ABB CK10B, CK11B, CK12B, CK10C, CK11C Installation Instructions

Add to My manuals
2 Pages

ABB CK10B, CK11B, CK12B, CK10C, CK11C contactors are suitable for use on a circuit capable of delivering not more than 30,000 RMS symmetrical amperes, 600 volts maximum when protected by H, J, K, RK5 class fuses, or a circuit breaker having an interrupting rating not less than 10,000 RMS symmetrical amperes, 600 volts maximum. They can be used in three-phase or four-phase applications, with horsepower ratings ranging from 220 to 606 kW. These contactors are equipped with electronic modules that allow them to be used with AC or DC coils. They also have a variety of features that make them ideal for use in a wide range of applications, including:

advertisement

ABB CK10B, CK11B, CK12B, CK10C, CK11C Installation Instructions | Manualzz

DEH-022

CK10C-CK11C

Installation Instructions

WARNING: Disconnect power from source before installing, modifying or servicing.

CONTACS

MOUNTING

WIRING

COIL CHANGE

IEC COUNTRIES

CK10C-3, CK11C-3

M

AC1 AC3

220V

240V

P (kW)

380V

415V 500V

220V

240V

P (kW)

380V

415V 500V

228 395 519 125 220 300

266 460 606 160 280 400

CK10C-4, CK11C-4

Cat.No.

CK10C

CK11C

AC/

DC Pole

E

3

4

E

3

4

11

11

USA & CANADA (UL, CSA)

Three-phase

A2

Horsepower kW

50

Hz

Motor Voltage-60 Hertz

A1

Coil

200-

208

220-

240

440-

480

550-

600

380/

415

125 150 300 400 220

Starter

Max.

Fullload

Amps

398

150 200 400 500 280 480

COIL

With electronic module. AC/DC (Types CK___E___)

COD.

Voltage

D(1)

24V

28V

F

42V

48V

J

110V

127V

N

220V

250V

U

380V

415V

Y

440V

500V

Suitable for use on circuit capable of delivering not more than

10,000 RMS symmetrical amperes, 600 volts maximun when protect by H, J, K, RK5 class fuses, or a circuit breaker having an interrupting rating not less than 10,000 RMS symmetrical amperes, 600 volts maximun.

Use only whitn overload relay manufactured by GE POWER

CONTROLS, serie RT.

For use in enclosures whith minimum dimensions 42 in. by

16 in. by 10 in.

USA & CANADA

USE LUG KIT CKX01

Suitable For Use On A Circuit Capable Of Delivering Not More Than (a) RMS Symmetrical Amperes, (b)

Volts Maximun, When Protected by (c) Class Fuses Rated (d) Amperes Maximun, or When Protected by (e) Type (f) Circuits Breakers, Rated (g) Amperes Maximun. For Use In Enclosures With Minimum

Overall Dimensions of (h)."

Catalog

Number

CK10C

CK11C

CK10C

CK11C

CK10C

CK11C

CK10C

CK10C

CK11C

CK11C

CK10C

CK10C

CK11C

CK11C

Max

FLA

Overload

Relay

Model

Short Circuit

Rating

382

480

382

480

382

480

---

---

---

382

382

480

480

---

---

---

---

---

---

---

RT5,RT5L 382

382

480

480

RT5,RT5L

RT5,RT5L

RT5,RT5L

RMS Sym

Amperes

(a)

30,000

30,000

30,000

30,000

100,000

100,000

65,000

35,000

65,000

35,000

65,000

35,000

65,000

35,000

Maximum Fuse Size

Volts

Max

(b)

480

480

480

480

480

480

480

480

600

600

600

600

600

600

Class

(c)

H, RK5, J or L

H, RK5, J or L

---

---

J

J

---

---

---

---

---

---

---

---

Maximum Breaker

Max

Size

(d)

1000A

1000A

---

---

600A

600A

---

---

---

---

---

---

---

---

Make

(e)

---

--any any

---

---

GE

GE

GE

GE

GE

GE

GE

GE

Size

(f)

---

--any any

---

---

SGL

SGH

SGL

SGH

SGL

SGH

SGL

SGH

Model

Max

Size

(g)

---

---

600A

600A

---

---

600A

600A

600A

600A

600A

600A

600A

600A

Minimum

Enclosure

Volume

(cu in)

(h)

