advertisement
USER’S MANUAL
Variable-frequency drive for
3-phase and single-phase
AC motors
170-543-0004
Copyright
© 2006 by
Bison Gear & Engineering
All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from Bison Gear & Engineering. The information and technical data in this manual are subject to change without notice. Bison Gear &
Engineering and its Divisions make no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of its merchantability and fitness for a given purpose. Bison Gear & Engineering and its Divisions assume no responsibility for any errors that may appear in this manual and make no commitment to update or to keep current the information in this manual.
KC0304
Printed in the United States of America.
Safety Warnings
SHOCK
HAZARD
AVOID
HEAT
KEE
DR
OID
ATION
•
This symbol
denotes an important safety tip or warning. Please read these instructions carefully before performing any of the procedures contained in this manual.
•
DO NOT INSTALL, REMOVE, OR REWIRE THIS
EQUIPMENT WITH POWER APPLIED. Have a qualified electrical technician install, adjust and service this equipment. Follow the National Electrical Code and all other applicable electrical and safety codes, including the provisions of the Occupational Safety and Health Act
(OSHA), when installing equipment.
•
Reduce the chance of an electrical fire, shock, or explosion by using proper grounding, over-current protection, thermal protection, and enclosure. Follow sound maintenance procedures.
It is possible for a drive to run at full speed as a result of a component failure. Bison strongly recommends the installation of a master switch in the main power input to stop the drive in an emergency.
Circuit potentials are at 115 VAC or 230 VAC above earth ground. Avoid direct contact with the printed circuit board or with circuit elements to prevent the risk of serious injury or fatality. Use a non-metallic screwdriver for adjusting the calibration trimpots. Use approved personal protective equipment and insulated tools if working on this drive with power applied.
i
ii
General Information
The Bison Variable Frequency Drive Series are solid-state, variable-frequency AC motor drives. The 170-543-0004 utilizes a 115 or 230 VAC, 50/60 Hz, single-phase input, and is factory calibrated for an output of 0 to 60 Hz. They will operate any 1 HP or smaller, 208/230-volt three-phase-
AC-induction, single-phase permanent split capacitor motor
(see page v) and can be user calibrated for 0 through 120
Hz output.
Although 170-543-0004 inverters can operate over their full speed range, most motors will operate with constant torque over a 10:1 speed range, 6 Hz to 60 Hz, and constant horsepower above 60 Hz. (Inverter-duty motors may operate satisfactorily over a 20:1 speed range.) Some motors can be satisfactorily operated at speeds as low as
50 rpm (speed range 50:1). Below 50 rpm, some motors may show signs of “stepping” or “cogging”, and may run warmer.
*Although the 170-543-0004 will allow a minimum of 0 Hz, the actual minimum frequency is dependent on motor type and load. The motor may need to be derated for low-frequency (30 Hz and lower) operation. Please consult the motor manufacturer.
Many 3-phase inverter manufacturers claim that they can run single-phase motors effectively. This is normally accomplished by wiring only 2 phases; however, this method may cause instabilities due to the lack of feedback from one of the motor connections. Furthermore, motor torque will be reduced considerably because the phases are 120° apart. Although the 170-543-0004 uses this method of connection, its fundamental design enables it to operate efficiently under these conditions.
The 170-543-0004 features solid-state reversing with adjustable acceleration and deceleration. The 170-543-
0004 may also interface with motor thermal protection through the enable circuit.
iii
iv
170-543-0004 FEATURES & BENEFITS
• SOLID-STATE CIRCUITRY
• SOLID-STATE REVERSING
• ADJUSTABLE CARRIER FREQUENCY (4 kHz - 16 kHz)
• MULTIPLE MOTOR OPERATION
• THREE-PHASE AND SINGLE-PHASE MOTOR CONTROL
LED INDICATORS
ADJUSTABLE
CALIBRATION
TRIMPOTS
POWER
(green)
DECEL
ENABLE
(red)
ACCEL
FAULT
(red)
MIN
MAX
TORQUE
(yellow)
BOOST
STANDARD ISOLATION
ACCEPTS A 0 - 5 VDC,
0 - 10 VDC, or 4 - 20 mA
NON-ISOLATED SIGNAL
SLIP COMP
TQ LIMIT
ZERO SET
VOLTAGE DOUBLER
DOUBLES THE OUTPUT
VOLTAGE TO THE AC
MOTOR WHEN 115 IS APPLIED
BRAKE
TIME
BRAKE
CURRENT
Figure 1. 170-543-0004 Features & Benefits
Important Information
Warning
Caution should be taken when operating fan-cooled motors at low speeds because their fans may not move sufficient air to properly cool the motor. Bison recommends “inverter-duty” motors when the speed range is beyond 10:1. v
In addition to standard 3-phase induction motors, the following motor types may be used with the 170-543-0004:
• Permanent split capacitor (PSC)
• Shaded pole
• AC synchronous
The following motor types MAY NOT be used:
• Split phase
• Capacitor start
• Repulsion induction
• Series Universal AC/DC
• Any motor with starting switch (centrifugal or relay) and/or separate starting winding.
