Below you will find brief information for Sunline 2000 BQ036, Sunline 2000 BQ048, Sunline 2000 BQ060. These YORK heat pumps are convertible single package units, designed for light commercial and commercial applications. They offer flexible installation options (roof curb, slab, etc.), a Simplicity control board, and various factory-mounted options for customized functionality. They include a 5-year parts warranty on the compressor and electric heat elements.
Advertisement
Advertisement
036-21508-005-A-0305
®
TECHNICAL GUIDE
SINGLE PACKAGE HEAT PUMP UNITS
BQ 036, 048 & 060
3, 4 & 5 NOMINAL TONS
10.0 SEER
DESCRIPTION
YORK Sunline 2000™ heat pumps are convertible single package units with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units include:
• Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
• Permanently lubricated motors
• Bottom or side air discharge configuration capability
(field convertible)
• Manufactured under the quality standards of ISO9001
• Simplicity
TM
Control Board
• Copper tube/aluminum fin coils
• Easy access to all components
• Rigging holes in base rails for lifting
• Fork lift slots on three sides
• Single point power connection
• Complete factory package - tested, charged and wired
• CSA agency listing on all units
WARRANTY
• Factory Limited Parts Warranty
• One-year parts warranty
• A Five-year parts warranty on the compressor and electric heat elements.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
2
036-21508-005-A-0305
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE
. . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 40
Fig. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . 12
2 TYPICAL FIELD POWER & CONTROL WIRING 34
3 UNIT DIMENSIONS (3 - 5 TON HEAT PUMP)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 35
5 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . 36
6 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . 36
7 DISCONNECT/BLOWER ACCESS LOCATION 37
8 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 38
9 FOUR AND SIX POINT LOADING . . . . . . . . . . . 39
10 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . 40
Tbl. #
LIST OF FIGURES
LIST OF TABLES
TABLE OF CONTENTS
Pg. #
Pg. #
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 15
2 CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . 15
3 BQ036 COOLING CAPACITIES (3 TON) . . . . . 16
4 BQ048 COOLING CAPACITIES (4 TON) . . . . . 17
5 BQ060 COOLING CAPACITIES (5 TON) . . . . . 18
6 BQ HEATING CAPACITIES . . . . . . . . . . . . . . . . 19
7 SUPPLY AIR BLOWER PERFORMANCE (3 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . 20
8 SUPPLY AIR BLOWER PERFORMANCE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . 21
9 SUPPLY AIR BLOWER PERFORMANCE (5 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . 22
10 SUPPLY AIR BLOWER PERFORMANCE (3 - 5
TON DIRECT DRIVE) - SIDE DUCT
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11 BELT DRIVE BLOWER MOTOR AND DRIVE
DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
12 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . 24
13 ELECTRIC HEATER CFM LIMITATIONS . . . . . 24
14 ELECTRICAL DATA - BQ036 & 048 DIRECT
DRIVE WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15 ELECTRICAL DATA - BQ060 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE
OUTLET 26
16 ELECTRICAL DATA - BQ036 & 048 BELT
DRIVE WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
17 ELECTRICAL DATA - BQ060 BELT DRIVE
WITHOUT POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
18 ELECTRICAL DATA - BQ036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
19 ELECTRICAL DATA - BQ060 DIRECT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . 30
20 ELECTRICAL DATA - BQ036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . 31
21 ELECTRICAL DATA - BQ060 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . 32
22 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 33
23 ELECTRIC HEAT CORRECTION FACTORS . . 33
24 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 33
25 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 37
26 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 37
27 BQ 4 POINT LOADS WEIGHT DISTRIBUTION 39
28 BQ 6 POINT LOADS WEIGHT DISTRIBUTION 39
29 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 39
30 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 39
Unitary Products Group
036-21508-005-A-0305
PRODUCT NOMENCLATURE
Product Catagory
D = Air Cond., Single Package
B = Heat Pump, Single Package
3-5 Ton Sunline Model Number Nomenclature
B Q 048 C00 A 2 A AA 1
Product Generation
1 = First Generation
2 = Second Generation
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Nominal Cooling
Capacity - MBH
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
Additional Options
(See Next Page)
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Unitary Products Group 3
036-21508-005-A-0305
4
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Standard Cabinet
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AJ SS Drain Pan
AK SS Drain Pan & Phase Monitor
AL SS Drain Pan & Coil Guard
AM SS Drain Pan & Dirty Filter Switch
AN SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
AS Bottom Drain Connection
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CS CPC Controller, DFS, APS, SS Drain Pan
CT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Unitary Products Group
036-21508-005-A-0305
Standard Cabinet
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JS Johnson UNT Controller, DFS, APS, SS Drain Pan
JT Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
JU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
JV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
JW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
JX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
HS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
HT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
HU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
HV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
HW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
HX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
NT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
NU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
NV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
NW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
NX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
Unitary Products Group 5
6
036-21508-005-A-0305
Standard Cabinet
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
T1 Technicoat Condenser & SS Drain Pan
T3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T4 Technicoat Evaporator & SS Drain Pan
T6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
T7 Technicoat Evaporator & Condenser Coils & SS Drain Pan
T9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
LA Simplicity Intelli-Comfort Controller
LB Simplicity Intelli-Comfort Controller, & Phase Monitor
LC Simplicity Intelli-Comfort Controller, & Coil Guard
LD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
LE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
LF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
LG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
LH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
LJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
LK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
LL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
LM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
LN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
LP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
LQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
LR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
LS Simplicity Intelli-Comfort Controller, SS Drain Pan
LT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
LU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
LV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
LW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
LX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
WA Intelli-Comfort w/Mod Link Controller
WB Intelli-Comfort w/Mod Link Controller, & Phase Monitor
WC Intelli-Comfort w/Mod Link Controller, & Coil Guard
WD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
WE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil
Unitary Products Group
036-21508-005-A-0305
Standard Cabinet
WF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
WG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
WH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
WJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
WK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
WL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
WM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
WN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
WP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
WQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
WR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
WS Intelli-Comfort w/Mod Link Controller, SS Drain Pan
WT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
WU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
WV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
WW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
WX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Hinged Filter Door & Toolless Access Cabinet
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BJ SS Drain Pan & Hinged Filter Door & Toolless Access Panels
BK SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
BL SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
BM SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BN SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BS Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DS CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
DT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
DU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
DV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
DW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Unitary Products Group 7
8
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
DX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
ES Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
ET Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
EU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
EV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
EW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
EX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
GS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
GT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
GU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
GV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
GW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
GX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Unitary Products Group 9
036-21508-005-A-0305
Hinged Filter Door & Toolless Access Cabinet
QD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
QF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
QJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
QK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
QN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
QP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
QQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
QR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
QS Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
QT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
QU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
QV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
QW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
QX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
10 Unitary Products Group
036-21508-005-A-0305
FEATURES
All models are available with a wide variety of factorymounted options such as electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guards to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor air damper options:
• Single enthalpy economizer
• Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components.
• Simplicity ™ Controls - Simplicity ™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
• Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
• Nuisance Trip Protection - To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.
• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time.
Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
• Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty
• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
• BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as SImplicity ™
INTELLI-Comfort™, Novar, Honeywell, Johnson, and
CPC.
Unitary Products Group 11
036-21508-005-A-0305
FIGURE 1 UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1
TM
processes. Coating is applied by total immersion of the complete coil for maximum protection.
• ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
• FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.
• CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
• DISCONNECT SWITCH - For heat pump units with electric heat, an HACR breaker sized to the unit is provided.
For heat pump units without electric heat, a switch sized to the largest electric heat available for the particular unit is provided. Factory-installed option only.
