- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- ABB
- TLE Series 160-500 kVA/kW UPS
- Operating manual
advertisement
Critical Power
TLE Series 160/200/225/ 250
TLE Series 300/350/400/500
User Manual
Uninterruptible Power Supply
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
T +41 (0)91 / 850 51 51
F +41 (0)91 / 850 52 52 www.gecriticalpower.com
imagination at work
Critical Power
Model:
Issued by:
Approved by:
Date of issue:
TLE Series 160 – 200 - 225 – 250 – 300 – 400 - 500 UL S2B
Product Document Department – Riazzino - CH
R & D Department – Riazzino - CH
04/23/2018
File name:
Revision:
GE_UPS_OPM_TLE_SUL_M16_M50_2bU_V010
1.0
Identification No.:
Up-dating
8600180580P
Revision Concern
COPYRIGHT © 2018 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
Date
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE .
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 2/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Dear Customer ,
We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE .
We trust that the use of the TLE Series 160 - 500
Uninterruptible Power Supply System, developed and produced to the highest standards of quality, will give you complete satisfaction.
Please read carefully the User Manual , which contains all the necessary information and describes all you need to know about the use of the UPS.
Thank you for choosing GE !
START-UP AND COMMISSIONING
A GE GLOBAL SERVICES FIELD ENGINEER must perform start-up and commissioning of the UPS.
Please Contact GE GLOBAL SERVICES at least two weeks prior to schedule start-up and commissioning at 1-800-637-1738, or by E-mail at [email protected]
.
g
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland www.gecriticalpower.com
Distributed in the USA by g
GE Energy Connections
Critical Power
3100 Technology – Suite 200
Plano, TX 75074
T: +1 800-637-1738
www.geindustrial.com/products/ critical-power
Your Service Center g
GE Energy Connections
Critical Power
601 Shiloh Road
Plano, TX 75074
24/7 T: +1 800-637-1738
24/7 F: +1 866-765-3595
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 3/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Preface
Congratulations on your choice of a TLE Series Uninterruptible Power Supply (UPS).
It will help eliminate load disturbances due to unexpected power problem.
This User Manual describes the function of the UPS module, the purpose and location of the switches, the meaning of the system events related to the front panel indication, and provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installation Guide, which describes how to prepare the installation site, and it provides weight, dimensions and procedures for moving, installing and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE
assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
WARNING!
TLE Series 160 – 500 is a Category C3 UPS Product (according to IEC 62040-2).
This is a product for commercial and industrial application in the second environment − installation restrictions or additional measures may be needed to prevent disturbances.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please contact your GE Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the installation of the UPS, options and battery system.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and personnel safety.
Parallel System version secured with RPA
When included in the text, this symbol refers to operation needed only for RPA Parallel System.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 4/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Table of content
Page
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 5/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models TLE Series 160 - 500 that should be followed during installation and maintenance of the UPS and battery.
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest GE Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage remains at the terminals of the electrolytic capacitors.
- UPS’s and battery system require a 12 months periodic maintenance to operate reliably and safely.
This should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- End user must follow applicable regional occupational safety codes/regulations during installation, operation and equipment maintenance. This may require additional field marking or labeling defining appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our GE Service Center for product specific information.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104 ° F
(40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25 ° C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (55 ° C).
The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 6/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must install and service the battery.
The installation must conform to national and local codes.
Keep unauthorised personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear.
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewellery.
Do not carry metal objects in your pockets where the objects can fall into the battery cabinet. High energy through conductive materials could cause severe burns.
2 Tools must have insulated handles and must be insulated so that they will not short battery terminals.
Do not allow a tool to short between individual or separate battery terminals or to the cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could fall onto the battery or into the cabinet.
3 Disconnect charging source prior to connecting or disconnecting battery terminals.
Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
8 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity controlled indoor area, free of contaminants.
9 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the battery conductors.
10 Where conductors may be exposed to physical damage, protect the conductors in accordance with all applicable codes.
11 If you are replacing the battery or repairing battery connections, shut OFF the UPS and remove the battery fuses.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 7/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 8/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
2 LAYOUT
2.1
LAYOUT TLE Series 160 - 220 - 225 - 250
TLES_UL_225-250_
S1_UPS_GE_02
Fig. 2.1-3 Control Panel
Fig. 2.1-1 TLE Series 160 - 200 - 225 - 250 General view
TLES_UL_2
25-250_S1
_UPS_GE_0
3
+ -
I ON Q1
TLES_UL_225-25
0_S1_Switch Q
1_01
Fig. 2.1-4 Q1 - UPS Output switch
Q1
I ON
Fig. 2.1-2 TLE Series 160 - 200 - 225 - 250 - General view with open doors
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 9/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
2.2
LAYOUT TLE Series 300 - 400 - 500
TLES_UL_400-500_
S1_UPS_GE_02
Fig. 2.2-3 Control Panel
Fig. 2.2-1 TLE Series 300 – 400 - 500 - General view
TLES_UL_4
00-500_S1
_UPS_GE_0
3a
I ON Q1
TLES_UL_400-500_
S1_Switch Q1_01
Fig. 2.2-4 Q1 - UPS Output switch
Q1
I ON
- +
Fig. 2.2-2 TLE Series 300 – 400 - 500 - General view with open doors
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 10/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
3 INTRODUCTION
The TLE Series 160 - 500 Uninterruptible Power Supply (UPS) provides the energy supply for critical loads which need a reliable, continuous free from voltage disturbances and frequency fluctuations supply.
In case the power provided by the Utility Fails , or exceeds the permitted tolerances, the power to supply the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load ) or until the Utility power returns.
TLE Series 160 - 500 is a truly VFI double conversion Uninterruptible Power Supply
(UPS), equipped with automatic bypass, where the Load is normally supplied by the
Inverter .
If the Inverter is not able to supply the required Output Voltage , or when overload or short-circuit on the output occur, the Load is instantly transferred to the Utility via the Automatic Bypass .
The UPS automatically returns to normal mode when the failure condition is restored.
TLE Series 160 - 500 can be configured, if chosen, for the eBoost™ Operation Mode
(Option - High efficiency: up to 99% / Fast power transfer: <2ms) permitting maximum energy saving.
KEY FEATURES :
More Critical equipment supported
Rated at 1 Power Factor, TLE Series 160 - 500 delivers more real power than other UPS in the market.
With today’s trend toward power factor corrected loads, TLE Series 160 - 500 can support more total
Load than any other UPS available, allowing you to support a greater number of today’s enterprise computing Power Factor Corrected (PFC) equipment.
High Efficiency
Thanks to type Advanced Neutral Point Clamped three level IGBT technology, TLE Series 160 - 500 guarantees a high overall performance.
Intelligent Energy Management (IEM) combined with RPA , results in the most cost efficient and reliable
UPS solution in the industry.
Fully digital
Digital Signal Processor (DSP) , Flash memory and Advanced Neutral Point Clamped are the technology corner stones of a new age of power quality and power reliability.
RPA™ - Redundant Parallel Architecture™ Parallel System
GE provides a unique technology called Redundant Parallel Architecture™ (RPA™) that can parallel
Uninterruptible Power Supply (UPS) modules with true redundancy.
With RPA™ , there is no need for external electronics or switches to control the UPS modules in the parallel system.
One of the UPS modules in the system arbitrarily takes a leadership role, while the other UPS modules have access to all control parameters.
If one UPS fails to operate, the load is automatically redistributed among the others.
If the lead UPS fails to operate then a different UPS automatically takes on the leadership role.
The RPA™ systems are designed to have no single points of failure, ensuring the highest level of power protection for critical loads.
Extremely flexible
Tailor made power protection to meet your individual installation requirements; TLE Series 160 - 500 offers various options like EMC filter and our comprehensive software for mission control and data protection to cover all your application needs.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 11/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4 DESCRIPTION
TLE Series 300/350/400/500
TLE Series 160/200/225/ 250
TLE Series 160 - 500 is one of the best performing and most reliable three-phase
UPS systems providing critical power protection for a wide range of applications.
Every TLE Series 160 - 500 system operates in VFI mode (Voltage Frequency
Independent) yielding the maximum levels of power reliability for all mission-critical processes.
With proven technology the TLE Series 160 - 500 UPS provides top class reliability and performance.
With backfeed protection and compliance to EMC standards the TLE Series 160 - 500 complies to current standards.
Reliability can be further increased by paralleling up to six UPS units utilizing GE’s unique RPA™ technology (Redundant Parallel Architecture) .
With RPA every UPS is controlled in a true peer-to-peer configuration with redundancy in all critical elements and functions, eliminating all single points of failure.
The decentralized bypass offers great flexibility to up or down grade the system in case future needs might change.
TLE Series 160 - 500 , BEST IN CLASS EFFICIENCY
• High efficiency in double conversion mode up to 96.5% and eBoost ™ operation mode up to 99%.
• High efficiency at partial and reduced loads for cost benefits in operating conditions.
• Higher efficiency at partial load in RPA Systems with adaptive capacity control (IEMi Operation Mode )
• TLE Series 160 - 500 products designed in compliance with UL 1779 standard, C3 level for immunity, i.e. can withstand possible disturbances and noise without affecting standard operating conditions.
• Advanced User Interface with touch screen display guided menu.
• Reduced energy consumption costs.
• Reduced size and costs of the air conditioning system.
• Compact design, saving installation space.
NOTE !
Through their complete life cycle, all GE UPS systems are fully supported by GE
Service Teams which provide world-class, 24x7 preventive and corrective services, training and application expertise.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 12/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.1
BLOCK DIAGRAM AND MAIN ELEMENTS
Fig. 4.1-1 Block Diagram TLE Series 160 - 500
The TLE Series 160 - 500 system can be divided into the following main elements:
Control System
TLE Series 160 - 500 is designed with microprocessor-controlled signal processing circuits.
The interface between the operator and the unit is provided by the monitoring system on the front panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The Active IGBT Rectifier converts the 3-phase utility voltage into a controlled and regulated DC-voltage, supplying the Inverter and to charge the battery through the battery-charger .
Thanks to modulation strategy applied to IGBT Bridge , the rectifier provides clean input power in terms of low THDi and unity power factor.
Inverter
The Inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and frequency, which is completely independent and isolated from the AC-input voltage.
Automatic Bypass
The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module) , used to provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection
All TLE Series 160 - 500 UPS's are equipped with an automatic system for the protection against voltage back feeding towards Utility , through the Bypass (UL 1778 and CSA C22.2 no. 107.3).
This protection works automatically by opening contactor K6 (in series with the thyristors of the static switch) and eventually K7 , and acts in case of internal defects of the system.
Battery
The Battery supplies the DC power to the Inverter when the Utility is out of acceptable tolerances.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 13/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.2
OPERATION MODES
4.2.1
Normal VFI Operation Mode (Voltage Frequency Independent)
Under normal conditions the Load is permanently powered by the Inverter with constant amplitude and frequency.
The Rectifier , powered by the Utility , supplies the Inverter and the battery-charger keeps the battery fully charged.
The Inverter converts the DC voltage in a new
AC sine wave voltage with constant amplitude and frequency independently from the input
Utility Power .
4.2.2
eBoost™ Operation Mode (option)
Fig. 4.2.1-1 Block diagram normal VFI Operation Mode eBoost ™ e High efficiency (up to 99%)
Boost Fast power transfer (< 2ms)
When the eBoost™ Operation Mode is selected, and the Utility Power is available, the Load is normally powered through the
Automatic Bypass .
When the Utility Voltage is detected out of the prescribed tolerances, the Load is automatically transferred to the Inverter .
When the Utility recovers, the Load returns to the Automatic Bypass after a variable time
Fig. 4.2.2-1 Block diagram eBoost™ Operation Mode defined by the control unit.
The eBoost™ Operation Mode can be used for single units or the RPA Parallel System , for up to 6 UPS modules, with all units individually able to supply power through a redundant communication bus.
The eBoost™ Operation Mode can be configured directly by the user for higher efficiency, considering the Utility reliability and criticality of the Load .
The selection between the two operation modes “ VFI mode and eBoost™ Operation Mode ”, or switching between operation modes at required time, can be done through the UPS control panel (see Section 6.4
/ eBoost ).
NOTE !
The eBoost™ Operation Mode is available only if enabled at the factory or by a GE
GLOBAL SERVICES FIELD ENGINEER .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 14/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.2.3
Utility Failure Operation
When the Utility is no longer within acceptable tolerances, the Battery will provide the DC power to the Inverter .
