDC-643EDF49ED40 V2 EN

Figure 57: Binary input configuration

72

GUID-B804DF59-FFE6-42FE-8E41-5A2A125DCD46 V2 EN

Figure 58: GOOSE configuration

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-4CF3B8E5-F756-4892-AE71-C4AA5895F075 V2 EN

Figure 59: Internal signal configuration

611 series

Operation Manual

73

Section 4

Using the HMI

1MRS757453 C

74

GUID-085A93F1-AD8B-42E4-9362-407C7057EA20 V2 EN

Figure 60: Binary outputs and LEDs configuration

3.

On the Binary Outputs and LEDs Configuration matrix view, click Expand all to see the expanded page for configuring individual OSWGAPC instances.

Use the Expand all and Collapse all buttons to move from the Binary Outputs and LEDs Configuration overview page to the more detailed view and back.

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-17AA5E7D-88EA-4B1D-AC4E-20EDBAC329F6 V1 EN

Figure 61: Binary outputs and LEDs configuration expanded view

4.

Click Enable Write to edit field values.

Figure 62

shows an example view of updating or changing the input signal configuration. One of the binary input channels has been mapped to one blocking input of a protection function through input switch group ISWGAPC and selector switch group SELGAPC functions.

Click one of the input switch group ISWGAPC connection channel shown in green.

Click and select the binary input in the selector switch group SELGAPC function shown in green.

Write the connection setting to IED and refresh values.

611 series

Operation Manual

75

Section 4

Using the HMI

1MRS757453 C

4.2.15

4.2.15.1

GUID-B6CE346B-D178-4FD1-B77C-084430E985AF V1 EN

Figure 62: Example view of changing binary input connections

For more information on editing field values, see the corresponding chapter.

Import and export of settings

Protection relay's setting parameters can be imported and exported in the XRIO file format.

Exporting settings

Relay setting parameters can be exported in XRIO file format.

1.

Click Import/Export on the menu bar.

2.

Click Export Settings . The export file includes all parameters except status parameters and parameters writable only in LHMI.

76 611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

4.2.15.2

611 series

Operation Manual

GUID-7BF72874-B597-4EB9-B37D-72D58578647D V1 EN

Figure 63: Exporting settings

3.

Click Save to export the settings to the computer.

Importing settings

The parameter export and import function can be utilized, for example, when the relay parameters are set using the WHMI instead of PCM600. The relay settings engineered with PCM600 can be exported to XRIO files and imported to the WHMI. The WHMI can be used to write the settings to the protection relays. The WHMI can also be used to read the relay setting parameters and to export those to files, which can be used by

PCM600. WHMI imports all parameters from the import file except lockable and read only parameters.

The exporting and importing of settings is sensitive to the protection relay contents. Settings are exported and imported for one protection relay at a time. The export files of a specific protection relay can be exchanged between PCM600, WHMI and the actual physical protection relay. To avoid errors and to efficiently manage the exporting and importing of settings, for example, in a substation with several devices, ensure that the names of the export files identify the protection relay to which the file should be imported.

Ensure that the correct settings are imported to the correct protection relay. Wrong settings may cause the protection relay to malfunction.

1.

Click Import/Export on the menu bar.

2.

Click Browse and choose the file to be imported.

77

Section 4

Using the HMI

1MRS757453 C

78

GUID-977DDC47-343A-446E-BF59-E06F8330AAD1 V1 EN

Figure 64: Browsing import settings

3.

Click Import Settings .

Wait until the file transfer is complete.

GUID-9752BEBA-ECEA-4CB9-B77A-A887DBE744BB V1 EN

Figure 65: Importing settings

4.

Click OK to commit the imported settings to the protection relay.

Wait until the import is complete.

• Click Cancel to cancel the importing. Both the WHMI and the protection relay revert to the settings in use prior to the import.

611 series

Operation Manual

1MRS757453 C

Section 4

Using the HMI

GUID-3F9E3F90-BEC8-40D9-85CF-B837B5F3DE26 V1 EN

Figure 66: Writing parameter settings

4.2.16

611 series

Operation Manual

GUID-25214819-0E23-4A36-98DE-99B47A63D46A V1 EN

Figure 67: Parameter settings written to protection relay

Only editable parameters are written to the protection relay during the import. If part of the import fails, the faulty parameters are listed separately.

Exporting report summary

The Report summary page allows exporting events, fault records, disturbance records and the parameter list.Events, fault records and the parameter list are saved in TXT format. Saved files contain all events, fault records and settings.Disturbance records are saved in CFG and DAT formats.

1.

Click Report summary on the menu bar.

2.

Select the items to be exported.

79

Section 4

Using the HMI

1MRS757453 C

Click Select all to select all items and click Clear all to clear all selections.

3.

From the Disturbance records drop-down list, select the amount of records to be saved.

All

Last 1

Last 10

4.

Click Save to export the ZIP file with the selected files.

4.2.17

GUID-9693E936-E4D0-48CD-B0FE-9F928935198A V1 EN

Figure 68: Report summary page

Using Web HMI help

The context-sensitive WHMI help provides information on a single parameter, for example.

Move the mouse over the to display the help dialog box.

80 611 series

Operation Manual

1MRS757453 C

GUID-1769ECA8-EC02-4260-B658-8698D54E89DB V2 EN

Figure 69: Opening the WHMI help

Section 4

Using the HMI

611 series

Operation Manual

81

82

1MRS757453 C

Section 5 IED operation

5.1

5.2

Section 5

IED operation

Normal operation

In a normal protection relay use situation, the basic operation includes monitoring and checking procedures.

• Monitoring measured values

• Checking object states

• Checking function setting parameters

• Checking events and alarms

All basic operations can be performed via the LHMI, WHMI or with PCM600.

For more information, see the PCM600 documentation.

Disturbance identification

Disturbances and their causes can be identified by indicator LEDs: Ready, Start and

Trip. During normal operation, the Ready LED is steady green.

Table 16:

LED

Start LED

Start LED

Trip LED

Ready LED

Disturbance indications

State

Yellow, steady

Yellow, flashing

Red, steady

Green, flashing

Description

Protection started

Protection function blocked

Protection operated

Internal fault

Further actions to be taken to identify the disturbance:

• Checking programmable LEDs

• Reading event history

• Checking fault records

• Analyzing disturbance recordings

611 series

Operation Manual

83

Section 5

IED operation

5.2.1

5.2.2

5.2.3

5.2.4

84

1MRS757453 C

Document the disturbance before clearing the information from the protection relay.

Only authorized and skilled personnel should analyze possible errors and decide on further actions. Otherwise, stored disturbance data can be lost.

Disturbance recording triggering

Disturbance recordings are normally triggered by protection relay applications when they detect fault events. Disturbance recordings can also be triggered manually or periodically. The manual trigger generates an instant disturbance report. Use this function to get a snapshot of the monitored signals.

Disturbance record analysis

The protection relay collects disturbance records of fault events which are set to trigger the disturbance recorder. Disturbance data is collected and stored for later viewing and analysis. The disturbance recorder data can be read and analyzed with

PCM600.

For more information, see the PCM600 documentation.

Disturbance reports

PCM600 can be used for creating reports of disturbance recorder data.

For more information, see the PCM600 documentation.

Relay self-supervision

The relay self-supervision handles internal run-time fault situations.The main indication of an internal fault is a flashing green Ready LED.

Internal faults can be divided to hardware errors, run-time errors in the application or operating system and communication errors. Further actions always depend on the cause of the error.

611 series

Operation Manual

1MRS757453 C

5.3

5.3.1

5.3.2

611 series

Operation Manual

Section 5

IED operation

Only authorized and skilled personnel should analyze the errors and decide on further actions.

The protection relay records system registrations, relay status data and events.

Document all the recorded data from the protection relay before resetting the tripping and relay lockout functions.