• BAS - Building Automation System Controls
Simplicity ™ INTELLI-Comfort™ CONTROL - The
York® Simplicity ™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
12 Unitary Products Group
036-21508-005-A-0305
Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity ™
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.
• Simplicity ™ INTELLI-Comfort™ with MOD LINK CON-
TROL The York® Simplicity ™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
• Novar® BAS CONTROL The Novar® ETC-3 building automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
• JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
• CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
• HONEYWELL BAS CONTROL The Honeywell
W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
• STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
• BOTTOM DRAIN CONNECTION An optional bottom drain connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines.
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
NOTE: Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
Unitary Products Group 13
036-21508-005-A-0305
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
• BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
• CO
2
SENSOR - Senses CO
2
levels and automatically overrides the economizer when levels rise above the present limits.
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
• HAIL GUARD - Hail guard is available to protect the unit from hail damage. This is a sloped hood that fits above the coil.
14 Unitary Products Group
036-21508-005-A-0305
TABLE 1: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP
IWG
BLOWER
SPEED KW 63 125
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
250 500 1,000 2,000 4,000 8,000
SWL dB(A)
036
048
060
1,200
1,600
2,000
0.6
0.55
0.45
LOW
HIGH
HIGH
0.60
0.80
1.00
84
85
86
84
85
86
74
75
76
67
68
69
69
70
71
62
63
64
57
58
59
52
53
54
74
75
76
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
dB(A)
@
10Ft.
2
41
42
43
TABLE 2: CAPACITY RATINGS
ARI RATINGS
1
UNIT SIZE
(MBH)
COOLING PERFORMANCE
SOUND
RATING
2 bels
HSPF
MBH SEER EER MBH
036
048
39
48
10.00
10.20
9.20
9.25
8.6
8.6
7.3
6 .
7
7.0
39.0
48.0
060 59 10.00
9.20
8.4
59.0
NOTES:
1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2. Rated in accordance with ARI Standard 270.
47°F
HEATING CAPACITY
COP
3.0
3.0
3.0
MBH
23.0
26.4
36.0
17°F
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input
in watt-hoursduring the same period.
EER = Energy Efficiency Ratio-the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in
BTUH per watt (BTUH/watt).
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance
(BTU’s per hour) divided by the total electric input (watts) x 3.412.
HSPF = Heating Seasonal Performance Factor - the total heating output during a normal annual usage period for heating divided by the total electric power input during
the same period. (Based on Region IV minimum design heating requirement).
COP
2.1
2.0
2.1
Unitary Products Group 15
036-21508-005-A-0305
TABLE 3: BQ036 COOLING CAPACITIES (3 TON)
AIR ON
EVAPORATOR
COIL
CFM
1750
1500
1400
1200
1050
900
WB °F
67
62
57
72
67
62
57
72
67
62
57
67
62
57
72
67
62
57
72
72
67
62
57
72
TOTAL
CAP.
1
MBH
41
38
37
45
41
36
36
45
39
35
35
44
40
40
47
45
41
41
48
51
46
42
42
49
POWER
INPUT
2
kW
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.2
3.2
3.4
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.4
3.4
3.3
3.3
3.4
86
36
38
37
28
34
36
36
26
31
35
35
39
40
40
31
39
41
41
33
37
40
42
42
35
83
32
37
37
25
30
35
36
24
28
34
35
36
39
40
27
37
41
41
29
32
40
42
42
30
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
29
36
36
22
27
33
34
20
25
32
32
32
38
39
24
33
40
41
24
28
36
41
42
26
77
25
32
33
19
24
30
31
17
22
29
30
28
34
35
20
29
37
38
20
24
31
39
40
22
74
22
29
30
16
20
27
28
15
19
25
26
23
30
31
16
24
32
34
16
19
26
34
35
18
71
18
25
26
-
17
24
25
-
17
23
24
20
26
27
-
20
28
29
-
-
21
29
30
-
68
14
21
22
-
14
21
22
-
14
20
21
15
22
23
-
15
24
25
-
-
16
24
25
-
47
44
38
37
46
42
37
36
45
41
36
36
44
39
35
35
42
38
34
33
40
35
32
31
3.6
3.6
3.5
3.6
3.6
3.5
3.5
3.6
3.6
3.5
3.5
3.7
3.6
3.6
3.7
3.7
3.6
3.5
3.7
3.7
3.7
3.6
3.6
3.7
86
34
35
35
26
31
34
33
23
27
32
31
36
36
36
29
36
37
36
30
34
38
38
37
32
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
30
34
35
23
27
33
33
21
25
30
31
33
35
36
25
34
37
36
27
29
38
38
37
28
80
27
33
34
20
25
31
31
17
22
28
28
29
34
35
22
30
36
36
22
25
34
37
37
24
77
23
29
31
17
22
28
28
15
19
25
26
26
30
31
18
27
33
33
18
22
29
35
35
20
74
20
26
28
14
18
25
25
13
17
22
23
21
27
27
14
22
28
29
15
17
24
30
30
16
71
17
23
24
-
15
22
22
-
15
20
21
18
23
24
-
18
25
25
-
-
20
26
26
-
AIR ON
EVAPORATOR
COIL
TOTAL
CAP.
1
MBH
32
31
40
34
33
32
41
35
34
34
42
37
44
40
35
35
43
38
30
30
38
32
29
29
POWER
INPUT
2
kW
105°F
TEMPERATURE OF AIR ON CONDENSER COIL
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
1
MBH
30
29
35
31
32
32
37
32
33
32
39
34
42
36
34
33
41
35
29
28
34
29
27
26
POWER
INPUT
2
kW
115°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
CFM
1750
1500
1400
1200
1050
900
WB °F
62
57
72
67
62
57
72
67
62
57
72
67
72
67
62
57
72
67
62
57
72
67
62
57
3.9
3.8
4.0
3.9
3.9
3.8
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.8
3.8
3.9
3.9
3.8
3.8
86
32
31
24
28
33
32
27
30
34
34
28
32
31
34
35
35
30
32
30
30
21
25
29
29
83
31
31
22
24
32
32
23
27
34
34
25
30
27
34
35
35
26
31
29
30
20
22
27
29
80
30
31
19
22
31
31
20
24
33
34
21
26
24
31
34
35
22
27
27
28
16
20
25
26
77
26
27
16
19
28
28
17
21
30
31
17
23
20
26
32
33
19
24
25
25
14
18
23
24
74
24
25
14
16
24
24
13
18
26
28
14
19
16
22
28
29
15
20
22
23
12
15
20
21
71
21
21
-
14
21
21
-
15
23
24
-
16
-
18
24
25
-
16
20
20
-
13
18
19
68
17
18
-
11
18
18
-
11
19
20
-
12
-
13
20
20
-
12
17
18
-
11
16
17
4.1
4.0
4.2
4.1
4.1
4.0
4.1
4.0
4.2
4.1
4.1
4.1
4.2
4.1
4.1
4.1
4.2
4.1
4.0
4.0
4.1
4.0
4.0
4.0
86
30
29
21
25
32
32
24
28
33
32
26
30
30
31
34
33
29
30
29
28
19
23
27
26
83
29
29
19
22
31
32
21
24
33
32
23
27
26
31
34
33
25
28
28
28
18
20
25
26
80
28
29
17
20
30
31
18
22
32
32
19
24
23
28
33
33
21
25
26
26
15
18
24
23
77
25
25
14
18
27
28
15
19
29
29
16
21
19
24
31
31
18
22
24
24
12
16
21
22
74
22
23
12
15
24
24
12
17
25
26
13
17
15
20
27
27
15
18
21
21
11
14
18
19
71
19
20
-
12
20
21
-
14
22
22
-
15
-
16
23
23
-
15
19
19
-
12
17
17
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
16
17
-
10
17
18
-
10
19
19
-
11
-
12
19
19
-
11
16
17
-
10
15
15
NOMINAL RATING
68
13
19
20
-
12
19
20
-
12
17
18
13
19
20
-
14
21
21
-
-
15
21
22
-
16 Unitary Products Group
036-21508-005-A-0305
TABLE 4: BQ048 COOLING CAPACITIES (4 TON)
AIR ON
EVAPORATOR
COIL
CFM
2000
1800
1600
1400
1200
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
TOTAL
CAP.
