Graco 311208A Therm-O-Flow 200, U.S. Owner's Manual

Instructions Important Safety Instructions. Read all warnings and instructions in this manual. Save these instructions. 200 Liter (55 Gallon) Drum Size Therm-O-Flow 200 ® 311208A Hot Melt Drum Unloaders For applying hot melt sealant and adhesive materials. Maximum Operating Temperature (All Models): 400°F (204°C) Maximum System Air Supply Pressure 100 psi (0.7 MPa, 7 bar) NXT 2200 Powered Unloaders, Models A-1 and A-4 2300 psi (15.9 MPa, 159 bar) Maximum Fluid Working Pressure 100 psi (0.7 MPa, 7 bar) Maximum Air Motor Pressure NXT 3400 Powered Unloaders, Models A-2 and A-5 3000 psi (20.7 MPa, 207 bar) Maximum Fluid Working Pressure 82 psi (0.57 MPa, 5.7 bar) Maximum Air Motor Pressure NXT 6500 Powered Unloaders, Models A-3 and A-6 3000 psi (20.7 MPa, 207 bar) Maximum Fluid Working Pressure 43 psi (0.29 MPa, 2.9 bar) Maximum Air Motor Pressure See page 2 for Contents Graco Inc. P.O. Box 1441 Minneapolis, MN 55440-1441 Copyright 2006, Graco Inc. is registered to I.S. EN ISO 9001 TI7936A Contents Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Component Identification . . . . . . . . . . . . . . . . . . 8 Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . 10 Heat Control Zone Selection . . . . . . . . . . . . . . . 12 Air Line Modules . . . . . . . . . . . . . . . . . . . . . . . . 13 Installation Procedure . . . . . . . . . . . . . . . . . . . . . . 14 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Location Requirements . . . . . . . . . . . . . . . . . . . 14 Mechanical Setup . . . . . . . . . . . . . . . . . . . . . . . 14 Electrical Setup . . . . . . . . . . . . . . . . . . . . . . . . . 15 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Connecting the Electrical Control Panel to a Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Overview of the Temperature Controller Settings 20 Purging the System . . . . . . . . . . . . . . . . . . . . . . 20 Optional Low Level Kit 253559 . . . . . . . . . . . . . 21 Operator Controls . . . . . . . . . . . . . . . . . . . . . . . . . 22 Main Power Disconnect . . . . . . . . . . . . . . . . . . . 22 EasyKey Display and Keypad . . . . . . . . . . . . . . 22 LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 EasyKey Display Screens . . . . . . . . . . . . . . . . . . . 24 Power Up Screens . . . . . . . . . . . . . . . . . . . . . . 24 Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Setup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Purge Before Using Equipment . . . . . . . . . . . . . 30 Set Values on EasyKey . . . . . . . . . . . . . . . . . . . 30 Material Loading . . . . . . . . . . . . . . . . . . . . . . . . 30 System Heat Up . . . . . . . . . . . . . . . . . . . . . . . . 32 Prime Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Prime System . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Pressure Relief Procedure . . . . . . . . . . . . . . . . 35 Trigger Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Ram Pressure Relief Procedure . . . . . . . . . . . . 36 Drum Changing . . . . . . . . . . . . . . . . . . . . . . . . . 37 System Shutdown . . . . . . . . . . . . . . . . . . . . . . . 39 Dual Ram Cross-Over Installation . . . . . . . . . . . . 40 Typical Installation . . . . . . . . . . . . . . . . . . . . . . . 40 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Ram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Ground Fault Interrupt . . . . . . . . . . . . . . . . . . . . 41 Power in a Tandem System . . . . . . . . . . . . . . . . 41 Resetting the Ground Fault Interrupt . . . . . . . . . 41 2 Light Tower Kit (Optional) . . . . . . . . . . . . . . . . . . . 41 Alarm Troubleshooting . . . . . . . . . . . . . . . . . . . . . 41 Ram Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 43 Heated Pump Troubleshooting . . . . . . . . . . . . . . . 44 Air Motor Troubleshooting . . . . . . . . . . . . . . . . . . 44 Electrical Control Panel Troubleshooting . . . . . . 45 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Ram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Ground Fault interrupt . . . . . . . . . . . . . . . . . . . . 46 Power in a Tandem System . . . . . . . . . . . . . . . . 46 Ram Service . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Removing a Material Drum from the Supply Unit 47 Servicing the Ram Plate . . . . . . . . . . . . . . . . . . 47 Servicing Wipers . . . . . . . . . . . . . . . . . . . . . . . . 47 Pump Removal and Replacement . . . . . . . . . . . . 49 Replacing Heater Bands and Sensors in Pump Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . 54 240 VAC Supply - Internal Control Box . . . . . . . 54 Electrical Control Schematic. . . . . . . . . . . . . . . 55 Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 All Models Supply Unit . . . . . . . . . . . . . . . . . . . . 62 Therm-O-Flow Pump, Part No. 253575 . . . . . . . 64 Therm-O-Flow Pump Module using NXT 3400 and NXT 6500 Models . . . . . . . . . . . . . . . . . . . . 66 Therm-O-Flow Pump Module using NXT 2200 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Series A Heated Pump . . . . . . . . . . . . . . . . . . . 70 Heated Platens . . . . . . . . . . . . . . . . . . . . . . . . . 72 Platen Coil Checking . . . . . . . . . . . . . . . . . . . . . 74 EZ Key Assembly, Part No. 253147 . . . . . . . . . . 75 Swirl Kit, Part No. 253263 . . . . . . . . . . . . . . . . . 76 Drip Shield Mount Kit, Part No. 253479 . . . . . . . 77 Drum Ram Post Saddle Clamp, Part No. C32463 78 Heavy Duty Drum Band Clamp, Part No. 918395 79 Fiber Drum Reinforcement Clam Shell Clamp, Part No. 918397 . . . . . . . . . . . . . . . . . . . . . . . . . 80 Vent Hood Accessory Kit for 6-1/2 In. Ram, Part No. 233559 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 All Models Control Panel Component Layout . . 82 Control Box Spare Parts List . . . . . . . . . . . . . . . 83 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Ram Mounting and Clearance Dimensions . . . . 84 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 86 Graco Information . . . . . . . . . . . . . . . . . . . . . . . 86 311208A Warnings Warnings The following are general warnings related to the setup, use, grounding, maintenance, and repair of this equipment. Additional, more specific warnings may be found throughout the body of this manual where applicable. Symbols appearing in the body of the manual refer to these general warnings. When these symbols appear throughout the manual, refer back to these pages for a description of the specific hazard. WARNING BURN HAZARD Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe burns, do not touch hot fluid or equipment. Wait until equipment/fluid has cooled completely. SPLATTER HAZARD During blow off of platen splatter may occur. • Use minimum drum removal air pressure. MOVING PARTS HAZARD Moving parts can pinch or amputate fingers and other body parts. • Keep clear of moving parts. • Do not operate equipment with protective guards or covers removed. • Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure in this manual. Disconnect power or air supply. ELECTRIC SHOCK HAZARD Improper grounding, setup, or usage of the system can cause electric shock. • Turn off and disconnect power at main switch before disconnecting any cables and before servicing equipment. • Connect only to grounded power source. • All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations. TOXIC FLUID OR FUMES HAZARD Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed. • Read MSDS’s to know the specific hazards of the fluids you are using. • Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines. EQUIPMENT MISUSE HAZARD Misuse can cause death or serious injury. • Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals. • Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request MSDS from distributor or retailer. • Check equipment daily. Repair or replace worn or damaged parts immediately with genuine Graco replacement parts only. • Do not alter or modify equipment. • For professional use only. • Use equipment only for its intended purpose. Call your Graco distributor for information. • Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces. • Do not kink or over bend hoses or use hoses to pull equipment. • Keep children and animals away from work area. • Do not operate when fatigued or under the influence of drugs or alcohol. • Comply with all applicable safety regulations. 311208A 3 Warnings WARNING PERSONAL PROTECTIVE EQUIPMENT You must wear appropriate protective equipment when operating, servicing, or when in the operating area of the equipment to help protect you from serious injury, including eye injury, inhalation of toxic fumes, burns, and hearing loss. This equipment includes but is not limited to: • Protective eyewear. • Clothing and respirator as recommended by the fluid and solvent manufacturer. • Gloves. • Hearing protection. SKIN INJECTION HAZARD High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment. • Do not point gun at anyone or at any part of the body. • Do not put your hand over the spray tip. • Do not stop or deflect leaks with your hand, body, glove, or rag. • Do not spray without tip guard and trigger guard installed. • Engage trigger lock when not spraying. • Follow Pressure Relief Procedure in this manual, when you stop spraying and before cleaning, checking, or servicing equipment. FIRE AND EXPLOSION HAZARD Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent fire and explosion: • Use equipment only in well ventilated area. • Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static arc). • Keep work area free of debris, including solvent, rags and gasoline. • Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present. • Ground equipment and conductive objects in work area. See Grounding instructions. • Use only grounded hoses. • Hold gun firmly to side of grounded pail when triggering into pail. • If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment until you identify and correct the problem. • Keep a fire extinguisher in the work area. 4 311208A Warnings 311208A 5 Overview Overview How the Therm-O-Flow 200 Works A heated platen melts the sealant or adhesive and directs the molten material to the pump inlet. The material then travels through a heated Check–Mate pump and heated fluid moves to the application tool. Model Numbers This manual will refer to the typical model number listed below when defining parts in your application. The model number stamped on your machine defines the equipment in the following 10 categories: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Motor Heated Platen Follower Seals Drum Ram Number of heat zones Heat Controls Supply Voltage Control Panel Drum Unloader Options Application Accessories Hose Kit Layout Typical Model Number: TOF200A–D–1–A–1–P–6–2–A–F–1–N–1–1–D–P–N-N Model TOF200A Code A 1 2 55 gal./200 liter Hot Melt Drum Unloader Air Motor Selection NXT 2200 HLS quiet air motor (23:1 Power Ratio) with pump NXT 3400 HLS quiet air motor (36:1 Power Ratio) with pump If Code E option N is selected, then Codes F and G must also be option N and Code H is ignored. Code F Customer’s Power Supply Voltage 2 220/240 Vac 50/60 Hz 3 phase 3 380/400 Vac 50/60 Hz 3 phase 4 470/490 Vac 50/60 Hz 3 phase 5 570/590 Vac 50/60 Hz 3 phase N No electrical control panel 3 NXT 6500 HLS quiet air motor (70:1 Power Ratio) with pump N No air motor or pump B Standard unit – uses EasyKey 4 NXT 2200 HLS quiet air motor (23:1 Power Ratio) with pump and heavy duty packings A Advanced unit – EasyKey with discrete I/O, Ethernet, light tower, and proximity switches. 