vi
Contents
Safety Warnings
General Information
Important Information v
Specifications 1 ii i
Dimensions
Layouts
2
3
Jumper Locations 4
Installation 5
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Shielding guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Heat sinking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Input AC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Motor connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Speed Adjust Potentiometer Connections . . . . . . . . . . . . . . . . . . . . . . . . . .18
Signal and Optional Switch Connections . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Voltage or Current Follower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Operation 22
Voltage Doubler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
To reverse motor direction: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Starting and stopping methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
To coast the motor to a stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
To brake the motor to a stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Thermal protection of the motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Line starting and stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
vii
Calibration 31
Calibration procedure Setup for 60 Hz Motors: . . . . . . . . . . . . . . . . . . . . . . . . .33
MAXIMUM SPEED (MAX SPD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
MINIMUM SPEED (MIN SPD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
TORQUE LIMIT (TQ LIMIT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
ACCELERATION (ACCEL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
DECELERATION (DECEL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
BOOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
SLIP COMPENSATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Calibration Procedure Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Application Notes 38
Independent adjustable speeds with DIR switch . . . . . . . . . . . . . . . . . . . . . . .38
RUN/JOG switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Single speed potentiometer control of multiple motors . . . . . . . . . . . . . . . . . . .40
Quick Reversing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Troubleshooting 42
Before troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
POWER LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
ENABLE LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
TQ LIMIT LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Unconditional Warranty Inside Back Cover
Tables
Table 1. Line Fusing Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
viii
Illustrations
Figure 1. 170-543-0004 Series Features & Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iv
Figure 2. 170-543-0004 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 3. 170-543-0004 Circuit Board Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 4. 170-543-0004 Jumper Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 5. AC Line Connections for 170-543-0004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figure 6. Voltage Doubler Feature for 170-543-0004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 7. Motor Connections-Single Phase Operation (pre-wired cap) . . . . . . . . . . . . . . . . . .16
Figure 8. Motor Connections -Single Phase Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 9. Motor Connections -Three Phase Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 10. Speed Adjust Potentiometer Connections to TB501 . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 11. Signal and Optional Switch Connections for 170-543-0004 . . . . . . . . . . . . . . . . . . .20
Figure 12. Jumper Settings-JMP504 and JMP505 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Figure 13. 170-543-0004 Jumper Settings-JMP506 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 14. Thermal Overload Switch with Optional Enable / Disable Switch . . . . . . . . . . . . . . .28
Figure 15. Jumper Settings--JMP503 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Figure 16. 170-543-0004 Calibration Trimpot Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Figure 17. Independent Adjustable Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Figure 18. RUN/JOG Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Figure 19. Single Speed Potentiometer Control of Multiple Motors . . . . . . . . . . . . . . . . . . . . . .40
Figure 20. 170-543-0004 Quick Reversing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Figure 21. 170-543-0004 Diagnostic LED location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Specifications
Drive
170-543-0004
1-Phase
Input
(VAC)
*
115 / 230
1 or 3-Phase
Output
(VAC)
230
Max
HP
1
Max Continuous
Output
Current (AC) †
4.0
AC
Amps
In
14/7
*
Connect only 115 VAC line input to the 115 VAC terminals. Application of 230 VAC line input when set for 115
VAC will result in severe damage to the motor and drive, and possible explosion and injury.
† Derate current by 2% per degree if the operating temperature is above 40°C. Under no circumstances may the ambient temperature exceed 55° C.
AC Voltage Input Range 115/230 VAC ± 10%, 50/60 Hz single phase
Standard Carrier Frequency 16 KHz
Output Frequency Range
Maximum Output Frequency Range
0 – 120 Hz
30 – 120 Hz
Minimum Output Frequency Range 0 – 30 Hz
Acceleration Time Range 1 – 12 seconds
Deceleration Time Range
Analog Input Voltage Range
1 – 12 seconds
0 – 5VDC,0-10VDC,4-20mA**
Input Impedance, S1 to S2
Braking Current
Braking Time
Vibration
Weight
Ambient Operating Temperature Range
~ 100K ohms
0-100% rated output
1 – 12 seconds
0.5G max (20 – 50 Hz)
0.1G max (> 50 Hz)
3.0 lb
10° – 40° C
** Isolation is standard, and allows for non-isolated speed input, enable and direction switch inputs to be used.
1
2
Dimensions
7.200 [ 183 ]
6.350 [161]
0.89
[22.6]
POWER
FWD
OFF
REV
3
4
5 6
7
8
1
0
10
SPEED
ADJUSTABLE SPEED
REVERSING
AC MOTOR CONTROL
0.188
[5]
0.73 [18.5]
CONDUIT HOLES
2 PLACES
4.56 [116]
2.12 [53.8]
2.20
[55.9]
3.40
[86.4]
ALL DIMENSIONS IN INCHES [MILLIMETERS]
Figure 2. 170-543-0004 Dimensions
BOTTOM PLATE
Layout
C501
JMP504
1 2 3
115
230
C508
JMP501
SCR501
TB501
JMP505
MIN
IC501 T501
C502
IL501
JMP503
UV TRIP
RESTART
IL504
ENABLE
BRAKE
COAST
JMP506
IL501
POWER
IL502
FAULT
J501
BR501
MAX
ACCEL
DECEL
SLIP
COMP
Q14
C501
BOOST
IL503
Q13
R88
R89
D20
D21
Q11 R76
TORQUE
LIMIT
D19
C503
JMP504
INPUT SELECT
1-2 = VDC
2-3 = mA
JMP505
RANGE SELECT
1 = 0 - 5 VDC
2 = 0 - 10 VDC
3 = 4 - 20 mA
FU5
4mA
ZERO
SET
FU502
SCR502
D18
BRAKE
CURRENT
C504
BRAKE
TIME
JMP502
Figure 3. 170-543-0004 Circuit Board Layout
3
4
Jumper Locations
JMP503
JMP506
JMP501
(GENERAL LOCATION)
JMP502
JMP501
FU502
C508
SCR501
SCR502
C501
D18
JMP504
1 2 3
TB501
JMP505
MIN
IC501 T501
C502
IL501
JMP503
UV TRIP
RESTART
IL504
ENABLE
BRAKE
COAST
JMP506
IL501
POWER
IL502
FAULT
J501
UV TRIP
Q14
C501
BR501
MAX
ACCEL
DECEL
SLIP
COMP
BOOST
IL503
R88
R89
Q13
D20
D21
Q11 R76
D19
C503
TORQUE
LIMIT
JMP504
INPUT SELECT
1-2 = VDC
2-3 = mA
JMP505
RANGE SELECT
1 = 0 - 5 VDC
2 = 0 - 10 VDC
3 = 4 - 20 mA
FU5
4mA
ZERO
SET
C504
BRAKE
CURRENT
BRAKE
TIME
JMP502
L1 L2 U V W
TB502
JMP504
JMP505
Figure 4. 170-543-0004 Jumper Locations
Installation
쇵
Warning
DO NOT install, rewire, or remove this control with input power applied.