1
MBH
53
51
47
47
52
49
46
45
50
47
44
44
55
52
48
48
56
53
49
49
POWER
INPUT
2
kW
4.0
4.0
3.9
3.9
4.0
3.9
3.8
3.8
3.9
3.9
3.8
3.7
4.0
4.0
3.9
3.9
4.1
4.0
4.0
3.9
86
37
46
47
47
34
42
46
45
31
38
44
44
40
47
48
48
42
48
49
49
83
33
42
47
47
30
38
45
45
27
35
42
43
35
44
48
48
36
47
49
49
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
28
37
46
47
26
34
42
43
24
31
39
39
30
39
47
48
31
41
48
49
77
24
33
41
42
22
30
38
39
20
28
35
36
25
34
43
43
26
36
44
44
74
-
28
37
38
-
26
34
35
-
24
32
32
-
29
38
38
-
30
38
38
71
-
24
32
33
-
22
30
31
-
21
28
29
-
24
33
33
-
25
33
33
68
-
-
28
29
-
-
26
27
-
-
25
25
-
-
28
28
-
-
28
28
53
51
46
46
53
51
47
45
52
50
45
44
49
47
43
42
47
45
40
40
4.4
4.3
4.2
4.1
4.3
4.2
4.1
4.1
4.2
4.2
4.1
4.0
4.4
4.4
4.3
4.2
4.5
4.4
4.3
4.3
86
36
44
45
44
33
42
43
42
29
37
40
40
38
44
47
45
40
46
46
46
80
27
38
44
44
25
34
40
40
22
30
36
36
28
39
45
45
29
41
45
46
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
32
43
45
44
29
38
42
42
25
34
39
39
33
44
47
45
35
45
46
46
77
23
34
40
40
21
30
36
36
18
27
32
32
23
34
40
40
24
35
41
41
74
-
29
36
36
-
26
32
32
-
23
29
29
-
29
36
35
-
30
35
35
71
-
25
31
31
-
22
28
28
-
20
25
25
-
24
31
30
-
24
30
30
AIR ON
EVAPORATOR
CFM
2000
1800
1600
1400
1200
COIL
WB °F
67
62
57
72
67
62
57
62
57
72
67
72
67
62
57
72
67
62
57
72
TOTAL
CAP.
1
MBH
42
39
39
44
40
38
37
42
42
49
44
51
46
43
43
50
45
41
41
47
POWER
INPUT
2
kW
4.9
4.7
4.6
4.6
4.8
4.7
4.6
4.5
4.8
4.6
4.5
4.4
4.7
4.5
4.4
4.4
4.6
4.5
4.4
4.3
86
40
42
43
43
38
41
42
42
35
40
41
41
32
38
39
39
28
36
38
37
105°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
35
42
43
43
33
41
42
42
31
40
41
41
28
36
38
39
25
32
36
37
80
40
41
24
32
37
37
21
41
42
26
35
29
39
42
43
28
37
29
34
34
TEMPERATURE OF AIR ON CONDENSER COIL
77
35
36
20
28
33
33
18
37
37
22
31
24
34
37
38
23
32
25
29
30
74
32
32
-
24
28
29
-
32
33
-
26
-
28
32
32
-
27
22
27
27
71
27
28
-
20
25
25
-
27
27
-
22
-
23
27
28
-
22
18
22
23
68
23
23
-
-
20
21
-
22
23
-
-
21
22
-
-
-
-
-
20
20
TOTAL
CAP.
1
MBH
37
37
44
37
36
36
42
39
38
46
39
49
41
40
40
47
40
36
35
35
POWER
INPUT
2
4.7
4.7
5.0
4.8
4.7
4.6
4.9
4.8
4.7
5.1
4.9
5.2
5.0
4.9
4.8
5.1
4.9
4.7
4.6
4.6
kW
86
37
37
31
36
36
36
28
39
38
34
36
39
40
40
40
37
37
34
35
35
115°F
83
34
35
36
24
31
34
35
39
38
29
36
34
40
40
40
32
36
37
37
27
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
80
30
34
34
21
27
30
31
37
38
25
32
29
37
39
40
27
35
36
37
23
77
26
30
31
17
24
28
29
74
21
26
26
-
20
24
24
29
30
-
23
-
26
29
30
-
25
28
28
-
34
33
20
28
23
32
34
34
22
30
33
34
19
1
71
17
22
23
-
17
20
21
24
25
-
19
-
21
23
24
-
20
24
25
-
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
-
18
19
-
-
17
18
19
20
-
-
18
19
-
-
-
-
19
20
-
NOMINAL RATING
68
-
-
27
27
-
-
24
24
-
-
22
22
-
-
26
25
-
-
24
24
Unitary Products Group 17
036-21508-005-A-0305
TABLE 5: BQ060 COOLING CAPACITIES (5 TON)
AIR ON
EVAPORATOR
COIL
CFM
2500
2250
2000
1750
1500
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
TOTAL
CAP.
1
MBH
66
63
59
58
64
61
57
57
62
59
55
55
67
64
60
59
68
65
61
60
POWER
INPUT
2
kW
5.6
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.3
5.6
5.6
5.5
5.5
5.7
5.6
5.6
5.5
86
45
56
59
58
42
52
57
57
38
48
55
55
48
57
60
59
51
58
61
60
83
40
51
59
58
37
47
56
57
34
43
52
54
42
54
60
59
44
56
61
60
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
80
34
45
55
57
32
42
51
53
30
39
47
49
36
48
57
58
38
50
59
59
77
29
40
50
52
27
37
46
48
25
35
43
45
30
42
51
52
31
43
53
53
74
-
35
44
46
-
33
41
44
-
31
39
41
-
36
45
46
-
37
46
47
71
-
29
39
41
-
28
37
39
-
26
35
37
-
30
39
40
-
30
39
40
68
-
-
33
36
-
-
32
34
-
-
30
32
-
-
33
34
-
-
33
33
67
64
59
58
66
63
57
57
65
61
56
56
62
59
54
54
60
57
52
52
5.9
5.9
5.8
5.7
5.9
5.8
5.7
5.7
5.8
5.8
5.7
5.6
5.9
5.9
5.8
5.8
6.0
5.9
5.9
5.8
86
45
55
56
56
43
53
54
54
41
51
52
52
48
55
57
57
51
56
59
58
80
34
45
54
55
33
44
52
53
32
42
50
51
36
48
55
56
38
50
57
57
95°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
40
51
56
56
38
48
54
54
36
46
52
52
42
54
57
57
45
56
59
58
77
29
40
49
50
28
39
48
49
28
38
46
47
30
42
50
50
31
43
50
51
74
-
34
44
44
-
34
43
43
-
34
42
42
-
35
44
45
-
37
44
44
71
-
29
38
39
-
29
38
39
-
29
38
39
-
29
38
39
-
30
38
39
AIR ON
EVAPORATOR
CFM
2500
2250
2000
1750
1500
COIL
WB °F
67
62
57
72
67
62
57
62
57
72
67
72
67
62
57
72
67
62
57
72
TOTAL
CAP.