Relay parametrization

Protection relay parameters are set via the LHMI, WHMI or PCM600.

Setting parameters need to be calculated according to the electrical network conditions and the electrical characteristics of the protected equipment. The protection relay's settings need to be verified before the protection relay is connected to a system.

Document all changes to parameter settings.

For more information, see the PCM600 documentation.

Settings for relay functionality

Function settings can be edited one by one by navigating to the individual setting values, for example via the LHMI. The values in other setting groups should be known before editing a certain setting value.

After completing the editing of setting group values, the new values are activated. The user can either commit the edited values or discard them. Setting values can also be copied from one setting group to another.

Settings for different operating conditions

Protection relay settings can be designed for various operation conditions by defining different setting values to different setting groups. The active setting group can be changed by the relay application or manually via the LHMI, WHMI or PCM600.

85

86

1MRS757453 C

Section 6 Operating procedures

Section 6

Operating procedures

6.1

6.1.1

6.1.1.1

Monitoring

Indications

The operation of the protection relay can be monitored via three different indications on the LHMI.

• Three indicator LEDs with fixed functionality: Ready, Start and Trip

• 8 programmable LEDs

• Information on the display

Monitoring indication messages

Indication messages and tripping data are shown in a dialog box. Only one dialog box can be shown at a time, therefore the relay has internal priority for indication messages and tripping data. Internal fault and warning messages have always higher priority than start or trip information. Trip information has always higher priority than start information.

1.

Read the indication message in the dialog box.

The message can indicate the starting or tripping of protection functions or an internal fault in the device.

2.

Press to close the indication message without clearing it or press to activate the Clear view and to clear messages.

6.1.1.2

611 series

Operation Manual

GUID-851D3AA9-F22C-49E9-B964-032A24C94B9F V1 EN

Figure 70: Indication message

Monitoring an internal relay fault

The flashing green LED indicates an internal relay fault. Internal relay fault messages are shown in a dialog box. Only one dialog box can be shown at a time, therefore the

87

Section 6

Operating procedures

1MRS757453 C relay has internal priority for indication messages and tripping data. Internal fault has always higher priority than a warning.

See the troubleshooting section for more details.

6.1.1.3

6.1.2

6.1.2.1

88

GUID-216C00ED-ACFF-43AA-A2A6-B53C0FDE8D49 V1 EN

Figure 71: Fault indication

1.

Select Main menu/Monitoring/IED status/Self-supervision to monitor the latest fault indication.

2.

Press or to scroll the view.

Monitoring condition monitoring data

1.

Select Main menu/Monitoring/I/O status/Condition monitoring .

2.

Press or to scroll the view.

3.

Press to enter or to exit a submenu.

With PCM600 the user can map output signals from condition monitoring related function blocks to the appropriate destinations.

Measured and calculated values

Measurement view in Main Menu/Measurements shows the momentary actual values for various power system measurements.

All values show the momentary measurement value and some include demand values calculated from a set period.

Invalid or questionable measurement values are presented in parentheses.

Measured values

Measured values can be accessed through the LHMI, WHMI or PCM600.

611 series

Operation Manual

1MRS757453 C

6.1.2.2

6.1.3

6.1.3.1

611 series

Operation Manual

Section 6

Operating procedures

Table 17:

Indicator

IL1-A

IL2-A

IL3-A

I

0

-A

U

0

-kV

U12-kV f-Hz

S-MVA

P-MW

Q-MVar

PF

Ng-Seq-A

Ps-Seq-A

Zro-Seq-A

Ng-Seq-kV

Ps-Seq-kV

Zro-Seq-kV

Examples of the measured values

Description

Current measured on phase L1

Current measured on phase L2

Current measured on phase L3

Measured earth-fault current

Measured residual voltage

Measured phase-to-phase voltage U12

Measured frequency

Total apparent power

Total active power

Total reactive power

Average power factor

Negative-phase-sequence current

Positive-phase-sequence current

Zero-phase-sequence current

Negative-phase-sequence voltage

Positive-phase-sequence voltage

Zero-phase-sequence voltage

Using the local HMI for monitoring

1.

Select Main menu/Measurements to monitor measured and calculated values.

The list of protection relay's basic measurements is shown.

2.

Scroll the view with and .

Recorded data

The protection relay is provided with intelligent and flexible functionality that collects different kinds of data. The recorded data gives substantial information for post fault analysis.

• Disturbance records

• Fault records

• Events

Creating disturbance recordings

Normally disturbance recordings are triggered by the protection relay applications but the recording can also be triggered manually.

89

Section 6

Operating procedures

1.

Select Main menu/Disturbance records .

2.

Select Trig recording with or .

3.

Press , change the value with or and press again.

1MRS757453 C

6.1.3.2

GUID-01F7D531-894B-4D66-A777-4DE7B301EE43 V1 EN

Figure 72: Changing the value

The disturbance recorder is now triggered.

Monitoring disturbance recorder data

Upload individual disturbance recordings from the protection relay with the PCM600 software to monitor disturbance recorder data.

1.

Select Main menu/Disturbance records .

All the disturbance recorder information is listed.

2.

Scroll the view with or .

The following items are listed in the view:

Number of recordings currently in the protection relay's memory.

Remaining amount of recordings that fit into the available recording memory.

Recording memory used in percentage.

If the periodic triggering function is used, the time to trigger which indicates the remaining time to the next periodic triggering of the disturbance recorder.

6.1.3.3

90

GUID-42054948-9852-436A-AA73-FCD44FAA2E60 V1 EN

Figure 73: Monitoring disturbance recorder via the LHMI

Controlling and reading of disturbance recorder data

Disturbance recorder data can be controlled and read with PCM600. It can also be read via WHMI.

611 series

Operation Manual

1MRS757453 C

6.1.3.4

Section 6

Operating procedures

For more information, see the PCM600 documentation.

Monitoring fault records

Timestamps of the fault records are shown as a list. The first fault record is the newest.

1.

Select Main Menu/Monitoring/Recorded data/Fault record .

2.

To navigate between the fault records, press and .

3.

To enter or exit a submenu, press or .

6.1.3.5

GUID-DE6008BE-30F6-4FD7-A6C3-E65CDC6FCBE0 V1 EN

Figure 74: Monitoring fault records

Monitoring events

Event view contains a list of events produced by the application configuration. Each event takes one view area. The header area shows the currently viewed event index and the total amount of the events. The most recent event is always first.

The HMI Event Filtering tool can be used to configure the event visibility in the LHMI.

1.

Select Main Menu/Events .

2.

Press to view the first event.

Date, time, device description, object description and event text elements of the event are shown.

3.

Press or to scroll the view.

GUID-6D652E3A-0ECD-4025-9FE2-1535AEA9B1D4 V1 EN

Figure 75: Monitoring events

611 series

Operation Manual

91

Section 6

Operating procedures

6.1.4

6.1.4.1

1MRS757453 C

Remote monitoring

The protection relay supports comprehensive remote monitoring.

Monitoring protection relays remotely

Use the PCM600 tool and WHMI to operate the protection relay remotely.

• Read maintenance record and version log.

• Analyze disturbance record data.

• Create disturbance records.

• Monitor protection relay values.

For more information, see the PCM600 documentation.

6.2

6.2.1

Controlling

Controlling via the control menu

The primary equipment can be controlled via the LHMI with the Open and Close buttons when the protection relay is set to the local-control mode and accessing the control operations is authorized.

1.

Press to open or to close the object.

2.

Enter the password when prompted.

3.

To confirm the operation, select Yes and press .

GUID-6210E7B8-A5E3-4869-B654-18EB78E9D3DF V1 EN

Figure 76: Opening circuit breaker

• To cancel the operation, select No and press .

