Canadian Solar CS3K-P-FG, CS3U-P-FG, CS6X-P-FG Installation Manual
Advertisement
Advertisement
INSTALLATION
MANUAL OF
DYMOND MODULE
For professional use only
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
1.0 GENERAL INFORMATION
1.1 INSTALLATION MANUAL DISCLAIMER
1.2 LIMITATION OF LIABILITY
2.0 SAFETY PRECAUTIONS
3.0 MECHANICAL / ELECTRICAL SPECIFICATIONS
4.0 UNPACKING AND STORAGE
5.0 MODULE INSTALLATION
5.1 MODULE WIRING
5.2 MODULE GROUNDING
6.0 MOUNTING INSTRUCTIONS
7
.
0 MAINTENANCE
AMENDED EDITIONS AND DATES
ANNEX A: MECHANICAL AND ELECTRICAL RATINGS
ANNEX B: DOUBLE GLASS MODULE
INSTALLATION MANUEL SUPPLEMENT
|4
|4
|4
|4
|6
|7
|8
|5
|5
|8
|9
|10
|10
|12
www.canadiansolar.com
4 |
1.0
GENERAL INFORMATION
This general manual provides important safety information relating to the installation, maintenance and handling of double glass solar modules. Professional installer must read these guidelines carefully and strictly follow these instructions. Failure to follow these instructions may result in death, injury or property damage. The installation and handling of PV modules requires professional skills and should only be performed by qualified professionals.
Installers must inform end -users (consumers) the aforesaid information accordingly.
The word "module" or "PV module" used in this manual refers to one or more double glass solar modules. This manual is only valid for the double glass module type CS6K-P-FG, CS6X-P-FG, CS6K-M-
FG, CS6K-MS-FG and CS6X-M-FG. Please retain this manual for future reference. We recommend visiting www.canadiansolar.com
regularly for the most updated version.
1.1
INSTALLATION MANUAL DISCLAIMER
The information contained in this manual is subject to change by Canadian Solar Inc. without prior notice. Canadian Solar Inc. gives no warranty of any kind whatsoever, either explicitly or implicitly, with respect to the information contained herein.
This Manual (or document) is written in English with
Chinese (or other language) translation for reference only. In case there are inconsistencies or conflicts between the English version and the Chinese version
(or other language version) of this Manual (or document), the English version shall prevail and take control in all respects.
1.2
LIMITATION OF LIABILITY
Canadian Solar Inc. shall not be held responsible for damages of any kind, including – without limitation – bodily harm, injury or damage to property, in connection with handling PV modules, system installation, or compliance or non-compliance with the instructions set forth in this manual.
2.0
SAFETY PRECAUTIONS
Warning: Before attempting to install, wire, operate and/or service the module and other electrical equipment, all instructions should be read and understood.
PV module interconnectors pass direct current
(DC) when exposed to sunlight or other light sources. Contact with electrically active parts of the module, such as terminals, can result in injury or death, irrespective of whether or not the module and the other electrical equipment have been connected.
Avertissement: Toutes les instructions devront
être lues et comprises avant de procéder à l’installation, le câblage, l’exploitation et/ou l’entretien des panneaux. Les interconnexions des panneaux conduisent du courant continu
(CC) lorsque le panneau est exposé à la lumière du soleil ou à d’autres sources lumineuses.
Tout contact avec des éléments sous tension du panneau tels que ses bornes de sortie peut entraîner des blessures ou la mort, que le panneau soit connecté ou non.
GENERAL SAFETY
· All modules must be installed by licensed electricians in accordance with the applicable electrical codes such as, the latest National Electrical Code (USA) or
Canadian Electric Code (Canada), or other national or international electrical codes.
Protective clothing (non-slip gloves, clothes, etc.) must be worn during installation to prevent direct contact with 30 VDC or greater, and to protect your hands from sharp edges.
Prior to installation, remove all metallic jewelry to prevent accidental exposure to live circuits.
When installing or handling modules in light rain, morning dew or strong wind, appropriate safety measures should be taken to avoid damaging the modules or injuring people.