Failure to heed this warning may result in fire, explosion, or serious injury.
Circuit potentials are at 115 or 230 VAC above ground. To prevent the risk of injury or fatality, avoid direct contact with the printed circuit board or with circuit elements.
Do not disconnect any of the motor leads from the drive unless power is removed. Opening any one motor lead may damage the drive.
Wait at least one minute after power is removed from drive before working on drive.
5
6
Mounting
Warning
DO NOT install, rewire, or remove this
control with input power applied. Doing so may cause fire or serious injury. Make sure that you read and understand the Safety
Warnings before attempting installation.
NOTE: Horizontal mounting may require derating the drive. See your Bison representative for more information
• It is recommended that the drive be oriented with the chassis vertical for best heat dissipation. Horizontal mounting, while acceptable, may require some thermal derating.
• Four 0.19-inch (5 mm) wide slots accept #8 pan head screws. Fasten the heatsink chassis to the subplate.
• Drive components are sensitive to electrostatic fields.
Avoid direct contact with the circuit board. Hold the drive by the chassis only.
• Protect the drive from dirt, moisture, and accidental contact. Provide sufficient room for access to the terminal block and calibration trimpots.
• Mount the drive away from the heat sources. Operate the drive within the specified ambient operating temperature range.
• Prevent loose connections by avoiding excessive vibration of the drive.
• The chassis must be earth grounded. Use a star washer beneath the head of at least one of the mounting screws to penetrate the anodized chassis surface and to reach bare metal.
7
8
Wiring
쇵
Warning
DO NOT install, rewire, or remove this control with
input power applied. Failure to heed this warning may result in fire, explosion, or serious injury.
Circuit potentials are at 115 or 230 VAC above ground.
To prevent the risk of injury or fatality, avoid direct contact with the printed circuit board or with circuit elements.
Do not disconnect any of the motor leads from the drive unless power is removed. Opening any one motor lead may damage the drive.
Wait at least one minute after power is removed from drive before working on drive.
• Use 20 – 24 AWG wire for speed adjust potentiometer wiring. Use 14 AWG wire for AC line (L1, L2) and motor
(U,V and W) wiring.
Shielding guidelines
Warning
Under no circumstances should power and logic
leads be bundled together. Induced voltage can cause unpredictable behavior in any electronic device, including motor controls.
As a general rule, Bison recommends shielding of all conductors.
If it is not practical to shield power conductors, Bison recommends shielding all logic-level leads. If shielding the logic leads is not practical, the user should twist all logic leads with themselves to minimize induced noise.
It may be necessary to earth ground the shielded cable. If noise is produced by devices other than the drive, ground the shield at the drive end. If noise is generated by a device on the drive, ground the shield at the end away from the drive. Do not ground both ends of the shield.
9
10
If the drive continues to pick up noise after grounding the shield, it may be necessary to add AC line filtering devices, or to mount the drive in a less noisy environment.
Logic wires from other input devices, such as motion controllers and PLL velocity controllers, must be separated from power lines in the same manner as the logic I/O on this drive.
Heat sinking
The 170-543-0004 drive is delivered with a heat sink chassis. Ensure that there is adequate space above and below the drive for proper convection air flow. A small fan may be necessary for proper cooling in restricted space applications. Bison recommends mounting the drive vertically.
11
Fusing
The 170-543-0004 includes AC power line fuses on the main PC Board. Use fast-acting fuses rated for 250 VAC or higher. See Table 1 for recommended line fuse sizes.
Table 1. Line Fusing Chart
Drive
170-543-0004
1-Phase
Input
(VAC)
115 / 230
Max
HP
1
AC
Amps
In
14/7
AC Line
Fuse
Size (Amps)
15
12
Connections
All power input and power output connections are made to TB502.
Warning
DO NOT connect this equipment with power
applied. Failure to heed this directive may result in fire or serious injury.
Bison strongly recommends the installation of a master power switch in the voltage input line. The switch contacts should be rated at a minimum of 20
Amps and 250 volts.
Input AC Power connections
Connect the AC power input to TB502 L1 and L2 as shown in Figure 5 (page 13). Connect an external master stop switch. Install the switch in series of the AC power input as shown.
Figure 5. AC Line Connections for 170-543-0004
13
14
W a r n i n g
Do not connect 230 VAC line input when the drive is set for
Ꮨ
115 VAC input. This will result in severe damage to the motor. and can lead to explosion and/or injury.
Connect AC Power input to L1 and L2 as shown in
Figure 5 (page 13).
