Entes MPR-53S Manual
Entes MPR-53 is a network analyzer that allows the measurement of different electrical parameters in a network, such as voltage (including THD), current, active power (including demand), reactive power and apparent power. It also provides information about energy consumption, harmonics and power factor. The device comes with a backlit LCD display that shows all the measured parameters and it is possible to choose which units to display. It is also possible to connect the device to a computer via a serial interface to transfer the measured data.
Advertisement
Advertisement
NETWORK ANALYSER
MPR-53/53S
TECHNICAL DATA
Operating Voltage (Un)
Operating frequency (f)
IIn
: Please look behind the device.
: 45-65 Hz
Auxiliary supply Power Consumption : < 4 VA
Measuring Input Power Consumption: < 1VA
VIn : 10-300 V AC 45-65 Hz. (L-N)
: 10-500 V AC 45-65 Hz. (L-L)
: 0.05 - 5.5 A~
2-120 A~ (for CT-25)
Measuring Range
Class
Voltage Transformer Ratio (Vtr)
Current Transformer Ratio (Ctr)
Max. Ctr x Vtr
Demand Time
Serial Interface (for MPR-53S)
Baud Rate (for MPR-53S)
Address (for MPR-53S)
Parity (for MPR-53S)
Pulse Output
Switch Period
: 10V...200 kV AC
: 0...215 M (W,VAr,VA)
: 99999999999.9 kWh, kVArh
: 1% ± 1 digit [(10%-110%) xFull Scale]
: 0,1 ... 4000,0
: 1 ... 2000
: 40.000
: 1-60 min. (programmable)
: MODBUS RTU (RS 485)
Optically Isolated, programmable
: 2400-38400 bps
: 1-247
: No, Odd, Even, 8 Data bits, 2 Stop Bits
: NPN Transistor
: Min. 100 msec pulse perriod
80 msec pulse width
Operation Current
Operation Voltage
Input
Ambient Temperature
Display
Dimensions
Equipment Protection Class
Box Protection Class
Box Material
Installation
: Max. 50 mA
: 5.....24 V DC, max. 30 VDC
: 12...48 V AC / DC
: -5°C; +50°C
: Red LED Display
: PR-19, PK-26
: Double Insulation-Class II ( )
: IP 40 (front panel)
: Non-flammable
: Panel Mounted (PR-19)
Rail Mounted (PK-26)
Wire Thickness (for terminal block) : 2.5 mm
2
Weight
Installation Category
: 0.45 kg (PR-19, PK-26)
: Class III
Factory Settings
Trafo :
Ctr (Current Transformer Ratio) : 0001 trn (Turn number for CT-25 device): 01
Utr (Voltage Transformer Ratio) : 0001.0
CAL (Calculation Method) : 1
Eng Cnt :
E-1 (Energy Counter 1) : on
E-2 (Energy Counter 2) : on
Pin : 0000 (Not Activated)
PULSE : rAt (Ratio) : 1k o-1 (Output 1) : A-I o-2 (Output 2) : r-L
RS-485 :
Adr (Address) : 1
Bau (Baud Rate) : 9600
PAr (Parity) : no dEtý (Delay Time) : 15
PRECAUTIONS FOR INSTALLATION AND SAFE USE
The current terminal connections must be implemented with using CT-25.
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment..
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
- Only for rack panel mounting.
8
A3918/Rev.3
NETWORK ANALYSER
MPR-53/53S
General
MPR-53/53S is developed for measuring all the electrical parameters on the network. Measured parameters are shown in 5 separate displays.This allows to monitor more than 50 parameters at the same time. MPR-53S has also
MODBUS serial interface feature.
Phase
Displays
S W, S VA and
Hz Display
S VAr and
Cos j Display
Back button
ESC button
Phase Displays
UP button
DOWN button
Max. LED
SET
Minimum LED
Demand LED
UP
DOWN
Max. LED
SET
Minimum LED
Demand LED
S W, S VA and Hz
Display
S VAr ve Cos
Display j Back ESC
Using of MPR-53/53S:
Parameters are shown in L1, L2, L3 displays (V
Power ( S
Total Reactive Power (
LN
; V
LL
; A; I
N kWh, kVarh, THD) by using up-down buttons. Total Active ( S
; W; VAr; VA; Cos j
W), Total Apparent
VA) and Frequency (Hz) are selected by back button.