5 NXT 3400 HLS quiet air motor (36:1 Power Ratio) with pump and heavy duty packings T Tandem primary unit – Unloader A in a primary unit. 6 NXT 6500 HLS quiet air motor (70:1 Power Ratio) with pump and heavy duty packings S Tandem secondary unit – Unloader B in a tandem unit. N No electrical control panel Code B Heated Platen Style Code G Display and Interface Options A MegaFlo high flow drum platen Code H B Standard fin design drum platen E English C Smooth bottom (no fin) drum platen F French Tire Plate Seal Style G German 2 Black EPDM/EPDM, SS wire braid 400oF hose wipers w/spring retention S Spanish J Japanese 1 lower Black EPDM/Chlorobutyl, SS wire braid 375oF hose wiper and 1 upper White Silicone 375oF T-wiper C Chinese (Simplified) Code C 1 2 3 4 Code D 1 lower Black EPDM/Chlorobutyl, SS wire braid 400oF hose wiper and 1 upper Green Silicone, fiberglass braid 400oF, hose wiper 2 White Silicone 250oF T-Wipers Drum Ram Style P Pneumatic Ram H Hydraulic Ram Code E 6 Product Description Number of Heat Zones 6 6 Zones 8 8 Zones N No electrical control panel (includes pneumatic controls, independently mounted) Code J Language Selection Drum Clamp Options 1 Fiber drum reinforcement clam shell 2 Heavy duty drum band clamp 3 Drum ram post saddle clamps N Code K N Y Code L No drum clamp option Vent Hood Kit None Vent Hood Kit Swirl Solenoid Kit N None 1 Single Swirl Solenoid Kit 2 Dual Swirl Solenoid Kit 311208A Overview N Code M None Type of Hose Connection P Manual gun bottom feed with Swirl & .030 orifice None Q Manual gun top feed with Swirl & .030 orifice 1 Single hose and end-of-hose device R 243694 with Swirl & .030 orifice 2 Dual hose and end-of-hose device from tee kit S 3 Hose to (compensator or regulator) with either (second hose to dispense valve and end-of-hose device) or to (end-of-hose device) without a second hose. N 244909 with Swirl & .030 orifice Code Q Hose 2 B -8 (.41” ID) by 10 feet, 3000 psi C -8 (.41” ID) by 15 feet, 3000 psi Hose 1 D -8 (.41” ID) by 10 feet for Air Swirl, 3000 psi -8 (.41” ID) by 10 feet, 3000 psi E -8 (.41” ID) by 15 feet for Air Swirl, 3000 psi C -8 (.41” ID) by 15 feet, 3000 psi H -10 (.51” ID) by 6 feet, 3000 psi D -8 (.41” ID) by 10 feet for Air Swirl, 3000 psi J -10 (.51” ID) by 10 feet, 3000 psi -8 (.41” ID) by 15 feet for Air Swirl, 3000 psi K -10 (.51” ID) by 15 feet, 3000 psi H -10 (.51” ID) by 6 feet, 3000 psi L -10 (.51” ID) by 20 feet, 3000 psi J -10 (.51” ID) by 10 feet, 3000 psi M -10 (.51” ID) by 25 feet, 3000 psi K -10 (.51” ID) by 15 feet, 3000 psi N None L -10 (.51” ID) by 20 feet, 3000 psi P -12 (.62” ID) by 10 feet, 3000 psi M -10 (.51” ID) by 25 feet, 3000 psi Q -12 (.62” ID) by 15 feet, 3000 psi N None R -12 (.62” ID) by 20 feet, 3000 psi -12 (.62” ID) by 10 feet, 3000 psi S -12 (.62” ID) by 25 feet, 3000 psi -12 (.62” ID) by 15 feet, 3000 psi T -16 (.87” ID) by 6 feet, 3000 psi -12 (.62” ID) by 20 feet, 3000 psi U -16 (.87” ID) by 10 feet, 3000 psi -12 (.62” ID) by 25 feet, 3000 psi V -16 (.87” ID) by 15 feet, 3000 psi T -16 (.87” ID) by 6 feet, 3000 psi W -16 (.87” ID) by 20 feet, 3000 psi U -16 (.87” ID) by 10 feet, 3000 psi X -16 (.87” ID) by 25 feet, 3000 psi V -16 (.87” ID) by 15 feet, 3000 psi Y -20 (1.13” ID) by 10 feet, 3000 psi W -16 (.87” ID) by 20 feet, 3000 psi Z -20 (1.13” ID) by 15 feet, 3000 psi -16 (.87” ID) by 25 feet, 3000 psi Code R -20 (1.13” ID) by 10 feet, 3000 psi E Manual gun with top feed swivel -20 (1.13” ID) by 15 feet, 3000 psi F Manual gun top feed with electric switch End of Hose 1 Device G Manual gun with bottom feed swivel 240V 23:1 heated pressure compensator valve H Manual gun with bottom feed with electric switch 240V 51:1 heated pressure compensator valve J Air operated heated dispense valve C Heated distribution manifold K Air operated high flow heated dispense valve D Heated air operated mastic pressure regulator L Air operated snuff-back heated dispense valve Manual gun with top feed swivel M 45” distribution header with valve F Manual gun top feed with electric switch N None G Manual gun with bottom feed swivel P Manual gun bottom feed with Swirl & .030 orifice H Manual gun with bottom feed with electric switch Q Manual gun top feed with Swirl & .030 orifice J Air operated heated dispense valve R 243694 with Swirl & .030 orifice Air operated high flow heated dispense valve S 244909 with Swirl & .030 orifice Code N B E P Q R S X Y Z Code P A B E K L Air operated snuff-back heated dispense valve M 45” distribution header with valve TOF200A Code - A - B - C - D - E - F - G - H End of Hose 2 Device - J - K - L - M - N - P - Q R Model Code Layout 311208A 7 Overview Component Identification Before you install the system you should be familiar with the system components. See FIG. 1 for the Therm-O-Flow system components. Air Line Components The following components are included with the unit. See FIG. 1. • System Master Air Valve (A) is used to shut off the air supply to the system. • Air Line Filter (B) removes dirt and moisture from the compressed air supply. • Air Motor Air regulator (C) and (V) control the outlet pressure by adjusting the air pressure to the air motor. • Air Motor Master Air Valve (D) is used to shut off the air supply to the air motor and bleed trapped air from the air motor. • Air motor Air Supply Hose connects the air regulator to the air motor. Air and Fluid Hoses The Therm-O-Flow 200 requires Graco single-circuit material hoses rated at a maximum of 1250 watts. When installing a system make sure: • all air and fluid hoses are properly sized for your system. Heat Control Zone Selection The Therm-O-Flow 200 has 6 or 8 heat zones. Zones 1 and 2 are always used for the heated drum platen and the heated pump. Zones 3 and 4, 5 and 6, and 7 and 8 are each available as paired zones through 16-pin connectors. The heated hoses have a 16-pin connector on the inlet end cable, and an 8-pin connector on the outlet end cable. All heated valves, manifolds, and heaters are equipped with an 8-pin matching connector. Pneumatic Control Panel The pneumatic control panel includes the following. See FIG. 1. • Auto Depressurization Valve exhausts air from the air motor at shutoff. The built-in control delays start-up to allow material to thoroughly heat. • Ram Air Regulators (N, P) control the air pressure to the ram. There are separate air regulators to control the ram pressure in the up and down directions. • Ram Up/Down Lever (R) changes the direction of the ram. • Blow-off air regulator (T) controls the air pressure to the platen blow-off valve. • Platen Blow-off Valve (S) directs air to the underside of the platen when depressed. User Display (EasyKey™) • A simple user interface consisting of an LCD display and keypad. • Keypad contains the buttons which control the Therm-O-Flow 200 operations. Vent Hood Kit (if supplied) The vent hood assembly is designed to efficiently draw fumes to the factory exhaust system during drum change-out. This assembly requires a connection to a factory ventilation system that draws a minimum air flow of 8.4 m3/min (300 scfm). This kit is recommended for Polyurethane Reactive (PUR) applications. 8 311208A Overview Component Identification M U AB L W J AA S K T C R TI8134A A V N P E D Y,Z F G H B TI8158A TI7936A X FIG. 1: Component Identification Key: A B C D E F G H J K L M System Master Air Valve (bleed-type) Air Line Filter Air Motor Air Regulator (bleed-type) Air Motor Master Air Valve (bleed-type) Ram Heated Pump Platen Air Inlet (1/2” npt) Electrical Control Panel Main Power Disconnect Switch EasyKey™ Display and Keypad Pneumatic Control Panel 311208A N P R S T U V W X Y Z AA AB Ram Up Air Regulator Ram Down Air Regulator Ram Up/Down Lever Platen Blow-off Valve Blow-Off Air Regulator Electrical Power Input Air Motor Enable Solenoid/Depressurization Valve NXT Air Motor Air Motor Remote Piloted Air Regulator Ram Plate Bleed Stick Drum Blow Off Valve (behind ram plate bleed stick Y) Maintenance Call Ethernet Connection 9 Typical Installation Typical Installation The typical installation discussed and shown is only a guide for selecting and installing system components and accessories. See FIG. 2. Contact your Graco distributor for help in designing a system to suit your particular needs. • Make sure there is sufficient overhead clearance for the pump and ram when the ram is in the fully raised position. • If you are installing a vent hood make sure there is sufficient horizontal clearance for it. The air-powered ram extruder forces high viscosity fluids into the intake valve of the fluid pump. Wiper rings and other accessory equipment for use with this ram are listed in Technical Data on page 85. • Make sure the air regulators for the pump and ram are fully accessible. • Make sure there is easy and safe access to an appropriate electrical power source. The National Electrical Code requires 3 feet of open space in front of the electrical panel. For information about converting the ram from air to hydraulic operation, contact your Graco distributor. 2. Make sure that you will be able to level the base of the ram using metal shims. Power Requirements See Technical Data on page 85. Selecting a Location for the Ram Refer to the Dimensions drawing on page 84 for ram mounting and clearance dimensions. When selecting a location for the ram keep the following in mind: 1. There should be sufficient space for installing and using the equipment. 10 3. When you bolt the ram to the floor the anchors should be long enough to prevent the unit from tipping. Refer to the Dimensions drawing on page 84 for more information. 4. If you are installing a vent hood, make sure the ram is installed near a connection to the factory ventilation system. System Accessories and Modules Before you install the system you should be familiar with the parts discussed in the subsequent paragraphs. 311208A Typical Installation Typical Installation (Advanced Unit Shown) 101 Electrical Control Panel 102 Ram Module 104 Heated Follower Plate 106 Depressurization Valve/Air Motor Enable Solenoid 109 Pump and Air Motor Assembly 115 Air Motor Mounting Bracket 202 Air Filter 204 Air Motor Remote-Piloted Air Regulator 211 Ram Up/Ram Down Lever 214 System Master Air Valve (required) 226 Main Air Line Inlet 319 Ram Plate Bleed Stick 327 Lower Wiper 329 Upper Wiper 330 Drum Blow Off Valve 332 Drum Low and Empty Sensors Lift Locations (if air is supplied to the system and ram lever is set to down) 101 CAUTION Do not use motor lift ring to lift entire system. See ram lift locations, FIG. 2. 109 115 332 211 102 106 TI7937A 319 329 214 226 202 204 327 330 104 TI8158A FIG. 2: Typical Installation 311208A 11 Typical Installation Heat Control Zone Selection The Therm–O–Flow 200 can be ordered with 6 (code E–6) or 8 (code E–8) heat zones (see Fig.3). Zones 1 and 2 are always used for heated drum platen and the heated pump. Zones 3 and 4, 5 and 6, and optional zones 7 and 8 are each available as paired zones through a 16–pin connector. :/.% #ONTROL 0LATEN :/.% #ONTROL The heated hoses have a 16–pin connector on the inlet end cable, and an 8–pin connector on the outlet end cable. All heated valves, manifolds and heaters are equipped with an 8–pin matching connector. Accessory cables are available for other possible combinations. See FIG. 3. 6ALVE 6ALVE 6ALVE (OSE (OSE (OSE :/.% #ONTROL :/.% :/.% #ONTROL #ONTROL :/.% #ONTROL :/.% #ONTROL WATTS MAX WATTS MAX WATTS MAX WATTS MAX 0UMP WATTS MAX :/.% #ONTROL WATTS MAX 4) FIG. 3: Heat Control Zone Selection 12 311208A Typical Installation Air Line Modules Air Motor bleed-type master air valve (D) is required in your system to relieve motor air pressure. Trapped air can cause the pump to cycle unexpectedly, which could result in serious bodily injury. 4-Regulator Air Control Module (shown) For more information, refer to FIG. 1 on page 9. The following components are included with the module: • System Master Air Valve (bleed-type) (D) is used to shut off the air supply to the entire supply unit. • Air Motor Master Air Valve (bleed-type) (D) is supplied in your system to relieve air trapped between it and the air motor when the valve is energized (see Warning above). This bleed valve should be easily accessible and located downstream from the air regulator. 311208A • Air Motor Air Regulator (C) controls pump outlet pressure by adjusting the air pressure to the air motor. It is located on the pneumatic control panel. • The Air Motor Enable Solenoid, see FIG. 1 page 9, letter (X) delays startup to allow material to heat thoroughly. • Ram Air Regulator (N,P) controls the air pressure to the ram. There are separate air regulators to control the ram pressure in the up and down directions. • Ram Plate Blow-off Valve (S,T) controls the air to the ram plate blow-off. Part No. 297401 is used if “None” is selected for Configurator Code E, F, and G. Fluid Line Accessories (Typical) A pressure compensator valve controls fluid pressure to the gun/valve, and dampens pressure surges. Install the pressure compensator valve in the position shown in the Typical Installation, using adapters as necessary. 13 Installation Procedure Installation Procedure CAUTION Do not use motor lift ring to lift entire system. See lift locations, FIG. 2. The installation procedure includes: front of the pneumatic control panel and the electrical control panel. 