ABB Power Supply Instructions
Add to My manuals8 Pages
ABB Power Supply is a highly flexible and reliable power supply unit designed to meet the demanding requirements of various industrial applications. It offers a wide range of features and capabilities that make it an ideal choice for powering sensitive electronic equipment, control systems, and other critical loads.
Here's a brief overview of the key features and possible use cases of the ABB Power Supply:
-
Wide input voltage range: The power supply can operate with input voltages ranging from 85 to 264 VAC, making it suitable for use in a variety of electrical environments.
-
Regulated output voltage: The power supply provides a stable and regulated output voltage, ensuring consistent performance of connected equipment.
advertisement
GE Energy
Industrial Solutions
GEH-6253 Installation Instructions
Power Supply Assembly
For Spectra
®
RMS Molded-Case Circuit Breakers with micro EntelliGuard
TM
, MicroVersaTrip
®
PM or MicroVersaTrip
®
Plus Trip Units
For Catalog Number SPSAA
Circuit Breaker Accessory
Overview
The General Electric Power Supply Assembly is used to provide +24Vdc Control Power to Spectra ® RMS Molded-
Case Circuit Breakers with micro EntelliGuard TM or
MicroVersaTrip ® PM/Plus Trip Units via the Distribution
Cable System.
The Power Supply Assembly also provides power to the
Voltage Conditioner Assembly or Voltage Conditioner
Plate. Spectra ® RMS Molded-Case Circuit Breakers with micro EntelliGuard™ (with advanced metering) and
MicroVersaTrip ® PM Trip Units require connection to a
Voltage Conditioner Assembly or Voltage Conditioner
Plate to function properly.
The Power Supply Assembly is rated 24 watts (+24Vdc@
1.0 amp) and has the maximum capacity to power a
Distribution Cable System consisting of either a Voltage
Conditioner Assembly or a Voltage Conditioner Plate
AND 20 Spectra ® RMS Molded-Case Circuit Breakers with micro EntelliGuard TM or MicroVersaTrip ® PM/Plus
Trip Units with a maximum system cable length of 40 feet.
The assembly requires a minimum input voltage of
85Vac @ 60 Hz to operate properly (the maximum voltage rating is 240Vac @ 60 Hz). This input must
be fused with 2-amp class CC fuses (not included).
The Power Supply Assembly is designed to operate in temperatures between 0°C and 70°C.
GEH-6253 Installation Instructions
Figure 1 shows how the Power Supply Assembly is used in a typical MicroVersaTrip ® PM system. Figure 2 shows how the Power Supply Assembly is used in a typical MicroVersaTrip ® Plus system. The micro EntelliGuard TM Trip Unit can be used with either configuration, i.e. Figure 1 or Figure 2. The connection diagram shown in Figure 2 applies to micro EntelliGuard TM Trip Units with Basic Metering.
Figure 1. Typical MicroVersaTrip ® PM Trip Unit System detailing the Power Supply Assembly.
GEH-6253 Installation Instructions
Figure 2. Typical MicroVersaTrip ® Plus Trip Unit System detailing the Power Supply Assembly.
GEH-6253 Installation Instructions
Supplemental 24Vdc input terminals are provided for systems that have access to an external +24Vdc power supply. If this supplemental input is connected, the assembly will continue to pass the control power to breakers and accessories connected to the Distribution
Cable System if the primary AC power is lost or drops below the 85Vac minimum requirement. This backup input must meet ANSI C37.90.1 for oscillatory and fast transient surges (the Power Supply Assembly provides this protection for the primary AC input).
• “Output to 24Vdc”
– Two-screw terminal block for optional control power output (in lieu of using the Distribution Cable System).
• “Supplemental Input 24Vdc”
– Two-screw terminal block for connection of an external +24Vdc power supply.
By plugging the Power Supply Assembly into the
Distribution Cable System, you create system wide signals that are available to all breakers connected to the system; a list of those functions appears in Table 2.
