HRVCRSVU1157
Heat Recovery Ventilator
Installation Instructions
HRVCRSVU1157
A11189
NOTE : Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory- authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER ,
WARNING , and CAUTION . These words are used with the safety- alert symbol.
DANGER identifies the most serious hazards, which will result in severe personal injury or death.
WARNING signifies hazards, which could result in personal injury or death.
CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
The Heat Recovery Ventilator (HRV) is used to exchange indoor stale air with outside fresh air. The HRV unit is equipped with a special heat recovery core which transfers sensible heat between the fresh incoming air and stale exhaust air.
It is required to locate the HRV in a conditioned space. Special attention should be given to condensate drain, duct application, balancing the HRV, and locating unit for easy access and routine maintenance. The cross- flow design core allows entering and leaving air streams to transfer heat energy without mixing.
LOCATION
Inspect Equipment
Move carton to final installation location. Remove the HRV from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete.
!
WARNING
PERSONAL INJURY, ELECTRIC SHOCK OR
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and property damage.
1.
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2.
We recommend that your unit be inspected by a specialized technician once a year.
3.
Before servicing or cleaning the unit, disconnect power cord from electrical outlet.
4.
This unit is not designed to provide combustion and/or dilution air for fuel- burning appliances.
5.
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6.
Do not use the units with any solid- state speed control device other than the corresponding ones listed in Table
1.
7.
This unit must be grounded. The power supply cord has a
3- prong grounding plug for your personal safety. It must be plugged into a mating 3- prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances. Do not remove the ground prong. Do not use an extension cord.
8.
Do not install in a cooking area or connect directly to any appliances.
9.
Do not use to exhaust hazardous or explosive materials and vapors.
10. When performing installation, servicing or cleaning these units, it is recommended to wear safety glasses and gloves.
11. Due to the weight of the unit, two installers are recommended to perform installation.
12. When applicable local regulations comprise more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
1.
To avoid premature clogged filters, turn OFF the unit during construction or renovation.
2.
Please read specification label on product for further information and requirements.
3.
Be sure to duct air outside – Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
4.
Intended for residential installation only in accordance with the requirements of NFPA 90B (for a unit installed in USA) or Part 9 of the National Building Code of
Canada (for a unit installed in Canada).
5.
Do not run any air ducts directly above or closer than
2- ft (0.61 m) to any furnace or its supply plenum, boiler, or other heat producing appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 9- ft 10- in (3 m) from this plenum connection to the furnace.
6.
The ductwork is intended to be installed in compliance with all applicable codes.
7.
When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit operates adequately.
8.
If the ductwork passes through an unconditioned space
(e.g.: attic), the ducts must be insulated, and the unit must operate continuously except when performing maintenance and/or repair. Also, the ambient temperature of the house should never drop below 18 _ C (65 _ F).
UNIT
HRVCRSVU1157
Table 1 – Solid State Speed Control Device
One Touch main wall control
Standard main wall control
Basic main wall control
20 minute timer
CONTROL
2
Air Distribution
Stale Air to outside
Fresh air from outside
Stale air from building
TECHNICAL DATA
Fresh air to building
Stale air from building
Filtered air to building
A11190 A11191
Fig. 1 - Normal Operation Fig. 2 - Defrost or Recirculation
Defrost Cycles
_ F
23
14
- 17
Outside Temperature
_ C
- 5
- 10
- 27
Defrost Cycles (Minutes)
Defrosting
7
7
10
HRVCRSVU1157
Operation Between
Each Defrost Cycle
25
25
22
Extended Defrost Cycles ( Minutes)
Defrosting
Operation Between
Each Defrost Cycle
9
9
10
In a cold region (outside temperature - 17 _ F [- 27 _ C] and lower), it may be necessary to setup EXTENDED DEFROST. See page 10.
23
23
22
23 9 /
16
”
(599 mm)
2 ¹/
16
”
(53 mm)
24 9 /
16
”
(624 mm)
22 ½”
(572 mm)
3 13 /
16
”
(97 mm)
7 7 /
16
”
(189 mm)
14 1 /
16
”
(358 mm)
14 15 /
16
”
(380 mm)
18 ¼”
(464 mm)
Fig. 3 - Dimensions HRVCRSVU1157
NOTE: Every port fits 6” round duct.