92 611 series

Operation Manual

1MRS757453 C

Section 6

Operating procedures

6.2.2

GUID-00AE25C7-C645-4DCF-AE1E-263A099A4E33 V1 EN

Figure 77: Cancelling operation

The time between selecting the object and giving a control command is restricted by an adjustable time-out. When an object is selected, the control command has to be given within this time.

With default configurations it is possible to control a breaker open even when the breaker is in an intermediate state.

Controlling with the closing delay

Close delay mode and Close delay need to be set to be able to control objects with the closing delay.

The closing operation from the LHMI can be delayed by a predefined period of time.

1.

Press to close the selected object.

• If there are several controllable objects, select the object and press confirm the selection.

to

2.

To confirm the operation, select Yes and press .

After the control operation is confirmed, the delay is activated.

Cancel the control by pressing any key when the delay is active.

611 series

Operation Manual

GUID-12920059-656E-44F3-B0D8-07535BA6A5E0 V1 EN

Figure 78: Delay view

When the delay is activated, it is recommended not to change any closing delay parameters in the WHMI during the delayed time as it affects the delayed circuit breaker closing. If the

93

Section 6

Operating procedures

6.3

6.3.1

1MRS757453 C delayed circuit breaker closing fails, the LHMI status shows

Select timeout or Status only .

The display backlight stays on for the delay also if the backlight timeout is shorter than the closing delay.

Resetting IED

Clearing and acknowledging via the local HMI

All messages and indications, including LEDs and latched outputs as well as registers and indications, including recordings can be reset, acknowledged or cleared in the

Clear view. Selecting Main menu/Clear activates the Clear menu for selecting the wanted clearance or reset function. Events and alarms assigned to programmable

LEDs can also be cleared in the Clear menu.

1.

Select Main menu/Clear to activate the Clear view.

All the items that can be cleared are shown.

Indications and LEDs

Programmable LEDs

Events

Metering records

Disturbance records

Fault records

Temperature of three-phase thermal protection for feeders and thermal overload protection for motors

Reset of autoreclosing

Operation time of runtime counter for machines and devices

Counters for autoreclosing and motor start-up supervision

Master trip

94

GUID-6A5EE8B5-5F4B-4F35-958D-645F1134D69B V1 EN

Figure 79: Clear view

2.

Select the item to be cleared with or .

3.

Press , change the value with or and press again.

611 series

Operation Manual

1MRS757453 C

6.4

6.4.1

6.4.1.1

Section 6

Operating procedures

The item is now cleared.

4.

Repeat the steps to clear other items.

Use the button as a shortcut for clearing. The first three-second press clears the indications. The second three-second press clears the programmable LEDs.

Changing the IED functionality

Defining the setting group

Activating a setting group

Protection relay settings are planned in advance for different operation conditions by calculating setting values to different setting groups. The active setting group can be changed by the protection relay application or manually from the menu.

1.

Select Main menu/Settings/Setting group/Active group and press .

GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN

Figure 80: Active setting group

2.

Select the setting group with or .

3.

Press to confirm the selection or to cancel.

GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN

Figure 81: Selecting the active setting group

4.

Commit the settings.

Remember to document the changes you make.

611 series

Operation Manual

95

Section 6

Operating procedures

6.4.1.2

1MRS757453 C

Copying a setting group

Setting group 1 can be copied to another group or to all available groups.

1.

Select Main menu/Settings/Setting group/Copy group 1 and press .

2.

Change the options with or and press to confirm the selection.

6.4.1.3

GUID-0FD1E855-51B6-4CD5-9120-C73079B6C9CB V1 EN

Figure 82: Copying setting group 1 into 6

Browsing and editing setting group values

1.

Select Main menu/Settings/Settings and press .

2.

Select the setting group to be viewed with or and press to confirm the selection.

GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN

Figure 83: Selecting a setting group

3.

To browse the settings, scroll the list with and and to select a setting press

.

4.

To browse different function blocks, scroll the list with and and to select a function block press . To move back to the list, press .

The function block list is shown in the content area of the display. On the left in the header, you see the current setting group, and on the right the menu path.

5.

To browse the parameters, scroll the list with and and to select a parameter, press .

The setting group values are indicated with #.

96 611 series

Operation Manual

1MRS757453 C

Section 6

Operating procedures

6.

GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN

Figure 84: Setting group parameter

To select a setting group value, press and to edit the value press .

GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN

Figure 85: Selecting the setting group value

Only values within the selected setting group can be changed.

7.

Press or to change the value and to confirm the selection.

6.4.2

611 series

Operation Manual

GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN

Figure 86: Editing the setting group value

The active setting group is indicated with an asterisk * .

Switching the Operation parameter of a function block on or off restarts all control and protection functions.

Activating programmable LEDs

1.

Select Main menu/Configuration/Programmable LEDs.

2.

Select a programmable LED with or .

3.

Press to enter the selection and to change the programmable LED mode.

4.

Change the mode with or and press to confirm the selection.

97

Section 6

Operating procedures

6.4.3

1MRS757453 C

See the technical manual for details on LED configuration.

Setting autoscroll delay

Autoscroll delay parameter sets the delay of scrolling down measurements view if it is set as default view and the user is logged out. Autoscroll is active if the delay value is not zero.

1.

Select Main menu/Configuration/ HMI/Autoscroll delay and press .

2.

Select delay time with or .

3.

Press to confirm the selection.

GUID-E526F966-6D6C-4BB9-885A-C990CDC19EC1 V1 EN

Figure 87: Autoscroll delay

98 611 series

Operation Manual

1MRS757453 C

Section 7 Troubleshooting

7.1

7.1.1

7.1.2

7.1.3

7.1.3.1

611 series

Operation Manual

Section 7

Troubleshooting

Fault tracing

Identifying hardware errors

1.

Check the module with an error.

Check the relay supervision events in Main menu/Monitoring/IED status/

Self-supervision for a faulty hardware module.

2.

Inspect the protection relay visually.

Inspect the protection relay visually to find any physical error causes.

If you can find some obvious physical damage, contact ABB for repair or replacement actions.

3.

Check whether the error is external or internal.

Check that the error is not caused by external origins.

Remove the wiring from the protection relay and test the input and output operation with an external test device.

If the problem remains, contact ABB for repair or replacement actions.

Identifying runtime errors

1.

Check the error origin from the protection relay's supervision events Main menu/Monitoring/IED status/Self-supervision .

2.

Reboot the protection relay and recheck the supervision events to see if the fault has cleared.

3.

In case of persistent faults, contact ABB for corrective actions.

Identifying communication errors

Communication errors are normally communication interruptions or synchronization message errors due to communication link breakdown.

• In case of persistent faults originating from protection relay's internal faults such as component breakdown, contact ABB for repair or replacement actions.

Checking front communication link operation

• To verify front communication, check that both LEDs above the RJ-45 communication port are lit.

99

Section 7

Troubleshooting

7.1.3.2

7.1.4

7.2

7.2.1

100

1MRS757453 C

Table 18:

LED

Uplink

Communication

Front communication LEDs

Communication ok

Steady green light

Flashing yellow light

Checking time synchronization

• Check the time synchronization via LHMI in Main menu/Monitoring/IED status/Time synchronization .

Running the display test

A short display test is always run, when auxiliary voltage is connected to the protection relay. The display test can also be run manually.

All the LEDs are tested by turning them on simultaneously. The display shows a set of patterns so that all the pixels are activated. After the test, the display returns to normal state.

Clear any indications on the display before running the display test manually.

Indication messages

Internal faults

Internal fault indications have the highest priority on the LHMI. None of the other LHMI indications can override the internal fault indication.

An indication about the fault is shown as a message on the LHMI. The text

Internal Fault with an additional text message, a code, date and time, is shown to indicate the fault type.

Different actions are taken depending on the severity of the fault. The protection relay tries to eliminate the fault by restarting. After the fault is found to be permanent, the protection relay stays in the internal fault mode. All other output contacts are released and locked for the internal fault. The protection relay continues to perform internal tests during the fault situation.

