ABB REM611 2.0 IEC, Motor Protection, Application Instructions

Add to My manuals
84 Pages

advertisement

ABB REM611 2.0 IEC, Motor Protection, Application Instructions | Manualzz

RELION® 611 SERIES

Motor Protection and Control

REM611

Application Manual

Document ID: 1MRS757457

Issued: 2019-04-10

Revision: E

Product version: 2.0

© Copyright 2019 ABB. All rights reserved

Copyright

This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

www.abb.com/relion

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties.

All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.

This product has been designed to be connected and communicate data and information via a network interface which should be connected to a secure network.

It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures (such as, but not limited to, installation of firewalls, application of authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the product and the network, its system and interface included, against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not liable for any such damages and/or losses.

This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN

60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Table of contents

REM611

Application Manual

Table of contents

Section 1 Introduction.......................................................................3

This manual........................................................................................ 3

Intended audience.............................................................................. 3

Product documentation.......................................................................4

Product documentation set............................................................4

Document revision history............................................................. 4

Related documentation..................................................................5

Symbols and conventions...................................................................5

Symbols.........................................................................................5

Document conventions..................................................................6

Functions, codes and symbols...................................................... 6

Section 2 REM611 overview............................................................ 9

Overview.............................................................................................9

Product version history..................................................................9

PCM600 and relay connectivity package version........................10

Operation functionality......................................................................10

Optional functions........................................................................10

Physical hardware............................................................................ 10

Local HMI......................................................................................... 11

Display.........................................................................................12

LEDs............................................................................................13

Keypad........................................................................................ 13

Web HMI...........................................................................................14

Command buttons....................................................................... 15

Authorization.....................................................................................16

Audit trail......................................................................................17

Communication.................................................................................19

Self-healing Ethernet ring............................................................20

Ethernet redundancy................................................................... 21

Secure communication................................................................23

Section 3 REM611 standardized configuration ............................. 25

Standardized configuration...............................................................25

Switch groups................................................................................... 26

Input switch group ISWGAPC..................................................... 26

Output switch group OSWGAPC.................................................27

Selector switch group SELGAPC................................................ 27

Connection diagrams........................................................................29

Configuration A.................................................................................30

1

2

Table of contents

Applications................................................................................. 30

Functions.....................................................................................31

Default I/O connections.......................................................... 32

Predefined disturbance recorder connections........................32

Functional diagrams.................................................................... 33

Functional diagrams for protection......................................... 33

Functional diagrams for disturbance recorder and supervision functionsrecorder................................................ 40

Functional diagrams for control and interlocking....................42

Switch groups..............................................................................44

Binary inputs...........................................................................45

Internal signal......................................................................... 47

Binary outputs and LEDs........................................................48

GOOSE.................................................................................. 61

Section 4 Requirements for measurement transformers................65

Current transformers........................................................................ 65

Current transformer requirements for overcurrent protection......65

Current transformer accuracy class and accuracy limit factor...................................................................................... 65

Non-directional overcurrent protection................................... 66

Example for non-directional overcurrent protection................67

Section 5 Protection relay's physical connections..........................69

Inputs................................................................................................69

Energizing inputs.........................................................................69

Phase currents....................................................................... 69

Residual current..................................................................... 69

Auxiliary supply voltage input...................................................... 69

Binary inputs................................................................................70

Outputs............................................................................................. 70

Outputs for tripping and controlling..............................................70

Outputs for signalling...................................................................71

IRF...............................................................................................71

Section 6 Glossary......................................................................... 73

REM611

Application Manual

1MRS757457 E

Section 1 Introduction

1.1

1.2

Section 1

Introduction

This manual

The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.

Intended audience

This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and principles.

REM611

Application Manual

3

Section 1

Introduction

1.3

1.3.1

Product documentation

Product documentation set

1MRS757457 E

4

1.3.2

Quick start guide

Quick installation guide

Brochure

Product guide

Operation manual

Installation manual

Connection diagram

Engineering manual

Technical manual

Application manual

Communication protocol manual

IEC 61850 engineering guide

Point list manual

Cyber security deployment guideline

GUID-0777AFDA-CADF-4AA9-946E-F6A856BDF75E V1 EN

Figure 1: The intended use of manuals in different lifecycles

Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion .

Document revision history

Document revision/date

A/2011-11-18

B/2016-02-22

Product version

1.0

2.0

C/2016-10-11

D/2017-10-31

E/2019-04-10

2.0

2.0

2.0

History

First release

Content updated to correspond to the product version

Content updated

Content updated

Content updated

REM611

Application Manual

1MRS757457 E

1.3.3

1.4

1.4.1

REM611

Application Manual

Section 1

Introduction

Download the latest documents from the ABB Web site http://www.abb.com/substationautomation .

Related documentation

Name of the document

Modbus Communication Protocol Manual

IEC 61850 Engineering Guide

Engineering Manual

Installation Manual

Operation Manual

Technical Manual

Cyber Security Deployment Guideline

Document ID

1MRS757461

1MRS757465

1MRS241255

1MRS757452

1MRS757453

1MRS757454

1MRS758337

Symbols and conventions

Symbols

The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function.

5

6

Section 1

Introduction

1.4.2

1.4.3

1MRS757457 E

Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

Document conventions

A particular convention may not be used in this manual.

• Abbreviations and acronyms are spelled out in the glossary. The glossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using the push button icons.

To navigate between the options, use and .

• Menu paths are presented in bold.

Select Main menu/Settings .

• LHMI messages are shown in Courier font.

To save the changes in nonvolatile memory, select Yes and press .

• Parameter names are shown in italics.

The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks.

The corresponding parameter values are "On" and "Off".

• Input/output messages and monitored data names are shown in Courier font.

When the function starts, the START output is set to TRUE.

• This document assumes that the parameter setting visibility is "Advanced".

Functions, codes and symbols

Table 1:

Function

Protection

Functions included in the relay

IEC 61850

Three-phase non-directional overcurrent protection, low stage, instance 1

Three-phase non-directional overcurrent protection, instantaneous stage, instance 1

Non-directional earth-fault protection, low stage, instance 1

Non-directional earth-fault protection, high stage, instance 1

Negative-sequence overcurrent protection for machines, instance 1

Negative-sequence overcurrent protection for machines, instance 2

Loss of load supervision

Motor load jam protection

Table continues on next page

PHLPTOC1

PHIPTOC1

EFLPTOC1

EFHPTOC1

MNSPTOC1

MNSPTOC2

LOFLPTUC1

JAMPTOC1

IEC 60617 IEC-ANSI

3I> (1)

3I>>> (1)

Io> (1)

Io>> (1)

I2>M (1)

I2>M (2)

3I<

Ist>

51P-1 (1)

50P/51P (1)

51N-1 (1)

51N-2 (1)

46M (1)

46M (2)

37

51LR

REM611

Application Manual

1MRS757457 E

Section 1

Introduction

Function

Motor start-up supervision

Phase reversal protection

Thermal overload protection for motors

Circuit breaker failure protection

Master trip, instance 1

Other

Input switch group 1)

Output switch group 2)

Selector 3)

Minimum pulse timer (2 pcs) 4)

Minimum pulse timer (2 pcs, second resolution), instance 1

Move (8 pcs), instance 1

Control

Circuit-breaker control

Emergency start-up

Condition monitoring and supervision

Trip circuit supervision, instance 1

Trip circuit supervision, instance 2

Runtime counter for machines and devices

Logging

Disturbance recorder

Fault recorder

Measurement

Three-phase current measurement, instance 1

Sequence current measurement

Residual current measurement, instance 1

1) 10 instances

2) 20 instances

3) 6 instances

4) 10 instances

IEC 61850

STTPMSU1

PREVPTOC1

MPTTR1

CCBRBRF1

TRPPTRC1

ISWGAPC

OSWGAPC

SELGAPC

TPGAPC

TPSGAPC

MVGAPC

CBXCBR1

ESMGAPC1

TCSSCBR1

TCSSCBR2

MDSOPT1

RDRE1

FLTRFRC1

CMMXU1

CSMSQI1

RESCMMXU1

IEC 60617

Is2t n<

I2>>

3Ith>M

IEC-ANSI

49,66,48,51LR

46R

49M

3I>/Io>BF 51BF/51NBF

Master Trip (1) 94/86 (1)

ISWGAPC

OSWGAPC

SELGAPC

TP

TPS (1)

MV (1)

ISWGAPC

OSWGAPC

SELGAPC

TP

TPS (1)

MV (1)

I <-> O CB

ESTART

TCS (1)

TCS (2)

OPTS

I <-> O CB

ESTART

TCM (1)

TCM (2)

OPTM

-

DR (1)

3I

I1, I2, I0

Io

DFR(1)

FR

3I

I1, I2, I0

In

REM611

Application Manual

7

8

1MRS757457 E

Section 2 REM611 overview

2.1

2.1.1

REM611

Application Manual

Section 2

REM611 overview

Overview

REM611 is a dedicated motor protection relay for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry. Typically, the relay is used with circuit breaker or contactor-controlled medium-sized or small motors in a variety of drives, such as pumps and conveyors, crushers and choppers, mixers and agitators, and fans and aerators.

REM611 is a member of ABB’s Relion ® product family and part of the 611 protection and control product series. The 611 series relays are characterized by their compactness and withdrawable-unit design.

The 611 series offers simplified yet powerful functionality for most applications.

Once the application-specific parameter set has been entered, the installed protection relay is ready to be put into service. The further addition of communication functionality and interoperability between substation automation devices offered by the IEC 61850 standard adds flexibility and value to end users as well as electrical system manufacturers.

The 611 series relays fully support the IEC 61850 standard for communication and interoperability of substation automation devices, including fast GOOSE (Generic

Object Oriented Substation Event) messaging, and can now also benefit from the extended interoperability provided by Edition 2 of the standard. The relays further support the parallel redundancy protocol (PRP) and the high-availability seamless redundancy (HSR) protocol. The 611 series relays are able to use IEC 61850 and

Modbus® communication protocols simultaneously.

Product version history

Product version

1.0

2.0

Product history

Product released

High-availablity seamless redundancy (HSR) protocol

Parallel redundancy protocol (PRP-1)

Two selectable indication colors for LEDs (red or green)

Online binary signal monitoring with PCM600

IEEE 1588 v2 time synchronization

Profibus adapter support

Import/export of settings via WHMI

Setting usability improvements

HMI event filtering tool

IEC 61850 Edition 2

Support for configuration migration (starting from Ver.1.0 to Ver.2.0)

Software closable Ethernet ports

Report summary via WHMI

9

Section 2

REM611 overview

2.1.2

1MRS757457 E

PCM600 and relay connectivity package version

• Protection and Control IED Manager PCM600 Ver.2.7 or later

• REM611 Connectivity Package Ver.2.0 or later

Communication Management

Configuration Wizard

Disturbance Handling

Event Viewer

Fault Record tool

Firmware Update

HMI Event Filtering

IEC 61850 Configuration

IED Compare

IED Configuration Migration

IED User Management

Label Printing

Lifecycle Traceability

Parameter Setting

Signal Matrix

Signal Monitoring

Download connectivity packages from the ABB Web site http://www.abb.com/substationautomation or directly with Update

Manager in PCM600.

