FLM BK PB M12 DI 8 M12
Fieldline Modular Bus Coupler for PROFIBUS
With 8 Digital Inputs
AUTOMATIONWORX
© PHOENIX CONTACT - 05/2005
Data Sheet
Description
The device connects a Fieldline modular station to
PROFIBUS-DP and is also used to acquire digital signals.
– Channel-specific diagnostics for different I/O devices
– Dynamic configuration and empty spaces
Features
– Connection to PROFIBUS-DP using M12 connectors
(B-encoded)
– Opens the Fieldline modular local bus using M12 connectors (B-encoded)
– Connection of digital sensors using M12 connectors
– Flexible voltage supply concept
– LED diagnostic and status indicators for bus operation and voltage supply
– Short-circuit and overload protection of the sensor supply
7 0 0 8 A 0 0 1
– IP65/IP67 protection
Figure 1 FLM BK PB M12 DI 8 M12
onlinecomponents.com
This data sheet is only valid in association with the FLS FLM SYS INST UM E (Order No. 26 98 97 3) and
FLS FLM PB SYS PRO UM E (Order No. 26 99 07 9) user manuals.
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com
.
A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf
.
7008_en_01
PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 • www.phoenixcontact.com
www.phoenixcontact.com/salesnetwork
1
FLM BK PB M12 DI 8 M12
Pin Assignment
F E
B U S
B U S I N
I N
B U S O U T
O U T
U L M D
B F
1 0
1 2
1 0
R U N
2 M B D
L S
L B
O U T
L B O U T
I 1 I 2
I 3 I 4
I 5 I 6
I 7 I 8
L S
I N
I N
L S
B K P B
U S
Figure 2 Connections of the
FLM BK PB M12 DI 8 M12
I N 1 / I N 2
I N 3 / I N 4
I N 5 / I N 6
I N 7 / I N 8
7 0 0 8 A 0 0 2
Des.
FE
BUS IN
BUS OUT
LB OUT
U
LS
IN
U
LS
OUT
IN1 to IN8
Meaning
Functional earth ground
PROFIBUS IN
PROFIBUS OUT
Local bus OUT (FLM local bus)
Power supply IN
(logic and sensor supply)
Voltage supply OUT (logic and sensor supply) for additional devices
Inputs 1 to 8
In general, the maximum current load of 4 A per contact must not be exceeded.
onlinecomponents.com
PHOENIX CONTACT
2
7008_en_01
Pin Assignment PROFIBUS
B U S I N B U S O U T
L B O U T
FLM BK PB M12 DI 8 M12
Local Bus Pin Assignment (LB OUT)
L B O U T
6 6 2 5 B 0 0 4
Figure 3 PROFIBUS pin assignment
(M12 B-encoded)
Pin
1
2
3
4
5
BUS IN
VP
RxD/TxD-N (A)
DGND
RxD/TxD-P (B)
Shield
BUS OUT
VP
RxD/TxD-N (A)
DGND
RxD/TxD-P (B)
Shield
The shield is connected to FE in the device.
Figure 4
7 0 0 8 A 0 0 5
Local bus pin assignment (LB OUT)
Pin
1
2
3
4
5
LB OUT
DO
DO
DI
DI
GND
The thread is used for shielding.
7008_en_01 onlinecomponents.com
PHOENIX CONTACT
3
Pin Assignment of the Voltage Supply U
LS
I N O U T
Pin Assignment of the Inputs
FLM BK PB M12 DI 8 M12
6 9 5 4 A 0 0 3
Figure 5 Pin assignment of the voltage supply U
LS
6 6 2 5 A 0 0 6
Figure 6 Pin assignment of the inputs
3
4
5
Pin
1
2
IN
U
L
+24 V
U
S
GND
U
L
GND
U
S
+24 V
U
U
U
U
L
OUT
S
L
S
+24 V
GND
GND
+24 V
500 kbaud / 2 Mbaud 500 kbaud / 2 Mbaud
You can change the transmission speed on the local bus from 500 kBaud to 2 MBaud. The transmission speed is switched to 2 Mbaud by jumpering +24 V (U
L
, Pin 1) to Pin 5.