611 series

Operation Manual

1MRS757453 C

Section 7

Troubleshooting

The internal fault code indicates the type of internal relay fault. When a fault appears, the code must be recorded so that it can be reported to ABB customer service.

611 series

Operation Manual

GUID-DFF011AA-989D-4D59-B7A0-A282FEAD48D9 V1 EN

Figure 88: Fault indication

Table 19:

Fault indication

Internal Fault

System error

Internal Fault

File system error

Internal Fault

Test

Internal Fault

SW watchdog error

Internal Fault

SO-relay(s),X100

Internal Fault

SO-relay(s),X120

Internal Fault

SO-relay(s),X130

Internal Fault

PO-relay(s),X100

Internal Fault

PO-relay(s),X120

Internal Fault

PO-relay(s),X130

Internal Fault

Conf. error,X000

Internal Fault

Conf. error,X100

Internal Fault

Conf. error,X120

Internal Fault

Conf.error,X130

Internal fault indications and codes

Fault code

2

Additional information

An internal system error has occurred.

7

8

10

43

45

46

53

55

56

62

63

65

66

72

A file system error has occurred.

Internal fault test activated manually by the user.

Watchdog reset has occurred too many times within an hour.

Faulty Signal Output relay(s) in card located in slot X100.

Faulty Signal Output relay(s) in card located in slot X120.

Faulty Signal Output relay(s) in card located in slot X130.

Faulty Power Output relay(s) in card located in slot X100.

Faulty Power Output relay(s) in card located in slot X120.

Faulty Power Output relay(s) in card located in slot X130.

Card in slot X000 is wrong type, is missing, does not belong to original configuration or card firmware is faulty.

Card in slot X100 is wrong type or does not belong to the original composition.

Card in slot X120 is wrong type, is missing or does not belong to the original composition.

Card in slot X130 is wrong type, is missing or does not belong to the original composition.

Card in slot X000 is faulty.

Internal Fault

Card error,X000

Internal Fault

Card error,X100

Table continues on next page

73 Card in slot X100 is faulty.

101

Section 7

Troubleshooting

7.2.2

1MRS757453 C

Fault indication

Internal Fault

Card error,X120

Internal Fault

Card error,X130

Internal Fault

LHMI module

Internal Fault

RAM error

Internal Fault

ROM error

Internal Fault

EEPROM error

Internal Fault

FPGA error

Internal Fault

RTC error

Internal Fault

COM card error

83

84

116

80

81

82

Fault code

75

76

79

Additional information

Card in slot X120 is faulty.

Card in slot X130 is faulty.

LHMI module is faulty. The fault indication may not be seen on the LHMI during the fault.

Error in the RAM memory on the CPU card.

Error in the ROM memory on the CPU card.

Error in the EEPROM memory on the CPU card.

Error in the FPGA on the CPU card.

Error in the RTC on the CPU card.

Error in the COM card.

Warnings

Warnings are indicated with the text Warning additionally provided with the name of the warning, a numeric code and the date and time on the LHMI. The warning indication message can be manually cleared.

If a warning appears, record the name and code so that it can be provided to ABB customer service.

102

GUID-9EE0CFE1-0DB1-46B7-96A3-F3A0B6CC8018 V1 EN

Figure 89: Warning

Table 20: Warning indications and codes

Warning indication

Warning

Watchdog reset

Warning

Power down det.

Warning

IEC61850 error

Table continues on next page

Warning code

10

11

20

Additional information

A watchdog reset has occurred.

The auxiliary supply voltage has dropped too low.

Error when building the IEC 61850 data model.

611 series

Operation Manual

1MRS757453 C

7.3

7.3.1

7.3.2

611 series

Operation Manual

Section 7

Troubleshooting

Warning indication

Warning

Modbus error

Warning

Dataset error

Warning

Report cont. error

Warning

GOOSE contr. error

Warning

SCL config error

Warning

Logic error

Warning

SMT logic error

Warning

GOOSE input error

Warning

GOOSE Rx. error

Warning

AFL error

Warning

Comm. channel down

Warning

Unack card comp.

Warning

Protection comm.

Warning code

21

24

25

28

29

26

27

33

35

30

32

40

50

Additional information

Error in the Modbus communication.

Error in the Data set(s).

Error in the Report control block(s).

Error in the GOOSE control block(s).

Error in the SCL configuration file or the file is missing.

Too many connections in the configuration.

Error in the SMT connections.

Error in the GOOSE connections.

Error in the GOOSE message receiving.

Analog channel configuration error.

Redundant Ethernet (HSR/PRP) communication interrupted.

A new composition has not been acknowledged/accepted.

Error in protection communication.

Correction procedures

Rebooting the software

1.

Select Main menu/Configuration/General/Software reset and press .

2.

Change the value with or and press .

Restoring factory settings

In case of configuration data loss or any other file system error that prevents the protection relay from working properly, the whole file system can be restored to the original factory state. All default settings and configuration files stored in the factory are restored. Only the administrator can restore the factory settings.

1.

Select Main menu/Configuration/General/Factory setting and press .

2.

Set the value with or and press .

3.

Confirm by selecting Yes with or and press .

103

Section 7

Troubleshooting

7.3.3

7.3.4

104

1MRS757453 C

The protection relay restores the factory settings and restarts. Restoring takes 1...3

minutes. Confirmation of restoring the factory settings is shown on the display a few seconds, after which the relay restarts.

Avoid the unnecessary restoring of factory settings, because all the parameter settings that are written earlier to the relay will be overwritten with the default values. During normal use, a sudden change of the settings can cause a protection function to trip.

Restoring factory settings also resets the IP address for the rear port and the corresponding subnet mask to the factory default settings.

To restore factory settings from bootloader mode, press ESC + simultaneously for 5 seconds.

Setting passwords

If user authorization is off or the user is logged in as an administrator, user passwords can be set via the LHMI or WHMI or with PCM600.

Local passwords can be changed only via the LHMI. Remote passwords can be changed via the LHMI or WHMI or with PCM600.

1.

Select Main menu/Configuration/Authorization/Passwords .

2.

Select the password to be reset with or .

3.

Press , change the password with or and press again.

4.

Repeat steps 2 and 3 to set the rest of the passwords.

If the administrator password is lost, contact ABB's technical customer support to retrieve the administrator level access.

Identifying relay application problems

• Check that the function is on.

• Check the blocking.

• Check the mode.

• Check the measurement value.

• Check the connection to trip and disturbance recorder functions.

• Check the channel settings.

611 series

Operation Manual

1MRS757453 C

7.3.4.1

7.3.4.2

Section 7

Troubleshooting

Inspecting wiring

The physical inspection of wiring connections often reveals the wrong connection for phase currents or voltages. However, even though the phase current or voltage connections to protection relay terminals might be correct, wrong polarity of one or more measurement transformers can cause problems.

• Check the current or voltage measurements and their phase information from

Main menu/Measurements .

• Check that the phase information and phase shift between phases is correct.

• Correct the wiring if needed.

• Check the actual state of the connected binary inputs from Main menu/

Monitoring/I/O status/Binary input values .

• Test and change the relay state manually in Main menu/Tests/Binary outputs .

Sample data interruptions

Occasionally protection relays can receive corrupted or faulty measurement data during runtime. In these cases the operation system halts the corresponding application execution until correct data is received. In case of permanent faults, the measurement chain should be checked to remove the origin of the faulty measurement data.

In case of persistent faults originating from protection relay's internal faults, contact ABB for repair or replacement actions.

611 series

Operation Manual

105

106

1MRS757453 C

Section 8 Commissioning

8.1

8.2

8.2.1

Section 8

Commissioning

Commissioning checklist

Familiarize yourself with the protection relay and its functionality before you start the commissioning work.