1
MBH
55
50
50
57
53
48
48
53
53
62
57
64
59
54
54
63
58
52
52
60
POWER
INPUT
2
kW
6.0
5.9
5.9
5.8
5.9
5.9
5.8
5.8
5.9
5.9
5.8
5.7
5.9
5.8
5.7
5.7
5.8
5.8
5.7
5.6
86
51
51
54
54
48
51
53
53
45
51
52
52
41
48
50
50
38
47
48
48
105°F
SENSIBLE CAPACITY
1
ENTERING DRY BULB, °F
83
44
51
54
54
42
51
53
53
39
49
52
52
37
46
50
50
34
43
48
48
80
51
51
32
41
48
48
30
52
52
34
44
38
49
51
52
36
46
38
45
45
TEMPERATURE OF AIR ON CONDENSER COIL
77
46
46
27
36
43
43
25
46
46
28
38
31
42
46
46
30
40
34
41
41
74
40
40
-
31
39
39
-
40
41
-
33
-
36
40
41
-
34
30
37
38
71
35
36
-
26
34
34
-
34
35
-
27
-
29
33
33
-
28
26
32
32
68
30
31
-
-
29
30
-
28
27
-
-
26
26
-
-
-
-
-
28
28
TOTAL
CAP.
1
MBH
48
47
56
51
46
45
53
49
49
59
53
60
54
49
49
60
54
48
44
43
POWER
INPUT
2
6.4
6.4
6.7
6.5
6.4
6.3
6.6
6.5
6.4
6.8
6.5
6.9
6.6
6.5
6.5
6.8
6.6
6.4
6.3
6.2
kW
86
48
47
40
43
46
45
36
49
49
44
45
50
54
49
49
47
47
41
44
43
115°F
83
43
46
45
31
39
44
43
49
49
38
45
43
53
49
49
41
47
48
47
35
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
80
38
43
43
27
35
39
40
47
48
33
42
37
47
48
49
35
45
46
46
30
77
33
38
38
23
30
35
36
74
29
33
33
-
26
30
30
36
37
-
31
-
34
35
35
-
32
36
36
-
42
43
27
36
30
41
42
43
29
39
42
43
25
1
71
24
28
28
-
22
26
26
30
31
-
26
-
27
28
28
-
26
31
32
-
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.35kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
68
-
24
25
-
-
22
23
24
25
-
-
22
23
-
-
-
-
25
25
-
NOMINAL RATING
68
-
-
33
34
-
-
33
34
-
-
34
35
-
-
32
33
-
-
31
32
18 Unitary Products Group
036-21508-005-A-0305
TABLE 6: BQ HEATING CAPACITIES
Model Tonnage
3
4
5
CFM
1750
1400
1200
1050
2000
1600
1200
2500
2000
1500
RET. AIR °F
55
70
80
55
70
80
55
55
70
80
55
70
80
70
80
55
70
80
55
70
80
55
70
55
70
80
80
55
70
80
CAP
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
& KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
3.3
18.2
5
17.5
5.2
16.1
5.4
18
4.7
3.3
11.6
3.4
10.7
3.5
10.9
3.1
10.5
3.2
9.6
17.3
4.9
15.9
5.1
16.2
4.5
15.6
4.7
14.4
4.9
12.3
3.4
11.8
3.5
10.9
3.6
12.1
10.8
2.9
9.9
2.9
11.2
2.6
10.2
2.8
9.3
2.8
-10
13.1
2.9
11.9
3
10.9
3.1
12.4
2.7
11.4
2.9
10.4
3
11.8
2.7
3.4
24.7
5.1
23.7
5.3
21.8
5.6
24.4
4.8
3.4
16.3
3.5
15
3.6
15.3
3.2
14.7
3.3
13.5
23.5
5
21.6
5.3
22
4.6
21.2
4.8
19.5
5
17.3
3.5
16.6
3.6
15.3
3.7
17
13.5
3
12.4
3.1
14.1
2.7
12.8
2.9
11.7
3
0
16.4
3
15
3.1
13.6
3.2
15.5
2.9
14.1
3
13.1
3.1
14.8
2.8
OUTDOOR AIR TEMPERATURE, °F (72% RH)
3.5
31.1
5.2
29.9
5.4
27.5
5.7
30.8
4.9
3.5
21.2
3.6
19.5
3.8
19.9
3.3
19.1
3.4
17.6
29.6
5.1
27.2
5.4
27.8
4.7
26.7
4.9
24.6
5.1
22.5
3.6
21.6
3.8
19.9
4
22
19.4
3.1
17.8
3.2
20.3
2.9
18.5
3
16.7
3.1
10
23.5
3.2
21.5
3.4
19.6
3.4
22.5
3
20.3
3.2
18
3.2
21.3
3
3.6
38.4
5.3
37
5.5
34
5.8
38.1
5
3.6
26.6
3.7
24.5
3.9
24.9
3.4
24
3.5
22
36.6
5.2
33.7
5.5
34.3
4.8
33
5
30.4
5.2
28.2
3.6
27.1
3.8
24.9
4
27.7
24
3.3
22
3.4
25.2
3
22.8
3.2
20.7
3.3
20
29.1
3.3
26.7
3.4
24.3
3.5
27.7
3.1
25.2
3.3
23.2
3.4
26.5
3.1
3.8
45.6
5.3
43.9
5.6
40.4
5.9
45
5.3
3.6
33.2
3.8
30.5
4
31.7
3.5
30.5
3.6
28.1
43.3
5.5
39.8
5.8
41.4
5
39.8
5.2
36.6
5.5
36.3
3.8
34.9
4
32.1
4.1
34.5
24.9
3.4
22.9
3.5
26.1
3.3
23.6
3.3
21.5
3.4
30
30.2
3.5
27.7
3.6
25.2
3.8
28.7
3.3
26.1
3.5
24.2
3.6
27.5
3.3
4
55.4
5.6
53.3
5.9
49
6
54.7
5.5
3.8
40.7
4
37.4
4.2
38.9
3.7
37.4
3.8
34.4
52.6
5.8
48.4
6.1
50.2
5.3
48.3
5.5
44.5
5.8
44.5
4
42.8
4.2
39.4
4.4
42.3
34.4
3.6
31.5
3.7
35.9
3.3
32.7
3.5
29.8
3.6
40
41.7
3.7
38.2
3.8
34.8
3.9
39.6
3.5
36.1
3.7
33.3
3.8
37.8
3.4
4.6
64.7
5.9
62.2
6.2
57.2
6.5
63.9
5.8
4.4
49.2
4.6
45.3
4.8
47
4.2
45.2
4.4
41.6
61.4
6.1
56.5
6.4
58.7
5.5
56.4
5.8
51.9
6.1
53.8
4.6
51.7
4.8
47.6
5
51.2
38.8
3.7
35.6
3.8
40.6
3.5
36.9
3.6
33.6
3.7
50
47
3.8
43.1
3.9
39.3
4.1
44.7
3.6
40.7
3.8
37.6
3.9
42.7
3.5
5.2
75.6
6.5
72.7
6.8
66.9
7.2
74.7
6.4
5
56.3
5.2
51.8
5.4
53.8
4.8
51.7
5
47.6
71.8
6.7
66.1
7
68.6
6.1
66
6.4
60.7
6.7
61.6
5.2
59.2
5.4
54.5
5.7
58.6
39.7
3.8
36.5
3.9
41.6
3.5
37.8
3.7
34.4
3.8
60
48.2
3.9
44.1
4.1
40.2
4.2
45.8
3.7
41.6
3.9
38.5
4
43.7
3.6
Unitary Products Group 19
036-21508-005-A-0305
TABLE 7: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
AIR
FLOW
CFM
3
1 , 2
2000
1900
1800
1700
1600
1500
1400
1300
1200
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
-
-
-
-
-
817
790
-
775
700
-
-
-
-
-
-
854
828
802
-
-
-
-
-
850
760
670
-
-
-
-
-
893
867
840
818
-
-
-
-
920
840
745
665
-
-
-
-
930
906
881
858
842
833
-
-
995
905
815
740
695
650
-
-
970
944
920
898
882
867
858
847
1065
980
900
820
755
705
665
640
1008
985
961
940
922
904
893
880
1125
1040
970
890
835
765
725
680
1046
1025
1001
980
962
942
932
916
1170
1100
1030
950
895
820
785
730
UNIT
TONNAGE
3
1
,
2
2000
1900
1800
1700
1600
1500
1400
1300
AIR
FLOW
CFM
0.90
1.00
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
1.40
1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1103
1085
1270
1210
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1064
1040
1020
1003
982
970
1145
1075
1005
945
880
835
1102
1081
1060
1044
1024
1010
1180