6,720

6,720

6,720

6,720

11,960

11,960

11,960

11,960

11,960

11,960

11,960

11,960

11,960

11,960

START-STOP

1

14

13

FIGURE A

PUSHBUTTONS

OFF ON

( OMIT WIRE "B" )

FIGURE B

2 POSITION

SELECTOR SWITCH

HAND

OFF

AUTO

1

COIL

13

1

(IF USED)

FOR

I

CONNECTIONS

REFER TO

FIGURE A

FIGURE B

OR

FIGURE C

(IF USED)

CONTACTOR

STARTER: (Contactor

& Overload)

13

1

COIL

14

WIRING DIAGRAM

L3

L1 L2

WIRE "B"

13

14

21

L1

22

T1

OL

T1

A1

M

L2

T2

OL

T2

A2

L3

T3

OL

T3

( OMIT WIRE "B" )

COIL T2

T1

MOTOR

T3

REMOTE

DEVICE

L1

FIGURE C

3 POSITION

SELECTOR SWITCH

D

13

FRONT VIEW

31 43

32

44

WIRE

"A"

95

96

97

OL

96

OL

M-Line Contactor. I-Indicating Light. D-Maintaining

Contac Pilot Device. OL-Thermal Overload Relay.

For Separate Control-On Contactors, omit wire "A" and connect source to coil and to 1 on control device.

Product Quality Inspection Certificate

The product passed Quality Inspection

Country of Origin:

Manufacturer:

Factory address:

Poland

GE Power Controls ul Lodowa 88

92-313 Lodz (Poland)

NOTE: Additional over-current protection may be required. Refer to the

National Electrical Code or local electrical code as required.

Single phase applications: Single phase starters require all three overload heaters to be energized for proper operations. For single phase operations use separate conductor and connect overload load terminal T2 to contactor line terminal L3. Connect load to overload terminals T1 and T3. Connect incoming power to contactor line terminals L1 and L2.

These instructions do not purport cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the GE Company.

Power Controls B.V.

400B60115P-03

GE ED&C

Plainville, CT USA

72 125 165 45

123 214 281 55

75 100

90 100

CK75C

CK08C

A

E

A

E

3 11

3

11

40 50 100 125 75 10 25 140

50 60 125 150 90 15 30 156

114 196 259 65 110 132 CK85B

A

E

3 11

60 75 150 150 132 192 1

76 143 173 30 55 75 CK07B

A

E

4 11 N/A N/A N/A N/A N/A N/A

3

1

2

228 395 519 125 220 300

266 460 606 160 280 400

381 658 823 220 375 480

E

E

E

3

4

3

4

3

4

11

11

11

125 150 300 400 -

200 250 400 500 -

200 250 500 600 -

398

480

590

473 823 1083 220 375 480 CK13B A

3

4

00

11

N/A N/A N/A N/A N/A N/A

DEH-022 Installation Instructions

CONTACS

MOUNTING

WIRING

WARNING: Disconnect power from source before installing, modifying or servicing.

COIL CHANGE

Three Poles

IEC COUNTRIES

M

AC1 AC3

220V

240V

P (kW)

380V

415V 500V

220V

240V

P (kW)

380V

415V 500V

381 658 823 220 375 480

COIL

With electronic module. AC/DC (Types CK___E___)

COD.

Voltage

D(1)

24V

28V

F

42V

48V

J

110V

127V

N

220V

250V

U

380V

415V

Y

440V

500V

Cat.No.

CK10B

CK11B

CK12B

AC/

DC Pole

E

E

00

11

00

11

E

11

Four Poles

USA & CANADA (UL, CSA)

Three-phase

A2

Horsepower

Motor Voltage-60 Hertz kW

50

Hz

A1

Coil

200-

208

220-

240

440-

480

550-

600

380/

415

Starter

Max.

Fullload

Amps

200 250 500 600 -

Suitable for use on circuit capable of delivering not more than

10,000 RMS symmetrical amperes, 600 volts maximun when protect by H, J, K, RK5 class fuses, or a circuit breaker having an interrupting rating not less than 10,000 RMS symmetrical amperes, 600 volts maximun.

Use only whitn overload relay manufactured by GE POWER

CONTROLS, serie RT.

For use in enclosures whith minimum dimensions 42 in. by

16 in. by 10 in.

