ABB CP-PX 24/10.5 & CP-PX 24/14.6 Instructions
Add to My manuals2 Pages
ABB CP-PX 24/10.5 & CP-PX 24/14.6 are primary switch mode power supplies, designed for a variety of industrial applications. With their wide input voltage range (90-132 / 180-264 V AC) and adjustable output voltage (21.6 - 26.4 V DC), these devices offer great flexibility and can be used in a variety of electrical systems. The power supplies are highly efficient (typ. 86%), feature constant current limiting and automatic recovery after a fault condition, and provide protection against overvoltage, overload, and short circuit.
advertisement
I
(EN) Illustrations of the products
(ZH)
产品外形说明
CP-PX 24/10.5
CP-PX 24/14.6
(EN) Operating and installation instructions
Primary switch mode power supplies CP-PX range
Note: These operating and installation instructions cannot claim to contain all detailed information of all types of this product range and can even not consider every possible application of the products. All statements serve exclusively to describe the product and have not to be understood as contractually agreed characteristics.
Further information and data is obtainable from the catalogues and data sheets of this product, from the local ABB sales organisations as well as on the ABB homepage www.abb.com. Subject to change without prior notice. The
English text applies in cases of doubt.
Warning! Hazardous voltage! Installation by person with electrotechnical expertise only and in accordance with the speci fi c national regulations (e.g., VDE, etc). Before installing this unit, read these operating and installation instructions carefully and completely. The devices are maintenance-free chassis-mounted units.
(ZH) 操作与安装指南
初级开关电源 CP-PX
注意: 本操作指南不包含技术数据和全部应用说明 , 所有数据只是具有对产品特性进行说明的作用 , 因此不具备
法律效应。详细说明请参阅技术样本或联络 ABB 当地办事处或浏览 ABB 网站( www.abb.com
)。如有更改恕不通
知。并以英文为标准。
警告!危险电压!仅可由电气专业人员安装且需符合特定的国家规定(如 VDE
读该安装说明。此产品为免维护底板安装器件。
等)。安装前 , 请仔细且全部阅
32.5±0.3
32.0±0.3
150.0±0.3
150.0±0.3
1.2 Nm (10.5 lb.in)
4.0 x 0.8 mm (0.157 x 0.031
" ) or PH2
1 X 10 mm (0.394")
0.3...4.0 mm² (22...10 AWG)
1 X 10 mm (0.394")
0.3...4.0 mm² (22...10 AWG)
1 X 10 mm (0.394")
0.3...4.0 mm² (22...10 AWG)
For all terminals.
LED
Output voltage U out
U out
OUTPUT OK:
LED green
215.0±1
(EN) A: the screw hole for mounting. The screw depth in module <= 4 mm.
B: Screw torque: M3.0 screw < 0.75 N.m, M4.0 screw < 0.8 N.m.
C: The min. distance between other module is 20 mm.
(ZH) 说明:
A :客户安装孔 , 其中螺纹孔处安装螺钉在电源内不应超过 4 mm ;
B :建议扭矩 : M3.0
螺钉 < 0.75 N.m, M4.0
螺钉 < 0.8 N.m
;
C :安装时与其它器件的最小间距为 20 mm 。
输入电压选择开关
( Input Voltage selection Switch )
(EN) Safety instructions and warnings
Disconnect system from supply network! protect against switching on.
Before start of operation: unit. Before operation the following must be ensured:
•
• ovided for the end product to disengage unit and supply cables from supply mains if required.
• The protective earth conductor must be connected to the terminal .
• Rate the output lines for the output current of the device and connect them with the correct polarity.
• ( min. 20 mm).
In operation:
• Do not modify the installation (primary and secondary side)! High current! Risk of electric arcs and electric shock
(danger to life)!
• Risk of burns: Depending on the operation conditions the enclosure can become very hot.
• If the internal fuse blows, most probably the device is defective. In this case, an examination of the device by the
manufacturer is necessary.
Warning: High voltage! Stored energy! Energy hazard at output!
The device contains components with high stored energy and circuits with high voltage! Do not introduce any objects into the device, and do not open the unit. With some devices of this range the output is capable of providing hazardous energy. Ensure that the service personnel is protected against inadvertent contact with parts carrying energy.
Because of no PFC, CP-PX 24/10.5 and CP-PX 24/14.6 are not intended to be connected to public low-voltage distribution system according the national directive.
(ZH) 安全指示和警告
将系统与电源断开
在安装 、 维护和修改系统之前 , 先将系统与电源断开。
开始运行前:
注意!不正确的安装/操作可能会带来不安全或运行故障 , 甚至损坏电源。开始运行前必须保证 :
• 按国家标准(一级保护)将电源连接到主回路。
• 电源电缆和系统元件必须有熔断器保护。在主回路和电源之间必须安装断开设备(用作电源从主回路断开)。
• 保护地导线必须接。
• 注意电源输出电流的极性 , 正确连接输出导线。
• 安装电源时必须考虑有效的通风散热间隙 ( 最小 20 mm )。
运行中:
• 不要更改安装(初级和次级)!高电流 !电弧和电击危险(生命危险)!