The Inverter will maintain continuous AC power to the
Load until the Battery Voltage reaches the lower limit of the Inverter operation capability.
During the discharge, the LCD screen shows the estimated time the Battery can support the critical Load .
Prior to complete Battery discharge, the " stop operation" alarm (shut-down imminent) warns the operator that the
Battery is almost discharged and the UPS is about to shut down.
Fig. 4.2.3-1 Block diagram Utility Failure operation
In case of RPA Parallel System
With a Parallel System for power capacity (see Section 4.3)
• With the Bypass Utility power available, a “Battery low” warning on any unit will cause the Load to be transferred to Utility (after a selectable time delay).
• With Bypass Utility power not available, a “Battery low” warning on any unit will start the “stop
operation” timer (adjustable).
The Load will shut down at the end of the “ stop operation” time period.
With a Parallel System for redundancy (see Section 4.3)
• When a Battery low warning occurs on a unit not necessary to support the present Load, this unit will shut down after a timeout period (selectable).
The Load is shared between the other units.
• As the warning occurs on one unit necessary to support the present Load, the system starts the
" stop operation" timeout (selectable).
The Load will shut down at the end of the “ stop operation” time period.
4.2.4
Utility Recovery Operation
As soon as the AC input power recovers, the Rectifier will start automatically , supplying DC power to the Inverter and recharging the Battery .
If the Inverter was previously shut down due to low
Battery , the Load will be initially powered by Utility through the Automatic Bypass .
When the Battery is sufficiently recharged to ensure a minimum time of operation with the present Load , the
Inverter will start automatically and the Load will be transferred back to the Inverter .
Fig. 4.2.4-1 Block diagram Utility recovery operation
In case of RPA Parallel System
When the AC input power recovers, the Rectifiers will start-up sequentially, according to their number in the Parallel System. This minimizes the initial inrush current.
The Inverters will start-up automatically, but only when the Battery has been sufficiently recharged for a minimum runtime with the present Load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from the Automatic Bypass back to the Inverter output.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 15/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.2.5
Automatic Bypass
In normal operation, the Load is supplied by the Inverter .
When the control system detects a fault in the Inverter , an overload condition or a shortcircuit condition, the Automatic Bypass will transfer the critical Load to the Utility without interruption.
When the Inverter recovers, or the overload or short-circuit condition is corrected, the
Load will be automatically transferred back to Fig. 4.2.5-1 Block diagram Automatic Bypass the Inverter .
If the UPS is unable to return to normal mode following an automatic transfer to Bypass mode , an alarm condition will be initiated.
In case of RPA Parallel System
Each unit has its own internal Bypass.
These units are continuously exchanging information, enabling all of the internal Bypass circuits in a
Parallel System to operate simultaneously.
If the Inverter of a unit fails, its Bypass circuit remains available to the Parallel System.
It is excluded only if the unit is separated from the common bus by opening its output switch Q1 .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 16/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.3
RPA PARALLEL SYSTEM OPERATION
4.3.1
Introduction to the RPA Parallel System
Fig. 4.3.1-1 Block diagram RPA Parallel System operation
Two or more equal power units can be paralleled to increase the output power ( paralleling for capacity ) or to improve the overall reliability of an UPS system ( paralleling for redundancy ).
The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the Load equally.
The modular concept of TLE Series allows parallel operation of up to 6 units , without using paralleling switchgear, external bypass circuits or common control circuitry (see Fig. 4.3.1-1 ).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal power .
In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the
Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n out of n+1 redundant paralleled modules must be equal to or higher than the required Load power.
The Load will be equally shared by the n+1 units connected on the output bus.
Should one of the n+1 paralleled units trip Off-line, the remaining (n) modules will supply the Load , maintaining conditioned power to the critical Load .
From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between
Failures).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 17/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.3.2
Features of RPA Parallel System
The TLE Series 160 - 500 Parallel System is designed to provide a complete Redundant Parallel
Architecture , and is free from common equipment.
Not only the Inverters but also the Bypass functions are redundant.
When one UPS needs maintenance or service, the Load is powered by the other units.
The redundant communication bus to which all units are connected keeps each unit informed about the status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
4.3.3
System control
A high-speed redundant, serial communication bus , guarantees the exchange of data and thus the communication between the CPU's of each unit.
Each module controls is own function and operational status and communicates with all other modules, in order to act or react if necessary, adapting to the new conditions.
4.3.4
Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units synchronize to this unit, which in turn synchronizes to the Utility Bypass voltage, as long as the latter is within tolerances.
In case of reference failure, another unit in the Parallel System is automatically chosen to take over the reference role.
The Bypass Input for all the units of the Parallel System must be supplied from the same AC source (no phase shift allowed between them).
4.3.5
Load sharing
On each unit of the Parallel System , Inverter Output Voltage and Current are measured and applied to a
Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or fuses should be installed between the units output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in order to totally isolate a unit if needed.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 18/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.3.6
IEMi Operation Mode (option)
NOTE !
IEMi and eBoost Operation Mode are mutually exclusive; they cannot be simultaneously available on a system.
Fig. 4.3.6-1 Functional diagram of a Parallel System RPA in IEMi Operation Mode
GE offers the IEMi - Intelligent Energy Management integrated option to optimize energy cost while maintaining the highest possible reliability for Parallel Redundant Uninterruptible Power Supply units
(max. 6).
For Parallel System installations, secured with Redundant Parallel Architecture ™ (RPA ™ ) , IEMi Operation
Mode saves energy by dynamically utilizing the UPS units as needed to meet the required load without compromising the power quality to the critical load.
The software will calculate the number of UPS units which are needed for load supply based on following:
• Redundancy (N+1 or N+2) • Rectifier status
• Inverter operating time
• System Load
• IEMi Operation Mode programming
Particularly, the UPS control logic determines the minimal set of UPSs required to maintain a reliable supply to the critical load.
Then, an efficiency optimization algorithm determines the best UPS configuration in order to maintain the running UPS in their highest efficiency operating region.
Energy losses are reduced by switching the Inverter section of one or more units to a stand-by state.
The critical load is fed by the remaining units operating in double-conversion.
As load increases, other units are gradually switched on-line in order to maintain the required redundancy level.
The IEMi - Intelligent Energy Management integrated option is only available on parallel installations.
It is clear that in order to enjoy the benefits of IEMi operation a system programmed for N+1 redundancy requires a parallel installation of at least three UPSs, while four UPSs are required for N+2 redundancy.
IEMi - Intelligent Energy Management integrated is an option, and it is available only if introduced at the factory, or if introduced in field installations by a GE GLOBAL SERVICES FIELD ENGINEER.
Benefits of IEMi - Intelligent Energy Management integrated include:
•
•
•
Higher efficiency (reduced losses) in low-load conditions (efficiency optimization)
No compromise on power quality (double-conversion operation)
No compromise on system reliability (redundant operation).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 19/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.4
UPS PARALLELED ON THE SAME BATTERY
NOTE !
A Parallel System with a Common Battery for two or more UPS (max. 4 units), requires a particular installation and adequate setting of some parameters, (accessible only through password), and can therefore only be done by a GE QUALIFIED ENGINEER.
Usually each UPS Unit runs with its own Battery .
In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 4.4-1 ), the sharing circuit between the individual UPS is integrated in the communication bus of the system in order to assure an equal sharing of the Rectifiers output currents.
1 –
2 –
3 –
4 –
5 –
6 –
7 –
Rectifier
Inverter
Automatic Bypass
Utility Input
Load Bus Bar
External Battery Fuse
External Battery
Fig. 4.4-1 Diagram RPA system with UPS on Common Battery
Pay attention to the following recommendations:
• The units delivered for this functioning mode needs special parameters setting, so they must be prepared in advance before the installation.
• The installation must be performed only with the UPS system completely shut down.
• The AC Rectifiers input power (4) must be the same, with clockwise phase rotation for each unit.
• Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
• It is mandatory to install the fuses / MCB (6) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons (see Installation Guide to Section 4.8.2
).
• In case a unit must be powered down for maintenance, switch-OFF the concerned unit before open the DC fuses / MCB on the Battery line (6).
• It is recommended to connect an external NO free contact “Battery Fuses” to the UPS and to enable the function by setting the parameter (see Section 9.1
).
• If an emergency generator set supplies the UPS, and the free contact “Generator ON” is connected to the Customer Interface , connect a separate NO free contact on each parallel unit.
• The parameters enabling the Battery test , both manual and automatic, must be set in the same mode on all the units sharing a Common Battery .
• Do not connect the temperature sensor for automatic battery floating voltage compensation.
• Do not enable the function Boost charge .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 20/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
4.5
SERVICE AND TECHNICAL SUPPORT
For any request of technical support please contact your local GE Service Center .
Your GE Service Center (see page 3)
g
GE Digital Energy
6595 RIAZZINO (CH)
MADE IN POLAND
Model
Serial Nr.
Series
Input Freq.
Input Voltage
Input Current
Hz
Product. Year
VAC: 3W + N + PE
A
Output Power
Output Freq.
Output Voltage
Output Current kVA
Hz at Pow. factor
VAC: 3W + N + PE lag.
A
Q1
I ON
Q2
I ON
- +
I ON
Q2
I ON Q1
TLES_UL_225-500_S
2_Label identificatio n_01
The requested data permitting to identify your UPS are marked on the identification label fixed on the front of the cabinet, behind the lower front door.
For fast and efficient technical support please mention the data marked on the identification label.
Fig. 4.5-1 Identification label
4.6
WARRANTY
GE , operating through its authorized agents, warrants that the standard products will be free of defects in materials and workmanship for a period as per contract specifications.
NOTE !
This warranty does not cover failures of the product which result from incorrect installation, misuse, alterations by persons other than authorized agents, or abnormal working conditions.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 21/91
User Manual TLE Series 160 - 500 UL S2B
4.7
RECYCLING INSTRUCTIONS
Critical Power
NOTE !
This product has been designed to respect the environment, using materials and components respecting eco-design rules.
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs
(Halogen Carbon Fluor Clorid) .
PACKING MATERIAL RECYCLING
GE , in compliance with environment protection, uses only environmentally friendly material.
UPS packing materials must be recycled in compliance with all applicable regulations.
RECYCLING AT THE END OF SERVICE LIFE !
GE , in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialized companies!
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 22/91
User Manual TLE Series 160 - 500 UL S2B
5 CONTROL PANEL
5.1
CONTROL PANEL
Critical Power
Fig. 5.1-1 Control Panel
The Control Panel , positioned on the UPS front door, acts as the UPS user interface.
Main features:
•
LCD Touch screen color graphic display. See Chapter 6.
•
•
Multilanguage communication interface:
English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovenian, Chinese,
Swedish, Russian and Dutch.
Synoptic diagram indicating UPS status.
• Command keys and parameters setting.
•
UPS status control LED.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 23/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6 LCD SCREEN
Composed of an LCD color “Touch Screen” which provides the following information to users:
• Synoptic diagram indicating UPS status.
•
UPS operating, AC and DC metering information.
•
History of events (alarms and messages).
•
Functionality can be programmed to meet customer needs by changing parameters.
•
Operation commands of the UPS.
6.1
HOME SCREEN
Fig. 6.1-1 LCD screen
The LCD screen , after 5 minutes of inactivity, shuts down the backlight.
To reactivate it, it is sufficient to press any keys mentioned to Section 6.1.1
.
If the keypad remains inactive for 5 minutes or longer, during the viewing of a screen such as
MEASURES , EVENTS , SETUP or COMMANDS , the LCD screen returns automatically to the main screen.
Pressing the key “UPS status” for a few seconds automatically sets the “ENGLISH” language on the LCD screen .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 24/91
User Manual TLE Series 160 - 500 UL S2B
6.1.1
Description of the selection keys
Critical Power
Fig. 6.1.1-1 LCD screen
MEASURES
EVENTS
SETUP
COMMANDS
RPA
Parallel
System
MUTE
Shows electric parameters values and statistics of use.
See Section 6.2
.
Shows in chronological order, all the events occurred (alarms, messages, commands, handling, etc.).
See Section 6.3.
Allows the user to customize some UPS functions to specific requirements and to view UPS identification data.
See Section 6.4
.
Allows the user to execute UPS operation commands.
See Section 6.5
.
Shows the status of operation of the RPA Parallel System .
See Section 6.6
.