S VAr) and Cos j are selected by Esc button.
;
Digital Inputs
MPR-53/53S has 2 digital inputs which are used to monitor the status of electrical contacts. Digital input has 2 functions :
- Enabling remote control of the data received through the digital input terminal
(battery, thermostat, circuit breaker, pumps status)
- Controlling energy counters and determining which energy counter will be
active.
Energy Pulse Outputs
MPR-53/53S has 2 Energy Pulse Outputs. These outputs give the pulses only for E-1 (Energy Counter).
Pul1 and Pul2: In o-1 (Pulse1), o-2 (Pulse2) menus which are in the pulse menu, device give pulse according to selected energy parameters as [Active energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)].
Please refer to the pulse menu for the coefficients of energies.
Monitoring of Min.,Max. and Max. Demand Values:
Min. and max. values are defined for V
LN
, V
LL
, A, W, VAr, VA, S W, demand values are defined for A, W, VAr, VA, S W, S VA, S VAr
S VAr, S VA
.
If measured instant value is smaller than min. value which was stored before,
; it is stored as new min. value. If measured instant value is greater than max.
value which was stored before, it is stored as new max. value.
Demand value is the average value of the measured values in demand time
(15 minute).
If one of defined parameters is displayed (ie. A) when deman button is pressed min., max or max. demand values are displayed. When an undefined parameter is displayed (ie. Cos is continued to display.
j ) if demand button is pressed, instant value
Monitoring THD Values
When V
LN
and THD leds light on, voltage THD is monitored and also if A and THD leds light on, current THD is monitored.
Monitoring Neutral Current
Neutral current can be monitored by scrolling after 3-phases current values has displayed.
H-L-M LEDs
H-L-M LEDs are dedicated to displaying the min., max. and max. demand values according to selected parameters.
H: Maximum Value, L: Minimum Value, M: Max. Demand Value
1
Calculation Methods for Active / Reactive Power Values
If the led on the most left side blinks it represents that active powers / reactive powers direction is negative.
There are two methods for calculating total active and total reactive powers:
1) Active / Reactive power can be calculated by summing import and export values and displaying as a single value.
2) Active / Reactive power can be calculated according to direction as import / export.
Note :
1) The dot at the most right digit of the fourth display (During S W is displayed) represents that displayed value is export active power value.
Vice versa, displayed value is import active power value.
2) The dot at the most right digit of the fourth display (During S VAr is displayed) represents that displayed value is capacitive reactive power value. Vice versa, displayed value is inductive reactive power value.
3) The displayed parameter will not change if power is off after 30 seconds of stand-by (ie. A).
Measured Parameters:
V
V
LN
LL
(Phase Voltage )
(Phase to Phase Voltage)
W (Active Power)
VAr (Reactive Power)
VA (Apparent Power)
Cos j
AI ( kWh) (Import Active Energy I)
A (Phase Current, Neutral Current) AE (kWh) (Export Active Energy) rI (kVArh) (Import Reactive Energy) rE(kVArh) (Export Reactive Energy)
THD (Total Harmonic Distortion)
Hz. (Frequency)
S W (Total Active Power)
S VAr (Total Reactive Power)
S VA (Total Apparent Power)
FUNCTIONS OF BUTTONS
In the monitoring mode, it is used to switch between
(V
LN
, V
LL
, A, W, VAr, VA, Cos j , kWh, kVarh, THD) parameters.
At the programming mode, it provides to increase value of desired parameter and pass to the next menu.
In the monitoring mode, it is used to pass between
(V
LN
, V
LL
, A, W, VAr, VA, Cos j , kWh, kVarh, THD) parameters.
At the programming mode, it provides to decrease value of desired parameter and pass to the prevides menu.
(SET) In the monitoring mode, it is used to switch between min., max., demand and instant values. When it is pressed for 3 seconds, programming mode it is entered.
In the programming mode, it is used for saving parameters and moving to the sub menu.
(Back) In the monitoring mode, it is used to switch between S W, S VA and Hz parameters. It used to switch to the previous digit in submenu.
(ESC) In the monitoring mode, it provides to switch between and Cos j
S VAr
values. In the programming mode, it is used to enter to the upper menu or it is used to quit from the programming mode without saving values.
If user password is activated and set button is pressed for 3 seconds, a pin code is required in order to enter to the menu.