• 灼热危险:运行环境可能会使外壳非常热。
• 如果内部熔断器熔断 , 电源很可能被损坏。必须由生产商检测。
警告:高电压!存储能量!输出端危险!
电源包含有高能量存储元件 , 回路带高电压!严禁在电源中放入其它物体 , 严禁开盖!因为电源带危险能量 , 请
确保维护人员可以防护由于疏忽碰触到高能量器件。
由于该产品系列没有 PFC ,所以按照国家规定, CP-PX 24/10.5
和 CP-PX 24/14.6
不能用于公共低压配电系统。
Ⅱ
(EN)
(ZH)
Characteristic curves of input voltage T a
= 25 ℃
输入电压降额曲线 T a
= 25 ℃
I out
[A]
I out
[A]
Input voltage [V]
Input voltage [V]
Ⅲ
(EN) Characteristic curves of temperature
(ZH) 温度特性曲线
Ambient temperature [ ℃ ]
Ambient temperature [ ℃ ]
IV
(EN) Mounting:
1. Screw installation
2. DIN-rail installation
(ZH) 安装:
1. 螺钉安装
2. DIN导轨安装
Thickness=T
M3×L screw with double washers(L=T+5)
Thickness=T
(EN) Electrical connection:
Input side [L, N, ]
Connect the input terminals L, N, (Fig. I ).
Cable cross sections, stripping length of the cable, tightening torque etc. - see technical data.
The protective earth conductor must be connected (class of protection I).
The installation must be executed acc. EN 62368-1, provide a suitable disconnecting device (e.g., line protection switch) in the supply line.
Fuse protection of the input side - see technical data.
Output side [+,+,-,-]
Rate the lines for the maximum output current or provide a separate fuse protection.
Fuse protection of the output side - see technical data.
We recommend choosing the cable cross section as large as possible in order to minimize voltage drops.
Observe the polarity.
The power supplies are overvoltage, overload and short-circuit proof (see technical data).
Operating/Function:
Adjustment of the output voltage:
The output voltage can be adjusted in the range of 21.6 - 26.4 V DC by means of the potentiometer “V Out”.
M3×L screw with double washers(L=T+5)
(ZH) 电气连接:
输入侧 [L, N, ]
输入端子的连接 L, N, (图 I )
导线截面积、剥线长度和锁紧力矩等 -- 请参见技术参数
保护接地必须连接 (保护等级
安装必须遵守 EN 62368-1
I )
,在供电回路中提供合适的断开设备(如线路保护开关)
输入侧的熔断器保护 -- 请参见技术参数
输出侧 [+,+,-,-]
根据最大输出电流来选择导线,或提供单独的熔断器保护
输出侧的熔断器保护 -- 请参见技术参数
我们建议导线的截面积尽可能大,以减小压降
注意极性
电源带过压、过载和短路保护(参见技术参数)
运行/功能:
输出电压的调节
:
输出电压可通过电位计 “V Out” 在 21.6 - 26.4 V DC 之间进行调节。
Technical data
Data at Ta = 25 o C, Uin = 230 V AC and rated values, unless otherwise indicated
Type
Input circuit - Supply circuit
Rated input voltage U in
Input voltage range
Frequency range AC
Typ. input current at 115 V AC at 230 V AC
Typical power consumption
Hold-up time at 230 V AC at 115 V AC at 230 V AC
Recommended backup fuse for wire protection at 1.5 mm²
Output circuit - Power output
Rated output power
Rated output voltage
Adjustment range of the output voltage
Rated output current I r
-20 °C ≤ T a
≤ 50 °C
Current limiting at short circuit
Derating of the output current 50 °C ≤ T a
≤ 70 °C
Residual ripple and switching peaks acc. to IEC/EN 61204, class A
General data
Ef fi ciency
Degree of protection (IEC/EN 60529)
Protection class (IEC/EN 61140)
Environmental data
Ambient temperature ranges operation rated load storage
Isolation data
Pollution degree
Overvoltage category (EN 62368-1) < 2000 m
CP-PX 24/10.5
CP-PX 24/14.6
L, N
115 / 230 V AC, by switch
90-132 / 180-264 V AC, by switch
47-63 Hz
5 A
3 A
293 W
6.5 A
4 A
407 W
14 ms
20 ms
1 pole miniature circuit breaker ABB type S 200, with B or C characteristic, max. rating 16 A
+, -
250 W 350 W
24 V DC
21.6 - 26.4 V DC
10.5 A 14.6 A
Constant current, recovers automatically after fault condition is removed
4%/°C
1)
≤ 120 mVp-p
Typ.86% housing : IP 20
I
-20...+60 °C (-4...+140 °F)
-20...+50 °C (-4...+122 °F)
-40...+85 °C (-40...+185 °F)
2
II
1) Constant current: If there is a short circuit or overload, the current of power supply is limited to a value but the output voltage is cut to almost zero.