NOTE: The 170-543-0004 is equipped with a voltagedoubler feature, which converts a 115 VAC input to a
230 VAC output, for use with 230V motors. The drive output current rating remains the same for either AC input voltage. Use caution when connecting this output.
If the input voltage is 115 VAC and the desired output voltage is 230 VAC (voltage doubler mode), set jumpers as shown in Figure 6 (page 15).
If the input voltage is 230 VAC and the desired output voltage is 230 VAC (no voltage doubler), set jumpers as shown in Figure 6 (page 15).
Refer to Figure 4 (page 4) for jumper locations.
NOTE: The 170-543-0004 series of drives covered in this manual are meant to be used with 208/230 VAC motors only. DO NOT use this series of drives with 115 VAC motors.
15
JMP501
Jumper Pins 2 & 3 for 115 VAC input
Jumper Pins 1 & 2 for 230 VAC input
JMP502
Jumper Pins 1 & 2 for 115 VAC input
Jumper Pins 2 & 3 for 230 VAC input
Figure 6. Voltage Doubler Feature for 170-543-0004
16
Motor connections
Motor connections are made to TB502
Single-phase operation
For single-phase operation, connect the motor as shown below in Figure 7. Ensure that the prewired capacitor and its associated motor coil are connected to terminals U and
V as shown. This connection may be internal if using a 2wire motor. If the motor has three leads, you must make this connection yourself.
To reverse a single phase permanent split capacitor motor, connect the motor as shown in Figure 8 (page 17). The motor cap must be removed from the circuit.
DO NOT use a direction switch with this wetup
Figure 7. Single Phase Operation (pre-wired cap)
Motor run cap must be removed from the circuit
This method works with most (but not all) motors.
Figure 8. Single Phase Operation (Reversing)
Three-phase operation
Connect a three-phase motor to terminals U, V and W as shown in Figure 9 below.
17
Figure 9. Three-phase Operation
18
Speed Adjust Potentiometer Connections
Set JMP504 for VDC input by jumpering pins 1 & 2. Set
JMP505 for 0-5 VDC by jumpering pin column 1. Refer to Figure 4 (page 4) for Jumper Locations. Connect a speed adjust potentiometer to terminals S1, S2 and S3.
Make sure the potentiometer is connected so that the motor speed will increase as the potentiometer is turned clockwise. See Figure 10 below.
NOTE: These settings and connections are factory installed on the 170-543-0004 drive.
10K OHM
SPEED ADJUST
POTENTIOMETER
CW
TB501
D
S3 S2 S1 E1
E2
Figure 10. Speed Adjust Potentiometer Connections to TB501
Signal and Optional Switch Connections
All signal and switch connections are made at TB501. Use
20 - 24 AWG wire for speed adjust potentiometer and switch connections.
NOTE: The Enable/Disable and Direction switch are factory installed on the 170-543-0004 drives.
ENABLE/DISABLE switch
Connect a single-pole, single-throw ENABLE/DISABLE switch between the ENABLE (E2) and COMMON (E1) terminals as shown. Open the switch to disable the drive and coast or brake to a stop. Refer to page 26 for stopping method. Close the switch to accelerate to set speed at a rate controlled by the ACCEL trimpot. The ENABLE input is isolated.
DIRECTION (D) switch
Connect a single-pole, single-throw DIRECTION switch between the (D) and COMMON (E1) terminals as shown in
Figure 11 (page 20). Opening the switch will cause the motor to rotate in the forward direction; closing the switch will reverse motor rotation. The DIRECTION input is isolated.
The drive will decelerate the motor to a stop, (at the DECEL trimpot setting), before reversing, so there is no need to wait for the motor to coast or brake to a stop before changing direction. For faster reversing see Application Notes (page
38).
19
20
D S3 S2 S1 E1 E2
Figure 11. Signal and Optional Switch
Connections for 170-543-0004
Voltage or Current Follower
Drives can be configured to follow an isolated or a grounded (non-isolated) voltage or current signal. To configure the drive to follow a voltage or current signal, connect the signal leads to the S1 and S2 terminals on
TB501 as shown in Figure 11 above. Ensure that the following jumper terminals are properly set as shown in
Figure 12 (page 21).
21
JMP504 Input Type
Jumper pins 1 & 2 for Voltage follower or speed pot mode.
Jumper pins 2 & 3 for Current follower.
JMP505 Input Range Settings
Set jumper in position 1 for 0-5 VDC signal or speed pot input.
Set jumper in position 2 for 0-10 VDC signal.
Set jumper in position 3 for 4-20 mA signal. *
* The 4-20 mA ZERO SET potentiometer should be used to calibrate the zero (or minimum) speed of the drive with
4mA applied to the input. For voltage inputs this pot should be set to full CCW.
JMP504
JMP504
1 2 3
1 & 2 for Voltage Input
2 & 3 for Current Input
JMP505
JMP505
1 2 3
1 = 0 - 5 VDC INPUT
2 = 0 - 10 VDC INPUT
3 = 4 - 20 mA INPUT
Figure 12. Jumper Settings--JMP504 and JMP505
22
Operation
쇵
Warning
Dangerous voltages exist on the drive when it is powered, and up to 60 seconds after power is
removed and the motor stops. BE ALERT. High voltages can cause serious or fatal injury.
Do not change jumper settings with power applied.
Ensure that jumper settings are compatible with the motor being controlled.
쇵
Voltage Input Warning
DO NOT connect 230 VAC line input when the
drive is set for 115 VAC input. This will result in severe damage to the motor and drive, and possible explosion and/or injury.