Current Transformer Ratio Setup
In this menu, current transformer ratio is set between 1 - 2000.
Note: If the current transformer is not used between the system and MPR-53/53S, current transformer ratio is entered as 1.
Example: If a current transformer which has a ratio of 250/5A is used between the system and MPR-53/53S; Current transformer ratio is entered as 50 (250/5).
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted devices, trA Fo trn is displayed instead.)
( Not: trA Fo Utr menu can be displayed by scrolling the UP/DOWN buttons.)
Press SET button. Blinking the first digit of displayed value appears.
(trA Fo Utr menu can be programmed similarly.)
Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use BACK button to go to previous digit. After you entered the last digit press SET button, trA Fo Ctr / trA Fo trn / trA Fo Utr is displayed. on can be selected by scrolling UP/DOWN buttons. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
NETWORK ANALYSER
MPR-53/53S
Programming the Turn Number:
This menu is available for CT-25 adapted devices. User enter the turn number, which is the number of how many tour the current cable has rounded into the CT-25. Numbers can be selected between 1-20. Greater the number of turn means greater the sensivity.
1
2.00
120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
Voltage Transformer Ratio Setup
In this menu, voltage transformer ratio is set between
0000,1 - 4000,0.
Note: If the voltage transformer is not used between the system and MPR-53/53S, voltage transformer ratio is entered as 1.
Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and MPR-53/53S; Voltage transformer ratio is entered as 345. (34500/100)
Reactive Energy Calculation Method Setting
Three different methods exist for reactive energy calculation in
MPR-53/53S. Brief informations about these methods are explained in below table.
Related values which must be entered in the menu are also indicated in the table in order to select reactive power calculation method for mechanical and digital energymeters.
Mechanical Energymeter
(Vectoral summation of 3-phase)
Digital Energymeter
(Each phase seperately)
0 1
Reactive Energy
(Q)
90° rotation of voltage vector and multiply with current
Description
It is the most preferred reactive power calculation methode.
4
2
5
3 S
¥ n=1
V n
.I
n
.sin( j n
) to 19 th harmonics. This calculation methode is mostly preferred for network analysers.
S 2 -P 2
Power Triangle Methode : According to this methode;
Q = S 2 -P 2
(Q : Reactive power, S : Active power, P : Apparent power)
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button (trA Fo Ctr menu is displayed)
By using UP-DOWN buttons, find
CAL CUL Atý on menu.
Press SET button. (Most right digit of 5th display blinks)
By using UP-DOWN buttons, select energy calculation method.
Press set button, CAL CUL Atý on is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Demand Time Setup:
In this menu,demand time is set between 1-60 minutes.
Press SET button for 3 sec. (trA Fo menu is displayed)
By using UP-DOWN buttons find
dE tý menu.
Press SET button (First digit blinks.)
Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use BACK button to go to previous digit. After you entered the last digit press SET button, dE tý is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Monitoring and Erasing of minimum, maximum and energy values:
In this menu, values of min.,max. or energy counters are erased.
It saves the instantaneously measured min. and max. values of
MPR-53/53S into its memory. Please kindly look at to the section of FUNCTIONS OF BUTTONS for min. and max. values.
Note : Measured electrical parameters which are saved to the memory are not affected from the electric interruptions.
In the rESEt menu; when you quit from all menus, if you confirm the changes,min. and max. values of all parameters or energy counter values are erased at the same time.
For erasing the values of min. and max. or energy counter,
In the measurement mode :
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons, find rES Et menu.
Press SET button.
(rESEt HL menu is displayed)
By using UP-DOWN buttons, select which parameter you want to reset.
Press SET button, one of the parameter rES Et dE / rES Et HL / rES Et E-1 / rES Et E-2 is displayed.
By using UP-DOWN buttons, if you want to delete the min., max., max. demand or energy; select yES otherwise select no option.
Press SET button. (rES Et dE / rES Et HL / rES Et E-1 / rES Et E-
2 is displayed. Data is entered but is not activated yet. For activating the new data please follow the below steps.)
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
2
NETWORK ANALYSER
MPR-53/53S
PK 26 Box Connection Diagram
+_
Max: 30 VDC
(12-48V DC)
- + - +
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
Un
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
L1
L2
L3
N
3 Phase neutral k
K l
L k
K L l k
K l
L
+_
Max: 30 VDC
L1
L2
L3
1A
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
N k
K L l k
K l
L k
K
3 Phase without neutral l
L
*Available only for MPR-53S
Note: For CT-25 models: k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.