• Ensure that you have all the needed station drawings such as single line and wiring diagrams.

• Ensure that your version of the technical manual applies to the protection relay version you test.

• Ensure that your setting software and connectivity packages work with the protection relay version you test.

• Find out if you need any additional software.

• Ensure that you have the relay settings either on paper or in electronic format. The settings and logic should be well documented.

• Inspect the settings to ensure that they are correct.

• Ensure that you have the correct cable to connect your PC to the protection relay's communication port. The RJ-45 port supports any CAT 5 Ethernet cable but the recommendation is STP.

• Test your PC's communication port before you go to the site.

• Find out who to contact if you have trouble and make sure you have a means to contact them.

• Find out who is responsible for the settings.

• Ensure that you have with you the proper test equipment and all needed connection cables.

• Ensure that the owner of the switchgear familiarizes you with the work site and any special aspects of it.

• Ensure that you know how to operate in emergency situations. Find out where the first aid and safety materials and exit routes are.

Checking the installation

Checking of the power supply

Check that the auxiliary supply voltage remains within the permissible input voltage range under all operating conditions. Check that the polarity is correct before powering the protection relay.

611 series

Operation Manual

107

Section 8

Commissioning

8.2.2

8.2.3

108

1MRS757453 C

Checking CT circuits

Check that the wiring is in strict accordance with the supplied connection diagram.

The CTs must be connected in accordance with the terminal diagram provided with the protection relay, both with regards to phases and polarity. The following tests are recommended for every primary CT or CT core connected to the protection relay.

• Primary injection test to verify the current ratio of the CT, the correct wiring up to the protection relay and correct phase sequence connection (that is L1, L2, L3.)

• Polarity check to prove that the predicted direction of the secondary current flow is correct for a given direction of the primary current flow. This is an essential test for the proper operation of the directional function, protection or measurement in the protection relay.

• CT secondary loop resistance measurement to confirm that the current transformer secondary loop DC resistance is within specification and that there are no high resistance joints in the CT winding or wiring.

• CT excitation test to ensure that the correct core in the CT is connected to the protection relay. Normally only a few points along the excitation curve are checked to ensure that there are no wiring errors in the system, for example, due to a mistake in connecting the CT's measurement core to the protection relay.

• CT excitation test to ensure that the CT is of the correct accuracy rating and that there are no short circuited turns in the CT windings. Manufacturer's design curves should be available for the CT to compare the actual results.

• Earthing check of the individual CT secondary circuits to verify that each threephase set of main CTs is properly connected to the station earth and only at one electrical point.

• Insulation resistance check.

• Phase identification of CT shall be made.

Both the primary and the secondary sides must be disconnected from the line and the protection relay when plotting the excitation characteristics.

If the CT secondary circuit is opened or its earth connection is missing or removed without the CT primary being de-energized first, dangerous voltages may be produced. This can be lethal and cause damage to the insulation. The re-energizing of the CT primary should be prohibited as long as the CT secondary is open or unearthed.

Checking VT circuits

Check that the wiring is in strict accordance with the supplied connection diagram.

611 series

Operation Manual

1MRS757453 C

8.2.4

8.2.4.1

8.2.4.2

Section 8

Commissioning

Correct possible errors before continuing to test the circuitry.

Test the circuitry.

• Polarity check

• VT circuit voltage measurement (primary injection test)

• Earthing check

• Phase relationship

• Insulation resistance check

The polarity check verifies the integrity of circuits and the phase relationships. The polarity must be measured as close to the protection relay as possible to ensure that most of the wiring is also checked.

The primary injection test verifies the VT ratio and the wiring all the way from the primary system to the protection relay. Injection must be performed for each phase-toneutral circuit and each phase-to-phase pair. In each case, voltages in all phases and neutral are measured.

Checking binary input and output circuits

Checking binary input circuits

• Preferably, disconnect the binary input connector from the binary input cards.

• Check all the connected signals so that both the input level and the polarity are in accordance with the protection relay specifications.

Do not use AC voltage. Binary inputs are rated for DC voltage only.

Checking binary output circuits

• Preferably, disconnect the binary output connector from the binary output cards.

• Check all connected signals so that both load and voltage are in accordance with the protection relay specifications.

611 series

Operation Manual

109

Section 8

Commissioning

8.3

8.3.1

1MRS757453 C

Authorizations

User authorization

The user categories have been predefined for the LHMI and WHMI, each with different rights and default passwords.

Passwords are settable for all predefined user categories. The LHMI password must be at least four and WHMI password at least nine characters. The maximum number of characters is 8 for the LHMI password and 20 for the WHMI password. Only the following characters are accepted.

• Numbers 0-9

• Letters a-z, A-Z

• Space

• Special characters !"#%&'()*+´-./:;<=>?@[\]^_`{|}~

User authorization is disabled by default and can be enabled via the

LHMI or WHMI path Main Menu/Configuration/Authorization/

Passwords .

Table 21:

Username

VIEWER

OPERATOR

ENGINEER

ADMINISTRATOR

Predefined user categories and default passwords

LHMI password

0001

WHMI password User rights remote0001 Only allowed to view

0002

0003

0004 remote0002 remote0003 remote0004

Authorized to make operations

Allowed to change protection relay parameters, but no operation rights

Full access

For user authorization for PCM600, see PCM600 documentation.

110 611 series

Operation Manual

1MRS757453 C

8.4

8.4.1

8.4.1.1

Section 8

Commissioning

Setting IED and communication

Setting the communication between protection relays and

PCM600

The communication between the protection relay and PCM600 is independent of the used communication protocol within the substation or to the NCC. It can be seen as a second channel for communication.

The media is always Ethernet and communication is based on TCP/IP.

Each protection relay has an Ethernet front connector for PCM600 access. Depending on the station concept and the used station protocol, additional Ethernet interfaces may be available on the rear side of the protection relay. All Ethernet interfaces can be used to connect PCM600.

When an Ethernet based station protocol is used, the PCM600 communication can use the same Ethernet port and IP address. The protection relay is able to separate the information belonging to the PCM600 dialog.

To configure the physical connection and the IP addresses:

1.

Set up or get the IP addresses of the protection relays.

2.

Set up the PC for a direct link or connect the PC or workstation to the network.

3.

Configure the IP addresses in the PCM600 project for each protection relay.

The addresses are used for communication between protection relays and

PCM600.

Communication link options between PCM600 and protection relays

Two options are available for the connection of PCM600 to the protection relay.

• Direct point to point link between PCM600 and the protection relay

• Indirect link via a station LAN or from remote via a network

Point to point link

The protection relay is provided with an RJ-45 connector on the LHMI. The front communication port is mainly used for configuration and setting purposes. The front communication port should not be connected to any Ethernet network.

The protection relay has a DHCP server for the front interface. The DHCP server assigns an IP address to the computer connected to the front interface. The computer's

LAN interface has to be configured to obtain the IP address automatically.

611 series

Operation Manual

111

Section 8

Commissioning

8.4.2

1MRS757453 C

LAN or WAN network

In TCP/IP networking, a LAN is often but not always implemented as a single IP subnet. A router connects LANs to a WAN. In IP networking, the router maintains both a LAN address and a WAN address. Design considerations for computer networks cover a wide range of topics including layout, capacity planning, and security. To some extent, the network configuration also depends on user preferences.

Communication settings

The protection relay is provided with an RJ-45 front port on the LHMI. This connector is mainly used for configuration and setting purposes. The rear port IP address and the corresponding subnet masks can be set via the LHMI. The front port uses a fixed IP address 192.168.0.254, and it also provides DHCP server to assign an IP address for the connected computer. The rear Ethernet interface has a factory default IP address

192.168.2.10 when the complete protection relay is delivered.

Different communication ports are available via optional communication modules.

Ethernet RJ-45 and optical Ethernet LC are the two rear port Ethernet communication options. Rear port Ethernet is intended for station bus communication.

