- Computers & electronics
- Networking
- Network switches
- ABB
- REM611 2.0 IEC, Motor Protection, Application
- Instructions
advertisement
—
RELION® 611 SERIES
Motor Protection and Control
REM611
Application Manual
Document ID: 1MRS757457
Issued: 2019-04-10
Revision: E
Product version: 2.0
© Copyright 2019 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/relion
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network.
It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.
Table of contents
REM611
Application Manual
Table of contents
Section 1 Introduction.......................................................................3
Intended audience.............................................................................. 3
Product documentation.......................................................................4
Product documentation set............................................................4
Document revision history............................................................. 4
Related documentation..................................................................5
Symbols and conventions...................................................................5
Symbols.........................................................................................5
Document conventions..................................................................6
Functions, codes and symbols...................................................... 6
Section 2 REM611 overview............................................................ 9
Product version history..................................................................9
PCM600 and relay connectivity package version........................10
Operation functionality......................................................................10
Optional functions........................................................................10
Physical hardware............................................................................ 10
Display.........................................................................................12
LEDs............................................................................................13
Keypad........................................................................................ 13
Web HMI...........................................................................................14
Command buttons....................................................................... 15
Authorization.....................................................................................16
Audit trail......................................................................................17
Communication.................................................................................19
Self-healing Ethernet ring............................................................20
Ethernet redundancy................................................................... 21
Secure communication................................................................23
Section 3 REM611 standardized configuration ............................. 25
Standardized configuration...............................................................25
Switch groups................................................................................... 26
Input switch group ISWGAPC..................................................... 26
Output switch group OSWGAPC.................................................27
Selector switch group SELGAPC................................................ 27
Connection diagrams........................................................................29
Configuration A.................................................................................30
1
2
Table of contents
Applications................................................................................. 30
Functions.....................................................................................31
Default I/O connections.......................................................... 32
Predefined disturbance recorder connections........................32
Functional diagrams.................................................................... 33
Functional diagrams for protection......................................... 33
Functional diagrams for control and interlocking....................42
Switch groups..............................................................................44
Binary inputs...........................................................................45
Internal signal......................................................................... 47
Binary outputs and LEDs........................................................48
GOOSE.................................................................................. 61
Section 4 Requirements for measurement transformers................65
Current transformers........................................................................ 65
Current transformer requirements for overcurrent protection......65
Non-directional overcurrent protection................................... 66
Example for non-directional overcurrent protection................67
Section 5 Protection relay's physical connections..........................69
Energizing inputs.........................................................................69
Phase currents....................................................................... 69
Residual current..................................................................... 69
Auxiliary supply voltage input...................................................... 69
Binary inputs................................................................................70
Outputs for tripping and controlling..............................................70
Outputs for signalling...................................................................71
IRF...............................................................................................71
Section 6 Glossary......................................................................... 73
REM611
Application Manual
1MRS757457 E
Section 1 Introduction
1.1
1.2
Section 1
Introduction
This manual
The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.
Intended audience
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and principles.
REM611
Application Manual
3
Section 1
Introduction
1.3
1.3.1
Product documentation
Product documentation set
1MRS757457 E
4
1.3.2
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual
Communication protocol manual
IEC 61850 engineering guide
Point list manual
Cyber security deployment guideline
GUID-0777AFDA-CADF-4AA9-946E-F6A856BDF75E V1 EN
Figure 1: The intended use of manuals in different lifecycles
Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion .
Document revision history
Document revision/date
A/2011-11-18
B/2016-02-22
Product version
1.0
2.0
C/2016-10-11
D/2017-10-31
E/2019-04-10
2.0
2.0
2.0
History
First release
Content updated to correspond to the product version
Content updated
Content updated
Content updated
REM611
Application Manual
1MRS757457 E
1.3.3
1.4
1.4.1
REM611
Application Manual
Section 1
Introduction
Download the latest documents from the ABB Web site http://www.abb.com/substationautomation .
Related documentation
Name of the document
Modbus Communication Protocol Manual
IEC 61850 Engineering Guide
Engineering Manual
Installation Manual
Operation Manual
Technical Manual
Cyber Security Deployment Guideline
Document ID
1MRS757461
1MRS757465
1MRS241255
1MRS757452
1MRS757453
1MRS757454
1MRS758337
Symbols and conventions
Symbols
The electrical warning icon indicates the presence of a hazard which could result in electrical shock.
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a certain function.
5
6
Section 1
Introduction
1.4.2
1.4.3
1MRS757457 E
Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button icons.
To navigate between the options, use and .
• Menu paths are presented in bold.
Select Main menu/Settings .
• LHMI messages are shown in Courier font.
To save the changes in nonvolatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• Input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
• This document assumes that the parameter setting visibility is "Advanced".
Functions, codes and symbols
Table 1:
Function
Protection
Functions included in the relay
IEC 61850
Three-phase non-directional overcurrent protection, low stage, instance 1
Three-phase non-directional overcurrent protection, instantaneous stage, instance 1
Non-directional earth-fault protection, low stage, instance 1
Non-directional earth-fault protection, high stage, instance 1
Negative-sequence overcurrent protection for machines, instance 1
Negative-sequence overcurrent protection for machines, instance 2
Loss of load supervision
Motor load jam protection
Table continues on next page
PHLPTOC1
PHIPTOC1
EFLPTOC1
EFHPTOC1
MNSPTOC1
MNSPTOC2
LOFLPTUC1
JAMPTOC1
IEC 60617 IEC-ANSI
3I> (1)
3I>>> (1)
Io> (1)
Io>> (1)
I2>M (1)
I2>M (2)
3I<
Ist>
51P-1 (1)
50P/51P (1)
51N-1 (1)
51N-2 (1)
46M (1)
46M (2)
37
51LR
REM611
Application Manual
1MRS757457 E
Section 1
Introduction
Function
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip, instance 1
Other
Input switch group 1)
Output switch group 2)
Selector 3)
Minimum pulse timer (2 pcs) 4)
Minimum pulse timer (2 pcs, second resolution), instance 1
Move (8 pcs), instance 1
Control
Circuit-breaker control
Emergency start-up
Condition monitoring and supervision
Trip circuit supervision, instance 1
Trip circuit supervision, instance 2
Runtime counter for machines and devices
Logging
Disturbance recorder
Fault recorder
Measurement
Three-phase current measurement, instance 1
Sequence current measurement
Residual current measurement, instance 1
1) 10 instances
2) 20 instances
3) 6 instances
4) 10 instances
IEC 61850
STTPMSU1
PREVPTOC1
MPTTR1
CCBRBRF1
TRPPTRC1
ISWGAPC
OSWGAPC
SELGAPC
TPGAPC
TPSGAPC
MVGAPC
CBXCBR1
ESMGAPC1
TCSSCBR1
TCSSCBR2
MDSOPT1
RDRE1
FLTRFRC1
CMMXU1
CSMSQI1
RESCMMXU1
IEC 60617
Is2t n<
I2>>
3Ith>M
IEC-ANSI
49,66,48,51LR
46R
49M
3I>/Io>BF 51BF/51NBF
Master Trip (1) 94/86 (1)
ISWGAPC
OSWGAPC
SELGAPC
TP
TPS (1)
MV (1)
ISWGAPC
OSWGAPC
SELGAPC
TP
TPS (1)
MV (1)
I <-> O CB
ESTART
TCS (1)
TCS (2)
OPTS
I <-> O CB
ESTART
TCM (1)
TCM (2)
OPTM
-
DR (1)
3I
I1, I2, I0
Io
DFR(1)
FR
3I
I1, I2, I0
In
REM611
Application Manual
7
8
1MRS757457 E
Section 2 REM611 overview
2.1
2.1.1
REM611
Application Manual
Section 2
REM611 overview
Overview
REM611 is a dedicated motor protection relay for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry. Typically, the relay is used with circuit breaker or contactor-controlled medium-sized or small motors in a variety of drives, such as pumps and conveyors, crushers and choppers, mixers and agitators, and fans and aerators.
REM611 is a member of ABB’s Relion ® product family and part of the 611 protection and control product series. The 611 series relays are characterized by their compactness and withdrawable-unit design.
The 611 series offers simplified yet powerful functionality for most applications.
Once the application-specific parameter set has been entered, the installed protection relay is ready to be put into service. The further addition of communication functionality and interoperability between substation automation devices offered by the IEC 61850 standard adds flexibility and value to end users as well as electrical system manufacturers.
The 611 series relays fully support the IEC 61850 standard for communication and interoperability of substation automation devices, including fast GOOSE (Generic
Object Oriented Substation Event) messaging, and can now also benefit from the extended interoperability provided by Edition 2 of the standard. The relays further support the parallel redundancy protocol (PRP) and the high-availability seamless redundancy (HSR) protocol. The 611 series relays are able to use IEC 61850 and
Modbus® communication protocols simultaneously.
Product version history
Product version
1.0
2.0
•
•
•
•
•
•
•
•
•
•
•
•
•
Product history
Product released
High-availablity seamless redundancy (HSR) protocol
Parallel redundancy protocol (PRP-1)
Two selectable indication colors for LEDs (red or green)
Online binary signal monitoring with PCM600
IEEE 1588 v2 time synchronization
Profibus adapter support
Import/export of settings via WHMI
Setting usability improvements
HMI event filtering tool
IEC 61850 Edition 2
Support for configuration migration (starting from Ver.1.0 to Ver.2.0)
Software closable Ethernet ports
Report summary via WHMI
9
Section 2
REM611 overview
2.1.2
1MRS757457 E
PCM600 and relay connectivity package version
• Protection and Control IED Manager PCM600 Ver.2.7 or later
• REM611 Connectivity Package Ver.2.0 or later
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Communication Management
Configuration Wizard
Disturbance Handling
Event Viewer
Fault Record tool
Firmware Update
HMI Event Filtering
IEC 61850 Configuration
IED Compare
IED Configuration Migration
IED User Management
Label Printing
Lifecycle Traceability
Parameter Setting
Signal Matrix
Signal Monitoring
Download connectivity packages from the ABB Web site http://www.abb.com/substationautomation or directly with Update
Manager in PCM600.
2.2
2.2.1
2.3
Operation functionality
Optional functions
• Modbus TCP/IP or RTU/ASCII
• IEEE 1588 time v2 synchronization
• High-availability seamless redundancy protocol (HSR)
• Parallel redundancy protocol (PRP)
Physical hardware
The protection relay consists of two main parts: plug-in unit and case. The content depends on the ordered functionality.