A11192
3
TYPICAL INSTALLATIONS
Use the following illustrations as guidelines to help you decide on how the unit will be installed. All the units should be hung from the joists.
If required, bathroom fans and a range hood may be used to exhaust stale air. Also, for homes with more than one level, we recommend one exhaust register at the highest level.
There are 3 installation methods: Fully ducted, Central Draw Point and Simplified Installation.
NOTE : An electrical outlet has to be available within 3- ft of the unit.
Fully Ducted System (Primarily for homes with radiant hot water or electric baseboard heat.)
Stale air coming from the registers located at the highest level of the house is exhausted to the outside. Fresh air from outside is filtered and supplied by the register located in the lowest liveable level.
Homes with more than one level require at least one exhaust register at the highest level.
See Fig. 4.
Simplified Installation (Connection to a forced air system.)
Stale air is exhausted to the outside. Fresh air from outside is filtered and supplied to the return (plenum) or the supply duct of the forced air unit. See Fig. 6.
To avoid cross- contamination and achieve the highest efficiencies, the forced air system blower must always be ON.
NOTE : Homes with multiple forced air systems should have one unit on each system.
A11193
Fig. 4 - Fully ducted system
Central Draw Point (Connection to a forced air system.)
Stale air coming from the registers located at the highest level of the house is exhausted to the outside. Fresh air from outside is filtered and supplied to the return (plenum) or the supply duct of the forced air unit. See Fig. 5.
For this type of installation, it is not essential that the forced air system blower runs when the unit is in operation, but it is recommended.
NOTE : Home with multiple forced air systems should have one unit on each system.
A11195
Fig. 6 - Simplified Installation
INSTALLATION
Inspect the contents of the box
Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, ports, power cord, etc.
Unit Door
HRVCRSVU1157 has one door. The unit door can be relocated on the back of the unit. This can be helpful to optimize duct configuration while keeping access for unit maintenance. To change door location, follow these steps (see Fig. 7):
A.
Remove both door lower mechanical screws no. 8- 32 x 1- in
(1) and set aside.
B.
Open (2) and lift out the door (3).
To remove unit back panel, repeat steps A and B, but instead of removing 2 mechanical screws, there are 4 metal screws to be removed. Hang the door to the back of the unit and secure it by tightening its both lower mechanical screws. Hang back panel to the front of the unit and secure it by tightening its four metal screws.
A
B
Fig. 5 - Central Draw Point
A11194
1
4
3
Fig. 7 - Hanging the door
2
A11196
Locating the unit
Choose an appropriate location for the unit.
S
Within an area of the house where the ambient temperature is between 50 _ F (10 _ C) and 122 _ F (50 _ C) (basement, furnace room, closet, etc.).
S Away from living areas (dining room, living room, bedroom), if possible.
S So as to provide easy access to the interior of the unit, for maintenance.
S Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
S
Away from hot chimneys and other fire hazards.
S Allow for a power source (standard 3- prong grounding outlet).
S
Close to a drain. If no drain is close by, use a pail to collect run- off.
Hang the unit with the four chains and springs provided. See Fig.
8.
S If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived- in level.
Calculating duct size
Use Table 2 to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values. Avoid installing ducts that will have to carry air flows near the maximum values and never install a duct if its air flow exceeds the maximum value.
NOTE : Examples below use imperial units. The same calculation applies to metric units.
A.
Example of calculation:
Problem: The installation requires two exhaust registers (one for the kitchen, and the other for the bathroom). The registers are connected to a main duct which will connect to the unit
(high speed performance value of 140 cfm). What size of duct should be used for the main exhaust duct and for both end branches leading to the registers? (See Fig. 9.)
Solution: Simplified method. (For a more detailed method of calculating duct size, refer to the ASHRAE or HRAI HAND-
BOOK.)