Communication protocols used via Ethernet ports are IEC 61850-8-1 and Modbus

TCP/IP. The RS-485 twisted pair is used for rear port communication. Modbus RTU/

Modbus ASCII is the protocol available for serial communication.

If the protocol does not operate as expected, check that other serial protocols are not using the COM port.

Use the correct Ethernet connectors in the protection relay with redundant communication protocols like HSR and PRP. protection relays with HSR/PRP support have three Ethernet connectors and redundant Ethernet ports are marked as LAN A and LAN B. The third

Ethernet port without any LAN marking works as an interlink port.

Thus, an additional redundancy box is not needed. For example, laptops with PCM600 must be connected via a redundancy box to access a protection relay which is part of the HSR network.

The redundant communication module has three operation modes:

“Normal”, “HSR” and “PRP”. The operation mode can be changed from communication settings.

For more information, see the communication protocol manuals and the technical manual.

112 611 series

Operation Manual

1MRS757453 C

8.4.2.1

611 series

Operation Manual

Section 8

Commissioning

Serial communication ports and drivers

Depending on the hardware configuration, the protection relay can be equipped with one or several UART-based serial communication ports. The communication ports can be either galvanic (RS-485) or fiber optic. The protection relay uses serial ports and drivers as different types of serial communication protocol links.

Serial ports are called COM1, COM2 and so on, depending on the number of serial ports in the relay hardware configuration. Each COM port driver has its own setting parameters found via the LHMI in Configuration/Communication/COMn (n= 1,2,

…).

Since the same protection relay usually supports a variety of different communication hardware options, all COM port driver setting parameters are not relevant for every communication hardware type.

Table 22:

COM parameter

Fiber mode

Serial mode

CTS Delay

RTS Delay

Baudrate

COM port parameters in different HW options

Values

0 = No fiber

1 = Fiber light ON/loop

Hardware options 1)

Used in the fiber optic mode only.

Note that ”No fiber “ mode is the same as the galvanic mode.

2 = Fiber light OFF/loop

3 = Fiber light ON/star

4 = Fiber light OFF/star

0 = RS485 2wire

1 = RS485 4wire

0…60000 [ms]

0…60000 [ms]

1 = 300

2 = 600

For galvanic modes. RS-type depends on the communication card used.

Note that this setting parameter is relevant only if Fiber mode is set to “No

Fiber”.

RS232 mode only

RS232 mode only

All modes

3 = 1200

4 = 2400

5 = 4800

6 = 9600

7 = 19200

8 = 38400

9 = 57600

10 = 115200 [bits/sec]

1) When fiber mode is used, the Serial mode parameter value must be “RS485 2wire”.

In addition to setting the COM parameter, a communication card with many hardware options may also require changing the jumpers on the communication card.

113

Section 8

Commissioning

8.4.2.2

114

1MRS757453 C

Connection of a serial communication protocol to a specific serial port

The serial communication protocol (instance) settings include a setting parameter called Serial port n (n = protocol instance number). Setting options for this parameter are “COM1”, “COM2” and so on. The desired serial port for the protocol instance is selected through this parameter.

All link setting parameters are not found in the COMn settings.

Additional link setting parameters are found in the setting parameter list of the used serial protocol, since some serial protocol standards allow changes in link parameters, while other protocol standards do not.

Serial link diagnostics and monitoring

Serial communication diagnostics and monitoring is divided between the serial link driver and the serial communication protocol. The lower level physical and protocolindependent aspects of the UART-based serial communication are monitored in the serial link driver. Diagnostic counters and monitoring values are found via the LHMI in Monitoring/Communication/COMn (n= 1,2,…).

Depending on the communication protocol, the serial driver software receives single characters or complete protocol frames, based on the frame start/stop characters or on timing.

Monitoring data for a COM channel can be divided into basic and detailed diagnostic counters.

Table 23:

Parameter

Characters received

Frames received

Monitoring data for a COM channel

Range

0…2147483646

Type

Basic

0…2147483646 Basic

Description

Number of separate characters received.

Frames discarded 0…2147483646

Frames transmitted

0…2147483646

CD Lost 0…2147483646

Basic

Basic

Detailed

Number of successfully received complete frames.

Number of frames discarded.

Number of frames transmitted.

Collision

CTS Timeout

0…2147483646

0…2147483646

Detailed

Detailed

Detailed

Number of carrier-detect signal lost during receive.

Number of collisions detected.

Number of clear-to-send signal timeout errors.

Number of transmission timeout errors.

Transmission timeout

0…2147483646

Parity errors 0…2147483646

Table continues on next page

Detailed Number of character parity errors detected.

611 series

Operation Manual

1MRS757453 C

Section 8

Commissioning

Parameter

Overrun errors

Framing errors

Link status

Range

0…2147483646

0…2147483646

1

Type

Detailed

Detailed

Description

Number of character overrun errors detected.

Number of character overrun errors detected.

1 = Reset counters (by entering 1 the diagnostic counters are reset)

Whether all diagnostic counters are relevant depends on the communication hardware and communication protocol.

Table 24: Basic diagnostic counters

Counter

Characters received

Frames received

Frames discarded

Frames transmitted

Function

Counts all incoming non-erroneous characters.

This counter operates regardless of if the serial driver is set to detect a whole protocol link frame or just separate characters.

Counts all protocol specific non-erroneous frames received. Protocol-specific frames can be based on timing (for example, Modbus RTU) or on special start and stop characters (for example,

Modbus ASCII).

Counts all protocol-specific erroneous frames received. If the driver detects an error while receiving a frame, the frame is automatically discarded. This also means that the protocol in question will never receive a faulty frame from the driver. When this counter is increased, one of the detailed error counters is also incremented.

Counts all protocol-specific frames transmitted from the COM channel.

Table 25:

Counter

CD Lost

Detailed error counters

Collision

CTS Timeout.

Table continues on next page

Function

In RS-232 handshake mode, characters are to be received as long as Carrier Detect (CD) signal is active. This counter is incremented if the CD signal is lost during reception.

Counts transmission collisions. Used in RS-485 mode by some protocols where transmissions could collide. For example, DNP3 unsolicited mode.

In RS-232 handshake mode the Clear To Send

(CTS) signal is not received as reply to this device

Request To Send (RTS) signal.

611 series

Operation Manual

115

Section 8

Commissioning

8.4.2.3

8.4.2.4

116

1MRS757453 C

Counter

Transmission timeout.

Parity errors

Overrun errors

Framing errors

Function

In RS-232 handshake mode. If the CTS signal goes inactive during transmission then the transmission is halted. Transmission will be resumed when CTS goes active again. The whole frame transmission must anyhow be ready within a specified time. If this timeout elapses then this counter is incremented. Result will be that the end of the frame is not being transmitted out.

Counts parity errors detected in characters.

Counts overrun errors detected in characters.

Counts framing errors detected in characters

Table 26:

Parameter

Link status

Link status

Function

Link status in write direction: By writing 1 to the parameter the diagnostic counters are reset to 0.

Link status in monitoring direction: If the driver is in use by any communication protocol, the monitoring value shows 1. In other case, the value is 0.

Defining Ethernet port settings

Change the Ethernet port settings primarily via PCM600 to ensure that

PCM600 is able to export a consistent configuration to SYS600.

Ethernet port settings are recommended to be changed only when the device is stand-alone and properly configured.

1.

Select Main menu/Configuration/Communication/Ethernet/Rear port .

2.

Define the settings for the Ethernet port.

IP address

Subnet mask

Default gateway of the optional rear port Ethernet connector

Defining serial port settings

1.

Select Main menu/Configuration/Communication/COM1 or COM2 .

2.

Define the settings for the serial port.

It is possible to change the general serial communication parameters per port.

Select fiber or galvanic mode with the proper baud rate, parity and delays depending on the system architecture and the selected physical communication port.