Key to reset general alarm and buzzer.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 25/91
User Manual TLE Series 160 - 500 UL S2B
6.1.2
Description of the signaling LEDs
Critical Power
Fig. 6.1.2-1 LCD screen
UPS model
Date (format “ MM/DD/YYYY ”).
Time AM or PM (format “ HH.MM.SS
”). eBoost (green color)
LED ON/lit indicates that the UPS is operating in eBoost™ mode.
IEMi (green color)
LED ON/lit indicates that the UPS is operating in IEMi mode.
Service Key (yellow color)
Key for disabling the Service Key procedure.
Used only by the GE Service Center .
LEDS UPS STATUS
LED LOAD PROTECTED (green color)
When lit, indicates that the UPS is functioning correctly and the Load is system protected (Load supplied either from Inverter or from Automatic Bypass in case of eBoost™ Operation Mode).
When blinking, indicates that a regular maintenance service is needed (SERVICE REQUIRED) .
May be reset by a GE Service Technicians only.
See Section 9 – Maintenance – Service check .
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in service mode , not supplying the Load .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 26/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
LED ALARM (yellow color)
It blinks when one or more alarm is activated. The internal Buzzer is ON .
The LED remains blinking (with the alarm condition still present) and the buzzer stops when the key
“MUTE” is pressed.
The LED ALARM is also lighted when the Load is not protected by UPS or in case Q1 is open.
•
LED STOP OPERATION (red color)
It warns about the imminent Inverter stop (default parameter = 3 min.) and the consequent Load shutdown as result of:
•
The battery is fully discharged and the Load cannot be transferred on Utility .
Overtemperature or overload condition (>102%) and the Load cannot be transferred on Utility .
Bypass
Data regarding Bypass .
See Section 6.2
.
Rectifier
Data regarding Rectifier .
See Section 6.2
.
Load output
Data regarding Load .
See Section 6.2
.
Battery
Data regarding Battery .
See Section 6.2
.
Green color: indicates battery charged.
Yellow color: indicates STOP OPERATION status.
Red color: indicates low battery.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 27/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
LEDs on Synoptic Diagram
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/Battery charger
LED 4 Automatic Bypass
LED 5 LOAD
Examples of typical scenarios in the Synoptic Diagram:
Load supplied by Inverter Load supplied by Automatic Bypass eBoost Operation Mode Load supplied by Battery
IEMi Operation Mode, unit on-line IEMi Operation Mode, unit stand-by
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 28/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.2
MEASURES
MEASURES
In this mode the keys perform the following functions:
The MEASURES mode is entered any time the
“ MEASURES ” key is pressed.
The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like AC, DC and various statistics.
Return to HOME screen.
Shows the main screen EVENTS .
See Section 6.3
.
Shows the main screen SETUP .
See Section 6.4
.
Shows the main screen COMMANDS .
See Section 6.5
.
Shows the operating status of the RPA PARALLEL SYSTEM .
See Section 6.6
.
Key to reset general alarm and buzzer.
Shows the screen Battery .
Shows the screen Rectifier .
Shows the screen Bypass .
Shows the screen Inverter .
Shows the screen Load .
Shows the screen Booster .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 29/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
BATTERY SCREEN
Voltage
The battery voltage.
Current
The battery current (negative values correspond to the discharge of the battery).
Temperature
The temperature of the battery (“XXX” indicates sensor disabled).
Autonomy
The estimated backup time with the present Load.
Note: the backup time is computed given the unit load.
Therefore, during IEMi Operation Mode , on-line units may show a reduced backup time.
However, following a power outage, all Inverters are forced on-line.
Therefore, during battery operation every unit shows the true battery autonomy.
Charge level
The battery charge level.
On battery time
Total operating time of the UPS on battery (in hours).
BATTERY DISCHARGE COUNTER / Residual Charge Level
The number of discharges combined with the percentage of the available residual battery capacity at the time utility power is restored.
Battery charger status
Battery charge status (Off / Float / Boost).
RECTIFIER SCREEN
Frequency
The input frequency of the Rectifier.
Voltage L1 / Voltage L2 / Voltage L3
3-phase Utility voltage PHASE /NEUTRAL .
Voltage DC-link 1
DC-Link 1 voltage.
Voltage DC-link 2
DC-Link 2 voltage.
Main failure count
Total number of times a gap of utility in the Rectifier has been reordered.
Temperature
Rectifier inlet L1 Coil temperature (Normal / Alarm).
Temperature a
Temperature of the Rectifier bridge (lower module).
Temperature b
Temperature of the Rectifier bridge (upper module).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 30/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
BYPASS SCREEN
Frequency
The frequency of the input Utility.
Voltage L1 / Voltage L2 / Voltage L3
3-phase Utility voltage PHASE
/NEUTRAL.
Current L1 / Current L2 / Current L3
Input Utility current for the 3-phases.
Main failure count
The total number of minor Utility faults (Bypass Utility out of tolerance faults).
Number of fast transients
The number of fast transients occurred on the bypass utility on the last seven days.
Bypass quality index
The statistic evaluation in % (100= good; 0= bad) of the Bypass utility.
Status
Bypass status: free / blocked.
INVERTER SCREEN
Frequency
The output frequency of the Inverter.
Voltage L1 / Voltage L2 / Voltage L3
3-phase output voltage
PHASE/NEUTRAL.
Status
The synchronization status of the
Inverter with respect to Utility:
-
-
Synchronized.
Not synchronized.
Temperature
“XXX” indicates disabled function.
Temperature a
The temperature of the Inverter bridge (lower module).
Temperature b
The temperature of the Inverter bridge (upper module).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 31/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Active power
Apparent power
Power factor
Status
Inverter operating time Total operating time for the Inverter (in hours).
Apparent power
UPS operation time
Active Power eBoost operation time
Overload counter
IEMi operation time
Load active power (kW) for each phase.
Load apparent power (kVA) for each phase.
Load power factor: + inductive load / - capacitive load
Source of the power supplied to the Load.
Total apparent Load power (kVA).
Total operating time for the UPS (in hours).
Total effective Load power (kW).
LOAD SCREEN
Voltage L1 / L2 / L3
Output voltage PHASE/NEUTRAL for each phase.
Current L1 / L2 / L3
The output current as RMS values for each phase.
Percent load L1 / L2 / L3
The output Load as percentage for each phase.
Total operating time for the UPS in eBoost™ Operation Mode (in hours).
This counter is displayed only when eBoost™ Operation Mode is available
(option).
Total number of detected output overloads.
Total operating time for the UPS in IEMi Operation Mode (in hours).
This counter is displayed only when IEMi Operation Mode is available (option).
Voltage DC-link 2
Status
Temperature
Temperature a
Temperature b
BOOSTER SCREEN
Battery voltage
The battery voltage.
Battery current
The battery current (negative values correspond to the discharge of the battery).
Voltage DC-link 1
DC-link 1 voltage.
DC-link 2 voltage.
Booster status (Off / Booster / Charger).
Temperature of the 4 th leg’s bridge.
Booster temperature (lower module).
Booster temperature (upper module).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 32/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.3
EVENTS
EVENTS
The EVENTS mode is entered any time the
“ EVENTS ” key is pressed.
The LCD will display a series of screens corresponding to the last 511 events (User
Log).
In this mode the keys perform the following functions:
Shows the main screen MEASURES .
See Section 6.2
.
Return to HOME screen.
Shows the main screen SETUP .
See Section 6.4
.
Shows the main screen COMMANDS .
See Section 6.5
.
Shows the operating status of the RPA PARALLEL SYSTEM .
See Section 6.6
.
Key to reset general alarm and buzzer.
Shows the screen User Events .
Shows the screen Service Events . Reserved for the GE Service Center .
Shows the previous 50 events.
Shows the previous 5 events.
Shows the next 5 events.
Shows the next 50 events.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 33/91
User Manual TLE Series 160 - 500 UL S2B
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Critical Power
SCREEN ACTIVE ALARMS
Shows active events with their GE standard code and a text describing the event in the selected language.
SCREEN USER LOG
User Log
Chronologically view 5 events per screenshot.
Event characteristic:
Number chronologically assigned to
-
an event (Nr. 511 is the more recent,
Nr. 1 is the first).
Data (MM/DD/YYYY).
Exact hour of the moment when the
-
event occurred (HH/MM/SS/ thousandth).
Number of standard GE code of the event.
Explicit text describing the event in the selected language.
SCREEN SERVICE LOG
Service Log
Chronologically view 5 events per screenshot with service related info.
Event characteristic:
Number chronologically assigned to
-
an event (Nr. 1022 is the more recent, Nr. 1 is the first).
Data (MM/DD /YYYY).
Exact hour of the moment when the
event occurred (HH/MM/SS/ thousandth).
Number of standard GE code of the event.
Page 34/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.3.1
Events (alarms and messages)
Each of the following listed events, alarm or message, can be displayed on the LCD screen , on a PC with the software “GE Data Protection” installed or with the monitoring system “GE iUPSGuard” .
Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the UPS (which are additionally signaled with the LED ALARM and acoustically with the buzzer ), while the messages indicate the various states of operation of the UPS (stored in the events list, but not activating the LED ALARM and the acoustical alarm ).
6.3.2
Alarms list
Code
4000
4001
4004 UPS FAILURE ON PARALLEL SYSTEM
4006
4007
4008
4009
4010
4011
4012
4013
4100
4102
4103
Alarm
SETUP VALUES LOST
REGULATION BOARD FAILURE
BUS JA CRC FAILURE
BUS JB CRC FAILURE
BUS JA FAILURE
BUS JB FAILURE
CONNECTIVITY BUS FAILURE
EARTH LEAKAGE CURRENT
LOAD GROUND FAULT
CAN BUS FAILURE
RECTIFIER FUSES FAILURE
K4 CLOSING FAILURE
K4 OPENING FAILURE
Description
Parameters are lost and have been replaced with default values.
Please contact nearest GE Service Center for intervention.
A blocked DSP on the Control board causes this alarm, and consequently the shut-down of Rectifier and Inverter and the opening of K3.
The master unit detected the slave unit missing on the communication bus even though switch Q1 is still closed.
The parallel communication bus system is subject to high errors rate on channel JA.
The parallel communication bus system is subject to high errors rate on channel JB.
There is an interruption in the channel JA of the parallel communication bus system.
There is an interruption in the channel JB of the parallel communication bus system.
The connectivity communication bus is faulty or interrupted.
The unit has detected an earth leakage current above a configured threshold (typically 5% of the maximum rated input current).
Applicable to 3-wire (3ph+PE) distribution only.
The unit has detected load ground current above a configured threshold.
Applicable to 3-wire (3ph+PE) distribution only.
The Control Panel communication bus is faulty or interrupted.
The u-switch mounted on the Rectifier input fuses indicates a blown fuse, and consequently it is shut down.
Clearance of this condition allows you to restart the
Rectifier.
K4 not closed despite a closing command being issued. Signaled by auxiliary contact.
Rectifier cannot start.
K4 not open despite an opening command being issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 35/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Code
4104
4105
4106
4110
4115
4116
4117
4118
4121
4125
Alarm
BATTERY FUSES FAILURE
RECTIFIER OVERTEMPERATURE
RECTIFIER TRANSFORMER
OVERTEMPERATURE
RECTIFIER UTILITY OUT OF
TOLERANCE
LOW BATTERY VOLTAGE
HIGH BATTERY VOLTAGE
BATTERY EARTH FAULT
BATTERY FAULT
HIGH DC RIPPLE
HIGH DC-LINK VOLTAGE
Description
This function, when enabled on input programmable relays (password required), warns the user about the external Battery Fuses failure or MCB opening.
Signaled by NO free contact.
Temperature sensor indicates a situation of overtemperature on the Rectifier bridge.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as long as this condition persists.
The temperature sensor inside the input transformer winding indicates overtemperature.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as long as this condition persists.
Rectifier Input Utility is out of tolerance (voltage, frequency or phase).
The Battery has been discharged and reached
“stop operation” time-out (default 3 minutes), and the Inverter will be shut down.
It will restart automatically only when the Battery has recharged enough for a minimum runtime.
Dangerous high DC Voltage caused Inverter shutdown.
Inverter restarts automatically after Battery returns to floating voltage.
A leakage current to earth has been detected on the DC circuit.
During battery test the voltage falls under the critical level (depending setting parameters).
Battery test is stopped.
A high ripple is present in the battery voltage.
Detection of high voltage on the DC-link.