10 REM611
Application Manual
1MRS757457 E
2.4
Section 2
REM611 overview
Table 2:
Main unit Slot ID
Plug-in unit
-
X100
Case
X120
X000
Plug-in unit and case
Content options
HMI
Auxiliary power/BO module
AI/BI module
Optional communication module
Small (4 lines, 16 characters)
48...250 V DC/100...240 V AC; or 24...60 V DC
2 normally-open PO contacts
1 change-over SO contacts
1 normally-open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
Configuration A:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A) 1)
4 binary inputs
See technical manual for details about different type of communication modules.
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of the protection relay. The binary input thresholds are selectable within the range 16…176
V DC by adjusting the binary input setting parameters.
See the installation manual for more information about the case and the plug-in unit.
The connection diagrams of different hardware modules are presented in this manual.
Table 3:
Conf.
A
Number of physical connections in configuration
CT
Analog channels
4
VT
-
BI
4
Binary channels
BO
6
Local HMI
The LHMI is used for setting, monitoring and controlling the protection relay. The
LHMI comprises the display, buttons, LED indicators and communication port.
REM611
Application Manual
11
Section 2
REM611 overview
1MRS757457 E
REF611
Overcurrent
Earth-fault
Phase unbalance
Thermal overload
AR sequence in progress
Disturb.rec.trigged
Trip circuit failure
Breaker failure
2.4.1
12
GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN
Figure 2: Example of the LHMI
Display
The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.
Table 4: Small display
Character size 1)
Small, mono-spaced (6 × 12 pixels)
Large, variable width (13 × 14 pixels)
1) Depending on the selected language
Rows in the view
5
3
Characters per row
20
8 or more
The display view is divided into four basic areas.
REM611
Application Manual
1MRS757457 E
Section 2
REM611 overview
1 2
2.4.2
2.4.3
3
GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN
Figure 3: Display layout
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
4
LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 8 programmable LEDs on front of the LHMI. The LEDs can be configured with the LHMI, WHMI or PCM600.
Keypad
The LHMI keypad contains push buttons which are used to navigate in different views or menus. With the push buttons you can give open or close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
REM611
Application Manual
13
Section 2
REM611 overview
1MRS757457 E
2.5
GUID-B681763E-EC56-4515-AC57-1FD5349715F7 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push buttons and RJ-45 communication port
Web HMI
The WHMI allows secure access to the protection relay via a Web browser. When the
Secure Communication parameter in the protection relay is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The
WHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.
WHMI is enabled by default.
WHMI offers several functions.
• Programmable LEDs and event lists
• System supervision
• Parameter settings
• Measurement display
• Disturbance records
• Fault records
• Phasor diagram
• Signal configuration
• Importing/Exporting parameters
• Report summary
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
14 REM611
Application Manual
1MRS757457 E
Section 2
REM611 overview
2.5.1
REM611
Application Manual
GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V2 EN
Figure 5: Example view of the WHMI
The WHMI can be accessed locally and remotely.
• Locally by connecting the laptop to the protection relay via the front communication port.
• Remotely over LAN/WAN.
Command buttons
Command buttons can be used to edit parameters and control information via the
WHMI.
Table 5:
Name
Command buttons
Description
Enabling parameter editing
Disabling parameter editing
Writing parameters to the protection relay
Refreshing parameter values
Printing out parameters
Committing changes to protection relay's nonvolatile flash memory
Table continues on next page
15
Section 2
REM611 overview
2.6
1MRS757457 E
Name Description
Rejecting changes
Showing context sensitive help messages
Error icon
Clearing events
Triggering the disturbance recorder manually
Saving values to TXT or CSV file format
Freezing the values so that updates are not displayed
Receiving continuous updates to the monitoring view
Deleting the disturbance record
Deleting all disturbance records
Saving the disturbance record files
Viewing all fault records
Clearing all fault records
Importing settings
Exporting settings
Selecting all
Clearing all selections
Refreshing the parameter list view
Authorization
Four user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords.
The default passwords in the protection relay delivered from the factory can be changed with Administrator user rights.
User authorization is disabled by default for LHMI but WHMI always uses authorization.
16 REM611
Application Manual
1MRS757457 E
2.6.1
REM611
Application Manual
Section 2
REM611 overview
Table 6:
Username
VIEWER
OPERATOR
ENGINEER
ADMINISTRATOR
Predefined user categories
•
•
•
•
User rights
Read only access
Selecting remote or local state with
Changing setting groups
Controlling
Clearing indications
(only locally)
•
•
•
•
•
•
•
•
•
Changing settings
Clearing event list
Clearing disturbance records
Changing system settings such as IP address, serial baud rate or disturbance recorder settings
Setting the protection relay to test mode
Selecting language
All listed above
Changing password
Factory default activation
For user authorization for PCM600, see PCM600 documentation.
Audit trail
The protection relay offers a large set of event-logging functions. Critical system and protection relay security-related events are logged to a separate nonvolatile audit trail for the administrator.
Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of system and security-related events and changes in the protection relay. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in LHMI and WHMI and Event Viewer in PCM600.
The protection relay stores 2048 audit trail events to the nonvolatile audit trail.
Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. Nonvolatile memory is based on a memory type which does not need battery backup nor regular component change to maintain the memory storage.
Audit trail events related to user authorization (login, logout, violation remote and violation local) are defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined user names or user categories. The user audit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.
17
Section 2
REM611 overview
1MRS757457 E
Table 7: Audit trail events
Audit trail event
Configuration change
Firmware change
Firmware change fail
Attached to retrofit test case
Removed from retrofit test case
Setting group remote
Setting group local
Control remote
Control local
Test on
Test off
Reset trips
Setting commit
Time change
View audit log
Login
Logout
Password change
Firmware reset
Audit overflow
Violation remote
Violation local
Description
Configuration files changed
Firmware changed
Firmware change failed
Unit has been attached to retrofit case
Removed from retrofit test case
User changed setting group remotely
User changed setting group locally
DPC object control remote
DPC object control local
Test mode on
Test mode off
Reset latched trips (TRPPTRC*)
Settings have been changed
Time changed directly by the user. Note that this is not used when the protection relay is synchronised properly by the appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).
Administrator accessed audit trail
Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Password changed
Reset issued by user or tool
Too many audit events in the time period
Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in
PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list together with process related events.
To expose the audit trail events through Event list, define the
Authority logging level parameter via Configuration/
Authorization/Security . This exposes audit trail events to all users.
18 REM611
Application Manual
1MRS757457 E
2.7
REM611
Application Manual
Section 2
REM611 overview
Table 8:
Audit trail event
Configuration change
Firmware change
Firmware change fail
Attached to retrofit test case
Removed from retrofit test case
Setting group remote
Setting group local
Control remote
Control local
Test on
Test off
Reset trips
Setting commit
Time change
View audit log
Login
Logout
Password change
Firmware reset
Violation local
Violation remote
Comparison of authority logging levels
None
Configurati on change
●
●
●
●
Authority logging level
Setting group
Setting group, control
●
●
●
●
●
●
●
●
● ●
●
●
●
●
●
●
●
●
●
●
Settings edit
●
●
●
●
●
●
●
●
●
●
●
●
●
All
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Communication
The protection relay supports a range of communication protocols including IEC
61850 and Modbus ® . Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the protection relays, is only enabled by the IEC
61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file format. The protection relay can send and receive binary signals from other devices
(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,
19
Section 2
REM611 overview
2.7.1
1MRS757457 E where the highest performance class with a total transmission time of 3 ms is supported. The protection relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard.
The protection relay can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus.
All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The protection relay can be connected to
Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber-optic LC connector (100Base-FX). An optional serial interface is available for
RS-485 communication.
Self-healing Ethernet ring
For the correct operation of self-healing loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The protection relay itself does not support link-down detection or RSTP.
The ring recovery process is based on the aging of the MAC addresses, and the linkup/link-down events can cause temporary breaks in communication. For a better performance of the self-healing loop, it is recommended that the external switch furthest from the protection relay loop is assigned as the root switch (bridge priority
= 0) and the bridge priority increases towards the protection relay loop. The end links of the protection relay loop can be attached to the same external switch or to two adjacent external switches. A self-healing Ethernet ring requires a communication module with at least two Ethernet interfaces for all protection relays.
20 REM611
Application Manual
1MRS757457 E
Client A
Manag ed Eth ernet switch with RSTP su pport
Section 2
REM611 overview
Client B
Manag ed Eth ernet switch with RSTP su pport
Network
Network
2.7.2
REM611
Application Manual
GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V2 EN
Figure 6: Self-healing Ethernet ring solution
The Ethernet ring solution supports the connection of up to 30 protection relays. If more than 30 protection relays are to be connected, it is recommended that the network is split into several rings with no more than 30 protection relays per ring. Each protection relay has a 50-μs store-and-forward delay, and to fulfil the performance requirements for fast horizontal communication, the ring size is limited to 30 protection relays.
Ethernet redundancy
IEC 61850 specifies a network redundancy scheme that improves the system availability for substation communication. It is based on two complementary protocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocol
PRP and high-availability seamless redundancy HSR protocol. Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection. Therefore, both are able to overcome the failure of a link or switch with a zero-switchover time, thus fulfilling the stringent real-time requirements for the substation automation horizontal communication and time synchronization.
PRP specifies that each device is connected in parallel to two local area networks.
HSR applies the PRP principle to rings and to the rings of rings to achieve costeffective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for all 611 series protection relays.
21
Section 2
REM611 overview
1MRS757457 E
IEC 62439-3:2012 cancels and replaces the first edition published in
2010. These standard versions are also referred to as IEC 62439-3
Edition 1 and IEC 62439-3 Edition 2. The protection relay supports
IEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.
PRP
Each PRP node, called a double attached node with PRP (DAN), is attached to two independent LANs operated in parallel. These parallel networks in PRP are called
LAN A and LAN B. The networks are completely separated to ensure failure independence, and they can have different topologies. Both networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid communication failures. Non-PRP nodes, called single attached nodes (SANs), are either attached to one network only (and can therefore communicate only with
DANs and SANs attached to the same network), or are attached through a redundancy box, a device that behaves like a DAN.
Managed
Ethernet switch
IEC 61850 PRP
Managed
Ethernet switch
22
GUID-AA005F1B-A30B-48F6-84F4-A108F58615A2 V1 EN
Figure 7: PRP solution
In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an
Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames. In some cases, default
PC workstation adapters are not able to handle the maximum-length Ethernet frames with the PRP trailer.
There are different alternative ways to connect a laptop or a workstation as SAN to a
PRP network.