Main duct: Table indicates for a 6- in duct: recommended air flow: 120 cfm, maximum air flow: 180 cfm. The 140 cfm high speed air flow is close enough to the recommended value (120) and far away enough from the maximum value (180). Therefore, a 6- in duct or larger is an appropriate choice for the main exhaust duct.
End branches: Each end branch will have to transport a 70 cfm air flow (140 divided by 2). Table 2 indicates for a 5- in duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The high speed air flow of 70 cfm is close enough to the recommended value (75) and far away enough from the maximum value (110). Therefore, a 5- in duct or larger is an appropriate choice for both end branches.
NOTE : A 4- in duct would have been too small because the maximum acceptable value for a 4- in duct is 60 cfm.
5-in
∅,
70 cfm
End branches
A11197
Fig. 8 - Chain spring installation
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Make sure the unit is level.
Main branch
6-in
∅,
140 cfm
Planning of the ductwork
S
Keep it simple. Plan for a minimum of bends and joints.
S Keep the length of insulated ducts to a minimum.
S Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would cause clogging of the filters and recovery module.
DUCT DIAMETER
4 inch (102 mm) round
5 inch (127 mm ) round
6 inch (152 mm) round
A11199
Fig. 9 - Main exhaust leading to registers
B.
Fig. 10 is an example of a design for a fully ducted system with a unit having a high speed performance of 140 cfm.
Table 2 – Ductwork Sizing Table
RECOMMENDED AIR FLOW
40 CFM (19 L/S or 68 M 3 /H)
75 CFM (35 L/S or 127 M 3 /H)
120 CFM (57 L/S or 204 M 3 /H)
MAXIMUM AIR FLOW
60 CFM (28 L/S or 102 M 3 /H)
110 CFM (52 L/S or 187 M 3 /H)
180 CFM (85 L/S or 306 M 3 /H)
5
4-in 4-in
4-in
∅,
47 cfm
5-in
∅,
93 cfm
5-in
∅,
67 cfm
5-in
4-in
4-in
4-in
∅,
46 cfm
4-in
4-in
∅,
37 cfm
5-in
6-in
4-in
4-in
∅,
24 cfm
4-in
5-in
∅,
74 cfm
6-in
∅,
160 cfm
6-in
∅,
160 cfm
5-in
∅,
62 cfm
5-in
5-in
5-in
∅,
86 cfm
Fig. 10 - Fully ducted system
Installing the ductwork and registers
Fully ducted system (see Fig. 4)
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property damage.
Never install a stale air exhaust register in a closed room where combustion device operates, such as a gas furnace, a gas water heater or a fireplace.
descending to occupant’s level.)
S If a register must be floor installed, direct the airflow up the wall.
Central Draw Point System (see Fig. 5)
Stale air exhaust ductwork
Same as for Fully Ducted System described above.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property damage.
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.
Stale air exhaust ductwork
S Install the stale air exhaust registers where the contaminants are produced: kitchen, living room, etc. Position the registers as far from the stairway as possible and in such a way that the air circulates in all the lived- in spaces in the house.
S If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.
S Install the registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
S
If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400- ft/min (122 m/min), then the register type is too small. Replace with a larger one.
Fresh air distribution ductwork
S
Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.
S
Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.
S
Install the registers either in the ceiling or high on the walls with air flow directed towards the ceiling. (The cooler air will then cross the upper part of the room and mix with room air, before
!
CAUTION
A11198
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the unit. Also, the use of metal duct is highly recommended.
Fresh air distribution ductwork
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply side connection
S Cut an opening into the furnace supply duct at least 18- in (0.5
m) from the furnace/air handler.
S
Connect this opening to the Fresh air distribution port of the unit (use metal duct , see Fig. 11).
6
Metal duct
Minimum 18-in
(0.5m)
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the unit. Also, the use of metal duct is highly recommended. For a Return- Return installation, the furnace blower must be in operation when the unit is in operation.
There are 2 methods for connecting the unit to the furnace/air handler.
Stale air intake
S Cut an opening into the furnace/air handler return duct not less than 10- ft (3.1 m) from the furnace/air handler (see Fig. 13)
S
Connect this opening to the Exhaust air from building port of the unit.