4. Make sure there is easy and safe access to an appropriate electrical power source. The National Electrical Code requires 3 ft (0.9 m) of open space in front of the electrical panel. 5. Apply 50 psi download pressure to ram. • unpacking the ram • locating and installing the ram • mechanical setup • electrically connecting hoses to the electrical control panel • grounding the system • connecting the electrical control panel to a power source 7. Lift off pallet using a crane or a forklift. • connecting to an air source 8. Position the ram in the desired location. • setting controls on the electrical control panel 9. Level the base of the ram, using metal shims. Unpacking 1. Inspect the shipping box carefully for damage. Contact the carrier promptly if there is damage. 2. Open the box and inspect the contents carefully. There should not be any loose or damaged parts in the box. 3. Compare the packing slip against all items in the box. Report any shortages or other inspection problems immediately. CAUTION Do not use motor lift ring to lift entire system. See lift locations, FIG. 2. 4. Remove the unit from the skid and place it in the desired location (See Location Requirements). Location Requirements 1. Make sure there is sufficient overhead clearance for the pump and ram when the ram is in the fully raised position (approximately 110 in. [280 cm]). 2. If you are installing a vent hood, make sure there is sufficient horizontal clearance for it. Locate the ram near a connection to the factory ventilation system. 3. Make sure the air regulators for the pump and ram are fully accessible, with room to stand directly in 14 6. Wrap the bar with the lifting sling. See FIG. 2 for proper lift spots. CAUTION Do not use motor lift ring to lift entire system. See lift locations, FIG. 2. 10. Bolt the ram to the floor, using anchors that are long enough to prevent the unit from tipping. 11. If your unit is equipped with optional level controls, remove from the electrical control panel and twist into place on top of the electrical control panel. Mechanical Setup 1. Check, and if necessary, tighten the heated hose connection at the pump outlet. 2. Wrap exposed fittings on pump outlet with Nomex insulation and secure insulation using fiberglass tape. 3. Fill displacement pump wet cup 2/3 full with Graco Throat Seal Liquid (TSL). 4. Back-off all air regulators to their full counterclockwise position. The ram UP/DOWN lever is shipped inside the pneumatic control panel and should be screwed onto the face of the control now. 5. Connect a 1/2 in. (13 mm) air line from an air source to the system air inlet, see FIG. 1, page 9, letter (H) capable of delivering a minimum of 15 cfm (0.4 m3/m) at 100 psi (0.7 MPa, 7.0 bar). Do not use quick disconnects. 311208A Installation Procedure Electrical Setup Electrically Connect Hoses Connect Power Source The Therm-O-Flow 200 requires Graco single-circuit material hoses rated at a maximum of 1250 watts. The electrical control panel comes already attached and wired to the ram, however before the supply unit becomes functional you must connect the electrical control panel to a power source. 1. Securely tighten 16-pin electrical connectors on long heated hose leads into 16-socket receptacles located on the back of the electrical control panel. See FIG. 4. 2. Securely tighten 8-socket electrical connectors on short heated hose leads into 8-pin receptacle located on the dispense valves. Hose One Hose Two Required voltage and amperage is noted on the control panel label. Also see Table 1. Before running power to the unit, make sure the plant electrical service meets the machine’s electrical requirements. 1. Open electrical enclosure door and locate main disconnect. 2. Have a qualified electrician connect your plant power to the electrical control panel disconnect switch according to local codes. A 1-3/8 in. (35 mm) diameter opening is provided on top of the panel, above the connections. This opening is suitable for a 1 in. npt conduit or strain relief fitting. Hose Three (Optional) TI8136A FIG. 4: Rear View of Electrical Control Box Table 1 Electrical Requirements AC Panel Voltage HZ Phase 220 / 240 50/60 3 380 / 400 50/60 3 470 / 490 50/60 3 570 / 590 50/60 3 Platen Selection Full Load Amps BB & BC BA BB & BC BA BB & BC BA BB & BC BA 70 80 42 48 35 40 29 32 BB = Standard grid platen: 18 Kw BA = Mega-Flow platen: 21 Kw BC = Smooth bottom platen: 18 Kw 311208A 15 Installation Procedure Grounding • Air and fluid hoses: Use only electrically conductive hoses. Ground the supply unit as instructed here and in the individual component manuals. • Dispensing/Spray Gun: Follow the dispensing/spray gun grounding instructions. • Object material is applied to: Ground according to your local code. • Material drums: Ground according to your local code. Use only metal drums placed on a grounded surface. Do not place the drum on a nonconductive surface, such as paper or cardboard, which interrupts the grounding continuity. • Maintain grounding continuity when flushing or relieving pressure: Follow the instructions in your separate gun manual for safely grounding your gun while flushing. To reduce the risk of fire, explosion, or electric shock: • The power source conduit is not an adequate ground for the system. The unit must be bonded to either the building ground or a true earth ground. To reduce the risk of static sparking, ground the pump, the object being dispensed to, and all other spraying/dispensing equipment used or located in the spraying/dispensing area. Check your local electrical code for detailed grounding instructions for your area and type of equipment. 16 311208A Installation Procedure Connecting the Electrical Control Panel to a Power Source The electrical control panel (FIG. 5) comes already attached and wired to the ram, however before the supply unit becomes functional, you must connect the electrical control panel to a power source. Have a trained electrician connect the electrical control panel (Fig. 5) to a grounded electrical source that has the required service ratings, see Electrical Requirements on page 15. CAUTION If power and grounding connections are not done properly, the equipment will be damaged and the warranty will be voided. Check the label on the control box for the proper voltage. BB = Standard grid platen: 18 Kw BA = Mega–Flow platen: 21 Kw BC = Smooth bottom platen: 18 Kw Electrical Control Panel For information about specific terminal locations and connections, see All Models Control Panel Component Layout on page 82. To connect the control panel to the electrical source: 1. Locate the opening in the control panel’s top housing for the conduit that will enclose the wire from the facility’s power source. The hole will accept a 1” conduit fitting. It is 1.3” dia. (33mm). 2. Thread the wire from the power source into the control panel housing, and then connect the power source wires to the appropriate terminals on the DISCONNECT switch. TI7935A FIG. 5: Electrical Control Panel 311208A 17 Installation Procedure Check the Resistance Between the Supply Unit and the True Earth Ground. To reduce the risk of fire, explosion, or electric shock the resistance between the supply unit components and true earth ground must be less than 0.25 ohms. Have a qualified electrician check the resistance between each supply unit component and the true earth ground. The resistance must be less than 0.25 ohms. If the resistance is greater than 0.25 ohms a different ground site may be required. Do not operate the system until the problem is corrected. Use a meter that is capable of measuring resistance at this level. Sensor Resistance Checks. To reduce risk of injury or damage to equipment, conduct these electrical checks with the main disconnect OFF. The package includes up to eight heat sensors and controllers for each of the heated zones. To check sensor resistance: 1. Make sure the power is off and that the disconnect switch is in the OFF position. 2. Make electrical resistance checks for the components. 3. Replace any parts whose resistance readings do not comply with the ranges listed in the RTD Sensors chart below. Checking Resistance. Check resistance at ambient room temperature (63°– 77° Fahrenheit). RTD Sensors Zone Component 1 2 3 4 5 6 7 8 18 Ram Plate Fluid Pump Dispense Hose 1 Dispense Gun 1 Dispense Hose 2 Dispense Gun 2 Dispense Hose 3 Dispense Gun 3 Terminals Value Range 2011 & 2012 2051 & 2061 2081 & 2091 2111 & 2121 2261 & 2271 2291 & 2301 2321 & 2331 2351 & 2361 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 108 +/- 2% ohms 311208A Installation Procedure Heater Resistance Checks. 2. Make electrical resistance checks for the components. Refer to All Models Control Panel Component Layout on page 82 for wiring diagram information. To reduce risk of injury or damage to equipment, conduct these electrical checks with the main power disconnect OFF. 3. Replace any parts whose resistance readings do not comply with the ranges listed in Table 1 on page 15. To check heater resistance: Check resistance at ambient room temperature (63°– 77°F) (17°– 25°C). 1. Make sure the power is off and that the disconnect switch is in the OFF position. Table 2 Heaters Zone Component 1 Platen Between Terminals AB, BC, CD, DE, EF, FA AB, BC, CD, DE, EF, FA For Unit Voltage Platen Model Code Resistance Values (ohms) 220/240 VAC 16.5Ω +1 / -2 19.5Ω +2 / -3 16.5Ω +1 / -2 19.5Ω +2 / -3 16.5Ω +1 / -2 19.5Ω +2 / -3 16.5Ω +1 / -2 19.5Ω +2 / -3 100,000Ω Min 380/400 VAC 470/490 VAC AB, BC, CD, DE, EF, FA 570/590 VAC BA BB, BC BA BB, BC BA BB, BC BA BB, BC Any to GND Table 3 Heaters Zone 2 Component Pump Between Terminals T1/T3, T2/T3, B1/B3, B2/B3 T1/T3, T2/T3, B1/B3, B2/B3 For Unit Voltage Platen Model Code Any Any 380/400 470/490 Same 311208A 570/590 Resistance Values (ohms) 192.0 +/- 19.2Ω BA BB, BC BA BB, BC BA BB, BC 19 Installation Procedure Overview of the Temperature Controller Settings a. If the two substances are compatible omit the remaining steps in this procedure and refer to the start up and operation instructions. Temperature controls are set in the zone configuration setup screens. See Run Screens on page 24 for information about setting temperature controls. b. If the two substances are incompatible perform the remaining steps in this procedure to flush the system at ambient temperature. P, I, and d settings are preset for device types and will not need to be changed. Refer to the Zone Setup Screens on page 25 for a list of device types and how to set them for each zone. Purging the System Purging the system before its initial use can prevent material contamination, which may cause the material to fail or perform poorly. CAUTION Purge the system before performing the initial material loading procedure. The system was factory- tested using a light soluble oil, a soybean oil, or some other oil as tagged. Flush the system to avoid contaminating the material that has been designated for initial material loading. To purge the system perform the following procedure: Use fluids that are chemically compatible with the equipment wetted parts. See the Technical Data sections of all the equipment manuals. 3. Select a drum of material that can eliminate the factory-test oil from the system. If necessary, check with Graco or the material supplier for a recommended solvent. 4. Before purging be sure the entire system and waste drum is properly grounded. Refer to Grounding on page 16. 5. Turn all heat zones to 70°F (21.1°C). This allows air to the air motor, with no alarms, in a cold state. Remove any dispense valve orifices before purging. Reinstall after purging has been completed. 1. Select the material for the initial material load. 2. Verify whether the factory-test oil and the initial material load are compatible: 6. Purge the material through the system for approximately 1 to 2 minutes. 