7
+_
Max: 30 VDC
(12-48V DC)
- + - +
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
1A N
L1
L2
L3 k
K
3 Phase without neutral current input with
Aron wiring configuration l
L k
K l
L
+_
Max: 30 VDC
(12-48V DC)
- + - +
Gnd A B TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
1A
N
L1
L2 k
K
L3
3 Phase without neutral current input with
Aron wiring configuration l
L k
K L l
NETWORK ANALYSER
MPR-53/53S
PR 19 Box Connection Diagram
L1
L2
L3
N
3 Phase neutral k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
7
L1
Pul C
( 12-48V DC )
InC In1 In2
13 1415 16 17 18
Pul 1 Pul 2
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
L1
N
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
7
L1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 1415 16 17 18
6
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Voltage Measuring Input
L2
8
L3
9 10
N
Auxiliary
Supply
11 12
L1
N
L1
L2
L3 k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
7
L1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 1415 16 17 18
6
GND B A TR
Pul 1 Pul 2
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
3 Phase without neutral
*Available only for MPR-53S
Note: For CT-25 models: k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.
L1
N
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
7
L1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 1415 16 17 18
6
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Voltage Measuring Input
L2
8
L3
9
N
10 11
Auxiliary
Supply
12
L1
N
3 Phase without neutral current input with
Aron wiring configuration
6
NETWORK ANALYSER
MPR-53/53S
Pulse Menu
In this menu, three parameters can be selected :
PUL SE rAt ýo, PUL SE o-1, PUL SE o-2
PUL SE rAt : Pulse menu which is defined for how many pulses deticated for energy consumption. PUL SE rAt value can be assigned as below:
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA); 1 Mwh/MVArh/MVA.
PUL SE o-1 / PUL SE o-2: 1 Pulse is taken for respected energy consumption which assigned in PUL SE rAt. o-1 / o-2 can be assigned as below :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons, find PULSE menu.
Press SET button (PUL SE rAt ýo menu is displayed)
By using UP-DOWN buttons, select PUL SE rAt ýo,
PUL SE o-1 or PUL SE o-2.
Press SET button (1k / A-I / r-L blink)
By using UP-DOWN buttons, select required parameter.
Press SET button. (Data is entered but is not activated yet.
For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Energy Counter (Eng Cnt) Menu
MPR-53/53S has 2 energy counters :
Energy counter 1 (E-1), Energy counter 2 (E-2).
E-1 / E-2 have 4 parameters : on : Activate E-1 / E-2 counters for energy counting without depending on any parameter.
ý-1 : Activate E-1 / E-2 counters, when digital input 1 is on (=1).
ý-2 : Activate E-1 / E-2 counters, when digital input 2 is on (=1).
E-2: E-1 does not count when E-2 is activated. (Only for E-1)
E-1: E-2 does not count when E-1 is activated. (Only for E-2)
Note: Counting status is undefned if E-2 is selected on E-1 and if E-1 is selected on
E-2. When the status is defined as above, both energy counters count while digital input is not on (=1), but if either one or both digital inputs are on (=1) then counters will not count.
Press SET button for 3 seconds (trA Fo menu is displayed)
User password Setup:
In this menu user password is defined and activated.
You must define and activate a 4 digit user password for preventing device settings from the illegal usage.
There are 2 sub menus under the Pýn menu.
Changing of User Password:
This menu is used to change the user password .
Note: Factory default value for user password is
0000
To change the user password,
In the monitoring mode :
Press SET button for 3 seconds (trA Fo menu is displayed)
Bu using UP-DOWN buttons, find Pýn menu.
Press SET button (Pýn ACt IUA tE menu is displayed)
By using the UP-DOWN buttons, find Pýn CHA ngE menu.
By using UP-DOWN-SET buttons, enter the old password
By using UP-DOWN-SET buttons, enter the new password
By using UP-DOWN-SET buttons, re-enter the new password.
Press SET button, Pýn CHA ngE is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Activating the user password:
This menu is used for activating the user password.
After the user password is activated, while the instant values are observed,user password is required in order to enter to the menu. If the wrong user password is entered, user can not enter to the menu.
Note: Factory default value of user password is 0000
By using UP-DOWN buttons, find Eng Cnt menu.