REM611
Application Manual
1MRS757457 E
Section 2
REM611 overview
• Via an external redundancy box (RedBox) or a switch capable of connecting to
PRP and normal networks
• By connecting the node directly to LAN A or LAN B as SAN
• By connecting the node to the protection relay's interlink port
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames, one over each port. Both frames circulate in opposite directions over the ring and each node forwards the frames it receives, from one port to the other. When the originating node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring protocol is needed. Individually attached nodes, SANs, such as laptops and printers, must be attached through a “redundancy box” that acts as a ring element. For example, a 615 or 620 series protection relay with HSR support can be used as a redundancy box.
Devices not supporting HSR
Ethernet switch
Redundancy box
Redundancy box
Redundancy box
X
X
IEC 61850 HSR
X
Unicast traffic
Message is recognized as a duplicat e and is immediately forwarded
Sending device removes the message from t he ri ng
2.7.3
REM611
Application Manual
GUID-B24F8609-0E74-4318-8168-A6E7FCD0B313 V1 EN
Figure 8: HSR solution
Secure communication
The protection relay supports secure communication for WHMI and file transfer protocol. If the Secure Communication parameter is activated, protocols require TLS based encryption method support from the clients. In this case WHMI must be connected from a Web browser using the HTTPS protocol and in case of file transfer the client must use FTPS.
As a factory default, Secure Communication is “ON”.
23
24
1MRS757457 E
Section 3
REM611 standardized configuration
Section 3 REM611 standardized configuration
3.1
REM611
Application Manual
Standardized configuration
REM611 is available in one configuration.
To increase the user-friendliness of the configuration and to emphasize the simplicity of usage of the relay, only the application-specific parameters need setting within the relay's intended area of application.
The standard signal configuration can be altered by local HMI, Web HMI or optional application functionality of Protection and Control IED Manager PCM600.
Table 9:
Description
Motor protection
Standardized configuration
Conf.
A
Table 10: Supported functions
Function
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, instantaneous stage
Non-directional earth-fault protection, low stage
Non-directional earth-fault protection, high stage
Negative-sequence overcurrent protection for machines
Loss of load supervision
Motor load jam protection
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip
Control
Circuit-breaker control
Emergency start-up
Condition monitoring and supervision
Trip circuit supervision
Table continues on next page
IEC 61850
PHLPTOC
PHIPTOC
CBXCBR
ESMGAPC
TCSSCBR
EFLPTOC
EFHPTOC
MNSPTOC
LOFLPTUC
JAMPTOC
STTPMSU
PREVPTOC
MPTTR
CCBRBRF
TRPPTRC
A
1
1
1
1
1
1 1)
1 1)
2
1
1
1
1
1
1
2
25
Section 3
REM611 standardized configuration
3.2
3.2.1
26
1MRS757457 E
Function
Runtime counter for machines and devices
Logging
Disturbance recorder
Fault recorder
Measurement
Three-phase current measurement
IEC 61850
MDSOPT
RDRE
FLTRFRC
A
1
1
1
Sequence current measurement
Residual current measurement
Other
Input switch group
Output switch group
Selector
CMMXU
CSMSQI
RESCMMXU
ISWGAPC
OSWGAPC
SELGAPC
1
1
1
10
20
6
Minimum pulse timer (2 pcs)
Minimum pulse timer (2 pcs, second resolution)
TPGAPC
TPSGAPC
10
1
Move (8 pcs) MVGAPC 1
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standardized configuration.
() = optional
1) Io selectable by parameter and default value is "Io measured"
Switch groups
The default application configurations cover the most common application cases, however, changes can be made according to specific needs through LHMI, WHMI and PCM600.
Programming is easily implemented with three switch group functions including input switch group ISWGAPC, output switch group OSWGAPC and selector switch group
SELGAPC. Each switch group has several instances.
Connections of binary inputs to functions, GOOSE signals to functions, functions to functions, functions to binary outputs and functions to LEDs have been preconnected through corresponding switch groups.
The real connection logic and the application configuration can be modified by changing the parameter values of the switch groups. It is also possible to modify the real connection logic and the application configuration through the matrix view in the signal configuration menu in the WHMI.
Input switch group ISWGAPC
The input switch group ISWGAPC has one input and a number of outputs. Every input and output has a read-only description. ISWGAPC is used for connecting the input
REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration signal to one or several outputs of the switch group. Each output can be set to be connected or not connected with the input separately via the “OUT_x connection” setting.
3.2.2
GUID-2D549B56-6CF7-4DCB-ACDE-E9EF601868A8 V1 EN
Figure 9: Input switch group ISWGAPC
Output switch group OSWGAPC
The output switch group OSWGAPC has a number of inputs and one output. Every input and output has a read-only description. OSWGAPC is used for connecting one or several inputs to the output of the switch group via OR logic. Each input can be set to be connected or not connected with the OR logic via the “IN_x connection” settings. The output of OR logic is routed to switch group output.
3.2.3
REM611
Application Manual
GUID-1EFA82D5-F9E7-4322-87C2-CDADD29823BD V1 EN
Figure 10: Output switch group OSWGAPC
Selector switch group SELGAPC
The selector switch group SELGAPC has a number of inputs and outputs. Every input and output has a read-only description. Each output can be set to be connected with one of the inputs via the OUT_x connection setting. An output can also be set to be not connected with any of the inputs. In SELGAPC, one output signal can only be connected to one input signal but the same input signal can be routed to several output signals.
27
Section 3
REM611 standardized configuration
1MRS757457 E
GUID-E3AEC7AB-2978-402D-8A80-C5DE9FED67DF V1 EN
Figure 11: Selector switch group SELGAPC
28 REM611
Application Manual
1MRS757457 E
3.3
L1
L2
L3
Connection diagrams
Section 3
REM611 standardized configuration
REM611
P1
P2
P1
S1
P2
S2
M
3~
S1
S2
X120
1
2
3
4
8
9
10
11
5
6
7
12
13
14
1/5A
N
1/5A
N
1/5A
N
1/5A
N
BI 1
BI 2
BI 3
BI 4
IL1
1)
IL2
IL3
Io
SO1
PO3
TCS1
PO4
TCS2
IRF
PO1
PO2
SO2
1) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
GUID-7AEBF2ED-BF20-4D85-A67A-9489E5EB7603 V1 EN
Figure 12: Connection diagram for configuration A when used with a circuitbreaker-controlled motor drive
+
U aux
-
X100
1
2
3
4
5
6
7
21
23
24
14
16
17
15
19
18
20
22
8
9
10
11
12
13
REM611
Application Manual
29
Section 3
REM611 standardized configuration
L1
L2
L3
3.4
3.4.1
30
1MRS757457 E
REM611
P1
P2
P1
S1
P2
S2
M
3~
S1
S2
X120
1
2
3
4
10
11
12
13
14
5
6
7
8
9
1/5A
N
1/5A
N
1/5A
N
1/5A
N
BI 1
BI 2
BI 3
IL2
IL3
Io
BI 4
IL1
1)
SO1
PO3
TCS1
PO4
TCS2
IRF
PO1
PO2
SO2
1) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
GUID-21265C90-98B5-45F2-9B83-AC93CBB8C44E V1 EN
Figure 13: Connection diagram for configuration A when used with a contactorcontrolled motor drive
The protection principles are mostly the same for circuit-breaker controlled and contactor controlled motor drives. Because the contactor is not able to break high currents, the relay must be set in such a way that the relay does not open the contactor at faults of high current magnitudes. Faults are cleared with fuses.
U
+
aux
X100
1
2
3
4
5
6
7
14
16
17
15
19
18
20
22
21
23
24
8
9
10
11
12
13
Configuration A
Applications
Configuration A for motor protection and control is mainly intended for the protection, control, measurement and supervision of asynchronous motors and the associated drives in manufacturing and process industry.
The protection relay with a standardized configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the protection relay enables this configuration
REM611
Application Manual
1MRS757457 E
3.4.2
3I
Io
Section 3
REM611 standardized configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
Functions
REM611 MOTOR PROTECTION RELAY
PROTECTION
Master Trip
Lockout relay
94/86
3I<
37
2×
I2>M
46M
I2>>
46R
Is2t n<
49, 66, 48, 51LR
3Ith>M
49M
3I>>>
50P/51P
3I>/Io>BF
51BF/51NBF
Ist>
51LR
3I>
51P-1
Io>
51N-1
Io>>
51N-2
M
GUID-5E2D4B1E-9287-4833-BB0A-BB310A16E2CD V2 EN
Figure 14: Functionality overview for configuration A
LOCAL HMI
I
ESC
O
Control
Events
Measurements
Disturbance records
A
R
L
STANDARD
CONFIGURATION
A
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
- Local/Remote push button on LHMI
- Self-supervision
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
- Web-HMI
CONDITION MONITORING
AND SUPERVISION
OPTS
OPTM
2×
TCS
TCM
CONTROL AND INDICATION 1)
Object
CB
Ctrl 2)
1
Ind 3)
-
DC -
ES -
1) Check availability of binary inputs/outputs
from technical documentation
2) Control and indication function for
primary object
3) Status indication function for
primary object
ESTART
ESTART
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus®
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
Serial: RS-485
Redundant protocols:
HSR
PRP
RSTP
MEASUREMENT
- I, Io
- Limit value supervision
- Symmetrical components
Analog interface types
Current transformer
Voltage transformer
1)
Conventional transformer inputs
REMARKS
Optional function
3× No. of instances
Io/Uo
Calculated value
OR Alternative function to be defined when ordering
1)
4
-
REM611
Application Manual
31
Section 3
REM611 standardized configuration
3.4.2.1
3.4.2.2
1MRS757457 E
Default I/O connections
Table 11:
Binary input
X120-BI1
X120-BI2
X120-BI3
X120-BI4
Default connections for binary inputs
Description
Emergency start
Circuit breaker closed position indication
Circuit breaker open position indication
External restart inhibit
Table 12:
Binary input
X100-PO1
X100-PO2
X100-SO1
X100-SO2
X100-PO3
X100-PO4
Default connections for binary outputs
Description
Restart enable
Breaker failure backup trip to upstream breaker
General start indication
General operate indication
Open circuit breaker
Close circuit breaker
3
4
5
6
7
8
Table 13:
LED
1
2
Default connections for LEDs
Description
Short circuit protection operate
Combined operate indication of the other protection functions
Thermal overload protection operate
Motor restart inhibit
Emergency start enabled
Disturbance recorder triggered
TCS or runtime counter alarm
Circuit-breaker failure operate
Predefined disturbance recorder connections
Table 14:
Channel
1
2
3
4
Predefined analog channel setup
Description
IL1
IL2
IL3
Io
Connector pins
X120:1-2
X120:3,2
X120:4,2
X120:5-6
Connector pins
X100:6-7
X100:8-9
X100:10-11,(12)
X100:13-14
X100:15,19
X100:20,24
32 REM611
Application Manual
1MRS757457 E
3.4.3
3.4.3.1
Section 3
REM611 standardized configuration
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
Functional diagrams
The functional diagrams describe the default input, output, programmable LED, switch group and function-to-function connections. The default connections can be viewed and changed with switch groups in PCM600, LHMI and WHMI according to the application requirements.