7. Remove the drum if purge material was used. 20 311208A Installation Procedure Optional Low Level Kit 253559 This kit is standard on Code G options A,T, and S. The kit must be purchased if Code G option B is selected. The Low Level Kit is used to indicate that a drum is EMPTY or LOW, depending on the adjustment of the proximity switch. The kit contains a sensor mounting bracket (A), activator (B), sensors (C), and a cable for connecting to the Therm-O-Flow 200 control panel. See FIG. 6. The low and empty conditions will be displayed in the status bar of the EasyKey display. An optional light tower is also available. With the optional light tower a yellow light indicates a drum low condition. A flashing yellow light indicates a drum empty condition. In a tandem system a red light indicates both drums are empty. When ordering this kit individually to connect to an existing Therm-O-Flow 200 unloader assembly, use the bolts, screws and washers provided to mount to the closest ram post to the control box. Mount the limit switches to the bracket as shown. Increasing the distance between the low and empty sensors (C) increases the heat up time for the tandem secondary system. Lowering the drum empty sensor forces the heated follower plate lower into the drum. If this is set too low the pump could cavitate causing a system alarm. A ",5% -47 490 * * #/2$ '2)0 7)2%$ !4 '2!#/ C 02/8 3%.3/2 ,/7 ". 7( 0#" 5.,/!$%2 "/!2$ "+ B %84%2.!, #/.42/, #/- "5 "+ 7( 02/8 3%.3/2 %-049 ". "5 #/2$ '2)0 * ". TI8137A !)2 3/,%./)$ #", "5 '.7( #/2$ '2)0 '2%%. -47 490 * ", .# ", ", ", 2%3%26%$ &/2 &5452% 53% * (!2.%33 Therm-O-Flow 200 with Proximity Switches Installed. Ram is in full down position. 2.0” Proximity Sensor Connections !7' 490 2.0” 3.0” TI8161A FIG. 6: Optional Low level Kit 311208A 21 Operator Controls Operator Controls EasyKey Display and Keypad Main Power Disconnect The EasyKey Display is a simple user interface consisting of an LCD display (A) and keypad (B). See FIG. 8. Turns system power on or off. Includes system circuit breaker. See FIG. 7. POWER ON Use to input numerical data, enter Setup screens, scroll through screens, and select setup values. See EasyKey Display Screens page 24 for additional keypad/screen navigation information. The EasyKey includes numbered keys to enter values in setup and the following function keys. See Table 4. A TI8138A POWER OFF TI8139A FIG. 7: Main Power Disconnect B In a Tandem System, the secondary unloader provides 24VDC power to the EasyKey display. This allows the primary unloader to be powered down for maintenance without interrupting production. All accessories (light tower, swirl, etc.) and the display board on the primary system will have power when the secondary unloader is powered on and the primary unloader is powered off. TI8140A FIG. 8: EasyKey Display and Keypad Table 4: Key Descriptions Key Function Setup: press to enter or exit Setup mode. Enter: if cursor is in drop-down list box, press Enter key to view drop-down list. Press Enter to save a value either keyed in from the numerical keypad or selected from a drop-down list. Up Arrow: move to previous field or drop-down list item. Down Arrow: move to next field, or drop-down list item. Left Arrow: move to previous screen. 22 311208A Operator Controls Table 4: Key Descriptions Right Arrow: move to next screen. System On/Off: On starts system. Activates , , , and keys. Heat State Toggle: Starts heaters in all zones where they are enabled. Cycles through heat states (Heat Off, Heat On/Heat Soak/Run, Setback). Clear: Clears alarms and warnings. Pump Ready: Allows pump to cycle after a DRUM EMPTY condition is removed or a MOTOR ERROR is cleared. Pump Crossover: Transitions the active system to the inactive unloader. LCD Display E Temperature Readout: Shows current temperature of each zone, in temperature units selected in Table 7, see page 29. F Status Bar: shows current operation mode or alarm. G Current Date and Time H Security Level: a padlock appears on the screen if a password is required to enter Setup mode. If the password was set to 0, no padlock appears and setup can be entered without a password. The two run screens show graphical and text information related to setup and spray operations. A screen saver option is available in the Advanced Setup screen 4 (see Table 7, page 29). A B C D Animation: When there is flow, the air motor piston and pump displacement rod move and the gun appears to spray. Total Job Volume: recorded in units selected in Table 7, see page 29. Press twice to reset Total Job Volume to zero. Current Flow Rate: Flow rate displayed in units selected in Adv tab of setup. See Table 7 on page 29. Zone Number and Icon: Shows which zone data is currently being displayed. Icon indicates component for that zone. 311208A You must be in system off mode to enter setup . Alarm Alerts the user to an alarm condition. Press the alarm. to clear 23 EasyKey Display Screens EasyKey Display Screens Power Up Screens When the EasyKey power switch is turned on, the Graco logo screen and the phrase establishing communication displays for several seconds before the system run screen appears. If the EasyKey cannot communicate with any board during the power on phase, the phrase “Communication Error” displays on the Graco Logo screen. Once communications are established the System Run Screen appears. See FIG. 10. Run screens and setup screens are the two main screen types that provide information and system control. Zone Run Screen This screen contains all specific zone information for each zone in the system. Tandem and expansion systems will contain two zone run screens A and B, one for each set of 4,6, or 8 zones. The Zone Run screen steps through the operating status of each zone in sequence. See FIG. 10. Temperature setpoints are adjustable on this screen if Setpoint Adjust is turned on. See Advanced Screens, page 28. Setpoints will be highlighted in a box. Use the move through the setpoints. or keys to Run Mode Run Screens System Run Screen From the Zone Run screen, press or to access the System Run screen. This screen displays a summary of all zones. See FIG. 9. FIG. 10: Zone A Run Screen FIG. 9: System Run Screen FIG. 11: Zone B Run Screen 24 311208A EasyKey Display Screens Setup Mode Zone Setup Screens Entering Setup Zone Setup has 2 screens. The screen number appears on the right side of the screen. See FIG. 12 and FIG. 13. See Table 5 : Zone Setup Screens on page 26 for settings. Press to enter or exit Setup. You must be in system off state to enter setup. Password Screen If a password was enabled, you must enter the password before entering Setup mode. See Table 7, page 29. Entering the wrong password returns you to the Run screens. Press to show drop-down lists and to enter your selection. If a password is enabled, “Setup Locked” displays momentarily after exiting Setup mode and returning to the Run screens. Setup Screen Menu The setup screens, contains all four tabs across the bottom of the screen for zone, timer, report, and advanced screens. The Setup screen menu appears at the bottom of all Setup screens, with the current screen highlighted. See FIG. 12 and FIG. 13. FIG. 13: Setup Screen 2 FIG. 12: Setup Screen 1 311208A 25 EasyKey Display Screens Table 5: Zone Setup Screens Screen Setting 1 Unloader See (FIG. 12) Zone Selection Numeric Description In single system always A. In tandem or expansion system it is selectable between A and B. Enter desired zone (1-8). Zone 1 (platen) and zone 2 (pump) are fixed. All other zones are selectable (hose, gun, regulator, manifold, meter). Select On or Off to turn zone heat on or off. Select desired component for heat zones 3 through 8. Zone 1 (platen) and zone 2 (pump) are fixed. Zone icons on Run screens will match selections. Enable On/Off Zone Type Hose/ Gun/ Regulator/ Manifold/ Meter Assign to Tandem system only. Determines unloader zone is assigned to for heat control. 2 Setpoint Numeric Enter the temperature to which material needs to be heated. Consult material See (FIG. 13) supplier for recommended material application temperatures. Setback Numeric Enter desired temperature to maintain during downtime, so material will not cool completely. Calibrate +/Select +/ -, then enter desired calibration temperature. Use if Zone Temp Numeric reading does not match ambient temperature of location. Alarm Numeric Enter temperature range from setpoint at which an alarm condition will occur. Range +/Warning Numeric Enter temperature range from setpoint at which a warning condition will Range +/occur. 26 311208A EasyKey Display Screens Timer Screen Report Screen Timer settings are explained in Table 6 : Timer Setup Screen. See also FIG. 14 and FIG. 15. The Report screen shows the most recent 12 alarms, with the date and time. Use the all the alarms. See FIG. 16. or keys to see Grand total is displayed in liters, gallons, pounds, kilograms, or cycles, based on the units set in Advanced screen 2. See Table 7, page 29. Grand total cannot be reset. There are no selectable settings on the Report screen. FIG. 14: Timer Screen Disabled FIG. 16: Report Screen FIG. 15: Timer Screen, with individual day and setback action selected Table 6: Timer Setup Screen Setting Day Selection Individual/ M-F/ S-S/ All Description Select desired day(s). Selected days will be highlighted in calendar on screen. Event Number 1-5 Select desired event number (maximum of 5 events per day). Action None No timer value entered for selected event. Off Turns off timer for selected event. On Turns on timer for selected event. Setback Turns on setback function for selected event. Clear All Clears all timer events for selected day. Numeric Enter hours (0-23) and minutes (0-59). Time 311208A 27 EasyKey Display Screens Advanced Screens Advanced setup has 3 screens. The screen number appears on the right side of the screen. See FIG. 17 through FIG. 19, and Table 7 : Advanced Setup Screens on page 29. FIG. 17: Advanced Screen 1 Press to show drop-down lists and to enter your selection. FIG. 19: Advanced Screen 3 FIG. 18: Advanced Screen 2 The specific gravity listed in the material data sheet may be for solid form at room temperature. For accurate weight calculations, Specific Gravity at the application temperature should be used otherwise these weight calculations may be inaccurate. 28 311208A EasyKey Display Screens Table 7: Advanced Setup Screens Screen Setting Selection 1 Language English, See (FIG. 17) Spanish, German, French, Japanese, Chinese, custom Number 6+8 / 6+4 / Zones 8+4 / 6+6 / 8+8 Change Yes/No Setpoint Tempera- °F/°C ture Units Heat Soak Numeric 2 Units See (FIG. 18) 7-Day Timer Pump Inactivity External Pump Enable Runaway Rate Specific Gravity 3 Month See (FIG. 19) Day Year Time Password Screen Saver Time 311208A cycles/ gallons/ liters/ lbs/ kg On/Off Yes/No On/Off Numeric Numeric Numeric Numeric Numeric Numeric Numeric Numeric Description Language displayed. The language is set at factory. The number of zones in system is set at the factory. Select Yes or No to allow operator to change setpoints from Zone Run screen. Select desired temperature units. Enter time (in minutes) to delay air motor start after all zones reach temperature setpoints. Select desired units. Affects units used for Run screen job totalizers and Report screen grand total volume. (Enable / Disable 7 day timer). If pump does not move for 2 hours, zones switch to setback temperatures. If 2 more hours pass without pump movement, system shuts off. Select Yes or No. Allows external device to control pump. Enter speed (cycles/min) at which air motor will be shutdown, to prevent runaway. Used to determine units when weights are selected (Lbs / Kgs). Select current month (1-12). Select current day (1-31). Select current year (4 digits). Enter hours (0-23) and minutes (0-59). Is only used to enter Setup mode. Default is 0, which means no password is required to enter setup. To set a password, enter a number (1–9999). Enter minutes (1-99) for screen to be inactive before screen saver turns on (screen dims). Press any key to restore. Default is 0 (screen saver off). 29 Setup Setup Purge Before Using Equipment 2. Place the ram UP/DOWN lever in the UP position. The equipment was tested with lightweight oil, which is left in the fluid passages to protect parts. To avoid contaminating your fluid with oil, purge the equipment with a compatible material before using the equipment. See Purging the System, page 20. Set Values on EasyKey Set desired values on EasyKey setup menus. See Setup Mode, page 25. Material Loading CAUTION Do not use a drum of material that has been dented or otherwise damaged; damage to the platen wipers may result. TI8141A 3. Slowly turn the ram UP regulator (N) clockwise until the ram begins to rise See. FIG. 20. 4. When the ram is fully raised, install the drum centering guides. An empty drum clamp can interfere with up and down operation of the ram. When raising or lowering the ram, make sure the drum clamp stays clear of the platen assembly. Before loading material, make sure there is a minimum overhead clearance of 110" (2.8 m) and all air regulators are backed off to their full counterclockwise position. 