Voltage Doubler
Warning
DO NOT connect 230 VAC line input when drive is
set for 115 VAC input. This will result in severe damage to the motor and drive, and possible explosion or severe injury.
23
The 170-543-0004 drive is equipped with a unique voltagedoubling feature, for use when 230 VAC input voltage is not available. This feature converts a 115 VAC input to a 230
VAC output, for use with 230V motors. The drive output current rating remains the same for either AC input voltage.
Refer to Figure 6 (page 15) for connection information. Use extreme caution when connecting this feature. Incorrect use of this feature may result in fire and/or serious injury.
NOTE: The 170-543-0004 is meant to be used with
208/230 VAC motors only. DO NOT use this drive with 115 VAC motors.
24
Startup
Warning
DO NOT change jumper settings with power
applied. Ensure that jumper settings are compatible with the motor being controlled.
Before applying power, verify that no conductive material is present on the printed circuit board.
1. Verify that no conductive material is present on the PCB.
2. Verify that the correct voltage is connected to the inputs before applying power. DO NOT CONNECT 230 VAC line voltage to a 115 VAC configured drive. Applying power in this manner will damage the motor and drive.
3. Set the speed adjust potentiometer or reference signal to zero (full CCW).
4. Set the DIRECTION switch (if installed) to the desired direction. If no switch is installed, add or remove a jumper across the (D) and (E1) terminals, as required.
5. Set the ENABLE/DISABLE switch (if installed) to
ENABLE, or short the ENABLE (E2) and (E1) terminals on TB501.
6. Apply 115 or 230 VAC, 50/60 Hz, single-phase power to the drive. The green POWER LED will come on after an initial delay of 1 - 2 seconds. If the POWER LED does not light, check the line fuses to ensure that they are properly installed and not open.
25
7. If you attempt to startup and the yellow TQ LED comes on, the control has entered torque limit mode. To avoid this occurrence, you may: a. increase the torque limit setting*, or b. lengthen the acceleration time enough to accommodate the starting torque needed by adjusting the ACCEL trimpot.
* Do not set the torque limit setting above 150% of the motor’s nameplate current rating.
To reverse motor direction:
To reverse the direction of motor shaft rotation while the motor is running, set the DIRECTION switch to the opposite position. If no DIRECTION switch is installed, open or short the (DIR) and (E1) terminals on TB501, as required.
When a new direction is selected, there is no need to open the enable input. The control will automatically decelerate the motor to zero speed, reverse direction, and then accelerate the motor back to the set speed. Acceleration and deceleration rates are controlled by the ACCEL/DECEL trimpot settings. If quicker reversing is needed refer to applications notes section page 38 for further detail.
NOTE: DO NOT use the DIRECTION switch if there is a capacitor in the motor windings.
26
Starting and stopping methods
(factory set to COAST position)
To coast the motor to a stop
Insure that JMP506 is set to the COAST position as shown in Figure 13 (page 27). Refer to Figure 4 (page 4) for
Jumper Locations. To coast the motor to a stop open the
ENABLE/DISABLE switch, or remove the jumper between
ENABLE (E2) and COMMON (E1) terminals of TB501.
Refer to page 19 for instructions on switch installation.
To brake the motor to a stop
Insure that JMP506 is set to the BRAKE position as shown in Figure 13 (page 27). Refer to Figure 4 (page 4) for
Jumper Locations. Confirm BRAKE CURRENT and
BRAKE TIME potentiometers are calibrated to a desired value. BREAK CURRENT is adjustable from 0-100% of rated output current. BRAKE TIME is adjustable from 1 -12 seconds. To brake the motor, open the ENABLE/DISABLE switch, or remove the jumper between ENABLE (E2) and
COMMON (E1) terminals of TB501. Refer to page 19 for instructions on switch installation.
27
1
2
3
BRAKE
COAST
JMP506 (on top board)
Jumper Pins 1 & 2 to Brake
Jumper Pins 2 & 3 to Coast
Figure 13. Jumper Settings--JMP506
Thermal protection of the motor
The enable input can also act as a motor thermal protection circuit for motors having a built-in thermal protector. These thermal protectors are operated only by motor heat and open the enable circuit when the motor reaches a temperature capable of causing damage to the motor winding.
28
Normally, these thermal procedures automatically close the circuit when the motor has cooled to a safe temperature. In operation, the drive can be disabled by opening the enable switch or opening the thermal overload switch. See Figure
14 below.
ENABLE / DISABLE
SWITCH
CLOSE TO ENABLE
THERMAL
OVERLOAD
SWITCH
TB501
E2 (ENABLE)
E1 (COMMON)
Figure 14. Thermal Overload Switch with Optional
Enable / Disable Switch
Line starting and line stopping
Warning
Bison strongly recommends the installation of a master power switch in the voltage input line (see
Power and Fuse connections, page 13). The switch contacts should be rated at a minimum of 20 Amps and 250 volts.
29
Line starting/line stopping (applying and removing AC voltage input) may be configured to operate two different ways by use of JMP503.
When JMP503 is set to the UV TRIP position as shown in
Figure 15 (page 30), the drive will stop and latch off when an under voltage condition, (bus voltage drops below
200VDC), occurs. This can occur due to line sag, line transients, or line disconnect. The drive may then be restarted by cycling the ENABLE off then on, or waiting until the DC bus drops to zero, (approximately 1 minute), at which point the drive will restart upon reapplication of line power. Refer to Figure 4 (page 4) for Jumper Locations.