1115
1050
995
920
870
-
1121
1100
1086
1067
1053
-
1140
1085
1035
965
920
-
-
-
-
1107
1099
-
-
-
-
1000
960
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1200 953 780 992 815 1034 855 1080 905 -
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
-
20 Unitary Products Group
036-21508-005-A-0305
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
AIR
FLOW
CFM
4
1 , 2
2000
1900
1800
1700
1600
1500
1400
1300
1200
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
-
-
-
-
-
817
790
-
775
700
-
-
-
-
-
-
854
828
802
-
-
-
-
-
850
760
670
-
-
-
-
-
893
867
840
818
-
-
-
-
920
840
745
665
-
-
-
-
930
906
881
858
842
833
-
-
995
905
815
740
695
650
-
-
970
944
920
898
882
867
858
847
1065
980
900
820
755
705
665
640
1008
985
961
940
922
904
893
880
1125
1040
970
890
835
765
725
680
1046
1025
1001
980
962
942
932
916
1170
1100
1030
950
895
820
785
730
UNIT
TONNAGE
4
1
,
2
2000
1900
1800
1700
1600
1500
1400
1300
1200
AIR
FLOW
CFM
0.90
1.00
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
1.40
1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1103
1085
1270
1210
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1064
1040
1020
1003
982
970
1145
1075
1005
945
880
835
1102
1081
1060
1044
1024
1010
1180
1115
1050
995
920
870
-
1121
1100
1086
1067
1053
-
1140
1085
1035
965
920
-
-
-
-
1107
1099
-
-
-
-
1000
960
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
953 780 992 815 1034 855 1080 905 -
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group 21
036-21508-005-A-0305
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
AIR
FLOW
CFM
5
1 , 2
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
0.20
0.30
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.40
0.50
0.60
0.70
0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
1032
1005
980
930
877
-
-
-
-
-
1405
1260
1160
1060
950
-
-
-
-
-
1054
1024
1002
957
908
-
-
-
-
-
1470
1275
1170
1070
975
-
-
-
-
-
1074
1049
1022
983
941
894
855
-
-
-
1525
1370
1190
1080
1000
885
815
-
-
-
1094
1069
1044
1010
976
940
903
884
864
-
1560
1440
1250
1100
1020
940
860
815
770
-
1116
1090
1066
1039
1009
980
950
925
908
882
1595
1475
1350
1160
1050
980
905
850
805
740
1140
1116
1090
1064
1040
1014
988
964
948
926
1620
1505
1410
1260
1100
1020
940
880
835
780
1167
1142
1117
1092
1070
1047
1022
1001
987
965
910
870
830
1640
1535
1440
1340
1225
1095
970
UNIT
TONNAGE
5
1
,
2
AIR
FLOW
CFM
0.90
1.00
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
1.10
1.20
1.30
1.40
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
1.50
1100
1079
1058
1035
1020
1004
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
-
1193
1170
1148
1121
1665
1580
1480
1385
-
1202
1180
1155
-
1620
1530
1425
-
-
-
1190
-
-
-
1475
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1285
1180
1060
960
900
860
1133
1110
1090
1071
1056
1038
1340
1240
1135
1030
965
880
1169
1143
1122
1103
1088
1070
1385
1280
1190
1100
1035
925
1205
1178
1158
1134
1118
1101
1445
1330
1240
1140
1065
980
-
1222
1196
1164
1145
1130
-
1375
1295
1175
1105
1045
-
-
-
1197
1170
1158
-
-
-
1205
1130
1075
-
-
-
-
1198
1184
-
-
-
-
1150
1110
22 Unitary Products Group
036-21508-005-A-0305
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
4
5
1
1
1
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
CFM
-
0.20
WATTS
-
1660
1470
-
1810
1635
-
2390
2270
850
750
-
910
810
-
1350
1320
CFM
-
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.30
0.40
0.50
WATTS
-
CFM
-
WATTS
-
CFM
1720
WATTS
825
1630
1440
-
1780
1610
-
2350
2230
820
725
-
880
780
-
1300
1270
1590
1410
2000
1740
1580
2500
2300
2190
780
700
1010
850
760
1400
1255
1220
1550
1370
1950
1700
1555
2420
2245
2145
750
675
975
825
740
1350
1210
1170
UNIT
TONNAGE
3
1
4
1
5
1
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
CFM
1600
1450
1290
1840
1620
1510
2260
2130
2030
0.70
WATTS
765
690
625
910
775
715
1250
1120
1070
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.80
0.90
CFM
1540
1400
1250
1770
1560
1460
2160
2065
1960
WATTS
735
665
610
825
740
690
1190
1075
1020
CFM
1490
1360
1220
1660
1480
1400
2060
1990
1890
WATTS
700
650
600
825
700
660
1135
1030
970
CFM
1380
1270
1130
1530
1390
1300
1925
1900
1810
1.00
WATTS
670
610
560
775
660
615
1065
970
920
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values .
CFM
1665
0.60
WATTS
795
1500
1330
1905
1665
1540
2340
2190
2090
720
650
945
800
730
1300
1165
1110
TABLE 11: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
3 TON
4 TON
5 TON
BLOWER
RANGE
(RPM)
790/1120
790/1120
850/1220
MOTOR
1
HP
1 1/2
1 1/2
1 1/2
FRAME
56
56
56
ADJUSTABLE MOTOR PULLEY
DESIG-
NATION
1VL40
1VL40
1VL40
OUTSIDE
DIA.
(IN.)
2.7-3.7
2.7-3.7
2.7-3.7
PITCH
DIA.
(IN.)
2.4-3.4
2.4-3.4
2.4-3.4
BORE
(IN.)
5/8
5/8
5/8
DESIG-
NATION
AK61
AK61
AK56
FIXED BLOWER PULLEY
OUTSIDE
DIA.
(IN.)
5.9
5.9
5.4
PITCH
DIA.
(IN.)
5.7
5.7
5.2
BORE
(IN.)
1
1
1
DESIG-
NATION
A36
A36
A36
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
37.3
37.3
37.3
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.
QTY.