Do not allow children and unauthorized
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 5 persons near the installation site or storage area of modules.
· If the disconnects and over current protective devices (OCPD) cannot be opened or the inverter cannot be powered down, cover the fronts of modules in the PV array with an opaque material to stop the production of electricity when installing or working on a module or wiring.
· Use electrically insulated tools to reduce the risk of electric shock.
· Do not use or install broken modules.
circuit current under STC should be multiplied by
1.25 when determining component voltage ratings, conductor ampacities, overcurrent device ratings, and the size of controls connected to the PV output.
An additional 1.25 multiplier for the short-circuit current (giving a total multiplier of 1.56), may be applicable when sizing conductors and fuses, as described in section 690-8 of U.S. NEC.
4.0
UNPACKING AND STORAGE
PRECAUTIONS
· Contact with module surfaces or frames may cause electric shock if the front or rear glass is broken.
· Keep the junction box cover closed at all times.
· Do not connect or disconnect modules when current from the modules or an external source is present.
· Do not disassemble a module or remove any
module part.
· Do not artificially concentrate sunlight onto a module.
· The PV module does not contain any serviceable parts.
Do not attempt to repair any part of the module.
· Module should be stored in a dry and ventilated environment to avoid direct sunlight and moisture. If modules are stored in an uncontrolled environment, the storage time should be less than
3 months and extra precautions should be taken to prevent moisture exposure to connectors or sunlight exposure to modules.
· Unpack module pallets carefully, following the steps shown on the pallet. Unpack, transport and store the modules with care.
· Modules must always be unpacked by two people.
When handling modules always use both hands.
3.0
MECHANICAL / ELECTRICAL
SPECIFICATIONS
Module electrical ratings are measured under Standard Test Conditions (STC) of 1 kW/m2 irradiance, with an air mass (AM) spectrum of 1.5, and a cell temperature of 25°C. Detailed electrical and mechanical characteristics of Canadian Solar Inc. crystalline silicon PV modules can be found in Annex A (Mechanical And Electrical Ratings). Main electrical characteristics under STC are also stated on each module label. The maximum system voltage for double glass module type is 1000V (UL) and 1500V (IEC).
Under certain conditions, a module may produce more current or voltage than its STC rated power. As a result, a module open-circuit voltage and short-
· Do not lift modules by their wires or junction box; lift them by the frame.
· No stacking of modules.
· Do not place excessive loads on the module or twist the module frame.
· Do not stand, step, walk and/or jump on modules. www.canadiansolar.com
6 |
· Do not drop or place objects (such as tools) on the modules.
· Do not carry modules on your head.
· Do not use sharp instruments on the modules.
· Do not place modules on top of each other
· Do not leave modules unsupported or unsecured.
· Do not change the wiring of bypass diodes.
· Keep all electrical contacts clean and dry.
PRODUCT IDENTIFICATION
· Each module is equipped with two identical barcodes (one inside the laminate under the front glass, the second on the rear side of the module) that act as a unique identifier. Each module has a unique serial number containing 14 digits.
· A nameplate is also affixed to the rear glass of each module. This nameplate specifies the model type, as well as the main electrical and safety characteristics of the module.
5.0
MODULE INSTALLATION
PRECAUTIONARY MEASURES
AND GENERAL SAFETY
· Prior to installing modules please obtain information about any requirements and necessary approvals for the site, installation and inspection from the relevant authorities.
· Check applicable building codes to ensure that the construction or structure (roof, facade, support, etc.) can bear the module system load.
· Canadian Solar Inc. double glass solar modules have been qualified for Application Class A
(equivalent to Safety Class II requirements).
Modules rated under this class should be used in systems operating at voltage above 50 V or power above 240 W, where general contact access is anticipated.
Please note
DO NOT STAND OR STEP on the modules under any circumstances.
Localized heavy loads may cause severe microcracks at cell level, which in turn may compromise module reliability. Failure to comply with the above caution will void Canadian Solar Inc.’s warranty.