A11200
Fig. 11 - Main supply leading to registers
S
Make sure the unit duct forms an elbow inside the furnace/air handler ductwork.
S If desired, interlock (synchronize) the furnace/air handler blower operation (see page 11, ELECTRICAL CONNECTION TO
FURNACE).
Method 2: Return side connection
S Cut an opening into the furnace return duct not less than 10- ft
(3.1 m) from the furnace/air handler (A+B).
S Connect this opening to the Fresh air distribution port of the unit (see Fig. 12).
NOTE: For Method 2, it is not essential that the furnace/air handler runs when the unit is operation, but we recommend it. If desired, interlock (synchronize) the furnace/air handler blower operation (see page 11, ELECTRICAL CONNECTION TO
FURNACE).
A
Metal duct
Minimum 18-in
(0.5 m)
B
A
A+B = Not less than 10-ft (3.1 m)
Fig. 13 - Method 1: Supply- return connection
A11202
Fresh air distribution
S Same instructions as for Method 1 or Method 2.
For Method 2 (Return- return), make sure there is a distance of at least 3- ft (0.9 m) between the 2 connections to the furnace/air handler. See Fig. 14.
B
A+B=Not less than 10-ft (3.1m)
A11201
Fig. 12 - Return side connection
Simplified installation
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property damage.
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.
A
B
Minimum 3-ft
(0.9 m)
A+B = Not less than 10-ft (3.1 m)
A11203
Fig. 14 - Method 2: Return- return connection
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
If using Method 2, make sure the furnace/air handler blower operation is synchronized with the unit operation. See page
11, ELECTRICAL CONNECTION TO THE FURNACE.
7
NOTE : For Method 1, it is not essential to synchronize the furnace blower operation with the unit operation, but it is recommended.
Connecting the ducts to the unit
Insulated flexible ducts
Use the following procedure to connect the insulated flexible ducts to the ports of the unit ( Exhaust air to outside and Fresh air from outside ports).
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts.
1. Pull back the insulation to expose the flexible duct.
2. Attach the flexible duct to the port using tie wrap.
3. Pull the insulation over the joint and tuck in between the inner and outer rings of the double collar.
4. Pull down the vapor barrier (shaded part in Fig. 15) over the outer ring to cover it completely. Fasten in place the vapor barrier using the port strap (included in unit parts bag). To do so, insert one collar pin through vapor barrier and first strap hole, then insert the other collar pin through vapor barrier and center strap hole and close the loop by inserting the first collar pin in the last strap hole.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the ducts.
Non- insulated rigid ducts
Use metal screws and duct tape to connect the rigid ducts to the unit ports.
Non- insulated flexible ducts
Use tie wraps to connect the flexible ducts to the unit ports.
1 2
3
4
Collar pin
Collar pin
Non-insulated rigid ducts
Fig. 15 - Ductwork installation
Non-insulated flexible ducts
A11204
A11205
Fig. 16 - Ductwork installation
8
INSTALLING TWO EXTERIOR HOODS
Choose an appropriate location to install the exterior hoods:
S
There must be a minimum distance of 6- ft (1.8 m) between the hoods to avoid cross- contamination
S
There must be a minimum distance of 18- in (457 mm) from the ground
Make sure the intake hood is at least 6 feet (1.8 m) away from the following:
S Dryer exhaust, high efficiency furnace vent, central vacuum vent
S
Gas meter exhaust, gas barbecue grill
S Any exhaust from a combustion source
S
Garbage bin and any other sources of contamination
Refer to figure beside for connecting insulated ducts to the exterior hoods. An “Anti- gust intake hood’’ should be installed in regions where a lot of snow is expected to fall.
Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the drain source. Make sure this loop is located OVER the “T” as shown. Run the tube to the floor drain or to an alternative drain pipe or pail.
IMPORTANT : If using a pail to collect water, locate the tube end approximately 1- in (25 mm) from the top of the pail in order to prevent water from being drawn back up into the unit.