3
4
5
Pin
1
2
Input Socket (INx/INx+1)
U
S
+24 V
Input x+1
GND
Input x
FE
Assignment of the Input Sockets
Voltages U
L
and U
S
at female connector U
LS
OUT can each only carry a maximum current of
2 A.
6 9 5 4 B 0 0 5
Assignment of the input sockets Figure 7
onlinecomponents.com
Two input signals can be connected to each input socket.
PHOENIX CONTACT
4
7008_en_01
FLM BK PB M12 DI 8 M12
Local Diagnostic and Status Indicators
U L
B F
M D
R U N
2 M B D
Rotary Encoding Switches
Set the station address using both rotary encoding switches
X10 (for the first digit of a two-digit number) and X1 (for the second digit of a two-digit number). The PROFIBUS master addresses the device by means of this station address.
I N
B U S
U L M D
B F
1 0
1 2
1 0
R U N
O U T
L B
O U T
2 M B D
L S
The valid value range is between 1 and 126.
A new address value is only accepted upon device power up.
I 1 I 2
I 3 I 4
I 5 I 6
X X
X X
X X
X X
I 7 I 8
U S
I N
L S
B K P B
U S
7 0 0 8 A 0 0 3
Figure 8 Diagnostic and status indicators of the
FLM BK PB M12 DI 8 M12
onlinecomponents.com
PHOENIX CONTACT
5
7008_en_01
FLM BK PB M12 DI 8 M12
BF
MD
US
Des.
UL
RUN
Color
Green LED
ON:
OFF:
Red LED
Meaning
Communications power
Communications power present.
Communications power too low.
No cyclic data transmission:
– PROFIBUS not connected, master not active
– Incorrect settings (configuration via master, station address)
Timeout expired
Device addressed by PROFIBUS;a parameterization was received LED OFF:
No power supply for the device
(In this state the "UL" LED also is off because of the missing 24 V communications power.)
Device status LED green/red/ yellow
Green ON:
Green, flashing:
1 Hz
Device ready to operate
A recoverable error is present (local bus not complete).
Green/red
Flashing
(flicker)
Red ON
Red flashing:
1 Hz
Yellow flashing:
1 Hz
OFF:
LED green/red/ yellow
Green ON
Green, flashing:
1 Hz
Station in process data mode.
Device in selftest state.
An irrecoverable error is present.
Local bus is read, no process data transmission on local bus.
More than 64 devices configured or system restriction of 244 bytes of process data/configuration data exceeded.
Voltage not present.
Status of local bus communication
Local bus is running data cycles.
I/O error present.
Red ON
Red/yellow
Local bus stopped.
onlinecomponents.com
Flashing: 1 Hz
Green/yellow
There are differences between specified and current configuration.
Preprogrammed error values are written to the outputs.
Flashing: 1 Hz PLC stopped or PROFIBUS connection interrupted (cable, connector).
PCP error on a local bus device Yellow flashing:
1 Hz
OFF: Voltage not present.
Green/red LED Voltage supply for inputs IN1 to IN8
Green ON: Voltage supply present.
Red ON:
OFF:
Overload or voltage supply too low.
Voltage supply not present.
PHOENIX CONTACT
6
7008_en_01
FLM BK PB M12 DI 8 M12
Internal Circuit Diagram
I N
B U S
B U S
O U T
5 V
2 4 V
5 V
2 4 V
P B
µ C
L B
L B O U T
L S
O U T
L S
I N
Figure 9
7 0 0 8 A 0 1 0
Internal wiring of the connection points
Key:
P B
L B
Functional earth ground
Optocoupler
Protocol chip
Local bus/protocol unit
Power supply unit with electrical isolation
Input
LED
Electrically isolated area
For information on electrically isolated areas, please refer to page 12.
onlinecomponents.com
PHOENIX CONTACT
7
7008_en_01
FLM BK PB M12 DI 8 M12
Connection Example
I 1 I 2
I 3 I 4
6 9 5 4 A 0 0 8
Figure 10 Typical sensor connections
Connection Notes
Meet noise immunity requirements
Connect FE using a mounting screw or a cable connection to the FE connection latch (when mounting on a non-conductive surface).
Ensure degree of protection
To ensure IP65/IP67 protection, cover unused sockets with protective caps.