1. Open the system master air valve (bleed-type) (A). N P A TI8142A FIG. 20: Pneumatic Control Panel 5. Apply a thin coating of high temp grease lubricant (part no. 115982) to the platen drum seals (V). See FIG. 21. TI835A 6. Add TSL fluid to wet cup. Fill approximately 2/3 full. 7. Open drum, remove any packing material, and inspect material for any contamination. 8. Slide the drum into position, positioning it evenly between the drum centering guides. Be sure it is pushed all the way against the stops at the back of the ram baseplate. 30 311208A Setup 9. Remove the platen bleed handle (W). See FIG. 21. 10. Place the ram UP/DOWN lever in the DOWN position. 12. After the platen seals (V) enter the material drum, adjust the ram DOWN air regulator (P) to 30-50 psi (207-345 kPa, 2.1-3.4 bar). See FIG. 20 and FIG. 21. 13. When the ram stops, reinsert the platen bleed handle (W) and hand tighten. See FIG. 21. TI8141A CAUTION Lowering the ram without a drum in place can damage the drum centering guides (if equipped). 11. See FIG. 20. Slowly turn the ram DOWN regulator (P) clockwise to approximately 5-10 psi (34-69 kPa, 0.3-0.7 bar). The platen will begin to lower into the drum. W V TI8143A FIG. 21: Platen 311208A 31 Setup System Heat Up Prime Pump To reduce the risk of bursting a hose, never pressurize a hot melt system before turning on the heat. The air will be locked from the air motor until all temperature zones are within a preset window of the temperature set points. CAUTION The dispense valve must be kept open over a waste container while the system is heating up and also when cooling down. This will prevent a pressure build-up caused by fluids or gasses expanding from the heat. 1. Turn the main disconnect on the electrical control panel door to the ON position. In a Tandem system, after a drum change has occurred on the inactive unloader, pressing the Pump Ready button will allow five minutes of air to the air motor to allow for the pump to be primed. The inactive unloader must be within its warning deviation setpoints and in the Ready or Heat On state. If the five minute timer runs out before the inactive unloader is primed, pressing the Pump Ready button again will repeat the air to the air motor. 1. Make sure the system has completed the approximately 40 minute heat soak cycle and is up to temperature. 2. Close the air motor valve (D). POWER ON D TI8138A TI7936A 2. Press . Display status bar reads Heat Off. 3. Press . The zones begin to heat (provided they are enabled). Display status bar reads Heat On. When temperature reaches setpoint, display status bar reads Run Mode. 3. Adjust the air motor air regulator (C) to approximately 20 psi (138 kPa, 1.38 bar) on pneumatic panel. The air will be locked from the air motor until all temperature zones are within a preset window of the temperature set points, allowing the system to heat fully and complete the material heat soak period. C TI8142A 32 311208A Setup 4. Place a waste container under the bleed stem (Z). Using an adjustable wrench, open the bleed stem counterclockwise 1/3 -1/2 turn. See FIG. 22. 5. If a new drum was installed and the unit is equipped with proximity sensors, press the Pump Ready button 8. If the pump does not cycle, close the pump bleed-type master air valve (D), adjust the air motor air regulator (C) up by 5 psi (34 kPa, 0.3 bar). Never adjust the regulator by more than 5 psi (34 kPa, 0.3 bar) increments. 9. Prime the pump until it moves smoothly in both directions with no air popping or erratic movement and close the pump bleed-type master air valve (D). 10. Close the bleed stem (Z). See FIG. 22. . If the unit is not equipped with proximity Z sensors, press the Clear button if a motor error is present, then press the Pump Ready button . 6. With waste container in place, slowly open the air motor valve (D). D TI8143A TI7936A 7. Make sure the pump begins to cycle and heated material flows from the bleed stem (Z) after several cycles of the pump. 311208A FIG. 22: Bleed Stem 33 Setup Prime System 3. Place the dispense valve over a waste container. 4. Slowly open the system master air valve. 5. Prime the system until a smooth flow of material dispenses from the dispense valve. 1. Close the system master air valve (bleed-type) (A). 2. If using a manual gun, lock the dispense valve trigger open by pulling and securing the trigger using the trigger retainer (Z). 6. Close the system master air valve and release trigger lock. 7. Engage trigger lock. Trigger Lock Engaged Z TI8049A TI8051A 34 The system is now ready to operate. 311208A Operation Operation Pressure Relief Procedure 3. Disengage trigger lock. Trigger Lock Disengaged Follow Pressure Relief Procedure when you stop spraying and before cleaning, checking, servicing, or transporting equipment. This procedure describes how to relieve pressure for the supply unit. Use this procedure whenever you shut off the unit and before checking or adjusting any part of the system to reduce the risk of serious injury. TI8050A 4. Hold a metal part of the gun firmly to a grounded metal pail. Trigger the gun to relieve pressure. 5. Engage trigger lock. 1. Engage trigger lock. Trigger Lock Engaged Trigger Lock Engaged TI8049A TI8049A 2. Close the system master air valve (bleed-type) (A). A 6. Open all fluid drain valves in the system, having a waste container ready to catch drainage. Leave drain valve(s) open until you are ready to spray again. If you suspect the spray tip or hose is clogged or that pressure has not been fully relieved after following the steps above, VERY SLOWLY loosen hose end coupling to relieve pressure gradually, then loosen completely. Clear hose or tip obstruction. 7. To relieve pressure in the ram, see page 36. Trigger Lock Always engage the trigger lock when you stop spraying to prevent the gun from being triggered accidentally by hand or if dropped or bumped. 311208A 35 Operation Ram Pressure Relief Procedure 5. Exhaust air from both sides of the ram: a. Move the ram UP/DOWN lever to the DOWN position until all air is exhausted from one side of the ram. Follow Pressure Relief Procedure when you stop spraying and before cleaning, checking, servicing, or transporting equipment. To relieve air pressure in the ram: 1. Relieve the supply unit pressure, see page 35. 2. Place the ram UP/DOWN lever in the DOWN position. Move the ram to the DOWN position. TI8141 b. Move the ram UP/DOWN lever to the UP position until all air is exhausted from the other side of the ram. TI8141 3. When the ram reaches the full down position, place the ram UP/DOWN lever in the center position (off). 4. Close the system master air valve (bleed-type) (A). TI8141 A TI8135 36 311208A Operation Drum Changing Follow the procedure below to change the drum on a fully heated machine. CAUTION Be sure to reload the empty supply unit with a full drum of material immediately. Do not raise the ram and remove the platen from the empty drum until you are ready to immediately install a new drum. In a Tandem system, after a drum change has occurred on the inactive unloader, pressing the Pump Ready button will allow five minutes of air to the air motor to allow for the pump to be primed. The inactive unloader must be within its warning deviation setpoints and in the Ready or Heat On state. If the five minute timer runs out before the inactive unloader is primed, pressing the Pump Ready button again will repeat the air to the air motor. 1. Place the ram UP/DOWN lever in the UP position. Do not raise the ram and remove the platen from the empty drum unless the supply unit is at full operating temperature. Drum changes can only be performed when the system is heated. An empty drum clamp can interfere with the up and down operation of the ram. When raising or lowering the ram, make sure the drum clamp stays clear of the platen assembly. Do not use a drum of material that has been dented or otherwise damaged; damage to the platen wipers can result. TI8135A 2. Dial ram up regulator pressure to 0 psi. No Proximity Sensors The pump will cavitate and a motor error will appear in the EasyKey status bar. The air motor will shut off and the heat will continue to be applied for approximately 1 hour. With Proximity Sensors Drum empty will appear in the EasyKey status bar. The air motor will shut off and the heat will continue to be applied for approximately 1 hour. If the light tower kit is installed a flashing yellow light indicates that the drum is empty and ready to change. In a tandem system a flashing red light means that both drums are empty and the system has shut down. Excessive air pressure in the material drum could cause the drum to rupture, causing serious injury. The platen must be free to move out of the drum. Attempting to change a drum when the supply unit is cold could result in injury, damage to the equipment, or rupture of the material drum. Never use drum blow-off air with cold adhesive or a damaged drum. Positive pressure is released from the drum when the platen seal is pulled clear. A splatter shield accessory for low viscosity material is available. 311208A 37 Operation 3. Adjust the platen blow-off air regulator (T) to 20-30 psi (138-207 kPa, 1.4-2.1 bar). T TI8142A It is only necessary to lubricate the platen seals on initial material loading. For tandem systems the pump ready button will turn the air motor on for approximately 5 minutes to prime the pump. This can be repeated as necessary. If both unloaders in the system are empty, the pump ready and transition sequence will depend on the unloader to transition to the Run state. ✓ Active unloader cleared. Inactive unloader empty. 4. Push and hold the blow-off air push button (S). The platen will begin to raise. • Pressing the pump ready button while the active unloader is in the Heat On state will cause the active unloader to transition to the Run state. S ✓ Inactive unloader cleared. Active unloader empty. • TI8142A 5. When platen is clear of the drum, increase the ram up pressure to 10-15 psi (69-103 kPa, 0.69-1.03 bar) to continue to raise the heated follower plate. ✓ Both unloaders cleared before pressing Pump Ready. • Pressing the pump ready button while the inactive unloader is in the Heat On state will cause the inactive unloader to transition to the Ready state. The Transition button must be pressed to transfer active unloader status to the Ready unloader. Pressing the Pump Ready button again while the now inactive loader is in the Heat On state, will cause the inactive unloader to transition to the ready state. • Pressing the Pump Ready button while the inactive unloader is in the Heat Off state and the active unloader is in the Heat On state will cause the active unloader to transition to the Run state. • This sequence is required to force the user to only engage one unloader at a time. This prevents accidental pumping of air into the system. 6. Once the ram is in the full up position place the drum cover in the brackets provided. Never reach under the heated platen after it leaves the drum. Serious burns could result from dripping material. 7. Follow the steps in Material Loading (page 30) and Prime Pump (page 32). 8. After drum change, press the Pump Ready Button to reverse the air motor control. 9. Prime the pump. 38 Pressing the pump ready button while the inactive unloader is in the Heat On state will cause the inactive unloader to transition to the Ready state. The active state can then be transitioned to the loaded unit. 311208A Operation System Shutdown 4. Lock the dispense valve trigger open by pulling and securing the trigger using the trigger retainer (Z). Follow the procedure below for normal system shut down, such as at the end of the work day. 1. Make sure the pump rod (Y) is parked in the down position. Z Y TI8051A CAUTION Many hot melt materials tend to expand when heating up and may cause a heated hose to burst. Avoid the potential of bursting a hose by opening the dispense valve during system heat up and lock the dispense valve trigger open every time you shut the system down. TI7937A 5. If the optional 7-day timer is not being used, set the main disconnect to OFF. 2. Close the system master air valve (bleed-type)(A). If 7-day timer is required, system need to be in the system on or heat off state. A POWER OFF TI8139A 3. If a 7-day timer is not being used, enable Pump Inactivity (see Table 7, page 29). 