FLM BK PB M12 DI 8 M12

Fieldline Modular Bus Coupler for PROFIBUS

With 8 Digital Inputs

AUTOMATIONWORX

© PHOENIX CONTACT - 05/2005

Data Sheet

Description

The device connects a Fieldline modular station to

PROFIBUS-DP and is also used to acquire digital signals.

– Channel-specific diagnostics for different I/O devices

– Dynamic configuration and empty spaces

Features

– Connection to PROFIBUS-DP using M12 connectors

(B-encoded)

– Opens the Fieldline modular local bus using M12 connectors (B-encoded)

– Connection of digital sensors using M12 connectors

– Flexible voltage supply concept

– LED diagnostic and status indicators for bus operation and voltage supply

– Short-circuit and overload protection of the sensor supply

7 0 0 8 A 0 0 1

– IP65/IP67 protection

Figure 1 FLM BK PB M12 DI 8 M12

onlinecomponents.com

This data sheet is only valid in association with the FLS FLM SYS INST UM E (Order No. 26 98 97 3) and

FLS FLM PB SYS PRO UM E (Order No. 26 99 07 9) user manuals.

Make sure you always use the latest documentation.

It can be downloaded at www.download.phoenixcontact.com

.

A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf

.

7008_en_01

PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany

Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 • www.phoenixcontact.com

www.phoenixcontact.com/salesnetwork

1

FLM BK PB M12 DI 8 M12

Pin Assignment

F E

B U S

B U S I N

I N

B U S O U T

O U T

U L M D

B F

1 0

1 2

1 0

R U N

2 M B D

L S

L B

O U T

L B O U T

I 1 I 2

I 3 I 4

I 5 I 6

I 7 I 8

L S

I N

I N

L S

B K P B

U S

Figure 2 Connections of the

FLM BK PB M12 DI 8 M12

I N 1 / I N 2

I N 3 / I N 4

I N 5 / I N 6

I N 7 / I N 8

7 0 0 8 A 0 0 2

Des.

FE

BUS IN

BUS OUT

LB OUT

U

LS

IN

U

LS

OUT

IN1 to IN8

Meaning

Functional earth ground

PROFIBUS IN

PROFIBUS OUT

Local bus OUT (FLM local bus)

Power supply IN

(logic and sensor supply)

Voltage supply OUT (logic and sensor supply) for additional devices

Inputs 1 to 8

In general, the maximum current load of 4 A per contact must not be exceeded.

onlinecomponents.com

PHOENIX CONTACT

2

7008_en_01

Pin Assignment PROFIBUS

B U S I N B U S O U T

L B O U T

FLM BK PB M12 DI 8 M12

Local Bus Pin Assignment (LB OUT)

L B O U T

6 6 2 5 B 0 0 4

Figure 3 PROFIBUS pin assignment

(M12 B-encoded)

Pin

1

2

3

4

5

BUS IN

VP

RxD/TxD-N (A)

DGND

RxD/TxD-P (B)

Shield

BUS OUT

VP

RxD/TxD-N (A)

DGND

RxD/TxD-P (B)

Shield

The shield is connected to FE in the device.

Figure 4

7 0 0 8 A 0 0 5

Local bus pin assignment (LB OUT)

Pin

1

2

3

4

5

LB OUT

DO

DO

DI

DI

GND

The thread is used for shielding.

7008_en_01 onlinecomponents.com

PHOENIX CONTACT

3

Pin Assignment of the Voltage Supply U

LS

I N O U T

Pin Assignment of the Inputs

FLM BK PB M12 DI 8 M12

6 9 5 4 A 0 0 3

Figure 5 Pin assignment of the voltage supply U

LS

6 6 2 5 A 0 0 6

Figure 6 Pin assignment of the inputs

3

4

5

Pin

1

2

IN

U

L

+24 V

U

S

GND

U

L

GND

U

S

+24 V

U

U

U

U

L

OUT

S

L

S

+24 V

GND

GND

+24 V

500 kbaud / 2 Mbaud 500 kbaud / 2 Mbaud

You can change the transmission speed on the local bus from 500 kBaud to 2 MBaud. The transmission speed is switched to 2 Mbaud by jumpering +24 V (U

L

, Pin 1) to Pin 5.