SYSTEM FIRE RATING
· The fire rating for this module is only valid when the product is installed as specified in the mechani cal mounting instructions.
· Canadian Solar Inc. double glass modules have been certified by CSA as Type 3 for fire performance.
· When installing the modules on rooftop, please ensure the assembly is mounted over a fire resistant roof covering rated for the application.
· A photovoltaic system composed of UL1703 certified modules mounted on a UL2703 certified mounting system should be evaluated in combination with roof coverings in accordance with UL1703 standard, with respect to meeting the same fire classification as the roof assembly.
· Mounting systems with a System Fire Class Rating
(Class A, B or C), tested in conjunction with fire rated “Type 3” rated modules, are considered acceptable for use with Canadian Solar Inc. modules, provides the mounting system does not violate any other requirements of this manual.
· Any mounting system limitations on inclination or accessories required to maintain a specific System
Fire Class Rating should be clearly specified in the installation instructions and UL2703 certification of the mounting system supplier.
ENVIRONMENTAL CONDITIONS
· The module is intended for use in general open-air climates, as defined in IEC 60721-2-1: Classification of environmental conditions Part 2-1: Environmental conditions appearing in nature - temperature and humidity.
· Please consult the Canadian Solar Inc. technical support department for more information on the use of modules in special climates.
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 7
Do not install modules near naked flames or flammable materials.
Do not immerse modules in water or constantly expose modules to water
(either fresh or salt) (i.e. from fountains, sea spray).
· The recommended maximum series fuse rating is stated in a table in the Annex.
· Modules should be safely fixed to bear all expected loads, including wind and snow loads.
· A minimum clearance of 0.394 in (10 mm) or more between modules is required to allow for thermal expansion of the modules. The clearance is from the plastic protect corner to adjacent plastic protect connector.
· Exposing modules to salt (i.e. marine environments) or sulfur (i.e. sulfur sources, volcanoes) incurs the risk of module corrosion.
· Failure to comply with these instructions will void
Canadian Solar Inc. warranty.
OPTIMUM ORIENTATION AND TILT
INSTALLATION REQUIREMENTS
· Ensure that the module meets the general technical system requirements. Ensure that other systems components do not damage modules mechanically or electrically.
· To maximize your annual yield, find out the optimum orientation and tilt for PV modules in your region.
The highest yields are achieved when sunlight shines perpendicularly onto the PV modules.
AVOID SHADING
· Modules can be wired in series to increase voltage or in parallel to increase current. To connect modules in series, connect the cables from the positive terminal of one module to the negative terminal of the next module. To connect in parallel, connect the cables from the positive terminal of one module to the positive terminal on the next module.
· Only connect the quantity of modules that corresponds to the voltage specifications of the inverters used in the system. Modules must not be connected together to create a voltage higher than the maximum permitted system voltage, even under the worst local temperature conditions.
· A maximum of two strings can be connected in parallel without using over-current protection device
(fuses…) incorporated in series within each string.
Three of more strings can be connected in parallel if an appropriate and certified over-current protec tion device is installed in series with each string.
· Only modules with similar electrical outputs should be connected in the same series to avoid or minimize mismatch effects in arrays.
· To minimize risk in the event of an indirect lightning strike, avoid forming loops when designing the system.
· Even minor partial shading (e.g. from dirt deposits) reduces yields. A module can be considered to be unshaded if its entire surface is free from shading all year round. Sunlight should be able to reach the module even on the shortest day of the year.
· Permanent shading conditions can affect module service lifetime, due to accelerated ageing of the encapsulation material and thermal stress on the bypass diodes.
RELIABLE VENTILATION
· Sufficient clearance (at least 3.94 in (10 cm)) bet ween the module frame and the mounting surface is required to allow cooling air to circulate around the back of the module. This also enables condensation or moisture to dissipate.
· Any other specific clearance required for main taining a system fire rating should prevail. Detailed clearance requirements pertaining to system fire ratings must be provided by your racking supplier.