30
When JMP503 is set to the RESTART position as shown in
Figure 15 below (factory set to UV trip), the drive will stop when an under voltage condition, (bus voltage drops below
200 VDC), occurs. This can occur due to line sag, line transients, or line disconnect. There is a 1.5 second restart delay after the bus voltage returns to normal. Refer to
Figure 4 (page 4) for Jumper Locations.
1
2
3
JMP503
UV TRIP
RESTART
JMP503 (on bottom board)
Pins 1 & 2 to Trip
Pins 2 & 3 to Restart
UV TRIP: Drive has a low voltage fault & must be manually re-enabled or the bus voltage must go to zero and then return to operation potential to restart.
RESTART: Drive has a low voltage fault & will momentarily stop then auto-restart when input voltage returns to minimum level.
Figure 15. Jumper Settings--JMP503
Calibration
쇵
Warning
Dangerous voltages exist on the drive when it is powered, and up to 60 seconds after power is removed and the motor stops.
When possible, disconnect the voltage input from the drive before adjusting the trimpots. If the trimpots must be adjusted with power applied, use insulated tools and the appropriate personal protection equipment. BE
ALERT. High voltages can cause serious or fatal injury.
31
The 170-543-0004 has ten user-adjustable trimpots. Each drive is factory calibrated to its maximum horsepower rating. Re-adjust the calibration trimpot settings to accommodate lower horsepower motors. See Figure 16
(page 32) for 170-543-0004 series trimpot locations.
All adjustments increase with clockwise (CW) rotation and decrease with counter-clockwise (CCW) rotation. Use a non-metallic screwdriver for calibration. Each trimpot is identified on the printed circuit board.
32
ZERO SET
JMP 504
1 2 3
4mA
ZER O
SET
TB 501
JMP 505
MIN
IC501 T501
IL 501
JMP 503
U V TRI P
RESTART T
IL 504
ENABLE
JMP 506
BRAKE
CO AST
IL 501
PO WE R
IL 502
FA U LT
J501
Q 14
C501
R88
R89
Q 13
D21 C
D2 0
Q 11 7R
D1 9
C503
MAX
ACCEL
DECEL
SLIP COMP
BOOST
IL 503
TO RQ UE
LIMIT
JMP 504
INP UT SELE CT
1-2 = VD C
2- 3 = m A
JMP 505
RAN G E SELE CT
1 = 0 - 5 VD C
2 = 0 - 1 0 VD C
3 = 4 - 2 0 m A
D1 8
C504
BRAKE
CURRENT
BRAKE
TIME
MIN
MAX
DECEL
SLIP COMP
ACCEL
BOOST
TQ LIMIT
BRAKE
CURRENT
BRAKE
TIME
Figure 16. 170-543-0004 Calibration Trimpot Locations
Calibration Procedure Setup for 60 Hz Motors:
1. Set JMP501 & JMP502** to appropriate input voltage setting (115/230VAC). Refer to Figure 4 (page 4) for
Jumper Locations.
2. Set the ENABLE switch to the DISABLE (open) position.
If no switch is installed, remove the jumper between the
(E2) and (E1) terminals of TB501.
3. Set the DIRECTION switch to the FWD (open) position.
If no switch is installed, confirm that there is no jumper between the (D) and (E1) terminals of TB501.
4. Set all trimpots except TQ LIMIT and MAX fully counterclockwise (CCW).
5. Set the TQ LIMIT trimpot to maximum (full CW).
6. Set the MAX trimpot to the 50% position.
7. Set the speed adjust potentiometer or reference signal to zero (full CCW):
8. Calibrate the trimmer pots as follows:
33
MAXIMUM SPEED (MAX)
Rotate the speed adjust potentiometer full CW or set the reference signal to maximum. Using a hand-held tachometer or analog frequency meter as a reference, adjust the MAX trimpot until the desired maximum speed or frequency is reached.
34
MINIMUM SPEED (MIN)
Rotate the speed adjust potentiometer CCW or set the signal reference to a minimum. Adjust the MIN trimpot until the motor has stopped (for zero speed setting), or until desired minimum speed has been reached. The MAX may need to be readjusted after calibration of the MIN.
TORQUE LIMIT (TQ LIMIT)
Warning
Although the TORQUE LIMIT trimpot can be set up
to 150% of the drive nameplate rating, continuous operation beyond the drive nameplate rating may cause damage to the motor and/or drive.
1. With no power applied to the drive, connect a (true RMS) ammeter in series with one of the motor leads.
2. Set the TQ LIMIT trimpot to full CCW.
3. Carefully lock the motor shaft. Ensure that the motor is firmly mounted.
4. Apply line power. The motor should be stopped.
5. Set the speed adjust potentiometer or reference signal to maximum speed. The motor should remain stopped.
6. Slowly rotate the TQ LIMIT trimpot clockwise (CW) until the ammeter reads 120% of maximum motor current.
35
7. Set the speed adjust potentiometer or reference signal to zero speed.
8. Remove power from the drive.
9. Remove the lock from the motor shaft.
10. Remove the ammeter in series with the motor lead.
ACCELERATION (ACCEL)
1. Set the speed adjust potentiometer or reference signal to zero and wait for the motor to come to a stop (or minimum speed).
2. Set the speed adjust potentiometer or reference signal to maximum speed (full CW) and note the time the motor takes to accelerate to maximum speed.
3. If the acceleration time differs from the desired time, adjust the ACCEL trimpot until the desired time is reached. Rotating the ACCEL trimpot CW increases the acceleration time.
DECELERATION (DECEL)
1. Set the speed adjust potentiometer or reference signal to maximum (full CW) and wait for the motor to reach maximum speed.
36
2. Set the speed adjust potentiometer or reference signal to minimum speed (full CCW) and note the time the motor takes to decelerate to minimum speed.