1
1
1
Unitary Products Group 23
036-21508-005-A-0305
TABLE 12: STATIC RESISTANCES
DESCRIPTION
ECONOMIZER
1, 2
ELECTRIC
HEATERS
1
5-15KW
20-30KW
BOTTOM DUCT CONNECTIONS
1
1000
0.07
0.04
0.06
0.06
1200
0.08
0.05
0.07
0.07
1400
0.09
0.06
0.08
0.08
1600
RESISTANCE, IWG
CFM
1800 2000
0.11
0.07
0.09
0.09
0.13
0.08
0.11
0.10
0.15
0.10
0.13
0.11
2200
0.17
0.12
0.15
0.12
2400
0.20
0.14
0.17
0.14
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
2600
0.23
0.16
0.20
0.16
TABLE 13: ELECTRIC HEATER CFM LIMITATIONS
UNIT MODEL SIZE NOMINAL
TONS
3
4
5
VOLTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
5
1100
1100
-
-
1300
1300
-
-
1600
1600
-
-
7
1100
1100
1100
-
1300
1300
1300
-
1600
1600
1600
-
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
10
1200
1200
1200
1200
1300
1300
1300
1300
1600
1600
1600
1600
15
1200
1200
1200
1200
1300
1300
1300
1300
1600
1600
1600
1600
20
1300
1300
1300
1300
1300
1300
1300
1400
1600
1600
1600
1600
-
-
-
-
30
-
-
-
-
1600
1600
1600
1800
24 Unitary Products Group
036-21508-005-A-0305
TABLE 14: ELECTRICAL DATA - BQ036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
19.0
19.0
11.9
11.9
5.9
4.8
25.0
25.0
14.7
14.7
7.7
6.4
105
105
85
85
42
34
105
105
130
130
64
52
1.7
1.7
1.7
1.7
1.0
1
2.3
2.3
2.3
2.3
1.3
1.3
4.4
4.4
4.4
4.4
2.2
2.2
5.0
5.0
5.0
5.0
2.2
2.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
15
25
35
40
15
25
30
35
45
70
90
40
50
50
60
80
90
90
100
125
150
40
50
50
60
60
80
90
100
125
150
60
80
25
30
35
40
15
25
30
35
80
30
45
50
60
70
90
15
90
125
150
30
40
45
50
70
45
60
70
80
110
150
45
70
80
Minimum
Circuit
Ampacity
Amps
13.1
23.3
28.3
33.6
42.4
10.8
23.5
2 9.9
36.3
67.0
80.8
25.7
41.6
48.2
57.5
73.5
89.4
77.6
93.8
121.4
149.0
25.7
39.6
45.1
53.4
38.6
62.6
72.2
86.6
110.1
134.0
38.6
66.2
20.8
25.8
31.0
39.9
8.6
21.3
27.7
34.1
76.1
21.0
36.9
43.5
52.8
68.8
84.7
10.6
85.1
112.7
140.3
21.0
34.9
40.4
48.7
62.3
29.9
53.9
63.5
77.9
101.4
125.4
29.9
57.5
68.9
Max Fuse /
BRKR
1
Size
Amps
Unitary Products Group 25
036-21508-005-A-0305
TABLE 15: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
32.1
32.1
19.3
19.3
10.0
7.9
148
148
137
137
62
50
2.3
2.3
2.3
2.3
1.3
1.3
6.6
6.6
6.6
6.6
3.3
3.3
0.0
0.0
0.0
0.0
0.0
0.0
NONE 0.0
2CE04510506 4.0
2CE04510706
2CE04511006
5.6
8.0
2CE04511506
2CE04512006
11.9
15.9
2CE04513006 22.2
NONE 0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
5.3
7.5
10.6
15.9
2CE04512006
2CE04513006
21.2
29.6
NONE 0.0
2CE04510525
2
2CE04510725
2
4.0
5.6
2CE04511025 8.0
2CE04511525
2CE04512025
11.9
15.9
2CE04513025 22.2
NONE 0.0
2CE04510525
2
2CE04510725
2
5.3
7.5
2CE04511025
2CE04511525
10.6
15.9
2CE04512025
2CE04513025
21.2
29.6
NONE 0.0
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
6.8
10.1
13.6
19.5
28.8
NONE 0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
0.0
10.2
15.3
20.4
29.3
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
100
125
25
35
35
40
50
70
20
30
35
40
60
125
50
60
70
70
90
60
70
80
90
100
110
125
150
175
225
50
60
80
100
100
110
125
150
200
80
Minimum
Circuit
Ampacity
Amps
96.8
122.0
17.1
27.3
32.3
37.5
46.4
60.4
52.5
60.8
74.3
88.2
110.1
33.0
49.0
55.6
64.9
80.8
13.6
26.3
32.7
39.1
50.1
76.6
88.1
104.2
131.8
159.4
203.2
33.0
46.9
49.0
73.1
82.7
97.1
120.5
144.6
182.4
49.0
Max Fuse /
BRKR
1
Size
Amps
26 Unitary Products Group
036-21508-005-A-0305
TABLE 16: ELECTRICAL DATA - BQ036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
19.0
19.0
11.9
11.9
5.9
4.8
25.0
25.0
14.7
14.7
7.7
6.4
105
105
85
85
42
34
105
105
130
130
64
52
1.7
1.7
1.7
1.7
1.0
1
2.3
2.3
2.3
2.3
1.3
1.3
7.6
7.6
5.2
5.2
2.6
2
7.6
7.6
5.2
5.2
2.6
2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
23.5
0.0
10.2
15.3
20.4
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
48.4
57.7
73.7
89.6
13.5
23.7
28.7
34.0
25.9
39.8
45.3
53.6
67.2
81.0
25.9
41.8
42.8
11.4
23.8
30.2
36.5
112.7
136.7
38.8
66.4
77.8
94.0
121.6
149.2
8.4
21.1
27.5
33.9
41.2
65.2
74.8
89.2
63.1
76.9
21.8
37.7
44.3
53.6
69.6
85.5
11.0
21.2
26.2
31.4
40.3
72.1
88.3
115.9
143.5
21.8
35.7
41.2
49.5
33.0
57.1
66.7
81.1
104.6
128.6
33.0
60.7
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
5.3
7.5
10.6
15.9
21.2
0.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR1
Size Amps
20
25
30
35
50
60
80
90
45
15
25
35
40
70
90
40
50
40
50
50
60
125
150
60
80
90
100
125
150
60
80
90
100
15
25
30
35
50
60
70
90
70
80
30
45
15
25
30
35
45
80
90
125
150
30
40
45
50
110
150
50
70
50
70
70
90
Unitary Products Group 27
036-21508-005-A-0305
TABLE 17: ELECTRICAL DATA - BQ060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
32.1
32.1
19.3
19.3
10.0
7.9
148
148
137
137
62
50
2.3
2.3
2.3
2.3
1.3
1.3
7.6
7.6
5.2
5.2
2.6
2
0.0
0.0
0.0
0.0
0.0
0.0
NONE 0.0
2CE04510506 4.0
2CE04510706
2CE04511006
5.6
8.0
2CE04511506
2CE04512006
11.9
15.9
2CE04513006 22.2
NONE 0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
5.3
7.5
10.6
15.9
2CE04512006
2CE04513006
21.2
29.6
NONE 0.0
2CE04510525
2
2CE04510725
2
4.0
5.6
2CE04511025 8.0
2CE04511525
2CE04512025
11.9
15.9
2CE04513025 22.2
NONE 0.0
2CE04510525
2
2CE04510725
2
5.3
7.5
2CE04511025
2CE04511525
10.6
15.9
2CE04512025
2CE04513025
21.2
29.6
NONE 0.0
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
6.8
10.1
13.6
19.5
28.8
NONE 0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
0.0
10.2
15.3
20.4
29.3
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
100
125
25
30
35
40
50
60
20
30
35
40
50
110
50
60
60
70
80
60
70
80
90
100
110
125
150
175
225
50
60
80
100
100
110
125
150
200
80
Minimum
Circuit
Ampacity
Amps
95.4
120.6
16.4
26.6
31.6
36.8
45.7
59.7
51.1
59.4
72.9
86.8
108.7
31.6
47.6
54.2
63.5
79.4
12.5
25.3
31.6
38.0
49.1
77.6
89.1
105.2
132.8
160.4
204.2
31.6
45.5
50.0
74.1
83.7
98.1
121.5
145.6
183.4
50.0
Max Fuse /
BRKR
1
Size
Amps
28 Unitary Products Group