± 1”
Exhaust hood
18-in
(457 mm) 6-ft
(1.8 m)
Intake hood
Optional duct location
Tape and duct tie
6-ft
(1.8 m)
18-in
(457 mm)
A11206
Fig. 17 - Exterior hoods
Connecting the drain
Cut 2 sections of the plastic tube, at least 16- in (406 mm) long, and attach them to each inner drain fitting, located under the unit.
Join both short sections to the “T” junction and main tube as shown in Fig. 18.
A11209
Fig. 19 - Drain connection
CONTROLS
This unit is equipped with an integrated control located under the unit, on the recessed side of electrical compartment. Plug the unit.
Unit booting sequence
The unit booting sequence is similar to a personal computer boot sequence. Each time the unit is plugged in after being unplugged, or after a power failure, the unit will perform a 30- second booting sequence before starting to operate.
During the booting sequence, the integrated control LED will light
GREEN (unit set in normal defrost) or AMBER (unit set in extended defrost) for 5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for the rest of the booting sequence. During this RED light phase, the unit is checking and resetting the motorized damper position. Once the motorized damper position completely set, the RED light turns off and the booting sequence is done.
NOTE : No command will be taken until the unit is fully booted.
Integrated control
Use the push button (1) to control the unit. The LED (2) will then show on which mode the unit is in. See Fig. 20.
2
1
16"
(406 mm)
16"
(406 mm)
Fig. 18 - Drain connection
A11208
9
Bottom of the unit
Fig. 20 - Integrated control
A11210
Refer to Table 3 to see how to operate the unit using its integrated control.
Table 3 – Integrated control
PRESS ON PUSH
BUTTON
Once
Twice
Three Times
LED COLOR
Amber
Green
No Light
RESULTS
Unit is on low speed
Unit is on high speed
Unit is Off
If a problem occurs during the unit operation, its integrated control
LED (2) will blink. The color of the blinking light depends on the type of error detected. Refer to Troubleshooting on page 15 for further details.
Setting extended defrost
These units are factory set to normal defrost. In cold region
(outside temperature - 17 _ F [- 27 _ C] and lower), it may be necessary to setup extended defrost. During the first 2 seconds of booting sequence, while the integrated control LED is GREEN, press on push button for 3 seconds to set the unit in extended defrost; the LED will blink AMBER to show the unit is in extended defrost mode. After that, the LED will shut off, then light
RED (the unit returns in its booting sequence).
Electrical connection to main controls
For more convenience, this unit can also be controlled using an optional main wall control.
NOTES :
1.
IMPORTANT: The integrated control must be turned
OFF to use an optional main control.
2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Always disconnect the unit before making any connections.
Failure in disconnecting power could result in electrical shock or damage of the wall control or electronic module inside the unit.
Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls. Check if all wires are correctly inserted in their corresponding holes in the terminal block. (A wire is correctly inserted when its orange receptacle is lower than another one without wire. See Fig. 21, wire A is correctly inserted, but wire B is not.)
1 2
A B
A11211
Fig. 21 - Terminal connector
NO C NC I OC OL Y R G B
Main wall control
One Touch - Rear view
Y G B OC G B
Fig. 22 - Electrical connection to One touch
A11212
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Never install more than one optional main wall control per unit. Make sure that the wires do not short- circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.
NO C NC I OC OL Y R G B
Fig. 23 Electrical connection to stamdard or basic main wall contro l
A11213
10
20-MINUTE
PUSH-BUTTON SWITCHES
(5 MAXIMUM)
NO C NC I OC OL Y R G B
A11214
Fig. 24 - Electrical connection to 20- minute lighted push button timer(s)
NOTE : If an optional auxiliary control is activated and then, the
Dehumidistat (or Humidity Control) is being activated, the
Dehumidistat (or Humidity Control) will override the auxiliary control commands.
Once the control(s) connections have been made, insert the terminal connector on the recessed side of electrical compartment.
See Fig. 25.
Terminal connector
NOTE : For information about the operation of the wall controls, refer to the user guide.
ELECTRICAL CONNECTION TO THE
FURNACE
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Never connect a 120- volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control
For a furnace connected to a cooling system:
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing “Y” at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the ALTERNATE FURNACE
INTERLOCK WIRING. See Fig. 26.