5.1
MODULE WIRING
www.canadiansolar.com
8 |
CORRECT WIRING SCHEME
· Ensure that the wiring is correct before starting up the system. If the measured open circuit voltage (Voc) and short-circuit current (Isc) differ from the specifications, this indicates that there is a wiring fault.
CORRECT CONNECTION OF PLUG CONNECTORS
· Make sure that connections are safe and tight.
Plug connector should not be subjected to stress from the exterior. Connectors should only be used to connect the circuit. They should never be used to turn the circuit on and off. damage by taking appropriate precautions.
Avoid exposure to direct sunlight.
5.2
MODULE GROUNDING
· EQUIPMENT GROUNDING: double glass modules do not present any exposed conductive parts, and therefore do not require to be electrically grounded for compliance to the National Electrical Code.
· Proper equipment grounding is still required for the racking system in compliance with all local electrical codes and regulations. Please refer to the racking system user instructions.
USE OF SUITABLE MATERIALS
· Only use dedicated solar cable and suitable plugs
(wiring should be sheathed in a sunlight-resistant conduit or, if exposed, should itself be sunlight- resistant) that meet local fire, building and electrical regulations. Please ensure that all wiring is in perfect electrical and mechanical condition.
· Installers may only use 2.5-10 mm 2 (8-14 AWG) single conductor cable listed and labeled as PV Wire or TUV 2PfG1169 approved, that is 90°C wet rated with proper insulation that is able to withstand the maximum possible system open-circuit voltage.
Only copper conductor material should be used.
Select a suitable conductor gauge to minimize voltage drop and ensure that the conductor ampacity complies with local regulations (i.e. NEC
690.8(D)).
6.0
MOUNTING INSTRUCTIONS
STANDARD MODULES
For a clear understanding of our modules, please refer to the illustration of a module shown below:
Junction box
Plastic corners
Cables and connectors
(-)
(+)
CABLE PROTECTION
· Secure the cables to the mounting system using
UV-resistant cable ties. Protect exposed cables from damage by taking appropriate precautions
(e.g. placing them inside a plastic conduit). Avoid exposure to direct sunlight.
· A minimum bending radius of 60 mm is required when securing the junction box cables to the racking system.
CONNECTOR PROTECTION
· Protect exposed connectors from weathering
The applicable regulations pertaining to work safety, accident prevention and securing the construction site must be observed. Workers and third party personnel shall wear or install fall arrest equipment.
Any third party need to be protected against injuries and damages.
· The mounting design must be certified by a registered professional engineer. The mounting design and procedures must comply with local codes and requirements from all relevant authorities.
· Each module must be securely fastened at a minimum of 4 points on two opposite sides.
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 9
Canadian Solar Inc. recommends mounting rails with a minimum width of 40mm for ±2400Pa load and a minimum width of 60mm for +5400 Pa
/-2400Pa load.
· Install and tighten the module clamps to the mounting rails using the torque stated by the mounting hardware manufacturer. System designer and installer are responsible for load calculations and for proper design of support structure. It is recommended to use a torque wrench for installation. Tightening torques should respectively be within 17~23 Nm (12.5~17.0 ft-lb)
(23 Nm (17.0 ft-lb) is recommend) for M8x1.25-
Grade 8.8 coarse thread bolts, depending on bolt class.
· Use appropriate corrosion-proof fastening materials. All mounting hardware (bolts, spring washers, flat washers, nuts) should be made with stainless steel.
· Clamp material should be anodized aluminum alloy or steel of appropriate grade. One buffer rubber material (Recommended material is EPDM) must be added between the clamp and the glass.
· Canadian Solar Inc. warranty may be void in cases where improper clamps or unsuitable installation methods are found. When installing clamps, take measures so as:
1. Not to bend the laminate excessively.
2. Not to cast shadow on the cells.
3. Not to damage or scratch the surface of the glass.
4. To ensure the clamps overlap the module by
13 mm to 15 mm.