The analog channels have fixed connections towards the different function blocks inside the protection relay’s configuration. Exceptions from this rule are the seven analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a core balance current transformer.
Functional diagrams for protection
The functional diagrams describe the protection relay’s protection functionality in detail and picture the factory default connections.
REM611
Application Manual
33
Section 3
REM611 standardized configuration
1MRS757457 E
OVERCURRENT PROTECTION
PHLPTOC1
3I>(1)
3I
BLOCK
51P-1(1)
OPERATE
START
ENA_MULT
OSWGAPC9
IN_1 OUT
SELGAPC4
IN_11 OUT_2
PHIPTOC1
3I>>>(1)
3I
BLOCK
50P/51P(1)
OPERATE
START
ENA_MULT
OSWGAPC8
IN_2 OUT
SELGAPC4
IN_10 OUT_1
STTPMSU1_MOT_STARTUP
MOTOR JAM PROTECTION
JAMPTOC1
I st
>(1)
3I
BLOCK
51LR(1)
OPERATE
START
OSWGAPC9
IN_9 OUT
SELGAPC4
IN_11 OUT_2
LED 2
LED 1
LED 2
GUID-2D4262CD-1143-45C7-AFA7-08386DA760C6 V1 EN
Figure 15: Overcurrent protection
Two overcurrent stages are offered for overcurrent and short-circuit protection. The motor jam protection function JAMPTOC1 is blocked by the motor startup protection function. PHLPTOC1 can be used for overcurrent protection and PHIPTOC1 for the short-circuit protection. The operation of PHIPTOC1 is not blocked by default by any functionality. PHIPTOC1 should be set over the motor start current level to avoid unnecessary operation.
All operate signals are connected to Master Trip. Short-circuit protection PHIPTOC1 operate signal is connected to the alarm LED 1, low stage overcurrent protection
PHLPTOC1 and motor jam protection JAMPTOC1 operate signals are connected to the alarm LED 2.
34 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
EARTH-FAULT PROTECTION
EFLPTOC1
Io>(1)
51N-1(1)
Io
BLOCK
ENA_MULT
OPERATE
START
IN_3
OSWGAPC9
OR
OUT
IN_4
SELGAPC4
IN_11 OUT_2
LED 2
EFHPTOC1
Io>>(1)
51N-2(1)
Io
BLOCK
ENA_MULT
OPERATE
START
GUID-4A25DE53-3F12-407B-9AFC-C8BB252AD350 V1 EN
Figure 16: Earth-fault protection
Two non-directional earth-fault stages EFLPTOC1 and EFHPTOC1 are offered to detect phase-to-earth faults that may be a result of, for example, insulation ageing.
The operate signals of the earth-fault protections are connected to Master Trip and also to alarm LED 2.
REM611
Application Manual
35
Section 3
REM611 standardized configuration
36
1MRS757457 E
X120-BI1
Emergency Start Enable
SELGAPC1
IN_1 OUT_1
EMERGENCY START AND RESTART INHIBIT
ESMGAPC1
ESTART(1)
3I
BLOCK
ST_EMERG_ENA
ST_EMERG_RQ
OSWGAPC12
IN_6 OUT
SELGAPC4
IN_14 OUT_5
MPTTR1
3Ith>M(1)
49M(1)
3I
BLOCK OPERATE
START_EMERG
AMB_TEMB
ALARM
BLK_RESTART
OSWGAPC10
IN_12 OUT
SELGAPC4
IN_12 OUT_3
LED 5
LED 3
TRPTTR1_TRIP
CBXCBR1_EXE_OP
OR IN1
IN2
TPSGAPC1
OUT1
OUT2
X120-BI4
External Restart Inhabit
IN_4
SELGAPC1
OUT_4
STTPMSU1_LOCK_START
MNSPTOC1_BLK_RESTART
MNSPTOC2_BLK_RESTART
OR
OR
OSWGAPC11
IN_9 OUT
SELGAPC4
IN_13 OUT_4
LED 4
Restart Inhabit
GUID-FD95A972-9F46-4374-98F8-EDDB1879CFB2 V1 EN
Figure 17: Emergency start and restart inhibit
The emergency start function ESMGAPC1 allows motor start-ups although the restart inhibit is activated. The emergency start is enabled for ten minutes after the selected binary input (X120:BI1) is energized. On the rising edge of the emergency start signal the following takes place.
• Calculated thermal level is set slightly below the restart inhibit level to allow at least one motor startup.
• Value of the cumulative start-up time counter STTPMSU1 is set slightly below the set restart inhibit value to allow at least one motor startup.
• Set operate values of the temperature stages in MPTTR1 function is increased by
10 percent.
• External restart inhibit signal (X100:PO1) is ignored.
• Alarm LED 5 is activated.
The external restart inhibit signal is ignored for as long as the emergency start is activated. A new emergency start cannot be made until the emergency start signal has been reset and the emergency start time of 10 minutes has expired.
The thermal overload protection function MPTTR1 detects short- and long term overloads under varying load conditions. When the emergency start request is issued for the emergency start function, it activates the corresponding input of the thermal overload function. When the thermal overload function has issued a restart blocking, which inhibits the closing of the circuit breaker when the machine is overloaded, the emergency start request removes this blocking and enables the restarting of the motor.
REM611
Application Manual
1MRS757457 E
REM611
Application Manual
Section 3
REM611 standardized configuration
The operate signal of thermal overload protection function MPTTR1 is connected to
Master Trip and to alarm LED 3.
The restart inhibit is activated for a set period when a circuit breaker is opened. This is called remanence voltage protection where the motor has damping remanence voltage after circuit breaker opening. Reclosing after a too short period of time can lead to stress for the machine and other apparatuses. The remanence voltage protection waiting time can be set to a timer function TPSGAPC1.
The restart inhibit is also activated when one of the following conditions is met.
• An active trip command or
• Motor startup supervision has issued lockout or
• Motor unbalance function has issued restart blocking or
• An external restart inhibit is activated by a binary input (X120:BI4).
LED 4 is the alarm indication of restart inhibit.
X120-BI2
CB Closed Position
SELGAPC1
IN_2 OUT_2
ESMGAPC_ST_EMERG_ENA
MOTOR START AND RUNTIME COUNTER
STTPMSU1
I
S
2t n<(1)
BLOCK
BLK_LK_ST
CB_CLOSED
STALL_IND
OPR_IIT
OPR_STALL
MOT_START
ST_EMERG_ENA LOCK_START
IN_10
IN_11
OSWGAPC9
OR
OUT
SELGAPC4
IN_11 OUT_2
MDSOPT1
OPTS(1)
OPTM(1)
BLOCK
POS_ACTIVE
ALARM
WARNING
OSWGAPC14
IN_5 OUT
SELGAPC4
IN_16 OUT_7
LED 2
LED 7
GUID-CA463B2F-038E-4287-A5F2-A903BDF1300B V1 EN
Figure 18: Motor startup supervision
With the motor startup supervision function STTPMSU1 the starting of the motor is supervised by monitoring three-phase currents or the status of the energizing circuit breaker of the motor.
When the emergency start request is activated by ESMCAPC1 and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout is deactivated and emergency starting is available.
The operate signals (OPR_IIT and OPR_STALL) of the motor start-up supervision function STTPMSU1 are connected to Master Trip and to alarm LED 2.
The motor running time counter MDSOPT1 provides history data since the latest commissioning. The counter counts the total number of motor running hours and is
37
Section 3
REM611 standardized configuration
1MRS757457 E incremented when the energizing circuit breaker is closed. The alarm of the runtime counter is connected to alarm LED 7.
UNBALANCE PROTECTION
MNSPTOC1
I
2
>M(1)
46M(1)
3I
BLOCK_OPR
OPERATE
ALARM
BLK_RESTART
MNSPTOC2
I
2
>M(2)
46M(2)
3I
BLOCK_OPR
OPERATE
ALARM
BLK_RESTART
LOSS OF LOAD PROTECTION
LOFLPTUC1
3I<(1)
37(1)
3I
BLOCK
OPERATE
START
PHASE REVERSAL PROTECTION
PREVPTOC1
I
2
>>(1)
46R(1)
3I
BLOCK
OPERATE
START
IN_5
OSWGAPC9
IN_6
IN_7
IN_8
OR
OUT
SELGAPC4
IN_11 OUT_2
LED 2
GUID-6E213083-656E-4188-816E-8CBB1703DF44 V1 EN
Figure 19: Unbalance, loss of load and phase reversal protection
Two negative-sequence overcurrent stages MNSPTOC1 and MNSPTOC2 are offered for phase unbalance protection. These functions are used to protect the motor against phase unbalance caused by, for example, a broken conductor. Phase unbalance in network feeding of the motor causes overheating of the motor.
The loss of load situation is detected by LOFLPTUC. The loss of load situation can happen, for example, if there is damaged pump or a broken conveyor.
38 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
The phase reversal protection PREVPTOC1 is based on the calculated negative phase-sequence current. It detects too high NPS current values during motor start-up, caused by incorrectly connected phases, which in turn causes the motor to rotate in the opposite direction.
All operate signals above are connected to Master Trip and to the alarm LED 2.
CIRCUIT BREAKER FAILURE PROTECTION
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
OR
CCBRBRF1
3I>/Io>BF(1)
51BF/51NBF(1)
3I
Io
START
POSCLOSE
CB_FAULT
BLOCK
CB_FAULT_AL
TRBU
TRRET
SELGAPC3
IN_4 OUT_2
OSWGAPC15
IN_7 OUT
X100 PO2
SELGAPC4
IN_17 OUT_8
LED 8
SELGAPC1
IN_2 OUT_2
X120-BI2
CB Closed Position
GUID-2A807DD6-2138-4B0F-A622-BB7DE2B4C253 V1 EN
Figure 20: Circuit breaker failure protection
The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a number of different protection stages in the protection relay. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.
CCBRBRF1 has two operating outputs: TRRET and TRBU . The TRRET operate output is used for retripping its own circuit breaker through the Master Trip 1. The
TRBU output is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 8 is used for backup ( TRBU ) operate indication.