2.2

2.2.1

2.3

Operation functionality

Optional functions

• Modbus TCP/IP or RTU/ASCII

• IEEE 1588 time v2 synchronization

• High-availability seamless redundancy protocol (HSR)

• Parallel redundancy protocol (PRP)

Physical hardware

The protection relay consists of two main parts: plug-in unit and case. The content depends on the ordered functionality.

10 REM611

Application Manual

1MRS757457 E

2.4

Section 2

REM611 overview

Table 2:

Main unit Slot ID

Plug-in unit

-

X100

Case

X120

X000

Plug-in unit and case

Content options

HMI

Auxiliary power/BO module

AI/BI module

Optional communication module

Small (4 lines, 16 characters)

48...250 V DC/100...240 V AC; or 24...60 V DC

2 normally-open PO contacts

1 change-over SO contacts

1 normally-open SO contact

2 double-pole PO contacts with TCS

1 dedicated internal fault output contact

Configuration A:

3 phase current inputs (1/5 A)

1 residual current input (1/5 A or 0.2/1 A) 1)

4 binary inputs

See technical manual for details about different type of communication modules.

1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring core-balance current transformers.

Rated values of the current and voltage inputs are basic setting parameters of the protection relay. The binary input thresholds are selectable within the range 16…176

V DC by adjusting the binary input setting parameters.

See the installation manual for more information about the case and the plug-in unit.

The connection diagrams of different hardware modules are presented in this manual.

Table 3:

Conf.

A

Number of physical connections in configuration

CT

Analog channels

4

VT

-

BI

4

Binary channels

BO

6

Local HMI

The LHMI is used for setting, monitoring and controlling the protection relay. The

LHMI comprises the display, buttons, LED indicators and communication port.

REM611

Application Manual

11

Section 2

REM611 overview

1MRS757457 E

REF611

Overcurrent

Earth-fault

Phase unbalance

Thermal overload

AR sequence in progress

Disturb.rec.trigged

Trip circuit failure

Breaker failure

2.4.1

12

GUID-E15422BF-B3E6-4D02-8D43-D912D5EF0360 V1 EN

Figure 2: Example of the LHMI

Display

The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.

Table 4: Small display

Character size 1)

Small, mono-spaced (6 × 12 pixels)

Large, variable width (13 × 14 pixels)

1) Depending on the selected language

Rows in the view

5

3

Characters per row

20

8 or more

The display view is divided into four basic areas.

REM611

Application Manual

1MRS757457 E

Section 2

REM611 overview

1 2

2.4.2

2.4.3

3

GUID-24ADB995-439A-4563-AACE-1FAA193A8EF9 V1 EN

Figure 3: Display layout

1 Header

2 Icon

3 Content

4 Scroll bar (displayed when needed)

4

LEDs

The LHMI includes three protection indicators above the display: Ready, Start and

Trip.

There are also 8 programmable LEDs on front of the LHMI. The LEDs can be configured with the LHMI, WHMI or PCM600.

Keypad

The LHMI keypad contains push buttons which are used to navigate in different views or menus. With the push buttons you can give open or close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.

REM611

Application Manual

13

Section 2

REM611 overview

1MRS757457 E

2.5

GUID-B681763E-EC56-4515-AC57-1FD5349715F7 V1 EN

Figure 4: LHMI keypad with object control, navigation and command push buttons and RJ-45 communication port

Web HMI

The WHMI allows secure access to the protection relay via a Web browser. When the

Secure Communication parameter in the protection relay is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The

WHMI is verified with Internet Explorer 8.0, 9.0, 10.0 and 11.0.

WHMI is enabled by default.

WHMI offers several functions.

• Programmable LEDs and event lists

• System supervision

• Parameter settings

• Measurement display

• Disturbance records

• Fault records

• Phasor diagram

• Signal configuration

• Importing/Exporting parameters

• Report summary

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

14 REM611

Application Manual

1MRS757457 E

Section 2

REM611 overview

2.5.1

REM611

Application Manual

GUID-CD531B61-6866-44E9-B0C1-925B48140F3F V2 EN

Figure 5: Example view of the WHMI

The WHMI can be accessed locally and remotely.

• Locally by connecting the laptop to the protection relay via the front communication port.

• Remotely over LAN/WAN.

Command buttons

Command buttons can be used to edit parameters and control information via the

WHMI.

Table 5:

Name

Command buttons

Description

Enabling parameter editing

Disabling parameter editing

Writing parameters to the protection relay

Refreshing parameter values

Printing out parameters

Committing changes to protection relay's nonvolatile flash memory

Table continues on next page

15

Section 2

REM611 overview

2.6

1MRS757457 E

Name Description

Rejecting changes

Showing context sensitive help messages

Error icon

Clearing events

Triggering the disturbance recorder manually

Saving values to TXT or CSV file format

Freezing the values so that updates are not displayed

Receiving continuous updates to the monitoring view

Deleting the disturbance record

Deleting all disturbance records

Saving the disturbance record files

Viewing all fault records

Clearing all fault records

Importing settings

Exporting settings

Selecting all

Clearing all selections

Refreshing the parameter list view

Authorization

Four user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords.

The default passwords in the protection relay delivered from the factory can be changed with Administrator user rights.

User authorization is disabled by default for LHMI but WHMI always uses authorization.

16 REM611

Application Manual

1MRS757457 E

2.6.1

REM611

Application Manual

Section 2

REM611 overview

Table 6:

Username

VIEWER

OPERATOR

ENGINEER

ADMINISTRATOR

Predefined user categories

User rights

Read only access

Selecting remote or local state with

Changing setting groups

Controlling

Clearing indications

(only locally)

Changing settings

Clearing event list

Clearing disturbance records

Changing system settings such as IP address, serial baud rate or disturbance recorder settings

Setting the protection relay to test mode

Selecting language

All listed above

Changing password

Factory default activation

For user authorization for PCM600, see PCM600 documentation.

Audit trail

The protection relay offers a large set of event-logging functions. Critical system and protection relay security-related events are logged to a separate nonvolatile audit trail for the administrator.

Audit trail is a chronological record of system activities that allows the reconstruction and examination of the sequence of system and security-related events and changes in the protection relay. Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in LHMI and WHMI and Event Viewer in PCM600.

The protection relay stores 2048 audit trail events to the nonvolatile audit trail.

Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the FIFO principle. Nonvolatile memory is based on a memory type which does not need battery backup nor regular component change to maintain the memory storage.

Audit trail events related to user authorization (login, logout, violation remote and violation local) are defined according to the selected set of requirements from IEEE

1686. The logging is based on predefined user names or user categories. The user audit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.

17

Section 2

REM611 overview

1MRS757457 E

Table 7: Audit trail events

Audit trail event

Configuration change

Firmware change

Firmware change fail

Attached to retrofit test case

Removed from retrofit test case

Setting group remote

Setting group local

Control remote

Control local

Test on

Test off

Reset trips

Setting commit

Time change

View audit log

Login

Logout

Password change

Firmware reset

Audit overflow

Violation remote

Violation local

Description

Configuration files changed

Firmware changed

Firmware change failed

Unit has been attached to retrofit case

Removed from retrofit test case

User changed setting group remotely

User changed setting group locally

DPC object control remote

DPC object control local

Test mode on

Test mode off

Reset latched trips (TRPPTRC*)

Settings have been changed

Time changed directly by the user. Note that this is not used when the protection relay is synchronised properly by the appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).

Administrator accessed audit trail

Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or

LHMI.

Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or

LHMI.

Password changed

Reset issued by user or tool

Too many audit events in the time period

Unsuccessful login attempt from IEC 61850-8-1 (MMS),

WHMI, FTP or LHMI.

Unsuccessful login attempt from IEC 61850-8-1 (MMS),

WHMI, FTP or LHMI.

PCM600 Event Viewer can be used to view the audit trail events and process related events. Audit trail events are visible through dedicated Security events view. Since only the administrator has the right to read audit trail, authorization must be used in

PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.

Audit trail events can be configured to be visible also in LHMI/WHMI Event list together with process related events.

To expose the audit trail events through Event list, define the

Authority logging level parameter via Configuration/

Authorization/Security . This exposes audit trail events to all users.

18 REM611

Application Manual

1MRS757457 E

2.7

REM611

Application Manual

Section 2

REM611 overview

Table 8:

Audit trail event

Configuration change

Firmware change

Firmware change fail

Attached to retrofit test case

Removed from retrofit test case

Setting group remote

Setting group local

Control remote

Control local

Test on

Test off

Reset trips

Setting commit

Time change

View audit log

Login

Logout

Password change

Firmware reset

Violation local

Violation remote

Comparison of authority logging levels

None

Configurati on change

Authority logging level

Setting group

Setting group, control

● ●

Settings edit

All

Communication

The protection relay supports a range of communication protocols including IEC

61850 and Modbus ® . Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the protection relays, is only enabled by the IEC

61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file format. The protection relay can send and receive binary signals from other devices

(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,

19

Section 2

REM611 overview

2.7.1

1MRS757457 E where the highest performance class with a total transmission time of 3 ms is supported. The protection relay meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard.

The protection relay can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus.

All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The protection relay can be connected to

Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fiber-optic LC connector (100Base-FX). An optional serial interface is available for

RS-485 communication.

Self-healing Ethernet ring

For the correct operation of self-healing loop topology, it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches. Otherwise, connecting the loop topology can cause problems to the network. The protection relay itself does not support link-down detection or RSTP.

The ring recovery process is based on the aging of the MAC addresses, and the linkup/link-down events can cause temporary breaks in communication. For a better performance of the self-healing loop, it is recommended that the external switch furthest from the protection relay loop is assigned as the root switch (bridge priority

= 0) and the bridge priority increases towards the protection relay loop. The end links of the protection relay loop can be attached to the same external switch or to two adjacent external switches. A self-healing Ethernet ring requires a communication module with at least two Ethernet interfaces for all protection relays.

20 REM611

Application Manual

1MRS757457 E

Client A

Manag ed Eth ernet switch with RSTP su pport

Section 2

REM611 overview

Client B

Manag ed Eth ernet switch with RSTP su pport

Network

Network

2.7.2

REM611

Application Manual

GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V2 EN

Figure 6: Self-healing Ethernet ring solution

The Ethernet ring solution supports the connection of up to 30 protection relays. If more than 30 protection relays are to be connected, it is recommended that the network is split into several rings with no more than 30 protection relays per ring. Each protection relay has a 50-μs store-and-forward delay, and to fulfil the performance requirements for fast horizontal communication, the ring size is limited to 30 protection relays.

Ethernet redundancy

IEC 61850 specifies a network redundancy scheme that improves the system availability for substation communication. It is based on two complementary protocols defined in the IEC 62439-3:2012 standard: parallel redundancy protocol

PRP and high-availability seamless redundancy HSR protocol. Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection. Therefore, both are able to overcome the failure of a link or switch with a zero-switchover time, thus fulfilling the stringent real-time requirements for the substation automation horizontal communication and time synchronization.

PRP specifies that each device is connected in parallel to two local area networks.

HSR applies the PRP principle to rings and to the rings of rings to achieve costeffective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for all 611 series protection relays.

21

Section 2

REM611 overview

1MRS757457 E

IEC 62439-3:2012 cancels and replaces the first edition published in

2010. These standard versions are also referred to as IEC 62439-3

Edition 1 and IEC 62439-3 Edition 2. The protection relay supports

IEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.