The rectifier, booster and Inverter will switch off for protection purposes.
The rectifier may only be switched on again if the
DC-Link’s voltage value falls below 430V.
4126 4 th LEG CONTROL SATURATION (Imax) The current in the fourth leg has reached its highest
4130 TURN ON RECT. OR SHUTDOWN UPS
Rectifier and Inverter are OFF.
The DC power supply is discharging the Battery.
4140
4141
4142
RECTIFIER CONTROL FAILURE
ISMAX DETECTION RECTIFIER
RECTIFIER CURRENT MAX
Rectifier must be restarted or Battery must be disconnected in order to avoid damage.
Rectifier Voltage hasn’t reached the set value
(probably fault on regulation loop).
LED Rectifier on control panel is blinking.
After 3 IS-Max condition within the time frame specified in respective parameter, the Rectifier remains shut-down.
Will cause immediate shut-down of the Rectifier.
Based on the value inserted in the respective parameter.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 36/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Code
4143
4146
Alarm
BOOSTER/BATTERY CHARGER
CURRENT MAX
4TH LEG DRIVER FAILURE
Description
Detection of maximum current in the booster/battery charger.
The Booster/Battery charger and Inverter will switch off for protection purposes.
The Booster’s driver indicates the presence of a defect which switches the power off.
4147 BATTERY CHARGER DRIVER FAILURE The Battery charger driver indicates a defect,
4150 BOOSTER OVERTEMPERATURE
The temperature of the booster bridge exceeds the machine’s set limit or the coil’s sensor is on.
4151
4301
4304
4305
4307
4TH LEG OVERTEMPERATURE
INVERTER FUSES
K7 CLOSING FAILURE
K7 OPENING FAILURE
INVERTER TRANSFORMER
OVERTEMPERATURE
The temperature of the 4 th leg’s bridge exceeds the machine’s set limit.
The alarm signals an Inverter outlet fuses fault, causing it to switch off immediately.
It may only be manually switched on after the alarm has ceased.
K7 not closed despite a closing command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
K7 not open despite an opening command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
The temperature sensor of the Inverter Transformer indicates overtemperature.
Elapsed “stop operation” time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
4308
4309
4310
4311
4312
4320
4321
4340
DC FUSES FAILURE
DRIVER FAILURE
IGBT RECTIFIER DRIVER FAILURE
BOOSTER DRIVER FAILURE
INVERTER VOLTAGE OUT
OF TOLERANCE
ISMAX DETECTION
HIGH CURRENT SHARING
INVERTER CONTROL FAILURE
Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.
An abnormal condition has been detected on one or more power modules of the Inverter (temperature or overcurrent).
Inverter shut-down and cannot be started as long as the alarm is present.
Indicates a failure on the driver board or the Rectifier
IGBT bridge.
The Rectifier is shut-down.
Driver Booster error signal.
Inverter Output Voltage is out of the tolerances ( ±
10%).
Inverter is switched OFF.
Detection of Inverter Bridge (Is) current limit causing the Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can be restarted manually.
A high exchange current value is detected between the UPS of the Parallel System.
The “Slave” oscillator is not in synchronized with the
Master; thus causing the shut-down of its Inverter.
If after a restart the condition remains, the LED inside the Inverter symbol on the panel will not light up, indicating that this Inverter cannot supply the
Load anymore.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 37/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Code
4404
4405
4406
Alarm
K6 CLOSING FAILURE
K6 OPENING FAILURE
SSM FAILURE
4410 BYPASS UTILITY OUT OF TOLERANCE
4420
4421
4520
4522
4530
4531
4563
4570
4571
4581
4608
K3 CLOSING FAILURE
K3 OPENING FAILURE
NO INVERTER POWER
FAN FAILURE
LOAD LOCKED ON UTILITY
LOAD ON UTILITY BY ERROR
DETECTOR
EMERGENCY OFF ACTIVATED
OVERLOAD
OVERLOAD: LOAD ON UTILITY
INVERTER AND UTILITY
NOT SYNCHRONIZED
ECO CONFIG FAILURE
Description
K6 open despite a closing command being issued.
Signaled by auxiliary contact.
The Load cannot be supplied by Automatic Bypass.
K6 closed despite an opening command being issued. Signaled by auxiliary contact.
A faulty current has been detected in the staticswitch causing the opening of the contactor K6 for
10 seconds.
After 3 times K6 remains definitively open.
Only a GE Service Technician can reset the alarm.
The Utility Bypass Voltage is out of the tolerances ( ±
10%).
K6 opens, synchronization with Utility is inhibited and transfer to Utility is blocked.
K3 open despite a closing command.
Inverter is switched OFF.
It can be restarted manually after recovery of the alarm condition.
K3 not open despite an opening command.
Be aware the DC Capacitors could remain charged.
The Load supplied by Utility exceeds the Inverter power.
The Load remains supplied by Utility until the alarm stays ON.
The Fan Control Board indicates a malfunction of one or more ventilators.
Load is locked on Utility because 3 transfers on
Utility have been detected in a short time (default 30 sec.).
The transfer will be free after a time defined in parameter (default 30 sec.).
Load is transferred to Utility because the error detector detected a disturbance on the output voltage.
Alarm after detection of an “EPO - Emergency Power
Off” from an external safety device connected on
Customer Interface Board.
Consequently K4, K6, K7 open, Rectifier, Inverter and
SSM are switched Off.
The UPS system is in an overload condition > 105% on Inverter, or > 150% on Utility.
With Utility unavailable, a sequence of “stop operation” starts.
Time out depends on degree of overload.
With Utility Bypass supply available and Load
> 115%, the Load is transferred on Utility.
Load will be transferred again automatically on
Inverter when Load < 100%.
The voltages of Utility and Inverter are not synchronized, which causes the opening of K6.
The propagation of the eBoost / IEMi configuration to other units in a Parallel System failed.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 38/91
User Manual TLE Series 160 - 500 UL S2B
Code
4697
4698
4700
4701
4702
4900
4955
4998
4999
Critical Power
Alarm
BATTERY OVERTEMPERATURE
BATTERY POWER INSUFFICIENT
DC LOW
POWER SUPPLY BOARD FAILURE
LOSS OF REDUNDANCY
LOAD LOCKED ON INVERTER
OVERTEMPERATURE
LOAD OFF DUE TO EXTENDED
OVERLOAD
LOAD OFF DUE TO LOW BATT. OR
TEMP.
Description
Detection of Battery overtemperature condition.
Only a GE Service Technician can reset the alarm.
In case of Utility Failure, with the actual Load, the run time would be below stop operation time
(default 3 minutes).
Battery voltage is at the lowest limit.
Inverter will remain Off until the battery voltage reaches the value in parameter.
Detection of a failure on the Power Supply Board, in particular from the DC supply.
Can be enabled or disabled with respective parameter.
A time of lost redundancy superior than specified in respective parameter was detected.
The Load is locked on Inverter after 3 Load transfers within 30 seconds.
After time out (default 30 sec.) Bypass will be free.
An overtemperature condition has been detected on
Inverter.
Elapsed “stop operation” time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
Load Off after time-out of “stop operation” for overload on Inverter (time depending on the % of overload).
Load Off after time-out of “stop operation” with missing Utility due to Battery low voltage or overtemperature condition.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 39/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.3.3
Messages list
Code
4002
4144
4145
4148
4149
4161
4162
4003
4111
4119
4120
4122
4123
4124
4163
4164
4302
Message
WATCHDOG RESET
SENSOR AUTO-CALIBRATION ERROR
RECTIFIER UTILITY OK
BATTERY TEST STARTED
BATTERY TEST STOPPED
MANUAL BOOST CHARGE START
AUTOMATIC BOOST CHARGE START
MANUAL/AUTOMATIC BOOST CHARGE
STOP
BOOSTER ON
BOOSTER OFF
BATTERY CHARGER ON
BATTERY CHARGER OFF
RECTIFIER ON
RECTIFIER OFF
GENERATOR ON
GENERATOR OFF
INVERTER CANNOT BE TURNED ON
Description
The microprocessor has detected an incorrect operation:
Transfers the load on utility and performs a program reset.
The Inverter will restart automatically and will supply the load.
The voltage/current reading were not correctly calibrated when the UPS was switched on.
Rectifier Input Utility is again within the admitted tolerance (voltage, frequency and phase).
Start of Manual or Automatic Battery Test.
End of Manual or Automatic Battery Test.
Recharging has been manually activated from the control panel, bringing the final load up to the value of the respective parameter.
After the battery has discharged, an automatic boost charge has started to recharge the battery based on pre-defined settings.
The automatic boost charge has finished. The battery’s voltage will return to the maintenance value.
A manually activated boost charge will finish if: it is manually interrupted, the initial timer setting has expired, or the rectifier is not functioning correctly (Alarm 4140).
The battery voltage will return to the maintenance value.
The booster is switched ON.
It transfers energy from the battery to the DClink.
The booster is switched Off.
The battery charger is switched on and is charging the battery.
The battery charger is switched off.
Rectifier started.
Rectifier shut-down.
Customer Interface (X1 - 11, 22) received a Genset ON signal.
Operating mode depend on setting of
Parameters.
Customer Interface (X1 - 11, 22) received a Genset OFF signal.
Function Bypass enabled depends on setting of
Parameter.
Inverter cannot be switched on because one of the following conditions is still present:
- Overtemperature - K7 opening Failure
- Low Battery Voltage - High Battery Voltage
- Inverter Fuses
- Overload
- DC Low
- EPO - Emergency Power Off
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 40/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Code
4303
4361
4362
4411
4500
4521
4534
4535
4536
4561
4562
4564
4567
Message
INVERTER CANNOT BE TURNED OFF
INVERTER ON
INVERTER OFF
BYPASS UTILITY OK
COMMAND LOAD OFF
NO BYPASS POWER
MULTIPLE LOAD TRANSFER
BYPASS LOCKED
BYPASS FREE
LOAD OFF
DETOUR ON
DETOUR OFF
COMMAND LOAD ON UTILITY
Description
Inverter cannot be switched OFF, because the
Load cannot be switched to Utility (voltage out of tolerance, not synchronized, BP blocked).
The command to start the Inverter has been activated on the control panel.
The command to switch OFF the Inverter has been activated by the control panel or automatically for alarm presence.
Bypass Input Utility is again within tolerance
(voltage, frequency and phase).
Disconnection of the Load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop Operation.
With the Load supplied by Automatic Bypass, a
Utility Failure or K6 opening occurred.
2 transfers Inverter- Utility have been detected in a short time (default 30 sec.).
Bypass is not available.
Contactor K6 is open, SSM deactivated.
Bypass is enabled.
Contactor K6 is closed.
Push-button “Load Off” on the UPS Control Panel has been pressed, with the output circuit switch
Q1 closed.
The auxiliary contact indicates that “Q2 -
Manual Bypass” was closed.
The auxiliary contact indicates that “Q2 -
Manual Bypass” was opened.
The control unit received a command to transfer the Load on Utility.
4568
4572
COMMAND LOAD ON INVERTER
NO MORE OVERLOAD
The control unit received a command to transfer the Load on Inverter.
End of the overload condition detected with alarm 4570.
4580 INVERTER AND UTILITY SYNCHRONIZED The voltages of Inverter and Utility Bypass are
4582
4583
4600
4601
COMMAND NOT TO SYNCHRONIZE
COMMAND TO SYNCHRONIZE
COMMAND UPS ON
COMMAND UPS STAND BY
Command not to synchronize with Utility.
Command to synchronize with Utility.
The eBoost operation mode function has been disabled or the programmed time is expired.
The UPS returns to VFI mode supplying the Load normally by Inverter.
The function eBoost operation mode is enabled, and according to the time program the UPS will
4602
4603
Q1 OPEN
Q1 CLOSED run in eBoost mode, supplying the Load normally by utility.
The auxiliary contact indicates that the output switch Q1 was opened.
The auxiliary contact indicates that the output switch Q1 was closed.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 41/91
User Manual TLE Series 160 - 500 UL S2B
Code
4604
4605
4606
4607
4609
4699
4763
4764
4798
4799
Critical Power
Message
COMMAND IEMi ON
COMMAND IEMi OFF eBoost/IEMi ACTIVATION ALLOWED eBoost/IEMi ACTIVATION INHIBITED eBoost INHIBITED - LOW LOAD
BATTERY TEST IMPOSSIBLE
REMOTE CONTROL ON
REMOTE CONTROL OFF
SERVICE KEY ACTIVATED
SERVICE KEY DEACTIVATED
Description
The IEMi Operation Mode function is enabled, and according to the time program the UPS system will run in IEMi Operation Mode.