REM611
Application Manual
39
Section 3
REM611 standardized configuration
3.4.3.2
40
1MRS757457 E
Functional diagrams for disturbance recorder and supervision functionsrecorder
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
OR
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
OR
OR
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
SELGAPC1_ Emeragency Start Enable
SELGAPC1_ CB Closed Position
SELGAPC1_ CB Open Position
SELGAPC1_External Restart Inhibit
MPTTR1_ALARM
MPTTR1_BLK_RESTART
STTPMSU1_MOT_START
STTPMSU1_LOCK_START
MNSPTOC1_BLK_RESTART
MNSPTOC2_BLK_RESTART
CCBRBRF1_TRRET
CCBRBRF1_TRBU
ESMGAPC1_ST_EMERG_ENA
MDSOPT1_ALARM
SELGAPC1_External Trip
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
DISTURBANCE RECORDER
C17
C18
C19
C20
C21
C22
C23
C24
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
C25
C26
C27
C28
C29
C30
C31
C32
C33
C1
C2
C3
C4
C5
C6
C34
C35
C36
C37
C38
RDRE1
TRIGGERED
OSWGAPC13
IN_2
OUT
SELGAPC4
IN_15 OUT_6
LED 6
GUID-889C71B7-80CD-4AAD-8768-1FF326ECD0BC V1 EN
Figure 21: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. The active setting group is also to be recorded via
SG_1_ACT to SG_6_ACT . The disturbance recorder triggered signal indication is connected to LED 6.
Table 15:
Channel number
Binary channel 1
Disturbance recorder binary channel default value
Channel id text
PHLPTOC1_START
Binary channel 2
Binary channel 3
Binary channel 4
Binary channel 5
Binary channel 6
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
Binary channel 7
Binary channel 8
Binary channel 9
LOFLPTUC1_START
PREVPTOC1_START
PHLxPTOC1_OPERATE
Binary channel 10
Binary channel 11
Table continues on next page
EFxPTOC1_OPERATE
MNSPTOC_OPERATE
Level trigger mode
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
4=level trigger off
4=level trigger off
4=level trigger off
REM611
Application Manual
1MRS757457 E
REM611
Application Manual
Channel number
Binary channel 12
Binary channel 13
Binary channel 14
Binary channel 15
Binary channel 16
Binary channel 17
Binary channel 18
Binary channel 19
Binary channel 20
Binary channel 21
Binary channel 22
Binary channel 23
Binary channel 24
Binary channel 25
Binary channel 26
Binary channel 27
Binary channel 28
Binary channel 29
Binary channel 30
Binary channel 31
Binary channel 32
Binary channel 33
Binary channel 34
Binary channel 35
Binary channel 36
Binary channel 37
Binary channel 38
Section 3
REM611 standardized configuration
Channel id text
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPOTC1_OPERATE
STTPMSU1_OPR_IIT
STPPMSU1_OPR_STALL
MPTTR1_OPERATE
SELGAPC1_Emeragecy Start Enable
SELGAPC1_CB_Closed
SELGAPC1_CB_Open
SELGAPC1_External Restart Inhibit
MPTTR1_ALARM
MPTTR1_BLK_RESTART
STTPMSU1_MOT_START
STTPMSU1_LOCK_START
MNSPTOC1_BLK_RESTART
MNSPTOC2_BLK_RESTART
CCBRBRF1_TRRET
CCBRBRF1_TRBU
ESMGAPC1_ST_EMERG_ENA
MDSOPT1_ALARM
SELGAPC1_External Trip
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
Level trigger mode
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
1=positive or rising
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
1=positive or rising
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
4=level trigger off
TRIP CIRCUIT SUPERVISION
X120-BI3
CB Open Position
SELGAPC1
IN_3 OUT_3
TRPPTRC1_TRIP
X120-BI2
CB Closed Position
SELGAPC1
IN_2 OUT_2
OR
IN_1
SELGAPC2
OUT_1
IN_2 OUT_2
BLOCK
TCSSCBR1
ALARM
BLOCK
TCSSCBR2
ALARM
IN_3
IN_4
OSWGAPC14
OR
OUT
SELGAPC4
IN_16 OUT_7
LED 7
GUID-B8A3C114-7F36-4BE7-BD1E-686CD026514F V1 EN
Figure 22: Supervision functions
41
Section 3
REM611 standardized configuration
3.4.3.3
1MRS757457 E
By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with the circuit breaker normally open/closed auxiliary contact.
Functional diagrams for control and interlocking
MASTER TRIP #1
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPETATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERTAE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
CCBRBRF1_TRRET
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OSWGAPC1
OR
OUT
SELGAPC1_External Trip
GOOSERCV_BIN 2_OUT
OR
GOOSERCV_BIN 3_OUT
SELGAPC1_RST_LKOUT
CBXCBR1_EXE_OP
IN1
IN2
MVGAPC1
Q1
Q2
OR
TRPPTRC1
BLOCK TRIP
OPERATE CL_LKOUT
RST_LKOUT
OR
IN_1
SELGAPC3
OUT_5
X100 PO3
GUID-474301B2-7F20-4968-8937-19F360077C7E V2 EN
Figure 23: Master trip
The operate signals from the protections and an external trip are connected to the trip output contact PO3 (X100:15-19) via the corresponding Master Trip (TRPPTRC1).
Open control commands to the circuit breaker from the local or remote
CBXCBR1_EXE_OP are connected directly to the output PO3 (X100:15-19).
TRPPTRC1 provides the lockout/latching function, event generation and the trip signal duration setting. One binary input through SELGAPC1 can be connected to the
RST_LKOUT input of Master Trip. If the lockout operation mode is selected, it is used to enable external reset.
42 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
CIRCUIT BREAKER CONTROL
X120-BI2
CB Closed Position
X120-BI3
CB Open Posit ion
Always True
IN_2
SELGAPC1
OUT_2
IN_3
IN_5
OUT_3
OUT_7
TRPPTRC1_TRIP
Restart Inhibit
AND
CBXCBR1
PO SOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
CBXCBR1_EXE_OP
SELGAPC3
IN_3 OUT_6
SELGAPC3
IN_2 OUT_1
X100 PO4
X100 PO1
GUID-009E5CDF-D8FF-4B3C-9253-4B2F20B010B6 V2 EN
Figure 24: Circuit breaker control
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the master trip logics. An always true signal is also connected to ENA_CLOSE via SELGAPC1 by default. The open operation is always enabled.
When the motor restart is inhibited, the BLK_CLOSE input is activated and closing of the circuit breaker is not possible. When all conditions of the circuit breaker closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and PO1 output
(X100:6-7) is closed.
REM611
Application Manual
43
Section 3
REM611 standardized configuration
3.4.4
1MRS757457 E
COMMON ALARM INDICATION 1 & 2
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OSWGAPC3
OR OUT
IN1
TPGAPC1
OUT1
SELGAPC3
IN_5 OUT_3
IN_9 OUT_4
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OSWGAPC7
OR OUT
IN1
TPGAPC3
OUT1
X100 SO1
X100 SO2
GUID-0B2EDC5B-7CC1-4DDC-A831-F16DB266E4FC V1 EN
Figure 25: Common alarm indication
The signal outputs from the protection relay are connected to give dedicated information.
• Start of any protection function SO1 (X100:10-12)
• Operation (trip) of any protection function SO2 (X100: 13-15)
TPGAPC functions are timers and used for setting the minimum pulse length for the outputs. There are seven generic timers TPGAPC1...7 available in the protection relay.
Switch groups
In configuration A, the switch group function blocks are organized in four groups: binary inputs, internal signal, GOOSE as well as binary outputs and LEDs.
44 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
Binary Inputs
(1...4)
Received GOOSE
(0...19)
GOOSE
GOOSE
GOOSE
SELGAPC1
Binary Inputs
Binary Inputs
GOOSE
ISWGAPC9
GOOSE Blocking
ISWGAPC10
GOOSE Block CB
ISWGAPC2
ISWGAPC1
Blocking
Protection and Control
PHLPTOC1 PHIPTOC1
EFLPTOC1
MNSPTOC1
EFHPTOC1
MNSPTOC2
LOFLPTUC1
JAMPTOC1
PREVPTOC1
STTPMSU1
MPTTR1
CCBRBRF1
CBXCBR1
ESMGAPC1
MDSOPT1
TCSSCBR1
TCSSCBR2
Internal Signal
SELGAPC2
TCS Blocking
GUID-B073CD8D-C5A4-4C29-95D4-2BF60D981594 V1 EN
Figure 26: Configuration A switch group overview
3.4.4.1
Binary Outputs and LEDs
OSWGAPC2
OSWGAPC1
SELGAPC3
Master trip
SELGAPC4
OSWGAPC6
OSWGAPC5
OSWGAPC4
OSWGAPC3
Start
OSWGAPC10
OSWGAPC9
OSWGAPC8
OSWGAPC7
Trip
OSWGAPC16
OSWGAPC15
OSWGAPC14
OSWGAPC13
OSWGAPC12
OSWGAPC11
Alarm
Binary Outputs
LEDs
Binary Outputs
(1...6)
LEDs
(1…8)
Binary inputs
The binary inputs group includes one SELGAPC and two ISWGAPCs. SELGAPC1 is used to route binary inputs to ISWGAPC or directly to protection relay functions.
ISWGAPC1 and ISWGAPC2 are used to configure the signal to block the protection functions.
X120-BI1
X120-BI2
X120-BI3
X120-BI4
SELGAPC1
Blocking 1
ISWGAPC1
Blocking 2 ISWGAPC2
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFHPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFHPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
GUID-DB4D9782-7195-40BA-A357-C296DCB26810 V1 EN
Figure 27: Binary inputs
REM611
Application Manual
45
Section 3
REM611 standardized configuration
1MRS757457 E
SELGAPC1
SELGAPC1 has inputs from protection relay binary inputs. IN_1 ...
IN_4 are binary inputs from X100. An always true signal is connected to IN_5 . SELGAPC1 outputs are used to route inputs to different functions. By setting SELGAPC1, binary inputs can be configured for different purposes.