BOOST
3. If the deceleration time differs from the desired time, adjust the DECEL trimpot until the desired time is reached. Rotating the DECEL pot CW increases the deceleration time.
The BOOST trimpot is used to increase motor torque at low speeds. The minimum setting is sufficient for most applications and does not need to be adjusted. If the motor stalls or runs erratically at very low speeds (below 10 Hz), the boost trimpot may need adjustment.
1. Run the motor at the lowest continuous frequency/speed required.
2. Monitor the motor phase current (with a true RMS meter) while very slowly turning the BOOST trimpot CW until the motor operates properly, or 100% of the motor nameplate current is reached.
NOTE: Use the absolute minimum amount of BOOST necessary to achieve proper motor operation. Improper use of the BOOST feature may cause motor and/or drive overheating and failure.
37
SLIP COMPENSATION (SLIP COMP)
Slip compensation is used to minimize the normal speed changes occurring in an induction motor from no load to full load conditions.
1. Using the speed adjust potentiometer or reference signal, run the motor at the desired RPM under a no load condition. Measure the RPM with a tachometer.
2. Without changing the speed adjust potentiometer or reference signal, apply a full load to the motor, and bring the motor speed back up using the SLIP COMP pot to the originally measured RPM.
3. These procedures, (1&2), may need to be repeated several times to reach the desired accuracy required.**
**Wide speed range accuracy of the slip compensation method depends heavily on motor slip vs. frequency characteristics.
Calibration Procedure Conclusion
1. Set the speed adjust potentiometer or reference signal to zero (full CCW).
2. Disable the drive by opening the ENABLE/DISABLE switch or removing the jumper from TB501 (E2) and
(E1) terminals.
3. Remove power to the motor and drive. Calibration is now complete.
38
Application Notes
Independent adjustable speeds with DIR switch
Replace the speed adjust potentiometer with two singlepole multi-position switches, and two or more potentiometers in parallel, with a total parallel resistance of
10K ohms. Figure 17 below shows the connection of two independent speed adjust potentiometers that can be mounted at two separate operating stations.
TB501
FORWARD
SPEED
20K OHM
REVERSE
SPEED
20K OHM
FORWARD
REVERSE
E2
E1
S1
S2
S3
D (DIRECTION)
Figure 17. Independent Adjustable Speeds
RUN/JOG switch
Use a single-pole, two-position switch for the RUN/JOG switch, and a single-pole, normally open, momentary operated pushbutton for the JOG pushbutton. Set JMP506 to either Coast or Brake depending on how the motor should stop.
Connect the RUN/JOG switch and JOG pushbutton to terminal board TB501 as shown in Figure 18 below. The motor stops when the RUN/JOG switch is set to JOG.
Press the JOG pushbutton to jog the motor. Return the
RUN/JOG switch to RUN for normal operation.
39
NORMALLY OPEN
RUN/JOG
PUSHBUTTON
JOG
RUN/JOG
SWITCH
TB501
RUN
E2 (ENABLE)
E1 (COMMON)
S1
S2
S3
D
Figure 18. RUN/JOG Switch
40
Single speed potentiometer control of multiple motors
Warning
The combined current draw of all motors must not exceed the current rating of the drive.
The 170-543-0004 is capable of operating up to eight 3phase motors simultaneously. All motors must be of the same type and must control similar loads. Connect each motor as shown in Figure 19 below.
MOTOR
A
MOTOR
B
CW
10K OHM
SPEED ADJUST
POTENTIOMETER
S3
S2
S1
U V W
Figure 19. Single Speed Potentiometer Control of Multiple Motors
41
Quick Reversing
To reverse the direction of motor shaft rotation, install a
DPDT center off switch as shown in Figure 20 below. The drive will stop the motor before reversing, so there is no need to wait for the motor to coast to a stop before changing direction. JMP506 must be set to brake. Refer to
Figure 4 (page 4) for Jumper Locations.
FWD
STOP
REV
DPDT CENTER
OFF SWITCH
TB501
E2 (ENABLE)
E1 (COMMON)
S1
S2
S3
D
Figure 20. 170-543-0004 Quick Reversing
42
Troubleshooting
쇵
Warning
Dangerous voltages exist on the drive when it is powered, and up to 60 seconds after power is removed and the motor stops.
When possible, disconnect the voltage input from the drive while troubleshooting. BE ALERT. High voltages can cause serious or fatal injury.
Before troubleshooting
Perform the following steps before starting any procedure in this section:
• Disconnect AC voltage input from the drive. Wait 60 seconds for power to discharge. The green POWER LED will blink while power is discharging.
• Check the drive closely for damaged components.
• Check that no wire, chips, or other foreign material has become lodged on the printed circuit board.
• Verify that every connection is correct and in good condition.
• Verify that there are no short circuits or grounded connections.
• Check that the drive’s rated phase current and RMS voltage are consistent with the motor ratings.
For additional assistance, contact your local Bison distributor, or the factory direct by telephone at:
1-800-AT-BISON
43
44
Diagnostic LEDs
Bison 170-543-0004 is equipped with diagnostic LED’s to assist the user in troubleshooting and monitoring equipment status while in use. Refer to Figure 21 (page 45) for diagnostic LED locations.
POWER LED
The green POWER LED is on when AC line voltage is applied and the control’s low-voltage power supply is operational.
ENABLE LED
The red ENABLE LED turns on whenever the inverter output is enabled.