The IEMi Operation Mode has been disabled or the programmed time is expired. eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation of the functions.
Customer Interface Board (X1 - 11, 22) received an eBoost/IEMi control signal. eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited. eBoost™ Operation Mode inhibited due to minimal load not reached.
Automatic Battery Test is not possible due to:
-
-
No Utility Rectifier or Bypass.
Battery not fully charged.
-
Load is below 10% or above 80%.
Test is postponed for 1 week.
Inverter can be started or shut-down by remote control.
Commands source can be chosen depending on the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
Inverter cannot be started or shut-down by remote control.
Commands source can be chosen depending on the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
The Service Key validity period has expired.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 42/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.4
SETUP
SETUP
The SETUP mode is entered any time the
“ SETUP ” key is pressed.
This screen allows the user to modify some parameters permitting to adapt some functions of the UPS to his/her needs, described as follows.
The LCD will display a series of screens containing the user parameters, accessible without password protection.
In this mode the keys perform the following functions:
Shows the main screen MEASURES .
See Section 6.2.
Shows the main screen EVENTS .
See Section 6.3
.
Return to HOME screen.
Shows the main screen COMMANDS .
See Section 6.5
.
Shows the operating status of the RPA PARALLEL SYSTEM .
See Section 6.6
.
Key to reset general alarm and buzzer.
Shows the screen User .
Shows the screen Service Basic .
Reserved for the GE Service Center , at this level the parameters access is protected by a code .
Shows the screen Service Full .
Reserved for the GE Service Center , at this level the parameters access is protected by a code .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 43/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Parity
Data bits
Stop bit
Handshake
PRINTER SCREEN
The UPS is capable of communicating to a serial printer, to printout disparate information.
Please be sure to have a serial printer with a serial RS232 interface.
This is the only printer-interface supported by the UPS.
Baudrate
This parameter controls the baud rate used for data transmission.
This parameter controls the parity used for data transmission. odd / even / None can be selected.
In case “None” has been set, automatically the parameter “Data bits = 8” is used, independently of the value of “Data Bits” set.
This parameter controls the length of the data word on the serial line during data transmission.
Parameter not programmable.
This parameter is used to determine the communication protocol used when printing.
Valid values are “XON” standing for the XON/XOFF protocol or “None” standing for any protocol.
By using the keys MEASURES / ALARMS / PARAMETERS / ALL it is possible to print selected data
PRINTER
COMMANDS
NOTE !
Please configure your printer with the following parameters :
115200/None/8/2/None (115200 bauds/sec, no parity, 8 bits, no Handshake).
Time
Language
UPS name
DISPLAY SCREEN
Date
You can adjust the date of the real time clock existing in the UPS by the means of this parameter ( “mm-month, dd-day, yyyy-year” ).
The value you enter is thoroughly checked to be a correct date in the format “MM.DD.YYYY” .
You can adjust the time of the real time clock existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a correct time in the format
“HH.MM.SS” . The time is specified in AM/PM format.
This parameter allows the choice of language used to display the information.
Valid choices are: English, German, Italian, Spanish, French, Finnish, Polish,
Portuguese, Czech, Slovenian, Chinese, Swedish, Russian and Dutch .
The user can choose the name of the UPS model shown on the main screen (max.
20 characters).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 44/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power eBOOST SCREEN (option)
This screen is displayed only when eBoost™ Operation Mode is available
(option).
Enabled
This parameter (values Yes / No) enables or disables the eBoost™ Operation
Mode .
If the value is “Yes” and the current time is in the interval for the current day, the eBoost™ Operation Mode is active.
In case of RPA Parallel System
If eBoost™ Operation Mode is currently disabled (No) and Q1 is closed, when programming it to enable (Yes) the selected configuration will automatically be propagated to all units in the RPA Parallel System .
The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list .
In order to check the Inverter function, at least 1 minute of VFI mode must be programmed during the week (the Yes/No parameter is automatically disabled if this condition is not satisfied) .
In case this minimum time in VFI mode is not respected, the eBoost™ Operation Mode will be disabled .
If the value is “No” , the UPS is normally operating in VFI / double conversion mode at all times .
When the UPS is in eBoost™ Operating Mode the eBoost LED is ON (green light).
NOTE !
The configuration of the activation schedule can only be updated when eBoost™ Operation
Mode is disabled (Enabled: No) .
DAY
For the weekdays from “Monday to Sunday”, the edit mode (edit day) allows to define time intervals when the UPS is operating in eBoost™ Operation Mode . The hour is given in 24-hour format.
These intervals are defined by:
Start Time: The hour of the day after which the eBoost™ Operation Mode is enabled.
The eBoost™ Operation Mode is enabled until the following “Stop Time” time is reached
(the “Stop Time” time of the same day if this is later than the “Start Time” time, the “Stop
Time” time of the following day otherwise).
Stop Time: The hour of the day before which the eBoost™ Operation Mode is enabled.
The eBoost™ Operation Mode is enabled starting from the preceding “Start Time” time (the “Start Time” time of the same day if this is earlier than the “Stop Time” time, the “Start Time” time of the previous day otherwise).
Identical times for “Start Time” and “Stop Time” maintain the existing mode only in case the previous command was “Start Time” and the following command will be “Stop Time” .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 45/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
HOURS/DAY
The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the operation mode parameter window (ceiling value).
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
• Date and Time.
• eBoost™ screen how many hours of eBoost™ Operation Mode have been selected for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from the Inverter. eBoost™ Operation Mode is only possible if the UPS load exceeds a minimum threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI mode .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 46/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
IEMi SCREEN (option)
This screen is displayed only when IEMi
Operation Mode is available (option).
Enabled
This parameter (values Yes/No) enables or disables the IEMi Operation Mode .
If the value is “Yes” and the current time is in the interval for the current day, the
IEMi Operation Mode .
Redundancy
Redundancy level: N+1, N+2.
Note: the redundancy level can only be updated when IEMi Operation Mod e is disabled (Enabled: No).
In order to enjoy the benefits of IEMi Operation Mode operation a system programmed for N+1 redundancy requires a parallel installation of at least three UPSs, while four UPSs are required for N+2 redundancy .
The IEMi Operation Mode must be available on all units in a Parallel System .
In case of RPA Parallel System
If IEMi Operation Mode is currently disabled (No) and Q1 is closed, when programming it to enable (Yes) the selected configuration will automatically be propagated to all units in the RPA Parallel System .
If IEMi Operation Mode is currently enabled (Yes) and Q1 is closed, when programming it to disable (No) all stand-by Inverters in the system will be switched on-line.
The activation / deactivation of IEMi Operation Mode is indicated each time in the event list. In order to force a test of all Inverters in the system, at least 1 minute of normal operation must be programmed during the week (the Yes/No parameter is automatically disabled if this condition is not satisfied). In case this minimum time in normal VFI operation is not respected, the IEMi Operation Mode will be disabled. If the value is “No”, the UPS is operating in normal VFI / double conversion mode at all times.
When the UPS is in IEMi Operating Mode the IEMi LED is ON (green light).
NOTE !
The configuration of the activation schedule can only be updated when IEMi
Operation Mode is disabled (Enabled: No).
DAY
For the weekdays from “Monday to Sunday” , the edit mode (edit day) allows to define time intervals when the UPS is operating in IEMi Operation Mode . The hour is given in 24-hour format.
These intervals are defined by:
Start Time: The hour of the day after which the IEMi Operation Mode is enabled.
The IEMi Operation Mode is enabled until the following “Stop Time” time is reached (the
“Stop Time” time of the same day if this is later than the “Start Time” time, the “Stop
Time” time of the following day otherwise).
Stop Time: The hour of the day before which the IEMi Operation Mode is enabled.
The IEMi Operation Mode is enabled starting from the preceding “Start Time” time (the “Start Time” time of the same day if this is earlier than the “Stop Time” time, the “Start Time” time of the previous day otherwise).
Identical times for “Start Time” and “Stop Time” maintain the existing mode only in case the previous command was “Start Time” and the following command will be “Stop Time” .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 47/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
HOURS/DAY
The number of IEMi Operation Mode hours per weekday “Monday to Sunday” is displayed in the operation mode parameter window (ceiling value).
NOTE !
To avoid undesired IEMi Operation Mode, verify:
• Date and Time.
• IEMi screen how many hours of IEMi Operation Mode have been selected for each day of the week.
NOTE !
For IEMi Operation Mode to become active a manual Inverter start is required at start-up and after a Load Off reset.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
TOUCH SCREEN
This screen permits the adjustment
( “Calibrate” key) of the LCD’s “Touch
Screen” sensitivity.
IDENTIFICATION SCREEN
ID
Number of UPS in the RPA Parallel
System (0 for single unit).
Model
UPS model, power range and series number.
S/N
The UPS serial number.
UPS SW version
The UPS software version.
Display SW version
The LCD display software version.
Page 48/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.5
COMMANDS
COMMANDS
The COMMANDS mode is entered any time the “ COMMANDS ” key is pressed.
Allows the user to execute UPS operation commands.
In this mode the keys perform the following functions:
Shows the main screen MEASURES .
See Section 6.2.
Shows the main screen EVENTS .
See Section 6.3
.
Shows the main screen SETUP .
See Section 6.4
.
Return to HOME screen.
Shows the operating status of the RPA PARALLEL SYSTEM .
See Section 6.6
.
Key to reset general alarm and buzzer.
Shows the screen Commands 2 .
Shows the screen Commands 1 .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 49/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
COMMANDS 1 SCREEN
Allows the user to execute UPS operation commands.
Rectifier
Rectifier ON
Rectifier switching ON command.
Rectifier RESET
Rectifier restore command.
Reserved for the GE Service Center .
Led Rectifier status
Indicates the Rectifier’s status: ON = lit OFF = turned Off
Inverter
Inverter ON
Inverter switching ON command.
NOTE !
When eBoost™ Operation Mode or IEMi Operation Mode is enabled, control of
Inverter status and selection of the feed path is done autonomously by the
UPS control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™
Operation Mode or IEMi Operation Mode is enabled.
Inverter OFF
Inverter switching OFF command.
This command is also used as “ EPO - Emergency Power Off” reset after the contact closing.
NOTE !
Inverter OFF command is disabled when eBoost™ Operation Mode or IEMi
Operation Mode is enabled.
Led Inverter status
It indicates the Inverter status:
ON / OFF / Pre-charge / Pre-charge completed / Soft-start
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 50/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Module shutdown
System shutdown
Module shutdown
Load Off command for a single UPS.
NOTE !
This command will immediately disconnect the Load.
“Module shutdown” cannot disconnect the UPS from the Load with “Q2 -
Manual Bypass switch” (only if provided by customer) closed.
For the RPA Parallel System
In an RPA Parallel System, the “Module shutdown” command disconnects the
Load to the selected unit only (“Q1 – UPS Output switch” closed).
Module shutdown RESET
“Module shutdown” restore command for an individual UPS.
Led Module shutdown status
Shows the “Module shutdown” status: ACTIVE / NOT ACTIVE
Booster
System shutdown
Load Off command for an RPA Parallel System .
NOTE !
This command will immediately disconnect the Load.
“System shutdown” cannot disconnect the RPA Parallel System from the
Load with “Q2 - Manual Bypass switch” (only if provided by customer) closed.
For the RPA Parallel System
If “System shutdown” is pressed on one unit connected to the Parallel Bus (“Q1 –
UPS Output switch” closed), all the units are separated from the Load.
System shutdown RESET
“System shutdown” restore command for a RPA Parallel System .
For the RPA Parallel System
The “System shutdown reset” must be done only on one unit connected to the
Parallel Bus (“Q1 – UPS Output switch” closed).
Led System shutdown status
Shows the “System shutdown” status: ACTIVE / NOT ACTIVE
Only for GE Service Center .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 51/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
COMMANDS 2 SCREEN
Allows the user to execute UPS operation commands.
System on bypass
Function not enabled.
Battery Charger
Function not enabled.
Buzzer TEST
Acoustical alarm test (acoustical alarm should be always activated).
Module shutdown procedure
Guides throught the procedures to shutdown a single UPS or a RPA Parallel System unit.
Attention : For a single UPS this implies the load disconnection.