PRP

Each PRP node, called a double attached node with PRP (DAN), is attached to two independent LANs operated in parallel. These parallel networks in PRP are called

LAN A and LAN B. The networks are completely separated to ensure failure independence, and they can have different topologies. Both networks operate in parallel, thus providing zero-time recovery and continuous checking of redundancy to avoid communication failures. Non-PRP nodes, called single attached nodes (SANs), are either attached to one network only (and can therefore communicate only with

DANs and SANs attached to the same network), or are attached through a redundancy box, a device that behaves like a DAN.

Managed

Ethernet switch

IEC 61850 PRP

Managed

Ethernet switch

22

GUID-AA005F1B-A30B-48F6-84F4-A108F58615A2 V1 EN

Figure 7: PRP solution

In case a laptop or a PC workstation is connected as a non-PRP node to one of the PRP networks, LAN A or LAN B, it is recommended to use a redundancy box device or an

Ethernet switch with similar functionality between the PRP network and SAN to remove additional PRP information from the Ethernet frames. In some cases, default

PC workstation adapters are not able to handle the maximum-length Ethernet frames with the PRP trailer.

There are different alternative ways to connect a laptop or a workstation as SAN to a

PRP network.

REM611

Application Manual

1MRS757457 E

Section 2

REM611 overview

• Via an external redundancy box (RedBox) or a switch capable of connecting to

PRP and normal networks

• By connecting the node directly to LAN A or LAN B as SAN

• By connecting the node to the protection relay's interlink port

HSR

HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs. For each frame sent, a node, DAN, sends two frames, one over each port. Both frames circulate in opposite directions over the ring and each node forwards the frames it receives, from one port to the other. When the originating node receives a frame sent to itself, it discards that to avoid loops; therefore, no ring protocol is needed. Individually attached nodes, SANs, such as laptops and printers, must be attached through a “redundancy box” that acts as a ring element. For example, a 615 or 620 series protection relay with HSR support can be used as a redundancy box.

Devices not supporting HSR

Ethernet switch

Redundancy box

Redundancy box

Redundancy box

X

X

IEC 61850 HSR

X

Unicast traffic

Message is recognized as a duplicat e and is immediately forwarded

Sending device removes the message from t he ri ng

2.7.3

REM611

Application Manual

GUID-B24F8609-0E74-4318-8168-A6E7FCD0B313 V1 EN

Figure 8: HSR solution

Secure communication

The protection relay supports secure communication for WHMI and file transfer protocol. If the Secure Communication parameter is activated, protocols require TLS based encryption method support from the clients. In this case WHMI must be connected from a Web browser using the HTTPS protocol and in case of file transfer the client must use FTPS.

As a factory default, Secure Communication is “ON”.

23

24

1MRS757457 E

Section 3

REM611 standardized configuration

Section 3 REM611 standardized configuration

3.1

REM611

Application Manual

Standardized configuration

REM611 is available in one configuration.

To increase the user-friendliness of the configuration and to emphasize the simplicity of usage of the relay, only the application-specific parameters need setting within the relay's intended area of application.

The standard signal configuration can be altered by local HMI, Web HMI or optional application functionality of Protection and Control IED Manager PCM600.

Table 9:

Description

Motor protection

Standardized configuration

Conf.

A

Table 10: Supported functions

Function

Protection

Three-phase non-directional overcurrent protection, low stage

Three-phase non-directional overcurrent protection, instantaneous stage

Non-directional earth-fault protection, low stage

Non-directional earth-fault protection, high stage

Negative-sequence overcurrent protection for machines

Loss of load supervision

Motor load jam protection

Motor start-up supervision

Phase reversal protection

Thermal overload protection for motors

Circuit breaker failure protection

Master trip

Control

Circuit-breaker control

Emergency start-up

Condition monitoring and supervision

Trip circuit supervision

Table continues on next page

IEC 61850

PHLPTOC

PHIPTOC

CBXCBR

ESMGAPC

TCSSCBR

EFLPTOC

EFHPTOC

MNSPTOC

LOFLPTUC

JAMPTOC

STTPMSU

PREVPTOC

MPTTR

CCBRBRF

TRPPTRC

A

1

1

1

1

1

1 1)

1 1)

2

1

1

1

1

1

1

2

25

Section 3

REM611 standardized configuration

3.2

3.2.1

26

1MRS757457 E

Function

Runtime counter for machines and devices

Logging

Disturbance recorder

Fault recorder

Measurement

Three-phase current measurement

IEC 61850

MDSOPT

RDRE

FLTRFRC

A

1

1

1

Sequence current measurement

Residual current measurement

Other

Input switch group

Output switch group

Selector

CMMXU

CSMSQI

RESCMMXU

ISWGAPC

OSWGAPC

SELGAPC

1

1

1

10

20

6

Minimum pulse timer (2 pcs)

Minimum pulse timer (2 pcs, second resolution)

TPGAPC

TPSGAPC

10

1

Move (8 pcs) MVGAPC 1

1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standardized configuration.

() = optional

1) Io selectable by parameter and default value is "Io measured"

Switch groups

The default application configurations cover the most common application cases, however, changes can be made according to specific needs through LHMI, WHMI and PCM600.

Programming is easily implemented with three switch group functions including input switch group ISWGAPC, output switch group OSWGAPC and selector switch group

SELGAPC. Each switch group has several instances.

Connections of binary inputs to functions, GOOSE signals to functions, functions to functions, functions to binary outputs and functions to LEDs have been preconnected through corresponding switch groups.

The real connection logic and the application configuration can be modified by changing the parameter values of the switch groups. It is also possible to modify the real connection logic and the application configuration through the matrix view in the signal configuration menu in the WHMI.

Input switch group ISWGAPC

The input switch group ISWGAPC has one input and a number of outputs. Every input and output has a read-only description. ISWGAPC is used for connecting the input

REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration signal to one or several outputs of the switch group. Each output can be set to be connected or not connected with the input separately via the “OUT_x connection” setting.

3.2.2

GUID-2D549B56-6CF7-4DCB-ACDE-E9EF601868A8 V1 EN

Figure 9: Input switch group ISWGAPC

Output switch group OSWGAPC

The output switch group OSWGAPC has a number of inputs and one output. Every input and output has a read-only description. OSWGAPC is used for connecting one or several inputs to the output of the switch group via OR logic. Each input can be set to be connected or not connected with the OR logic via the “IN_x connection” settings. The output of OR logic is routed to switch group output.

3.2.3

REM611

Application Manual

GUID-1EFA82D5-F9E7-4322-87C2-CDADD29823BD V1 EN

Figure 10: Output switch group OSWGAPC

Selector switch group SELGAPC

The selector switch group SELGAPC has a number of inputs and outputs. Every input and output has a read-only description. Each output can be set to be connected with one of the inputs via the OUT_x connection setting. An output can also be set to be not connected with any of the inputs. In SELGAPC, one output signal can only be connected to one input signal but the same input signal can be routed to several output signals.

27

Section 3

REM611 standardized configuration

1MRS757457 E

GUID-E3AEC7AB-2978-402D-8A80-C5DE9FED67DF V1 EN

Figure 11: Selector switch group SELGAPC

28 REM611

Application Manual

1MRS757457 E

3.3

L1

L2

L3

Connection diagrams

Section 3

REM611 standardized configuration

REM611

P1

P2

P1

S1

P2

S2

M

3~

S1

S2

X120

1

2

3

4

8

9

10

11

5

6

7

12

13

14

1/5A

N

1/5A

N

1/5A

N

1/5A

N

BI 1

BI 2

BI 3

BI 4

IL1

1)

IL2

IL3

Io

SO1

PO3

TCS1

PO4

TCS2

IRF

PO1

PO2

SO2

1) The IED features an automatic short-circuit

mechanism in the CT connector when plug-in

unit is detached

GUID-7AEBF2ED-BF20-4D85-A67A-9489E5EB7603 V1 EN

Figure 12: Connection diagram for configuration A when used with a circuitbreaker-controlled motor drive

+

U aux

-

X100

1

2

3

4

5

6

7

21

23

24

14

16

17

15

19

18

20

22

8

9

10

11

12

13

REM611

Application Manual

29

Section 3

REM611 standardized configuration

L1

L2

L3

3.4

3.4.1

30

1MRS757457 E

REM611

P1

P2

P1

S1

P2

S2

M

3~

S1

S2

X120

1

2

3

4

10

11

12

13

14

5

6

7

8

9

1/5A

N

1/5A

N

1/5A

N

1/5A

N

BI 1

BI 2

BI 3

IL2

IL3

Io

BI 4

IL1

1)

SO1

PO3

TCS1

PO4

TCS2

IRF

PO1

PO2

SO2

1) The IED features an automatic short-circuit

mechanism in the CT connector when plug-in

unit is detached

GUID-21265C90-98B5-45F2-9B83-AC93CBB8C44E V1 EN

Figure 13: Connection diagram for configuration A when used with a contactorcontrolled motor drive

The protection principles are mostly the same for circuit-breaker controlled and contactor controlled motor drives. Because the contactor is not able to break high currents, the relay must be set in such a way that the relay does not open the contactor at faults of high current magnitudes. Faults are cleared with fuses.

U

+

aux

X100

1

2

3

4

5

6

7

14

16

17

15

19

18

20

22

21

23

24

8

9

10

11

12

13

Configuration A

Applications

Configuration A for motor protection and control is mainly intended for the protection, control, measurement and supervision of asynchronous motors and the associated drives in manufacturing and process industry.

The protection relay with a standardized configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the protection relay enables this configuration

REM611

Application Manual

1MRS757457 E

3.4.2

3I

Io

Section 3

REM611 standardized configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.