036-21508-005-A-0305
TABLE 18: ELECTRICAL DATA - BQ036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
19.0
19.0
11.9
11.9
5.9
4.8
25.0
25.0
14.7
14.7
7.7
6.4
105
105
85
85
42
34
105
105
130
130
64
52
1.7
1.7
1.7
1.7
1.0
1
2.3
2.3
2.3
2.3
1.3
1.3
4.4
4.4
4.4
4.4
2.2
2.2
5.0
5.0
5.0
5.0
2.2
2.2
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
10.0
10.0
5.0
4.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
23.5
0.0
10.2
15.3
20.4
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
58.2
67.5
83.5
99.4
18.2
28.4
33.4
38.7
35.7
49.6
55.1
63.4
77.0
90.8
35.7
51.6
47.5
14.8
27.5
33.9
40.5
120.1
144.1
48.6
76.2
87.6
103.8
131.4
159.0
12.6
25.3
31.7
38.1
48.6
72.6
82.2
96.6
72.3
86.1
31.0
46.9
53.5
62.8
78.8
94.7
15.6
25.8
30.8
36.0
44.9
78.9
95.1
122.7
150.3
31.0
44.9
50.4
58.7
39.8
63.9
73.5
87.9
111.4
135.4
39.8
67.5
0.0
10.6
15.9
21.2
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
4.0
5.6
8.0
11.9
15.9
0.0
10.6
15.9
21.2
5.3
7.5
10.6
15.9
21.2
0.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
60
70
90
100
25
30
35
40
50
20
30
35
45
80
100
50
60
50
60
60
70
125
150
70
90
100
110
150
175
70
90
100
110
15
30
35
40
60
70
80
100
80
90
40
50
20
30
35
40
45
90
100
125
175
40
50
60
60
125
150
50
80
50
70
80
90
Unitary Products Group 29
036-21508-005-A-0305
TABLE 19: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
32.1
32.1
19.3
19.3
10.0
7.9
148
148
137
137
62
50
2.3
2.3
2.3
2.3
1.3
1.3
6.6
6.6
6.6
6.6
3.3
3.3
10.0
10.0
10.0
10.0
5.0
4.0
NONE 0.0
2CE04510506 4.0
2CE04510706
2CE04511006
5.6
8.0
2CE04511506
2CE04512006
11.9
15.9
2CE04513006 22.2
NONE 0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
5.3
7.5
10.6
15.9
2CE04512006
2CE04513006
21.2
29.6
NONE 0.0
2CE04510525
2
2CE04510725
2
4.0
5.6
2CE04511025 8.0
2CE04511525
2CE04512025
11.9
15.9
2CE04513025 22.2
NONE 0.0
2CE04510525
2
2CE04510725
2
5.3
7.5
2CE04511025
2CE04511525
10.6
15.9
2CE04512025
2CE04513025
21.2
29.6
NONE 0.0
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
6.8
10.1
13.6
19.5
28.8
NONE 0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
0.0
10.2
15.3
20.4
29.3
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
110
150
30
40
40
45
60
70
25
35
40
45
60
70
80
90
100
125
60
70
80
80
100
110
110
125
150
175
225
60
70
90
110
110
125
150
175
200
90
Minimum
Circuit
Ampacity
Amps
106.8
132.0
22.1
32.3
37.3
42.5
51.4
65.4
62.5
70.8
84.3
98.2
120.1
43.0
59.0
65.6
74.9
90.8
17.6
30.3
36.7
43.1
54.1
86.6
98.1
114.2
141.8
169.4
213.2
43.0
56.9
59.0
83.1
92.7
107.1
130.5
154.6
192.4
59.0
Max Fuse /
BRKR
1
Size
Amps
30 Unitary Products Group
036-21508-005-A-0305
TABLE 20: ELECTRICAL DATA - BQ036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
19.0
19.0
11.9
11.9
5.9
4.8
25.0
25.0
14.7
14.7
7.7
6.4
105
105
85
85
42
34
105
105
130
130
64
52
1.7
1.7
1.7
1.7
1.0
1
2.3
2.3
2.3
2.3
1.3
1.3
7.6
7.6
5.2
5.2
2.6
2
7.6
7.6
5.2
5.2
2.6
2
10.0
10.0
10.0
10.0
5.0
4.0
10.0
10.0
10.0
10.0
5.0
4.0
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510725
2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
NONE
2CE04511058
2CE04511558
2CE04512058
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
23.5
0.0
10.2
15.3
20.4
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
58.4
67.7
83.7
99.6
18.6
28.8
33.8
39.1
35.9
49.8
55.3
63.6
77.2
91.0
35.9
51.8
47.9
15.0
27.8
34.2
40.5
122.7
146.7
51.2
78.8
90.2
106.4
134.0
161.6
12.4
25.1
31.5
37.9
51.2
75.2
84.8
99.2
73.1
86.9
31.8
47.7
54.3
63.6
79.6
95.5
16.0
26.2
31.2
36.4
45.3
82.1
98.3
125.9
153.5
31.8
45.7
51.2
59.5
43.0
67.1
76.7
91.1
114.6
138.6
43.0
70.7
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
BRKR
1
Size
Amps
60
70
90
100
25
30
35
40
50
20
30
35
45
80
100
50
60
50
60
60
70
125
150
70
90
100
110
150
175
70
90
90
110
15
30
35
40
60
70
80
100
80
90
40
50
20
30
35
40
50
90
100
150
175
40
50
60
60
60
80
80
100
125
150
60
80
Unitary Products Group 31
036-21508-005-A-0305
TABLE 21: ELECTRICAL DATA - BQ060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
Voltage
Compressors
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater kW
Heater
Amps
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
32.1
32.1
19.3
19.3
10.0
7.9
148
148
137
137
62
50
2.3
2.3
2.3
2.3
1.3
1.3
7.6
7.6
5.2
5.2
2.6
2
10.0
10.0
10.0
10.0
5.0
4.0
NONE 0.0
2CE04510506 4.0
2CE04510706
2CE04511006
5.6
8.0
2CE04511506
2CE04512006
11.9
15.9
2CE04513006 22.2
NONE 0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
5.3
7.5
10.6
15.9
2CE04512006
2CE04513006
21.2
29.6
NONE 0.0
2CE04510525
2
2CE04510725
2
4.0
5.6
2CE04511025 8.0
2CE04511525
2CE04512025
11.9
15.9
2CE04513025 22.2
NONE 0.0
2CE04510525
2
2CE04510725
2
5.3
7.5
2CE04511025
2CE04511525
10.6
15.9
2CE04512025
2CE04513025
21.2
29.6
NONE 0.0
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
2
2CE04513046
2
6.8
10.1
13.6
19.5
28.8
NONE 0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
0.0
10.2
15.3
20.4
29.3
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
110
150
30
35
40
45
60
70
20
30
40
45
60
70
80
90
100
125
60
70
70
80
90
110
110
125
150
175
225
60
70
90
110
110
125
150
175
200
90
Minimum
Circuit
Ampacity
Amps
105.4
130.6
21.4
31.6
36.6
41.8
50.7
64.7
61.1
69.4
82.9
96.8
118.7
41.6
57.6
64.2
73.5
89.4
16.5
29.3
35.6
42.0
53.1
87.6
99.1
115.2
142.8
170.4
214.2
41.6
55.5
60.0
84.1
93.7
108.1
131.5
155.6
193.4
60.0
Max Fuse /
BRKR
1
Size
Amps
32 Unitary Products Group
036-21508-005-A-0305
TABLE 22: PHYSICAL DATA
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
TABLE 23: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTI-
PLIER
208
240
480
600
208
230
460
575
1.00
0.92
0.92
0.92
MODELS
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP (Direct Drive)
Fan Motor HP (Belt Drive)
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Propeller Dia. (in.)