Nut
Spring washer
Flat washer Top Middle Clamp
Rubber
5. To ensure the thickness of the clamps is at least 3 mm.
Nut
Spring washer
Flat washer Top End Clamp
Rubber
Rail Bolt Bottom End Clamp Glass
· Clamp positions are of crucial importance for the reliability of the installation, the clamp centerline must only be positioned within the authorized position ranges indicated in ANNEX B, depending on the configuration and load.
· The module is only considered to comply with
UL1703 when mounted as specified in the instructions in ANNEX B. Any module without a frame
(laminate) shall not be considered to comply with the requirements of UL 1703 unless the module is mounted with hardware that has been tested and evaluated with the module under this standard or by a field Inspection certifying that the installed module complies with the requirements of UL
1703.
· Double glass modules can be mounted to a support structure by means of clamps. For recommended installation methods and load, please refer to
ANNEX B and contact your local representative for further information. Failure to use a recognized installation method will void Canadian Solar Inc. warranty.
Glass Rail
7.0
MAINTENANCE
· Regular maintenance is required to keep modules clear of snow, bird droppings, seeds, pollen, leaves, branches, dirt spots, and dust.
Bolt Bottom Middle Clamp
· Modules with sufficient tilt (at least 15°), generally do not require cleaning (rain will have a selfwww.canadiansolar.com
10 | cleaning effect). If the module has become soiled, it shall be washed with water and a non-abrasive cleaning implement (sponge) during the cool part of the day. Do not scrape or rub dry dirt away, as this may cause micro scratches.
· Snow should be removed using a soft brush.
· The system shall be periodically inspected to verify the integrity of all wiring and supports.
· To protect against electric shock or injury, electrical or mechanical inspections and maintenance should be performed by qualified personnel only and on a regular basis.
· Please refer to our Installation Manual Annex
(Section Annex D: Module Cleaning Guideline) for more information on module cleaning.
AMENDED EDITIONS
AND DATES
· Rev 1.0 is released in June 2015
· Rev 1.1 is released in Aug. 2015.
· Rev 1.2 is released in January 2016.
· Rev 1.3 is released in May 2016.
· Rev 1.4 is released in June 2016.
· Rev 1.5 is released in July 2016.
· Rev 1.6 is released in March 2017.
ANNEX A:
MECHANICAL AND ELECTRICAL RATINGS
Standard Test Conditions are: irradiance of 1 kW/m 2 , air mass (AM) spectrum of 1.5, and cell temperature of 25°C. The electrical characteristics are respectively within ±10 percent or [0; +5 W] of the indicated values for Isc, Voc and Pmax. Specifications are subject to change without notice.
Table 1:
Mechanical and Electrical Ratings under STC
Module Type
CS6K-245P-FG
CS6K-250P-FG
CS6K-255P FG
CS6K-260P-FG
CS6K-265P-FG
CS6K-270P-FG
CS6K-275P-FG
CS6K-280P-FG
CS6K-285P-FG
CS6K-290P-FG
CS6K-295P-FG
CS6K-300P-FG
CS6K-245M-FG
CS6K-250M-FG
CS6K-255M-FG
CS6K-260M-FG
CS6K-265M-FG
CS6K-270M-FG
CS6K-275M-FG
Maximum
Power
Pmax <W>
Operating voltage
Vmp <V>