X120-BI1
X120-BI2
X120-BI3
X120-BI4
Always True
X120/1-2 BI1
IN_1
X120/3-2 BI2
IN_2
X120/4-2 BI3
IN_3
X120/5-6 BI4 IN_4
IN_5
SELGAPC1
OUT_1
Emergency
Start Enable
OUT_2
CB Closed Position
OUT_3
OUT_4
CB Open Position
External
Restart Inhabit
ESMGAPC1_ST_EMERG_RQ
CCBRBRF1_POSCLOSE
CBXCBR1_POSCLOSE
STTPMSU1_CB_CLOSED
MDSOPT1_POS_ACTIVE
SELGAPC2_IN_2
CBXCBR1_POSOPEN
SELGAPC2_IN_1
OSWGAPC1_IN_9
OUT_5
Blocking 1
ISWGAPC1_IN
OUT_6 STTPMSU1_STALL_IND
OUT_7
OUT_8
CB Close Enable
TRPTTRC1_
RST_LKOUT
OUT_9
External Trip
OUT_10
Setting Group 2
OUT_11
Setting Group 3
OUT_12
Setting Group 4
OUT_13
Blocking 2
CBXCBR1_ENA_CLOSE
TRPTTRC1_RST_LKOUT
TRPTTRC1_OPERATE
PROTECTION_BI_SG_2
PROTECTION_BI_SG_3
PROTECTION_BI_SG_4
ISWGAPC2_IN
GUID-258C736E-87B1-4824-877D-028149F2C734 V1 EN
Figure 28: SELGAPC1
ISWGAPC1
ISWGAPC1 is used to select which protection functions are to be blocked by changing
ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output
OUT_5 Blocking 1 . ISWGAPC1 outputs are connected to the BLOCK inputs of the protection functions.
46 REM611
Application Manual
1MRS757457 E
3.4.4.2
REM611
Application Manual
Section 3
REM611 standardized configuration
SELGAPC1_OUT_5
Blocking 1
IN
ISWGAPC1
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
GUID-6E734529-073D-4F12-B419-795329059725 V1 EN
Figure 29: ISWGAPC1
ISWGAPC2
ISWGAPC2 is used to select which protection functions are to be blocked by changing
ISWGAPC2 parameters. ISWGAPC2 input is routed from SELGAPC1 output
OUT_13 Blocking 2 . ISWGAPC2 outputs are connected to the BLOCK inputs of the protection functions.
SELGAPC1_OUT_13
Blocking 2
IN
ISWGAPC2
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
GUID-F0B3B75C-1393-4BBC-8B59-D0AF0A01CC28 V1 EN
Figure 30: ISWGAPC2
Internal signal
The internal signal group is used to configure the logic connections between function blocks. There is one SELGAPC in this group.
47
Section 3
REM611 standardized configuration
3.4.4.3
1MRS757457 E
SELGAPC2 is used to configure trip circuit supervision blocking from circuit breaker open or close position.
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Open Position
CB Closed Position
GUID-14FFE748-CC11-4B9C-8646-3CE37598F108 V1 EN
Figure 31: Internal signal
SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC2
SELGAPC2 inputs are circuit breaker closed and open positions from SELGACP1.
SELGAPC2 outputs are routed to the BLOCK input of the trip circuit supervision
TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 is used for the open circuit breaker, X100-PO4 is used for the closing circuit breaker. TCSSCBR1 is blocked by the circuit breaker open position,
TCSSCBR2 is blocked by the circuit breaker closed position. If X100-PO3 is used for closing the circuit breaker, TCSSCBR1 needs to be blocked by the circuit breaker close position (OUT_1 connection=IN_2). If X100-PO4 is used for the open circuit breaker, TCSSCBR2 needs to be blocked by the circuit breaker open position (OUT_2 connection=IN_1).
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Open Position
IN_1
CB Closed Position
IN_2
SELGAPC2
OUT_1
OUT_2
GUID-E3CF0FAF-958C-45FF-B2AA-5EA151CB83D9 V1 EN
Figure 32: SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
Binary outputs and LEDs
In standard configuration A, the signals route to binary outputs, and LEDs are configured by OSWGAPCs. There are totally 15 OSWGAPC instances. They can be categorized to four groups, including one Master trip, four start, four trip and six alarm signals. The OSWGAPC outputs are connected to binary outputs and LEDs via
SELGAPC3 and SELGAPC4.
• SELGAPC3 is used to configure the OSWGAPC signals to the protection relay binary outputs. SELGAPC4 is used to configure the OSWGAPC signals to
LEDs.
• OSWGAPC1 is used for Master trip. The inputs are routed from the protection functions operate and circuit-breaker failures re-trip.
• OSWGAPC2 is not used.
48 REM611
Application Manual
1MRS757457 E
REM611
Application Manual
Section 3
REM611 standardized configuration
• OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are start signals from the protection functions.
• OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs are operation signals from the protection functions.
• OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs are alarm signals from the protection and monitoring functions.
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
CCBRBRF1_TRRET
OSWGAPC1
Master Trip 1
TRPPTRC1
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
OSWGAPC3
OSWGAPC4
OSWGAPC5
OSWGAPC6
Start 1
IN1
TPGAPC1
OUT1
Start 2 IN2 OUT2
Start 3
IN1
TPGAPC2
OUT1
Start 4 IN2 OUT2
OSWGAPC7
OSWGAPC8
OSWGAPC9
OSWGAPC10
Trip 1
IN1
TPGAPC3
OUT1
Trip 2
Trip 3
IN2 OUT2
IN1
TPGAPC4
OUT1
Trip 4
IN2 OUT2
OSWGAPC11
MPTTR1_ALARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
OSWGAPC12
OSWGAPC13
OSWGAPC14
OSWGAPC15
OSWGAPC16
GUID-B88C7F08-15E7-49D6-81B5-77D601043F49 V1 EN
Figure 33: Binary outputs
Alarm 1
IN1
TPGAPC5
OUT1
Alarm 2
IN2
Alarm 3
OUT2
IN1
TPGAPC6
OUT1
Alarm 4
IN2
Alarm 5
OUT2
IN1
TPGAPC7
Alarm 6
IN2 OUT2
SELGAPC3
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
49
Section 3
REM611 standardized configuration
50
1MRS757457 E
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
CCBRBRF1_TRRET
OSWGAPC1
Master Trip 1
TRPPTRC1
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
OSWGAPC3 Start 1
OSWGAPC4 Start 2
OSWGAPC5 Start 3
OSWGAPC6 Start 4
OSWGAPC7 Trip 1
OSWGAPC8 Trip 2
OSWGAPC9 Trip 3
OSWGAPC10 Trip 4
SELGAPC4
MPTTR1_ALARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
OSWGAPC11
Alarm 1
OSWGAPC12
Alarm 2
OSWGAPC13
Alarm 3
OSWGAPC14
Alarm 4
OSWGAPC15
Alarm 5
OSWGAPC16
Alarm 6
GUID-4E0F7B4E-1505-454B-B888-E342110B9C21 V1 EN
Figure 34: LEDs
SELGAPC3
SELGAPC3 is used to configure the OSWGAPC outputs to the protection relay binary outputs. The master trip signals are connected to SELGAPC3 via TRPPTRC.
Start, trip and alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are timers and used for setting the minimum pulse length for the outputs
SELGAPC3 outputs are connected with X100 binary outputs.
REM611
Application Manual
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
1MRS757457 E
Section 3
REM611 standardized configuration
CBXCBR_EXE_OP
TRPPTRC1_TRIP
CBXCBR_CLOSE_ENA
CBXCBR_EXE_CL
CCBRBRF1_TRBU
OSWGAPC3_OUT
OSWGAPC4_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
CB Open
IN_1
SELGAPC3
OUT_1
IN_2
CB Close
IN_3
Backup Trip
IN_4
IN1 OUT1
TPGAPC1
IN2 OUT2
Start 1
Start 2
IN1 OUT1
TPGAPC2
IN2 OUT2
Start 3
Start 4
IN1 OUT1
TPGAPC3
IN2 OUT2
Trip 1
Trip 2
IN1 OUT1
TPGAPC4
IN2 OUT2
Trip 3
Trip 4
IN1 OUT1
TPGAPC5
IN2 OUT2
Alarm 1
Alarm 2
IN1 OUT1
TPGAPC6
IN2 OUT2
Alarm 3
Alarm 4
IN1 OUT1
TPGAPC7
IN2 OUT2
Alarm 5
Alarm 6
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
IN_14
IN_15
IN_16
IN_17
IN_18
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
GUID-87B71BC7-0429-4924-8CE1-E2D826D35313 V1 EN
Figure 35: SELGAPC3
SELGAPC4
SELGAPC4 is used to configure the OSWGAPC outputs to LEDs. Master trip signals are connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signals are connected to SELGAPC4 directly. SELGAPC4 outputs are connected to programmable LED1 to LED8.
REM611
Application Manual
51
Section 3
REM611 standardized configuration
1MRS757457 E
CBXCBR_EXE_OP
TRPPTRC1_TRIP
CBXCBR_CLOSE_ENA
CBXCBR_EXE_CL
CCBRBRF1_TRBU
OSWGAPC3_OUT
OSWGAPC4_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
CB Open
IN_1
SELGAPC4
Start 1
IN_2
CB Close
IN_3
Backup Trip
IN_4
IN_5
Start 2
IN_6
Start 3
IN_7
Start 4
IN_8
Trip 1
IN_9
Trip 2
IN_10
Trip 3
IN_11
Trip 4
Alarm 2
IN_12
Alarm 1
IN_13
IN_14
Alarm 3
IN_15
Alarm 4
IN_16
Alarm 5
IN_17
Alarm 6
IN_18
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
GUID-C244E62D-8C47-4071-AC47-6EFE47CB4CCE V1 EN
Figure 36: SELGAPC4
Master trip OSWGAPCs
OSWGAPC1 is used to route the protection function operate signals to Master trip.
OSWGAPC1 have the same inputs from the protection function operates. The output is connected to the TRPPTRC function.
52 REM611
Application Manual
1MRS757457 E
REM611
Application Manual
Section 3
REM611 standardized configuration
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
CCBRBRF1_TRRET
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
IN_1
IN_2
IN_3
IN_4
OSWGAPC1
OUT
Master trip 1
TRPPTRC 1_OPERATE
GUID-4D055596-58DD-4785-9A32-3356CE4C325D V1 EN
Figure 37: OSWGAPC1
Start OSWGAPCs
OSWGAPC instances 3...6 are used to configure the protection start signals. These four OSWGAPCs have the same inputs from the protection function start signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly.