Press SET button (Eng Cnt E-1 menu is displayed)
By using UP-DOWN buttons, select
Eng Cnt E-1 / Eng Cnt E-2.
Press SET button. (on blinks)
By using UP-DOWN buttons, select required parameter.
Press SET button. (Data is entered but is not activated yet.
For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
3
For activating the user password, In the monitoring mode :
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons, find Pýn menu.
Press SET button (Pýn ACt IUA tE menu is displayed.)
Press SET button (First digit blinks)
Enter the values for blinking digits by using UP-DOWN buttons, switch to other digits by using SET button use BACK button to switch to previous digit Pýn ACt oF is displayed. on can be selected by using UP / DOWN buttons. (Data is entered but is not activated yet. For activating the new data please follow below steps)
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
NETWORK ANALYSER
MPR-53/53S
Serial Communication (Available only for MPR-53S)
MPR-53S has MODBUS RTU communication protocol which is optical isolated. All measured parameters can be transfer to the computer.
Transformer ratios and communication parameters can be set, saved parameters for demand and energy values can be reset.
Parameter Settings (Available only for MPR-53S)
Address : 001-247
Baud Rate : 2400, 4800, 9600, 19200, 34800 bps
Parity : no, odd and EUEn
Press SET button for 3 seconds (trA Fo menu is displayed)
T
By using UP-DOWN buttons, find rS-485 menu.
Press SET button (Adr ESS menu is displayed)
By using UP-DOWN buttons, select Adr ESS / bAU d /
PArýty
Press SET button. (001 / 9600 / no displayed)
By using UP-DOWN buttons, select required parameter
(001...247 / 2400...38400 / no, EUEn, odd).
Press SET button, Adr ESS / bAU d / PArýty displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
MODBUS RTU PROTOCOL (Available only for MPR-53S)
Standart MODBUS RTU message is shown below.
ADDRESS
8 BIT
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247 ) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave.
CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.
Available Modbus Function:
03H READ HOLD REGISTERS
06H
10H
FUNCTION
8 BIT
DATA
NX8BIT
PRESET SINGLE REGISTER
PRESET MULTIPLE REGISTERS
CRCH CRCL T
Read Hold (03) function is used for reading measured values and set value.
If any request of reading of a register, excepted mentioned in register table, device will send an error message. For example to read phase1 voltage by sending a message to the device.
01 03 00 00 00 02 XX XX
01 Device address
03 Function
00 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
XX CRC MSB
XX CRC LSB
4
Preset Single Register (06) function is used for writting the setting values, erasing the energy counter or resetting the min., max., demand values.
Current transformers ratio can be set 0-2000, voltage transformer ratio can be set 1-40000. Min., Max. and Demand values can be only clear. If sent value is outside of this range device responds with an error message.
i.e.
Setting CT as 100;
01 06 80 02 00 64 XX XX
01 Device address
06 Function
80 MSB address
02 LSB address
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Preset Multiple Register(10H) is used to set more then one register at same time.
i.e.
Setting CT as 100, Ut as 20.0;
01 10 80 00 00 02 04 00 C8 00 64 XX XX
01 Device Address
10 Function
80 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
04 Byte count
00 Data MSB
C8 Data LSB
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Digital Inputs (Available only for MPR-53S)
Digital input are sent in 16 bit hexadecimal format as below:
55H 15
U U U U U U
MSB
U: undefined
U U U U U U U U
1
DIN2 input 2
0
DIN1 input 1
If 12-48 V AC / DC is applied to ln1 (Input 1), 0 (zero) bit of DIN register is set as 1. Otherwise, 0 (zero) bit is set as 0.
If 12-48 V AC / DC is applied to ln2 (Input 2), 1st bit of DIN register is set as 1. Otherwise, 1st bit is set as 0.
The Parameters are sent in 32bit Hexadecimal format. For Example, 230.0V
voltage will be sent as 000008FCH. Cos
0.980 Cos j j values shall be divided to 1000.
will be sent as 000003D4H. Energy values are sent in 64 bytes.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
Specifications for data cable ;
- 24 AWG or thicker
- Less than 100 ohm/ km
- Nominal characteristic impedance at 100 kHz of 100 ohms
- Less than 60 pF/m mutual capacitance (between two wires in a pair)
- Less than 120 pF/m mutual pair capacitance ( the capacitance between one wire and all others connected to earth).