Avoid damage to the electronics
Make sure you only supply the sensors with the voltage U
S
provided at the connection points.
Avoid polarity reversal
Avoid polarity reversal of the supply voltages
U
L
and U
S device.
in order to prevent damage to the
onlinecomponents.com
Observe connection point assignment
When connecting the sensors, observe the assignment of the connection points to the
PROFIBUS IN process data (see "Process
Data" on page 9).
PHOENIX CONTACT
8
7008_en_01
FLM BK PB M12 DI 8 M12
Configuration Data
ID number
Input address area
07E9
8 bits
Process Data
Assignment of the Connection Points to the IN Process Data
(Byte.bit) view Byte
Bit
Device Input
7
8
6
7
5
6
4
5
Byte 0
3
4
2
3
1
2
0
1
Diagnostic Data
Mapping of the Diagnostic Data in PROFIBUS
Diagnostic
Data
Byte 0
Byte 1
Byte 2
Byte 3
Bit 7
X
X
X
X
Bit 6
X
X
X
X
Bit 5
X
X
X
X
Bit 4
X
X
X
X
Byte 4
Byte 5
0
1
0
1
0
1
0
0
Bit 3
X
X
X
X
0
1
Bit 2
X
X
X
X
1
0
Bit 1
X
X
X
X
1
0
Bit 0
Remark
1
1
X
X
X
X
Station status 1
Station status 2
Station status 3
Master address diagnostics
High ID number
Low ID number
Bytes 0 to 5 are PROFIBUS standard. Bytes 6 to 78 are device-specific. For information on device-specific bytes, please refer to the FLS FLM PB SYS PRO UM E user manual, Order No. 26 99 07 9.
If a diagnostic event occurs the diagnostic data is always sent to the master by means of a diagnostic telegram generated once by the device. The current status of the diagnostic data can be read by the device at any time.
For further information on the diagnostic data please refer to the FLS FLM PB SYS PRO UM E user manual,
onlinecomponents.com
PHOENIX CONTACT
9
7008_en_01
FLM BK PB M12 DI 8 M12
Technical Data
Device Dimensions
1 6 8 m m
( 6 . 6 1 4 ' ' )
1 7 8 m m
( 7 . 0 0 8 ' ' )
General Data
Order Designation
Order No.
Housing dimensions (width x height x depth)
Weight
Type of sensor connection
Permissible temperature (operation)
Permissible temperature (storage/transport)
Permissible humidity (storage/transport)
FLM BK PB M12 DI 8 M12
27 36 33 0
70 mm x 178 mm x 49.3 mm
285 g, approximately
2, 3 or 4-wire technology
-25°C to +60°C
-25°C to +85°C
95%
For a short period, slight condensation may appear on the housing.
7 0 0 8 A 0 0 6
Permissible air pressure (operation)
Permissible air pressure (storage/transport)
Degree of protection
Class of protection
80 kPa to 106 kPa (up to 2,000 m above sea level)
70 kPa to 106 kPa (up to 3,000 m above sea level)
IP65/IP67 according to IEC 60529
Class 3 according to VDE 0106, IEC 60536
Mechanical Requirements
Vibration test
Sinusoidal vibrations according to EN 60068-2-6
5g load in each space direction
Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and negative in each space direction
onlinecomponents.com
Phoenix Contact.
PHOENIX CONTACT
10
7008_en_01
FLM BK PB M12 DI 8 M12
Voltage Supply
Nominal value
Range
Current consumption at U
L
at 24 V DC
At 500 kbaud
At 2 Mbaud
Current consumption at U
S
at 24 V DC
24 V DC
18 V DC to 30 V DC, ripple included
75 mA, typical (100 mA, maximum)
75 mA, typical (100 mA, maximum)
15 mA + sensor current, typical (600 mA, maximum)
Voltages U
L
and U
S
at female connector U
LS
OUT can each only carry a maximum current of 2 A.