Bottom of the unit
Fig. 25 - Terminal connector
Standard furnace interlock wiring
A11219
Alternate furnace interlock wiring
FOUR
WIRES
TWO WIRES heating only
W
R
G
C
Y
FURNACE
24-VOLT
TERMINAL BLOCK
W R G Y
THERMOSTAT
TERMINALS
TWO WIRES
4 WIRES
2 WIRES heating only
W
G
C
W R G Y
THERMOSTAT
TERMINAL wiring
nuts
NO
NC
C
FURNACE
24-VOLT
TERMINAL BLOCK
COOLING SYSTEM
Fig. 26 - Electrical connection to furnace
2 WIRES
11
COOLING SYSTEM
A11215
10 9 8 7 6 5 4 3 2 1
120 V 100 V
1 2 3
JU1
1 2 3
JU1 JU1
12
BALANCING THE UNIT
What you need to balance the unit
S A magnehelic gauge capable of measuring 0 to 1 inch of water
(0 to 249 Pa) and 2 plastic tubes.
S The balancing chart of the unit.
A11217
Fig. 28 - Magnehelic gauge
Preliminary stages to balance the unit
S Seal all the unit ductwork with tape. Close all windows and doors.
S Turn off all exhaust devices such as range hood, dryer and bathroom fans.
S Make sure the balancing dampers are fully open by setting both damper balancing tools completely vertical.
S
Make sure all filters are clean (if it is not the first time the unit is balanced).
Balancing procedure
1. Set the unit to high speed.
NOTE: Make sure that the furnace/air handler blower is
ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace/air handler blower OFF. If the outside temperature is below 0
_
C/32
_
F, make sure the unit is not running in defrost while balancing.
(By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.)
2. Place the magnehelic gauge on a level surface and adjust it to zero.
3. Connect tubing from gauge to EXHAUST air flow pressure taps (the ones with arrows, see insets in illustration beside).
Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops below zero, reverse the tubing connections.
4. Note the CFM value from balancing chart located on unit.
5. Repeat steps 3 and 4, but to FRESH air flow pressure taps.
6. Match highest CFM value to lowest by adjusting the balancing damper corresponding to the highest value.
Stale air flow
Fig. 29 - Damper balancing tool
A11218
Fresh air flow
A11220
Fig. 30 - Balancing procedure
7. Secure both dampers in place with a fastening screw (included).
8. Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address).
NOTES :
1. Use conversion chart provided with the unit to convert magnehelic gauge readings to equivalent cfm values.
2. The unit is considered balanced even if there is a difference of 10 cfm (or 5 l/s or 17 m 3 /h) between the two air flows.
13
4
SERVICE PARTS
2
3
1
6
5
7
8
8
9
10
14
15
16
11
12
13
9
10
7
8
ITEM
1
2
3
4
5
6
DESCRIPTION
Oval Port
Double Collar Oval Port
Exhaust Damper Spring
Motor Assembly
Balancing Tool
Defrost Damper
Damper System Assembly (including Item 6)
Core Filter
Heat Recovery Core
Door Assembly
PCB
Transformer
Capacitor 5 F
Thermistor Kit (not shown)
Hardware Kit (not shown)
PCB Connector (not shown)
Fig. 31 - Parts
1
1
1
1
1
2
1
1
1
2
QTY
2
2
1
2
2
1
11
12
13
HRVCRSVU1157
18206
18207
18221
18197
18220
18200
18199
18204
18203
SV64922
19342
18219
16042
15749
08304
16416
A11223
14
If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where the problem occurs on the unit.
LED flashes GREEN
LED flashes AMBER
LED flashes RED
1
Problems
Unit does not work.
ERROR TYPE ACTION
Thermistor error
Damper error
Motor error
Possible causes
Replace thermistor
Go to point 6
Go to point 9
The circuit board may be defective.
UNIT STATUS
Unit works but will defrost frequently
Unit does not work
Unit does not work
You should try this
Unplug the unit. Disconnect the main control and the optional(s) controls(s) (if need be). Jump G and B terminals.