3

4

5

Pin

1

2

Input Socket (INx/INx+1)

U

S

+24 V

Input x+1

GND

Input x

FE

Assignment of the Input Sockets

Voltages U

L

and U

S

at female connector U

LS

OUT can each only carry a maximum current of

2 A.

6 9 5 4 B 0 0 5

Assignment of the input sockets Figure 7

onlinecomponents.com

Two input signals can be connected to each input socket.

PHOENIX CONTACT

4

7008_en_01

FLM BK PB M12 DI 8 M12

Local Diagnostic and Status Indicators

U L

B F

M D

R U N

2 M B D

Rotary Encoding Switches

Set the station address using both rotary encoding switches

X10 (for the first digit of a two-digit number) and X1 (for the second digit of a two-digit number). The PROFIBUS master addresses the device by means of this station address.

I N

B U S

U L M D

B F

1 0

1 2

1 0

R U N

O U T

L B

O U T

2 M B D

L S

The valid value range is between 1 and 126.

A new address value is only accepted upon device power up.

I 1 I 2

I 3 I 4

I 5 I 6

X X

X X

X X

X X

I 7 I 8

U S

I N

L S

B K P B

U S

7 0 0 8 A 0 0 3

Figure 8 Diagnostic and status indicators of the

FLM BK PB M12 DI 8 M12

onlinecomponents.com

PHOENIX CONTACT

5

7008_en_01

FLM BK PB M12 DI 8 M12

BF

MD

US

Des.

UL

RUN

Color

Green LED

ON:

OFF:

Red LED

Meaning

Communications power

Communications power present.

Communications power too low.

No cyclic data transmission:

– PROFIBUS not connected, master not active

– Incorrect settings (configuration via master, station address)

Timeout expired

Device addressed by PROFIBUS;a parameterization was received LED OFF:

No power supply for the device

(In this state the "UL" LED also is off because of the missing 24 V communications power.)

Device status LED green/red/ yellow

Green ON:

Green, flashing:

1 Hz

Device ready to operate

A recoverable error is present (local bus not complete).

Green/red

Flashing

(flicker)

Red ON

Red flashing:

1 Hz

Yellow flashing:

1 Hz

OFF:

LED green/red/ yellow

Green ON

Green, flashing:

1 Hz

Station in process data mode.

Device in selftest state.

An irrecoverable error is present.

Local bus is read, no process data transmission on local bus.

More than 64 devices configured or system restriction of 244 bytes of process data/configuration data exceeded.

Voltage not present.

Status of local bus communication

Local bus is running data cycles.

I/O error present.

Red ON

Red/yellow

Local bus stopped.

onlinecomponents.com

Flashing: 1 Hz

Green/yellow

There are differences between specified and current configuration.

Preprogrammed error values are written to the outputs.

Flashing: 1 Hz PLC stopped or PROFIBUS connection interrupted (cable, connector).

PCP error on a local bus device Yellow flashing:

1 Hz

OFF: Voltage not present.

Green/red LED Voltage supply for inputs IN1 to IN8

Green ON: Voltage supply present.

Red ON:

OFF:

Overload or voltage supply too low.

Voltage supply not present.

PHOENIX CONTACT

6

7008_en_01

FLM BK PB M12 DI 8 M12

Internal Circuit Diagram

I N

B U S

B U S

O U T

5 V

2 4 V

5 V

2 4 V

P B

µ C

L B

L B O U T

L S

O U T

L S

I N

Figure 9

7 0 0 8 A 0 1 0

Internal wiring of the connection points

Key:

P B

L B

Functional earth ground

Optocoupler

Protocol chip

Local bus/protocol unit

Power supply unit with electrical isolation

Input

LED

Electrically isolated area

For information on electrically isolated areas, please refer to page 12.

onlinecomponents.com

PHOENIX CONTACT

7

7008_en_01

FLM BK PB M12 DI 8 M12

Connection Example

I 1 I 2

I 3 I 4

6 9 5 4 A 0 0 8

Figure 10 Typical sensor connections

Connection Notes

Meet noise immunity requirements

Connect FE using a mounting screw or a cable connection to the FE connection latch (when mounting on a non-conductive surface).

Ensure degree of protection

To ensure IP65/IP67 protection, cover unused sockets with protective caps.