311208A 39 Dual Ram Cross-Over Installation Dual Ram Cross-Over Installation Typical Installation . Cross-Over cable is included with the Dual Ram part no 15H385 Cross-Over Cable TI7937A TI7937A EZKey Setup Drum Change Procedure See EasyKey Display Screens on page 24. See Drum Changing on page 37. 40 311208A Maintenance Maintenance Light Tower Kit (Optional) Ram Periodically (once a month), inspect the ram guide sleeves, rods and cylinders for wear or damage. See instruction manual 310523. The optional light tower kit Part #253547, has the following color and flashing lights to signal warnings and alarms. Ground Fault Interrupt Green denotes an active system where the pump will activate when material is needed. Periodically (once a month) test the ground fault interrupt switch by pushing the TEST button. Yellow denotes user attention is required. Power in a Tandem System In a Tandem System, the secondary unloader provides 24VDC power to the EasyKey display. This allows the primary unloader to be powered down for maintenance without interrupting production. All accessories (light tower, swirl, etc.) and the display board on the primary system will have power when the secondary unloader is powered on and the primary unloader is powered off. Flashing yellow denotes a drum is empty (when equipped with proximity sensors). Red denotes immediate user attention is required due to an alarm condition or interruption of material flow. The user should be aware that in the case of a motor error on a Single or Tandem system, or a Tandem system with both drums empty, heat may be applied to the platen and pump to allow for a drum change. Alarm Troubleshooting The Therm-O-Flow alarms alert you to a problem and help prevent system shut downs or application errors. If an alarm occurs, operation may stop and the following occurs. Resetting the Ground Fault Interrupt This electrical control panel is equipped with a ground fault interrupt (GFPE) circuit breaker. If the disconnect switch is ON, but all lights on the electrical control panel are off review troubleshooting procedures. • Light Tower Changes (if equipped) • Status bar on the EasyKey Display shows the description • Alarm out puts a signal sent to I/O To Clear the alarm and restart the TOF 200 press the Error Clear key on the easy key display. See Table 8 : Therm-O-Flow Alarms. Table 8: Therm-O-Flow Alarms Warnings Cause With optional light tower, the yellow light illuminates and green light remains on if in run mode. High Temperature - occurs when a zone temperature is above the setpoint plus warning deviation specified in the zone tab of the setup screen. 311208A 41 Alarm Troubleshooting Table 8: Therm-O-Flow Alarms Low temperature - occurs when a zone temperature is below the setpoint minus warning deviation specified in the zone tab of the setup screen, Drum Low - occurs when the drum low proximity sensor is activated die to the ram position. Alarms Cause With optional light tower, the red light illuminates. High Temperature - occurs when a zone temperature is above the setpoint plus alarm deviation specified in the zone tab of the setup screen, Low Temperature - occurs when the zone temperature is below the setpoint minus alarm deviation specified in the zone tab of the setup screen while the unloader is in the run state. Sensor Error - occurs in the following conditions when an enabled zone does not increase in temperature within two minutes while the system is in the Heat On state. This is the short circuit state o f an RTD sensor. Or when a zone temperature exceeds 500°F (260°C). This is the open circuit state of an RTD sensor Heat Control Error - occurs if the conductor relay on a temperature board is not closed when a zone of the temperature board is enabled and in a heat state for the active unloader, Communication Error - there are two possibilities: • Start up - Occurs if the easy Key display board cannot communicate with any board in the system. • Normal Operation - occurs if any board in the system, including tandem unloader, cannot communicate with the EasyKey Display board. Events Cause Drum Empty - occurs when the drum empty proximity sensor is activated for the ram position. With optional light tower the yellow light begins flashing and the green light turns off. Motor Shutdown - occurs when the pump exceeds the motor shutdown rate set in the advanced tab of the setup screen. With optional light tower the red light turns on and the green light turns off. Maintenance Call - occurs in advanced unit if user presses maintenance call button. With optional light tower the yellow light turns on. 42 311208A Ram Troubleshooting Ram Troubleshooting Problem Ram will not raise or lower. Cause Solution Closed main air valve or clogged air line, Open air valve; clear air line. Not enough ram air pressure. Increase ram air pressure. Worn or damaged ram piston. Replace piston. See instruction manual 310523. Platen not fully up to temperature. Wait for full temperature. Ram air pressure too high. Decrease ram air pressure. Dented drum has stopped platen. Fix or replace drum. Ram raises or lowers too fast. Ram “up / down” air pressure too high. Decrease ram air pressure. Air leaks around cylinder rod. Worn rod seal. Replace o-rings in guide sleeve. See instruction manual 310523. Fluid squeezes past platen wipers. Ram air pressure too high. Decrease ram air pressure. Worn or damaged wipers. Replace wipers. Directional valve not in the down position. Position handle in the down position. Closed main air valve or clogged air line. Open air valve; clear air line. Not enough air pressure. Increase air pressure. Worn or damaged ram piston. Replace piston. See instruction manual 310523. Ram directional valve closed or clogged. Open valve; clear valve or exhaust. Ram directional valve dirty, worn, or damaged. Clean; repair valve. Dented drum has stopped platen. Fix or replace drum. Closed main air valve or clogged air line. Open air valve; clear air line. Pump will not prime properly, or pumps air. Air pressure will not push platen out of drum. 311208A Not enough blow-off air pressure. Increase blow-off air pressure. Blow-off valve passage clogged. Clean valve passage. Dented drum has stopped platen. Fix or replace drum. Wipers bonded to drum or drum liner. Lubricate wipers with high temperature grease at every drum change. 43 Heated Pump Troubleshooting Heated Pump Troubleshooting For additional troubleshooting information about the pump, see the pump’s documentation. Problem Rapid downstroke or upstroke (pump cavitation). Cause Solution Material not heated to proper temperature. Check and adjust temperature to proper set point. Wait for pump/platen to heat up. Air is trapped in pump. Bleed air from pump. See Prime Pump, page 32. Downstroke: Dirty or worn pump intake valve. Clean or repair. See Pump Manual. Upstroke: Dirty or worn pump piston valve. Clean or repair. Material leaks around pump outlet. Loose outlet fitting. Tighten outlet fitting. Material leaks around bleed port. Loose bleed port fitting. Tighten bleed port fitting. Pump will not move up and down. Problem with air motor. See Air Motor Manual. Foreign object lodged in pump. Relieve pressure. See Pump Manual. Worn throat seals. Replace throat seals. See Servicing the Throat packings in manual 308570 or 311536. Leak around pump wet-cup. Air Motor Troubleshooting For additional air motor troubleshooting information, see the air motor manual supplied. Problem Cause Solution Air motor will not run. Air motor solenoid is off. Wait for heat zones in use to reach “window” around temperature set values. Air motor stalled. Damaged main air valve spool or poppets. Rebuild main air valve. See Air Motor Manual. Air continuously exhausting around air motor shaft. Damaged air motor shaft seal. Replace air motor shaft seal. See Air Motor Manual. Air continuously exhausting around air valve/slide valve. Air valve/slide valve gasket is damaged. Replace the valve gasket. See Air Motor Manual. Air continuously exhausting from muffler when motor is idle. Internal seal damage. Rebuild air motor. See Air Motor Manual. Icing on muffler. Air motor operating at high pressure or high cycle rate. Reduce pressure, cycle rate, or duty cycle of motor. 44 311208A Electrical Control Panel Troubleshooting Electrical Control Panel Troubleshooting Problem Disconnect is ON, but EasyKey not lit. Cause Solution The ground fault interrupt has been activated. Have a qualified electrician check wiring. One or more fuses or circuit breakers tripped. Have a qualified electrician check wiring. High temperature alarm. The temperature of a heated component has gone out of range. Supply unit automatically turns off power to supply unit components and air motor. Unit turns power back on when overheated components reach appropriate temperatures. Heat is turned off after a period of pump inactivity. Pump has not moved within the programmed time period and the inactivity timer has been triggered. See Table 7, page 29. Pump Ready button does not clear flashing pump ready icon. Unloader not in Heat On state and/or zones have not reached warning deviation level. Turn system to Heat On state and wait until all zones reach warning deviation level. 311208A 45 Service Service Ram Periodically (once a month), inspect the ram guide sleeves, rods and cylinders for wear or damage, replace all worn parts. See the Service section of Form 310523 for instructions on replacing worn parts. Pump See the material pump instructions for its inspection frequency. Ground Fault interrupt Periodically (at least once a month) test the ground fault interrupt switch by pushing the TEST button. Power in a Tandem System In a Tandem System, the secondary unloader provides 24VDC power to the EasyKey display. This allows the primary unloader to be powered down for maintenance without interrupting production. All accessories (light tower, swirl, etc.) and the display board on the primary system will have power when the secondary unloader is powered on and the primary unloader is powered off. Ram Service To relieve ram air pressure, follow the Ram Pressure Relief Procedure on page 36. For more information about servicing the ram, see instruction manual 310523. Ram Pressure relief Procedure To reduce the risk of serious injury whenever you service the ram, always follow the Ram Pressure Relief Procedure on page 36. 46 311208A Service Removing a Material Drum from the Supply Unit Servicing Wipers The material and equipment will be hot! The material and equipment will be hot! Before you perform the procedures in this section, remove the material drum from the supply unit. Only remove the drum from the supply unit while the supply unit is hot. Observe the cautions and warnings, then follow steps 1 through 7 of the Drum Changing procedure in Graco form 309180, Installation and Operation Guide. 1. To replace a worn or damaged wiper (V) raise the ram plate up out of the drum. Be sure to follow all the cautions and warnings. Perform steps 1 through 7 of the Drum Changing procedure on page 37. See Instruction manual 309196 for instructions about replacing tee wipers. See FIG. 23: Servicing the Ram Plate This section describes service you can perform without removing the ram plate from the supply unit: • servicing wipers • replacing heat sensors To remove the ram plate from the supply unit, see Separating the Air Motor from the Pump on page 49. For information about replacing wires that connect the ram plate to the pump, see Form 310530, or contact your Graco distributor. 311208A TI8143A V FIG. 23 Wipers 47 Service Replacing Heat Sensors 5. Remove the sensor from the ram plate. 6. Disconnect the two sensor wires from the J1 or J2 of PCB201. See Fig FIG. 24. The material and equipment will be hot! 1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, follow the procedure for Removing a Material Drum from the Supply Unit on page 47. 2. Make sure the ram plate is down and the ram hand valve is in the OFF position. See page 46. To reduce the risk of injury or damage to equipment, make sure the main disconnect is off before continuing with this procedure. 3. Turn OFF the main electrical disconnect switch. 4. Remove the front and right side pump cover. 48 PCB 246 PCB 201 PCB 226 J1 J2 J3 J4 J1 J2 J3 J4 FIG. 24 7. Attach the leads from the new sensor to the leads of the old sensor and pull the new sensor leads into the main control panel. 8. Install the new sensor into the follower/tire plate after coating with non-silicone hear sink compound. Tighten compression nut. 9. Connect the two wires from the new sensor to the J1 or J2 of PCB201. 