245
250
255
260
265
285
290
295
300
270
275
245
250
255
260
265
270
275
280
31.4
31.6
31.8
32.0
30.3
30.4
30.5
30.7
30.9
31.1
31.3
30.0
30.1
30.2
30.4
30.6
30.8
31.0
31.3
Operating current
Imp <A>
Open Circuit Voltage
Voc <V>
Short Circuit Max. Series
Current
Isc <A>
Fuse
Rating <A>
Overall
Dimension
<mm>
Weight
<kg>
9.06
9.18
9.28
9.38
8.09
8.22
8.35
8.48
8.61
8.67
8.80
8.17
8.30
8.43
8.56
8.66
8.75
8.88
8.95
38.3
38.5
38.6
38.8
37.4
37.5
37.7
37.8
37.9
38.2
38.3
37.1
37.2
37.4
37.5
37.7
37.9
38.0
38.2
9.64
9.72
9.81
9.92
8.61
8.74
8.87
8.99
9.11
9.19
9.31
8.74
8.87
9.00
9.12
9.23
9.32
9.45
9.52
15
15
1658ˣ 992 ˣ 5.8
(65.3 ˣ 39.1 ˣ 0.23 in) without junctionbox and corner protector
1658ˣ 992 ˣ 5.8
(65.3 ˣ 39.1 ˣ
0.23 in) without junction-box and corner protector
23
23
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 11
Module Type
CS6K-280M-FG
CS6K-285M-FG
CS6K-290M-FG
CS6K-295M-FG
CS6K-300M-FG
CS6K-305M-FG
CS6K-250MS-FG
CS6K-255MS-FG
CS6K-260MS-FG
CS6K-265MS-FG
CS6K-270MS-FG
CS6K-275MS-FG
CS6K-280MS-FG
CS6K-285MS-FG
CS6K-290MS-FG
CS6K-295MS-FG
CS6K-300MS-FG
CS6K-305MS-FG
CS6K-310MS-FG
CS6X-290P-FG
CS6X-295P-FG
CS6X-300P-FG
CS6X-305P-FG
CS6X-310P-FG
CS6X-315P-FG
CS6X-320P-FG
CS6X-325P-FG
CS6X-330P-FG
CS6X-335P-FG
CS6X-340P-FG
CS6X-345P-FG
CS6X-290M-FG
CS6X-295M-FG
CS6X-300M-FG
CS6X-305M-FG
CS6X-310M-FG
CS6X-315M-FG
CS6X-320M-FG
CS6X-325M-FG
CS6X-330M-FG
CS6X-335M-FG
CS6X-340M-FG
CS6X-345M-FG
CS6X-350M-FG
37.2
37.4
37.5
37.8
37.9
38.1
38.3
36.5
36.6
36.7
36.9
36.3
36.4
36.6
36.8
37.0
32.7
32.9
35.9
36.0
36.1
37.2
37.4
37.6
37.8
31.7
31.9
32.1
32.3
32.5
30.7
30.9
31.1
31.3
31.5
31.5
31.7
31.9
32.1
32.4
32.5
30.5
36.3
36.4
8.61
8.69
8.8
8.87
8.97
9.06
9.14
8.22
8.33
8.44
8.53
8.41
8.52
8.61
8.69
8.78
9.33
9.43
8.08
8.19
8.30
8.88
8.96
9.05
9.13
8.84
8.94
9.05
9.14
9.24
8.31
8.42
8.53
8.63
8.74
8.89
8.98
9.09
9.19
9.25
9.38
8.2
8.00
8.11
45.6
45.8
45.9
46.1
46.2
46.4
46.6
45
45.2
45.3
45.5
44.8
44.9
45.1
45.3
45.5
39.9
40.1
44.4
44.5
44.6
45.6
45.8
45.9
46.0
38.9
39.1
39.3
39.5
39.7
37.9
38.1
38.3
38.5
38.7
38.5
38.6
38.7
38.9
39.1
39.2
37.7
44.7
44.9
Maximum
Power
Pmax <W>
Operating voltage
Vmp <V>
Operating current
Imp <A>
Open Circuit Short Circuit Max. Series
Voltage
Voc <V>
Current
Isc <A>
Fuse
Rating <A>
Overall
Dimension
<mm>
Weight
<kg>
320
325
330
335
340
345
350
300
305
310
315
305
310
315
320
325
305
310
290
295
300
330
335
340
345
280
285
290
295
300
255
260
265
270
275
280
285
290
295
300
305
250
290
295
15
15
15
1658ˣ 992 ˣ 5.8
(65.3 ˣ 39.1 ˣ 0.23 in) without junctionbox and corner protector
1968ˣ 992 ˣ 5.8mm
(77.5ˣ 39.1 ˣ 0.23 in) without junctionbox and corner protector
1968ˣ 992 ˣ 5.8mm
(77.5ˣ 39.1 ˣ 0.23 in) without junctionbox and corner protector
23
27.5
27.5
9.13
9.21
9.31
9.41
9.48
9.56
9.67
8.74
8.84
8.95
9.04
8.97
9.08
9.18
9.26
9.34
9.91
9.99
8.64
8.76
8.87
9.45
9.54
9.62
9.69
9.51
9.59
9.67
9.75
9.83
9.11
9.19
9.27
9.35
9.43
9.43
9.51
9.59
9.68
9.78
9.89
9.03
8.51
8.63
www.canadiansolar.com
12 |
ANNEX B:
DYMOND MODULE INSTALLATION
MANUAL SUPPLEMENT
All the basic requirements of the main installation manual should apply to this supplement, unless otherwise specified.