Functions

REM611 MOTOR PROTECTION RELAY

PROTECTION

Master Trip

Lockout relay

94/86

3I<

37

I2>M

46M

I2>>

46R

Is2t n<

49, 66, 48, 51LR

3Ith>M

49M

3I>>>

50P/51P

3I>/Io>BF

51BF/51NBF

Ist>

51LR

3I>

51P-1

Io>

51N-1

Io>>

51N-2

M

GUID-5E2D4B1E-9287-4833-BB0A-BB310A16E2CD V2 EN

Figure 14: Functionality overview for configuration A

LOCAL HMI

I

ESC

O

Control

Events

Measurements

Disturbance records

A

R

L

STANDARD

CONFIGURATION

A

ALSO AVAILABLE

- Disturbance and fault recorders

- Event log and recorded data

- Local/Remote push button on LHMI

- Self-supervision

- Time synchronization: IEEE 1588 v2,

SNTP, IRIG-B

- User management

- Web-HMI

CONDITION MONITORING

AND SUPERVISION

OPTS

OPTM

TCS

TCM

CONTROL AND INDICATION 1)

Object

CB

Ctrl 2)

1

Ind 3)

-

DC -

ES -

1) Check availability of binary inputs/outputs

from technical documentation

2) Control and indication function for

primary object

3) Status indication function for

primary object

ESTART

ESTART

COMMUNICATION

Protocols:

IEC 61850-8-1

Modbus®

Interfaces:

Ethernet: TX (RJ-45), FX (LC)

Serial: RS-485

Redundant protocols:

HSR

PRP

RSTP

MEASUREMENT

- I, Io

- Limit value supervision

- Symmetrical components

Analog interface types

Current transformer

Voltage transformer

1)

Conventional transformer inputs

REMARKS

Optional function

3× No. of instances

Io/Uo

Calculated value

OR Alternative function to be defined when ordering

1)

4

-

REM611

Application Manual

31

Section 3

REM611 standardized configuration

3.4.2.1

3.4.2.2

1MRS757457 E

Default I/O connections

Table 11:

Binary input

X120-BI1

X120-BI2

X120-BI3

X120-BI4

Default connections for binary inputs

Description

Emergency start

Circuit breaker closed position indication

Circuit breaker open position indication

External restart inhibit

Table 12:

Binary input

X100-PO1

X100-PO2

X100-SO1

X100-SO2

X100-PO3

X100-PO4

Default connections for binary outputs

Description

Restart enable

Breaker failure backup trip to upstream breaker

General start indication

General operate indication

Open circuit breaker

Close circuit breaker

3

4

5

6

7

8

Table 13:

LED

1

2

Default connections for LEDs

Description

Short circuit protection operate

Combined operate indication of the other protection functions

Thermal overload protection operate

Motor restart inhibit

Emergency start enabled

Disturbance recorder triggered

TCS or runtime counter alarm

Circuit-breaker failure operate

Predefined disturbance recorder connections

Table 14:

Channel

1

2

3

4

Predefined analog channel setup

Description

IL1

IL2

IL3

Io

Connector pins

X120:1-2

X120:3,2

X120:4,2

X120:5-6

Connector pins

X100:6-7

X100:8-9

X100:10-11,(12)

X100:13-14

X100:15,19

X100:20,24

32 REM611

Application Manual

1MRS757457 E

3.4.3

3.4.3.1

Section 3

REM611 standardized configuration

Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.

Functional diagrams

The functional diagrams describe the default input, output, programmable LED, switch group and function-to-function connections. The default connections can be viewed and changed with switch groups in PCM600, LHMI and WHMI according to the application requirements.

The analog channels have fixed connections towards the different function blocks inside the protection relay’s configuration. Exceptions from this rule are the seven analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents. The signal marked with Io represents the measured residual current via a core balance current transformer.

Functional diagrams for protection

The functional diagrams describe the protection relay’s protection functionality in detail and picture the factory default connections.

REM611

Application Manual

33

Section 3

REM611 standardized configuration

1MRS757457 E

OVERCURRENT PROTECTION

PHLPTOC1

3I>(1)

3I

BLOCK

51P-1(1)

OPERATE

START

ENA_MULT

OSWGAPC9

IN_1 OUT

SELGAPC4

IN_11 OUT_2

PHIPTOC1

3I>>>(1)

3I

BLOCK

50P/51P(1)

OPERATE

START

ENA_MULT

OSWGAPC8

IN_2 OUT

SELGAPC4

IN_10 OUT_1

STTPMSU1_MOT_STARTUP

MOTOR JAM PROTECTION

JAMPTOC1

I st

>(1)

3I

BLOCK

51LR(1)

OPERATE

START

OSWGAPC9

IN_9 OUT

SELGAPC4

IN_11 OUT_2

LED 2

LED 1

LED 2

GUID-2D4262CD-1143-45C7-AFA7-08386DA760C6 V1 EN

Figure 15: Overcurrent protection

Two overcurrent stages are offered for overcurrent and short-circuit protection. The motor jam protection function JAMPTOC1 is blocked by the motor startup protection function. PHLPTOC1 can be used for overcurrent protection and PHIPTOC1 for the short-circuit protection. The operation of PHIPTOC1 is not blocked by default by any functionality. PHIPTOC1 should be set over the motor start current level to avoid unnecessary operation.

All operate signals are connected to Master Trip. Short-circuit protection PHIPTOC1 operate signal is connected to the alarm LED 1, low stage overcurrent protection

PHLPTOC1 and motor jam protection JAMPTOC1 operate signals are connected to the alarm LED 2.

34 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

EARTH-FAULT PROTECTION

EFLPTOC1

Io>(1)

51N-1(1)

Io

BLOCK

ENA_MULT

OPERATE

START

IN_3

OSWGAPC9

OR

OUT

IN_4

SELGAPC4

IN_11 OUT_2

LED 2

EFHPTOC1

Io>>(1)

51N-2(1)

Io

BLOCK

ENA_MULT

OPERATE

START

GUID-4A25DE53-3F12-407B-9AFC-C8BB252AD350 V1 EN

Figure 16: Earth-fault protection

Two non-directional earth-fault stages EFLPTOC1 and EFHPTOC1 are offered to detect phase-to-earth faults that may be a result of, for example, insulation ageing.

The operate signals of the earth-fault protections are connected to Master Trip and also to alarm LED 2.

REM611

Application Manual

35

Section 3

REM611 standardized configuration

36

1MRS757457 E

X120-BI1

Emergency Start Enable

SELGAPC1

IN_1 OUT_1

EMERGENCY START AND RESTART INHIBIT

ESMGAPC1

ESTART(1)

3I

BLOCK

ST_EMERG_ENA

ST_EMERG_RQ

OSWGAPC12

IN_6 OUT

SELGAPC4

IN_14 OUT_5

MPTTR1

3Ith>M(1)

49M(1)

3I

BLOCK OPERATE

START_EMERG

AMB_TEMB

ALARM

BLK_RESTART

OSWGAPC10

IN_12 OUT

SELGAPC4

IN_12 OUT_3

LED 5

LED 3

TRPTTR1_TRIP

CBXCBR1_EXE_OP

OR IN1

IN2

TPSGAPC1

OUT1

OUT2

X120-BI4

External Restart Inhabit

IN_4

SELGAPC1

OUT_4

STTPMSU1_LOCK_START

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

OR

OR

OSWGAPC11

IN_9 OUT

SELGAPC4

IN_13 OUT_4

LED 4

Restart Inhabit

GUID-FD95A972-9F46-4374-98F8-EDDB1879CFB2 V1 EN

Figure 17: Emergency start and restart inhibit

The emergency start function ESMGAPC1 allows motor start-ups although the restart inhibit is activated. The emergency start is enabled for ten minutes after the selected binary input (X120:BI1) is energized. On the rising edge of the emergency start signal the following takes place.

• Calculated thermal level is set slightly below the restart inhibit level to allow at least one motor startup.

• Value of the cumulative start-up time counter STTPMSU1 is set slightly below the set restart inhibit value to allow at least one motor startup.

• Set operate values of the temperature stages in MPTTR1 function is increased by

10 percent.

• External restart inhibit signal (X100:PO1) is ignored.

• Alarm LED 5 is activated.

The external restart inhibit signal is ignored for as long as the emergency start is activated. A new emergency start cannot be made until the emergency start signal has been reset and the emergency start time of 10 minutes has expired.

The thermal overload protection function MPTTR1 detects short- and long term overloads under varying load conditions. When the emergency start request is issued for the emergency start function, it activates the corresponding input of the thermal overload function. When the thermal overload function has issued a restart blocking, which inhibits the closing of the circuit breaker when the machine is overloaded, the emergency start request removes this blocking and enables the restarting of the motor.

REM611

Application Manual

1MRS757457 E

REM611

Application Manual

Section 3

REM611 standardized configuration

The operate signal of thermal overload protection function MPTTR1 is connected to

Master Trip and to alarm LED 3.

The restart inhibit is activated for a set period when a circuit breaker is opened. This is called remanence voltage protection where the motor has damping remanence voltage after circuit breaker opening. Reclosing after a too short period of time can lead to stress for the machine and other apparatuses. The remanence voltage protection waiting time can be set to a timer function TPSGAPC1.

The restart inhibit is also activated when one of the following conditions is met.

• An active trip command or

• Motor startup supervision has issued lockout or

• Motor unbalance function has issued restart blocking or

• An external restart inhibit is activated by a binary input (X120:BI4).

LED 4 is the alarm indication of restart inhibit.

X120-BI2

CB Closed Position

SELGAPC1

IN_2 OUT_2

ESMGAPC_ST_EMERG_ENA

MOTOR START AND RUNTIME COUNTER

STTPMSU1

I

S

2t n<(1)

BLOCK

BLK_LK_ST

CB_CLOSED

STALL_IND

OPR_IIT

OPR_STALL

MOT_START

ST_EMERG_ENA LOCK_START

IN_10

IN_11

OSWGAPC9

OR

OUT

SELGAPC4

IN_11 OUT_2

MDSOPT1

OPTS(1)

OPTM(1)

BLOCK

POS_ACTIVE

ALARM

WARNING

OSWGAPC14

IN_5 OUT

SELGAPC4

IN_16 OUT_7

LED 2

LED 7

GUID-CA463B2F-038E-4287-A5F2-A903BDF1300B V1 EN

Figure 18: Motor startup supervision

With the motor startup supervision function STTPMSU1 the starting of the motor is supervised by monitoring three-phase currents or the status of the energizing circuit breaker of the motor.

When the emergency start request is activated by ESMCAPC1 and STTPMSU1 is in lockout state, which inhibits motor starting, the lockout is deactivated and emergency starting is available.

The operate signals (OPR_IIT and OPR_STALL) of the motor start-up supervision function STTPMSU1 are connected to Master Trip and to alarm LED 2.

The motor running time counter MDSOPT1 provides history data since the latest commissioning. The counter counts the total number of motor running hours and is

37

Section 3

REM611 standardized configuration

1MRS757457 E incremented when the energizing circuit breaker is closed. The alarm of the runtime counter is connected to alarm LED 7.

UNBALANCE PROTECTION

MNSPTOC1

I

2

>M(1)

46M(1)

3I

BLOCK_OPR

OPERATE

ALARM

BLK_RESTART

MNSPTOC2

I

2

>M(2)

46M(2)

3I

BLOCK_OPR

OPERATE

ALARM

BLK_RESTART

LOSS OF LOAD PROTECTION

LOFLPTUC1

3I<(1)

37(1)

3I

BLOCK

OPERATE

START

PHASE REVERSAL PROTECTION

PREVPTOC1

I

2

>>(1)

46R(1)

3I

BLOCK

OPERATE

START

IN_5

OSWGAPC9

IN_6

IN_7

IN_8

OR

OUT

SELGAPC4

IN_11 OUT_2

LED 2

GUID-6E213083-656E-4188-816E-8CBB1703DF44 V1 EN

Figure 19: Unbalance, loss of load and phase reversal protection

Two negative-sequence overcurrent stages MNSPTOC1 and MNSPTOC2 are offered for phase unbalance protection. These functions are used to protect the motor against phase unbalance caused by, for example, a broken conductor. Phase unbalance in network feeding of the motor causes overheating of the motor.

The loss of load situation is detected by LOFLPTUC. The loss of load situation can happen, for example, if there is damaged pump or a broken conveyor.

38 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

The phase reversal protection PREVPTOC1 is based on the calculated negative phase-sequence current. It detects too high NPS current values during motor start-up, caused by incorrectly connected phases, which in turn causes the motor to rotate in the opposite direction.

All operate signals above are connected to Master Trip and to the alarm LED 2.