Module start-up procedure
Guides throught the procedures to start-up the UPS.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 52/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
6.6
RPA PARALLEL SYSTEM
RPA
PARALLEL SYSTEM
(option)
The RPA PARALLEL SYSTEM is entered any time the “ RPA ” key is pressed.
This screen is only displayed when the
RPA Parallel System is available (option).
The LCD screen will provide some information on the RPA Parallel System.
In this mode the keys perform the following functions:
Shows the main screen MEASURES .
See Section 6.2.
NOTE! During IEMi Operation Mode , the “Percent Load” information is computed based on on-line units only.
Shows the main screen EVENTS .
See Section 6.3
.
Shows the main screen SETUP .
See Section 6.4
.
Shows the main screen COMMANDS .
See Section 6.5
.
Return to HOME screen.
Key to reset general alarm and buzzer.
Shows the screen for the next RPA Parallel System units
Shows the screen of the previous RPA Parallel System units .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 53/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
Description of the RPA Parallel System screen’s main elements
RECT Rectifier green color = On / grey color = Off
CHRG / BST Battery Charger / Booster green color = On / grey color = Off
INV Inverter green color = On / grey color = Off
BYP Automatic Bypass green color = On / grey color = Off
UPS1÷6
M
Number of UPS in the RPA Parallel System
Master unit of the RPA System Parallel
Input Utility status (for RECT – Rectifier and BYP - Bypass)
Battery status (for CHRG – Battery Charger) green color = On / grey color = Off
Q1 Load output switch
Q2 Manual Bypass switch
(only if provided by customer)
Open
Closed
Examples of the main RPA Parallel System unit status situations
Open
Closed
UPS with Load supplied by Inverter or
On-line UPS in IEMi Operation Mode
UPS with Load supplied by Automatic Bypass
UPS with Load supplied by Battery
UPS in stand-by in an
Redundant RPA Parallel System or
Stand-by UPS in IEMi Operation Mode
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
UPS in eBoost Operation Mode
UPS with Load supplied by Manual Bypass
(only if provided by customer)
Page 54/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7 OPERATION
NOTE !
TLE Series 160 - 500 requires the introduction of a “START-UP KEY” code to perform the first commissioning.
ESC ENTER
The "START-UP KEY" code can be
introduced by a GE Service Technician only.
The introduction of the "START-UP
KEY" code is mandatory to proceed to the first start-up of the UPS.
WARNING !
Verify that the input/output connections have been performed by qualified personnel before connecting Utility input voltage and verify that the equipment is correctly grounded.
Open only the front door, do not remove any panels.
Now you can initiate the start-up procedure of the UPS system.
There is no need for specific knowledge if you follow carefully the step-by-step instructions given below.
However we recommend that at least the initial procedure should be performed by an instructed person.
Check after every step for correct reaction of the UPS (LEDs on the panel), and correct voltage and current measurements, before you proceed to the next step.
If you encounter any problems during the following procedures, you should not continue, but contact your GE Service Center.
This symbol refers to the operations of a RPA Parallel System.
NOTE ! eBoost™ Operation Mode and IEMi Operation Mode MUST BE DISABLED prior to performing any operation, including start-up, shut-down, removing/adding a unit from/to a Parallel System.
Find on the following pages the descriptions of the various procedures of start-up and shut-down for single and parallel UPSs , divided into the following principal chapters:
8.1 PROCEDURES FOR SINGLE TLE Series 160 - 500
8.2
PROCEDURES FOR SINGLE TLE Series 160 - 500 FUNCTIONING AS FREQUENCY CONVERTER
8.3
PROCEDURES FOR TLE Series 160 - 500 PARALLEL SYSTEM
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 55/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.1
PROCEDURES FOR SINGLE TLE Series 160 - 500
7.1.1
Initial start-up of the TLE Series 160 - 500
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
This procedure must be performed for the first start-up following the installation, with the UPS completely switched Off and not powered.
Open the front door and make sure that:
•
•
•
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switches Q1 and CB3 (option) are open (Pos. O) and the “External Battery Protections” must be open (Pos. O).
TLE Series 160 – 200 -225 - 250
CB3
(Option)
TLE Series 300 – 400 - 500
CB3
(Option)
ON
OFF
ON
OFF
I ON
Q1
I ON
Q1
Q1
CB3
LED ALARM
TLES_UL_225-250
UPS Output switch
TLES_UL_400-500
_S2_Switch Q1-CB
3_01
External Battery switch (option)
Command Inverter ON
Command
System shutdown
LEDs on Synoptic Diagram
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED LOAD PROTECTED
Command Inverter OFF
Command
System shutdown Reset
1. Switch-ON the Utility voltage from the input distribution (both Rectifier and Bypass if separated).
The UPS performs a “Self-test” .
A successful termination of the tests will be indicated with Overall test results “OK” .
Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your GE Service Center .
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 56/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
During the first commissioning TLE Series 160 - 500 requests a set-up of the UPS configuration parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The set-up of the UPS configuration parameters must be done only by a GE Service
Technician .
The set-up of mistaken values could compromise the integrity and reliability of the
UPS .
UPS
Language
Date (dd.mm.yyyy)
Time (24h)
Input Frequency
Output Frequency
Inverter Voltage
This parameter allows the choice of language used to display the information.
You can adjust the date of the real time clock existing in the UPS by the means of this parameter.
The value you enter is thoroughly checked to be a correct date in the format “dd.mm.yyyy” .
You can adjust the time of the real time clock existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a correct time in the format “hh.mm.ss” .
The time is specified in 24-hour format.
Input frequency value (50 Hz / 60Hz).
Inverter output frequency value (50 Hz / 60Hz).
Output voltage PHASE/NEUTRAL of the Inverter (277V).
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 57/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
BATTERY
Capacity
Recharge Mode
Float Voltage
Ah capacity of the Battery.
Recharge type of the Battery
-
Normal
-
NiCd
Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid
Battery without boost-charge.
Nickel Cadmium Battery with boost-charge.
Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge .
-
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Valve Regulated Lead Acid Battery (VRLA) :
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge :
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge :
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge :
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Recharge Current
Flooded Lead Acid Battery with boost-charge :
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Stop Operation Time Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
Cells Number of cells of the Battery, see “ Float voltage ”.
Example: 240 battery cells
-
40 blocks / 12Vdc Battery
-
-
80 blocks / 6Vdc Battery
240 blocks / 2Vdc Battery
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer .
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 58/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
2. Close “Q1 - UPS Output switch” (Pos. I) .
• The Load is supplied by the Utility through the Automatic Bypass .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
Attention: check the right DC polarities on both side of the switch/fuse holder!
3. Connect the Battery to the UPS by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch” (option).
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery charger) is lit.
4. Insert the Inverter performing the command "Inverter ON" .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• The Load is automatically transferred from Automatic Bypass to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
5. Operation mode selection.
TLE Series 160 - 500 is delivered normally selected for permanent VFI operation.
If available, the eBoost™ Operation Mode can be enabled and the eBoost Start Time & eBoost Stop Time can be programmed for each day of the week (see Section 6.4 SETUP / eBoost) .
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case of a Utility Failure.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 59/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.1.2
Complete UPS shut-down
NOTE !
Follow this procedure only in case the UPS system and the Load must be completely powered-down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
Initial status:
Load supplied from Inverter .
1.
Perform the command “System shutdown” .
Perform the command “System shutdown ” through the screen: Commands 1 / System shutdown /
Shutdown .
• Load is disconnected from UPS.
• Rectifier and Inverter are shut down and all contactors are opened.
• LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
• LED ALARM is lit.
2. Open “Q1 - UPS Output switch” (Pos. O) .
3. Disconnect the Battery from the UPS by opening, if present, the “CB3 – External Battery switch” (option) and then the “External Battery Protections”.
NOTE ! Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Before performing the next procedure (4) wait 5 minutes for DC-Link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage has reached 10Vdc.
4. Disconnect the Utility from the input distribution .
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 60/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.1.3
Restore to normal operation after “System shutdown” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram after performed the command “System shutdown”, with LOAD NOT
SUPPLIED.
1. Restore the command “System shutdown” .
Restore the command “System shutdown ” through the screen:
Commands 1 / System shutdown / Reset .
• The Load is supplied by the Utility through the Automatic Bypass .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 61/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
2. Connect the Battery to the UPS by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch”
(option).
NOTE !
Before performing the next procedure (3) make sure that the LED 3 (Booster/Battery charger) is lit.
3. Insert the Inverter performing the command “Inverter ON" .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• The Load is automatically transferred from Automatic Bypass to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
END OF PROCEDURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 62/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.1.4
Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram after performed the command “EPO - Emergency Power Off”, with LOAD
NOT SUPPLIED.
1. Restore the “EPO -Emergency Power Off” button.
• Press “MUTE” key to reset Alarm and Acoustical Alarm .
• LED ALARM remains lit.
2. Perform the “Inverter OFF” command .
Perform the “Inverter OFF” command from the screen: Commands 1 / Inverter / OFF .
• Load is transferred to Utility by Automatic Bypass .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Continue →
Page 63/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
3. Connect the Battery to the UPS by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch”
(option).
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery charger) is lit.
4. Insert the Inverter performing the command “Inverter ON" .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• The Load is automatically transferred from Automatic Bypass to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
END OF PROCEDURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 64/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.2
PROCEDURES SINGLE TLE Series 160 - 500 FUNCTIONING AS FREQUENCY
CONVERTER
When the TLE Series 160 - 500 functions as a Frequency Converter , the Automatic Bypass function is disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shut-down for maintenance purposes, also the Load must be shut-down or disconnected.
7.2.1
Initial Start-up of the TLE Series 160 - 500 as frequency converter
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
Open the front door and make sure that:
•
•
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
•
The switches Q1 and CB3 (option) are open (Pos. O) and the “External Battery Protections” must be open (Pos. O).
TLE Series 160 – 200 -225 - 250
CB3
(Option)
TLE Series 300 – 400 - 500
CB3
(Option)
ON
ON
OFF
OFF
I ON
Q1
I ON
Q1
Q1
CB3
LED ALARM
TLES_UL_225-250
UPS Output switch
TLES_UL_400-500
_S2_Switch Q1-CB
3_01
External Battery switch (option)
LEDs on Synoptic Diagram
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED LOAD PROTECTED
Command Inverter ON Command Inverter OFF
Command
System shutdown
1. Switch-ON the Utility voltage from the input distribution.
Command
System shutdown Reset
The UPS performs a “Self-test” .
A successful termination of the tests will be indicated with Overall test results “OK” .
Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your GE Service Center .
LED 4 Automatic Bypass
LED 5 LOAD on UPS
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 65/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
During the first commissioning TLE Series 160 - 500 requests a set-up of the UPS configuration parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The set-up of the UPS configuration parameters must be done only by a GE Service
Technician .
The set-up of mistaken values could compromise the integrity and reliability of the
UPS .
UPS
Language
Date (dd.mm.yyyy)
Time (24h)
Input Frequency
Output Frequency
Inverter Voltage
This parameter allows the choice of language used to display the information.
You can adjust the date of the real time clock existing in the UPS by the means of this parameter.
The value you enter is thoroughly checked to be a correct date in the format “dd.mm.yyyy” .
You can adjust the time of the real time clock existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a correct time in the format “hh.mm.ss” .
The time is specified in 24-hour format.
Input frequency value (50 Hz / 60Hz).
Inverter output frequency value (50 Hz / 60Hz).
Output voltage PHASE/NEUTRAL of the Inverter (277V).
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Continue →
Page 66/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
BATTERY
Capacity
Recharge Mode
Float Voltage
Ah capacity of the Battery.
Recharge type of the Battery
-
Normal
-
NiCd
Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid
Battery without boost-charge.
Nickel Cadmium Battery with boost-charge.
Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge .
-
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Valve Regulated Lead Acid Battery (VRLA) :
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge :
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge :
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge :
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Recharge Current
Flooded Lead Acid Battery with boost-charge :
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Stop Operation Time Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
Cells Number of cells of the Battery, see “ Float voltage ”.
Example: 240 battery cells
-
40 blocks / 12Vdc Battery
-
-
80 blocks / 6Vdc Battery
240 blocks / 2Vdc Battery
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer .
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 67/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
2. Close “Q1 - UPS Output switch” (Pos. I) .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
Before performing the next procedure (4) make sure that the LED 3
(Booster/Battery charger) is lit.