10. Replace the pump covers. 311208A Pump Removal and Replacement Pump Removal and Replacement For information about servicing the Check-Mate™ 800 Displacement Pump, see Instruction Manual 308570. 9. Pump must be in the full down position (air motor shaft fully extended). 1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, perform steps 1 through 6 of the Drum Changing procedure on page 37. It is important that the pump rod is in the fully down (parked) position. Reverse the above procedure to reinstall a new or rebuilt pump. 2. Make sure the ram plate is down and the ram hand valve is in the neutral position. Separating the Air Motor from the Pump This procedure must be done with the unit still warm. The material and equipment will be hot! 1. If vent hood is installed, remove it. To reduce the risk of serious injury whenever you are instructed to relieve pressure, always follow the Pressure Relief Procedure on page 35. 3. Bleed off excess material and pressure in the system by opening the dispense gun and catching the material in a waste container. 4. On the electrical control panel, turn off the system heat (D). See FIG. 25. 5. Turn OFF the main electrical power supply to the unit. Follow all applicable safety procedures and lockout rules. 6. Turn OFF the main electrical disconnect (E) located on the left side of the Them-O-Flow 200. 2. Remove the air motor top cover. 3. Disconnect electrical cable from air motor. 4. Remove air line from air motor and air lines to the follower blow-off valve. 5. Tightly strap the air motor to the tie bar with a cable through the air motor lift ring and around the tie bar. 6. Loosen U-bolts from follower lift rods. 7. Remove nuts (F) from pump/air motor stand-off rods at the pump end. See FIG. 25. 8. Remove nuts and bolts holding cable tract to air motor support plate. 9. Slide end of cable track outboard of the mounting plate. 10. Remove nuts (2) from follower lift rods. To reduce the risk of injury or damage to equipment, make sure the main disconnect is off before continuing with this procedure. 7. Disconnect all material hoses. 8. Remove the pump sheet metal enclosure (A). See FIG. 25. 11. Fully loosen pump rod coupler to the air motor rod (G). 12. Slowly raise elevator to achieve enough separation of the pump (air motor) tie rods to remove the pump. 13. Remove the pump. 14. Reverse this procedure to reinstall the new or rebuilt air motor. a. Remove the cover screws (B). Removing the Follower Plate b. Disconnect the pump heater wires, the ground wire, and the sensor mounted to the pump. c. Remove the follower sensor (C). 311208A 1. Disconnect the follower power wires and the follower ground wire from within the main control panel and pull out of conduit. 49 Pump Removal and Replacement 2. Remove the follower plate assembly from the ram. 3. Reverse this procedure to reinstall the new or rebuilt follower plate assembly. E D G F C A B TI7832 FIG. 25 50 311208A Replacing Heater Bands and Sensors in Pump Module Replacing Heater Bands and Sensors in Pump Module Module heaters and sensor can be serviced without removing the pump module from the supply unit. Remove the front shrouds. When finished servicing the pump module re-attach shrouds. 3. Loosen the clamp holding sensor on pump (G). See FIG. 26. This procedure can be done when the Therm-O-Flow 200 is cool. Removing/Replacing Heater Band 3 1. Remove the screws that hold the front shroud in place and remove the front shroud. 2. Disconnect the electrical wires from heater band (3). See FIG. 26. G 3. Remove the screw that holds the heater band in place. 3 4. Remove the heater band from pump. 5. Coat the inside of the heater with non silicone heat sink compound before mounting. Maximum thickness is .005”. Coat only to within 3/4” of vertical ends. 6. Install a new heater band in the same location as the old heater band: TI8144A a. Locate heater terminals so they line up with back of pump. FIG. 26 b. Re-connect heater wires and re-attach ceramic caps that insulate terminal. 4. Tie the leads of the new sensor to the old sensor and remove the old sensor. The leads of the new sensor will be easily drawn through the conduit for reconnecting. Removing/Replacing Sensor 5. Replace the sensor (H) in clamp: Tighten the heater band. 1. Remove the screws that hold the front shroud in place and remove front shroud. a. Place sensor approximately 30° counter clock-wise from pump outlet. 2. If sensor wire is connected to electrical enclosure, disconnect it. b. Tighten clamp. 6. Re-connect sensor wire to electrical enclosure. 311208A 51 Replacing Heater Bands and Sensors in Pump Module Removing/Replacing RTD Sensor 1. Remove the screws that hold the front shroud in place and remove front shroud. c. Place RTD sensor approximately 30° counter clock-wise from pump outlet. d. Tighten clamp. 2. If RTD sensor wire is connected to electrical enclosure, disconnect it. 7. Re-connect sensor wire to electrical enclosure. 3. Loosen the clamp holding sensor on pump. Inspection/Maintenance Frequency 4. Tie the leads of the new RTD sensor to the old RTD sensor and remove the old sensor. The leads of the new sensor will be easily drawn through the conduit for reconnecting. The pump packings do not require any other service or maintenance, except as described in the Daily Maintenance Procedures. See 308570 for inspection frequency of the pump. 5. Remove RTD sensor. Throat Packings 6. Replace the sensor (H) in clamp: Refer to manual 308570 for a list of throat packing kits and replacement instructions. 52 311208A 311208A 53 Electrical Schematics Electrical Schematics 240 VAC Supply - Internal Control Box 8 '.$ '.$ 7 7 7 7 7 7 '.$ '.$ &5 8 8 &5 8 ",!#+ -47 490 ./ 42!.3&/2-%2 6 5.)4 8 8 8 8 42!.3&/2-%2 6 5.)4 8 6 7 8 6 6 7 7 4 7 7 7 6 2/54% 7)2%3 4/7!2$3 2%!2 /& %.#,/352% 8 8 &)'52% 54 311208A Electrical Schematics Electrical Control Schematic. TI8076 311208A 55 6 ! ! ,).% $# ).42& ,).% '5.!58 24$ :/.% '5.!58 24$ :/.% % % $( " $( " $' * * * $' $( ! $( ! $( " $' * * 6 * * * * * * * $( " $( ! $' % $( ! ",5% -47 490 $( " $' % $( " $( ! $( ! $' ",5% -47 490 !,, 6 0/7%2 7)2%$ !4 '2!#/ 24$ 3%.3/2 0,!4).5²# $# ).42& '5.!58 24$ :/.% '5.!58 24$ :/.% 4/ #/.. '5.!58 24$ :/.% (/3%!58 24$ :/.% 05-0 24$ :/.% &/,,/7%2 24$ :/.% 6 ",5% -47 4/ "% 7)2%$ !3 47)34%$ 0!)2 490 0,!#%3 0#" 4%-0%2!452% "/!2$ 0#" 4%-0%2!452% "/!2$ * * * * * 23 23 #/ * 332 332 332 332 332 332 332 332 '5.!58 :/.% (/3%!58 :/.% '5.!58 :/.% (/3%!58 :/.% ",5% -47 490 '5.!58 :/.% (/3%!58 :/.% 05-0 :/.% &/,,/7%2 :/.% !7' 47)34%$ 0!)2 342!.$%$ #/.$ 3()%,$%$ "%,$%. ",5% -47 490 !,, 332 #/), 7)2).' #/- #/- #/2$ '2)0 "5 7( "+ ". "5 7( "+ ". #/2$ '2)0 #/- * ", ", ", .# ", '2%%. -47 490 (!2.%33 &/2 &5452% 53% * !7' 490 %84%2.!, #/.42/, #/2$ '2)0 '.7( "5 * ". * * * * 23 "%,$%. #/2$ '2)0 "+ 2$ 7( '. "+ "+ #", * *- 6 ",5% -47 490 4/0 2%%$ %84%2.!, 4/ #/.42/, 0#" 5.,/!$%2 "/!2$ !.!,/' 3%.3/2 56 2%%$ 37)4#(%3 !)2 3/,%./)$ #", 02/8 3%.3/2 %-049 02/8 3%.3/2 ,/7 7)2%$ !4 '2!#/ Electrical Schematics Electrical Control Schematic TI8077 311208A 3#!,% ,)'(4 4/7%2 3#!,% Advanced Unit Shown ,/# !002/8 !3 3(/7. ' $)3#/..%#4 ,/# !002/8 !3 3(/7. -!).4%.!.#% #!,, 37)2, 37)2, !)2 -/4/2 3/,%./)$ (( #/..%#4)/. (( #/..%#4)/. (( #/..%#4)/. 02/8)-)49 %-049 02/8)-)49 ,/7 !)2 -/4/2 #!",% 0/7%2 #/.$5)4 &,/7 8 7)2% $5#4 332 &5 /////////////// 0#" &5 &5 &5 &5 //////// &5 //////// '&%0 0#" 8 7)2% $5#4 0#" 8 7)2% $5#4 /////////////// $# ).42& 8 7)2% $5#4 332 23 #2/33 /6%2 #/--5.)#!4)/. 332 $)')4!, )/ 332 %4(%2.%4 332 ,/# !002/8 !3 3(/7. 332 ./ 0!243 !)2&,/7 &!. 332 8 7)2% $5#4 //////// &5 $ & " % ! # " 4 " 4 " 4 332 '.$ '.$ '.$ &5 &5 #/. #/. //////// '.$ "53 $# ).42& &5 '.$ ,5' $)3# 7 7 7 7 7 7 '.$ '.$ 03 8 7)2% $5#4 8 7)2% $5#4 311208A ,& %84%2.!, 0/7%2 ). Electrical Schematics Electrical Control Schematic TI8079 57 8 7)2% $5#4 #2/33 /6%2 #/-- * & 0#" %4(%2.%4 #!2$ $)30,!9 -%-"2!.% 37)4#( (!2.%33 "%,$%. ,/#!, 23 "+ 2$ & & * * * * * * * * * * #/ 9%,,/7 "2/7. 2%$ /2!.'% 7()4%/2!.'% 7()4%9%,,/7 7()4%'2%%. 7()4%",5% ,4 ",5% -47 490 ,)'(4 4/7%2 #/- * 7()4%0520,% '2%%. ",5% 0520,% '2%9 7()4% 7()4%",!#+ 7()4%"2/7. 7()4%2%$ 7()4%'2%9 .# .# .# .# .# .# 6 * #/- !7' 490 * $' $' $( # $( # ",5% -47 490 $' # $ ! " $( # $' & 6 37)2, 3/,%./)$ %84%2.!, 4/ #/.42/, 37)2, 3/,%./)$ -!).4%.!.#% #!,, "544/. #/.4!#43 !2% ./ 0" $( # $' % $( # $' '5. 37)4#(%3 $( # !7' 490 * ,!-0 37)4#( #", * 37)4#( * * * 6 $)')4!, )/ ).4%2&!#% 58 Electrical Schematics Electrical Control Schematic TI8078 311208A 0#" %!39 +%9 "/!2$ 311208A 59 Electrical Connections Schematic Schematic continued on next page (page 61) 1 60 All wires to be run through conduit and into enclosure. Conduit to be run through cable track. 311208A Electrical Connections Schematic Schematic continued on previous page (page 59) 1 All wires to be run through conduit and into enclosure. Conduit to be run through cable track. 2 All hoses to be run through cable track. Through 2 x 3 slot in pedestal. And through 311208A 1.75 hole in pedestal. 61 Parts Parts All Models Supply Unit 11 10 4 5 13 15◆ 12 19◆ 8 16◆ 1 17◆ 6 18◆ 3 TI8145A 15◆ 2 14 TI7922A 62 311208A Parts Parts All Models Supply Unit Ref No. 1 2 3 Part No. Description Qty 253237 6” motor w/glass-filled tfe seals 1 and 50 psi relief valve, see manual 311238 253238 7.5” motor w/glass-filled tfe seals 1 and 85 psi relief valve, see manual 311239 253239 10.375” motor w/glass-filled tfe 1 seals and 100 psi relief valve, see manual 311162 253240 6” motor with cf/tfe grease pack 1 seals and 50 psi relief valve, see manual 311238 1 253241 7.5” motor with cf/tfe grease pack seals and 85 psi relief valve, see manual 311239 253242 10.375” motor with cf/tfe grease 1 pack seals and 100 psi relief valve, see manual 311162 Drum Platen, see Heated Platens 1 on page 72 1 Tire Plate Seals, see manual 309196 for a list of replacement parts 311208A Ref No. 4 5 6 7 8 10 11 12 13 14 15◆ 16◆ 17◆ 18◆ 19◆ ◆ Part No. Description 253247 RAM, see manual 310523 253248 RAM, see manual 310523 Electrical Enclosure CLAMPS, see parts starting on page 78 Vent Hood Kit, see page 81 253137 Pneumatic controls KIT, light tower 253288 CABLE, way KEY, easy KIT, proximity (included on Adv. and TS units) 297401 Stand Alone Pneumatic Controls, see manual 310523 C14043 LABEL, warning 15H668 LABEL, warning C14009 LABEL, warning 184090 LABEL, warning 196548 LABEL, warning Qty 1 1 1 1 1 1 1 1 1 4 2 2 2 1 Replacement Danger and Warning labels, tags, and cards are available at no cost. 63 Parts Therm-O-Flow Pump, Part No. 253575 11 17 22 4,10,14 6 11,13 18 20,21 9 3 TI8145A TI7934A 16,19 12,15 6 9 5 5 TI8146A 64 311208A Parts Therm-O-Flow Pump, Part No. 253575 Ref No. 3 4 5 6 9 10 11 12 13 Part No. 15H159 15H174 218093 253137 253229 100016 101864 107194 111303 311208A Description PEDESTAL, TOF 200 BRACKET, mounting enclosure HOSE, coupled CONTROL, air assembly HOSE coupled WASHER, lock SCREW, cap WASHER, plain NUT, hex Qty. 1 1 1 1 1 8 8 4 4 Ref No. 14 15 16 17 18 19 20 21 22 Part No. Description 112166 SCREW, cap sch 116940 SCREW, cap socket head, 5/16 18 100575 SCREW, cap hex head 253288 CABLE, track 15H543 BRACKET, mounting robotrack 101971 WASHER, thrust 100307 NUT, hex 120186 HOLT, mounting u-bolt 120187 SCREW, button head Qty. 8 4 4 1 1 4 4 2 2 65 Parts Therm-O-Flow Pump Module using NXT 3400 and NXT 6500 Models 1 34 26 26 14 23 29 30 24 31,32,33 25 2 7 8 9 17 7 16 TI8132A 66 311208A Parts Therm-O-Flow Pump Module using NXT 3400 and NXT 6500 Models Ref No. 1 2 7 8 9 14 16 17 Part No. See Table See Table 120271 120275 C31012 15H396 See Table C03507 Pump Assy No. Description MOTOR, Air Qty. 1 PUMP 1 HEATER SENSOR, RTD CLAMP ADAPTER, rod pump VALVE, safety 2 1 1 1 1 SUPPORT, sensor 1 Description Ratio 253238 NXT 3400 GF/TFE 36:1 253239 NXT 6500 GF/TFE 70:1 253241 NXT 3400 CF/TFE 36:1 253242 NXT 6500 CF/TFE 70:1 311208A Ref No. 23 24 25 26 29 30 31 32 33 34 Part No. 184129 120186 106166 15H542 15H395 C19837 15H297 C38162 C38163 120375 Description Qty. COLLAR, coupling 2 NUT, coupling 1 NUT, mach, hex 3 BRACKET, motor mount 2 ROD, tie 3 SCREW, cap, sch 4 CONDUCTOR, ground 1 SCREW, machine 1 WASHER, lock, ext tooth 1 ADAPTER, elbow, 3/4” NPTI x 1/2” 1 NPTE Max Air Pressure Max Fluid Pressure Ref No. 1 Qty. Ref No. Ref No. 2 Qty. 16 Qty. .57 MPA (5.7 Bar) 83 psi .29 MPA (2.9 Bar) 43 psi .57 MPA (5.7 Bar) 83 psi .29 MPA (2.9 Bar) 43 psi 20.7 MPa (207 Bar) 3000 psi 20.7 MPa (207 Bar) 3000 psi 20.7 MPa (207 Bar) 3000 psi 20.7 MPa (207 Bar) 3000 psi N32LH0 1 237795 1 120306 1 N65LH0 1 237795 1 120012 1 N34LH0 1 253141 1 120306 1 N65LH0 1 253141 1 120012 1 67 Parts Therm-O-Flow Pump Module using NXT 2200 Models 1 34 15 14 26 30 23 29 24 31,32,33 7 25 8 9 17 2 16 7 TI8147A 68 311208A Parts Therm-O-Flow Pump Module using NXT 2200 Models For NXT 2200 Models Ref No. 1 2 7 8 9 14 15 16 17 Part No. N22LH0 See Table 120271 120275 C31012 15H397 15H398 103347 C03507 Description NXT 2200 AIR MOTOR PUMP HEATER SENSOR, RTD CLAMP ADAPTER, rod pump ADAPTER, motor mount VALVE, safety SUPPORT, sensor Qty. 1 1 2 1 1 1 3 1 1 Ref No. 23 24 25 26 29 30 31 32 33 34 Part No. 184129 186925 106166 15H173 15H395 109211 15H297 C38162 C38163 120375 Description Qty. COLLAR, coupling 2 NUT, coupling 1 NUT, mach, hex 3 BRACKET, motor mount 1 ROD, tie 3 SCREW, cap, sch 3 CONDUCTOR, ground 1 SCREW, machine 1 WASHER, lock, ext tooth 1 ADAPTER, elbow, 3/4” NPTI x 1/2” 1 NPTE Pump Assy No. Description Ref No. 2 Max Air Pressure Max Fluid Pressure Qty. 253237 253240 NXT 2200 GF/TFE NXT 2200 CF/TFE 237795 237141 0.7 MPA (7 Bar) 100 psi 0.7 MPA (7 Bar) 100 psi 15.9 MPa (159 Bar) 2300 psi 15.9 MPa (159 Bar) 2300 psi 1 1 311208A 69 Parts Series A Heated Pump Pump Top Heater Pump Bottom Heater Platen Heater Platen RTD Pump RTD TI8148A 70 311208A Parts Electrical wiring shown below is located in the electrical enclosure. 