CIRCUIT BREAKER FAILURE PROTECTION

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

OR

CCBRBRF1

3I>/Io>BF(1)

51BF/51NBF(1)

3I

Io

START

POSCLOSE

CB_FAULT

BLOCK

CB_FAULT_AL

TRBU

TRRET

SELGAPC3

IN_4 OUT_2

OSWGAPC15

IN_7 OUT

X100 PO2

SELGAPC4

IN_17 OUT_8

LED 8

SELGAPC1

IN_2 OUT_2

X120-BI2

CB Closed Position

GUID-2A807DD6-2138-4B0F-A622-BB7DE2B4C253 V1 EN

Figure 20: Circuit breaker failure protection

The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a number of different protection stages in the protection relay. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU . The TRRET operate output is used for retripping its own circuit breaker through the Master Trip 1. The

TRBU output is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU operate output signal is connected to the output PO2 (X100:

8-9). LED 8 is used for backup ( TRBU ) operate indication.

REM611

Application Manual

39

Section 3

REM611 standardized configuration

3.4.3.2

40

1MRS757457 E

Functional diagrams for disturbance recorder and supervision functionsrecorder

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

OR

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

OR

OR

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

SELGAPC1_ Emeragency Start Enable

SELGAPC1_ CB Closed Position

SELGAPC1_ CB Open Position

SELGAPC1_External Restart Inhibit

MPTTR1_ALARM

MPTTR1_BLK_RESTART

STTPMSU1_MOT_START

STTPMSU1_LOCK_START

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

CCBRBRF1_TRRET

CCBRBRF1_TRBU

ESMGAPC1_ST_EMERG_ENA

MDSOPT1_ALARM

SELGAPC1_External Trip

SG_1_ACT

SG_2_ACT

SG_3_ACT

SG_4_ACT

SG_5_ACT

SG_6_ACT

DISTURBANCE RECORDER

C17

C18

C19

C20

C21

C22

C23

C24

C7

C8

C9

C10

C11

C12

C13

C14

C15

C16

C25

C26

C27

C28

C29

C30

C31

C32

C33

C1

C2

C3

C4

C5

C6

C34

C35

C36

C37

C38

RDRE1

TRIGGERED

OSWGAPC13

IN_2

OUT

SELGAPC4

IN_15 OUT_6

LED 6

GUID-889C71B7-80CD-4AAD-8768-1FF326ECD0BC V1 EN

Figure 21: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. The active setting group is also to be recorded via

SG_1_ACT to SG_6_ACT . The disturbance recorder triggered signal indication is connected to LED 6.

Table 15:

Channel number

Binary channel 1

Disturbance recorder binary channel default value

Channel id text

PHLPTOC1_START

Binary channel 2

Binary channel 3

Binary channel 4

Binary channel 5

Binary channel 6

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

Binary channel 7

Binary channel 8

Binary channel 9

LOFLPTUC1_START

PREVPTOC1_START

PHLxPTOC1_OPERATE

Binary channel 10

Binary channel 11

Table continues on next page

EFxPTOC1_OPERATE

MNSPTOC_OPERATE

Level trigger mode

1=positive or rising

1=positive or rising

1=positive or rising

1=positive or rising

1=positive or rising

1=positive or rising

1=positive or rising

1=positive or rising

4=level trigger off

4=level trigger off

4=level trigger off

REM611

Application Manual

1MRS757457 E

REM611

Application Manual

Channel number

Binary channel 12

Binary channel 13

Binary channel 14

Binary channel 15

Binary channel 16

Binary channel 17

Binary channel 18

Binary channel 19

Binary channel 20

Binary channel 21

Binary channel 22

Binary channel 23

Binary channel 24

Binary channel 25

Binary channel 26

Binary channel 27

Binary channel 28

Binary channel 29

Binary channel 30

Binary channel 31

Binary channel 32

Binary channel 33

Binary channel 34

Binary channel 35

Binary channel 36

Binary channel 37

Binary channel 38

Section 3

REM611 standardized configuration

Channel id text

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPOTC1_OPERATE

STTPMSU1_OPR_IIT

STPPMSU1_OPR_STALL

MPTTR1_OPERATE

SELGAPC1_Emeragecy Start Enable

SELGAPC1_CB_Closed

SELGAPC1_CB_Open

SELGAPC1_External Restart Inhibit

MPTTR1_ALARM

MPTTR1_BLK_RESTART

STTPMSU1_MOT_START

STTPMSU1_LOCK_START

MNSPTOC1_BLK_RESTART

MNSPTOC2_BLK_RESTART

CCBRBRF1_TRRET

CCBRBRF1_TRBU

ESMGAPC1_ST_EMERG_ENA

MDSOPT1_ALARM

SELGAPC1_External Trip

SG_1_ACT

SG_2_ACT

SG_3_ACT

SG_4_ACT

SG_5_ACT

SG_6_ACT

Level trigger mode

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

1=positive or rising

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

1=positive or rising

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

4=level trigger off

TRIP CIRCUIT SUPERVISION

X120-BI3

CB Open Position

SELGAPC1

IN_3 OUT_3

TRPPTRC1_TRIP

X120-BI2

CB Closed Position

SELGAPC1

IN_2 OUT_2

OR

IN_1

SELGAPC2

OUT_1

IN_2 OUT_2

BLOCK

TCSSCBR1

ALARM

BLOCK

TCSSCBR2

ALARM

IN_3

IN_4

OSWGAPC14

OR

OUT

SELGAPC4

IN_16 OUT_7

LED 7

GUID-B8A3C114-7F36-4BE7-BD1E-686CD026514F V1 EN

Figure 22: Supervision functions

41

Section 3

REM611 standardized configuration

3.4.3.3

1MRS757457 E

By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with the circuit breaker normally open/closed auxiliary contact.

Functional diagrams for control and interlocking

MASTER TRIP #1

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPETATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERTAE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

CCBRBRF1_TRRET

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_13

OSWGAPC1

OR

OUT

SELGAPC1_External Trip

GOOSERCV_BIN 2_OUT

OR

GOOSERCV_BIN 3_OUT

SELGAPC1_RST_LKOUT

CBXCBR1_EXE_OP

IN1

IN2

MVGAPC1

Q1

Q2

OR

TRPPTRC1

BLOCK TRIP

OPERATE CL_LKOUT

RST_LKOUT

OR

IN_1

SELGAPC3

OUT_5

X100 PO3

GUID-474301B2-7F20-4968-8937-19F360077C7E V2 EN

Figure 23: Master trip

The operate signals from the protections and an external trip are connected to the trip output contact PO3 (X100:15-19) via the corresponding Master Trip (TRPPTRC1).

Open control commands to the circuit breaker from the local or remote

CBXCBR1_EXE_OP are connected directly to the output PO3 (X100:15-19).

TRPPTRC1 provides the lockout/latching function, event generation and the trip signal duration setting. One binary input through SELGAPC1 can be connected to the

RST_LKOUT input of Master Trip. If the lockout operation mode is selected, it is used to enable external reset.

42 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

CIRCUIT BREAKER CONTROL

X120-BI2

CB Closed Position

X120-BI3

CB Open Posit ion

Always True

IN_2

SELGAPC1

OUT_2

IN_3

IN_5

OUT_3

OUT_7

TRPPTRC1_TRIP

Restart Inhibit

AND

CBXCBR1

PO SOPEN

POSCLOSE

ENA_OPEN

ENA_CLOSE

BLK_OPEN

BLK_CLOSE

AU_OPEN

AU_CLOSE

TRIP

SYNC_OK

SYNC_ITL_BYP

SELECTED

EXE_OP

EXE_CL

OP_REQ

CL_REQ

OPENPOS

CLOSEPOS

OKPOS

OPEN_ENAD

CLOSE_ENAD

CBXCBR1_EXE_OP

SELGAPC3

IN_3 OUT_6

SELGAPC3

IN_2 OUT_1

X100 PO4

X100 PO1

GUID-009E5CDF-D8FF-4B3C-9253-4B2F20B010B6 V2 EN

Figure 24: Circuit breaker control

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the master trip logics. An always true signal is also connected to ENA_CLOSE via SELGAPC1 by default. The open operation is always enabled.

When the motor restart is inhibited, the BLK_CLOSE input is activated and closing of the circuit breaker is not possible. When all conditions of the circuit breaker closing are fulfilled, the CLOSE_ENAD output of the CBXCBR1 is activated and PO1 output

(X100:6-7) is closed.

REM611

Application Manual

43

Section 3

REM611 standardized configuration

3.4.4

1MRS757457 E

COMMON ALARM INDICATION 1 & 2

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

OSWGAPC3

OR OUT

IN1

TPGAPC1

OUT1

SELGAPC3

IN_5 OUT_3

IN_9 OUT_4

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

OSWGAPC7

OR OUT

IN1

TPGAPC3

OUT1

X100 SO1

X100 SO2

GUID-0B2EDC5B-7CC1-4DDC-A831-F16DB266E4FC V1 EN

Figure 25: Common alarm indication

The signal outputs from the protection relay are connected to give dedicated information.

• Start of any protection function SO1 (X100:10-12)

• Operation (trip) of any protection function SO2 (X100: 13-15)

TPGAPC functions are timers and used for setting the minimum pulse length for the outputs. There are seven generic timers TPGAPC1...7 available in the protection relay.

Switch groups

In configuration A, the switch group function blocks are organized in four groups: binary inputs, internal signal, GOOSE as well as binary outputs and LEDs.

44 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

Binary Inputs

(1...4)

Received GOOSE

(0...19)

GOOSE

GOOSE

GOOSE

SELGAPC1

Binary Inputs

Binary Inputs

GOOSE

ISWGAPC9

GOOSE Blocking

ISWGAPC10

GOOSE Block CB

ISWGAPC2

ISWGAPC1

Blocking

Protection and Control

PHLPTOC1 PHIPTOC1

EFLPTOC1

MNSPTOC1

EFHPTOC1

MNSPTOC2

LOFLPTUC1

JAMPTOC1

PREVPTOC1

STTPMSU1

MPTTR1

CCBRBRF1

CBXCBR1

ESMGAPC1

MDSOPT1

TCSSCBR1

TCSSCBR2

Internal Signal

SELGAPC2

TCS Blocking

GUID-B073CD8D-C5A4-4C29-95D4-2BF60D981594 V1 EN

Figure 26: Configuration A switch group overview

3.4.4.1

Binary Outputs and LEDs

OSWGAPC2

OSWGAPC1

SELGAPC3

Master trip

SELGAPC4

OSWGAPC6

OSWGAPC5

OSWGAPC4

OSWGAPC3

Start

OSWGAPC10

OSWGAPC9

OSWGAPC8

OSWGAPC7

Trip

OSWGAPC16

OSWGAPC15

OSWGAPC14

OSWGAPC13

OSWGAPC12

OSWGAPC11

Alarm

Binary Outputs

LEDs

Binary Outputs

(1...6)

LEDs

(1…8)

Binary inputs

The binary inputs group includes one SELGAPC and two ISWGAPCs. SELGAPC1 is used to route binary inputs to ISWGAPC or directly to protection relay functions.

ISWGAPC1 and ISWGAPC2 are used to configure the signal to block the protection functions.