Clamping Location Illustration
Illustration A
A A
Illustration B
A B B A
A A
Clamping on module long side, four clamp points;
Mounting rails must run perpendicularly to the module long side.
The following clamps in table 2 have been approved as compatible with Canadian Solar double glass module CS6K-P-FG, CS6K-M-FG and CS6K-MS-FG.
A B B A
Clamping on module long side, six clamp points;
Mounting rails must run perpendicularly to the module long side.
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 13
Table 2:
CS6K-P-FG, CS6K-M-FG and CS6K-MS-FG compatible clamps
Mounting
Method
2-A-1
2-A-2
2-B-1
Supplier
NISSEI METALS
CO.,LTD.
2-B-2
2-B-3
K2 Systems GmbH
/ Everest Solar
Systems, LLC
2-B-4
2-C-1
2-C-2
2-C-3
2-C-4
2-D-1
2-D-2
2-D-3
2-D-4
Schletter Inc. /
Schletter GmbH
Xiamen Grace
SolarTechnology co.,ltd.
Clamp Image Clamp Type & length Clamp Quantity Load (Pa)
Certification
Body
SA-TOK-UA (End clamp)
/ SA-KOK-UA (Middle clamp), clamp length=120 mm four clamps,
A=380±20 mm,
see illustration A six clamps,
A=250±20 mm,
B=579±20 mm,
see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE
K2 frameless clamp,
4-7.2 mm, clamp length= 100 mm
K2 frameless clamp,
4-7.2 mm, clamp length=200 mm
A=380±20 mm, four clamps
A=380±20 mm, four clamps
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
K2 frameless clamp,
4-7.2 mm, clamp length= 80 mm six clamps,
A=250±20 mm,
B=579±20 mm,
see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE / CSA
VDE / CSA
K2 frameless clamp,
4-7.2 mm, clamp length= 100 mm six clamps,
A=250±20 mm,
B=579±20 mm,
see illustration B
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide, 3-8 mm, clamp length=100 mm
Profi clamp, wide, 3-8 mm, clamp length=200 mm four clamps,
A=380±20 mm, see illustration A four clamps,
A=380±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE / CSA
Profi clamp, wide, 3-8 mm, clamp length=80 mm six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide, 3-8 mm, clamp length=100 mm six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp)/
GS-EC (End clamp), clamp length=100 mm four clamps,
A=380±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp)/
GS-EC (End clamp), clamp length=200 mm four clamps,
A=380±20 mm, see illustration A
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
GS-IC (Middle clamp)/
GS-EC (End clamp), clamp length=80 mm
GS-IC (Middle clamp)/
GS-EC (End clamp), clamp length=100 mm six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE / CSA
VDE / CSA www.canadiansolar.com
14 |
Mounting
Method
2-E-1
2-E-2
2-E-3
Powerway
Renewable Energy
Co.,Ltd
2-E-4
2-F-1
2-F-2
2-F-3
2-F-4
Supplier
Akcome Metals
Technology
(Suzhou) Co.,Ltd.