611 series

Operation Manual

1MRS757453 C

8.4.2.5

8.4.2.6

8.4.3

8.4.3.1

Section 8

Commissioning

Setting communication protocol parameters

1.

Select Main menu/Configuration/Communication/<protocol> .

2.

Change the protocol specific settings.

Possible settings to be changed are, for example, the selected communication port, address and link mode.

Connecting jumper connectors

See the technical manual for details on jumper connectors.

Setting the local HMI

Changing the local HMI language

1.

Select Main menu/Language and press .

2.

Change the language using or .

3.

Press to confirm the selection.

4.

Commit the changes.

8.4.3.2

611 series

Operation Manual

GUID-8588E7BB-6C58-4D6E-8690-27D46738B25F V1 EN

Figure 90: Changing the LHMI language

To change the language using a shortcut, press and simultaneously anywhere in the menu.

Adjusting the display contrast

Adjust the display contrast anywhere in the menu structure to obtain optimal readability.

To increase the contrast, press simultaneously

To decrease the contrast, press simultaneously

and

and

.

.

117

Section 8

Commissioning

8.4.3.3

8.4.3.4

8.4.3.5

1MRS757453 C

The selected contrast value is stored in the non-volatile memory if you are logged in and authorized to control the protection relay. After an auxiliary power failure, the contrast is restored.

Changing display symbols

Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and

IEC-ANSI.

1.

Select Main Menu/Configuration/HMI/FB naming convention and press

.

2.

Change the display symbols with or .

3.

Press to confirm the selection.

The protection relay has to be rebooted if the WHMI display symbols are changed. With the LHMI, the change takes effect immediately.

Changing the default view

The default view of the display is Measurements unless set otherwise.

1.

Select Main menu/Configuration/HMI/Default view and press .

2.

Change the default view with or .

3.

Press to confirm the selection.

Setting the system time and time synchronization

1.

Select Main menu/Configuration/Time/System time .

2.

Select the parameter with or .

3.

Press , change the value with or and press again.

4.

Repeat steps 2 and 3 to set the rest of the system time parameters.

5.

Select Main menu/Configuration/Time/Synchronization/Synch source and press .

6.

Select the time synchronization source with or .

7.

Press to confirm the selection.

Setting daylight saving time

The protection relay can be set to determine the correct date for the DST shift every year. The UTC time is used to set the DST.

118 611 series

Operation Manual

1MRS757453 C

Section 8

Commissioning

1.

Set the DST on day (weekday) and DST off day (weekday) parameters to define on which week day the time shift occurs.

2.

Set the DST on date (day) , DST on date (month) and DST off date (month) parameters to define on which month and week the time shift occurs.

The DST on/off date must precede the selected DST on/off day and be within the same week as the DST shift.

Table 27: Possible date values for DST change on Sunday

Day of the DST shift

First Sunday of the month

DST on/off date (day)

1

Second Sunday of the month

Third Sunday of the month

Fourth Sunday of the month

Last Sunday, if the month has 30 days

Last Sunday, if the month has 31 days

8

15

22

24

25

For example, if the DST is observed from the last Sunday in March to the last

Sunday in October and the time shift occurs at 01:00 UTC, the setting parameters are the following.

DST on time (hours):

DST on time (minutes):

DST on date (day):

DST on date (month):

DST on day (weekday):

DST off time (hours):

DST off time (minutes):

DST off date (day):

DST off date (month):

DST off day (weekday):

2 h

0 min

25

March

Sunday

1 h

0 min

25

October

Sunday

Set the DST on day (weekday) and DST off day (weekday) to

"reserved" to determine the exact date and time for the DST shift.

Repeat the setting yearly, as the time for the DST shift is not on the same date every year.

To disable the DST, set the DST in use parameter to "False".

611 series

Operation Manual

119

Section 8

Commissioning

8.4.4

8.4.4.1

Setting IED parameters

Defining setting groups

Selecting a setting group for editing

1.

Select Main Menu/Settings/Edit setting group .

2.

Select the setting group to be edited with or .

3.

Press to confirm the selection.

4.

Edit the settings.

1MRS757453 C

120

GUID-3A58D472-E755-4244-9B1C-EA18EB6B5709 V1 EN

Figure 91: Selecting a setting group

Browsing and editing setting group values

1.

Select Main menu/Settings/Settings and press .

2.

Select the setting group to be viewed with or and press to confirm the selection.

GUID-6450A624-16A7-48AF-8639-B4F1757B5FCC V1 EN

Figure 92: Selecting a setting group

3.

To browse the settings, scroll the list with and and to select a setting press

.

4.

To browse different function blocks, scroll the list with and and to select a function block press . To move back to the list, press .

The function block list is shown in the content area of the display. On the left in the header, you see the current setting group, and on the right the menu path.

5.

To browse the parameters, scroll the list with and and to select a parameter, press .

The setting group values are indicated with #.

611 series

Operation Manual

1MRS757453 C

Section 8

Commissioning

6.

GUID-470022EF-8EF1-4DEE-8232-9551A5909021 V1 EN

Figure 93: Setting group parameter

To select a setting group value, press and to edit the value press .

GUID-AC6882D0-EAA3-4801-8F48-0AF386BBA42E V1 EN

Figure 94: Selecting the setting group value

Only values within the selected setting group can be changed.

7.

Press or to change the value and to confirm the selection.

GUID-96592CE2-D2ED-45E6-97EF-F6EC8FB9503C V1 EN

Figure 95: Editing the setting group value

The active setting group is indicated with an asterisk * .

Switching the Operation parameter of a function block on or off restarts all control and protection functions.

Activating a setting group

Protection relay settings are planned in advance for different operation conditions by calculating setting values to different setting groups. The active setting group can be changed by the protection relay application or manually from the menu.

1.

Select Main menu/Settings/Setting group/Active group and press .

611 series

Operation Manual

121

Section 8

Commissioning

1MRS757453 C

8.4.4.2

GUID-7745367A-2719-48D1-BB56-D1A0A61865B6 V1 EN

Figure 96: Active setting group

2.

Select the setting group with or .

3.

Press to confirm the selection or to cancel.

GUID-38B010F4-57F3-4089-8457-57C2EDE31683 V1 EN

Figure 97: Selecting the active setting group

4.

Commit the settings.

Remember to document the changes you make.

Relay parametrization

Protection relay parameters are set via the LHMI, WHMI or PCM600.

Setting parameters need to be calculated according to the electrical network conditions and the electrical characteristics of the protected equipment. The protection relay's settings need to be verified before the protection relay is connected to a system.

Document all changes to parameter settings.

For more information, see the PCM600 documentation.

122 611 series

Operation Manual

1MRS757453 C

8.4.4.3

8.4.4.4

8.5

8.5.1

Section 8

Commissioning

Defining disturbance recorder channel settings

1.

Select Main Menu/Configuration/Disturbance recorder/Channel settings .

2.

Press or to select the wanted channel and parameter.

3.

To change channel settings, press .

Each analog channel has an equal set of parameters and correspondingly, each binary channel has an equal set of parameters.

Configuring analog inputs

1.

Select Main Menu/Configuration/Analog inputs .

2.

Select the analog input to be configured with or .

3.

Press , change the value with or and press again.

For CTs, the secondary current and primary current need to be set to the correct values.

For VTs, the secondary voltage and primary voltage need to be set to the correct values.

Testing protection relay operation

The protection relay has to be in the test mode before the digital outputs and certain output signals of protection and other functions can be activated.

Selecting the IED test mode

The test mode can be activated using the LHMI. The green Ready LED is flashing to indicate that the test mode is activated. By default, the test mode can only be changed from the LHMI. Activation by remote client is possible, see the technical manual.

The Ready LED also flashes if the protection relay detects a diagnostic failure. Check the test mode setting and the protection relay's IRF alarm contact status to find the reason for the failure.