X120-BI1

X120-BI2

X120-BI3

X120-BI4

SELGAPC1

Blocking 1

ISWGAPC1

Blocking 2 ISWGAPC2

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFHPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFHPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

GUID-DB4D9782-7195-40BA-A357-C296DCB26810 V1 EN

Figure 27: Binary inputs

REM611

Application Manual

45

Section 3

REM611 standardized configuration

1MRS757457 E

SELGAPC1

SELGAPC1 has inputs from protection relay binary inputs. IN_1 ...

IN_4 are binary inputs from X100. An always true signal is connected to IN_5 . SELGAPC1 outputs are used to route inputs to different functions. By setting SELGAPC1, binary inputs can be configured for different purposes.

X120-BI1

X120-BI2

X120-BI3

X120-BI4

Always True

X120/1-2 BI1

IN_1

X120/3-2 BI2

IN_2

X120/4-2 BI3

IN_3

X120/5-6 BI4 IN_4

IN_5

SELGAPC1

OUT_1

Emergency

Start Enable

OUT_2

CB Closed Position

OUT_3

OUT_4

CB Open Position

External

Restart Inhabit

ESMGAPC1_ST_EMERG_RQ

CCBRBRF1_POSCLOSE

CBXCBR1_POSCLOSE

STTPMSU1_CB_CLOSED

MDSOPT1_POS_ACTIVE

SELGAPC2_IN_2

CBXCBR1_POSOPEN

SELGAPC2_IN_1

OSWGAPC1_IN_9

OUT_5

Blocking 1

ISWGAPC1_IN

OUT_6 STTPMSU1_STALL_IND

OUT_7

OUT_8

CB Close Enable

TRPTTRC1_

RST_LKOUT

OUT_9

External Trip

OUT_10

Setting Group 2

OUT_11

Setting Group 3

OUT_12

Setting Group 4

OUT_13

Blocking 2

CBXCBR1_ENA_CLOSE

TRPTTRC1_RST_LKOUT

TRPTTRC1_OPERATE

PROTECTION_BI_SG_2

PROTECTION_BI_SG_3

PROTECTION_BI_SG_4

ISWGAPC2_IN

GUID-258C736E-87B1-4824-877D-028149F2C734 V1 EN

Figure 28: SELGAPC1

ISWGAPC1

ISWGAPC1 is used to select which protection functions are to be blocked by changing

ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output

OUT_5 Blocking 1 . ISWGAPC1 outputs are connected to the BLOCK inputs of the protection functions.

46 REM611

Application Manual

1MRS757457 E

3.4.4.2

REM611

Application Manual

Section 3

REM611 standardized configuration

SELGAPC1_OUT_5

Blocking 1

IN

ISWGAPC1

OUT_1

OUT_2

OUT_3

OUT_4

OUT_5

OUT_6

OUT_7

OUT_8

OUT_9

OUT_10

OUT_11

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

GUID-6E734529-073D-4F12-B419-795329059725 V1 EN

Figure 29: ISWGAPC1

ISWGAPC2

ISWGAPC2 is used to select which protection functions are to be blocked by changing

ISWGAPC2 parameters. ISWGAPC2 input is routed from SELGAPC1 output

OUT_13 Blocking 2 . ISWGAPC2 outputs are connected to the BLOCK inputs of the protection functions.

SELGAPC1_OUT_13

Blocking 2

IN

ISWGAPC2

OUT_1

OUT_2

OUT_3

OUT_4

OUT_5

OUT_6

OUT_7

OUT_8

OUT_9

OUT_10

OUT_11

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

GUID-F0B3B75C-1393-4BBC-8B59-D0AF0A01CC28 V1 EN

Figure 30: ISWGAPC2

Internal signal

The internal signal group is used to configure the logic connections between function blocks. There is one SELGAPC in this group.

47

Section 3

REM611 standardized configuration

3.4.4.3

1MRS757457 E

SELGAPC2 is used to configure trip circuit supervision blocking from circuit breaker open or close position.

SELGAPC1_OUT_2

SELGAPC1_OUT_3

CB Open Position

CB Closed Position

GUID-14FFE748-CC11-4B9C-8646-3CE37598F108 V1 EN

Figure 31: Internal signal

SELGAPC2

TCSSCBR1_BLOCK

TCSSCBR2_BLOCK

SELGAPC2

SELGAPC2 inputs are circuit breaker closed and open positions from SELGACP1.

SELGAPC2 outputs are routed to the BLOCK input of the trip circuit supervision

TCSSCBR1 and TCSSCBR2.

By default, X100 PO3 is used for the open circuit breaker, X100-PO4 is used for the closing circuit breaker. TCSSCBR1 is blocked by the circuit breaker open position,

TCSSCBR2 is blocked by the circuit breaker closed position. If X100-PO3 is used for closing the circuit breaker, TCSSCBR1 needs to be blocked by the circuit breaker close position (OUT_1 connection=IN_2). If X100-PO4 is used for the open circuit breaker, TCSSCBR2 needs to be blocked by the circuit breaker open position (OUT_2 connection=IN_1).

SELGAPC1_OUT_2

SELGAPC1_OUT_3

CB Open Position

IN_1

CB Closed Position

IN_2

SELGAPC2

OUT_1

OUT_2

GUID-E3CF0FAF-958C-45FF-B2AA-5EA151CB83D9 V1 EN

Figure 32: SELGAPC2

TCSSCBR1_BLOCK

TCSSCBR2_BLOCK

Binary outputs and LEDs

In standard configuration A, the signals route to binary outputs, and LEDs are configured by OSWGAPCs. There are totally 15 OSWGAPC instances. They can be categorized to four groups, including one Master trip, four start, four trip and six alarm signals. The OSWGAPC outputs are connected to binary outputs and LEDs via

SELGAPC3 and SELGAPC4.

• SELGAPC3 is used to configure the OSWGAPC signals to the protection relay binary outputs. SELGAPC4 is used to configure the OSWGAPC signals to

LEDs.

• OSWGAPC1 is used for Master trip. The inputs are routed from the protection functions operate and circuit-breaker failures re-trip.

• OSWGAPC2 is not used.

48 REM611

Application Manual

1MRS757457 E

REM611

Application Manual

Section 3

REM611 standardized configuration

• OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are start signals from the protection functions.

• OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs are operation signals from the protection functions.

• OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs are alarm signals from the protection and monitoring functions.

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

CCBRBRF1_TRRET

OSWGAPC1

Master Trip 1

TRPPTRC1

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

OSWGAPC3

OSWGAPC4

OSWGAPC5

OSWGAPC6

Start 1

IN1

TPGAPC1

OUT1

Start 2 IN2 OUT2

Start 3

IN1

TPGAPC2

OUT1

Start 4 IN2 OUT2

OSWGAPC7

OSWGAPC8

OSWGAPC9

OSWGAPC10

Trip 1

IN1

TPGAPC3

OUT1

Trip 2

Trip 3

IN2 OUT2

IN1

TPGAPC4

OUT1

Trip 4

IN2 OUT2

OSWGAPC11

MPTTR1_ALARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

OSWGAPC12

OSWGAPC13

OSWGAPC14

OSWGAPC15

OSWGAPC16

GUID-B88C7F08-15E7-49D6-81B5-77D601043F49 V1 EN

Figure 33: Binary outputs

Alarm 1

IN1

TPGAPC5

OUT1

Alarm 2

IN2

Alarm 3

OUT2

IN1

TPGAPC6

OUT1

Alarm 4

IN2

Alarm 5

OUT2

IN1

TPGAPC7

Alarm 6

IN2 OUT2

SELGAPC3

X100 PO1

X100 PO2

X100 SO1

X100 SO2

X100 PO3

X100 PO4

49

Section 3

REM611 standardized configuration

50

1MRS757457 E

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

CCBRBRF1_TRRET

OSWGAPC1

Master Trip 1

TRPPTRC1

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

OSWGAPC3 Start 1

OSWGAPC4 Start 2

OSWGAPC5 Start 3

OSWGAPC6 Start 4

OSWGAPC7 Trip 1

OSWGAPC8 Trip 2

OSWGAPC9 Trip 3

OSWGAPC10 Trip 4

SELGAPC4

MPTTR1_ALARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

OSWGAPC11

Alarm 1

OSWGAPC12

Alarm 2

OSWGAPC13

Alarm 3

OSWGAPC14

Alarm 4

OSWGAPC15

Alarm 5

OSWGAPC16

Alarm 6

GUID-4E0F7B4E-1505-454B-B888-E342110B9C21 V1 EN

Figure 34: LEDs

SELGAPC3

SELGAPC3 is used to configure the OSWGAPC outputs to the protection relay binary outputs. The master trip signals are connected to SELGAPC3 via TRPPTRC.

Start, trip and alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are timers and used for setting the minimum pulse length for the outputs

SELGAPC3 outputs are connected with X100 binary outputs.

REM611

Application Manual

LED1

LED2

LED3

LED4

LED5

LED6

LED7

LED8

1MRS757457 E

Section 3

REM611 standardized configuration

CBXCBR_EXE_OP

TRPPTRC1_TRIP

CBXCBR_CLOSE_ENA

CBXCBR_EXE_CL

CCBRBRF1_TRBU

OSWGAPC3_OUT

OSWGAPC4_OUT

OSWGAPC5_OUT

OSWGAPC6_OUT

OSWGAPC7_OUT

OSWGAPC8_OUT

OSWGAPC9_OUT

OSWGAPC10_OUT

OSWGAPC11_OUT

OSWGAPC12_OUT

OSWGAPC13_OUT

OSWGAPC14_OUT

OSWGAPC15_OUT

OSWGAPC16_OUT

CB Open

IN_1

SELGAPC3

OUT_1

IN_2

CB Close

IN_3

Backup Trip

IN_4

IN1 OUT1

TPGAPC1

IN2 OUT2

Start 1

Start 2

IN1 OUT1

TPGAPC2

IN2 OUT2

Start 3

Start 4

IN1 OUT1

TPGAPC3

IN2 OUT2

Trip 1

Trip 2

IN1 OUT1

TPGAPC4

IN2 OUT2

Trip 3

Trip 4

IN1 OUT1

TPGAPC5

IN2 OUT2

Alarm 1

Alarm 2

IN1 OUT1

TPGAPC6

IN2 OUT2

Alarm 3

Alarm 4

IN1 OUT1

TPGAPC7

IN2 OUT2

Alarm 5

Alarm 6

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_13

IN_14

IN_15

IN_16

IN_17

IN_18

OUT_2

OUT_3

OUT_4

OUT_5

OUT_6

X100 PO1

X100 PO2

X100 SO1

X100 SO2

X100 PO3

X100 PO4

GUID-87B71BC7-0429-4924-8CE1-E2D826D35313 V1 EN

Figure 35: SELGAPC3

SELGAPC4

SELGAPC4 is used to configure the OSWGAPC outputs to LEDs. Master trip signals are connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signals are connected to SELGAPC4 directly. SELGAPC4 outputs are connected to programmable LED1 to LED8.