- Twisted Pair
ERROR CODES (Available only for MPR-53S)
Slave device (MPR-53S) sends error message when receive any missing query.
Error codes are given below.
01 Invalid Function: If any message except given above is used, then 01 error messages will be sent.
02 Invalid Register: Error 02 will be send when a reading of a register is requested, except the registers which mentioned in table.
03 Invalid data: If any different value is been set for dedicated Transformer values and nonzero for demand value, then error message 03 will be sent.
NETWORK ANALYSER
MPR-53/53S
MPR-53S COMPUTER CONNECTION
31 DEVICES CAN BE CONNECTED AT THE SAME LINE
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
TR B A GND
...
MPR-53S-31
TR B A GND
MPR-53S-2
TR B A GND
MPR-53S-1
MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
MAX. 1200 mt.
MAX. 1200 mt.
TRB A GND
MPR-53S -247
...
REPEATER
PC
MPR-53S -31
...
MPR-53S -2 MPR-53S -1
RS485/RS232
CONVERTER
B
A
GND
PC
Dimensions
10.8
30.1
7.6
9.5
79.3mm
70mm
60.6
26.5
21.5
53.0
58.0
10.0
106.0
Type PK 26
5
96mm
Type PR 19
NETWORK ANALYSER
MPR-53/53S
MODBUS REGISTER MAP
MODBUS REGISTER MAP
ADDRESS
114
116
118
120
122
124
126
128
98
100
102
104
106
108
110
112
130
132
134
136
138
140
142
144
146
148
150
82
84
86
88
74
76
78
80
90
92
94
96
66
68
70
72
58
60
62
64
40
42
44
46
32
34
36
38
48
50
52
54
56
24
26
28
30
16
18
20
22
8
10
12
14
4
6
0
2
*Available only for MPR-53S
ADDRESS
(HEX)
0000
0002
0004
0006
0008
000A
000C
000E
0062
0064
0066
0068
006A
006C
006E
0070
0072
0074
0076
0078
007A
007C
007E
0080
0082
0084
0086
0088
008A
008C
008E
0090
0092
0094
0096
003A
003C
003E
0040
0042
0044
0046
0048
004A
004C
004E
0050
0052
0054
0056
0058
005A
005C
005E
0060
0010
0012
0014
0016
0018
001A
001C
001E
0020
0022
0024
0026
0028
002A
002C
002E
0030
0032
0034
0036
0038
REGISTER
L1 PHASE VOLTAGE
L2 PHASE VOLTAGE
L3 PHASE VOLTAGE
L1 PHASE CURRENT
L2 PHASE CURRENT
L3 PHASE CURRENT
NEUTRAL CURRENT
L1-L2 PHASE-PHASE VOLTAGE
L2-L3 PHASE-PHASE VOLTAGE
L3-L1 PHASE-PHASE VOLTAGE
L1 PHASE ACTIVE POWER
L2 PHASE ACTIVE POWER
L3 PHASE ACTIVE POWER
L1 PHASE REACTIVE POWER
L2 PHASE REACTIVE POWER
L3 PHASE REACTIVE POWER
L1 PHASE APPARENT POWER
L2 PHASE APPARENT POWER
L3 PHASE APPARENT POWER
L1 PHASE COS
L2 PHASE COS j
L3 PHASE COS j j
TOTAL IMPORT ACTIVE POWER
TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER
TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER
AVERAGE INDUCTIVE COS j
AVERAGE CAPACITIVE COS j
FREQUENCY
L1 PHASE VOLTAGE ANGLE
L2 PHASE VOLTAGE ANGLE
L3 PHASE VOLTAGE ANGLE
L1 PHASE CURRENT ANGLE
L2 PHASE CURRENT ANGLE
L3 PHASE CURRENT ANGLE
L1 PHASE VOLTAGE THD
L2 PHASE VOLTAGE THD
L3 PHASE VOLTAGE THD
L1 PHASE CURRENT THD
L2 PHASE CURRENT THD
L3 PHASE CURRENT THD
DIGITAL INPUT STATUS
IMPORT ACTIVE ENERGY-1
EXPORT ACTIVE ENERGY-1
INDUCTIVE REACTIVE ENERGY-1
CAPACITIVE REACTIVE ENERGY-1
IMPORT ACTIVE ENERGY-2
EXPORT ACTIVE ENERGY-2
INDUCTIVE REACTIVE ENERGY-2
CAPACITIVE REACTIVE ENERGY-2
L1 PHASE MIN. VOLTAGE
L2 PHASE MIN. VOLTAGE