Digital Inputs
Number
Nominal input voltage
Range
Nominal input current
Current flow
Delay time
Permissible cable length to the sensor
8
24 V DC
-30 V DC < U
IN
< + 30 V DC
5 mA
Linear in the range 1 V < U
IN
< 30 V t
ON
= 2.9 ms, typical t
OFF
= 2.6 ms, typical
<
30 m
Input Characteristic Curve
Input Voltage (V)
-30 < U
IN
< 0.7
3
6
9
12
15
18
21
Typical Input Current (mA)
0
0.5
1.0
1.5
2.2
3.0
3.6
4.4
24 5.1
27 5.8
Sensor Supply
U
S
6.6
30
onlinecomponents.com
Minimum sensor voltage -1 V
Nominal current per channel 600 mA
Nominal current per device 600 mA
Overload protection
Short-circuit protection
Electronic per device
Electronic per device
PHOENIX CONTACT
11
7008_en_01
FLM BK PB M12 DI 8 M12
Error Messages to the Higher-Level Control or Computer System
Sensor supply short-circuit Yes
Sensor supply overload Yes
If an error is triggered by an overload or short circuit of the sensor supply, the device switches off the sensor supply of the channels and updates the diagnostics. The corresponding error message can then be read out by the master. If the sensor supply U
S
is not sufficiently high, the master can read out an appropriate error message also.
Interface
Bus system
Incoming Bus
Coupling of shield connection
Transmission Speed
Outgoing Bus
Coupling of shield connection
Transmission Speed
PROFIBUS DP
Directly to FE
12 Mbaud, maximum
Directly to FE
12 Mbaud, maximum
For transmission rates of more than 3 MBaud in PROFIBUS, series inductance is available in the device.
Please observe the installation instructions of the PROFIBUS User Organization.
Electrical Isolation/Isolation of the Voltage Areas
For device connection, please note the instructions and regulations in the "Installing the Fieldline Product
Range" user manual FLS FLM SYS INST UM E (Order No. 26 98 97 3).
Separate Potentials in the FLM BK PB M12 DI 8 M12
- Test Distance
24 V supply (bus logic) / FE
24 V supply (bus logic) / digital inputs
(sensor supply/I/O)
24 V supply (bus logic)/incoming remote bus
Digital inputs (sensor supply/I/O) / FE
- Test Voltage
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
500 V AC, 50 Hz, 1 min
Digital inputs (sensor supply / I/O)/ incoming remote bus
Incoming remote bus / FE
500 V AC, 50 Hz, 1 min
onlinecomponents.com
PHOENIX CONTACT
12
7008_en_01
FLM BK PB M12 DI 8 M12
Ordering Data
Ordering Data Device and Accessories
Description
Fieldline Modular Bus Coupler for PROFIBUS
With 8 Digital Inputs
Protective caps (for unused sockets)
Protective caps (for unused male connectors)
5-pos. shielded metal socket, B-encoded, for the incoming local bus
Shielded metal connector, 5-pos., B-encoded, for the outgoing remote bus and local bus
Markers
Bridging cable for power supply,
A-encoded, 5-pos., unshielded
Bridging cable for the local bus,
B-encoded, 5-pos., shielded
Assembly system for 5 devices
Assembly system for 7 devices
Order Designation
FLM BK PB M12 DI 8 M12
IBS IP PROT-IO
PROT-M12-M
SACC-M12FSB-5SC SH
SACC-M12MSB-5SC SH
Order No.
Pcs./Pkt.
27 36 33 0 1
27 59 91 9 5
27 36 19 4 5
15 13 59 6 1
15 13 57 0 1
ZBF 12:UNBEDRUCKT
SAC-5P-MS/ 0,13-186/FS
SCO
SAC-5P-MSB/0,13-PUR/FSB
SCO SH
FLM MP 5
FLM MP 7
08 09 73 5 10
15 18 48 1 1
15 18 47 8 1
27 36 66 0 1
27 36 67 3 1
Additional accessories for connecting the sensors and actuators can be found in the Phoenix Contact
PLUSCON catalog.
Ordering Data for Documentation
Description
"Installing the Fieldline Product Range" user manual
"Configuring a PROFIBUS DP System Using Devices in the Fieldline Product Range" user manual
Order Designation
FLS FLM SYS INST UM E
Order No.
26 98 97 3
Pcs./Pkt.
1
FLS FLM PB SYS PRO UM E 26 99 07 9 1
onlinecomponents.com
PHOENIX CONTACT
13
7008_en_01