FAULT LED
The red FAULT LED blinks on and off when the drive output is locked out or not ENABLED and any one of the following fault conditions occur:
1. Overvoltage
• 170-543-0004 230AC controls: DC bus exceeds 400 VDC
2. Undervoltage
• 170-543-0004 230AC controls: DC bus drops below 200 VDC
3. Instantaneous Overcurrent Trip - Inverter output current has exceeded safe levels (250%).
Note:
The FAULT condition must be reset using the ENABLE function of the drive (opening and closing the ENABLE input).
45
TORQUE (TQ) LIMIT LED
The yellow TQ LIMIT LED is on when the drive output current exceeds the threshold set by the TQ LIMIT trimpot.
When the TQ LIMIT LED turns on, shut down the motor and drive by disabling or removing power. Check the motor to make sure it is not jammed or overloaded. The TQ LIMIT trimpot may need to be recalibrated. See the Calibration section (page 31) for information on calibrating the TQ
LIMIT trimpot.
C501
4mA
ZERO
SET
JMP504
1 2 3
TB501
JMP505
C502
IL501
IL504
ENABLE
POWER
IL501 IL502
FAULT
JMP501
Figure 21. LED locations
IL503
TORQUE
LIMIT
46
Problem Possible
Cause
Suggested
Solution
Internal line fuse blows 1. Line fuses are the wrong size.
2. Motor or motor cable is shorted to ground.
3. Nuisance tripping caused by a combination of ambient conditions and high-current spikes (i.e. reversing).
1. Check that line fuses are properly sized for the motor being used.
2. Check motor cable and motor for shorts.
3. Add a blower to cool the drive components; increase TQ LIMIT settings (page 34).
Internal line fuse does not blow, but the motor does not run
1. Speed adjust potentiometer or voltage input signal is set to zero speed.
2. Speed adjust potentiometer or voltage input signal is not properly connected to drive input; connections are open.
1. Increase the speed adjust potentiometer setting or voltage input signal.
2. Check connections to input. Verify that connections are not open.
Problem Possible
Cause
Suggested
Solution
47
Internal line fuse does not blow, but the motor does not run (cont.)
3. Drive is “tripped” off or has gone into thermal overload.
4. Drive has been disabled.
3. Disable, then reenable the drive.
4. Ensure that
ENABLE (EN) and
COM terminals are properly connected.
Motor runs too slow or too fast at set speed
5. Drive is in current limit.
6. Drive is not receiving
AC voltage input.
7. Motor is not connected.
1. MAX SPD trimpot is not calibrated correctly.
5. Verify that motor is not jammed.
Increase TQ LIM setting if it is set too low (page 34).
6. Apply AC line voltage to L1 and
L2.
7. Connect motor to drive outputs U, V and W.
1. Calibrate MAX SPD trimpot (page 33).
48
Problem Possible
Cause
Suggested
Solution
Motor will not reach the desired speed
Motor pulsates or surges under load
1. MAX SPD setting is too low.
2. Nominal input voltage may be too low for motor
3. Motor is overloaded.
1. Motor “bouncing” in and out of torque limit.
1. Increase MAX SPD setting (page 33).
2. Compare motor voltage to input voltage; replace motor if necessary
3. Check motor load.
Resize the motor or drive if necessary.
1. Make sure motor is not undersized for load; adjust TQ LIM setting CW (page
34).
Motor does not reverse 1. Defective DIRECTION switch connection.
2. Reversing circuit not working properly.
3. Motor not wired correctly for reverse
1. Check DIRECTION switch connection.
2. Check reversing circuit by shorting
TB501 (D) terminal to (E1) terminal with jumper wire.
3. Check motor wiring
Review motor connections section
Problem
TQ is unsatisfactory at high speeds.
Possible
Cause
Suggested
Solution
49
1. TQ LIMIT set too low.
2. Load may exceed rating of motor/drive.
3. Nominal input voltage may be too low for motor.
1. Check TQ LIM setting (page 34).
2. “Fix” load (i.e., straighten mounting, coupling, etc.); or replace motor and drive with motor and drive rated for higher horsepower.
3. Compare motor voltage to input voltage. Replace motor if necessary.
50
NOTES
NOTES
51
Bison Warranty Policy
The Company warrants to the Buyer the products sold hereunder to be free of defects in material and workmanship under normal use and service for a period of one (1) year from the date of shipment. The obligation of the Company under this warranty is limited to repair or replacing at its option, any part or parts, which upon examination shall disclose to the reasonable satisfaction of the Company to have been defective in material or workmanship. Buyer must return the products to the Company’s factory, shipping charges prepaid, and with complete information as to alleged defects and the installation, operation and service of the products. Except as otherwise expressly stated herein the Company makes no representation of warranty of any kind, express or implied, as to merchantability, fitness for a particular purpose, or any other matter with respect to the products sold hereunder.
Bison Gear & Engineering Corp.
3850 Ohio Ave. -- St. Charles, IL 60174
Phone: 1-800-AT-BISON www.bisongear.com
Document Number: 250-0421; Revision 0 -- May 2006
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 16 Mounting
- 18 Wiring
- 19 Shielding guidelines
- 20 Heat sinking
- 21 Fusing
- 22 Connections
- 22 Input AC Power Connections
- 26 Motor connections
- 28 Speed Adjust Potentiometer Connections
- 29 Signal and Optional Switch Connections
- 30 Voltage or Current Follower
- 33 Voltage Doubler
- 34 Startup
- 35 To reverse motor direction
- 36 Starting and stopping methods
- 36 To coast the motor to a stop
- 36 To brake the motor to a stop
- 37 Thermal protection of the motor
- 39 Line starting and stopping