L3 PHASE MIN. VOLTAGE
L1-L2 PHASE-PHASE MIN. VOLTAGE
L2-L3 PHASE-PHASE MIN. VOLTAGE
L3-L1 PHASE-PHASE MIN. VOLTAGE
L1 PHASE MIN. CURRENT
L2 PHASE MIN. CURRENT
L3 PHASE MIN. CURRENT
L1 PHASE MIN. ACTIVE POWER
L2 PHASE MIN. ACTIVE POWER
L3 PHASE MIN. ACTIVE POWER
L1 PHASE MIN. REACTIVE POWER
L2 PHASE MIN. REACTIVE POWER
L3 PHASE MIN. REACTIVE POWER
L1 PHASE MIN. APPARENT POWER
L2 PHASE MIN. APPARENT POWER
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R/W
R/W
R
R
R
R
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
RANGE
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(0-5000)xUT
(0-5000)xUT
(0-5000)xUT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 -18000)xCTxVT
(0 -18000)xCTxVT
(0 -18000)xCTxVT
(-1000 -1000)
(-1000 -1000)
(-1000 -1000)
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(-1000 -1000)
(-1000 -1000)
(4000 -7000)
0-360
0-360
0-360
0-360
0-360
0-360
0-999
0-999
0-999
0-999
0-999
0-999
-
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
MULTIPLIER
1
1
0.1
0.1
0.1
0.1
0.1
0.1
1
1
1
1
1
1
1
1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
-
1
1
1
1
1
1
0.01
1
1
1
1
1
1
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.001
0.001
UNIT
VArh
VArh
Volt
Volt
Volt
Volt
Volt
Volt
VArh
VArh
Wh
Wh
Wh
Wh
VArh
VArh
Amper
Amper
Amper
Watt
%
%
%
%
%
-
Wh
Wh
Hz
Degre
Degre
Degre
Degre
Degre
Degre
%
Wh
Wh
VArh
VArh
Watt
Watt
Var
Var
Var
VA
VA
Volt
Volt
Volt
Amper
Amper
Amper
Amper
Volt
VA
VA
VA
-
-
-
Watt
Watt
Volt
Volt
Watt
Watt
Watt
Var
Var
Var
Var
Var
VA
-
-
FORMAT long int long int long int long int long int long int long int long int long int long int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int
long int long int long int long int long int long int int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int int int int unsigned int int int
A4309/Rev.1
ADDRESS
226
228
230
232
234
236
238
240
210
212
214
216
218
220
222
224
242
244
246
248
250
252
254
184
186
188
190
192
194
196
198
168
170
172
174
176
178
180
182
200
202
204
206
208
152
154
156
158
160
162
164
166
ADDRESS
(HEX)
0098
009A
009C
009E
00A0
00A2
00A4
00A6
00D2
00D4
00D6
00D8
00DA
00DC
00DE
00E0
00E2
00E4
00E6
00E8
00EA
00EC
00EE
00F0
00F2
00F4
00F6
00F8
00A8
00AA
00AC
00AE
00B0
00B2
00B4
00B6
00B8
00BA
00BC
00BE
00C0
00C2
00C4
00C6
00C8
00CA
00CC
00CE
00D0
00FA
00FC
00FE
REGISTER
L3 PHASE MIN. APPARENT POWER
TOTAL MIN. IMPORT ACTIVE POWER
TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER
TOTAL MIN. EXPORT REACTIVE POWER
TOTAL MIN. APPARENT POWER
L1 PHASE MAX. VOLTAGE
L2 PHASE MAX. VOLTAGE
L3 PHASE MAX. VOLTAGE
L1-L2 PHASE-PHASE MAX. VOLTAGE
L2-L3 PHASE-PHASE MAX. VOLTAGE
L3-L1 PHASE-PHASE MAX. VOLTAGE
L1 PHASE MAX. CURRENT
L2 PHASE MAX. CURRENT
L3 PHASE MAX. CURRENT
L1 PHASE MAX. ACTIVE POWER
L2 PHASE MAX. ACTIVE POWER
L3 PHASE MAX. ACTIVE POWER
L1 PHASE MAX. REACTIVE POWER
L2 PHASE MAX. REACTIVE POWER
L3 PHASE MAX. REACTIVE POWER
L1 PHASE MAX. APPARENT POWER
L2 PHASE MAX. APPARENT POWER
L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER
