MAN0933-05-EN_599DIMx10_Datasheet Specifications / Installation
1 Specifications
Number of Inputs
Commons per Module
Input Voltage Range
Rated Input Current
Input Resistance
Isolation
ON Voltage (Current) Level
OFF Voltage (Current) Level
Response Time
Specifications
DIM510
8
DIM610
16
DIM710
32
1
24 VDC (20.4 – 28.8 VDC)
About 4mA
Approx. 5.6k
Ω
500VDC or greater
>19VDC (>3mA)
<6VDC (<1mA)
Configurable for
1/3/5/10/20/70/100mS (3mS default)
Labeled 1-8 for each input group LED indication
Backplane Power Consumed
@5V (all inputs on)
30mA 40mA 50mA
Terminal Type
Optional Spring-Clamp
Terminal Strip
Number of Terminals
Terminal Torque Rating
M2 Screw Type,
Removable
HE599
TRM010
HE599
TRM010 +
HE599
TRM008
10posn
8posn +
10 posn
0.22 to 0.25 N-m
1.95 to 2.21 in-lb
M3 Fixed
None
40-pins
1.2 N-m
10.6 in-lb
16-28AWG (copper)
7mm
Accepted Wire Size
Wire Stripping Length
Storage Temp.
General Specifications
Operating Temp.
Relative Humidity
DIM510 DIM610
-25
to 70
Celsius
DIM710
-0
to 55
Celsius
5 to 95% Non-condensing
Dimensions WxHxD
Weight
CE & UL Compliance
20mm x 90mm x 60mm
0.7
9” x 3.54” x 2.36”
40g
(1.4oz.)
52g
(1.8oz.)
60g
(2.1oz.)
CE, UL & C-UL
Class I, Div 2 Groups A, B, C & D
2 Wiring – I/O
1 2 3 4 5 6 7 8
1
2
3
4
5
6
7
8
+
+ -
C
24VDC
DIM510 Wiring
24VDC
A
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1
2
3
4
5
6
7
8
B
1
2
3
4
5
6
7
8
+
+
-
C
24VDC
GROUP A LEDs
GROUP B LEDs
DIM610 Wiring
24VDC
SmartRail
24VDC Input Modules
HE599DIM510 (8pt), HE599DIM610 (16pt), HE599DIM710 (32pt)
Positive/Negative Logic
24VDC
24VDC
GROUP A
3
4
1
2
TERMINAL
A01
B01
A02
B02
GROUP B
3
4
1
2
5
6
7
8
5
6
A03
B03
A04
B04
A05
B05
A06
B06
A07
GROUP C
GROUP D
7
8
3
4
1
2
5
4
5
2
3
6
7
8
1
6
7
8
B07
A08
B08
A09
B09
A10
B10
A11
B11
A12
B12
A18
B18
A19
B19
A20
B20
A13
B13
A14
B14
A15
B15
A16
B16
A17
B17
DIM710 Wiring (SmartLink Terminal Strip)
GROUP A
GROUP B
24VDC
4
5
6
7
8
1
2
3
6
7
4
5
8
1
2
3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
24VDC
4
5
6
7
8
1
2
3
6
7
4
5
8
1
2
3
GROUP A LEDs
GROUP B LEDs
GROUP C LEDs
GROUP D LEDs
GROUP C
GROUP D
24VDC
DIM710 Wiring
40-pin IDE Header cannot be
directly wired. SmartLink
Terminal Strip recommended
__________________________________________________________________________________________________________________________________________________________________
5/24/2019 Page 1 of 3
MAN0933-04-EN
D
C
B
2.1 Input Wring Terminals
Group Input DIM510 Terminal
8
1
2
3
4
2
3
4
5
6
7
5
6
7
8
4
5
6
7
8
1
1
2
3
A
5
6
7
8
1
2
3
4
Commons
Commons
No Connect
10posn – Terminal 1
10posn – Terminal 2
10posn – Terminal 3
10posn – Terminal 4
10posn – Terminal 5
8posn – Terminal 1
8posn – Terminal 2
8posn – Terminal 3
8posn – Terminal 4
8posn – Terminal 5
10posn – Terminal 6
10posn – Terminal 7
10posn – Terminal 8
8posn – Terminal 6
8posn – Terminal 7
8posn – Terminal 8
10posn – Terminal 9 10posn – Terminal 9
10posn – Terminal 10 10posn – Terminal 10
N/A
10posn – Terminal 1
10posn – Terminal 2
10posn – Terminal 3
10posn – Terminal 4
10posn – Terminal 5
10posn – Terminal 6
10posn – Terminal 7
10posn – Terminal 8
N/A
N/A
N/A
N/A
DIM610 Terminal
N/A
N/A
N/A
N/A
A19
A18
A17
A16
A15
A14
B09
B08
B07
B06
B05
A20
A13
A12
A11
A10
A09
A08
A07
A06
A05
A02
A01
B04
B03
A04
A03
DIM710
Pin
B20
B19
B18
B17
B16
B15
B14
B13
B02
B01
B12
B11
B10
Note: Groups A, B, C & D are share the same common
2.2 SmartLink Wiring Accessories
Note: The TRM040 accessories utilize different cables. They are high-density cables, and the pin out on the accessory side of the unit is different.
Description
SmartLink Wiring Accessories
Part Number
40pin DIN-rail mounted
Terminal Strip
HE599TRM040
40pin Cable, 0.5m
40pin Cable, 2.0m
HE599CBL040
HE599CBL240
Specifications / Installation
HE599TRM040
40-Pin Din Rail Mounted Terminal Strip for DIM710
NOTE: This product come with two labeling strips. Ensure that the Digital
Input strip is placed in the product’s display.
General Specifications
Rated Voltage
Rated Current
Withstanding voltage
Applicable cable
T/B screw
Screw torque
Ambient temperature rating
Dimensions (L x W x D)
AC, DC 125V
1A
600V
1.25mm/max
M3 x 10L
1.2N / m (12Kgf / cm)
-10°C to 50°C (non-condensing)
149mm x 40mm x 36.8mm
HE599CBL040 (Shown)
.5m Cable for Relay block TRM040 to DIM710 module
HE599CBL240
2.0m Cable for Relay block TRM040 to DIM710 module
Note: Connector with ~80° angle connector must be inserted into the
Relay block. Straight connector must be inserted into Module
_________________________________________________________________________________________________________________________________________________________________
5/24/2019 Page 2 of 3
MAN0933-05-EN_599DIMx10_Datasheet
3 Configuration DATA
The SmartRail digital input modules feature a configurable input filter, set in Cscape (9.1 or later):
Cscape Configuration Data – Selectable per Module
Parameter Selections
1ms
Input Response
3ms
5ms
10ms
20ms
70ms
100ms
Specifications / Installation
4 Installation / safety
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or
Non-hazardous locations only
WARNING - EXPLOSION HAZARD -
Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous
WARNING - EXPLOSION HAZARD -
Substitution of any component may impair suitability for Class I, Division 2
WARNING – POSSIBLE EQUIPMENT DAMAGE
Remove power from the I/O Base and any peripheral equipment connected to this local system before adding or replacing this or any module. a. All applicable codes and standards should be followed in the installation of this product.
For detailed installation and a handy checklist that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
Warning: Electrical
Shock Hazard.
Warning: Consult user documentation.
5 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279 http://www.hornerautomation.com
Email: [email protected]
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web: http://www.horner-apg.com
Email: [email protected]
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
__________________________________________________________________________________________________________________________________________________________________
5/24/2019 Page 3 of 3