Avoid damage to the electronics

Make sure you only supply the sensors with the voltage U

S

provided at the connection points.

Avoid polarity reversal

Avoid polarity reversal of the supply voltages

U

L

and U

S device.

in order to prevent damage to the

onlinecomponents.com

Observe connection point assignment

When connecting the sensors, observe the assignment of the connection points to the

PROFIBUS IN process data (see "Process

Data" on page 9).

PHOENIX CONTACT

8

7008_en_01

FLM BK PB M12 DI 8 M12

Configuration Data

ID number

Input address area

07E9

8 bits

Process Data

Assignment of the Connection Points to the IN Process Data

(Byte.bit) view Byte

Bit

Device Input

7

8

6

7

5

6

4

5

Byte 0

3

4

2

3

1

2

0

1

Diagnostic Data

Mapping of the Diagnostic Data in PROFIBUS

Diagnostic

Data

Byte 0

Byte 1

Byte 2

Byte 3

Bit 7

X

X

X

X

Bit 6

X

X

X

X

Bit 5

X

X

X

X

Bit 4

X

X

X

X

Byte 4

Byte 5

0

1

0

1

0

1

0

0

Bit 3

X

X

X

X

0

1

Bit 2

X

X

X

X

1

0

Bit 1

X

X

X

X

1

0

Bit 0

Remark

1

1

X

X

X

X

Station status 1

Station status 2

Station status 3

Master address diagnostics

High ID number

Low ID number

Bytes 0 to 5 are PROFIBUS standard. Bytes 6 to 78 are device-specific. For information on device-specific bytes, please refer to the FLS FLM PB SYS PRO UM E user manual, Order No. 26 99 07 9.

If a diagnostic event occurs the diagnostic data is always sent to the master by means of a diagnostic telegram generated once by the device. The current status of the diagnostic data can be read by the device at any time.

For further information on the diagnostic data please refer to the FLS FLM PB SYS PRO UM E user manual,

onlinecomponents.com

PHOENIX CONTACT

9

7008_en_01

FLM BK PB M12 DI 8 M12

Technical Data

Device Dimensions

1 6 8 m m

( 6 . 6 1 4 ' ' )

1 7 8 m m

( 7 . 0 0 8 ' ' )

General Data

Order Designation

Order No.

Housing dimensions (width x height x depth)

Weight

Type of sensor connection

Permissible temperature (operation)

Permissible temperature (storage/transport)

Permissible humidity (storage/transport)

FLM BK PB M12 DI 8 M12

27 36 33 0

70 mm x 178 mm x 49.3 mm

285 g, approximately

2, 3 or 4-wire technology

-25°C to +60°C

-25°C to +85°C

95%

For a short period, slight condensation may appear on the housing.

7 0 0 8 A 0 0 6

Permissible air pressure (operation)

Permissible air pressure (storage/transport)

Degree of protection

Class of protection

80 kPa to 106 kPa (up to 2,000 m above sea level)

70 kPa to 106 kPa (up to 3,000 m above sea level)

IP65/IP67 according to IEC 60529

Class 3 according to VDE 0106, IEC 60536

Mechanical Requirements

Vibration test

Sinusoidal vibrations according to EN 60068-2-6

5g load in each space direction

Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and negative in each space direction

onlinecomponents.com

Phoenix Contact.

PHOENIX CONTACT

10

7008_en_01

FLM BK PB M12 DI 8 M12

Voltage Supply

Nominal value

Range

Current consumption at U

L

at 24 V DC

At 500 kbaud

At 2 Mbaud

Current consumption at U

S

at 24 V DC

24 V DC

18 V DC to 30 V DC, ripple included

75 mA, typical (100 mA, maximum)

75 mA, typical (100 mA, maximum)

15 mA + sensor current, typical (600 mA, maximum)

Voltages U

L

and U

S

at female connector U

LS

OUT can each only carry a maximum current of 2 A.