Additional 24Vdc output connections are supplied for applications where +24Vdc control power is required independent of the Distribution Cable System (i.e. feeding an Air Circuit Breaker or Insulated Case Breaker with a
MicroVersaTrip ® PM/Plus or EntelliGuard TM TU Trip Unit).
NOTE: THE POWER SUPPLY ASSEMBLY IS SIZED FOR A
MAXIMUM OF 20 BREAKERS . Use of the Power Supply
Assembly to provide voltage sensing signals and/or
+24Vdc control power to a main Air Circuit Breaker or a main Insulated Case Breaker with a MicroVersaTrip ®
PM/Plus or EntelliGuard TM TU Trip Unit reduces the total quantity of 20 Spectra ® RMS Molded-Case Circuit
Breakers with micro EntelliGuard TM or MicroVersaTrip ®
PM/Plus Trip Units by one. The overall maximum cabling length of the system remains 40 feet.
Table 2. Signals Available on the Distribution Cable System by connection of the Power Supply Assembly.
Spectra with
® RMS ™ Breaker micro EntelliGuard™ or
MicroVersaTrip ® PM Trip Unit
Control Power (+24Vdc)
Spectra ® RMS Breaker with
MicroVersaTrip ® Plus or micro EntelliGuard™ with
Basic Metering Trip Unit
Control Power (+24Vdc)
Control Power (-common) Control Power (-common)
Dimensions, Weights and Wiring Diagrams
A Power Supply Assembly dimensioned drawing is provided in Figure 3 to assist in mounting the assembly.
The maximum unit weight is two and a half pounds.
The Power Supply Assembly contains five connection points. The following list contains a description and type of connection points.
• “To Distribution Cable”
– 12-pin plug connector that mates with the 12-pin receptacle of a Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60).
• “To Voltage Conditioner”
– 12-pin plug connector that mates with the 12-pin receptacle of a Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60). For
Spectra ® RMS Molded-Case Circuit Breakers with
MicroVersaTrip ® PM Trip Units, the other end of the harness MUST connect to either a Voltage
Conditioner Assembly (catalog number SVCAA) or a Voltage Conditioner Plate (catalog number
SVCA120Y, SVCA208Y, SVCA240D, SVCA277Y,
SVCA480Y, SVCA480D or SVCA600D) for the breaker to function properly.
• “Input”
– Three-screw terminal block for connection of the primary AC source (85Vac to 240Vac @ 50/60 Hz)
AND a ground connection.
Figure 3. Dimensioned drawing of the Power Supply Assembly
(dimensions shown in inches).
GEH-6253 Installation Instructions
Figure 4 shows how the Power Supply Assembly is used in a typical MicroVersaTrip ® PM system. Figure 5 shows how the Power Supply Assembly is used in a typical MicroVersaTrip ® Plus system. The micro EntelliGuard TM Trip Unit can be used with either configuration, i.e. Figure 4 or Figure 5. The connection diagram shown in Figure 5 applies to micro EntelliGuard TM Trip Units with Basic Metering.
Figure 4. Wiring connections to the Power Supply Plate for a typical MicroVersaTrip ® PM System.
GEH-6253 Installation Instructions
Figure 5. Wiring connections to the Power Supply Plate for a typical MicroVersaTrip ® Plus System
GEH-6253 Installation Instructions
Connections
The screw terminals on the Power Supply Assembly are labeled by function for clarity. The terminal strip pocket will accommodate a spade lug or ring terminal with a tongue width up to 0.320 inches. The terminal screw size is 10-32. To make the connection, attach an appropriate spade lug or ring terminal to the wire, then slip the fastener beneath the terminal screw and tighten.
The Power Supply Assembly also contains two 12-pin plug connectors. The connectors are keyed so they cannot be inserted incorrectly into a mating 12-pin receptacle connector.
PARTS AND OPTIONS
There are no user-serviceable components or parts within the Power Supply Assembly; however, in order for the unit to be properly protected the 85Vac to
240Vac 60Hz INPUT must be fused. Table 3 lists the fuses and fuse holders that are recommended for use with the Power Supply Assembly.