Clamp Image Load (Pa)
Certification
Body
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=100 mm four clamps,
A=380±20 mm, see illustration A
PW-CS-01 (End clamp) /
PW-CS-02 (Middle clamp), clamp length=200 mm four clamps,
A=380±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=80 mm six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=100 mm six clamps,
A=250±20 mm,
B=579±20 smm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=100 mm four clamps,
A=380±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=200 mm four clamps,
A=380±20 mm, see illustration A
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=80 mm
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=100 mm six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B six clamps,
A=250±20 mm,
B=579±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE / CSA
VDE / CSA
VDE / CSA
VDE/CSA
VDE/CSA
VDE / CSA
VDE / CSA
The following clamps in table 3 have been approved as compatible with Canadian Solar double glass module CS6X-P-FG and CS6X-M-FG.
EN-Rev IM-FDM-EN/1.6 Copyright © March 2017. Canadian Solar Inc.
| 15
Table 3:
CS6X-P-FG and CS6X-M-FG compatible clamps
Mounting
Method
3-A-1
3-B-1
Supplier
NISSEI METALS
CO.,LTD.
3-B-2
3-B-3
K2 Systems GmbH
/ Everest Solar
Systems, LLC
3-B-4
3-C-1
3-C-2
3-C-3
3-C-4
3-D-1
3-D-2
3-D-3
3-D-4
Schletter Inc. /
Schletter GmbH
Xiamen Grace
SolarTechnology co.,ltd.
Clamp Image Clamp Type & length Clamp Quantity Load (Pa)
Certification
Body
SA-TOK-UA (End clamp)
/ SA-KOK-UA (Middle clamp), clamp length=120mm six clamps,
A=300±20mm,
B=684±20mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE
K2 frameless clamp,
4-7.2 mm, clamp length=130 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
K2 frameless clamp,
4-7.2 mm, clamp length=250 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
K2 frameless clamp,
4-7.2 mm, clamp length=100 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
K2 frameless clamp,
4-7.2 mm, clamp length=130 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide,
3-8 mm, clamp length=130 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide,
3-8 mm, clamp length=250 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide,
3-8 mm, clamp length=100 mm six clamps,
A=300±20mm,
B=684±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
Profi clamp, wide,
3-8 mm, clamp length=130 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp)
/ GS-EC (End clamp), clamp length=130 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp) /
GS-EC (End clamp), clamp length=250 mm four clamps,
A=440±20 mm, see illustration A
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp)
/ GS-EC (End clamp), clamp length=100 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
VDE / CSA
GS-IC (Middle clamp)
/ GS-EC (End clamp), clamp length=130 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA www.canadiansolar.com
Mounting
Method
3-E-1
3-E-2
3-E-3
3-E-4
3-F-1
3-F-2
3-F-3
3-F-4
Supplier
Powerway
Renewable Energy
Co.,Ltd
Akcome Metals
Technology
(Suzhou) Co.,Ltd.
Clamp Image Clamp Type & length
Clamp Quantity
& Location
Load (Pa)
Certification
Body
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=130 mm
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=250 mm
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=100 mm
PW-CS-01(End clamp) /
PW-CS-02 (Middle clamp), clamp length=130 mm four clamps,
A=440±20 mm, see illustration A four clamps,
A=440±20 mm, see illustration A six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=130 mm
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=250 mm four clamps,
A=440±20 mm, see illustration A four clamps,
A=440±20 mm, see illustration A
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=100 mm
AK-EC-DG (End clamp)
/ AK-MC-DG (Middle clamp), clamp length=130 mm six clamps,
A=300±20 mm,
B=684±20 mm, see illustra tion B six clamps,
A=300±20 mm,
B=684±20 mm, see illustration B
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
Downforce load≤2400 Pa
Uplift load ≤2400 Pa
Downforce load≤5400 Pa
Uplift load ≤2400 Pa
VDE / CSA
VDE / CSA
VDE / CSA
VDE / CSA
VDE/CSA
VDE/CSA
VDE / CSA
VDE / CSA
(*) Design Load and safety factor will be determined by the racking suppliers or professional engineer. For detailed information, please follow local structural code or contact professional structural engineer.
(*) Connector protector is not included in the above illustration.
CANADIAN SOLAR INC.
545 Speedvale Avenue West, Guelph, Ontario, Canada N1K 1E6 www.canadiansolar.com

Download
Advertisement