Attention: check the right DC polarities on both side of the switch/fuse holder!
3. Connect the Battery to the UPS by closing the “External Battery Protections” and close, if present, the “CB3 – External Battery switch” (option).
4. Insert the Inverter performing the command “Inverter ON" .
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• Load is now supplied from Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case of a Utility Failure.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 68/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.2.2
Complete shut-down of the TLE Series 160 - 500 as frequency converter
NOTE !
Follow this procedure only in case the UPS system and the Load must be completely powered-down.
Initial status:
Load supplied from Inverter .
1. Perform the command “System shutdown” .
Perform the command “System shutdown ” through the screen: Commands 1 / System shutdown / Shutdown
• Load is disconnected from UPS.
• Rectifier and Inverter are shut-down and all contactors are opened.
• LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
• LED ALARM is lit.
2. Open “Q1 - UPS Output switch” (Pos. O) .
3. Disconnect the Battery from the UPS by opening, if present, the “CB3 – External Battery switch” (option) and then the “External Battery Protections”.
NOTE !
Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Before performing the next procedure (4) wait 5 minutes for DC-Link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage has reached 10Vdc.
4. Disconnect the Utility from the input distribution .
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 69/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.2.3
Restore to normal operation after “System shutdown” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
View of the Synoptic Diagram after performed the command “System shutdown”, with LOAD NOT
SUPPLIED.
1. Restore the command “System shutdown” .
Restore the command “System shutdown ” through the screen:
Commands 1 / System shutdown / Reset
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
2. Connect the Battery to the UPS by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch”
(option).
NOTE !
Before performing the next procedure (3) make sure that the LED 3 (Booster/Battery charger) is lit.
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 70/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
3. Insert the Inverter performing the command “Inverter ON" .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
END OF PROCEDURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 71/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.2.4
Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
View of the Synoptic Diagram after performed the command “EPO -Emergency
Power Off”, with LOAD NOT SUPPLIED.
1. Restore the “EPO -Emergency Power Off” button .
• Press “MUTE” key to reset Alarm and Acoustical Alarm .
• LED ALARM remains lit.
2. Perform the “Inverter OFF” command .
Perform the “Inverter OFF” command from the screen: Commands 1 / Inverter / OFF .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1
(Rectifier) remains lit.
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 72/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
3. Connect the Battery to the UPS by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch”
(option).
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery charger) is lit.
4. Insert the Inverter performing the command “Inverter ON" .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“ LOAD SUPPLIED BY INVERTER” .
END OF PROCEDURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 73/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3
PROCEDURES FOR TLE Series 160 - 500 PARALLEL SYSTEM
7.3.1
TLE Series 160 - 500 Parallel System start-up
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
This procedure must be performed for the first start-up following the installation, with the Parallel
System completely switched Off and not powered.
Open the front door on all UPS units and make sure that:
•
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
•
•
The safety screens are fixed in their position.
The switches Q1 and CB3 (option) are open (Pos. O) and the “External Battery Protections” must be open (Pos. O).
TLE Series 160 – 200 -225 - 250
CB3
(Option)
TLE Series 300 – 400 - 500
CB3
(Option)
ON
ON
OFF
OFF
I ON
I ON
Q1
Q1
Q1
CB3
TLES_UL_225-250
TLES_UL_400-500
_S2_Switch Q1-CB
3_01
UPS Output switch
External Battery switch (option)
LEDs on Synoptic Diagram
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED ALARM LED LOAD PROTECTED
Command Inverter ON Command Inverter OFF
Command
Module shutdown
Command
Module shutdown Reset
Command
System shutdown
Command
System shutdown Reset
1. Switch-ON the Utility voltage, on all UPS units, from the input distribution (both Rectifier and bypass if separated).
The UPS performs a “Self-test” .
A successful termination of the tests will be indicated with Overall test results “OK” .
Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your GE Service Center .
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 74/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
During the first commissioning TLE Series 160 - 500 requests a set-up of the UPS configuration parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The set-up of the UPS configuration parameters must be done only by a GE Service
Technician .
The set-up of mistaken values could compromise the integrity and reliability of the
UPS .
UPS
Language
Date (dd.mm.yyyy)
Time (24h)
Input Frequency
Output Frequency
Inverter Voltage
This parameter allows the choice of language used to display the information.
You can adjust the date of the real time clock existing in the UPS by the means of this parameter.
The value you enter is thoroughly checked to be a correct date in the format “dd.mm.yyyy” .
You can adjust the time of the real time clock existing in the UPS by means of this parameter.
The value you enter is thoroughly checked to be a correct time in the format “hh.mm.ss” .
The time is specified in 24-hour format.
Input frequency value (50 Hz / 60Hz).
Inverter output frequency value (50 Hz / 60Hz).
Output voltage PHASE/NEUTRAL of the Inverter (277V).
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 75/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
BATTERY
Capacity
Recharge Mode
Float Voltage
Ah capacity of the Battery.
Recharge type of the Battery
-
Normal
-
NiCd
Valve Regulated Lead Acid Battery (VRLA), NiCd without boost-charge and Flooded Lead Acid
Battery without boost-charge.
Nickel Cadmium Battery with boost-charge.
Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge .
-
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Valve Regulated Lead Acid Battery (VRLA) :
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge :
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge :
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge :
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Recharge Current
Flooded Lead Acid Battery with boost-charge :
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Stop Operation Time Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
Cells Number of cells of the Battery, see “ Float voltage ”.
Example: 240 battery cells
-
40 blocks / 12Vdc Battery
-
-
80 blocks / 6Vdc Battery
240 blocks / 2Vdc Battery
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer .
Continue →
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 76/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
2. Close “Q1 - UPS Output switch” (Pos. I) on all Units .
• When closing “Q1 - UPS Output switch” on the last unit of the Parallel System , the Automatic Bypass of all
Units connects to the Load .
• Rectifiers start automatically, blinking LED 1 (Rectifier) indicates Soft-start .
• At the end of Rectifier Soft-start , the LED 1 (Rectifier) remains lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
Synoptic Diagram of first unit Synoptic Diagram of other units
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
Attention: check the right DC polarities on both side of the switch/fuse holder!
3. Connect the Battery on all Units by closing the “External Battery Protections” and close, if present, the “CB3 – External Battery switch” (option).
Synoptic Diagram of first unit Synoptic Diagram of other units
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery charger) is lit.
4. Insert the Inverter performing the “Inverter ON” command on first unit .
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER / ON .
• Soft-start of Inverter , indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• In case of sufficient output power, the output will transfer to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic Diagram of first unit
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Synoptic Diagram of other units
Continue →
Page 77/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
5. Insert the Inverter performing the “Inverter ON” command on all other units .
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• As soon as the output power of the Inverters is sufficient to supply the Load , the output of the units with running Inverter will transfer to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY INVERTER” .
Synoptic Diagram of first unit Synoptic Diagram of other units
6. Operation mode selection.
TLE Series 160 - 500 is delivered normally selected for permanent VFI operation.
If available, the eBoost™ Operation Mode can be enabled and the eBoost Start Time & eBoost Stop Time can be programmed for each day of the week (see Section 6.4 SETUP / eBoost) .
If available, the IEMi Operation Mode can be enabled and the IEMi Start Time & IEMi Stop Time can be programmed for each day of the week (see Section 6.4 SETUP / IEMi) .
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case of a Utility Failure.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 78/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3.2
Separate a UPS unit from the Redundant Parallel System
NOTE !
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
NOTE !
The Load is powered by the UPS Redundant Parallel System.
One UPS unit of the Parallel System has to be turned Off, while the Load is shared between the other units supplying the parallel bus.
WARNING !
The control bus cable connecting J1A - J2A and J1B - J2B cannot be connected or disconnected after the system has been powered on.
Initial status
:
Load supplied from all Inverters of the
Redundant Parallel System .
1. Disconnect the Inverter performing the “Inverter OFF” command on the Unit to separate .
1 - Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF .
2 - Repeat the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF .
With Redundant System , performing the “Inverter OFF” command the Inverter shuts down and it will stay OFF.
Performing the “Inverter OFF” command the Load is transferred to the Utility and the Inverter remains operating, it means the system is not redundant.
In this case is not possible to switch-OFF one unit without transferring the Load on Utility .
• Load supplied from Inverter(s) of the other Unit(s) of the Parallel System.
Synoptic diagram of the unit to separate Synoptic diagram of other units
2. Open “Q1 - UPS Output switch” (Pos. O) on the Unit to separate.
• LED ALARM is lit.
Synoptic diagram of the unit to separate
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Synoptic diagram of other units
Continue →
Page 79/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
3. Perform the command “Module shutdown” on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command screen:
“Module shutdown
Commands 1 / Module shutdown /
” through
Shutdown the
.
Synoptic diagram of the unit to separate Synoptic diagram of other units
4. Disconnect the Battery on the Unit to separate by opening, if present, the “CB3 – External
Battery switch” (option) and then the “External Battery Protections”.
Press “MUTE” key to reset Acoustical Alarm . LED ALARM remains lit.
Synoptic diagram of the unit to separate Synoptic diagram of other units
NOTE !
Before performing the next procedure (5) wait 5 minutes for DC-Link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage has reached 10Vdc.
5. Disconnect the Utility supply on the Unit to separate .
LCD display is Off
Synoptic diagram of the unit to separate
END OF PROCEDURE
Synoptic diagram of other units
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest GE Service Center.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 80/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3.3
Reconnect a UPS unit to Redundant Parallel System
NOTE:
The Load is still powered by the other units supplying the parallel bus.
This UPS unit will be powered on and connected to the parallel bus in order to share the Load with each other's.
The high speed bus cable connecting J1A - J2A and J1B - J2B in any case cannot be connected or disconnected after the system has been powered on.
The bus terminals must be properly connected before powering the additional unit.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
Open the front door, of the Unit to reconnect, and make sure that:
•
•
•
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The protection panels are fastened in their correct position.
The switches Q1 and CB3 (option) are open (Pos. O) and the “External Battery Protections” must be open (Pos. O).
1. Switch-ON the Utility voltage, on the Unit to reconnect, from the input distribution (both
Rectifier and bypass if separated).
At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm .
LED ALARM remains lit.
Synoptic diagram of the unit to reconnect Synoptic diagram of other units
2. Close “Q1 - UPS Output switch” (Pos. I) on the Unit to reconnect .
• Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start .
• At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
Synoptic diagram of the unit to reconnect
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Synoptic diagram of other units
Continue →
Page 81/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES
/ Rectifier) !
Before performing the next procedure (4) make sure that the LED 3
(Booster/Battery charger) is lit.
3. Connect the Battery on the Unit to reconnect by closing the “External Battery Protections” and close, if present, the “CB3 – External Battery switch” (option).
Synoptic diagram of the unit to reconnect Synoptic diagram of other units
4. Insert the Inverter performing the command "Inverter ON” on the Unit to reconnect .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• After Soft-start of the Inverter , the Inverter connects automatically to the other Units of the Parallel
System .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY INVERTER” .
Synoptic diagram of the unit to reconnect
END OF PROCEDURE
Synoptic diagram of other units
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 82/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3.4
Complete Parallel System shut-down
NOTE !
The UPS Parallel System and the Load have to be completely powered down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
Initial status:
Load supplied from all Inverters of the Parallel
System .
1. Perform the command “System shutdown” on anyone of the units .
Perform the command “System shutdown ” through the screen:
Commands 1 / System shutdown / Shutdown .
• Load is disconnected from UPS Parallel System.
• Rectifiers and Inverters are shut down and all Contactors are opened.
• LED ALARM is lit.
Synoptic diagram of first unit
2. Open “Q1 - UPS Output switch” (Pos. O) on all Units .
Synoptic diagram of other units
Synoptic diagram of first unit Synoptic diagram of other units
3. Disconnect on all Units the Battery from the UPS by opening, if present, the “CB3 – External
Battery switch” (option) and then the “External Battery Protections”.
Press “MUTE” key to reset Acoustical Alarm . LED ALARM remains lit.
• Wait 5 minutes for DC-Link Capacitors discharge. Use the MEASURES/Rectifier screen to ensure that the
DC-link1 and DC-link 2 voltage has reached 10Vdc .
4. Disconnect the Utility supply on all Units .
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 83/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3.5
Restore to normal operation after “System shutdown” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that all units of the Parallel System are in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram, on all UPS units, after performed the command “System shutdown”, with LOAD NOT SUPPLIED.