Plug the unit back and wait about 10 seconds. If the motors run on high speed and the damper opens, the circuit board is not defective.
2
3
The damper actuator does not work.
The wall control does not work.
The fuse may be defective.
The damper actuator or the integrated damper mechanism may be defective.
The circuit board or the transformer may be defective.
Check if fuse F1 is blown. In that case, replace fuse F1 as per product nameplate.
Unplug the unit. Disconnect the main control and the optional controls(s) (if need be). Wait 10 seconds and plug the unit back. Check if the damper opens. If not, use a multimeter and check for 24 V AC on J12- 1 and J12- 2 (in electrical compartment). If there is 24 VAC, replace the entire damper assembly.
NOTE: It is normal to experience a small delay (7- 8 seconds) before detecting the 24 V AC signal at start- up.
This signal will stay during 17- 18 seconds before disappearing.
If there is no 24 V AC, check for 24V AC between J8- 1 and
J8- 2. If there is 24V AC, replace the circuit board, and if there is no 24V AC, change the transformer.
The wires may be in reverse position.
Ensure that the color coded wires have been connected to their appropriate places.
The wires may be broken.
Inspect every wire and replace any that are damaged.
The wire in the wall OR the wall control may be defective.
Remove the wall control and test it right beside the unit using another shorter wire. If the wall control works there, change the wire. If it does not, change the wall control.
4 The Dehumidistat (or Humidity control) does not work OR the
20- minute push button timer does not work OR its indicator light does not stay on.
5
6
The supply and/or exhaust motor do not work.
The defrost cycle does not work
(the fresh air duct is frozen) OR the fresh air distributed is very cold.
The wires may be in reverse position.
Ensure that the color coded wires have been connected to their appropriate places.
The Dehumidistat (or Humidity control) or push button may be defective.
Jump the OL and OC terminals. If the unit switch to high speed, remove the Dehumidistat or push button and test it right beside the unit using another shorter wire. If it works here, change the wire. If it doesn’t, change the Dehumidistat or the push button.
The fuse may be defective.
The jumper JU1 may be in wrong position or missing.
Jumper J11 may be missing.
The circuit board or transformer may be detective.
The motor(s) or capacitor(s) may be defective
Check if fuse F1 is blown. In that case, replace fuse F1 as per product nameplate.
Make sure that jumper is properly located as per wiring diagram on page 12.
Make sure there is a jumper on connector J11.
NOTE: Refer to the FAN MOTOR SPEED SELECTION table of the wiring diagram on page 12 to know what the voltage reading must be. Press on the integrated control push button until the unit turn on low speed (the LED will light AM-
BER). Using a multimeter, check the voltage on J4- 1 and
J4- 2 (for supply motor), and on J5- 1 and J5- 2 (for exhaust motor). Then set the unit on high speed by pressing on the integrated control push button one more time (the
LED will light GREEN). Using a multimeter, check the voltage on J4- 1 and J4- 2 (for supply motor), and on
J5- 1 and J5- 2 (for exhaust motor). If all the readings correspond to the right voltage values, the circuit board is not defective. If one or both readings are different, change the transformer. If no voltage is present, change the circuit board.
Using a multimeter, check the ohms value on each motor connectors. For BLUE and BLACK motor wires, the right value is 49 ohms. For BLUE and BROWN motor wires, the right value is 79 ohms. For BROWN and BLACK motor wires, the right value is 126 ohms. If the ohms values are the same, the motor is not defective. Replace the motor capacitor.
Ice deposits may be hindering the damper operation.
The damper rod or the port damper itself may be broken.
The damper actuator or circuit board may be defective.
Remove the ice.
Inspect these parts and replace if necessary.
See point 2.
7 The integrated control push button does not work.
The 30- second boot sequence is not completed.
See Unit Booting Sequence, page 9.
15
These products earned the
ENERGY STAR ® by meeting strict energy efficiency guidelines set by
Natural Resources Canada and the US EPA. They meet ENERGY
STAR requirements only when used in Canada.
2018 CAC / BDP
D
7310 W. Morris St.
D
Indianapolis, IN 46231 Edition Date: 05/18
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16