Digital Inputs

Number

Nominal input voltage

Range

Nominal input current

Current flow

Delay time

Permissible cable length to the sensor

8

24 V DC

-30 V DC < U

IN

< + 30 V DC

5 mA

Linear in the range 1 V < U

IN

< 30 V t

ON

= 2.9 ms, typical t

OFF

= 2.6 ms, typical

<

30 m

Input Characteristic Curve

Input Voltage (V)

-30 < U

IN

< 0.7

3

6

9

12

15

18

21

Typical Input Current (mA)

0

0.5

1.0

1.5

2.2

3.0

3.6

4.4

24 5.1

27 5.8

Sensor Supply

U

S

6.6

30

onlinecomponents.com

Minimum sensor voltage -1 V

Nominal current per channel 600 mA

Nominal current per device 600 mA

Overload protection

Short-circuit protection

Electronic per device

Electronic per device

PHOENIX CONTACT

11

7008_en_01

FLM BK PB M12 DI 8 M12

Error Messages to the Higher-Level Control or Computer System

Sensor supply short-circuit Yes

Sensor supply overload Yes

If an error is triggered by an overload or short circuit of the sensor supply, the device switches off the sensor supply of the channels and updates the diagnostics. The corresponding error message can then be read out by the master. If the sensor supply U

S

is not sufficiently high, the master can read out an appropriate error message also.

Interface

Bus system

Incoming Bus

Coupling of shield connection

Transmission Speed

Outgoing Bus

Coupling of shield connection

Transmission Speed

PROFIBUS DP

Directly to FE

12 Mbaud, maximum

Directly to FE

12 Mbaud, maximum

For transmission rates of more than 3 MBaud in PROFIBUS, series inductance is available in the device.

Please observe the installation instructions of the PROFIBUS User Organization.

Electrical Isolation/Isolation of the Voltage Areas

For device connection, please note the instructions and regulations in the "Installing the Fieldline Product

Range" user manual FLS FLM SYS INST UM E (Order No. 26 98 97 3).

Separate Potentials in the FLM BK PB M12 DI 8 M12

- Test Distance

24 V supply (bus logic) / FE

24 V supply (bus logic) / digital inputs

(sensor supply/I/O)

24 V supply (bus logic)/incoming remote bus

Digital inputs (sensor supply/I/O) / FE

- Test Voltage

500 V AC, 50 Hz, 1 min

500 V AC, 50 Hz, 1 min

500 V AC, 50 Hz, 1 min

500 V AC, 50 Hz, 1 min

Digital inputs (sensor supply / I/O)/ incoming remote bus

Incoming remote bus / FE

500 V AC, 50 Hz, 1 min

onlinecomponents.com

PHOENIX CONTACT

12

7008_en_01

FLM BK PB M12 DI 8 M12

Ordering Data

Ordering Data Device and Accessories

Description

Fieldline Modular Bus Coupler for PROFIBUS

With 8 Digital Inputs

Protective caps (for unused sockets)

Protective caps (for unused male connectors)

5-pos. shielded metal socket, B-encoded, for the incoming local bus

Shielded metal connector, 5-pos., B-encoded, for the outgoing remote bus and local bus

Markers

Bridging cable for power supply,

A-encoded, 5-pos., unshielded

Bridging cable for the local bus,

B-encoded, 5-pos., shielded

Assembly system for 5 devices

Assembly system for 7 devices

Order Designation

FLM BK PB M12 DI 8 M12

IBS IP PROT-IO

PROT-M12-M

SACC-M12FSB-5SC SH

SACC-M12MSB-5SC SH

Order No.

Pcs./Pkt.

27 36 33 0 1

27 59 91 9 5

27 36 19 4 5

15 13 59 6 1

15 13 57 0 1

ZBF 12:UNBEDRUCKT

SAC-5P-MS/ 0,13-186/FS

SCO

SAC-5P-MSB/0,13-PUR/FSB

SCO SH

FLM MP 5

FLM MP 7

08 09 73 5 10

15 18 48 1 1

15 18 47 8 1

27 36 66 0 1

27 36 67 3 1

Additional accessories for connecting the sensors and actuators can be found in the Phoenix Contact

PLUSCON catalog.

Ordering Data for Documentation

Description

"Installing the Fieldline Product Range" user manual

"Configuring a PROFIBUS DP System Using Devices in the Fieldline Product Range" user manual

Order Designation

FLS FLM SYS INST UM E

Order No.

26 98 97 3

Pcs./Pkt.

1

FLS FLM PB SYS PRO UM E 26 99 07 9 1

onlinecomponents.com

PHOENIX CONTACT

13

7008_en_01