USA & CANADA

START-STOP

1

14

13

FIGURE A

PUSHBUTTONS

OFF ON

( OMIT WIRE "B" )

FIGURE B

2 POSITION

SELECTOR SWITCH

HAND

OFF

AUTO

1

COIL

13

1

(IF USED)

FOR

OR

I

CONNECTIONS

REFER TO

FIGURE A

FIGURE B

FIGURE C

(IF USED)

CONTACTOR

STARTER: (Contactor

& Overload)

13

1

COIL

14

WIRING DIAGRAM

L2 L3

L1

WIRE "B"

13

14

21

L1

22

T1

OL

T1

A1

M

L2

T2

OL

T2

A2

L3

T3

OL

T3

( OMIT WIRE "B" )

COIL

T2

T1

MOTOR

T3

REMOTE

DEVICE

L1

FIGURE C

3 POSITION

SELECTOR SWITCH

D

13

FRONT VIEW

31 43

32

44

WIRE

"A"

95

96

97

OL

96

OL

M-Line Contactor. I-Indicating Light. D-Maintaining

Contac Pilot Device. OL-Thermal Overload Relay.

For Separate Control-On Contactors, omit wire "A" and connect source to coil and to 1 on control device.

NOTE: Additional over-current protection may be required. Refer to the

National Electrical Code or local electrical code as required.

Single phase applications: Single phase starters require all three overload heaters to be energized for proper operations. For single phase operations use separate conductor and connect overload load terminal T2 to contactor line terminal L3. Connect load to overload terminals T1 and T3. Connect incoming power to contactor line terminals L1 and L2.

USE LUG KIT CKX01

Suitable For Use On A Circuit Capable Of Delivering Not More Than (a) RMS Symmetrical Amperes, (b)

Volts Maximun, When Protected by (c) Class Fuses Rated (d) Amperes Maximun, or When Protected by (e) Type (f) Circuits Breakers, Rated (g) Amperes Maximun. For Use In Enclosures With Minimum

Overall Dimensions of (h)."

Catalog

Number

Max

FLA

Overload

Relay

Model

Short Circuit

Rating

CK10B 382 RT5A,RT5LA

CK10B 382

CK10B 382

RT5B,RT5LB

RT5C,RT5LC

CK10B 382

CK10B 382

RT5D,RT5LD

---

CK11B 480 RT5A,RT5LA

RT5B,RT5LB CK11B 480

CK11B 480

CK11B 480

RT5C,RT5LC

RT5D,RT5LD

RT5D,RT5LD CK11B 480

CK11B 480

CK12B 590

CK12B 590

CK12B 590

CK12B 590

CK12B 590

CK12B 590

---

RT5A,RT5LA

RT5B,RT5LB

RT5C,RT5LC

RT5D,RT5LD

RT5D,RT5LD

---

RMS Sym

Amperes

(a)

Volts

Max

(b)

18,000 600

18,000 600

18,000 600

18,000 600

18,000 600

30,000 600

30,000

30,000

30,000

600

600

600

30,000

30,000

30,000

600

600

600

30,000

30,000

30,000

600

600

600

30,000

30,000

600

600

Maximum Fuse Size

Class

(c)

K

K

K

K

K

K

K

K

K

K

K

K

K

K

K

K

K

Maximum Breaker

Size

Minimum

Enclosure

Volume

(cu in)

Max

Size

(d)

Make

(e)

400A

600A

800A

800A

800A

400A

600A

800A

900A

---

---

---

1000A ---

1000A ---

400A ---

---

---

---

---

---

---

600A

800A

900A

1000A

1000A

---

---

---

---

---

Model

Max

Size

(g) (f) (h)

--1000 11,960

--1000 11,960

---

---

---

1000

1000

1000

11,960

11,960

11,960

--1200 11,960

---

---

---

1200

1200

1200

11,960

11,960

11,960

---

---

---

1200

1200

1200

11,960

11,960

11,960

---

---

---

1200

1200

1200

11,960

11,960

11,960

---

---

1200

1200

11,960

11,960

Product Quality Inspection Certificate

The product passed Quality Inspection

Country of Origin:

Manufacturer:

Factory address:

Poland

GE Power Controls ul Lodowa 88

92-313 Lodz (Poland)

These instructions do not purport cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the GE Company.

Power Controls B.V.

400B60115P-03

GE ED&C

Plainville, CT USA

473 823 1083 220 375 480 CK13B A

3

4

00

11

N/A N/A N/A N/A N/A N/A