REM611

Application Manual

51

Section 3

REM611 standardized configuration

1MRS757457 E

CBXCBR_EXE_OP

TRPPTRC1_TRIP

CBXCBR_CLOSE_ENA

CBXCBR_EXE_CL

CCBRBRF1_TRBU

OSWGAPC3_OUT

OSWGAPC4_OUT

OSWGAPC5_OUT

OSWGAPC6_OUT

OSWGAPC7_OUT

OSWGAPC8_OUT

OSWGAPC9_OUT

OSWGAPC10_OUT

OSWGAPC11_OUT

OSWGAPC12_OUT

OSWGAPC13_OUT

OSWGAPC14_OUT

OSWGAPC15_OUT

OSWGAPC16_OUT

CB Open

IN_1

SELGAPC4

Start 1

IN_2

CB Close

IN_3

Backup Trip

IN_4

IN_5

Start 2

IN_6

Start 3

IN_7

Start 4

IN_8

Trip 1

IN_9

Trip 2

IN_10

Trip 3

IN_11

Trip 4

Alarm 2

IN_12

Alarm 1

IN_13

IN_14

Alarm 3

IN_15

Alarm 4

IN_16

Alarm 5

IN_17

Alarm 6

IN_18

OUT_1

OUT_2

OUT_3

OUT_4

OUT_5

OUT_6

OUT_7

OUT_8

LED1

LED2

LED3

LED4

LED5

LED6

LED7

LED8

GUID-C244E62D-8C47-4071-AC47-6EFE47CB4CCE V1 EN

Figure 36: SELGAPC4

Master trip OSWGAPCs

OSWGAPC1 is used to route the protection function operate signals to Master trip.

OSWGAPC1 have the same inputs from the protection function operates. The output is connected to the TRPPTRC function.

52 REM611

Application Manual

1MRS757457 E

REM611

Application Manual

Section 3

REM611 standardized configuration

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

CCBRBRF1_TRRET

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_13

IN_1

IN_2

IN_3

IN_4

OSWGAPC1

OUT

Master trip 1

TRPPTRC 1_OPERATE

GUID-4D055596-58DD-4785-9A32-3356CE4C325D V1 EN

Figure 37: OSWGAPC1

Start OSWGAPCs

OSWGAPC instances 3...6 are used to configure the protection start signals. These four OSWGAPCs have the same inputs from the protection function start signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly.

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

OSWGAPC3

OUT

Start 1 TPGAPC1_IN1

SELGAPC4_IN_5

GUID-A31C0C14-4E97-42CE-A258-9F67303CA97A V1 EN

Figure 38: OSWGAPC3

53

Section 3

REM611 standardized configuration

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

OSWGAPC4

OUT

Start 2 TPGAPC1_IN2

SELGAPC4_IN_6

GUID-BF6A707E-0820-44BC-A654-377F5266CF7D V1 EN

Figure 39: OSWGAPC4

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

OSWGAPC5

OUT

Start 3 TPGAPC2_IN1

SELGAPC4_IN_7

GUID-EF6B516A-ABA9-4604-852C-29F071EA90E6 V1 EN

Figure 40: OSWGAPC5

1MRS757457 E

54 REM611

Application Manual

1MRS757457 E

REM611

Application Manual

Section 3

REM611 standardized configuration

PHLPTOC1_START

PHIPTOC1_START

EFLPTOC1_START

EFHPTOC1_START

MNSPTOC1_START

MNSPTOC2_START

LOFLPTUC1_START

PREVPTOC1_START

IN_1

IN_2

IN_3

IN_4

IN_5

IN_6

IN_7

IN_8

OSWGAPC6

OUT

Start 4 TPGAPC2_IN2

SELGAPC4_IN_8

GUID-7F2855BD-9393-4926-A2BA-50F84960B850 V1 EN

Figure 41: OSWGAPC6

Trip OSWGAPCs

OSWGAPC instances 7...10 are used to configure the protection operate signals that belong to the trip group. These four OSWGAPCs have the same inputs from the operate signals of the protection functions. The output is routed to SELGAPC3 via

TPGAPC timer and to SELGAPC4 directly.

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_1

IN_2

IN_3

IN_4

OSWGAPC7

OUT

Trip 1 TPGAPC3_IN1

SELGAPC4_IN_9

GUID-446A9E27-5573-47FE-AFEC-6FE2D14F5953 V1 EN

Figure 42: OSWGAPC7

55

Section 3

REM611 standardized configuration

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

GUID-356729D2-5456-464E-8F12-B15C742ACEE8 V1 EN

Figure 43: OSWGAPC8

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_1

IN_2

IN_3

IN_4

OSWGAPC8

OUT

Trip 2 TPGAPC3_IN2

SELGAPC4_IN_10

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

GUID-08AE8FD5-AB2F-4C08-9BD7-26101E8839C8 V1 EN

Figure 44: OSWGAPC9

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_1

IN_2

IN_3

IN_4

OSWGAPC9

OUT

Trip 3 TPGAPC4_IN1

SELGAPC4_IN_11

1MRS757457 E

56 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

PHLPTOC1_OPERATE

PHIPTOC1_OPERATE

EFLPTOC1_OPERATE

EFHPTOC1_OPERATE

MNSPTOC1_OPERATE

MNSPTOC2_OPERATE

LOFLPTUC1_OPERATE

PREVPTOC1_OPERATE

JAMPTOC1_OPERATE

STTPMSU1_OPR_IIT

STTPMSU1_OPR_STALL

MPTTR1_OPERATE

IN_5

IN_6

IN_7

IN_8

IN_9

IN_10

IN_11

IN_12

IN_1

IN_2

OSWGAPC10

IN_3

IN_4

OUT

Trip 4 TPGAPC4_IN2

SELGAPC4_IN_12

GUID-2AF62F8D-8475-4D18-9FFB-F72272B7D96D V1 EN

Figure 45: OSWGAPC10

Alarm OSWGAPCs

OSWGAPC instances 11...16 are used to configure the alarm signals that belong to the alarm group. These six OSWGAPCs have the same inputs from the alarm signals. The output is routed to SELGAPC3 via TPGAPC timer and to SELGAPC4 directly.

REM611

Application Manual

57

Section 3

REM611 standardized configuration

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

OSWGAPC11

IN_2

IN_3

IN_4

OUT

GUID-C9345E38-B0BF-4853-9888-9A92C413DE61 V1 EN

Figure 46: OSWGAPC11

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

OSWGAPC12

IN_2

IN_3

IN_4

OUT

Alarm 2

TPGAPC5_IN2

SELGAPC4_IN_14

GUID-91DAB4B9-9CE4-4878-8421-C69465BBAA9F V1 EN

Figure 47: OSWGAPC12

1MRS757457 E

58 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

IN_2

OSWGAPC13

IN_3

IN_4

OUT

Alarm 3 TPGAPC6_IN1

SELGAPC4_IN_15

GUID-1B72F2FB-CFCA-4ADE-83D7-09B1B7DFA7A0 V1 EN

Figure 48: OSWGAPC13

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

OSWGAPC14

IN_2

IN_3

IN_4

OUT

GUID-B0663B18-DC37-4BF3-847F-4256D58B3786 V1 EN

Figure 49: OSWGAPC14

REM611

Application Manual

59

Section 3

REM611 standardized configuration

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

IN_2

OSWGAPC15

IN_3

IN_4

OUT

Alarm 5 TPGAPC7_IN1

SELGAPC4_IN_17

GUID-5128779C-1AB0-4F3E-B16C-E97007644D6A V1 EN

Figure 50: OSWGAPC15

MPTTR1_AMARM

RDRE_TRIGGERED

TCSSCBR1_ALARM

TCSSCBR2_ALARM

MDSOPT1_ALARM

ESMGAPC1_ST_EMERG_ENA

CCBRBRF1_TRBU

CCBRBRF1_TRRET

RESTART_INHIBIT

SELGAPC1_OUT_9

TRPPTRC1_CL_LKOUT

IN_5

IN_6

IN_7

IN_8

IN_9

External Trip

IN_10

IN_11

IN_1

IN_2

OSWGAPC16

IN_3

IN_4

OUT

Alarm 6 TPGAPC7_IN2

SELGAPC4_IN_18

GUID-1C25A420-9D17-403A-A494-74550E6EC9DD V1 EN

Figure 51: OSWGAPC16

1MRS757457 E

60 REM611

Application Manual

1MRS757457 E

3.4.4.4

Section 3

REM611 standardized configuration

GOOSE

In the configuration, there are 20 GOOSERCV_BIN functions and 1

GOOSERCV_MV function. Each GOOSERVC_BIN function can be connected to one received binary GOOSE signal and the GOOSERVC_MV function can be connected to one received analog GOOSE signal. The signal connection can be configured in PCM600.

• GOOSERCV_BIN instances 0 and 1 are used for blocking protection functions.

Signals from these two GOOSERCV_BINs are connected to ISWGAPC9.

ISWGAPC9 is used to configure which protection function block is blocked.

• GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE. Signals from these two GOOSERCV_BINs are connected to TRPPTRC1 trip.

• GOOSERCV_BIN instances 4 to 19 are used for blocking the circuit breaker operation. Signals from these 16 GOOSERCV_BINs are connected to

ISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal to block the circuit breaker open or close operation.

• GOOSERCV_MV instance 1 is used for ambient temperature measurement from

GOOSE. Signal from this GOOSERCV_MV is connected to the input

AMB_TEMP of MPTTR1.

REM611

Application Manual

61

Section 3

REM611 standardized configuration

1MRS757457 E

GOOSERCV_BIN:0

GOOSERCV_BIN:1

OR

GOOSE Blcoking

ISWGAPC9

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

GOOSERCV_BIN:2

GOOSERCV_BIN:3

GOOSERCV_BIN:4

GOOSERCV_BIN:5

OR

GOOSE

External Trip

TRPPTRC1_OPERATE

OR

GOOSE Block CB

ISWGAPC10

CBXCBR1_BLK_CLOSE

CBXCBR1_BLK_OPEN

GOOSERCV_BIN:19

GOOSERCV_MV:1 MPTTR1_AMB_TEMP

GUID-CDAE630B-B30B-492D-B387-960CBA32A3BC V2 EN

Figure 52: GOOSE overview

ISWGAPC9

ISWGAPC9 is used to configure which protection functions can be blocked by the received GOOSE signals. ISWGAPC9 inputs are received GOOSE signals from

GOOSERCV_BIN:0 and GOOSERCV_BIN:1. The outputs are connected to the block inputs of the protection functions.

62 REM611

Application Manual

1MRS757457 E

Section 3

REM611 standardized configuration

GOOSERCV_BIN:0_OUT

GOOSERCV_BIN:1_OUT

GOOSE Blocking

IN

ISWGAPC9

OUT_1

OUT_2

OUT_3

OUT_4

OUT_5

OUT_6

OUT_7

OUT_8

OUT_9

OUT_10

OUT_11

PHLPTOC1_BLOCK

PHIPTOC1_BLOCK

EFLPTOC1_BLOCK

EFHPTOC1_BLOCK

JAMPTOC1_BLOCK

MNSPTOC1_BLOCK

MNSPTOC2_BLOCK

LOFLPTUC1_BLOCK

STTPMSU1_BLOCK

PREVPTOC1_BLOCK

MPTTR1_BLOCK

GUID-0A6BC123-F2FB-493F-BA08-D0885E2724CC V1 EN

Figure 53: ISWGAPC9

ISWGAPC10

ISWGAPC10 is used to block the circuit breaker operation from the received GOOSE signals. ISWGAPC10 inputs are received GOOSE signals from GOOSERCV_BIN:

4 to GOOSERCV_BIN:19. The outputs are connected to block the circuit breaker close and open operation.