The test mode is useful for simulated testing of functions and outputs without providing current inputs.

1.

Select Main menu/Tests/IED test/Test mode and press .

611 series

Operation Manual

123

Section 8

Commissioning

1MRS757453 C

8.5.2

8.5.3

124

GUID-774C947C-70BA-479D-B795-C9222BD17715 V1 EN

Figure 98: Entering test mode

2.

Select the test mode status with or .

3.

Press to confirm the selection.

If the test mode is not cancelled, it remains on and the Ready LED remains flashing.

Testing the digital I/O interface

To activate or deactivate, for example, a digital output:

1.

Select Main menu/Tests/Binary outputs/X100 (PSM)/X100-PO1 and press

.

2.

Select the value with or .

3.

Press to confirm the selection.

If the optional BIO-module (X110) is included in the protection relay, the menu path could also be Main menu/Tests/Binary Outputs/

X110 (BIO)/<binary output> .

Testing functions

Activate or deactivate an output signal for protection or other function to test the function.

1.

Select Main Menu/Tests/Function tests/Current protection/<function block name> and press .

2.

Select the output signal to be activated or deactivated with or and press

.

3.

To deactivate all output signals for the function, select Reset with or and press .

611 series

Operation Manual

1MRS757453 C

8.5.4

Section 8

Commissioning

Selecting the internal fault test

The internal fault may be tested by using the LHMI. When enabling the test, the internal relay fault output contact is activated, the green Ready LED is flashing and internal fault test indication is shown on the LHMI. See the technical manual for the internal relay fault output contact location. The internal fault can only be activated by using the LHMI.

Differing from real internal fault situation, the other output contacts are not released and locked during the test. In other words, protection functions can operate and trip the outputs when the internal fault is tested.

1.

Select Main menu/Tests/IED test/Internal fault test and press .

8.5.5

611 series

Operation Manual

GUID-C60A750A-B76E-4676-A0AE-05BFF595A5D2 V1 EN

Figure 99: Internal fault test

2.

Select the value with or .

3.

Press to confirm the selection.

Selecting the IED blocked or IED test and blocked mode

The IED blocked mode and the IED test and blocked mode can be activated using the

LHMI. The yellow Start LED flashes when the device is in the IED blocked or IED test and blocked mode. The green Ready LED flashes to indicate that the IED test and blocked mode is activated. By default, the test mode can only be changed from the

LHMI. Activation by remote client is possible, see the technical manual.

The Ready LED also flashes if the IED detects a diagnostic failure.

Check the test mode setting and the protection relay's IRF alarm contact status to find the reason of the failure.

The test mode can be used for simulated testing of functions and outputs without providing current inputs. The IED blocked mode can be used to block the physical outputs to the process.

1.

Select Main menu/Tests/IED test/Test mode and press .

2.

Select the test mode status with or . Press to confirm the selection.

125

Section 8

Commissioning

8.6

1MRS757453 C

If the IED blocked or IED test and blocked mode is not cancelled, it remains on and the Start and/or Ready LEDs remain flashing.

ABB Product Data Registration

The ABB Product Data Registration feature traces composition changes in the protection relay's SW or HW. Traceability allows better support and maintenance possibilities.

After a composition change, an LCT indication is seen on the LHMI at the protection relay startup. The PCM600 reads the changed data from the protection relay.

Therefore a connection to the protection relay must be established first. Composition data can be read with PCM600 by enabling LCT during PCM600 installation and activating collection in PCM600 from 'Lifecycle Handling' menu. For detailed information see PCM600 online help.

The LCT indication is cleared in the same way as other indications. If composition data is not collected with PCM600, the indication reappears after protection relay's reboot.

If the LCT indication appears, update the protection relay composition to avoid information mismatch. The LCT indication does not affect the functionality of the protection relay.

GUID-4DC42A7C-150D-4B60-A4EC-679581F98F44 V1 EN

Figure 100: LCT indication

The number of composition changes can be seen from the Composition changes parameter in Main Menu/Monitoring/IED status .

126 611 series

Operation Manual

1MRS757453 C

Section 9 Glossary

611 series

Operation Manual

Section 9

Glossary

100BASE-FX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses fiber optic cabling

100BASE-TX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses twistedpair cabling category 5 or higher with RJ-45 connectors

AC Alternating current

ANSI

CAT 5

American National Standards Institute

A twisted pair cable type designed for high signal integrity

COMTRADE Common format for transient data exchange for power systems. Defined by the IEEE Standard.

CPU Central processing unit

CSV

CT

DAN

DC

DHCP

DPC

DST

EEPROM

EMC

Ethernet

Comma-separated values

Current transformer

Doubly attached node

1. Direct current

2. Disconnector

3. Double command

Dynamic Host Configuration Protocol

Double-point control

Daylight-saving time

Electrically erasable programmable read-only memory

Electromagnetic compatibility

A standard for connecting a family of frame-based computer networking technologies into a LAN

FB

FIFO

Firmware

FPGA

FTP

FTPS

Function block

First in, first out

System software or hardware that has been written and stored in a device's memory that controls the device

Field-programmable gate array

File transfer protocol

FTP Secure

127

Section 9

Glossary

128

1MRS757453 C

GOOSE

HMI

HSR

HTTPS

Generic Object-Oriented Substation Event

Human-machine interface

High-availability seamless redundancy

Hypertext Transfer Protocol Secure

HW

IEC

Hardware

International Electrotechnical Commission

IEC 61850 International standard for substation communication and modeling

IEC 61850-8-1 A communication protocol based on the IEC 61850 standard series

IED Intelligent electronic device

IEEE 1686

IP

IP address

IRF

Standard for Substation Intelligent Electronic Devices'

(IEDs') Cyber Security Capabilities

Internet protocol

A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol.

1. Internal fault

2. Internal relay fault

Inter-Range Instrumentation Group's time code format B IRIG-B

LAN

LC

LCD

LCP

LCT

LED

LHMI

Local area network

Connector type for glass fiber cable, IEC 61754-20

Liquid crystal display

Liquid crystal polymer

Life cycle traceability

Light-emitting diode

Local human-machine interface

MAC

MMS

Media access control

1. Manufacturing message specification

2. Metering management system

Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices.

Modbus ASCII Link mode using 7-bit ASCII characters

Modbus RTU Link mode using 8-bit binary characters

NCC Network control center

611 series

Operation Manual

1MRS757453 C

611 series

Operation Manual

Section 9

Glossary

PA

PBT

PC

PCM600

PRP

R/L

RAM

REB611

REF611

REM611

REU611

RJ-45

RoHS

ROM

RS-232

RS-485

RSTP

RTC

SAN

SCL

SMT

SNTP

STP

SVG

SW

TCP/IP

UTC

VT

WAN

WHMI

XRIO

Polyamide

Polybutylene terephthalate

1. Personal computer

2. Polycarbonate

Protection and Control IED Manager

Parallel redundancy protocol

Remote/Local

Random access memory

Busbar and multipurpose differential protection and control relay

Feeder protection and control relay

Motor protection and control relay

Voltage protection and control relay

Galvanic connector type

Restriction of hazardous substances

Read-only memory

Serial interface standard

Serial link according to EIA standard RS485

Rapid spanning tree protocol

Real-time clock

Single attached node

XML-based substation description configuration language defined by IEC 61850

Signal Matrix tool in PCM600

Simple Network Time Protocol

Shielded twisted-pair

Scalable vector graphics

Software

Transmission Control Protocol/Internet Protocol

Coordinated universal time

Voltage transformer

Wide area network

Web human-machine interface eXtended Relay Interface by OMICRON

129

130

131

ABB Distribution Solutions

Distribution Automation

P.O. Box 699

FI-65101 VAASA, Finland

Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/relion

© Copyright 2019 ABB. All rights reserved.