TOTAL MAX. EXPORT ACTIVE POWER
TOTAL MAX. IMPORT REACTIVE POWER
TOTAL MAX. EXPORT REACTIVE POWER
TOTAL MAX. APPARENT POWER
L1 PHASE MAX. CURRENT DEMAND
L2 PHASE MAX. CURRENT DEMAND
L3 PHASE MAX. CURRENT DEMAND
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER
L2 PHASE MAX. DEMAND APPARENT POWER
L3 PHASE MAX. DEMAND APPARENT POWER
TOTAL IMPORT MAX. DEMAND ACTIVE POWER
TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER
TOTAL EXPORT MAX. DEMAND REACTIVE POWER
TOTAL MAX. DEMAND APPARENT POWER
MODBUS REGISTER MAP
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RANGE
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-5000)xUT
(0-5000)xUT
(0-5000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
ADDRESS
32768
32769
32770
32771
32772
32773
32774
32775
32776
32777
32778
32779
32780
32781
ADDRESS
(HEX)
8000
8001
8002
8003
8004
8005
8006
8007
8008
8009
800A
800B
800C
800D
REGISTER
VOLTAGE TRANSFORMER RATIO
CURRENT TRANSFORMER RATIO
CALCULATION METHOD
DEMAND TIME
PULSE RATIO
PULSE OUTPUT 1 PARAMETER SETTING
PULSE OUTPUT 2 PARAMETER SETTING
ENERGY COUNTER 1 SELECTION
ENERGY COUNTER 2 SELECTION
COMMUNICATION ADDRESS
BAUD RATE
PARITY
PASSWORD ENABLE
PASSWORD
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RANGE
0-40000
0-2000
0-5
1-60
0-6
0-5
0-5
0-3
0-3
0 - 247
1 - 5
0 - 2
0-1
0-9999
UNIT
PULSE OUTPUT 1-2
PARAMETER SETTING 0-5 :
0: Active
1: Active Import
2: Active Export
3: Reactive
4: Reactive Import
5: Reactive Export
PULSE RATIO 0-6 :
0: 1 Watt / Pulse
1: 10 Watt / Pulse
2: 100 Watt / Pulse
3: 1 kW / Pulse
4: 10 kW / Pulse
5: 100 kW / Pulse
6: 1 MW / Pulse
ENERGY COUNTER 1 SELECTION 0-3 :
0 : On (EC -Energy counter- will count on all conditions)
1: EC will count when Digital Input1 is 1 (1=active)
2: EC will count when Digital Input2 is 1 (1=active)
3: Inverse Energy Counter 2 (It will count when EC2 is not counted)
ENERGY COUNTER 2 SELECTION 0-3 :
0 : On (EC -Energy counter- will count on all conditions)
1: EC will count when Digital Input1 is 1 (1=active)
CALCULATION 0-5 :
2: EC will count when Digital Input2 is 1 (1=active)
3: Inverse Energy Counter 1 (It will count when EC1 is not counted)
Refer to Reactive Energy Calculation Method Setting on page 2.
-
-
minute
-
-
-
-
-
-
-
-
-
-
UNIT
Amper
Amper
Amper
Watt
Watt
Watt
Watt
Watt
Watt
Var
Var
Var
Var
Var
Var
VA
VA
VA
Watt
Watt
Var
Var
VA
VA
Watt
Watt
Var
Var
VA
Volt
Volt
Volt
Volt
Volt
Volt
Amper
Amper
Amper
Watt
Watt
Watt
Var
Var
Var
VA
VA
VA
Watt
Watt
Var
Var
VA
MULTIPLIER FORMAT
-
-
-
-
0.1
1
-
1
-
-
-
-
-
short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int
BAUD RATE 1-5 :
1: 38400 bps
2: 19200 bps
3: 9600 bps
4: 4800 bps
5: 2400 bps
PARITY 0-2 :
0: No
1: Odd
2: Even
PASSWORD ENABLE 0-1 :
0: Disable
1: Enable
MULTIPLIER
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
FORMAT unsigned int unsigned int unsigned int int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int unsigned int int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int