380 and 480V Pump Heater B2 Jumper, Phoenix pn 3005947 B1 T2 T1 T3 4L2 B3 5L1 575V Pump Heater Jumper, Phoenix pn 3005947 5L1 B2 B1 T2 T1 T3 4L2 B3 380 and 480V Pump Heater B2 Jumper, Phoenix pn 3005947 B1 T2 5L1 4L2 T1 T3 B3 311208A 71 Parts Heated Platens Part No, 253218 Heated Drum Platen, Mega Flo (Code B - option A) Part No, 253219 Heated Drum Platen, Standard Grid (Code B - Option B) Part No. 253220 Drum Heated Platen, Smooth Bottom (no fin) (Code B - Option C) Standard Grid Plate Part No. 253219 Smooth Bottom No Grid Plate Part No. 253220 28 27 10 See detail C If one ring terminal see detail A. If two ring terminals see detail B 14,15 9 8 7 11 6 12,13 5 24 24 25 Mega-Flo Plate Part No. 253218 25 26 26 Detail C 72 Detail A Detail B 311208A Parts Part No, 253218 Heated Drum Platen, Mega Flo (Code B-A) Part No, 253219 Heated Drum Platen, Standard Grid (Code B-B) Part No. 253220 Drum Heated Platen, Smooth Bottom (no fin) (Code B-C) Ref No. 1 2 4 5 6 7 8 9 10 11 12 Part No. Description See Table 9 Drum Platen Chart Below C32204 PACKING, O-ring C19049 SCREW, mach, slotted, RND HD 15H298 SENSOR, temperature C32201 GASKET, follower 158491 FITTING, nipple 158581 COUPLING, hex 617227 HANDLE, follower, bleed 246501 VALVE, blow off 100361 PLUG, pipe 100133 Qty 1 1 1 1 1 1 1 1 1 4 6 Ref No. 13 14 15 18 19 20 21 23 24 25 26 Part No. Description C19846 SCREW, cap socket, HD 150707 PLATE, designation 100508 SCREW, drive See Table 9 Drum Platen Chart Below See Table 9 Drum Plated Chart Below 15H295 CONDUCTOR 15H296 CONDUCTOR 15H297 CONDUCTOR 065367 SLEEVE, fiberglass, hi-temp 112901 NUT, hex 111640 WASHER, lock, internal Qty 6 1 2 --2 4 1 3 12 12 Table 9 Drum Platen Chart Part No. Description Item 1 Qty Element Resistance Item 18 Qty Item 19 Qty 253218 Mega-Flo Plate 194254 1 16.5Ω +1 / -2 15H293 2 15H294 4 253219 Standard Grid Plate 617225 1 19.2Ω +2 / -3 15H293 4 15H294 2 253220 Smooth Plate C57358 1 19.2Ω +2 / -3 15H293 4 15H294 2 'ROUND SCREW A A A B B ,EFT B A B A A B B B ,EFT A B A A 2IGHT A B 2IGHT A B B B A 'ROUND SCREW /HMS ACROSS PAIRS 311208A /HMS ACROSS PAIRS 73 Parts Platen Coil Checking To check resistance across each coil to ensure that each is working properly place an ohm meter across the platen coils as shown in the Heater Terminal Pattern illustration, or place an ohm meter across the terminals in the Therm-O-Flow control box shown below. 8 7)2% $5#4 &5 &5 332 $ & " % ! # " 4 " 4 " 4 $# ).42& #/. Therm-O-Flow Control Box 6a 6b 21 19 20 19 6b F F 5b 6a F 20 18 F E 4a 5b E E 21 19 4b 20 21 C 18 21 A 1a Smooth and Standard Platen Wiring 74 2b 21 B B 1b 18 A C C 2a 2b 20 3b 19 B 3a 18 3a B 21 4a D D 3b 18 C 4b 19 D D 21 18 5a E 5a 2a 1a 19 A 21 A 1b MegaFlo Platen Wiring 311208A Parts EZ Key Assembly, Part No. 253147 5 2 3 4 1 TI7918A TI7919A Back of EZ Key Assembly Ref No. 1 2 3 4 5 Part No. 15F793 117769 249480 15G965 118431 311208A Description LABEL, operations DISPLAY, graphics BOARD, circuit assembly PLATE, blank SCREW, pan head cross 4-40 Qty 1 1 1 1 4 75 Parts Swirl Kit, Part No. 253263 6 11 8 7 5 1 4 2 TI7921A 3 Air In Ref. No. 1 2 3 4 5 6 76 Part No. Description Qty. .125 ID hose barb x 1/4 NPT Male 1 brass fitting Regulator 1 Gauge 1 1/4 to 1/8 Brass Hex Nipple 1 Solenoid Valve 120384 Cable 1 Ref. No. 7 8 9 10 11 Part No. Description Tube Fitting Nylon tube Socket head cap screw (not shown) Tube Clamp (not shown) Regulator mounting bracket Qty. 1 3 ft. 2 1 1 311208A Parts Drip Shield Mount Kit, Part No. 253479 Ref. No. 1 2 3 Part No. 15E028 15H609 100131 Description BRACKET, tray BOLT, U 7.5 LG x 6” pipe NUT, full hex Qty 2 2 4 Ref. No. 4 5 Part No. Description 100133 WASHER, lock 115694 TRAY, drip shield, hot melt Qty 4 2 5 1 3 4 2 3 4 TI8149A 311208A 77 Parts Drum Ram Post Saddle Clamp, Part No. C32463 Option Code J-3 Ref No. 1 2 3 4 Part No. C32424 160111 100103 100307 Description BOLT, U, 7” CLAMP, barrel PIN, cotter NUT, hex Ref No. 5 6 7 8 Qty 2 1 2 4 Part No. 100133 C38182 C32461 166265 Description WASHER, lock WASHER, plain CLAMP, saddle PIN, pivot Qty 4 2 2 1 3 8 6 5 7 4 2 1 5 5 4 4 6 5 4 7 TI8150A 3 78 311208A Parts Heavy Duty Drum Band Clamp, Part No. 918395 Option Code J-2 Ref No. 2 3 4 5 6 Part No. 100101 918421 918423 617395 100133 Description SCREW, cap, hex HD CLAMP, back half assembly KIT, repair PIN, quick release WASHER, lock 11 8,7,6,2 Ref No. 7 8 9 10 11 Qty 8 1 1 2 8 Part No. C19200 617433 617395 100131 C32424 Description WASHER, plain SPACER, drum clamp CLAMP, saddle NUT, full hex BOLT, U 7” 6,10 3 9 Qty 8 8 4 8 4 11 4 5 TI8151A 311208A 79 Parts Fiber Drum Reinforcement Clam Shell Clamp, Part No. 918397 Option Code J-1 Ref No. 1 2 3 Part No. C32271 C19126 100133 Description CLAMSHELL SCREW, cap hex HD WASHER, lock Ref No. 4 5 6 7 Qty 1 8 12 Part No. 100307 617340 C32424 617341 Description NUT, hex CLAMP, saddle BOLT, U, 7” MOUNT, clam shell Qty 8 4 4 2 1 3,4 5 6 2,3 7 TI8152A 80 311208A Parts Vent Hood Accessory Kit for 6-1/2 In. Ram, Part No. 233559 Ref No. 1 2 3 5◆ Part No. ◆ Replacement Danger and Warning labels, tags, and cards are available at no cost. Description VENT hood 112166 SCREW, cop sch 100016 WASHER, LOCK C14038 LABEL, warning 1 Qty 1 4 4 1 5 2 3 TI8153A 311208A 81 82 0#" 0#" 0#" 8 '.$ '.$ 8 '.$ "53 $ & " % ! # " 4 " 4 " 4 $# ).42& 332 ./ 0!243 !)2&,/7 8 7)2% $5#4 8 7)2% $5#4 03 8 8 8 7)2% $5#4 7 7 7 7 7 7 '.$ '.$ &5 &5 332 #/. &5 &5 &5 &5 &5 &5 &5 332 332 332 332 332 332 8 7)2% $5#4 ////// &5 #/. 8 7)2% $5#4 //////////////// $# ).42& //////////////// '&%0 '.$ '.$ '.$ 8 7)2% $5#4 Parts All Models Control Panel Component Layout 8 7)2% $5#4 '.$ ,5' &!. $)3# ////// 8 7)2% $5#4 TI8079A 311208A Parts Control Box Spare Parts List Check the control box number on your machine, then find that control box on the tables on this and the following pages. Refer to the illustration on page 86 for device numbers. Graco Part No. Description Qty. in Panel 249404 Unloader Board 1 249405 Temperature Board 1 253544 Ethernet Card 1 253147 Easy Key Display Kit 1 249480 Easy Kit Display Board 1 117769 LCD Graphic Display 1 120397 Proximity Sensors 1 253547 Light Tower Kit 1 120400 Discrete I/O Cable 1 15H386 Air Motor Sensor Cable 1 120436 Air Motor Solenoid Cable 1 15H385 Crossover Comm Cable 1 120384 Swirl Cable 1 15H298 Platen RTD Sensor 1 120275 Pump RTD Sensor 1 120271 Pump Heater 600W 1 120398 18 amp Watlow SSR 1 120399 65 amp Watlow SSR 1 120437 Disconnect 60A 1 120438 Disconnect 80A 1 120439 Door Operating Mech - Disconnect 1 120440 Shaft Disconnect 1 116214 15A Fuse 1 120426 7A Fuse 1 116208 6A Fuse 1 116209 2-1/4A Fuse 1 120427 DC Pwr Supply 24V 1 120428 GFPE 1 120430 5KVA Transformer 1 253548 Maintenance Call Button Kit 1 More Repair Parts for 4 Zone Accessory or Expansion 120443 Switch for 4 Zone Acc/Exp 1 311208A 83 Dimensions Dimensions Ram Mounting and Clearance Dimensions 61 in. (154.9 cm) 42 in. (106.7 cm) 25 in. (63.5 cm) 32.5 in. (82.6 cm) 21 in. (53.3 cm) TI7932A 60 in. (152.4 cm) Ram measures 110 in. (279.4 cm) high when fully raised. 89 in. (226.1 cm) 13 in. (33 cm) 84 48 in. (121.9 cm) TI7937A 311208A Technical Data Technical Data Displacement pump effective area . . . . . . . . . . . . . . . . . . 1.24 in.2 (8 cm2) Volume per cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.7 in.3 (192 cm3) Pump cycles per 1 gal. (3.8 liters) . . . . . . . . . . . . . . . . . . 21 Maximum fluid working pressure NXT 2200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2300 psi (15.9 MPa, 159 bar) NXT 3400. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3000 psi (20.7 MPa, 207 bar) NXT 6500. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3000 psi (20.7 MPa, 207 bar) Maximum air input pressure . . . . . . . . . . . . . . . . . . . . . . . NXT 2200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NXT 3400. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NXT 6500. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maximum pump operating temperature . . . . . . . . . . . . . . 100 psi (0.7 MPa, 7 bar) 82 psi (0.57 MPa, 5.7 bar) 43 psi (0.29 MPa, 2.9 bar) 400°F (204°C) Air motor piston effective area NXT 2200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28.3 in.2 (182 cm2) NXT 3400. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44.2 in.2 (285 cm2) NXT 6500. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84.5 in.2 (545 cm2) Air inlet size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/2 npsm(f) Pump fluid outlet size . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 in. npt(f) Wetted parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Carbon steel; brass; chrome, zinc, and nickel plating; 304, 316, 440, and 17-4 PH grades of stainless steel; alloy steel; ductile iron; PTFE Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 lb (545 kg) Displacement pump weight . . . . . . . . . . . . . . . . . . . . . . . 81 lb (37 kg) Instruction Manuals Heated Hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309160 Wiper Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309196 Bare Displacement Pump Lower . . . . . . . . . . . . . . . . 308570 6.5 in. (165 mm) Global Ram Module . . . . . . . . . . . . 310523 Power requirements Compressed air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-50 scfm (typical) Voltage (as selected) . . . . . . . . . . . . . . . . . . . . . . . . . 220/240 V, 3-phase, 50/60 Hz 380/400 V, 3-phase, 50/60 Hz 470/490 V, 3-phase, 50/60 Hz 575 V, 3-phase, 50/60 Hz Peak consumption* with standard melt grid. . . . . . . . . . . . . . . . . . . . . . . . 24.5 kVa with MegaFlo melt grid. . . . . . . . . . . . . . . . . . . . . . . . 27.5 kVa with smooth melt grid . . . . . . . . . . . . . . . . . . . . . . . . . 24.5 kVa * Includes drum melt grid, pump, and a 5 kVa transformer for the 230 V hoses and accessories. 311208A 85 Graco Standard Warranty Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco's written recommendations. This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco. This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation. THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. Graco's sole obligation and buyer's sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale. GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties. In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise. FOR GRACO CANADA CUSTOMERS The parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés à la suite de ou en rapport, directement ou indirectement, avec les procedures concernées. Graco Information TO PLACE AN ORDER, contact your Graco distributor, or call this number to identify the distributor closest to you: 1-800-328-0211 Toll Free 612-623-6921 612-378-3505 Fax All written and visual data contained in this document reflects the latest product information available at the time of publication. Graco reserves the right to make changes at any time without notice. MM 311208 Graco Headquarters: Minneapolis International Offices: Belgium, China, Japan, Korea GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440-1441 www.graco.com 311208A 5/2006
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
Download PDF
advertisement