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OSWGAPC3
OUT
Start 1 TPGAPC1_IN1
SELGAPC4_IN_5
GUID-A31C0C14-4E97-42CE-A258-9F67303CA97A V1 EN
Figure 38: OSWGAPC3
53
Section 3
REM611 standardized configuration
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OSWGAPC4
OUT
Start 2 TPGAPC1_IN2
SELGAPC4_IN_6
GUID-BF6A707E-0820-44BC-A654-377F5266CF7D V1 EN
Figure 39: OSWGAPC4
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OSWGAPC5
OUT
Start 3 TPGAPC2_IN1
SELGAPC4_IN_7
GUID-EF6B516A-ABA9-4604-852C-29F071EA90E6 V1 EN
Figure 40: OSWGAPC5
1MRS757457 E
54 REM611
Application Manual
1MRS757457 E
REM611
Application Manual
Section 3
REM611 standardized configuration
PHLPTOC1_START
PHIPTOC1_START
EFLPTOC1_START
EFHPTOC1_START
MNSPTOC1_START
MNSPTOC2_START
LOFLPTUC1_START
PREVPTOC1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OSWGAPC6
OUT
Start 4 TPGAPC2_IN2
SELGAPC4_IN_8
GUID-7F2855BD-9393-4926-A2BA-50F84960B850 V1 EN
Figure 41: OSWGAPC6
Trip OSWGAPCs
OSWGAPC instances 7...10 are used to configure the protection operate signals that belong to the trip group. These four OSWGAPCs have the same inputs from the operate signals of the protection functions. The output is routed to SELGAPC3 via
TPGAPC timer and to SELGAPC4 directly.
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_1
IN_2
IN_3
IN_4
OSWGAPC7
OUT
Trip 1 TPGAPC3_IN1
SELGAPC4_IN_9
GUID-446A9E27-5573-47FE-AFEC-6FE2D14F5953 V1 EN
Figure 42: OSWGAPC7
55
Section 3
REM611 standardized configuration
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
GUID-356729D2-5456-464E-8F12-B15C742ACEE8 V1 EN
Figure 43: OSWGAPC8
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_1
IN_2
IN_3
IN_4
OSWGAPC8
OUT
Trip 2 TPGAPC3_IN2
SELGAPC4_IN_10
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
GUID-08AE8FD5-AB2F-4C08-9BD7-26101E8839C8 V1 EN
Figure 44: OSWGAPC9
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_1
IN_2
IN_3
IN_4
OSWGAPC9
OUT
Trip 3 TPGAPC4_IN1
SELGAPC4_IN_11
1MRS757457 E
56 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
PHLPTOC1_OPERATE
PHIPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC1_OPERATE
MNSPTOC1_OPERATE
MNSPTOC2_OPERATE
LOFLPTUC1_OPERATE
PREVPTOC1_OPERATE
JAMPTOC1_OPERATE
STTPMSU1_OPR_IIT
STTPMSU1_OPR_STALL
MPTTR1_OPERATE
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_1
IN_2
OSWGAPC10
IN_3
IN_4
OUT
Trip 4 TPGAPC4_IN2
SELGAPC4_IN_12
GUID-2AF62F8D-8475-4D18-9FFB-F72272B7D96D V1 EN
Figure 45: OSWGAPC10
Alarm OSWGAPCs
OSWGAPC instances 11...16 are used to configure the alarm signals that belong to the alarm group. These six OSWGAPCs have the same inputs from the alarm signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly.
REM611
Application Manual
57
Section 3
REM611 standardized configuration
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
OSWGAPC11
IN_2
IN_3
IN_4
OUT
GUID-C9345E38-B0BF-4853-9888-9A92C413DE61 V1 EN
Figure 46: OSWGAPC11
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
OSWGAPC12
IN_2
IN_3
IN_4
OUT
Alarm 2
TPGAPC5_IN2
SELGAPC4_IN_14
GUID-91DAB4B9-9CE4-4878-8421-C69465BBAA9F V1 EN
Figure 47: OSWGAPC12
1MRS757457 E
58 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
IN_2
OSWGAPC13
IN_3
IN_4
OUT
Alarm 3 TPGAPC6_IN1
SELGAPC4_IN_15
GUID-1B72F2FB-CFCA-4ADE-83D7-09B1B7DFA7A0 V1 EN
Figure 48: OSWGAPC13
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
OSWGAPC14
IN_2
IN_3
IN_4
OUT
GUID-B0663B18-DC37-4BF3-847F-4256D58B3786 V1 EN
Figure 49: OSWGAPC14
REM611
Application Manual
59
Section 3
REM611 standardized configuration
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
IN_2
OSWGAPC15
IN_3
IN_4
OUT
Alarm 5 TPGAPC7_IN1
SELGAPC4_IN_17
GUID-5128779C-1AB0-4F3E-B16C-E97007644D6A V1 EN
Figure 50: OSWGAPC15
MPTTR1_AMARM
RDRE_TRIGGERED
TCSSCBR1_ALARM
TCSSCBR2_ALARM
MDSOPT1_ALARM
ESMGAPC1_ST_EMERG_ENA
CCBRBRF1_TRBU
CCBRBRF1_TRRET
RESTART_INHIBIT
SELGAPC1_OUT_9
TRPPTRC1_CL_LKOUT
IN_5
IN_6
IN_7
IN_8
IN_9
External Trip
IN_10
IN_11
IN_1
IN_2
OSWGAPC16
IN_3
IN_4
OUT
Alarm 6 TPGAPC7_IN2
SELGAPC4_IN_18
GUID-1C25A420-9D17-403A-A494-74550E6EC9DD V1 EN
Figure 51: OSWGAPC16
1MRS757457 E
60 REM611
Application Manual
1MRS757457 E
3.4.4.4
Section 3
REM611 standardized configuration
GOOSE
In the configuration, there are 20 GOOSERCV_BIN functions and 1
GOOSERCV_MV function. Each GOOSERVC_BIN function can be connected to one received binary GOOSE signal and the GOOSERVC_MV function can be connected to one received analog GOOSE signal. The signal connection can be configured in PCM600.
• GOOSERCV_BIN instances 0 and 1 are used for blocking protection functions.
Signals from these two GOOSERCV_BINs are connected to ISWGAPC9.
ISWGAPC9 is used to configure which protection function block is blocked.
• GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE. Signals from these two GOOSERCV_BINs are connected to TRPPTRC1 trip.
• GOOSERCV_BIN instances 4 to 19 are used for blocking the circuit breaker operation. Signals from these 16 GOOSERCV_BINs are connected to
ISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal to block the circuit breaker open or close operation.
• GOOSERCV_MV instance 1 is used for ambient temperature measurement from
GOOSE. Signal from this GOOSERCV_MV is connected to the input
AMB_TEMP of MPTTR1.
REM611
Application Manual
61
Section 3
REM611 standardized configuration
1MRS757457 E
GOOSERCV_BIN:0
GOOSERCV_BIN:1
OR
GOOSE Blcoking
ISWGAPC9
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
GOOSERCV_BIN:2
GOOSERCV_BIN:3
GOOSERCV_BIN:4
GOOSERCV_BIN:5
OR
GOOSE
External Trip
TRPPTRC1_OPERATE
OR
GOOSE Block CB
ISWGAPC10
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
GOOSERCV_BIN:19
GOOSERCV_MV:1 MPTTR1_AMB_TEMP
GUID-CDAE630B-B30B-492D-B387-960CBA32A3BC V2 EN
Figure 52: GOOSE overview
ISWGAPC9
ISWGAPC9 is used to configure which protection functions can be blocked by the received GOOSE signals. ISWGAPC9 inputs are received GOOSE signals from
GOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to the block inputs of the protection functions.
62 REM611
Application Manual
1MRS757457 E
Section 3
REM611 standardized configuration
GOOSERCV_BIN:0_OUT
GOOSERCV_BIN:1_OUT
GOOSE Blocking
IN
ISWGAPC9
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
PHLPTOC1_BLOCK
PHIPTOC1_BLOCK
EFLPTOC1_BLOCK
EFHPTOC1_BLOCK
JAMPTOC1_BLOCK
MNSPTOC1_BLOCK
MNSPTOC2_BLOCK
LOFLPTUC1_BLOCK
STTPMSU1_BLOCK
PREVPTOC1_BLOCK
MPTTR1_BLOCK
GUID-0A6BC123-F2FB-493F-BA08-D0885E2724CC V1 EN
Figure 53: ISWGAPC9
ISWGAPC10
ISWGAPC10 is used to block the circuit breaker operation from the received GOOSE signals. ISWGAPC10 inputs are received GOOSE signals from GOOSERCV_BIN:
4 to GOOSERCV_BIN:19. The outputs are connected to block the circuit breaker close and open operation.
GOOSERCV_BIN:4_OUT
GOOSERCV_BIN:5_OUT
GOOSERCV_BIN:6_OUT
...
GOOSERCV_BIN:19_OUT
GOOSE Blocking CB
IN
GUID-CB5DD0EA-3C0F-4683-AC0B-692A403A6757 V1 EN
Figure 54: ISWGAPC10
ISWGAPC10
OUT_1
OUT_2
CBXCBR1_BLK_CLOSE
CBXCBR1_BLK_OPEN
REM611
Application Manual
63
64
1MRS757457 E
Section 4
Requirements for measurement transformers
Section 4 Requirements for measurement transformers
4.1
4.1.1
4.1.1.1
REM611
Application Manual
Current transformers
Current transformer requirements for overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be chosen carefully. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity, and co-ordination of protection. However, when the CT is correctly selected, a fast and reliable short circuit protection can be enabled.
The selection of a CT depends not only on the CT specifications but also on the network fault current magnitude, desired protection objectives, and the actual CT burden.
Current transformer accuracy class and accuracy limit factor
The rated accuracy limit factor (F n
) is the ratio of the rated accuracy limit primary current to the rated primary current. For example, a protective current transformer of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protective current transformers, the accuracy class is designed by the highest permissible percentage composite error at the rated accuracy limit primary current prescribed for the accuracy class concerned, followed by the letter "P" (meaning protection).
Table 16:
Accuracy class
5P
10P
Limits of errors according to IEC 60044-1 for protective current transformers
Current error at rated primary current (%)
±1
±3
Phase displacement at rated primary current minutes
-
±60 centiradians
-
±1.8
Composite error at rated accuracy limit primary current (%)
5
10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protection. The 5P class provides a better accuracy.
The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy.
In practise, the actual accuracy limit factor (F a
) differs from the rated accuracy limit factor (F n
) and is proportional to the ratio of the rated CT burden and the actual CT burden.
65
Section 4
Requirements for measurement transformers
The actual accuracy limit factor is calculated using the formula:
F a
≈
F n
×
S in
+ S n
S in
+ S
A071141 V1 EN
F n
S in
S the accuracy limit factor with the nominal external burden S n the internal secondary burden of the CT the actual external burden
1MRS757457 E
4.1.1.2
66
Non-directional overcurrent protection
The current transformer selection
Non-directional overcurrent protection does not set high requirements on the accuracy class or on the actual accuracy limit factor (F a
) of the CTs. It is, however, recommended to select a CT with F a
of at least 20.