Fan Motor Hp
Nom. CFM
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Reciprocating Type
Quantity Per Unit (15” X 20” X 1” or 2“)
Quantity Per Unit (14” X 25” X 1” or 2“)
Total Face Area (sq. ft.)
Refrigerant 22
(lbs./oz.)
036
12 X 10
1/2
1 1/2
4
16
4.3
22
1/3
4300
1
20
17.1
1
2
1
6.6
7/12
1
2
1
6.6
9/2
BQ
048
12 X 10
3/4
1 1/2
3
15
5.1
22
1/2
4200
1
20
17.1
TABLE 24: VOLTAGE LIMITATIONS
1
POWER SUPPLY
VOLTAGE
MIN.
187 208/230-3-60
460-3-60
575-3-60
414
518
MAX.
253
506
506
1. Utilization Range “A” in accordance with ARI Standard
110.
1
2
1
6.6
8/4
060
12 X 10
1
1 1/2
3
15
5.1
24
1/2
4500
1
20
17.1
Unitary Products Group 33
036-21508-005-A-0305
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
1
TERMINALS
RH
UNIT TERMINAL
STRIP TB1
ADD
JUMPER
RC R
Y
W
G
W1
W2
G
C
Y1
Y2
24 VOLT
TRANSFORMER
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT
1
TERMINALS UNIT TERMINAL
STRIP TB1
ADD
JUMPER
ADD
JUMPER
4
RC
RH
Y1
Y2
W1
W2
G
B
LED 1
LED 2
COM
A1
A2
T
T
NOT
USED
4
2
3
R
Y1
Y2
W1
W2
G
C
X
OCC
TO REMOTE SENSOR
2TH040702224 IF USED
24 VOLT
TRANSFORMER
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER.
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
ADD
JUMPER
THERMOSTAT
1
TERMINALS
RH
RC
Y
W
G
SINGLE STAGE
UNIT TERMINAL
STRIP TB1
R
Y1
W1
G
C
24 VOLT
TRANSFORMER
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
FIGURE 2 TYPICAL FIELD POWER & CONTROL WIRING
34 Unitary Products Group
036-21508-005-A-0305
FIGURE 3 UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW
FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD
Unitary Products Group
DETAIL “A”
35
036-21508-005-A-0305
DETAIL “B”
FIGURE 5 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
FIGURE 6 UNIT DIMENSIONS (REAR VIEW)
36 Unitary Products Group
036-21508-005-A-0305
FILTER
ACCESS
BLOWER MOTOR
ACCESS
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the blower housing inside the blower compartment) A,B
WIRING ENTRY
(See Detail “B”)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
FIGURE 7 DISCONNECT/BLOWER ACCESS LOCATION
TABLE 25: UTILITIES ENTRY
HOLE
A
B
C
D
OPENING SIZE (DIA.)
7/8” KO
1
2” KO
1
1-5/8” KO
1-1/2” KO
USED FOR
Control Wiring
Power Wiring
2
Side
Bottom
Side
Bottom
Gas Piping (Front)
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the side in the insulation.
2. Do not remove the 2” knockout ring.
TABLE 26: MINIMUM CLEARANCES
LOCATION CLEARANCE
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
1
24” (Cooling/Electric Heat)
32” (Gas Heat)
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
24” (Less Economizer)
36” (With Economizer)
24”
0”
Above Unit
2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
Unitary Products Group 37
036-21508-005-A-0305
FIGURE 8 TYPICAL APPLICATIONS
38 Unitary Products Group
036-21508-005-A-0305
44 7 /
8
D
A
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
BACK OF UNIT
82 1 /
4
C
Y
B
CONDENSER COIL
END OF UNIT
44 7 /
8
A
F
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
E
FIGURE 9 FOUR AND SIX POINT LOADING
TABLE 27: BQ 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL A
BQ036
BQ048
BQ060
628
668
693
139
148
154
TABLE 28: BQ 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL A B
628 93 92 BQ036
BQ048
BQ060
668
693
99
103
98
102
TABLE 29: CENTER OF GRAVITY
DIMENSION 3 - 5 TON
X
Y
40-¾”
19-¾”
TABLE 30: OPERATING WEIGHTS (LBS.)
BASIC UNIT
OPTIONS
ACCY.
MODEL SIZE
BQ
Economizer
Motorized Damper
Electric Heater
5 - 7 kW
10 - 15 kW
20 - 30 kW
Roof Curb
Barometric Relief / Fixed Air Damper
Belt-Drive Blower
C
91
97
100
B
137
146
151
3 TON
628
D
116
123
128
C
174
185
192
B
BACK OF UNIT
82 1 /
4
D
Y
4 TON
668
50
26
18
23
28
92
10
5
E
117
125
129
C
CONDENSER COIL
END OF UNIT
D
177
189
196
F
119
126
131
5 TON
693
Unitary Products Group 39
036-21508-005-A-0305
FIGURE 10 - ROOF CURB DIMENSIONS
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000
TM
units are convertible single package heat pumps. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
Models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged heat pumps designed for outdoor mounted installation.
The units shall have minimum SEER ratings of 10.0. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with
DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insu-
40 Unitary Products Group
036-21508-005-A-0305 lated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
REFRIGERANT COMPONENTS
Compressor: a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils: a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b.
Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall include: a.
Independent fixed-orifice expansion devices.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F of sub-cooling at design conditions.
UNIT CONTROLS a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil. f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.
h.
Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.
i.
Unit control board shall have on-board diagnostics and fault code display.
j.
Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F.
k.
Control board shall monitor each refrigerant safety switch independently.
l.
Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and auto-
Unitary Products Group 41
036-21508-005-A-0305 matic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS a.
Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
• Compressor 5 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).
• BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
• POWER EXHAUST OPTION - To work in conjunction with economizers.
• ELECTRIC HEATERS
• ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assembling.
• MANUAL OUTDOOR AIR DAMPER
• COIL GUARD KIT - Guard for cooling coil.
• HAIL GUARD
OTHER FACTORY INSTALLED OPTIONS
• POWER EXHAUST OPTION - To work in conjunction with economizers.
• TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
• ELECTRONIC SINGLE ENTHALPY ECONOMIZER
• DIRTY FILTER SWITCH
• PHASE MONITOR
• COIL GUARD
• POWERED GFI CONVENIENCE OUTLET
• NON-POWERED GFI CONVENIENCE OUTLET
42 Unitary Products Group
036-21508-005-A-0305
• BAS CONTROLS ( SImplicity ™ INTELLI-Comfort™ ,
CPC, JOHNSON, HONEYWELL, NOVAR)
• BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
• HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
• STAINLESS STEEL DRAIN PAN
• BOTTOM DRAIN CONNECTION
• 2" PLEATED FILTERS
• DISCONNECT SWITCH
• SUPPLY AIR SMOKE DETECTOR
• RETURN AIR SMOKE DETECTOR
Unitary Products Group 43
Subject to change without notice. Printed in U.S.A.
Copyright © 2005 by Unitary Products Group. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21508-005-A-0305
Supersedes: 036-21508-004-A-0504