Table 3. Recommended replacement fuses for use with the
Power Supply Assembly.
Class CC Current limiting Fuse Fuse Holder
Gould-Shawmut ATMR 2 Gould-Shawmut 3012R & DFC3M
To connect to the Power Supply Assembly plugs, align the receptacle interlock connector of a Distribution
Cable Harness with the plug hook connector of the
Power Supply Assembly. Insert the receptacle until the interlock and hook catch (see Figure 6). To disconnect from the Power Supply Assembly, press down at the rear of the receptacle interlock until the interlock clears the plug hook and withdraw the receptacle interlock
(see Figure 7).
If the incoming AC power supply is greater than the
240 Vac @ 60 Hz maximum rating of the Power Supply
Assembly, then refer to Table 4 for a listing of GE control power transformers that are recommended for use with the Power Supply Assembly. The INPUT to the
Power Supply Assembly must always be protected. It is recommended that the primary side of the control power transformer be fused with the fuses previously described.
Figure 6. Slide view of receptacle-plug insertion into the
Power Supply Assembly.
If there is a preference to purchase a +24Vdc Power
Supply that has factory-mounted AC line fuses and/ or a higher AC voltage rating, Table 5 contains a listing of GE Power Supply Plates. These Power Supply Plates contain the Power Supply Assembly as an integral part of the plate and are factory-wired from the Power
Supply Assembly to the control power transformer
(where required) and to the fuse holders (one set of fuses is included).
Table 4. Recommended GE Control Power Transformers for use with the Power Supply Assembly.
Input Rating
480Vac @ 50/60 Hz
600Vac @ 50/60 Hz
Pri / Sec Rating
480Vac / 120Vac
600Vac / 120Vac
Catalog Number
9T58K2802
9T58K2824
Table 5. Available GE Power Supply Plates.
Voltage
Rating
Catalog
Number
AC line
Fuses
Comments
120 Vac SPSA120 1,2 amp larger mounting plate with fuse holder
208 Vac SPSA208 2,2 amp larger mounting plate with fuse holder
240 Vac SPSA240 2,2 amp larger mounting plate with fuse holder
Figure 7. Side view of receptacle-plug removal from the
Power Supply Assembly.
GEH-6253 Installation Instructions
Additional Information
Refer to these other user’s manuals for more details·:
GEH-5934 MicroVersaTrip ® Plus and MicroVersaTrip ®
PM Trip Units in Spectra ® RMS Molded-
Case Circuit Breakers
GEH-700 Spectra ® G Breaker w/ micro EntelliGuard™ Trip Unit
GEH-701 Spectra ® K Breaker w/ micro EntelliGuard™ Trip Unit
GEH-702 micro EntelliGuard™ Trip Unit Users Manual
DEH-41318 Universal Rating Plug
GEH-6250 Voltage Module
GEH-6251
GEH-6252
Power Supply Plate
Voltage Conditioner Plate
GEH-6254 Voltage Conditioner Assembly
GEH-703 MET Battery Pack Adapter
GEH-704 MET Advanced Distribution Cable
Junction Box
DEH-006 Distribution Cable Junction Box
GEH-705 MET Distribution Cable Extension (20-pin)
GEH-6256 Distribution Cable Extension (12-pin)
GEH-6255 Distribution Cable Harness (12-pin)
GEH-706 MET Distribution Cable Terminal Blocks
(11 point & 22 point)
GEH-6257 Distribution Cable Terminal Block (11 point)
GEH-6491 POWER LEADER™ Modbus Concentrator
GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide
GEH-707 MET Sealable Cover kits
DEH-4568 GTU digital test kit (GTUTK20)
GEH-5551 Shunt Trip and UVR instructions
GEH-5593 Aux switch and bell alarm
GEK-64467 TIM-1 Zone Selective Interlock Module
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and micro EntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.