GOOSERCV_BIN:4_OUT

GOOSERCV_BIN:5_OUT

GOOSERCV_BIN:6_OUT

...

GOOSERCV_BIN:19_OUT

GOOSE Blocking CB

IN

GUID-CB5DD0EA-3C0F-4683-AC0B-692A403A6757 V1 EN

Figure 54: ISWGAPC10

ISWGAPC10

OUT_1

OUT_2

CBXCBR1_BLK_CLOSE

CBXCBR1_BLK_OPEN

REM611

Application Manual

63

64

1MRS757457 E

Section 4

Requirements for measurement transformers

Section 4 Requirements for measurement transformers

4.1

4.1.1

4.1.1.1

REM611

Application Manual

Current transformers

Current transformer requirements for overcurrent protection

For reliable and correct operation of the overcurrent protection, the CT has to be chosen carefully. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity, and co-ordination of protection. However, when the CT is correctly selected, a fast and reliable short circuit protection can be enabled.

The selection of a CT depends not only on the CT specifications but also on the network fault current magnitude, desired protection objectives, and the actual CT burden.

Current transformer accuracy class and accuracy limit factor

The rated accuracy limit factor (F n

) is the ratio of the rated accuracy limit primary current to the rated primary current. For example, a protective current transformer of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protective current transformers, the accuracy class is designed by the highest permissible percentage composite error at the rated accuracy limit primary current prescribed for the accuracy class concerned, followed by the letter "P" (meaning protection).

Table 16:

Accuracy class

5P

10P

Limits of errors according to IEC 60044-1 for protective current transformers

Current error at rated primary current (%)

±1

±3

Phase displacement at rated primary current minutes

-

±60 centiradians

-

±1.8

Composite error at rated accuracy limit primary current (%)

5

10

The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protection. The 5P class provides a better accuracy.

The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy.

In practise, the actual accuracy limit factor (F a

) differs from the rated accuracy limit factor (F n

) and is proportional to the ratio of the rated CT burden and the actual CT burden.

65

Section 4

Requirements for measurement transformers

The actual accuracy limit factor is calculated using the formula:

F a

F n

×

S in

+ S n

S in

+ S

A071141 V1 EN

F n

S in

S the accuracy limit factor with the nominal external burden S n the internal secondary burden of the CT the actual external burden

1MRS757457 E

4.1.1.2

66

Non-directional overcurrent protection

The current transformer selection

Non-directional overcurrent protection does not set high requirements on the accuracy class or on the actual accuracy limit factor (F a

) of the CTs. It is, however, recommended to select a CT with F a

of at least 20.

The nominal primary current I

1n

should be chosen in such a way that the thermal and dynamic strength of the current measuring input of the protection relay is not exceeded. This is always fulfilled when

I

1n

> I kmax

/ 100,

I kmax

is the highest fault current.

The saturation of the CT protects the measuring circuit and the current input of the protection relay. For that reason, in practice, even a few times smaller nominal primary current can be used than given by the formula.

Recommended start current settings

If I kmin

is the lowest primary current at which the highest set overcurrent stage is to operate, the start current should be set using the formula:

Current start value < 0.7 × (I kmin

/ I

1n

)

I

1n

is the nominal primary current of the CT.

The factor 0.7 takes into account the protection relay inaccuracy, current transformer errors, and imperfections of the short circuit calculations.

The adequate performance of the CT should be checked when the setting of the high set stage overcurrent protection is defined. The operate time delay caused by the CT saturation is typically small enough when the overcurrent setting is noticeably lower than F a

.

REM611

Application Manual

1MRS757457 E

4.1.1.3

Section 4

Requirements for measurement transformers

When defining the setting values for the low set stages, the saturation of the CT does not need to be taken into account and the start current setting is simply according to the formula.

Delay in operation caused by saturation of current transformers

The saturation of CT may cause a delayed protection relay operation. To ensure the time selectivity, the delay must be taken into account when setting the operate times of successive protection relays.

With definite time mode of operation, the saturation of CT may cause a delay that is as long as the time constant of the DC component of the fault current, when the current is only slightly higher than the starting current. This depends on the accuracy limit factor of the CT, on the remanence flux of the core of the CT, and on the operate time setting.

With inverse time mode of operation, the delay should always be considered as being as long as the time constant of the DC component.

With inverse time mode of operation and when the high-set stages are not used, the AC component of the fault current should not saturate the CT less than 20 times the starting current. Otherwise, the inverse operation time can be further prolonged.

Therefore, the accuracy limit factor F a

should be chosen using the formula:

F a

> 20 × Current start value / I

1n

The Current start value is the primary start current setting of the protection relay.

Example for non-directional overcurrent protection

The following figure describes a typical medium voltage feeder. The protection is implemented as three-stage definite time non-directional overcurrent protection.

REM611

Application Manual

67

Section 4

Requirements for measurement transformers

1MRS757457 E

68

A071142 V1 EN

Figure 55: Example of three-stage overcurrent protection

The maximum three-phase fault current is 41.7 kA and the minimum three-phase short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59.

The start current setting for low-set stage (3I>) is selected to be about twice the nominal current of the cable. The operate time is selected so that it is selective with the

next protection relay (not visible in Figure 55

). The settings for the high-set stage and instantaneous stage are defined also so that grading is ensured with the downstream protection. In addition, the start current settings have to be defined so that the protection relay operates with the minimum fault current and it does not operate with the maximum load current. The settings for all three stages are as in

Figure 55 .

For the application point of view, the suitable setting for instantaneous stage (I>>>) in this example is 3 500 A (5.83 × I

2n

). I

2n

is the 1.2 multiple with nominal primary current of the CT. For the CT characteristics point of view, the criteria given by the current transformer selection formula is fulfilled and also the protection relay setting is considerably below the F a

. In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons.

REM611

Application Manual

1MRS757457 E

Section 5

Protection relay's physical connections

Section 5 Protection relay's physical connections

5.1

5.1.1

5.1.1.1

5.1.1.2

5.1.2

Inputs

Energizing inputs

Phase currents

The protection relay can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied.

However, at least terminals X120:7-8 must be connected.

Table 17:

Terminal

X120:7-8

X120:9-10

X120:11-12

Phase current inputs included in configuration A

Description

IL1

IL2

IL3

Residual current

Table 18:

Terminal

X120:13-14

Residual current input included in configuration A

Description

Io

Auxiliary supply voltage input

The auxiliary voltage of the protection relay is connected to terminals X100:1-2. At

DC supply, the positive lead is connected to terminal X100:1. The permitted auxiliary voltage range (AC/DC or DC) is marked on the top of the LHMI of the protection relay.

Auxiliary voltage supply Table 19:

Terminal

X100:1

X100:2

Description

+ Input

- Input

REM611

Application Manual

69

Section 5

Protection relay's physical connections

5.1.3

5.2

5.2.1

70

1MRS757457 E

Binary inputs

The binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for remote control of protection relay settings.

Binary inputs of slot X120 are available with configuration A.

Table 20:

Terminal

X120:1

X120:2

X120:3

X120:2

X120:4

X120:2

X120:5

X120:6

Binary input terminals X120-1...6

Description

BI1, +

BI1, -

BI2, +

BI2, -

BI3, +

BI3, -

BI4, +

BI4, -

Outputs

Outputs for tripping and controlling

Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. In the factory default configuration, the trip signals from all the protection stages are routed to PO3 and PO4.

Output contacts Table 21:

Terminal

X100:6

X100:7

X100:8

X100:9

X100:15

X100:16

X100:17

X100:18

X100:19

X100:20

X100:21

X100:22

X100:23

X100:24

Description

PO1, NO

PO1, NO

PO2, NO

PO2, NO

PO3, NO (TCS resistor)

PO3, NO

PO3, NO

PO3 (TCS1 input), NO

PO3 (TCS1 input), NO

PO4, NO (TCS resistor)

PO4, NO

PO4, NO

PO4 (TCS2 input), NO

PO4 (TCS2 input), NO

REM611

Application Manual

1MRS757457 E

5.2.2

5.2.3

Section 5

Protection relay's physical connections

Outputs for signalling

Output contacts SO1 and SO2 in slot X100 can be used for signalling on start and tripping of the protection relay. On delivery from the factory, the start and alarm signals from all the protection stages are routed to signalling outputs.

Output contacts X100:10...14

Table 22:

Terminal

X100:10

X100:11

X100:12

X100:13

X100:14

Description

SO1, common

SO1, NC

SO1, NO

SO2, NO

SO2, NO

IRF

The IRF contact functions as an output contact for the self-supervision system of the protection relay. Under normal operating conditions, the protection relay is energized and the contact is closed (X100:3-5). When a fault is detected by the self-supervision system or the auxiliary voltage is disconnected, the contact X100:3-5 drops off and the contact X100:3-4 closes.

IRF contact Table 23:

Terminal

X100:3

X100:4

X100:5

Description

IRF, common

Closed; IRF, or U aux

disconnected

Closed; no IRF, and U aux

connected

REM611

Application Manual

71

72

1MRS757457 E

Section 6 Glossary

REM611

Application Manual

Section 6

Glossary

100BASE-FX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses fiber optic cabling

100BASE-TX A physical medium defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses twistedpair cabling category 5 or higher with RJ-45 connectors

611 series Series of numerical protection and control relays for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment

CB

CSV

Circuit breaker

Comma-separated values

CT

DAN

DC

DPC

EMC

Ethernet

Current transformer

Doubly attached node

1. Direct current

2. Disconnector

3. Double command

Double-point control

Electromagnetic compatibility

A standard for connecting a family of frame-based computer networking technologies into a LAN

FIFO

FTP

FTPS

GOOSE

HMI

HSR

HTTPS

First in, first out

File transfer protocol

FTP Secure

Generic Object-Oriented Substation Event

Human-machine interface

High-availability seamless redundancy

Hypertext Transfer Protocol Secure

IEC

IEC 61850

International Electrotechnical Commission

International standard for substation communication and modeling

IEC 61850-8-1 A communication protocol based on the IEC 61850 standard series

IED Intelligent electronic device

73

Section 6

Glossary

1MRS757457 E

RSTP

SAN

SNTP

SO

WAN

WHMI

NPS

PCM600

PO

PRP

REM611

RJ-45

RS-485

IRIG-B

LAN

LC

LCD

LED

LHMI

MAC

MMS

Modbus

IEEE 1686

IP address

Standard for Substation Intelligent Electronic Devices'

(IEDs') Cyber Security Capabilities

A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol.

Inter-Range Instrumentation Group's time code format B

Local area network

Connector type for glass fiber cable, IEC 61754-20

Liquid crystal display

Light-emitting diode

Local human-machine interface

Media access control

1. Manufacturing message specification

2. Metering management system

A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices.

Negative phase sequence

Protection and Control IED Manager

Power output

Parallel redundancy protocol

Motor protection and control relay

Galvanic connector type

Serial link according to EIA standard RS485

Rapid spanning tree protocol

Single attached node

Simple Network Time Protocol

Signal output

Wide area network

Web human-machine interface

74 REM611

Application Manual

75

ABB Distribution Solutions

Distribution Automation

P.O. Box 699

FI-65101 VAASA, Finland

Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/relion

© Copyright 2019 ABB. All rights reserved.

advertisement

Related manuals

Download PDF

advertisement

Table of contents