PMI RDAT 220-100 Datasheet


Add to my manuals
2 Pages

advertisement

PMI RDAT 220-100 Datasheet | Manualzz

NORM ENERJI

AUTOMATION TYPE BATTERY CHARGER TECHNICAL SPECIFICATIONS

GENERAL

Model / Power

Topology 

Control 

INPUT

Input Isolation Transformer

Nominal Voltage and Tolerance

Input Wiring

Nominal Frequency

THDI

Cosφ

Input Protection

OUTPUT

Battery Charging Principle 

Rated Power

Nominal Output Voltage

Output Voltage Adjustment

Nominal Output Current

Output Current Adjustment

Static Tolerance 

Output Voltage Ripple RMS

Efficiency at full load

Boost voltage (V/C)

Float voltage (V/C)

Dynamic Response (w/out battery group)

Dynamic Response (with battery group)

Output Protection

Filtering

CONTROL ELEMENTS

Battery Test

Boost Timer

Current Limitation

RDAT 220‐100 / 22.000 W

6 Pulse / Full Bridge Phase Angle Controlled Thyristor Module Rectifier

Microprocessor Controlled System

Galvanically isolated / Primary & Secondary Earth Screened

380VAC ±15%  

3 Phase 3 Wires 

50Hz  ±5%

<35% with 6 pulse

 0.8 with 6 pulse

Thermic Magnetic Overcurrent protection via MCB and Overvoltage / Undervoltage protection

Constant Current/ Constant Voltage

22.000 W

220VDC

220VDC system between 220VDC and 300VDC

100 A

0‐100% of Nominal Output Current

<1% with 6 pulse

1% RMS AC of Output Voltage with 6 pulse

>90% 

2,4 lead acid battery 1,60 NiCd Battery (Depends on battery manufacturer recommendation)

2,23 lead acid battery 1,40 NiCd battery (Depends on battery manufacturer recommendation)

±10% of Output Voltage at 200msec (100% load change)

±2% of Output Voltage at 200msec (100% load change)

Short Circuit, NH Fuse and Overvoltage / Undervoltage protection

L‐C Filter

Automatic or manual selectable. Please refer to user manual for details

0 – 99,9 hours adjustable by 1 minute accuracy

Total output current and battery current can be adjusted separately

ALARM CONTACTS

Open or closed free alarm contacts 

Line MCB OFF / Mains Failure , Battery MCB OFF, Load MCB OFF, low battery failure, over output voltage, charger failure, over temperature, and earth fault 

DISPLAY PANEL & MEASUREMENT

Measurements

Indicators

Adjustable Parameters

Event History

LCD Display for Load Output Voltage, Rectifier Total Output  Current , Battery Output Voltage / Current and Line Voltage / Frequency

Float mode, Boost mode, Current mode, Equalize mode, Battery ending, Low battery, Battery test failure, Line MCB OFF, Fan failure, Over voltage, 

Under voltage, Over temperature, Rectifier failure, Mains ON (LED indication), Load MCB (LED indication), Battery MCB (LED indication), Earth Fault ( 

+ / ‐)

Boost charge voltage, Float charge voltage,  Low battery voltage , Battery test , Charger output current, Battery charge current, Battery automatic  boost current and float current, Auto & Manual boost selection, Manual boost time, LED test and On ‐ OFF.

Line MCB ON / OFF, Battery MCB ON / OFF, Load MCB ON / OFF, AC Line Input High / Low / Normal , Low Battery, Battery OK, Rectifier Overvoltage 

/ Undervoltage / OK, Overtemperature / Normal Temperature, Battery Test Fail / OK events are displayed on time base. Last 250 events recorded  and displayed on front panel and on PC via RS 485

On Warning Messages 2 Short ‘beep’ per 2 seconds Sound Alarm

COMMUNICATION AND PARALLELING (OPTIONAL)

Communication

Paralleling

Modbus, TCP/IP, Profibus and SNMP Communications via RS485 port  ‐ EXCLUDED

Active or Passive Load Sharing available on request ‐ EXCLUDED

LVD (OPTIONAL)

LVD

DROPPER DIODES (OPTIONAL)

Dropper Diodes

Protection of Battery from Deep Discharge via Contactor. Available on request ‐ EXCLUDED

Dropper Diodes for Float and Boost Voltage Regulations. Available on request ‐ EXCLUDED

NORM ENERJI

SAFETY & ENVIRONMENT

Circuit Breakers

Over Voltage Protection 

Electrical Interference Reduction 

Electrical Standards

Protection Level / Color 

Isolation Voltage

MTBF 

Enclosure Material 

Cooling 

Cable Entry 

Distribution

Heater & Lightning

Operating Temperature

Relative humidity 

Operating Altitude 

Noise Level 

Cabin Dimension

BATTERY CHARGER TECHNICAL SPECIFICATIONS

Input: Miniatur circuit breakers; Output: NH Fuse ; Battery: NH Fuse 

IEEE 587 4500 A, 110 Joules (standard)

FCC Part 15 Class B

EN 50091‐1 (Security) / EN 50091‐2 (EMC)

IP20 / RAL7035 as standard)

2000VAC input/chassis and output/chassis

100,000 hrs. (w/out battery group)

Mild Steel, Zinc‐phosphate coated; 100 µm electrostatic paint; 1.5 mm thickness

Forced fans

Bottom

Available on request ‐ EXCLUDED

Available on request ‐EXCLUDED

 ‐10 / +40 °C

  5 ‐ 90 %

Max. 2000 Mt.

Max. 60 db

(H)1950 (W)650 (D)700mm (For both RDAT 220‐100 & RDAT 48‐40