1. Restore the command “System shutdown” of the Parallel System .
Restore the command “System shutdown” , on anyone of the Parallel Units, through the screen:
Commands 1 / System shutdown / Reset .
• The Load is supplied by the Utility through the Automatic Bypass of all Units .
• Rectifiers start automatically, blinking LED 1 (Rectifier) indicates Soft-start.
• At the end of Rectifier Soft-start, the LED 1 (Rectifier) remains lit. LED ALARM are lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
Synoptic diagram of first unit
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Synoptic diagram of other units
Continue →
Page 84/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
2. Connect the Battery on all Units by closing the
“External Battery Protections” and close, if present, the “CB3 – External Battery switch”
(option).
NOTE !
Before performing the next procedure (3) make sure that the LED 3 (Booster/Battery charger) is lit.
3. Insert the Inverter performing the “Inverter ON” command on first unit .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter , indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• In case of sufficient output power, the output will transfer to Inverter.
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic diagram of first unit Synoptic diagram of other units
4. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• As soon as the output power of the Inverters is sufficient to supply the Load , the output of the units with running Inverter will transfer to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY INVERTER” .
Synoptic diagram of first unit
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
END OF PROCEDURE
Synoptic diagram of other units
Page 85/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
7.3.6
Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before proceeding, as this procedure will result in the connection of power to the load circuit(s).
NOTE !
Before performing this operation, make sure that all units of the Parallel System are in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the “CB3 -External
Battery switch – option” MUST BE OPEN.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram, on all UPS units, after performed the command “EPO -
Emergency Power Off”, with LOAD NOT
SUPPLIED.
1. Restore the “EPO -Emergency Power Off” button.
• Press “MUTE” key to reset Alarm and Acoustical Alarm .
• LED ALARM remains lit.
2. Perform the “Inverter OFF” command on all Units.
Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF .
• Rectifiers start automatically.
LEDs 1 (Rectifier) blinking, indicates Soft-start .
• After performed the “Inverter OFF” command on the last unit of the Parallel System , the output of all
Units connect to Automatic Bypass .
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY AUTOMATIC BYPASS” .
Synoptic diagram of first unit
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Synoptic diagram of other units
Continue →
Page 86/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier) !
3. Connect the Battery on all Units by closing the “External Battery Protections” and close, if present, the “CB3 – External Battery switch” (option).
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery charger) is lit.
4. Insert the Inverter performing the “Inverter ON” command on first unit .
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter , indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• In case of sufficient output power, the output will transfer to Inverter.
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic diagram of first unit Synoptic diagram of other units
5. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON .
• Soft-start of Inverter indicated with blinking LED 2 (Inverter) .
• At the end of Soft-start the LED 2 (Inverter) remains lit.
• As soon as the output power of the Inverters is sufficient to supply the Load , the output of the units with running Inverter will transfer to Inverter .
• LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram , on all UPS units, must display the status “ LOAD SUPPLIED BY INVERTER” .
Synoptic diagram of first unit
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
END OF PROCEDURE
Synoptic diagram of other units
Page 87/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
8 OPTIONS
8.1
CONNECTIVITY OPTIONS
3-ph SNMP/WEB plug-in adapter
SNMP - Simple Network Management Protocol
The 3-ph SNMP/WEB plug-in adapter is an interface to the Ethernet Network , and provides UPS information via the standard SNMP Protocol (UPS-MIB (RFC-1628);
GE Single MIB; GE Parallel MIB).
The UPS can therefore be managed by a Network Management System (NMS) or by our applications (for instance GE iUPSGuard or GE Data Protection) , which uses this information to determine the state of the UPS in order to guarantee safe and orderly shut-down of the server, when needed.
GE iUPSGuard
GE’s iUPSGuard is a remote monitoring solution for UPS, providing status monitoring and alarm notification that supports all GE UPS product lines, anytime, anywhere. iUPSGuard provides current and detailed information about UPS operation, including its configuration, internal alarms and operating conditions over web. iUPSGuard notifies personnel of critical alarms and events via email or SMS, allowing a User or GE Service Technician to make timely decisions on critical conditions.
In addition, comprehensive data collection and analysis improves diagnostics capability and enhances response time.
Continuous monitoring and ongoing maintenance help ensure maximum performance of your UPS equipment as it protects business critical applications.
GE Data Protection
GE Data Protection software can communicate with the UPS over RS-232 , USB or SNMP to receive status information and measurement values of the UPS. In case of a critical condition (time on battery, remaining battery autonomy time or low battery) for the Load, the software starts a controlled shut-down.
An enhanced alarm management system provides the possibility to start applications, send messages, and send e-mails for every upcoming or disappearing alarm.
8.2
OPTIONS IN UPS CABINET
eBoost™ Operation Mode
High efficiency operating mode, where the load is supplied directly by utility and automatically transferred to Inverter if the voltage is out of prescribed tolerances.
IEMi Operation Mode
High efficiency operating mode for RPA installations operating in low load conditions, where the efficiency is maximized by switching one or more units to a stand-by state, thereby driving the on-line units towards their higher efficiency operating region.
RPA Kit
Redundant Parallel Architecture
Up to 6 units parallel possible for redundancy or capacity in RPA configuration.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 88/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
9 MAINTENANCE
WARNING !
All maintenance and service works must be performed by A GE Service Technician.
9.1
MAINTENANCE
A UPS system, like other electrical equipment, needs periodic preventive maintenance.
A regular maintenance check of your installation guarantees higher reliability of your safe power supply.
GE recommends to perform the first service within 12 months from the commissioning date or within 18 months from delivery date.
Subsequent services to perform every 12 months .
Preventive maintenance work on the UPS can be done only by a GE Service Technicians .
We therefore recommend you sign a Maintenance and Service contract with the local GE Service
Center organization.
9.1.1
Service check
If this lamp lights up during normal operation, the unit has not been serviced for the last 20,000 hours by a GE Service Technician .
Some components of the UPS which need periodic maintenance, if not replaced, could cause a reliability reduction of the supply system
We highly recommend that you contact your GE Service Center for preventive maintenance work.
NOTE !
Never ignore a Service Check alarm!
Failure to perform mandatory preventative maintenance on components documented in the UPS product manual may result in thermal damage to the equipment, its surroundings, and an increased risk of personnel injury.
Refer to Section 9.1.2 to 9.1.6 for this important detail.
9.1.2
Fans and ventilation
We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to guarantee proper air circulation in the unit and in the Battery .
The fans eventually wear out and must be substituted when a UPS alarm is triggered, in order to ensure the reliability of the UPS
9.1.3
Other components with limited lifetime
Various components, such as the DC and AC filter capacitors and the lithium battery on the “ P3 -Control
Panel ” (memory saving), must be systematically substituted in order to maintain the UPS’S reliability.
The substitution of these components is signaled by a UPS alarm going off.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 89/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
9.1.4
Battery
NOTE !
Perform mandatory battery maintenance per battery’s manufacturer product manual. This includes electrical and thermal measurements, inspection, cleaning, replacement and re-torque of connections.
Failure to perform proper maintenance on the battery, per the battery manufacturer’s recommendation, including scheduled battery replacement, may result in thermal damage to the equipment and an increased risk of personnel injury.
GE declines any responsibility for any damage to the system and the surrounding caused by battery when the battery maintenance program is provided by other than
GE itself and GE authorized partners.
We recommend a periodic Manual Battery Test , especially if the Automatic Battery Test is disabled, in order to verify if the Battery can provide the expected backup time in case of Utility Failure .
We recommend that this test is performed at least every 3 months , especially if the Battery is not sufficiently discharged during normal operation.
The discharge time you use should be at least half of the Battery runtime.
For Automatic & Manual Battery Test setting, a special code is required to enter user set-up parameters.
The start-up technician has access to this code and can program this feature during start-up.
Please consider that, if you did a full Battery Test to verify the full runtime of the Battery , the charger needs at least 8 hours to recharge the Battery up to 90% of its capacity.
Long shut-down periods of the UPS system
To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 12 hours every 3 months .
If not the Battery may be permanently damaged.
9.1.5
UPS room conditions and temperature
The UPS room and the Battery Room have to be maintained clean and free from dust.
A high temperature of the UPS room and of the Battery Room affect the lifetime of several components inside the equipment.
The Battery is very sensitive to room temperatures above 77°F (25°C).
9.1.6
Preventive maintenance program
a) Cleaning, a visual inspection and a mechanical inspection of the UPS modules. b) Replacement of defective parts or the preventive replacement of parts with a defined lifetime. c) “Updating” of the equipment (technical improvements subsequent to the delivery). d) Check the calibration of DC voltage and Inverter Output Voltage and Frequency . e) Check of the settings of the electronic regulation, the control and the alarm circuits of the
Rectifier(s) and Inverter(s) . f) Functional checks on Thyristors , Diodes , Transformers , Filter Components , e.g. to ensure that they are operating within the specified design parameters. g) Overall performance test including a Utility Failure simulation with and without the Load . h) Monitoring Battery operation in discharge and recharge mode including any boost charge duties.
NOTE !
Ask to your local GE Service Center to submit the form of Preventive Maintenance
Contract suitable for your specific needs.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 90/91
User Manual TLE Series 160 - 500 UL S2B
Critical Power
10 NOTES
10.1
NOTES FORM
It is recommended to note in this section Notes , with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc.
Date Description Done by
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Page 91/91
User Manual TLE Series 160 - 500 UL S2B
advertisement
Related manuals
advertisement
Table of contents
- 6 IMPORTANT SAFETY INSTRUCTIONS
- 9 LAYOUT
- 9 LAYOUT TLE SERIES
- 11 INTRODUCTION
- 12 DESCRIPTION
- 13 BLOCK DIAGRAM AND MAIN ELEMENTS
- 14 OPERATION MODES
- 14 Normal VFI Operation Mode (Voltage Frequency Independent)
- 14 eBoost™ Operation Mode (option)
- 15 Utility Failure Operation
- 15 Utility Recovery Operation
- 16 Automatic Bypass
- 17 RPA PARALLEL SYSTEM OPERATION
- 17 Introduction to the RPA Parallel System
- 18 Features of RPA Parallel System
- 18 System control
- 18 Synchronization
- 18 Load sharing
- 19 IEMi Operation Mode (option)
- 20 UPS PARALLELED ON THE SAME BATTERY
- 21 SERVICE AND TECHNICAL SUPPORT
- 21 WARRANTY
- 22 RECYCLING INSTRUCTIONS
- 23 CONTROL PANEL
- 24 LCD SCREEN
- 24 HOME SCREEN
- 25 Description of the selection keys
- 26 Description of the signaling LEDs
- 29 MEASURES
- 33 EVENTS
- 35 Events (alarms and messages)
- 35 Alarms list
- 40 Messages list
- 43 SETUP
- 49 COMMANDS
- 53 RPA PARALLEL SYSTEM
- 55 OPERATION
- 56 PROCEDURES FOR SINGLE TLE SERIES
- 56 Initial start-up of the TLE Series
- 60 Complete UPS shut-down
- 61 Restore to normal operation after “System shutdown” with Load not supplied
- 63 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 65 PROCEDURES SINGLE TLE SERIES 160 - 500 FUNCTIONING AS FREQUENCY CONVERTER
- 65 Initial Start-up of the TLE Series 160 - 500 as frequency converter
- 69 Complete shut-down of the TLE Series 160 - 500 as frequency converter
- 70 Restore to normal operation after “System shutdown” with Load not supplied
- 72 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 74 PROCEDURES FOR TLE SERIES 160 - 500 PARALLEL SYSTEM
- 74 TLE Series 160 - 500 Parallel System start-up
- 79 Separate a UPS unit from the Redundant Parallel System
- 81 Reconnect a UPS unit to Redundant Parallel System
- 83 Complete Parallel System shut-down
- 84 Restore to normal operation after “System shutdown” with Load not supplied
- 86 Restore to normal operation after “EPO - Emergency Power Off” with Load not supplied
- 88 OPTIONS
- 88 CONNECTIVITY OPTIONS
- 88 OPTIONS IN UPS CABINET
- 89 MAINTENANCE
- 89 Service check
- 89 Fans and ventilation
- 89 Other components with limited lifetime
- 90 Battery
- 90 UPS room conditions and temperature
- 90 Preventive maintenance program
- 91 NOTES
- 91 NOTES FORM