The nominal primary current I
1n
should be chosen in such a way that the thermal and dynamic strength of the current measuring input of the protection relay is not exceeded. This is always fulfilled when
I
1n
> I kmax
/ 100,
I kmax
is the highest fault current.
The saturation of the CT protects the measuring circuit and the current input of the protection relay. For that reason, in practice, even a few times smaller nominal primary current can be used than given by the formula.
Recommended start current settings
If I kmin
is the lowest primary current at which the highest set overcurrent stage is to operate, the start current should be set using the formula:
Current start value < 0.7 × (I kmin
/ I
1n
)
I
1n
is the nominal primary current of the CT.
The factor 0.7 takes into account the protection relay inaccuracy, current transformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the high set stage overcurrent protection is defined. The operate time delay caused by the CT saturation is typically small enough when the overcurrent setting is noticeably lower than F a
.
REM611
Application Manual
1MRS757457 E
4.1.1.3
Section 4
Requirements for measurement transformers
When defining the setting values for the low set stages, the saturation of the CT does not need to be taken into account and the start current setting is simply according to the formula.
Delay in operation caused by saturation of current transformers
The saturation of CT may cause a delayed protection relay operation. To ensure the time selectivity, the delay must be taken into account when setting the operate times of successive protection relays.
With definite time mode of operation, the saturation of CT may cause a delay that is as long as the time constant of the DC component of the fault current, when the current is only slightly higher than the starting current. This depends on the accuracy limit factor of the CT, on the remanence flux of the core of the CT, and on the operate time setting.
With inverse time mode of operation, the delay should always be considered as being as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the AC component of the fault current should not saturate the CT less than 20 times the starting current. Otherwise, the inverse operation time can be further prolonged.
Therefore, the accuracy limit factor F a
should be chosen using the formula:
F a
> 20 × Current start value / I
1n
The Current start value is the primary start current setting of the protection relay.
Example for non-directional overcurrent protection
The following figure describes a typical medium voltage feeder. The protection is implemented as three-stage definite time non-directional overcurrent protection.
REM611
Application Manual
67
Section 4
Requirements for measurement transformers
1MRS757457 E
68
A071142 V1 EN
Figure 55: Example of three-stage overcurrent protection
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice the nominal current of the cable. The operate time is selected so that it is selective with the
next protection relay (not visible in Figure 55
). The settings for the high-set stage and instantaneous stage are defined also so that grading is ensured with the downstream protection. In addition, the start current settings have to be defined so that the protection relay operates with the minimum fault current and it does not operate with the maximum load current. The settings for all three stages are as in
For the application point of view, the suitable setting for instantaneous stage (I>>>) in this example is 3 500 A (5.83 × I
2n
). I
2n
is the 1.2 multiple with nominal primary current of the CT. For the CT characteristics point of view, the criteria given by the current transformer selection formula is fulfilled and also the protection relay setting is considerably below the F a
. In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons.
REM611
Application Manual
1MRS757457 E
Section 5
Protection relay's physical connections
Section 5 Protection relay's physical connections
5.1
5.1.1
5.1.1.1
5.1.1.2
5.1.2
Inputs
Energizing inputs
Phase currents
The protection relay can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied.
However, at least terminals X120:7-8 must be connected.
Table 17:
Terminal
X120:7-8
X120:9-10
X120:11-12
Phase current inputs included in configuration A
Description
IL1
IL2
IL3
Residual current
Table 18:
Terminal
X120:13-14
Residual current input included in configuration A
Description
Io
Auxiliary supply voltage input
The auxiliary voltage of the protection relay is connected to terminals X100:1-2. At
DC supply, the positive lead is connected to terminal X100:1. The permitted auxiliary voltage range (AC/DC or DC) is marked on the top of the LHMI of the protection relay.
Auxiliary voltage supply Table 19:
Terminal
X100:1
X100:2
Description
+ Input
- Input
REM611
Application Manual
69
Section 5
Protection relay's physical connections
5.1.3
5.2
5.2.1
70
1MRS757457 E
Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for remote control of protection relay settings.
Binary inputs of slot X120 are available with configuration A.
Table 20:
Terminal
X120:1
X120:2
X120:3
X120:2
X120:4
X120:2
X120:5
X120:6
Binary input terminals X120-1...6
Description
BI1, +
BI1, -
BI2, +
BI2, -
BI3, +
BI3, -
BI4, +
BI4, -
Outputs
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. In the factory default configuration, the trip signals from all the protection stages are routed to PO3 and PO4.
Output contacts Table 21:
Terminal
X100:6
X100:7
X100:8
X100:9
X100:15
X100:16
X100:17
X100:18
X100:19
X100:20
X100:21
X100:22
X100:23
X100:24
Description
PO1, NO
PO1, NO
PO2, NO
PO2, NO
PO3, NO (TCS resistor)
PO3, NO
PO3, NO
PO3 (TCS1 input), NO
PO3 (TCS1 input), NO
PO4, NO (TCS resistor)
PO4, NO
PO4, NO
PO4 (TCS2 input), NO
PO4 (TCS2 input), NO
REM611
Application Manual
1MRS757457 E
5.2.2
5.2.3
Section 5
Protection relay's physical connections
Outputs for signalling
Output contacts SO1 and SO2 in slot X100 can be used for signalling on start and tripping of the protection relay. On delivery from the factory, the start and alarm signals from all the protection stages are routed to signalling outputs.
Output contacts X100:10...14
Table 22:
Terminal
X100:10
X100:11
X100:12
X100:13
X100:14
Description
SO1, common
SO1, NC
SO1, NO
SO2, NO
SO2, NO
IRF
The IRF contact functions as an output contact for the self-supervision system of the protection relay. Under normal operating conditions, the protection relay is energized and the contact is closed (X100:3-5). When a fault is detected by the self-supervision system or the auxiliary voltage is disconnected, the contact X100:3-5 drops off and the contact X100:3-4 closes.
IRF contact Table 23:
Terminal
X100:3
X100:4
X100:5
Description
IRF, common
Closed; IRF, or U aux
disconnected
Closed; no IRF, and U aux
connected
REM611
Application Manual
71
72
1MRS757457 E
Section 6 Glossary
REM611
Application Manual
Section 6
Glossary
100BASE-FX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses fiber optic cabling
100BASE-TX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses twistedpair cabling category 5 or higher with RJ-45 connectors
611 series Series of numerical protection and control relays for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment
CB
CSV
Circuit breaker
Comma-separated values
CT
DAN
DC
DPC
EMC
Ethernet
Current transformer
Doubly attached node
1. Direct current
2. Disconnector
3. Double command
Double-point control
Electromagnetic compatibility
A standard for connecting a family of frame-based computer networking technologies into a LAN
FIFO
FTP
FTPS
GOOSE
HMI
HSR
HTTPS
First in, first out
File transfer protocol
FTP Secure
Generic Object-Oriented Substation Event
Human-machine interface
High-availability seamless redundancy
Hypertext Transfer Protocol Secure
IEC
IEC 61850
International Electrotechnical Commission
International standard for substation communication and modeling
IEC 61850-8-1 A communication protocol based on the IEC 61850 standard series
IED Intelligent electronic device
73
Section 6
Glossary
1MRS757457 E
RSTP
SAN
SNTP
SO
WAN
WHMI
NPS
PCM600
PO
PRP
REM611
RJ-45
RS-485
IRIG-B
LAN
LC
LCD
LED
LHMI
MAC
MMS
Modbus
IEEE 1686
IP address
Standard for Substation Intelligent Electronic Devices'
(IEDs') Cyber Security Capabilities
A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol.
Inter-Range Instrumentation Group's time code format B
Local area network
Connector type for glass fiber cable, IEC 61754-20
Liquid crystal display
Light-emitting diode
Local human-machine interface
Media access control
1. Manufacturing message specification
2. Metering management system
A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices.
Negative phase sequence
Protection and Control IED Manager
Power output
Parallel redundancy protocol
Motor protection and control relay
Galvanic connector type
Serial link according to EIA standard RS485
Rapid spanning tree protocol
Single attached node
Simple Network Time Protocol
Signal output
Wide area network
Web human-machine interface
74 REM611
Application Manual
75
—
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/relion
© Copyright 2019 ABB. All rights reserved.
advertisement
Related manuals
advertisement
Table of contents
- 7 Table of contents
- 9 Introduction
- 9 This manual
- 9 Intended audience
- 10 Product documentation
- 10 Product documentation set
- 10 Document revision history
- 11 Related documentation
- 11 Symbols and conventions
- 11 Symbols
- 12 Document conventions
- 12 Functions, codes and symbols
- 15 REM611 overview
- 15 Overview
- 15 Product version history
- 16 PCM600 and relay connectivity package version
- 16 Operation functionality
- 16 Optional functions
- 16 Physical hardware
- 17 Local HMI
- 18 Display
- 19 LEDs
- 19 Keypad
- 20 Web HMI
- 21 Command buttons
- 22 Authorization
- 23 Audit trail
- 25 Communication
- 26 Self-healing Ethernet ring
- 27 Ethernet redundancy
- 29 Secure communication
- 31 REM611 standardized configuration
- 31 Standardized configuration
- 32 Switch groups
- 32 Input switch group ISWGAPC
- 33 Output switch group OSWGAPC
- 33 Selector switch group SELGAPC
- 35 Connection diagrams
- 36 Configuration A
- 36 Applications
- 37 Functions
- 38 Default I/O connections
- 38 Predefined disturbance recorder connections
- 39 Functional diagrams
- 39 Functional diagrams for protection
- 46 Functional diagrams for disturbance recorder and supervision functionsrecorder
- 48 Functional diagrams for control and interlocking
- 50 Switch groups
- 51 Binary inputs
- 53 Internal signal
- 54 Binary outputs and LEDs
- 67 GOOSE
- 71 Requirements for measurement transformers
- 71 Current transformers
- 71 Current transformer requirements for overcurrent protection
- 71 Current transformer accuracy class and accuracy limit factor
- 72 Non-directional overcurrent protection
- 73 Example for non-directional overcurrent protection
- 75 Protection relay's physical connections
- 75 Inputs
- 75 Energizing inputs
- 75 Phase currents
- 75 Residual current
- 75 Auxiliary supply voltage input
- 76 Binary inputs
- 76 Outputs
- 76 Outputs for tripping and controlling
- 77 Outputs for signalling
- 77 IRF
- 79 Glossary